thyristor controlled series capacitor fair copy 1234

105
CHAPTER-1 INTRODUCTION 1.1 PROBLEM DEFINITION AND FORMULATION The electric power flow problem is the most studied and documented problem in power system engineering. In essence, this problem is the calculation of line loading given the generation and demand levels. Load flow calculation provide power flows and voltages for a specified power system subject to the regulating capability of generators, condensers, and tap changing under load transformers as well as specified net interchange between individual operating systems. This information is essential for the continuous evaluation of the current performance of a power system and for analyzing the effectiveness of alternative plans for system expansion to meet increased load demand. These analysis require the calculation of numerous load flows for both normal and emergency operating conditions. 1

Upload: senthilk23

Post on 08-Apr-2015

166 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Thyristor Controlled Series Capacitor FAIR COPY 1234

CHAPTER-1

INTRODUCTION

1.1 PROBLEM DEFINITION AND FORMULATION

The electric power flow problem is the most studied and

documented problem in power system engineering. In essence, this problem

is the calculation of line loading given the generation and demand levels.

Load flow calculation provide power flows and voltages for a specified

power system subject to the regulating capability of generators, condensers,

and tap changing under load transformers as well as specified net

interchange between individual operating systems. This information is

essential for the continuous evaluation of the current performance of a power

system and for analyzing the effectiveness of alternative plans for system

expansion to meet increased load demand. These analysis require the

calculation of numerous load flows for both normal and emergency

operating conditions.

The power flow problem is formulated as a set of nonlinear

equations. Many calculation methods have been proposed to solve this

problem. Among them, N-R method and fast-decoupled load flow method

are two very successful methods. In general, the decoupled power flow

methods are only valid for weakly loaded network with large X/R ratio

network. For system conditions with large angles across lines (heavily

loaded network) and with special control that strongly influence active and

reactive power flows, Newton-Raphson method may be required.

1

Page 2: Thyristor Controlled Series Capacitor FAIR COPY 1234

Therefore, when the AC power flow calculation is needed in

systems with FACTS devices, Newton-Raphson method is a suitable power

flow calculation method in the system with TCSC when high accuracy is

required. The basic requirement of power system is to meet the demand that

varies continuously. That is, the amount of power delivered by the power

companies must be equal to that of consumer’s need. Unfortunately, nobody

guarantees that unexpected things such as generator fault or line fault and

line tripping would not happen.

Due to its fast control characteristics and continuous

compensation capability, FACTS devices have been researched and adapted

in power system engineering area. There are so many advantages in FACTS

device; it can increase dynamic stability, loading capability of lines and

system security. It can also increase utilization of lowest cost generation.

The key role of FACTS device is to control the power flow actively and

effectively. In other words, it can transfer power flow from one line to

another within its capability. This project work focuses on the operation of

the TCSC under line overloaded that may cause any other transmission line

to be overflowed, the operation at emergency state should be different from

the operation at normal state.

Thyristor controlled series capacitor (TCSC) is one of

generation FACTS controller which control the effective line reactance by

connecting a variable capacitive reactance in series with line. The variable

capacitive reactance is obtained using FC-TCR combination with

mechanically switched capacitor sections in series. In load flow, studies the

2

Page 3: Thyristor Controlled Series Capacitor FAIR COPY 1234

TCSC can represented in many forms. For example, the model presented is

based on the concept of a variable series compensator whose changing

capacitive reactance adjusts itself in order to constrain the power flow across

the branch to a specified value. The power transmitted over an ac

transmission line is a function of the line impedance, the magnitude of

sending end and receiving end voltages, and the phase angle between these

voltages.

Traditional techniques of reactive line compensation and step

like voltage adjustment are generally used to alter these parameters to active

power transmission control. Fixed and mechanically switched shunt and

series reactive compensation are employed to modify the natural impedance

characteristics of transmission line in order to establish the desired effective

impedance between the sending and receiving ends to meet power

transmission requirements. Voltage regulating and phase shifting

transformers with mechanical tap-changing gears are also used to minimize

voltage variation and to control the power flow.

These conventional methods provide adequate control under

steady state and slowly changing conditions, but are largely ineffective in

handling dynamic disturbances. The traditional approach to contain dynamic

problems is to establish generous stability margins in enabling the system to

recover from faults, line and generator outages, and equipment failures. This

approach, although reliable, results in a significant under utilization of the

transmission system. As a result of recent environmental restrictions, right of

way issues, and construction cost increases, and deregulation policies, there

3

Page 4: Thyristor Controlled Series Capacitor FAIR COPY 1234

is an increasing recognition of the necessity to utilize existing transmission

system assets to the maximum extend possible.

The Thyristor Controlled Series Capacitor (TCSC) is a

transmission system which uses reliable high-speed Thyristor based high-

speed controllable elements. Issues include increased utilization of existing

facilities such as secure system operation at higher power transfers across

existing transmission lines which are limited by stability constraints, the

development of control designs for FACTS devices, and determination of

functional performance requirements for FACTS components.

Voltage control and stability problem are not new to the

electrical utility industry but are now receiving special attention in many

system. Voltage stability problems normally occur in heavily stressed

system while the disturbance leading to voltage collapse may be initiates by

a variety of causes; the underlying problem is an inherent weakness in the

power system. The principle factor contributing to voltage collapse are the

generator reactive power / voltage control limits, load characteristics,

characteristics of voltage control devices such as transformer under load tap

changer (ULTC) and FACTS (Flexible AC Transmission System) devices.

Voltage Stability improvement is one of the main objective for

power systems to provide quality and reliable supply. This makes

interesting and investigations in the area of voltage stability improvement,

FACTS device can quench the burning need of voltage stability.

4

Page 5: Thyristor Controlled Series Capacitor FAIR COPY 1234

Though many FACTS device available like SVC, TCSC, UPFC

etc.., TCSC (Thyristor Controlled Series Capacitor) inspires power systems

engineers to make use of it for the improvement of voltage stability.

Obviously this project use TCSC for voltage stability improvement.

To know the voltage level of all the buses in the power systems,

Load Flow among all the buses should be known. This can be found by

using standard Load Flow programs. This project uses NR- method to know

load flow among all the buses in the power system. Voltage levels of the

buses are compared before and after connection of TCSC in the power

system which demonstrates voltage stability improvements.

1.2 VOLTAGE STABILITY

According to the IEEE definition, “the voltage stability refers to

the ability of a power system to maintain steady voltages at all busses in the

system after being subjected to a disturbance from a given initial operating

condition”.

Voltage stability like any other stability is a dynamic problem.

However, from the static analysis certain useful information such as

loadability limit and proximity of the operating point to this limit can be

obtained. The pattern of the voltage decay in the vicinity of the voltage

collapse point will not be known from the static analysis.

5

Page 6: Thyristor Controlled Series Capacitor FAIR COPY 1234

1.3 VOLTAGE COLLAPSE

A power system at a given operating state and subjected to a

given disturbance undergoes voltage collapse if post-disturbance equilibrium

voltages are below acceptable limits. Voltage collapse may come total

blackout or partial in the power system.

The progressive decline the voltage leads to voltage collapse. A

system enters to a state of voltage instability when a disturbance, increase in

load demand, or change in system conditions causes a progressive and

uncontrolled decline in bus voltage. The main factor causing the instability

is the inability of the power system to meet the reactive power demand.

1.3.1 Causes of Voltage Collapse

1. Load on the transmission line is too high

2. Reactive power sources are too far from the load centers

3. Insufficient load reactive compensation

1.3.2 Voltage Stability analysis methods

Various methods that are available in the literature for the

analysis of the voltage stability are,

1. P-V Curve

2. Q-V Curve

3. Modal Analysis

4. Minimum Singular Value Decomposition

6

Page 7: Thyristor Controlled Series Capacitor FAIR COPY 1234

1.3.3 P-V Curve

The P-V Curves (Thierry VAN CUTSEM, 1998) have been

used to analyze voltage stability of a power system. P–V curves are useful to

calculate the amount of corrective measure needed to achieve a desired MW

margin. For constant current and constant admittance loads the system is

voltage stable throughout the P-V curve. For constant power load, voltage

stability limit and maximum loadability limit are the same.

The point at which the loadability limit is attained is called as

the nose point or collapse point. The loadability limit at the bus depends on

the reactive power support that this bus can receive from the neighboring

buses. Corrective measures are required when the current operating point is

either very close to the loadability limit or following a contingency the

loadability limit itself becomes lower than the bus load. Reactive power

compensation can be used to increase the loadability limit.

7

PmaxP0

Nose Point

P(MW)System Load

V

VSM

Fig1.1 Typical P–V Curve

Curve

0

Page 8: Thyristor Controlled Series Capacitor FAIR COPY 1234

From Figure 1.1 Voltage Stability Margin (VSM) is given by,

VSM = Pmax – P0(1.1)

where,

P0 : Active Load on the system (operating point)

Pmax : Maximum loading of the system

1.3.4 Voltage Stability Enhancement

Voltage Stability Enhancement is important in planning of

power system. If the state of the power system is found to possess a voltage

stability margin less than the desired level, then it is subjected to voltage

stability enhancement process. Voltage stability enhancement process

enforces voltage stability margin to the desired level.

1.4 REVIEW OF LITERATURE

Literature survey was carried out under three category to cater

the objective of the project. As voltage stability problem is one of the

important problem in the power system and FACTS device attracts power

system engineers to solve these kind of problem the project aims to improve

voltage stability margin by incorporating TCSC into the power system.

Three category of the literature survey are,

1) Voltage Stability

2) FACTS device

3) Power Flow techniques for FACTS device connected power

8

Page 9: Thyristor Controlled Series Capacitor FAIR COPY 1234

system.

In category two, some of the important literatures are: Rusejla

Ponjavic Sadikoic, Mevludin Glavic research work paper in the title “Effect

of FACTS device on steady State Voltage Stability” which demonstrates the

effect of SVC and TCSC on IEEE 39 bus system. A.J.F. Keri, X.Lombard,

and A.A. Edris provide tool for power utility engineers to evaluate the

application of TCSC, its impacts on Power System.

