T H E U L T I M A T E M C B
48
■ Technologically advanced range of
MCB based distribution equipment
■ Incorporates many unique features
of benefit to all of our customers
■ Satisfies the diverse requirements of
the user, contractor, specifier, OEM
and distributor
■ Incorporates the revolutionary
RCBO
■ Distribution boards accept both
MCBs to BSEN60898 & BS1361
HRC fuses
■ Memshield 2 MCBs and ancillary
devices can be DIN-rail mounted and
connected with comb busbar
Memshield 2 type A and type B
distribution boards of equal width can be
vertically stacked and interlinked to
provide additional outgoing ways.
SP HRC fuse carriers can be fitted to
any Memshield 2 distribution board and
incorporate an MEM BS1361 HRC
fuse fitted plus facility for a spare fuse
contained in the carrier.
Memshield 2 devices are suitable
for DIN-rail mounting and can be
inter-connected with comb busbar.
Memshield 2 MCBs are rated at 10kA
Icn to BSEN60898 & BSEN60947-2.
MCBs comply with Lloyds Register of
Shipping. MCBs and RCCBs have
positive contact indication.REVOLUTIONARY...
The unique RCBO pod can be
fitted to any SP or SPSN MCB
offering hundreds of possible
combinations of circuit and
earth fault protection.
A wide choice of incoming
devices are available including
direct connection, switch-
disconnector, MCB, MCCB,
RCCB or fused combination
switch.Top or bottom cable entry.
Memshield 2 P47-91 1/8/02 10:01 Page 5
49
D I S T R I B U T I O N S Y S T E M
11129
5
4
1613
10
8
36
7
2
1
15
14
9
6
5
4
2
1
8
7
11
3
12
10
THE FEATURE PACKED, REVOLUTIONARY MEMSHIELD 2 RCBO
1 Earth fault sensitivity pod can be fitted to any standard SP or SPSN
Memshield MCB
2 Unique revolutionary design means that an RCBO within a SP (18mm) module
can be achieved
3 SP configuration allows a far greater number of devices to be fitted in a
distribution board
4 Use of the standard Memshield 2 MCB means that there are hundreds of possible
RCBO combinations providing an incredible choice
5 Standard features of the MCB are retained but with the added flexibility of earth
fault protection
6 Memshield 2 RCBOs are suitable for use in any Memshield 2 distribution board
or ideally suited to OEM applications
7 Four choices of sensitivity to meet the requirements of any installation
8 Time delay versions available to allow correct function of any downstream
residual current devices
9 The Memshield 2 RCBO complies with BSEN61009
10 An RCBO can be ordered simply by selecting the most suitable MCB for an
application and then adding the appropriate sensitivity suffix
11 The all new British design developed using state-of-the-art CAD equipment gives
you the assurance of quality, safety and performance
12 Earth fault protection is maintained even if the neutral connection is lost
13 Version suitable for use on 110V 50/60Hz systems
THE FEATURE PACKED MEMSHIELD 2 MCB
1 Any SP or SPSN MCB can be factory or site fitted with an RCBO pod providing
hundreds of possible combinations allowing you even more flexibility
2 Magnetic Type characteristics to BSEN60898 B, C, D for wide choice
of applications
3 Foolproof positive contact indication gives you the assurance of isolation function
4 Breaking capacities of up to 10kA (BSEN60898) allow increased
installation opportunities
5 Five pole configurations (SP, SPSN, DP, TP, with FP) and 14 current ratings (1,
2, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A) for increased flexibility
6 Quality trip free mechanism prevents MCBs from being held ‘ON’
7 Optional padlock dolly for positive locking ‘ON’ or ‘OFF’
8 High performance current limiting design for safer installations
9 Optional screw and terminal shields for full shrouding of MCBs
10 All new ‘easy fit’ British design using state-of-the-art CAD equipment gives you
the assurance of quality, safety and performance
11 Generous, wire-in, wire-out, box type terminals for cables up to 25mm2, and fork
type comb busbar facilities on line and load side for OEM installations
12 Terminals clamp cable and fork type comb busbar simultaneously
13 Mounting on standard 35mm DIN-rail to BS5584/EN50 022 for individual and
OEM installations
14 Finger protected combination head screws to increase safety and allow
easier installation
15 Optional rear connectors to allow cables up to 50mm2 to be terminated where
space is limited
16 Thermally calibrated to 40ºC with 50ºC option to cover a wider range of
ambient temperatures
Memshield 2 P47-91 1/8/02 10:02 Page 6
1 Easy fit, DIN-rail mounting, incoming devices simply slot
into place easing installation
2 HRC fuse modules can be fitted in place of outgoing MCBs
increasing flexibility
3 Attractive two-tone grey finish over rust protected steel
enclosure for lasting durability
4 Main earth stud allows earth to be terminated inside or
outside the enclosure
5 Type A distribution boards comply with BS5486:Pt 12 & 13
and BSEN60439-3; type B with BS5486:Pt 12 and
BSEN60439-3
6 Heavy guage removable gland plates are provided top and
bottom for ease of installation
7 Shrouded neutral bar for increased safety
8 Fully shrouded busbar for increased safety
9 Busbar design eliminates risk of ‘hot spots’
10 Earth and neutral bars can accommodate up to
25mm2
cables
11 Modular sizes and removable gland plates allow distribution
boards to be stacked vertically
12 Optional connecting kits can be used to electrically connect
two distribution boards together vertically. TPN boards can
also be linked horizontally (not shown)
13 Covers fit within enclosure dimensions allowing
adjacent mounting
50
M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM E M S H I E L D 2 F E A T U R E S A N D B E N E F I T S
4
1011
18
15
8
2
24
23
26
16
7
21
20
9
125
3
27
65
THE FEATURE PACKED MEMSHIELD 2 TYPE A SPN DISTRIBUTION BOARD
13
14
Memshield 2 P47-91 1/8/02 10:02 Page 7
14 The door can be closed when MCBs are padlocked ‘ON’
or ‘OFF’ to increase safety (not shown)
15 Unique blanking modules can be used to blank off
unused outgoing ways. The blanking module is the
profile of an MCB, so that it shrouds the busbar stab as
well for increased safety
16 Generous cable space is provided. Space behind the pan
assembly, on type A boards, allows bottom entry/exit
of cables
17 Optional adjustable flush mounting kits provide the
solution even where the mounting surface is uneven;
non-adjustable on type A (not shown)
18 All distribution boards have dished keyhole mounting
slots for easy surface installation even when the
mounting surface is uneven
19 Optional busbar connecting blocks for type A boards
allow the installer to fit DIN-rail mounted control
devices onto the pan assembly providing protection and
control for additional flexibility with economy and
compact size (not shown)
20 Pan assembles are fully removable to ease installation
21 Neutral links can be removed
for testing purposes
22 An optional clean earth kit can
be site installed for computer
installations - standard on TPN
distribution boards (not shown)
23 The door, when locked, covers
all devices and front cover
screws to prevent unwanted
access (not shown)
24 Doors can be site fitted with
either door barrel lock kits or
padlocking kits. Padlocking
kits allow the user to
standardise on all padlocking
arrangements for an
installation (not shown)
25 All incomers (except direct
connection) have positive
contact indication
26 Distribution boards can be fitted
with a wide range of extension
boxes including glazed door
types so the user can easily
identify the status of the fitted
control devices (not shown)
27 Modern styling allows the
range to discreetly blend in
with both industrial and
commercial premises
28 Dual earth and neutral bars on TPN distribution boards
for ease of installation
29 TPN and TPSN incoming device options include a 125A
fuse combination switch to give a compact solution to
discrimination problems at high current levels
30 TPN incomer options allow the fitting of MCCBs from
16A up to 200A
31 Split load, dual tariff and double pole distribution
boards are available as standard
32 Double pole boards can be fitted with SPSN MCBs
and SPSN RCBOs
33 Top entry distribution boards available.
51
THE FEATURE PACKED MEMSHIELD 2 TYPE B TPN DISTRIBUTION BOARD
23 14
13
27
7
5
21125
4
2
3
266
1831
11
20915
8
2810
2930
24
Memshield 2 P47-91 1/8/02 10:02 Page 8
52
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D S P N T Y P E A A N D D P V E R S I O N S - T Y P E A F O R M A T
Standard SPN type A distribution boards are available in six
sizes with a choice of 2, 4, 7, 10, 13, or 16 outgoing ways. DP
versions of type A distribution boards are also available having
5 or 8 DP outgoing ways. A wide range of incomers can be
fitted to allow for the flexibility needed in modern installations.
Split load and dual tariff SPN type A distribution boards are
available with up to 19 outgoing ways.
They comply fully with BS5486:Pt 12 & 13 and BSEN60439-3.
INCOMING DEVICES
100A lugs; 100A SPSN switch-disconnector; 100A SPSN
RCCB. For full range of SPSN RCCBs suitable for use as
incoming devices see page 65.
Please consult our Technical Services department for details of
an even wider choice of incoming devices.
OUTGOING DEVICES
For type A distribution boards: 1-63A Memshield 2 SP MCBs.
Types B, C, D, 10kA to BSEN60898; 5-45A fuse carriers,
16kA to BS1361; 1-63A 18mm SP RCBOs
For double pole distribution boards: 1-63A Memshield 2 SPSN
or DP MCBs. Types B, C, D, 10kA to BSEN60898; 1-63A
36mm SPSN RCBOs.
FEATURES
Distribution boards of equal width can be stacked vertically
without any other accessories. They can be electrically
connected to give more outgoing ways by using a connector kit
(see page 60).
