teste de placas graco.pdf

Upload: glauber-aquino

Post on 01-Mar-2018

247 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/26/2019 teste de placas graco.pdf

    1/107

    Rev. N 10/11 /07

    Electrical and Mechanical Repair Tips

    WARNINGThis manual should only be used

    by a qualified Service Technician.

    For Contractor Sprayers

    -

    -

    Black

    Red

    Yel

    Yel

    3.00

    First choice whenquality counts.

  • 7/26/2019 teste de placas graco.pdf

    2/107

    Table of Contents

    Basic meter terminology and testing procedures...............................................................................................5-11

    Error Code Chart .............................................................................................................................................12-28

    Brushless type motor test Ultra-Max IIs ........................................................................................................ 20,21

    Brush type motor test............................................................................................................................................ 22

    Electric Sprayers

    241989 Control board (190ES,SPX, 295ST):

    Motor will not start ............................................................................................................................. 31,32

    Motor Test ............................................................................................................................................... 22

    Motor will not shut off............................................................................................................................ 29

    245892 Control board (190ES, SP, SPX, ST, STX):

    Motor will not start ............................................................................................................................. 33,34

    Motor Test ............................................................................................................................................... 22

    Motor will not shut off............................................................................................................................ 29

    253118 Control Board (190ES, Models 232900F, 232901E, 233797E, 233815E)

    Motor will not start ............................................................................................................................. 35,36

    Motor Test ............................................................................................................................................... 22 Motor will not shut off............................................................................................................................ 29

    249052 C (390 , Performance 390, Nova 390 ):

    Motor will not run .............................................................................................................................. 37,38

    Motor test ............................................................................................................................................ .....22

    Motor will not shut off............................................................................................................................ 39

    235707, 235008 Control Board (390ST, 390STS, 395ST, 450ST, 455ST, Duron 390, 395, 495, Nova SP,

    SPX):

    Motor will not run ................................................................................................................................... 40

    Motor test ................................................................................................................................................ 41

    Motor will not shut off............................................................................................................................ 42

    241990 Control Board (395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super):

    Motor will not run .............................................................................................................................. 43,44

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

    246379 Control Board (Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595, Performance Max

    395/495/595, ST Max 395/495/595):

    Motor will not run .............................................................................................................................. 45,46

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

    287909 Control Board (490II, 495II, 595II):

    Motor will not run .............................................................................................................................. 47,48

    Motor test ........................................................................................................................................... 20,21

    Motor will not shut off............................................................................................................................ 29237659 Control Board (Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600):

    Motor will not run .............................................................................................................................. 49,50

    Motor test ................................................................................................................................................ 22

    Motor will not shut off ............................................................................................................... 29240168 Control Board (695,795,1095):

    Motor will not run .............................................................................................................................. 51,52

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

  • 7/26/2019 teste de placas graco.pdf

    3/107

    244237 Control Board (695,795,1095):

    Motor will not run .............................................................................................................................. 53,54

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

    287247,287941 Control Board (695II, 795II, 1095II, 1595II, MarkIV, MarkV):

    Motor will not run .............................................................................................................................. 55,56

    Motor test ........................................................................................................................................... 20,21

    Motor will not shut off............................................................................................................................ 29

    244232 Control Board (1595 Mark V):

    Motor will not run .............................................................................................................................. 57,58

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

    239750,239751 Control board located under sprayer (1500,1595, Mark V):

    Motor will not run ......................................................................................................................... 59,60,61

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 29

    236563 Control Board, Retrofit Kit 236974 (1000,900,750 and 500, 590,700 updated control boxes)

    Motor will not run .............................................................................................................................. 62,63

    Motor test ................................................................................................................................................ 22

    Motor will not shut off............................................................................................................................ 64

    Electr ic Motor Kit for Convert ible Sprayers

    236528 Control Board (GM 5000):

    Motor will not run .............................................................................................................................. 65,66

    236528 Control Board (GMAX 5900):

    Motor will not run .............................................................................................................................. 67,68

    Motor runs, no AC output to sprayer control board. .......................................................................... 69,70

    246129 & 246125 Control Board (GH 200/230/300 Convertible Sprayer):

    Motor will not run ................................................................................................................................... 71

    GasPoweredSprayers

    238672 Control Box (GM3000):

    Fluid Pump will not run...................................................................................................................... 72,73

    Fluid Pump will not shut off.................................................................................................................... 74

    287486 Control Board (GMAX Sprayers 3400):

    Fluid Pump will not run...................................................................................................................... 75,76

    Fluid Pump will not stop pumping .......................................................................................................... 30

    239056, Retrofit Kit 239693, 239266, 236974 (GM Sprayers 3500,3012,5000,7000):

    Fluid Pump will not run...................................................................................................................... 77,78

    Fluid Pump will not shut off.................................................................................................................... 79

    220974, 221033, 222369 Pressure Control With Bourdon Tube (GM Sprayers 3500,5000):

    Fluid Pump will not run...................................................................................................................... 80,81

    Fluid Pump will not shut off.................................................................................................................... 82

    241093 Control Board (Non-Display), (3900,5900,7900):

    Fluid Pump will not run................................................................................................................. 83,84,85

    Fluid Pump will not stop pumping .......................................................................................................... 30

    245394 Control Board (Display), (3900,5900,7900):

    Fluid Pump will not run...................................................................................................................... 86,87

    Fluid Pump will not stop pumping .......................................................................................................... 30

  • 7/26/2019 teste de placas graco.pdf

    4/107

    287516 Control Board: GMax II Sprayers (Display and Non-Display), (3900,5900,7900):

    Fluid Pump will not run...................................................................................................................... 88,89

    Fluid Pump will not stop pumping .......................................................................................................... 30

    237373 Control Board, Retrofit Kit 237669 (GM 10,00, GMax 10,000)

    Fluid Pump will not run...................................................................................................................... 90,91

    Fluid Pump will not stop pumping .......................................................................................................... 92

    HydraMax Sprayers:

    Operational Overview ............................................................................................................................. 93

    Piston rod stuck in the up position........................................................................................................... 94

    Piston rod stuck in the down position...................................................................................................... 95

    Control Board Off.................................................................................................................................... 96

    LineStripers

    238672 Control Board (GM3000 LineLazer):

    Fluid Pump will not run...................................................................................................................... 72,73

    Fluid Pump will not stop pumping .......................................................................................................... 74

    287486 Control Board (LineLazer 3400):

    Fluid Pump will not run...................................................................................................................... 75,76

    Fluid Pump will not stop pumping .......................................................................................................... 30220974, 221033, 222369 Pressure Control With Bourdon Tube (GM LineLazer 3500,5000):

    Fluid Pump will not run...................................................................................................................... 80,81

    Fluid Pump will not shut off.................................................................................................................... 82

    241543 Updated Control Board (GM LineLazer 3500,5000)

    Fluid Pump will not run................................................................................................................ 97,98,99

    Fluid Pump will not shut off.................................................................................................................. 30

    241093 Control Board LineLazer (3900II, 5900II)

    Fluid Pump will not run................................................................................................................. 83,84,85

    Fluid Pump will not stop pumping .......................................................................................................... 30

    245512 Control Board(LineLazer 3900III, 5900III):

    Fluid Pump will not run.................................................................................................................. 100.101

    Fluid Pump will not stop pumping .......................................................................................................... 30287689 Control Board(LineLazer 3900IV, 5900IV):

    Fluid Pump will not run.................................................................................................................. 102,103

    Fluid Pump will not stop pumping .......................................................................................................... 30

    Engine Generator Test ........................................................................................................................... 104

    Sensor Test ............................................................................................................................................ 105

    Light Kit Troubleshooting..................................................................................................................... 106

    4

  • 7/26/2019 teste de placas graco.pdf

    5/107

    BASIC ELECTRICAL TERMINOLOGYIn any discussion of electricity, there are three basic terms you will need to understand.

    CURRENT

    VOLTAGE

    RESISTANCE

    CURRENT:

    Current is the movement of the electrical charge.Current Flows through the wires from the power source to the load.

    Current is measured in AMPERES (AMPS, A or I). See Figure 1.

    NOTE: Meter is only clamped around one wire.

    VOLTAGE:

    Voltage is the force that causes current to flow in a circuit.

    Voltage is measured in VOLTS (V or E). See Figure 2.