In category three, some of the important literatures are: A.

Nabavi-Niaki and M. R. Iravani (1996) use sequential method for solving

these kind of problem i.e. line flow in the line to which TCSC is to be

connect is found by NR-method and then four equation each corresponding

one TCSC control variable is solved iteratively. This method has some

drawback to overcome this drawback Fuerte-Esquivel C. R., and Acha E

use simultaneous method for solving load flow problem with TCSC. In

simultaneous method four equations each corresponding to one TCSC

control variable is included in jacobian matrix itself, so one can get system

state variables and control variables simultaneously. In this project the

concept of simultaneous method is used and, follow the newly derived

equation which makes different and ease to use for the TCSC connected

power system

The project mainly deals with the enhancement of static voltage

stability of power system. This project proposes a decoupled model of

TCSC, for maintaining desired voltage profile and voltage stability with the

prescribed stability margin.

9

Page 10: Thyristor Controlled Series Capacitor FAIR COPY 1234

1.5 OUTLINE OF THE THESIS

It includes derivation power flow injections of the TCSC for

two voltage sources, and incorporating the newly derived equation into the

power flow problem. Here Newton Raphson (NR) method is used to solve

the power flow and also TCSC inclusion, the Jacobian matrix and the

number equation to be solved are altered according to the need. MATLAB

program were developed to demonstrate the proposed work. It is generalized

program and may use for the multiple TCSC connection in the power

systems. The results for various conditions are obtained and performance of

the power system is compared before and after TCSC connection. Six bus

systems is considered in this project.

A brief outline of the various chapters of the thesis is as

follows. In Chapter 1, a brief introduction of the project and basic definition

of the frequently used technical terms are given. Literature survey for the

project work, proposal for the project work, introduction of the Flexible AC

Transmission (FACTS) device and their needs, different types of FACTS

device and their benefits and finally advantage of TCSC which makes

suitable for the proposed work are explained.

In Chapter 2, Operating principle and working of the system

without TCSC is given in the power flow model is deeply explained and the

needed equations are derived.

10

Page 11: Thyristor Controlled Series Capacitor FAIR COPY 1234

In Chapter 3, Operating principle and working of the TCSC is

given and then how the TCSC in included into the power flow model is

deeply explained and the needed equations are derived.

In Chapter 4, Ward and Hale Six bus system is considered with

TCSC connection and also final conclusion of the project work are carried

out with future work of TCSC are presented.

1.6 INTRODUCTION TO FACTS DEVICES

Flexible alternating current transmission systems (FACTS)

devices are used for the dynamic control of voltage, impedance and phase

angle of high voltage AC lines. FACTS devices provide strategic benefits

for improved transmission system management through: better utilization of

existing transmission assets; increased transmission system reliability and

availability; increased dynamic and transient grid stability; increased quality

of supply for sensitive industries (e.g. computer chip manufacture); and

enabling environmental benefits. Typically the construction period for a

facts device is 12 to 18 months from contract signing through

commissioning.

1.7 NECESSITY OF FACTS DEVICES

The need for more efficient electricity systems management has

given rise to innovative technologies in power generation and transmission.

Worldwide transmission systems are undergoing continuous changes and

restructuring. They are becoming more heavily loaded and are being

11

Page 12: Thyristor Controlled Series Capacitor FAIR COPY 1234

operated in ways not originally envisioned. Transmission systems must be

flexible to react to more diverse generation and load patterns. In developing

countries, the optimized use of transmission systems investments is also

important to support industry, create employment and utilize efficiently

scarce economic resources.

Flexible AC Transmission Systems (FACTS) is a technology

that responds to these needs. It significantly alters the way transmission

systems are developed and controlled together with improvements in asset

utilization, system flexibility and system performance.

1.8 TYPES OF FACTS DEVICES

1) Static VAR compensator (SVC)

2) Thyristor controlled series compensator (TCSC)

3) Static Synchronous compensator (STATCOM)

4) Unified power flow controller (UPFC)

1.8.1 Static VAR compensator (SVC)

Static VAR Compensators (SVC’s), the most important FACTS

devices, have been used for a number of years to improve transmission line

performance and improves the voltage profile of the bus by injecting VAR

power in to the bus where it needs by resolving dynamic voltage problems.

The accuracy, availability and fast response enable SVC’s to provide high

performance steady state and transient voltage control compared with

12

Page 13: Thyristor Controlled Series Capacitor FAIR COPY 1234

classical shunt compensation. SVC’s are also used to damp out the power

swings, improve transient stability, and reduce system losses by optimized

reactive power control.

1.8.2 Thyristor controlled series compensator (TCSC)

Thyristor controlled series compensators (TCSCs) are an

extension of conventional series capacitors through adding a Thyristor

controlled reactor. Placing a controlled reactor in parallel with a series

capacitor enables a continuous and rapidly variable series compensation

system. The main benefits of TCSCs are increased energy transfer, damping

out of power oscillations, damping out of sub synchronous resonances, and

control of line power flow.

1.8.3 Static Synchronous compensator (STATCOM)

STATCOM are GTO (gate turn-off type thyristor) based

SVC’s. Compared with conventional SVC’s they don’t require large

inductive and capacitive components to provide inductive or capacitive

reactive power to high voltage transmission systems. It is used only to

compensate real power calculation. This results in smaller land

requirements. An additional advantage is the higher reactive output at low

system voltages where a STATCOM can be considered as a current source

independent from the system voltage. STATCOM have been in operation for

approximately 5 years.

13

Page 14: Thyristor Controlled Series Capacitor FAIR COPY 1234

1.8.4 Unified power flow controller (UPFC)

Connecting a STATCOM, which is a shunt connected

device, with TCSC which is a series branch in the transmission line via

its DC circuit results in a UPFC. This device is comparable to a phase

shifting transformer but can apply a series voltage of the required phase

angle instead of a voltage with a fixed phase angle. The UPFC combines

the benefits of a STATCOM and a TCSC. This can be overloaded

shortly. Also it is used for compensating both real and reactive power.

1.9 BENEFITS OF FACTS DEVICES

(A) Better utilization of existing transmission system assets

In many countries, increasing the energy transfer capacity and

controlling the load flow of transmission lines are of vital importance,

especially in de-regulated markets, where the locations of generation and the

bulk load centers can change rapidly. Frequently, adding new transmission

lines to meet increasing electricity demand is limited by economical and

environmental constraints. FACTS devices help to meet these requirements

with the existing transmission systems.

(B) Increased transmission system reliability and availability

Transmission system reliability and availability is affected by

many different factors. Although FACTS devices cannot prevent faults, they

can mitigate the effects of faults and make electricity supply more secure by

reducing the number of line trips. For example, a major load rejection results

14

Page 15: Thyristor Controlled Series Capacitor FAIR COPY 1234

in an over voltage of the line which can lead to a line trip. SVC’s or

STATCOMs counteract the over voltage and avoid line tripping.

(C) Increased dynamic and transient grid stability

Long transmission lines, interconnected grids, impacts of

changing loads and line faults can create instabilities in transmission

systems. These can lead to reduced line power flow, loop flows or even to

line trips. FACTS devices stabilize transmission systems with resulting

higher energy transfer capability and reduced risk of line trips, which

increase quality of supply for sensitive industries.

Modern industries depend upon high quality electricity supply

including constant voltage, and frequency and no supply interruptions.

Voltage dips, frequency variations or the loss of supply can lead to

interruptions in manufacturing processes with high resulting economic

losses.

(D) Environmental benefits

FACTS devices are environmentally friendly. They contain no

hazardous materials and produce no waste or pollutions. FACTS help

distribute the electrical energy more economically through better utilization

of existing installations thereby reducing the need for additional

transmission lines.

15

Page 16: Thyristor Controlled Series Capacitor FAIR COPY 1234

1.10 BENEFITS OF TCSC

The TCSC's high speed switching capability provides a

mechanism for controlling line power flow, which permits increased loading

of existing transmission lines, and allows for rapid readjustment of line

power flow in response to various contingencies. The TCSC also can

regulate steady-state power flow within its rating limits. Transmission

loading may be limited by system stability or transient stability of

generation. The TCSC is a powerful new tool to help relieve these

constraints.

Its controls can be designed to modulate the line reactance and

provide damping to system swing modes, with dramatic results. This

condition was simulated using the actual Slatt control system and GE's

power system simulator with damping deliberately reduced. (See Figure 3.)

In the top trace, large, undamped system swings are produced as the result of

a fault.

At six seconds the TCSC damping function is manually

engaged, at which point there is a dramatic increase in the damping. The

control dead band stops further action in this test case, but normally the

system's inherent damping would make the power swings die out entirely.

the level of damping introduced by the TCSC, per dollar invested, is

unequaled by any other device and the fast action permits increased line

loading for the same stability constraint. The output of generating plants

may also be limited by transient instability under certain contingency

conditions. The fast-acting TCSC can provide the means of rapidly

increasing power transfer upon detection of the critical contingencies,

16

Page 17: Thyristor Controlled Series Capacitor FAIR COPY 1234

resulting in increased transient stability.Finally the TCSC provides a

mechanism for greatly reducing a potential sub-synchronous resonance

problem at thermal generators electrically close to transmission lines with

series compensation. In some cases, the inability to mitigate SSR with

conventional series capacitors has limited line compensation to levels

between 20 and 40 percent. With even a small percentage of TCSC, the total

compensation can be increased significantly.

1.11 ADVANTAGES OF FACTS DEVICES

FACTS devices provides concurrent real and reactive control of

series line compensation with out an external electric energy source. It also

provides the following benefits:

1. Voltage Stability

2. VAR Compensation

3. Static & Dynamic stability

FACTS devices has needed control facilities for voltage

stability improvement it obvious choice for selecting for the project that

demonstrates the voltage stability improvement. Also it helps to improve

voltage stability, sub synchronous resonance, and damping of power swings

etc. It also provides us to make better power flow control and also helps to

minimize the real and reactive power losses.