Memshield modular control devices can be fitted by using a
busbar block kit to adapt the busbar (see page 60). AM13,
AMSL64/37 and AMDT74 distribution boards can be mounted
on top of any type B distribution board. A clean earth kit can
be used for computer installations (see page 60).
DOUBLE POLE DISTRIBUTION BOARDS
Memshield 2 double pole distribution boards have been
developed for specialist applications.
They allow for single pole and switched neutral MCBs to be
fitted on all outgoing circuits which is necessary for the control
of circuits situated in hazardous areas.
SPSN or DP MCBs and SPSN RCBOs can be fitted.
For 3 phase, 4 wire systems please contact us for details of our
four pole range of Memshield 2 distribution boards.
A-SELECT DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
2 way SPN type A AM2
4 way SPN type A AM4
7 way SPN type A AM7
10 way SPN type A AM10
13 way SPN type A AM13
16 way SPN type A AM16
5 way DP type A format AM5D
8 way DP type A format AM8D
B-SELECT 100A INCOMING DEVICE:
Incoming device supplied separately to distribution board.
DESCRIPTION LIST NO.
SPSN switch-disconnector (isolator) MS1001N
DP lugs (direct connection) MBT1002
SPSN 30mA RCCB AM100HE
SPSN 100mA RCCB AM100ME
SPSN 300mA RCCB AM100LE
SPSN 100mA time delayed RCCB AM100MET
SPSN 300mA time delayed RCCB AM100LET
C-EXAMPLE:
AM4 + MS1001N = 4 way SPN distribution board with 100A
switch-disconnector.
Use pages 61-64 to select outgoing devices and accessories.
Memshield 2 P47-91 1/8/02 10:02 Page 9
SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A
SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.
DESCRIPTION LIST NO.
10 way; 4 ways RCCB protected AMSL64
10 way; 7 ways RCCB protected AMSL37
13 way; 4 ways RCCB protected AMSL94
13 way; 7 ways RCCB protected AMSL67
13 way; 10 ways RCCB protected AMSL310
19 way; 10 ways RCCB protected AMSL910
N.B. AMSL910 = 2 row unit
DUAL TARIFF DISTRIBUTION BOARDS FITTED WITH 2
INCOMING SWITCH-DISCONNECTORS*
DESCRIPTION LIST NO.
7 + 4 way AMDT74
10 + 4 way AMDT104
7 + 7 way AMDT77
*Please consult our Technical Services department for other incomer
types, or configurations.
Example:
AMSL37 = 10 way SPN distribution board with main 100A switch
disconnector, and 7 RCCB protected ways.
CABLE CAPACITIES mm2
LUGS 50
SWITCH-DISCONNECTOR 50
RCCB 50
MCBs 25
EARTH BARS 25
NEUTRAL BARS 25
53
S P L I T L O A D & D U A L T A R I F F S P N T Y P E A
■ Clean earth kit available for all type Adistribution boards.
■ Any number of type A distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.
■ Consult us for even more incomer options.
■ Modular control/command devices can befitted into any SPN type A distributionboard by using the unique busbar block kit.See page 60 for details.
Memshield 2 P47-91 1/8/02 10:03 Page 10
54
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D 1 2 5 A T P N T Y P E B
A - SELECT 125A DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
4 way TPN type B BM41
6 way TPN type B BM61
8 way TPN type B BM81
12 way TPN type B BM121
16 way TPN type B BM161
24 way TPN type B BM242
B - SELECT 100/125A INCOMING DEVICE:
Incoming device supplied separately to distribution board.
DESCRIPTION LIST NO.
100A TP switch-disconnector (isolator) BMS1003
100A SPSN switch-disconnector (isolator) BMS1001N4*
125A TP switch-disconnector (isolator) BMS1253
100A TPSN switch-disconnector (isolator) BMS1004
100A TP lugs (direct connection) BMBT1003
100A TPSN 30mA RCCB BMR30
100A TPSN 100mA RCCB BMR100**
100A TPSN 300mA RCCB BMR300
100A TPSN 300mA RCCB BMR300Twith time delay
63A TP Type C MCB BMCH363
100A TP switch-disconnector BMCC1003feeding 100A TP AC1 contactor c/w
control circuit fuse & terminal block,
housed in extension box.
Top entry distribution boards with factory fitted 125A TP switch-
disconnector- add suffix T125 to list no. e.g. BM41T125.Not applicable to 24 way board; BM242.
*TPN to SPN conversion kit included.
**Not suitable for BM242.
C - EXAMPLE:
BM61 + BMS1003 = 6 way TPN distribution board with 100A
switch-disconnector.
Use pages 61 - 64 to select outgoing devices & accessories.
Standard 125A and 200A TPN type B distribution boards are
available with a choice of 4, 6, 8, 12, 16 or 24 outgoing ways.
A wide range of incomers can be fitted to allow for the
flexibility needed in modern installations. They comply fully
with BS5486 : Pt 12 and BSEN60439-3.
INCOMING DEVICES, 125A MAX
100A lugs; 100A SPSN, TP, or TPSN switch-disconnectors,
125A TP switch-disconnectors, 100A TPSN RCCBs; 63A TP
MCB. Please consult our Technical Services department for
details of other incoming device types.
INCOMING DEVICES, 200A
200A lugs; 200A SPSN, or TP switch-disconnectors; and any
TP ‘F’ frame MCCB up to 200A. All standard 100A
distribution board incomers can also be fitted.
OUTGOING DEVICES
1-63A Memshield 2 SP, DP and TP MCBs Types B, C, D, 10kA
to BSEN60898; 5-45A fuse carriers, 16kA to BS1361; 1-
63A SP 18mm RCBOs.
FEATURES
Distribution boards of equal width can be stacked vertically
without any other accessories. They can be electrically
connected vertically or horizontally to give more outgoing ways
by using a connector kit (see page 60). Memshield modular
control devices can be fitted by using an extension box (see
page 60). Many SPN type A distribution boards can be
mounted on top of any type B distribution board.
A clean earth facility is standard for computer installations.
Memshield 2 P47-91 1/8/02 10:03 Page 11
55
S T A N D A R D 2 0 0 A T P N T Y P E B
■ Two type B distribution boards can bepositioned side by side and electricallyinter-connected with a connector kit.
■ Any number of type B distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.
■ Clean earth facility standard within alltype B distribution boards.
■ Any TPN (type B) distribution board can
be simply converted to SPN by fitting
a conversion kit and SPSN switch-
disconnector incoming device.
■ Consult us for even more incoming options.
A - SELECT 200A DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
4 way TPN type B BM42
6 way TPN type B BM62
8 way TPN type B BM82
12 way TPN type B BM122
16 way TPN type B BM162
24 way TPN type B BM242
B - SELECT INCOMING DEVICE UP TO 200A:
Incoming device supplied separately to distribution board. 200A
switch-disconnector and MCCB incoming devices are supplied with
cable entry boxes. (100A incomers from page 54 can also be used).
DESCRIPTION LIST NO.
200A TP switch-disconnector (isolator) BMS2003†
160A TP switch-disconnector (isolator) BMS1603
200A SPSN switch-disconnector (isolator) BMS2001N*
TP kit for ‘F’ frame MCCB** BMIK2003†
TP lugs (direct connection) BMBT2003
Top entry distribution boards with factory fitted 160A TP switch -
disconnector - Add suffix T160 to list no. e.g. BM42T160.Not applicable to 24 way board BM242.
*Not suitable for BM242. TPN to SPN conversion kit included.
**Select ‘F’ frame MCCB for use with BMIK2003 from following table.
† Add suffix ‘P’ when these are to be fitted to BM242.
F FRAME MCCBS
DESCRIPTION Icu Ics LIST NO.
TP 100A 25kA 100% MFL1003
TP 125A 25kA 100% MFL1253
TP 160A 25kA 100% MFL1603
TP 200A 25kA 100% MFL2003
CABLE CAPACITIES mm2
LUGS (100A) 50
SWITCH-DISCONNECTOR (100A) 50
RCCB 50
LUGS (200A) 120
SWITCH-DISCONNECTOR (125A & 160A) 70
SWITCH-DISCONNECTOR (200A) 120
MCCB (‘F’ Frame type) 120
MCBs 25
EARTH BARS 25
NEUTRAL BARS 25
Memshield 2 P47-91 1/8/02 10:03 Page 12
56
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF C S I N C O M E R S T P N T Y P E B , D P V E R S I O N S - T Y P E B F O R M A T
FUSED COMBINATION SWITCH INCOMERS
TPN type B distribution boards are also available with a choice of
fitted TP or TPSN FCS incomers. The FCS incomer uses MEM BS88
fuses, which allow the unit to be fused from 2-125A. This is a benefit
for applications where the load may increase in the future, as the FCS
can be re-fused accordingly.
The exclusive use of MEM fuselinks in this equipment will extend thewarranty period to 3 years.
These distribution boards comply fully with BS5486 : Pt 12 and
BSEN60439-3.
125A TP DISTRIBUTION BOARDS WITH FITTED FUSE
COMBINATION SWITCH INCOMERS.
DESCRIPTION INCOMER LIST NO.
4 way TPN type B TP FCS BMFCS4
6 way TPN type B TP FCS BMFCS6
8 way TPN type B TP FCS BMFCS8
12 way TPN type B TP FCS BMFCS12
16 way TPN type B TP FCS BMFCS16
4 way TPN type B TPSN FCS BMFCSN4
6 way TPN type B TPSN FCS BMFCSN6
8 way TPN type B TPSN FCS BMFCSN8
12 way TPN type B TPSN FCS BMFCSN12
16 way TPN type B TPSN FCS BMFCSN16
N.B. All distribution boards with FCS type incomer are supplied with
125A fuses.
