teste de placas graco.pdf
TRANSCRIPT
-
7/26/2019 teste de placas graco.pdf
1/107
Rev. N 10/11 /07
Electrical and Mechanical Repair Tips
WARNINGThis manual should only be used
by a qualified Service Technician.
For Contractor Sprayers
-
-
Black
Red
Yel
Yel
3.00
First choice whenquality counts.
-
7/26/2019 teste de placas graco.pdf
2/107
Table of Contents
Basic meter terminology and testing procedures...............................................................................................5-11
Error Code Chart .............................................................................................................................................12-28
Brushless type motor test Ultra-Max IIs ........................................................................................................ 20,21
Brush type motor test............................................................................................................................................ 22
Electric Sprayers
241989 Control board (190ES,SPX, 295ST):
Motor will not start ............................................................................................................................. 31,32
Motor Test ............................................................................................................................................... 22
Motor will not shut off............................................................................................................................ 29
245892 Control board (190ES, SP, SPX, ST, STX):
Motor will not start ............................................................................................................................. 33,34
Motor Test ............................................................................................................................................... 22
Motor will not shut off............................................................................................................................ 29
253118 Control Board (190ES, Models 232900F, 232901E, 233797E, 233815E)
Motor will not start ............................................................................................................................. 35,36
Motor Test ............................................................................................................................................... 22 Motor will not shut off............................................................................................................................ 29
249052 C (390 , Performance 390, Nova 390 ):
Motor will not run .............................................................................................................................. 37,38
Motor test ............................................................................................................................................ .....22
Motor will not shut off............................................................................................................................ 39
235707, 235008 Control Board (390ST, 390STS, 395ST, 450ST, 455ST, Duron 390, 395, 495, Nova SP,
SPX):
Motor will not run ................................................................................................................................... 40
Motor test ................................................................................................................................................ 41
Motor will not shut off............................................................................................................................ 42
241990 Control Board (395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super):
Motor will not run .............................................................................................................................. 43,44
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
246379 Control Board (Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595, Performance Max
395/495/595, ST Max 395/495/595):
Motor will not run .............................................................................................................................. 45,46
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
287909 Control Board (490II, 495II, 595II):
Motor will not run .............................................................................................................................. 47,48
Motor test ........................................................................................................................................... 20,21
Motor will not shut off............................................................................................................................ 29237659 Control Board (Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600):
Motor will not run .............................................................................................................................. 49,50
Motor test ................................................................................................................................................ 22
Motor will not shut off ............................................................................................................... 29240168 Control Board (695,795,1095):
Motor will not run .............................................................................................................................. 51,52
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
-
7/26/2019 teste de placas graco.pdf
3/107
244237 Control Board (695,795,1095):
Motor will not run .............................................................................................................................. 53,54
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
287247,287941 Control Board (695II, 795II, 1095II, 1595II, MarkIV, MarkV):
Motor will not run .............................................................................................................................. 55,56
Motor test ........................................................................................................................................... 20,21
Motor will not shut off............................................................................................................................ 29
244232 Control Board (1595 Mark V):
Motor will not run .............................................................................................................................. 57,58
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
239750,239751 Control board located under sprayer (1500,1595, Mark V):
Motor will not run ......................................................................................................................... 59,60,61
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 29
236563 Control Board, Retrofit Kit 236974 (1000,900,750 and 500, 590,700 updated control boxes)
Motor will not run .............................................................................................................................. 62,63
Motor test ................................................................................................................................................ 22
Motor will not shut off............................................................................................................................ 64
Electr ic Motor Kit for Convert ible Sprayers
236528 Control Board (GM 5000):
Motor will not run .............................................................................................................................. 65,66
236528 Control Board (GMAX 5900):
Motor will not run .............................................................................................................................. 67,68
Motor runs, no AC output to sprayer control board. .......................................................................... 69,70
246129 & 246125 Control Board (GH 200/230/300 Convertible Sprayer):
Motor will not run ................................................................................................................................... 71
GasPoweredSprayers
238672 Control Box (GM3000):
Fluid Pump will not run...................................................................................................................... 72,73
Fluid Pump will not shut off.................................................................................................................... 74
287486 Control Board (GMAX Sprayers 3400):
Fluid Pump will not run...................................................................................................................... 75,76
Fluid Pump will not stop pumping .......................................................................................................... 30
239056, Retrofit Kit 239693, 239266, 236974 (GM Sprayers 3500,3012,5000,7000):
Fluid Pump will not run...................................................................................................................... 77,78
Fluid Pump will not shut off.................................................................................................................... 79
220974, 221033, 222369 Pressure Control With Bourdon Tube (GM Sprayers 3500,5000):
Fluid Pump will not run...................................................................................................................... 80,81
Fluid Pump will not shut off.................................................................................................................... 82
241093 Control Board (Non-Display), (3900,5900,7900):
Fluid Pump will not run................................................................................................................. 83,84,85
Fluid Pump will not stop pumping .......................................................................................................... 30
245394 Control Board (Display), (3900,5900,7900):
Fluid Pump will not run...................................................................................................................... 86,87
Fluid Pump will not stop pumping .......................................................................................................... 30
-
7/26/2019 teste de placas graco.pdf
4/107
287516 Control Board: GMax II Sprayers (Display and Non-Display), (3900,5900,7900):
Fluid Pump will not run...................................................................................................................... 88,89
Fluid Pump will not stop pumping .......................................................................................................... 30
237373 Control Board, Retrofit Kit 237669 (GM 10,00, GMax 10,000)
Fluid Pump will not run...................................................................................................................... 90,91
Fluid Pump will not stop pumping .......................................................................................................... 92
HydraMax Sprayers:
Operational Overview ............................................................................................................................. 93
Piston rod stuck in the up position........................................................................................................... 94
Piston rod stuck in the down position...................................................................................................... 95
Control Board Off.................................................................................................................................... 96
LineStripers
238672 Control Board (GM3000 LineLazer):
Fluid Pump will not run...................................................................................................................... 72,73
Fluid Pump will not stop pumping .......................................................................................................... 74
287486 Control Board (LineLazer 3400):
Fluid Pump will not run...................................................................................................................... 75,76
Fluid Pump will not stop pumping .......................................................................................................... 30220974, 221033, 222369 Pressure Control With Bourdon Tube (GM LineLazer 3500,5000):
Fluid Pump will not run...................................................................................................................... 80,81
Fluid Pump will not shut off.................................................................................................................... 82
241543 Updated Control Board (GM LineLazer 3500,5000)
Fluid Pump will not run................................................................................................................ 97,98,99
Fluid Pump will not shut off.................................................................................................................. 30
241093 Control Board LineLazer (3900II, 5900II)
Fluid Pump will not run................................................................................................................. 83,84,85
Fluid Pump will not stop pumping .......................................................................................................... 30
245512 Control Board(LineLazer 3900III, 5900III):
Fluid Pump will not run.................................................................................................................. 100.101
Fluid Pump will not stop pumping .......................................................................................................... 30287689 Control Board(LineLazer 3900IV, 5900IV):
Fluid Pump will not run.................................................................................................................. 102,103
Fluid Pump will not stop pumping .......................................................................................................... 30
Engine Generator Test ........................................................................................................................... 104
Sensor Test ............................................................................................................................................ 105
Light Kit Troubleshooting..................................................................................................................... 106
4
-
7/26/2019 teste de placas graco.pdf
5/107
BASIC ELECTRICAL TERMINOLOGYIn any discussion of electricity, there are three basic terms you will need to understand.
CURRENT
VOLTAGE
RESISTANCE
CURRENT:
Current is the movement of the electrical charge.Current Flows through the wires from the power source to the load.
Current is measured in AMPERES (AMPS, A or I). See Figure 1.
NOTE: Meter is only clamped around one wire.
VOLTAGE:
Voltage is the force that causes current to flow in a circuit.
Voltage is measured in VOLTS (V or E). See Figure 2.