17

Page 18: Thyristor Controlled Series Capacitor FAIR COPY 1234

CHAPTER 2

POWER FLOW MODEL WITHOUT TCSC

2.1 INTRODUCTION

Generally, the power flow model without TCSC is nothing but

the normal Newton Raphson method. It is used to calculate power flow of

the system. And also it is used to calculate the load flow, line losses, and

total cost of function. Here load flow, line losses are calculated using

jacobian matrix compared with the specified accuracy.

Many calculation methods have been proposed to solve this

problem Among them Newton-Raphson method and fast decoupled load

flow method are two very successful methods. In general, the decoupled

power flow methods are only valued for weakly loaded network with large

X/R ratio network. By using Newton-Raphson method, we can over come

the general weakly loaded network. So Newton-Raphson method may be

required. Therefore when the AC power flow calculation is needed in system

with FACTS devices. So Newton-Raphson method is a suitable power flow

calculation method because high accuracy is required.

2.2 PROBLEM STATEMENT

Complex current at bus-i,

18

Page 19: Thyristor Controlled Series Capacitor FAIR COPY 1234

(2.1)

Where,

n = number of the buses

Y = Bus admittance matrix

I = Complex current in the bus

V = Complex voltage in the bus

Pi + jQi = Complex power in the bus

i,j= bus number

In polar form,

(2.2)

Complex power at bus-i,

Pi – jQi = Vi* Ii (2.3)

Therefore, (2.4)

Separating real and imaginary parts,

(2.5)

(2.6)

19

Page 20: Thyristor Controlled Series Capacitor FAIR COPY 1234

Equation 2.3 and 2.4 constitute a set of nonlinear algebraic

equations in terms of the independent variables, voltage magnitude in pu,

and phase angle in radians.

We have two equations for each load bus, given by 2.5 and 2.6,

and one equation for each generator bus, given by 2.5.

Expanding 2.5 and 2.6 in Taylor’s series about the initial

estimate and neglecting all higher order terms results in the following set of

linear equations. In short form, it can be written as

(2.7)

∆P- Change in real power

∆Q- Change in reactive power

J1, J2, J3, J4- Jacobian elements

∆δ- Change in load angle

∆|V|- change in voltage

The terms ΔPi(k) and ΔQi

(k) are the difference between the

scheduled and the calculated values, known as the power residuals, given by

ΔPi(k) = Pi

sch – Pi(k) (2.8)

ΔQi(k) = Qi

sch – Qi(k) (2.9)

The new estimates for bus voltages are,

δi(k+1) = δi

(k) + Δ δi(k) (2.10)

20

Page 21: Thyristor Controlled Series Capacitor FAIR COPY 1234

|Vi(k+1)|= |Vi

(k)| + |Δ Vi(k)| (2.11)

The diagonal and the off-diagonal elements of J1 are

(2.12)

(2.13)

The diagonal and the off-diagonal elements of J2 are

(2.14)

(2.15)

The diagonal and the off-diagonal elements of J3 are

(2.16)

(2.17)

The diagonal and the off-diagonal elements of J4 are

21

Page 22: Thyristor Controlled Series Capacitor FAIR COPY 1234

(2.18)

(2.19)

2.3 PROBLEM FORMULATION FOR SYSTEM WITHOUT TCSC

Excitation Voltage Source real power (PE)

PE = Real { VE IE* } (2.20)

PE = ( - VE VET Sin (E - ET) / XE) (2.21)

Boosting Voltage Source real power (PB)

PB = Real {VB IB* } (2.22)

PB = ( - VB VET Sin (B - ET) / XB) + (VB VBT Sin (B - BT) / XB) (2.23)

TCSC Power Flow constraints are:

PB = PE (2.24)

The superscript T indicates transposition. ∆X is the solution

vector and Jac is the Jacobian matrix. The TCSC linearized power equations

22

Page 23: Thyristor Controlled Series Capacitor FAIR COPY 1234

are combined with the lineralized system of equations corresponding to the

rest of the network,

F(X) = Jac ∆X (2.25)

Where,

F(X) = [∆P ∆Q ∆PBT ∆PET ∆QBT ∆QET]T (2.26)

∆X = [∆ ∆V ∆B ∆E ∆VB ∆VE]T (2.27)

(2.28)

H = ∂P / ∂ (2.29)

N = ∂P / ∂V (2.30)

J = ∂Q / ∂ (2.31)

L = ∂Q / ∂V (2.32)

2.4 ALGORITHM FOR LOAD FLOW WITHOUT TCSC

23

Page 24: Thyristor Controlled Series Capacitor FAIR COPY 1234

1) For load buses, where Pisch and Qi

sch are specified, voltage

magnitude and phase angle are set equal to the slack bus values or 1.0 and 0.

For generator buses voltage phase angle is set as 0. In addition to this one

more fictitious bus B’ (load bus) is included. The exciter bus E is converted

into generator bus.

2) For load buses Pi(k) and Qi

(k) are calculated from equations 2.5 and

2.6 and ΔPi(k) and ΔQi

(k) are calculated from equations 2.7 and 2.8.

3) For generator buses, Pi(k) and ΔPi

(k) is calculated from equations 2.5

and 2.6 respectively

4)The elements of the Jacobian matrix H, N, J and L are calculated

form equations 2.29 to 2.30.

5) The linear simultaneous equation 2.28 is solved.

6) The new voltage magnitude and phase angle are computed from

equation 2.27.

7) The process is continued until the residual of f(X) from equation

2.26 are less than the specified accuracy (F(X) =Jac (∆X)).

CHAPTER 3

24

Page 25: Thyristor Controlled Series Capacitor FAIR COPY 1234

POWER FLOW MODEL WITH TCSC

3.1 INTRODUCTION TO TCSC

Thyristor Controlled Series Capacitors (TCSCs) are finding

increasing application in power systems, mainly as series compensators in

transmission lines, designed to control power flow, to increase transient

stability, or to dampen power oscillations and sub synchronous resonances.

TCSCs represent an example of a flexible AC transmission system (FACTS)

component.

To understand and control the interactions between FACTS

devices such as TCSCs and the utility system, there is an increasing need for

convenient models that will allow fast and accurate transient simulations and

facilitate control design. However, it is difficult to analyze the dynamics of

TCSC systems, because they incorporate both continuous time dynamics

(associated with the voltages and currents on capacitors and inductors) and

discrete events (associated with the switching of the thyristors). The standard

quasi-static approximation models the TCSC as a variable fundamental-

frequency reactance; the line and TCSC dynamics are omitted. This

approach is widely used because of its simplicity, but relies on the

assumption that the transmission system is operating in sinusoidal steady-

state, with the only dynamics being that of the generators. This quasi-static

approximation lacks accuracy when voltage stability, transient stability or

other dynamic phenomena are of interest; several authors have already

shown that TCSC dynamics cannot always be neglected.

25

Page 26: Thyristor Controlled Series Capacitor FAIR COPY 1234

In an attempt to characterize the dynamic behavior of the TCSC

system , sampled-data models for TCSCs have been developed. They predict

system behavior very well, and also offer an analytical basis for control

design. However, this approach presents some disadvantages: the model

derivation is relatively complicated; the model structure has no clear relation

to the system configuration; and the model does not interface well with the

standard phasor-based models of generator dynamics. This project work

derives TCSC model based on time-varying Fourier coefficients that capture

the phasor dynamics of the TCSC.

Restricting our focus to the representation of the fundamental

frequency components, we obtain a natural dynamic extension of the usual

quasi-static phasor analysis. Various simplifications and refinements of the

fundamental model are possible; some of these variations are developed in

this project work. The same approach has been used in order to analyze the

line dynamics together with the generator dynamics, and earlier in to

develop frequency selective averaged models for power converters. This

approach can be viewed as intermediate between detailed time domain

circuit representation (as used in EMTP) and the quasi-static sinusoidal

steady-state approximation.

Our models of TCSC phasor dynamics represent the dynamics

of the fundamental currents and voltages and their harmonics in a simple but

powerful way. The models are well suited to efficient simulation of

transients. As the models are modular, the inclusion of line dynamics and

generator dynamics is straightforward. In this chapter we introduce the time-

varying Fourier coefficient representation that will be used in this project

26

Page 27: Thyristor Controlled Series Capacitor FAIR COPY 1234

work. Also we review the basic operation of a TCSC and derives our

fundamental phasor dynamics model for the TCSC, and from that only we

obtained a reduced-order version of it. Finally it presents numerical

simulations that validate the model and we show the results of embedding

the TCSC model in a larger model that incorporates line dynamics.

3.2 TCSC OPERATION

Figure 3.1 shows the circuit diagram of a single-phase TCSC.

Fig 3.1 TCSC module

The system is composed of a fixed capacitor in parallel with a

Thyristor Controlled Reactor (TCR). The switching elements of the TCR

consist of two anti-paralleled thyristors, which alternate their switching at

the supply frequency. The system is controlled by varying the phase delay of

the thyristor firing pulses relative to the zero crossings of some reference

waveform. The effect of such variation can be interpreted as a variation in

the value of the capacitive/inductive reactance at the fundamental frequency.

27

Page 28: Thyristor Controlled Series Capacitor FAIR COPY 1234

In our analysis, the thyristor2 will be ideal, so that

nonlinearities due to the thyristor turn on and turn-off are neglected. We also

assume that the line current is essentially sinusoidal, and take it to be the

reference waveform for the synchronization of the firing pulses a slight

modification of our analysis is needed if the synchronization instead done

with the capacitor voltage Vc. The waveforms of the TCSC are shown in

Fig. 3.1, with I denoting the current through the TCR branch.

The thyristor is turned on after a delay relative to the zero-

crossing the line current, and keeps conducting until here the inductor

current becomes zero. In steady-state, the conductor angle becomes

symmetrical with respect to the peak value of the line current, and the angle

between the negative peak of the inductor current (which occurs at the zero-

crossing of the capacitor voltage) and the positive peak of the line current

goes to zero. In this project work we will assume firing angle control for the

TCSC minor modifications are needed for conduction angle control.

