Tender No: 1800000049 Page 1 of 307 MAZAGON DOCK SHIPBUILDERS LIMITED (Formerly known as Mazagon Dock Ltd.) CIN : U35100MH1934GOI002079 (A Government of India Undertaking) Shipbuilders to the Nation Dockyard Road, Mazagon, Mumbai 400 010. INDIA MODERNISATION OF MDL GUEST HOUSE, MDL, MUMBAI. VOLUME-IV TECHNICAL SPECIFICATION & PREFERRED MAKE

Upload: lamtruc

Post on 16-Apr-2018

236 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 1 of 307

MAZAGON DOCK SHIPBUILDERS LIMITED (Formerly known as Mazagon Dock Ltd.)

CIN : U35100MH1934GOI002079 (A Government of India Undertaking)

Shipbuilders to the Nation Dockyard Road, Mazagon,

Mumbai 400 010. INDIA

MODERNISATION OF MDL GUEST HOUSE, MDL, MUMBAI.

VOLUME-IV

TECHNICAL SPECIFICATION

&

PREFERRED MAKE

Page 2: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 2 of 307

TENDER DOCUMENT

FOR

CIVIL & INTERIOR, PLUMBING, ELECTRICAL,

CCTV, FIRE ALARM & HVAC WORKS

MODERNISATION OF MDL GUEST HOUSE, MDL,

DOCKYARD ROAD, MUMBAI

I N D E X

Sr. No. Description Page Nos.

From To

I GENERAL 3 5

II I S CODE 6 24

III TECHNICAL SPECIFICATIONS-CIVIL WORKS 25 226

IV TECHNICAL SPECIFICATIONS-ELECTRICAL

WORKS

227 279

V TECHNICAL SPECIFICATIONS-HVAC WORKS 280 307

Page 3: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 3 of 307

TECHNICAL SPECIFICATIONS

GENERAL

i. The detailed specifications given hereinafter are for the items of works described in

the schedule of quantities attached herein & shall be guidance for proper execution

of work to the required standards.

ii. It may also be noted that the specification are of generalized nature & these shall be

read in conjunction with the description of item in schedule of quantities &

drawings. The work also includes all minor details of construction which are

obviously & fairly intended & which may not have been referred to in these

documents but are essential for the entire completion in accordance with standard

Engineering practice.

iii. Unless specifically otherwise mentioned, all the applicable codes & standards

published by the Indian standard Institution & all other standard which may be

published by them before the date of receipt of tenders, shall govern in all respects

of dosing workmanship quality & propitious of materials & methods of testing,

method of measurements etc. Wherever any reference to any Indian Standard

specifications occurs in the documents relating to this contract, the same shall be

inclusive of all amendments issued to or revisions thereof, if any, up to the date of

receipt of tenders.

iv. In case there is no I.S.I specification for the particular work, such work shall be

carried out in accordance with the instructions in all respects, & requirements of

the Engineers-in-Charge. Wherever any reference to any Indian standard

specification occurs in the documents relating to this contract, the same shall be

inclusive of all amendment issued there to or revisions thereof, if any, up to the

date of receipt of tenders.

v. The work shall be carried out in a manner complying in all respects with the

requirements of relevant bye-laws of the Municipal Committee/Municipal

Corporation/Development Authority/Improvement Trust under the jurisdiction of

which the work is to be executed or as directed by the Engineer-in-Charge and,

unless otherwise mentioned, nothing extra shall be paid on this account.

vi. Samples of various materials, fitting etc. proposed to be incorporated in the work

shall be submitted by the contractor for approval of the Engineers-in-Charge before

order for bulk supply is placed.

vii. The contractor shall take instructions from the Engineer-in-Charge regarding

collection and stacking of materials in any place. No excavated earth or building

materials shall be stacked on areas where other buildings, roads, services,

compound walls etc. are to be constructed.

viii. The contractor shall maintain in perfect condition all works executed till the

completion of the entire work allotted to him. Where phased delivery is

contemplated, this provision shall apply to each Phase.

ix. The contractor shall give a performance test of the entire installation(s) as per

standard specifications before the work is finally accepted & nothing extra

whatsoever shall be payable to the contractor for the test.

Page 4: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 4 of 307

x. The contractor shall clear the site thoroughly of all scaffolding materials & rubbish

etc. left out of his work & dress the site around the building to the satisfactions &

his decision in writing shall be final & binding on all concerned.

xi. Post construction inspection and testing: After completion of the work and

during maintenance period liability of the contractor, the work shall also be

subjected to 'Post construction inspection and testing'. In case the materials or

articles incorporated in the work are found to be inferior, though the sample

collected for the same might have been passed at the time of execution, it shall be

the responsibility of the contractor to replace the same at his own cost, failing

which the Department may rectify the same at the risk and cost of the contractor or

Department may accept the work as sub-standard, and cost be adjusted from the

outstanding security deposit, as per the terms and conditions of the contract for the

work.

xii. The MDL, shall be the sole deciding authority as to the meaning, interpretations

and implications for various provisions of the specifications and his decision in

writing shall be final and binding on all concerned.

xiii. In case any different or discrepancy between the specification & the

description in the schedule of quantities, the schedule of quantities shall take

precedence. In case of any difference or discrepancy between specification &

drawing, the specification shall take precedence.

A. Pricing The rate for each item of work shall, unless expressly stated otherwise, include the

following (but not limited to the list given below) for the completion of works in all

respects as per conditions of Contract, technical specifications, drawing :

1. All taxes such as Octroi, Sales tax, VAT, Service tax, Royalties, Transportation, Freights, Packing and forwarding charges Insurance , local taxes and all the prevailing taxes etc.

2. All requirements and expenses for completion of work/item as per Rules and Regulations of Local Bodies, State Government and Central Government of India.

3. All materials, equipments, accessories, consumable, controls and instruments, tools, tackles, plants, scaffolding/double scaffolding labour, maintenance, fixing, cleaning, , making good hauling, hoisting etc., for carrying out the item/work.

4. Waste on material and labour. 5. Loading, Unloading, handling/double handling, setting out protection from

weather, temporary supports, platforms, construction of temporary godowns/store for keeping of store etc., and the maintenance, of the same, dismantling of temporary works, disposal of debris and all other labour necessary for the execution of works.

6. Testing the installation as often as necessary, Contractors to arrange for all special instruments and tools required for such testing or getting it tested at approved lab.

7. Painting of all equipment, pipes, and supports etc., as per color codes to be decided for various systems.

8. Fees for testing the materials, equipment or overall installation by appropriate authorities as approved by MDL as per the latest version of IS. The testing lab will be decided by MDL/Consultant. Cost of the testing of materials shall be borne by the contractor.

9. Necessary coordination with all concerned agencies/persons involved in the completion of work.

Page 5: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 5 of 307

10. All requirements of specification and drawings. Description of work given in the schedule of quantities is a brief description and shall be read in conjunction with specifications and drawings whether specifically mentioned or otherwise.

11. Removal of wrappings/ covering and carting away all unwanted material including POP.

The rates quoted by the tenderer will be deemed to be for the finished work complete in all

respects with accessories, fitting, mounting arrangements normally provided with such

equipment and/or needed for execution, completion, safe operation of equipment as

required though they may not have been specifically mentioned in technical specifications,

drawings and/or schedule of equipment.

All minor Masonry, Carpentry and Civil works such as cutting opening in Masonry Walls,

Internal Partitions, Chasing on walls, etc. and making good the same to match existing

works shall be provided by the contractor, whenever, asked for by the Consultant.

Page 6: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 6 of 307

II – LIST OF INDIAN STANDARDS::

Following are the various pertinent Indian Standards, relevant to

buildings work :

(All Latest Versions of I.S. codes shall be referred)

I. S. CODE

NO.

S U B J E C T

A. CIVIL WORKS

1. CARRIAGE OF MATERIALS

4082-1996 Recommendations on stacking & storage of constn. materials and

components at site.

2. EARTH WORK

1200 Pt. I-1992 Method of measurement of Earth work.

4081-1986 Safety code for Blasting and related drilling operations.

6313 (Part 2)

2001

Anti Termite Measures in Buildings Part – 2 Pre-constructional

chemical treatment

3. MORTAR

196-1966 Atmospheric conditions for testing (Reaffirmed - 1990)

269-1989 33 Grade Ordinary, rapid hardening and low heat Portland cement

383-1970 Coarse and fine aggregates from natural sources for concrete.

455-1989 Portland blast furnace slag cement

650-1991 Standard sand for testing of cement

712-1984 Building Limes

1489-1991 Portland pozzolana cement Fly ash based

1514-1990 Methods of sampling & Test for Quick Lime & Hydrated Lime.

(Reaffirmed - 1996)

1542-1992 Sand for Plastering.

1727-1967 Methods of tests for pozzolanic materials

2250-1981 Code of practice for Preparation and use of masonry mortar.

(Reaffirm- 1990)

2386-1963 Methods of Test for Aggregates for Concrete

2386 Pt.I-1 963 Particle size and shape

2386 Pt. II-1963 Estimation of deleterious materials and organic impurities

2386 Pt.III-1 963 Specific gravity, density, voids, absorption and bulking

3025-1964 Methods of sampling & test (Physical & Chemical) water used in

industry. (Reaffirmed-2003)

Page 7: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 7 of 307

I. S. CODE

NO.

S U B J E C T

3812-1981 Fly Ash using as pozzolana and admixtures (Reaffirmed - 1999)

4031-1996 Methods of physical tests for hydraulic cement (Reaffirmed – 1996)

4032-1985. Method of chemical analysis of hydraulic cement (Reaffirmed - 1990)

4098-1983 Lime pozzolana mixture (Reaffirmed - 1989)

4 . C ONCRETE WOR K

383-1970 Coarse and fine aggregate from natural sources for concrete

(Reaffirm - 1990)

456-2000 Code of practice for plain and reinforced concrete

516-1959 Method of test for strength of concrete (Reaffirmed in 2004)

1199-1959 Method of sampling and analysis of concrete

1200 (Pt.II)-987 Methods of measurements of cement concrete work. (Reaffirm -

1992)

1322-1993 Bitumen felts for water proofing and damp proofing. (Reaffirm -

1998)

1661-1 987(Pt.I II) Code of practice for application of cement lime plaster

finishes.(Reaffirm- 1999)

2386-1977(Pt.1 to

8)

Methods of test for aggregate for concrete

2386 (Pt.I)-1 963 Test for particle size and shape

2386 (Pt.II)-1963 Test for estimation of deleterious materials and organic impurities

2386 (Pt.III)-1 963 Test for specific gravity, density, voids, absorption and bulking

2386 (Pt.IV)-1963 Mechanical properties

2645-1975 Specification for integral water proofing compounds

I. S. CODE NO. S U B J E C T

2686-1977 Specification for cinder aggregate for use in lime concrete. (Reaffirm

- 1992)

3812-1981 Fly Ash using as pozzolana and admixtures for concrete.

(Reaffirmed - 1999) 7861-1975 (Pt.I) Hot weather concreting. .(Reaffirmed -1990)

7861-1981 (Pt.II) Cold weather concreting. .(Reaffirmed -1992)

9103-1999 Admixture for concrete.

5. R.C.C. WORK

432-1982 Mild steel & medium tensile steel bars and hard drawn steel wire for

concrete reinforcement.

432 (Pt.I)-1982 Mild steel and medium tensile steel bars

456-2000 Code of practice for plain and reinforced concrete

Page 8: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 8 of 307

457-1957 COP for general const. of plain & reinforced concrete for dams &

other massive structure. 516-1959 Methods of test for strength of concrete

1161-1963 Specifications for steel tubes for structural purposes

1199-1959 Methods of sampling and analysis of concrete. (Reaffirmed - 1999)

1200 (Pt.II) -

1974

Method of measurement of cement concrete work

1200(Pt.V) -

1982

Method of measurement of form work. (Reaffirmed - 1989)

1343-1980 Code of practice for pre-stressed concrete.

1566-1982 Hard drawn steel wire fabric for concrete reinforcements (II Rev.)

(Reff.1998)

1780-1961 Specifications for cold twisted steel bars for concrete reinforcement *

1785-1983

(Part-I& II)

Specifications for plain hard drawn steel wire for pre-stressed

concrete

1786-1985 H.Y.S.D./ Cold twisted steel bars for concrete reinforcement

Reaffirmed - 1990)

2090-1983 Specifications for high tensile steel bars used in prestressed

concrete.

2204-1962 Code of practice for construction of reinforced concrete shell roof.

(Reaffirmed - 1990)

2210-1988 Criteria for the design of shell structure and folded plates

(Reaffirmed - 1998)

2502-1963 COP for bending and fixing of bars for concrete reinforcement.

(Reaffirmed - 1999)

2750-1964 Specifications for steel scaffoldings

2751-1979(Reaf-

1992)

COP for welding of mild steel bars used for reinforced concrete

construction.

2911-1984 Code of practice for design & Constn. of pile foundations

I. S. CODE

NO.

S U B J E C T

2911(Pt.I)-

1979.(Reaf-97).

Design & construction of Pile Foundations - Bored precast concrete

piles.

2911 (Pt.III)-1

980

Under reamed pile foundations

2911 (Pt.IV)-

1985

Load test on Piles

3201-1988 Criteria for design and construction of precast concrete trusses.

(Reaffirmed - 1995)

3370.(Part I to

IV)-1965

Code of practice for concrete structures for storage of liquids.

(Reaffirmed - 1999)

3385-1965 Code of practice for measurement of Civil Engineering works - Pile

Foundation)

Page 9: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 9 of 307

3414-1968 Code of practice for design and installation of joints in buildings.

(Reaffirmed - 1990)

3558-1983(Reaf-

91)

Code of practice for use of immersion vibrators for consolidating

concrete

3696 (Pt.I & II) I-1987: Safety code of scaffolds; II-1991: Safety code of ladders

3935-1966 Code of practice for composite construction. (Reaffirmed – 1998)

4014-1967 (Pt.

& II)

COP for steel tubular scaffolding (I: Definition/Material; II: Safety

Resolutions) (Raffir 1999)

4926-2003 Code of practice for Ready Mix Concrete

4990-1993 Specifications for plywood for concrete shuttering work. (Reaffirmed

- 1998)

10262-1982 Code of practice for design mix. (Reaffirmed - 1999)

6. EQUIPMENTS

460-1985 (Pt-

I,II& III)

Specification for test sieves. (Reaffirmed - 1998)

1791-1985 Specification for batch type concrete mixer. (Reaffirmed – 1990)

2430-1986 Methods for sampling of Aggregates for concrete.

2505-1992 General requirement for concrete vibrators, immersion type

2506-1985 General requirements for screed board concrete vibrators

2514-1963 Specification for concrete vibrating tables. (Reaffirmed - 1991)

3366-1965 Specification for pan vibrators. (Reaffirmed – 1991)

4656-1968 Specification for form vibrators for concrete. (Reaffirmed-1991)

2722-1964(Reaf-

95)

Specification for portable swing weigh batchers for concrete (single

and double bucket type).

2750-1964 Specification for steel scaffolding. (Reaffirmed – 1991)

7. BRICK WORK:

1077-1992 Common burnt clay building bricks

1200 (Pt.III)-

19920

Method of measurements of brick work. (Reaffirmed - 1992)

I. S. CODE

NO. S U B J E C T

2116-1980 Sand for masonry mortars. (Reaffirmed - 1998)

2212-1991 Code of practice for brick work

2250-1981 Code of practice for Preparation & use of masonry mortar.

(Reaffirmed - 1990)

3102-1971 Classification of burnt clay solid bricks

Page 10: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 10 of 307

3495 (Pt.ItoIV)-

1992 Method for test for burnt clay building brick

5454-1978 Method for sampling of clay building bricks. (Reaffirmed - 1995)

2185 (Part 3)

1984 Auto-claved cellular (Aerated) Concrete Blocks

8. STONE WORK:

1121 (Pt.I)-1974 Methods for determination of compressive, transverse & shear

strengths of natural building stones

1122-1974 Methods for determination of specific gravity and porosity of natural

building stones

1123-1975 Methods for identification examination of natural building stones

1124-1974 Methods of test for water absorption of natural building stones

1125-1974 Methods of test for weathering of natural building stones

1126-1974 Methods of test for durability of natural building stones

1129-1972 Dressing of natural building stones

1200 (Pt.IV)-

1976 Method of measurement of stone masonry. (Reaffirmed - 1992)

1597-1992 Code of practice for construction of stone masonry

1597. (Pt.I)-

1992

Code of practice for construction of Rubble stone masonry.

(Reaffirmed -1996)

1597 (Pt.II)-

1992

Code of practice for construction of ashlar masonry (Reaffirmed

- 1996)

1805-1973 Glossary of Terms relating to stone Quarrying and dressing.

Reaffirmed - 1993)

4101 (Pt.I)-1967 Stone facing. (Reaffirmed - 1990)

9. MARBLE WORK:

1122-1974 Methods for determination of specific gravity and porosity of natural

building stones

1124-1974 Methods of test for water absorption of natural building stones

1130-1969 Marble (blocks, slabs and tiles)

10. WOOD WORK:

204-1991/92 Tower bolts (Part I-1991: ferrous metals; Part II - 1992 : Non ferrous

metals).

205-1992 Non-ferrous metal butt hinges

I. S. CODE

NO. S U B J E C T

420-1953 Putty used on metal frame (withdrawn).

1734 - 1983 Methods of tests for plywood (IIR) (Ref 1993)

206-1992 Tee and strap hinges

207-1964 Gate and shutter hooks and eyes. (Reaffirmed - 1996)

Page 11: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 11 of 307

208-1987 Door handles

281-1991 Mild steel sliding door bolts for use with padlocks

287-1973(Reaf-

98)

Recommendation for maximum permissible moisture contents of timber

used for Different purposes.

303-1989 Plywood for general purpose

362-1991 Parliament hinges

363-1993 Hasps and staples

364-1993 Fanlight catch

401-1982 Code of practice for preservation of timber

419 - 1967 Putty for use on window frame (I Rv.) (and out 3)

451-1999 Technical supply condition for wood screws

452-1973 Door springs, rat-tail type(II Rev.) (Reaffirmed 1990)

453-1993 Double acting spring hinges. (Reaffirmed – 1999)

723-1972 Steel counter sunk head wire nails. (Reaffirmed - 1996)

729.1979 Drawer locks, cup board locks, and box locks (III Rev.) (Reaffirmed

1992)

848-1974 Synthetic resin adhesive for plywood (phenolic and aminoplastic) ( I

RV) (

851-1978 Synthetic resin adhesive for construction work ( Non-structural)

in wood (I-Rev.) (amt )(Reaffirmed 1990)

852-1994 Specifications for animal glue for general wood working purposes. (II

Rev)

1003-1994 Timber panelled and glazed shutters

1003(Pt.I)-2003 Door shutters (III Rev.) (a 1)

1003(Pt.II)-1994 Window and ventilator shutters (III Rev.)

1019-1974 Rim latches. (Reaffirmed - 1991)

1141-1993 Code of practice for seasoning of timber (II Rev.)

1200 Method of measurement of Building and Civil Engineering works

1200(Pt.XIV)-

1984 Glazing. (Reaffirmed - 1990)

1200(Pt.XII)-1

973 Wood work and joinery. (Reaffirmed - 1992)

I. S. CODE

NO. S U B J E C T

1322-1993 Bitumen felts for water proofing and damp proofing.

1328-1996 Veneered decorative plywood

1341-1992 Steel Butt hinges (VI Rev.)

Page 12: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 12 of 307

1378-1987 Oxidized copper finishes. (Reaffirmed - 1998)

1568-1970 Wire cloth for general purposes. (Reaffirmed - 1998)

1629-1960 Rules for grading of out size of timber. Superseded in I.S. 1331

1658-1977 Fiber hard board. (Reaffirmed - 1990)

1659-2004 Block boards

1708-1986 Method of testing of clear specimen of timber (II Rev) (Q.1)

(Reaffirmed 1990)

1823-1980 Floor door stoppers. (Reaffirmed - 1992)

1868-1996 Anodic coating on Aluminium & its alloy (II Rev.) (Reaffirmed 1991)

875-PET 1987 Dead locds – Unit not of bldg. & stored materials

2191-1983 Wooden flush door shutter (cellular and hollow core type).

(Reaffirmed - 1991)

1837 - 1966 For light pirot (I Rev.) (Reaffirmed 1990)

2095-1982 Gypsum plaster bow (I Rev) (an.1) (Ref. 1991)

2096-1992 A.C. flat sheet (I Rev.)

3828 - 1968 Ventilator chains (Reaf. 1990)

4835 - 1979 Polyvinyl acatete dispssion base adhasive for wood (1990)

2191 (Pt.I)-1983 Plywood face panels. (Reaffirmed - 1991)

2191 (Pt.II)-

1983

Particle board face panels and hard board face panels. (Reaffirmed-

1991)

2202-1999 Wooden flush door shutters (solid core type)

2202 (Pt.I)-1999 Plywood face panels for wooden flush door shutters

2202 (Pt.II)-

1983

Particle board face panels for wooden flush door shutters.

(Reaffirmed - 1991)

2209(Pt.I)-1976 Mortise locks (vertical type) (Reaffirmed 1992)

2380-1981 Method of test for wood particle board and boards from lingo

cellulosic materials (Reaf.1993)

2681-1993 Non ferrous metal sliding door bolts(aldrop) for use with pad locks

2835-1987 Flat transparent sheet glass (3rd Revision). (Reaffirmed - 1992)

3087-1985 Wood particle boards (medium density) for general purpose (1990)

3097-1980 Veneered particle boards (1st Revision).

Page 13: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 13 of 307

I. S. CODE

NO. S U B J E C T

3400 (Part I )-

1987 Method of test for vulcanized rubbers (1991)

3400-(Pt.II)-

2003 Hardness (1981)

3400-(Pt.IV)-1

987 Accelerated aging (1993)

3400 (Pt.IX)-

2003 Relative density and density. (Reaffirmed - 1990)

3564-1996 Door closers (Hydraulically regulated)

3618-1966 Phosphate treatment of iron and steel for protection against

corrosion. (Reaffirmed - 1991)

3813-1967 'C' hooks for use with swivels (1992)

3818-1992 Continuous (Piano) hinges

3847-1992 Mortise night latches

4020-1998 (1 to

16) Methods of tests for wooden flush Doors (Type tests)

4021-1995 Timber door, window and ventilator frames

4827-1983 Electroplated coating of nickel and chromium on copper and copper

alloys

4948-2002 Welded steel wire fabric for general use. (Reaffirmed - 1992)

4992-1975 Door Handles for mortise locks (vertical type). (Reaffirmed - 1990)

51 87-1972 Flush bolts (1990)

5523-1983 Method of testing anodic coating on aluminium & its alloys.

(Reaffirmed -1991)

5930-1970 Mortise latch (vertical types) (1991)

6318-1971 Plastic window stays & fasteners

6607-1972 Rebated mortise locks (vertical type)

6760-1972 Slotted countersunk head wood screws. (Reaffirmed - 1988)

71 96-1974 Hold fasts (1992)

71 97-1974 Double action floor springs (without oil check) for heavy doors

7534-1985 Sliding loacking bolt for use with padlocks. (Reaffirmed – 1991)

8756 - 1978 Mortice bell catches for use in wooden almirah (1992)

14856-2000 Glass fibre reinforced plastic (GRP) panel type door shutters for

internal use – Specifications

1 1 . S T E E L W O R K

Page 14: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 14 of 307

63-1978 Whiting for paints. (Reaffirmed - 1994)

198-1978 Varnish, gold size. (Reaffirmed - 1991)

12406 - 1988 Medium density fibre board for general purpose - (1992)

I. S. CODE

NO. S U B J E C T

277-2003 Specification for galvanised steel sheets (plain and corrugated)

278-1978 Galvanised steel barbed wire for fencing. (Reaffirmed - 1991)

800-1984 Code of practice for use of structural steel in general building

construction

806-1968 Code of practice for use of steel tube in general building

construction

813-1986 Scheme of symbols for welding. (Reaffirmed – 2003).

814-1991 Covered electrodes for metal arc welding of structural steel

(Reaffirmed 2003)

814 (Pt-I)-1974 For welding products other than sheets. *

814 (Pt-II)-1974 For welding sheets. *

817-1966 Code of practice for training and testing of metal arc welders.

(Reaffirmed – 2003)

818-1968 (Reaf-

03)

COP for safety & healthy requirements in electric & gas welding &

cutting operation.

1038-1983 Steel doors, windows and ventilators

1081-1960(Reaf-

91)

COP for fixing & glazing of metal (steel & aluminium) doors, windows

& ventilators

1148-1982(Reaf-

92)

Hot rolled steel rivet bars (upto 40 mm diameters)for structural

purposes (Reaffirmed 2001)

1161-1998 Steel tubes for structural purposes

1182-1

983(Reaf-00)

Recommended practice for radiographic examination of fusion

welded butt joints in steel plates.

1200 (Pt-VIII)-

1993 Method of measurements of steel work and iron works

1363-1992 (Pt.

1- 3)

Hexagon bolts, nuts & lock nuts (dia. 6 to 39 mm) & black hexagon

screws (dia. 6 to 24 mm).(Reaf-98)

1599-1

985(Reaf-9 1)

Method for bend test for steel products other than sheet, strip, wire

& tube (reaffirmed 1996).

1608-1995 Method for tensile testing of steel products (Reaffirmed 2001)

1821-1987 Dimensions for clearance holes for metric bolts. (Reaffirmed - 2003)

1852-1985 Rolling and cutting tolerance for hot rolled steel products.

(Reaffirmed - 1991)

1977-1969 Structural steel (ordinary quality) (Reaffirmed 2001)

2062-1999 Structural steel (fusion welding quality). Supersedes IS 226-1 975

4351-2003 Steel door frames. (Reaffirmed – 1991)

Page 15: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 15 of 307

4736-1986 Hot-dip zinc coatings on steel tubes. (Reaffirmed – 2001)

6248-1979 Metal rolling shutters and rolling grills

7452-1990 Hot rolled steel sections for doors, windows & ventilators.

I. S. CODE

NO. S U B J E C T

12 . FLOOR ING :

210-1993 Grey iron casting (Reaffirmed 1999)

653-1992 Sheet linoleum

777-1988 Glazed earthen-ware tiles

809-1992 Rubber flooring materials for general purpose

1122-1974 Methods for determination of specific gravity (*and porosity of natural

building stones)

1124-1974 Method of test for water absorption of natural building stones

1130-1969 Marble (blocks, slabs and tiles). (Reaffirmed – 1993)

1197-1970 Code of practice for laying of rubber floors. (Reaffirmed – 1990)

1198-1982 Code of practice for laying and maintenance of linoleum floors

1200 (Pt.XI)-

1977 Method of measurements of pavings and floor finishes.

1237-1980 Cement concrete flooring tiles. (Reaffirmed – 1990)

1443-1972 Code of practice for laying and finishing of cement concrete flooring

tiles

1661-1972 Code of practice for application of cement and cement lime plaster

finishes

2114-1984 Code of practice for laying in situ terrazzo floor finish

2571-1970 Code of practice for laying in situ cement concrete flooring

3400-1 987

(Part 1 to

22)

Method of Test of vulcanized rubbers. (Reaffirmed – 2003)

3400 (Pt.II)-

2003 Hardness

3400 (Pt.X)-

1977 Compression set at constant strain. (Reaffirmed – 2003)

3462-1986 Flexible P.V.C. Flooring. (Reaffirmed – 1991)

4631-1986 Code of practice for laying of resin floor toppings (Reaffirmed – 2001)

5318-1969 Code of practice for laying of flexible P.V.C. sheet & tiles flooring

5389-1969 Code of practice for laying of hardwood parquet and wood block floors.

(Reaffirmed – 1998)

Page 16: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 16 of 307

9197-1979 Specifications for epoxy resin, hardeners and epoxy resin compositions

for floor topping (Reaffirmed – 2001)

13630 (Pt.1

to 13) Methods of tests for ceramic tiles (Part 1 to 13 : 1992-1993)

13 . ROOF I NG :

73-1 992 Paving Bitumen (Reaffirmed 1998)

277-2003 Galvanised steel sheets (plain and corrugated)

I. S. CODE

NO. S U B J E C T

458-2003 Concrete pipes (with and without reinforcement)

459-1992 Unreinforced corrugated and semi corrugated asbestos cement sheets

651-1992 Salt glazed stone ware pipes and fittings

702-1988 Industrial Bitumen

1199-1959 Method of Sampling & Analysis of concrete. (Reaffirmed - 1991)

1200 (Pt.IX)-

1973 Method of measurements of roof covering (including cladding)

1200 (Pt.X)-

1973 Method of measurements of ceiling and lining

13607 -

1992

Ready Mixed Paint, Finishing, General Purposes, Synthetic (Reaffirmed

2002)

1322-1993 Bitumen felts for water proofing and damp-proofing. (Reaffirmed -1988)

1346-1991 Code of practice for waterproofing of roof with bitumen felts

1609-1991 Code of practice for laying damp proof treatment using bitumen felts

1626-

1994(Part I-

Asbestos cement building pipes, gutters and fittings (Spigot and socket

types)

1834-1984 Specification for hot applied sealing compounds for joints in concrete.

(Reaffirmed - 1990)

1838-(Pt.I &

II)-1983

Preformed filler for expansion joints in concrete- non-extruding and

resilient type Bitumen impregnated fiber). (Reaffirmed - 1990)

2115-1980 Code of practice for flat roof finish: mud phuska. (Reaffirmed - 1998)

2633-1986 Method of testing uniformity of coating on zinc coated articles.

(Reaffirmed – 2001)

3007-(Pt.I)-

1999

Code of practice for laying of corrugated asbestos cement sheets.

(Reaffirmed – 1991)

3007-(Pt.II)-1

965

Code of practice for laying of semi corrugated asbestos cement sheet.

(Reaffirmed - 1991)

3348-1965 Fiber insulation boards. (Reaffirmed - 1990)

3607-1979 Magnesite for chemical Industry. (Reaffirmed – 2003)

71 93-1994 Specifications for glass fiber base coal tar Pitch & Bitumen felts.

Page 17: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 17 of 307

8183-1993 Bonded mineral wool. (Reaffirmed 2004)

14. FINISHING

75-1973 Linseed oil, raw and refined. (Reaffirmed – 2003)

77-1976 Linseed oil, boiled, for paints. (Reaffirmed - 1999)

102-1962 Ready mixed paint, brushing, red, lead, non setting, priming.(

Reaffirmed - 1996)

104-1979 Specification for ready mixed paint, brushing, zinc chrome, priming.

(Reaffirmed - 1999)

133-1993 Enamel, interior (a) under coating (b) finishing colour as required

I. S. CODE

NO. S U B J E C T

137-1965 Ready mixed paint, brushing, matt or egg-shell flat, finishing,

interior, to Indian Standard Colour, as required. (Reaffirmed – 1999)

158-1981 Ready mixed paint, brushing, bituminous, black lead free acid alkali,

water and heat

168-1993 Ready mixed paint, air drying for general purpose.(Reaffirmed 2002)

217-1988 Cut back bitumen (reaffirmed 1999)

218-1983 Creosote and anthracene oil for use as wood preservatives (Reaffirmed

1998)

290-1961 Coal tar black paint. (Reaffirmed – 1996)

337-1975 Varnish, finishing interior. (Reaffirmed – 2001)

341-1973 Black Japan, types A, B, and C (Reaffirmed 2002)

347-1975 Varnish, shellac for general purpose. (Reaffirmed – 2001)

348-1968 French polish. (Reaffirmed – 2001)

419-1967 Putty for use of window frames. (Reaffirmed – 2001)

427-1965 Distemper, dry, colour as required. (Reaffirmed – 1999)

428-2000 Washable distemper

524-1983 Varnish, finishing, exterior, synthetic. (Reaffirmed – 2000)

525-1968 Varnish, finishing, exterior and general purposes. (Reaffirmed –2001)

533-1998 Gum spirit of turpentine (oil of turpentine) (Reaffirmed 2003)

712-1984 Specification for building limes. (Reaffirmed - 1995)

1200 (Pt.

XII)-1976 Method of measurements of plastering and pointing

Page 18: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 18 of 307

1200

(Pt.XIII)-1994

Method of measurements of white washing, colour washing,

distempering and other finishes

1200 (Pt.XV)-

1987 Methods of measurements of painting, polishing & varnishing.

2095-1996

(Pt.I - III) Gypsum plaster boards

2096-1992 Asbestos cement flat sheets.

2339-1963 Aluminium paint for general purposes, in dual container. (Reaffirmed –

1999)

2547-1976

(Pt I & II) Gypsum building plaster (Reaff. 1992)

2932-2003 Enamel synthetic, exterior (a) Under coating (b) Finishing.

2933-1975 Enamel, Exterior (a) Under coating (b) Finishing

5410-1992 Cement paint (Reaffirmed 1999)

5411 (Pt.I)-1

974 Plastic emulsion paint for interior use. (Reaffirmed – 1993)

I. S. CODE

NO. S U B J E C T

6278-1971 Code of practice for white washing & colour washing. (Reaffirmed -

1991)

14276-195 Cement particle board

15. DEMOLITION AND DISMANTLING:

1200(Pt.XVIII

)-1974

Method of measurements of demolition and dismantling

16. SAFETY CODES

818-1968

(Reaf-03)

Safety and healthy requirements in Electric and gas welding and

cutting operations.

3696 (Pt.I)-1

987 Safety code for scaffolds

3696 (Pt.II)-

1991 Safety code for ladders

3764-1992 Safety code for Excavation works

4081-1986 Safety code for blasting and related drilling operation

4130-1991 Safety code for Demolition of Building

5916-1970 Safety code for construction involving use of hot bituminous materials

6922-1973 Structural subject to underground blasts code of practice for safety

and design of structure subject to underground blasts.

7293-1974 Working with construction machinery- safety code for

Page 19: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 19 of 307

III – MANDATORY TESTS

NOTES:

The mandatory tests shall be carried out when the quantity of materials to incorporate in the work exceeds the minimum quantity specified.

Optional tests specified or any other tests, shall be carried out in case of specialized works or important structures as per direction of the Engineer-in-Charge.

Testing charges, including incidental charges and cost of sample for testing shall be borne by the contractor for all tests.

In case of non-IS materials, it shall be the responsibility of the contractor to establish the conformity of material with relevant IS specification by carrying out necessary tests. Testing charges including incidental charge and cost of sample for testing shall be borne by the contractor for such tests.

THE MANDATORY TESTS SHALL BE AS FOLLOWS:

Material Test Field /

laboratory

test

Test procedure

Minimum

quantity of

material / Work

for carrying out

the test

Frequency of

testing

Reinforced cement concrete work

Water for Construction purposes

Ph value Limits of Acidity Limits of Alkality Percentage of solids Chlorides Suspended matter Sulphates Inorganic solids Organic solids

Lab IS 3025 Water from each

source

Before commencement of work & thereafter:

Mandatory – Once in one year from each source;

Optional: once in 3

months from each

source; Municipal

supply - optional.

Reinforced

cement

concrete

b) slump test Field IS: 1199 a) 20 cu.m. for slabs, beams and connected columns .

b)5 Cu.m in case of cloumns

a) 20 cu.m. Part

there of or more frequently as require by the Engr.-in-Charge.

b) Every 5 Cu.m.

Page 20: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 20 of 307

c) cube test Lab IS : 516 a) 20 cu.m. In slab, beams, & connected columns. b) 5 cum in case of columns

a) every 20 cum of

a day's concreting

.(Ref. as per

frequency of

sampling).

b) Every 5 cum.

Ready mixed cement (IS-4926) concrete

Cube test Lab IS-516 and as

per Para 6.3.2 of IS-4926-2003

50 cum One for every 50cum of production or every 50 batches, whichever is the

greater frequency

Note : for all other small items and where RCC done in a day is less than 5 cum, test may be carried out as required by Engineer-in-Charge.

Mortars:

Lime Chemical & physical properties of lime

Laboratory IS; 6932 (part 1 to x)

5 M.T. 10 M.T. or part there of as decided by the Engineer-in-Charge

Sand Bulking of Sand

Field 20 CU.M. Every 20 cu.m or part thereof or more frequently as decided by Engineer-In-Charge

Silt content Field IS:383 20 CU.M. Every 20 cu.m or part thereof or more frequently as decided by Engineer-in-Charge

Particle size and distribution

Field Laboratory decided by Engr -in-Charge

IS:383 40 CU.M. Every 40 cu.m. of fine aggregate / sand required in RCC. work only.

Organic Impurities

Field .. DO.. 20 CU.M. Every 20 cu.m. or part thereof or more frequently as decided by the Engineer-in-Charge

Chloride & sulphate content tests

Optional Once in three months.

Material Test

Field /

laboratory

test

Test

procedure

Minimum

quantity of

material /

Work

for carrying

out

the test

Frequency of

testing

Cement Test

requirement

Fineness

(m²/kg)

IS 4031

(Part-II)

Each

fresh lot

Every 50 MT or

part

Thereof

Page 21: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 21 of 307

Normal

consistency

IS 4031

(Part-IV)

Setting time

(minutes)

a) Initial

b) Final

IS 4031

(Part-V)

Soundness a)Le-

Chat expansion

(mm)

b) Autoclave (%)

IS 4031

(Part-III)

Compressive

Strength (Mpa)

a) 72+/-1 hr

b) 168+/-2hr

IS 4031

(Part-VI)

Stone

Aggregate

a)

Percenta

ge of

soft or

deleterious

materials

General visual

inspection / Lab

test where

required by

the Engr-in-

Charge

IS 2386 Part

II

One test for

each source

One test for each

source

Particle size

distribution

Field / Lab - 10 cu.m Every 40 cum. Or

part thereof and

Once in three months for each source for coarse and fine aggregates required

in RCC works, for a minimum quantity - 10 cum for coarse aggregate and 40

cum for fine aggregate.

a) Estimationof

Organic

impurities

Field / Lab IS 2386 Part

II

10 Cum -do-

b) Specific

Gravity

Field / Lab IS 2386 10 Cum -do-

Bulk Density Field / Lab IS 2386 10 Cum -do-

Page 22: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000049

Page 22 of 307

Material Test

Field /

laboratory

test

Test

procedure

Minimum

quantity of

material /

Work

for carrying

out

the test

Frequency of

testing

b) Aggregate

crushing

strength

Field / Lab IS 2386 10 Cum -do-

c) Aggregate

impact value

Field / Lab IS 2386 10 Cum -do-

Timber Moisture Field (by

moisture

meter)

Laboratory

test as

required by

Engineer-

in-Ch.

1 Cu.M. Every one Cum or

part thereof

Flush

Door

End immersion

test Knife test

Adhesion test

Laboratory IS: 2202

(Part 1) &

(Part II)

26 shutters As per sampling

and testing as

instructed by

the Engineer-in-

Charge.

Bricks Testing of bricks

/

brick tiles for

dimensions

Compressive

strength

Water absorption

Efflorescence

Laboratory IS 3495

Part I to

IV

No. of bricks

to be

selected &

bricks lot

20 : 2001 to

10000

32 : 10001 to

35000

50 : 35001 to

50000

20 : for every

addl. 50000

or part

thereof.

If < 20000,

As per

decision of

EIC.

Permissible

defective bricks in

the sample

1

2

3

1

Page 23: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 23 of 307

Material Test

Field /

laborato

ry test

Test

procedur

e

Minimum

quantity of

material /

Work for

carrying out

the test

Frequency of testing

Concrete

Blocks

Dimensions of

block

Block Density

Compressive

strength

Water absorption

Drying shrinkage

Moisture

movement

Retest – Drying

shrinkage &

Moisture

movement if

required

Field

Laborator

y

IS 2185 –

Part 1

20 blocks

from every

consignment

of 5000

blocks.

As per sampling and

testing as instructed

by

the Engineer-in-

Charge.

Steel for

RCC

Physical tests

a) Tensile strength

b) Retest

c) Re-bound test

d) Nominal mass

e) Bend test

f) Elongation test

g) Proof stress

Lab

/ field

IS

1608

IS

1786

IS

1786

IS

1786

IS

1599

IS

1786

IS

1786

Each

lot

from

each

source

from

each

diame

ter

of bar

Below 100

Tonnes

Dia < 10

mm one

sample for

each 25

tonnes or

part thereof

If dia is >10

mm but less

than 16

mm: One

sample each

35 tonnes or

part thereof.

If dia >16

mm one

sample for

each 45

tonnes

Above 100 Tonnes

Dia < 10 mm one

sample for each 40

tonnes or part

thereof

If dia is >10 mm

but less than 16

mm

One sample for

each 45 tonnes or

part thereof.

If dia >16 mm

one sample for

each 50 tonnes.

Page 24: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 24 of 307

Chemical Tests:

1 .Carbon

Constituent

2.Sulphur

3.Phosphorus

4.Phosphorus &

IS

1786

For every fresh

lot of one truck

or less as

directed by the

Engineer-in-

Charge. Soil core

test

OMC

Proctor density

As per IS

12175

Two for

every 50

sqm

As per Para 1.10 &

1.11 of this book

OTHER MANDATORY TESTS: Soil core tests; Testing aggregate - particle size distribution;

Ceramic tiles, Mosaic tiles

CI pipes: Dimensional, mass, Hydrostatic; GI pipes; Lead; RCC hume pipes; Stoneware

pipes

OPTIONAL TESTS: Testing aggregate-surface moisture, impact value pectrographic;

alkali reaction; Dimensional tests of bricks; Testing the mass of zinc coating on GI door

frame, steel windows, test for chemical and physical properties; Anodic coating on

aluminium fittings and aluminium sections, Unit weight of aluminium sections;

Testing structural steel; Chequered plate, Unit weight, Thickness, Chemical and physical

properties

Presence of preservative on factory made panelled door, kiln seasoned chemically treated

wood products, Moisture content in wood products.