    FIGURE 1

    FIGURE 2

    ON/OFF

    Switch

    Ref 58

    PowerPlug

    Red (+)

    White

    Black

    Green

    Black ()

    Black

    from Motor

    ON/OFF

    Switch

    Ref 58

    Power

    Plug

    Potentiometer Ref 37

    Red (+)

    White

    Black

    Green

    Black ()

    Black

    120 AC

    V

    Motor

    5

  • 7/26/2019 teste de placas graco.pdf

    6/107

    BASIC ELECTRICAL TERMINOLOGY

    RESISTANCE:

    Resistance is anything that causes an opposition to the flow of current in a circuit.Resistance is used to control the amount of voltage and/or amperage in a circuit.

    Resistance is measured in OHMS - . See Figure 3.A common component check would be motor and clutch field windings.

    FIGURE 3

    -

    -

    Black

    Red

    Yel

    Yel

    Known Value

    -

    Known Value

    +

    -

    6

  • 7/26/2019 teste de placas graco.pdf

    7/107

    CONTINUITY TESTING

    Checking continuity is one of the most common tests in electrical troubleshooting. Continuity is the ability of a wire or electrical component to

    conduct current. When you use a continuity tester, you connect a circuit (the continuity tester) that you know works, to a wire or a component that

    may or may not work. The continuity tester will tell you if the wire or component is capable of conducting current.

    Continuity testers are available at almost any hardware store.

    A volt-ohmmeter or VOM can also be used to check continuity. This meter can be purchased at most electrical or electronic supply stores.

    To test a component for continuity:

    1 Check the tester by connecting the leads.

    * If using a test light the light should turn on.

    * If using a digital volt-ohmmeter, the screen should show 00 if OL appears the meter needs to be repaired.

    SWITCH TESTING-ROCKER

    Common test procedure for a SPST Switch:

    0.000

    7

  • 7/26/2019 teste de placas graco.pdf

    8/107

    WIRE CONTINUITY TESTING

    Continuity testing will NOT find wire fragmentation!!

    Example:

    120 Vac input static voltage and drops to 119Vac load voltage.

    A good piece of wire will carry line and load voltage.

    Damaged / Fragmented Wire Damaged / Fragmented Wire

    Pinched Wire

    120 Vac input static voltage and drops to 76Vac load voltage.

    Other causes:

    Poor stripping of outer insulation.

    Poor crimp.

    A defective piece of wire may carry line voltage but will NOT carry load voltage

    8

  • 7/26/2019 teste de placas graco.pdf

    9/107

    GROUND TESTING

    Every corded electric sprayer that comes into your shop for repair should be tested as described below, to make sure that it is properly grounded.

    Pull the machines plug out of the wall outlet and connect one lead from a DC continuity test light or a VOM to the (round) ground terminal on the

    plug.

    NOTE:

    If the ground terminal is broken off of the plug, install a new plug.

    Touch the test light (or VOM) leads to several bare metal surfaces on the body of the machine. If the light (or meter) indicates continuity, the machine

    is properly grounded. If the light (or meter) doesnt indicate continuity trace through the ground (green) wiring on the machine to determine where

    the break is.

    Improper installation or alteration of grounding plug could results in risk of electric shock, fire or explosion that could cause serious injury or death.

    The other function of the grounding plug is to protect the control board from static build up. If the plug is missing this could cause permanent damage

    to the control board.

    9

  • 7/26/2019 teste de placas graco.pdf

    10/107

    CAPACITOR TESTING:

    A capacitor is an electrical component that stores electricity. Capacitors are usually used to help start a motor or make a motor run more efficiently.

    The following instructions can be used to test any capacitor.

    WARNING!A CAPACITOR CAN SHOCK YOU EVEN WHEN A MACHINE IS UNPLUGGED. NEVER TOUCH CAPACITOR TERMINALS WITH

    YOUR FINGERS. ALWAYS USE TOOLS WITH INSULATED HANDLES. NEVER DISCHARGE A CAPACITOR NEAR FLAMMABLE

    LIQUIDS OR VAPORS.

    1 Visually inspect the capacitor for leaks, mechanically damage or loose terminals. Replace it if any of these problems exist.

    2 Unplug the machine and remove the capacitor(s).

    If capacitor(s) are attached to the control board the test can not be performed.

    3 SEE ABOVE WARNING Using a screwdriver with

    insulated handles, hold so that the blade contacts the

    capacitor terminals as shown in Fig. A. This will

    discharge the capacitor.

    4 Put a volt-Ohm meter on the R X 100 scale.

    5 While watching the meter, connect the 2 leads to the 2 terminals on the capacitor.

    If the capacitor is good, the meter needle will go to the right (toward 0 resistance) (Fig. 1), then to the left (toward - maximum resistance)

    If the meter needle goes all the way to the right and stays there, the capacitor is defective.(Fig.2)

    If the meter needle stays all the way to the left (doesn't move at all when connected to the capacitor), the capacitor is defective.(Fig. 3)

    FIG. A

    Capacitor

    GOOD BAD BAD

    10

  • 7/26/2019 teste de placas graco.pdf

    11/107

    RECTIFIER

    (See Fig. 1) Now we come to the most popular application of the diode: rectifcation. Simply rectifcation is the conversion of alternating

    current (AC) to direct current (DC). This almost always involves the use of some device that only allows one-way flow of electrons.

    As we have seen, this is exactly what a diode does.

    RECTIFIER TESTING:

    The following instructions can be used to test any bridge rectifer.Use a DC continuity test light or a VOM (on the R x 100 scale) for all tests.

    Disconnect all wires from the rectifer.

    AC

    AC

    +-

    FIG. 1

    1 Connect test leads as shown in Figure A. If the meter beeps, the rectifer is

    defective. If the meter does not beep, go to the next step.

    2 Connect test leads as shown in Figure B. If the meter does not beep, the

    rectifer is defective. If the meter beeps, go to the next step.

    3 Connect test leads as shown in Figure C. If the meter beeps, the rectifer is

    defective. If the meter does not beep, go to the next step.

    4 Connect test leads as shown in Figure D. If the meter does not beep, the

    rectifer is defective. If the meter beeps, go to the next step.

    5 Connect test leads as shown in Figure E. If the meter beeps, the rectifer isdefective. If the meter does not beep, go to the next step.

    6 Connect test leads as shown in Figure F. If the meter does not beep, the rectifer is defective. If the meter beeps, go to the next step.

    7 Connect test leads as shown in Figure G. If the meter beeps, the rectifer is defective. If the meter does not beep, go to the next step.

    8 Connect test leads as shown in Figure H. If the meter does not beep, the rectifer is defective. If the meter beeps, the recti fer is good.

    0.000OL OL 0.000

    0.000OL OL 0.000

    FIG. A FIG. B FIG. C FIG. D

    FIG. E FIG. F FIG. G FIG. H

    DC DC

    11

  • 7/26/2019 teste de placas graco.pdf

    12/107

    Instruction for checking the ERORR CODES:

    1. Relieve pressure leave prime valve open and power switch OFF.

    2. If sprayer has no display, remove the control box cover to view the control board LED status light.

    3. Plug sprayer into correct AC power, grounded outlet.

    4. Turn pressure control knob clockwise turn.5. Turn Power switch ON.

    6. View digital display. If digital display is not available, view the control board LED status light

    instead.

    The Codes below ar e for several different models.

    DIGITAL

    DISPLAY

    CONTROL BOARD

    STATUS LIGHT.INDICATION

    GO TO

    PAGE

    Digital_Display

    _BlankNever Lights No power to microprocessor on control board. 13

    - - - -

    PSI icon not

    blinking

    Blinks once and stops Power to board is ok, No RUN command to motor.

    14

    - - - -

    PSI iconblinking

    Constant on Control is commanding motor to run. 15

    Unreadable 1 Blink every 3 seconds

    Board is trying to start up. Unplug transducer, pot

    and display. If still blinking replace board. If itstops blinking one of the 3 parts are faulty.

    Reconnect the parts one at time to find the faulty

    part.

    Displays high

    pressure Improper pressure signal from transducer 16

    E=02 Blinks 2 x repeatedly High pressure signal from transducer 17

    E=03 Blinks 3 x repeatedly Transducer failure or connection error 18

    E=04 Blinks 4 x repeatedly Excessive Wall voltage 19

    E=05 Blinks 5 x repeatedly High current or motor is not turning. 20-22E=06 Blinks 6 x repeatedly

    Motor is too hot or motor/thermal device

    connection may be bad.23

    E=07 Blinks 7 x repeatedly Exceeded 2000 psi during timed flush cycle. 24

    E=08 Blinks 8 x repeatedly Low wall voltage 24

    E=09 Blinks 9 x repeatedly Motor sensor failure 25

    E=10 Blinks 10 x repeatedly High control board temperature 26

    E=11 Blinks 11 x repeatedly Excessive motor speed 26

    E=12 Blinks 12 x repeatedly High Current 27

    E=13 Blinks 13 x repeatedly Model not selected 27

    EMPTY Watchdog mode is activated. Sprayer will stop

    running when pressure drops sharply28

    Cal

    Older Ultra-Maxs

    Unplug the display, If sprayer operates Replace the

    Display. If the sprayer does not operate replace thecontrol board.

