test report no. 327059€¦ · (test report no. 327059 dated 31/07/2015) sheet 4 of 9 follows...

9
Comp. AV Revis. FT This test report consists of 9 sheets. Sheet 1 of 9 CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval. Istituto Giordano S.p.A. Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia Tel. +39 0541 343030 - Fax +39 0541 345540 [email protected] - www.giordano.it PEC: ist-[email protected] Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v. R.E.A. c/o C.C.I.A.A. (RN) 156766 Registro Imprese di Rimini n. 00 549 540 409 TEST REPORT No. 327059 Place and date of issue: Bellaria-Igea Marina - Italy, 31/07/2015 Customer: UCS ULTRAFLEX CONTROL SYSTEMS S.r.l. - Via XXV Aprile, 45 - 16012 BUSALLA (GE) - Italy Date test requested: 29/06/2015 Order number and date: 67035, 29/06/2015 Date sample received: 30/06/2015 Date test effected: 30/06/2015 Purpose of test: resistance to heat of actuator for smoke and heat exhaust ventilators in accord- ance with standard UNI EN 12101-2:2004 clause 7.5 Test site: Istituto Giordano S.p.A. - Blocco 7 - Via Verga, 6 - 47043 Gatteo (FC) - Italy Origin of sample: sampled and supplied by the Customer Identification of sample received: n. 2015/1696/B Sample name* The test sample is a member of the product family called “Sintesi 24”. (*) according to that stated by the Customer.

Upload: others

Post on 10-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

Comp. AV

Revis. FT This test report consists of 9 sheets.

Sheet

1 of 9

CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.

Istituto Giordano S.p.A.

Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia

Tel. +39 0541 343030 - Fax +39 0541 345540

[email protected] - www.giordano.it

PEC: [email protected]

Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.

R.E.A. c/o C.C.I.A.A. (RN) 156766

Registro Imprese di Rimini n. 00 549 540 409

TEST REPORT No. 327059

Place and date of issue: Bellaria-Igea Marina - Italy, 31/07/2015

Customer: UCS ULTRAFLEX CONTROL SYSTEMS S.r.l. - Via XXV Aprile, 45 - 16012 BUSALLA (GE) -

Italy

Date test requested: 29/06/2015

Order number and date: 67035, 29/06/2015

Date sample received: 30/06/2015

Date test effected: 30/06/2015

Purpose of test: resistance to heat of actuator for smoke and heat exhaust ventilators in accord-

ance with standard UNI EN 12101-2:2004 clause 7.5

Test site: Istituto Giordano S.p.A. - Blocco 7 - Via Verga, 6 - 47043 Gatteo (FC) - Italy

Origin of sample: sampled and supplied by the Customer

Identification of sample received: n. 2015/1696/B

Sample name*

The test sample is a member of the product family called “Sintesi 24”.

(*) according to that stated by the Customer.

Page 2: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 2 of 9 follows

Description of sample*

The test sample is an electric chain actuator for smoke and heat exhaust ventilators with the following speci-

fications:

– voltage supply: 24 Vdc ± 10 %;

– electronic connection: 2 wires;

– operation: by polarity inversion;

– stroke: 380 mm;

– force (in push action): 90 N;

– force (in pull action): 200 N;

– speed: ~ 14 mm/s;

– current absorption (with max load): 1 A;

– parallel connection: yes;

– limit stop: micro switches;

– safety stop: electronic;

– feedback: open/close;

– casing: silver anodized, dark brown anodized, white painted RAL 9010.

The actuator move a ventilator consisting of an outward-opening bottom-hung window fitted in a vertical fa-

cade. The window has the following characteristics:

– window dimension: 500 mm × 700 mm;

– window materials: aluminium profiles and sheet-steel infill.

(*) according to that stated by the Customer.