FIGURE 1
FIGURE 2
ON/OFF
Switch
Ref 58
PowerPlug
Red (+)
White
Black
Green
Black ()
Black
from Motor
ON/OFF
Switch
Ref 58
Power
Plug
Potentiometer Ref 37
Red (+)
White
Black
Green
Black ()
Black
120 AC
V
Motor
5
-
7/26/2019 teste de placas graco.pdf
6/107
BASIC ELECTRICAL TERMINOLOGY
RESISTANCE:
Resistance is anything that causes an opposition to the flow of current in a circuit.Resistance is used to control the amount of voltage and/or amperage in a circuit.
Resistance is measured in OHMS - . See Figure 3.A common component check would be motor and clutch field windings.
FIGURE 3
-
-
Black
Red
Yel
Yel
Known Value
-
Known Value
+
-
6
-
7/26/2019 teste de placas graco.pdf
7/107
CONTINUITY TESTING
Checking continuity is one of the most common tests in electrical troubleshooting. Continuity is the ability of a wire or electrical component to
conduct current. When you use a continuity tester, you connect a circuit (the continuity tester) that you know works, to a wire or a component that
may or may not work. The continuity tester will tell you if the wire or component is capable of conducting current.
Continuity testers are available at almost any hardware store.
A volt-ohmmeter or VOM can also be used to check continuity. This meter can be purchased at most electrical or electronic supply stores.
To test a component for continuity:
1 Check the tester by connecting the leads.
* If using a test light the light should turn on.
* If using a digital volt-ohmmeter, the screen should show 00 if OL appears the meter needs to be repaired.
SWITCH TESTING-ROCKER
Common test procedure for a SPST Switch:
0.000
7
-
7/26/2019 teste de placas graco.pdf
8/107
WIRE CONTINUITY TESTING
Continuity testing will NOT find wire fragmentation!!
Example:
120 Vac input static voltage and drops to 119Vac load voltage.
A good piece of wire will carry line and load voltage.
Damaged / Fragmented Wire Damaged / Fragmented Wire
Pinched Wire
120 Vac input static voltage and drops to 76Vac load voltage.
Other causes:
Poor stripping of outer insulation.
Poor crimp.
A defective piece of wire may carry line voltage but will NOT carry load voltage
8
-
7/26/2019 teste de placas graco.pdf
9/107
GROUND TESTING
Every corded electric sprayer that comes into your shop for repair should be tested as described below, to make sure that it is properly grounded.
Pull the machines plug out of the wall outlet and connect one lead from a DC continuity test light or a VOM to the (round) ground terminal on the
plug.
NOTE:
If the ground terminal is broken off of the plug, install a new plug.
Touch the test light (or VOM) leads to several bare metal surfaces on the body of the machine. If the light (or meter) indicates continuity, the machine
is properly grounded. If the light (or meter) doesnt indicate continuity trace through the ground (green) wiring on the machine to determine where
the break is.
Improper installation or alteration of grounding plug could results in risk of electric shock, fire or explosion that could cause serious injury or death.
The other function of the grounding plug is to protect the control board from static build up. If the plug is missing this could cause permanent damage
to the control board.
9
-
7/26/2019 teste de placas graco.pdf
10/107
CAPACITOR TESTING:
A capacitor is an electrical component that stores electricity. Capacitors are usually used to help start a motor or make a motor run more efficiently.
The following instructions can be used to test any capacitor.
WARNING!A CAPACITOR CAN SHOCK YOU EVEN WHEN A MACHINE IS UNPLUGGED. NEVER TOUCH CAPACITOR TERMINALS WITH
YOUR FINGERS. ALWAYS USE TOOLS WITH INSULATED HANDLES. NEVER DISCHARGE A CAPACITOR NEAR FLAMMABLE
LIQUIDS OR VAPORS.
1 Visually inspect the capacitor for leaks, mechanically damage or loose terminals. Replace it if any of these problems exist.
2 Unplug the machine and remove the capacitor(s).
If capacitor(s) are attached to the control board the test can not be performed.
3 SEE ABOVE WARNING Using a screwdriver with
insulated handles, hold so that the blade contacts the
capacitor terminals as shown in Fig. A. This will
discharge the capacitor.
4 Put a volt-Ohm meter on the R X 100 scale.
5 While watching the meter, connect the 2 leads to the 2 terminals on the capacitor.
If the capacitor is good, the meter needle will go to the right (toward 0 resistance) (Fig. 1), then to the left (toward - maximum resistance)
If the meter needle goes all the way to the right and stays there, the capacitor is defective.(Fig.2)
If the meter needle stays all the way to the left (doesn't move at all when connected to the capacitor), the capacitor is defective.(Fig. 3)
FIG. A
Capacitor
GOOD BAD BAD
10
-
7/26/2019 teste de placas graco.pdf
11/107
RECTIFIER
(See Fig. 1) Now we come to the most popular application of the diode: rectifcation. Simply rectifcation is the conversion of alternating
current (AC) to direct current (DC). This almost always involves the use of some device that only allows one-way flow of electrons.
As we have seen, this is exactly what a diode does.
RECTIFIER TESTING:
The following instructions can be used to test any bridge rectifer.Use a DC continuity test light or a VOM (on the R x 100 scale) for all tests.
Disconnect all wires from the rectifer.
AC
AC
+-
FIG. 1
1 Connect test leads as shown in Figure A. If the meter beeps, the rectifer is
defective. If the meter does not beep, go to the next step.
2 Connect test leads as shown in Figure B. If the meter does not beep, the
rectifer is defective. If the meter beeps, go to the next step.
3 Connect test leads as shown in Figure C. If the meter beeps, the rectifer is
defective. If the meter does not beep, go to the next step.
4 Connect test leads as shown in Figure D. If the meter does not beep, the
rectifer is defective. If the meter beeps, go to the next step.
5 Connect test leads as shown in Figure E. If the meter beeps, the rectifer isdefective. If the meter does not beep, go to the next step.
6 Connect test leads as shown in Figure F. If the meter does not beep, the rectifer is defective. If the meter beeps, go to the next step.
7 Connect test leads as shown in Figure G. If the meter beeps, the rectifer is defective. If the meter does not beep, go to the next step.
8 Connect test leads as shown in Figure H. If the meter does not beep, the rectifer is defective. If the meter beeps, the recti fer is good.
0.000OL OL 0.000
0.000OL OL 0.000
FIG. A FIG. B FIG. C FIG. D
FIG. E FIG. F FIG. G FIG. H
DC DC
11
-
7/26/2019 teste de placas graco.pdf
12/107
Instruction for checking the ERORR CODES:
1. Relieve pressure leave prime valve open and power switch OFF.
2. If sprayer has no display, remove the control box cover to view the control board LED status light.
3. Plug sprayer into correct AC power, grounded outlet.
4. Turn pressure control knob clockwise turn.5. Turn Power switch ON.
6. View digital display. If digital display is not available, view the control board LED status light
instead.
The Codes below ar e for several different models.
DIGITAL
DISPLAY
CONTROL BOARD
STATUS LIGHT.INDICATION
GO TO
PAGE
Digital_Display
_BlankNever Lights No power to microprocessor on control board. 13
- - - -
PSI icon not
blinking
Blinks once and stops Power to board is ok, No RUN command to motor.
14
- - - -
PSI iconblinking
Constant on Control is commanding motor to run. 15
Unreadable 1 Blink every 3 seconds
Board is trying to start up. Unplug transducer, pot
and display. If still blinking replace board. If itstops blinking one of the 3 parts are faulty.
Reconnect the parts one at time to find the faulty
part.