    8888Digital Display Switches

    not set.

    Set switches on back of digital display to the

    appropriate settings.

    Motor Hums Constant onPerform appropriate motor tests, if motor tests ok,

    replace control board.

    12

  • 7/26/2019 teste de placas graco.pdf

    13/107

    Symptoms: Sprayer does not run at all

    Digital Display is blank

    Control board status light never lights

    What does this mean?No power to the control board or display or control board is likely the problem.

    Troubleshooting Procedure:

    1. Set sprayer to OFF. Unplug digital display. Set sprayer to ON. If sprayer runs, replace display. If not, go to

    next step.

    2. Set sprayer ON and check for A.C. voltage at the control board. If no voltage, check power source andwiring back to power cord.

    3. Set sprayer to OFF and disconnect power to sprayer.Check continuity from power cord plug (through

    power switch) to control board.

    4. If power cord, switch, EMI filter and wiring continuity is ok, replace control board.

    13

  • 7/26/2019 teste de placas graco.pdf

    14/107

    Symptoms: Sprayer does not run at all

    Digital Display shows dashes and Psi icon is not blinking

    Control board status light blinks once when switch is turned on but then stays off.

    What does this mean?Power to board is ok but there is no RUN command to the motor. Either the potentiometer or control board is

    likely the problem.

    Troubleshooting Procedure:

    Check potentiometer & connectionsto control board. Set sprayer to OFF.

    Disconnect potentiometer from control board socket. Check that potentiometer and control board contacts areclean and secure.

    Reconnect potentiometer to control board socket. Set sprayer ON

    and control knob to turn clockwise. If sprayer does not run, set

    sprayer to OFF and go to next step.

    Connect a known good potentiometer to control board socket and set sprayer ON and control knob to turn

    clockwise. If ok, replace pot. Replace control board if sprayer still does not run. But first, verify transducer

    and connections are ok. See next page.

    OR

    Short center pin of socket to each outer pin. Install new potentiometerif sprayer runs. Replace control board if sprayer does not run. But first,

    verify transducer and connections are ok. See next page.

    Check transducer & connectionsto control board. Set sprayer to OFF anddisconnect power to sprayer.

    Disconnect transducer from control board socket. Check that transducer and control board contacts are

    clean and secure.

    Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob to turn

    clockwise. If sprayer does not run, set sprayer to OFF and go to next step.

    Connect a known good transducer to control board socket.

    Set sprayer ON and control knob to turn clockwise. Install new transducer if sprayer runs. Replace control

    board if sprayer does not run.

    _ _ _

    14

  • 7/26/2019 teste de placas graco.pdf

    15/107

    Symptoms: Sprayer does not run at all

    Digital Display shows dashes and Psi icon is blinking

    Control board status light blinks and stays on constant.

    E5 error code brushless unit

    What does this mean?There is power to control board, the potentiometer and transducer are ok and the control is commanding the

    motor to run. Either the motor, motor connections, capacitor connections (brush type motor) or control board is

    likely the problem.

    Troubleshooting Procedure:

    1. Check motor and connections to control board. Also check

    capacitor connections to control board for brush style motor.

    2. Set sprayer to OFF and disconnect power to sprayer.

    3. Disconnect motor connector from control board socket. Check that motor connector and control boardcontacts are clean and secure.

    Check that connections at capacitor are secure. CAUTION

    CAPACITOR MAY STILL HAVE A CHARGE ON IT!

    4. Check motor. Remove pump pin and connect a D.C. voltmeter across two motor wires red & black (brushtype) red, black, blue (brushless type) Spin motor fan and check for a voltage to register on meter. Repeat

    for all motor wire combinations brushless type only. If voltage notpresent, check brushes. If ok, replace

    motor. If voltage present, go to next step.

    5. Reconnect motor connector to control board socket. Connectpower, set sprayer ON and control knob to

    turn clockwise. If sprayer does not run, replace control board.

    _ _ _

    15

  • 7/26/2019 teste de placas graco.pdf

    16/107

    Symptoms: Sprayer does not run at all

    Digital Display shows a pressure reading

    and Psi icon on

    Control board status light off.

    E2 error code Brushless unit (possible)

    What does this mean?Improper pressure signal to control board, with no pressure in sprayer. The transducer or connections is likely

    the problem.

    Troubleshooting Procedure:

    1. Set sprayer to OFF anddisconnect power to sprayer.

    2. Check transducer & connectionsto control board.

    3. Disconnect transducer from control board socket. Check that transducer and control board

    contacts are clean and secure.

    4. Reconnect transducer to control board socket. Connect power; set sprayer ON and control knob to turn

    clockwise. If sprayer does not run, set sprayer to OFF and go to next step.

    5. Connect a known good transducer to control board socket.

    Set sprayer ON and control knob to turn clockwise. Install newtransducer if sprayer runs. Replace control board if sprayer does

    not run.

    XXXX Psi

    16

  • 7/26/2019 teste de placas graco.pdf

    17/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=02

    Control board status light blinks 2x repeatedly.

    What does this mean?The control board is detecting an excessive pressure. The transducer or connections is likely the problem.

    Troubleshooting Procedure:1. Make sure there is no pressure in the system (see pressure relief procedure). Check fluid path for clogs,

    such as clogged filter.

    2. If running Auto Clean, open prime valve and trigger gun.

    3. Use airless paint spray hose with no metal braid. in. x 50 ft minimum. Smaller hose or metal braid hose

    may result in high-pressure spikes.

    4. Set sprayer to OFF anddisconnect power to sprayer.

    5. Check transducer & connectionsto control board.

    6. Disconnect transducer from control board socket. Check that transducer and control board contacts are

    clean and secure.

    7. Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob to turn

    clockwise. If sprayer does not run properly, set sprayer to OFF and go to next step.

    8. Replace transducer. Connect power, set sprayer ON and control

    knob to turn clockwise. Install new transducer if sprayer runs

    properly. Replace control board if sprayer does not run properly.

    E=02

    17

  • 7/26/2019 teste de placas graco.pdf

    18/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=03

    Control board status light blinks 3x repeatedly.

    What does this mean?The control board is not detecting a pressure signal.

    The pressure transducer or connections are likely the problem.

    Troubleshooting Procedure:

    1. Set sprayer to OFF and disconnect power to sprayer.

    2. Check transducer & connections to control board.

    3. Disconnect transducer from control board socket. Check that transducer and control board

    contacts are clean and secure.

    4. Reconnect transducer to control board socket. Connect power, set sprayer ON and control knob

    to turn clockwise. If sprayer does not run, set sprayer to OFF and go to next step.

    5. Connect a known good transducer to control board socket.

    6. Set sprayer ON and control knob to turn clockwise. Install new

    7. transducer if sprayer runs. Replace control board if sprayer does not run.

    8. You can also check transducer resistance with an ohmmeter;

    Between red & black wires less then 9 k ohm and 3-6 k ohm between green & yellow

    wires.

    E=03

    18

  • 7/26/2019 teste de placas graco.pdf

    19/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=04

    Control board status light blinks 4x repeatedly.

    What does this mean?Voltage applied to the sprayer is too high.

    Troubleshooting Procedure:

    1. Make sure the sprayer is plugged into the proper AC power source. Less than 138 volts for 120V

    sprayers and less than 260V for 230V sprayers.

    E=04

    19

  • 7/26/2019 teste de placas graco.pdf

    20/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=05

    Control board status light blinks 5x repeatedly.

    What does this mean?The control is commanding the motor to run but the motor shaft does not rotate. Possibly locked rotor condition,an open connection exists between the motor and control, there is a problem with the motor or control board orthe motor amp draw is excessive.

    Ultamax lls: Brushless motors test when the motor isrunnning at the start of the test. For all others go to step 1.

    With the prime valve open and pressure relieved, start and stop the motor 15 times using the set point pot(Pressure Switch). If the motor restarts each time at no load Motor is probably bad (Resolver in the motor)replace the motor. If the motor will not restart every time then the board is at fault (running on 2 phase) replace

    the circuit board.