TESTING, TOLERANCE, ACCEPTANCE AND MODE OF PAYMENT:

a) The material should pass all tests and tolerance in dimensional, chemical, physical

properties should be within the limit as stipulated in relevant IS for acceptance. Such

materials shall be accepted as standard.

b) Payment shall be restricted to standard unit mass, or as specified in the schedule of

work, without making any cost adjustment towards mass or any other properties,

provided the material pass all the tests and tolerances are within the specified limits. In

case of non-standard materials, materials not covered under any IS Specifications, such

as aluminium sections, the payment shall be made based on the actual unit weight

basis as determined by testing at random sampling.

Page 25: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 25 of 307

TECHNICAL SPECIFICATION

CIVIL WORKS

Page 26: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 26 of 307

TECHNICAL SPECIFCIATIONS FOR CIVIL WORKS

1. EARTH WORK

1.1. SCOPE OF WORK:

The scope of work covered under this specifications pertains to excavation of

foundations, trenches, pits and over areas, in all sorts of soils, soft and hard rock,

correct to dimensions given in the drawing including shoring, protections of existing

underground utilities if any, such as water lines, electric cables etc., dewatering and

shoring if necessary, stacking the useful materials as directed within the lead

specified, refilling around the foundation and into the plinth with selected useful

excavated earth and disposing off the surplus earth/materials within specified lead

and finishing the surface to proper levels, slopes and camber etc. all complete.

1.2. SITE CLEARANCE:

Before the earth work is started the area coming under cutting and filling shall be

cleared of all obstructions, loose stones, shrubs, rank vegetation, grass, brush-

wood, trees and saplings of girth upto 30 cm. measured at a height of one metre

above ground and rubbish removed upto a distance of 150 metres outside the

periphery of the area under clearance. The roots of trees shall be removed to a

minimum depth of 60 cm. below ground level, or a minimum of 30cm. below

formation level whichever is lower, and the hollows filled up with earth, levelled and

rammed. This work is deemed to be included in the earth work items and no separate

payment will be admissible for the work.

The trees of girth above 30 cm. measured at a height of one meter above ground,

shall only be cut after permission of the Engineer-in-charge is obtained in writing.

The roots shall also be removed as described in the preceding sub-Para. Payment for

cutting and removing roots of such trees shall be made separately. Any material

obtained from the site will be the property of the Department and the useful materials

as decided by the Engineer-incharge will be conveyed and properly stacked as

directed within the lead specified.

1.3. SETTING OUT AND MAKING PROFILES :

Masonry or concrete pillars will be erected at suitable points in the area to serve as

bench marks for the execution of the work. These bench marks shall be connected

with G. T. S. or any other permanent bench mark approved by the Engineer-in-

charge. Necessary profiles with pegs, bamboos and strings or Burjis shall be made to

show the correct formation levels before the work is started. The contractor shall

supply labour and materials for setting out and making profiles and Burjis for the

work at his own cost and the same shall be maintained during the excavation work.

The Department will show grid Co-ordinate or other reference points. It shall be the

responsibility of the contractor to set out centre lines correctly with reference to the

drawings and install substantial reference marks. Checking of such alignment by

the Department will not absolve the contractor from his responsibility to execute the

work strictly in accordance with the drawings.

1.4. EXCAVATION :

The contractor shall notify the Engineer-in-charge before starting excavation and

before the ground is disturbed, to enable him to take existing levels for the purpose

Page 27: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 27 of 307

of measurements. The ground levels shall be taken at 5 to 15 metres intervals in

uniformly sloping ground and at closer distance where local mounts, pits or

undulations are met with, as directed by the Engineer-in-charge. The ground levels

shall be recorded in field books and plotted on plans, which shall be signed by the

Contractor and the Engineer-in-charge, before the earth work is actually started.

The labour required for taking levels, shall be supplied by the Contractor at his own

cost. The Contractor shall perform excavation in all types of soils, murrum, soft and

hard rock, boulders etc. in foundation, over areas and in trenches to widths, lines,

levels, grades and curves as shown in the drawing or lesser widths, lines and levels

as directed by the Engineer-in-charge and as per items in the schedule of quantities.

1.4.1. The item in the schedule of quantities shall specify the excavation in trenches

or over areas. For this purpose, the excavation for any depth in trenches for

foundation not exceeding 1.5 m. in width or 10 sqm. on plan shall be described as

Excavation in foundation trenches.

1.4.2. Excavation exceeding 1 .5m in width as well as 10 sqm. on plan (excluding

trenches for pipes, cables etc.) and exceeding 30 cm in depth shall be described as

Excavation over areas.

1.4.3. Excavation exceeding 1.5m in width as well as 10 sqm. on plan but not

exceeding 30 cm. in depth shall be described as Surface Excavation.

1.5. Classification of Earth Work: The earth work shall be classified under the

following main categories and measured separately for each category.

a) All types of soils, murrum, boulders.

b) Soft rock.

c) Hard rock.

1.5.1.

a) All types of Soils, Murrum, Boulders : This includes earth, murrum, top deposits

of agricultural soil, reclaimed soil, clay, sand or any combination thereof and soft and

hard murrum, shingle etc. which is loose enough to be removed with spades, shovel

and pick axes. Boulders not more than 0.03 cum. in volume found during the course

of excavation shall also fall under this classification.

b) Excavation in Soft Rock : This shall include all materials which are rock or hard

conglomerate, all decomposed weathered rock, highly fissured rock, old masonry,

boulders bigger than 0.03 cum. in volume but not bigger than 0.5 cum. and other

varieties of soft rock which can be removed only with pick axes, crow bars, wedges

and hammers with some difficulty. The mere fact that the contractor resorts to

blasting and/or wedging and chiseling for reasons of his own, shall not mean the

rock is classificable as hard rock.

c) Excavation in Hard Rock : This includes all rock other than soft rock mentioned in

Para 1.5.1 (b) viz. soft rock, occurring in masses, boulders having approximate

volume more than 0.5 cum. plain or reinforced cement concrete, which can best be

removed by blasting or chiseling and wedging where blasting cannot be permitted

owing to any restriction at site.

Page 28: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 28 of 307

i) Excavation in Hard Rock by Blasting : Where blasting is permitted the excavation

in rock shall be done by means of blasting. No heavy blasting will be permitted and

only controlled/muffled blasting will be permitted at the discretion of the Engineer-in-

Charge. The Contractor shall be governed by the relevant statutory laws, rules and

regulations on explosives, pertaining to the acquisition, transport, storage, handling

and use of explosive which shall be rigidly followed and shall obtain himself all

necessary materials and equipment for blasting. Blasting shall be executed through

a licensed blaster with prior permission from police authorities. Prior to blasting

sufficient notice shall be given to concerned parties to avoid danger to people,

materials and nearby structures. All the damages caused by careless blasting if any

shall be made good by the contractor at his own expenses.

ii) Excavation in Hard Rock by Chiseling and Wedging : Where blasting is not

permitted and if the Engineer-in-Charge so desires, the excavation shall be done by

chiseling and wedging or any other agreed method.

NOTE : All the excavated hard rock obtained shall be stacked properly and neatly

within the specified lead by the contractor as directed by the Engineer-in-Charge.

1.6. EXCAVATION PARAMETERS : The excavation under all classifications in

areas in trenches or in pits shall be carried out systematically. Cutting shall be done

from top to bottom and no under-pining or undercutting will be allowed. The bottom

and sides of excavation shall be dressed to proper level, slopes, steps, camber etc. by

removing high spots, and ramming thoroughly as directed by the Engineer-in-

charge.

All the excavation shall be carried out strictly to the dimensions given in the drawing.

The width shall generally be of the width of mud mat concrete and depth as shown in

drawing or as directed by the Engineer-in-Charge, according to availability of the

desired bearing capacity of soil below. Any excavation if taken below the specified

depths and levels, the contractor shall at his own cost fill up such overcut to the

specified level with cement concrete 1:4:8 in case of excavation in all types of soils

and with cement concrete 1:2:4 in case of excavation in soft and hard rock.

After the excavation is completed, the contractor shall notify the Engineer-in-Charge

to that effect and no further work shall be taken up until the Engineer-in-Charge has

approved the depth and dimensions and also the nature of foundation materials.

Levels and measurements shall also be recorded prior to taking up any further work.

1.7. SHORING :

Unless separately provided for in the schedule of quantities, the quoted rate for

excavation shall include excavation of slopes to prevent falling in soil by providing

and/or fixing, maintaining and removing of shoring, bracing etc. The contractor would

be responsible for the design of shoring for proper retaining of sides of trenches, pits

etc. with due consideration to the traffic, superimposed loads etc. Shoring shall be of

sufficient strength to resist the pressure and ensure safety from slips and to prevent

damage to work and property and injury to persons. It shall be removed as directed after

items for which it is required are completed. Should the slips occur, the slipped material

shall be removed and slope dressed to a modified stable slope. Removal of the slipped

earth will not be measured for payment.

Page 29: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 29 of 307

DEWATERING :

Unless specifically provided for as a separate item in the schedule of quantities, rate

shall also include bailing or pumping out all water which may accumulate in the

excavation during the progress of further works such as mud mat concrete, R.C.

footings, shuttering etc. either due to seepage, springs, rain or any other cause and

diverting surface flow by bunds or other means. Care shall be taken to ensure that the

water discharged sufficiently away from the foundations to keep it free from nuisance

to other works in the neighbourhood.

1.8. DISPOSAL OF EXCAVATED MATERIALS :

a) ANTIQUITES : Any finds of archaeological interest such as relics of antiquity, coins,

fossils or other articles of value shall be delivered to the Engineer-in-Charge and shall

be the property of the Government.

b) USEFUL MATERIALS : Any material obtained from the excavation which in the

opinion of the Engineer-in-Charge is useful, shall be stacked separately in regular

stacks as directed by the Engineer-in-Charge and shall be the property of the

Government.

No material excavated from foundation trenches of whatever kind they may be are to be

placed even temporarily nearer than about 3 m. from the outer edge of excavation.

Discretion of the Engineer-in-Charge in such cases is final. All materials excavated will

remain the property of the Department. Rate for excavation includes sorting out of the

useful materials and stacking them separately as directed within the specific lead.

Materials suitable and useful for backfilling or other use shall be stacked in convenient

place but not in such a way as to obstruct free movement of materials, workers and

vehicles or encroach on the area required for constructional purposes. It shall be used

to the extent required to completely backfill the structure to original ground level or

other elevation shown on the plan or as directed by the Engineer-in-Charge. Materials

not useful in anyway shall be disposed off, levelled and compacted as directed by

the Engineer-in-charge within a specified lead. The site shall be left clean of all

debris and levelled on completion.

1.9. BACKFILLING IN SIDES OF FOUNDATIONS, PLINTH, UNDER FLOOR ETC. :

The back filling shall be done after the concrete or masonry has fully set and shall be

done in such a way as not to cause under-thrust on any part of the structure. Where

suitable excavated material is to be used for back filling, it shall be brought from the

place where it was temporarily deposited and shall be used in backfilling. The scope of

work for back filling/filling in foundation, plinth, under floors etc. shall include filling

for all the buildings covered under the contract. Surplus earth available from one

building, if required, shall be used for backfilling/filling for other buildings also within

the specified lead mentioned in the item.

All timber shoring and form work left in the trenches, pits, floors etc. shall be removed

after their necessity ceases and trash of any sort shall be cleared out from the

excavation. All the space between foundation masonry or concrete and the sides of

excavation shall be backfilled to the original surface with approved materials in layers

not exceeding 150 mm. in thickness, watered and well consolidated by means of

rammers to at least 90% of the consolidation obtainable at optimum moisture content

Page 30: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 30 of 307

(Proctor density). Flooding with water for consolidation will not be allowed. Areas

inaccessible to mechanical equipment such as areas adjacent to walls and columns etc.

shall be tamped by hand rammer or by hand held power rammers to the required

density. The backfill shall be uniform in character and free from large lumps, stones,

shingle or boulder not larger than 75 mm. in any direction, salt, clods, organic or other

foreign materials which might rot. The backfilling in plinth and under floors shall be

done in similar way in layers not exceeding 150 mm. thick and shall be well

consolidated by means of mechanical or hand operated rammers as specified to achieve

the required density.

Test to establish proper consolidation as required will be carried out by the Department

at rates specified. Two tests per 50 sqm. will be taken to ascertain the proper

consolidation. The cost of tests carried out will be recovered from the contractors bill.

1.10. FILLING IN PLINTH AND UNDER FLOORS:

After the available suitable excavated materials are exhausted as backfilling, the

contractor shall notify the Engineer-in-Charge, of the fact and levels taken jointly with

Engineer-in-Charge. The earth, murrum, sand, gravel etc. or such materials suitable

for filling proposed to be filled under floors and so mentioned in the item of schedule of

quantities shall then be brought to site from approved locations and sources.

i) Earth Filling : The earth, soft murrum etc. so brought shall be filled up in layers of 15

cm depth, each layer being well watered and consolidated by approved hand or

mechanical tampers or other suitable means to achieve the required density.

ii) Gravel or Sand Filling : Gravel if required to be filled under floors, shall be single

washed gravel of approved quality and of size varying from 12 mm. to 20 mm. it shall

be uniformly blinded with approved type of soil and/or sand to obtain full compaction.

Gravel shall be filled in specified thickness and shall be well watered and rammed

entirely to the satisfaction of the Engineer-in-Charge.

If sand is required to be filled under floors, it shall be clean, medium grained and free

from impurities. The filled in sand shall be kept flooded with water for 24 hrs. to

ensure maximum consolidation. Any temporary work required to maintain sand under

flooded condition shall be done by the contractor at his own cost. The surface shall

then be well dressed and got approved from Engineer-in-Charge before any other work

is taken over the fill.

1.11. LEAD & LIFT

LEAD : The lead for disposal/deposition of excavated materials shall be as specified in

the respective item of work. For the purpose of measurements of lead, the area to be

excavated or filled or area on which excavated material is to be

deposited/disposed off shall be divided in suitable blocks and for each of the

block, the distance between centre lines shall be taken as the lead which shall be

measured by the shortest straight line route on the plan and not the actual route

adopted.

LIFT : Lift shall be measured from ground level. Excavation up to 1.5 m depth below

ground level and depositing excavated material on the ground shall be included in the

item of earthwork for various kinds of soil. Extra lift shall be measured in unit of 1.5 m

or part thereof. Obvious lift shall only be measured; that is lifts inherent in the lead due

Page 31: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 31 of 307

to ground slope shall not be measured except for lead upto 250 m. All excavation shall

be measured in successive stages of 1 .5 m stating the commencing level. This shall

not apply to cases where no lift is involved as in hill side cutting.

1.12. MODE OF MEASUREMENTS:

1.12.1. All excavation in areas having depth more than 30 cm. pits, trenches etc.

shall be measured net. The dimensions for the purpose of payment shall be

reckoned on the horizontal area of the excavation at the base for foundations of the

walls, columns, footings, rafts or other foundations, multiplied by the mean depth

from the surface of ground determined by levels. Excavation for side slopes will not

be paid for. Excavation in areas having depths less than 30 cms. shall be measured

as surface excavation on square metre basis, mentioning the average depth of

excavation.

Reasonable working space beyond concrete dimensions shall be allowed for

waterproofing and shuttering works in underground water tanks, sumps, septic

tanks etc., where considered necessary in the opinion of the Engineer-in-Charge.

However the same shall be limited to the following:

i) Waterproofing

and

works upto 2M

depth

Maximum upto 600mm from face of concrete

surface

ii) Waterproofing

and

works beyond 2M

depth

Maximum upto 900mm from face of concrete

surface.

1.12.2. Wherever direct measurements of rock excavation are not possible, volume of

rock be calculated on the basis of length, breadth and depth of stacks made at site

as mentioned in Para 1.5.1 (c). The net volume shall be worked out by reducing it by

50%, taking the voids into consideration as 50%. Similarly to arrive at net quantity to

be paid in the case of soil, reduction @ 20% of corresponding stack/truck

measurements shall be made.

1.12.3. The rate for excavation shall include carting and disposing and levelling

the excavated materials within the specified lead. The rate shall also be inclusive

of cost of all tools, plants, explosives, shoring, dewatering at various stages, labour,

materials etc. to complete all the operations specified.

1.12.4. The backfilling and consolidation in sides of foundation and in plinth with

excavated material will not be paid for separately. The rate quoted for excavation

shall be deemed to have been included the cost of stacking of excavated materials,

conveying within the specified lead, picking of selected stacked materials, conveying

it to the place of final backfill, compaction to the required proctor density etc.

1.12.5. Payment for filling and consolidation inside the trenches, sides of foundations,

plinth etc. with selected materials brought by the contractor other than the excavated

Page 32: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 32 of 307

material, shall be paid for separately as per the rates in schedule of quantities which

includes cost of such materials/excavation, royalty, its conveyance within the

specified lead, watering, consolidating, dressing etc. Actual quantity of consolidated

filling shall be measured and paid in cubic metres upto two places of decimal.

1.12.6. The rate quoted in cum. for items of excavation is deemed to include the

necessary additional quantity of excavation involved beyond the authorized

dimensions of Para no 1.13 ( for waterproofing and shuttering works in underground

water tanks, sumps, septic tanks, Raft etc.) which may be necessary to be carried out

for carrying out the work in an engineering manner, decided upon by the contractor.

Therefore no extra payment will be made for any excavation done other than the

required quantity as per the plan dimension indicated in the drawings.

1.12.7. Measurements for excavation over areas shall be determined by levels or by

“Dead men” or both at the discretion of the Engineer-in-Charge. If however the

Engineer-in-Charge decides on measurement by levels, levels of site shall be jointly

taken and recorded by the Engineer-in-Charge or his representatives and the

contractor, before commencement of the work and after completion of the work and

the quantity of work done shall be computed based on these levels. The volume of

earth work shall be computed based on “Simpsons formula” or any other approved

method at the discretion of the Engineer-in-Charge.

* * * *

4. PLAIN / REINFORCED CONCRETE AND ALLIED WORKS:

4.1. SCOPE :

Scope of the specification deals with the structural and general use of plain and

reinforced cement concrete.. The specifications cover the qualitative and quantitative

requirements in respect of selection of ingredients, proportioning, manufacture of

concrete, transport, placing, consolidation, curing, finishing, acceptance criteria

etc., These specifications also cover the requirement of form work and

reinforcement.

4.2. Unless otherwise specified, the manufacture and placing of concrete shall be

done by weigh batching. However, in the specific cases where mechanized batching

system (Ready mix concrete), mechanical transport and pumping is specified the

same shall be followed as per the terms of the contract.

4.3. CEMENT CONCRETE (PLAIN AND REINFORCED):

4.3.1. The quality of materials and method and control of manufacture and transportation of

all concrete work in respect of mix, whether reinforced or otherwise, shall conform to

the applicable portions of these specifications.

4.3.2. Mandatory tests: The Engineer-in-Charge shall have the right to inspect the

sources of materials, the layout and operation of procurement and storage of

materials, the concrete batching and mixing equipments and the quality control

system. The contractor shall arrange such an inspection and the Engineer-in-Charge

approval shall be obtained prior to starting the concrete work. List of mandatory test

for RCC to be carried out is enclosed as Annexure "A".

4.3.3. Materials for Standard Concrete : The ingredients to be used in the manufacture

Page 33: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 33 of 307

of standard concrete shall consist solely of a standard type Portland/Portland

pozzolana cement, clean sand, natural coarse aggregate, clean water, ice and

admixtures if specially called for on drawings or schedule of quantities.

4.3.3.1. Cement: Unless otherwise specified or called for in the contract specifications,

cement shall be any of the following and the type selected should be appropriate for

the intended use and as per the contract conditions, specifications and drawings.

a) 33 Grade Ordinary Portland cement conforming to IS 269

b) 43 Grade ordinary Portland cement conforming to IS 8112

c) 53 Grade ordinary Portland Cement conforming to IS 12269

d) Portland slag cement conforming to IS 455.

e) Porland pozzolana cement (fly ash based ) conforming to IS 1489 (Part I)

f) Portland pozzolana cement (calcined clay based conforming to IS 1489 (Part 2)

g) Sulphate resisting Portland cement conforming to IS 12330.

In case the job requires specific use of any of the following cements the same shall

be used with the prior approval of the EIC and necessary precautions with regard to

their setting and hardening time, time required for de-shuttering, curing etc., shall

be taken after carefully complying with specific literature with regard to those types.

1. High Alumina cement - conforming to IS 6452

2. Low heat cement - conforming to IS 12600

3. Super sulphate cement - conforming to IS 6909

4. Rapid Hardening cement - conforming to IS 8041

5. Blended Cement for finishing work as below

Other combinations of Portland Cement with mineral admixtures of quality

conforming to relevant Indian Standards laid down may also be used in the

manufacture of concrete provided that there are satisfactory data on their suitability,

such as performance test on concrete containing them and only in such case where in

specifically called for in the contract.

4.3.3.1(A). Mineral Admixtures

Pozzolana: Pozzolanic materials conforming to relevant Indian Standards may be

used with the permission of Engineer-in-charge, provided uniform blending with

cement is ensured.

Fly ash (pulverized fuel ash): Fly ash conforming to Grade 1 of IS 3812 may be

used as part replacement of ordinary Portland cement provided uniform blending

with cement is ensured.

Page 34: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 34 of 307

Silica fume: Silica fume conforming to a standard approved by the deciding

authority can be used as part replacement of cement provided uniform blending

with the cement is ensured.

Note: The silica fume (very fine non –crystalline silicon dioxide)is a by-product of

the manufacture of silicon, ferrosilicon or the like, from quartz and carbon in

electric arc furnace. It is usually used in proportion of 5 to 10 percent of the

cement content of a mix.

Rice husk ash: Rice husk ash giving required performance and uniformity

characteristics may be used with the approval of the deciding authority.

Note: Rice husk ash is produced by burning rice husk and contain large

proportion of silica. To achieve amorphous state, rice husk may be burnt at

controlled temperature. It is necessary to evaluate the product from a particular

source for performance and uniformity since it can range from being as

deleterious as silt when incorporated in concrete. Water demand and drying

shrinkage should be studied before using rice husk.

Metakaoline: Metakaoline having fineness between 700 to 900m²/kg may be

used as pozzolanic material in concrete.

Note: Metakaoline is obtained by calcination of pure or refined kaolintic clay at a

temperature between 650 0C and 8500C, followed by grinding to achieve a

fineness of 700 to 900 m²/kg. The resulting material has high pozzolanicity.

Ground Granulated Blast Furnace Slag: Ground granulated blast Furnace slag

obtained by grinding granulated blast furnace slag conforming to IS 12089 may

be used as part replacement of ordinary Portland cement provided uniform

blending with cement is assured.

A certified report attesting to the conformity of the cement to I.S. specifications

by the cement manufacturers chemist shall be furnished to the Engineer-in-

Charge, if demanded. The Contractor, shall make his own arrangements for the

storage of adequate quantity of cement at no extra cost at the site of work as per

instructions and approval of the Engineer-in-Charge.

Specification for Storage:

Cement in bags shall be stored and stacked in a shed, which is dry, leak-proof

and moisture proof as far as possible. Storage under tarpaulins will not be

permitted. Flooring of the shed shall consists of the two layers of dry bricks laid

on well consolidated earth to avoid contact of cement bags with the floor.

Stacking shall be done about 150 to 200 mm clear above the floor using wooden

planks. Cement bags shall be stacked at least 450 mm clear off the walls and in

rows of two bags leaving in a space of at least 600 mm between two consecutive

rows. In each row the cement bags shall be kept closed together so as to reduce

air circulation. Stacking shall not be more than ten bags high to avoid lumping

under pressure. In stacks more than eight bags high, the cement bags shall be

arranged in header and stretcher fashion i.e alternately lengthwise and crosswise

so as to tie the stacks together and minimize the danger of toppling over.

Damaged or reclaimed or partly set cement will not be permitted to be used and

shall be removed from the site. The storage arrangements shall be such that

Page 35: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 35 of 307

there is no dead storage consignments in cement shall be stored as received and

shall be consumed in the order of their delivery.

Cement held in store for a period of ninety (90) days or longer shall be retested

before use in work. Should at any time the Engineer-in-Charge have reasons to

consider that any cement is defective, then irrespective of its origin and/or

manufacturers test certificate, such cement shall be tested immediately at a

National Test Laboratory/Departmental Laboratory or such approved laboratory,

and until the results of such tests are found satisfactory, it shall not be used in

any work.

4.3.3.2. Aggregates :

a) “Aggregate” in general designates both fine and coarse inert materials used in the

manufacture of concrete.

b) “Fine Aggregate” is aggregate most of which passes through 4.75 mm I.S. sieve.

c) “Coarse Aggregate” is aggregate most of which is retained on 4.75 mm I.S. sieve.

Aggregate shall comply with requirement of IS 383. As far as possible preference shall

be given to machine broken and graded aggregate.

All fine and coarse aggregates proposed for use in the work shall be subject to the

Engineer-in-Charge’s approval and after specific materials have been accepted, the

source of supply of such materials shall not be changed without prior approval of

the Engineer-in-Charge.

Aggregate shall, except as noted above, consists of natural sand, crushed stone and

gravel from a source known to produce satisfactory aggregate for concrete and shall

be chemically inert, strong, hard, durable against weathering, of limited porosity

and free from deleterious materials that may cause corrosion to the reinforcement or

may impair the strength and/or durability of concrete. The grading of aggregates

shall be such as to produce a dense concrete of specified strength and consistency

that will work readily into position without segregation and shall be based on the

“mix design” and preliminary test on concrete specified herein-after.

Sampling and testing : Sampling of the aggregates for mix design and

determination of suitability shall be taken under the supervision of the Engineer-in-

Charge and delivered to the laboratory, well in advance of the schedule for placing of

concrete. Records of tests which have been made on proposed aggregates and on

concrete made from this source of aggregates shall be furnished to the Engineer-in-

Charge in advance of the work for use, in determining suitability of the proposed

aggregate.

Storage of aggregates : All coarse and fine aggregates shall be stacked separately in

stock piles in the material yard near the work site in bins properly constructed to

avoid inter mixing of different aggregates. Contamination with foreign materials and

earth during storage and while heaping the materials shall be avoided. The aggregate

must be of specified quality not only at the time of receiving at site but also at the

time of loading into mixer. Rakers shall be used for lifting the coarse aggregate from

bins or stock piles. Coarse aggregate shall be piled in layers not exceeding 1.00

metres in height to prevent conning or segregation. Each layer shall cover the entire

area of the stock pile before succeeding layers are started. Aggregates that have

Page 36: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 36 of 307

become segregated shall be rejected. Rejected material after re-mixing may be

accepted, if subsequent tests demonstrate conformity with required gradation.

Specific Gravity : Aggregates having a specific gravity below 2.6 (saturated surface

dry basis) shall not be used without special permission of the Engineer-in-Charge.

4.3.3.2.1. Fine Aggregate: Fine aggregate except as noted above, and for other than

light weight concrete shall consist of natural or crushed sand conforming to I.S. 383.

The sand shall be clean, sharp, hard, strong and durable and shall be free from dust,

vegetable substances, adherent coating, clay, loam, alkali, organic matter, mica, salt

or other deleterious substances which can be injurious to the setting

qualities/strength/durability of concrete.

4.3.3.2.2. Machine Made Sand : Machine made sand will be acceptable, provided the

constituent rock composition is sound, hard, dense, non-organic, uncoated and

durable against weathering. Machine made sand shall be accepted provided grading

& finer particle limits conform to IS 383.

4.3.3.2.3. Screening and Washing : Sand shall be prepared for use by such screening

or washing or both, as necessary, to remove all objectionable foreign matter while

seParating the sand grains to the required size fractions. Sand with silt content more

than 3 percent will not be permitted to be used unless the same is washed and silt

content is brought within 3% by weight.

Foreign Material Limitations : The percentages of deleterious substances in sand,

delivered to the mixer shall not exceed the following:

Percent by weight

Sl.No Substances Uncrushed Crushed

i) Material finer than 75

micron 3.00 15.00

ii) Shale 1.00 --

iii) Coal and lignite 1.00 1.00

iv) Clay lumps 1.00 1.00

v)

Total of all above

substances

including items (i)

to (iv) for

5.00 2.00

GRADATION : Unless otherwise directed or approved, the grading of sand shall be

within the limits indicated hereunder.

I.S. Sieve

Designation

Percentage passing for

Grading

Zone -I

Grading

Zone -II

Grading

Zone -III

Grading

Zone -IV

9.5 mm 100 100 100 100

4.75mm 90-100 90-100 90-100 95-100

2.36mm 60-95 75-100 85-100 95-100

Page 37: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 37 of 307

1.18 mm 30-70 55-90 75-100 90-100

600 micron 15-34 35-59 60-79 80-1 00

300 micron 5-20 8-30 8-30 20-65

150 micron 0-10 0-10 0-10 0-15

Where the grading falls outside the limits of any particular grading zone of sieves,

other than 600 micron (I.S.) sieve by not more than 5%, it shall be regarded as falling

within that grading zone. This tolerance shall not be applied to percentage passing

the 600 micron (I.S.) sieve or to percentage passing any other sieve size on the

coarser limit of grading zone I or the finer limit of grading zone IV. Fine aggregates

conforming to Grading Zone IV shall not be used unless mix designs and preliminary

tests have shown its suitability for producing concrete of specified strength and

workability.

Fineness Modulus : The sand shall have a fineness modulus of not less than 2.2 or

more than 3.2. The fineness modulus is determined by adding the cumulative

percentages retained on the following I.S. sieve sizes (4.75 mm, 2.36 mm, 1.18 mm,

600 micron, 300 micron and 150 micron) and dividing the sum by 100.

4.3.3.2.4. Coarse Aggregate : Coarse aggregate for concrete, except as noted above and

for other than light weight concrete shall conform to I.S. 383. This shall consist of

natural or crushed stone and gravel, and shall be clean and free from elongated,

flaky or laminated pieces, adhering coatings, clay lumps, coal residue, clinkers, sag,

alkali, mica, organic matter or other deleterious matter.

The coarse aggregate and fine aggregate shall be tested from time to time as required

by the Engineer-in-Charge to ascertain its suitability for use in construction and the

charges for testing aggregate shall be born by the contractor as specified herein

after.

Screening and Washing : Crushed rock shall be screened and/or washed for the

removal of dirt or dust coating, if so demanded by Engineer-in-Charge.

Grading : Coarse aggregates shall be either in single or graded, in both the cases.

The grading shall be within the following limits:

I.S. Sieve

Designati

on

Percentage passing for single sized

aggregates of

Percentage passing for

graded

63

mm

40

mm

20

mm

16mm 12

.5mm

10 mm 40 mm 20 mm 16

mm

12.5

mm 75 mm 100 - - - - - - - - -

53 mm 85-

100

100 - - - - 100 - - -

37.5 mm 0-30 85-

100

100 - - - 95-100 100 - -

19 mm 0-5 0-20 85-

100

100 - - 30-70 95-100 100 100

13.2 mm - - - 85-100 100 - - - 90-1

00

-

11.2 mm - - - - 85-100 100 - - - 90-

100 9.5 mm - 0-5 0-20 0-30 0-45 85-100 10-35 25-55 30-70 40-85

4.75 mm - 0-5 0-5 0-10 0-20 0-20 0-5 0-10 0-10 0-10

2.36 mm - - - - 0-5 0-5 - - - -

Page 38: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 38 of 307

The pieces shall be angular in shape and shall have granular or crystalline surfaces.

Friable, flaky and laminated pieces, mica and shale, if present, shall be only in such

quantities that will not, in the opinion of Engineer-in-Charge, affect adversely the

strength and/or durability of concrete, the maximum size of coarse aggregate shall

be the maximum size specified above, but in no case greater than 1/4 of the

minimum thickness of the member, provided that the concrete can be placed without

difficulty so as to surround all reinforcement thoroughly and fill the corners of form.

Plums above 160 mm. and upto any reasonable size can be used in plain mass

concrete work of large dimensions upto a maximum limit of 20% by volume of

concrete when specifically approved by Engineer-in-Charge. For heavily reinforced

concrete members, the nominal maximum size of the aggregate shall be 5 mm. less

than the minimum clear distance between the reinforcing main bars or 5mm less

than the minimum cover to the reinforcement whichever is smaller. The amount of

fine particles occurring in the Free State or as loose adherent shall not exceed 1%

when determined by laboratory sedim entation tests as per I.S. 2386. After 24 hours

immersion in water, a previously dried sample shall not have gained more than 10%

of its oven dry weight in air, as determined by I.S.2386.

Foreign Material Limitations : The percentages of deleterious substances in the

coarse aggregate delivered to the mixer shall not exceed the following :

Percentage by weight of

aggregates Sl.No. Substances Uncrushed Crushed

i) Material finer than 75 micron I.S.

Sieve

3.00 3.00

ii) Coal and lignite 1.00 1.00

iii) Clay lumps 1.00 1.00

iv) Soft fragments 3.00 --

v) Total of all the above substances 5.00 5.00

4.3.3.3. WATER :

Water used for both mixing and curing shall be clean and free from injurious

amounts of deleterious materials.viz oils, acids, alkalis, salts, sugar, organic

materials or other substances that may be deleterious to concrete or steel. Potable

waters are generally satisfactory for mixing and curing concrete. In case of doubt, the

suitability of water for making concrete shall be ascertained by the compressive

strength and initial setting time test specified in I.S. 456 - 2000. The sample of water

taken for testing shall be typical of the water proposed to be used for concreting, due

account being paid to seasonal variation. The samples shall not receive any

treatment before testing other than that envisaged in the regular supply of water

proposed for use in concrete. The sample shall be stored in a clean container

previously rinsed out with similar water.

Average 28 days compressive strength of at least three 150 mm. concrete cubes

prepared with water proposed to be used shall not be less than 90% of the average

strength of three similar concrete cubes prepared with distilled water as per IS - 516.

The initial setting time of test block made with the appropriate cement and the water

proposed to be used shall not be less than 30 minutes and shall not differ by more

than (+/-) 30 minutes from the initial setting time of control test block prepared with

Page 39: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 39 of 307

the same cement and distilled water. The test blocks shall be prepared and tested in

accordance with the requirements of I.S. 4031 (Part 5).

Where water can be shown to contain an excess of acid, alkali, sugar or salt,

Engineer-in-Charge may refuse to permit its use. As a guide, the following

concentrations represent the maximum permissible values:

a) Limits of acidity : To neutralize 100 ml sample of water, using phenolphthalein as

an indicator, it should not require more than 5 ml. of 0.02 normal NaOH. The details

of test shall be as per I.S. 3025 (Part 22)

b) Limits of alkalinity : To neutralize 100 ml sample of water, using mixed indicator ,

it should not require more than 25 ml. of 0.02 normal H2SO4. The details of test

shall be as per I.S. 3025 (Part 23).

c) Permissible limits for solids shall be as under (water):

Sl.No. Type of solid Tested as

per

Permissible limit (Max.)

i) Organic IS 3025 (Part

18)

200 mg / l

ii) Inorganic IS 3025 (Part

18)

3000 mg / l

Iii) Sulphates (as

SO2)

IS 3025 (Part

24) 400 mg / l

iv) Chlorides (asCl) IS 3025 (Part

32)

2000 mg / l for concrete not

containing

embedded steel and 500 mg/l

for v) Suspended

matter

IS 3025 (Part

17) 2000mg / l

d) The PH value of water shall be not less than 6.

DESIGN MIX CONCRETE :

All reinforced concrete in the works shall be “Design Mix Concrete” as defined in I.S.

456-2000.

4.4.1. Mix Design : This is to investigate the grading of aggregates, water cement ratio,

workability and the quantity of cement required to give works cubes of the

characteristic strength specified. The proportions of the mix shall be determined by

weight. Adjustment of aggregate proportions due to moisture present in the aggregate

shall be made. Mix proportioning shall be carried out according to the ACI standard

designation ACI- 613or Design of concrete mixes - Road research Note No.4,

Department of Scientific and Industrial Research U.K. or I.S. 10262 - 1982.

After award of the work, if so desired by the contractor, he/they may be allowed by

the Engineer-in-Charge, till the designed mix is obtained, to carry out the reinforced

concrete work in foundation and plinth as per equivalent nominal mix against the

specified design mix concrete as per I.S. Codes. However, all other specification for

design mix shall govern for nominal mix also and nothing extra shall be paid for use

of extra cement or else on this account whether the cement is supplied by the

Department or procured by the contractor. Where the quantity of RCC is very small,

Page 40: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 40 of 307

under such circumstance equivalent nominal mix can also be permitted by the

Engineer-in-Charge.

GRADES OF CONCRETE : The concrete shall be in grades designated as

below.

Group Grade Specified Characteristic compressive

strength of Ordinary concrete M 10 10

M 15 15

M 20 20

Standard Concrete M 25 25

M 30 30

M 35 35

M 40 40

M 45 45

M 50 50

M 55 55

High strength

concrete

M 60 60

M 65 65

M 70 70

M 75 75

M 80 80

NOTE :

1. The characteristic strength is defined as the strength of material below which not

more than 5% of the test results are expected to fall.

2. In the designation of a concrete mix, letter "M" refers to the mix and the number to

the specified characteristic compressive strength of 150 mm. size cubes at 28 days

expressed in N/ mm2.

3. Minimum Cement Content, Maximum Water Cement Ratio and Minimum Grade of Concrete for Different Exposures with Normal Weight Aggregates of 20 mm Nominal Maximum size.

Plain concrete Reinforced concrete

Sr

No. Exposure

Minimum

cement

content

Kg/m3

Maximum

Free Water

Cement

Ratio

Minimum

grade of

concrete

Minimum

Cement

Content

Kg/m3

Maximum

Free Water

Cement

Ratio

Minimum

Grade of

concrete

(1) (2) (3) (4) (5) (6) (7) (8)

i) Mild 220 0.60 - 300 0.55 M-20

ii) Moderate 240 0.60 M-15 300 0.50 M-25

iii) Severe 250 0.50 M-20 320 0.45 M-30

iv) Very

severe

260 0.45 M-20 340 0.45 M-35

v) Extreme 280 0.40 M-25 360 0.40 M-40

Page 41: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 41 of 307

NOTE:

1. Cement content prescribed in this table is irrespective of the grades of cement

and it is inclusive of additions mentioned in mineral admixtures. The additions such

as fly ash or ground granulated blast furnace slag may be taken into account in the

concrete composition with respect to the cement content and water-cement ratio if

the suitability is established and as long as the maximum amounts taken into

account do not exceed the limit of pozzolana and slag specified in IS 1489 (Part 1)

and IS 455 respectively.

2. Minimum grade for plain concrete under mild exposure condition is not

specified.

Nominal cover to meet Durability Requirements

Exposure Nominal concrete cover in mm not

less than Mild 20

Moderate 30

Severe 45

Very severe 50

Extreme 75

NOTES

1. For main reinforcement up to 12 mm diameter bar for mild exposure the nominal

cover may be reduced by 5 mm.

2. Unless specified otherwise, actual concrete cover should not deviate from the

required nominal cover by + 10 mm

3. For exposure conditions ‘severe’ and ‘ very severe’ , reduction of 5 mm may be made,

where concrete grade is M 35 and above.

Nominal cover to meet specified period of fire resistance

Fire

resis-

-tance

Nominal cover

BEAMS SLABS RIBS COLUMN

S Simply

Supported

Continuo

us

Simply

Supporte

Continuo

us

Simply

Supporte

Continuo

us

H mm mm mm mm mm mm mm

0.5 20 20 20 20 20 20 40

1 20 20 20 20 20 20 40

1.5 20 20 25 20 35 20 40

2 40 30 35 25 45 35 40

3 60 40 45 35 55 45 40

4 70 50 55 45 65 55 40

NOTES

1. The nominal covers given relate specifically to the minimum member dimensions as per drawing

Page 42: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 42 of 307

2. Cases that lie below the bold line require attention to the additional measures necessary to reduce the risks of spalling.

Adjustments to Minimum cement contents for Aggregates other than 20 mm

Nominal Maximum size:

Sl.No Nominal maximum

Aggregate size mm

Adjustments to

Minimum cement

content kg/ m3 (1) (2) (3)

i) 10 +40

ii) 20 0

iii) 40 -30

For concrete of compressive strength greater than M55 design Parameters given in

the standard may not be applicable and the values may be obtained from specialized

Literatures and experimental results.

The mix shall be designed to produce the grade of concrete having the required

workability and characteristic strength not less than appropriate values given in the

table above.

DEGREE OF CONTROL:

Selection of Water Cement Ratio : Since different cements and aggregates of

different maximum size, grading, surface texture, shape and other characteristics

may produce concretes of different compressive strength for the same free water

cement ratio, the relationship between strength and free water-cement ratio should

preferably be established for the materials actually to be used. In the absence of such

data, the preliminary free water-cement ratio (by mass) corresponding to the target

strength at 28 days may be selected from the relationship shown in Fig.1 of I.S.

10262 .

Alternately, the preliminary free water cement ratio (by mass) corresponding to the

target average strength may be selected from the relationship in Fig.2- I.S. 10262,

using the curve corresponding to the 28 days cement strength to be used for the

purpose.

Other relevant items to be used with design of mix should strictly conform to the

relevant clauses and appendices of I.S. 10262 .

The calculated mix proportions shall be checked by means of trial batches as per IS

10262

The free water cement ratio selected as above, should be checked against the limiting

water cement ratio for the requirement of durability and the lower of the two values

should be adopted.

Whenever there is a change either in required strength of concrete or water cement

ratio or workability or the source of aggregates and/or cement, fresh tests shall be

carried out to determine the revised proportion of the mix to suit the altered

conditions. While designing mix proportions, over wet mixes shall always be avoided.

Page 43: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 43 of 307

While fixing the value for water cement ratio for Design Mix assistance may be derived

from the standard graph showing the relationship between the 28 days compressive

strength of concrete mixes with different water-cement ratios and the 7 days

compressive strength of cement tested in accordance with I.S.269.

It will be contractors sole responsibility to establish the concrete mix designs for

different grades of concrete specified in the work consistent with the workability

required for nature of work and also taking into consideration the assumed standard

deviation which will be expected at site or by establishing the standard deviation

based on 30 test results at site for each grade of concrete so as to produce concrete of

required strength, durability and surface finish. The materials and proportions used

in making the tests to be carried out either at site or under laboratory, conditions

shall be similar in all respects to those to be actually employed in the works, as the

object of these tests is to determine the proportions of cement, aggregates and water

necessary to produce the concrete of the required consistency to give such specified

strength.