DOUBLE POLE DISTRIBUTION BOARDS
Memshield 2 double pole distribution boards have been developed for
specialist applications.
Double pole distribution boards have a single pole and switched neutral
incoming circuit. They allow for single pole and switched neutral
MCBs to be fitted on all outgoing circuits which is necessary for the
control of circuits situated in hazardous areas.
SPSN or DP MCBs and SPSN RCBOs can be fitted.
For 3 phase, 4 wire systems please contact us for details of our four
pole range of Memshield 2 distribution boards.
DP DISTRIBUTION BOARDS TYPE B FORMAT WITH FITTED
100A SPSN MAIN SWITCH-DISCONNECTOR.
DESCRIPTION LIST NO.
6 way DP (5 way SPSN) type B format BM61D
12 way DP (11 way SPSN) type B format BM121D
18 way DP (17 way SPSN) type B format BM181D
24 way DP (23 way SPSN) type B format BM241D
Memshield 2 P47-91 1/8/02 10:03 Page 13
SPLIT LOAD BOARDS
Split load TPN type B distribution boards are factory fitted with a
main 100A switch-disconnector and a 30mA RCCB. Please consult
our Technical Services department for details of other incoming
device options.
MODULAR ENCLOSURES
Memshield 2 modular enclosures can be used to house Memshield
2 protective and command devices. Enclosures are available to
house from 2 to 45 x 18mm modules in moulded or metal
construction up to IP55.
Up to three Memshield 2 type A pan assemblies can be fitted into
an enclosure.
To select a suitable enclosure, select the devices required and
calculate the amount of 18mm modules required, then select the
enclosure that can accommodate at least that many 18mm modules.
BMX 15 module enclosures can be mounted onto AM13 or any
Memshield 2 TPN distribution board. Distribution board accessories
e.g. door lock kit are suitable for use with BMX type enclosures.
BMXDC enclosures are fitted with earth and neutral bars as
standard. Additional earth and neutral bars for 30 and 45 way
enclosures are available for specific applications.
Metal enclosures will accommodate all modular devices, ie;
MCBs, RCCBs, RCBOs, fuse modules and command devices.
Moulded enclosures 4/6 QEL, 4EME and AM1SL will not
accept RCBOs.
4EME will accept command devices and TPSN RCCBs only.
CABLE EXTENSION BOXES
Cable extension boxes are for use with larger cables or for special
applications e.g. metering, etc. They can be fitted top and/or
bottom. All 200A type incomers include a cable extension box
where necessary.
All enclosures and extension boxes can be fitted top and/or bottom
of distribution boards in any quantity.
100A SPLIT LOAD DISTRIBUTION BOARDS WITH FITTED
100A MAIN SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.
DESCRIPTION LIST NO.12 way; 8 ways RCCB protected BMSL4812 way; 6 ways RCCB protected BMSL6612 way; 4 ways RCCB protected BMSL8416 way; 8 ways RCCB protected BMSL88
MEMSHIELD 2 ENCLOSURES - FOR MODULAR DEVICES
EARTH CAPACITYWITH DOOR TERMINAL IP RATING IN 18MM LIST NO.
PROVIDED MODULES
MOULDED ENCLOSURESNo yes IP30 2 AM1SLNo yes IP30 4 4EMEYes yes IP55 4 4QELYes yes IP55 6 6QEL
METAL ENCLOSURESYes yes IP4X 4 BMXDC4Yes yes IP4X 6 BMXDC6Yes yes IP4X 9 BMXDC9Yes yes IP4X 15 BMXDC15Yes yes IP4X 18 BMXDC18Yes yes IP4X 30 BMXDC30Yes yes IP4X 45 BMXDC45
Yes-glazed yes IP4X 6 BMXDCG6Yes-glazed yes IP4X 9 BMXDCG9Yes-glazed yes IP4X 15 BMXDCG15Yes-glazed yes IP4X 18 BMXDCG18Yes-glazed yes IP4X 30 BMXDCG30Yes-glazed yes IP4X 45 BMXDCG45
N.B. AM1SL, 4QEL, 6QEL, can be wire sealed.
ENCLOSURE ACCESSORIES
DESCRIPTION LIST NO.Blanking module for unused MBPways-metal enclosures
Additional earth bar for 30 & 45 BMXE15way BMXDC enclosures
Additional neutral bar for 30 & 45 BMXN15way BMXDC enclosures
Door barrel lock for 4, 6, 9, 15 way AMDLBMXDC enclosures
Door barrel lock for 30 & 45 way BMDLBMXDC enclosures
Padlocking kit for 4, 6, 9, 15 way AMPLBMXDC enclosures
Padlocking kit for 30 & 45 way BMPLBMXDC enclosures
Padlock for AMPL/BMPL PD1EXTENSION BOXES FOR TPN AND AM13 DISTRIBUTION BOARDS.
DESCRIPTION LIST NO.Cable spreader extension box, 162mm high BMXPC1Cable spreader extension box, 250mm high BMXPC2
57
S P L I T L O A D B O A R D S , E X T E N S I O N B O X E S A N D M O D U L A R E N C L O S U R E S
Memshield 2 P47-91 1/8/02 10:03 Page 14
58
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF L U S H M O U N T I N G K I T S & P A N A S S E M B L I E S
FLUSH KITS
Type A and type B distribution boards are suitable for flush mounting
applications by using the appropriate kit except 24 way TPN.
FEATURES
Memshield 2 type B flush mounting kits can be adjusted to
accommodate slightly uneven mounting surfaces.
Please contact our Technical Services department for other
flush mounting possibilities.
MEMSHIELD 2 FLUSH MOUNTING KITS
DISTRIBUTION BOARD TYPE LIST NO.
AM4, BMXDC6, BMXDCG6 AMFK4
AM7, BMXDC9, BMXDCG9 AMFK7
AM10, AM5D AMFK10
AM13, AMSL37, AMSL64, AMDT74, AMFK13BMXDC15, BMXDCG15
AM8D, AM16, AMDT77, AMDT104, AMFK16AMSL67, AMSL94, AMSL310
BM41, BM61D BMFK1
BM61, BM42 BMFK2
BM81, BM62, BM121D BMFK3
BM82 BMFK4
BM121, BM122, BM181D, BMFK5BMXDC45, BMXDCG45
BM161, BM162, BM241D BMFK6
BMSL48, BMSL66, BMSL84 BMFK7
BM42* BMFK21
BM62* BMFK22
BM82* BMFK23
BM122* BMFK24
BM162* BMFK25
*When fitted with BMIK2003, BMS2003, BMS2001N,or BMXPC1
PAN ASSEMBLIES
Memshield pan assemblies offer a high degree of flexibility for
custom applications.
SPN types are available with 4, 7, 10, 13, and 16 ways. DP types
with 5, 6, 8, 12, 18 and 24 ways. TPN types with 4, 6, 8, 12,16
and 24 TP ways.
Where the switching of outgoing neutrals on 3 phase pan
assemblies is required, eg: for switching circuits in hazardous
areas, please contact us.
Refer to pages 52, 54 and 55 for incoming devices.
Add suffix ‘P’ to incomer kits BMS2001N, BMS2003 and
BMIK2003 to order kit without cable box.
Refer to pages 61 and 68 for outgoing devices.
FEATURES
Memshield 2 pan assemblies are suitable for inclusion in other
factory built assemblies and as replacements for distribution board
interiors. Pan assemblies feature fully shrouded busbars. The
busbars can be connected by using a busbar connector kit. SPN
distribution boards can be adapted to take modular control devices
using a busbar kit to adapt the busbar, see page 60.
Please contact our Technical Services department for other pan
assembly types.
MEMSHIELD 2 PAN ASSEMBLIES (INTERIORS)
DESCRIPTION LIST NO.
100A 4 way SPN without incomer AMP4
100A 7 way SPN without incomer AMP7
100A 10 way SPN without incomer AMP10
100A 13 way SPN without incomer AMP13
100A 16 way SPN without incomer AMP16
100A 5 way DP without incomer AMP5D
100A 8 way DP without incomer AMP8D
200A 6 way DP main lugs fitted BMP61D
200A 12 way DP main lugs fitted BMP121D
200A 18 way DP main lugs fitted BMP181D
200A 24 way DP main lugs fitted BMP241D
125A 4 way TPN without incomer BMP41
125A 6 way TPN without incomer BMP61
125A 8 way TPN without incomer BMP81
200A 4 way TPN without incomer BMP42
200A 6 way TPN without incomer BMP62
200A 8 way TPN without incomer BMP82
200A 12 way TPN without incomer BMP122
200A 16 way TPN without incomer BMP162
200A 24 way TPN main lugs fitted BMP242L
MEMSHIELD 2 PAN ASSEMBLIES (WITHOUT EARTH AND
NEUTRAL BARS)
DESCRIPTION LIST NO.
200A 4 way TPN main lugs fitted BMPS42
200A 6 way TPN main lugs fitted BMPS62
200A 8 way TPN main lugs fitted BMPS82
200A 12 way TPN main lugs fitted BMPS122
200A 16 way TPN main lugs fitted BMPS162
200A 24 way TPN main lugs fitted BMP242LWEN
Memshield 2 P47-91 1/8/02 10:03 Page 15
59
M E M S H I E L D 2 T V S S R A N G E
The MEMSHIELD 2 Surge Protective Device has been developed
specifically for application with Memshield 2 ‘A’ Type and ‘B’ Type
single and three phase MCB distribution boards, ensuring outstanding
product performance for all sensitive, mission critical and general
purpose loads. The UL1449 Second Edition and UL1283 listed devices
provide high peak surge current ratings and exceptionally low real-
world measured limiting (let-through) voltage values, together with
outstanding durability, assuring the Memshield 2 range will provide a
lifetime of effective, maintenance free protection for all electrical and
electronic systems.