    Troubleshooting Procedure ULTRA-MAX II(Brushless Type Motors)

    1. Remove the pump pin and try to run the sprayer. If the motor runs check for locked or frozen pumpor drive train. If sprayer does not run, go to next step.

    2. Set sprayer to OFF and disconnect power to sprayer .

    3. Disconnect motor connector(s) from control board socket(s). Check that motor connector andcontrol board contacts are clean and secure. If tests ok go to step 4.

    5. Spin Test: Test at the large 4-pin motor field connector. Disconnect the fluid pump from thesprayer. Test motor by placing a jumper across pins 1 & 2. Rotate the motor fan at about 2-revolutions/second. A cogging resistance to motion should be felt at the fan. The motor needsreplacing if no resistance is felt. Repeat for pin combinations 1 & 3 and 2 & 3. Pin 4, the greenground wire, is not used in this test. If it tests good go to step 5 Resolver test

    E=05

    Spin Test

    4. Set sprayer to OFF spin the motor fan 1/4 turn. Restart sprayer. If sprayer runs, replace control board.If not, go to step 5.

    Step 1

    4 3 2 1 4 3 2 1

    Step 3

    4 3 2 1

    Step 2

    GRN BLU RED BLK GRN BLU RED BLK GRN BLU RED BLK

    20

  • 7/26/2019 teste de placas graco.pdf

    21/107

    Resolver Test

    NOTE: 490II, 495II and 595II Brushless motors will not have a resolver plug.

    5. Resolver Test: Test the 6-pin Resolver connector on the end of the cable that connects the motor tothe circuit board. Use a volt-ohm meter to test resistance. Should read 44 ohms across pins 1 & 4,167 ohms across pins 2 & 5, and 167 ohms across pins 3 & 6. Inspect the 6 sockets in the connectorto make sure they are not causing a bad connection. Squeeze the socket back to size if one appearstoo large. If it tests good go to step 6.

    6. Field Short Test: Test at the large 4-pin motor field connector. There should not be continuity from

    pin 4, the ground wire, to any of the remaining 3 pins. If it tests good replace the Control Board.

    12

    345

    644 ohms

    Step 1

    12

    345

    6167 ohms

    Step 2

    12

    345

    6

    167 ohms

    Step 3

    7. Checking the motor thermistor: Unplug the Black wires. Set meter to Ohms.

    Meter should read 100K(+ or -)10%. Note: motor should be cooled down.

    -

    100k ohm

    +

    -

    To Motor

    Black

    Control

    Board

    21

  • 7/26/2019 teste de placas graco.pdf

    22/107

    Troubleshooting Procedure for Brush Type Motors:

    1. Remove the pump pin and try to run the sprayer.If the motor runs check for locked or frozen pumpor drive train. If sprayer does not run, go to next step.

    2. Set sprayer to OFF and disconnect power to sprayer .

    3. Disconnect motor connector(s) from control board socket(s). Check that motor connector andcontrol board contacts are clean and secure. If ok go to Step 4.

    4. See capacitor test page. CAUTION - CAPACITOR MAY STILL HAVE ACHARGE! If it test ok go to step 5.

    5. Check motor. Connect a D.C. voltmeter across two motorwires red & black spin the motor fanand check for a voltage to register on the meter. If voltage not present, check brushes. If ok, replacemotor. If voltage present, go to next step.

    6. Reconnect motor connector(s) to control board socket(s). Connect power, set sprayer ON andcontrol knob to turn clockwise. If motor does not run, replace control board.

    OR

    +-9 volt

    battery

    Step 1

    -

    BEEP

    Step 2

    +-

    -

    -

    1-3 ohms

    Step 3

    -

    OL

    +

    Step 4

    Ground

    -

    Checking the motor wires for a short.

    Put the (-) meter lead on the motor case.

    Move the (+) meter lead to each wire.

    Meter should read open on all the wires.

    Perform a spin test by connecting

    a 9 volt battery or larger to the

    motor leads. Motor leads may vary

    in style and size. Locate the 2 wires

    going to the carbon brushes normally

    Red and Black.

    Spin the motor while checking.

    If a open is found replace the motor.

    Checking the motors thermal protection.

    Meter should read continuity or Ohms

    depending on the motor.

    Note: motor should be cooled down.

    Black

    RedYellow

    Black

    RedYellow

    Black

    RedYellow

    Black

    RedYellow

    Use CAUTION not to distort the connectors when inserting the meter probes.

    22

  • 7/26/2019 teste de placas graco.pdf

    23/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=06

    Control board status light blinks 6x repeatedly.

    What does this mean?Motor is too hot or motor/thermal device connections are likely the problem.

    Troubleshooting Procedure:

    Quick test for Ultra Max ll's Only:

    Note: This test is only for the BRUSHLESS MODELS. For all others go to step 1.

    Motor must be cooled down for the test. Unplug thermistor wires from the control board, turn the sprayer on,

    if motor starts the thermistor switch is bad, replace the motor. If motor still does not start or error code is still

    present replace the control board. Step 3 should also be performed if a VOM is available to confirm that the

    thermistor is shorted.

    1. Check thermal sensor and connections to control board. Set sprayer to OFF anddisconnect power to

    sprayer.

    2. Disconnect motor / temp connector from control board socket. Check that transducer and control board

    contacts are clean and secure.

    3. Measuringthe resistance of thethermal device. NOTE: A low resistance reading would be indicating to

    the control board that the motor is hot. The resistance for most motors with yellowsensor wires will be

    about 100 k ohm.If the reading is not correct,replace motor. Motors with a thermal switch you will test

    for continuity.If open replace the motor.

    4. Reconnect motor / temp connector to control board socket. Connect power, set sprayer ON and control

    knob to turn clockwise. If sprayer does not run, replace control board.

    5. If connections are all OK, allow sprayer to cool. If sprayer runs when cool, correct cause of overheating.

    Keep sprayer in cooler location with good ventilation. Make sure motor air intake is not blocked.

    6. If the sprayer still does not run after cooling off, replace the motor.

    E=06

    23

  • 7/26/2019 teste de placas graco.pdf

    24/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=07

    Control board status light blinks 7x repeatedly.

    What does this mean?Pressure exceeded 2000 psi while using the flush timer (AutoClean Timer)

    Troubleshooting Procedure:1. This error only occurs when using the flush timer. Do not use the flush timer mode when spraying.

    2. When using the flush timer for AutoClean , make sure that the gun trigger, prime valve and AutoClean

    valve are all open before starting the motor.

    Symptoms: Sprayer does not run at all

    Digital Display shows E=08

    Control board status light blinks 8x repeatedly.

    What does this mean?Voltage applied to the sprayer is too low.

    Troubleshooting Procedure:

    Make sure the sprayer is plugged into the proper AC power. More then 90 volts for 120V sprayers and at least

    200 volts for 230V sprayers) Check the voltage at the control board. If below 90 or 200 volts repair or replace

    cord or switch. If voltage at the boards is above 90 or 200 replace the control board.

    E=07

    E=08

    24

  • 7/26/2019 teste de placas graco.pdf

    25/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=09

    Control board status light blinks 9x repeatedly.

    What does this mean?The control is not receiving a motor position sensor signal. The resolver or connections is likely the problem.

    (Ultra Max II motors only)

    Troubleshooting Procedure:

    1. Set sprayer to OFF.

    2. Disconnect motor and resolver connectors from control board sockets. Check that connector and controlboard contacts are clean and secure.

    3. Check the resolver connections and resistance. Take three resistance readings at the resolver connector,

    between the two rows. The readings should be about: 44 ohms and 167 ohms twice. If any reading is

    open, replace motor.

    4. Make sure the connector sockets are not (or do not get) spread out or damaged. This may cause the

    motor not to run. If any of the sockets are out of shape or enlarged, the sockets can be pinched tighter

    for a better contact.

    5. Reconnect motor connectors to control board sockets. Set sprayer ON and control knob to turn

    clockwise. If motor does not run, replace control board.

    E=09

    25

  • 7/26/2019 teste de placas graco.pdf

    26/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=10

    Control board status light blinks 10x repeatedly.

    What does this mean?Control board power module high operating temperature. The module

    is likely too hot or motor running too hot.

    (Ultra Max II motors only)

    Troubleshooting Procedure:

    1. Make sure the motor air intake is not blocked

    2. Make sure control board is properly connected to the back plate and that conductive thermal paste isused on the power components.