4.4.2. STANDARD DEVIATION:

The standard Deviation for each grade of concrete shal be calculated separately.

STANDARD DEVIATION BASED ON TEST RESULTS :

a) Number of test results - The total number of test results required to constitute and

acceptable record for calculation of standard deviation shall be not less than 30.

Attempts should be made to obtain the 30 test results, as early as possible, when a

mix is used for the first time.

b) Standard deviation to be brought up to date - The calculation of the standard

deviation shall be brought upto date after every change of mix design and at least

once a month.

Determination of standard deviation :

i) Concrete of each grade shall be analysed separately to determine its standard

deviation.

The standard deviation of concrete of a given grade shall be calculated using the

following formula from the results of individual tests of concrete of that grade

obtained as specified for test strength of sample:

ii) Estimated standard deviation S = √{ Σ ∆² ÷ (n-1)}

iii) Where ∆ = Deviation of the individual test strength from the average strength of a

sample and n = Number of sample test results.

iv) When significant changes are made in the production of concrete (for example

changes in the materials used, mix design, equipments or technical control), the

standard deviation value shall be separately calculated for such batches of concrete.

Assumed Standard Deviation:

Where sufficient test results for a particular grade of concrete are not available, the

value of standard deviation given in table below may be assumed for design of mix in

Page 44: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 44 of 307

the first instance. As soon as the results of samples are available, actual calculated

standard deviation shall be used and the mix designed properly. However, when

adequate past records for a similar grade exist and justify to the designer a value of

standard deviation different from that shown in table below, it shall be permissible to

use that value.

Grade of

Concrete

Assumed Standard

Deviation

N/

mm²

M 10

M 15

3.5

M 20

M25

4.0

M30

M35

M40

5.0

Note: The above values correspond to the site control having proper storage of

cement: weigh batching of all materials: controlled addition of water: regular

checking of all materials: aggregate grading and moisture contents : and periodical

checking of workability: and strength. Where there is deviation from the above the

values given in the above table shall be increased by 1 N / mm.2

4.4.3. Proportioning, Consistency, Batching and Mixing of Concrete:

4.4.3.1. Proportioning :

Aggregate : The proportions which shall be decided by conducting preliminary tests

shall be by weight. These proportions of cement, fine and coarse aggregates shall be

maintained during subsequent concrete batching by means of weigh batchers

conforming to I.S. 2722, capable of controlling the weights within one percent of the

desired value. Except where it can be shown to the satisfaction of the Engineer-in-

Charge that supply of properly graded aggregate of uniform quality can be maintained

over the period of work, the grading of aggregate shall be controlled by obtaining the

coarse aggregate in different sizes and blending them in the right proportions. The

different sizes shall be stacked in separate stock piles. The grading of coarse and fine

aggregates shall be checked as frequently as possible, as determined by the

Engineer-in-Charge, to ensure maintaining of grading in accordance with samples

used in preliminary mix design. The materials shall be stock piled well in advance of

use.

Cement : The cement shall be measured by weight. Every facility should be provided

to the Engineer-in-Charge for sampling and inspection of stored cement at site of

work.

Page 45: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 45 of 307

Exposure conditions: General environment:

S.No: Environment Exposure Conditions

(1) (2) (3)

i) Mild Concrete surfaces protected against weather or

aggressive conditions,

ii) Moderate

Concrete surfaces sheltered from severe rain or freezing

whilst wet

Concrete exposed to condensation and rain

Concrete continuously under water

iii) Severe

Concrete surfaces exposed to severe rain, alternate

wetting and drying or

occasional freezing whilst wet or severe condensation.

iv) Very severe

Concrete surfaces exposed to seawater spray, corrosive

fumes or severe

freezing conditions whilst wet.

v) Extreme Surface of members in tidal zone

Members in direct contact with liquid/solid aggressive

chemicals.

WATER : Only such quantity of water shall be added to the cement and aggregate in

the concrete mix as to ensure dense concrete, specified surface finish, satisfactory

workability, consistent with strength stipulated for each class of concrete. The water

added to the mix shall be such as not to cause segregation of materials or the

collection of excessive free water on the surface of the concrete.

Definition of water cement ratio :The water cement (W/C) ratio is defined as the

weight of water in mix (including the surface moisture of the aggregates) divided by

the weight of the cement in the mix.

Water cement ratio :The actual water cement ratio to be adopted shall be

determined in each instance by contractor and approved by the Engineer-in-charge.

Proportioning by water-cement ratio : The W/C ratio specified for use by the

Engineer-in-Charge shall be maintained. Contractor shall determine the water

content of the aggregate as frequently as directed by the Engineer in-Charge as the

work progresses and as specified in I.S. 2386 part III and the amount of mixing water

added at the mixer shall be adjusted as directed by the Engineer-in-charge so as to

maintain the specified W/C ratio. To allow for the variation in their moisture content,

suitable adjustments in the weights of aggregates shall also be made.

4.4.3.2. Consistency and slump : Concrete shall be of a consistency and workability

suitable for the conditions of the job. After the amount of water required is

determined, the consistency of mix shall be maintained throughout the progress of

the corresponding parts of the work and approved tests e.g. slump tests, compacting

factor tests etc. in accordance with I.S. 1199, shall be conducted from time to time

to ensure the maintenance of such consistency.

Page 46: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 46 of 307

The following tabulation gives a range of workability which shall generally be used

for various types of construction unless other wise instructed by the Engineer-in-

Charge.

Workability of concrete :

Placing condition Degree of

workability

Slump

(mm) (1) (2) (3)

Blinding Concrete;

Shallow Sections;

Very low See note 1.

Mass concrete; Lightly reinforced Sections in

slabs, Beams,

walls, columns; Floors; Hand placed

pavements; Canal lining;

Low 25-75

Heavily Reinforced sections In slabs, beams,

walls, columns,

Medium 50-100

75-100 Trench fill, In-situ piling High 100-1 50

Tremie Concrete Very High See note 2.

Note :

1. For most of the placing conditions, internal vibrators (needle vibrators) are suitable.

The diameter of the needle shall be determined based on the density and spacing of

reinforcement bars and thickness of sections. For tremie concrete, vibrators are not

required to be used.

2. the ’very low’ category of workability where strict control is necessary, for example

pavement quality concrete, measurement of workability by determination of

compacting factor will be more appropriate than slump (see IS 1199) and a value of

compacting factor of 0.75 to 0.80 is suggested.

3. In the ‘Very high’ category of workability, measurement of workability by

determination of flow will be appropriate (see IS 9103).

PRODUCTION OF CONCRETE:

QUALITY ASSURANCE MEASURES:

In order that the properties of the completed structure be consistent with the

requirements and the assumptions made during the planning and the design,

adequate quality assurance measures shall be taken. The construction should result

in satisfactory strength, serviceability and long term durability so as to lower the

overall life-cycle cost. Quality assurance in construction activity relates to proper

design use of adequate materials and components to be supplied by the producers,

proper workmanship in the execution of works by the contractor and ultimately

proper care during the use of structure including timely maintenance and repair by

the owner.

Page 47: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 47 of 307

Quality assurance measures are both technical and organizational. Some common

cases should be specified in a general Quality Assurance Plan which shall identify the

key elements necessary to provide fitness of the structure and the means by which

they are to be provided and measured with the overall purpose to provide confidence

that the realized project will work satisfactorily in service fulfilling intended needs.

The job of quality control and quality assurance would involve quality audit of both

the inputs as well as the outputs. Inputs are in the form of materials for concrete;

workmanship in all stages of batching, mixing, transportation; placing, compaction

and curing; and the related plant, machinery and equipments; resulting in the

output in the form of concrete in place. To ensure proper performance, it is

necessary that each step in concreting which will be covered by the next step is

inspected as the work proceeds.

Each party involved in the realization of a project should establish and implement a

Quality Assurance Plan, for its participation the project. Suppliers and contractors

activities shall be covered in the plan. The individual quality assurance plans shall

fit into the general Quality Assurance Plan. A quality assurance plan shall define the

tasks and responsibilities of all persons involved , adequate control and checking

procedures, and the organization maintaining adequate documentation of building

process and its results. Such documentation should generally include:

a) test reports and manufacturers certificate for materials, concrete mix design

details;

b) pour cards for site organization and clearance for concrete placement;

c) record of site inspection of workmanship, field tests

d) non-conformance reports, change orders;

e) quality control charts;

f) statistical analysis.

NOTE – Quality control charts are recommended wherever the concrete is in

continuous production over considerable period.

4.4.3.3. Batching and mixing of concrete :

BATCHING

To avoid confusion and error in batching, consideration should be given to using the

smallest practical number of different concrete mixes on any site or in any one plant.

In batching concrete, the quantity of both cement and aggregate shall be determined

by mass; admixture, if solid, by mass; liquid admixture may however be measured in

volume or mass; water shall be weighed or measured by volume in a calibrated tank

( see also IS4925)

Ready mixed concrete supplied by ready-mixed concrete plant shall be preferred. For

large and medium project sites the concrete shall be sourced from ready-mixed

concrete plants or from on site or off site batching and mixing plants ( see IS 4926)

Except where it can be shown to the satisfaction of the engineer-in-charge that

supply of properly graded aggregate of uniform quality can be maintained over a period

Page 48: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 48 of 307

of work, the grading of aggregate should be controlled by obtaining the coarse

aggregate in different sizes and blending them in the right proportions when required,

the different sizes being stocked in separate stock – piles. The material should be

stock-piled for several hours preferably a day before use. The grading of coarse and

fine aggregate should be checked as frequently as possible, the frequency for a given

job being determined by the engineer-in-charge to ensure that the specified grading is

maintained.

The accuracy of the measuring equipment shall be within +/- 2 % of the quantity of

cement being measured and within +/- 3 percent of the quantity of aggregate,

admixtures and water being measured.

Proportion / Type and grading of aggregate shall be made by trial in such a way so as

to obtain densest possible concrete. All ingredients of the concrete should be used by

mass only.

Volume batching may be allowed only where weigh-batching is not practical and

provided accurate bulk densities of materials to be actually used in concrete have

earlier been established. Allowance for bulking shall be made in accordance with IS

2386 (Part 3). The mass volume relationship should be checked as frequently as

necessary, the frequency for the given job being determined by engineer-in-charge to

ensure that the specified grading is maintained.

It is important to maintain the water-cement ratio constant at its correct value. To

this end determination of moisture contents in both fine and coarse aggregates shall

be made as frequently as possible the frequency for a given job being determined by

the engineer-in-charge according to weather conditions. The amount of the added

water shall be adjusted to compensate for any observed variations in the moisture

content. For the determination of moisture content in the aggregates IS 2386 (Part 3)

may be referred to. To allow for the variation in mass of aggregate due to variation in

their moisture content, suitable adjustments in the masses of aggregates shall also be

made. In the absence of exact data only in the case of nominal mixes the amount of

surface water may be estimated from the values given in table below.

Surface water carried by aggregate

Sr.

No. Aggregate

Approximate quantity of

surface water Percent by

mass

l/m3

(1) (2) (3) (4)

i) Very wet sand 7.5 120

ii) Moderately wet sand 5.0 80

iii) Moist sand 2.5 40

iv) Moist gravel or crushed rock 1.25 –2.5 20 – 40

Coarser aggregate less the water it

No substitutions in materials used on the work or alterations in the established

propositions except as permitted as above shall be made without additional tests to

show that the quality and strength of concrete are satisfactory.

Page 49: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 49 of 307

MIXING:

Concrete shall be mixed in a mechanical mixer. The mixer should with IS 1791 and

IS 12119. The mixers shall be fitted with water measuring (metering) devices. The

mixing shall be continued until there is a uniform distribution of the materials and

the mass is uniform in colour and consistency. If there is segregation after

unloading from the mixer, the concrete should be remixed.

For guidance, the mixing time shall be at least 2 min. For other types of more

efficient mixers, manufacturers recommendations shall be followed; for hydrophobic

cement it maybe decided by the Engineer-in-Charge.

Workability should be checked at frequent intervals.

Dosage of retards, plasticizers and super plasticizers shall be restricted to 0.50,1.0

and 2.0 % respectively by weight of cementecious materials and unless higher value

is agreed upon between the manufacturer and constructor based on performance

test.

Each time the work stops, the mixer shall be cleaned out and when next commencing

the mixing, the first batch shall have 10% additional cement to allow for sticking in

the drum.

4.5. SAMPLING AND TESTING CONCRETE IN THE FIELD: Facilities required for

sampling materials and concrete in the field, if Engineer-in-Charge so desires, shall

be provided by contractor at no extra cost. The following equipment with operator

shall be made available at Engineers request (all must be in serviceable condition):

1. Cast iron cube moulds 15 cm. Size 12 Nos.(min.)

2. Slump cone complete with tamping rod 1 Set

3. Lab. balance to weigh upto 5 kg. with sensitivity of 10 1 No.

4. Laboratory balance of 2 kg. capacity and of sensitivity

of 1 gm.

1 No.

5. I.S. sieves for coarse and fine aggregates. 1 Set

6. A set of measures from 5 ltrs. to 0.1 ltr. 1 Set

7. Electric oven with thermostat upto 120 0C. 1 No.

8. Pycnometer 1 No.

9. Calibrated glass jar 1 ltr. Capacity 2 Nos.

10 Glass flasks and metal containers As required

11 Concrete cube testing machine (optional) 1 No.

4.6. TESTING CHARGES : Different tests required to be carried out for concrete

works including the mix design, cube tested as per the above specifications shall be

got done by the contractor at his own cost in one of the approved laboratories. The

choice of laboratory shall rest with the Department. All incidental charges / cost

shall be borne by the contractor.

4.7. SAMPLING AND STRENGTH TEST OF CONCRETE:

Samples from fresh concrete shall be taken as per I.S. 1199 and cubes shall be made, cured and tested at 28 days in accordance with I.S. 516 .

In order to get a relatively quicker idea of the quality of concrete, option tests on

beams for modulus of rupture at 72 (+/-) 2 hours or at 7 days or compressive

Page 50: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 50 of 307

strength tests at 7 days may be carried out in addition to 28 days compressive

strength tests. For this purpose, the values given in table below may be taken for

general guidance in the case of concrete made with ordinary cement. In all cases, the

28 days compressive strength specified shall alone be the criterion for acceptance or

rejection of the concrete. If however, from test carried out in particular job over a

reasonably long period, it has been established to the satisfaction of the Engineer-

in-Charge that a suitable ratio between 28 days compressive strength and modulus of

rupture at 72 (+/-) 2 hours or 7 days or compressive strength at 7 days may be

accepted, the Engineer-in-Charge may suitably relax the frequency of 28 days

compressive strength, provided the expected strength values at the specified early

age are consistently met.

Optional Tests Requirements of Concrete:

Grade of

Concrete

Compressive strength on

15 cm cubes min. at 7

days

Modulus of rupture by

beam At 72 (+/-)

2

At 7 days

N / mm2 N / mm²

M 10 7.0 1.2 1.7

M 15 10.0 1.5 2.1

M 20 13.5 1.7 2.4

M 25 17.0 1.9 2.7

M 30 20.0 2.1 3.0

M 35 23.5 2.3 3.2

M 40 27.0 2.5 3.4

4.7.2. Frequency of Sampling :

Sampling Procedure : A random sampling procedure shall be adopted to ensure that

each concrete batch shall have a reasonable chance of being tested, i.e. the sampling

should be spread over the entire period of concreting and cover all mixing units.

Frequency : The minimum frequency of sampling of concrete of each grade shall be

in accordance with following:

Quantity of concrete Number of samples

in the work (in cum.) 1-5 1

6-15 2

16-30 3

31-50 4

51 and above 4 plus one additional for each

additional

At least one sample shall be taken from each shift. Where concrete is continuous

production unit, such as ready - mixed concrete plant, frequency of sampling may be

agreed upon mutually by suppliers and purchasers.

Page 51: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 51 of 307

4.7.3. Test Specimen : Three test specimen shall be made from each sample for testing at

28 days. Additional cubes may be required for various purposes such as to

determine the strength of concrete at 7days or at the time of striking the form work

or to determine the duration of curing or to check the testing error. Additional cubes

may also be required for testing cubes cured by accelerated methods as described in

I.S. 9013 - 1978. The specimen shall be tested as described in I.S. 516 - 1959.

4.7.4. Test Strength of Samples : The test strength of the samples shall be the average of

the strength of three specimen. The individual variation should not be more than

(+/-) 15 percent of the average.

4.7.5. Consistency : Slump test shall be carried out as often as demanded by the

Engineer-in-Charge and invariably from the same batch of concrete from which the

test cubes are made. Slump tests shall be done immediately after sampling.

4.7.6. Standard Deviation : Vide clause 4.4.2 of this specification.

4.8. ACCEPTANCE CRITERIA :

The concrete shall be deemed to comply with the strength requirements when both

the following conditions are met:

(a) The mean strength determined from any group of four consecutive test

results complies with the appropriate limits in column 2 of Table below

(b) Any individual test result complies with the appropriate limits in column of

Table below.

Characteristic Compressive Strength Compliance Rquirement:

Specified

grade

Mean of the Group of 4

Non-

overlapping

consecutive test

Individual test results

in

N/mm²

(1) (2) (3)

M 15 = / > fck+ 0.825 x

established

standard deviation

(rounded off

= / >fck –3 N/ mm²

0.5 N/mm2

or

= / > fck + 3 N / mm²

M 20

Or

Above

= / > > fck + 0.825 x

established

standard deviation

(rounded off

to nearest 0.5 N/ mm²

or

= / > fck – 4 N / mm²

Note – In the absence of established value of standard deviation, the values given in

(assumed standard deviation) may be assumed, and attempt should be made to

Page 52: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 52 of 307

obtain results of 30 samples as early as possible to establish the value of standard

deviation.

Flexural Strength

When both the following conditions are met, the concrete complies with the specified

flexural strength.

(a) The mean strength determined from any group of four consecutive test

results exceeds the specified characteristic strength by at least 0.3 N/mm2

(b) The strength determined from any test result is not less than the specified

characteristic strength less 0.3N/mm2

Quantity of Concrete Represented by Strength Test Results.

The quantity of concrete represented by a group of four consecutive test results shall

include the batches from which the first and last samples were taken together with

all intervening batches.

For the individual test result requirements given in column 2 of above table or in

item (b) of flexural strength, only the particular batch from which the sample was

taken shall be at risk.

Where the mean rate of sampling is not specified the maximum quantity of concrete

that four consecutive test results represent shall be limited to 60m3

If the concrete is deemed not to comply pursuant to above the structural adequacy of

the parts affected shall be investigated and any consequential action as needed shall

be taken.

Concrete of each grade shall be assessed separately

Concrete is liable to be rejected if it is porous or honey-combed, its placing has been

interrupted without providing a proper construction joint, the reinforcement has

been displaced beyond the tolerances specified, or construction tolerances have not

been met. However, the hardened concrete may be accepted after carrying out

suitable remedial measures to the satisfaction of the Engineer-in-Charge.

4.9. ADMIXTURES :

Admixtures, if used shall comply with IS 9103. Previous experience with and data on

such materials should be considered in relation to the likely standards of

supervision & workmanship to the work being specified. Admixtures should not

impair durability of the concrete not combined with the constituent to form harmful

compounds nor increase the risk of corrosion of reinforcement.

The workability, compressive strength and the slump loss of concrete with & without

the use of admixtures shall be established during the trial mixes before use of

admixtures.

The relative density of liquid admixtures shall be checked for such drum containing

admixtures and compared with the specified value before acceptance.

Page 53: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 53 of 307

The chloride content of the admixtures shall be independently tested for each batch

before acceptance. If two or more admixtures are used simultaneously in the same

concrete mix data should be obtained to assess their interaction and to ensure their

compatibility.

General :

Admixture may be used in concrete only with the approval of Engineer-in-charge

based upon evidence that, with the passage of time neither the compressive strength

nor its durability reduced. When admixtures are used, the designed concrete mix

shall be corrected accordingly. Admixtures shall be used as per manufacturers

instructions and in the manner and with the control specified by Engineer-in-

Charge.

i) Calcium Chloride : Calcium chloride shall not be used for accelerating set of the

cement for any concrete containing reinforcement or embedded steel parts. When

calcium chloride is permitted to be used, such as in mass concrete works, it shall be

dissolved in water and added to the mixing water in an amount not to exceed 1 .5

percent of the weight of cement in each batch of concrete.

ii) Air Entraining Agents : Where specified and approved by Engineer-in-charge,

neutralized vinsol resin or any other approved air entraining agent may be used to

produce the specified amount of air in the concrete mix and these agents shall

conform to the requirements of ASTM standard 6.260, Air Entraining admixtures for

concrete. The recommended total air content of the concrete is 4% (+/-) 1%. The

method of measuring air content shall be as per I.S.1199.

iii) Retarding Admixtures : Where specified and approved by Engineer-in-Charge,

retarding agents shall be added to the concrete mix in quantities specified by

Engineer-in-Charge.

iv) Water Reducing Admixtures : Where specified and approved by Engineer-in-

Charge, water reducing lingo sulfonate mixture shall be added in quantities specified

by Engineer-in-Charge. The admixtures shall be added in the form of a solution.

v) Water Proofing Agents : Where specified and approved by Engineer-in-Charge,

chloride and sulphate free water proofing agents shall be added in quantities

specified by Engineer-in-Charge.

vi) Other Admixtures : Engineer-in-Charge may at his discretion, instruct contractor

to use any other admixture in the concrete.

4.10. INSPECTION OF STRUCTURES :

Immediately after stripping the form work, all concrete shall be carefully inspected

and any defective work or small defects, either removed or made good before concrete

has thoroughly hardened, as instructed by Engineer-in-Charge.

In case of doubt regarding the grade of concrete used or results of cube strength are

observed to be lower than the designed strength as per specifications at 28 days,

compressive strength test of concrete based on core test, ultrasonic test and/or load

test shall be carried out by the digital ultrasonic concrete tester by an approved

agency as directed by the Engineer-in-Charge all at the cost of the contractor. In

case these tests do not satisfy the requirements, the Department will be at liberty to

Page 54: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 54 of 307

reject the concrete, and the contractor, at his own cost, has to dismantle and re-do

the same or carry out such remedial measures as approved by the Department.

4.11. TESTING OF STRUCTURES :

4.11.1. Optional Tests : Engineer-in-charge, if he so desires, may order for tests to

be carried out on cement, sand, coarse aggregate, water etc. in accordance with the

relevant Indian Standards.

Tests on cement will be carried out by Department and shall include (i) fineness

test, (ii) test for normal consistency, (iii) test for setting time, (iv) test for soundness,

(v) test for compressive strength, (vi) test for heat of hydration (by experiment and by

calculations) in accordance with I.S.269.

Tests on sand shall include (i) sieve test, (ii) test for organic impurities, (iii)

decantation test for determining clay and silt content, (iv) specific gravity test, (v) test

for unit weight and bulkage factor, (vi) test for sieve analysis and fineness modulus.

Tests on coarse aggregate shall include (i) sieve analysis, (ii) specific gravity and unit

weight of dry, loose and rounded aggregate, (iii) soundness and alkali aggregate

reactivity, (iv) petrographic examination, (v) deleterious materials and organic

impurities, (vi) test for aggregate crushing value.

The test on aggregates would normally be ordered to be carried out only if Engineer-

in-charge feels the materials are not in accordance with the specifications or if the

specified concrete strengths are not obtained and shall be performed by contractor at

an approved test laboratory. Contractor shall have to pay all the charges of optional

tests. If the work cubes do not give the stipulated strengths, Engineer-in-Charge

reserves the right to ask contractor to dismantle such portions of the work, which in

his opinion are unacceptable and re-do the work to the standards stipulated at

contractors cost.

The unit rate for concrete shall be all inclusive including making preliminary mix

design and test cubes, works cubes, testing them as per specifications, slump tests,

optional tests etc. Complete. However, the Department will test the cubes

departmentally. The contractor will have to make arrangements for transportation to

the laboratory and testing charges will be borne by the contractor.

The contractor should also conduct conclusive tests such as ultrasonic pulse test,

core test etc. to prove the suitability of concrete, in case cube tests give

unsatisfactory results. The cost of the conclusive test should be borne by the

contractor.

4.11.2. Core Test : The points from which cores are to be taken and the number of

cores required, shall be at the discretion of the Engineer-in-Charge and shall be

representative of the whole of concrete concerned.

In no case, however, shall fewer than three cores be tested. Cores shall be prepared

and tested as described in I.S. 516

4.11.3. Concrete in the member represented by a core test shall be considered

acceptable if the average equivalent cube strength of the cores is equal to at least

85% of the cube strength of the grade of concrete specified for the corresponding age

and no individual core has a strength less than 75%.

Page 55: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 55 of 307

In case the core test results do not satisfy the requirements as above or where such

tests have not been done, load test (see 4:11:3) may be resorted to.

4.11.4. LOAD TESTS ON PARTS OF STRUCTURE :

Load tests should be carried out as soon as possible after expiry of 28 days from the

time of placing of concrete.

The structure should be subjected to a load equal to full dead load of the structure

plus 1.25 times the imposed load for a period of 24 hours and then the imposed load

shall be removed.

Note: Dead load includes weight of the structural members plus weight of finishes

and walls or partitions, if any, as considered in the design.

The deflection due to imposed load only shall be recorded. If within 24 hours of

removal of the imposed load, the structure does not recover at least 75% of the

deflection under super imposed load, the test may be repeated after a lapse of 72

hours. If the recovery is less than 80%, the structure shall be deemed to be

unacceptable.

If the maximum deflection in mm. shown during 24 hours under load is less than

40L2/D, where L is the effective span in M. and D the overall depth of the section in

mm, it is not necessary for recovery to be measured and the recovery provision as

above will not apply.

4.11.5. Other non-destructive test methods may be adopted, in which case the

acceptance criteria shall be agreed upon between the Engineer-in-Charge and the

Contractor and the test shall be done under expert guidance.

MEMBERS OTHER THAN FLEXURAL MEMBERS:

Members other than flexural members should be preferably investigated by

analysis.

Non – destructive tests:

Non-destructive tests are used to obtain estimation of properties of concrete in the

structure. The methods adopted include ultrasonic pulse velocity [see IS 13311 (Part

1)] and rebound hammer [IS 13311 (Part 2)], probe penetration, pull out and

maturity. Non destructive tests provide alternatives to core tests for estimating the

strength of concrete in a structure, or can supplement the data obtained from a

limited number of cores. These methods are based on measuring a concrete property

that bears some relationship to strength/ the accuracy of these methods, in part is

determined by the degree of correlation between strength and the physical quality

measured by the non-destructive tests.

Any of these methods may be adopted, in which case the acceptance criteria shall be

agreed upon prior to testing.

4.11.6. TESTING OF UNDERGROUND WATER TANK/SEPTIC TANK/UNDERGROUND

STRUCTURES :

The tank will be tested after the completion according to the procedure laid down here:

Page 56: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 56 of 307

The middle compartment shall be filled first to its full height and the leakage if any

shall be checked on its outer surfaces and if found, the same shall be examined

carefully and defects rectified/grouted if necessary. The drop in level of surface of

water shall also be recorded for 48 hours. If this drop in level exceeds 20 mm. and

shows any leakage in the said walls, necessary steps shall be taken in consultation

with the Engineer-in-Charge.

After this compartment is tested to the satisfaction of the Engineer-in-Charge, all

water from middle compartment shall be pumped into side compartment to the full

height and checked for water leakages from the outer surfaces of the tank as well as

inner surface of the middle compartment. The drop in level of surface of water shall

also be checked as stated above and defects rectified.

The external surface of the tank shall then be plastered and cured as per the

specifications and back filling shall be taken up thereafter. The water from the

compartments shall then be pumped out and the inner surface of the tank in all

compartments then be checked and defects rectified.

After satisfactory completion of checks, internal plaster shall be taken up as

specified in the specifications.

The contractor shall be responsible for carrying out the complete test, rectifying the

leakages if any. The cost of providing all equipments, labour for carrying out tests

shall be borned by the contractor. The rates quoted for concreting items for

constructing under ground water tank shall be inclusive of testing of RCC tank for

water tightness as per above specifications. The contractor shall make his own

arrangement to tap the water from the departmental supply line for filling the tank, if

supply of water stipulated under Schedule ‘A’. If supply of water not stipulated under

Schedule ‘A’, the contractor shall make his own arrangement as per contract

conditions at his own cost.

4.11.7. UNSATISFACTORY TESTS :

Should the results of any test prove unsatisfactory, or the structure shows signs of

weakness, undue deflection or faulty construction, contractor shall remove and

rebuild the member or members involved or carry out such other remedial measures

as may be required by Engineer-in-Charge. Contractor shall bear the cost of so doing,

unless the failure of the member or members to fulfill the test conditions is proved to

be solely due to faulty design. The cost of load and other tests shall be borne by

Contractor if the tests show unsatisfactory results; otherwise such costs will be

borne by the Department.

4.12. CONCRETE IN ALKALI SOILS WATER & AGGREGATES:

Some aggregates containing particular varieties of silica may be susceptible to attack

by alkalis (Na20 and K20) originating from cement and other sources, producing an

expansive reaction which can cause cracking and disruption of concrete. Damage to

concrete from this reaction will normally only occur when all the following are present

together.

a) A high moisture level, within the concrete.

b) A cement with high alkali content, or another source of alkali;

c) Aggregate containing an alkali reactive constituent.

Page 57: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 57 of 307

Where the service records of particular cement / aggregate combination are well

established, and do not include any instances of cracking due to alkali-aggregate

reaction, no further precautions should be necessary. When the materials are

unfamiliar, precautions should take one or more of the following forms:

a) Use of non-reactive aggregate from alternate sources

b) Use of low alkali ordinary Portland cement having total alkali content not more than

0.6 percent (as Na2O equivalent).

Further advantage can be obtained by use of fly ash (Grade I) conforming to IS 381

2or granulated blast furnace slag conforming to IS 12089 as part replacement of

ordinary Portland cement (having total alkali content as Na2O equivalent not more

than 0.6 percent) provided fly ash content is at least 20 % or slag content is at least

50 percent.

a) Measures to reduce the degree of saturation of the concrete during service such as

use of impermeable membranes

b) Limiting the cement content in the concrete mix and thereby limiting total alkali

content in the concrete mix as per approval of Engineer- in-charge.

Chlorides in the concrete

Whenever there is chlorides in concrete there is an increased risk of corrosion of

embedded metal. The higher the chloride content or if subsequently exposed to

warm moist conditions, the greater the risk of corrosion. All constituents may

contain chlorides and concrete may be contaminated by chlorides from the external

environment. To minimise the chance of deterioration of concrete from harmful

chemical salts, the levels of such harmful salts in concrete materials, that is, cement,

aggregates, water and admixtures, as well as by diffusion from the environment

should be limited. The total amount of chloride content (as Cl) in the concrete at the

time of placing shall be as given below in the table.

Limits of Chloride Content of Concrete

Sl.

No Type or Use of Concrete

Maximum Total Acid

soluble

Chloride Content

Expressed as

kg/m3 of Concrete.

(1) (2) (3)

i) Concrete containing metal and steam

cured at 0.4

ii) Reinforced concrete or plain concrete

containing 0.6

iii) Concrete not containing embedded

metal or any 3.0

The total acid soluble chloride content should be calculated from the mix

proportions and the major chloride contents of each of the constituents. Whenever

Page 58: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 58 of 307

possible the total chloride content of the concrete should be determined as per the

approval of the Engineer-in-Charge.

Sulphates in concrete:

Sulphates are present in most cements and in some aggregates; excessive amounts

of water-soluble sulphate from these or other mix constituents can cause expansion

and disruption of concrete. To prevent this, the total water-soluble sulphate content

of the concrete mix, expressed as SO3, should not exceed 4 per cent by mass of the

cement in the mix. The sulphate content should be calculated as the total from the

various constituents of the mix as per the approval of the Engineer-in-Charge.

The 4 percent limit does not applied to concrete made with super sulphated cement

complying with IS 6909 or as approved by the Engineer-in-Charge.

4.13. PREPARATION PRIOR TO CONCRETE PLACEMENT, FINAL INSPECTION &

APPROVAL :

Before the concrete is actually placed in position, the inside of the form work shall be

inspected to see that they have been cleaned and oiled. Temporary openings shall be

provided to facilitate inspection, especially at bottom of columns and wall forms, to

permit removal of saw dust, wood shavings, binding wire, rubbish, dirt etc. Opening

shall be placed or holes drilled so that these materials and water can be removed

easily. Such openings / holes shall be later suitably plugged.

The various traders shall be permitted ample time to install drainage and plumbing

lines, floor and trench drain, conduits, hangers, anchors, inserts, sleeves, bolts,

frames and other miscellaneous embedments to be cast in the concrete as indicated

on the drawing or as necessary for the proper execution of the work. All such

embedments shall be correctly positioned and securely held in the forms to prevent

displacement during depositing and vibrating of concrete.

Slots, openings, holes, pockets etc. shall be provided in the concrete work in the

positions indicated in the drawings or as directed by the Engineer-in-Charge.

Reinforcement and other items to be cast in concrete shall have clean surfaces that

will not impair bond.

Prior to concrete placement, all works shall be inspected and approved by Engineer-

in-Charge, and if found unsatisfactory, concrete shall not be poured until all defects

have been corrected at contractors cost.

Approval by Engineer-in-Charge of any and all materials and work as required herein

shall not relieve contractor from his obligations to produce finished concrete in

accordance with the drawings and specifications.

4.13.1. RAIN OR WASH WATER :

No concrete shall be placed in wet weather or on a water covered surface. Any

concrete that has been washed by heavy rain shall be entirely removed, if there is

any sign of cement and sand having been washed from the concrete mixture. To

guard against damage which may be caused by rain, the works shall be covered with

tarpaulins immediately after the concrete has been placed and compacted before

leaving the work unattended. Any water accumulating on the surface of the newly

Page 59: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 59 of 307

placed concrete shall be removed by approved means and no further concrete shall

be placed thereon until such water is removed. To avoid flow of water over/around

freshly placed concrete, suitable drains and sumps shall be provided.

4.13.2. BONDING MORTAR :

Immediately before concrete placement begins, prepared surfaces, except form work,

which will come in contact with concrete to be placed, shall be covered with a bonding

mortar of same strength of concrete.

4.13.3. TRANSPORTATION :

All buckets, containers or conveyers used for transporting concrete shall be mortar-

tight. All means of conveyance shall be adopted to deliver concrete of the required

consistency and plasticity without segregation or loss of slump whatever method of

transportation is employed. Chute shall not be used to transport the concrete without

the written permission of the Engineer-in-Charge and concrete shall not be rehandled

before placing.

4.13.4. Retempered or Contaminated Concrete :

Concrete must be placed in its final position before it becomes too stiff to work. On no

account water shall be added after the initial mixing. Concrete which has become stiff

or has been contaminated with foreign materials and which has not been placed

within half an hour of mixing water with cement shall be rejected.

4.13.5. CLEANING OF EQUIPMENT :

All equipments used for mixing, transporting and placing of concrete shall be

maintained in clean condition. All pans, buckets, hoppers, chutes, pipe lines and

other equipments shall be thoroughly cleaned after each period of placement.

4.13.6. PROCEDURE FOR PLACING OF CONCRETE :

1. Engineers Approval of Equipment and Methods : Before any concrete is placed, the

entire placing programme, consisting of equipment, layout proposed procedures and

methods shall be submitted to Engineer-in-Charge and no concrete shall be of such

size and design to ensure a practically continuous flow of concrete during depositing

without segregation of materials, considering the size of the job and placement

location.

2. Time Interval Between Mixing and Placing : Concrete shall be placed in its final

position before the cement reaches its initial set and concrete shall normally be

compacted in its final position within thirty minutes of leaving the mixer and once

compacted it shall not be disturbed.

3. Avoiding Segregation : Concrete shall in all the cases be deposited as nearly as

practicable directly in its final position and shall not be rehandled or caused to flow in

a manner which will cause segregation, loss of materials, displacement of

reinforcement, shuttering or embedded inserts or impair its strength. For locations

where direct placement is not possible, and in narrow forms, contractor shall provide

suitable prop and Elephant Trunks to confine the movement of concrete. Special care

shall be taken when concrete is dropped from a height, especially if reinforcement is

in the way, particularly in columns and thin walls.

Page 60: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 60 of 307

4. Placing by Manual Labour : Except when otherwise approved by Engineer-in-Charge,

concrete shall be placed in the shuttering by shovels or other approved implements

and shall not be dropped from a height more than 1.0 m. or handle in a manner

which will cause segregation.

5. Placing by Mechanical Equipment : The following specifications shall apply when

placing of concrete by sue of mechanical equipment is specially called for while

inviting bids or is warranted, considering the nature of work involved.

The control of placing shall begin at the mixer discharge. Concrete shall be discharged

by a vertical drop into the middle of the bucket of hopper and this principle of a

vertical discharge of concrete shall be adhered-to through out all stages of delivery

until the concrete comes to rest in its final position.

Type of buckets : All concrete shall be conveyed from the mixer to the place of final

deposit in suitable buckets, dumpers, containers which shall be leak-tight. All means

of conveyance shall be adopted for delivering concrete to the required consistency/

workability and plasticity without segregation.

Central bottom dump buckets of a type that provides for positive regulation of the

amount and rate deposition of concrete in all dumping position shall be employed.

Operation of Bucket : In placing concrete in large open areas, the bucket shall be

spotted directly over the position designated and then lowered for dumping. The open

bucket shall clear the concrete already in place and the height of drop shall not

exceed 1.0 m. The bucket shall be opened slowly to avoid high vertical bounce.

Dumping of buckets on the swing or in any manner which results in seParation of

ingredients or disturbance of previously placed concrete will not be permitted.

6. Placement in Restricted Forms : Concrete placed in restricted forms by borrows,

buggies, cars, short chutes or hand shovelling shall be subject to the requirement for

vertical delivery of limited height to avoid segregation and shall be deposited as nearly

as practicable in its final position.

7. Chutting : Where it is necessary to use transfer chutes, specific approval of

Engineer-in-Charge must be obtained to type, length, slopes, baffles, vertical

terminal and timing of operations. These shall be so arranged that almost

continuous flow of concrete is obtained at the discharge and without segregation. To

allow for the loss of mortar against the sides of the chutes, the first mixes shall have

less coarse aggregate. During cleaning of chutes, the waste water shall be kept clear

of the forms. The concrete shall not be permitted to fall from the end of the chutes

by more than 1.0 m. Chutes, when approved for use, shall have slopes not flatter

than 1 vertical to 3 horizontal and not steeper than 1 vertical to 2 horizontal, chutes

shall be of metal or metal line and of rounded cross section. The slopes of all chute

sections shall be approximately same. The discharge end of the chutes shall be

maintained above the surfaces of the concrete in the forms.

8. Placing by Pumping/ Pneumatic Placers : Concrete may be conveyed and placed

by mechanically operated equipment e.g. pumps or pneumatic placers, only with the

written permission of Engineer-in-Charge. The slump shall be held to the minimum,

necessary for conveying concrete by this method.

Page 61: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 61 of 307

When pumping is adopted, before pumping of concrete is started, the pipelines shall

be lubricated with one or two batches of mortar composed of one part cement and

two parts sand. The concrete mix shall specially designed to suit pumping. Care shall

be taken to avoid stoppages in work once pumping has started.

When pneumatic placer is used, the manufacturers advice on layout of pipeline shall

be followed to avoid blockages and excessive wear. Restraint shall be provided at the

discharge box to cater for the reaction at the end.

Manufacturers advice shall be followed regarding concrete quality and all other

related matters when pumping/ pneumatic placing equipments are used.

9. Concrete in Layers : Concreting, once started, shall be continuous until the pour is

completed. Concrete shall be placed in successive horizontal layers of uniform

thickness ranging from 15 cm. to 90 cm. as directed by Engineer-in-Charge. These

shall be placed as rapidly as practicable to prevent the formation of cold joints or

planes of weakness between each succeeding layers within the pour. The thickness

of each layer shall be such that it can be deposited before the previous layer has

stiffened. The bucket loads or other units of deposit, shall spotted progressively

along the face of the layer with such overlap as will facilitate spreading the layer to

uniform depth and texture with a minimum of shovelling stones into mortar rather

than mortar on to stones. Such a condition shall be corrected by redesign of mix or

other means, as directed by Engineer-in-Charge.

Bedding of Layers : The top surface of each pour and bedding planes shall be

approximately horizontal unless otherwise instructed.

COMPACTION :

4.13.7. COMPACTION : Concrete shall be compacted during placing, with approved

vibrating equipment, until the concrete has been consolidated to the maximum

practicable density, is free of pockets of coarse aggregate and fits tightly against all

form surfaces, reinforcement and embedded fixtures. Particular care shall be taken

to ensure that all concrete placed against the form faces and into corners of forms or

against hardened concrete at joints is free from voids or cavities. The use of

vibrators shall be consistent with the concrete mix and caution is to be exercised

not to over vibrate the concrete to the point of segregation.

1. Type of Vibrators : Vibrators shall conform to I.S. specifications. Type of vibrators

to be used shall depend upon the structure where concrete is to be placed. Shutter

vibrators, to be effective, shall be firmly secured to the form work which must be

sufficiently rigid to transmit the vibrations and strong enough not to be damaged by

it. Immersion vibrators shall have No load frequency amplitude and acceleration as

per I.S.2505 depending on the size of the vibrator. Immersion vibrators in sufficient

numbers and each of adequate size shall be used to properly consolidate all

concrete. Tapping or external vibrating of forms by hand tools or immersion

vibrators will not be permitted.

2. Use of Vibrators : The exact manner application and the most suitable machines for

the purpose must be carefully considered and operated by experienced men.