PROTECTION:Active Response Network (ARN) provides optimum suppression of
internal switching generated transients.
Threshold Response Network (TRN) provides maximum suppression
of high energy impulse generated transients.
This assures excellent protection of sensitive electronic, electro-
mechanical and micro-processor based equipment.
GENERAL SPECIFICATIONS:
DESCRIPTION: Parallel configured, hard wire connected, 80kA
per phase peak surge current Transient Voltage
Surge Suppressor.
APPLICATION: Location Categories B and A, medium and low
exposure level. General purpose, sensitive, and
mission critical loads. Small AC power service
entrances (≤ 200amps), sub and final circuit
Memshield 2 MCB distribution boards.
WARRANTY: 10-Year Free Replacement.
UNIT LISTINGS: UL1449 Second Edition, UL1283 Filter.
QUALITY: ISO 9001: 1994 Quality System Certification
BSI FM 30833.
MECHANICAL SPECIFICATIONS:
TVSS ENCLOSURE: IP23 rated steel enclosure.
MOUNTING: Conduit fitting and multi-point mounting feet.
CONNECTION: Standard products include approx. 450mm factory
fitted stranded cable #10 AWG (≈ 6mm2). Flush
mounting plate available, order list number ZPLATE-4
SHIPPING WEIGHT: 2.2kg.
TVSS MODULESEach TVSS module is supplied complete with the following:
■ TVSS unit as detailed above
■ 32A Type C MCB; SP for Type A (SPN) and TP for Type B
(TPN) distribution boards
■ Fittings to attach TVSS unit to distribution board
■ Full instructions
TVSS MODULE KIT LIST NO.
For Type A (SPN) distribution boards M2SSK1
For Type B (TPN) distribution boards M2SSK3
For full details of TVSS products refer to the Transient Voltage
Surge Suppression catalogue available on request.
Memshield 2 P47-91 1/8/02 10:04 Page 16
UNIQUE BUSBAR BLOCK KIT
Memshield 2 type A SPN distribution boardsoffer the installer unique flexibility.
By using a busbar block kit a standard type Adistribution board can be adapted on site to accept Memshield 2 DIN-rail mounting control devices as well as MCBs. The kit includes ashorter busbar, to replace the standard busbar, which simply clips tothe pan assembly, plus a mounting rail for the control devices.
Use of a busbar block kit can mean that a conventional extension boxfor control devices is unnecessary - saving the installer time and spaceas well as providing the user with a neater more compact installation.
The number of ways indicated in the table are for outgoing MCBs,remaining ways in the distribution board can be fitted with control devices.
Eg:- 10 way type A board = AM10, fitted with MMBK4 willaccommodate 4 x SP MCBs plus up to 6 x SP control devices.
BUSBAR BLOCK KIT LIST NO.
4 way SP busbar block MMBK4
7 way SP busbar block MMBK7
10 way SP busbar block MMBK10
13 way SP busbar block MMBK13
60
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SA C C E S S O R I E S
DISTRIBUTION TOTAL TOTAL TOTALBOARD LIST NO. NUMBER OF EARTH NUMBER OF EARTH NUMBER OF EARTH
TERMINALS FITTED TERMINALS IF TERMINALS IFAS STANDARD 2 OFF BMNE8 ADDED 2 OFF BMNE16 ADDED
BM41 16 28 N/ABM42 16 28 52
BM61 22 28 N/A
BM62 22 28 52
BM81 28 N/A N/A
BM82 28 N/A 52
BM121 40 N/A N/A
BM122 40 N/A 52
BM161 52 N/A N/A
BM162 52 N/A N/A
*Incoming device required for each linked distribution board.
†100A vertical kits can be uprated to 200A in order to connect 2 x 200A distribution boards by replacing suppliedcable with cable of appropriate rating.
DESCRIPTION LIST NO.Blanking module for unused way MBPBlanking module for half unused way when MCB auxiliary alarm contacts used MABP500 ml aerosol of light grey paint 2APDoor barrel lock for SPN distribution boards AMDLDoor padlocking kit for SPN distribution boards AMPLCoupling kit for 2 SPN distribution boards (vertical)* AMCKClean earth kit for SPN distribution boards 5 terminal AME5Clean earth kit for SPN distribution boards 11 terminal AME11Gland plate for AM4 MGP1Gland plate for AM7 MGP2Gland plate for AM10 MGP3Gland plate for AM13 MGP4Gland plate for AM16 MGP5IP42 gland plate for AM4, BMXDC6, BMXDCG6 MGP142IP42 gland plate for AM7, BMXDC9, BMXDCG9 MGP242IP42 gland plate for AM10 MGP342IP42 gland plate for AM13, BMXDC15, BMXDCG15 MGP442IP43 gland plate for BMXDC30/45, BMXDCG30/45 and all type B distribution boards except 24 way TPN
MGP442
IP42 gland plate for AM16 MGP542Door barrel lock for TPN distribution boards BMDLDoor padlocking kit for TPN distribution boards BMPL100A coupling kit for 2 TPN distribution boards (vertical)*†.Not suitable for BM242
BMCKV
125A coupling kit for 2 TPN distribution boards (horizontal). Not suitable for BM242
BMCKH
SPN conversion kit for TPN distribution boards BMSPNIP4X gland plate for all TPN distribution boards BMGP4Padlock for SPN and TPN distribution board padlock kits PD1
ADDITIONAL EARTH TERMINALS
Type B, TPN distribution boards aresupplied as standard with the number ofearth terminals shown in the table.
If required this can be increased byadditional earth bars List No. BMNE8 orBMNE16 - see table:
GENERAL ACCESSORIES
Distribution boards have front mounting
screws behind the door so that the cover cannot
be removed when the door is locked with a door
barrel lock or door padlocking kit providing a
high degree of security.
Keys for AMDL and BMDL are common
and will fit all.
Gland plates are available to increaseenclosure protection to IP42 on 4, 7, 10 &16 way A type enclosures; IP43 on all Btype enclosures except 24 way TPN.
Please contact our Technical Servicesdepartment for details of gland plateswithout knock-outs.
Memshield 2 P47-91 31/7/02 16:12 Page 17
M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SM I N I A T U R E C I R C U I T B R E A K E R S - T Y P E B & C 1 0 K A
61
The Memshield 2 MCB is an all new high performance
current limiting device with the ability to disconnect short
circuits of up to 10kA.
The feature packed device is both British designed and
manufactured, using the latest technology.
Memshield 2 miniature circuit breakers are available in one
of the widest ranges available in the world; over 600
different types are available.
The MCBs are suitable for use with Memshield 2 distribution
boards. In addition MCBs are suitable for a wide range of
OEM applications.
Current ratings are available in 1, 2, 4, 6, 8, 10, 13, 16, 20,
25, 32, 40, 50, and 63A. The range is available with types
B, C, and D, in single pole (SP), single pole and switched
neutral (SPSN), double pole (DP), triple pole (TP) and four
pole (FP) configurations.
On SPSN the switched neutral is unprotected, on DP and FP
all poles are protected.
SPSN MCBs are fitted with neutral contacts which make first
and break last.
FEATURES
Memshield 2 MCBs are available with a breaking capacity of
10kA to BSEN60898 & BSEN60947-2.
They are suitable for use on DC systems from 24V to 120V;
fault level at 24V = 6kA; 120V = 4kA.
NOTE: When a residual current pod is added to the MCB (see
P63) to form an RCBO, the combination is suitable for use on
240v AC systems, it cannot be used on DC systems.
The MCBs are calibrated to 40ºC.
MCBs can be supplied with 50ºC ambient calibration. To order
insert ‘X’ at the end of the MCB list number eg:- MCH 116X.Please contact our Technical Services department for details
of Memshield 2 MCBs suitable for other reference
calibration temperatures.
MEMSHIELD 2 MCBS - TYPE B TO BSEN60898 (IEC898), 3 TO
5 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP
1 MBH101 MBH101N MBH201 MBH301 MBH401
2 MBH102 MBH102N MBH202 MBH302 MBH402
4 MBH104 MBH104N MBH204 MBH304 MBH404
6 MBH106 MBH106N MBH206 MBH306 MBH406
8 MBH108 MBH108N MBH208 MBH308 MBH408
10 MBH110 MBH110N MBH210 MBH310 MBH410
13 MBH113 MBH113N MBH213 MBH313 MBH413
16 MBH116 MBH116N MBH216 MBH316 MBH416
20 MBH120 MBH120N MBH220 MBH320 MBH420
25 MBH125 MBH125N MBH225 MBH325 MBH425
32 MBH132 MBH132N MBH232 MBH332 MBH432
40 MBH140 MBH140N MBH240 MBH340 MBH440
50 MBH150 MBH150N MBH250 MBH350 MBH450
63 MBH163 MBH163N MBH263 MBH363 MBH463
MEMSHIELD 2 MCBS - TYPE C TO BSEN60898 (IEC898), 5 TO
10 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP1 MCH101 MCH101N MCH201 MCH301 MCH401
2 MCH102 MCH102N MCH202 MCH302 MCH402
4 MCH104 MCH104N MCH204 MCH304 MCH404
6 MCH106 MCH106N MCH206 MCH306 MCH406
8 MCH108 MCH108N MCH208 MCH308 MCH408
10 MCH110 MCH110N MCH210 MCH310 MCH410
13 MCH113 MCH113N MCH213 MCH313 MCH413
16 MCH116 MCH116N MCH216 MCH316 MCH416
20 MCH120 MCH120N MCH220 MCH320 MCH420
25 MCH125 MCH125N MCH225 MCH325 MCH425
32 MCH132 MCH132N MCH232 MCH332 MCH432
40 MCH140 MCH140N MCH240 MCH340 MCH440
50 MCH150 MCH150N MCH250 MCH350 MCH450
63 MCH163 MCH163N MCH263 MCH363 MCH463
APPLICATIONS
■ SP MCBs can be used in type A distribution boards.
