topic 2 refrigeration notes

Upload: cia-lev-lim

Post on 01-Mar-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Topic 2 Refrigeration Notes

    1/56

    Refrigeration

    Topic 2

  • 7/25/2019 Topic 2 Refrigeration Notes

    2/56

    1. Introduction

    ! Refrigeration - method of reducing the temperature of a system below that of

    the surroundings and maintaining it at the lower temperature by continuously

    extracting the heat from it.

    !The principle of refrigeration is based onsecond law of thermodynamics. Itstates that heat does not flow from a low temperature body to a high

    temperature body without the help of an external work.

  • 7/25/2019 Topic 2 Refrigeration Notes

    3/56

    1. Introduction

    ! In refrigeration process, the heat is

    continuously removed from a system

    at lower temperature and transfer it

    to the surroundings at a higher

    temperature. This operation

    according to second law ofthermodynamics can only be

    performed by the aid of the external

    work.

    ! Therefore in a refrigeration system,power is to be supplied to remove

    heat continuously from the

    refrigerator to keep it cool at a

    temperature less than the

    surroundings.! Note: For history of refrigeration, refer to Dossats

    book Chapter 1.

  • 7/25/2019 Topic 2 Refrigeration Notes

    4/56

    1. Introduction

    ! Direct and reverse heat engines

  • 7/25/2019 Topic 2 Refrigeration Notes

    5/56

    1. Introduction

    ! Direct and reverse heat engines

  • 7/25/2019 Topic 2 Refrigeration Notes

    6/56

    2. Fundamental terms

    ! Refrigerant diagram

    ! The characteristics of a refrigerant can be illustrated in a diagram using the

    primary properties as x- and y-axis. The primary properties are normally

    chosen as energy content and pressure (P-h diagram).

    ! Energy content is represented by the thermodynamic property of specific

    enthalpy - quantifying the change in energy content per mass unit of the

    refrigerant as it undergoes processes in a refrigeration system.

    ! typically applicable interval for pressure is large. Therefore, diagrams use a

    logarithmic scale for pressure.

  • 7/25/2019 Topic 2 Refrigeration Notes

    7/56

    2. Fundamental terms

    ! The diagram is arranged

    so that it displays the

    liquid, vapour and

    mixture regions for the

    refrigerant. Liquid is

    found to the left (with a

    low energy content) -

    vapour to the right (with ahigh energy content).

    ! In between its the

    mixture region which are

    bounded by a curve -

    called the saturationcurve. The fundamental

    processes of evaporation

    and condensation are

    illustrated.

  • 7/25/2019 Topic 2 Refrigeration Notes

    8/56

    2. Fundamental terms

  • 7/25/2019 Topic 2 Refrigeration Notes

    9/56

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    10/56

    ! Evaporator

    ! The pressure-enthalpy chart plots the

    properties of a refrigerantrefrigerant

    pressure (vertical axis) versus enthalpy

    (horizontal axis).

    ! The cycle starts with a cool, low-pressure

    mixture of liquid and vapor refrigerant

    entering the evaporator where it absorbs

    heat from the relatively warm air/water or

    other fluid that is being cooled.

    ! This transfer of heat boils the liquid

    refrigerant in the evaporator, and this

    superheated refrigerant vapor is drawn to

    the compressor.

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    11/56

    ! Compressor

    ! The compressor draws in the

    superheated refrigerant vapor and

    compresses it to a pressure and

    temperature high enough that it can

    reject heat to another fluid.

    ! This hot, high-pressure refrigerant

    vapor then travels to the condenser.

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    12/56

    ! Condenser

    ! Within the condenser, heat is

    transferred from the hot refrigerant

    vapor to relatively cool ambient air or

    cooling water.

    ! This reduction in the heat content of

    the refrigerant vapor causes it to

    desuperheat, condense into liquid,

    and further subcool before leaving

    the condenser for the expansion

    device.