    3. Replace control board.

    4. Replace motor.

    Symptoms: Sprayer does not run at all

    Digital Display shows E=11

    Control board status light blinks 11x repeatedly.

    What does this mean?Excessive motor speed. The control is sensing abrupt motor speed change. The sprayer drive or motor resolver

    is likely the problem.

    (Ultra Max II motors only)

    Troubleshooting Procedure:

    1. Check for damaged gears or disconnected pump.

    2. Run sprayer at low pressure to check for normal operation.

    3. Replace drive or motor as needed.

    E=10

    E=11

    26

  • 7/26/2019 teste de placas graco.pdf

    27/107

    Symptoms: Sprayer does not run at all

    Digital Display shows E=12

    Control board status light blinks 12x repeatedly.

    What does this mean?The control board is detecting an excessive amp draw. The motor circuit is possibly shorting out, a locked rotor

    condition exists or the control boards has a problem. (Ultra Max II motors only)

    Troubleshooting Procedure:

    1. Set sprayer to OFF.

    2. Disconnect motor connector from control board socket. Check that motor connector and control board

    contacts are clean and secure.

    3. With the motor unplugged turn the control knob fully counter clockwise. Set sprayer ON. If E=12 does

    not display, control board is ok. If E=12 is displayed, control board is faulty, before replacing the board

    check for possible short circuits in motor wiring.

    4. Reconnect motor connector to control board socket.

    5. Set sprayer to OFF. Remove the pump pin and try to run the sprayer. If the motor runs check for locked

    or frozen pump or drive train. If display shows E=12 (or control board status light blinks 12x

    Repeatedly) replace motor.

    Symptoms: Sprayer does not run at all

    Digital Display shows E=13

    Control board status light blinks 13x repeatedly.

    What does this mean?Model select resistors on control board not properly selected.(Ultra Max II motors only)

    Troubleshooting Procedure:Resistors on control board must be properly clipped to identify model type, see replacement control board

    instruction manual.

    E=12

    E=13

    27

  • 7/26/2019 teste de placas graco.pdf

    28/107

    Symptoms: Sprayer does not run at all

    Digital Display shows EMPTY

    What does this mean?

    Watchdog mode is activated. Sprayer will stop running when pressure drops sharply. This prevents pump

    runaway when out of paint, clogged inlet strainer, severe leak.

    Troubleshooting Procedure:Watchdog mode can be deactivated (See sprayer instruction manual)

    To restart the sprayer after a Watchdog trip, turn pressure control to zero and back up or turn power off/ then on.

    EMPTY

    28

  • 7/26/2019 teste de placas graco.pdf

    29/107

    Electric Motor will not shut off:

    1. Relieve pressure, leave prime valve open and power switch OFF.2. Remove the control box cover so the control board status light can be viewed if available.

    Troubleshooting Procedure:

    With a pressure gauge plumbed into the paint hose,

    plug the sprayer in. Turn the power switch on, does

    the gauge read the sprayersmaximum pressure and

    continues to build pressure?

    Mechanical problem: See the properfluid pump manual for the sprayer for

    further trouble shooting procedures.

    Is light on at the control

    board? If the board has no

    light the answer is yes.

    Replace the control board.

    Unplug the transducer from controlboard, does motor stop running?

    Bad transducer, replaceand test with a new one.

    Replace the control board.

    YES

    YES

    YES

    Shorted Board.

    NO

    NO

    NO

    29

  • 7/26/2019 teste de placas graco.pdf

    30/107

    Gas Sprayers (Fluid Pump)runs all the time:

    1. Relieve pressure, leave prime valve open, power switch OFF.

    2. Remove the control box cover.

    Troubleshooting Procedure:

    With a pressure gauge plumbed into the paint

    hose, start the engine. Turn the pump switch on,

    does the gauge read the sprayers maximum

    pressure and continues to build pressure?

    Mechanical problem: See the properfluid pump manual for the sprayer forfurther trouble shooting procedures.

    Unplug the transducer from controlthe board, does the pump stop.

    Bad transducer, replaceand test with a new one.

    Replace the control board.

    NO

    NO

    YES

    YES

    YES

    With the clutch wires plugged in.

    Do you have 10-18 DC Volts

    at the clutch test points?

    NODisconnect the clutch wires from

    the control board. Does the pump

    stop running?

    Mechanical problem in the clutch pinion

    assembly. (Clutch may be to close to the rotor).

    YES

    NO

    Check for a short from the

    2 clutch wires to the frame.

    If shorted repair or replace

    the faulty wire.

    30

  • 7/26/2019 teste de placas graco.pdf

    31/107

    NO

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards light(s).

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has a

    defective

    thermistor switch.

    See pages 32for the steps and illustrations.

    NO

    See step 4.

    Is there

    continuity

    through the

    thermistor

    wires?

    See step 5.Does the

    motor run?

    See motor

    test section.

    Motor will not start:

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace

    the power Cord.

    NO

    Replace

    Potentiometer.Pressure Switch

    190ES,SPX,295ST

    Control Board 241989 (Capacitor on Motor)

    Connect a test

    transducer to

    the board.

    Does themotor run

    Replace the

    transducer.

    Replace

    Control

    Board.Yes

    No No

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    31

  • 7/26/2019 teste de placas graco.pdf

    32/107

    Capacit

    or

    190ES,SPX,295ST

    Control Board 241989

    L2M+TO2 TO1

    L1

    M-

    J12J10

    Black

    Black

    White

    Ground

    Grn

    RedRed Black

    Black

    Yellow

    L2

    L1

    Black

    White

    Control

    Board

    Step 1

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board.

    110-120 AC

    V

    -

    +

    -

    Step 2

    Cord plugged in.

    Switch ON.

    Wires connected

    to ON/Off Switch.

    +

    -

    M+

    M-

    White

    Yellow

    Black

    Control

    Board

    100 + DC

    V

    Step 3

    Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    -

    Potentiometer

    110-120 AC

    V

    -

    J12

    J10

    Step 5

    Potentiometer

    Cord plugged in.

    Switch ON.Potentionmeter

    disconnected.

    Control

    Board

    -

    BEEP

    Checking the motor

    thermistor switch .

    Unplug the 2 yellow

    wires from TO2 and TO1

    Meter should read

    continuity. Note: motor

    should be cooled down.

    L2

    TO2TO1

    L1

    -

    Step 4

    Control

    Board

    (Capacitor on Motor)

    32

  • 7/26/2019 teste de placas graco.pdf

    33/107

    NO

    Replace Potentiometer.

    Pressure Switch

    Replace the

    power switch.

    If moto r is hot letcool and retest, if

    step 6 still shows an

    open replace moto r.

    The motor has a

    defective

    thermistor switch.

    See pages34for the steps and illustrations.

    NO

    See step 4 .Is there

    continuity

    through the

    thermistor

    wires?

    See step 5 .

    Does the moto r run?

    See motor

    test section.

    190ES,DTX,SP,SPX,ST,STX

    (Capacitor on PC board)Control Board 245892

    Motor will not start:

    See step 2.

    Do you haveover 100 AC

    volts?

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    See step 3 .

    Is there over

    100 DC volts?

    YES

    YES

    Repair or repl ace the

    power Cord.

    NO

    Check the motor for a short

    before replacing fuse. See

    moto r test section.If motor

    tests ok install a new fuse

    with the motor

    unplugged.Turn sprayer on,

    if the fuse doesn t open

    replace the motor.

    Is the fuse

    good.

    YES

    NO

    YES

    YES

    Connect a test

    transducer to

    the board.

    Does the

    motor run

    Replace the

    transducer.

    Replace the

    Control

    Board

    Yes

    No No

    Remove the control box cover.Turn the sprayer on. Observe

    the control boards light(s).

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    33

  • 7/26/2019 teste de placas graco.pdf

    34/107

    Pressure

    Transducer

    Motor

    Yellow

    Ground

    Black

    Black

    White

    White

    Green

    FUSE

    J8J7

    NL

    M+ M-

    T01

    T02

    D7

    Red Black

    F1

    Step 1110-120 AC

    V

    -

    White

    FUSE

    NL

    F1

    Black

    Control Board

    -

    +

    Cord plugged in.

    Switch ON.

    Wires connected.

    Reference F1 on the

    Control board for

    proper meter location.

    110-120 AC

    V

    -

    -

    +

    Step 2

    Cord plugged in.

    Switch ON.

    Wires connected

    to ON/Off Switch.

    Control

    Board

    100 + DC

    V

    Step 3Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    Motor

    Yellow

    FUSE

    M+ M-

    T01

    T02

    RedBlack

    F1

    -

    J8

    Step 5

    Potentiometer

    Cord plugged in.