■ SP, DP and TP MCBs can be used in type B distribution boards.
■ SPSN and DP MCBs can be used in DP distribution boards.
■ FP MCBs are for specialist OEM applications.
Memshield 2 P47-91 31/7/02 16:12 Page 18
62
M I N I A T U R E C I R C U I T B R E A K E R S - T Y P E D , 1 0 K A ;
F U S E C A R R I E R S - T Y P E B S .
FUSE CARRIERS
The Memshield 2 fuse carrier range uses high performance MEM
BS1361 type HRC fuses capable of disconnecting short circuits of up
to 16kA.
The fuse carriers and fuses are both British designed and
manufactured, using the latest technology. The protection of circuits by
Memshield 2 fuse and carriers is particularly applicable where circuits
exhibit high inrush e.g. high frequency lighting. The fuse carriers are
suitable for use with Memshield 2 SPN and TPN type distribution
boards. In addition fuse carriers are suitable for a wide range of OEM
type applications.
Current ratings are available in 5, 10, 15, 20, 30, 35, 40, and 45A
ratings. The range is available as SP devices only.
FEATURES
Memshield 2 fuse carriers feature a fully shrouded contact mechanism.
Each unit is supplied with a 240v fuse fitted, and facility for a spare
fuse, which can be contained within the fuse carrier.
For 415v applications contact us for details of suitable fuse units
and fuselinks.
Note - Memshield 2 types MFM35/40/45 units are 36mm wide and
require 2 SP distribution board ways.
MEMSHIELD 2 MCBS - TYPE D TO BSEN60898 (IEC898), 10
TO 20 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP
1 MDH101 MDH101N MDH201 MDH301 MDH401
2 MDH102 MDH102N MDH202 MDH302 MDH402
4 MDH104 MDH104N MDH204 MDH304 MDH404
6 MDH106 MDH106N MDH206 MDH306 MDH406
8 MDH108 MDH108N MDH208 MDH308 MDH408
10 MDH110 MDH110N MDH210 MDH310 MDH410
13 MDH113 MDH113N MDH213 MDH313 MDH413
16 MDH116 MDH116N MDH216 MDH316 MDH416
20 MDH120 MDH120N MDH220 MDH320 MDH420
25 MDH125 MDH125N MDH225 MDH325 MDH425
32 MDH132 MDH132N MDH232 MDH332 MDH432
40* MDL140 MDL140N MDL240 MDL340 MDL440
50* MDL150 MDL150N MDL250 MDL350 MDL450
63* MDL163 MDL163N MDL263 MDL363 MDL463
*6kA
MEMSHIELD 2 FUSES - HRC FUSE CARRIERS FOR
BS1361 FUSES (240V RATED).
UNDER VOLTAGE RELEASE LIST NO.
For remote tripping of an emergency stop loop. M2UV240240V AC
AUXILIARY AND ALARM CONTACTS
Auxiliary and alarm contact devices can be fitted together on
one MCB.
Each is incorporated in a 1/2 module (9mm) casing with terminals
protected to IP2 capable of accepting cable up to 2.5mm2 . A half
module blanking plate is available List no. MABP.
These devices are designed and manufactured to BS
EN60947.5.1.
Contact ratings: AC14 240V ac 50Hz 6A DC14 125V dc 1A
SHUNT TRIPS AND UVRS
Suitable for all Memshield 2 MCBs and RCBOs including those
with either auxiliary or alarm contacts. A shunt trip and
undervoltage release can be fitted together on one MCB.
Each is incorporated in a 1 module (18mm) casing with terminals
protected to IP2 capable of accepting cable up to 2.5mm2
Contact ratings: AC14 240V ac 50Hz 5A DC 14 125V dc 1A
AUXILIARY CONTACT DESCRIPTION LIST NO.
A changeover switch incorporating a test function to allow
remote indication of the position of the MCB contacts.
The auxiliary contact will not differentiate between an M2AUMCB that is “off” or “tripped”. The auxiliary contact
can be used in conjunction with a remote supply and signal
lamps, bells or buzzers.
The above devices are simply clipped to the left hand side of
an MCB or RCBO and have terminals at one end to allow
connection to pan assemblies and comb busbar.
RATING SPARE LIST NO.A FUSES SP5 5LC MFM0510 1510LC MFM1015 15LC MFM1520 20LC MFM2030 30LC MFM3035 35LCS MFM3540 40LCS MFM4045 45LCS MFM45
ALARM CONTACT DESCRIPTION LIST NO.
A changeover switch incorporating reset and test
function providing remote indication of an MCB M2ALwhich has tripped under fault conditions.
SHUNT TRIP DESCRIPTION LIST NO.
An open circuit shunt release for remote trippping of
an MCB offering three voltage options for AC &
DC applications
24V AC 24V DC M2STA
48V - 110V AC 48V-60V DC M2STB
240V AC 110V DC M2STC
Memshield 2 P47-91 31/7/02 16:12 Page 19
STANDARD READY ASSEMBLED RCBOS - SPTYPE C
This table highlights examples of the more commonly required
RCBO units incorporating Type C Memshield 2 MCBs.
RATING A SENSITIVITY SENSITIVITY10MA LIST NO. 30MA LIST NO.
6 MCH106R10 MCH106R3010 MCH110R10 MCH110R3016 MCH116R10 MCH116R3020 MCH120R10 MCH120R3032 MCH132R10 MCH132R3040 - MCH140R30
RCBOS FACTORY ASSEMBLED TO ORDER
Any standard Memshield 2 SP or SPSN MCB can be factory
fitted with residual current protection.
To order your RCBO simply select the MCB from pages 61/62
and add the required sensitivity suffix shown in the table
below, the RCBO will be supplied as a fully fitted unit.
SENSITIVITY MA SUFFIX LIST NO.10mA, 230-240V AC R10*30mA, 230-240V AC R30100mA, 230-240V AC R100100mA time delayed, 230-240V AC R100D300mA time delayed, 230-240V AC R300D
* 10mA RC units can be fitted to MCBs up to 32A only.
FIELD FITTABLE RESIDUAL CURRENT (RC)UNITS
Any standard Memshield 2 SP or SPSN MCB can be field
fitted with a residual current unit.
To order simply select the required sensitivity suffix from the
table below, the residual current unit will be supplied for you
to fit to your MCB. Contact us for availability.
SENSITIVITY MA SUFFIX LIST NO.30mA, 110V AC MR30/110100mA, 110V AC MR100/11030mA, 230-240V AC MR30100mA, 230-240V AC MR100100mA time delayed, 230-240V AC MR100D300mA time delayed, 230-240V AC MR300D
D.C. Components in the LoadThe RCBO is capable of responding to the superimposition of components ofcurrent on the supply caused by the operation of equipment using rectifiedvoltages in compliance with BSEN 61009.
Loss of Supply NeutralUnder loss of supply neutral conditions the r.c. element of the device willcontinue to provide earth leakage protection.With these conditions and upon detection of an earth leakage current theRCBO will operate within its normal characteristics.
High Voltage SuppressionHigh voltage suppression is incorporated and the unit is therefore ideal foruse with supply equipment susceptible to such mains borne transients.
63
M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SR C B O ( C O M B I N E D M C B / R C D ) - T Y P E B , C , A N D D
REVOLUTIONARY!
The Memshield 2 RCBO combines the functions of an RCCB and an
MCB. The unique, revolutionary design allows hundreds of RCBO
possibilities within a module as little as 18mm wide. This allows a far
greater number of devices to be fitted into a distribution board.
All the features of the standard MCB are maintained but with the
added flexibility of residual current protection.
Memshield 2 SP RCBOs are suitable for use in any Memshield 2
distribution board.
Due to the unique method of construction any Memshield 2 SP orSPSN MCB can be fitted with residual current protection.
So for applications where a SP 63A type D MCB with 300mA time
delayed residual current protection is required MEM have the answer!
A new version of the residual current pod is available for use on 110V
50/60Hz systems.
ADDING EARTH FAULT PROTECTION TO YOUR MCB
There are three options each complying with BSEN61009:
1 Choose from the standard ready assembled range of RCBOs
incorporating Type C MCBs.
2 RCBOs factory assembled to order; select your MCB followed by the
earth fault sensitivity suffix from the relevant table. Remember any
SP or SPSN MCB can be fitted with earth fault protection.
Example: MDL150R100 = 50A SP Type D MCB factory
assembled with 100mA residual current protection.
3 Field fittable Residual Current (RC) Units; an RCBO can be
assembled on site. This provides two benefits: Previously installed
Memshield 2 SP & SPSN MCBs can be upgraded to include residual
current protection, also stock of SP & SPSN Memshield 2 MCBs
previously supplied can be upgraded to include earth fault protection.
Example: A field fitted MR30 will convert any SP or SPSN MCB
into an RCBO with 30mA residual current sensitivity.
NOTE: SPSN RCBOs must NOT be fitted in TPN type B distribution
boards. SPSN RCBOs are limited for use in DP versions of type A and
type B distribution boards.
To guarantee discrimination with downstream residual current devices
any upstream residual current device should be time delayed. The time
delay period is between 150-400mS.
New
RESIDUAL CURRENT OPERATED CIRCUIT BREAKERS WITH INTEGRAL OVERCURRENT PROTECTION.
