the development of a roebel cable based 1 mva hts...
TRANSCRIPT
The development of a Roebel cable based
1 MVA HTS transformer
Neil Glasson
11 October 2011
Mike Staines1, Mohinder Pannu2, N. J. Long1, Rod Badcock1, Nathan Allpress1, Logan Ward1
1 Industrial Research Limited, New Zealand2 Wilson Transformer Pty Ltd, Melbourne
Outline
• Introduction
• Design overview
• Roebel cable
• Short circuit fault
• High voltage insulation
• Heat transfer
• Cryostat design
• Summary
Project Partners
www.hts110.co.nz
www.wtc.com.au
www.eteltransformers.co.nz
www.fabrum.co.nz
www.pbworld.com
www.vectorelectricity.co.nz
www.gcsuperconductors.com
www.weltec.ac.nz
www.aut.ac.nz
Design parametersParameter Value
Primary Voltage 11,000 V
Secondary Voltage 415 V
Maximum Operating Temperature 70 K, liquid nitrogen cooling
Target Rating 1 MVA
Primary Connection Delta
Secondary Connection Wye
LV Winding20 turns 15/5 Roebel cable per phase
(20 turn single layer solenoid winding)
LV Rated current 1390 A rms
HV Winding918 turns of 4 mm YBCO wire per phase
(24 double pancakes of 38.25 turns each)
HV Rated current 30 A rms
HV winding
• Uses 4 mm Superpower tape
• I/Ic ~ 25%
• Polyimide wrap insulation
• 24 double pancakes
• No encapsulation due to
concerns of
– Poorer heat transfer
– Voids lowering withstand voltage
– Potential Ic degradation
LV winding
• Single layer solenoid on fibre glass composite former
• Liquid nitrogen in contact with cable surface
• YBCO Roebel Cable
– L = 20 m
– 15/5 (15 strands, 5 mm width)
– Self field Ic ~ 1400 A @ 77 K
• No strand or cable insulation
• Flux deflectors will be added
First transformer cable configured for end-to-end Ic test
Core
• Warm core with
cruciform, 6-stepped
section of high grade
core steel
• No-load loss of about
750 W
– At 20:1 cooling penalty,
cold bore is not feasible
YBCO Roebel Cable
Roebel cable or Continuously Transposed Cable (CTC) is useful for
Forming a high current capacity conductor
100’s to 1000’s of Amps (even 10,000s at low T)
Reducing AC losses
rule of thumb – magnetisation losses scale with strand width
Strands wound together and geometric parameters
Roebel strand
Cables are labelled with the convention
# of strands / strand width
We are making two designs 15/5 and 10/2
Roebel Cable ManufacturePunch tool and
frame
Tape de-spool
Tape re-spool
Control
systems
Set-up for automated
multi-strand Roebel
strand production.
(a)
(b)
(c)
(d)
Formation of Roebel punched strands in 40 mm and 12
mm wide feedstock material.
(a) 4 x 5 mm strands in 40 mm wide material,
(b) 1 x 5 mm wide strand in 12 mm wide material,
(c) 10 x 2 mm strands in 40 mm wide material,
(d) 3 x 2 mm wide strands in 12 mm wide material.
Punching
WindingAutomated planetary wind system for
15/5 cable
Capable of winding several hundred
continuous metres of cable.
Wire qualification
0 10 20 30 40 500.90
0.92
0.94
0.96
0.98
1.00
Co
rre
latio
n
Position (m)
Wire 2
22 )()(
))((),(
yyxx
yyxxYXCorrel
For Roebel we require 2D uniformity
- Scan wire magnetically (penetrated
or remnant field)
- Quantify uniformity using statistical
correlation with an ideal magnetic
profile
Correlation along a
length of YBCO wire, a
minimum Correl can be
specified for input wire
Where |Correl | ≤ 1 X is a dataset representing calculated field
Y{y1…yj} is magnetic data across tape
0.000 T
200mm
(a)(a)
0.023 T
(b)
We use continuous scanning of the Remnant
magnetic field to assess tape quality (a) tape
with a known defect, and (b) tape with only
small scale variability.
