three-phase transformers and autobanks

22
Three-Phase Transformers and Autobanks T 1

Upload: others

Post on 18-Oct-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Three-Phase Transformers and Autobanks

Three-Phase Transformers and Autobanks

T

1

Page 2: Three-Phase Transformers and Autobanks

Three-Phase Transformers and Autobanks

2

Page 3: Three-Phase Transformers and Autobanks

Three-Phase Transformers and Autobanks

Converting pair-wise test data to “T” model data for short-circuit calculations.

150/200/250MVA 115 : 13.2 : 230kV

ZHM = j5.5% ZHL = j36% ZML = j28%

H M L

%67.3150

100%5.5 jj

NEWHMZ

%24150

100%36Z

NEWHL jj

%7.18150

100%28Z

NEWML jj

Calculate the “T” model for the three-winding bank:

%5.42

Z-ZZ Z MLHLHM

H j

%82.02

Z-ZZ Z HLMLHM

M j

%5.192

Z-ZZ Z HMMLHL

L j

First, put them on 100MVA base

Note: As a check, add the resulting “T” leakage impedances between turns. E.g. ZHM = ZH + ZM etc. and you should get the proper winding-winding test leakage impedances. 3

Page 4: Three-Phase Transformers and Autobanks

Three-Phase Transformers and Autobanks

%5.42

Z-ZZ Z MLHLHM

H j

%82.02

Z-ZZ Z HLMLHM

M j

%5.192

Z-ZZ Z HMMLHL

L j

H M

L

H M L

Positive Sequence

4

Page 5: Three-Phase Transformers and Autobanks

Three-Phase Transformers and Autobanks

%5.42

Z-ZZ Z MLHLHM

H j

%82.02

Z-ZZ Z HLMLHM

M j

%5.192

Z-ZZ Z HMMLHL

L j

H M

L

H M L

Zero Sequence

Note: Look at test report, zero sequence is often different than positive. 5

Page 6: Three-Phase Transformers and Autobanks

Autobanks as Polarizing Source for Ground Relays

CT inside the delta.

6

Page 7: Three-Phase Transformers and Autobanks

1. From the nameplate we see the H-X impedance is 3.99% on 10MVA base. 2. To evaluate the effectiveness of the autobank tertiary as a polarizing source we

need to know the zero sequence impedance data for the bank. Below is the “T” model as provided by the manufacturer.

3. The zero-sequence impedance is usually equal to the positive-sequence impedance in an autobank (typically shell core design).

4. Next, build symmetrical component model for short-circuit calculations…

7

Page 8: Three-Phase Transformers and Autobanks

8

Page 9: Three-Phase Transformers and Autobanks

To evaluate the autobank tertiary as a polarizing source we only need look at the zero sequence network and determine if current in the tertiary has the same relative direction and phase for faults on both sides of the bank.

9

Page 10: Three-Phase Transformers and Autobanks

Faults on the H side of the bank…

10

Page 11: Three-Phase Transformers and Autobanks

Faults on the H side of the bank…

Bus X

j0.110 j0.045

Bus H

j0.04384-j 0.00206

j0.08127

XI0

IT

Using simple current division we can find out how much of the I0 that flows from the autobank to the fault splits through the tertiary branch.

j0.08127)j0.00206(j0.110

j0.00206)(j0.110II 0T

0T I0.57I

Because this is a positive result we can expect IT to have the relative direction indicated by the arrow with a phase angle near the same as that of I0 (exactly the same if homogenous system). We will compare this result with what we find next for a fault on the X side to determine if this is a consistent polarizing source.

11

Page 12: Three-Phase Transformers and Autobanks

Faults on the X side of the bank…

Using simple current division we can find out how much of the I0 that flows from the autobank to the fault splits through the tertiary branch.

0T I0.52I

Because this is also a positive result we know that IT will have the same relative direction and phase angle relationship as before for faults on both sides of the autobank – making it a reliable source for polarizing.

j0.08127)j0.0450(j0.04384

j0.0450)(j0.04384II 0T

12

Page 13: Three-Phase Transformers and Autobanks

What if the negative branch of the “T” was larger than the zero sequence source impedance on that side of the bank?

Using current division we can find out how much of the I0 that flows from the autobank to the fault splits through the tertiary branch at IT.

j0.08127)j0.03(j0.01

j0.03)(j0.01II 0T

0T I0.33I

Because this is a negative result we know that IT will have a phase angle 180° away from I0 for faults on the X side of the autobank – and because faults on the H side produce polarizing current that is in phase with the I0 going into bus H from the autobank this is not a consistent polarizing source - making it an unreliable source for polarizing.

13

Page 14: Three-Phase Transformers and Autobanks

A few points… • All you need to evaluate the autobank tertiary for polarizing is the zero sequence “T” equivalent of the transformer and the minimum expected zero sequence source impedance on each side of the bank. • The reversal occurs because either the H-side or X-side zero sequence “T” branch is negative AND when added to the zero sequence source impedance on that side the result is negative. • The negative zero sequence branch typically occurs in the medium voltage branch but sometimes in the high voltage branch (or not at all). • The impedance of the tertiary branch in the autobank zero sequence “T” is always large such that the denominator of the current division equation will always be positive. • Even if your studies determine that the current will always have the same relative direction and phase angle relationship for faults on either side of the bank it still may not be a suitable polarizing source – it may not provide adequate current to satisfy the minimum sensitivity of the protective relay for all expected faults. This must be studied as well.

14

Page 15: Three-Phase Transformers and Autobanks

15

Page 16: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

16

Page 17: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Note: As a check, add the resulting “T” leakage impedances between turns. E.g. XHM = XH + XM 17

Page 18: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Using the same approach as earlier we can calculate the zero sequence current that flows from the H winding to a fault on the H side of the transformer and by current division we find that in the medium voltage winding.

18

Page 19: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Now, to do ampere-turn calculations we need to recognize a simple relationship between the “T” model and the physical windings themselves. They both have polarity marks that directly relate the two so that the “sense” of current flow in the T model matches the “sense” of current flow in the actual windings.

19

Page 20: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Now, we calculate the ampere-turns equation such that terms with a directional sense “into” polarity dots equals terms with a directional sense “out of” polarity dots. The only tricky part for the autotransformer as compared to a conventional bank is to use the proper voltage for the section of winding that each current flows through. Also, we are interested in the actual amperes coming up the common section of winding so we calculate it via Kirchhoff's nodal analysis.

Note: We could have calculated actual winding amperes like Blackburn did instead of only zero sequence amperes, but, we took advantage of the fact that we know only zero sequence flows in the delta tertiary. The positive and negative sequence components of the ampere turns would have balanced between the M and H winding and had no effect on the calculation of circulating delta I0. 20

Page 21: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Now that we know the current in the delta it is an easy matter to connect our CT to provide polarizing current to our relays.

Further: We can easily use ampere-turns in the other two phases of the autobank (B & C) to calculate the phase current in the 138kV side.

21

Page 22: Three-Phase Transformers and Autobanks

Autobank example from Blackburn’s Symmetrical Components text – shows ampere-turns calculations (page 236)

Complete solution of bank phase currents…

22