Displays high
pressure Improper pressure signal from transducer 16
E=02 Blinks 2 x repeatedly High pressure signal from transducer 17
E=03 Blinks 3 x repeatedly Transducer failure or connection error 18
E=04 Blinks 4 x repeatedly Excessive Wall voltage 19
E=05 Blinks 5 x repeatedly High current or motor is not turning. 20-22E=06 Blinks 6 x repeatedly
Motor is too hot or motor/thermal device
connection may be bad.23
E=07 Blinks 7 x repeatedly Exceeded 2000 psi during timed flush cycle. 24
E=08 Blinks 8 x repeatedly Low wall voltage 24
E=09 Blinks 9 x repeatedly Motor sensor failure 25
E=10 Blinks 10 x repeatedly High control board temperature 26
E=11 Blinks 11 x repeatedly Excessive motor speed 26
E=12 Blinks 12 x repeatedly High Current 27
E=13 Blinks 13 x repeatedly Model not selected 27
EMPTY Watchdog mode is activated. Sprayer will stop
running when pressure drops sharply28
Cal
Older Ultra-Maxs
Unplug the display, If sprayer operates Replace the
Display. If the sprayer does not operate replace thecontrol board.
8888Digital Display Switches
not set.
Set switches on back of digital display to the
appropriate settings.
Motor Hums Constant onPerform appropriate motor tests, if motor tests ok,
replace control board.
12
-
7/26/2019 teste de placas graco.pdf
13/107
Symptoms: Sprayer does not run at all
Digital Display is blank
Control board status light never lights
What does this mean?No power to the control board or display or control board is likely the problem.
Troubleshooting Procedure:
1. Set sprayer to OFF. Unplug digital display. Set sprayer to ON. If sprayer runs, replace display. If not, go to
next step.
2. Set sprayer ON and check for A.C. voltage at the control board. If no voltage, check power source andwiring back to power cord.
3. Set sprayer to OFF and disconnect power to sprayer.Check continuity from power cord plug (through
power switch) to control board.
4. If power cord, switch, EMI filter and wiring continuity is ok, replace control board.
13
-
7/26/2019 teste de placas graco.pdf
14/107
Symptoms: Sprayer does not run at all
Digital Display shows dashes and Psi icon is not blinking
Control board status light blinks once when switch is turned on but then stays off.
What does this mean?Power to board is ok but there is no RUN command to the motor. Either the potentiometer or control board is
likely the problem.
Troubleshooting Procedure:
Check potentiometer & connectionsto control board. Set sprayer to OFF.
Disconnect potentiometer from control board socket. Check that potentiometer and control board contacts areclean and secure.
Reconnect potentiometer to control board socket. Set sprayer ON
and control knob to turn clockwise. If sprayer does not run, set
sprayer to OFF and go to next step.
Connect a known good potentiometer to control board socket and set sprayer ON and control knob to turn
clockwise. If ok, replace pot. Replace control board if sprayer still does not run. But first, verify transducer
and connections are ok. See next page.
OR
Short center pin of socket to each outer pin. Install new potentiometerif sprayer runs. Replace control board if sprayer does not run. But first,
verify transducer and connections are ok. See next page.
Check transducer & connectionsto control board. Set sprayer to OFF anddisconnect power to sprayer.
Disconnect transducer from control board socket. Check that transducer and control board contacts are
clean and secure.
Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob to turn
clockwise. If sprayer does not run, set sprayer to OFF and go to next step.
Connect a known good transducer to control board socket.
Set sprayer ON and control knob to turn clockwise. Install new transducer if sprayer runs. Replace control
board if sprayer does not run.
_ _ _
14
-
7/26/2019 teste de placas graco.pdf
15/107
Symptoms: Sprayer does not run at all
Digital Display shows dashes and Psi icon is blinking
Control board status light blinks and stays on constant.
E5 error code brushless unit
What does this mean?There is power to control board, the potentiometer and transducer are ok and the control is commanding the
motor to run. Either the motor, motor connections, capacitor connections (brush type motor) or control board is
likely the problem.
Troubleshooting Procedure:
1. Check motor and connections to control board. Also check
capacitor connections to control board for brush style motor.
2. Set sprayer to OFF and disconnect power to sprayer.
3. Disconnect motor connector from control board socket. Check that motor connector and control boardcontacts are clean and secure.
Check that connections at capacitor are secure. CAUTION
CAPACITOR MAY STILL HAVE A CHARGE ON IT!
4. Check motor. Remove pump pin and connect a D.C. voltmeter across two motor wires red & black (brushtype) red, black, blue (brushless type) Spin motor fan and check for a voltage to register on meter. Repeat
for all motor wire combinations brushless type only. If voltage notpresent, check brushes. If ok, replace
motor. If voltage present, go to next step.
5. Reconnect motor connector to control board socket. Connectpower, set sprayer ON and control knob to
turn clockwise. If sprayer does not run, replace control board.
_ _ _
15
-
7/26/2019 teste de placas graco.pdf
16/107
Symptoms: Sprayer does not run at all
Digital Display shows a pressure reading
and Psi icon on
Control board status light off.
E2 error code Brushless unit (possible)
What does this mean?Improper pressure signal to control board, with no pressure in sprayer. The transducer or connections is likely
the problem.
Troubleshooting Procedure:
1. Set sprayer to OFF anddisconnect power to sprayer.
2. Check transducer & connectionsto control board.
3. Disconnect transducer from control board socket. Check that transducer and control board
contacts are clean and secure.
4. Reconnect transducer to control board socket. Connect power; set sprayer ON and control knob to turn
clockwise. If sprayer does not run, set sprayer to OFF and go to next step.
5. Connect a known good transducer to control board socket.
Set sprayer ON and control knob to turn clockwise. Install newtransducer if sprayer runs. Replace control board if sprayer does
not run.
XXXX Psi
16
-
7/26/2019 teste de placas graco.pdf
17/107
Symptoms: Sprayer does not run at all
Digital Display shows E=02
Control board status light blinks 2x repeatedly.
What does this mean?The control board is detecting an excessive pressure. The transducer or connections is likely the problem.
Troubleshooting Procedure:1. Make sure there is no pressure in the system (see pressure relief procedure). Check fluid path for clogs,
such as clogged filter.
2. If running Auto Clean, open prime valve and trigger gun.
3. Use airless paint spray hose with no metal braid. in. x 50 ft minimum. Smaller hose or metal braid hose
may result in high-pressure spikes.
4. Set sprayer to OFF anddisconnect power to sprayer.
5. Check transducer & connectionsto control board.
6. Disconnect transducer from control board socket. Check that transducer and control board contacts are
clean and secure.
7. Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob to turn
clockwise. If sprayer does not run properly, set sprayer to OFF and go to next step.
8. Replace transducer. Connect power, set sprayer ON and control
knob to turn clockwise. Install new transducer if sprayer runs
properly. Replace control board if sprayer does not run properly.
E=02
17
-
7/26/2019 teste de placas graco.pdf
18/107
Symptoms: Sprayer does not run at all
Digital Display shows E=03
Control board status light blinks 3x repeatedly.
What does this mean?The control board is not detecting a pressure signal.
The pressure transducer or connections are likely the problem.
Troubleshooting Procedure:
1. Set sprayer to OFF and disconnect power to sprayer.
2. Check transducer & connections to control board.
3. Disconnect transducer from control board socket. Check that transducer and control board
contacts are clean and secure.
4. Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob
to turn clockwise. If sprayer does not run, set sprayer to OFF and go to next step.
5. Connect a known good transducer to control board socket.
6. Set sprayer ON and control knob to turn clockwise. Install new
7. transducer if sprayer runs. Replace control board if sprayer does not run.
8. You can also check transducer resistance with an ohmmeter;
Between red & black wires less then 9 k ohm and 3-6 k ohm between green & yellow
wires.
E=03
18
-
7/26/2019 teste de placas graco.pdf
19/107
Symptoms: Sprayer does not run at all
Digital Display shows E=04
Control board status light blinks 4x repeatedly.
What does this mean?Voltage applied to the sprayer is too high.
Troubleshooting Procedure:
1. Make sure the sprayer is plugged into the proper AC power source. Less than 138 volts for 120V
sprayers and less than 260V for 230V sprayers.