3.3 POWER FLOW MODEL OF TCSC

Complex current at bus-i,

(3.1)

Where,

n = number of the buses

Y = Bus admittance matrix

28

Page 29: Thyristor Controlled Series Capacitor FAIR COPY 1234

I = Complex current in the bus

V = Complex voltage in the bus

Pi + jQi = Complex power in the bus

i,j – bus number

In polar form,

(3.2)

Complex power at bus-i,

Pi – jQi = Vi* Ii (3.3)

Therefore,

(3.4)

Separating real and imaginary parts,

(3.5)

(3.6)

Equation 3.5 and 3.6 constitute a set of nonlinear algebraic

equations in terms of the independent variables, voltage magnitude in p.u,

29

Page 30: Thyristor Controlled Series Capacitor FAIR COPY 1234

and phase angle in radians. We have two equations for each load bus, given

by 3.5 and 3.6, and one equation for each generator bus, given by 3.5.

Expanding 3.5 and 3.6 in Taylor’s series about the initial

estimate and neglecting all higher order terms results in the following set of

linear equations. In short form, it can be written as

(3.7)

The terms ΔPi(k) and ΔQi

(k) are the difference between the

scheduled and the calculated values, known as the power residuals, given by

ΔPi(k) = Pi

sch – Pi(k) (3.8)

ΔQi(k) = Qi

sch – Qi(k) (3.9)

The new estimates for bus voltages are,

δi(k+1) = δi

(k) + Δ δi(k) (3.10)

|Vi(k+1)|= |Vi

(k)| + |Δ Vi(k)| (3.11)

The diagonal and the off-diagonal elements of J1 are

(3.12)

(3.13)

30

Page 31: Thyristor Controlled Series Capacitor FAIR COPY 1234

The diagonal and the off-diagonal elements of J2 are

(3.14)

(3.15)

The diagonal and the off-diagonal elements of J3 are

(3.16)

(3.17)

The diagonal and the off-diagonal elements of J4 are

(3.18)

(3.19)

3.4 PROBLEM FORMULATION FOR SYSTEM WITH TCSC

Let the power flow equation of TCSC are solved as follows

Excitation Terminal real and reactive power flow

PET = Real { VET IE* + VET IB* } (3.20)

31

Page 32: Thyristor Controlled Series Capacitor FAIR COPY 1234

PET = ( - VET VB Sin (ET - B) / XB) + (VET VBT Sin (ET - BT) / XB) +

(VET VE Sin (ET - E) / XE) (3.21)

QET = Img { VET IE* + VET IB* } (3.22)

QET = (VET 2 / XB) + ( VET

2 / XE) + (VET VB Cos (ET - B) / XB) -

(VET VBT Cos (ET - BT) / XB) - (VET VE Cos (ET - E) / XE) (3.23)

Boosting Terminal real and reactive power flow

PBT = Real { VBT IB* } (3.24)

PBT = ( - VBT VET Sin (BT - ET) / XB) - (VBT VB Sin (BT - B) / XB)

(3.25)

QBT = Img { VBT IB* } (3.26)

QBT = ( - VBT 2 / XB) + (VBT VET Cos (BT - ET) / XB) +

(VBT VB Cos (BT - B) / XB) (3.27)

Excitation Voltage Source real power

PE = Real { VE IE* } (3.28)

32

Page 33: Thyristor Controlled Series Capacitor FAIR COPY 1234

PE = ( - VE VET Sin (E - ET) / XE) (3.29)

Boosting Voltage Source real power

PB = Real {VB IB* } (3.30)

PB = ( - VB VET Sin (B - ET) / XB) + (VB VBT Sin (B - BT) / XB) (3.31)

TCSC Power Flow constraints are:

Boosting voltage source real power=Excitation voltage source real power

PB = PE (3.32)

To find TCSC control variables (VE VB E B) Taylors series expansion

method is used as follows

f(PET) = ( - VET VB Sin (ET - B) / XB) + (VET VBT Sin (ET - BT) / XB) +

(VET VE Sin (ET - E) / XE) - PET (3.33)

f(QET) = (VET 2 / XB) + ( VET

2 / XE) + (VET VB Cos (ET - B) / XB) -

(VET VBT Cos (ET - BT) / XB) - (VET VE Cos (ET - E) / XE) - QET

(3.34)

f(PBT) = ( - VBT VET Sin (BT - ET) / XB) - (VBT VB Sin (BT - B) / XB) – PBT

(3.35)

f(QBT)=(VBT VET Cos (BT - ET) / XB) + (VBT VB Cos (BT - B) / XB) –

VBT 2/XB -QBT (3.36)

33

Page 34: Thyristor Controlled Series Capacitor FAIR COPY 1234

The superscript T indicates transposition. ∆X is the solution

vector and Jac is the Jacobian matrix. The TCSC linearized power equations

are combined with the linearized system of equations corresponding to the

rest of the network,

F(X) = Jac ∆X (3.37)

Where,

F(X) = [∆P ∆Q ∆PBT ∆PET ∆QBT ∆QET]T (3.38)

∆X = [∆ ∆V ∆B ∆E ∆VB ∆VE]T (3.39)

(3.40)

H = ∂P / ∂ (3.41)

N = ∂P / ∂V (3.42)

J = ∂Q / ∂ (3.43)

34

Page 35: Thyristor Controlled Series Capacitor FAIR COPY 1234

L = ∂Q / ∂V (3.44)

3.5. ALGORITHM FOR LOAD FLOW WITH TCSC

1) For load buses, where Pisch and Qi

sch are specified, voltage

magnitude and phase angle are set equal to the slack bus values or

1.0 and 0. For generator buses voltage phase angle is set as 0. In

addition to this one more fictitious bus B’ (load bus) is included.

The exciter bus E is converted into generator bus.

2) For load buses Pi(k) and Qi

(k) are calculated from equations 3.5 and

3.6 and ΔPi(k) and ΔQi

(k) are calculated from equations 3.7 and 3.8.

3) For generator buses, Pi(k) and ΔPi

(k) is calculated from equations 3.5

and 3.8 respectively

4) The elements of the Jacobian matrix H, N, J and L are calculated

form equations 3.41 to 3.44. In addition to these four rows

corresponds to equations 3.32 – 3.36 and four columns

corresponds to four TCSC control variables (B E VB VE) are

augmented as shown in equation 3.40

5) The linear simultaneous equation 3.39 is solved.

6) The new voltage magnitude and phase angle are computed from

equation 3.39.

7) The process is continued until the residual of f(X) from equation

3.38 are less than the specified accuracy (F(X) = Jac ∆X).

35

Page 36: Thyristor Controlled Series Capacitor FAIR COPY 1234

CHAPTER 4

APPLICATION OF TCSC FOR WARD AND HALE

6 BUS SYSTEM

36

Page 37: Thyristor Controlled Series Capacitor FAIR COPY 1234

4.1. WARD AND HALE 6 BUS SYSTEM

The line data and bus data of the 6-bus system are given in

Tables A-2 and A-3 respectively given in appendix. The Table A-2

corresponds to the resistance, tap ratios and half line charging. The Limits of

bus voltages, load side real and reactive power and generator side real and

reactive power are given in table A-3. The single line diagram of Ward and

Hale System is given in appendix A-1.

4.2. RESULTS AND OBSERVATION

4.2.1. Results of the system without TCSC:

-------------------------------------------------------------------------- Base Case Details . . . -------------------------------------------------------------------------- Power Flow Solution by Newton-Raphson Method Maximum Power Mismatch = 0.000898141 No. of Iterations = 3-------------------------------------------------------------------------- Bus Voltage Angle ------Load------ ---Generation--- Injected No. Mag. Degree MW Mvar MW Mvar Mvar -------------------------------------------------------------------------- 1 1.005 0.000 150.000 0.000 517.446 -36.418 0.000 2 1.010 0.622 0.000 0.000 243.000 -35.527 0.000 3 1.020 -8.297 0.000 0.000 74.000 207.772 0.000 4 1.000 -8.397 200.000 0.000 42.000 -47.650 0.000 5 0.993 -7.752 500.000 0.000 0.000 0.000 0.000-------------------------------------------------------------------------- Total 850.000 0.000 876.446 88.178 0.000

Table 4.1- Output of load flow without TCSC

Line Flow & Losses

Line Power at bus Line flow Line lossfrom to MW MVAR MVA MW MVAR1 367.446 -36.418 369.246

37

Page 38: Thyristor Controlled Series Capacitor FAIR COPY 1234

25

-56.828424.386

35.591-72.055

67.053430.460

0.66818.529

0.44555.037

2134

243.00057.49679.506105.998

-35.527-35.146-4.7844.458

245.58367.38779.650106.092

0.6680.9331.655

0.44512.43816.550

3245

74.000-78.57354.62597.949

207.77217.22261.039129.629

220.55780.43981.912162.473

0.9330.9673.806

12.4381.2902.537

423

-158.000-104.343-53.657

-47.65012.092-59.749

165.029105.04180.306

1.6550.967

16.5501.290

531

-500.000-94.143-405.857

0.000-127.092127.092

500.000158.162425.291

3.80618.529

2.53755.037

Total Loss 26.558 88.298

--------------------------------------------------------------------------

The Lambda Values @ Various Nodes In The Generator Buses Are . . .