    Switch ON.

    Potentionmeter

    disconnected.

    Control

    Board

    Yellow

    J7

    T01

    T02

    -

    BEEP

    Checking the motor

    thermistor switch .

    Unplug the 2 yellow

    wires from TO2 and TO1

    Meter should read

    continuity. Note: motor

    should be cooled down.

    -

    Step 4

    Control

    Board

    190ES,DTX,SP,SPX,ST,STX

    (Capacitor on PC board)Control Board 245892

    34

  • 7/26/2019 teste de placas graco.pdf

    35/107

    Remove the motor

    cover. See step 1. Do

    you have over 100 AC

    volts?

    Replace pressure

    control switch.

    If motor is hot let cool and

    retest, if step 4 still shows an

    open replace motor. The

    motor has a defective

    thermistor switch.

    Replace

    control board.

    See pages 36 for the steps and illustrations.

    NO

    YES

    See step 3.

    Is there over

    100 DC volts?

    See step 4.

    Is there continuity

    through the

    thermistor wires?

    See step 5.

    Does the motor run?

    NO

    See motor test section.

    YES

    NO

    Replace the

    power switch.

    See step 2.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    Repair or replace the

    power Cord.

    Check the motor for a short

    before replacing fuse. See

    motor test section.If motor

    tests ok install a new fuse

    with the motor

    unplugged.Turn sprayer on,

    if the fuse doesnt openreplace the motor.

    Is the fuse

    good.

    YES

    NO

    YES

    NO

    190ES 232900,F;232901,E;233797,E;233815,E

    Control Board 253118

    Motor will not start:

    YES

    35

  • 7/26/2019 teste de placas graco.pdf

    36/107

    Motor

    L

    Black

    J1

    N

    WhiteF1

    Fuse

    BlackWhite

    Ground

    Green

    Black

    Black

    Yellow

    Red

    Yellow

    White

    Black

    -

    +

    100 + DC

    V

    Step 3

    Cord plugged in.Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    F1

    Fuse

    Red Black

    -

    J1

    Step 5 Cord plugged in.

    Switch ON.

    Pressure switch unplugged.

    Control

    Board

    Insulated Jumper wire

    stripped on the ends

    Pressure

    switch

    Control

    Board

    Checking the motor

    thermistor switch .

    Unplug the motor.

    Meter should read

    continuity. Note: motor

    should be cooled down.

    F1

    Fuse

    Control

    Board

    -

    BEEP

    Yellow Yellow

    -

    Step 4

    Step 1Cord plugged in.

    Switch ON.

    Wires connected.

    Reference F1 on the

    Control board for

    proper meter location.

    NWhite

    F1

    Fuse

    -

    +

    110-120 AC

    V

    -

    110-120 AC

    V

    -

    Step 2Cord plugged in.Switch ON.

    Wires connected

    to ON/Off Switch.

    190ES 232900,F;232901,E;233797,E;233815,E

    Control Board 253118

    36

  • 7/26/2019 teste de placas graco.pdf

    37/107

    NO

    Replace the

    control board.Faulty switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has a

    defective

    thermistor switch.

    See pages38 for the steps and illustrations.

    NO

    See step 5.

    Is there

    continuity

    through the

    thermistor

    wires?

    See step 6.

    Does themotor run?

    See motor

    test section.

    See step 2.

    Do you haveover 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 4.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace

    the power Cord.

    NO

    Replace

    Pressure Switch

    Replace Control Board.No

    249052 Control Board

    Motor will not run

    See step 3. Do

    you have over

    100 AC volts?

    If the fuse is

    blown check

    the motor for

    a short before

    replacing the

    control board.

    NO

    YES

    37

  • 7/26/2019 teste de placas graco.pdf

    38/107

    On/Off

    Switch

    Pressure

    Switch

    Motor

    FUSE

    F1

    Grnd.

    249052 Control Board Trouble Shooting

    J1

    J3J4

    BlkRed

    Yellow

    J3J4

    Control

    Board

    To

    Power Cord

    Step 1

    Cord plugged in.

    Switch ON.Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    -

    On/Off

    Switch

    FUSE

    F1

    J4

    Control

    Board

    Step 2

    Cord plugged in.

    Switch ON.Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    -

    +

    On/Off

    Switch

    FUSE

    F1

    J4

    Control

    Board

    Step 3

    Cord plugged in.

    Switch ON.Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    -

    +

    Blk

    Red

    Yellow

    Control

    Board

    100 + DC

    V

    Step 4Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts

    -

    -

    -

    BEEPChecking the motor

    thermistor switch .

    Unplug the motor

    wires from control

    board.

    Carefully insert the

    meter probes into the

    2 yellow wires.

    Meter should read

    continuity.

    Note: motor should be

    cooled down.

    +

    Yellow

    -

    Step 5

    J1

    Step 6

    Motor plugged in. Cord plugged in.

    Switch ON.

    Pressure switch

    unplugged.

    Control

    Board

    Insulated Jumper wire

    stripped on the ends

    +

    Red

    Blk38

  • 7/26/2019 teste de placas graco.pdf

    39/107

    249052 Control Board Trouble Shooting

    Motor Will Not Shut Off

    With a pressure gauge plumbed into the paint gun

    hose, turn the power switch on, does the gauge readthe sprayers maximum pressure and continue to

    build pressure?

    Mechanical problem: Sprayer cannot build to

    proper pressure. See the proper fluid pumpmanual for further troubleshooting procedures.

    See Fig.1 Unplug the pressure control's (A)plugfrom the control board. Does the motor stop?

    No

    No

    Yes

    Yes

    Replace the pressure control.

    Replace the control board.

    A

    Fig. 1

    Pressure Control

    39

  • 7/26/2019 teste de placas graco.pdf

    40/107

    NO

    Replace the

    power switch.

    NO

    See step 3.

    Is there

    continuity

    through the

    thermistor

    switch.

    See step 5.

    Does the motor run?

    See motor

    test section.

    See step 2.

    Do you haveover 100 AC

    volts?YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    See step 4.

    Is there over

    100 DC volts?

    YES

    Repair or replace thepower Cord.

    See pages 41for the steps.

    235707, 235008 Control Board

    Check all the wiring

    connection to the 2

    small motor wires, if

    ok replace motor. Faulty

    thermistor switch.

    NO

    YES

    Replace Control Board.No

    See step 6.

    Does the presure

    switch test ok?

    YES

    Replace

    Pressure Switch

    Check the pressure transducer for

    hardened paint or damaged or

    worn components. Clean or replace.

    YES

    No

    40

  • 7/26/2019 teste de placas graco.pdf

    41/107

    Black

    -ML

    Black

    N

    White

    110-120 AC

    V

    -

    Cord plugged in.

    Switch ON.

    Wires connected.

    -

    +

    Step 1

    Motor

    Wht/Blk

    RedRed

    Blk

    ThermistorSwitch (NC)

    -

    BEEPChecking the motor

    thermistor switch .Unplug the 2 red wires.

    Meter should read

    continuity. Note: motor

    should be cooled down.

    Step 3

    +-

    +M-M

    Motor Start Board

    BlkWht/Blk

    Control

    Board

    100 + DC

    V

    Step 4Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts

    -

    +

    -

    Black

    -ML

    Black

    N

    White

    110-120 AC

    V

    -

    Cord plugged in.Switch ON.

    Wires connected.

    -

    +

    Step 2

    J5Control

    Board

    Step 5

    Black

    +M-M

    Motor

    Motor Start Board

    L

    Wht/Blk

    Black

    Ground

    White Red WhiteRed

    N

    Blk White

    Thermistor

    Switch (NC)

    Pressure Control

    Switch

    J5

    1

    Cord plugged in.

    Switch ON.

    Pressure Switch

    unplugged.

    Remove pressure control and check the

    micro switch operation with ohmmeter:

    (1) With pressure knob at the lowest setting

    and stem pushed into the control, readings

    should be: white & black = 1 ohm max.

    white & red = open. (2) With pressure knob

    at the highest setting, readings should be:

    white & black = open; white & red =

    1 ohm max. If any of the above tests are not

    correct it's a NO.

    -

    BEEP

    Step 6

    +

    -

    235707, 235008 Control Board Trouble Shooting

    41

  • 7/26/2019 teste de placas graco.pdf

    42/107

    235008 Control Board Trouble Shooting

    Motor Will Not Shut Off

    Yes

    Yes

    NOReplace the PressureControl Assembly .