Immersion vibrators shall be inserted vertically at points not more than 450 mm.

apart and withdrawn when air bubbles cease to come to the surface. Immersion

vibrators shall be withdrawn very slowly. In no case shall immersion vibrators be

Page 62: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 62 of 307

used to transport concrete inside the forms. Particular attention shall be paid to

vibration at the top of lift, e.g. in a column or wall.

3. Melding successive batches : When placing concrete in layers, which are advancing

horizontally as the work progress, great care shall be exercised to ensure adequate

vibration, blending and melding of the concrete between the successive layers.

4. Penetration of vibrators : The immersion vibrator shall penetrate the layer being

placed and also penetrate the layer below while the under layer is still plastic to

ensure good bond and homogeneity between the two layers and prevent the formation

of cold joints.

5. Vibrating against reinforcement : Care shall be taken to prevent contact of

immersion vibrators against reinforcement steel. Immersion vibrators shall not be

allowed to come in contact with reinforcement steel after start of initial set. They shall

also not be allowed to come in contact with forms or finished surfaces.

6. Use of Form Attached Vibrators : Form attached vibrators shall be used only with

specific authorisation of Engineer-in-Charge.

7. Use of surface vibrators : The use of surface vibrators will not be permitted under

normal conditions. However, for thin slabs, such as highways, runways and similar

construction, surface vibrations by specifically designed vibrators may be permitted,

upon approval of Engineer-in-Charge.

4.13.8. STONE POCKETS AND MORTAR PONDAGES : Formation of stone pockets or

mortar pondages in corners and against faces of forms shall not be permitted.

Should these occur, they shall be dug out, reformed and refilled to a sufficient depth

and shape for thorough bounding as directed by Engineer-in-Charge.

4.13.9. PLACEMENT INTERVAL : Except when placing with slip forms, each

placement of concrete in multiple lift work, shall be allowed to set for at least 24

hours after the final set of concrete and before the start of a subsequent placement.

1. Special Provision in Placing : When placing concrete in walls with openings, in

floors of integral slab and beam construction and other similar conditions, the

placing shall stop when the concrete reaches the top of the opening in walls or

bottom horizontal surface of the slabs as the case may be. Placing shall be resumed

before the concrete in place takes initial set, but not until it has had time to settle

as determined by Engineer-in-charge.

2. Placing Concrete Through Reinforcing Steel : While placing concrete through

reinforcing steel, care shall be taken to prevent segregation of the coarse aggregate.

Where the congregation of steel make placing difficult, it may be necessary to

temporarily move the top steel aside to get proper placement and restore reinforcing

steel to design position.

4.13.10. BLEEDING : Bleeding or free water on top of concrete being deposited in to

the forms, shall be caused to stop the concrete pour and the conditions causing this

defect corrected before any further concreting is resumed.

Page 63: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 63 of 307

4.14. CONSTRUCTION JOINTS AND KEYS :

Concrete shall be placed without interruption until completion of the part of the

work between predetermined construction joints, as specified therein after. Time

lapse between the pouring of adjoining units shall be as specified in the drawings or

as directed by Engineer-in-Charge.

Construction joints and cold joints:

Joints are a common source of weakness and therefore it is desirable to avoid them. If

this is not possible, their number shall be minimized . Concreting shall be carried

out continuously up to construction joints the position and arrangement of which

shall be indicated by the designer. Construction joints should comply with IS 11817.

Construction joints shall be placed at accessible locations to permit cleaning out of

laitance, cement slurry and unsound concrete, in order to create rough/uneven

surface. It is recommended to clean out laitance and cement slurry by using wire

brush on the surface of joint immediately after initial setting of concrete and to clean

at the same immediately thereafter. The prepared surface should be in a clean

saturated surface dry condition when fresh concrete is placed, against it. In the case

of construction joints at locations where the previous pour has been cast against

shuttering the recommended method of obtaining a rough surface for the previously

poured concrete is to expose the aggregate with a high pressure water jet or any

other appropriate means.

Fresh concrete should be thoroughly vibrated near construction joints so that mortar

from the new concrete flows between large aggregates and develop proper bond with

old concrete.

Where high shear resistance is required at the construction joints, shear keys

may be provided.

Sprayed curing membranes and release agent s should be thoroughly removed from

joint surfaces.

If stopping of concreting becomes unavoidable anywhere, a properly formed

construction joint shall be made where the work is stopped. Joints shall be either

vertical or horizontal, unless shown otherwise in drawing. In case of an inclined or

curved member, the joints shall be at right angles to the axis of the member.

Vertical joints in walls shall be kept to a minimum. Vertical joints shall be formed

against a stop board, horizontal joints shall be level and wherever possible, arranged,

so that the joint lines coincide with the architectural features of the finished work.

Battens, shall be nailed to the form work to ensure a horizontal line and if directed,

shall also be used to form a grooved joint. For tank walls, similar work joints shall

be formed as per I.S. 3370. Concrete that is in the process of setting shall not be

disturbed or shaken by traffic either on the concrete itself or upon the shuttering.

Horizontal and vertical construction joints and shear keys shall be located and shall

conform in detail to the requirements of the plans unless otherwise directed by

Engineer-in-Charge. Where not described, the joints shall be in accordance with the

following:

1. Column Joints : In a column, the joint shall be formed 75 mm. below the lowest

soffit of the beams including haunches if any. In flat slab construction the joint

Page 64: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 64 of 307

shall be 75 mm. below the soffit of column capital. At least 2 hours shall elapse after

depositing concrete in column, piers or walls, before depositing in beams, girders or

slabs supported thereon.

2. Beam and Slab Joints : Concrete in a beam shall be placed throughout without a

joint but if the provision of a joint is unavoidable, the joint shall be vertical and at

the centre or within the middle third of the span unless otherwise shown in drawing.

Where a beam intersects a girder, the joints in the girder shall be offset a distance

equal to twice the width of the beam and additional reinforcement provided for shear.

The joints shall be vertical throughout the full thickness of the concrete member. A

joint in a slab shall be vertical and Parallel to the principal reinforcement. Where it is

unavoidable at right angles to the principle reinforcement, the joint shall be vertical

and at the middle of span.

3. Joints in Liquid Retaining Structures : Vertical construction joints in watertight

construction will not be permitted unless indicated on the drawings. Where a

horizontal construction joint is required to resist water pressure, special care shall be

taken in all phases of its construction to ensure maximum water tightness.

4. Dowels : Dowels for concrete work, not likely to be taken up in the near future,

shall be wrapped in tar paper and burlap.

5. Mass Foundations : Mass foundations shall be poured in lifts not exceeding 1.5 m.

in height unless, otherwise indicated on the drawings and approved by Engineer-in-

Charge.

6. Treatment of Construction Joints on Resuming Concreting : Drier shall be used

for the top lift or horizontal pours to avoid a laitance. All laitance and loose stones

shall be thoroughly and carefully removed by wire brushing/ hacking and surface

washed.

Just before concreting is resumed, the roughened joint surface shall be thoroughly

cleaned and loose matter removed and then treated with a thin layer of cement grout

of proportion specified by Engineer-in-Charge and worked well into the surface. The

new concrete shall be well worked specially against the prepared face before the

grout mortar sets. Special care shall be taken to obtain thorough compaction and to

avoid segregation of the concrete along the joint plane.

4.15. CURING, PROTECTING, REPAIRING, AND FINISHING:

1. Curing : All concrete shall be cured by keeping it continuously damp for the period

of time required for complete hydration and hardening to take place. Preference

shall be given to the use of continuous sprays or ponded water, continuously

saturated covering of sacking, canvas, hessian or other absorbent materials, or

approved effective curing compounds applied with spraying equipment capable of

producing a smooth, even textured coat. Extra precautions shall be exercised in

curing concrete during cold and hot weather as outlined hereinafter. The quality of

curing water shall be the same as that used for mixing concrete.

Certain types of finish or Preparation for overlaying concrete must be done at certain

stages of curing process and special treatment may be required for specific concrete

surface finish.

Page 65: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 65 of 307

Curing of concrete made of high alumina cement and supersulphated cement shall

be carried out as directed by Engineer-in-Charge.

1. Curing with Water : Fresh concrete shall be kept continuously wet for a minimum

period of 14 days from the date of placing of concrete, following a lapse of 12 to 24

hours after laying concrete. The curing of horizontal surfaces exposed to the drying

winds shall however begin immediately the concrete has hardened. Water shall be

applied to unformed concrete surfaces within 1 hour after concrete has set. Water

shall be applied to formed surfaces immediately upon removal of forms. Quantity of

water applied shall be controlled so as to prevent erosion of freshly placed concrete.

2. Continuous Spraying : Curing shall be assured by use of an ample water supply

under pressure in pipes, with all necessary appliances of hose sprinklers and

spraying devices. Continuous fine mist spraying or sprinkling shall be used, unless

otherwise specified or approved by Engineer-in-Charge.

3. Alternate Curing Methods : Whenever in the judgment of Engineer-in-Charge, it

may be necessary to omit the continuous spray method, covering of clean sand or

other approved means such as wet gunny bags, which will prevent loss of moisture

from the concrete, may be used. Any type of covering which would stain or damage

the concrete during or after the curing period, will not be permitted. Covering shall

be kept continuously wet during the curing period.

For curing of concrete in pavements, side-walks, floors, flat roofs or other level

surfaces, the ponding method of curing is preferred. The method of containing the

ponded water shall be approved by Engineer-in-Charge. Special attention shall be

given to edges and corners of the slab to ensure proper protection to these areas.

The ponded areas shall be kept continuously filled with water during the curing

period.

4. Curing Compounds : Surface coating type curing compound shall be used only on

special permission of Engineer-in-Charge. Curing compounds shall be liquid type

while pigmented, conforming to U.S. Bureau of Reclamation Specification. No curing

compound shall be used on surface where future blending with concrete, water or

acid proof membrane or painting is specified.

5. Curing Equipment : All equipments and materials required for curing shall be on

hand and ready for use before concrete is placed.

6. Moist Curing: Exposed surfaces of concrete shall be kept continuously in a damp or

wet condition by ponding or by covering with a layer of sacking , canvas, hessian or

similar materials and kept constantly wet for at least seven days from the date of

placing concrete. In case of ordinary Portland cement and at least ten days where

mineral admixtures or blended cement are used. The period of curing shall not be

less than ten days of concrete exposed to dry and hot wheather conditions. In the

case of concrete the mineral admixtures or blended cement are used, it is

recommended that the above minimum periods may be extended to fourteen days as

per the approval of the Engineer-in-Charge.

7. Membrane Curing: Approved curing compounds may be used in lieu of moist curing

with the permission of Engineer-in-charge. Such compounds shall be applied to all

exposed surfaces of the concrete as soon as possible after the concrete has set.

Impermeable membranes such as poly ethylene sheeting covering, closely the

Page 66: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 66 of 307

concrete surface may also be used to provide effective barrier against evaporation.

For the concrete containing Portland pozzolana cement, Portland slag cement or

mineral admixtures increased period of curing may be decided by Engineer-in-charge.

The rate of strength development at early age of concrete made with super sulphated

cement is significantly reduced at lower temperatures. Super sulphated cement

concrete is seriously affected by inadequate curing and the surface has to be kept

moist for at least seven days or more as per the approval of the Engineer-in-Charge.

4.16. PROTECTING FRESH CONCRETE :

Fresh concrete shall be protected from the elements, from defacements and damage

due to construction operations by leaving forms in place for ample period as

specified later in this specification. Newly placed concrete shall be protected by

approved means such as tarpaulins from rain, sun and winds. Steps as approved by

Engineer-in-Charge, shall also be taken to protect immature concrete from damage

by debris, excessive loading, vibrations, abrasion or contact with other materials etc.

that may be warned against and prevented from disturbing green concrete during its

setting period. If it is necessary that workmen enter the area of freshly placed

concrete, Engineer-in-Charge may require that bridges be placed over the area.

4.17. REPAIR AND REPLACEMENT OF UNSATISFACTORY CONCRETE :

Immediately after the shuttering is removed, the surface of concrete shall be very

carefully gone over and all defective areas called to the attention of Engineer-in-

Charge who may permit patching of the defective areas or else reject the concrete unit

either partially or entirely. Rejected concrete shall be removed and replaced by

Contractor at no additional expense to the Department. Holes left by form bolts etc.

shall be filled up and made good with mortar composed of one part of cement to one

and half parts of sand passing through 2.36 mm. I.S. sieve after removing any loose

stones adhering to the concrete. Mortar filling shall be struck off flush at the face of

the concrete. Concrete surface shall be finished as described under the particular

item of work.

Superficial honey combed surfaces and rough patches shall be similarly made good

immediately after removal of shuttering, in the presence of Engineer-in-Charge and

superficial water and air holes shall be filled in. The mortar shall be well worked into

the surface with wooden float. Excess water shall be avoided. Unless instructed

otherwise by Engineer-in-Charge, the surface of the exposed concrete placed against

shuttering shall be rubbed down immediately on removal of shuttering to remove fine

or other irregularities, care being taken to avoid damaging the surfaces. Surface

irregularities shall be removed by grinding.

If reinforcement is exposes or the honey combing occurs at vulnerable position e.g.

ends of beams or columns, it may be necessary to cut out the member completely or

in part and reconstruct. The decision of Engineer-in-Charge shall be final in this

regard. If only patching is necessary, the defective concrete shall be cut out till solid

concrete is reached (or to a minimum depth of 25 mm.), the edges being cut

perpendicular to the affected surface or with a small under cut if possible, anchors,

tees or dowels shall be provided in slots whenever necessary to attach the new

concrete securely in place. An area extending several centimetres beyond the edges

Page 67: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 67 of 307

and the surfaces of the prepared voids shall be saturated with water for 24 hours

immediately before the patching material is placed.

1. Use of Epoxy : The use of epoxy for bonding fresh concrete used for repairs will be

permitted upon written approval of Engineer-in-Charge. Epoxies shall be applied in

strict accordance with the instruction of the manufacturer.

2. Method of Repair : Small size holes having surface dimensions about equal to the

depth of the hole, holes left after removal of form bolts, grout insert holes and slots

cut for repair of cracks shall be repaired as follows:

The hole to be patched shall be roughened and thoroughly soaked with clean water

until absorption stops.

A 5 mm. thick layer of grout of equal parts of cement and sand shall be well brushed

into the surface to be patched followed immediately by the patching concrete which

shall be well consolidated with a wooden float and left slightly proud of the

surrounding surface. The concrete patch shall be built up in 10 mm. thick layers.

After an hour or more, depending upon weather conditions, it shall be worked off

flush with a wooden float and a smooth finish obtained by wiping with hessian. Steel

trowel shall not be used for this purpose. The mix for patching shall be of the same

materials and in the same proportions as that used in the concrete being repaired,

although some reduction in the maximum size of the coarse aggregates may be

necessary and the mix shall be kept as dry as possible.

Mortar filling by air pressure (guniting) shall be used for repair of areas to large

and/ or too shallow for patching with mortar. Patched surfaces shall be given a final

treatment to match the colour and texture of the surrounding concrete. White

cement shall be substituted for ordinary cement, if so directed by Engineering-in-

Charge, to match the shade of the patch with the original concrete.

3. Curing of Patched Work : The patched area shall be covered immediately with an

approved non-staining water-saturated material such as gunny bags, which shall be

kept continuously wet and protected against sun and wind for a period of 24 hours.

Thereafter, the patched area shall be kept wet continuously by a fine spray of

sprinkling water for not less than 10 days.

4. Approval by Engineer-in-Charge : All materials, procedures and operations used in

the repair of concrete and also the finished repair work shall be subject to the

approval of Engineer-in-Charge. All fillings shall tightly bonded to the concrete and

shall be sound, free from shrinkage cracks after the fillings have been cured and

dried.

4.18. FINISHING :

This specification is intended to cover the treatment of concrete surfaces of all

structures.

1. Finish for Formed Surfaces : The type of finish for formed concrete surfaces shall

be as follows, unless otherwise specified by the Engineer in charge:

For surfaces against which backfill or concrete is to be placed, no treatment is

required except repair of defective areas.

Page 68: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 68 of 307

For surfaces below grade, which will receive waterproofing treatment, the concrete

shall be free of surface irregularities which would interfere with proper application of

the water-proofing materials which is specified for use.

Unless specified, surfaces which will be exposed when the structure is in service shall

receive no special finish, except repair of damaged or defective concrete, removal of

fins and abrupt irregularities, filling of holes left by form ties and rods and clean up

of loose or adhering debris.

Surfaces which will be exposed to the weather and which would normally be levelled,

shall be sloped for drainage. Unless the drawing specify a horizontal surface or

shows the slope required, the tops of narrow surfaces such as staircase treads,

walls, curbs and Parapets shall be sloped across the width approx. as 1 in 30.

Broader surfaces such as walkways, roads, parking areas and platforms shall be

sloped about 1 in 50. Surfaces that will be covered by backfill or concrete, sub floors

to be covered with concrete topping, terrazzo or quarry tile and similar surfaces

shall be smooth, screeded and leveled to produce even surfaces. Surface

irregularities shall not exceed 6mm. Surfaces which will not be covered by backfill,

concrete or tile topping such as outside decks, floors of galleries and sumps,

Parapets, gutters, sidewalks, floors and slabs shall be consolidated, screeded and

floated.

Excess water and laitance shall be removed before final finishing. Floating may be

done with hand or power tools and started as soon as the screeded surface has

attained a stiffness to permit finishing operations and these shall be the minimum

required to produce a surface uniform in texture and free from screed marks or other

imperfections. Joints and edges shall be tooled as called for on the drawings or as

directed By Engineer-in-Charge.

2. Standard Finish for Exposed Concrete : Exposed concrete shall mean any concrete

other than floors or slabs exposed to view upon completion of the job. Unless

otherwise specified on the drawings, the standard finish for exposed concrete shall be

of smooth finish.

A smooth finish shall be obtained with use of lined or plywood forms having smooth

and even surfaces and edges. Panels and form linings shall be of uniform size and

be as large as practicable and installed with closed joints. Upon removal of forms,

the joint marks shall be smoothed off and all blemishes, projections etc. removed,

leaving the surfaces reasonably smooth and unmarred.

3. Integral Cement Concrete Finish : When specified on the drawings, an integral

cement concrete finish of specified thickness for floors and slabs shall be applied

either monolithic or bonded, as specified in the drawings and as per I.S.2571. The

surface shall be compacted and then floated with a wooden float or power floating

machine. The surface shall be tested with a straight edge and any high and low

spots eliminated. Floating or trowelling of the finish shall be permitted only after all

surface water has evaporated. Dry cement or a mixture of dry cement and sand shall

not be sprinkled directly on the surface of the cement finish to absorb moisture or to

stiffen the mix.

4. Rubbed Finish : A rubbed finish shall be provided only on exposed concrete

surfaces as specified on the drawings. Upon removal of forms, all fins and other

projections on the surfaces shall be carefully removed, off sets leveled and voids

Page 69: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 69 of 307

and/ or damaged sections immediately saturated with water and repaired by filling

with concrete or mortar of the same composition as was used in the surfaces. The

surfaces shall then be thoroughly wetted and rubbed with carborandum or other

abrasive. Cement mortar may be used in the rubbing, but the finished surfaces shall

not be brush coated with either cement or grout after rubbing. The finished surfaces

shall present a uniform and smooth appearance.

4.19. PROTECTION :

All concrete shall be protected against damage until final acceptance by Engineer-

in-Charge.

4.20. FOUNDATION BEDDING, BONDING AND JOINTING :

All surfaces upon or against which concrete will be placed shall be suitably prepared

by thoroughly cleaning, washing and dewatering as may be indicated in the plans or

as Engineer-in-Charge may direct to meet the various situations encountered in the

work.

Soft or spongy areas shall be cleaned out and back filled with either a soil cement

mixture, lean concrete or clean sand fill compacted to minimum density of 90%

Modified Proctor, unless otherwise mentioned in schedule of quantities.

Prior to construction of form work for any item where soil will not act as bottom form,

approval shall be obtained from Engineer-in-Charge as to the suitability of the soil.

4.21. PREPARATION OF ROCK STRATA OF FOUNDATIONS :

To provide tight bond with rock foundations, the rock surface shall be prepared and

the following general requirements shall be observed:

Concrete shall not be deposited on large sloping rock surface. Where required by

Engineer-in-Charge or as indicated on the plans, the rock shall be cut to form rough

steps or benches to provide roughness or a more suitable bearing surface.

Rock foundation stratum shall be prepared by picking, barring, wedging and similar

methods which will leave the rock in an entirely sound and unshattered condition.

Shortly before concrete is placed, the rock surface shall be cleaned with high

pressure water and air jet even though it may have been previously cleaned in that

manner.

Prior to placing concrete, the rock surface shall be kept wet for a period of 2 to 4

hours unless otherwise directed by the Engineer-in-Charge.

Before placing concrete on rock surfaces, all water shall be removed from

depressions to permit through inspection and proper bonding of the concrete to the

rock.

4.22. PREPARATION OF EARTH STRATA OF FOUNDATIONS :

All earth surfaces upon which or against which concrete is to be placed, shall be well

compacted and free from standing water, mud or debris. Soft, yielding soils shall be

removed and replaced with suitable earth and well compacted as directed by the

Page 70: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 70 of 307

Engineer-in-Charge. Where specified, lean concrete shall be provided in the earth

stratum for receiving concrete. The surface of absorptive soil against which concrete

is to be placed shall be moistened thoroughly so that no moisture will be drawn form

the freshly placed concrete and later shall help to cure the concrete.

4.23. PREPARATION OF CONCRETE SURFACES :

Preparation of concrete surface upon which additional concrete is to be placed later,

shall preferably be done by scarifying and cleaning while the concrete is between its

initial and final set. This method shall be used wherever practicable and shall

consist of cutting the surface with picks and stiff brooms and by use of an approved

combination of air and water jet as directed by Engineer-in-charge. Great care shall

be taken in performing this work to avoid removal of too much mortar and the

weakening of the surface by loosening of aggregate. When it is not practicable to

follow the above method, it will be necessary to employ air tools to remove laitance

and roughen the surface.

The final required result shall be a pitted surface from which all dirt, unsound

concrete, laitance and glazed mortar have been removed.

4.24. BONDING TREATMENT (MORTAR) :

After rock or concrete surfaces upon which new concrete is to be placed have been

scarified, cleaned and wetted as specified herein, it shall receive a bonding

treatment, immediately before placement of the concrete.

The bonding medium shall be a coat of cement sand mortar. The mortar shall have

the same cement-sand proportion as the concrete which shall be placed on it. The

water cement ratio shall be determined by placing conditions and as approved by

Engineer-in-Charge.

Bonding mortar shall be placed in sufficient quantity to completely cover the surface

about 10 mm. thick for rock surface and about 5 mm. thick for concrete surfaces. It

shall be brushed or broomed over the surface and worked thoroughly into all cracks,

crevices and depressions. Accumulations or puddles of mortar shall not be allowed

to settle in depressions and shall be brushed out to a satisfactory degree as

determined by Engineer-in-Charge.

Mortar shall be placed at such a rate that it can be brushed over the surface just in

advance of placement of concrete. Only as much area shall be covered with mortar

as can be covered with concrete before initial set in the mortar takes place. The

amount of mortar that will be permitted to be placed at any one-time, or the area

which is to cover, shall be in accordance with Engineer-in-Charge.

4.25. CLEANING AND BONDING OF FORMED CONSTRUCTION JOINTS :

Vertical construction joints shall be cleaned as specified above or by other methods

approved by Engineer-in-Charge. In placing concrete against formed construction

joints, the surfaces of the joints, where accessible, shall be coated thoroughly with

the specified bed-joint bonding mortar immediately before they are covered with

concrete or by scrubbing with wire brooms, dipped into the fresh concrete. Where it

is impracticable to apply such a mortar coating, special precautions shall be taken

to ensure that the new concrete is brought into intimate contact with the surface of

the joint by carefully puddling and spading with aid of vibrators and suitable tools.

Page 71: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 71 of 307

4.26. EXPANSION AND CONTRACTION :

Provision shall be made for expansion and contraction in concrete by use of special

type joints located as shown in the drawings. Construction joint surfaces shall be

treated as specified in the specifications, shown in the drawings or as directed by

Engineer-in-Charge.

4.27. HOT WEATHER REQUIREMENTS :

All concrete work performed in hot weather shall be in accordance with I.S. 456,

except as herein modified.

Admixtures may be used only when approved by Engineer-in-Charge.

Adequate provision shall be made to lower concrete temperatures by cool

ingredients, eliminating excessive mixing, preventing exposure of mixers and

conveyers to direct sunlight and the use of reflective paint, on mixers etc. The

temperature of the freshly placed concrete shall not be permitted to exceed 300C.

Consideration shall be given to shading aggregate stock piles from direct rays of the

sun and spraying stock piles with water, use of cold water available and burying,

insulation, shading and/ or painting white the pipe lines and water storage tanks

and conveyances.

In order to reduce loss of mixing water, the aggregates, wooden forms, subgrade,

adjacent concrete and other moisture absorbing surfaces, shall be well wetted prior

to concreting. Placement and finishing shall be done as quickly as possible.

Extra precautions shall be taken for the protection and curing of concrete.

Consideration shall be given to continuous water curing and protection against high

temperatures and drying hot wind for a period of at least 7 days immediately after

concrete has set and after which normal curing procedures may be resumed.

4.28. PLACING CONCRETE UNDER WATER :

Under all ordinary conditions all foundations shall be completely dewatered and

concrete placed in the dry. However, when concrete placement under water is

necessary, all work shall conform to I.S.456 and procedure shall be as follows:

Method of Placement : Concrete shall be deposited under water by means of

tremies or drop bottom buckets of approved type.

4.29. DIRECTION, INSPECTION AND APPROVAL :

All work requiring placement of concrete underwater shall be designed, directed and

inspected with regard to the local circumstances and purposes. All under water

concrete shall be placed according to the plans or specifications and as directed and

approved by Engineer-in-Charge.

4.30. PRECAST CONCRETE & 4.31 PRECAST REINFORCED CONCRETE

Precast concrete & precast reinforced concrete shall comply with I.S. 456, and with

the following requirements:

4.31.1. General requirements : Precast reinforced concrete units such as columns,

Page 72: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 72 of 307

fencing posts, door and window frames, lintels, chajjas, copings, sills, shelves,

slabs, louvers etc. shall be of grade of mix as specified and cast in forms or moulds.

The forms / moulds shall be of fiber glass or of steel sections for better finish.

Provision shall be made in the forms and moulds to accommodate fixing devices

such as nibs, clips, hooks, bolts and forming of notches and holes. Precast concrete

shall be cast on suitable bed or platform with firm foundation and free from wind.

The contractor may precast the units on a cement or steel platform which shall be

adequately oiled provided the surface finish is of the same standard as obtained in

the forms. Each unit shall be cast in one operation. Contractor shall be responsible

for the accuracy of the level or shape of the bed or platform. A suitable serial

number and the date of casting shall be impressed or painted on each unit.

4.31.2. Concrete used for precasting the units should be well proportioned, mixed,

placed and thoroughly compacted by vibrations or tamping to give a dense concrete

free from voids and honeycombing.

4.31.3. Precast articles shall have a dense surface finish showing no coarse aggregate

and shall have no cracks or crevices likely to assist in disintegration of concrete or

rusting of steel or other defects that would interfere with the proper placing of the

units. All angles of the precast units with the exception of the angles resulting from

the splayed or chamfered faces shall be true right angles. The arises shall be clean

and sharp except those specified or shown to be rounded. The wearing surface shall

be true to the lines. On being fractured, the interior of the units should present a

clean homogenous appearance.

4.31.4. The longitudinal reinforcement shall have a minimum cover of 12 mm or twice

the diameter of the main bar, whichever is more, unless otherwise directed in

respect of all items except fencing posts or electric posts where the minimum cover

shall be 25 mm.

4.31.5. CURING

After having been cast in the mould or form the concrete shall be adequately

protected during setting in the first stages of hardening from shocks and from

harmful effects of frost, sunshine, drying winds and cold. The concrete shall be

cured at least for 7 days from the date of casting.

4.31.6. The precast articles shall be matured for 28 days before erection or being built

in so that the concrete shall have sufficient strength to prevent damage to units

when first handled. Side shutters shall not be struck in less than 24 hours after

depositing concrete and no precast unit shall be lifted until the concrete reaches

a strength of at least twice the stress to which the concrete may be subjected at

the time of lifting.

4.31.7. MARKING

Precast units shall be clearly marked to indicate the top of member and its

location and orientation in the structure.

4.31.8. Precast units shall be stored, transported and placed in position in such a

manner that they will not be overstressed or damaged. The lifting and removal of

precast units shall be undertaken without causing shocks, vibration or under

bending stresses to or in the units. Before lifting and removal takes place,

Page 73: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 73 of 307

contractor shall satisfy Engineer-in-Charge or his representative that the

methods he proposes to adopt for these operations will not over-stress or

otherwise affect seriously the strength of the precast units. The reinforced side of

the units shall be distinctly marked.

4.32. PRECAST CEMENT CONCRETE JALI :

4.32.1. The Jali shall be of cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone

aggregate 6 mm nominal size) reinforced with 1 .6 mm thick mild steel wire,

unless otherwise specified.

4.32.2. Fixing : The Jali shall be set in position true to plumb and level before the

joints, sills and soffits of the openings are plastered. It shall then be properly

grouted with cement mortar 1:3 (1 cement : 3 coarse sand) and rechecked for

levels. Finally the jambs, sills and soffits shall be plastered embedding the jali

uniformly on all sides.

4.32.3. Measurement : The Jali shall be measured for its gross superficial area. The

length and breadth shall be measured correct to a cm. The thickness shall not be

less than that specified.

4.32.4. Rate : The rate shall be inclusive of materials and labour involved in all the

operations described above except plastering of jambs, sill and soffits, which will

be paid for under relevant items of plastering.

4.33. CURING :

All precast work shall be protected from the direct rays of the sun for at least 7

days after casting and during that period each units shall be kept constantly

watered or preferably by completely immersed in water if the size of unit so

permits. Otherwise curing practices as given in clauses stated earlier shall be

followed.

4.34. SLOTS, OPENINGS ETC. :

Slots, openings or holes, pockets etc. shall be provided in the concrete work in

the positions indicated in the drawings or as directed by the Engineer-in-Charge.

Any deviation from the approved drawings shall be made good by contractor at

his own expenses without damaging any other work. Sleeves, bolts, inserts etc.

shall also be provided in concrete work where so specified.

4.35. GROUTING :

4.35.1. Standard Grout : Grout shall be provided as specified in the drawing.

The proportions of grout shall be such as to produce a flowable mixture

consistent with minimum water content and shrinkage. The grout proportions

shall be limited as follows:

Page 74: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 74 of 307

Use Grout thickness Mix. proportions W/C. Ratio in

(Max.)

a)Fluid

mix

Under 25 mm. One part Portland

cement

0.44

b) General 25 mm. and over

but less than 50

mm.

One part Portland

cement

to 2 parts of sand.

0.53

c) Stiff

mix.

50 mm. and over One part Portland

cement to

0.53

Sand shall be such as to produce a flowable grout without any tendency to

segregate. Sand, for general grouting purposes, shall be graded within the

following limits:

Passing I.S. sieve 2.36 mm. 95 to 100%

Passing I.S. sieve 1.18 mm. 65 to 95%

Passing I.S. sieve 300 micron above 10 to 30%

Passing I.S. sieve 150 micron above 3 to 10%

Sand for fluid grouts shall have the fine material passing the 300 and 150 micron

sieves at the upper limits specified above.

Sand for stiff grouts, shall meet the usual grading specifications and concrete.

Surface to be grouted shall be thoroughly roughened and cleaned of all foreign

matter and laitance.

Anchor bolts, anchor bolt holes and bottom of equipment and column base plates

shall be cleaned of all oil, grease, dirt and loose material. The use of hot, strong,

caustic solution for this purpose will be permitted.

Prior to grouting, the hardened concrete surfaces to be grouted, shall be saturated

with water. Water in anchor bolt holes shall be removed before grouting is started.

Forms around base plates shall be, reasonably, tightened to prevent leakage of

the grout.

Adequate clearance shall be provided between forms and base plate to permit

grout to be worked properly into place.

Grouting, once started shall be done quickly and continuously to prevent

segregation, bleeding and breakdown of initial set. Grout shall be worked from

one side of one end to the other to prevent entrapment of air. To distribute the

grout and to ensure more release from entrapped air, link chains can be used to

work the grout into place.

Grouting through holes in base plate shall be by pressure grouting.

Variations in grout mixes and procedures shall be permitted if approved by the

Engineer-in-Charge.

Page 75: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 75 of 307

4.35.2. Special Grout : Special grout where specified on the drawing shall be

provided in strict accordance with the manufacturers instructions/ specifications

on the drawings.

4.36. INSPECTION :

All materials, workmanship and finished construction shall be subject to the

continuous inspection and approval of Engineer-in-Charge.

All rejected materials supplied by contractor and all rejected work or construction

performed by contractor, as is not in conformance with the specifications and

drawings, shall immediately be replaced at no additional expense to the

Department.

Approval of any preliminary material or phase of work shall in no way relieve the

contractor from the responsibility of supplying concrete and/ or producing

finished concrete in accordance with the specifications and drawings.

All concrete shall be protected against damage until final acceptance by the

Department or its representatives.

4.37. CLEAN UP :

Upon the completion of concrete work, all forms, equipments, construction tools,

protective coverings and any debris resulting from the work shall be removed

from the premises.

All debris i.e. empty containers, scrap wood etc. shall be removed to dump daily

or as directed by the Engineer-in-Charge.

The finished concrete surfaces shall be left in a clean condition to the

satisfaction of the Engineer-in-Charge.

4.38. PLAIN CEMENT CONCRETE FOR GENERAL WORK :

For plain cement concrete work, the specification for materials viz. cement, sand,

fine and coarse aggregates and water shall be the same as that specified in

reinforced concrete work specification.

But the proportion of mix will be nominal and the ratio of fine and coarse

aggregate may be slightly adjusted within limits, keeping the total value of

aggregates to a given volumes of cement constant to suit the sieve analysis of both

the aggregates. Cement shall on no account be measured by volume, but it shall

always be used directly from the bags (i.e. 50 kg/bag).

The proportion of cement, sand, aggregate and water for concrete of proportion

1:5:10, 1:4:8, 1:3:6 & 1:2:4 by volume shall generally consist of quantities as

given below :

Page 76: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 76 of 307

Proportio

n

of

Ingredien

ts

Cement Quantity of materials used per bag of

cement

Fine

aggregate

(sand)

Coarse

aggregate

Total of fine

sand

coarse

aggregates

Water

1:5:10 1 175 ltrs. 350

ltrs.

800

kgs.

60 ltrs.

1:4:8 1 140 ltrs. 280 625 45 ltrs.

1:3:6 1 105 ltrs. 210

ltrs.

480

kgs.

34 ltrs.

1:2:4 1 70 ltrs. 140

ltrs.

330

kgs.

32 ltrs.

The quantity of water used shall be such as to produce concrete of consistency

required by the particular class of work and shall be decided by the use of a

slump cone. Sufficient care should be taken to see that no excess quantity of

water is used. The final proportion of the aggregate and quantity of water shall be

decided by the Engineer-in-charge on the basis of test in each case.

Mix proportion Cement

in bags

Sand

in cum

Coarse Aggregate in CUM Water

Ordinary mix in

volume 40 mm 20 mm 12 mm

1:5:10 2.60 0.475 0.6623 0.2583 - 156

1:4:8 3.40 0.500 0.688 0.6883 - 153

1:3:6 (with 40mm

aggr.)

4.4 0.485 0.672 0.672 0.262 176

1:3:6 (with 20 mm 4.4 0.485 - 0.727 0.242 162.5

1:2:4 (with 20 mm

aggr.)

6.4 0.47 - 0.705 0.235 205

1:2:4 (with 40 mm 6.4 0.47 0.544 0.241 0.126 235

1:1.5:3 8.0 0.441 - 0.6615 0.2205 240

1:1:2 12.2

0

0.45 - 0.675 0.225 330

The slump shall be specified for each class of work and shall in general be as

follows:

Type of concrete Max. slump (in

mm.) Mass concrete 50

Concrete below water proofing treatment 50

Coping 25

Floor paving 50

All plain concrete should be preferably mixed in a drum type powder driven

machine with a loading hopper which will permit the accurate measure of various

ingredients. If hand mixing is authorised, it should be done on a water tight

platform.

The mixing of each batch in the concrete mixer shall continue for not less than

1.5 minutes after the materials and water are in the mixer. The volume is mixed

materials per batch shall not exceed the manufacturers rated capacity of the

Page 77: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 77 of 307

mixer. The mixer shall rotate at a peripheral speed of about 60 metres per

minute.

Concrete shall be poured and consolidated in its final position within half an hour

of mixing. The retempering of concrete which has partially hardened, that is

remixing with or without additional cement aggregate or water shall not be

permitted. Concrete of mix 1:3:6 and 1:2:4 will be required to be vibrated if

specified and directed by the Engineer. In case of the thickness of concrete is

more than 150 mm., it may be vibrated as directed by the Engineer.

The concrete shall be cured for 10 days in ordinary weather and 15 days in hot

weather.

Measurements for the work done shall be exact length, breadth and depth shown

in figures on the drawings or as directed by the Engineer and after the concrete is

consolidated. No extra shall be paid for excess quantity resulting from faulty

workmanship.

4.39. SPECIFIC REQUIREMENTS FOR CONCRETE AND ALLIED WORKS :

The following specific requirements shall be met within addition to those provided

in the clause of specification for Concrete and allied works.

4.39.1. General : If so specified in Schedule ‘A’ for the work, the Department shall

supply with specification for “Concrete and allied works” and the contractor shall

be solely responsible for supplying mixed concrete in accordance with the

specification for concrete and allied works and also this specification. The rates

for the reinforced concrete work shall be based on the issue rates of cement and

steel as given in the schedule ‘A’.

4.39.2. Water : Clean water in pipes under pressure shall be provided by the

contractor with all necessary equipment for giving a nozzle pressure of not less

than 2.0 kg/ sqcm. for the convenient and effective jetting of rock foundations and

concrete surfaces, for cooling aggregate required for concrete, for curing concrete

and other requirements.

4.39.3. Fire Protection System : The contractor shall provide and maintain at all

times in adequate fire protection system to protect his equipment, materials and

construction In case of an emergency, the contractor shall permit the Engineer-

in-Charge to use the system for protecting equipment, works etc. on the project.

4.39.4. Concrete : The rates for all concrete work should be based as per

specifications and taking into consideration the guidelines indicated in special

instruction under relevant clause.

4.39.5. The Placement Intervals : Each placement of concrete shall be allowed to set

for a period of 48 hours and longer when required, before the start of subsequent

placement. A time gap between the two adjoining pours in the horizontal plane

and the two adjacent pours in the vertical plane shall be 7 days and 3 days

respectively.

4.39.6. FINISHING OF CONCRETE :

1. General : Unless otherwise specified, concrete finishes shall conform to the

Page 78: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 78 of 307

following specifications: Finish F1, F2 and F3 shall describe formed

surface.

Finish U1, U2 and U3 shall describe un-formed surface.

Off sets or fins caused by disposed or misplaced form sheathing lining or form

sections or by defective form lumber shall be referred to as abrupt irregularities.

All other irregularities shall be referred to as gradual irregularities. Gradual

irregularities shall be measured as deviation from a plane surface with a

template 1.5 m. long for formed surface and 3 m. long for unformed surfaces.

2. Formed Surfaces :

Finish F1—shall apply to all formed surfaces for which finish F2, F3 or any other

special finish is not specified and shall include filling up all form tie holes.

Finish F2—shall apply to all formed surfaces so shown on the drawings or

specified by the Engineer-in-Charge. This shall include filling all form tie-holes,

repair of gradual irregularities exceeding 6 mm., removal of ridges and abrupt

irregularities by grinding.

Finish F3—shall apply to all formed surfaces exposed to view or where shown in

the drawings or specified by the Engineer-in-Charge. Finish F3 - shall include all

measures specified for Finish-F2 and in addition, Filling air holes with mortar

and treatment of the entire surface with sack rubbed finish. It shall also include

clean up of loose and adhering debris. Where a sack rubbed finish is specified,

the surfaces shall be prepared within two days after removal of the forms.

The surface shall be wetted and allowed to dry slightly before mortar is applied

by sack rubbing. The mortar used shall consist of one part cement to one and

half parts by volume of fine (minus No. 16 mesh) sand. Only sufficient mixing

water to give the mortar a workable consistency shall be used. The mortar shall

then be rubbed over the surface with a fine burlap or linen cloth so as to fill all

the surface voids. The mortar rubbed in the voids shall be allowed to stiffen and

solidify after which the whole surface shall be wiped clean so that the surface

presents a uniform appearance without air holes, irregularities etc.

Curing of the surface shall be continued for a period of ten (10) days.

3. Unformed Surfaces :

Finish U1—shall apply to all unformed surfaces for which the finish U2, U3 or

any other special finish is not specified and shall include screeding the surface of

the concrete to the required slope and grade. Unless the drawing specifies a

horizontal surface or shows the slope required, the tops of narrow surfaces such

as stair, treads, walls, curbs and Parapets shall be sloped approximately 10 mm.

per 300 mm. width. Surfaces to be covered by backfill or concrete sub-floors to

be covered with concrete topping, terrazzo and similar surfaces shall be smooth

screeded and leveled to produce even surface, irregularities not exceeding 6 mm.

Finish U2—shall apply to all unformed surfaces as shown in the drawing or

specified by the Engineer-in-Charge and shall include screeding and applying a

wood float finish to the surface of the concrete to the required slopes and grade.

Page 79: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 79 of 307

Repair of abrupt irregularities unless a roughened texture is specified. Repair of

gradual irregularities exceeding 6 mm.

Finish U3—shall apply to unformed surfaces for which a high degree of surface

smoothness is required, where shown on the drawing or specified by the

Engineer-in-Charge. This shall include screeding, floating and applying a steel

trowel finish to the surface of the concrete to the required slopes and grade.

Repair of abrupt irregularities.

Repair of gradual irregularities exceeding 6 mm., finishing joints and edges of

concrete with edging tools.