0 2 4 6 8 10 120.010
0.015
0.020
0.025
0.030
0.035
0.040 cor_0.99
cor_0.90
cor_0.75
Fie
ld (
T)
Position (mm)
Example Profiles
Some wire is extremely good !
Roebel cable performance
• Measured end-to-end Ic of
cable is 1400 A DC @ 77 K.
• Design calls for 1390 A rms
= 1970 A peak.
• Ic tests on strand samples at
70 K and subsequent
analysis predicts 2500 A
cable Ic. Ipeak/Ic = 0.79
• This is yet to be confirmed
by experiment on a cable at
70 K.
Use of load line method to predict cable critical current
Described by Staines et al, The development of a Roebel cable
based 1 MVA HTS transformer, to be published in Supercond. Sci. Technol. 24 (2011)
Short circuit fault handling
• 2 second short circuit withstand is a common requirement of conventional transformer standards.
• What is a realistic target for HTS?– HTS lacks the resistive conductor cross sectional area to carry a
short circuit for 2 seconds. What is a realistic short circuit duration for an HTS transformer?
• Determine fault current limiting performance.– HTS under short circuit exhibits highly non-linear response – how will
this limit fault current?
• Cable strand has exposed cut edges.– Roebel strand is punched – exposing edges of conductor. Does this
pose a risk of conductor damage due to ingress of LN2 and then subsequent heating in a short circuit?
Short circuit simulation
• Adiabatic model – assumes no heat transfer from the
conductor into liquid nitrogen.
• Assuming instantaneous shift of current into 40 micron
thickness of copper (20 micron each side,
Ω= 12.5 x 10-3 / m per strand @ 77 K).
• Simulation incorporates temperature dependence of
both resistance and thermal capacity of the conductor.
Simulation output
• LV winding will reach
350 K at t = 200 ms
• Impedance doubles
from 0.05 pu to 0.1 pu
initially then up to 0.5 pu
over 200ms (due to change
in resistance as
temperature increases).
-0.05 0 0.05 0.1 0.15 0.2 0.25 0.350
100
150
200
250
300
350
400
450
Tp, T
s vs. Time
Time (s)T
p,
Ts (
K)
TP
Ts
Tp=Temperature of primary windingTs= Temperature of secondary winding
Simulation output
• Fault limited peak
current = 14 kA
(about 35% of the peak
that would occur if
limited only by the 0.05
pu leakage reactance).
pu = per unit, actual value divided by base value.
Cable will offer significant
current limiting during a
short circuit fault.
V2F
V2E
V2D
V2C
V2B
V2A
+ve Terminal
-ve Terminal
Current Shunt
V1
Short circuit strand testing
• 200 ms DC pulse, peaking
at >15 V/m in strand
(transformer short circuit
voltage = 12 V/m).
• T increased to 300 K
in 60 ms
• There was no damage
(no change in Ic).
• Repeat test after 3 week
soak in LN2.
Conclusion – 200 ms duration short circuit is OK and
there is no evidence of damage due to nitrogen ingress
into the exposed cut edge of the cable strands.
Impulse response in HV winding
From VOLNAProprietary modelling software – modelling response to standard 95 kV impulse
21 kV peak voltage
High voltage insulation
* Guide for the statistical analysis of
electrical insulation breakdown data
• 95 kV impulse response modelling
– HV winding must withstand 550 V from turn-to-turn.
(21 kV / 38 turns per double pancake)
– Commercial 25 micron polyimide wrapped insulation was
tested to confirm suitability.
• Two wrapped strands held
together and stressed
until breakdown @ 77 K.
• 20 tests analysed according
to IEC 62539*
• Insulation will survive 2 kV.