--------------------------------------------------------------------------

Node 1 --> 61.74

Node 2 --> 60.60

Node 3 --> 64.40

Node 4 --> 65.40

--------------------------------------------------------------------------

The Total Production Cost Of All Generators = 32248.08 Fr

--------------------------------------------------------------------------

4.2.2. Results of the system with TCSC:

~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

After TCSC connection

38

Page 39: Thyristor Controlled Series Capacitor FAIR COPY 1234

TCSC connected between Bus 2 and Bus 4 Exciter Bus=2 and Booster Bus=6

~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

Power Flow Solution by Newton-Raphson Method

Maximum Power Mismatch = 0.000259387

No. of Iterations = 7

Bus Voltage Angle ------Load------ ---Generation--- Injected ----TCSC--- No. Mag. Degree MW Mvar MW Mvar Mvar MW MVAR 1 1.005 0.000 150.000 0.000 504.098 -6.303 0.000 0.000 0.000 2 1.010 0.415 0.000 0.000 243.000 20.347 0.000 -96.461 -11.454 3 1.020 -7.109 0.000 0.000 67.000 148.887 0.000 0.000 0.000 4 1.000 -7.616 200.000 0.000 38.000 -79.871 0.000 0.000 0.000 5 1.012 -7.340 500.000 0.000 0.000 0.000 0.000 0.000 0.000 6 1.010 0.590 0.000 0.000 0.000 0.000 0.000 96.461 10.413 Total 850.000 0.000 852.098 83.060 0.000

Table 4.2- Output of load flow with TCSC

Line Flow & Losses line Power at bus Line flow Line lossFrom to MW MVAR MVA MW MVAR1 354.098 -6.303 354.154

39

Page 40: Thyristor Controlled Series Capacitor FAIR COPY 1234

25

-78.835432.933

-10.5664.263

79.540432.954

0.3130.186

0.62655.677

213

146.53979.14867.391

8.89311.192-2.300

146.80979.93667.430

0.3130.223

0.6268.914

3245

67.000-67.16866.56567.603

148.88711.21485.559359.114

163.26868.098108.40385.358

0.2230.5650.350

8.9142.2590.700

463

-162.000-96.000-66.000

-79.8713.429-83.300

180.62096.061106.278

0.4610.565

13.8422.259

531

-500.000-67.253-432.747

0.000-51.41451.414

500.00084.654435.791

0.3500.186

0.70055.677

64

96.46196.461

10.41310.413

97.02197.021 0.461 13.842

Total Loss 2.098 82.018

------------------------------------------------------------------------ The Lambda Values @ Various Nodes In The Generator Buses Are . . .

--------------------------------------------------------------------------

Node 1 --> 61.00

Node 2 --> 61.00

Node 3 --> 61.00

Node 4 --> 61.00

--------------------------------------------------------------------------

The Total Production Cost Of All Generators = 30744.72 Fr

--------------------------------------------------------------------------

Observation:

The above tables 4.1& 4.2 represent the output of load flow for

system without and with TCSC respectively. From these tables, the line

40

Page 41: Thyristor Controlled Series Capacitor FAIR COPY 1234

losses are calculated and compared. From the above results, the power flow

solution for the system with TCSC is relatively lesser than for the system

without TCSC. In above table 4.1, the real and reactive power losses are

calculated as 26.558 MW, 88.298 MVAR respectively which is relatively

higher as compared to system with TCSC having real and reactive power

losses as 2.098 MW, 82.018 MVAR respectively. From these above tables

4.1& 4.2 real power loss is reduced higher than reactive power loss and the

total production cost for system without TCSC is 32248.08 Fr which is

reduced upto 30744.72 Fr for system with TCSC. The load flow with TCSC

possesses low real and reactive power losses as compared to load flow

without TCSC. Comparing the above two programs, we can conclude that in

load flow with TCSC real power loss, reactive power loss are reduced.

Hence the total cost of production function will be reduced in load flow with

TCSC compared without TCSC.

4.3. CONCLUSION

41

Page 42: Thyristor Controlled Series Capacitor FAIR COPY 1234

This project work has presented a Newton-Raphson load flow

algorithm to solve power flow problems in power systems with Thyristor

controlled series capacitor (TCSC). This algorithm is capable of solving

power networks very reliably. The IEEE 6 Bus system has been used to

demonstrate the proposed method over a wide range of power flow

variations in the transmission system. It has also been observed that in IEEE

30 Bus system the results upto Ybus formation has been achieved and in

future load flow can also be determined. It has also been observed that it is

possible to place TCSC in specific transmission lines to improve the system

performance. The proposed algorithm has been tested for IEEE-6 Bus

system and it provides better power flow control. We have implemented and

tested the TCSC scheme on 6 bus Ward-Hale system. We have illustrated

how the proposed allocation scheme of TCSC, in which the voltage stability

margin is improved and losses are reduced after connecting the TCSC into

the power system.

4.4. FUTURE WORK

42

Page 43: Thyristor Controlled Series Capacitor FAIR COPY 1234

IEEE 30-BUS SYSTEM

To test the performance of the proposed algorithm IEEE 30 bus

test system as shown in figure A-5 with 230kv and 100 MVA base has been

considered. Specified power flow control over the transmission lines has

been achieved by determining the converged firing angle ‘α’.

The TCSC has been designed with an inductance of 5.2 mH and

capacitor of 200F.The firing angle of TCSC corresponding to the desired

increase in power in the line without TCSC.

Out of 41 lines available in the system, solutions for specific

lines have been presented. Unfortunately rest of the lines fails to provide

better power flow control with TCSC. Even though the solutions for positive

increase in power flow are demonstrated but the same procedure can be

repeated for negative power flow control also.

Data for sample problem

Tables A-6, A-7, A-8, A-9 gives the details of the generator,

transformer, load and bus data respectively for the IEEE 30 bus system is

given in appendices. The figure A-5 shows the line diagram of IEEE 30 bus

system also given in appendices.

APPENDICES

A-1 Bus diagram for Ward and Hale 6 bus system:

43

Page 44: Thyristor Controlled Series Capacitor FAIR COPY 1234

Fig A-1 Six Bus Ward and Hale System

TABLE A2-Line Data of Six bus system

Bus Bus R X ½ B Tap Max

44

Page 45: Thyristor Controlled Series Capacitor FAIR COPY 1234

nl nr P.U P.U P.U Setting Rating1 6 0.123 0.518 0.0 0 65.0

1 4 0.080 0.370 0.0 0 75.0

1 4 0.080 0.470 0.0 0 75.0

2 5 0.282 0.640 0.0 0 65.0

2 3 0.723 1.050 0.0 0 40.0

4 6 0.087 0.407 0.0 0 30.0

4 3 0.0 0.133 0.0 0.956 60.0

6 5 0.0 0.300 0.0 0.981 70.0

TABLE A3 Bus Data of Six bus system

BusNo

Bus Code

Voltage Mag

Angle deg

load Generator Injected Qsh

MW MVAR MW MVAR Q min Q max

1 1 1.05 0.0 0.0 0.0 0.0 0.0 -50.0 100.0 0.0

2 2 1.05 0.0 0.0 0.0 50.0 0.0 -25.0 50.0 0.0

3 0 1.00 0.0 55.0 13.0 0.0 0.0 0.0 0.0 0.0

4 0 1.00 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

5 0 1.00 0.0 30.0 18.0 0.0 0.0 0.0 0.0 3.0

6 0 1.00 0.0 50.0 5.0 0.0 0.0 0.0 0.0 1.5

A-4 Program coding

45

Page 46: Thyristor Controlled Series Capacitor FAIR COPY 1234

Load Flow without TCSC

clear allclc

basemva = 100; accuracy = 0.001; maxiter = 50;sigma = 0.001;kl = 1;kg = kl;lamda = 0.1;

% 1- Slack Bus; 2- PV Bus: 0- PQ Bus% Bus Bus Voltage Angle ----Load---- --------Generator------- Injected% No Code Mag. Degree MW Mvar MW Mvar Qmin Qmax Mvarbusdata = [1 1 1.005 0.0 150.0 0.0 0.0 0.0 -30.0 100.0 0.0 2 2 1.010 0.0 0.0 0.0 243.0 0.0 -40.0 90.0 0.0 3 2 1.020 0.0 0.0 0.0 74.0 0.0 0.0 0.0 0.0 4 2 1.000 0.0 200.0 0.0 42.0 0.0 0.0 0.0 0.0 5 0 0.986 0.0 500.0 0.0 0.0 0.0 0.0 0.0 0.0];k = 0.01; % Line Data% Bus bus R X 1/2 B tap Line% nl nr p.u. p.u. p.u. setting Rating linedata=[1 2 0.005+k 0.01 0.0 1 200 2 3 0.005+k 0.20 0.0 1 300 2 4 0.005+k 0.15 0.0 1 150 3 4 0.005+k 0.02 0.0 1 150 3 5 0.005+k 0.01 0.0 1 400 1 5 0.0001+k 0.03 0.0 1 500]; fprintf('\n\n--------------------------------------------------------------------------');fprintf('\n Base Case Details . . . \n');fprintf('--------------------------------------------------------------------------\n');

lfybus; % Forms The Bus Admittance Matrixlfnewton; % Newton Raphson Power Flow

46

Page 47: Thyristor Controlled Series Capacitor FAIR COPY 1234

busout; % Prints The Power Flow Solution on the Screenlineflow; % Computes & Displays the Line Flow and Losses

cost = zeros(nbus, 1)';costg = zeros(nbus, 1)';costl = zeros(nbus, 1)';lamda = zeros(nbus - 1, 1)';

cof_a = [10 10 0.05 12 12 0.10 12 20 0.30 20 15 0.60];cof_b = zeros(5,2);

% Load datafload = [1 130 170 85 20 4 180 220 95 30 5 480 520 120 15]; slp = zeros(3,1);

% Find Slope for i = 1 : 3 slp(i)= (fload(i,3) - fload(i,2)) / (fload(i,5) - fload(i,4));end

fload = [fload slp];

% Find b - Coffecients Of Loadfor i = 1 : nbus for inl = 1:3 if (i == fload(inl)) cof_b(i,1) = fload(inl,3) * fload(inl,6) + fload(inl,4); cof_b(i,2) = fload(inl,6) / 2; end endend

% % Find Cost Of Load% for i = 1 : nbus

47

Page 48: Thyristor Controlled Series Capacitor FAIR COPY 1234

% costl(i) = cof_b(i,1)*Pd(i) + cof_b(i,2)*Pd(i)*Pd(i);% if i ~= 1 & i ~= 4% lamda(i)= lamda(i) + cof_b(i,1) + 2*cof_b(i,2)*Pd(i);% end% end