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    13/56

    ! Expansion valve

    ! The high-pressure liquid refrigerant flows

    through the expansion device, causing a

    large pressure drop that reduces the

    pressure of the refrigerant to that of theevaporator.

    ! This pressure reduction causes a small

    portion of the liquid to boil o", or flash,

    cooling the remaining refrigerant to the

    desired evaporator temperature.

    ! The cooled mixture of liquid and vapor

    refrigerant then enters the evaporator to

    repeat the cycle.

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    14/56

    3. Basic refrigeration cycle

  • 7/25/2019 Topic 2 Refrigeration Notes

    15/56

    4. Refrigeration effect

    ! The change in enthalpy that occurs in

    the evaporator is called the

    refrigeration e"ect.

    ! This is the amount of heat that each

    kg of liquid refrigerant will absorb

    when it evaporates.

    ! In comparison, the same system

    without subcooling produces less

    refrigeration e"ect.

  • 7/25/2019 Topic 2 Refrigeration Notes

    16/56

    4. Refrigeration effect

    ! Superheating occurs inside the final length

    of tubes at which temperature di"erence

    between refrigerant and air is highest

    ! Such large temperature di"erence

    increases the rate of heat transfer and therefrigerant vapor absorbs much heat.

    ! Liquid refrigerant completely evaporated

    ! Superheating shifts from the liquid/vapor

    region to vapor

    ! It ensures the refrigerant vapor is

    completely free liquid before entering the

    compressor.

  • 7/25/2019 Topic 2 Refrigeration Notes

    17/56

    5. Heat pumps

    ! A heat pump extracts heat from a heatsource and rejects heat to air or water at a

    higher temperature.

    ! Usually it is a packaged air conditioner or a

    packaged unit with a reversing valve or

    other changeover setup, in which the

    refrigerant flow to the condenser is changed

    to the evaporator.

    ! Alternatively, air passage through the

    evaporator may be changed over to

    passage through the condenser.

    ! A heat pump has all the main components

    of an air conditioner or package unit: fan,

    filters, compressor, evaporator, condenser,

    and a throttling device.

  • 7/25/2019 Topic 2 Refrigeration Notes

    18/56

    6. Cycle analysis of ideal cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    19/56

    6. Cycle analysis of ideal cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    20/56

    6. Cycle analysis of ideal cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    21/56

    7. Cycle analysis of practical cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    22/56

    7. Cycle analysis of practical cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    23/56

    7. Cycle analysis of practical cycles

  • 7/25/2019 Topic 2 Refrigeration Notes

    24/56

    8. Components of vapour compression system

  • 7/25/2019 Topic 2 Refrigeration Notes

    25/56

    Example 1

    Consider a vapour compression refrigeration cycle using R-134a based on

    the following conditions:

    Condenser temperature = 45C

    Evaporator temperature = 10C

    Sub-cooling at condenser = 3CSuperheating at evaporator = 3C

    Compressor e#ciency = 90%

    Plot the refrigeration cycle for the single stage compression.

    Find the refrigeration e"ect and the COP.

  • 7/25/2019 Topic 2 Refrigeration Notes

    26/56

    Example 1 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    27/56

    9. Two-stage vapour compression system

    ! Consists of two stage of compressionsystem

    ! Comprise with a high stage compressor

    and a low stage compressor or several

    single stage compressors in series.

    ! The pressure between the dischargepressure of the high stage and suction

    pressure of the low stage is called inter-

    stage pressure.

    ! To achieve a larger temperature range

    (cooler temperature) without requiring alarge pressure range in the compressor

  • 7/25/2019 Topic 2 Refrigeration Notes

    28/56

    9. Two-stage vapour compression system

  • 7/25/2019 Topic 2 Refrigeration Notes

    29/56

    9. Two-stage vapour compression system

    ! Volumetric e#ciency and compression ratio

  • 7/25/2019 Topic 2 Refrigeration Notes

    30/56

    9. Two-stage vapour compression system

    ! Vapor refrigerant at state point (1) enters the

    first stage of the compressor in dry saturated

    state.