Memshield 2 P47-91 31/7/02 16:12 Page 20
M E M S H I E L D 2 M C B O U T G O I N G D E V I C E SA C C E S S O R I E S
64
COMB BUSBAR END COVERS
For DP, TP and FP busbar configurations, supplied in packs of 10.
DESCRIPTION LIST NO.
For DP and TP comb busbars; MB2P, MB2F, MBEC23MB3P and MB3F
For FP comb busbars; MB4P and MB4F MBEC4
The wide range of Memshield 2 devices are complemented by a
range of dolly padlocking devices.
For MCBs, RCCBs, RCBOs, and MCCBs the device mechanism is
trip free which allows it to be padlocked ‘ON’ for security, but in
the event of a fault condition the device will still operate to
disconnect the fault. The device dolly will move to the tripped
position when the dolly lock is removed. These devices can also be
padlocked in the ‘OFF’ position.
NOTE: Distribution board doors can be closed when an MCB is
padlocked ‘ON’ or ‘OFF’.
MEMSHIELD 2 DEVICES GENERAL ACCESSORIES
DESCRIPTION LIST NO.
Dolly padlocking device for all MCBs MBL2and RCBOs
Dolly padlocking device for all SPSN RCCBs AML2
Dolly padlocking device for all 100A switches SML4
Dolly padlocking device for MCCB/BMS2003 2MFLL
Padlock for MBL2, AML2, SML4 PD2
Padlock for 2MFLL PD50
MCB terminal shroud (each) MTSH1
MCB terminal screw shield (each) MTS1
MCB terminal rear connectors, MBRC1capacity 50mm2 max. (each)
Spare 5A BS1361 fuse 5LC
Spare 10A BS1361 fuse 1510LC
Spare 15A BS1361 fuse 15LC
Spare 20A BS1361 fuse 20LC
Spare 30A BS1361 fuse 30LC
Spare 35A BS1361 fuse 35LCS
Spare 40A BS1361 fuse 40LCS
Spare 45A BS1361 fuse 45LCS
COMB BUSBAR
Comb busbar is available for specialist applications and can be
supplied in both pin and fork type formats.
Fork type comb busbar can be used with all Memshield 2 MCBs*
and TPSN RCCBs. Pin type comb busbar can be used with all
Memshield 2 MCBs, fuse modules, switch-disconnectors, terminal
blocks SPSN and TPSN RCCBs.
NOTE: Due to a height difference TPSN RCCBs cannot be
inter-connected with comb busbar when mounted in combination
with other devices.
Busbar material: Copper
Rated operational voltage: 240/415V
Rated operational current: 100A
Unused ways on comb busbar can be shielded by fitting the
Memshield 2 blanking module, it also provides a barrier in the
distribution board front cover aperture. List No. MBP.
*For incoming connections onto fork type comb busbar, MCB
terminals clamp cable and busbar simultaneously.
MEMSHIELD 2 COMB BUSBAR
Supplied in 1m lengths.
DESCRIPTION LIST NO.
16mm2 SP insulated pin type MB1P
20mm2 SP insulated fork type MB1F
16mm2 DP insulated pin type MB2P
16mm2 DP insulated fork type MB2F
16mm2 TP insulated pin type MB3P
16mm2 TP insulated fork type MB3F
16mm2 FP insulated pin type MB4P
16mm2 FP insulated fork type MB4F
Memshield 2 P47-91 31/7/02 16:13 Page 21
65
M E M S H I E L D 2 C O M M A N D D E V I C E SR E S I D U A L C U R R E N T C I R C U I T B R E A K E R S ; S P S N & T P S N
Memshield 2 RCCBs offer a tremendous range for installers.
Units are available with ratings up to 100A and sensitivities
from 10mA to 300mA time delayed.
These units are the first to conform to BSEN61008.
FEATURES
The SPSN electronic unit is capable of sensing DC components
in the supply, in accordance with BSEN61008. Generous cable
capacities of up to 50mm2 (TPSN with adaptor fitted. 35mm2
without adaptor) are provided. The SPSN devices will trip to a
central position under earth fault conditions. A flag indicator
shows positive contact position via window above dolly. The
RCCBs can be installed in a variety of enclosures (see page 57).
All SPSN units are suitable for 240v 50/60 Hz applications.
All TPSN units are suitable for 415v AC applications and also
have comb busbar facilities.
Please contact our Technical Services department for details
of other voltage/frequency possibilities.
AUXILIARY CONTACT MODULE
Memshield 2 TPSN RCCBs can be supplied fitted with an
auxiliary contact module adding a half module to the four
module device.
To order add suffix HR to list no. e.g: AM254HHR.
They incorporate 1N/O + 1 N/C contact.
Nominal voltage: Max 415V
Nominal Current: 6A at 400V (Resistive)
6A at 230V
2A at 400V
Terminals will accept cables up to 2.5mm2.
Contact us for availability.
MEMSHIELD 2 RCCBS - TPSN
DESCRIPTION LIST NO.
25A 30mA TPSN RCCB AM254H
40A 30mA TPSN RCCB AM404H
63A 30mA TPSN RCCB AM634H
80A 30mA TPSN RCCB AM804H
100A 30mA TPSN RCCB AM1004H
25A 100mA TPSN RCCB AM254M
40A 100mA TPSN RCCB AM404M
63A 100mA TPSN RCCB AM634M
80A 100mA TPSN RCCB AM804M
100A 100mA TPSN RCCB AM1004M
25A 300mA TPSN RCCB AM254L
40A 300mA TPSN RCCB AM404L
63A 300mA TPSN RCCB AM634L
80A 300mA TPSN RCCB AM804L
100A 300mA TPSN RCCB AM1004L
100A 300mA TPSN RCCB time delayed AM1004LT
Adaptor kit to accept up to 50mm2 cable AMBT
MEMSHIELD 2 RCCBS - SPSN
DESCRIPTION LIST NO.
16A 10mA SPSN RCCB AM16VHE
25A 30mA SPSN RCCB AM25HE
40A 30mA SPSN RCCB AM40HE
63A 30mA SPSN RCCB AM63HE
80A 30mA SPSN RCCB AM80HE
100A 30mA SPSN RCCB AM100HE
25A 100mA SPSN RCCB AM25ME
40A 100mA SPSN RCCB AM40ME
63A 100mA SPSN RCCB AM63ME
80A 100mA SPSN RCCB AM80ME
100A 100mA SPSN RCCB AM100ME
25A 300mA SPSN RCCB AM25LE
40A 300mA SPSN RCCB AM40LE
63A 300mA SPSN RCCB AM63LE
80A 300mA SPSN RCCB AM80LE
100A 300mA SPSN RCCB AM100LE
100A 100mA SPSN RCCB time delayed AM100MET
100A 300mA SPSN RCCB time delayed AM100LET
RESIDUAL CURRENT OPERATED CIRCUIT BREAKERSWITHOUT INTEGRAL OVERCURRENT PROTECTION.
Memshield 2 P47-91 31/7/02 16:13 Page 22
66
M E M S H I E L D 2 C O M M A N D D E V I C E SB E L L T R A N S F O R M E R S , T I M E S W I T C H E S , C O N T A C T O R S , I M P U L S E
R E L A Y S , T I M E D E L A Y R E L A Y S
Memshield 2 command devices allow increased flexibility for
both distribution board and OEM applications. SPN
distribution boards can accommodate command devices by
using a busbar block kit. Command devices can be
accommodated in modular enclosures. In addition all devices
are suitable for installation on ‘tophat’ symmetrical DIN-rail.
BELL TRANSFORMER
Devices can accommodate from 4-12v secondary from a 240v
AC primary supply. The AA2BT is not suitable for isolation duty.
TIME SWITCHES
Devices are available as analogue (dial) type or digital (LCD)
types. Quartz stabilised devices have a running reserve time of
150Hr and a recharge time of 70Hr. Digital time switches have a
running reserve of 150Hr, and a full recharge time of 140Hr. All
time switches have 1 c/o contact per channel and are suitable for
switching 16A resistive, 2.5A inductive loads at 240v 50Hz. For
higher rated loads time switches should be used in conjunction
with MEM Autoline heating & lighting contactors.
CONTACTORS
Memshield 2 modular contactors are available from 16A to 63A,
and from SP to FP. Devices are suitable for AC1 (general heating
& lighting loads) applications. All devices have N/O contacts.
Note; when several contactors are mounted it is advisable to fit a
blanking module, List no. MBP, every 2 contactors.
IMPULSE RELAYS
Memshield 2 modular impulse relays are available with 16A
N/O or C/O contacts. Impulse relays are often a suitable
replacement for contactors where low switching duty and low
energy consumption are important.
TIME DELAY RELAYS
Memshield 2 modular time delay relays (staircase switches)
are suitable for delay ‘OFF’ applications from 30 seconds to
15 minutes. For use on loads above 16A AC1 devices should
be used in conjunction with a suitable MEM contactor.
MEMSHIELD 2 BELL TRANSFORMERS
WIDTHDESCRIPTION PRIMARY SECONDARY IN 18MM
VOLTAGE VOLTAGE MODULES LIST NO.Non isolating 240v AC 4v 1A 2 AA2BT
8v 1A12v 0.67A
N.B. AA2BT supplied with full terminal shields & direct
mounting bracket.
MEMSHIELD 2 - TIME SWITCHES
MINIMUM WIDTHDESCRIPTION TYPE PROGRAMME IN 18MM LIST
TIME MODULES NO.
Non-quartz stabilised - 220/240v AC 50Hz
Analogue, 1 channel 24hr 30 mins 1 AT11SD
Analogue, 1 channel 24hr 30 mins 3 AT1SD
Analogue, 1 channel 7 day 180 mins 3 AT1SW
Quartz stabilised - 220/240v AC 50Hz
Analogue, 1 channel 24hr 30 mins 3 AT1QD
Analogue, 1 channel 7 day 180 mins 3 AT1QW
Digital quartz - 220/240v AC 50Hz single channel
Digital, 1 channel fully 1 min 1 AT11Pprog.
