  • The State GroupDivision 23

    3206 Orlando Drive

    Mississauga, ON L4V 1R5Canada

    PHONE: 905-672-2772

    FAX: 905-293-7548

    Christoph Stefanowicz

    FOR INFORMATION CONTACT

    02/01/13

    ENGINEERING DATA FOR

    CITY OF TORONTO PARKS & REC

    91 PORT UNION COMMUNITYCENTRE

    TORONTO, ONCANADA

    23_7232_91Port_Union

    ARCHITECT

    MCW ENGINEERING

    ENGINEER

    THE STATE GROUP

    CONTRACTOR

    Addendum No. 3 for RFP 9118-15-5083 - Page 2 of 82

  • Addendum No. 3 for RFP 9118-15-5083 - Page 3 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\OC-000.dwg

    TOCA

    0

    Table of Contents

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    DWG DESCRIPTION

    GENERAL

    Cover Sheet

    000 Riser DiagramLEG Legend & AbbreviationsTTRM1 TC Termination SpecificationTTRM2 TC Termination Spec. Sheet 2TWIR TC Wiring Specification

    CONTROL DRAWINGS

    001A HEATING PLANT MECH

    001B HEATING PLANT ELEC

    001C HEATING PLANT BOM/SEQUENCE

    002A COOLING PLANT MECH

    002B COOLING PLANT ELEC

    002C COOLING PLANT BOM/SEQUENCE003A COOLING TOWER MECH

    003B COOLING TOWER ELEC

    003C COOLING TOWER BOM/SEQUENCE004A AHU 1 MECH

    004B AHU 1 ELEC

    004C AHU 1 BOM/SEQUENCE005A AHU 2A MECH

    005B AHU 2A ELEC

    005C AHU 2A BOM/SEQUENCE006A AHU 2B MECH

    006B AHU 2B ELEC

    006C AHU 2B BOM/SEQUENCE007A AHU 4 MECH

    007B AHU 4 ELEC

    007C AHU 4 BOM/SEQUENCE008A AHU 5 MECH

    008B AHU 5 ELEC

    008C AHU 5 BOM/SEQUENCE009A AHU 6 MECH

    009B AHU 6 ELEC

    DWG DESCRIPTION

    CONTROL DRAWINGS

    009C AHU 6 BOM/SEQUENCE010A AHU 7 MECH

    010B AHU 7 ELEC

    010C AHU 7 BOM/SEQUENCE011A AHU 8 MECH

    011B AHU 8 ELEC

    011C AHU 8 BOM/SEQUENCE012A AHU 9 MECH

    012B AHU 9 ELEC

    012C AHU 9 BOM/SEQUENCE

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 4 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\egend.dwg

    LEG

    0

    Legend & Abbreviations

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    ELECTRICAL TERMINATION

    PNEUMATIC TERMINATION

    STANDARD DDC TERMINATION

    NOTE OR REVISION

    DETAILS

    CONTROL

    SYMBOL

    AC

    AD

    AE

    AF

    AFS

    AP

    APS

    AT

    ATD

    BELL

    BOIL

    CBL

    CKV

    CM

    CP

    CPU

    CRT

    CS

    CVC

    D

    DP

    DPR

    DPS

    DPTE

    DPTP

    EC

    EP

    ES

    ET

    FHC

    FM

    FMS

    FS

    FTP

    G

    CONTROL SYMBOL

    DESCRIPTION

    AIR COMPRESSOR

    AIR DRYER

    ACTUATOR ELECTRIC

    AIR FILTER

    AIR FLOW STATION

    ACTUATOR PNEUMATIC

    AUX. POWER SUPPLY

    AUTOMATIC TRAP

    AUTO TANK DRAIN

    BELL

    BOILER

    CABLES

    CHECK VALVE

    CONSTRUCTION MATERIALS

    COMPONENT PANEL

    CENTRAL PROCESSING UNIT

    CATHODE RAY TUBE

    CURRENT SWITCH

    CONSTANT VOLUME CONTROLLER

    DAMPER

    DEW POINT TRANSMITTER

    DIFFERENTIAL PRESS. REGULATOR

    DIFFERENTIAL PRESSURE SWITCH

    DIFF. PRESS. TRANSMITTER ELEC.

    DIFFERENTIAL PRESSURE PNEUMATIC

    ENTHALPY COMPARITOR

    ELECTRO-PNEUMATIC VALVE

    END SWITCH

    ENTHALPY TRANSMITTER

    FUME HOOD CONTROLLER

    FLOW MTR. (FLOW METER STATION)FIRE MGMT. SYSTEM

    FLOW SWITCH

    FLOW TRANSMITTER PNEU.

    DESCRIPTION

    CONTROL SYMBOL

    TRANSFORMER

    TRANSDUCER

    WELL

    VELOCITY TRANSMITTER ELECTRICAL

    VARIABLE AIR VOLUME CONTROLLER

    TEC VALVE ACTUATOR

    VALVE SERVICE PARTS

    UNIT VENT CONTROLLER

    UNIT CONDITIONER CONTROLLER

    TEMPERATURE TRANSMITTER PNEUMATIC

    TEMPERATURE TRANSMITTER ELECTRIC

    TIMER, TIME CLOCK

    TELCOM INTERFACE UNIT

    TRUNK INTERFACE

    THERMOMETER

    TERMINAL EQUIPMENT CONTROLLER

    THERMOSTAT, ELECTRIC

    TIME DELAY RELAY

    TEMPERATURE CONTROLLER(S200)

    TERMINAL BOX CONTROLLER

    ROOM THERMOSTAT, PNEUMATIC

    SWITCH PNEUMATIC

    SOLENOID VALVE

    STATIC PRESSURE REGULATOR

    SPEAKER

    SWITCH ELECTRIC

    SMOKE DETECTOR

    STEP CONTROLLER

    SOFTWARE

    RELIEF VALVE

    RESTRICTOR

    RELAY PNEUMATIC

    RELAY ELECTRIC

    XFMR

    XDR

    W

    VTE

    VB

    VA

    V*

    UVC

    UCC

    TTP

    TTE

    TMR

    TIU

    TI

    TH

    TEC

    TE

    TDR

    TC

    TBC

    T

    SW

    SV

    SPR

    SPKR

    SE

    SD

    SC

    S/W

    RV

    RS

    RP

    RE

    DESCRIPTION

    CONTROL SYMBOL

    SYMBOL

    CONTROL

    RECEIVER CONTROLLER

    PILOT VALVE

    PRINTER

    PRESSURE TRANSMITTER PNEUMATIC

    PRESSURE TRANSMITTER ELECTRIC

    PITOT TUBE

    PULL STATION

    POSITION SENSOR ELECTRIC

    POSITIONING SWITCH

    PRESSURE REDUCING VALVE

    PRESSURE REG. CONTROLLER

    PANEL

    POWER MONITOR

    PILOT LIGHT

    PRESSURE ELECTRIC SWITCH

    PROGRAMMABLE CLOCK TIMER

    PULSE ACCUMULATOR

    OBSOLETE

    MOTOR STARTER

    MAGNEHELIC GAUGE

    ELECTRONIC ACTUATOR

    MODEM

    LOW TEMP. DETECTOR PNEUMATIC

    LOW TEMP. DETECTOR ELECTRICPOWER SUPPLY 24VAC/24VDC

    LIQUID LEVEL TRANS.

    LIQUID LEVEL SWITCHLIMIT CONTROLLER (LIMITEM)ELECTRIC KILOWATT METER

    INTERCOM

    HUMIDITY TRANSMITTER PNEUMATIC

    HUMIDITY TRANSMITTER ELECTRIC

    HIGH TEMPERATURE DETECTOR

    HEAT PUMP CONTROLLER

    HORN

    HAND-OFF-AUTO SWITCH

    RC

    PV

    PTR

    PTP

    PTE

    PT

    PST

    PSE

    PS

    PRV

    PRC

    PNL

    PM

    PL

    PE

    PCT

    PA

    OBS

    MS

    MG

    ME

    MDM

    LTDP

    LTDE

    LPR

    LLT

    LLS

    LC

    KWM

    INT

    HTP

    HTE

    HTD

    HPC

    HORN

    HOA

    CONTROL

    SYMBOL

    TO CONTROL

    DEVICE

    R

    S

    S

    AOP

    DETAIL XX

    PAGE REFERENCEDETAIL XX

    ANALOG OUTPUT, PNEUMATICAOP

    ACTUATOR TECATEC

    AUTOZERO MODULEAZM

    CURRENT TRANSDUCERCT

    DDC DUAL DUCT CONTROLLER

    DEM DEMAND ENERGY MONITOR

    EXPANSION PANELEXP

    HAND-HELD OPERATOR'S TERMINAL

    HL HIGH LIMIT

    H

    HHC

    HYGROSTATS

    FAN FAN

    GD GAS DETECTOR

    HE HUMIDIFIER ELECTRIC

    P PUMP

    OPERATOR DATA PANELODP

    SPP STATIC PRESSURE PROBE

    TIE TRUNK ISOLATOR EXTENDER

    VALVEV

    VAC VIBRATION ISOLATOR

    READ AS " SEE PAGE 5A FOR MORE DETAIL "

    DIGITAL INPUT

    POINT ADDRESSING EXAMPLE

    LOGICAL POINT NAME

    POINT NUMBER

    DROP NUMBER

    NODE NUMBER

    REFERENCE NUMBER

    FLN TRUNK

    DETAIL MC

    DETAIL 5A

    AH1LTD

    0001:3.10.27

    TALON MODULAR CONTROLLER

    TALON COMPACT CONTROLLER

    TCM

    TCC

    GAUGE

    LOCAL USER INTERFACELUI

    CO2 TEMP TRANSMITTER ELECCTTE

    1 5/26/2014 CS AS-BUILT DRAWING

    2 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 5 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\CCTERM.dwg

    TTRM1

    0

    TC Termination Specification

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    ANALOG OUTPUT (AO,U,X) 0-10VDCI00

    ANALOG INPUT (UI,U,X) 4-20 mAM00 2-WIRE INTERNAL POWERED

    L

    DIGITAL OUTPUT (DO) NCA00 PULSED OR LATCHED

    DIGITAL OUTPUT (DO) NOB00 PULSED OR LATCHED

    EXCITATION+

    NH

    SIG

    NH

    NOTES:

    COMMON NOT CONNECTED1.

    CONTROLLED

    DEVICE

    NOTES:

    0 VDC ON CABINET FAILURE1.

    CONTROLLED

    DEVICE

    CONTROLLED

    DEVICE

    OR

    24V

    ORSIG

    COM

    NOTES:

    MAXIMUM WIRE RUN LENGTHS ARE BASED

    ON THE CURRENT DRAW AND WIRE GAGE.

    SEE DRAWING TWIR.

    MAXIMUM CONTACT CLOSURE RATE IS

    10 PER SECOND

    SEE CONTROL DRAWINGS FOR NORMAL

    DE-ENERGIZED CONTACT STATE

    TCC DO CONTACT RATINGS

    AC OPERATION:

    DC OPERATION:

    40W @ < 50VDC

    20W @ > 50VDC

    MAXIMUM CURRENT PROVIDED BY THE

    REFER TO DRAWING P2 ON TWIR FOR

    TCC 24VDC SENSOR SUPPLY.

    EXTERNAL POWER SUPPLY CAN EITHER

    BE A 24VDC POWER SUPPLY OR A

    24VAC TRANSFORMER DEPENDING ON

    THE SENSOR SELECTED. IF NOT AN

    ISOLATED NC CLASS 2 CIRCUIT THEN

    POWER SOURCE, NEUTRAL AND TCCOMPACT COMMON MUST BE BOTH

    CONNECTED TO THE SAME OR BONDED

    BUILDING APPROVED EARTH GROUND.