    ! This vapor is compressed to the inter-stage

    pressure Piat stage point (2)

    ! The mixture enters the second stage of

    compressor at state point (3)

    ! Hot gas compressed to condensing pressure

    Pcleaves compressor at state point (4)

    ! The hot gas is then discharged to the

    condenser and condenses into liquid state at

    state point (5).

  • 7/25/2019 Topic 2 Refrigeration Notes

    31/56

    Two-stage vapour compression system

    ! Upon passing the condenser, the sub-cooled

    liquid refrigerant at state point (5') flows through

    the high pressure side flow control device.

    ! A portion of liquid refrigerant evaporates into

    the vapour form in the flash cooler at state point

    (7) The flashed refrigerant cools the remainingportion of liquid refrigerant to the saturated

    temperature at state point (8) at the inter-stage

    pressure.

    ! The mixture of liquid and vapor refrigerant in

    flash cooler is at state point (6).

    ! Liquid refrigerant flows through low pressure

    expansion valve, a small amount of which is

    pre-flashed and the liquid vapor mixture enters

    the evaporator at state point (9). In the

    evaporator, all liquid refrigerant is evaporated

    into vapour form and flows to the first stage

    inlet.

  • 7/25/2019 Topic 2 Refrigeration Notes

    32/56

    9. Two-stage vapour compression system

    ! The inter-stage pressure of 2-stage compound system

    ! The inter-stage pressure is selected such that the compression ratios at

    various stages are approximately equal.

    ! The inter-stage pressure could be approximated by the following

    equation:

  • 7/25/2019 Topic 2 Refrigeration Notes

    33/56

    9. Two-stage vapour compression system

    ! Defining the enthalpy of various state points in the P-h diagram:

  • 7/25/2019 Topic 2 Refrigeration Notes

    34/56

    9. Two-stage vapour compression system

    ! The portion of flashed vapour refrigerant in the flash cooler

    ! In the flash cooler, there is x kg of vaporized refrigerant cools down the

    remaining liquid refrigerant (1-x) kg to the saturation temperature at the inter-

    stage pressure.

    From the heat balance point of view, we have

    ! Note that x is also the dryness fraction of the liquid-vapor mixture in the flashcooler at the inter-stage pressure. This equation could be expressed as

  • 7/25/2019 Topic 2 Refrigeration Notes

    35/56

    9. Two-stage vapour compression system

    ! Enthalpy of vapor mixture entering the second-stage compressor

    ! Heat balance at the mixing point before entering the second stage

    compressor could be show as follows:

  • 7/25/2019 Topic 2 Refrigeration Notes

    36/56

    9. Two-stage vapour compression system

    ! Coe#cient of Performance of the 2-stage compound system with a flash

    cooler

    The refrigeration e"ect in evaporator Qre (per kg of refrigerant through

    condenser) could be expressed as:

    ! Work input Winto the compressor (first and second stages) could be

    expressed as:-

  • 7/25/2019 Topic 2 Refrigeration Notes

    37/56

    9. Two-stage vapour compression system

    ! Advantages of using two-stage vapour compression system compared with a single

    stage system:

    ! The compression ratio of each stage in a two-stage system can be reduced so that

    the volumetric e#ciency can be increased.

    ! In two-stage system, the liquid refrigerant can be sub-cooled to the saturation

    temperature at the inter-stage pressure which in turn increases the refrigeration

    e"ect.

    ! In two-stage system, the discharge gas from the low stage compressor can be de-

    superheated that results in reduction of discharge temperature after the high stagecompression process.

    ! Disadvantage of multi-stages systems: High equipment cost due to complicated

    equipment.