Digital, 1 channel fully 1 min 2 AT1Pprog.
Digital, 2 channel fully 1 min 2 AT2Pprog.
N.B. All time switches supplied with terminal shields and detachable
wall mounting bracket.
MEMSHIELD 2 CONTACTORS
WIDTHDESCRIPTION COIL IN 18MMRATING A DUTY VOLTAGE CONTACTS MODULES LIST NO.16A SP AC1 230v AC 1-N/O, 1-N/C 1 AA16125A DP AC1 230v AC 2-N/O 1 AA20240A DP AC1 230v AC 2-N/O 2 AA40225A TP AC1 230v AC 3-N/O 2 AA20340A TP AC1 230v AC 3-N/O 3 AA40363A TP AC1 230v AC 3-N/O 3 AA63325A FP AC1 230v AC 4-N/O 2 AA20440A FP AC1 230v AC 4-N/O 3 AA40463A FP AC1 230v AC 4-N/O 3 AA634
Contact us for other ratings.
MEMSHIELD 2 IMPULSE RELAYS
WIDTHDESCRIPTION COIL IN 18MMRATING A VOLTAGE CONTACTS MODULES LIST NO.
16A SP 230v AC 1-N/O 1 AA161RA16A SP 230v AC 1-N/0, 1-N/C 1 AA161RB
MEMSHIELD 2 TIME DELAY RELAYS
WIDTHDESCRIPTION COIL IN 18MMRATING A VOLTAGE TYPE MODULES LIST NO.
16A SP 230v AC delay off 1 AA7
Memshield 2 P47-91 31/7/02 16:13 Page 23
M E M S H I E L D 2 C O M M A N D D E V I C E SS W I T C H - D I S C O N N E C T O R S A N D T E R M I N A L B L O C K S
67
SWITCH-DISCONNECTORS
Memshield 2 18mm modular switch-disconnectors have a similar profile to
Memshield 2 MCBs and conform to the requirements of BSEN60947-3,
100A 240/415v AC22B. Positive contact indication is also provided.
Terminals are box type allowing cable capacity up to 50mm2.
SPSN switch-disconnectors have neutral contacts which make
first - break last.
TERMINAL BLOCKS
Memshield 2 18mm modular terminal blocks are suitable for a wide
variety of uses. They can be used in outgoing circuits in place of a
Memshield 2 MCB or RCBO to tap off to other devices or boards.
Terminals are box type allowing cable capacity up to 50mm2. Suitable
for type A and B distribution boards.
MEMSHIELD 2 - SWITCH-DISCONNECTORS
For use in modular enclosures or on symetrical DIN-rail.
WIDTHDESCRIPTION IN 18MM LIST NO.
MODULES
100A SP 1 MS1001
100A SPSN* 2 MS1001N
100A DP* 2 MS1002
100A TP* 3 MS1003
100A TPSN* 4 MS1004
Padlock attachment - SML4
Padlock - PD2
*For switch-disconnectors for use as distribution board incomers refer
to pages 52, 54 and 55.
MEMSHIELD 2 - TERMINAL BLOCKS
For use in modular enclosures or on symetrical DIN-rail.
WIDTHDESCRIPTION IN 18MM LIST NO.
MODULES
100A 1P 1 MBT1001
100A DP* 2 MBT1002
100A TP* 3 MBT1003
*For terminal blocks for use as distribution board incomers refer to
pages 52, 54 and 55.
Memshield 2 P47-91 31/7/02 16:13 Page 24
22
M E M S H I E L D 2 M C B O U T G O I N G D E V I C E S 6 K AM I N I A T U R E C I R C U I T B R E A K E R S ; T Y P E B , C & D
68
This Memshield 2 MCB is current limiting in design with the ability
to disconnect short circuits up to 6kA.
The feature packed device is both British designed and manufactured,
using the latest technology.
The MCBs are suitable for use in a wide range of OEM type
applications. In addition, MCBs are suitable for use in Memshield
2 SPN and TPN distribution boards.
Current ratings are available in 1, 2, 4, 6, 8, 10, 13, 16, 20, 25, 32,
40, 50, and 63A ratings. The range is available with Types B, C, and
D, for SP, SPSN, DP, TP, FP pole configurations.
On SPSN the switched neutral is unprotected, on DP and FP all
poles are protected.
SPSN MCBs are fitted with neutral contacts which make first and
break last.
FEATURES
Memshield 2 MCBs are available with a breaking capacity of 6kA
to BSEN60898 & BSEN60947-2. The MCBs are normally
calibrated to 40ºC.
MCBs can be supplied with 50°c ambient calibration. To order insert
‘X’ at the end of the MCB list number eg:- MCL116X
Please contact our Technical Services department for details of
Memshield MCBs suitable for other reference calibration temperatures.
APPLICATIONS
■ SP MCBs can be used in type A distribution boards.
■ SP, DP and TP MCBs can be used in type B distribution boards.
■ SPSN and DP MCBs can be used in DP distribution boards.
■ FP MCBs are for specialist OEM applications.
MEMSHIELD 2 MCBS - TYPE B TO BSEN60898 (IEC898),
3 TO 5 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP
1 MBL101 MBL101N MBL201 MBL301 MBL401
2 MBL102 MBL102N MBL202 MBL302 MBL402
4 MBL104 MBL104N MBL204 MBL304 MBL404
6 MBL106 MBL106N MBL206 MBL306 MBL406
8 MBL108 MBL108N MBL208 MBL308 MBL408
10 MBL110 MBL110N MBL210 MBL310 MBL410
13 MBL113 MBL113N MBL213 MBL313 MBL413
16 MBL116 MBL116N MBL216 MBL316 MBL416
20 MBL120 MBL120N MBL220 MBL320 MBL420
25 MBL125 MBL125N MBL225 MBL325 MBL425
32 MBL132 MBL132N MBL232 MBL332 MBL432
40 MBL140 MBL140N MBL240 MBL340 MBL440
50 MBL150 MBL150N MBL250 MBL350 MBL450
63 MBL163 MBL163N MBL263 MBL363 MBL463
MEMSHIELD 2 MCBS - TYPE C TO BSEN60898 (IEC898),
5 TO 10 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP
1 MCL101 MCL101N MCL201 MCL301 MCL401
2 MCL102 MCL102N MCL202 MCL302 MCL402
4 MCL104 MCL104N MCL204 MCL304 MCL404
6 MCL106 MCL106N MCL206 MCL306 MCL406
8 MCL108 MCL108N MCL208 MCL308 MCL408
10 MCL110 MCL110N MCL210 MCL310 MCL410
13 MCL113 MCL113N MCL213 MCL313 MCL413
16 MCL116 MCL116N MCL216 MCL316 MCL416
20 MCL120 MCL120N MCL220 MCL320 MCL420
25 MCL125 MCL125N MCL225 MCL325 MCL425
32 MCL132 MCL132N MCL232 MCL332 MCL432
40 MCL140 MCL140N MCL240 MCL340 MCL440
50 MCL150 MCL150N MCL250 MCL350 MCL450
63 MCL163 MCL163N MCL263 MCL363 MCL463
MEMSHIELD 2 MCBS - TYPE D TO BSEN60898 (IEC898),
10 TO 20 x IN & BSEN60947-2
RATING LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.A SP SPSN DP TP FP
1 MDL101 MDL101N MDL201 MDL301 MDL401
2 MDL102 MDL102N MDL202 MDL302 MDL402
4 MDL104 MDL104N MDL204 MDL304 MDL404
6 MDL106 MDL106N MDL206 MDL306 MDL406
8 MDL108 MDL108N MDL208 MDL308 MDL408
10 MDL110 MDL110N MDL210 MDL310 MDL410
13 MDL113 MDL113N MDL213 MDL313 MDL413
16 MDL116 MDL116N MDL216 MDL316 MDL416
20 MDL120 MDL120N MDL220 MDL320 MDL420
25 MDL125 MDL125N MDL225 MDL325 MDL425
32 MDL132 MDL132N MDL232 MDL332 MDL432
40 MDL140 MDL140N MDL240 MDL340 MDL440
50 MDL150 MDL150N MDL250 MDL350 MDL450
63 MDL163 MDL163N MDL263 MDL363 MDL463
Memshield 2 P47-91 31/7/02 16:13 Page 25
69
D I S T R I B U T I O N B O A R D S A N D D E V I C E S - S P E C I F I C A T I O N
TYPE MCBS RCBOS RCCBS DP RCCBS FP FUSESStandards IEC60898, BSEN60898 BSEN61009 BSEN61008 BSEN61008 BS1361 Size 1
IEC60947-2, BSEN60947-2
Breaking Capacity toIEC60898/BSEN60898/IEC60947-2 10kA 10kA - - -BSEN60947-2 (H Type)
IEC60898/BSEN60898/IEC60947-2 6kA 6kA - - -BSEN60947-2 (L Type)
BS1361 - - - - 16kASensitivities (mA) - 10, 30, 100, 10, 30, 100, 300, 30, 100, 300, 300t.d. -
100t.d, 300t.d. 100t.d., 300t.d.