    FOR FURTHER DETAILS SEE EARTH

    GROUNDING RULES (125-3002) APOGEEWIRING GUIDELINES FOR FIELD PANELS

    AND EQUIPMENT CONTROLLERS.

    50mA OR LESS - 750ft/230m50mA TO 100mA - 375ft/115m

    REFER TO TCC TERMINATION TABLES

    FOR ACTUAL POINT ADDRESSES.

    COMMON TERMINAL MAY BE SHARED BY

    2 POINTS. AND ORDER MAY BE

    REVERSED ON ADJACENT POINTS.

    100mA TO 150mA - 250ft/76m150mA TO 200mA - 187ft/57m200mA TO 250mA - 150ft/46m

    4A @ 240VAC (RESISTIVE)3A @ 240VAC (INDUCTIVE)SIZE 4 MOTOR STARTER

    DI EXCITATION = 24VDC, 10mA

    UI, U EXCITATION = 24VDC, 6mA,

    150ms, 1mA

    WHERE H TERMINAL IS NOT A NEC

    CLASS 2 CIRCUIT, RELAY COMMONTERMINAL BRANCH CURRENT MUST BE

    EXTERNALLY LIMITED TO 10A MAXIMUM

    BY A NEC APPROVED MEANS. NOT A

    FUSE.

    WHERE REQUIRED, NEUTRAL TERMINALBRANCH CURRENT MUST BE EXTERNALLY

    LIMITED BA A NEC APPROVED MEANS.

    DI CANNOT BE USED FOR PULSE

    ACCUMULATION.

    UI, U, X MAXIMUM PULSE RATE = 20HZ

    (25ms PER STATE, 50ms PRE PULSE.

    ANALOG OUTPUT (X) 4-20 mAH00

    NOTES:

    0 mA ON CABINET FAILURE1.

    CONTROLLED

    DEVICE

    4-20 mA

    THIS POINT TYPE CANNOT SHARE2.

    A MODULE WITH A SELF-POWERED

    TYPE INPUT POINT.

    DIGITAL OUTPUT (AO,U,X) LATCHEDC00 VOLTAGE TO SOLID STATE RELAY

    DIGITAL OUTPUT (AO,U,X) SEQUENCEDD00 VOLTAGE TO SEQUENCING MODULE

    NOTES:

    0 VDC ON CABINET FAILURE1.

    MAY BE MULTI-STAGE2.

    EXCITATION +

    4-20 mA

    DEVICECOM

    SIG

    ANALOG INPUT (UI,U,X) 4-20mAN00 3-WIRE INTERNAL POWERED

    4-20 mA

    DEVICESIG

    COM

    ANALOG OUTPUT (AO,U,X) 0-10VDCJ00 VOLTAGE TO CURRENT CONVERTER

    DEVICE

    CONTROLLED

    N H

    NOTES:

    0 VDC ON CABINET FAILURE1.

    DEVICE

    CONTROLLED

    N H

    COM

    24V

    SIG

    OR

    24V

    OR

    24V

    24V

    OR

    DEVICE

    CONTROLLED

    V2C

    SIG

    COM

    24V

    OR

    DIGITAL INPUT (UI,U,X)F00 PULSE ACCUMULATOR

    DIGITAL INPUT (DI,UI,U,X)E00 DRY CONTACT

    2

    DI

    GND

    DI

    GND

    OR

    OR

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    1

    6

    11 12

    2

    5

    2

    5

    11 12

    6

    1

    1 9

    7

    6

    6

    7

    1 9

    1211

    9

    6

    9

    6

    6

    3

    4

    9

    6

    3

    9

    7

    6

    7

    10

    7

    6

    9

    7

    6

    9

    1211

    ANALOG INPUT (UI,U,X) 4-20mAO00 3-WIRE EXTERNAL POWERED

    EXCITATION +

    DEVICE

    4-20 mA

    COM

    SIG

    POWER

    SUPPLY

    + - E

    OR

    8

    6

    ANALOG INPUT (UI,U,X) 4-20mAQ00 4-WIRE EXTERNAL POWERED

    EXCITATION +/H

    EXCITATION -/N4-20 mA

    DEVICESIG

    COM

    SUPPLY

    -/N

    POWER

    +/H

    E

    OR

    9

    8 6

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 6 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\CCTERM2.dwg

    TTRM2

    0

    TC Termination Spec. Sheet 2

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    ANALOG INPUT (UI,U,X) 0-10VDCT00 3-WIRE EXTERNAL POWERED

    SUPPLY

    POWER

    +/H -/N

    DEVICE COM

    SIG

    EXCITATION +

    0-10Vdc

    ANALOG INPUT (UI,U,X) 0-10VDCU00 4-WIRE EXTERNAL POWERED

    COM

    DEVICE

    0-10VdcEXCITATION +/H

    EXCITATION -/NSIG

    -/N

    SUPPLY

    +/HPOWER

    E

    OR

    ANALOG INPUT (UI,U,X) 0-10VDCS00 3-WIRE INTERNAL POWERED

    ANALOG INPUT (UI,U,X) THERMISTORW00

    ANALOG INPUT (UI,U,X) RTDV00

    ANALOG INPUT (UI,U,X) 0-10 VdcR00 SELF POWERED TRANSDUCER

    SIG

    COM

    L

    V

    SIG

    COMSIG

    COM

    SIG

    NOTES:

    1000 OHM PLATINUM (375)1.

    1000 OHM PLATINUM (385)2.1000 OHM NICKEL3.

    4. CUSTOM

    NOTES:

    100 KOHM1.

    10 KOHM2.

    CUSTOM3.

    NOTES:

    TRANSDUCER POWERED FROM INPUT1.

    TRANSDUCER OUTPUT VOLTAGE2.

    EXCITATION+

    EXCITATION -/COM

    OR

    OR

    OR

    24V

    OR

    8

    6

    6

    9

    7

    6

    8

    8

    6

    6

    9

    6

    9

    9

    9Notes:

    1. FOR THE APPROPRIATE TERMINAL SYMBOL,PLEASE REFER TO THE RESPECTIVE POINT TYPE

    COLUMN.

    2. THE Common TERMNAL IS ALWAYS THE

    FOLLOWING SYMBOL:

    3. SEE BELOW FOR DIGITAL OUTPUT SYMBOL:

    NC

    C

    NO

    NC

    C

    NOSIG

    COM

    6

    9

    DIGITAL OUTPUT (X) 24 VDCAB00 RELAY DRIVE 22 mA MAX.

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 7 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\CCWIRE.dwg

    TWIR

    0

    TC Wiring Specification

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    4

    2

    MAXIMUM NUMBER HSTIE IN SERIES ON ALN TRUNK

    TABLE 4

    10 6 6

    SPEED

    7

    1200 4800 57.6K - 115.2K9600 - 38.4K

    BAUD BAUD BAUD BAUD

    SERIES TIE'S

    2.

    TABLE 3 NOTES:

    1. DISTANCES SHOWN ASSURE LESS THAN 10VOLTAGE

    DROP ACROSS THE WIRE FOR A TYPICAL STARTER.

    TCC DO CONTACT RATINGS

    GENERAL NOTES:

    4A @ 250VAC & 30VDC

    1

    CONDUIT SHARINGWIRE TYPECLASSCIRCUIT TYPE MAX. DISTANCE

    CODES

    CHECK LOCAL

    CODES

    CHECK LOCAL

    CODES

    CHECK LOCAL

    CHECK LOCAL

    CODES

    CODES

    CHECK LOCAL

    CODES

    CHECK LOCAL

    CHECK LOCAL

    CODES

    CODES

    CHECK LOCAL

    CM(FT4) or CMP(FT6)

    ANALOG OUTPUT 2

    0-10 V

    4-20 mA

    2ANALOG OUTPUT

    ANALOG INPUT 2

    1K Ni OR RTD

    ANALOG INPUT 2

    4-20 mA

    0-10 V

    2ANALOG INPUT

    DIGITAL INPUT 2TP not required, check 750ft

    job specs & local codes

    DIGITAL OUTPUT 1 & 2 SEE TABLE 3

    THHN

    REFER#12-14POWERAC LINE POWER

    TABLE 1

    TCC WIRING TYPE AND GAUGE REQUIREMENTS

    TABLE 2

    CABLE CONFIGURATION TWISTED PAIR OR TSP

    #18 TO #22 AWG (STRANDED)GAUGE

    n.a.CAPACITANCE

    SHIELDS NOT REQUIRED (IN CASE OF

    CM, CMP (75%C OR HIGHER)NEC CLASS

    TWISTS PER FOOT 6 MINIMUM

    TCC WIRE SPECIFICATIONS

    6 MINIMUM

    UL VOLTAGE RATING 300 VAC

    n.a.

    TWISTED PAIR (UNJACKETED) OR TSP

    UL TEMP. RATING 75%C (167%F)

    TWISTED SHIELDED PAIR

    24 AWG (STRANDED)

    12.5 pf/ft OR LESS

    100FOIL W/ DRAIN WIRE

    CM, CMP (75%C OR HIGHER)

    6 MINIMUM

    LOW-VOLTAGE POINT APPLICATIONS POINT USAGE ALN TRUNK

    NOT SPECIFIED

    NOT SPECIFIED NOT SPECIFIED

    NOT SPECIFIED

    NOT SPECIFIED

    MAXIMUM DO WIRE RUN LENGHTSTABLE 3

    WIRE SIZESTARTER

    SIZE

    NOMINAL

    INRUSH#18 #16 #14

    200 VA

    550 VA

    1150 VA

    1500 VA

    0

    1

    2

    3

    4

    500ft

    (152m)

    200ft

    (61m)

    100ft

    (30m)

    70ft

    (21m)

    900ft

    (274m)

    300ft

    (91m)

    150ft

    (46m)

    100ft

    (30m)

    1400ft

    (427m)

    500ft

    (152m)

    250ft

    (76m)

    200ft

    (61m)

    ETHERNET ALN 2 #24 (4) TPCODES

    CHECK LOCAL

    CM(FT4) or CMP(FT6)

    CM(FT4) or CMP(FT6)

    CM(FT4) or CMP(FT6)

    CM(FT4) or CMP(FT6)

    TO NEC

    (230 m)

    750ft

    (230 m)

    (230 m)

    750ft

    (230 m)

    750ft

    (230 m)

    750ft

    (230 m)

    750ft

    (90 m)

    295ft

    #18 to #24 AWG

    job specs & local codesTP not required, check

    #18 to #24 AWG

    FT4, FT6 (75%C OR HIGHER)CEC CLASS

    TSP, 100FOIL W/ DRAIN WIRE)

    #18 TO #22 AWG (STRANDED)

    NOT REQUIRED (IN CASE OFTSP, 100FOIL W/ DRAIN WIRE)

    NOT SPECIFIED FT4, FT6 (75%C OR HIGHER)

    1. UL RECOGNIZED WIRE (LABELED WITH A BACKWARDS 'RU') IS NOT FIELD INSTALLABLE. USE ONLY UL-LISTED WIRE.2. 300 VAC WIRE CAN BE USED IN FIELD PANELS CONTAINING VOLTAGES BELOW 150 VAC.