Heat transfer experiment
• Fix power dissipation in strand and measured
temperature rise of cable winding in LN2
• Used conductor with Tc < 65 K. Copper layer used as
both resistive heater and temperature sensor.
• Tested at 68 K and 77 K, both at atmospheric pressure.
Typical heat transfer regimes
Van SciverHelium Cryogenics
Note: hysteresis in transitions from one regime to the other and the shape of transition from convection to nucleate.
Heat transfer resultsHeat Transfer - Dependence on Bath Temperature
0.001
0.01
0.1
1
10
0.01 0.1 1 10
Conductor Temperature Rise, dT [K]
Po
we
r D
issip
ate
d [
W/m
]
77K Outer
77K Middle
77K Inner
Subcooled Outer
Subcooled Middle
Subcooled Inner
Assume 1 W/m of strand heating due to AC loss.
Sub cooling necessary to avoid nucleate boiling.
Convective cooling keeps T < 3 K.
Location of strand has minimal impact.
3
Convectiveheat transfer
Nucleate boiling
Sub cooled results are at 68 K and atmospheric pressure.Inner, middle and outer refer to position in Roebel cable strand stack –inner being against the winding former, outer being directly exposed to liquid nitrogen.
Desired conditions
inside the transformer cryostat
• The windings must be held in the temperature range
65K to 70K in order to achieve the required
performance of the superconducting cable.
• It is desirable to ensure that the evolution of gas in the
windings is minimized. Gas bubbles degrade the
dielectric performance of the LN2 as well as risking an
accumulation of gas that might thermally insulate
regions of the windings and give rise to hot spots.
S.M.Baek et al, Electrical Breakdown Properties of Liquid Nitrogen for Electrical Insulation Design of Pancake Coil Type HTS Transformer. IEEE Trans. Appl. Supercond. Vol 13, No.2, June 2003
Nitrogen phase diagram
Temperaturerange
Max. pressure
Vapour and liquid only co-exist on the saturation line
Operation at elevated pressure allows significant temperature increase before phase change.
Atmospheric pressure
Operation heremakes pressurevessel design easier
Cryostat layout• Common cryostat for
all three phases is best
– Smaller footprint and reduced heat load due to
fewer electrical bushings and reduced shell area.
– Simplified nitrogen circulation system – only one
inlet and one outlet required.
• Three individual cryostats - easiest to
manufacture
– Cryostat pressure design is easier
– Less risk with a simple cylindrical structure
• Compromise with three individual
eccentric cryostats
– Simple cylindrical shells
– Reduced transformer length and nitrogen volume
X
1.3 X
1.5 X
Cryostat lid arrangement
Gas in equilibrium due to temperature profile through foam
Liquid return
Electrical bushing
Bulk liquid at 65K – 70K
Foam insulation plug
Cryostat work in progress
Cryostat cold shell test vessel
Single phase cryostat base cold shell and mould
www.fabrum.co.nz
Summary
• Roebel cable described – high current capacity/low AC loss. Tests and analysis predict cable Ic of 2500 A at 70 K.
• Short circuit fault across the Roebel cable winding can be tolerated if disconnected within 200 ms.
• Standard copper stabilizer provides significant fault current limiting - Simulation predicts short circuit fault limited to 35% of the prospective fault current
• Standard 25 micron spiral wrapped polyimide insulation will withstand 2 kV turn-to-turn.
• 1 W/m continuous dissipation in sub-cooled LN2 will be below nucleate boiling regime.
• Cable temperature will be up to 3 K warmer than bulk LN2.
Summary cont...
• Cryostat design discussed. The target normal operating
temperature in the cryostat is in the range 65 K to 70 K.
• There is benefit in operating cryostats at elevated pressure.
• A foam plug beneath the lid will allow operation at elevated
pressure while maintaining a gas/liquid transition at some
point between the lid and the bulk liquid region.