E=04
19
-
7/26/2019 teste de placas graco.pdf
20/107
Symptoms: Sprayer does not run at all
Digital Display shows E=05
Control board status light blinks 5x repeatedly.
What does this mean?The control is commanding the motor to run but the motor shaft does not rotate. Possibly locked rotor condition,an open connection exists between the motor and control, there is a problem with the motor or control board orthe motor amp draw is excessive.
Ultamax lls: Brushless motors test when the motor isrunnning at the start of the test. For all others go to step 1.
With the prime valve open and pressure relieved, start and stop the motor 15 times using the set point pot(Pressure Switch). If the motor restarts each time at no load Motor is probably bad (Resolver in the motor)replace the motor. If the motor will not restart every time then the board is at fault (running on 2 phase) replace
the circuit board.
Troubleshooting Procedure ULTRA-MAX II(Brushless Type Motors)
1. Remove the pump pin and try to run the sprayer. If the motor runs check for locked or frozen pumpor drive train. If sprayer does not run, go to next step.
2. Set sprayer to OFF and disconnect power to sprayer .
3. Disconnect motor connector(s) from control board socket(s). Check that motor connector andcontrol board contacts are clean and secure. If tests ok go to step 4.
5. Spin Test: Test at the large 4-pin motor field connector. Disconnect the fluid pump from thesprayer. Test motor by placing a jumper across pins 1 & 2. Rotate the motor fan at about 2-revolutions/second. A cogging resistance to motion should be felt at the fan. The motor needsreplacing if no resistance is felt. Repeat for pin combinations 1 & 3 and 2 & 3. Pin 4, the greenground wire, is not used in this test. If it tests good go to step 5 Resolver test
E=05
Spin Test
4. Set sprayer to OFF spin the motor fan 1/4 turn. Restart sprayer. If sprayer runs, replace control board.If not, go to step 5.
Step 1
4 3 2 1 4 3 2 1
Step 3
4 3 2 1
Step 2
GRN BLU RED BLK GRN BLU RED BLK GRN BLU RED BLK
20
-
7/26/2019 teste de placas graco.pdf
21/107
Resolver Test
NOTE: 490II, 495II and 595II Brushless motors will not have a resolver plug.
5. Resolver Test: Test the 6-pin Resolver connector on the end of the cable that connects the motor tothe circuit board. Use a volt-ohm meter to test resistance. Should read 44 ohms across pins 1 & 4,167 ohms across pins 2 & 5, and 167 ohms across pins 3 & 6. Inspect the 6 sockets in the connectorto make sure they are not causing a bad connection. Squeeze the socket back to size if one appearstoo large. If it tests good go to step 6.
6. Field Short Test: Test at the large 4-pin motor field connector. There should not be continuity from
pin 4, the ground wire, to any of the remaining 3 pins. If it tests good replace the Control Board.
12
345
644 ohms
Step 1
12
345
6167 ohms
Step 2
12
345
6
167 ohms
Step 3
7. Checking the motor thermistor: Unplug the Black wires. Set meter to Ohms.
Meter should read 100K(+ or -)10%. Note: motor should be cooled down.
-
100k ohm
+
-
To Motor
Black
Control
Board
21
-
7/26/2019 teste de placas graco.pdf
22/107
Troubleshooting Procedure for Brush Type Motors:
1. Remove the pump pin and try to run the sprayer.If the motor runs check for locked or frozen pumpor drive train. If sprayer does not run, go to next step.
2. Set sprayer to OFF and disconnect power to sprayer .
3. Disconnect motor connector(s) from control board socket(s). Check that motor connector andcontrol board contacts are clean and secure. If ok go to Step 4.
4. See capacitor test page. CAUTION - CAPACITOR MAY STILL HAVE ACHARGE! If it test ok go to step 5.
5. Check motor. Connect a D.C. voltmeter across two motorwires red & black spin the motor fanand check for a voltage to register on the meter. If voltage not present, check brushes. If ok, replacemotor. If voltage present, go to next step.
6. Reconnect motor connector(s) to control board socket(s). Connect power, set sprayer ON andcontrol knob to turn clockwise. If motor does not run, replace control board.
OR
+-9 volt
battery
Step 1
-
BEEP
Step 2
+-
-
-
1-3 ohms
Step 3
-
OL
+
Step 4
Ground
-
Checking the motor wires for a short.
Put the (-) meter lead on the motor case.
Move the (+) meter lead to each wire.
Meter should read open on all the wires.
Perform a spin test by connecting
a 9 volt battery or larger to the
motor leads. Motor leads may vary
in style and size. Locate the 2 wires
going to the carbon brushes normally
Red and Black.
Spin the motor while checking.
If a open is found replace the motor.
Checking the motors thermal protection.
Meter should read continuity or Ohms
depending on the motor.
Note: motor should be cooled down.
Black
RedYellow
Black
RedYellow
Black
RedYellow
Black
RedYellow
Use CAUTION not to distort the connectors when inserting the meter probes.
22
-
7/26/2019 teste de placas graco.pdf
23/107
Symptoms: Sprayer does not run at all
Digital Display shows E=06
Control board status light blinks 6x repeatedly.
What does this mean?Motor is too hot or motor/thermal device connections are likely the problem.
Troubleshooting Procedure:
Quick test for Ultra Max ll's Only:
Note: This test is only for the BRUSHLESS MODELS. For all others go to step 1.
Motor must be cooled down for the test. Unplug thermistor wires from the control board, turn the sprayer on,
if motor starts the thermistor switch is bad, replace the motor. If motor still does not start or error code is still
present replace the control board. Step 3 should also be performed if a VOM is available to confirm that the
thermistor is shorted.
1. Check thermal sensor and connections to control board. Set sprayer to OFF anddisconnect power to
sprayer.
2. Disconnect motor / temp connector from control board socket. Check that transducer and control board
contacts are clean and secure.
3. Measuringthe resistance of thethermal device. NOTE: A low resistance reading would be indicating to
the control board that the motor is hot. The resistance for most motors with yellowsensor wires will be
about 100 k ohm.If the reading is not correct,replace motor. Motors with a thermal switch you will test
for continuity.If open replace the motor.
4. Reconnect motor / temp connector to control board socket. Connect power, set sprayer ON and control
knob to turn clockwise. If sprayer does not run, replace control board.
5. If connections are all OK, allow sprayer to cool. If sprayer runs when cool, correct cause of overheating.
Keep sprayer in cooler location with good ventilation. Make sure motor air intake is not blocked.
6. If the sprayer still does not run after cooling off, replace the motor.
E=06
23
-
7/26/2019 teste de placas graco.pdf
24/107
Symptoms: Sprayer does not run at all
Digital Display shows E=07
Control board status light blinks 7x repeatedly.
What does this mean?Pressure exceeded 2000 psi while using the flush timer (AutoClean Timer)
Troubleshooting Procedure:1. This error only occurs when using the flush timer. Do not use the flush timer mode when spraying.
2. When using the flush timer for AutoClean , make sure that the gun trigger, prime valve and AutoClean
valve are all open before starting the motor.
Symptoms: Sprayer does not run at all
Digital Display shows E=08
Control board status light blinks 8x repeatedly.
What does this mean?Voltage applied to the sprayer is too low.
Troubleshooting Procedure:
Make sure the sprayer is plugged into the proper AC power. More then 90 volts for 120V sprayers and at least
200 volts for 230V sprayers) Check the voltage at the control board. If below 90 or 200 volts repair or replace
cord or switch. If voltage at the boards is above 90 or 200 replace the control board.
E=07
E=08
24
-
7/26/2019 teste de placas graco.pdf
25/107
Symptoms: Sprayer does not run at all
Digital Display shows E=09
Control board status light blinks 9x repeatedly.
What does this mean?The control is not receiving a motor position sensor signal. The resolver or connections is likely the problem.
(Ultra Max II motors only)
Troubleshooting Procedure:
1. Set sprayer to OFF.
2. Disconnect motor and resolver connectors from control board sockets. Check that connector and controlboard contacts are clean and secure.