    2

    SIZE 4 MOTOR STARTER

    ALN TRUNK 2 #24 TSP CODESCHECK LOCAL

    SEE TABLE 4 ALN TRUNK 4000ft

    DISTANCE (1.2km)4000ft

    (1.2km)4000ft

    (1.2km)3280ft

    (1km)

    TIE MUST BE USED TO ISOLATE ALN BETWEEN TCC CONNECTED

    TO DIFFERENT SERVICE GROUNDS OR ON BOTH SIDES OF THE

    THE MAX ALN DISTANCE APPLIES TO EACH SIDE OF THE TIE.

    MMI EXT. CABLE3/4" & 1"

    TCC COMMN TERMINATIONSP3

    00

    24VAC VA RATING

    TCC FAMILY VA RATINGS & SENSOR SUPPLY

    NO MORE THAN SEVEN (7) FULLY LOADED

    RECEPTACLE IS PRE-WIRED AND MOUNTED

    COMMUNICATION CONNECTORS PLUG INTO TCC.

    ALN MUST BE DAISEY-CHAINED WHEN RUNNING

    E TERMINAL IS EARTH GROUNDED.

    USE ALN SHIELD TERMINATION P3A WHEN 24VAC

    19.2 k BAUD OR FASTER AND TRUNK TERMINATORS

    TERMINATE SHIELD AT LEAVING END OF

    IN FACTORY, FOR 115VAC SERVICE BOX ONLY.

    TCC CABINETS ALLOWED ON A SINGLE 3-WIRE CIRCUIT.

    TCC POWER WIRINGP2

    00

    TCC CONDUIT PENETRATIONSP1

    00

    ALN TRUNK ONLY.

    +-

    4.

    3.

    WIRE SECURING

    SCREWS IN TOP

    NOTES:

    2.

    1.

    TC COMPACT 16

    NOTES:

    2.

    1.

    PRODUCT

    1/2" & 3/4"C=

    DUPLEX RECEPTACLE

    TCC ON ETHERNET CONNECTOR

    COVER WITH

    (115VAC ONLY)

    HOT

    NEUT

    FOR ETHERNET PATCH CABLE

    RJ-45 SHIELDED JACK

    JUNCTION BOX

    TRANSFORMER IN POWER BOX.

    MADE IN FIELD18

    AC EARTH GROUND

    TO GROUNDING LUG AT

    GND

    "A"

    THESE CONNECTIONS

    WIRE NUT

    (TYP)

    TCC ENCLOSURE

    "C"

    POWER

    BOX

    OFF

    ON

    115VAC W/GND

    COVER

    WIRE

    KNOCKOUT

    VOLTAGE:

    XFMR POWER:

    LINE FREQUENCY:

    1" & 1-1/4"

    KNOCKOUT TYPES

    A=

    B=

    "B"

    "A"

    50 / 60 Hz

    102-132 VAC

    204-264 VAC

    200 VA (MAX.)

    SERVICE BOX MAX

    POWER SOURCE REQUIREMENTS

    "B"

    "A"

    "C""B""B""A""C""A""A"

    TCC SMALL ENCL.

    OFF

    ON

    CTLR

    DUPLEX RECEPTACLE

    CABLE TIE BARS

    (60 VA MAX)24V ACTUATOR

    (24 VAC,100 VA MAX)

    "C" (NOT SHOWN)

    TRANSFORMER

    WIRE COVER

    CAT5 OR BETTER

    ALN CABLE THAT EXITS BUILDING.

    24VDC mA

    100

    TC COMPACT 24 20 100

    USED AT BOTH ENDS OF LINE P3C.

    E: EALN ETHERNET CONNECTOR

    E TERMINAL IS OPEN.

    USE ALN SHIELD TERMINATION P3B WHEN 24VAC5.

    B: ALN TRUNK

    CONNECTOR

    - +

    ALN TERMINATOR

    H: TCC - HMI

    RJ45 JACK FOR RS232 SERVICE MODE

    SERIAL PRINTER OR TCC

    7. DO NOT INSERT RJ-11 6 PIN PLUG

    WITHOUT PIN 1 AND 8 VOIDS

    7

    EALN

    (4) TWISTED PAIR

    24AWG(STRANDED)

    13 pf/ft OR LESS

    CATEGORY 5 Min

    NOT REQUIRED

    MM, MMP

    NOT SPECIFIED

    NOT SPECIFIED

    NOT SPECIFIED

    4

    CODES

    CHECK LOCALANALOG INPUT 2

    100K/10K Thermistor CM(FT4) or CMP(FT6)

    750ft

    (230 m)#18-#24 TP or TSP

    3,6 5

    6

    1. WHEN DAISY-CHAINING 24VAC POWER TO CONTROLLERS USE #14 WIRE.

    2. CONDUIT SHARING RULES: ONLY WHERE LOCAL CODES PERMIT.

    BOTH CLASS1 AND CLASS 2 WIRING CAN BE RUN TO THE TCC PROVIDED

    THE CLASS 2 WIRE IS UL LISTED 300V 75°C(167°F) OR HIGHER OR THECLASS 2 WIRE IS NEC TYPE CM (FT4) (75°C OR HIGHER) OR CMP(FT6)(75°C OR HIGHER). NEC TYPE CL2 AND CL2P IS NOT ACCEPTABLE UNLESSALSO UL LISTED AND MARKED 300V 75°C (167°F) OR HIGHER

    3. TWISTED PAIR, NON-JACKETED UL LISTED 75°C(167°F) AND 300V, CABLECAN BE USED IN PLACE OF CM(FT4) OR CMP(FT6)(BOTH MUST BE RATED75°C OR HIGHER) CABLE WHEN CONTAINED IN CONDUIT PER LOCAL CODES.SEE THE FIELD PURCHASING GUIDE FOR WIRE.

    4. WIRE LENGTH AFFECTS POINT INTERCEPT ENTRY. ADJUST INTERCEPT

    ACCORDINGLY FOR EACH WIRE GAUGE AND SENSOR TYPE.

    5. SHIELDED TWISTED PAIR (TSP) IS NOT REQUIRED FOR ELECTRICAL NOISELEVELS UPTO 10 V/M. AT HIGHER LEVELS TSP MAY BE NEEDED.TERMINATESHIELD ON ENCLOSURE AND TAPE BACK ON POINT END.

    6. FOR 24AWG INSTALL CATEGORY5 OR BETTER CABLE PER

    ANSI/TIA/EIA-568-B.1 OR HIGHER. USE SOLID COPPER BETWEEN JACKBOXES. USE STRANDED COPPER PATCH CABLES 13ft (4m) TO CONNECTTCC AND 20ft (6m) TO CONNECT SWITCH OR HUB.

    ( COMPLY WITH LOCAL BUILDING CODES

    ( SIZE WIRE FOR LOAD, CURRENT, AND VOLTAGE.

    ( ALL WIRE TO BE APPROVED OR LISTED FOR THE INTENDED

    APPLICATION BY AGENCIES SUCH AS UL, NEC, CSA.

    ( ALWAYS REFER TO LOCAL CODES FOR CONDUIT SHARING.

    ( WIRING MUST HAVE INSULATION RATED FOR HIGHEST VOLTAGE

    CIRCUIT IN CONDUIT.

    ( THE ALN TRUNK MUST BE AN UNINTERRUPTED RUN BETWEEN

    CABINETS. NO SPLICES ALLOWED.

    ( CM/CMP/MM/MMP WIRE IS NOT USABLE FOR CLASS 1CIRCUITS.

    ( FOR EXTENDED TEMPERATURE INSTALLATIONS USE ONLY

    COPPER WIRE LISTED FOR 90°C OR HIGHER

    WIRE SECURING

    SCREWS IN TOP

    #18-#24 TP or TSP3,6 5

    #18-#24 TP or TSP3,6 5

    #18-#24 TP or TSP3,6 5

    #18-#24 TP or TSP3,6 5

    #18-#24 TP or TSP3,6 5

    115V OUTLETS: 200 VA (MAX.)

    G: USB DEVICE CONNECTOR

    FOR LAPTOP

    SHLD

    SHLD

    A: ALN TRUNK

    CONNECTOR

    (EOL ONLY)

    NOTE:

    REFER TO "APOGEE WIRING

    GUIDELINES FOR FIELD

    PANELS AND EQUIPMENT

    CONTROLLERS (125-3002)"FOR FLN WIRING CONFIG'S.

    TC COMPACT 36 35 200

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 8 of 82

  • AHU-1

    HTG-1 AHU 2A-

    TRUNK INTERFACE II

    TI 1-

    NETWORK 1

    ID# 7180MAC: 192.168.0.101

    ID# 71801MAC: 2

    ID# 71802MAC: 3

    NETWORK 7180

    AHU 2B-

    ID# 71803MAC: 4

    AHU 4-

    ID# 71804MAC: 5

    AHU 5-

    ID# 71805MAC: 6

    AHU 6-

    ID# 71806MAC: 7

    AHU 7-

    ID# 71807MAC: 8

    AHU 8-

    ID# 71808MAC: 9

    AHU 9-

    ID# 71809MAC: 10

    ID# 71810MAC: 11

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group All Rights Reserved

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\JOBS\23_7232_91PORT_UNION\SER.DWG

    000

    0

    Riser Diagram

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    LOCAL BUILDING NETWORK SWITCHTRIDIUM NIAGARA JACE 6

    IP ADDRESS: 172.18.84.153

    DEFAULT GATEWAY: 172.18.84.129

    SBNET MASK: 255.255.255.128

    CLG

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 9 of 82

  • 2

    NORTH

    WALL

    TTE 5

    -40/240%FBLD91.OAT

    HTG:0.0.6

    -

    DETAIL V

    1

    1

    2

    TTE 1

    -40/240%FBLD91.BLRHWR

    HTG:0.0.3

    DETAIL V

    1/2" X 3 1/2" NPT

    -

    FS 1-

    BOILER 1-

    BOILER SYSTEM FLOW DIAGRAM

    001A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: ENTIRE BUILDING

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EH2B2D REV 9 03/25/08

    SEE BOILER WIRING DETAIL ON DRAWING ?

    SEE PUMP MOTOR STARTER WIRING DETAIL ON DRAWING ?

    INSTALLATION NOTES:

    HWR

    HWS

    STR 1-

    P 1-

    CS 1

    BLD91.HWP1SS (Proof)HTG:0.0.4

    DETAIL E

    -

    RELAY AND CSR MOUNTED AT STARTER

    XFMR 1

    100 VA

    LOCATED @ FIELD PANEL

    -

    CIRC

    PUMP

    RELAY MOUNTED AT BOILER PANEL.

    1

    FS 2-

    BOILER 2-

    CIRC

    PUMP

    CS 2

    BLD91.HWP2SS (Proof)HTG:0.0.5

    DETAIL E

    -

    2P 2-

    STR 2-RE 1

    BLD91.HWP1SS (On/Off)HTG:0.0.22

    DETAIL B

    -

    RE 2

    BLD91.HWP2SS (On/Off)HTG:0.0.23

    DETAIL B

    -

    RE 4

    BLD91.BLR2SS (On/Off)HTG:0.0.21

    DETAIL B

    -

    RE 3

    BLD91.BLR1SS (On/Off)HTG:0.0.20

    DETAIL B

    -

    RE 7

    BLD91.BLR1SS (Proof)HTG:0.0.1

    DETAIL E

    -

    RE 8

    BLD91.BLR2SS (Proof)HTG:0.0.2

    DETAIL E

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 001A

    0

    HEATING PLANT MECH

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    HTG HTGPLNT HTG

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 10 of 82

  • PNL-__ STARTER WIRINGFIELD WIRINGFIELD PANEL POWER

    BOILER WATER WIRING DIAGRAM

    001B LOCATION: 91 PORT UNION COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EH2B2D REV 3 03/25/08

    START/STOP

    1

    1120VAC

    24N24H

    INSTALLATION NOTES:

    OL'S

    PUMP P-1

    ᅯᅫᅱ

    C

    120VAC

    START/STOP

    OL'S

    PUMP P-2

    ᅯᅫᅱ

    C

    120VAC

    PUMP STARTER.