    Remove pressure control and check themicro switch operation with a ohmmeter:

    (1) With pressure knob at the lowest setting andstem pushed into the control, readings should be:

    white & black = 1 ohm max. white & red = open.

    No Replace the control board.Unplug the pressure transducer switch plug

    from the control board. Does the motor stop?

    With a pressure gauge plumbed into the paint gunhose, turn the power switchon, does the gauge readthe sprayers maximum pressure andcontinue to

    build pressure?

    No

    Yes

    Mechanical problem: Sprayer cannot build toproper pressure. See the proper fluid pump

    manual for further troubleshooting procedures.

    Check the pressure transducer for

    hardened paint or damaged or worncomponents. Clean or replace

    MOTOR

    On/Off Switch

    To Pressure

    Transducer

    E

    A

    B

    CD

    42

  • 7/26/2019 teste de placas graco.pdf

    43/107

    NO

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards light(s).

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has a

    defective

    thermistor switch.

    See pages 44for the steps and illustrations.

    NO

    See step 4.

    Is there

    continuity

    through the

    thermistor

    wires?

    See step 5.Does the

    motor run?

    See motor

    test section.

    Motor will not start:

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace

    the power Cord.

    NO

    Replace

    Potentiometer.Pressure Switch

    Control Board 241990

    (395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super)

    Connect a test

    transducer to

    the board.

    Does themotor run?

    Replace the

    transducer.

    Replace

    Control

    Board.

    Yes

    No No

    See Error Code

    section for further

    troubleshooting.

    OnceNormal operation.

    Go to step 1.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Go to Step 1.

    Flashing

    No light Go to step 1.

    43

  • 7/26/2019 teste de placas graco.pdf

    44/107

    L2M+TO2 TO1

    L1

    M-

    J12J10

    Black

    Black

    White

    Ground

    Grn

    Red

    Black

    Yellow

    L2

    L1

    Black

    White

    Control

    Board

    Step 1

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board.

    110-120 AC

    V

    -

    +

    -

    Step 2

    Cord plugged in.

    Switch ON.

    Wires connected

    to ON/Off Switch.

    +

    -

    M+

    M-

    White

    Yellow

    Black

    Control

    Board

    100 + DC

    V

    Step 3

    Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    -

    Potentiometer

    110-120 AC

    V

    -

    J12

    J10

    Step 5

    Potentiometer

    Cord plugged in.

    Switch ON.Potentionmeter

    disconnected.

    Control

    Board

    Checking the motor

    thermistor switch .

    Unplug the 2 yellow

    wires from TO2 and TO1

    Meter should read

    continuity. Note: motor

    should be cooled down.

    L2

    TO2TO1

    L1

    -

    Step 4

    Control

    Board

    Control Board 241990

    (395/455/495ST Pro, Performance Pro 395/495, NOVA Pro & Super)

    -

    BEEP

    44

  • 7/26/2019 teste de placas graco.pdf

    45/107

    NO

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has adefective

    thermistor switch.

    NO

    See step 4.

    Is there

    continuity

    through the

    thermistorwires?

    See step 5. Does the

    motor run?

    See motor

    test section.

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace the

    power Cord.

    NO

    Replace Potentiometer.

    Pressure Switch

    See pages 46for the steps.

    Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595

    Performance Max 395/495/595, ST Max 395/495/595

    246379 Control Board

    Connect a testtransducer to

    the board.

    Does the

    motor run

    Replace the

    transducer.

    Replace theControl

    BoardYes

    NoNO

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards light(s).

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    45

  • 7/26/2019 teste de placas graco.pdf

    46/107

    Black

    110-120 AC

    V

    -

    -

    +

    Step 2

    Cord plugged in.

    Switch ON.

    Wires connected

    to ON/Off Switch.

    Black

    Control

    Board

    100 + DC

    V

    Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    -

    Motor

    -

    BEEPChecking the motor

    thermistor switch .

    Unplug the J11 2 yellow

    wires from control board.

    Meter should read

    continuity. Note: motor

    should be cooled down.

    +

    Yellow Thermistor

    Wires to motor

    -

    J11

    J8

    J7

    N

    L

    Cord plugged in.

    Switch ON.

    Potentionmeter

    disconnected.

    J8

    ControlBoard

    Step 3

    Step 4

    Step 5

    C15

    White

    110-120 AC

    V

    -

    Cord plugged in.

    Switch ON.

    Wires connected.

    +

    N

    L

    White

    Black

    -

    +

    Power

    Cord

    Step 1

    Yellow Thermistor

    Wires to motor

    Ultra 395/495/595, Ultimate Nova 395/SuperNova 495/595

    Performance Max 395/495/595, ST Max 395/495/595

    246379 Control Board

    Control

    Board

    ControlBoard

    46

  • 7/26/2019 teste de placas graco.pdf

    47/107

    Replace the

    power switch board.

    If motor is hot let

    cool and retest, if

    step 4 still shows low

    resistance replace motor.

    The motor has a

    defective thermistor .

    NO

    See step 4.

    Is there

    100K Ohms

    through the

    thermistor

    wires?

    See step 5.

    Does the motor run?

    See step 2.

    Do you have

    over 100 AC

    volts?

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    YES

    Repair or

    replace

    power

    Cord.

    NO

    Replace Potentiometer.

    Pressure Switch

    Control Board 287909

    (490ll, 495II,595ll)

    Motor will not Run:

    See pages 48for the steps.

    Connect a test

    transducer to

    the board.

    Does the

    motor run?

    Replace the

    transducer.

    Replace the

    Control

    BoardYes

    No No

    See step 3.

    Is there over

    100 AC volts?

    Replace the

    power switch board.YES

    NO

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards Green light.

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    YES

    47

  • 7/26/2019 teste de placas graco.pdf

    48/107

    Ground

    Motor

    L1

    L1

    D21

    L2BL1B

    Yellow

    Yellow

    Green

    Blue

    Red

    Blac

    k

    WhiteBlack

    Black

    White

    Green

    Step 1

    Cord plugged in.Switch ON.

    Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    +

    Ground

    L1

    L1

    L2BL1B

    WhiteBlack

    Black

    Power

    Cord

    -

    Step 2

    Cord plugged in.Switch ON.

    Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    +

    Ground

    L1

    L1

    L2BL1B

    WhiteBlack

    Black

    Power

    Cord

    -

    Step 3

    Cord plugged in.Switch ON.

    Wires connected

    to control board.

    Meter on AC Volts

    110-120 AC

    V

    -

    +

    Ground

    L1

    L1

    L2BL1B

    WhiteBlack

    Black

    Power

    Cord

    -

    Control

    Board

    Step 4

    -

    D21

    Yellow

    Yellow

    To Motor

    -

    J12

    Potentiometer

    Cord plugged in.

    Switch ON.

    Potentiometer

    disconnected.Control

    Board

    Step 5

    Control Board 287909

    (490ll, 495II,595ll)

    Checking the motor

    thermistor .

    Unplug the yellow wires.

    Meter should read 100K

    Note: motor should be

    cooled down.-

    100k ohm

    Transducer

    On/OffSwitch

    Board

    On/OffSwitch

    Board

    On/Off

    Switch

    Board

    On/Off

    Switch

    Board

  • 7/26/2019 teste de placas graco.pdf

    49/107

    NO

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has a

    defectivethermistor switch.

    See pages 50for the steps and illustrations.

    NO

    See step 4.

    Is there

    continuity

    through the

    thermistor

    wires?

    See step 5.Does the

    motor run?

    See motor

    test section.

    Motor will not start:

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace

    the power Cord.

    NO

    Replace

    Potentiometer.Pressure Switch

    Connect a test

    transducer to

    the board.

    Does the

    motor run?

    Replace thetransducer.

    Replace Control

    Board.

    Yes

    No No

    Control Board 237659

    Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600

    49

  • 7/26/2019 teste de placas graco.pdf

    50/107

    Potentiometer

    BlackBlack

    N

    L

    White

    M+ M-

    Blk

    Blk/Wht

    Motor

    Transducer

    On/Off

    Switch Red

    TS

    TS

    Control Board 237659

    Ultra 600,Ultimate 600,Ultra Plus 600,Ultimate Plus 600

    Step 1Cord plugged in.

    Switch ON.

    Wires connected

    to control board.

    Meter set to AC Volts.

    110-120 AC

    V

    -

    White

    ControlBoard

    NL

    -

    +

    Black

    Black to L

    Black to power cord

    Step 2

    Cord plugged in.Switch ON.