4.40. MODE OF MEASUREMENT FOR CONCRETE WORK :

General : Concrete as actually done shall be measured for payment, subject to

the following tolerances, unless otherwise stated hereinafter. Any work done

extra over the specified dimensions shall not be measured for payment.

a) Linear dimensions shall be measured in full centimetres except for the

thickness of slab which shall be measured to the nearest half centimetre.

b) Areas shall be worked out to the nearest 0.01 sqm.

c) Cubic contents shall be worked out to the nearest 0.001 cum.

d) The concrete shall be measured for its length, breadth and height/ depth

limiting dimensions to those specified on drawings or as directed by the

Engineer-in-Charge.

NOTE : The sizes of RCC members as assumed in the estimate are based on

preliminary drawings and are likely to be changed. The contractor is not entitled

to any extra claim due to such changes.

Deductions:

No deductions shall be made for the following :

a) Ends of dissimilar materials e.g. joists, beams, posts, girders, rafters, purlins,

trusses, corbels, steps etc. upto 500 sq cm. in cross section.

b) Opening upto 0.1 sqm. (1000 sq cm)

c) Volume occupied by reinforcement.

d) Volume occupied by pipes, conduits, sheathing etc. not exceeding 25 sq cm.

each in cross sectional area. Nothing extra shall be paid for leaving and

finishing such cavities and holes.

i. COLUMN FOOTING :

R.C.C. in foundation and footings shall be measured for its length, breadth and

depths limiting dimensions to those specified in drawing or as ordered in writing

by the Engineer-in-Charge. In case of tapering portions of column footings, the

quantities shall be calculated by the Formula : Volume V = H/3 x [ A1 + A2 +

Page 80: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 80 of 307

sqrt {A1 x A2}] ; where A1 = Area at top of footing, A2 = Area at bottom of footing

and H = Height of footing.

ii. COLUMN :

Column shall be measured from top of footings to the plinth level and from plinth

level to the structural slab level and to the subsequent structural slab levels.

Measurements for higher grade concrete in columns at its junction with lower

grade concrete beams shall be restricted to the column section supporting the

beam in question.

iii. WALL

All walls shall be measured from top of the wall footing to the plinth level and

from plinth level to the top of structural first floor and to subsequent floors.

iv. BEAM AND LINTEL :

Beam shall be measured from face to face of the columns, walls, cross beams

including haunches if any. The depth of the beams shall be measured from the

top of the slab to the bottom of the beam except in the case of inverted beam

where it shall be measured from top of slab to top of beams. The beams and lintels

with narrow width even though acting as facia in elevation in some cases, will be

measured as beams and lintels only.

v. SLAB:

The length and breadth of slab laid to correct thickness as shown in the detailed

drawings or as ordered by the Engineer-in-Charge shall be measured between

beams, walls and columns.

vi. CHAJJAS, FACIAS, FINS AND MULLIONS:

a) Chajjas shall be measured net from supporting faces upto the edges of chajjas

without any facia.

b) Facia shall be measured full excluding chajja thickness.

c) End fins shall be measured full.

d) Intermediate fins, mullions shall be measured between chajjas or other

supporting structural members.

e) Parapets shall be measured from top of slab/ chajja.

vii. STAIRCASE :

The concrete in all members of staircase like waist slabs, steps, cantilever steps,

stringer beams etc. shall be measured for their length, breadth and depth, limiting

dimensions to those specified on drawings. No deductions shall be made for

embedded plugs, pockets.

Rates: The rate for P.C.C/ R.C.C. shall include the cost of all materials, labour,

transport, tools and plants and all the operations mentioned hitherto, including

or excluding the cost of form work and/ or reinforcement as mentioned in the

Page 81: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 81 of 307

schedule of quantities. The rates also shall include the cost of testing materials,

mix design, cube test and allied incidental expenses.

* * *

5. FORM WORK :

5.0. GENERAL :

The form work shall consist of shores, bracings, sides of beams and columns,

bottom of slabs etc. including ties, anchors, hangers, inserts etc. complete which

shall be properly designed and planned for the work. The false work shall be so

constructed that up and down vertical adjustment can be made smoothly. Wedges

may be used at the top or bottom of timber shores, but not at both ends, to

facilitate vertical adjustment or dismantling of form work.

5.1. DESIGN OF FORM WORK :

The design and engineering of form work as well as its construction shall be the

responsibility of Contractor. If so instructed, the drawings and calculations for

the design of the form work shall be submitted well in advance to the Engineer-

in-Charge for approval before proceeding with work, at no extra cost to the

Department. Engineer-in-Charges approval shall not however, relieve Contractor

of the full responsibility for the design and construction of the form work. The

design shall take into account all the loads vertical as well as lateral that the forms

will be carrying including live and vibration leadings.

5.2. TOLERANCES :

Tolerances are a specified permissible variation from lines, grade or dimensions

given in drawings. No tolerances specified for horizontal or vertical building lines or

footings shall be constructed to permit encroachment beyond the legal boundaries.

Unless otherwise specified, the following tolerances will be permitted:

5.2.1. TOLERANCES FOR R.C. BUILDINGS :

i. Variation from the plumb:

a. In the line and surfaces of columns, piers, walls and in buttresses: 5 mm. per

2.5 m., but not more than 25 mm

b. For exposed corner columns and other conspicuous lines.

In any bay or 5 m. maximum: (+/-) 5 mm.

In 10 m. or more: (+/-) 10 mm.

ii. Variation from the level or from the grades indicated on the drawings.

a. In slab soffits, ceilings, beam soffits and in arrises.

In 2.5 m.: (+/-) 5 mm.

In any bay or 5 m. maximum: (+/-) 8 mm.

In 10 m. or more: (+/-) 15 mm.

Page 82: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 82 of 307

b. For exposed lintels, sills, Parapets, horizontal grooves and other conspicuous

lines.

In any bay or 5 m. maximum: (+/-) 15 mm.

In 10 m or more: (+/-) 10 mm.

iii. Variation of the linear building lines from established position in plan and

related position of columns, walls and partitions.

In any bay or 5 m. maximum: (+/-) 10 mm.

In 10 m or more: (+/-) 20 mm.

iv. Variations in the sizes and locations of sleeves, openings in walls and floors

except in the case of and for anchor bolts: (+/-) 5 mm.

v. Variation in cross-sectional dimensions of columns and beams and in the

thickness of slabs and walls: (+) 10 mm./(-) 5 mm.

vi. Footings:

a) Variation in dimensions in plan: (+) 50 mm./(-) 5 mm.

b) Misplacement or eccentricity: 2% of footing within the direction of

misplacement but not more than 50 mm.

c) Reduction in thickness: (-) 5% of specified thickness subject to maximum of 50

mm.

vii. Variation in steps.

a) In a flight of stairs.

Rise:

Tread:

b) In consecutive steps. (+/-) 3.0 mm. (+/-) 5.0 mm.

Rise: (+/-) 1.5 mm.

Tread: (+/-) 3 mm.

5.2.2. TOLERANCES IN OTHER CONCRETE

STRUCTURE :

A) All structures:

i) Variation of the constructed linear outline from established position in plan.

In 5 m.: (+/-) 10 mm.

In 10 m. or more: (+/-) 15 mm.

ii) Variation of dimensions to individual structure features from established

positions in plan.

In 20 m. or more: (+/-) 25 mm.

In buried constructions: (+/-)150 mm.

Page 83: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 83 of 307

iii) Variation from plumb, from specified batter or from curved surfaces of all

structures.

In 2.5 m.: (+/-) 10 mm.

In 5.0 m.: (+/-) 15 mm.

In 10.0 m. or more: (+/-) 25 mm.

In buried constructions: (+/-) Twice the above limits

iv) Variation from level or grade indicated on drawings in slabs, beams, soffits,

horizontal grooves and visible arises.

In 2.5 m.: (+/-) 5 mm.

In 7.5 m. or more: (+/-) 10 mm.

In buried constructions: (+/-) Twice the above limits.

v) Variation in cross-sectional dimensions of columns, beams, buttresses, piers

and similar members. (+)12 mm./(-) 6 mm.

vi) Variation in the thickness of slabs, walls, arch sections and similar members. :

(+)12 mm./(-) 6 mm.

B) Footings for columns, piers, walls, buttresses and similar members:

i) Variation of dimensions in plan: (+)50 mm./(-)12 mm.

ii) Misplacement or eccentricity: 2% of footing within the direction of

misplacement but not more than 50 mm.

iii) Reduction in thickness: 5% of specified thickness subject to a maximum of 50

mm.

Tolerances in other types of structures shall generally conform to those given in

Clause 2.4 of Recommended Practice for concrete form work (ACI 347)

5.3. TYPE OF FORMWORK :

Form work may be of timber, plywood, metal, plastic or concrete. For special

finishes, the formwork may be lined with plywood, steel sheets, oil tempered hard

board etc. Sliding forms and slip forms may be used with the approval of

Engineer-in- Charge.

5.4. FORMWORK REQUIREMENTS :

Forms shall conform to the shapes, lines, grades and dimensions including camber

of the concrete as called for in the drawings. Ample studs, waler braces, straps,

shores etc. shall be used to hold the forms in proper position without any

distortion whatsoever until the concrete has set sufficiently to permit removal of

forms. Forms shall be strong enough to permit the use of immersion vibrators. In

special cases, from vibrators may also be used. The shuttering shall be close

boarded. Timber shall be well seasoned, free form sap, shakes, loose knots, worm

holes, warps or other surface defects in contact with concrete. Faces coming in

contact with concrete shall be free from adhering grout, plaster, paint, projecting

Page 84: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 84 of 307

nails, splits or other defects. Joints shall be sufficiently tight to prevent loss of

water and fine material from concrete.

Plywood shall be used for exposed concrete surfaces, where called for. Sawn and

wrought timber may be used for unexposed surfaces. Inside faces of forms for

concrete surfaces which are to be rubbed finished shall be planed to remove

irregularities or unevenness in the face. Form work with lining will be permitted.

All new and used from lumber shall be maintained in a good condition with

respect to shape, strength, rigidity, water tightness, smoothness and cleanliness

of surfaces. Form lumber unsatisfactory in any respect shall not be used and if

rejected by Engineer-in-Charge shall be removed from the site.

Shores supporting successive stories shall be placed directly over those below or

be so designed and placed that the load will be transmitted directly to them.

Trussed supports shall be provided for shores that cannot be secured on

adequate foundation.

Formwork, during any stage of construction showing signs of distortion or

distorted to such a degree that the intended concrete work will not conform to

the exact contours indicated on the drawings, shall be repositioned and

strengthened. Poured concrete affected by the faulty formwork, shall be entirely

removed and the formwork corrected prior to placing new concrete.

Excessive construction camber to compensate for shrinkage settlement etc. that

may impair the structural strength of members will not be permitted.

Forms for substructure concrete may be omitted when, in the opinion of

Engineer-in-Charge, the open excavation is firm enough to act as the form. Such

excavations shall be slightly larger than required by the drawings to compensate

for irregularities in excavation and to ensure the design requirement.

Forms shall be so designed and constructed that they can be stripped in the order

required and their removal do not damage the concrete. Face formwork shall

provide true vertical and horizontal joints, conforming to the architectural

features of the structure as to location of joints and be as directed by Engineer-

in-Charge.

Where exposed smooth or rubbed concrete finishes are required, the forms shall

be constructed with special care so that the desired concrete surfaces could be

obtained which require a minimum finish.

BRACINGS, STRUTS AND PROPS :

Shuttering shall be braced, strutted, propped and so supported that it shall not

deform under weight and pressure of the concrete and also due to the movement

of men and other materials. Bamboos shall not be used as props or cross

bracings.

The shuttering for beams and slabs shall be so erected that the shuttering on the

sides of beams and under the soffit of slab can be removed without disturbing the

beam bottoms.

Page 85: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 85 of 307

Repropping of beams shall not be done except when props have to be reinstated

to take care of construction loads anticipated to be in excess of the design load.

Vertical props shall be supported on wedges or other measures shall be taken

whereby the props can be gently lowered vertically while striking the shuttering.

If the shuttering for a column is erected for the full height of the column, one

side shall be left open and built upon sections as placing of concrete proceeds, or

windows may be left for pouring concrete from the sides to limit the drop of

concrete to 1.0 m. or as directed by Engineer-in-Charge.

5.5. INSPECTION OF FORM WORK :

Following points shall be borne in mind while checking during erection of form

work and form work got approved by the Engineer-in-charge before placing of

reinforcement bars :

a. Any member which is to remain in position after the general dismantling is

done, should be clearly marked.

b. Material used should be checked to ensure that, wrong items / rejects are not

used.

c. If there are any excavations nearby which may influence the safety of form

works, corrective and strengthening action must be taken.

d.

i. The bearing soil must be sound and well prepared and the sole plates shall

bear well on the ground.

ii. Sole plates shall be properly seated on their bearing pads or sleepers.

iii. The bearing plates of steel props shall not be distorted.

iv. The steel parts on the bearing members shall have adequate bearing areas.

e. Safety measures to prevent impact of traffic, scour due to water etc. should be

taken. Adequate precautionary measures shall be taken to prevent accidental

impacts etc.

f. Bracing, struts and ties shall be installed along with the progress of form work

to ensure strength and work at intermediate stage. Steel sections (especially

deep sections) shall be adequately restrained against tilting, over turning and

form work should be restrained against horizontal loads. All the securing

devices and bracing shall be tightened.

g. The stacked materials shall be placed as catered for, in the design.

h. When adjustable steel props are used, they should :

i) be undamaged and not visibly bent.

ii) have the steel pins provided by the manufacturers for use.

iii) be restrained laterally near each end.

Page 86: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 86 of 307

iv) have means for centralising beams placed in the foreheads.

i. Screw adjustment of adjustable props shall not be over extended.

j. Double wedges shall be provided for adjustment of the form to the required

position wherever any settlement / elastic shortening of props occurs. Wedges

should be used only at the bottom end of single prop. Wedges should not be too

steep and one of the pair should be tightended / clamped down after

adjustment to prevent their shifting.

k. No member shall be eccentric upon vertical member.

l. The number of nuts and bolts shall be adequate.

m. All provisions of the design and / or drawings shall be complied with.

n. Cantilever supports shall be adequate.

o. Props shall be directly under one another in multistage constructions as far

as possible.

p. Guy ropes or stays shall be tensioned properly.

q. There shall be adequate provision for the movement and operation of vibrators

and other construction plant and equipment.

r. Required camber shall be provided over long spans.

s. Supports shall be adequate, and in plumb within the specified tolerances.

5.6. FORM OIL :

Use of form oil shall not be permitted on the surface which require painting. If the

contractor desire to use form oil on the inside of formwork of the other concrete

structures, a non staining mineral oil or other approved oil CEMOL-35 of Ms.

Hindustan Petroleum Co. Ltd. may be used, provided it is applied before placing

reinforcing steel and embedded parts. All excess oil on the form surfaces and any

oil on metal or other parts to be embedded in the concrete shall be carefully

removed. Before treatment with oil, forms shall be thoroughly cleared of dried

splatter of concrete from placement of previous lift.

5.7. CHAMFERS AND FILLERS :

All corners and angles exposed in the finished structure shall be formed with

mouldings to form chamfers or fillers on the finished concrete. The standard

dimensions of chamfers and fillets, unless otherwise specified, shall be 20 x 20

mm. Care shall be exercised to ensure accurate mouldings. The diagonal face of

the moulding shall be planed or surfaced to the same texture as the forms to

which it is attached.

Page 87: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 87 of 307

5.8. VERTICAL CONSTRUCTION JOINT CHAMFERS

Vertical construction joints on faces which will be exposed at the completion of the

work shall be chamfered as above except where not permitted by Engineer-in-

Charge for structural or hydraulic reasons.

5.9. WALL TIES :

Wire ties passing through the walls, shall not be allowed. Also through bolts shall

not be permitted. For fixing of formwork, alternate arrangements such as coil

nuts shall be adopted at the contractors cost.

5.10. REUSE OF FORMS :

Before reuse, all forms shall be thoroughly scraped, cleaned, nails removed, holes

that may leak suitably plugged and joints examined and when necessary repaired

and the inside retreated to prevent adhesion, to the satisfaction of Engineer-in-

charge. Warped lumber shall be resized. Contractor shall equip himself with

enough shuttering to complete the job in the stipulated time.

5.11. REMOVAL OF FORMS :

Contractors shall record on the drawings or a special register, the date upon

which the concrete is placed in each part of the work and the date on which the

shuttering is removed there from.

In no circumstances shall forms be struck until the concrete reaches a strength

of the at least twice the stress due to self weight and any construction erection

loading to which the concrete may be subjected at the time of striking formwork.

In normal circumstances (generally where temperatures are above 15 0C.) forms

may be struck after expiry of the following periods :

Stripping time:

Sl.No. Type of form work

Minimum

period

before

striking form work

a) Vertical form work to columns,

walls beams 16 – 24 h

b)

Soffit form work to slabs

(Props to be refixed

immediately after

removal of formwork)

3 days

Page 88: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 88 of 307

c)

Soffit form work to beams

(Props to be refixed

immediately after

removal of formwork

7 days

d)

Props to slabs:

1) Spanning up to 4.5 m

2) Spanning over 4.5 m

7 days

14 days

e)

Props to beams and arches;

1) spanning up to 6 m

2) spanning over 6 m

14 days

21 days

For other cements and lower temperature, the stripping time recommended above

may be suitably modified.

The number of props left under the sizes and the position shall be such as to

able to safety carry the full dead load of the slab, beam or arch., as the case may

be together with any live load likely to occur during curing or further

constructions.

Where the shape of the element is such that the form work has the reentrant

angles the form work shall be removed as soon as possible. After the concrete has

set, to avoid shrinkage cracking occurring due to the restraint imposed.

Striking shall be done slowly with utmost care to avoid damage to arise and

projection and without shock or vibration, by gently easing the wedges. If after

removing the formwork, it is found that timber has been embedded in the

concrete, it shall be removed and made good as specified earlier.

Reinforced temporary openings shall be provided, as directed by Engineer-in-

Charge, to facilitate removal of formwork which otherwise may be in-accessible.

Tie rods, clamps, form bolts etc. which must be entirely removed from walls or

similar structures shall be loosened not sooner than 24 hours nor later than 40

hours after concrete has been deposited. Ties, except those required to hold

forms in place, may be removed at the same time. Ties withdrawn from walls and

grade beams shall be pulled towards the inside face. Cutting ties back from the

faces of walls and grade beams will not be permitted. Work damaged due to

premature or careless removal of forms shall be re-constructed at contractors cost.

5.12. MODE OF MEASUREMENT :

In case the items of concreting are inclusive of cost of form work, no separate

measurements shall be taken for form work. However, if the form work is to be

paid separately and the item exists in the Schedule of Quantities for various

types of form work, the net area of exposed surface of concrete members as

Page 89: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 89 of 307

shown in drawings coming in contact with form work shall be measured under

item of formwork in square meters.

All temporary formwork such as bulk heads, stop boards provided at

construction joints which are not shown in the drawings shall not be measured.

No deductions shall be made for openings/ obstructions upto an area of 0.1 sqm.

and nothing extra shall be paid for forming such openings.

The rate shall include the cost of erecting, centering, shuttering materials,

transport, deshuttering and removal of materials from site and labour required

for all such operations etc.

6 . STEEL FOR CONCRETE REINFORCEMENT :

6.1. SCOPE OF MATERIAL:

The contractor shall make his own arrangement for procurement of

Reinforcement steel bars and wires for use in Reinforced Cement Concrete works.

Unless otherwise specified in drawings / Schedule of quantities, the steel bars

shall be of “High strength deformed steel bars and wires” conforming to the IS

1786 (latest revision), in the following strength grades:

a) Fe 415, Fe 415D;

b) Fe 500, Fe 500D;

c) Fe 550, Fe 550D; and

d) Fe 600.

Where “Fe” stands for specified minimum 0.2% proof / yield stress in N/mm2 and

“D” stands for same specified minimum 0.2% proof / yield stress but with

enhanced specified minimum percentage elongation.

6.2. TERMINOLOGY:

Elongation: The increase in length of a tensile test piece under stress, expressed

as a percentage of the original gauge of a standard piece.

Longitudinal Rib -A uniform continuous protrusion, Parallel to the axis of the

bar/wire (before cold-working, if any).

Nominal Diameter or Size- The diameter of a plain round bar/wire having the

same mass per metre length as the deformed bar/wire.

Nominal Mass -The mass of the bar/wire of nominal diameter and of density

0.00785 kg/cumm per meter.

Nominal Perimeter - 3.14 times the nominal diameter of a deformed bar/Wire.

Percent Proof Stress -The stress at which a non-proportional elongation equal to

0.2% of the original gauge length takes place.

Page 90: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 90 of 307

Uniform elongation - The elongation corresponding to the maximum load

reached in a tensile test (also termed as percentage total elongation at maximum

force).

Tensile Strength - The maximum load reached in a tensile test divided by the

effective cross-sectional area of the gauge length portion of the test piece (also

termed as ultirnate tensile stress).

Transverse Rib - Any rib on the surface of a bar/wire other than a longitudinal

rib.

Yield Stress - Stress (that is, load per unit cross sectional area) at which

elongation first occurs in the test piece without increasing the load during the

tensile test. In the case of steels with no such definite yield point, proof stress

shall be applicable.

The high strength deformed steel bars and wires for concrete reinforcement shall

be hot rolled steel without subsequent treatment or hot rolled steel with controlled

cooling and tempering and cold worked steel, and reinforcing bars and wires

which may be subsequently coated.

Steel bars shall be supplied from M/s. Steel Authority of India Ltd. (SAIL) or M/s.

TATA Steel (TISCO) or M/s. Rashtriya Ispat Nigam Ltd (RINL) or M/s. Indian Iron

& Steel Co. (IISCO) Ltd., from their own plants rolled from virgin material, and

shall be procured directly or from their authorised dealers and not from re-rollers

or conversion agents. The contractor shall supply copy of Documentary evidence

of purchase of steel from the specified manufacturers.

6.3. TESTS:

The contractor shall submit the test certificate of manufacturer. Regular tests on

steel supplied by the contractor shall be performed by the contractor at the

approved lab, in presence of the Departmental Engineers as per relevant Indian

Standards. Engineer-in-charge may require Contractor to perform necessary tests

of samples at random as per relevant B.I.S. All cost of such tests and incidentals

to such tests shall be borne by the Contractor. The quality, grade, colour coding

embossing marks etc. all shall be to the entire satisfaction of the Engineer-in-

Charge. Steel not conforming to above test criteria shall be rejected.

The Chemical, Physical & Mechanical properties of the steel reinforcement bars

shall be as per IS 1786. Unless otherwise specified, Selection and Preparation of

Test Sample shall be as per the requirements of IS 2062.

All test pieces shall be selected either from the cuttings of bars / wires; or from

any bar/wire after it has been cut to the required or specified size and the test

piece taken from any part of it. In neither case, the test piece shall be detached

from the bar/wire except in the presence of the EIC or his authorized

representative.

The test pieces shall be full sections of the bars/wires and shall be subjected to

physical tests without any further Modernizations. No reduction in size by

machining or otherwise shall be permissible, except in case of bars of size 28 mm

and above. No test piece shall be annealed or otherwise subjected to heat

treatment. Any straightening which a test piece may require shall be done cold.

Page 91: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 91 of 307

For the purpose of carrying out tests for tensile strength, proof stress, percentage

elongation and percentage elongation at maximum force for bars 28 mm in

diameter and above, deformations of the bars only may be machined. For such

bars, the physical properties shall be calculated using the actual area obtained

after machining. The following IS codes shall be referred for test methods:

SN Title IS No ISO No.

I Mechanical testing of metals -Tensile 1608 6892

ii Methods for bend test 1599 7438 &

1786

15630-1

iii Method for re-bend test for metallic wires &

bars

1786 15630-1

THE PROPERTIES AS PER IS 1786 – 2008 ARE REPRODUCED BELOW:

Chemical Composition of the bars shall conform to the following requirement:

Constituen

ts

Maximum Permissible

Percent Permissible

max.

Variation Fe

415 Fe 415D Fe 500 Fe 500D Fe 550 Fe

550D

Fe

600

Carbon 0.300 0.250 0.300 0.250 0.300 0.250 0.300 0.020%

Sulphur 0.060 0.045 0.055 0.040 0.055 0.040 0.040 0.005%

Phosphoru 0.060 0.045 0.055 0.040 0.050 0.040 0.040 0.005%

Sulphur &

Phosphoru

0.110 0.085 0.105 0.075 0.100 0.075 0.075 0.010%

Notes:

1. For welding of deformed bars, the recommendations of IS 9417 shall be followed.

2. In case of deviations from the specified maximum, two additional test samples

shall be taken from the same batch and subjected to the test or tests in which the

original sample failed. Should both additional test samples pass the test, the batch

from which they were taken shall be deemed to comply with this standard. Should

either of them fail, the batch shall be deemed not to comply with this standard

Mechanical Properties of High Strength Deformed Bars and Wires

Sl.

No. Property

Maximum Permissible

Fe 415 Fe

415D

Fe

500

Fe

500D

Fe

550

Fe

550D

Fe

600

1 2 3 4 5 6 7 8 9

i 0.2 percent proof

stress / yield

stress,

Min, N/mm²

415.0 415.0

500.0 550.0 550.0 600.0

Page 92: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 92 of 307

ii Elongation, percent,

Min. on gauge

length

5.65 ;A, where A

is

the Cross –

sectional

area of the test piece

14.5 18.0 12.0 16.0 10.0 14.5 10.0

iii Tensile strength,

Min

10%

more

than the

actual

0.2% proof

stress/yi

eld

stress

but

not less

than

485.0

N/mm2

12%

more

than the

actual

0.2% proof

stress/y

ield

stress

but

not less

than

500.0

N/mm2

8%

more

than

the

actual

0.2% proof

stress/y

iel

d stress

but not

less

than

545.0

N/mm2

10%

more

than the

actual

0.2% proof

stress/y

ield

stress

but

not less

than

565.0

N/mm2

6%

more

than

the

actual

0.2% proof

stress/

yiel

d stress

but not

less

than

585.0

N/mm2

8%

more

than the

actual

0.2% proof

stress/y

ield

stress

but

not less

than

600.0

N/mm2

6%

more

than

the

actual

0.2% proof

stress/

yiel

d stress

but not

less

than

660.0

N/mm2

iv Total elongation at

maximum

force,

percent, Min of

gauge

length 5.65 ;A,

where A is the

cross sectional

area of the test piece

- 5 - 5 - 5 -

Note: To satisfy Clause 26 of IS 456 -2000, no mixing of different types of grades

of bars shall be allowed in the same structural members as main reinforcement,

without prior written approval of the Engineer-in-Charge.

6.4. STACKING & STORAGE :

Steel for reinforcement shall be stored in such a way as to prevent distorting and

corrosion. The steel for reinforcement shall not be kept in direct contact with

ground. Fresh / Fabricated reinforcement shall be carefully stored to prevent

damage, distortion, corrosion and deteriorations. Care shall be taken to protect

steel from exposure to saline atmosphere during storage, fabrication and use. It

may be achieved by treating the surface of reinforcement with cement wash or by

suitable methods. Bars of different classifications, sizes and lengths shall be

Page 93: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 93 of 307

stored separately to facilitate issue in such sizes and lengths to cause minimum

wastage in cutting from standard length.

6.5. QUALITY :

Steel not conforming to specifications shall be rejected. All reinforcement shall be

clean, free from grease, oil, paint, dirt, loose mill, scale, loose rust, dust,

bituminous material or any other substances that will destroy or reduce the

bond. All rods shall be thoroughly cleaned before being fabricated. Pitted and

defective rods shall not be used. All bars shall be rigidly held in position before

concreting. No welding of rods to obtain continuity shall be allowed unless

approved by the Engineer-in-Charge. If welding is approved, the work shall be

carried as per I.S. 2751, according to best modern practices and as directed by the

Engineer-in-Charge. In all cases of important connections, tests shall be made to

prove that the joints are of the full strength of bars welded. Substitution of

reinforcement will not be permitted except upon written approval from Engineer-

in-charge.

6.6. NOMINAL SIZES

The nominal sizes of bars/wires shall be 4mrn, 5mrn, 6mrn, 8mrn, 10mrn, 12mrn,

16mrn, 20mrn, 25 mm, 28mrn, 32mrn, 36mrn, 40 mm. (Other sizes viz. 7mrn,

18mrn, 22 mm, 45 mm and 50 mm may be procured on specific stipulations).

6.7. NOMINAL MASS

For the purpose of checking the nominal mass, the density of steel shall be taken

as 0.00785 kg/mm3 of the cross-sectional area per metre. Unless otherwise

specified, the tolerances on nominal mass shall be as per following Table.

Tolerances on Nominal Mass

SN Nominal Size in mm Tolerance on the nominal mass in

Batch Individual

sample

Individual

sample for coils

only 1 2 3 4 5

i) Up to and including 10 ± 7 - 8 ± 8

ii) Over 10 up to and ± 5 - 6 ± 6

iii) Over 16 ± 3 - 4 ± 4

6.8. LAPS :

Laps and splices for reinforcement shall be shown on the drawings. Splices in

adjacent bars shall be staggered and the locations of all splices, except those

specified on the drawings, shall be approved by the Engineer-in-Charge. The bars

shall not be lapped unless the length required exceeds the maximum available

lengths of bars at site.

6.9. BENDING :

All bars shall be accurately bent according to the sizes and shapes shown on the

detailed working drawing / bar bending schedules. They shall be bent gradually

by machine or other approved means. Reinforcing bars shall not be straightened

Page 94: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 94 of 307

and re-bent in a manner that will injure the materials. Bars containing cracks or

splits shall be rejected. They shall be bent cold, except bars of over 25 mm. in

diameter which may be bent hot if specifically approved by the Engineer-in-

Charge. Bars that depend for their strength on cold working shall not be bent hot.

Bars bent hot shall not be heated beyond cherry red colour (not exceeding 6450C)

and after bending shall be allowed to cool slowly with out quenching. Bars

incorrectly bent shall be used only after straightening and re-bending be such as

shall not, in the opinion of the Engineer-in-Charge, injure the material. No

reinforcement bar shall be bent when in position in the work without approval,

whether or not it is partially embedded in hardened concrete. Bars having kinks or

bends other than those required by design shall not be used.

BENDING AT CONSTRUCTION JOINTS :

Where reinforcement bars are bent aside at construction joints and afterwards

bent back into their original position, care should be taken to ensure that at no

time the radius of the bend is less than 4 bar diameters for plain mild steel or 6

bar diameters for deformed bars. Care shall also be taken when bending back

bars to ensure that the concrete around the bar is not damaged.

6.10. FIXING / PLACING AND TOLERANCE ON

PLACING :

Reinforcement shall be accurately fixed by any approved means maintained in

the correct position as shown in the drawings by the use of blocks, spacers and

chairs as per I.S. 2502 to prevent displacement during placing and compaction of

concrete. Bars intended to be in contact at crossing point shall be securely bound

together at all such points with number 16 gauge annealed soft iron wire. The

vertical distances required between successive layers of bars in beams or similar

members shall be maintained by the provision of spacer bars at such intervals

that the main bars do not perceptibly sag between adjacent spacer bars.

TOLERANCE ON PLACING OF REINFORCEMENT :

Unless otherwise specified, reinforcement shall be placed within the following

tolerances :

Tolerance in spacing

a) For effective depth, 200 mm or less + /- 10 mm

b) For effective depth, more than 200 mm +/-10mm

6.11. COVER TO REINFORCEMENT :

Nominal cover is the design depth of concrete cover to all steel reinforcements,

including links. It is the dimension used in design and indicated in the drawings.

It shall be not less than the diameter of the bar. Unless otherwise specified, cover

to reinforcement shall be provided generally as per guidelines of IS 456.

Nominal cover to meet durability requirement:

Minimum values for the nominal cover of normal weight aggregate concrete which

should be provided to all reinforcement, including links depending on the

Page 95: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 95 of 307

condition of exposure described in 4.4 above and as per (nominal cover to meet

durability requirements).

However for a longitudinal reinforcing bar in a column nominal cover shall in any

case not be less than 40 mm or less than the diameter of such bar. In the case of

columns of minimum dimension of 200 mm or under, whose reinforcing bar do not

exceed 12 mm , a nominal cover of 25 mm may be used.

For footings minimum cover shall be 50 mm.

Nominal cover to meet specified period of fire resistance

Minimum values of nominal cover of normal-weight aggregate concrete to be

provided to all reinforcement including links to meet specified period of the

resistance as per the tables given under clause 4.4.1 of this specifications.

The cover shall in no case be reduced by more than one third of specified cover or

5 mm whichever is less.

Unless indicated otherwise on the drawings, clear concrete cover for

reinforcement (exclusive of plaster or other decorative finish shall be as follows:

a) At each end of reinforcing bar not less than 25mm., nor less than twice the

diameter of such, bar.

b) For a longitudinal reinforcing bar not less than 25 mm., nor more than 40

mm., nor less than the diameter of such bar. In the case of column of

maximum dimensions of 200 mm. or under, whose reinforcing bars do not

exceed 12 mm., a cover of 25 mm. may be used.

c) For longitudinal reinforcing bar in a beam, not less than 25mm., nor less than

diameter of such bar.

d) For tensile, compressive, shear, or other reinforcement in a slab, not less than

25 mm, nor less than the diameter of such bar, and

e) For any other reinforcement not less than 15 mm., nor less than the diameter

of such bar.

f) Increased cover thickness may be provided when surfaces of concrete members

are exposed to the action of harmful chemicals (as in the case of concrete in

contact with earth faces contaminated with such chemicals), acid, vapour,

saline atmosphere, sulphurous smoke (as in the case of steam-operated

railways) etc. and such increase of cover may be between 15 mm. and 50 mm.

beyond the figures given in (a to e) above as may be specified by the Engineer-

in-Charge.

g) For reinforced concrete members, totally immersed in sea water, the cover

shall be 40 mm. more than specified (a to e) above.

h) For reinforced concrete members, periodically immersed in sea water or

subject to sea spray, the cover of concrete shall be 50 mm. more than that

specified (a to e) above.

Page 96: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 96 of 307

i) For concrete of grade M 25 and above, the additional thickness of cover

specified in (f), (g) and (h) above may be reduced to half. In all such cases the

cover should not exceed 75 mm.

j) Protection to reinforcement in case of concrete exposed to harmful surroundings

may also be given by providing dense impermeable concrete with approved

protective coating, as specified on the drawings. In such case the extra cover,

mentioned in (h) and (i) above, may be reduced by the Engineer-in-Charge, to

those shown on the drawing.

k) The correct cover shall be maintained by cement mortar briquettes or other

approved means. Reinforcement for footings, grade beams and slabs on

subgrade shall be supported on precast concrete blocks as approved by the

Engineer-in-Charge. The use of pebbles or stones shall not be permitted.

l) The minimum clear distance between reinforcing bars shall be in accordance

with I.S. 456 or as shown in drawing.

6.12. THE BARS SHALL BE KEPT IN CORRECT

POSITION BY THE FOLLOWING METHODS.

a) In case of beam and slab construction precast cover blocks in cement mortar

1:2 (1 cement : 2 coarse sand ) about 4 x 4 cm section and of thickness equal

to the specified cover shall be placed between the bars and shuttering, so as to

secure and maintain the requisite cover of concrete over reinforcement.

b) In case of cantilevered and doubly reinforced beams or slabs, the vertical

distance between the horizontal bars shall be maintained by introducing

chairs, spacers or support bars of steel at 1.0 metre or at shorter spacing to

avoid sagging.

c) In case of columns and walls, the vertical bars shall be kept in position by

means of timber templates with slots accurately cut in them; or with block of

cement mortar 1:2 (1 cement : 2 coarse sand) of required size suitably tied to

the reinforcement to ensure that they are in correct position during

concreting.

d) In case of other R.C.C. structure such as arches, domes, shells, storage tanks

etc. a combination of cover blocks, spacers and templates shall be used as

directed by Engineer-in-Charge.

6.13. INSPECTION :

Erected and secured reinforcement shall be inspected and approved by Engineer-

in-Charge prior to placement of concrete.

6.14. MODE OF MEASUREMENT FOR

REINFORCEMENT FOR R.C.C. WORKS :

Reinforcement as detailed in schedule of quantities shall be measured for payment

lineally as per the cutting length nearest to a centimetre shown in bar bending

schedule submitted by the contractor and approved by the Engineer-in-Charge

Page 97: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 97 of 307

and weight calculated based on the standard weights as per I.S.1786, as

indicated in the following table:

Nominal size in

mm

6 7 8 10 12 16 18 20

Cross Sectional area

in mm2.

28.30 38.50 50.30 78.60 113.1

0

201.2

0

254.

60

314.30

Mass / Weight in Kg

/ RM

0.222 0.302 0.395 0.617 0.888 1.580 2 .000 2 .47

Nominal size in

mm

22 25 28 32 36 40 45 50

Cross Sectional area

in mm²

380.3

0

491.1

0

614.0

0

804.6

0

1018.

30

1257.

20

1591.1

0

1964.30

Mass / Weight in Kg

/ RM

2

.980

3.850 4.830 6.310 7.990 9.850 12.500 15.420

No allowance shall be made/ be measured in the weight for rolling margin. If

weight of bar(s) found to be more than the standard weights, the measurement /

payment shall be restricted to the standard weights as above. However, if weight

of bar(s) found to be less than the standard weights (but within the permissible

limit), the measurements / payment for the same shall be as per standard

weights.

Only authorized laps shall be measured. The cost of steel used by the contractor

in the reinforcement of beams, slabs and columns etc. will be paid as per the rate

of reinforcement only upto the extent shown in the drawings. As far as possible

laps in bars shall be avoided. Any laps and hooks provided by the contractor other

than authorised as per approved bar bending schedule will be considered to have

been provided by the contractor for his own convenience and shall not be measured

for payment. Pins, chairs, spacers shall be provided by the contractor wherever

required as per drawing and bar bending schedule and as directed by the

Engineer-in-Charge and shall be measured for payment. Fan hooks as required

shall be provided by the contractor under this item and shall be measured for

payment.

The rate shall include the cost of all materials and labour required for all above

operations including transport, wastage, straightening, cutting, bending, binding

and the binding wire required.

* * * *

8. READY MIX CONCRETE :

(SPECIFICATIONS FOR READY MIXED CONCRETE, CONFORMING TO IS

4926)

8.1. Ready mix Concrete shall conform to latest revision of IS : 4926 following are the

requirement for supply of R.M.C

8.1.A. Concrete delivered at site shall be in a plastic condition and requiring no further

treatment before being placed in the position in which it is to set and harden

8.1.B. The process of continuing the mixing of concrete at a reduced speed during

transportation to prevent segregation.

8.1.C. Truck mounted equipment designed to agitate concrete during transportation to

the site of delivery.

Page 98: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 98 of 307

8.1.D. Concrete produced by completely mixing cement, aggregates, admixtures if any

and water at a stationary central mixing plant and delivered in containers fitted

with agitating devices. The concrete may also be transported without being

agitated as a special case and as requested.

8.1.E. Concrete produced by placing cement, aggregates and admixtures, if any other

than those to be added with mixing water, in a truck mixer at the batching plant ,

the addition of water and admixtures to be added along with mixing water, and the

mixing being carried out entirely in the truck mixer either during the journey or on

arrival at the site of delivery. No water shall be added to the aggregate and cement

until the mixing of concrete commences.

8.2. MATERIALS :

8.2.A. The cement used shall be of specified grade ordinary Portland cement or low heat

Portland cement conforming to IS: 269 or Portland slag cement conforming to IS:

455 or Portland-pozzolana cement conforming to IS: 1489 or rapid hardening.

Portland cement conforming to IS: 8041 as may be specified at the time of placing

the order. If the type is not specified, ordinary Portland cement shall be used.

8.2.B. Fly ash when used for partial replacement of cement, shall conform to the

requirements of IS-3812 (Part I) and as specified by the users.

8.2.C. The aggregate shall conform to IS: 383. Fly ash when used as fine aggregate

shall conform to t he requirements of IS 3812 – (Part - II).

8.2.D. Water used for concrete shall conform to the requirement of IS 456-2000.

8.2.E. The admixtures shall conform to the requirements of IS : 456-2000 and their

nature, quantities and methods of use shall also be specified. Fly ash when used

as an admixture for concrete shall conform to IS : 3812 (Part II) – 1981. However,

partial replacement of cement by fly ash shall not be more than 15% of designed

requirement.

In case if fly ash is used more than 15%, the same shall be guided under table 5.1

of the IS, and in which case specific care shall be taken in terms of curing,

protecting, repairing, finishing, de-shuttering etc. as detailed in the Chapter “FLY

ASH CONCRETE”, here in after.

8.3. SUPPLY :

The ready-mixed concrete shall be manufactured and supplied on either of

the following basis :

i) Specified strength based on 28-day compressive strength of 15 -cm cubes

tested in accordance with IS : 456-2000.

ii) Specified mix proportion.

NOTE : Under special circumstances and as specified the strength of concrete in

(a) above may be based on 28-day or 7-day flexural strength of concrete instead of

compressive strength of 15-cm cube tested in accordance with IS : 456-2000.

8.3.A. When the concrete is manufactured and supplied on the basis of specified strength,

Page 99: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 99 of 307

the responsibility for the design of mix shall be that of the manufacturer and the

concrete shall conform to the requirements specified.

8.3.B. When the concrete is manufactured and supplied on the basis of specified mix

proportions, the responsibility for the design of the mix shall be that of the

purchaser and the concrete shall conform to the requirements specified.

8.4. GENERAL REQUIREMENTS:

8.4.A. When a truck mixer or agitator is used for mixing or transportation concrete, no

water from the truck-water system or from elsewhere shall added after the initial

introduction of the mixing water for the batch, when no arrival at the site of the

work, the slump of the concrete is less that specified, such additional water to

bring the slump within limits shall be injected into the mixer under such pressure

and direct flow that the requirements for uniformity specified.