    RELAY LOCATED NEAR

    BOILER PANEL.

    RELAYS LOCATED NEAR4

    3 VERIFY BOILER CABLE SPECIFICATION

    REQUIREMENTS W/BOILER MFG.

    2

    BLD91.HWP1SS (On/Off)HTG:0.0.22

    ON/OFF

    11

    10

    12

    BLD91.HWP1SS (Proof)HTG:0.0.4

    PROOF

    30

    29

    BLD91.BLR1SS (On/Off)HTG:0.0.20

    ON/OFF

    5

    4

    6

    BLD91.BLR1SS (Proof)HTG:0.0.1

    25

    26

    6.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIRMENTS OF

    2

    2

    FIELD PANEL.

    120VAC POWER TO XFMR

    FROM SAME CIRCUIT AS

    BLD91.HWP2SS (On/Off)HTG:0.0.23

    ON/OFF

    14

    13

    15

    BLD91.HWP2SS (Proof)HTG:0.0.5

    PROOF

    31

    32

    START/STOP

    4

    FS-1

    BLD91.OAT

    HTG:0.0.6

    33

    32

    BLD91.BLRHWR

    HTG:0.0.3

    28

    29

    TTE-5

    LOCATION: OUTSIDE MAIN MECH RM

    OA

    WHT

    BLKHWR+

    -

    COMMONBLK

    WHT

    BLK

    WHT +

    -BLK

    WHT

    BLD91.BLR2SS (On/Off)HTG:0.0.21

    ON/OFF

    8

    7

    9

    FS-2

    BLD91.BLR2SS (Proof)HTG:0.0.2

    27

    26

    PARALLEL WITH GAS VALVE.

    BOILER STATUS TO BE WIRED IN5

    START/STOP

    3

    3

    4

    4

    4

    RE-1

    C

    RE-2

    C

    RE-3

    C

    RE-7

    C

    RE-4

    C

    RE-8

    C

    M

    L3L2L1

    CS-1

    M

    L3L2L1

    CS-2

    BOILER-1

    ENABLE

    ##

    ##

    STATUS

    ##

    ##

    STATUS

    ##

    ##

    FLOW SWITCH

    INTERLOCK

    ##

    ##

    COMBUSTION

    AIR DAMPER

    ##

    ##

    INTERLOCK

    AIR DAMPER

    ##

    ##

    BOILER-2

    ENABLE

    ##

    ##

    STATUS

    ##

    ##

    STATUS

    ##

    ##

    FLOW SWITCH

    INTERLOCK

    ##

    ##

    COMBUSTION

    AIR DAMPER

    ##

    ##

    INTERLOCK

    AIR DAMPER

    ##

    ##

    TTE-1

    VA

    24 VAC

    XFMR-1

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    001BHEATING PLANT ELEC

    0

    23_7232CITY OF TORONTO PARKS & REC

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 11 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/14CSCS

    C:\Jobs\23_7232_91Port_Union\ATING PLANT-K00.dwg

    001CHEATING PLANT BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    CS 1-2 2 H906 VERIS 1006cut005 Current Switch,Split-Core,Adj,N.C.

    FS 1-2 2 BY OTHERS N/A N/A N/A

    RE 1-4 4 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    RE 7-8 2 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAE2130.010 SIEMENS 149807 IMMER TEMP SEN, NTC 10K OHM T 2, 4" PROB

    1 ARG100U SIEMENS N/A 1/2 NPT IMMERSION WELL SS (4")

    TTE 5 1 QAC2030U SIEMENS 149920 OUTDOOR AIR SNSR, NTC 10K OHM TYPE 2

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Panel Mounted Devices

    PNL 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    The boiler system shall be enabled whenever the heating flag is ON.

    The heating flag shall be programmed to operate as follows:

    May, June and September

    Occupied Mode

    ON when OAT is less than 10 Deg C or the lowest room temperature is less than 21 Deg C.

    OFF when OAT is above 15 Deg C and the lowest room temperature is above 21 Deg C.

    Unoccupied Mode

    ON when OAT is less than 8 Deg C and the lowest room temperature is less than 17.2 DegC.

    OFF when OAT is above 9 Deg C andthe lowest room temperature is above 17.2 Deg C.

    The operator can set the heating flag to MANUAL ON or MANUAL OFF if comfort conditions cannot be maintatined by the

    programmed set points

    The heating flag will be returned to AUTO control when the OAT rises above the programmed high limit set points orfalls

    below the preprogrammed low limit set points as follows:

    May, June and September

    Auto ON when OAT is less than 2 Deg C.

    Auto OFF when OAT is above 15 Deg C.

    October to April

    Auto ON when OAT is less than 3.9 Deg C.

    Auto OFF when OAT is above 18 Deg C.

    The boiler system heating return water temperature set point shall be reset based on OAT as follows:

    Occupied Mode

    OAT RWT

    -23 Deg C 76.6 Deg C

    0 Deg C 69 Deg C

    Boiler Staging:

    To maintain setpoint, the lead boiler starts. If the lead boiler has started, but the setpoint has not been reached

    within 5 minutes, the lag boiler is also started. Upon call for heat, if the lead boiler fails to start within 20seconds, the

    lag boiler is started

    Pump Control:

    Heating pump shall run continuously as long as the heating enable FLAG is ON.

    Heating boiler low water temperature alarm:

    If hot water return temperature drops below 21 Deg C an alarm shall be generated. Alarm shall reset when

    temperature rises above 26 Deg C.

    Addendum No. 3 for RFP 9118-15-5083 - Page 12 of 82

  • RE 1

    BLD91.CHP1SS (Proof)CLG:0.0.2

    DETAIL B

    -

    RE 2

    BLD91.CWP1SS (Proof)CLG:0.0.5

    DETAIL B

    -

    RE 3

    BLD91.CHL1SS (On/Off)CLG:0.0.21

    DETAIL B

    -

    XFMR 1

    100 VA

    LOCATED @ FIELD PANEL

    -

    1

    RELAY MOUNTED AT CHILLER.

    INSTALLATION NOTES:

    CSR AND RELAY MOUNTED AT STARTER.

    CHILLER

    CH-1

    2 STR 2-

    P 2-

    CS 2

    BLD91.CWP1SS (On/Off)CLG:0.0.23

    DETAIL E

    -

    TTE 2

    -40/240% FBLD91.CHLCWS

    CLG:0.0.1

    DETAIL V

    1/2" X 3 1/2" NPT

    -

    CS 1

    BLD91.CHP1SS (On/Off)CLG:0.0.20

    DETAIL E

    -

    P 1-

    CHWR

    CHWS

    SEE PUMP MOTOR STARTER WIRING DETAIL ON DRAWING ?

    SEE CHILLER WIRING DETAIL ON DRAWING ?

    CWR

    CWS

    1

    2

    1

    1 FS 1-1 FS 2-

    CHILLED WATER PIPING SYSTEM

    002A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: ENTIRE BUILDING

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EC1C1D REV 9 03/25/08

    STR 1-2

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 002A

    0

    COOLING PLANT MECH

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    CS 3

    BLD91.CHL1SS (Proof)CLG:0.0.3

    DETAIL E

    -

    1 5/26/2014 CS AS-BUILT DRAWING

    2 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 13 of 82

  • START/STOP

    1

    1120VAC

    24N24H

    INSTALLATION NOTES:

    OL'S

    CHILLED WATER PUMP STARTER

    ᅯᅫᅱ

    C

    120VAC

    PUMP STARTER.

    RELAYS LOCATED NEAR

    CHILLER PANEL.

    RELAYS LOCATED NEAR4

    3 VERIFY CHILLER CABLE SPECIFICATION

    REQUIREMENTS W/CHILLER MFG.

    2

    PNL-__ STARTER WIRINGFIELD WIRINGFIELD PANEL POWER

    BLD91.CHP1SS (On/Off)CLG:0.0.20

    CHILLED WATER PUMP ON/OFF

    5

    4

    6

    BLD91.CHP1SS (Proof)CLG:0.0.2

    CHILLED WATER PUMP PROOF

    27

    26

    5.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIRMENTS OF

    2

    FIELD PANEL.

    120VAC POWER TO XFMR

    FROM SAME CIRCUIT AS

    CHILLED WATER WIRING DIAGRAM

    002A LOCATION: MAIN MECHANICAL ROOMCOPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EC1C1D REV 2 03/25/08

    3

    START/STOP

    FS-1

    FS-2

    BLD91.CHL1SS (On/Off)CLG:0.0.21

    CHILLER ENABLE

    8

    7

    9

    BLD91.CHL1SS (Proof)CLG:0.0.3

    CHILLER RUNNING PROOF

    28

    29

    4

    BLD91.CWP1SS (Proof)CLG:0.0.5

    CONDENSER PUMP PROOF

    31

    32

    START/STOP

    2

    OL'S

    CONDENSER WATER PUMP STARTER

    ᅯᅫᅱ

    C

    120VAC

    BLD91.CWP1SS (On/Off)CLG:0.0.23

    CONDENSER PUMP ON/OFF

    14

    13

    15

    M

    L3L2L1

    CS-1

    M

    L3L2L1

    CS-2

    RE-1

    C

    RE-2

    C

    RE-3

    C

    VA

    24 VAC

    XFMR-1

    100

    BLD91.CHLCWS

    CLG:0.0.1

    25

    26 BLK

    WHT WHT

    BLK

    TTE-2

    CHWS-

    +

    COMMON

    EQUIP LOC

    ##

    ##

    ##

    ##

    FLOW

    SWITCH

    ##

    ##

    FLOW

    SWITCH

    ##

    ##

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    002BCOOLING PLANT ELEC

    0

    23_7232_91Port_UnionCITY OF TORONTO PARKS & REC

    COMP1STATUS

    CHILLER ENABLE

    CHILLER PRFON

    CLG CLGPLNT CLG

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    1 5/26/2014 CS AS-BUILT DRAWING

    2 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 14 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\HILLER PLANT-K00.dwg

    002C

    0

    COOLING PLANT BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    CS 1-4 4 H906 VERIS 1006cut005 Current Switch,Split-Core,Adj,N.C.

    FS 1-2 2 BY OTHERS N/A N/A N/A

    RE 1-4 4 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 2 1 QAE2130.010 SIEMENS 149807 IMMER TEMP SEN, NTC 10K OHM T 2, 4" PROB

    1 ARG100U SIEMENS N/A 1/2 NPT IMMERSION WELL SS (4")

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Panel Mounted Devices

    PNL 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    The chilled water system shall be enabled whenever the cooling flag is ON.

    The cooling flag shall be programmed to operate as follows:

    May, June and September

    Occupied Mode

    ON when OAT is greater than 15 Deg C or the highest room temperature is more than 25 Deg C.

    OFF when OAT is less than 10 Deg C and the highest room temperature is beow 25 Deg C.

    Unoccupied Mode

    Chilled water system is OFF.

    October to April

    Cooling flag is OFF.

    When cooling flag is turned ON;

    The Chilled Water and Condenser Water Pumps are commanded to start. When the chilled water pumps prove on, the

    Chiller shall be enabled after 5 minutes of pump run time and will maintain its integral chilled water set point.