Current Ratings (A) 1,2,4,6,8,10,13, 1,2,4,6,8,10,13,16, 16,25,32,40,63, 25,40,63, 80, 100 5, 10, 15, 20,16, 20, 25, 32, 40, 50, 63 20, 25, 32, 40,50, 63† 80, 100 30, 35, 40, 45
Voltage Rating 50/60Hz (v)* 24V DC (6kA) to 120V DC (4kA) 240V AC 240V AC 240/415V AC 240V AC& 240V/415V AC 110V AC
DIN-rail mounting Yes Yes Yes Yes Yes
Tunnel ‘Box’ Terminals Yes Yes Yes Yes Yes
Cable Capacity 25mm2 25mm2 50mm2 35mm2 25mm2
(50mm2 with adaptor)
Terminals Suitable For -Stranded Copper Cable Top & Bottom** Top & Bottom Top & Bottom Top & Bottom** Top & BottomSolid Copper Cable Top & Bottom** Top & Bottom Top & Bottom Top & Bottom** Top & BottomComb Busbar (Fork) Top & Bottom** Bottom - Top & Bottom** -Comb Busbar (Pin) Top & Bottom Bottom Top & Bottom Top & Bottom Top & BottomAluminium Cable Consult Us Consult Us Consult Us Consult Us Consult Us
*Please consult our Technical Services department for alternative ratings.
**Terminals will clamp cable and fork type comb busbars simultaneously.
†10mA only available up to 32A inclusive.
TYPE SPN A BOARDS TPN B BOARDSStandards BS5486 - Part 12 BS5486 - Part 12
BS5486 - Part 13 BSEN60439-3BSEN60439-3
Busbar Rating 100A 200ABusbar Type Fully Shrouded Solid Copper Fully Shrouded Dual Solid CopperVoltage Rating 240V AC 240/415V AC
50/60Hz 50/60HzIP Rating to BS5420:1977 IP4X IP4XEnclosure Body Type Light grey finish over Light grey finish over
Rust Protected Sheet Steel Rust Protected Sheet SteelEnclosure Paint Type* BS4800 Shade 00A07 BS4800 Shade 00A07Knockouts - Body 4/7/10 way; 2 off 33 x 60mm Knockouts each side
13/16 way; 4 off 33 x 60mm for Busbar Connecting Kitin rear plate
Cable Capacities100A Switch-disconnector 50mm2 50mm2
125A TP Switch-disconnector - 70mm2
160A TP Switch-disconnector - 70mm2
200A Switch-disconnector - 120mm2
100A Terminal Block (Lugs) 50mm2 50mm2
200A Terminal Block (Lugs) - M8 bolt100A SPSN RCCB 50mm2 -100A TPSN RCCB - 50mm2 (with adaptor fitted)16-200A F Frame MCCB - 120mm2
125A Fuse Combination Switch - M6Enclosure Earth Stud M6 bolt M8 boltIncoming Earth Terminal 25mm2 70mm2
Incoming Neutral Terminal - 70mm2 (125A boards)M8 bolt (200A boards)
Outgoing Earth Terminals 25mm2 25mm2
Outgoing Neutral Terminals 25mm2 25mm2
*Please consult our Technical Services department for full details of non -standardpaint finishes.
Memshield 2 P47-91 31/7/02 16:13 Page 26
22
M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM C B D I S T R I B U T I O N B O A R D D I M E N S I O N S
70
TYPE A 100A SPN 2 - 16 WAY, DP 5 & 8 WAY, SPLITLOAD AND DUAL TARIFF DISTRIBUTION BOARDS,1 ROW DIN-RAIL ENCLOSURES
AMSL910 SPLIT LOAD DISTRIBUTION BOARD
NOTE: For flush mounting aperture dimensions use equivalent
enclosure size. All dimensions in mm.
* Internal depth = 90mm.
TYPE B 100A TPN 4 - 24 WAY, DP 6 - 24 WAY, AND SPLIT LOAD DISTRIBUTION BOARDS, 3ROW DIN-RAIL ENCLOSURES*
LIST NO. A B C
AM2 152.0 38.5 77.0
AM4 238.0 81.5 163.0
AM7 292.0 108.5 217.0
AM5D, AM10 346.0 135.5 271.0
AM13 400.0 162.5 325.0
AM8D, AM16 454.0 189.5 379.0
AMSL37, AMSL64 400.0 162.5 325.0
AMSL67, AMSL94, AMSL310 454.0 189.5 379.0
AMSL910 346.0 135.5 271.0
AMDT74 400.0 162.5 325.0
AMDT77, AMDT104 454.0 189.5 379.0
ENCLOSURES
BMXDC4, BMXDCG4, 152.0 38.5 77.0
BMXDC6, BMXDCG6 238.0 81.5 163.0
BMXDC9, BMXDCG9 292.0 108.5 217.0
BMXDC15, BMXDCG15 400.0 162.5 325.0
125A BOARD 100/125A SWITCHDISCONNECTOR/100A RCCB
LIST NO. BMS1003, BMS1253, BMS1004, BMS1001N, BMBT1003, BMR100 OR
BMR300 OR NEOZED INCOMER
A B
BM41 403.0 497.5
BM61 457.0 551.5
BM61D 403.0 551.5
BM81 511.0 605.5
BM121D 511.0 659.5
BM81NZ 565.0 659.5
BM121, BM181D, 673.0 767.5BM121NZ
BM161, BM241D, 781.0 875.5BM81NZ
SPLIT LOAD
BMSL48, BMSL66, 727.0 821.5BMSL84
BMSL88 835.0 929.5
ENCLOSURES
BMXDC30, 457.0 551.5BMXDCG30
BMXDC45, 673.0 767.5BMXDCG45
BM241 = 1350mmH x 560mmW x 155mmD.
Memshield 2 P47-91 31/7/02 16:13 Page 27
71
TYPE B 200A TPN 4-24 WAY DISTRIBUTION BOARDS
TYPE B 4-16 WAY DISTRIBUTION BOARDS WITH FCS INCOMER
200A 200A LUGS 160/200A SWITCH BOARD BMBT2003 DISCONNECTOR/F-FRAME LIST NO. MCCB,BMS2001N, BMS1603,
BMS2003 OR BMIK2003
A B C A B C
BM42 457.0 - 551.5 457.0 579.5 713.5
BM62 511.0 - 605.5 511.0 633.5 767.5
BM82 565.0 - 659.5 565.0 687.5 821.5
BM122 673.0 - 767.5 673.0 795.5 929.5
BM162 781.0 - 875.5 781.0 903.5 1037.5
BM242 = 1350mmH x 560mmW x 155mmD.
LIST NO. A B C
BMFCS4, BMFCSN4 403.0 486.0 875.5
BMFCS6, BMFCSN6 457.0 540.0 929.5
BMFCS8, BMFCSN8 511.0 594.0 983.5
BMFCS12, BMFCSN12 673.0 702.0 1145.5
BMFCS16, BMFCSN16 781.0 810.0 1253.5
NOTE: For flush mounting aperture dimensions use equivalent enclosure size including extension box.
Flush mounting kit will also cover extension box. All dimensions in mm.
Memshield 2 P47-91 31/7/02 16:14 Page 28
2672
M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM C B P A N A S S E M B L Y D I M E N S I O N S
TYPE A PAN ASSEMBLIES
TYPE B PAN ASSEMBLIES
LIST NO. A B C
AMP4 218.5 147.5 109.0AMP7 272.5 201.5 163.0AMP5D, AMP10 326.5 255.5 217.0AMP13 380.5 309.5 271.0AMP8D, AMP16 434.5 363.5 325.0
LIST NO. A B C D
BMP41 307.0 369.5 109.5 38.5BMP61 361.0 423.5 163.5 38.5BMP81 415.0 477.5 217.5 38.5BMP42, BMP61D 307.0 423.5 109.5 92.5BMP62 361.0 477.5 163.5 92.5BMP82, BMP121D 415.0 531.5 217.5 92.5BMP122, BMP181D 523.0 639.5 325.5 92.5BMP162, BMP241D 631.0 747.5 433.5 92.5
All dimensions in mm.
52
LIST NO. A B
BMPS42 226 162
BMPS62 280 216
BMPS82 334 270
BMPS122 442 378
BMPS162 550 486
PAN-ASSEMBLIES WITHOUT EARTH & NEUTRAL
BMP242LWENBMP242L
6 x M6CLEARANCEHOLES
520.
552
0.5
109.
4
63.5
280.0
298.5
1168
.0
Memshield 2 P47-91 31/7/02 16:14 Page 29
73
D E V I C E D I M E N S I O N S
SP MCB/RCBOS
LIST NO. A B C
4EME 39.0 49.0 89.0AM1SL 33.0 20.0 53.0
LIST NO. A B C D E
4QEL 170.0 105.0 112.0 153.0 88.06QEL 170.0 135.0 112.0 130.0 80.0
HRC FUSE CARRIERS
SWITCH-DISCONNECTORS AND TERMINAL BLOCKS
All dimensions in mm.
RCDS 2 POLE 4 POLE
MOULDED ENCLOSURES 4/6 QEL 4EME/AM1SL
SWITCH DISCONNECTORS
LIST NO. A BMS1001 17.5MS1001N 35.0MS1002 35.0 76.0MS1003 52.5MS1004 70.0
TERMINAL BLOCKSMBT1001 17.5 67.0
64.8 8.8
20.9
45.1
89.8
AUXILIARY &ALARM CONTACTS
Memshield 2 P47-91 31/7/02 16:14 Page 30
74
M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MD E V I C E D I M E N S I O N S
AA403, AA404, AA633, AA634
All dimensions in mm.
BELL TRANSFORMER
AA2BT
TIME SWITCHES AT1SD, AT1SW,
AT1QD, AT1QW, AT1P†, AT2P†
CONTACTORS AA161, AA202 AA203, AA204, AA402
IMPULSE RELAYS AA161RA, AA161RB TIME DELAY RELAY AA7
Memshield 2 P47-91 31/7/02 16:15 Page 31