8.4.B. Unless otherwise specified when a truck or agitator is used for transporting

concrete, the concrete shall be delivered to the site of the work and discharge shall

be complete within 1 ½ hour (when the prevailing atmospheric temperature above

200C) and within 2 hours (when the prevailing atmosphere temperature is at or

below 20 0C) of adding the mixing water to the mix of cement and aggregate or

adding the cement to the aggregate whichever is earlier.

8.4.C. The temperature of the concrete at the place and time of delivery shall be not less

than 50C. Unless otherwise required by the purchaser, the concrete shall be

delivered when the site temperature is less than 2.50 C.

8.4.D. Adequate facilities shall be provided by the manufacturer/supplier to inspect the

materials used the process of manufacture and methods of delivery of concrete. He

shall also provide adequate facilities to take samples of the materials used.

8.4.E. The tests for consistency or workable shall be carried out in accordance with

requirements of IS 1199 by such other method as may be agreed to between the

purchaser and manufacturer.

8.4.F. The sampling and testing of concrete shall be done in accordance with the relevant

requirements of IS 456, IS 1199 and IS 516.

8.4.G. The compressive strength and flexural strength tests shall be carried out in

accordance with the requirement of IS: 516 and the acceptance criteria for

concrete whether supplied on the basis of specified strength or on the basis of mix

proportion, shall conform to the requirements and other related requirements of

IS: 456 -2000.

8.4.H. The testing shall be carried out in accordance with the requirements and the cost

shall be borne by the Contractor.

8.4.I. The manufacturer shall keep batch records of the quantities by mass all the solid

materials, of the total amount of water used in mixing and of the results of all

tests. If required insisted, the manufacturer shall furnish certificates, at agreed

intervals, giving this information.

8.4.J. Mode of measurement for ready mixed concrete (RMC) will be the same as mode of

measurement for concrete work already mentioned at page No. 42 & 43 of clause

Page 100: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 100 of 307

4.40. However, consumption of RMC shall be maintained at site. Wastage,

spillover, wastage due to pump blockage etc. shall not be considered for payment.

* * * *

9. FLY ASH CONCRETE

NOTES:

a) The fly ash should have consistent quality satisfying the requirements of Grade-1

FA of IS 3812 and Class-F of ASTM C-618.

b) The source of fly ash should be so selected that test results of fly ash samples

collected from these sources during last one year at frequency of maximum one

month interval should satisfy the requirements of above codes.

c) The characterization of fly ash which will be used should be done as per above

two codes for each batch of fly ash.

d) The fly ash should be stored in bins at the plant.

e) All concrete should be manufactured at RMC plant.

f) The mix proportion should be approved by competent authority. The information

to be supplied for approval would be identified by the competent authority.

g) Any change in mix proportion, after approval, should be concurred by appropriate

authority.

h) Samples to be taken, at each time of casting, for 7 days and 28 days.

i) All ingredients of concrete should satisfy the requirements of relevant IS codes

and specifications.

9.1.0. Curing, Protecting, Repairing and Finishing

9.1.1. Curing: All concrete shall be cured by keeping it continuously damp for the period

of time required for complete hydration and hardening to take place. Preference

shall be given to the use of continuous sprays or ponded water, continuously

saturated covering of sacking, canvas, hessian or other absorbent materials, or

approved effective curing compounds applied with spraying equipment capable of

producing a smooth, even textured coat. Extra precautions shall be exercised in

curing concrete during cold and hot weather as outlined hereinafter the quality of

curing water shall be the same as that used for mixing concrete.

Certain types of finish or Preparation for overlaying concrete must be done at

certain stages of curing process and special treatment may be required for

specific concrete surface finish.

Curing of concrete made of high alumina cement and super sulphated cement

shall be carried out as directed by Engineer-in-charge.

9.1.2. Curing of concrete with low water binder ratios having partial replacement of

cement by pozzolanic materials.

9.1.3. The structural elements with concrete having water binder ratio less than or equal

Page 101: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 101 of 307

to 0.4 or partial replacement of cement by pozzolanic materials (5% or above

replacement by silica fume or high reactivity metakaoline, or 15% or above by fly

ash) shall be cured in two stages, initial curing and final curing.

i) The initial curing should be started not later than 3 hours or initial setting

time, whichever is lower, after placement of concrete. The concrete surface

exposed to environment should be covered by plastic sheet or other type of

impermeable covers. The initial curing should be continued upto a minimum

period of 12 hours or 2 hours plus final setting time of concrete, whichever is

higher.

ii) Final curing should be done with water. It should commence immediately

after initial curing and continue upto a minimum period of 14 days.

9.1.4. CURING WITH WATER

Fresh concrete shall be kept continuously wet for a minimum period of 14 days

from the date of placing of concrete, following a lapse of 12 to 24 hours after

laying concrete. The curing of horizontal surfaces exposed to the drying winds

shall however begin immediately the concrete has hardened. Water shall be

applied to uniformed concrete surfaces within 1 hour after concrete has set.

Water shall be applied to formed surfaces immediately upon removal of forms .

Quantity of water applied shall be controlled so as to prevent erosion of freshly

placed concrete.

9.1.5. CONTINUOUS SPRAYING

Curing shall be assured by use of ample water supply under pressure in pipes,

with all necessary appliances of hose sprinklers and spraying devices.

Continuous fine mist spraying or sprinkling shall be used, unless otherwise

specified or approved by Engineer-in-charge.

9.1.6. ALTERNATE CURING METHODS:

Whenever in the judgement of Engineer-in-charge, it may be necessary to omit the

continuous spray method, covering of clean sand or other approved means such as

wet gunny bags, which will prevent loss of moisture from the concrete, may be

used. Any type of covering which would slain or damage the concrete during or

after the curing period, will not be permitted. Covering shall be kept continuously

wet during the curing period.

For curing of concrete in pavements, side walks, floors, flat roofs or other level

surfaces, the ponding method of curing is preferred. The method of containing the

ponded water shall be approved by Engineer-in-charge. Special attention shall be

given to edge and corner of the slab to ensure proper protection to these areas. The

ponded areas shall be kept continuously filled with water during the curing

period.

9.1.7. CURING COMPOUNDS :

Surface coating type curing compound shall be used only on special permission

of Engineer-in-charge. Curing compounds shall be liquid type while pigmented,

conforming to U.S Bureau of Reclamation Specification. No curing compound shall

Page 102: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 102 of 307

be used on surface where future blending with concrete water or acid proof

membrane or painting is specified.

9.1.8. Curing Equipment: All equipments and materials required for curing shall be on

hand and ready for use before concrete is placed.

9.2.0. Form Work

9.2.1. General: The form work shall consist of shores, bracings, sides of beams and

columns, bottom of slabs etc. including ties, anchors, hangers, inserts etc.

complete which shall be properly designed and planned for the work. The false

work shall be so constructed that up and down vertical adjustment can be made

smoothly. Wedges may be used at the top or bottom of timber shores, but not at

both ends, to facilitate vertical adjustment or dismantling of form work.

9.2.2. Design of Form Work: The design and engineering of form work as well as its

construction shall be the responsibility of Contractor. If so instructed the drawings

and calculations for the design of the form work shall be submitted well in advance

to the Engineer-in-charge for approval before proceeding with work, at no extra

cost to the Department. Engineer-in-charge approval shall not however, relieve

Contractor of the full responsibility for the design and construction of the form

work. The design shall take into account all the loads vertical as well as lateral

that the forms will be carrying including live and vibration headings.

9.2.3. Type of Form Work: Form work may be of timber, plywood, metal, plastic or

concrete. For special finishes, the form work may be lined with plywood, steel

sheets, oil tempered hard board etc. Sliding forms and slip forms may be used

with the approval of Engineer-in-charge.

9.2.4. Formwork Requirements: Forms shall conform to the shapes, lines grooves and

dimensions including camber of the concrete as called for in the drawings. Ample

studs, water braces, straps,shores etc. shall be used to hold the forms in proper

position without any distortion whatsoever until the concrete has set sufficiently

to permit removal of forms. Forms shall be strong enough to permit the use of

immersion vibrators. In special cases, form vibrators may also be used. The

shuttering shall be close boarded. Timber shall be well seasoned, free form sap,

shakes, loose knots, worm holes, wraps or other surface defects in contact with

concrete. Faces coming in contact with concrete shall be free from adhering grout,

plaster, paint, projecting nails, splits or other defects. Joints shall be sufficiently

light to prevent loss of water and fine material from concrete.

Ply wood shall be used for exposed concrete surfaces, where called for Sawn and

wrought timber may be used for unexposed surfaces. Inside faces of forms for

concrete surfaces which are to be rubbed finished shall be planned to remove

irregularities or unevenness in the face. Form work with lining will be permitted.

All new and used form lumber shall be maintained in a good condition with respect

to shape, strength, rigidity, water lightness, smoothness and cleanliness of

surfaces. Form lumber unsatisfactory in any respect shall not be used and if

rejected by Engineer-in-charge shall be removed from the site.

Shores supporting successive stories shall be placed directly over those below or

be so designed and placed that the load will be transmitted directly to them.

Page 103: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 103 of 307

Trussed supports shall be provided for shores that cannot be secured on adequate

foundation.

Form work, during any stage of construction showing signs of distortion of

distorted to such a degree that the intended concrete work will not conform to the

exact contours indicated on the drawings, shall be repositioned and

strengthened. Poured concrete affected by the faulty formwork, shall be entirely

removed and the formwork corrected prior to placing new concrete.

Excessive construction camber to compensate for shrinkage settlement etc. that

may impair the structural strength of members will not be permitted.

Forms for substructure concrete may be omitted when, in the opinion of

Engineer-in-charge, the open excavation is firm enough to act as the form. Such

excavations shall be slightly larger than required by the drawings to compensate

for irregularities in excavation and to ensure the design requirement.

Forms shall be so designed and constructed that they can be stripped in the order

required and their removal do not damage the concrete. Face form work shall

provide true vertical and horizontal joints, conforming to the architectural

features of the structure as to location of joints and be as directed by Engineer-

in-charge.

Where exposed smooth or rubbed concrete finishes are required, the forms shall be

constructed with special care so that the desired concrete surfaces could be

obtained which require a minimum finish.

9.2.5. Bracings, Struts and Props: Shuttering shall be braced, strutted, propped and

so supported that it shall not deform under weight and pressure of the concrete

and also due to the movement of men and other materials. Bamboos shall not be

used as props or cross bracings.

The shuttering for beams and slabs shall be so erected that the shuttering on the

sides of beams and under the soffits of slab can be removed without disturbing

the beam bottoms.

Repropping of beams shall not be done except when props have to be reinstated to

take care of construction loads anticipated to be in excess of the design load.

Vertical props shall be supported on wedges or other measures shall be taken

whereby the props can be gently lowered vertically while striking the shuttering.

If the shuttering for a column is erected for the full height of the column, one side

shall be left open and built upon sections as placing of concrete proceeds, or

windows may be left for pouring concrete from the sides to limit the drop of

concrete to 1.0 m or as directed by Engineer-in-charge.

9.2.6. Inspection of Form Work

Following points shall be borne in mind while checking during erection of form

work and form work got approved by the Engineer-in-charge before placing of

reinforcement bars.

a) Any members which is to remain in position after the general dismantling is

done, should be clearly marked.

Page 104: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 104 of 307

b) Material used should be checked to ensure that wrong items/rejects are not

used.

c) If there are any excavations nearby which may influence the safety of form

works, corrective and strengthening action must be taken.

d) i) The bearing soil must be sound and well prepared and the sole plates

shall bear well on the ground.

ii) Sole plates shall be properly seated on their bearing pads or sleepers.

iii) The bearing plates of steel props shall not be distorted.

iv) The steel parts on the bearing members shall have adequate bearing

areas.

e) Safety measures to prevent impact of traffic, scour due to water etc. should

be taken. Adequate precautionary measures shall be taken to prevent

accidental impacts etc.

f) Bracing, struts and ties shall be installed along with the progress of form

work to ensure strength and stability of form work at intermediate stage.

Steel sections (especially deep sections) shall be adequately restrained

against tilting, overturning and form work should be restrained against

horizontal loads. All the securing devices and bracing shall be tightened.

g) The stacked materials shall be placed as catered for, in the design.

h) When adjustable steel props are used, they should

i) Be undamaged and not visibly bent.

ii) Have the steel pins provided by the manufacturers for used

iii) Be restrained laterally near each end.

iv) Have means for centralising beams placed in the fork heads

v) Screw adjustment of adjustable props shall not be over extended

j) Double wedges shall be provided for adjustment of the form to the required

position wherever any settlement/elastic shortening of props occurs. Wedges

should be used only at the bottom end of single prop. Wedges should not be

too steep and one of the pair should be tightened/clamped down after

adjustment to prevent their shifting.

k) No member shall be eccentric upon vertical member

l) The number of nut sand bolts shall be adequate.

m) Provisions of the design and/or drawings shall be complied

n) Cantilever supports shall be adequate

Page 105: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 105 of 307

o) Props shall be directly under one another in multistage constructions as far

as possible.

p) Guy ropes or stays shall be tensioned properly

q) There shall be adequate provision for the movement and operation of

vibrators and other construction plant and equipment.

r) Required camber shall be provided over long spans

s) Supports shall be adequate, and in plumb within the specified tolerances.

9.2.7. Form Oil : Use of form oil shall not be permitted on the surface, which require

painting. If the contractor desire to use form oil on the inside of form work of the

other concrete structures, a non staining mineral oil or other approved oil CEMOL-

35 of M/s. Hindustan Petroleum Co. Ltd may be used, provided it is applied before

placing reinforcing steel and embedded parts. All excess oil on the form surfaces

and any oil on metal or other parts to be embedded in the concrete shall be

carefully removed. Before treatment with oil, forms shall be thoroughly cleared of

dried splatter of concrete from placement of previous lift.

Any loss of water through the shuttering should be strictly prevented from

placement specially for concrete mix with low water binder ratio or having partial

replacement of cement by pozzolana. In case of wooden shutter approved quality

of form oil or plastic sheet can be use for this purpose.

9.2.8. Chamfers and Fillers : All corners and angles exposed in the finished structure

shall be formed with mouldings to form chamfers or fillers on the finished

concrete. The standard dimensions of chamfers and fillets, unless otherwise

specified, shall be 20 x 20mm. Care shall be exercised to ensure accurate

mouldings. The diagonal face of the moulding shall be planed or surfaces to the

same texture as the forms to which it is attached.

9.2.8.1. Vertical Construction Joint Chamfers: Vertical construction joints on faces

which will be exposed at the completion of the work shall be chamfered as above

except where not, permitted by Engineer-in-charge for structural or hydraulic

reasons.

9.2.8.2. Wall Ties : Wire ties passing through the walls, shall not be allowed. Also

through bolts shall not be permitted. For fixing of form work, alternate

arrangements such as coil nuts shall be adopted at the contractors cost.

9.2.8.3. Reuse of Forms : Before reuse, all forms shall be thoroughly scraped, cleaned,

nails removed, holes that may leak suitably plugged and joints examined and

when necessary repaired and the inside retreated to prevent adhesion, to the

satisfaction of Engineer-in-charge. Warped lumber shall be resized. Contractor

shall equip himself with enough shuttering to complete the job in the stipulated

time.

9.2.8.4. Removal of Forms : Contractors shall record on the drawings or a special

register, the date upon which the

concrete is placed in each part of the work and the date on which the shuttering

is removed there from.

Page 106: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 106 of 307

In no circumstances shall forms be struck until the concrete reaches a strength of

the at least twice the stress due to self weight and any construction erection

loading to which the concrete may be subjected at the time of striking form work.

In normal circumstances (generally where temperatures are above 200 C.) forms

may be struck after expiry of the following periods.

S.

N

Part of Structure

Earliest concrete age at stripping

Cement with low

and

having pozzolanas

Ordinary

Portland

cement

concrete

Portland

Pozzolana

C.C

Fly Ash

Based

a) Walls, columns and

vertical sides

of beams

3 days 24 to 48

hours

as directed

by

the E-I-C.

3 days

b) Slabs(Props left Under) 14 days 3 days 7 days

c) Beam, soffits (Props left 14 days 7 days 10 days

d) Removal of props

i)Spanning upto 4.5m

ii) Spanning over 4.5m 14 days

14 days

7 days

14 days

10 days

14 days

e) Removal of props in

beams &

arches

i) Spanning upto 6m

ii) Spanning over 6m

14 days

14 days

14 days

21 days

14 days

21 days

f) For perforated 120mm 14 days 14 days 14 days

Skirting shall be done slowly with utmost care to avoid damage to arise and

application and without shock or vibration by gently easing the wedge etc. After

removing the form work, if it is found that timber has been embedded in the

concrete, it shall be removed and made good as specified earlier.

Reinforced temporary openings shall be provide as directed by Engineer-in-charge,

to facilitate removal of form work which otherwise may be in accessible.

Tie, rods, clamps form-bolts etc. which must be entirely removed from walls or

similar structures shall be loosened not sooner that 24 hours not later than 40

hours after concrete has been deposited. Ties, except those required to hold

forms in place, may be removed at the same time. Ties withdrawn from walls and

grade beams shall be pulled towards the inside face. Cutting ties back from the

faces of walls and grade beams will not be permitted. Work damaged due to

premature or careless removal of forms shall be re-constructed at contractor's

cost.

* * *

Page 107: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 107 of 307

1 1 . STRUCTURAL STEEL :

11.1. SCOPE OF WORK :

The work covered by this specification consists of furnishing and erecting of

structural steel complete in strict accordance with this specifications and the

applicable drawings.

11.2. MATERIALS :

11.2.1. All structural steel shall be of standard sections as marked on the drawings

and shall be free of scale, blisters, laminations, cracked edges and defects of any

sort. If the structural steel is not supplied by the Department and the Contractor

is required to bring such steel, the Contractor shall furnish duplicate copies of all

mill orders and/ or also the test report received from the mills, to satisfy the

Engineer-in-Charge.

11.2.2. All structural steel and electrodes shall comply in all respects with I.S.S. for

structural steel.

11.3. WORKMANSHIP :

All workmanship shall be of first class quality in every respect to the greatest

accuracy being observed to ensure that all parts will fit together properly on

erection.

All ends shall be cut true to planes. They must fit the abutting surfaces closely. All

stiffeners shall be fit tightly at both ends.

All butt ends of compression members shall be in close contact through the area

of the joints.

All holes in plates and section between 12 mm. and 20 mm. thick shall be punched

to such diameter that 3 mm. of metal is left all around the hole to be cleaned out

to correct size by reamer.

The base connection shall be provided as shown on drawings and the greatest

accuracy of workmanship shall be ensured to provide the best connections.

Figured dimensions on the drawings shall be taken.

11.4. ERECTION AND MARKING :

Erection and fabrication shall be according to I.S. 800-1984 section-11. During

erection, the work shall be securely braced and fastened temporarily to provide

safety for all erection stresses etc. No permanent welding shall be done until

proper alignment has been obtained.

Any part which do not fit accurately or which are not in accordance with the

drawings and specifications shall be liable to rejection and if rejected, shall be at

once be made good.

Engineer-in-Charge shall have full liberty at all reasonable times to enter the

contractors premises for the purpose of inspecting the work and no work shall be

taken down, painted or despatched until it has been inspected and passed. The

Page 108: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 108 of 307

contractor shall supply free of charge all labour and tools required for testing of

work.

11.5. DELIVERY AT SITE :

The contractor shall deliver the component parts of the steel work in an

undamaged state at the site of the works and the Engineer-in-Charge shall be

entitled to refuse acceptance of any portion which has been bent or otherwise

damaged before actual delivery on work.

11.6. SHOP DRAWINGS :

The shop drawings of structural steel based on contract drawings shall be

submitted to the Engineer-in-Charge. The necessary information for fabrication,

erection, painting of structure etc. must be furnished immediately after acceptance

of the tender.

11.7. PAINTING :

Painting should be strictly according to I.S. 1477-1971 (Part I-Pretreatment) and

I.S. 1477-1 971 (Part II-painting).

Painting should be carried out on dry surfaces free from dust, scale etc. The paint

shall be approved by the Engineer-in-Charge.

One coat of shop paint (red lead) shall be applied on steel, except where it is to be

encased in concrete or where surfaces are to be field welded.

11.8. WELDING :

Welding shall be in accordance with I.S. 816-1969, I.S. 819-1957, I.S. 1024-1979,

I.S. 1261-1959, I.S. 1323-1982 and I.S. 9595-1980 as appropriate. For welding of

any particular type of joint, welders shall give evidence of having satisfactory

completed appropriate tests as described in any of I.S. 817-1966, I.S. 1393-1961,

I.S. 7307 (Part-I)-1 974, I.S. 7310 (Part-I)-1974 and I.S. 7318 (Part-I)-1 974 as

relevant.

11.8.1. Welding Consumables : Covered electrodes shall conform to I.S. 814 (Part-I)-

1974 and I.S.814 (Part-II)-1974 or I.S. 1395-1 982 as appropriate.

Filler rods and wires for gas welding shall conform to I.S. 1278-1972.

The bare wire electrodes for submerged arc welding shall conform to I.S. 7280-1

974. The combination of arc and flash shall satisfy the requirements of I.S. 3613-1

974.

The filler rods and bare electrodes for gas shielded metal, arc welding shall conform

to I.S. 6419-1971 and I.S. 6560-1972 as appropriate.

11.8.2. Types of Welding: Arc welding (direct or alternating current) or Oxyacetylene

welding may be used. Field welding may be used. Field welding shall be by D.C.

11.8.3. Size of Electrode Runs: The maximum gauge of the electrodes for welding any

work and the size of run shall be based on the following tables.

Page 109: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 109 of 307

Average thickness of plate

or section

Maximum gauge or diameter of

electrodes to be used.

Less than 3/16" 10 S.W.G.

3/16" and above but less than

5/16" 8 S.W.G.

5/16" and above but less than

3/8" 6 S.W.G.

3/8" and above but less than

5/8" 4 S.W.G.

5/8" and above but less than

1" 5/1 6"dia.

1" and above thick section 3/8" dia.

Note : On any straight weld the first run shall not ordinarily be deposited with a

larger gauge electrode than No. 8 S.W.G. For subsequent runs the electrode shall

not be increased by more than two electrode size between consecutive runs.

11.8.4. Welding Contractors : The contractor shall ensure that each welding operator

employed on fabrication or erection is an efficient and dependable welder, who has

passed qualifying tests on the types of welds which will be called upon to make.

Sample test shall have to be given by the contractor to the entire satisfaction of

the Engineer-in-charge.

11.8.5. Welding Procedure :

a) Welding should be done with the structural steel in flat position in a down

hand manner wherever possible. Adequate steps shall be taken to maintain the

correct arc length, rate of travel, current and polarity for the type of electrode

and nature of work. Welding plant capacity shall be adequate to carry out the

welding procedure laid down. Adequate means of measuring the current shall

be available either as a part of the welding plant or by the provision of a

portable ammeter. In checking the welding current, a tolerance of 10% or 30

amperes from the specified value whichever is less shall be permitted.

b) The welding procedure shall be such as to ensure that the weld metal can be

fully and satisfactory deposited through the length and thickness of all joints

so that distortion and shrinkage stresses are reduced to the minimum and

thickness of welds meet the requirements of quality specified.

11.9. WORKMANSHIP :

11.9.1. Preparation of Fusion Faces : Fusion faces shall be cut by stearing machine

or gas cutting and later dressed by filling or grinding so that they shall be free

from irregularities such as would interfere with the deposition of the specified size

of weld to cause the defects. Fusion faces and the surrounding surfaces shall be

free from heavy slag, oil paint or any substance which might affect the quality of

the weld or impede the progress of welding. The welding face shall be free of rust

and shall have metal shine surfaces.

Page 110: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 110 of 307

The parts to be welded shall be brought into as close contact as possible and the

gap due to faulty workmanship or incorrect fit up shall not exceed 1/16". If

seParation of 1/16" or more occurs locally, the size of the fillet weld shall be

increased at such position by an amount of equal to the width of the gap.

The parts to be welded shall be maintained to their correct position during welding.

They shall be securely held in position by means of tack welds, service bolts,

clamps or rings before commencing welding so as to prevent and relative

movement due to distortion, wind or any other cause.

11.9.2. Step Back Method Should be Used to Avoid Distortion : The minimum leg

length of a fillet weld as deposited should not be less than the specified size and

the throat thickness as deposited should be not less than that tabulated below:

Throat Thickness of Fillet

Angle between fusion

faces 60 0-90 0

910-

100 0

101 0-

106 0

107 0-

113 0

114 0-

120 0

Throat thickness in

cms.

0.70 0.65 0.60 0.55 0.50

In no case should a concave weld be deposited without the specific approval of the

Engineer-in-Charge unless the leg length is increased above the specified length

so that the resultant throat thickness is as great as would have been obtained by

the deposition of a flat.

All welds shall be deposited in a pre-arranged order and sequence taking due

account of the effects of distortion and shrinkage stresses.

After making each run of welding, all slag shall be removed and final run shall be

protected by clean boiled linseed oil till approved.

The weld metal, as deposited, shall be free from crack, slag, excessive porosity,

cavities and other faults.

The weld metal shall be properly fused with the parent metal without overlapping or

serious undercutting at the toes of the weld.

The surfaces of the weld shall have a uniform and consistent contour and regular

appearance.

In welds containing crack, porosity or cavities in which the weld metal tends to

overlap on the parent metal without proper fusion, the defective portions of the

welds shall be out cut and re-welded. Where serious under cutting occurs,

additional weld metal shall be deposited to make good reduction. Testing of welded

joints shall be done as per relevant IS codes 3600, 3613, 4260, 7205, 7215, 7307,

7310, 7318.

11.10. MODE OF MEASUREMENT:

All structural steel shall be measured on weight basis in metric tonnes or quintals

or kgs. as mentioned in the schedule of quantities. The length or areas of various

members including gusset plates shall be measured correct to two places of

decimals and the net weight worked out from the standard steel tables approved

by Indian Standard Institution. No separate measurements shall be taken for

welding, riveting, bolting, field connections etc. The rate shall include cost of all

Page 111: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 111 of 307

labour, materials, scaffolding, transport and also cost of welding, riveting and

bolting, field connections if any all to complete the job as per specifications.

* * * *

12. BRICK WORK :

12.1. SCOPE OF WORK :

The work covered under this specification pertains to procurement of well burnt

clay bricks of class 35 unless otherwise specified and workmanship in building

walls of various thickness, in strict compliance with the specifications and

applicable drawings.

12.2. MATERIALS:

Brick shall be well burnt clay bricks of designated class and shall satisfy the

strength criteria and shall be got approved by the Engineer-in-Charge before

incorporation in the work. The bricks shall be hand moulded or machine moulded

and shall be free from nodules of free lime, visible cracks, flaws, warpage and

organic matter.

In general, the nominal size of bricks (F.P.S.) shall be 22.9 x 11.4 x 7 cm.

(9”x4.5”x2.75”). Permissible tolerance on dimensions shall not be more than (+/-)

8%. The contractor shall get approved the sample and source of bricks from

Engineer-in-Charge before procurement on large scale and shall maintain the

same for the entire work. The bricks shall have smooth rectangular faces with

sharp corner and shall be uniform in colour.

Bricks for Mumbai / Pune and surrounding areas, unless otherwise specified, shall

be as per relevant IS of class

designation 35 of size 22.5 x 11.1 x 7 cm. Permissible tolerance on dimensions

shall not be more than (+/-) 8%.

Unless otherwise specified, bricks for Eastern Zone works (Kolkata /

Bhubneshwar / Shillong etc.) shall be of class designation 75 of size 25 x 12.5 x

7.5 cm. Permissible tolerance on dimensions shall be as per relevant IS.

In case the size of bricks used in the work is found lesser than the specified one

but within the permissible tolerance i.e. {-} 8% , the following shall apply:

i. Extra cement consumed due to more number of joints and due to additional

thickness of plaster than the specified in the tender to match with adjoining

columns and beams, shall be borne by the contractor without any extra cost to

the department.

ii. If the plastering to be done is more than the specified thickness to maintain

the plaster surface to perfect line, level and plumb with adjoining columns,

beams, walls etc., the contractor shall be responsible to provide more

thickness of plaster at his own cost and nothing extra will be paid on this

account.

In case the size of bricks used in the work is found more than the permissible, the

contractor shall chip out the exposed edges of bricks upto the required level of wall

to receive specified thickness of plaster.

Page 112: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 112 of 307

Bricks shall generally conform to I.S. 1077-1992. In any case minimum crushing

strength shall not be less than 35 kg/cm2 and water absorption shall not be more

than 25% by weight. The Engineer-in-Charge shall have the right to reject bricks

obtained from any field where the soil has an appreciable quantity of sulphates

and chlorides. The specifications for cement, sand and water shall be same as

described herein before under cement concrete. Bricks shall be thoroughly soaked

in water before using till the bubbles ceases to come up. No half or quarter brick

shall be used except as closer. The closer shall be cut to required size and used near

the end of the walls. The walls shall be raised truly to plumb. The type of bond to

be adopted shall be decided by the Engineer-in-Charge, but vertical joints shall be

laid staggered.

12.3. WORKMANSHIP :

Four courses of brick work with four joints should not exceed by more than 40 mm.,

the same bricks piled one over the other without mortar.

Brick work shall not be raised more than 10 courses a day unless otherwise

approved by the Engineer-in-Charge. The brick work shall be kept wet for at least 7

days. Brick work shall be uniformly raised alround and no part shall be raised more

than 1.0 metre above another at any time.

All joints shall be thoroughly flushed with mortar of mix as specified in the

schedule of quantities, at every courses. Care shall be taken to see that the bricks

are bedded effectively and all joints completely filled to the full depth.

The joints of brick work to be plastered shall be raked out to a depth not less than

10 mm. as the work proceeds. The surface of brick work shall be cleaned down and

watered properly before the mortar sets.

The adhesion between the brick masonry surface and the concrete surface of

columns, beams, chajjas, lintels etc. should be proper by ensuring that the

concrete surface coming in contact with brick masonry is hacked/ chipped/ keyed,

cleaned and cement slurry is applied so that a proper bond is achieved between

the two dissimilar materials. It is the responsibility of the contractors to ensure

that there will not be any cracks/ fissures anywhere in the brick masonry.

In case the cracks appear subsequently in those areas, they should be made good

by cement grouting or epoxy putty grouting/ poly sulphide compound grouting or

as per standard modern specifications/ methods with the prior approval of the

Engineer-in-Charge, at the cost of the contractor.

All the courses shall be laid truly horizontal and all vertical joints shall be truly

vertical. Specified mortar of good and approved quality shall be used. Lime shall not

be used where reinforcement is provided in brick work. The mortar should

completely cover the bed and sides of the bricks. Proper care should be taken to

obtain uniform mortar joint throughout the construction. the walls should be

raised uniformly in proper, approved bond. In construction of the wall, first of all

two end corners are carefully laid to line and level and then in between portion is

built, with a cord stretching along the headers or stretchers held in position at the

ends. This helps in keeping the alignment of the courses and maintaining them in

level. Similarly all other courses are built. Care shall be taken to keep the

perpends properly aligned within following maximum permissible tolerances :

Page 113: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 113 of 307

a. Deviation from vertical within a storey shall not exceed 6 mm per 3 m height.

b. Deviation in verticality in total height of any wall of building more than one

storey in height shall not exceed 12.5mm.

c. Deviation from position shown on plan of any brick work shall not exceed 12.5

mm.

d. Relative displacement between load bearing wall in adjacent storeys intended to

be vertical alignments shall not exceed 6 mm.

e. A set of tools comprising of wooden straight edge, masonic spirit levels, square,

1 meter rule line and plumb shall be kept on the site of work for every 3

masons for proper check during the progress of work.

No brick work shall be carried on during frosty weather except with the written

permission of the Engineer-in-Charge, who will give special directions as to the

manner in which the work is to be performed. All brick work laid during the day,

shall, in seasons liable to frost, be properly covered up at night as directed by the

Engineer-incharge. Should any brick work be damaged by frost, the brick work

shall, at the discretion of the Engineer-in-Charge, be pulled down and made good,

at the cost of the contractor.

Concrete surfaces of columns, beams, lintels, chajjas etc. coming in contact with

masonry work shall be include wire brushing and cleaning brickwork covered with

fungus or deleterious materials.

Brick work shall be well watered/ cured throughout the day for at least a week from

the date of building and the work shall be protected from sun and rain.

HALF BRICK WORK:

Materials and workmanship for a half brick or brick on edge partition wall shall be

as specified above. The wall shall be stiffened by R.C.C. stiffeners of size 115 mm.

wide x 80 mm. thickness to the full length of wall and shall be provided with 2 Nos.

6 mm. diameter M.S. bars or as specified in the schedule as bottom reinforcement

(only the M.S. reinforcement will be paid separately under relevant item). These bars

shall be securely anchored at their end where the partition end. The free ends of the

reinforcement shall be keyed into the mortar of the main brick work to which the

half brick work is joined. Overlaps in reinforcement, if any, shall not be less than

30 cm.

The rates for brick work shall include the cost of the following:

i. Providing and fixing necessary single or double scaffolding and removing the

same after the work is completed.

ii. Form work for stiffeners concrete as required.

iii. Watering, curing, lifting of materials to any height.

iv. Raking out of joints to receive plaster.

v. Forming slab sittings, cutting or leaving holes for lugs of windows, doors, sills,

Page 114: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 114 of 307

switch boxes etc.

vi. Making good all holes, chases, etc. to any depth due to conduit pipes,

holdfasts, bolts, switch & plug boxes etc.

vii. Bedding and pointing precast lintels, sills etc. in or on walls. For the purpose of

measurements, the thickness of one brick wall and over shall be taken in terms of

multiples of half brick.

12.4. SAMPLING AND TESTS:

Samples of bricks shall be subjected to the following mandatory tests :

a) Dimensional tolerance b) Water absorption c) Efflorescence

d) Compressive strength

Note : 1. Cost of above tests shall be borne by the contractor.

2. Frequency of test shall be as per relevant IS specifications.

12.5. MODE OF MEASUREMENT :

13.5 a) For Brick Work Measured in Cubic Metres :

The contract rate shall be for a unit of one cubic metre of brick masonry as actually

done. 230 mm. thick (or as specified in schedule) brick walls shall be taken as one

brick thick.

All openings in brick work for doors, windows and ventilators shall be deducted to

get the net quantity of actual brick work done.

Openings or chases required for P.H. or electrical inserts less than 0.1 sqm. and

bearing of precast concrete members shall not be deducted.

No extra payment shall be made for any extra work involved in making the above

openings or placements.

13.5 b) For brick work measured in square metre :

Half brick thick masonry walls shall be measured in sqm. All openings in brick

work for doors and windows and ventilators shall be deducted to get the net

quantity of actual work done. Openings or chases required for P.H. or Electric

inserts less than 0.1 sqm. and bearing of precast concrete members shall not be

deducted. No extra payment shall be made for extra work involved in making the

above openings or placements.

* * * *

13. CEMENT CONCRETE FLOORING (IPS) :

13.0. SCOPE OF WORK :

The work covered under this specification consists of providing and laying at all

levels and floors, flooring of different types, strictly in accordance with these

specifications and relevant drawings.

Page 115: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 115 of 307

13.1. CEMENT CONCRETE FLOORING (INDIAN PATENT STONE)

:

13.1.1. Materials : The specifications for materials, grading, mixing and the

quantity of water to be added shall generally conform to their relevant

specifications described under plain and reinforced concrete. The maximum

size of coarse aggregate shall be 10 mm. The fine aggregate shall consist of

properly graded sand. Concrete shall be mixed preferably by machine, and

hand mixing shall be avoided as far as practicable.

13.1.2. Preparation of Base : The base concrete surface shall be thoroughly

chipped to remove laitance, caked mortar, loose sand, dirt etc. cleaned with

wire brush and washed clean and watered until no more water is absorbed.

Where the base concrete has hardened so much that roughening the surface

by wire brushes is not possible, the same shall be roughened by chipping or

hacking at close intervals. The surface shall be soaked with water for at least

12 hours and surface water removed and dried before laying the topping.

Before laying the concrete, cement slurry at 2.75 kg./ sqm. of surface shall be

applied for better bond. Concrete flooring shall then be laid in alternate bays in

pattern and joints, wide/ flush as per drawing. The edge of each panel into

which the floor is divided shall be supported by wooden or metal strips duly

oiled to prevent sticking. The panels shall be of uniform size and, unless

otherwise specified, no dimension of panel shall exceed 2 m. and the area of a

panel shall not be more than 2 sqm. However, the exact size of panel shall be

decided by the Engineer-in-Charge to suit the size of the room. The joints in the

floor finish shall extend through the borders and skirting/dado. The border

shall have mitred joints at the corners of the room. Where glass/ aluminium

dividing strips are proposed to be provided, the same shall be fixed in cement

mortar 1:2 @ 600 mm. centres or as specified in the schedule for full depth of

the finished floor.

The depth of dividing strips shall be the thickness as proposed for the finished

floor in the item. In the case of flush joins, alternate panels only may be cast

on same day. At least 48 hours shall elapse before the concreting of adjacent

bay is commenced.

13.1.3. Mixing : The topping concrete shall be of mix of one part of cement, two

parts of sand and 4 parts of well graded stone chips of 10 mm. maximum size.

The ingredients shall be thoroughly mixed with just sufficient water to the

required plasticity, having water cement ratio not more than 0.4.

13.1.4. Laying : The free water on the surface of the base shall be removed and

a coat of cement slurry to the consistency of thick cream shall be brushed on

the surface. On this fresh grouted base, the prepared cement concrete shall be

laid immediately after mixing. The concrete shall be spread evenly and laid

immediately after mixing. The concrete shall be spread and levelled carefully.

The concrete shall be completed and brought to the specified levels by means

of a heavy straight edge resting on the side forms and down ahead with a

sawing motion in combination with a series of lifts and drops alternatively with

small lateral shifts, either mechanically or manually as directed by the

Engineer-in-Charge.

Page 116: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 116 of 307

While concreting the adjacent bays, care shall be taken to ensure that the

edges of the previously laid bays are not broken by carelessness or hand

tamping. Immediately after laying the concrete, the surface shall be inspected

for high or low spots and any needed correction made up by adding or

removing the concrete and whole surface is again levelled. When the layer is

made even, the surface shall be completed by ramming or beating and then

screed to a uniform line and level. Before the initial set commences, the

surface shall be trowelled to smooth and even surface free from defects and

blemishes and tested with straight edges. No dry cement or mixture of dry

cement and sand shall be sprinkled directly or empty gunny bags spread over

the surface of the concrete to absorb excess water coming on top due to

floating.

13.1.5. Finishing the Surface : After the concrete has been fully compacted, it

shall be finished by trowelling or floating. Finishing operations shall start

shortly after the compaction of concrete and shall be spread over a period of one

to six hours depending upon the temperature and atmospheric conditions. The

surface shall be trowelled intermittently at intervals for several times so as to

produce a uniform and hard surface. The satisfactory resistance of floor to

wear depends largely upon the care with which trowelling is carried out. The

object of trowelling is to produce as hard and close knit a surface as possible.

The time interval allowed between successive trowelling is very important.

Immediately after laying only just sufficient trowelling shall be done to give a

level surface. Excessive trowelling in the earlier stages shall be avoided as this

tends to work a layer rich in cement to the surface, some time. After the first

trowelling, the duration depending upon the temperature, atmospheric

conditions and the rate of setting of cement used, the surface shall be

retrowelled many times at intervals to close any pores in the surface, and to

bring to surface and scrap off any excess water in concrete or laitance (it shall

not be trowelled back into the topping). The final trowelling shall be done well

before the concrete has become too hard but at such a time that considerable

pressure is required to make any impression on the surface. Trowelling of rich

mix of dry cement and fine aggregate on to the surface shall not be permitted.

Trowel marks should not be seen on the finished surface.

Where broom finish is specified, after the concrete has been thoroughly

compacted, and when most of the surface water has disappeared, the surface

shall be given broom finish with an approved type of brass or M.S. fiber. The

broom shall be pulled gently over the surface from edge to edge in such a

manner that corrugation shall be uniform in width and depth, the depth shall

be not more than 1.5 mm. Brooming shall be done when the concrete is in such

a condition that the surface will not be torn or unduly roughened by the

operation. Coarse or long bristles which cause irregularities or deep

corrugation shall be trimmed out. Brooms which are worn or otherwise

unsatisfactory shall be discarded.

After the concrete in the bays has set, the joints of the panels should be filled

with cement cream and neatly floated smooth or jointed. Care should be taken

that just the minimum quantity of cream for joint is used and excess spilling

over the already finished surface shall be removed when the cream is still

green.

Page 117: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 117 of 307

In case of wide joints the same shall be filled with pigmented cement concrete

(1:2:4) using approved pigment and the joint shall be finished in perfectly

straight line.

13.1.6. Steel Trowel Finish : Areas where Marblex tiles are proposed to be used

are required to have base concrete finished smooth by steel trowel.

13.1.7. Curing : The completed flooring shall be protected from sun, wind and

rain for the first two days and movement of persons over the floor is prohibited

during this period. The finished surface shall be covered and cured

continuously form the next day after finishing, at least for a period of 7 days.

Bunding with murrum for curing is prohibited as it will leave permanent stain

on the finished floor.

Curing shall be done by spreading sand and kept damp throughout the curing

period of seven days minimum. The surface shall be protected from any

damage to it whatsoever. The surface shall then be allowed to dry slowly. All

corners, junctions of floor with plastered wall surface shall be rounded off

when required at no extra cost.

13.1.8. Mode of Measurement : The rate for flooring and skirting shall be in

square metre of the area covered.

The length and width of the flooring shall be measured net between the faces

of skirting or dado or plastered faces of walls which is the proudest.

All openings in flooring exceeding 0.1 sqm. in area where flooring is not done

shall be deducted and net areas only shall be measured and paid for. Flooring

under dado, skirting or plaster shall not be measured for payment.

Nothing extra shall be paid for laying the floor at different levels in the same

room.

The dimensions shall be measured upto two places of decimals of a metre and

area worked out upto two places of decimal of a square metre.