    When cooling flag is turned OFF;

    The Chiller will be disabld, then the Chilled Water and Condenser Water pumps will be disabled 5 minutes after the chillerhas been disabled.

    1 5/26/2014 DG AS-BUILT DRAWING

    2 5/26/2014 CS AS-BUILT DRAWING

    3 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 15 of 82

  • RE 2

    BLD91.1L (On/Off)CLG:0.0.24

    DETAIL B

    -

    RE 1

    BLD91.1H (On/Off)CLG:0.0.13

    DETAIL B

    -

    XFMR 1

    100 VA

    LOCATED @ FIELD PANEL

    -

    TTE 1

    -40/240% FBLD91.CWS

    CLG:0.0.7

    DETAIL V

    1/2" X 3 1/2" NPT

    -

    1-CT

    CSR AND RELAYS MOUNTED AT STARTER.

    STR 1-

    CS 1

    BLD91.1L (Proof)CLG:0.0.6

    DETAIL E

    -

    CWS

    CWR

    SEE COOLING TOWER FAN STARTER WIRING DETAIL ON DRAWING ?

    INSTALLATION NOTES:

    1

    1

    COOLING TOWER DIAGRAM

    003A LOCATION:91 PORT UNION COMMUNITY CENTRESERVES: CHILLER

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EC1T1M REV 9 03/25/08

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13DGDGDG 003A

    0

    COOLING TOWER MECH

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    CLG CLGPLNT CLG

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    Addendum No. 3 for RFP 9118-15-5083 - Page 16 of 82

  • 2

    2 VIBRATION SWITCH WIRING BY DIV 16

    VA

    24 VAC

    XFMR-1

    100

    RE-2

    C

    RE-1

    C

    M

    L3L2L1

    CS-1

    TTE-1

    BLD91.1L (On/Off)CLG:0.0.24

    FAN SPPED: SLOW

    17

    16

    18

    3

    3

    COOLING TOWER STARTER.

    RELAY LOCATED NEAR

    SLOW

    POWERFIELD PANEL FIELD WIRING STARTER WIRINGPNL-__

    BLD91.CWS

    CLG:0.0.7

    CONDENSER WATER TEMP

    34

    35

    BLD91.1L / 1H (Proof)CLG:0.0.6

    CLG TWR PROOF

    33

    32

    BLD91.1H (On/Off)CLG:0.0.13

    FAN SPEED: FAST

    47

    48

    4.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIRMENTS OF

    WHT

    BLK

    COOLING TOWER WIRING DIAGRAM

    003B LOCATION: 91 PORT UNION COMMUNITY CENTRECOPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EC1T1M REV 4 03/25/08

    FAST

    FIELD PANEL.

    FROM SAME CIRCUIT AS

    120VAC POWER TO XFMR1

    1120VAC

    24N24H

    BLK

    WHT

    INSTALLATION NOTES:

    3

    CWS

    OL'S

    CT-1

    SSLOW

    FAST

    OFFAUTO OL'S

    S

    F

    F

    NC

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON BLD91 PORT UNION

    003BCOOLING TOWER ELEC

    23_7232CITY OF TORONTO PARKS & REC

    CLG CLGPLNT CLG

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    Addendum No. 3 for RFP 9118-15-5083 - Page 17 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/14DGDGDG

    C:\Jobs\23_7232_91Port_Union\OOLING TOWER-K00.dwg

    003CCOOLING TOWER BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    CS 1 1 H906 VERIS 1006cut005 Current Switch,Split-Core,Adj,N.C.

    RE 1-2 2 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAE2130.010 SIEMENS 149807 IMMER TEMP SEN, NTC 10K OHM T 2, 4" PROB

    1 ARG100U SIEMENS N/A 1/2 NPT IMMERSION WELL SS (4")

    XFMR 1 1 A7F30008355 N/A N/A N/A

    When cooling flag is turned ON;

    The Cooling Tower shall be enabled/disabled to maintain the Condenser Water Return Temperature (CWRT) at 26 Deg C.

    When the cooling flag is turned OFF;

    The Cooling Tower will continue to maintain the CWRT temp as long as the Chiller Water and Condenser Water pumps areenabled.

    Addendum No. 3 for RFP 9118-15-5083 - Page 18 of 82

  • RA

    OA SACCC

    H

    AHU SYSTEM FLOW DIAGRAM

    004A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 14 03/25/08

    1

    TTE 1

    -40/240 %FBLD91.A01.MAT

    AHU1:0.0.1

    -

    DETAIL V

    TTE 3

    -40/240 %FBLD91.A01.RAT

    AHU1:0.0.2

    -

    DETAIL V

    TTE 2

    -40/240 %FBLD91.A01.SAT

    AHU1:0.0.5

    -

    DETAIL V

    SQB

    0

    10

    AE 2

    6/9 VOLTSBLD91.A01.MAD

    AHU1:0.0.19

    -

    DETAIL I

    SQB

    0

    10

    AE 1

    6/9 VOLTS-

    POWERS

    TTE 4

    13/35 deg CBLD91.A01.RMT

    AHU1:0.0.3

    -

    DETAIL V

    CHWS

    CHWR

    V 1

    0/10 VOLTSBLD91.A01.CCV

    AHU1:0.0.17

    -

    DETAIL I

    V 2

    0/10 VOLTSBLD91.A01.HCV

    AHU1:0.0.18

    -

    DETAIL I

    SPACE SENSOR

    XFMR 1

    100 VA

    -

    INSTALLATION NOTES:

    COMPONENT PANEL_

    2

    3

    1

    RE 5

    BLD91.BLD91.A01..SAF (On/Off)AHU1:0.0.20

    DETAIL B

    -

    CS 1

    BLD91.BLD91.A01..SAF (Proof)AHU1:0.0.4

    DETAIL E

    -

    1

    SF -1

    CP 1-

    4

    SEE WIRING DETAIL ON ELECTRICAL DRAWING ?.

    COMPONENT PANEL.

    CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

    PROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING ?

    BY DIVISION 16.

    SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

    1

    2

    D 2

    NC

    -

    D 1

    NC

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 004A

    0

    AHU 1 MECH

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    BLD91.A01.LTD

    AHU1:0.0.6

    DETAIL E/00

    AHU1 AHU1 AHU1

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    3 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 19 of 82

  • 102 103

    BLK

    WHT

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    COMPONENT PANEL / POWERFIELD PANEL FIELD WIRING STARTER WIRING

    WHT

    BLK

    202 204

    120VAC

    1

    1

    120VAC

    204203

    MIXED AIR

    DISCH AIR

    RETURN AIR

    SPACE

    LOCATION: GYMNASIUMAHU SYSTEM - WIRING DIAGRAM

    004A LOCATION: GYMNASIUM MECH. ROOM

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 5 03/25/08

    V-1

    COOLING

    Y

    M

    GO

    G

    TTE-1

    TTE-2

    TTE-3

    POWERS

    TTE-4

    AE-1

    RA DAMPER

    8(Y)

    2(GO)

    1(G)

    AE-2

    OA DAMPER

    8(Y)

    2(GO)

    1(G)

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    PNL-__

    103102

    BLD91.A01.MAD

    AHU1:0.0.19

    MAD CONTROL SIGNAL (9-6V)

    57

    56

    BLD91.A01.MAT

    AHU1:0.0.1

    MIXED AIR TEMP

    25

    26

    BLD91.A01.CCV

    AHU1:0.0.17

    COOLING COIL VALVE

    53

    54

    BLD91.A01.SAT

    AHU1:0.0.5

    SUPPLY AIR TEMP

    31

    32

    BLD91.A01.RAT

    AHU1:0.0.2

    RETURN AIR TEMP

    27

    26

    BLD91.A01.RMT

    AHU1:0.0.3

    ROOM TEMP SENSOR

    28

    29

    BLD91.A01.SAF (PROOF)AHU1:0.0.4

    SUPPLY AIR FAN PROOF

    30

    29

    103102

    201

    BLD91.A01.SAF

    0.0.20

    SUPPLY AIR FAN (ON/OFF)

    3.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIREMENTS OF

    RE2-2

    109

    FASD-2SD-1

    2

    NEAR STARTER.

    RELAYS LOCATED

    START/STOP

    SHUT DOWN

    SAFETY

    SAME CIRCUIT AS FIELD PANEL.

    120VAC POWER TO XFMR FROM1

    120VAC

    INSTALLATION NOTES:

    SMOKE AND FIRE ALARM SHUTDOWN2

    OL'S

    SUPPLY FAN STARTER

    ᅯᅫᅱ

    C

    120VAC

    1

    201204

    204

    204

    108

    WIRING BY DIV 16.

    AND SMOKE DETECTOR POWER SUPPLY

    BLD91.A01.HCV

    AHU1:0.0.18

    HEATING COIL VALVE

    55

    56 BLK

    WHT

    BLK

    WHT

    V-2

    HEATING

    Y

    M

    GO

    G

    M

    L3L2L1

    CS-1

    RE-4

    C

    -

    RE-5

    C

    -

    VA

    24 VAC

    XFMR-1

    100

    VA

    24 VAC

    XFMR-2

    100

    VA

    24 VAC

    XFMR-3

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    004BAHU 1 ELEC

    0

    23_7232_91Port_UnionCITY OF TORONTO PARKS & REC

    BLD91.A01.MADRST

    AHU1:0.0.21

    MAD ISOLATION (ON/OFF)

    8

    7

    9

    BLD91.A01.LTD

    AHU1:0.0.6

    FREEZE STAT

    33

    32 AHU1 LTD

    AHU1 AHU1 AHU1

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    4 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 20 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\U 1-K00.dwg

    004C

    0

    AHU 1 BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    AE 1-2 2 EXISTING N/A N/A N/A

    CP 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    CS 1 1 H606 VERIS 1006cut016 Current Switch,Split-Core,Adj,N.C.,R1

    D SEE DAMPER SUBMITTAL

    RE 5 1 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAM2030.250 SIEMENS 149916 DUCT AV SNSR, NTC 10K OHM TYP2, 8 FT LG

    TTE 2-3 2 QAM2030.020 SIEMENS 149915 DUCT PT SNSR, NTC 10K OHM TYP2, 8 IN LG

    TTE 4 1 587-680 SIEMENS 587908 RAPTOR RS SENSING ONLY

    V SEE VALVE SUBMITTAL

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Unoccupied Mode:

    Unoccupied mode shall be enabled when TOD schedule is inactive. The unit shall be disabled. The unit shall cycle

    ON to maintain unoccupied space heating setpoint of 16 Deg C (Operator adjustable). During unit cycling, Outdoor Air

    Damper minimum position is 0%.

    Occupied Mode:

    Occupied mode shall maintain a space temp set point of 22 Deg C (Operator Adjustable).

    Zone Optimal Start:

    The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied

    warm-up period while still achieving comfort conditions bythe start of scheduled occupied period.

    Heating:

    The controller shall measure the space temperature and modulate the heating coil valve to maintain heating set

    point.

    Heating shall be enabled whenever:

    The zone temperature is below heating set point.

    AND the supply fan status is on.

    Cooling:

    The controller shall measure the average space temperature and modulate the cooling coil valve to maintain the

    cooling set point.

    Cooling shall been abled whenever:

    The zone temperature is above cooling set point.

    AND the supply fan status is on.

    Supply Fan Control:

    The supply fan shall run anytime the unit is commandedtorun, unless shutdown on safeties.

    Economizer:

    The controller shall measure the mixed air temperature and modulate the economizer dampers in sequence to

    maintain the mixed air set point of not less than 10c. The economizer is to act as the first stage of cooling.