% Find Cost Of Generationfor i = 1 : nbus if busdata(i,2) ~= 0 costg(i)= cof_a(i,1) + cof_a(i,2) * Pg(i) + cof_a(i,3) * Pg(i) * Pg(i); lamda(i)= lamda(i) + cof_a(i,2) + 2 * cof_a(i,3) * Pg(i); endend

fprintf('--------------------------------------------------------------------------\n');fprintf(' The Total Production Cost Of All Generators = %8.2f Fr', sum(costg));fprintf('\n--------------------------------------------------------------------------\n');

Load Flow with TCSC

48

Page 49: Thyristor Controlled Series Capacitor FAIR COPY 1234

clear allclcbasemva = 100; accuracy = 0.001; maxiter = 50;k = 1;PBT = 96.461; QBT = 10.413;PET = -PBT;QET = -1.1 * QBT;

% 1- Slack Bus; 2- PV Bus: 0- PQ Bus% Bus Bus Voltage Angle ----Load---- -------Generator------- Injected% No Code Mag. Degree MW Mvar MW Mvar Qmin Qmax Mvarbusdata = [1 1 1.005 0.0 150.0 0.0 0.0 0.0 -30.0 100.0 0.0 2 2 1.010 0.0 0.0 0.0 243.0 0.0 -40.0 90.0 0.0 3 2 1.020 0.0 0.0 0.0 67.0 0.0 0.0 0.0 0.0 4 2 1.000 0.0 200.0 0.0 38.0 0.0 0.0 0.0 0.0 5 0 0.986 0.0 500.0 0.0 0.0 0.0 0.0 0.0 0.0]; busdata_base = busdata;

% Bus bus R X 1/2 B = 1 for lines% nl nr p.u. p.u. p.u. > 1 or < 1 tr. % tap at bus nl linedata=[1 2 0.005 0.01 0.0 1 200 2 3 0.005 0.20 0.0 1 300 2 4 0.005 0.15 0.0 1 150 3 4 0.005 0.02 0.0 1 150 3 5 0.005 0.01 0.0 1 400 1 5 0.0001 0.03 0.0 1 500]; % FACT - TCSC Data % n sb rb Xse Xsh Vse Vsh facts=[1 2 4 0.1 0.1 0.2 1.1];

% Extract Facts detail

49

Page 50: Thyristor Controlled Series Capacitor FAIR COPY 1234

fmax = max(facts(:,1));fet = facts(:,2); fbt = facts(:,3);fxb = facts(:,4);fno = facts(:,1);fxe = facts(:,5);fvb = facts(:,6);fve = facts(:,7);%---------------------- Update TCSC connected Bus data--------------------------------------------

% Connection between Exciter Terminal & Booster Terminal is broken% New bus is connected to Booster terminal Bus - PV Bus fiter = 1;Ebus = facts(:,2);Bbus = facts(:,3);nl = linedata(:,1); nr = linedata(:,2);nbr = length(linedata(:,1)); nbus = max(max(nl), max(nr));for L = 1:nbr if nl(L) == Ebus & nr(L) == Bbus % Line data Update linedata(L,1) = nbus + 1; else,endend

% Exciter Terminal of TCSC - Power drawnbusdata_base(Ebus,12)= PET;busdata_base(Ebus,13)= QET;busdata_base(Ebus,2)= 2; busdata_base(Ebus,3)= 1.01; busdata_base(Ebus,4)= 0.0; Bbus = nbus + 1;% Booster Terminal of TCSC - Power Injection% New Bus is created - PV Bus - generation = line flow% Bus No. PV -- Voltage-- |--Load--| |-- Gen --| |-- Q limit-| Capacitor ---TCSC--% Bus Mag. Angle | P Q | | P Q | | Qmin Qmax| Bank(Var) P Qbusdataf=[Bbus 0 1.01 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 PBT QBT];

50

Page 51: Thyristor Controlled Series Capacitor FAIR COPY 1234

% Updated busdata with FACTS -Adding rowbusdata=[busdata_base;busdataf];

fprintf('\n~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~')fprintf('\n After TCSC connection ')fprintf('\n\n TCSC connected between Bus %g and Bus %g ',fet(fiter),fbt(fiter))fprintf('\t\t Exciter Bus=%g and Booster Bus=%g',Ebus,Bbus)fprintf('\n~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~\n')

lfybus % form the bus admittance matrixVmat=zeros(nbus+2,1);Amat=zeros(nbus+2,1);%----------------------------------------------------------------------------------------% Modified Newton Raphson Methodns=0;ng=0;Vm=0; delta=0; yload=0; deltad=0;

for k=1:nbus n = busdata(k,1); kb(n) = busdata(k,2); Vm(n) = busdata(k,3); delta(n) = busdata(k,4); Pd(n) = busdata(k,5); Qd(n) = busdata(k,6); Pg(n) = busdata(k,7); Qg(n) = busdata(k,8); Qmin(n) = busdata(k,9); Qmax(n) = busdata(k,10); Qsh(n) = busdata(k,11); PTCSC(n) = busdata(k,12); QTCSC(n)=busdata(k,13); if Vm(n) <= 0 Vm(n) = 1.0; V(n) = 1 + j * 0; else delta(n) = pi/180*delta(n);

51

Page 52: Thyristor Controlled Series Capacitor FAIR COPY 1234

V(n) = Vm(n)*(cos(delta(n)) + j*sin(delta(n))); P(n)=(Pg(n)-Pd(n)+PTCSC(n))/basemva; Q(n)=(Qg(n)-Qd(n)+ Qsh(n)+QTCSC(n))/basemva; S(n) = P(n) + j*Q(n); endendk=nbus;Vm(k+1)=fvb(fiter); Vm(k+2)=fve(fiter);delta(k+1)=0.0; delta(k+2)=0.0;

Vm_first=Vm;delta_first=delta;

for k=1:nbus if kb(k) == 1, ns = ns+1; else, end if kb(k) == 2 ng = ng+1; else, end ngs(k) = ng; nss(k) = ns;endYm = abs(Ybus);t = angle(Ybus);rowb=2*nbus-ng-2*ns;colb=rowb;m=2*nbus-ng-2*ns + 4*fmax;maxerror = 1; converge=1;iter = 0;

% Start of iterationsclear A DC J DX% maxiter=1;while maxerror >= accuracy & iter <= maxiter % Test for max. power mismatchfor i=1:mfor k=1:m A(i,k)=0; %Initializing Jacobian matrixend, endDC=zeros(1,m); DX=zeros(m,1);iter = iter+1;

52

Page 53: Thyristor Controlled Series Capacitor FAIR COPY 1234

for n=1:nbusnn=n-nss(n);lm=nbus+n-ngs(n)-nss(n)-ns;J11=0; J22=0; J33=0; J44=0; for i=1:nbr if nl(i) == n | nr(i) == n if nl(i) == n, l = nr(i); end if nr(i) == n, l = nl(i); end J11=J11+ Vm(n)*Vm(l)*Ym(n,l)*sin(t(n,l)- delta(n) + delta(l)); J33=J33+ Vm(n)*Vm(l)*Ym(n,l)*cos(t(n,l)- delta(n) + delta(l)); if kb(n)~=1 J22=J22+ Vm(l)*Ym(n,l)*cos(t(n,l)- delta(n) + delta(l)); J44=J44+ Vm(l)*Ym(n,l)*sin(t(n,l)- delta(n) + delta(l)); else, end if kb(n) ~= 1 & kb(l) ~=1 lk = nbus+l-ngs(l)-nss(l)-ns; ll = l -nss(l); % off diagonal elements of J1 A(nn, ll) =-Vm(n)*Vm(l)*Ym(n,l)*sin(t(n,l)- delta(n) + delta(l)); if kb(l) == 0 % off diagonal elements of J2 A(nn, lk) =Vm(n)*Ym(n,l)*cos(t(n,l)- delta(n) + delta(l));end if kb(n) == 0 % off diagonal elements of J3 A(lm, ll) =-Vm(n)*Vm(l)*Ym(n,l)*cos(t(n,l)- delta(n)+delta(l)); end if kb(n) == 0 & kb(l) == 0 % off diagonal elements of J4 A(lm, lk) =-Vm(n)*Ym(n,l)*sin(t(n,l)- delta(n) + delta(l));end else end else , end end Pk = Vm(n)^2*Ym(n,n)*cos(t(n,n))+J33; Qk = -Vm(n)^2*Ym(n,n)*sin(t(n,n))-J11; if kb(n) == 1 P(n)=Pk; Q(n) = Qk; end % Swing bus P if kb(n) == 2 Q(n)=Qk; if Qmax(n) ~= 0 Qgc = Q(n)*basemva + Qd(n) - Qsh(n)-(QTCSC(n)); if iter <= 7 if iter > 2 if Qgc < Qmin(n), Vm(n) = Vm(n) + 0.01; elseif Qgc > Qmax(n),

53

Page 54: Thyristor Controlled Series Capacitor FAIR COPY 1234

Vm(n) = Vm(n) - 0.01;end else, end else,end else,end end if kb(n) ~= 1 A(nn,nn) = J11; %diagonal elements of J1 DC(nn) = P(n)-Pk; end if kb(n) == 0 A(nn,lm) = 2*Vm(n)*Ym(n,n)*cos(t(n,n))+J22; %diagonal elements of J2 A(lm,nn)= J33; %diagonal elements of J3 A(lm,lm) =-2*Vm(n)*Ym(n,n)*sin(t(n,n))-J44; %diagonal of elements of J4 DC(lm) = Q(n)-Qk; endend%-------------------------------------------------------------------------------------