* * * *

14. CEMENT CONCRETE FLOORING WITH RED OXIDE TOPPING

14.1. GENERAL :

Red oxide of iron when used, gives an improved appearance to concrete flooring. The

specifications shall be as under.

14.2. RED OXIDE OF IRON :

Red oxide powder as the name indicates is a fine powder of iron oxide, red in colour

normally available in market shall be obtained in adequate quantity and stores in

clean dry place.

Page 118: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 118 of 307

14.3. PREPARATION OF BASE :

The specifications for cement concrete flooring (I.P.S.) shall be followed for this work

also.

14.4. UNDER LAYERS :

The under layer of flooring of specified thickness shall be of cement concrete 1:2:4

mix using 10mm. maximum size coarse aggregate. The dividing strips of aluminium

or glass if required to be retained shall not be removed and kept in position

properly. After the consolidation is over, the top surface shall be left rough by

drawing diagonal lines 2 mm. deep at 75 mm. centres both ways.

14.5. TOP LAYER :

14.5.1. Mortar: The top layer shall consist of uniform and smooth layer of

specified thickness and of mix 1.3 ( 1 cement: 3 coarse sand) and finished with

a floating coat of neat cement. The cement shall be mixed dry with red oxide

powder in the proportion of 3.5 kg. of red oxide to 50kg. (1 bag) of cement.

This mixture shall be used in both the cases i.e. for mixing mortar for top layer

and also for floating coat. Full quantity of materials required for one room

shall be mixed and kept ready to ensure uniform colour. Net mortar shall be

prepared in usual manner.

14.5.2. Laying of Top Layer: The top plaster shall be done the following day

after the under layer is laid. The plaster shall be done to specified thickness

(normally 10 mm.) and finished smooth with cement and red oxide slurry at 2.2

kg. of cement red oxide mix per sqm. The surface shall be polished smooth

with polishing stones.

Alternate panels shall then be taken in hand for laying under layers, top

layers as process repeated. Rounding at the junction with the wall shall be

done, if required, to a radius of 25 mm.

14.6. CURING: Similar to Cement concrete flooring (IPS)..

14.7. MODE OF MEASUREMENT: Similar to Cement concrete flooring (IPS).

* * * *

GENERAL NOTE FOR ALL TILING WORKS:

Where the size of flooring files and height of risers, skirting or dado does not admit

full size of other finished size tiles, the tile(s) are to be cut / sawn to the required

size and nothing extra shall be paid for the same.

15. KOTAH STONE FLOORING/ SKIRTING/ FACIA / SHELVES :

15.1. MATERIALS : . The stone shall be hard, sound, durable, homogeneous in

texture and resistant to wear. These shall be without any soft veins, cracks or flaws

and shall have uniform colour. They shall have natural surface free from broken flakes

on top. Hand cut/ machine cut for exposed edges and machine polished. Kotah stone

Page 119: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 119 of 307

shall be of the best quality and of the specified thickness, size and the shade, which

shall be got approved by the Engineer-in-charge.

The slabs / tiles shall be rectangular or square in shape or as per pattern shown in

drawing and as directed by the Engineer-in-charge. The sizes given in schedule of

quantities are tentative and can vary only slightly as per the availability in the

market. The thickness of the slab after it is dressed shall be 20, 25, 30 or 40 mm as

specified in the item. Tolerance of (+/-) 2 mm shall be allowed for the thickness. In

respect of length & width, tolerance in length & width shall be permissible upto (+/-) 5

mm for hand cut slabs & (+/-) 2 mm for machine cut slabs. At its thinnest, no stone

shall be thinner than the specified thickness.

Uniformity of size and colour / shade shall generally be maintained for the stones

used in any one room. The exposed surface shall be machine polished to a smooth,

even and true plane and the edges hand cut and dressed true and squares. The

evenness of the surface of slabs and edges of the slab shall not be marred by careless

dressing or handling and no patching up shall be allowed for the slab. The edges shall

be quite straight. The under face may be left as required or rough dressed. Before

taking up the work, samples of stone slabs to be used and their dressing and

polishing shall be got approved by the Engineer-in-charge and kept in his office as

approved sample and the stone slabs to be used shall conform to the same.

15.2. BEDDING/ BACKING COAT : In case of flooring / skirting / dado, the mortar

bedding / backing shall be of cement mortar of thickness and mix specified in the

schedule of work.

15.3. CEMENT MORTAR: Cement mortar bedding shall be as specified under

relevant specification for terrazzo / plain cement tile flooring.

15.4. CONSTRUCTION DETAILS: Cement mortar as specified for bedding shall be

uniformly mixed. The amount of water added shall be the minimum necessary to give

just sufficient plasticity for laying and satisfactory bedding. Care shall be taken in

preparing the mortar to ensure that there are no hard lumps that would interfere with

the even bedding of the stones. Before spreading the mortar, the sub-floor or base

shall be cleaned of all dirt, set mortar scum or laitance and of loose materials by

hacking and brought to original levels and then well wetted without forming pool of

water on surfaces.

15.5. FIXING THE STONE SLAB/ TILE : Before laying, the stone shall be thoroughly

wetted with clean water, neat cement grout (2.75 kg/ sqm.) of honey like consistency

shall be spread on the mortar bed over as much areas as could be covered with the

slabs within half an hour. The specified type of stone shall be laid on the neat cement

float and shall be evenly and firmly bedded to the required level and slope in the

mortar bed. Each stone shall be gently tapped with wooden mallet till it is firmly and

properly bedded. There shall be no hollows left. If there is a hollow sound on gently

tapping off the slab, such slab shall be removed and reset properly. The joints shall be

grouted with matching cement slurry. Approved pigment shall be used in cement

slurry to match with shade of stone. Pigment required to match the shade of stone

shall be supplied by the contractor at no extra cost. The stone adjoining the wall shall

go about 12mm. under the plaster, skirting or dado for the wall. All stone slabs, tiles

shall be so laid as to have continuous lines from various rooms to the corridors. No

change of lines shall be permitted at junction between rooms and corridors. Only one

piece machine cut, Kotah stone shall be used for treads and risers, unless otherwise

Page 120: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 120 of 307

specified in the tender schedule..

15.6. CURING : The work shall be kept well wetted with damp sand or water for

seven days.

15.7. POLISHING AND CLEANING : When the bedding and joints have completely

set and attained required strength, the surface shall be machine polished to give

smooth, even and true plane to the flooring. All flooring shall be thoroughly cleaned

and handed over free from any mortar stains etc. Polishing shall be done as per

relevant IS and IS-14223 (Specification for polished building stones).

15.8. SKIRTING AND DADO/ FACIA : The quality and type of stone shall be same as

mentioned for flooring except of their height and thickness or backing coat which

shall be as mentioned in item schedule. The backing shall conform to the

specifications for cement mortar specified for item of terrazzo tiles. Contractor should

take into consideration the fact that touching up of the plaster at the junction of

skirting / dado is invariably done after the skirting/ dado/ facia work is completed

and quote rates accordingly. Nothing extra for the same shall be entertained.

Fixing, curing, polishing and cleaning shall be as specified herein before under

cement/ terrazzo tile skirting. Polishing may be done by hand, but a smooth surface

and fine polishing shall be obtained. Joints shall be finished in neat matching cement

slurry. The junction of plaster and the upper edges of the dado/ skirting shall be

finished smoothly as directed by the Engineer-in-charge without any extra cost.

15.9. MODE OF MEASUREMENTS : Flooring, skirting and dado/ facia shall be

measured same as that for terrazzo cement tile, flooring/ skirting/ dado. Unless

otherwise specified, shelves shall be paid on area basis in sqm. calculated to two

places of decimal, where length and breadth shall be measured inclusive of bearings

correct to a cm. The permissible tolerance in the specified thickness shall be (+/-) 2

mm.

Note : Wastage in obtaining the required machine cut, hand cut sizes as specified

from the commercial sizes available in market shall be taken into consideration by

contractor while quoting the rate for work and no extra claim on this account shall

be entertained.

15.10. TANDUR STONE / CUDDAPPA STONE / POLISHED SHAHABAD STONE /

BLUE WADI STONE FLOORING / SKIRTING / DADO:

The specifications for these items shall be similar to those for Kotah stone as above.

Page 121: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 121 of 307

16. GLAZED TILE FLOORING, DADO/ SKIRTING/ FACIA.

16.1. MATERIALS :

White Glazed Tiles : The tiles shall be of approved make and shall generally conform

to IS : 777. They shall be flat and true to shape and free from cracks, blisters, welts,

crawling, crazing spots, chipped edges, corners or other imperfections detracting

from their appearance. The glazing shall be of uniform shade.

The tiles shall be of square or rectangular of nominal sizes such as 300x200mm,

150x150mm, 100x100mm, 100x200mm or other as directed by the EIC. The length

of all four sides shall be measured correct to 0.1 mm and average length-breadth

shall not vary more than (+ / -) 0.8 mm from specified dimensions. The variation of

individual dimensions from average value of length/breadth shall not exceed (+ / -)

0.5 mm. Tolerance in thickness shall be (+ / - ) 0.4 mm. Size of tiles different form

the specified one, may be allowed to be used with prior approval of the EIC.

The thickness of the tiles shall not be less than 5 mm or as specified in the items and

shall confirm to I.S. 777 in all respects. Samples of tiles shall be got approved by the

Engineer-in-charge before use on the work. Top surface of tile shall be glossy or matt

as specified. The underside of tiles shall not have glaze on more than 5% of the area

in order to have proper adherence to the back.

16.2. PREPARATION OF SURFACE & LAYING :

Sub grade concrete or RCC slab or side brick wall/ or plastered surfaces on which

tiles are to be laid shall be cleaned, wetted and mopped as specified for terrazzo tile

flooring.

The bedding/backing for the tile shall be of C.M. 1.3 or as specified and shall be

applied and allowed to harden. The mortar shall be roughened with wire brushes or

by scratching diagonal lines 1.5mm. deep at 7.5mm. centre both ways.

The back of tiles shall be buttered with a coat of grey cement slurry paste and edges

with white cement slurry and set in the bedding mortar. The tiles shall be tapped

gently with wooden mallet and corrected to proper planes and lines. The tile shall be

butt jointed in pattern and joints shall be as fine as possible. The top of skirting/

dado shall be truly horizontal and joints truly vertical.

After a period of curing of 7 days minimum, the tiles shall be cleaned and shall not

sound hollow when tapped.

The surface during laying shall be checked with a straight edge 2 m. long. Where full

size tiles cannot be fixed, these shall be cut/sawn to the required size & their edges

rubbed smooth to ensure straight and true joints.

Tiles shall enter not less than 10mm. under side skirting.

After the tiles have been laid, surplus cement grout shall be cleaned off.

16.3. MORTAR AND BEDDING :

Cement mortar for bedding shall be of proportion specified in items schedule and

shall conform to the specification for materials, Preparations etc. as specified under

Page 122: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 122 of 307

cement mortar. The amount of water added while preparing mortar shall be the

minimum necessary to give sufficient plasticity for laying. Care shall be taken in

Preparation of the mortar to ensure that there are no hard lumps that would interfere

with even bedding of the tiles. Before spreading the mortar bed the base shall be

cleaned of all dirt, scum or laitance and loose materials and well wetted without

forming any pools of water on the surface. The mortar of specified proportion and

thickness shall then be even and smoothly spread over the base by use of screed

battens to proper level or slope.

Cement mortar of thickness and proportion as specified in the schedule for dado

shall be applied to the wall after preparing the wall surface as specified under

cement plaster 20mm. thick and brought to correct line and plumb and the surface

left rough to receive the tiles.

16.4. FIXING OF TILES FOR FLOORING :

The tiles before laying shall be soaked in water for at least 2 hours. The tiles shall

be laid on the bedding mortar when it is still plastic but has become sufficiently stiff

to offer a fairly firm cushion for the tiles. Tiles which are fixed on the flooring

adjoining the wall shall be so arranged that the surface on the round edge tiles shall

correspond to the skirting or dado. Neat cement mortar grout 1:2, using fine sand

(table III, zone-IV and as per I.S. 383 ) of honey like consistency shall be spread over

the bedding mortar just to cover as much area as can be tiled within half an hour.

The edges of the tiles shall be smeared with neat white cement slurry and fixed in

this grout one after the other, each tile being well pressed and gently tapped with a

wooden mallet till it is properly bedded and in level with the adjoining tiles. There

shall be no hollows in bed or joints. The joints shall be kept as close as possible and

in straight line. The surface of the flooring during laying shall be frequently checked

with a straight edge about 2M long to obtain a true surface with the required slope.

The joints between tiles shall not exceed 1.00 mm. in width. The joint shall be

grouted with white/matching colour cement slurry. After fixing the tiles, finally in an

even plane or slope, the flooring shall be covered with wet sand and allowed

undisturbed for 14 days.

16.5. FIXING TILES FOR DADO & SKIRTING/FACIA :

The dado work, shall be done only after fixing the tiles/slabs on the floor. The

approved white glazed tiles before laying shall be soaked in water for at least 2

hours. Tiles shall be fixed when the cushioning mortar is still plastic and before it

gets very stiff.

The back of the tile shall be covered with this layer of cement mortar 1:2 using fine

sand (table III, zone IV, I.S. 383-1963) and the edge of the tile smeared with neat

white cement slurry. The tile shall then be pressed in the mortar and gently tapped

against the wall with a wooden mallet. The fixing shall be done from bottom of wall

upwards without any hollows in the bed of joints. Each tile shall be as close as

possible to one adjoining. The tiles shall be jointed with white cement slurry. Any

thickness difference in the thickness of the tiles shall be arranged out in cushioning

mortar so that all tiles faces are in one vertical plane. The joints between the tile

shall not exceed 1.00 mm. in width and they shall be uniform.

While fixing tiles in dado work, care shall be taken to break the joints vertically. The

top of the dado shall be touched up neatly with the rest of the plaster above.

Page 123: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 123 of 307

After fixing the dado/skirting etc. they shall be kept continuously wet for 7 days.

If doors, windows or other openings are located within the dado area, the corners,

sills, jambs etc. shall be provided with true right angles without any specials. The

contractor will not be entitled to any extra claims on this account for cutting of tiles

if required.

16.6. CLEANING :

After the tiles have been laid in a room or the days fixing work is completed, the

surplus cement grout that may have come out of the joints shall be cleaned off before

it sets. After the complete curing, the dado or skirting over shall be washed

thoroughly clean. In the case of flooring, once the floor has set, the floor shall be

carefully washed clean and dried. When dry, the floor shall be covered with oil free

dry saw dust. It shall be removed only after completion of the construction work and

just before the floor is used.

16.7. POINTING AND FINISHING :

The joints shall be cleaned off with wire brush to a depth of 3 mm. and all dust and

loose mortar removed. Joints shall then be flush pointed with white cement and floor

kept wet for 7 days and then cleaned. Finished floor shall not sound hollow when

tapped with a wooden mallet.

16.8. MODE OF MEASUREMENT :

Dado/flooring/skirting shall be measured in sqm. correct to two places of decimal.

Length and breadth shall be measured correct to 1 cm. between the exposed

surfaces of skirting or dado. No deductions shall be made nor extra paid for any

opening of area upto 0.1 sqm.

The rate shall include all the cost of labour and materials involved.

* * *

17. MARBLE STONE FLOORING, TREADS, RISERS, SILLS, CLADDING, DADO ETC.

:

17.1. MARBLE STONE SLABS :

The colour and quality of marble slabs shall be of the kind of marble specified in

item/drawings/as directed by the Engineer-in-charge. The marble from which the

slabs are made, shall be of selected quality, hard, sound, dense and homogenous in

texture, free from cracks, decay, weathering and flaws. Before starting the work, the

contractor shall get the samples of marble slabs approved by the Engineer-in-charge.

All slabs which goes into work shall strictly conform to the samples, failing which the

entire materials are likely to be rejected.

The slabs shall be machine polished and machine cut to the dimensions specified in

items of schedules of quantities/drawings and as directed by the Engineer-in-

charge.

Page 124: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 124 of 307

17.2. DRESSING OF SLABS :

Every stone shall be cut to the required size and shape, fine dressed on all sides to

the full depth so that a straight edge laid along the side of the stone is full in contact

with it. The top surface shall also be fine dressed to remove all waviness. The top

surface of slabs shall be machine polished and exposed edges machine cut, or as

specified in the item and as directed by the Engineer-in-charge. All visible angles

and edges of the slabs shall be true, square or as required, and free from chippings

and the surface shall be true and plane.

The thickness of the slabs shall be 25 mm. or as specified in the description of item.

The minimum size of stone to be used for various items shall be as mentioned in the

schedule of quantities/drawings of this tender. Marble stones of approved smaller

sizes other than mentioned in the schedule of quantities, if required for bands,

borders, flooring etc. shall be provided and laid as directed by the Engineer-in-

charge.

Any opening of required size and shape at any desired place in flooring, bands,

borders etc. shall be made in such a way that marble bounded by number of marble

stones/slabs. No broken or defaced stone shall be permitted in the work.

17.3. BEDDING/BACKING MORTAR :

The bedding/backing shall be of cement mortar/lime mortar of mix and thickness as

specified in the description of the item.

17.3.1. Mixing : The mixing of mortar shall be done in mechanical mixer or

hand mixing as specified/as directed by the Engineer-in-Charge.

a) Mixing in Mechanical Mixer : Cement and sand in the specified proportion

shall be mixed dry thoroughly in a mixer. Water shall then be added gradually

and wet mixing continued for at least one minute. Care shall be taken not to

add more water than that which shall bring the mortar to the consistency of

stiff paste.

Only the quantity of mortar, which can be used within 30 minutes of its mixing

shall be prepared at a time.

Mixer shall be cleaned with water each time, before suspending the work.

b) Hand Mixing : If approved by Engineer-in-Charge, hand mixing shall be

allowed. The measured quantity of sand shall be levelled on clean masonry

platform and cement bags emptied on top. In hand mixing, the quantity of

cement shall be increased by 5% over the approved constant, with no extra

cost to the Department. The cement and sand shall be thoroughly mixed dry

by being turned over and over, backwards and forwards, several times till the

mixture gives an uniform colour. The quantity or dry mix which can be used

within 30 minutes shall then be mixed on masonry through with just sufficient

quantity of water to bring the mortar to the consistency of stiff paste.

c) General : Mortar shall be used as soon as possible after mixing and before it

has begun to set, and in any case within 30 minutes after the water is added

to the dry mixture. Mortar unused for more than 30 minutes shall be rejected

and removed from the site of work immediately.

Page 125: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 125 of 307

17.4. LAYING - FLOORING :

Before laying the cement mortar bedding/backing, the concrete/brick, floor/wall

surfaces shall be thoroughly hacked, cleaned of all mortar scales, concrete lumps

etc., brushed, washed with water to remove mud, dirt etc. from the surface and shall

be thoroughly wetted. Until and unless the surface is approved by the Engineer-in-

Charge, the flooring shall not be started. A bedding of cement mortar of 20 mm.

average thickness with the minimum thickness at any place under the slab not less

than 13mm. shall be laid evenly and to the required slopes as directed. The marble

slabs shall be thoroughly washed and cleaned and then be laid on the bedding/

backing with cement floating at the rate of 4.39 kg./sqm. All slabs shall be truly

and evenly set in a thick cement slurry or paste like consistency applied to the sides

and bottom and over the prepared base. The slabs shall then be tamped down with a

wooden mallet until they are exactly in true plane and line with adjacent slabs. All

slabs shall be extended upto the unplastered surface of masonry walls/RCC

columns/RCC walls. The slabs shall be close jointed in matching cement slurry and

the cement slurry coming out through the thin joints shall be immediately wiped

clean. The grains of marble stone shall be matched as shown in drawing or as

directed by the Engineer-in-Charge. All slabs shall be so laid as to have continuous

lines from various rooms to the corridors. No change of lines shall be permitted at

junction between rooms and corridor, if the same flooring is specified in both the

places.

17.5. MARBLE SILLS, TREADS ETC. :

Marble stone for sills shall be of approved quality. Dressing of stone slab, mortar

mix. for bedding/backing, laying etc. shall be similar to as described above as far as

applicable. Marble slabs of specified thickness and width shall only be provided.

The length of the each slab required for the sill shall be of the pattern which shall

coincide with the lines of the mullions of windows where it is laid or as directed by

the Engineer-in-Charge. Normally it shall not be less than 1.0 m. length.

17.6. 24.6 MARBLE STONE DADO & CLADDING :

Only machine cut and machine polished marble stone will be used. Brass cramps

and brass pins of approved quality, size and make shall be provided. The brass pins

shall be provided at the meeting of two marble slabs both ways horizontally and

vertically. The brass cramps shall be provided at the places approved by the

Engineer-in-Charge. Marble to be used shall be of approved size, colour, type of

veins and laid as specified in schedule of quantities or to the pattern shown in

drawings or as directed by the Engineer-in-Charge. Laying of marble stone shall be

similar as stated above as far as applicable.

17.7. POLISHING AND FINISHING :

The polishing and finishing shall be carried out in the similar manner as specified

under chapter “TERRAZZO / CEMENT TILES FLOORING, SKIRTING / DADO ETC.”

as far as it is applicable.

17.8. MEASUREMENT :

Marble stone flooring, sills, treads, risers, dado cladding etc. shall be measured in

square metre correct to two places of decimal. The length and breadth shall be

Page 126: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 126 of 307

measured between the finished faces correct to two places of decimal of metre. No

deduction shall be made nor extra paid for any opening of area upto 0.05 sqm.

Nothing extra shall be paid for working at different levels.

NOTE : Wastage in marble slab cutting to get the required dimensions, as specified

in drawing or as directed by the Engineer-in-Charge shall be deemed to be

considered by the contractor while quoting the rate for work. The work shall be

measured as above and no extra claim will be entertained on this account.

17.9. RATE :

The rate shall include the cost of all materials, transport tools, plants, scaffolding

and labour involved in all operations described above.

* * *

18. VITRIFIED TILE FLOORING, DADO / SKIRTING / FACIA :

18.1. MATERIALS :

Vitrified Tiles: The tiles shall be of approved make like Marbonite / Granamite or

equivalent and shall generally conform to the approved standards. They shall be flat

and true to shape, free from cracks, crazing spots, chipped edges and corners.

Unless otherwise specified, the nominal sizes of tiles shall be as under:

The tiles shall be square or rectangular of nominal sizes such as: 600 x 600 mm;

900 x 900 mm or as per tender schedule / drawings or as directed by the Engineer-

in-Charge. Thickness shall be as per recommendations of the approved

manufacturers.

Technical specifications of the tiles shall be generally conforming

to the following standards:

TECHNICAL SPECIFICATIONS FOR VITRIFIED TILES

NO PROPERTY EXPECTED

STANDARDS 1 Deviation in length (+/-) 0.6%

2 Straightness of sides (+/-) 0.5%

3 Rectangularity (+/-) 0.6%

4 Surface flatness (+/-) 0.5%

5 Water absorption < 0.50%

6 Mohs. hardness > 6

7 Flexural strength > 27 N / mm²

8 Abrasion resistance < 204 mm²

9 Skid resistance (friction > 0.4

10 Glossiness Min. 85% reflection

The tiles shall conform to the relevant standards in all respects. Samples of tiles

shall be got approved from the Engineer-in-charge before bulk procurement for

incorporation in the work.

18.2. PREPARATION OF SURFACE FOR FLOORING: Following procedure shall be

followed:

Page 127: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 127 of 307

• Sub grade concrete or RCC slab or side brick wall / or plastered surfaces on

which tiles are to be laid shall be cleaned, wetted and mopped as specified for

terrazzo tile flooring.

• Mortar and bedding: Cement mortar for bedding shall be prepared of mix 1:4 or

as specified in the schedule of items, to a consistent paste and shall conform to

the specification for materials, Preparations etc. as specified under cement

mortar. The amount of water added while preparing mortar shall be the minimum

necessary to give sufficient plasticity for laying. Care shall be taken in

Preparation of the mortar to ensure that there are no hard lumps that would

interfere with even bedding of the tiles. Before spreading the mortar bed the base

shall be cleaned off all dirt, scum or laitance and loose materials and well wetted

without forming any pools of water on the surface. The mortar of specified

proportion and thickness shall then be evenly and smoothly spread over the base

by use of screed battens to proper level or slope.

• Once the mix is prepared, no further water be added and the same shall be used

within one hour of adding water. Apply on an average 20 mm thick bedding of

mortar over an area of 1 sqm. at a time over surface of the area for laying tiles, in

proper level and allowed to harden sufficiently to offer a fairly good cushion for

the tiles to set..

18.3. LAYING OF TILES FOR FLOORING : The tiling work shall be done as per the

pattern shown in the drawing or as directed by the Engineer-in-Charge. As a general

practice laying of tiles shall be commenced from the centre of the area and advanced

towards the walls. Cut tiles, if any, shall be laid along wall with necessary border

pattern as shown / directed by the Engineer-in-Charge. Tiling work shall be completed

by pressing tiles firmly into place along the wall / floor. A white cement slurry to the

back of the tile to be applied to ensure proper and full bedding. The tiles shall be laid

on the bedding mortar when it is still plastic but has become sufficiently stiff to offer

a fairly firm cushion for the tiles. Tiles, which are fixed on the flooring adjoining the

wall, shall be so arranged that the surface on the round edge tiles shall correspond to

the skirting or dado. Press gently the tile with wooden mallet for even adherence at the

back of the tile. Do not use an iron hammer or some heavy material to press the tile.

The edges of the tiles shall be smeared with neat white cement slurry and fixed in this

grout one after the other, each tile being well pressed and gently tapped with a

wooden mallet till it is properly bedded and in level with the adjoining tiles. There

shall be no hollows in bed or joints. The joints shall be kept as close as possible and

in straight line. Unless otherwise specified, joint-less tiling shall be done butting the

tiles with each other. If joint is specified, the same shall not exceed 1.00 mm. in

width. The joint shall be grouted with white / matching colour cement slurry. After

fixing the tiles, finally in an even plane or slope, the flooring shall be covered with

wet sand and allowed undisturbed for 14 days.

18.4. FIXING TILES FOR DADO & SKIRTING / FACIA : : The fixing of tiles on wall

surfaces shall be done only after completing fixing of the tiles on the floor. Following

procedure shall be followed:

• The back of tiles shall be cleaned off and covered with layer of approved adhesive

like BAL-ENDURA or equivalent with proper trowelling as per manufacturers

recommendations.

Page 128: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 128 of 307

• The edges of the tiles shall be smeared with the adhesive and fixed on the wall

one after the other, each tile being well pressed and gently tapped with a wooden

mallet till it is properly fixed in level with the adjoining tiles. There shall be no

hollows on the back or in joints. Unless otherwise specified, joint-less tiling shall be

done butting the tiles with each other. If joint is specified, the same shall not

exceed 1.00 mm. in width. The joint shall be grouted with approved adhesive. The

joints shall be kept in straight line or as per the approved pattern.

• While fixing tiles in dado / skirting work, care shall be taken to break the joints

vertically. The top line shall be touched up neatly with the rest of the plaster

above. If doors, windows or other openings are located within the dado area, the

corners, sills, jambs etc. shall be provided with true right angles without any

specials. The contractor will not be entitled to any extra claims on this account

for cutting of tiles if required.

• The fixing shall be done from bottom of wall to upward without any hollows in the

bed of joints. Each tile shall be as close as possible to one adjoining. All tiles faces

shall be in one vertical plane.

18.5. GROUTING OF JOINTS IN FLOOR / SKIRTING / DADO: The joints, if specified,

shall be cleaned off and all dust and loose particles removed. Joints shall then be filled

with approved adhesive like BAL-ENDURA or equivalent grouts. After finishing the

grouting process, after 15 minute, wipe off excess grout with a damp sponge and polish

the tiles with a soft & dry cloth for a clean surface. The Finished work shall not sound

hollow when tapped with a wooden mallet.

18.6. CLEANING : As directed by the Engineer-in-Charge, the tiles shall be cleaned

by mild acid (However, Hydrofluoric acid and its derivatives should not be used).

After the tiles have been laid in a room or the days fixing work is completed, the

surplus cement grout / adhesive that may have come out of the joints shall be

cleaned off before it sets. The dado / skirting shall be thoroughly cleaned. In the case

of flooring, once the floor has set, the floor shall be carefully washed clean and dried.

When drying, the floor shall be covered with oil free dry sawdust. It shall be removed

only after completion of the construction work and just before the floor is used.

18.7. MODE OF MEASUREMENT AND RATE: Dado / flooring / skirting shall be

measured in sqm correct to two places of decimal. Length and breadth shall be

measured correct to 1 cm. between the exposed surfaces of skirting or dado. No

deductions shall be made nor extra paid for any opening of area upto 0.1 sqm. The

rate shall include all the cost of labour and materials involved.

18.8. CLEANING AGENTS FOR VITRIFIED TILES:: Vitrified tiles are resistant to all

chemicals (except hydrofluoric acid and its derivatives), hence commercially available

detergents and cleaning agents can also be used for regular maintenance. Any spills

and stains must be removed immediately. If left dry they may leave stains, which

may be difficult to remove completely.

CLEANING AGENTS FOR VITRIFIED TILES

STAINS CLEANING AGENT

Robin Blue Household detergent / Warm water

Marker ink Turpentine / Acetone / Trichloroethylene

Pen ink Acetone / Isopropyl alcohol

Page 129: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 129 of 307

Methylene blue Isopropyl alcohol / Acetone

Sauce Ammonia solution

Cement Turpentine / Acetone / Trichloroethylene /

Tea Hydrochloric acid / Bleaching powder

Coffee Sodium hydroxide / Potassium hydroxide

Beer Sodium hydroxide / Potassium hydroxide

Diesel Acetone / Petrol

Lab indicator Acetone / Isopropyl alcohol

Cement and grouting Hydrochloric acid

Pencil mark Benzene or Toluene or Xylene

Plaster of Paris (POP) Ammonium sulphate solution

Iodine (Tincture iodine) Sodium hydroxide / Potassium hydroxide

Hair dye Per chloric acid

Paan Lemon juice or citric acid

Marker pen Acetone

19. WOOD WORK IN FRAMES, SHUTTERS AND PANELLING :

19.1. WOOD WORK :

All timber mentioned in the item in schedule of quantities shall be from the heart of a

sound tree of nature growth entirely free from sap wood. It shall be uniform in

texture, straight in fiber and shall be well and properly seasoned. It will be free from

large, loose, dead or cluster knots, wedges, injuries, open shakes, borer holes, rot,

decay date, discoloration, soft or spongy spot, hollow pockets, pith or centre bore

and all other defects or any other damages of harmful nature which will affect the

strength, durability, appearance and its usefulness for the purpose for which it is

required. Only properly seasoned timber shall be used.

TEAK WOOD:

First Class Teak Wood: Individual hard and sound knot shall not be more than

25mm in diameter and aggregate area of all knots shall not exceed one percent of

the area of the piece. Sapwood shall not be allowed.

Second Class Teak Wood: Individual hard and sound knot shall not be more than

40 mm in diameter and aggregate area of all knots shall not exceed one and half

percent of the area of the piece. Wood shall be generally free from sapwood, but

traces of sapwood may be allowed.

HARD WOOD:

No individual hard and sound knot shall exceed 25mm in diameter and aggregate

area of all knots shall not exceed one percent of the area of the piece. Sapwood is

very perishable and should not be used.

The samples of species to be used shall be deposited by the contractor with the

Engineer-in-Charge before commencement of the work. The contractor shall produce

cash vouchers and certificate from standard kiln seasoning plant operator about the

timber section to be used on the work having been kiln seasoned by them, failing

which it would not be so accepted as kiln seasoned. Seasoning of timber shall be

judged from its moisture content as laid down in I.S. 287. The seasoning of timber

shall conform to I.S.1141 -1 993. Scantling of all types of timber shall be straight.

Page 130: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 130 of 307

Warped scantling shall not be used. Before use in works, the scantling shall be kept

in covered and well-ventilated place and shall be got approved.

The workmanship shall be of best quality. All wrought timber is to be sawn, planed,

drilled or otherwise machine worked to the correct sizes and shall be as indicated in

drawing or as specified. All joinery work shall fit truly and without wedging or filling.

Wood work in frames shall be wrought. All frame joints shall be put together with

white lead and pinned with hard wood pins securing with corrosion resistant star

shaped metal pins as approved by the Engineer-in-charge. If after fixing in position,

any shrinking or substandard materials or bad workmanship is detected, the

contractor shall, forthwith remove them and replace the same at his own cost, all as

directed by the Engineer-in-charge.

Individual members shall be of continuous length. The finished size and sections

shall be as per drawing or as specified. The heads and posts of frames shall be

through tennoned into the mortises to the full widths as shown in the drawing. All

necessary mortising, tennoning, grooving, matching, tonguing, housing rebate and

other necessary works for correct jointing shall be carried out, in the best

workmanship like manner. Joints not specifically indicated shall be recognised form

of approved joints for each position. The door frames shall be provided with 6 nos.

approved iron hold fasts, fabricated out of 30 x 3 mm. section, 300 mm. long (150

mm. long for cross partitions) M.S. flats with spliced end in case they are abutting

brick masonry works. These M.S. hold fasts shall be embedded in plain cement

concrete 1:3:6 block of size 300 x 75 mm. depth (100 x 75 mm. for cross partitions)

and for full width of brick masonry. For frames abutting concrete surfaces, 6 nos.,

100 mm. long coach screws with sunk heads minimum 10 mm. from face of frames,

shall be provided. Each screw shall be secured in concrete with lead wool

sufficiently stuffed in the pre-drilled holes to receive the screws. Top member of door

frames for opening exceeding 1.25 m. in width, shall be secured with a coach screw

100 mm. long in centre of member. All other T.W. scantlings shall be fixed to

structural openings with wood screws of suitable size & rawl plug so as to get in

effective hold of at least 40 mm. Suitable teak wood plugs shall be provided to

conceal the screw heads. The door frame shall rest on concrete sub- base in ground

floor or structural floor slab in case of upper floors, the extra length of sides of

frames thus embedded below finished floors shall not be measured for payment. All

parts of wood work resting on or set in masonry or concrete shall be well painted

with two coats of bituminous paint or solignum as directed by the Engineer-in-

charge, prior to installations. All nails, screws, hold fasts, plates, plugs, pins

required for wood work joinery and fixing work, shall be provided by the contractor,

at his own cost. All materials shall be approved by Engineer-in-charge before using

in works. Painting of door frames shall be carried out as per specifications for

painting for wood work.

All the embedded timber shall be given two coats of hot tar or solignum before

erection. This is incidental to the item and shall not be measured for payment.

19.2. TEAK WOOD PANELLED SHUTTERS :

Teak wood door shutter shall generally conform to standard laid in I.S. 1002 or the

latest revision for requirements of materials, construction workmanship and shall be

of specified thickness and of 1st class C.P. teak wood of approved design with stiles,

top, bottom and lock rail generally as per drawing. Wherever shown, each panel

shall be in a single width piece, but when two or more pieces have to be used and

Page 131: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 131 of 307

are permitted, all of them shall be of equal width and shall be jointed with a tongue

and groove joint with chamfered edges glued together and reinforced with metal

dowels.

19.3. TEAK WOOD GLAZED SHUTTERS :

The specifications for teak wood panelled shutter shall generally apply to glazed

shutters for frame, stiles etc.

The sash and beading required for glazing shall be of the best teak wood and shall

be fixed as per the design shown in relevant drawing. Any mouldings, carvings shown

shall be worked out from the teak wood member of bigger size.

19.4. GLAZING :

Glazing shall be generally with 4 mm. thick plain sheet glass/bajra glass unless

otherwise mentioned in the schedule of quantities. The detailed specifications for

glazing given hereafter shall be followed generally.

19.5. FLUSH DOOR SHUTTERS :

Solid core flush door shutters shall be of 5 ply construction and approved make

generally conforming to the I.S. specification 2202-1991 (specification for wooden

flush door shutter- solid core type). The finished thickness of the shutter shall be as

mentioned in the schedule of items.

19.6. FACE VENEERS :

Commercial face veneers used in flush door shutter shall conform to the

requirements laid down in I.S. 303 -1989 specifications for ply wood for general

purposes (revised) interior grade.

Decorative face veneers used in flush door shutters shall be of grade - I and shall

conform to the requirements of decorative veneer specified for grade - I decorative ply

wood in I.S. 1328 - 1982 specifications for veneered decorative ply wood interior

grade. Thickness of veneers shall not exceed 1 mm.

19.7. ADHESIVES :

Phenol formaldehyde synthetic resin (liquid type adhesives) conforming to I.S. 848

specifications for synthetic resins shall be used for bonding.

19.8. LIPPING :

The lipping shall be of best quality hard wood variety unless otherwise mentioned.

In case teak wood lipping is mentioned in the schedule of quantities, it shall

conform the specification for best quality teak wood. The internal lipping around the

shutter sides shall be one piece of size not less than 25 mm. wide and depth equal

to the thickness of core. In case of double leaf shutters, the meeting stiles shall have

lipping of not less than 35 mm. deep. Thickness of external lipping, wherever

specified in the item, shall not be more than 10mm and not less than 6mm.

Page 132: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 132 of 307

19.9. WORKMANSHIP AND FINISH :

All the faces of the door shutter shall be at right angles. The shutter shall be free from

twist and warp in its plane. Both faces of the door shutters shall be sanded to a

smooth even texture. The workmanship and finish of the face panels shall be in

conformity with those specified in I.S. 303 - 1989 specification for plywood for

general purpose (revised) for commercial type and I.S. 1659 - 1990 specification for

block boards for decorative type.

19.10. TESTS :

Tests shall be conducted as per mandatory test requirement, by the Department at

contractors cost and acceptance criteria shall be as per I.S. 2202. The flush door

shutters manufactured shall be inspected for its quality and workmanship and tested

at the factory before dispatching. All facilities shall be extended for such inspection

and testing. The sampling and testing shall be as per the IS requirements and all

costs towards test including sample for destructive tests shall be borne by the

contractor.

19.11. TOLERANCE :

Tolerance on nominal width and height shall be (+/-) 3 mm. Tolerance on nominal

thickness shall be (+/-) 1.5mm. The thickness of the individual shutter shall be

uniform throughout.

19.12. MISCELLANEOUS :

Wherever mentioned in the Schedule of quantities, vision panels, venetians, plastic

laminates, push plates etc. shall be provided in the flush doors.

The vision panels shall be of size mentioned in the drawing and shall be provided with

teak wood lipping around the glass. The glass shall be 4 mm. thick or as specified of

best quality (M/s. Triveni, I.A.G., Shree Vallabh or equivalent approved), free from

defects.

Teak wood venetians or louvers shall generally conform to relevant specifications of

timber. Necessary grooves and rebate in frames shall be provided as per drawing.

Formica or approved equivalent plastic laminate of required design, required shade

and colour shall be provided and fixed on flush door to the required size on any side

of the shutter as shown in drawing. It shall be fixed with Fevicol or any other

approved adhesive. Fixing shall be done in such a way that there shall not be any

air gap, warpage or undulations on the surface. Finished surface of formica shall be

cleaned with wax polish.

The shutters shall be painted on commercial facing side with two coats of

synthetic/flat oil paint of approved shade and make over an approved coat of primer.

The decorative veneer side of the shutter shall be wax or french polished with two or

more coats so as to render a satisfactory surface.

The flush doors shall be single leaf or double leaf type as mentioned in the schedule

of quantities. In case of double leaf shutters, the meeting of the stiles shall be rebated

20 mm. and shall be either splayed or square type and the T.W. lipping around the

Page 133: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 133 of 307

meeting shall not be less than 35 mm. deep. The meeting stiles shall be in single

piece.

Sufficient care shall be taken to prevent any damage and loss of shape during

handling, transporting, stacking, fixing etc. The door shutters shall be handled with

utmost care to prevent any surface damage, warping etc.

19.13. MODE OF MEASUREMENT :

The work covered under the respective items in schedule and the above

specifications shall be measured as follows :

The cubic contents for wood work shall be measured for the finished size, limiting to

those shown in the drawings or ordered by the Engineer-in-charge. The cross

sectional dimensions shall be measured equivalent to nearest enclosing rectangle

(least rectangle/square) for wrought and planed sizes. The cubical content shall be

worked out correct upto three places of decimals of a cubic metre. The frames

embedded below finished floor shall not be measured.

The square meter areas for shutters shall be measured for the exposed surfaces of

shutter between frames from inside or outside whichever is more. The linear

dimensions shall be measured upto two places of decimals of a metre. The area for

payment shall be worked out correct upto two places of decimals of a square metre.

The rate for shutters shall include:

i. Cost of supply assembly and erecting in position.

ii. Cost of polishing, painting, supplying wood preservative, screws, nails, hold fasts

etc.

iii. Cost of labour for making adjustments in frames, if required, shutters and also

for fixing required fittings and fixtures.

iv. In case of flush doors, the rate for individual item mentioned in the schedule of

quantities shall include cost of shutters, labour for provision of glass for vision

panel, plastic laminate sheet push plate, teak wood louvers etc., transporting

charges and labour for fixing of fixtures and fastenings except fixing of door

closers and painting and polishing as specified.

* * *

20. PRESSED STEEL DOOR FRAME :

20.1. Scope of work : This specification lays down the requirements regarding

material, dimensions and construction of steel door frames for internal and external

use.

20.2. Material : Steel door frames shall be manufactured from commercial mild

steel sheets of 1.25 mm. thickness, conforming to I.S. 513 (Spn. for cold rolled

carbon steel sheets) or I.S. 1079 (Spn. for hot rolled carbon steel sheet and strip).

Sheets shall be galvanised for 240 g / Sqm. Zinc deposit on its surface including both

sides as per IS 277 – 2003.

Page 134: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 134 of 307

20.3. Standard sizes, Tolerances and Designations :

Sizes : The overall sizes and types of door frames shall be as shown in drawings. 5

mm. clearance on all the four sides shall be allowed for the purpose of fitting the

frame into modular openings.

Tolerances : The sizes indicated in drawings for door frames shall not vary by more

than (+/-) 2 mm.