Page 3: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 3 of 9 follows

Photo of the sample (inner side)

Photo of the sample (outer side)

Page 4: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows

Normative references

Testing was carried out in accordance with the applicable requirements of standard UNI EN 12101-2:2004

dated 01/12/2004 “Sistemi per il controllo di fumo e calore - Parte 2: Specifiche per gli evacuatori naturali di

fumo e calore” (“Smoke and heat control systems - Part 2: Specification for natural smoke and heat exhaust ventilators”) - clause

7.5 “Resistenza al calore” (“Resistance to heat”).

Test apparatus

The test was performed using a vertical furnace, identification code RSF004, with vertical wall provided with

hole size 3 m × 1 m. The furnace is equipped with oil burners and temperature sensors type K thermocouple.

SCHEMATICS DRAWINGS OF THE SAMPLE

(supplied by the customer)

Page 5: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 5 of 9 follows

Test method.

The test is performed according to the Annex G of UNI EN 12101-2 on 3 actuator and 3 ventilator simultane-

ously. The 3 ventilators are included in a single subframe, with external dimensions 2900 mm × 800 mm. The

subframe is inserted in the hole of size 3 m × 1 m of the masonry wall in vertical position. This report con-

tains test results of the actuator “Sintesi 24” installed in the central position of the following drawing and

photo.

DRAWING OF THE TEST VENTILATORS

11001020 500

2900

80

0

70

0

EXTERNAL

INTERNAL

INNER VIEW. OUTWARD-OPENING BOTTOM-HUNG WINDOW

Page 6: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 6 of 9 follows

Photo of masonry with ventilators (internal view)

Test results

Test conditions and test results are set out hereafter in the form of tables and diagrams.

Resistance to heat (in accordance with clause 7.5 of standard UNI EN 12101-2)

Ventilator “B” classification B 300

Furnace heating system No. 4 oil-fired burner

Dimensions of the tested ventilator B = 500 mm

L = 700 mm

Brief description of ventilator mock-up construction materials Aluminium frame, sheet-steel flap

Ventilator mock-up installation type and anchoring assembly

The ventilator mock-up was connected to the actuator by chain without limit arms

Page 7: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 7 of 9 follows

Temperature sensors No. 7 sensors type K thermocouple

Position of thermocouples

The thermocouples are positioned in accordance with standard UNI EN 12101-2 at 0,1 m from the masonry

and 0,1 m from the projection of the ventilators locating hole. No. 3 thermocouples are positioned at the

center of each ventilator, as shown in the following diagram (external view):

T1 T2 T3

T5

T7

T6T4

Temperature change over time

Time T1 T2 T3 T4 T5 T6 T7 Tmean

[min] [°C] [°C] [°C] [°C] [°C] [°C] [°C] [°C]

0 26 26 26 26 26 27 27 27

5 211 198 177 256 220 278 270 256

10 273 272 319 339 348 335 402 356

20 281 298 332 358 363 366 416 376

30 275 275 325 367 363 384 418 383

Tmean is the average temperature of the perimeter sensors T4, T5, T6 and T7.

Sensors T1, T2 and T3 at the center of the ventilators are used for information only.

Page 8: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 8 of 9 follows

Test temperature profiles

After 5 min from start of the burner the evacuator has been operated in its

opening position.

opening time: 22 s

Pass

Notes: during the test the actuator is not detached from the frame and kept the ventilator in open position

without limit arms

RESULT

The actuator “Sintesi 24” passed the test of resistance to heat

Note: This result is valid for the actuator coupled with the window described above

0

50

100

150

200

250

300

350

400

450

500

0 5 10 15 20 25 30

T1

T2

T3

T4

T5

T6

T7

Tmean

Te

mp

era

ture

C]

Time [min]

Page 9: TEST REPORT No. 327059€¦ · (Test report No. 327059 dated 31/07/2015) sheet 4 of 9 follows Normative references Testing was carried out in accordance with the applicable requirements

(Test report No. 327059 dated 31/07/2015) sheet 9 of 9 follows

Photo of the sample during test

Test Technician

(Dott. Floriano Tamanti)

Head of Smoke and Heat Exhaust

Ventilators Laboratory

(Dott. Floriano Tamanti)

Chief Executive Office

(Dott. Arch. Sara Lorenza Giordano)

............................................

............................................

............................................