“test before touch” easier said than done

41
Test Before Touch Test Before Touch Easier Said Than Done Easier Said Than Done Ken Crawford, DuPont Ken Crawford, DuPont Kent Haggerty, Dupont Kent Haggerty, Dupont

Upload: trandiep

Post on 05-Jan-2017

229 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: “Test Before Touch” Easier Said Than Done

““Test Before TouchTest Before Touch””Easier Said Than DoneEasier Said Than Done

Ken Crawford, DuPontKen Crawford, DuPontKent Haggerty, DupontKent Haggerty, Dupont

Page 2: “Test Before Touch” Easier Said Than Done

OverviewOverview

• Test Before Touch (TBT) Principles• Key Learnings by One Company• One Method for Performing a TBT• Induced Voltages • Medium Voltage Testing• Summary & Conclusions

Page 3: “Test Before Touch” Easier Said Than Done
Page 4: “Test Before Touch” Easier Said Than Done

How Would You Verify Power is Off?How Would You Verify Power is Off?

• What would be the plan?• What could go wrong?• What instruments to use?• What PPE is needed?• How to minimize hazards?• Where are the shock and arc hazards?• Are you qualified to work on this equipment?

Page 5: “Test Before Touch” Easier Said Than Done

Key Learnings in One CompanyKey Learnings in One Company• TBT Not Fully Understood• Inadequate Training

– No Planned Approach– Best Practices Not Documented– Did Not Warn of Common Mistakes

• Concepts Seemed Simple• Proper TBT Involves Knowledge and Planning

Page 6: “Test Before Touch” Easier Said Than Done

• Consider All Circuits Energized Until Tested• Test EVERY Conductor To Be Touched• PPE Is Required Until Test is Completed• Test Instrument Must Be Verified• Knowledge of Equipment Is Essential• Test Circuit Again If Job Continuity Is Broken• Testing Must Be Done At Each Location

Where Conductors Are Going To Be Touched

““Test Before TouchTest Before Touch”” (TBT) (TBT) Key PrinciplesKey Principles

Page 7: “Test Before Touch” Easier Said Than Done

Protect the PersonShock Protection

“#” indicates US ANSI voltage class“00” rated 500 volts; “2” rated 17,000 volts

Arc Flash Protection

Page 8: “Test Before Touch” Easier Said Than Done

Selecting The Proper TesterSelecting The Proper Tester

• Zero Indication Must Mean No Voltage Present

• Testers With Limitations– Multi-meters Can Be on Wrong Setting – Some Solenoid Testers May Not Always Indicate– Proximity Testers May Give False Indication

• Voltage Only Tester Should Be Used for TBT• No Single Voltage Tester Will Cover All

Applications

Page 9: “Test Before Touch” Easier Said Than Done

Solenoid Tester LimitationsSolenoid Tester LimitationsSolenoid testers may not indicate backfeed Solenoid testers may not indicate backfeed

from control power transformerfrom control power transformer

M

CA B

Control Power

Transformer

Ground Test Point120V480V

V

C

Solenoid Will Solenoid Will NOTNOT Activate Due to Impedance Activate Due to Impedance of Transformer and Testerof Transformer and Tester

Solenoid Testers With Voltage Indicating Solenoid Testers With Voltage Indicating Lights Are PreferredLights Are Preferred

Blown Fuse

Ground Test Point

Page 10: “Test Before Touch” Easier Said Than Done

Limitations of Proximity TestersLimitations of Proximity TestersMultiMulti--Conductor or Shielded Cables Conductor or Shielded Cables

Require Special AttentionRequire Special AttentionProximity Tester Reads Energized Conductor

Ground Conductor Shields Energized Conductor

Page 11: “Test Before Touch” Easier Said Than Done

Proximity Tester Limitations Proximity Tester Limitations for Low Voltage Testingfor Low Voltage Testing

• Detects AC Voltage Only• Will Not Indicate Voltage Inside

– Grounded Enclosures– Shielded Cables – Internally Wet Cables

• May Not Indicate Voltage if – Cable is Partially Buried– Insulated Test Point is Against Grounded Metal– Operator Isolated From Ground