3. Check the resolver connections and resistance. Take three resistance readings at the resolver connector,
between the two rows. The readings should be about: 44 ohms and 167 ohms twice. If any reading is
open, replace motor.
4. Make sure the connector sockets are not (or do not get) spread out or damaged. This may cause the
motor not to run. If any of the sockets are out of shape or enlarged, the sockets can be pinched tighter
for a better contact.
5. Reconnect motor connectors to control board sockets. Set sprayer ON and control knob to turn
clockwise. If motor does not run, replace control board.
E=09
25
-
7/26/2019 teste de placas graco.pdf
26/107
Symptoms: Sprayer does not run at all
Digital Display shows E=10
Control board status light blinks 10x repeatedly.
What does this mean?Control board power module high operating temperature. The module
is likely too hot or motor running too hot.
(Ultra Max II motors only)
Troubleshooting Procedure:
1. Make sure the motor air intake is not blocked
2. Make sure control board is properly connected to the back plate and that conductive thermal paste isused on the power components.
3. Replace control board.
4. Replace motor.
Symptoms: Sprayer does not run at all
Digital Display shows E=11
Control board status light blinks 11x repeatedly.
What does this mean?Excessive motor speed. The control is sensing abrupt motor speed change. The sprayer drive or motor resolver
is likely the problem.
(Ultra Max II motors only)
Troubleshooting Procedure:
1. Check for damaged gears or disconnected pump.
2. Run sprayer at low pressure to check for normal operation.
3. Replace drive or motor as needed.
E=10
E=11
26
-
7/26/2019 teste de placas graco.pdf
27/107
Symptoms: Sprayer does not run at all
Digital Display shows E=12
Control board status light blinks 12x repeatedly.
What does this mean?The control board is detecting an excessive amp draw. The motor circuit is possibly shorting out, a locked rotor
condition exists or the control boards has a problem. (Ultra Max II motors only)
Troubleshooting Procedure:
1. Set sprayer to OFF.
2. Disconnect motor connector from control board socket. Check that motor connector and control board
contacts are clean and secure.
3. With the motor unplugged turn the control knob fully counter clockwise. Set sprayer ON. If E=12 does
not display, control board is ok. If E=12 is displayed, control board is faulty, before replacing the board
check for possible short circuits in motor wiring.
4. Reconnect motor connector to control board socket.
5. Set sprayer to OFF. Remove the pump pin and try to run the sprayer. If the motor runs check for locked
or frozen pump or drive train. If display shows E=12 (or control board status light blinks 12x
Repeatedly) replace motor.
Symptoms: Sprayer does not run at all
Digital Display shows E=13
Control board status light blinks 13x repeatedly.
What does this mean?Model select resistors on control board not properly selected.(Ultra Max II motors only)
Troubleshooting Procedure:Resistors on control board must be properly clipped to identify model type, see replacement control board
instruction manual.
E=12
E=13
27
-
7/26/2019 teste de placas graco.pdf
28/107
Symptoms: Sprayer does not run at all
Digital Display shows EMPTY
What does this mean?
Watchdog mode is activated. Sprayer will stop running when pressure drops sharply. This prevents pump
runaway when out of paint, clogged inlet strainer, severe leak.
Troubleshooting Procedure:Watchdog mode can be deactivated (See sprayer instruction manual)
To restart the sprayer after a Watchdog trip, turn pressure control to zero and back up or turn power off/ then on.
EMPTY
28
-
7/26/2019 teste de placas graco.pdf
29/107
Electric Motor will not shut off:
1. Relieve pressure, leave prime valve open and power switch OFF.2. Remove the control box cover so the control board status light can be viewed if available.
Troubleshooting Procedure:
With a pressure gauge plumbed into the paint hose,
plug the sprayer in. Turn the power switch on, does
the gauge read the sprayersmaximum pressure and
continues to build pressure?
Mechanical problem: See the properfluid pump manual for the sprayer for
further trouble shooting procedures.
Is light on at the control
board? If the board has no
light the answer is yes.
Replace the control board.
Unplug the transducer from controlboard, does motor stop running?
Bad transducer, replaceand test with a new one.
Replace the control board.
YES
YES
YES
Shorted Board.
NO
NO
NO
29
-
7/26/2019 teste de placas graco.pdf
30/107
Gas Sprayers (Fluid Pump)runs all the time:
1. Relieve pressure, leave prime valve open, power switch OFF.
2. Remove the control box cover.
Troubleshooting Procedure:
With a pressure gauge plumbed into the paint
hose, start the engine. Turn the pump switch on,
does the gauge read the sprayers maximum
pressure and continues to build pressure?
Mechanical problem: See the properfluid pump manual for the sprayer forfurther trouble shooting procedures.
Unplug the transducer from controlthe board, does the pump stop.
Bad transducer, replaceand test with a new one.
Replace the control board.
NO
NO
YES
YES
YES
With the clutch wires plugged in.
Do you have 10-18 DC Volts
at the clutch test points?
NODisconnect the clutch wires from
the control board. Does the pump
stop running?
Mechanical problem in the clutch pinion
assembly. (Clutch may be to close to the rotor).
YES
NO
Check for a short from the
2 clutch wires to the frame.
If shorted repair or replace
the faulty wire.
30
-
7/26/2019 teste de placas graco.pdf
31/107
NO
Remove the control box cover.
Turn the sprayer on. Observe
the control boards light(s).
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has a
defective
thermistor switch.
See pages 32for the steps and illustrations.
NO
See step 4.
Is there
continuity
through the
thermistor
wires?
See step 5.Does the
motor run?
See motor
test section.
Motor will not start:
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or replace
the power Cord.
NO
Replace
Potentiometer.Pressure Switch
190ES,SPX,295ST
Control Board 241989 (Capacitor on Motor)
Connect a test
transducer to
the board.
Does themotor run
Replace the
transducer.
Replace
Control
Board.Yes
No No
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
31
-
7/26/2019 teste de placas graco.pdf
32/107
Capacit
or
190ES,SPX,295ST
Control Board 241989
L2M+TO2 TO1
L1
M-
J12J10
Black
Black
White
Ground
Grn
RedRed Black
Black
Yellow
L2
L1
Black
White
Control
Board
Step 1
Cord plugged in.
Switch ON.
Wires connected
to control board.
110-120 AC
V
-
+
-
Step 2
Cord plugged in.
Switch ON.
Wires connected
to ON/Off Switch.
+
-
M+
M-
White
Yellow
Black
Control
Board
100 + DC
V
Step 3
Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
-
Potentiometer
110-120 AC
V
-
J12
J10
Step 5
Potentiometer
Cord plugged in.
Switch ON.Potentionmeter
disconnected.
Control
Board
-
BEEP
Checking the motor
thermistor switch .
Unplug the 2 yellow
wires from TO2 and TO1
Meter should read
continuity. Note: motor
should be cooled down.
L2
TO2TO1
L1
-
Step 4
Control
Board
(Capacitor on Motor)
32
-
7/26/2019 teste de placas graco.pdf
33/107
NO
Replace Potentiometer.
Pressure Switch
Replace the
power switch.
If moto r is hot letcool and retest, if
step 6 still shows an
open replace moto r.
The motor has a
defective
thermistor switch.
See pages34for the steps and illustrations.
NO
See step 4 .Is there
continuity
through the
thermistor
wires?
See step 5 .
Does the moto r run?
See motor
test section.
190ES,DTX,SP,SPX,ST,STX
(Capacitor on PC board)Control Board 245892
Motor will not start:
See step 2.
Do you haveover 100 AC
volts?
See step 1.
Do you have
over 100 AC
volts?
NO
YES
See step 3 .
Is there over
100 DC volts?
YES
YES
Repair or repl ace the
power Cord.
NO
Check the motor for a short
before replacing fuse. See
moto r test section.If motor
tests ok install a new fuse
with the motor
unplugged.Turn sprayer on,
if the fuse doesn t open
replace the motor.