    The economizer shall be enabled whenever:

    Outside air temperature is less than 22 Deg C.

    The economizer shall close whenever:

    Mixed air temperature drops below 10 Deg C (adjustable).

    OR on loss of supply fan status.

    Alarms shall be provided as follows:

    Low Zone Temp: during occupied mode, if the zone temperature is less than the heating setpoint by 7 Deg C.

    High Supply Air Temperature: during occupied mode, if the supply air temperature is greater than 49 Deg C.

    Low Supply Air Temperature: during occupied mode, if the supply air temperature is less than 11 Deg C.

    4 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 21 of 82

  • RA

    OA SACCC

    H

    AHU 2A SYSTEM FLOW DIAGRAM

    006A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 14 03/25/08

    1

    TTE 1

    -40/240 %FBLD91.A02A.MAT

    AHU2A:0.0.1

    -

    DETAIL V

    TTE 3

    -40/240 %FBLD91.A02A.RAT

    AHU2A:0.0.2

    -

    DETAIL V

    TTE 2

    -40/240 %FBLD91.A02A.SAT

    AHU2A:0.0.5

    -

    DETAIL V

    SQB

    0

    10

    AE 2

    6/9 VOLTSBLD91.A02A.MAD

    AHU2A:0.0.19

    -

    DETAIL I

    SQB

    0

    10

    AE 1

    6/9 VOLTS-

    POWERS

    TTE 4

    13/35 deg CBLD91.A02A.RMT

    AHU2A:0.0.3

    -

    DETAIL V

    HWR

    HWS

    CHWS

    CHWR

    V 1

    0/10 VOLTSBLD91.A02A.CCV

    AHU2A:0.0.17

    -

    DETAIL I

    V 2

    0/10 VOLTSBLD91.A02A.HCV

    AHU2A:0.0.18

    -

    DETAIL I

    SPACE SENSOR

    XFMR 1

    100 VA

    -

    INSTALLATION NOTES:

    COMPONENT PANEL_

    2

    3

    1

    RE 5

    BLD91.A02A.SAF (On/Off)AHU2A:0.0.20

    DETAIL B

    -

    CS 1

    BLD91.A02A.SAF (Proof)AHU2A:0.0.4

    DETAIL E

    -

    1

    SF -1

    CP 1-

    4

    SEE WIRING DETAIL ON ELECTRICAL DRAWING ?.

    COMPONENT PANEL.

    CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

    PROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING ?

    BY DIVISION 16.

    SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

    1

    2

    D 2

    NC

    -

    D 1

    NC

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 005A

    0

    AHU 2A MECH

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    AHU3 AHU3 AHU3

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    1 5/26/2014 CS AS BUILT DRAWING

    2 5/26/2014 CS AS-BUILT DRAWING

    BLD91.A02A.LTD

    AHU2A:0.0.6

    DETAIL E/00

    Addendum No. 3 for RFP 9118-15-5083 - Page 22 of 82

  • 102 103

    BLK

    WHT

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    COMPONENT PANEL / POWERFIELD PANEL FIELD WIRING STARTER WIRING

    WHT

    BLK

    202 204

    120VAC

    1

    1

    120VAC

    204203

    MIXED AIR

    DISCH AIR

    RETURN AIR

    SPACE

    LOCATION: BILLIARD ROOMAHU SYSTEM - WIRING DIAGRAM

    005B LOCATION: 91 PORT UNION COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 5 03/25/08

    V-1

    COOLING

    Y

    M

    GO

    G

    TTE-1

    TTE-2

    TTE-3

    POWERS

    TTE-4

    AE-1

    RA DAMPER

    8(Y)

    2(GO)

    1(G)

    AE-2

    OA DAMPER

    8(Y)

    2(GO)

    1(G)

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    PNL-__

    103102

    BLD91.A02A.MAD

    AHU2A:0.0.19

    MIXED AIR DAMPER SIGNAL

    57

    56

    BLD91.A02A.MAT

    AHU2A:0.0.1

    MIXED AIR TEMP

    25

    26

    BLD91.A02A.CCV

    AHU2A:0.0.17

    COOLING COIL VALVE

    53

    54

    BLD91.A02A.SAT

    AHU2A:0.0.5

    SUPPLY AIR TEMP

    31

    32

    BLD91.A02A.RAT

    AHU2A:0.0.2

    RETURN AIR TEMP

    27

    26

    BLD91.A02A.RMT

    AHU2A:0.0.3

    ROOM TEMP SENSOR

    28

    29

    BLD91.A02A.SAF (PROOF)AHU2A:0.0.4

    SUPPLY AIR FAN (PROOF)

    30

    29

    103102

    201

    BLD91.A02A.SAF

    AHU2A:0.0.20

    SUPPLY AIR FAN (ON/OFF)

    3.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIREMENTS OF

    RE2-2

    109

    FASD-2SD-1

    2

    NEAR STARTER.

    RELAYS LOCATED

    START/STOP

    SHUT DOWN

    SAFETY

    SAME CIRCUIT AS FIELD PANEL.

    120VAC POWER TO XFMR FROM1

    120VAC

    INSTALLATION NOTES:

    SMOKE AND FIRE ALARM SHUTDOWN2

    OL'S

    SUPPLY FAN STARTER

    ᅯᅫᅱ

    C

    120VAC

    1

    201204

    204

    204

    108

    WIRING BY DIV 16.

    AND SMOKE DETECTOR POWER SUPPLY

    BLD91.A02A.HCV

    AHU2A:0.0.18

    HEATING COIL VALVE

    55

    56 BLK

    WHT

    BLK

    WHT

    V-2

    HEATING

    Y

    M

    GO

    G

    M

    L3L2L1

    CS-1

    RE-4

    C

    -

    RE-5

    C

    -

    VA

    24 VAC

    XFMR-1

    100

    VA

    24 VAC

    XFMR-2

    100

    VA

    24 VAC

    XFMR-3

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    005BAHU 2A ELEC

    0

    23_7232_91Port_UnionCITY OF TORONTO PARKS & REC

    BLD91.A02A.MADRST

    AHU2A:0.0.21

    MAD ISOLATION (ON/OFF)

    8

    7

    9

    BLD91.A02A.LTD

    AHU2A:0.0.6

    FREEZE STAT

    33

    32 AHU1 LTD

    AH2A AHU2A AHU2A

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 23 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\U 2A-K00.dwg

    005C

    0

    AHU 2A BOM/SEQUENCE

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    AE 1-2 2 EXISTING N/A N/A N/A

    CP 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    CS 1 1 H606 VERIS 1006cut016 Current Switch,Split-Core,Adj,N.C.,R1

    D SEE DAMPER SUBMITTAL

    RE 5 1 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAM2030.250 SIEMENS 149916 DUCT AV SNSR, NTC 10K OHM TYP2, 8 FT LG

    TTE 2-3 2 QAM2030.020 SIEMENS 149915 DUCT PT SNSR, NTC 10K OHM TYP2, 8 IN LG

    TTE 4 1 587-680 SIEMENS 587908 RAPTOR RS SENSING ONLY

    V SEE VALVE SUBMITTAL

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Unoccupied Mode:

    Unoccupied mode shall be enabled when TOD schedule is inactive. The unit shall be disabled. The unit shall cycle

    ON to maintain unoccupied space heating setpoint of 16 Deg C (Operator adjustable). During unit cycling, Outdoor Air

    Damper minimum position is 0%.

    Occupied Mode:

    Occupied mode shall maintain a space temp set point of 22 Deg C (Operator Adjustable).

    Zone Optimal Start:

    The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied

    warm-up period while still achieving comfort conditions bythe start of scheduled occupied period.

    Heating:

    The controller shall measure the space temperature and modulate the heating coil valve to maintain heating set

    point.

    Heating shall be enabled whenever:

    The zone temperature is below heating set point.

    AND the supply fan status is on.

    Cooling:

    The controller shall measure the average space temperature and modulate the cooling coil valve to maintain the

    cooling set point.

    Cooling shall been abled whenever:

    The zone temperature is above cooling set point.

    AND the supply fan status is on.

    Supply Fan Control:

    The supply fan shall run anytime the unit is commandedtorun, unless shutdown on safeties.

    Economizer:

    The controller shall measure the mixed air temperature and modulate the economizer dampers in sequence to

    maintain the mixed air set point of not less than 10c. The economizer is to act as the first stage of cooling.

    The economizer shall be enabled whenever:

    Outside air temperature is less than 22 Deg C.

    The economizer shall close whenever:

    Mixed air temperature drops below 10 Deg C (adjustable).

    OR on loss of supply fan status.

    Alarms shall be provided as follows:

    Low Zone Temp: during occupied mode, if the zone temperature is less than the heating setpoint by 7 Deg C.

    High Supply Air Temperature: during occupied mode, if the supply air temperature is greater than 49 Deg C.

    Low Supply Air Temperature: during occupied mode, if the supply air temperature is less than 11 Deg C.

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 24 of 82

  • RA

    OA SACCC

    H

    1

    TTE 1

    -40/240 %FBLD91.A02B.MAT

    AHU2B:0.0.1

    -

    DETAIL V

    TTE 3

    -40/240 %FBLD91.A02B.RAT

    AHU2B:0.0.2

    -

    DETAIL V

    TTE 2

    -40/240 %FBLD91.A02B.SAT

    AHU2B:0.0.5

    -

    DETAIL V

    SQB

    0

    10

    AE 2

    6/9 VOLTSBLD91.A02B.MAD

    AHU2B:0.0.19

    -

    DETAIL I

    SQB

    0

    10

    AE 1

    6/9 VOLTS-

    POWERS

    TTE 4

    13/35 deg CBLD91.A02B.RMT

    AHU2B:0.0.3

    -

    DETAIL V

    HWR

    HWS

    CHWS

    CHWR

    V 1

    6/9 VOLTSBLD91.A02B.CCV

    AHU2B:0.0.17

    -

    DETAIL I

    V 2

    6/9 VOLTSBLD91.A02B.HCV

    AHU2B:0.0.18

    -

    DETAIL I

    SPACE SENSOR

    XFMR 1

    100 VA

    -

    INSTALLATION NOTES:

    COMPONENT PANEL_

    2

    3

    1

    RE 5

    BLD91.A02B.SAF (On/Off)AHU2B:0.0.20

    DETAIL B

    -

    CS 1

    BLD91.A02B.SAF (Proof)AHU2B:0.0.4

    DETAIL E

    -

    1

    SF -1

    CP 1-

    4

    SEE WIRING DETAIL ON ELECTRICAL DRAWING ?.

    COMPONENT PANEL.

    CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

    PROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING ?

    BY DIVISION 16.

    SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

    1

    2

    D 2

    NC

    -

    D 1

    NC

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 006A

    0

    AHU 2B MECH

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    1 5/26/2014 CS AS-BUILT DRAWING

    BLD91.A02B.LTD

    AHU2B:0.0.6

    DETAIL E/00

    AH2B AHU2B AHU2B

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    Addendum No. 3 for RFP 9118-15-5083 - Page 25 of 82

  • 102 103

    BLK

    WHT

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    COMPONENT PANEL / POWERFIELD PANEL FIELD WIRING STARTER WIRING

    WHT

    BLK

    202 204

    120VAC

    1

    1

    120VAC

    204203

    MIXED AIR

    DISCH AIR

    RETURN AIR

    SPACE

    LOCATION: ACTIVITY RM BAHU SYSTEM - WIRING DIAGRAM

    006B LOCATION: 91 PORT UNION COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 5 03/25/08

    V-1

    COOLING

    Y

    M

    GO

    G

    TTE-1

    TTE-2

    TTE-3

    POWERS

    TTE-4

    AE-1

    RA DAMPER

    8(Y)

    2(GO)

    1(G)

    AE-2

    OA DAMPER

    8(Y)

    2(GO)

    1(G)

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    PNL-__

    103102

    BLD91.A02B.MAD

    AHU2B:0.0.19

    MIXED AIR DAMPER SIGNAL

    57

    56

    BLD91.A02B.MAT

    AHU2B:0.0.1

    MIXED AIR TEMP

    25

    26

    BLD91.A02B.CCV

    AHU2B:0.0.17

    53

    54

    BLD91.A02B.SAT

    AHU2B:0.0.5

    SUPPLY AIR TEMP

    31

    32

    BLD91.A02B.RAT

    AHU2B:0.0.2

    RETURN AIR TEMP

    27

    26

    BLD91.A02B.RMT

    AHU2B:0.0.3

    ROOM TEMP SENSOR

    28

    29

    BLD91.A02B.SAF (PROOF)AHU2B:0.0.4

    SUPPLY AIR FAN (PRFON)

    30

    29

    103102

    201

    BLD91.A02B.SAF

    AHU2B:0.0.20

    SUPPLY FAN (ON/OFF)

    3.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIREMENTS OF

    RE2-2

    109

    FASD-2SD-1

    2

    NEAR STARTER.

    RELAYS LOCATED

    START/STOP

    SHUT DOWN

    SAFETY

    SAME CIRCUIT AS FIELD PANEL.

    120VAC POWER TO XFMR FROM1

    120VAC

    INSTALLATION NOTES:

    SMOKE AND FIRE ALARM SHUTDOWN2

    OL'S

    SUPPLY FAN STARTER

    ᅯᅫᅱ

    C

    120VAC

    1

    201204

    204

    204

    108

    WIRING BY DIV 16.

    AND SMOKE DETECTOR POWER SUPPLY

    BLD91.A02B.HCV

    AHU2B:0.0.18

    55

    56 BLK

    WHT

    BLK

    WHT

    V-2

    HEATING

    Y

    M

    GO

    G

    M

    L3L2L1

    CS-1

    RE-4

    C

    -

    RE-5

    C

    -

    VA

    24 VAC

    XFMR-1

    100

    VA

    24 VAC

    XFMR-2

    100

    VA

    24 VAC

    XFMR-3

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group All Rights Reserved1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    C:\Jobs\23_7232_91Port_Union\U 2BA.dwg

    006BAHU 2B ELEC

    0

    23_7232_91Port_UnionCITY OF TORONTO PARKS & REC

    AHU3 AHU3 AHU3

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    BLD91.A02B.MADRST

    AHU2B:0.0.21

    MAD ISOLATION (ON/OFF)

    8

    7

    9

    BLD91.A02B.LTD

    AHU1:0.0.6

    FREEZE STAT

    33

    32 AHU1 LTD

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 26 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\U 2B-K00.dwg

    006C

    0

    AHU 2B BOM/SEQUENCE

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    AE 1-2 2 EXISTING N/A N/A N/A

    CP 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    CS 1 1 H606 VERIS 1006cut016 Current Switch,Split-Core,Adj,N.C.,R1

    D SEE DAMPER SUBMITTAL

    RE 5 1 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAM2030.250 SIEMENS 149916 DUCT AV SNSR, NTC 10K OHM TYP2, 8 FT LG

    TTE 2-3 2 QAM2030.020 SIEMENS 149915 DUCT PT SNSR, NTC 10K OHM TYP2, 8 IN LG

    TTE 4 1 587-680 SIEMENS 587908 RAPTOR RS SENSING ONLY

    V SEE VALVE SUBMITTAL

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Unoccupied Mode:

    Unoccupied mode shall be enabled when TOD schedule is inactive. The unit shall be disabled. The unit shall cycle

    ON to maintain unoccupied space heating setpoint of 16 Deg C (Operator adjustable). During unit cycling, Outdoor Air

    Damper minimum position is 0%.

    Occupied Mode:

    Occupied mode shall maintain a space temp set point of 22 Deg C (Operator Adjustable).

    Zone Optimal Start:

    The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied

    warm-up period while still achieving comfort conditions bythe start of scheduled occupied period.

    Heating:

    The controller shall measure the space temperature and modulate the heating coil valve to maintain heating set

    point.

    Heating shall be enabled whenever:

    The zone temperature is below heating set point.

    AND the supply fan status is on.

    Cooling:

    The controller shall measure the average space temperature and modulate the cooling coil valve to maintain the

    cooling set point.

    Cooling shall been abled whenever:

    The zone temperature is above cooling set point.

    AND the supply fan status is on.

    Supply Fan Control:

    The supply fan shall run anytime the unit is commandedtorun, unless shutdown on safeties.

    Economizer:

    The controller shall measure the mixed air temperature and modulate the economizer dampers in sequence to

    maintain the mixed air set point of not less than 10c. The economizer is to act as the first stage of cooling.

    The economizer shall be enabled whenever:

    Outside air temperature is less than 22 Deg C.

    The economizer shall close whenever:

    Mixed air temperature drops below 10 Deg C (adjustable).

    OR on loss of supply fan status.

    Alarms shall be provided as follows:

    Low Zone Temp: during occupied mode, if the zone temperature is less than the heating setpoint by 7 Deg C.

    High Supply Air Temperature: during occupied mode, if the supply air temperature is greater than 49 Deg C.

    Low Supply Air Temperature: during occupied mode, if the supply air temperature is less than 11 Deg C.

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 27 of 82

  • RA

    OA SACCC

    H

    AHU 4 SYSTEM FLOW DIAGRAM

    007A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: LIBRARY

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 14 03/25/08

    1

    TTE 1

    -40/240 %FBLD91.A04.MAT

    0.0.1

    -

    DETAIL V

    TTE 3

    -40/240 %FBLD91.A04.RAT

    0.0.2

    -

    DETAIL V

    TTE 2

    -40/240 %FBLD91.A04.SAT

    0.0.5

    -

    DETAIL V

    SQB

    0

    10

    AE 2

    0/10 VOLTSBLD91.A04.MAD

    0.0.19

    -

    DETAIL I

    SQB

    0

    10

    AE 1

    0/10 VOLTS-

    POWERS

    TTE 4

    13/35 deg CBLD91.A04.RMT

    0.0.3

    -

    DETAIL V

    HWR

    HWS

    CHWS

    CHWR

    V 1

    0/10 VOLTSBLD91.A04.CCV

    0.0.17

    -

    DETAIL I

    V 2

    0/10 VOLTSBLD91.A04.HCV

    0.0.18

    -

    DETAIL I

    SPACE SENSOR

    XFMR 1

    100 VA

    -

    INSTALLATION NOTES:

    COMPONENT PANEL_

    2

    3

    1

    RE 5

    BLD91.A04.SAF (ON/OFF)0.0.20

    DETAIL B

    -

    CS 1

    BLD91.A04.SAF (PROOF)0.0.4

    DETAIL E

    -

    1

    SF-1

    CP 1-

    4

    SEE WIRING DETAIL ON ELECTRICAL DRAWING ?.

    COMPONENT PANEL.

    CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

    PROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING ?

    BY DIVISION 16.

    SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

    1

    2

    D 2

    NC

    -

    D 1

    NC

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group All Rights Reserved

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\JOBS\23_7232_91PORT_UNION\U 4.DWG

    007A

    0

    AHU 4 MECH

    23_7232

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    AHU4 AHU4 AHU4

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    LPS

    HV 1

    0/10 VOLTSBLD91.A04.HUM

    0.0.21

    -

    DETAIL I

    1 5/26/2014 CS AS-BUILT DRAWING

    BLD91.A04.LTD

    AHU4:0.0.6

    DETAIL E/00

    Addendum No. 3 for RFP 9118-15-5083 - Page 28 of 82

  • 102 103

    BLK

    WHT

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    COMPONENT PANEL / POWERFIELD PANEL FIELD WIRING STARTER WIRING

    WHT

    BLK

    202 204

    120VAC

    1

    1

    120VAC

    204203

    MIXED AIR

    DISCH AIR

    RETURN AIR

    SPACE

    LOCATION: LIBRARYAHU SYSTEM - WIRING DIAGRAM

    007B LOCATION: 91 PORT UNION COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 5 03/25/08

    V-1

    COOLING

    Y

    M

    GO

    G

    TTE-1

    TTE-2

    TTE-3

    POWERS

    TTE-4

    AE-1

    RA DAMPER

    8(Y)

    2(GO)

    1(G)

    AE-2

    OA DAMPER

    8(Y)

    2(GO)

    1(G)

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    PNL-__

    103102

    BLD91.A04.MAD

    AHU4:0.0.19

    MIXED AIR DAMPER SIGNAL

    57

    56

    BLD91.A04.MAT

    AHU4:0.0.1

    MIXED AIR TEMP

    25

    26

    BLD91.A04.CCV

    AHU4:0.0.17

    COOLING COIL VALVE

    53

    54

    BLD91.A04.SAT

    AHU4:0.0.5

    SUPPLY AIR TEMP

    31

    32

    BLD91.A04.RAT

    AHU4:0.0.2

    RETURN AIR TEMP

    27

    26

    BLD91.A04.RMT

    AHU4:0.0.3

    ROOM TEMP SENSOR

    28

    29

    BLD91.A04.SAF.PROOF

    0.0.4

    SUPPLY AIR FAN (ON/OFF)

    103102

    201

    BLD91.A04.SAF

    0.0.20

    SUPPLY AIR FAN (ON/OFF)

    3.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIREMENTS OF

    RE2-2

    109

    FASD-2SD-1

    2

    NEAR STARTER.

    RELAYS LOCATED

    START/STOP

    SHUT DOWN

    SAFETY

    SAME CIRCUIT AS FIELD PANEL.

    120VAC POWER TO XFMR FROM1

    120VAC

    INSTALLATION NOTES:

    SMOKE AND FIRE ALARM SHUTDOWN2

    OL'S

    SUPPLY FAN STARTER

    ᅯᅫᅱ

    C

    120VAC

    1

    201204

    204

    204

    108

    WIRING BY DIV 16.

    AND SMOKE DETECTOR POWER SUPPLY

    BLD91.A04.HCV

    AHU4:0.0.18

    COOLING COIL VALVE

    55

    56 BLK

    WHT

    BLK

    WHT

    V-2

    HEATING

    Y

    M

    GO

    G

    M

    L3L2L1

    CS-1

    RE-4

    C

    -

    RE-5

    C

    -

    VA

    24 VAC

    XFMR-1

    100

    VA

    24 VAC

    XFMR-2

    100

    VA

    24 VAC

    XFMR-3

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group ALL RIGHTS RESERVED1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    007BAHU 4 ELEC

    0

    23_7232_91Port_UnionCITY OF TORONTO PARKS & REC

    BLD91.A04.HUM

    AHU4:0.0.21

    HUMIDIFIER ENABLE

    8

    7 BLK

    WHT

    BLK

    WHT

    INPUT

    POWER

    HV-1

    HUMIDITY

    +

    -

    N

    24V

    AHU4 AHU4 AHU4

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    BLD91.A04.MADRST

    AHU4:0.0.21

    MAD ISOLATION (ON/OFF)

    8

    7

    9

    BLD91.A04.LTD

    AHU1:0.0.6

    FREEZE STAT

    33

    32 AHU1 LTD

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 29 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\U 4-K00.dwg

    007C

    0

    AHU 4 BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    AE 1-2 2 EXISTING N/A N/A N/A

    CP 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    CS 1 1 H606 VERIS 1006cut016 Current Switch,Split-Core,Adj,N.C.,R1

    D SEE DAMPER SUBMITTAL

    RE 5 1 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAM2030.250 SIEMENS 149916 DUCT AV SNSR, NTC 10K OHM TYP2, 8 FT LG

    TTE 2-3 2 QAM2030.020 SIEMENS 149915 DUCT PT SNSR, NTC 10K OHM TYP2, 8 IN LG

    TTE 4 1 587-680 SIEMENS 587908 RAPTOR RS SENSING ONLY

    V SEE VALVE SUBMITTAL

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Unoccupied Mode:

    Unoccupied mode shall be enabled when TOD schedule is inactive. The unit shall be disabled. The unit shall cycle

    ON to maintain unoccupied space heating setpoint of 16 Deg C (Operator adjustable). During unit cycling, Outdoor Air

    Damper minimum position is 0%.