Page 12: “Test Before Touch” Easier Said Than Done

Testing Method on Testing Method on Low Voltage CircuitsLow Voltage Circuits

1. Test Ground to Phase for all Phases– Keeps Meter at Zero Volts for Most of the Test– Voltage Usually Lower (e.g. 277 Vs. 480)

2. Test Neutral to Phase (if available)– Provides Backup Test to Ground to Phase

3. Test Phase to Phase (if available)– Check Each Phase to All Other Phases (A-B,A-C,B-C)– May be Only Valid Test on Ungrounded Systems

Page 13: “Test Before Touch” Easier Said Than Done

Steps in Performing Steps in Performing Absence of Voltage Absence of Voltage

Tests Tests

Page 14: “Test Before Touch” Easier Said Than Done

Step 1 Step 1 -- Probing Position Probing Position • Place the Red Lead in the Meter

– Reduces Risk of Contact • Black Lead Placed on Ground First and

Removed Last

tester

Page 15: “Test Before Touch” Easier Said Than Done

Step 2 Step 2 -- Check MeterCheck Meter• Verify Meter on Energized Source Before & After

Test• Source Must Be Same Type (AC or DC) As The

Equipment To Be Tested.

Page 16: “Test Before Touch” Easier Said Than Done

Step 3 Step 3 -- Verify Circuit Is Verify Circuit Is ““OffOff””• Verify the Circuit Requiring Work is Turned "Off"

And Any Disconnect Knife Blades Are OpenKnife Blades Are Open

Page 17: “Test Before Touch” Easier Said Than Done

Step 4 Step 4 -- Ground to Phase TestGround to Phase Test• Must be Absolutely Certain of a Reliable Ground

– If Not Sure, Test Ground Point

• Reliable Ground Point Depends on Equipment

t

Page 18: “Test Before Touch” Easier Said Than Done

Step 4Step 4-- Ground to Phase Test Ground to Phase Test -- Cont.Cont.Ground Test Point Depends on the EquipmentGround Test Point Depends on the Equipment

Reliable Ground Test PointReliable Ground Test Point

Not a Reliable Ground Test Point

Page 19: “Test Before Touch” Easier Said Than Done

Reliable Ground Test Point

Not a Reliable Ground Test PointNot a Reliable Ground Test Point

Step 4 Step 4 -- Ground to Phase Test Ground to Phase Test -- Cont.Cont.Ground Test Point Depends on the EquipmentGround Test Point Depends on the Equipment

Page 20: “Test Before Touch” Easier Said Than Done

Test PointsTest Points• The Load Side of Switch Should be Tested First• Never Use Fuse Caps (Ferrules) as a Test Point

– Some Fuses Have Insulated Ferrules

Don’t Test Here

Page 21: “Test Before Touch” Easier Said Than Done

Test Points (contTest Points (cont’’d)d)

Phase Test Points

Test on the Fuse Holder Not the Fuse

Page 22: “Test Before Touch” Easier Said Than Done

Step 5 Step 5 -- Phase to Phase TestPhase to Phase Test

• Check Phase to Phase Even if Ground to Phase Checks Indicate "0" Volts– Provides Backup Check – May Be Only Valid Test on Ungrounded Systems

• Phase to Phase Test Alone Is Not Sufficient

Page 23: “Test Before Touch” Easier Said Than Done

CA B

Blown Fuses or faulty switch

PhasePhase--toto--Phase Test LimitationsPhase Test Limitations

Meter Meter Does NotDoes Not Indicate VoltageIndicate Voltage

xxxxxxxxx

voltmeter

voltmeter

VV

Proximity Tester DoesIndicate Voltage

Page 24: “Test Before Touch” Easier Said Than Done

Task: Replace Motor TTask: Replace Motor T--Leads in Leads in a a

3 Phase Motor Starter3 Phase Motor Starter

What Are The Minimum What Are The Minimum Number of Tests Required?Number of Tests Required?

Page 25: “Test Before Touch” Easier Said Than Done

CA B

Control Power

Transformer

120V480V

Motor

Test Points

M

Testing to Remove Motor Leads for Testing to Remove Motor Leads for 480V Starter480V Starter

A Total of 12 Tests Are Required A Total of 12 Tests Are Required 6 Ground To Phase & 6 Phase to Phase6 Ground To Phase & 6 Phase to Phase

Page 26: “Test Before Touch” Easier Said Than Done

Voltage Measured on Voltage Measured on ““DeDe--energizedenergized””LV Circuit, What Do You Do?LV Circuit, What Do You Do?