    Wires connected

    to ON/Off Switch.

    110-120 AC

    V

    -Meter set to AC Volts.

    On/Off

    Switch+

    -

    M+ M-

    Blk

    Blk/Wht

    Motor

    Red

    TS

    TS

    ControlBoard

    100 + DC

    V

    Step 3

    Cord plugged in.

    Switch ON.Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    + -

    -

    BEEP Checking the motor

    thermistor switch .

    Meter should read

    continuity. Note: motor

    should be cooled down.

    Step 4

    M+ M-

    Blk

    Blk/Wht

    Motor

    Red

    TS

    TS

    ControlBoard

    +

    -

    +

    Potentiometer

    Cord plugged in.

    Switch ON.

    Potentionmeter

    disconnected.

    Control

    Board

    Step 5

    50

  • 7/26/2019 teste de placas graco.pdf

    51/107

    NO

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows lowresistance replace motor.

    The motor has a

    defective thermistor .

    NO

    See step 4.

    Is there

    100K Ohmsthrough the

    thermistor

    wires?

    See step 5.

    Does the motor run?

    See motor

    test section.

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or replace the

    power Cord.

    NO

    Replace Potentiometer.

    Pressure Switch

    (695,795,1095)

    Motor will not Run:

    Control Board 240168

    See pages 52for the steps.

    Connect a test

    transducer to

    the board.

    Does the

    motor run

    Replace the

    transducer.

    Replace the

    Control

    BoardYes

    No No

    Jumper notnot cut.

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards Red light.

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light oncontinuously

    Flashing

    No light

    51

  • 7/26/2019 teste de placas graco.pdf

    52/107

    BLACK

    BLACK

    WHITERED (+)

    BLACK()

    GREEN

    VIOLET

    PressureTransducer

    ON/OFFSwitch

    Power SupplyCord

    Potentiometer

    from Motor

    Ground YELLOW

    M-

    L1 L2

    M+

    J4

    Control

    Board

    Step 1

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board.

    110-120 AC

    V

    -

    WHITE

    M-

    L1 L2

    M+

    BLACK

    -

    +

    Step 2

    Cord plugged in.Switch ON.

    Wires connected

    to ON/Off Switch.

    Control

    Board

    110-120 AC

    V

    -

    WHITE

    M-

    L1 L2

    M+

    BLACK

    -

    +

    100 + DC

    V

    Step 3

    Cord plugged in.

    Switch ON.Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    Control

    Board

    WHITE

    M-

    L1 L2

    M+

    BLACK+

    -

    J12

    Potentiometer

    Cord plugged in.

    Switch ON.

    Potentionmeter

    disconnected.

    Control

    Board

    Step 5

    Control

    Board

    Checking the motor thermistor .

    Unplug the yellow wires.

    Meter should read 100K

    Note: motor should be cooled down.

    Step 4

    YELLOW

    J4

    -

    100k ohm

    +

    -

    (695,795,1095)

    Control Board 240168

    1095 Only

    52

  • 7/26/2019 teste de placas graco.pdf

    53/107

    NO

    Replace the

    power switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has adefective

    thermistor switch.

    NO

    See step 4.

    Do you have

    open through

    the thermistor

    wires?

    See step 5.

    Does the motor run?

    See motor

    test section.

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    See step 3.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or

    replace the

    power Cord.

    NO

    Replace Potentiometer.

    Pressure Switch

    (695,795,1095)

    Motor will not run:

    Control Board 244237

    See pages 54for the steps.

    Connect a test

    transducer to

    the board.

    Does the

    motor run

    Replace the

    transducer.

    Replace the

    Control

    BoardYes

    NoNO

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards Red light.

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    53

  • 7/26/2019 teste de placas graco.pdf

    54/107

    -

    Potentiometer

    PressureTransducer

    ON/OFF

    Switch

    Black

    Display

    Motor

    Green

    L2L1

    D11

    J7 J12 J10 J9

    WhiteBlack

    Red

    Blk

    Yel

    Yel

    White

    Red LED

    Control

    Board

    Step 1

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board.

    110-120 AC

    V

    -

    +

    - L2L1

    WhiteBlack

    +

    Step 2Cord plugged in.

    Switch ON.

    Wires connected

    to ON/Off Switch.

    110-120 AC

    V

    -

    +-

    Control

    Board

    100 + DC

    V

    Step 3

    Cord plugged in.

    Switch ON.

    Pressure Switch

    Turned to high.

    Meter on DC volts.

    -

    J7

    Red

    Blk

    Yel

    Yel

    +-

    Control

    Board

    J7

    Red

    Blk

    Yel

    Yel

    -

    J12

    Potentiometer

    Cord plugged in.

    Switch ON.

    Potentionmeter

    disconnected.

    Control

    Board

    Step 5

    (695,795,1095)

    Control Board 244237

    Checking the motor

    thermistor switch .

    Meter should read

    continuity. Note: motorshould be cooled down.

    Step 4BEEP

    54

  • 7/26/2019 teste de placas graco.pdf

    55/107

    Replace the

    On/Off Switch.

    If motor is hot let

    cool and retest, if

    step 4 still shows low

    resistance replace motor.

    The motor has a

    defective thermistor .

    NO

    See step 3.

    Is there

    100K Ohms

    through the

    thermistor

    wires?

    See step 4.

    Does the motor run?

    See step 2.

    Do you have

    over 100 AC

    volts?

    See step 1.

    Do you have

    over 100 AC

    volts?

    NO

    YES

    YES

    YES

    Repair or replace the

    power Cord.

    NO

    Replace Potentiometer.

    Pressure Switch

    Control Board 287941 (With GFI Filter Coil)

    (695ll, 795II,1095ll,1595ll)

    Motor will not Run:

    See pages 56for the steps.

    Connect a test

    transducer to

    the board.

    Does the

    motor run?

    Replace the

    transducer.

    Replace the

    Control

    BoardYes

    No No

    YES

    Remove the control box cover.

    Turn the sprayer on. Observe

    the control boards Green light.

    See Error Code

    section for further

    troubleshooting.

    Once Normal operation.

    Light on

    continuously

    Control board

    commanding

    motor to run.

    Flashing

    No light

    55

  • 7/26/2019 teste de placas graco.pdf

    56/107

    287941 Only

    Watch Dog Switch

    On/ Open

    Off /Closed

    Transducer

    Potentiometer

    On/Off

    Switch

    Motor

    To Optional

    Display

    GFI Filter Coil

    on 287941updated 287247

    15 amp closed

    20 amp open

    Switch

    Power Cord

    Control Board 287247,287941 (With GFI Filter Coil)

    (695ll, 795II,1095ll,1595ll,MarkIV,MarkV)

    Control

    Board

    Step 1

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board

    and On-Off switch.

    Meter on AC Volts.

    110-120 AC

    V

    -

    WHITEBLACK

    On/Off

    Switch WHITEBLACK

    BLACK

    +

    -

    Power Cord

    Control

    Board

    Step 2

    Cord plugged in.

    Switch ON.

    Wires connected

    to control board

    and On-Off switch.

    Meter on AC Volts.

    110-120 AC

    V

    -

    On/Off

    Switch WHITEBLACK

    BLACK

    +

    -

    Power Cord

    Checking the motor

    thermistor .

    Unplug the yellow

    wires. Meter should

    read 100K. Note: motor

    should be cooled dow

    Step 3

    -

    100k ohm

    +- To Motor

    Blk

    Step 4

    Control Board

    Cord plugged in.

    Switch ON.

    Potentiometer

    disconnected.

    ControlBoard

    Neutral

    Black

    Black

    56

  • 7/26/2019 teste de placas graco.pdf

    57/107

    NO

    Replace the

    Filter.

    If motor is hot let

    cool and retest, if

    step 4 still shows an

    open replace motor.

    The motor has adefective

    thermistor switch.

    NO

    See step 5.

    Is there

    continuity

    through the

    thermistorwires?

    See step 6.

    Does the

    motor run?

    See motor

    test section.

    See step 2.

    Do you have

    over 100 AC

    volts?

    YES

    See step 1.

    Do you have

    over 100 AC

    volts?

    YES

    YES

    See step 4.

    Is there over

    100 DC volts?

    YES

    YES

    Repair or

    replace thepower Cord

    NO

    Replace Potentiometer.

    (Pressure Switch)

    (1595, MarkV)

    Motor will not run:

    Control Board 244232

    See pages 58for the steps.

    Replace the

    power switch.

    NO

    See step 3.

    Do you have

    ov