  • 7/25/2019 Topic 2 Refrigeration Notes

    38/56

    Example 2

    Consider a vapour compression refrigeration cycle using R-134a based on

    the following conditions:

    Condenser temperature = 45C

    Evaporator temperature = 10C

    Sub-cooling at condenser = 3CSuperheating at evaporator = 3C

    Compressor e#ciency = 90%

    Plot the refrigeration cycle for the two-stage compression.

    Find the refrigeration e"ect and the COP.

  • 7/25/2019 Topic 2 Refrigeration Notes

    39/56

    Example 2 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    40/56

    10. Vapour absorption system

    ! The vapour absorption refrigeration

    system is a heat operated system. It

    di"ers from the vapour compression

    refrigeration system only in the manner

    in which the circulation of the refrigerant

    is achieved.

    ! In this system, the compressor is

    replaced by an absorber, a generator

    and a pump. The refrigerant used in this

    system must be highly soluble in the

    solution known as absorbent. Thesystem uses ammonia as refrigerant and

    water as absorbent.

    ! Others: Water-LiBr, water-LiCl where

    water is refrigerant

  • 7/25/2019 Topic 2 Refrigeration Notes

    41/56

    10. Vapour absorption system

    ! The liquid refrigerant in the evaporator

    absorbs the heat from the medium to be

    cooled and it undergoes a change of

    phase from liquid to vapour. The low

    pressure vapour is then passed to the

    absorber. In the absorber, the low

    pressure ammonia vapour is dissolved inthe weak ammonia solution producing

    strong ammonia solution at low

    pressure.

    !The strong ammonia solution is thenpumped to a generator through the heat

    exchanger at high pressure. While

    passing through the heat exchanger, the

    strong ammonia solution is warmed up

    by the hot weak ammonia solution

    flowing from the generator to absorber.

  • 7/25/2019 Topic 2 Refrigeration Notes

    42/56

    10. Vapour absorption system

    ! The warm strong ammonia solution is

    heated by an external source in the

    generator. Due to the heating, the

    vapour gets separated from the solution.

    The vapour which is at high pressure

    and high temperature is condensed to

    low temperature in the condenser bycold water circulation.

    ! The high pressure liquid ammonia then

    passes through the expansion valve

    where it is expanded to low pressureand temperature. The low pressure and

    low temperature ammonia liquid again

    enters the evaporator where it absorbs

    the heat from the medium to be cooled

    and the cycle continues.

  • 7/25/2019 Topic 2 Refrigeration Notes

    43/56

    10. Vapour absorption system

    ! The P-h cycle is similar to that of a vapour compression cycle. Process 3 to 4

    is due to the mixing in the evaporator. Process 1 to 2 is due to the absorption.

  • 7/25/2019 Topic 2 Refrigeration Notes

    44/56

    10. Vapour absorption system

    ! The heat required to operate the

    system may be obtained from

    anywhere and is commonly a gas

    flame (Electrolux refrigeration

    system). This system is popular in

    caravan refrigerators.

  • 7/25/2019 Topic 2 Refrigeration Notes

    45/56

    11. Comparison between ...

    Vapour Compression Refrigeration System Vapour Absorption Refrigeration System

    Works using mechanical energy Works using heat energy

    Refrigerating capacity < 1000 tons Capacity is > 100 tons

    COP is much higher ( 4 to 10) COP is less than 2

    Noisy due to compressor Pump noise is less

    Chances of leakage of refrigerant are more No leakage

    Maintenance and operating cost is more Less maintenance cost

    Smaller in size Larger in size

    Wear and tear are more Less wear and tear

    Uses Freon-12 or any other refrigerant Only Ammonia is used as refrigerant

    Refrigerant vapour is compressed Refrigerant vapour is absorbed and heated

  • 7/25/2019 Topic 2 Refrigeration Notes

    46/56

    Example 3

    A heat pump uses a vapour compression cycle with refrigerant 12. The

    compressor is driven by a heat engine with a thermal e#ciency of 40%. Heat

    removed from the engine in the cooling system is recovered. This amounts to

    40% of the energy supplied in the fuel.