• Verify Proper Circuit & Equipment– Check Prints, Labels, Resources

• Determine if Voltage is Induced– Detected by Meters With High Input Z ~ 10 M Ω– Low Input Z Meters Collapse Induced Voltage Z~ 2 kΩ– Verify Voltage Collapses to “0” With Low Z Tester

• Voltage Still Present After Loading Circuit– Check for Backfeed, Equipment Failure

Page 27: “Test Before Touch” Easier Said Than Done

Close Coupling in Cable TrayClose Coupling in Cable Tray

V

High Z Digital Meter Reading 95VHigh Z Digital Meter Reading 95VAnalog Meter Reading 80V Analog Meter Reading 80V Low Z Digital Meter Reading 0VLow Z Digital Meter Reading 0V

Induced Voltage Value Depends Induced Voltage Value Depends on Meter Impedanceon Meter Impedance

Page 28: “Test Before Touch” Easier Said Than Done

Testing Insulated

Conductors

Page 29: “Test Before Touch” Easier Said Than Done

Testing Insulated ConductorsTesting Insulated Conductors• Use a Proximity Tester for a First Test• Should Not Be Used as the Only Test• If No Voltage Indicated

– Wearing PPE, Expose Conductor For Testing– Verify “0” Volts With Contact Meter

• Voltage Indicated with Proximity Tester– Verify Proper Circuit is Locked out– Re-Check source for Induced Voltage Using a High

Impedance Meter– If Voltage is Present, Load Circuit at Switch with a Low

Impedance Meter and Re-check Insulated Conductor

Page 30: “Test Before Touch” Easier Said Than Done

V

Verifying Induced Voltage on Insulated Verifying Induced Voltage on Insulated ConductorsConductors

Low Impedance Meter

Proximity Tester Indicates Induced Voltage on Insulated Conductor

Proximity Tester Does Not Indicate Voltage Due to Circuit Loading by Low Impedance Meter

Proximity Tester

Page 31: “Test Before Touch” Easier Said Than Done

Testing Testing Medium Medium Voltage Voltage CircuitsCircuits

Page 32: “Test Before Touch” Easier Said Than Done
Page 33: “Test Before Touch” Easier Said Than Done

Considerations in Testing Considerations in Testing Medium Voltage SystemsMedium Voltage Systems

• Proximity Testers Often Preferred Due to Strong Electric Fields– Direct Contact Not Required– Only One Probing Stick Needed– Can Test Taped Connections

• Shielded Conductors Cannot Be Tested Except at Terminal Connections– Spiking Tool May Be Necessary to Verify Shielded

Conductors Are De-energized

Page 34: “Test Before Touch” Easier Said Than Done

Shielded Cable - Proximity Tester Will Not Indicate

tttT

Proximity Tester Will Work Here

Medium Voltage Medium Voltage Shielded Cables Require Shielded Cables Require

Special AttentionSpecial Attention

Cable Shield Terminates Here

Page 35: “Test Before Touch” Easier Said Than Done

Which Shielded Cable Is DeWhich Shielded Cable Is De--Energized?Energized?

Page 36: “Test Before Touch” Easier Said Than Done

Gauss Meter For Cable IdentificationGauss Meter For Cable Identification

Page 37: “Test Before Touch” Easier Said Than Done

Spiking ToolSpiking Tool

Page 38: “Test Before Touch” Easier Said Than Done
Page 39: “Test Before Touch” Easier Said Than Done

Summary & ConclusionsSummary & Conclusions

• Consider All Circuits Energized Until Tested• Training and Knowledge Required • Plan for Testing• Use Proper Voltage Tester • Use Appropriate PPE• Test Before Touch Not Always Simple

Page 40: “Test Before Touch” Easier Said Than Done

TestTestEvery Circuit, Every Every Circuit, Every

Conductor, Every Time Conductor, Every Time BeforeBefore You You Touch!Touch!

It Could Save It Could Save Your Your Life!Life!

Page 41: “Test Before Touch” Easier Said Than Done

“Test Before Touch”Easier Said Than Done

Questions?