% PBT -----------------------l=Ebus;ll = l -nss(l); % Deltalk = nbus+l-ngs(l)-nss(l)-ns; % VoltA(rowb+1,ll)=(Vm(Bbus)*Vm(Ebus)*cos(delta(Bbus)-delta(Ebus)))/fxb(fiter);A(rowb+1,lk)=-((Vm(Bbus)*sin(delta(Bbus)-delta(Ebus)))/fxb(fiter));

l=Bbus;ll = l -nss(l); % Deltalk = nbus+l-ngs(l)-nss(l)-ns; % VoltA(rowb+1,ll)=-((Vm(Bbus)*Vm(Ebus)*cos(delta(Bbus)-delta(Ebus)))/fxb(fiter))... -((Vm(Bbus)*Vm(nbus+fiter)*cos(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter));A(rowb+1,lk)=-((Vm(Ebus)*sin(delta(Bbus)-delta(Ebus)))/fxb(fiter))... -((Vm(nbus+fiter)*sin(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter)); % PET -----------------------l=Ebus;ll = l -nss(l); % Deletlk = nbus+l-ngs(l)-nss(l)-ns; % Volt

% Modified flow

54

Page 55: Thyristor Controlled Series Capacitor FAIR COPY 1234

A(rowb+2,ll)=((Vm(Ebus)*Vm(nbus+fiter)*cos(delta(Ebus)-delta(nbus+fiter))/fxb(fiter)))... -((Vm(Ebus)*Vm(Bbus)*cos(delta(Ebus)-delta(Bbus))/fxb(fiter)))... -((Vm(Ebus)*Vm(nbus+2*fiter)*cos(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter)); A(rowb+2,lk)=((Vm(nbus+fiter)*sin(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter))... -((Vm(Bbus)*sin(delta(Ebus)-delta(Bbus))/fxb(fiter)))... -((Vm(nbus+2*fiter)*sin(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));

l=Bbus;ll = l -nss(l); % Delbtlk = nbus+l-ngs(l)-nss(l)-ns; % Volt

% Modified flowA(rowb+2,ll)=((Vm(Ebus)*Vm(Bbus)*cos(delta(Ebus)-delta(Bbus))/fxb(fiter))); A(rowb+2,lk)=-(Vm(Ebus)*sin(delta(Ebus)-delta(Bbus))/fxb(fiter));

% QBT -----------------------l=Ebus;ll = l -nss(l); % Deltalk = nbus+l-ngs(l)-nss(l)-ns; % VoltA(rowb+3,ll)=((Vm(Bbus)*Vm(Ebus)*sin(delta(Bbus)-delta(Ebus)))/fxb(fiter));A(rowb+3,lk)=(Vm(Bbus)*cos(delta(Bbus)-delta(Ebus)))/fxb(fiter);

l=Bbus;ll = l -nss(l); % Deltalk = nbus+l-ngs(l)-nss(l)-ns; % Volt

A(rowb+3,ll)=-((Vm(Bbus)*Vm(Ebus)*sin(delta(Bbus)-delta(Ebus)))/fxb(fiter))... -((Vm(Bbus)*Vm(nbus+fiter)*sin(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter));

A(rowb+3,lk)=((Vm(Ebus)*cos(delta(Bbus)-delta(Ebus)))/fxb(fiter))... +((Vm(nbus+fiter)*cos(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter))-(2*Vm(Bbus)/fxb(fiter)); % QET -----------------------l=Ebus;ll = l -nss(l); % Deletlk = nbus+l-ngs(l)-nss(l)-ns; % Volt

55

Page 56: Thyristor Controlled Series Capacitor FAIR COPY 1234

% Modified flowA(rowb+4,ll)=((Vm(Ebus)*Vm(nbus+fiter)*sin(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter))... -((Vm(Ebus)*Vm(Bbus)*sin(delta(Ebus)-delta(Bbus)))/fxb(fiter))... -((Vm(Ebus)*Vm(nbus+2*fiter)*sin(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));

A(rowb+4,lk)=-(2*Vm(Ebus)/fxb(fiter))- (2*Vm(Ebus)/fxe(fiter))... -((Vm(nbus+fiter)*cos(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter))... +((Vm(Bbus)*cos(delta(Ebus)-delta(Bbus)))/fxb(fiter))... +((Vm(nbus+2*fiter)*cos(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));

l = Bbus;ll = l -nss(l); % Delbtlk = nbus+l-ngs(l)-nss(l)-ns; % Volt

% Modified flowA(rowb+4,ll)=((Vm(Ebus)*Vm(Bbus)*sin(delta(Ebus)-delta(Bbus)))/fxb(fiter));A(rowb+4,lk)=((Vm(Ebus)*cos(delta(Ebus)-delta(Bbus)))/fxb(fiter));

% --------------------------- J5 Updation -----------------------------------------------% PBT--------A(rowb+1,colb+1)=(Vm(Bbus)*Vm(nbus+fiter)*cos(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+1,colb+2)=0;A(rowb+1,colb+3)=-((Vm(Bbus)*sin(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter));A(rowb+1,colb+4)=0;

% Modified flowA(rowb+2,colb+1)=-(Vm(Ebus)*Vm(nbus+fiter)*cos(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+2,colb+2)=((Vm(Ebus)*Vm(nbus+2*fiter)*cos(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));A(rowb+2,colb+3)=((Vm(Ebus)*sin(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter));A(rowb+2,colb+4)=-(Vm(Ebus)*sin(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter);

% QBT-------- A(rowb+3,colb+1)=(Vm(Bbus)*Vm(nbus+fiter)*sin(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+3,colb+2)=0;

56

Page 57: Thyristor Controlled Series Capacitor FAIR COPY 1234

A(rowb+3,colb+3)=(Vm(Bbus)*cos(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+3,colb+4)=0;

% Modified flowA(rowb+4,colb+1)=-(Vm(Ebus)*Vm(nbus+fiter)*sin(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+4,colb+2)=((Vm(Ebus)*Vm(nbus+2*fiter)*sin(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));A(rowb+4,colb+3)=-(Vm(Ebus)*cos(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter);A(rowb+4,colb+4)=((Vm(Ebus)*cos(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter)); % DC column matrix update----------FPBT=-((Vm(Bbus)*Vm(Ebus)*sin(delta(Bbus)-delta(Ebus)))/fxb(fiter))... -((Vm(Bbus)*Vm(nbus+fiter)*sin(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter));

% Modified flowFPET=((Vm(Ebus)*Vm(nbus+fiter)*sin(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter))... -((Vm(Ebus)*Vm(Bbus)*sin(delta(Ebus)-delta(Bbus)))/fxb(fiter))... -((Vm(Ebus)*Vm(nbus+2*fiter)*sin(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));

FQBT=((Vm(Bbus)*Vm(Ebus)*cos(delta(Bbus)-delta(Ebus)))/fxb(fiter))... +((Vm(Bbus)*Vm(nbus+fiter)*cos(delta(Bbus)-delta(nbus+fiter)))/fxb(fiter))... -(Vm(Bbus)*Vm(Bbus)/fxb(fiter));

% Modified flowFQET=-(Vm(Ebus)*Vm(Ebus)/fxb(fiter))- (Vm(Ebus)*Vm(Ebus)/fxe(fiter))... -((Vm(Ebus)*Vm(nbus+fiter)*cos(delta(Ebus)-delta(nbus+fiter)))/fxb(fiter))... +((Vm(Ebus)*Vm(Bbus)*cos(delta(Ebus)-delta(Bbus)))/fxb(fiter))... +((Vm(Ebus)*Vm(nbus+2*fiter)*cos(delta(Ebus)-delta(nbus+2*fiter)))/fxe(fiter));

DC(colb+1)=(PBT/basemva)-FPBT; % DELBDC(colb+2)=(PET/basemva)-FPET; % DELEDC(colb+3)=(QBT/basemva)-FQBT; % VBDC(colb+4)=(QET/basemva)-FQET; % VEQET=Q(Ebus)*basemva + Qd(Ebus) - Qsh(Ebus)-QTCSC(Ebus);%--------------------------------------------------DX=A\DC';for n=1:nbus nn=n-nss(n); lm=nbus+n-ngs(n)-nss(n)-ns;

57

Page 58: Thyristor Controlled Series Capacitor FAIR COPY 1234

if kb(n) ~= 1 delta(n) = delta(n)+DX(nn); end if kb(n) == 0 Vm(n)=Vm(n)+DX(lm); end end%--------------------------------------------------%TCSC DELE,DELB,VE,VB Updatedelta(nbus+1)= delta(nbus+1)+DX(rowb+1); % DELBdelta(nbus+2)= delta(nbus+2)+DX(rowb+2); % DELEVm(nbus+1)= Vm(nbus+1)+DX(rowb+3); % VBVm(nbus+2)= Vm(nbus+2)+DX(rowb+4); % VEVmat=[Vmat Vm'];Amat=[Amat delta'];maxerror=max(abs(DC));if iter == maxiter & maxerror > accuracy fprintf('\nWARNING: Iterative solution did not converged after ') fprintf('%g', iter), fprintf(' iterations.\n\n') fprintf('Press Enter to terminate the iterations and print the results \n') converge = 0; pause, else, end end

if converge ~= 1 tech= (' ITERATIVE SOLUTION DID NOT CONVERGE'); else, tech=(' Power Flow Solution by Newton-Raphson Method');end

V = Vm.*cos(delta)+j*Vm.*sin(delta);deltad=180/pi*delta;i=sqrt(-1);k=0;

for n = 1:nbus if kb(n) == 1 k=k+1; S(n)= P(n)+j*Q(n); Pg(n) = P(n)*basemva + Pd(n)-PTCSC(n); Qg(n) = Q(n)*basemva + Qd(n) - Qsh(n)-QTCSC(n); Pgg(k)=Pg(n); Qgg(k)=Qg(n); elseif kb(n) ==2