Is the fuse
good.
YES
NO
YES
YES
Connect a test
transducer to
the board.
Does the
motor run
Replace the
transducer.
Replace the
Control
Board
Yes
No No
Remove the control box cover.Turn the sprayer on. Observe
the control boards light(s).
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
33
-
7/26/2019 teste de placas graco.pdf
34/107
Pressure
Transducer
Motor
Yellow
Ground
Black
Black
White
White
Green
FUSE
J8J7
NL
M+ M-
T01
T02
D7
Red Black
F1
Step 1110-120 AC
V
-
White
FUSE
NL
F1
Black
Control Board
-
+
Cord plugged in.
Switch ON.
Wires connected.
Reference F1 on the
Control board for
proper meter location.
110-120 AC
V
-
-
+
Step 2
Cord plugged in.
Switch ON.
Wires connected
to ON/Off Switch.
Control
Board
100 + DC
V
Step 3Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
Motor
Yellow
FUSE
M+ M-
T01
T02
RedBlack
F1
-
J8
Step 5
Potentiometer
Cord plugged in.
Switch ON.
Potentionmeter
disconnected.
Control
Board
Yellow
J7
T01
T02
-
BEEP
Checking the motor
thermistor switch .
Unplug the 2 yellow
wires from TO2 and TO1
Meter should read
continuity. Note: motor
should be cooled down.
-
Step 4
Control
Board
190ES,DTX,SP,SPX,ST,STX
(Capacitor on PC board)Control Board 245892
34
-
7/26/2019 teste de placas graco.pdf
35/107
Remove the motor
cover. See step 1. Do
you have over 100 AC
volts?
Replace pressure
control switch.
If motor is hot let cool and
retest, if step 4 still shows an
open replace motor. The
motor has a defective
thermistor switch.
Replace
control board.
See pages 36 for the steps and illustrations.
NO
YES
See step 3.
Is there over
100 DC volts?
See step 4.
Is there continuity
through the
thermistor wires?
See step 5.
Does the motor run?
NO
See motor test section.
YES
NO
Replace the
power switch.
See step 2.
Do you have
over 100 AC
volts?
NO
YES
Repair or replace the
power Cord.
Check the motor for a short
before replacing fuse. See
motor test section.If motor
tests ok install a new fuse
with the motor
unplugged.Turn sprayer on,
if the fuse doesnt openreplace the motor.
Is the fuse
good.
YES
NO
YES
NO
190ES 232900,F;232901,E;233797,E;233815,E
Control Board 253118
Motor will not start:
YES
35
-
7/26/2019 teste de placas graco.pdf
36/107
Motor
L
Black
J1
N
WhiteF1
Fuse
BlackWhite
Ground
Green
Black
Black
Yellow
Red
Yellow
White
Black
-
+
100 + DC
V
Step 3
Cord plugged in.Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
F1
Fuse
Red Black
-
J1
Step 5 Cord plugged in.
Switch ON.
Pressure switch unplugged.
Control
Board
Insulated Jumper wire
stripped on the ends
Pressure
switch
Control
Board
Checking the motor
thermistor switch .
Unplug the motor.
Meter should read
continuity. Note: motor
should be cooled down.
F1
Fuse
Control
Board
-
BEEP
Yellow Yellow
-
Step 4
Step 1Cord plugged in.
Switch ON.
Wires connected.
Reference F1 on the
Control board for
proper meter location.
NWhite
F1
Fuse
-
+
110-120 AC
V
-
110-120 AC
V
-
Step 2Cord plugged in.Switch ON.
Wires connected
to ON/Off Switch.
190ES 232900,F;232901,E;233797,E;233815,E
Control Board 253118
36
-
7/26/2019 teste de placas graco.pdf
37/107
NO
Replace the
control board.Faulty switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has a
defective
thermistor switch.
See pages38 for the steps and illustrations.
NO
See step 5.
Is there
continuity
through the
thermistor
wires?
See step 6.
Does themotor run?
See motor
test section.
See step 2.
Do you haveover 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 4.
Is there over
100 DC volts?
YES
YES
Repair or replace
the power Cord.
NO
Replace
Pressure Switch
Replace Control Board.No
249052 Control Board
Motor will not run
See step 3. Do
you have over
100 AC volts?
If the fuse is
blown check
the motor for
a short before
replacing the
control board.
NO
YES
37
-
7/26/2019 teste de placas graco.pdf
38/107
On/Off
Switch
Pressure
Switch
Motor
FUSE
F1
Grnd.
249052 Control Board Trouble Shooting
J1
J3J4
BlkRed
Yellow
J3J4
Control
Board
To
Power Cord
Step 1
Cord plugged in.
Switch ON.Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
-
On/Off
Switch
FUSE
F1
J4
Control
Board
Step 2
Cord plugged in.
Switch ON.Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
-
+
On/Off
Switch
FUSE
F1
J4
Control
Board
Step 3
Cord plugged in.
Switch ON.Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
-
+
Blk
Red
Yellow
Control
Board
100 + DC
V
Step 4Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts
-
-
-
BEEPChecking the motor
thermistor switch .
Unplug the motor
wires from control
board.
Carefully insert the
meter probes into the
2 yellow wires.
Meter should read
continuity.
Note: motor should be
cooled down.
+
Yellow
-
Step 5
J1
Step 6
Motor plugged in. Cord plugged in.
Switch ON.
Pressure switch
unplugged.
Control
Board
Insulated Jumper wire
stripped on the ends
+
Red
Blk38
-
7/26/2019 teste de placas graco.pdf
39/107
249052 Control Board Trouble Shooting
Motor Will Not Shut Off
With a pressure gauge plumbed into the paint gun
hose, turn the power switch on, does the gauge readthe sprayers maximum pressure and continue to
build pressure?
Mechanical problem: Sprayer cannot build to
proper pressure. See the proper fluid pumpmanual for further troubleshooting procedures.
See Fig.1 Unplug the pressure control's (A)plugfrom the control board. Does the motor stop?
No
No
Yes
Yes
Replace the pressure control.
Replace the control board.
A
Fig. 1
Pressure Control
39
-
7/26/2019 teste de placas graco.pdf
40/107
NO
Replace the
power switch.
NO
See step 3.
Is there
continuity
through the
thermistor
switch.
See step 5.
Does the motor run?
See motor
test section.
See step 2.
Do you haveover 100 AC
volts?YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
See step 4.
Is there over
100 DC volts?
YES
Repair or replace thepower Cord.
See pages 41for the steps.
235707, 235008 Control Board
Check all the wiring
connection to the 2
small motor wires, if
ok replace motor. Faulty
thermistor switch.
NO
YES
Replace Control Board.No
See step 6.
Does the presure
switch test ok?
YES
Replace
Pressure Switch
Check the pressure transducer for
hardened paint or damaged or
worn components. Clean or replace.
YES
No
40
-
7/26/2019 teste de placas graco.pdf
41/107
Black
-ML
Black
N
White
110-120 AC
V
-
Cord plugged in.
Switch ON.
Wires connected.
-
+
Step 1
Motor
Wht/Blk
RedRed
Blk
ThermistorSwitch (NC)
-
BEEPChecking the motor
thermistor switch .Unplug the 2 red wires.
Meter should read
continuity. Note: motor
should be cooled down.
Step 3
+-
+M-M
Motor Start Board
BlkWht/Blk
Control
Board
100 + DC
V
Step 4Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts
-
+
-
Black
-ML
Black
N
White
110-120 AC
V
-
Cord plugged in.Switch ON.
Wires connected.
-
+
Step 2
J5Control
Board
Step 5
Black
+M-M
Motor
Motor Start Board
L
Wht/Blk
Black
Ground
White Red WhiteRed
N
Blk White
Thermistor
Switch (NC)
Pressure Control
Switch
J5
1
Cord plugged in.
Switch ON.
Pressure Switch
unplugged.
