the relevance of grid-forming converters and how to …

15
©Fraunhofer ISE/Foto: Guido Kirsch © Fraunhofer ISE THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO TEST THEM Tech Talk and Digital Lab Tour Soenke Rogalla, Rebekka Denninger, Roland Singer Fraunhofer Institute for Solar Energy Systems ISE The Smarter E Industry Days online/Freiburg, 21.07.2021 www.ise.fraunhofer.de

Upload: others

Post on 04-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

©Fraunhofer ISE/Foto: Guido Kirsch

© Fraunhofer ISE

THE RELEVANCE OF GRID-FORMING CONVERTERS

AND HOW TO TEST THEM

Tech Talk and Digital Lab Tour

Soenke Rogalla, Rebekka Denninger, Roland Singer

Fraunhofer Institute for Solar Energy Systems ISE

The Smarter E Industry Days

online/Freiburg, 21.07.2021

www.ise.fraunhofer.de

Page 2: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

2

Motivation

Why Do We Need Grid-Forming Converters?

Page 3: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

3

MotivationTowards 100% Renewable Energy Generation

Source: Energy Charts (www.energy-charts.info)

Share of inverter-connected generation Loss of

conventional power plants

Today: PV+wind regularilyexceed 80 % of generation

Page 4: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

4

"Electronification" of the Power Grids

Estimated installed inverter capacity for generation and storage in the German power grid

Plant type 2020* 2030** 2050***

Photovoltaics 54 GW 200 GW 415 GW

Wind onshore 54.8 GW144 GW 260 GW

Wind offshore 7.7 GW

Large battery storage 0.5 GW84 GW 170 GW

Home storage 0.7 GW

Electrolyzers 0.0 GW 5 GW 75 GW

Total 106 GW 433 GW 970 GW

Inverter capacities will increase4x in the next 10 years / 10x in the next 30 years

Inverters are the technological backbone of the future energygrid!

*) Energy Charts - Installed net capacity for electricity generation in Germany in 2020; Transmission system operators' data on prequalified battery storage for primary control power; Derived from 2018 Annual Report on Storage Monitoring Program & 2019 Update; BSW fact sheet on the German solar power industry 2020; **) Derived from the targets of the German government's Climate Protection Act 2021, National Hydrogen Strategy; ***) Fraunhofer ISE study "Pathways to a Climate Neutral Energy System"; 2020.

Page 5: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

5

Replacement of Synchronous Generators by Inverters

Synchronous Generator:

◼ Inherent voltage source behavior

◼ Inertia for rotating masses

◼ High overload capability

Inverter:

◼ Freely programmable electrical behavior

◼ High dynamic controllable

◼ Hardy overloadable

sou

rce

: G

E P

ow

er

Co

nve

rsio

n

sou

rce

: Si

em

en

s

Page 6: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

6

System Split of the UCTE Grid on 08.01.2021, 14:05hFrequency Reaction

Sources: http://gridradar.net/ , www.energy-charts.info, https://www.entsoe.eu/news/2021/01/15/system-separation-in-the-continental-europe-synchronous-area-on-8-january-2021-update)

High frequency gradients

RoCoF10s = -0.03 Hz/s

(Δf = 0.3 Hz / Δt = 10 s)

Source: entso-e

Source: Gridradar

System Split

Frequency response in the north-west area

Generation Mix UCTE-Grid

08.01.21

14:00

https://transparency.entsoe.eu/

Wind+ PV:

8.9 %

Power imbalance: 6.3 GW

Page 7: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

7

Definition

What Are Grid-Forming Converters?

Page 8: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

8

Control Types of Grid-Coupled Inverters

Current Controlled Voltage Controlled

Grid Following Grid Supporting Grid Leading Grid Forming

Type of SourceConstant current

sourceControlled current source

Fixed voltages

source

Controlled voltage source

behind an impedance

Application Power feed-inPower feed-in and provison

ancillary grid services

Island grids with

single voltage

source

Interconnected systems with

multiple sources

State of the art Required for future grids

Page 9: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

9

MotivationWhat are grid forming inverters (GFC)?

GFC should enable stable grid operation without synchronous generators.

◼ "Grid Forming Converters shall be capable of supporting the operation of the AC power system (from EHV to LV) under normal, disturbed and emergency states without having to rely on capabilities from Synchronous Generators (SGs). This shall include the capabilities for stable operation for the extreme operating case of supplying the complete demand from 100% converter based power sources. "1

[HPoPEIPS Report.]1Source: ENTSO-E, "Technical Report: High Penetration of Power Electronic Interfaced Power Sources and the Potential Contribution of Grid forming Converters," Jan. 2020.

Required feature of GFC according to HPoPEIPS report:

◼ Creating system voltage

◼ Contributing to fault level

◼ Sink for harmonics

◼ Sink for unbalance

◼ Contribution to inertia

◼ Preventing adverse controlinteractions

Page 10: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

10

Conformity Assessment

How Can We Test Grid-Forming Convertes?

Page 11: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

11

Testing Inverters at Fraunhofer ISE‘s Multi-MegawattLabInfrastructure: 110 kV/40 MVA Grid Connection

20 kV cable route

110 kV substation

Multi-Megawatt

Lab

40 MVA transformer

Te

st

Fie

ld A

Te

st

Fie

ld B

Te

st

Fie

ld C

Te

st

Fie

ld D

Te

st

Fie

ld E

1 1 0 k V g r id c o n n e c t io n (N e tz B W )

T r a n s fo r m e r

1 1 0 k V / 2 0 k V

4 0 M V A

2 0 k V c a b le

3 s y s te m s

0 .5 k m

2 0 k V b u s b a r

L a b

Z in k m a tte n s tr .

S u b s ta t io n

V o r d e r m a tte n s tr .

Network level 3

Network level 7

Network level 5

Network level 4

Network level 6

Page 12: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

12

Testing Inverters at Fraunhofer ISE‘s Multi-MegawattLabLaboratory equipment

◼ High-precision, broadband power measurement

◼ PV generator simulator (up to 2,000 V / 1.4 MW)

◼ Bidirectional DC sources (up to 1,000 V / 600 A)

◼ Highly dynamic network simulator with P-HIL functionality (up to 1 MVA)

◼ Climatic chamber (-30 ... +80 °C)

◼ Mobile and stationary FRT test equipment (4.5 MVA / 10 MVA)

◼ R, L and C loads (1.2 MW / 7 MVAr)

◼ Anti-islanding test stand (400 kVA)

PV generator simulator Network simulator / P-HIL

FRT test equipmentClimate chamber

Page 13: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

13

Multi-MegawattLab

Now Join Us On Our Virtual Lab Tour…

Page 14: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

14

Properties of GFC to Be Tested

◼ Structure according to technical propertiesBehavior of GRID FORMING CONVERTER

Voltagesource

behavior

• Stability ofthe voltagesource

• Effectiveinternal impedance

Voltagequality

• Sink forasym-metries

• Sink forharmonics

Inertia

• Inertia constant 𝑯

• Damping 𝑫

Overload and fault

behavior

• Voltagefault

• Phase fault

• Frequencyfault (RoCoF)

• System split

Active/Reactive power control

• Control accuracy

• Settling time

• Frequencycontrol (e.g. LFSM-O/-U)

• Voltagecontrol (e.g. Q(U))

Gridinteraction

• Impedance spectro-scopy

Page 15: THE RELEVANCE OF GRID-FORMING CONVERTERS AND HOW TO …

© Fraunhofer ISE

15

Thank you for your attention!

Fraunhofer Institute for Solar Energy Systems ISE

Soenke Rogalla

www.ise.fraunhofer.de