58

Page 59: Thyristor Controlled Series Capacitor FAIR COPY 1234

k=k+1; S(n)=P(n)+j*Q(n); Qg(n) = Q(n)*basemva + Qd(n) - Qsh(n)-QTCSC(n); Pgg(k)=Pg(n); Qgg(k)=Qg(n); end yload(n) = (Pd(n)- j*Qd(n)+j*Qsh(n))/(basemva*Vm(n)^2);end

for k=1:nbus busdataVm(k)=Vm(k); busdatadeltad(k)=deltad(k);endbusdata(:,3)=busdataVm'; busdata(:,4)=busdatadeltad';Pgt = sum(Pg); Qgt = sum(Qg); Pdt = sum(Pd); Qdt = sum(Qd);Qsht = sum(Qsh);

%-----------------------------------------------------------------------------------------------------busout_TCSC % Prints the power flow solution on the screenlineflow % Computes and displays the line flow and losses

cost = [0 0 0 0 0];costg = [0 0 0 0 0];costl = [0 0 0 0 0];lamda = [0 0 0 0 0];cof_a = [10 10 0.05 12 12 0.10 12 20 0.30 20 15 0.60];cof_b = zeros(5,2);% Load datafload =[1 130 170 85 20 4 180 220 95 30 5 480 520 120 15];slp = zeros(3,1);% Find Slope

59

Page 60: Thyristor Controlled Series Capacitor FAIR COPY 1234

for i = 1 : 3 slp(i)= (fload(i,3) - fload(i,2)) / (fload(i,5) - fload(i,4));endfload = [fload slp];

% Find b - coffecients for loadfor i = 1 : nbus - 1 for inl = 1 : 3 if (i == fload(inl)) cof_b(i,1) = fload(inl,3)*fload(inl,6) + fload(inl,4); cof_b(i,2) = fload(inl,6) / 2; end endend% % Find cost of load% for i = 1 : nbus - 1% costl(i)= cof_b(i,1)*Pd(i) + 2*cof_b(i,2)*Pd(i)*Pd(i);% if i~=4 & i~=1% lamda(i)= lamda(i) + cof_b(i,1) + cof_b(i,2)*Pd(i);% end% end

% Find cost of generationfor i = 1 : nbus - 1 if busdata(i,2) ~= 0 costg(i)= cof_a(i,1) + cof_a(i,2)*Pg(i) + cof_a(i,3)*Pg(i)*Pg(i); lamda(i)= lamda(i) + cof_a(i,2) + 2*cof_a(i,3)*Pg(i); endendfprintf('--------------------------------------------------------------------------\n');fprintf(' The Total Production Cost Of All Generators = %8.2f Fr', sum(costg));fprintf('\n--------------------------------------------------------------------------\n');

A-5 Bus diagram for 30 bus system:

60

Page 61: Thyristor Controlled Series Capacitor FAIR COPY 1234

Fig A-5 IEEE 30 BUS SYSTEM.

Table A-6 Generator data for 30 bus system

61

Page 62: Thyristor Controlled Series Capacitor FAIR COPY 1234

Table A-7-Transformer Data for 30 bus system

Transformer no

Bus

Tap Setting From to

1 6 9 1.0155

2 6 10 0.9629

3 4 12 1.0129

4 28 27 0.9581

Table A-8 Load Data for 30 bus system

Bus

No

Load Bus

No

Load

MW MVAR MW MVAR

1 0 0 16 3.5000 1.8000

Bus no PG Min MW

PG Max MW

QG Min MVAR

QG Max MVAR

1 50 200 -20 150

2 20 80 -20 60

5 15 50 -15 62.5

8 10 35 -15 48.7

11 10 30 -10 40.0

13 12 40 -15 44.7

62

Page 63: Thyristor Controlled Series Capacitor FAIR COPY 1234

2 21.7000 12.7000 17 9.0000 5.8000

3 2.4000 1.2000 18 3.2000 0.9000

4 7.6000 1.6000 19 9.5000 3.4000

5 94.2000 19.0000 20 2.2000 0.7000

6 0 0 21 17.5000 11.2000

7 22.8000 10.9000 22 0 0

8 30.0000 30.0000 23 3.2000 1.6000

9 0 0 24 8.7000 6.7000

10 5.8000 2.0000 25 0 0

11 0 0 26 3.5000 2.3000

12 11.2000 7.5000 27 0 0

13 0 0 28 0 0

14 6.2000 1.6000 29 2.4000 0.9000

15 8.2000 2.5000 30 10.6000 1.9000

Table A-9 Bus Data for 30 bus system

Branch no

From bus To bus R (p.u) X (p.u) B (p.u) Rating MVA

1 1 2 0.0192 0.0575 0.0264 130

2 1 3 0.0452 0.1852 0.0204 130

63

Page 64: Thyristor Controlled Series Capacitor FAIR COPY 1234

3 2 4 0.0570 0.1737 0.0184 65

4 3 4 0.0132 0.0379 0.0042 130

5 2 5 0.0472 0.1983 0.0209 130

6 2 6 0.0581 0.1763 0.0187 65

7 4 6 0.0119 0.0414 0.0045 90

8 5 7 0.0460 0.1160 0.0102 70

9 6 7 0.0267 0.0820 0.0085 130

10 6 8 0.0120 0.0420 0.0045 32

11 6 9 0.0 0.2080 0.0 65

12 6 10 0.0 0.5560 0.0 32

13 9 1 0.0 0.2080 0.0 65

14 9 10 0.0 0.1100 0.0 65

15 4 12 0.0 0.2560 0.0 65

16 12 13 0.0 0.1400 0.0 65

17 12 14 0.1231 0.2559 0.0 32

18 12 15 0.0662 0.1304 0.0 32

19 21 16 0.0945 0.1987 0.0 32

20 14 15 0.2210 0.1997 0.0 16

21 16 17 0.0824 0.1932 0.0 16

22 15 18 0.1070 0.2185 0.0 16

23 18 19 0.0639 0.1292 0.0 16

24 19 20 0.0340 0.0680 0.0 32

64

Page 65: Thyristor Controlled Series Capacitor FAIR COPY 1234

25 10 20 0.0936 0.2090 0.0 32

26 10 17 0.0324 0.0845 0.0 32

27 10 21 0.0348 0.0749 0.0 32

28 10 22 0.0727 0.1499 0.0 32

29 21 22 0.0116 0.0236 0.0 32

30 15 23 0.1000 0.2020 0.0 16

31 22 24 0.1150 0.1790 0.0 16

32 23 24 0.1320 0.2700 0.0 16

33 24 25 0.1885 0.3292 0.0 16

34 25 26 0.2544 0.3800 0.0 16

35 25 27 0.1093 0.2087 0.0 16

36 28 27 0.0 0.3690 0.0 65

37 27 29 0.2198 0.4153 0.0 16

38 27 30 0.3202 0.6027 0.0 16

39 29 30 0.2399 0.4533 0.0 16

40 8 28 0.0636 0.2000 0.0214 32

41 6 28 0.0169 0.0599 0.0065 32

REFERENCES

1. N. H. Hingorani, "Flexible AC transmission systems,"IEEE Spectrum,

p. 4045, Apr. 1993.

2. N. Cbristl, R. Hcdin, K. Sadck, P. Llitzelberger, p. E. Krduse, S.

M. McKcnna, A. H. Maiitaya, and D. Togerson, "Advanced series

65

Page 66: Thyristor Controlled Series Capacitor FAIR COPY 1234

compensations (ASC) with Thyristor controlled impedance," in Conj:

Large High Voltage Electric Sysrems (CIGXEJ, Paris, Sept. 1992, Paper

14/37/38-05.

3. S. G. Helbing and G. G. Kaiiidy, "investigations of an advanced form

of series compensation," IEEE Tranr. Power Delivery, vol. 9, no. 2, pp.

939-947, Apr. 1994.

4. C. R. Puerle-Esquivel and E. Acha, "A Newton-type algorithm for the

control of power flow in electrical power networks, "lEEE Trans. Power

System, vol. 12,no. 4,pp. 1474-1480,Nov. 1997.

5. SI C. R. Fuerte-Esquivel, E. Acha, S. G. Tan, and J. 1. Rico, "Efficient

object oriented power systems software far the analysis of large-scale

networks containing FACTS-controlled branches," IEEE Trans. Power

Systems, vol. 13, no. 2, pp. 464472, May 1998.

6. T. Faur and C. A. Csiiizares, "Effects of FACTS devices an system

loadability," in Pmc. N m h American Power Symposium (NAPS),

Bozeman, MT. USA, Oct. 1995, pp. 520-524.

7. Stott B, “Review of Load-flow Calculation Methods”, IEEE

Proceedings, Vol.62, pp. 916-929, July 1974.

8. Fuerte C.R., Acha E.: “A Newton-Type Algorithm for the Control

of Power Flow in Electrical Power Networks”: IEEE transactions

on Power Systems, vol. 12, N0.4, pp.1474-1480, November 1997

9. Noroozian M. and Andersson G. “Power Flow Control by Use of

Controllable Series Components”, IEEE Transactions on Power

Delivery, vol. 8, No. 3, pp.12-18, July 1993.

10. Noroozian M. Angquist L., Ghandhari M., Andersson G.

“Improving Power System Dynamics by Series-Connected FACTS

Devices”, IEEE Transactions on Power Delivery, vol. 12, No. 4,

66

Page 67: Thyristor Controlled Series Capacitor FAIR COPY 1234

pp.1635-1641, October 1997.

11. Song Y.H., Johns A.T: “Flexible AC Transmission Systems

(FACTS)”, The Institute of Electrical Engineers(IEE) Press,

London, U.K., 1999.

12 Hingorani N.G. and Gyugyi, L., “Understanding FACTS, Concepts

and Technology of Flexible AC Transmission Systems”, IEEE

Press, 2000.

13 Clark K. et al. “Thyristor Controlled Series Compensation

Application Study-Control Interaction Considerations”, IEEE

Transactions on Power Delivery vol.10, No. 2, 1031-1037, April

1995.

14. Claudio A. Canizares et al.: “Analysis of SVC and TCSC

Controllers in Voltage Collapse ”, IEEE transactions on Power

Systems vol.14, No. 1, pp. 158-165, February 1999.

1492

67