Remove pressure control and check the
micro switch operation with ohmmeter:
(1) With pressure knob at the lowest setting
and stem pushed into the control, readings
should be: white & black = 1 ohm max.
white & red = open. (2) With pressure knob
at the highest setting, readings should be:
white & black = open; white & red =
1 ohm max. If any of the above tests are not
correct it's a NO.
-
BEEP
Step 6
+
-
235707, 235008 Control Board Trouble Shooting
41
-
7/26/2019 teste de placas graco.pdf
42/107
235008 Control Board Trouble Shooting
Motor Will Not Shut Off
Yes
Yes
NOReplace the PressureControl Assembly .
Remove pressure control and check themicro switch operation with a ohmmeter:
(1) With pressure knob at the lowest setting andstem pushed into the control, readings should be:
white & black = 1 ohm max. white & red = open.
No Replace the control board.Unplug the pressure transducer switch plug
from the control board. Does the motor stop?
With a pressure gauge plumbed into the paint gunhose, turn the power switchon, does the gauge readthe sprayers maximum pressure andcontinue to
build pressure?
No
Yes
Mechanical problem: Sprayer cannot build toproper pressure. See the proper fluid pump
manual for further troubleshooting procedures.
Check the pressure transducer for
hardened paint or damaged or worncomponents. Clean or replace
MOTOR
On/Off Switch
To Pressure
Transducer
E
A
B
CD
42
-
7/26/2019 teste de placas graco.pdf
43/107
NO
Remove the control box cover.
Turn the sprayer on. Observe
the control boards light(s).
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has a
defective
thermistor switch.
See pages 44for the steps and illustrations.
NO
See step 4.
Is there
continuity
through the
thermistor
wires?
See step 5.Does the
motor run?
See motor
test section.
Motor will not start:
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or replace
the power Cord.
NO
Replace
Potentiometer.Pressure Switch
Control Board 241990
(395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super)
Connect a test
transducer to
the board.
Does themotor run?
Replace the
transducer.
Replace
Control
Board.
Yes
No No
See Error Code
section for further
troubleshooting.
OnceNormal operation.
Go to step 1.
Light on
continuously
Control board
commanding
motor to run.
Go to Step 1.
Flashing
No light Go to step 1.
43
-
7/26/2019 teste de placas graco.pdf
44/107
L2M+TO2 TO1
L1
M-
J12J10
Black
Black
White
Ground
Grn
Red
Black
Yellow
L2
L1
Black
White
Control
Board
Step 1
Cord plugged in.
Switch ON.
Wires connected
to control board.
110-120 AC
V
-
+
-
Step 2
Cord plugged in.
Switch ON.
Wires connected
to ON/Off Switch.
+
-
M+
M-
White
Yellow
Black
Control
Board
100 + DC
V
Step 3
Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
-
Potentiometer
110-120 AC
V
-
J12
J10
Step 5
Potentiometer
Cord plugged in.
Switch ON.Potentionmeter
disconnected.
Control
Board
Checking the motor
thermistor switch .
Unplug the 2 yellow
wires from TO2 and TO1
Meter should read
continuity. Note: motor
should be cooled down.
L2
TO2TO1
L1
-
Step 4
Control
Board
Control Board 241990
(395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super)
-
BEEP
44
-
7/26/2019 teste de placas graco.pdf
45/107
NO
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has adefective
thermistor switch.
NO
See step 4.
Is there
continuity
through the
thermistorwires?
See step 5. Does the
motor run?
See motor
test section.
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or replace the
power Cord.
NO
Replace Potentiometer.
Pressure Switch
See pages 46for the steps.
Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595
Performance Max 395/495/595, ST Max 395/495/595
246379 Control Board
Connect a testtransducer to
the board.
Does the
motor run
Replace the
transducer.
Replace theControl
BoardYes
NoNO
Remove the control box cover.
Turn the sprayer on. Observe
the control boards light(s).
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
45
-
7/26/2019 teste de placas graco.pdf
46/107
Black
110-120 AC
V
-
-
+
Step 2
Cord plugged in.
Switch ON.
Wires connected
to ON/Off Switch.
Black
Control
Board
100 + DC
V
Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
-
Motor
-
BEEPChecking the motor
thermistor switch .
Unplug the J11 2 yellow
wires from control board.
Meter should read
continuity. Note: motor
should be cooled down.
+
Yellow Thermistor
Wires to motor
-
J11
J8
J7
N
L
Cord plugged in.
Switch ON.
Potentionmeter
disconnected.
J8
ControlBoard
Step 3
Step 4
Step 5
C15
White
110-120 AC
V
-
Cord plugged in.
Switch ON.
Wires connected.
+
N
L
White
Black
-
+
Power
Cord
Step 1
Yellow Thermistor
Wires to motor
Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595
Performance Max 395/495/595, ST Max 395/495/595
246379 Control Board
Control
Board
ControlBoard
46
-
7/26/2019 teste de placas graco.pdf
47/107
Replace the
power switch board.
If motor is hot let
cool and retest, if
step 4 still shows low
resistance replace motor.
The motor has a
defective thermistor .
NO
See step 4.
Is there
100K Ohms
through the
thermistor
wires?
See step 5.
Does the motor run?
See step 2.
Do you have
over 100 AC
volts?
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
YES
Repair or
replace
power
Cord.
NO
Replace Potentiometer.
Pressure Switch
Control Board 287909
(490ll, 495II,595ll)
Motor will not Run:
See pages 48for the steps.
Connect a test
transducer to
the board.
Does the
motor run?
Replace the
transducer.
Replace the
Control
BoardYes
No No
See step 3.
Is there over
100 AC volts?
Replace the
power switch board.YES
NO
Remove the control box cover.
Turn the sprayer on. Observe
the control boards Green light.
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
YES
47
-
7/26/2019 teste de placas graco.pdf
48/107
Ground
Motor
L1
L1
D21
L2BL1B
Yellow
Yellow
Green
Blue
Red
Blac
k
WhiteBlack
Black
White
Green
Step 1
Cord plugged in.Switch ON.
Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
+
Ground
L1
L1
L2BL1B
WhiteBlack
Black
Power
Cord
-
Step 2
Cord plugged in.Switch ON.
Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
+
Ground
L1
L1
L2BL1B
WhiteBlack
Black
Power
Cord
-
Step 3
Cord plugged in.Switch ON.
Wires connected
to control board.
Meter on AC Volts
110-120 AC
V
-
+
Ground
L1
L1
L2BL1B
WhiteBlack
Black
Power
Cord
-
Control
Board
Step 4
-
D21
Yellow
Yellow
To Motor
-
J12
Potentiometer
Cord plugged in.
Switch ON.
Potentiometer
disconnected.Control
Board
Step 5
Control Board 287909
(490ll, 495II,595ll)
Checking the motor
thermistor .
Unplug the yellow wires.
Meter should read 100K
Note: motor should be
cooled down.-
100k ohm
Transducer
On/OffSwitch
Board
On/OffSwitch
Board
On/Off
Switch
Board
On/Off
Switch
Board
-
7/26/2019 teste de placas graco.pdf
49/107
NO
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has a
defectivethermistor switch.
See pages 50for the steps and illustrations.
NO
See step 4.
Is there
continuity
through the
thermistor
wires?
See step 5.Does the
motor run?
See motor
test section.
Motor will not start:
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or replace
the power Cord.
NO
Replace
Potentiometer.Pressure Switch
Connect a test
transducer to
the board.
Does the
motor run?
Replace thetransducer.
Replace Control
Board.
Yes
No No
Control Board 237659
Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600
49
-
7/26/2019 teste de placas graco.pdf
50/107
Potentiometer
BlackBlack
N
L
White
M+ M-
Blk
Blk/Wht
Motor
Transducer
On/Off
Switch Red
TS
TS
Control Board 237659
Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600
Step 1Cord plugged in.
Switch ON.
Wires connected
to control board.
Meter set to AC Volts.