    The heat pump cycle uses an ideal cycle with an evaporator at 5oC and a

    condenser at 12.19 bar. The vapour is dry saturated at inlet to the

    compressor. The condenser produces liquid at 45oC.

    Calculate the thermal advantage (Coe#cient of Performance) for the heat

    pump.

    The plant is to deliver 40 kW of heat with fuel power input of 14.14 kW.

    Determine the mass flow rate of refrigerant.

  • 7/25/2019 Topic 2 Refrigeration Notes

    47/56

    Example 3 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    48/56

    Example 4

    The power input to the compressor of an ammonia vapour compression plant

    is 8.2 kW. The mechanical e#ciency is 85%. The ammonia is dry saturated at

    -6oC at inlet to the compressor. After compression the vapour is at 11.67 bar.

    The compression has an isentropic e#ciency of 90%. The condenser

    produces saturated liquid.

    Calculate the following.

    i. The flow rate.

    ii. The coe#cient of performance for the refrigerator.

    iii. The coe#cient of performance for the heat pump.

  • 7/25/2019 Topic 2 Refrigeration Notes

    49/56

    Example 4 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    50/56

    Example 5

    A practical refrigerator using ammonia as the refrigerant operates with an evaporator

    pressure 1.902 bar and condenser pressure of 15.54 bar. The refrigerator uses 2-

    stage compression and expansion to improve e#ciency. The refrigerant enters the

    low pressure (LP) compressor with a dryness fraction of 0.8 at 1.902 bar and enters

    the high pressure (HP) compressor at 6.149 bar. The refrigerant at entry to the HP

    expansion valve is sub-cooled to 38oC and entry to the LP expansion valve is wet

    saturated at 10oC. The refrigerant expands in the HP expansion valve to a pressure

    6.149 bar into a separator where the vapour is returned to the entry of the HP

    compressor. The liquid refrigerant is expanded again in the LP expansion valve

    before entry to the evaporator.

    Evaluate the Coe#cient of Performance (COP) of the refrigerator.

  • 7/25/2019 Topic 2 Refrigeration Notes

    51/56

    Example 5 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    52/56

    Example 6

    20 lbm/min of liquid water-ammonia solution at 150 psia, 220 F and

    concentration of 0.25 lbm ammonia per lbm of solution is mixed in a steady-

    flow adiabatic process with 10 lbm/min of saturated water-ammonia solution

    at 150 psia and 100F. Find the enthalpy, concentration and temperature of the

    mixture.

  • 7/25/2019 Topic 2 Refrigeration Notes

    53/56

    Example 6 (solution)

  • 7/25/2019 Topic 2 Refrigeration Notes

    54/56

    Example 7

    Consider an aqua-ammonia absorption system and the following given data:

    condenser pressure 200 psia

    evaporating pressure 30 psia

    generator temperature 240 F

    temperature of vapour leaving dephlegmator 130 F

    temperature of strong solution entering rectifying column 200 F

    The heat exchanger lowers the temperature of the liquid, leaving the condenser at

    10 F. States 1,3,4,7,8 and 12 are saturated. Pressure drop in components and

    connecting lines is negligible. The system produces 100 tons of refrigeration.

    Determine

    (a) properties P, t, x andifor all state points of the system

    (b) mass flow rate for all parts of the system

    (c) power required for the pump, assuming 75% mechanical e#ciency

    (d) system coe#cient of performance (COP)

    (e) system refrigerating e#ciency.

  • 7/25/2019 Topic 2 Refrigeration Notes

    55/56

    Example 7

    12

    6

    5

    4

    3

    Weak liq. solution

    0

    07

    8

    10

    9 1112

    Strong liq.

    solution

  • 7/25/2019 Topic 2 Refrigeration Notes

    56/56

    Example 7 (solution)

    0

    0