    Occupied Mode:

    Occupied mode shall maintain a space temp set point of 22 Deg C (Operator Adjustable).

    Zone Optimal Start:

    The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied

    warm-up period while still achieving comfort conditions bythe start of scheduled occupied period.

    Heating:

    The controller shall measure the space temperature and modulate the heating coil valve to maintain heating set

    point.

    Heating shall be enabled whenever:

    The zone temperature is below heating set point.

    AND the supply fan status is on.

    Cooling:

    The controller shall measure the average space temperature and modulate the cooling coil valve to maintain the

    cooling set point.

    Cooling shall been abled whenever:

    The zone temperature is above cooling set point.

    AND the supply fan status is on.

    Supply Fan Control:

    The supply fan shall run anytime the unit is commandedtorun, unless shutdown on safeties.

    Economizer:

    The controller shall measure the mixed air temperature and modulate the economizer dampers in sequence to

    maintain the mixed air set point of not less than 10c. The economizer is to act as the first stage of cooling.

    The economizer shall be enabled whenever:

    Outside air temperature is less than 22 Deg C.

    The economizer shall close whenever:

    Mixed air temperature drops below 10 Deg C (adjustable).

    OR on loss of supply fan status.

    Humidifier:

    The humidifier is enabled when the supply fan proves on, and the Heating Coil Valve (HCV) position is 5% or

    greater. The humidifier has it's own humidistat, and controls it's own setpoint.

    Alarms shall be provided as follows:

    Low Zone Temp: during occupied mode, if the zone temperature is less than the heating setpoint by 7 Deg C.

    High Supply Air Temperature: during occupied mode, if the supply air temperature is greater than 49 Deg C.

    Low Supply Air Temperature: during occupied mode, if the supply air temperature is less than 11 Deg C.

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 30 of 82

  • RA

    OA SACC

    C

    H

    AHU 5 SYSTEM FLOW DIAGRAM

    008A LOCATION: 91 PORT UNION COMMUNITY CENTRESERVES: LIBRARY MEETING ROOM

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 14 03/25/08

    1

    TTE 1

    -40/240 %FBLD91.A05.MAT

    AHU5:0.0.1

    -

    DETAIL V

    TTE 3

    -40/240 %FBLD91.A05.RAT

    AHU5:0.0.2

    -

    DETAIL V

    TTE 2

    -40/240 %FBLD91.A05.SAT

    AHU5:0.0.5

    -

    DETAIL V

    SQB

    0

    10

    AE 2

    6/9 VOLTSBLD91.A05.MAD

    AHU5:0.0.19

    -

    DETAIL I

    SQB

    0

    10

    AE 1

    6/9 VOLTS-

    POWERS

    TTE 4

    13/35 deg CBLD91.A05.RMT

    AHU5:0.0.3

    -

    DETAIL V

    HWR

    HWS

    CHWS

    CHWR

    V 1

    6/9 VOLTSBLD91.A05.CCV

    AHU5:0.0.17

    -

    DETAIL I

    V 2

    6/9 VOLTSBLD91.A05.HCV

    AHU5:0.0.18

    -

    DETAIL I

    SPACE SENSOR

    XFMR 1

    100 VA

    -

    INSTALLATION NOTES:

    COMPONENT PANEL_

    2

    3

    1

    RE 5

    BLD91.A05.SAF (On/Off)AHU5:0.0.20

    DETAIL B

    -

    CS 1

    BLD91.A05.SAF (Proof)AHU5:0.0.4

    DETAIL E

    -

    1

    SF -1

    CP 1-

    4

    SEE WIRING DETAIL ON ELECTRICAL DRAWING ?.

    COMPONENT PANEL.

    CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

    PROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING ?

    BY DIVISION 16.

    SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

    1

    2

    D 2

    NC

    -

    D 1

    NC

    -

    CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS 008A

    0

    AHU 5 MECH

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    1 5/26/2014 CS AS-BUILT DRAWING

    AHU5 AHU5 AHU5

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    BLD91.A05.LTD

    AHU5:0.0.6

    DETAIL E/00

    Addendum No. 3 for RFP 9118-15-5083 - Page 31 of 82

  • 102 103

    BLK

    WHT

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    COMPONENT PANEL / POWERFIELD PANEL FIELD WIRING STARTER WIRING

    WHT

    BLK

    202 204

    120VAC

    1

    1

    120VAC

    204203

    MIXED AIR

    DISCH AIR

    RETURN AIR

    SPACE

    LOCATION: LIBRARY MTG RMAHU 5 SYSTEM - WIRING DIAGRAM

    008B LOCATION: 91 PORT UNION COMMUNITY CENTRE

    COPYRIGHT 2008 SIEMENS BUILDING TECHNOLOGIES, INC.

    EACVMCHN REV 5 03/25/08

    V-1

    COOLING

    Y

    M

    GO

    G

    TTE-1

    TTE-2

    TTE-3

    POWERS

    TTE-4

    AE-1

    RA DAMPER

    8(Y)

    2(GO)

    1(G)

    AE-2

    OA DAMPER

    8(Y)

    2(GO)

    1(G)

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    WHT

    BLK

    BLK

    WHT

    WHT

    BLK

    PNL-__

    103102

    BLD91.A05.MAD

    AHU5:0.0.19

    MIXED AIR DAMPER SIGNAL

    57

    56

    BLD91.A05.MAT

    AHU5:0.0.1

    MIXED AIR TEMP

    25

    26

    BLD91.A05.CCV

    AHU5:0.0.17

    COOLING COIL VALVE

    53

    54

    BLD91.A05.SAT

    AHU5:0.0.5

    SUPPLY AIR TEMP

    31

    32

    BLD91.A05.RAT

    AHU5:0.0.2

    RETURN AIR TEMP

    27

    26

    BLD91.A05.RMT

    AHU5:0.0.3

    ROOM TEMP SENSOR

    28

    29

    BLD91.A05.SAF (PROOF)AHU5:0.0.4

    SUPPLY AIR FAN (PRFON)

    30

    29

    103102

    201

    BLD91.A05.SAF (ON/OFF)AHU5:0.0.20

    SUPPLY AIR FAN

    5

    4

    6

    3.

    DRAWINGS.

    STANDARD WIRING SPECIFICATIONS

    ALL WIRING TO MEET REQUIREMENTS OF

    RE2-2

    109

    FASD-2SD-1

    2

    NEAR STARTER.

    RELAYS LOCATED

    START/STOP

    SHUT DOWN

    SAFETY

    SAME CIRCUIT AS FIELD PANEL.

    120VAC POWER TO XFMR FROM1

    120VAC

    INSTALLATION NOTES:

    SMOKE AND FIRE ALARM SHUTDOWN2

    OL'S

    SUPPLY FAN STARTER

    ᅯᅫᅱ

    C

    120VAC

    1

    201204

    204

    204

    108

    WIRING BY DIV 16.

    AND SMOKE DETECTOR POWER SUPPLY

    BLD91.A05.HCV

    AHU5:0.0.18

    HEATING COIL VALVE

    55

    56 BLK

    WHT

    BLK

    WHT

    V-2

    HEATING

    Y

    M

    GO

    G

    M

    L3L2L1

    CS-1

    RE-4

    C

    -

    RE-5

    C

    -

    VA

    24 VAC

    XFMR-1

    100

    VA

    24 VAC

    XFMR-2

    100

    VA

    24 VAC

    XFMR-3

    100

    c COPYRIGHT

    ENGINEER DRAFTER CHECKED BY INITIAL RELEASE LAST EDIT DATE

    The State Group All Rights Reserved1994-14

    REVISION HISTORY

    05/27/1402/01/13CSCS

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group

    TORONTO, ON

    C:\JOBS\23_7232_91PORT_UNION\U 5A.DWG

    008BAHU 5 ELEC

    0

    23_7232CITY OF TORONTO PARKS & REC

    AHU5 AHU5 AHU5

    REF# FIELD PANEL NAME FIELD PANEL NODE NAME

    BLD91.A05.MADRST

    AHU5:0.0.21

    MAD ISOLATION (ON/OFF)

    8

    7

    9

    BLD91.A05.LTD

    AHU1:0.0.6

    FREEZE STAT

    33

    32 AHU1 LTD

    1 5/26/2014 CS AS-BUILT DRAWING

    Addendum No. 3 for RFP 9118-15-5083 - Page 32 of 82

  • CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

    c COPYRIGHT

    ENGINEER

    REVISION HISTORY

    1994-14 The State Group ALL RIGHTS RESERVED

    FAX: 905-293-7548

    PHONE: 905-672-2772

    Canada

    Mississauga, ON L4V 1R5

    3206 Orlando Drive

    Division 23

    The State Group05/27/1402/01/13CSCS

    C:\Jobs\23_7232_91Port_Union\U 5-K00.dwg

    008C

    0

    AHU 5 BOM/SEQUENCE

    23_7232_91Port_Union

    TORONTO, ON

    CITY OF TORONTO PARKS & REC

    Control Qty Product Number Manufacturer Document Description

    Device Number

    Field Mounted Devices

    AE 1-2 2 EXISTING N/A N/A N/A

    CP 1 1 PXA-ENC19 SIEMENS 149475 ENCLOSURE ASSY 19"

    CS 1 1 H606 VERIS 1006cut016 Current Switch,Split-Core,Adj,N.C.,R1

    D SEE DAMPER SUBMITTAL

    RE 5 1 RIBU1C FUNCTIONAL DEVICES 1208cut013 RIB 120VAC 24VAC/DC SPDT

    TTE 1 1 QAM2030.250 SIEMENS 149916 DUCT AV SNSR, NTC 10K OHM TYP2, 8 FT LG

    TTE 2-3 2 QAM2030.020 SIEMENS 149915 DUCT PT SNSR, NTC 10K OHM TYP2, 8 IN LG

    TTE 4 1 587-680 SIEMENS 587908 RAPTOR RS SENSING ONLY

    V SEE VALVE SUBMITTAL

    XFMR 1 1 A7F30008355 N/A N/A N/A

    Unoccupied Mode:

    Unoccupied mode shall be enabled when TOD schedule is inactive. The unit shall be disabled. The unit shall cycle

    ON to maintain unoccupied space heating setpoint of 16 Deg C (Operator adjustable). During unit cycling, Outdoor Air

    Damper minimum position is 0%.

    Occupied Mode:

    Occupied mode shall maintain a space temp set point of 22 Deg C (Operator Adjustable).

    Zone Optimal Start:

    The unit shall use an optimal start algorit