110-120 AC
V
-
White
ControlBoard
NL
-
+
Black
Black to L
Black to power cord
Step 2
Cord plugged in.Switch ON.
Wires connected
to ON/Off Switch.
110-120 AC
V
-Meter set to AC Volts.
On/Off
Switch+
-
M+ M-
Blk
Blk/Wht
Motor
Red
TS
TS
ControlBoard
100 + DC
V
Step 3
Cord plugged in.
Switch ON.Pressure Switch
Turned to high.
Meter on DC volts.
-
+ -
-
BEEP Checking the motor
thermistor switch .
Meter should read
continuity. Note: motor
should be cooled down.
Step 4
M+ M-
Blk
Blk/Wht
Motor
Red
TS
TS
ControlBoard
+
-
+
Potentiometer
Cord plugged in.
Switch ON.
Potentionmeter
disconnected.
Control
Board
Step 5
50
-
7/26/2019 teste de placas graco.pdf
51/107
NO
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows lowresistance replace motor.
The motor has a
defective thermistor .
NO
See step 4.
Is there
100K Ohmsthrough the
thermistor
wires?
See step 5.
Does the motor run?
See motor
test section.
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or replace the
power Cord.
NO
Replace Potentiometer.
Pressure Switch
(695,795,1095)
Motor will not Run:
Control Board 240168
See pages 52for the steps.
Connect a test
transducer to
the board.
Does the
motor run
Replace the
transducer.
Replace the
Control
BoardYes
No No
Jumper notnot cut.
Remove the control box cover.
Turn the sprayer on. Observe
the control boards Red light.
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light oncontinuously
Flashing
No light
51
-
7/26/2019 teste de placas graco.pdf
52/107
BLACK
BLACK
WHITERED (+)
BLACK()
GREEN
VIOLET
PressureTransducer
ON/OFFSwitch
Power SupplyCord
Potentiometer
from Motor
Ground YELLOW
M-
L1 L2
M+
J4
Control
Board
Step 1
Cord plugged in.
Switch ON.
Wires connected
to control board.
110-120 AC
V
-
WHITE
M-
L1 L2
M+
BLACK
-
+
Step 2
Cord plugged in.Switch ON.
Wires connected
to ON/Off Switch.
Control
Board
110-120 AC
V
-
WHITE
M-
L1 L2
M+
BLACK
-
+
100 + DC
V
Step 3
Cord plugged in.
Switch ON.Pressure Switch
Turned to high.
Meter on DC volts.
-
Control
Board
WHITE
M-
L1 L2
M+
BLACK+
-
J12
Potentiometer
Cord plugged in.
Switch ON.
Potentionmeter
disconnected.
Control
Board
Step 5
Control
Board
Checking the motor thermistor .
Unplug the yellow wires.
Meter should read 100K
Note: motor should be cooled down.
Step 4
YELLOW
J4
-
100k ohm
+
-
(695,795,1095)
Control Board 240168
1095 Only
52
-
7/26/2019 teste de placas graco.pdf
53/107
NO
Replace the
power switch.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has adefective
thermistor switch.
NO
See step 4.
Do you have
open through
the thermistor
wires?
See step 5.
Does the motor run?
See motor
test section.
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
See step 3.
Is there over
100 DC volts?
YES
YES
Repair or
replace the
power Cord.
NO
Replace Potentiometer.
Pressure Switch
(695,795,1095)
Motor will not run:
Control Board 244237
See pages 54for the steps.
Connect a test
transducer to
the board.
Does the
motor run
Replace the
transducer.
Replace the
Control
BoardYes
NoNO
Remove the control box cover.
Turn the sprayer on. Observe
the control boards Red light.
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
53
-
7/26/2019 teste de placas graco.pdf
54/107
-
Potentiometer
PressureTransducer
ON/OFF
Switch
Black
Display
Motor
Green
L2L1
D11
J7 J12 J10 J9
WhiteBlack
Red
Blk
Yel
Yel
White
Red LED
Control
Board
Step 1
Cord plugged in.
Switch ON.
Wires connected
to control board.
110-120 AC
V
-
+
- L2L1
WhiteBlack
+
Step 2Cord plugged in.
Switch ON.
Wires connected
to ON/Off Switch.
110-120 AC
V
-
+-
Control
Board
100 + DC
V
Step 3
Cord plugged in.
Switch ON.
Pressure Switch
Turned to high.
Meter on DC volts.
-
J7
Red
Blk
Yel
Yel
+-
Control
Board
J7
Red
Blk
Yel
Yel
-
J12
Potentiometer
Cord plugged in.
Switch ON.
Potentionmeter
disconnected.
Control
Board
Step 5
(695,795,1095)
Control Board 244237
Checking the motor
thermistor switch .
Meter should read
continuity. Note: motorshould be cooled down.
Step 4BEEP
54
-
7/26/2019 teste de placas graco.pdf
55/107
Replace the
On/Off Switch.
If motor is hot let
cool and retest, if
step 4 still shows low
resistance replace motor.
The motor has a
defective thermistor .
NO
See step 3.
Is there
100K Ohms
through the
thermistor
wires?
See step 4.
Does the motor run?
See step 2.
Do you have
over 100 AC
volts?
See step 1.
Do you have
over 100 AC
volts?
NO
YES
YES
YES
Repair or replace the
power Cord.
NO
Replace Potentiometer.
Pressure Switch
Control Board 287941 (With GFI Filter Coil)
(695ll, 795II,1095ll,1595ll)
Motor will not Run:
See pages 56for the steps.
Connect a test
transducer to
the board.
Does the
motor run?
Replace the
transducer.
Replace the
Control
BoardYes
No No
YES
Remove the control box cover.
Turn the sprayer on. Observe
the control boards Green light.
See Error Code
section for further
troubleshooting.
Once Normal operation.
Light on
continuously
Control board
commanding
motor to run.
Flashing
No light
55
-
7/26/2019 teste de placas graco.pdf
56/107
287941 Only
Watch Dog Switch
On/ Open
Off /Closed
Transducer
Potentiometer
On/Off
Switch
Motor
To Optional
Display
GFI Filter Coil
on 287941updated 287247
15 amp closed
20 amp open
Switch
Power Cord
Control Board 287247,287941 (With GFI Filter Coil)
(695ll, 795II,1095ll,1595ll,MarkIV,MarkV)
Control
Board
Step 1
Cord plugged in.
Switch ON.
Wires connected
to control board
and On-Off switch.
Meter on AC Volts.
110-120 AC
V
-
WHITEBLACK
On/Off
Switch WHITEBLACK
BLACK
+
-
Power Cord
Control
Board
Step 2
Cord plugged in.
Switch ON.
Wires connected
to control board
and On-Off switch.
Meter on AC Volts.
110-120 AC
V
-
On/Off
Switch WHITEBLACK
BLACK
+
-
Power Cord
Checking the motor
thermistor .
Unplug the yellow
wires. Meter should
read 100K. Note: motor
should be cooled dow
Step 3
-
100k ohm
+- To Motor
Blk
Step 4
Control Board
Cord plugged in.
Switch ON.
Potentiometer
disconnected.
ControlBoard
Neutral
Black
Black
56
-
7/26/2019 teste de placas graco.pdf
57/107
NO
Replace the
Filter.
If motor is hot let
cool and retest, if
step 4 still shows an
open replace motor.
The motor has adefective
thermistor switch.
NO
See step 5.
Is there
continuity
through the
thermistorwires?
See step 6.
Does the
motor run?
See motor
test section.
See step 2.
Do you have
over 100 AC
volts?
YES
See step 1.
Do you have
over 100 AC
volts?
YES
YES
See step 4.
Is there over
100 DC volts?
YES
YES
Repair or
replace thepower Cord
NO
Replace Potentiometer.
(Pressure Switch)
(1595, MarkV)
Motor will not run:
Control Board 244232
See pages 58for the steps.
Replace the
power switch.
NO
See step 3.
Do you have
ov