20.4. Profile : Steel door frames with or without fanlight shall be made in the

profile as per I.S. 4351 (latest version) as per drawings. Any of the three profiles

mentioned in I.S. 4351 or sizes specified in the schedule of work may be supplied to

suit doors of either hand, opening inwards or outwards, as specified or directed.

20.5. Construction : Each door frame shall consist of hinge jamb, lock jamb, head

and, if required, angle threshold. The whole shall be rigidly fixed together by

mechanical means. Where no angle threshold is required, temporary base tie shall

be screwed to the feet of frames in order to form a rigid unit.

20.6. Base ties and angle thresholds : Base ties shall be of pressed mild steel 1.25

mm. thick adjustable to suit floor thickness of 25, 30, 35 or 40 mm. and removable,

or alternatively, thresholds of mild steel angle of section 50 x 25 mm., minimum,

shall be provided for external door frames.

20.7. Fittings: Fixing Lugs: There shall be three adjustable lugs with split end tail

to each jamb without fanlight, and four for jamb with fanlight. The head of the fixing

lug shall be of 120 mm. long and shall be made from flat steel strip 25 mm. wide and

not less than 1 .60 mm. thick.

The tail of the lugs for use with door frame profile shall be 200 mm. long and shall be

made of steel strip not less than 40 mm. wide and not less than 1.0 mm. thick.

Mortar Guards: Mortar guards specified in the tender shall be provided. These shall

be welded to the frame at the head of the frame for double shutter doors to make

provision for bolts.

Note: The term ‘double-shutter doors’ indicates ‘Pairs of side-hung doors’, that is, two

side-hung doors mounted in one frame thus forming a two-leaf door rebated together

at the lock strike.

Lock Strike Plate: There shall be an adjustable lock-strike plate of steel, complete

with mortar guard, to make provision for locks or latches complying with the relevant

Indian Standards. Lock-strike plates may be of brass when so specified in the tender;

otherwise they shall be of galvanised mild steel and fixed at 75 cm. to 90 cm. from

finished floor level.

Shock Absorbers: For side-hung door, there shall not be less than three buffers of

rubber or other suitable material inserted in holes in the rebate and one shall be

located on the centre line of the lock-strike plate and the other two at least 45 cm.

above and below the centre line of the lock-strike plate. For double-shutter doors,

there shall be two buffers of rubber or similar suitable material inserted in holes in

the rebate in the lock jamb only at the head and spaced 15 cm. at either side of the

centre line of the door.

Page 135: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 135 of 307

20.8. Mode of Measurements : The length shall be measured in running metres

correct to a cm. out to out of the frames. Threshold angle/base tie will not be

measured for payment, cost of which shall be included in pressed steel frame.

* * *

21. FACTORY MADE PARTICLES BOARD PANELLED DOOR SHUTTERS.

21.1. GENERAL : Factory made particle board panelled door shutters shall be made

of kiln seasoned and chemically treated timber as specified generally with stiles and

top rails of 100 mm. in width, bottom rail and lock rails of 150/1 75 mm. width and

panels made of 12 mm. thick both side commercial veneered teak wood particle board

or as specified in schedule of quantities, bonded with phenol formaldehyde synthetic

resin adhesive and generally conforming to I.S. 3091.

Factory made shutters, as specified shall be obtained from factories to be approved by

the Engineer-in-Charge and shall conform to I.S. 2202 (Part-I). The contractor shall

inform well in advance to the Engineer-in-Charge the name and address of the

factory where from the contractor intends to get the shutters manufactured. The

contractor will place order for manufacture of shutters only after written approval of

the Engineer-in-Charge in this regard is given. The contractor is bound to abide by

the decision of the Engineer-in-Charge and recommend the name of another factory

from the approved list, in case the factory already proposed by the contractor is not

found competent to manufacture quality shutters.

The contractor will also arrange stage-wise inspection of the shutters at factory of the

Engineer-in-Charge or his authorised representative. Contractor will have no claim if

the shutters brought at site are rejected by Engineer-in-Charge in part or in full lot

due to bad workmanship/quality. Such shutters will not be measured and paid and

the contractor shall remove the same from the site of the work within seven days

after the written instructions in this regard are issued by Engineer-in-Charge or his

authorised representative.

21.2. TIMBER :

The timber to be used in door shutters shall generally conform to relevant I.S.

specifications for materials, moisture content, seasoning, preservation and

workmanship.

All timber shall be from the heart of a sound tree of mature growth, entirely free

from sapwood. It shall be uniform in texture, straight in fiber and shall be well and

properly seasoned. It shall be free from large, loose, dead or cluster knots, soft or

spongy spots, hollow pockets, pith or centre heart, waves, injurious open shakes,

borer holes, rot, decay date, discoloration and all other defects or any other damages

of harmful nature which will affect the strength, durability, appearance of its

usefulness for the purpose for which it is required.

21.3. PARTICLE BOARD PANELS :

It shall be of well seasoned teak timber particles of uniform thickness, bonded with

liquid phenol formaldehyde synthetic resin adhesive of the hot press type. The

particle board shall be either flat plate on press or extrusion type as approved by the

Department conforming to the latest I.S. specifications. Panels shall be embedded

into frames to a minimum of 12 mm. with 1.5 mm. air gaps.

Page 136: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 136 of 307

21.4. SEASONING AND TREATMENT :

All timber to be used for sills and rails shall be kiln seasoned to the required

standards as per I.S. 1141 -1 973.

21.5. ADHESIVE :

The adhesive for bonding of stiles, rails etc. shall be of highly water resistant type

synthetic resins (liquid type) adhesive conforming to relevant specifications for

synthetic resins.

21.6. WORKMANSHIP AND FINISH :

The workmanship shall be of best quality. All members shall be in continues length.

All the faces of the door shutter shall be secured and in true planes. All wrought

timber is to be sawn, planed, drilled or otherwise moulded work to the correct size

and shapes indicated in drawing or as specified. All joinery work shall fit truly and

without wedging or filling. All the faces of the shutters shall be sanded to smooth even

texture. The finished sizes and sections shall be as per drawing or as specified. The

shutters shall be got approved from the Engineer-in-Charge at factory site before

carting the same to the site of work. The shutters damaged during the cartage and if

any sub-standard materials or bad workmanship is detected, the contractor, shall

forthwith remove them and replace the same at his own cost, all as directed by the

Engineer-in-charge.

21.7. 33.7 PRIMER COAT :

All factory made panel door shutters with seasoned teak wood/hard wood frame shall

be painted with approved Primer coat as per I.S. specifications 1003 (Part-I).

21.8. TESTS :

Tests shall be conducted as per mandatory test requirement by the Department at

the contractors cost. All shutters shall have manufacturer’s trade marks.

21.9. TOLERANCES :

Tolerances on nominal width and height shall be (+/-) 3 mm. Tolerance on nominal

thickness shall be (+/-) 1 .5 mm. The thickness of the shutter frame shall be uniform

throughout with a variation not exceeding 1 mm., when measured at two points.

21.10. SAMPLES :

Sample of door shutter shall be got approved before

manufacturing on large scale.

21.11. FIXING:

The shutter shall be fixed to teak wood or rolled M.S./EZ door frame (teak

wood/rolled steel in door frames paid under relevant items) with necessary fittings

as per drawing (cost of fittings and fixtures paid under relevant items). The shutter

shall be painted as specified. The shutters of specified thickness and of required

sizes as fixed in position as shown in drawing/schedule of quantities shall be

measured for payment. The length and width of

Page 137: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 137 of 307

the shutter fixed in position shall be measured correct upto three places of decimal

of a metre and the areas so worked out shall be corrected upto two places of decimal

of a square metre. The area of the shutter shall be measured for the exposed

surfaces of shutter between frames from inside or outside whichever is more.

21.12. RATE TO INCLUDE :

The rate quoted by the contractor shall be :

i) or supplying and fixing in position of finished shutters with necessary fittings

and fixtures as per drawings (excluding cost of fittings and fixtures which shall

be paid under relevant items).

ii) painting/polishing as specified and as directed by the Engineer-in-charge.

* * * *

22 . FITTINGS AND FIXTURES:

22.1. SCOPE OF WORK :

The work covered under these specifications consist of supplying different types of

fittings and fixtures required for doors, windows, ventilators etc. The supply shall be

in accordance with the specification, drawings / approved samples. Samples of

various fittings and fixtures proposed to be incorporated in the work shall be

submitted by the contractor for approval of the Engineer-in-charge before order for

bulk supply is placed.

22.2. GENERAL :

All fittings and fixtures shall conform to relevant IS code and made of brass,

anodized aluminium, iron oxidised (M.S.) or as specified. These shall be well made

reasonably smooth and free from sharp edges, corners, flaws and other defects.

Screw holes shall be counter sunk to suit the heads of the specified screws. All hinges

pins shall be of steel for brass hinges and aluminium alloy NR-6 or steel pins for

aluminium hinges with nylon washers or as specified. All riveted heads pertaining to

hinge pins shall be well formed. Screws supplied for fittings shall be of the same

metal and finish as the fittings. However brass cadmium plated/chromium plated

screws shall be supplied with aluminium fittings. Samples of each fixture/ fitting

shall be furnished by the contractor for approval of the Engineer-in-Charge. Order

for procurement of fittings and fixtures in bulk shall be placed only after approval by

the Engineer-in-Charge.

The fittings and fixtures to be incorporated in the work shall be strictly according to

the approved sample. Fittings shall be fixed in proper position as shown in the

drawing and as directed by the Engineer-in-Charge. These shall be truly vertical or

horizontal as the case may be. Screws shall be driven home with a screwdriver and

not hammered in. Recess shall be cut to the exact size and depth for the counter

sinking of hinges. The fittings and fixtures shall be fixed in a workman like manner

and any damages done either to fittings and fixtures or to the shutter frames etc.

should be rectified by the contractor at his own cost.

Page 138: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 138 of 307

Fittings shall be of Mild steel, Stainless steel, aluminium, brass or as specified. The

fittings shall be well made, smooth, and free from sharp edges and corners, flaws

and other defects.

Mild steel fittings shall be bright satin finish black stone aanodized or copper

oxidised (black finish), nickel chromium plated or as specified.

Brass fittings shall be finished bright satin finish or nickel chromium plated or

copper oxidised or as specified.

Aluminium fittings shall be aanodized to natural matt finish or dyed anodic

coating less than grade AC 10 of IS: 1868

Stainless steel fittings shall be non-magnetic, rust & moisture proof, strong &

sturdy. Pin of hinges shall also be of stainless steel.

22.3. BUTT HINGES : Brass and aluminium hinges shall be manufactured from the

extruded sections and shall be free from cracks and other defects. M.S. butt hinges

shall be cranked and manufactured from M.S. sheets. All butt hinges shall conform

to latest I.S. specifications butt hinges shall generally condorm to releval I.S viz IS

1341 (M.S.) IS : 205 (Cast brass & aluminium, IS : 362 (Parliament hinges); IS : 453

sprig higes, IS : 3818 (Piano higes) etc. The size of butt hinges shall be taken as the

length of the hinge. Width of the hinge shall be measured from the centre line of

hinge pin to end of flange.

22.4. PARLIAMENTARY HINGES : These shall be manufactured from extruded

section for brass and aluminium and from M.S. sheets for iron oxidised and shall be

free from cracks and other defects. The size of the parliamentary hinges shall be

taken as the width between open flanges, while the depth shall be as specified.

22.5. PIANO HINGES :

These shall be generally conformed to I.S. 3818 and shall be made of either brass

oxidised, aluminium aanodized, iron oxidised (M.S.) or as specified. Piano hinges

shall be fixed in the entire length of the cupboard shutters in a single piece. No joints

shall be allowed.

22.6. TOWER BOLTS : These shall generally conform to IS 204 (Part II & I). They

shall be well made and shall be free from defects.

The tower bolts shall be of the following types :

i. MS semi barrel tower bolt with ms sheet pressed barrel and G.I. bolt or with ms

barrel and MS Sheet bolt.

ii. Oxidised brass barrel tower bolt with brass sheet barrel and rolled or drawn

brass bolt.

iii. Anodised aluminium tower bolt with barrel and bolt of extruded sections of

aluminium alloy.

In case of M.S. tower bolt plates and straps after assembly shall be firmly anodize or

spot welded properly.

Page 139: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 139 of 307

The knobs of brass tower bolts shall be cast and the bolt fixed into the knob firmly

as per I.S. specifications. The tower bolt shall be finished to correct shape and

pattern so as to have a smooth action. Wherever specified, aluminium barrel tower

bolts shall be manufactured from extruded sections of barrel & bolts.

Knobs shall be properly screwed to the bolt and riveted at the back. The size of the

tower bolt shall be taken as the length of barrel without top socket.

22.7. Door Letch :

This shall be of MS, cast brass or as specified shall have smooth sliding action. MS

Latch shall be copper oxidised (black finish) or as specified. Brass Latch shall be

finished bright, CP or oxidised or as specified

22.8. ALDROPS :

These shall be oxidised brass or anodized aluminium, iron oxidised or as specified

and shall be capable of smooth sliding action and shall be as per relevant I.S. Brass

sliding door bolt (aldrop) shall be made from rolled brass generally confirming to IS :

2681. M.S. sliding door bolt shall generally conform to I.S.281. The hasp shall be of

cast brass and screwed to the bolt in a workman like manner. Alternatively the hasp

and the bolt may be in one piece. Bolts shall be finished to shape and threaded with

worth standard and provided with round brass washers and nuts of square or

hexagonal shape. All components shall be smooth and polished. The leading

dimensions of aldrop shall be as the length of the bolt and specified diameter.

22.9. DOOR HANDLES- BOW/PLATE HANDLES :

These should generally conform to IS : 208. Unless otherwise specified door handles

shall be of 100 mm size & windows handles of 75 mm size. These shall be of cast

brass of specified size, shape and pattern as approved by the Engineer-in-charge. All

edges and corners shall be finished smooth and correct to shape and dimensions.

Brass handles shall be finished bright, chromium plated or oxidised as specified.

Anodised aluminium or iron oxidised (M.S.) handles shall be of specified size, shape

and pattern. The size of the handle is taken as the inside grip of the handle. In case

of iron oxidised handles, the same shall be manufactured from M.S. sheet pressed

into oval section as per I.S.

22.10. MORTISE LOCK LATCH

This should generally conform to I.S. 2209. Handles shall conform to IS 4992.

Mortise lock with latches and a pair of level handles shall be 6 levers, with zinc alloy

pressure die cast/brass or as specified body of approved quality, and shall be right

or left handed as specified. The pair of handles shall be either brass chromium

plated or anodized aluminium of approved shape and pattern or as specified. It

shall be of the best Indian make of approved quality. The size of the lock shall be

determined by its length. The lock for single leaf door shall have plain face and that

for double leaf door a rebated face. Level handles with springs shall be mounted on

plates and shall be of approved quality, anodized aluminium or as specified.

Page 140: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 140 of 307

22.11. HYDRAULIC DOOR

CLOSER

This shall be generally conform to IS : 3564. Hydraulic door closer shall be of

approved quality and make. The operation of the Hydraulic door closer shall be very

smooth.

This should be of H.D.-66 for external/main doors and elegant - 63 for all internal

doors. The overall height should not be more than 170 mm. for H.D.-66 and 160 mm.

for elegant - 63, base shall be 110 x 60 mm. for H.D.-66 and 100 x 55 mm. for elegant

- 63 weighing not less than 4.5 kg. for H.D.-66 and 4 Kg. for elegant - 63. Speed of the

Hydraulic door closer shall be adjustable and latch closing also shall be adjustable

type. Suspension and lubrication of door closer shall be in perfect line and level.

22.12. The contractor shall provide for all the incidentals required for fixing these

fixtures and fittings such as cadmium plated screws etc. Fittings and fixtures shall be

fixed securely in a workman like manner all as directed by the Engineer-in-charge.

Any of the fixtures damaged during the fixing shall be removed and new one fixed in

their place and the surface of joinery made good where affected, at his own expense.

Mortise plates shall be used over holes where the bolts enter in the wood work. Metal

sockets shall be provided to all bolts where the shoot enter brick, stone, concrete etc.

The incidental Fixtures like mortise plates, metal sockets, screws etc. shall not be

paid for separately.

22.13. MORTICE NIGHT LATCH : This is a mortice lock having a single spring bolt

withdrawn from the outside by using the key and from inside by turning the knob

and with an arrangement whereby the lock can be prevented from being opened by

its key from outside while the night latch is used from inside the room.

This should generally conform to IS: 3847. It shall be cast or sheet brass, cast or

sheet aluminium alloy or mild steel as specified and of approved make. These shall

be bright finished or copper oxidised (black) finish as specified. Normal size of the

latch shall be denoted by the length of the face over the body in milimetres.

22.14. FLOOR DOOS STOPPER: The floor door stopper shall conform to IS: 1823.

This shall be made of cast brass of overall size as specified and shall have rubber

cushion. The shape and pattern of stopper shall be approved by the Engineer-in-

Charge. It shall be of brass finished bright, chromium plated or oxidised or as

specified. The size of door stopper shall be determined by the length of its plate. The

body of the door stopper shall be cast in one piece. All parts of the door stopper shall

be of good workmanship and finish and free from surface and casting defects.

Aluminium stopper shall have anodic coating of not less than grade AC-10 of IS

1868.

22.15. MODE OF MEASUREMENT AND RATE : Unless otherwise specified, all

fittings including all necessary accessories shall be measured in numbers and the

rate shall include the cost of all materials including taxes, octroi, excise duty, if any,

loading, unloading, transporting, cost of screws, bolts and other accessories and fixing

the same complete.

* * * *

Page 141: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 141 of 307

23. GLASS AND GLAZING :

23.1. SCOPE OF WORK :

The work covered by this specification include furnishing and fixing the glass panes

to teak wood or steel doors and windows, strictly in accordance with these

specifications and drawings.

23.2. MATERIALS :

i) Glass : The glass shall be special selected / selected ordinary quantity glass of

M/s. Shree Vallabh / Triveni / I.A.G. or of equivalent manufacture, as specified.

Toughened float glass of approved manufacturer shall be used wherever specified.

The glass shall be free from bubbles, flaws specks, waves, air holes, distortion,

scratches, cracks or other defects. The glasses in bulk quantities shall be brought

to site in Makers original packings and Makers guarantee shall be produced if

called for by the Engineer-in-charge. The glass shall be of required thickness as

mentioned in the items of schedule of quantities and/or drawing or as directed

by the Engineer-in-charge. The contractor shall submit the sample of the glass

which he proposes to use on the work and only such approved quality of glass

shall be used in the works. The glass brought to site shall be protected against

damages. Wherever frosted (obscure) glass is mentioned in the item of schedule of

quantities and / or shown in drawings, the glass shall be of sand blown pattern

and shall also be got approved from the Engineer-in-charge.

ii) Beading : The beading shall be of teak wood of superior quality timber in case of

teak wood doors and windows and/or required sizes mentioned in the items of

schedule of quantities and/or shown in drawing. In case of steel / Aluminium

doors and windows, the beading shall be anodised aluminium beading of channel

section as per sizes mentioned in the item and / or shown in the drawing. The

junction of the beadings shall be mitre jointed.

iii) Dimensions, Thickness and weight of the glass: Unless otherwise specified,

these shall be as per table given below. All panes shall have properly squared

corner and straight edges

Normal

thickness

Range of

thickness

Weight in kg /

sqm

3.0 mm 2.8 to 3.2 mm 07.5

4.0 mm 3.8 to 4.2 mm 10.0

4.8 mm 4.6 to 5.1 mm 11.9

5.5 mm 5.2 to 5.8 mm 13.5

6.3 mm 6.0 to 6.6 15.5

23.3. WORKMANSHIP :

The glass shall be cut to the required sizes of panels where it is to be fitted, and it

shall be so cut that it fits properly in the frames without rattling. Pre-measurement

of each panel prior to the cutting of glass is essential.

The beading shall then be fixed to glass panes and screwed at close intervals not

more than 10 cm. from each corner and the intermediate not more than 20 cm. apart.

Page 142: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 142 of 307

When the glass panes are fixed with aluminium beading having mitred joints, epoxy

resin or silicon sealant shall be applied covering the area in contact between the

glass panes and sash bars and also between glass panes and the beading. In case of

louvers, all the exposed edges of the glass shall be ground properly.

All glass panes shall be fixed within the aluminium framing by use of CP brass or SS

screws and the joints sealed with epoxy resin or silicon sealant to make the unit

completely waterproof. Glazing or caulking compound around the perimeter of glass

shall not be permitted. Fixed glass panes shall be supported by setting blocks. There

shall be no whistling or rattling.

23.4. GENERAL :

After the inspection is over and permitted by the Engineer-in-charge, glass panes

shall be cleaned off any labels, paints smears and spots and shall be washed from

both the sides and all glazing left clear, perfect and free from rattling. The contractor

shall provide all the scaffolding, tools and plants for fixing the glass panes at his

own cost. In case of steel windows, any hardware if fixed in position, shall be

removed temporarily before fixing the glass panes and which shall be re-fixed back

in position, all at the contractors cost.

23.5. MODE OF MEASUREMENT :

The rate for teak wood door/window shutters and/or steel door/window shall

normally cover the cost of glass and glazing also, unless otherwise mentioned. In case

the glazing is carried out as a separate item, the measurement shall be taken out to

cut size of teak wood/steel door/window frames forming the sides of glass panes and

area calculated to two places of decimal of a square meter.

The rate shall include the cost of supplying and fixing the glass panes, all materials,

labour, transport, scaffolding etc.

23.6 Glazing with patch fitting :

SS 316 brush finished patch fittings of approved make

6 + 6 mm thick sandwiched PVB glued, laminated glass or toughened glass as per

design and details.

Glass partition shall be complete with all stainless steel cappings and clamping or

fixing devices, resilient pads and seParators, as well as closures, gaskets and

sealants as required for a complete installation in strict accordance with the

manufacturers’ specifications.

All exposed metal fittings shall be manufactured from type 316 stainless steel, finish

to match approved samples.

All openings/ doors shall be provided with operating hardware, floor spring, patch

fittings, locks and as per details and requirements.

Mode of measurement :

The rate for teak wood door / window shutters and / or steel door / patch fittings

shall normally cover the cost of glass and glazing also, unless otherwise mentioned

and area calculated to two places of decimal of a square meter.

Page 143: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 143 of 307

The rate shall include the cost of supplying and fixing the glass panes, all materials,

labour, transport, scaffolding , hardware etc.

Guarantee:

All materials and workmanship in above work shall be guaranteed for a period of one

year (unless otherwise specified) from the date of handing over. Unqualified

performance guarantee for smooth operation of the windows, doors, wall spans and

precautionary measures against leakages etc. shall be furnished by the contractor on

stamped paper. If so specified, in schedule of quantities. Any defect found during the

guarantee period shall be replaced / made good to the original conditions / positions

entirely at the cost of the contractor.

* * *

24. STEEL DOORS, WINDOWS AND VENTILATORS:

SCOPE OF WORK :

The work covered under these specifications consist of supplying steel windows and

doors and ventilators, fixing, glazing etc. complete in strict accordance with the

specifications and relevant detailed/shop drawings.

24.1. GENERAL :

The contractor shall submit 6 copies of shop drawing covering all types of work

under this specification before manufacture. The drawing shall show all dimensions,

details of construction, installation, relating to adjoining and related work etc.

24.2. MATERIAL :

Shutters, frames etc. as dimensioned in the drawing shall be fabricated from I.S.

standard sections rolled by M/s. Man Industries or other approved equivalent. No

glazing bars shall be provided unless otherwise shown in drawing. Glazing used will

be clear sheet glass of special selected quality manufactured by M/s. Shree Vallabh

or other approved equivalent, unless otherwise specified. Steel sections shall be free

from rolling or other defects. They shall be easily welded and punched and shall be

cold straightened and shall conforming to latest I.S. 1038 - 1983. The anticorrosive

shop coat of paint shall be given before the materials are brought to site.

24.3. COUPLING BARS FOR COMPOSITE DOORS,WINDOWS AND VENTILATORS

:

All doors window, ventilators units shall be so constructed that those if required

may be coupled together by means of the standard mullion and weathered transom

bars and coupling pieces.

All steel hinges shall be projected steel hinges with non magnetic stainless steel pins

and washers to permit complete ease in cleaning the glass and shall be welded or

riveted to the frame.

24.4. FABRICATION :

The frames shall be square and flat and shall be constructed of sections cut to

length, mitred and welded at corners. All welding shall be electrical flash butt

welding excepting for the welding of steel sheets for the shutters.

Page 144: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 144 of 307

Sections shall be formed true to details with clean straight, sharply defined profiles

and free from defects that may impair its durability. All works shall be accurately

formed to the required dimensions, line and level. All joints shall be continuously

reinforced, fitted and continuously welded at the edges. Surface along joints shall be

ground to attain a smooth level surface even and flush with adjoining surfaces. All

frames shall be properly reinforced for the attachment of hardware. The heads of

frames for openings wider than 1.2 m. shall be reinforced to prevent sagging or

deflection when installed.

24.5. INSTALLATION:

The doors, windows and ventilators brought to site shall be stacked up site down on

wooden runner under cover. Fixing shall be done as per latest Indian Standard

Specifications. The size of the prepared openings shall be checked first and these

should be cleaned off all obstructions.

The doors/windows/ventilators shall not be forced into the walls but shall fixed into

prepared openings in workmen like manner.

All joints between masonry/concrete and the metal shall be fully filled with

approved mastic filler/putty in order to ensure water tightness. The joints shall be

neatly pointed with matching cement and excess material shall be removed.

All brick jambs and sill holes shall be cut 50 mm. square and 100 mm. deep for

fixing hold fasts. All concrete jambs and lintels, holes shall also be carefully drilled

and if reinforcing steel is encountered, the length of the hold fasts may be decreased

and existing surface made good to the original condition.

Any hard ware if fixed in position shall be removed before fixing the frames in the

structural openings and moving parts shall be secured with wire or string during

erection and while the building work is being completed to prevent damage to the

part. Hardware shall be fixed as late as possible preferably just before the final coat

of paint is applied. It shall be fitted in workmanlike manner so that it may not be

marked and mutilated by hammers and screws and pins are not marked and

mutilated by hammers and screwdrivers. It shall be tested for correct operations to

the satisfaction of the Engineer-in-charge.

24.6. DETAILS OF COMPONENT PARTS :

24.6.1. Doors : Door shutters shall be hung on projecting hinges of 67 mm size

and shall be fitted with mortise lock and two brass or bronze lever handles. In

case of double leaf doors, the first closing leaf of double leaf doors shall also be

provided with brass or bronze tower bolts concealed in the section at top and

bottom. These shall be so constructed as not to work loose or drop by their

own weight and necessary lugs, fittings, screws etc. shall be provided and

fitted properly at site.

24.6.2. Windows : Window shutters shall be hung on projecting hinges. One

leaf of the hinges shall be welded into a slot in the outer frame and the other

leaf of the hinges riveted to the opening shutters. Hinges may be of the friction

type in which case the window shall not be fitted with peg stay. In case of non-

friction projecting hinges, a brass or bronze three holes peg stays 300 mm.

long with pegs and brackets, welded or riveted to the frame shall also be

provided. Handles shall be of brass or bronze and shall be of brass or bronze,

Page 145: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 145 of 307

and shall be mounted on a mild steel handle plate welded to the shutter in

such a way that it should be fixed after the shutter is glazed. The handles

shall have a two point nose which shall engage with brass, bronze or

aluminium alloy as specified, striking plate, on the fixed frame so that it can

hold the shutters in a slightly openable as well in a fast position.

24.6.3. VENTILATORS : a) Top hung ventilators : These shall be fixed with

plain hinges, riveted to the fixed frames or welded to it after cutting a slot in it.

A peg stay 300 mm. long of brass or bronze with three holes, as in case of

windows shall be provided.

The locking bracket shall either be fitted to the fixed frame or to the

ventilators.

b) Centre Hung Ventilators : These shall be hung on two pairs of brass of

lead/tin/bronze cup pivots, riveted to the inner and outer frame of the

ventilators to permit these to swing through an angle of approximately 85 deg.

The opening portion of the ventilators shall be so balanced that it remains

open at any desired angle under normal weather condition.

A bronze or brass spring catch shall be provided at the top centre of the

ventilator. A brass cord pully wheel in a mild steel or malleable iron brackets,

shall be fitted with screws or welded at the sill and a cord eye shall be fixed to

inner frame of ventilators to facilitate opening of ventilators.

24.6.4. Composite Units : Composite units consist of a combination of two or

more units of doors, windows, ventilators etc. as the case may be. The different

units shall be coupled by using coupling sections. The coupling sections shall

be made from M.S. sheet 3.15 mm. in thickness and 56 mm. wide as per I.S.

1038-1957 Para 5.2 and these shall be fixed with bolts and nuts.

Wherever the ventilators, windows and doors shall have coupling section,

mastic cement shall be applied between the junctions to make the joints

watertight.

To calculate height or width of composite units, add 2.5 cm. for each mullion

or transom coupling bar for each unit.

24.7. FINISHING : All steel surfaces shall be thoroughly cleaned of rust, scale and

dirt by pickling and marking. A shop priming coat of superior quality red oxide or

equivalent shall then be given before despatch. Alternatively, where so specified, the

steel surfaces shall be treated for rust proofing by the hot dip zinc spray or electro

galvanising process, having a coating of not less than 60 microns thickness or as

specified. Zinc spray articles shall be given one coat of priming coat of superior

quality red oxide or equivalent.

Final finishing with two coats of synthetic enamel/flat oil paint of approved make and

shade shall be given after the doors ,windows and ventilators are erected/fixed in

final position. The rate shall be inclusive of final finishing coats including the priming

coat.

In case of galvanised doors, windows and sashes, their surfaces shall be treated with

copper acetate solution or other approved mordant solution to ensure proper

Page 146: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 146 of 307

adherence of paint, unless the galvanised surface has weathered adequately at the

time of final painting.

Non-ferrous parts and working parts such as handle stays, catches, handle pins,

hinge pins etc. shall not be painted.

24.8. GLASS AND GLAZING : Specifications for glazing given in this book under

chapter Glass and Glazing, shall also be applicable for steel doors / windows /

ventilators.

24.9. MODE OF MEASUREMENT : The mode of measurements for steel doors,

windows and ventilators for complete item of supply and fixing in position shall be

on area basis calculated in sqm. correct to two places of decimal. The height and

width of members shall be measured outer to outer edge of the members correct to 1

mm.

The rate for steel door, window and ventilator shall include cost of all fittings,

materials, hold fasts, glazing, painting, labour etc.

* * *

25. M. S. GRILLS / RAILINGS :

25.1. GENERAL :

The contractor shall submit 6 copies of shop drawings covering all types of work

under this specifications before manufacture. The drawing shall show all dimensions,

details of construction, installation relating to the adjoining work.

25.2. MATERIALS :

All structural steel shall conform to I.S. 226 sections for grills and shall be free from

loose mill scales, rusts, pittings or any other defects affecting its strength and

durability.

25.3. FABRICATION :

The grill shall be fabricated to the design and pattern shown in the drawings. All

joints shall be made in best workman like manner with slotting and welding as

required to the specified size and shape. The edge of the M.S. flats shall be suitably

mitred before welding to get the desired shape. The joints shall be filled to remove

excess stay after welding. Screws, nuts, washers, bolts, rivets and any other

miscellaneous fastenings, devices shall be of steel and shall be provided by the

contractor.

Manufactured M.S. grills then be fixed in between the posts, balusters, M.S. frame

work etc. to correct alignment. Any undulations, bends etc. found shall be rectified

by the contractor at his own cost. The complete assembly of grill/railing so fixed

shall be firm and there shall not be any lateral movements.

25.4. SAMPLES :

Samples of grill and railings shall be submitted for approval of the Engineer-in-

Charge and to be got approved before taking up for mass fabrication.

Page 147: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 147 of 307

25.5. INSTALLATION :

The approved grills shall be fixed in position where specified and shown in drawings

including in masonry walls, teakwood frames, hand railings etc. Any damages to

walls, frames etc. caused during fixing the grills shall be made good by grouting with

cement mortar/packing/repairing properly at the contractors cost.

25.6. PAINTING :

Painting shall be done as per the specifications specified under painting.

25.7. MODE OF MEASUREMENT :

Actual area of m.s. grill manufactured and fixed in position shall only be measured in

square metre for payment. All measurements shall be taken to two places of decimal

of a metre and area shall be calculated to second place of decimals of a square metre.

The rate is to include the cost of all materials, labour, transporting, fabricating,

installing, scaffolding if necessary, grouting etc. complete.

25.8. FINISHING/PAINTING/POLISHING FOR RAILING :

Teak wood hand rail shall be polished with wax polish/ french polish/solignum with

two or more coats over one coat of wood primer or painted with two coats of

synthetic enamel paint/flat oil paint of approved make and shade over one coat of

approved primer. M.S. grills, balusters etc. also to be painted as per specifications

specified under painting/polishing.

25.9. MODE OF MEASUREMENTS (HAND RAILS) :

Hand railing shall be measured for payment in running metre. The length shall be

measured along the top centre line of the hand rail and shall be measured between

ends of balusters, newels, posts as the case may be upto two places of decimals of a

metre. Rate shall include fabrication, leaving suitable pockets, grouting the same,

providing and fixing suitable teak wood plugs, fixing, all labour, materials, transport,

painting/polishing, finishing and scaffolding if necessary.

* * *

Page 148: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 148 of 307

26. ALUMINIUM DOORS, WALL SPANS, GLAZING ETC.

26.1. SCOPE OF WORK :

The scope of work in the present tender item includes fabrication, supply and

installation of white anodised matt finished aluminium entrance doors, glazing etc.

strictly in accordance with these specifications and relevant detailed approved shop

drawings.

26.2. GENERAL :

The material, fabrication and hardware shall conform to the IS 1948. The contractor

shall submit 6 copies of shops drawings covering all type/details of work as

generally shown in Architectural drawing and envisaged under these specifications

before manufacture. The drawing shall show all dimensions, details of construction,

installation of fixtures and relation to adjoining and related works. No fabrication

work shall be undertaken prior to obtaining approval of the shop drawings from the

Engineer-in-Charge. The tenderer shall intimate at the time of tendering, the type of

sections he proposes to use on the works.

26.3. MATERIALS :

Aluminium alloy for extruded sections for the above work shall correspond to I.S.

733 & 737 specifications or any further revision thereof(extruded sections shall

conform to I.S. Designation HE 9- WP. Hollow sections shall conform to I.S.

Designation HV9-WP) and shall be anodised before incorporating in the work. Anodic

coating shall conform to IS 1868. The frame work, stiles, mullions, beadings,

transoms and handles etc. shall be of aluminium anodised sections as shown in

detailed approved drawings. All aluminium sections shall be of INDAL or other

equivalent make as per drawing. The contractors can also propose nearest

alternative sections they manufacture/posses without changing the elevation,

structural stability & functional requirement. Department reserves the right to

accept the alternative section or otherwise. The sections shall be structurally

suitable to withstand all the loads, the members have to sustain. Counter sunk

screws, nuts, bolts, washers, rivets and other miscellaneous fastenings devices shall

be of approved brass cadmium plated or stainless as specified in the approved

drawing. Each door leaf shall be prepared to receive glazed panel of required

thickness. Glazing shall be done with neoprene dry set glazing gasket (of best quality

and approved make) with snap-in-bevelled white anodised matt finish aluminium

metal glazing stops inside and outside. All doors shall have off- set pivots, double

action (1800 minimum swing) floor springs with oil check boxes of approved

manufacture. All doors shall have 4 lever concealed brass body mortise lock without

handles as per manufacturers design, with concealed flush C.P. brass tower bolts

provided at suitable locations. All doors shall have push plates of design shown in

the approved drawing as described in the schedule of quantities. All entrances shall

be without thresholds. All aluminium surfaces in contact with masonry or concrete

shall be given a thick coat of bitumastic paint. After fabrication, aluminium sections

shall be protected from construction hazards that may damage their appearance or

finish. All exposed surfaces of aluminium door entrance shall be protected by

masking tape during transshipment and erection. All sections and hardware shall

have anodic film and cover a minimum thickness of 0.015 mm.

Page 149: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 149 of 307

26.4. FABRICATION :

The frames shall be manufactured square and flat, the corners of the frame being

fabricated to true right angle. All the fixed, sliding and opening frames shall be

constructed of sections which have been cut to length, mitred, welded and

mechanically fixed at the corners. Where hollow sections are used with welded joints,

argon-arc welding or flash butt welding shall be employed (Gas welding or brazing

not to be done). In case welded joints are used, anodising shall be done after

fabrication as a whole. All welding shall be on unexposed sides in order to prevent

pitting/discolouration of other surface imperfections after fixing etc. Necessary

allowance shall be made while manufacturing the aluminium door entrances, wall

spans and glazing for receiving plaster. No field fabrication of frames is permitted. A

thick layer of clear transparent lacquer based on methacrylates or cellulose butyrate

shall be applied on the finished sections of the aluminium work by the contractor to

protect the surfaces from wet cement, lime, dirts, dust etc. during the construction

activities. The size for door, window or ventilator frames shall not vary by more than

(+/-) 1.5 mm.

26.5. HARDWARE :

All cut outs, recesses, mortising or milling and operations required for fixing the

hardware shall be accurately made reinforced with packing plate as required to

ensure adequate strength of the connection. All the hardware accessories shall be of

best approved type and of anodised finish same as for the frames and other sections.

Each lock shall be supplied with two stainless steel keys and each key shall be with

number stamped thereon according to the number on doors so installed. All hardware

shall be free from defects, which may affect the appearance and serviceability. All

hardware shall be fixed after obtaining the prior approval of the Engineer-in-Charge.

Approved samples of hardware shall be kept in the custody of the Engineer-in-Charge.

Working and moving parts of locksets shall be accurately fitted to smooth, close

bearings and shall be free from rattle. The floor springs shall be of heavy-duty type

and should allow door operation smoothly and shall conform to IS 6315. The

contractor shall furnish a guarantee for all finishing and quality of hardware covered

under this section and which shall remain free from defects of any kind, either

materials and/or workmanship for a period of one year (unless otherwise specified)

from the date of completion/handing over of work. The contractor shall repair or

replace any and all defective work and damage caused, at any time or times during

that period within 3 days from the written notice. This shall be done without any

extra cost to the Department and to the complete satisfaction of the Engineer-in-

Charge. In case the same are not replaced immediately after the receipt of the notice

to do so, the Department shall do so at the cost of contractors. The cost as certified

by the Engineer-in-Charge shall be final and binding on the contractors.

26.6. FIXING :

Fixing and glazing of doors, windows and ventilators shall be conforming to IS 1081,

unless otherwise specified. The frames shall be accurately fixed in the flooring / brick

masonry or R.C.C. works. The fixing of the frame shall be done with cadmium plated

brass counter sunk screws driven on to the teak wood rough ground, or fixed to the

wall with hold fasts as directed by the Engineer-in-charge, and as shown in

approved drawings. All aluminium works shall be fixed in position as per relevant

Page 150: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 150 of 307

Indian Standard Specifications and code of practice for fixing and glazing of

aluminium work. Joints between metal and masonry shall be fully caulked with

mastic / polysulphide compound in order to ensure water tight joints as directed by

the Engineer-in-Charge. Joints shall be neatly painted with matching cement and

excess materials shall be removed. Fixing of aluminium door entrances, hardware

etc. shall be done in best workmanship like manner true to line, level, plane, plumb

etc. and all as directed by the Engineer-in-Charge. Breaking of floor for providing

floor springs and restoration of the floor finishes to the original specification and

finishes and minor additions and alterations to the openings shall be deemed to

have been included in the quoted rates.

26.7. GLASS AND GLAZING :

26.7.1. Glass : The glass shall be of selected quality/special selected quality of

M/s. Triveni / Shree Vallabh, I.A.G. or equivalent manufacture, as specified

under the chapter GLASS AND GLAZING.

26.7.2. Glazing Clips/Beading : The glazing clips/beading where specified in

drawings for aluminium/steel doors and windows shall be anodised aluminium

beading of channel section or as specified & as per sizes mentioned in the item

and/or shown in the drawing.

The junction of the beadings shall be mitre jointed. Holes for glazing clips shall

be drilled prior to fabrication and shall not be done at any later stage.

26.7.3. The glass shall be cut to the required sizes of panels where it is to be

fitted and it shall be so cut that it fits properly in the frames without rattling.

Premeasurement of each panel prior to the cutting of glass is essential.

The clips/beading shall then be fixed to glass panes and screwed at close

intervals not more than 10 cm. from each corner and the intermediate not

more than 20 cm. apart. When glass panes are fixed with wooden beadings

having mitred joints or aluminium beading, a thin layer of glaziers putty shall

be applied covering the area in contact between the glass and sash-bars and

beadings. In case of louvers all the exposed edges of the glass shall be ground

properly.

26.7.4. Glazing : The glass panes shall be fixed to the frame as mentioned

above with approved Neoprene dry set glazing gasket (of best quality and

approved make) with snap-in-bevelled white anodised matt finished aluminium

metal glazing stops inside and outside. In the fixed side and transom light, the

thickness of glass or panel shall be accommodated by the screw down glazing

stops. The glass panels shall be fixed firmly and truly Parallel to the plane of

frames. All damages or breakages during glazing shall be made good at the

contractors own cost till the work is properly taken over by the Engineer-in-

Charge. All wall spans glazing and entrances, fixed glazing etc. shall be tested

for water tightness. Any leakage found during testing, it is the responsibility of

the contractor to rectify the same without any extra claim.

26.7.5. General : After the inspection is over and permitted by the Engineer-in-

Charge, the glass panes shall be cleaned off any labels, paint smears and

spots and shall be washed from both the side and all glazing left clear, perfect

and free from rattling. The contractor shall provide all the scaffolding, tools

Page 151: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 151 of 307

and plants for fixing the glass panes at his own cost. In case of

aluminium/steel doors/windows any hardware if fixed in position shall be

removed temporarily before fixing the glass panes and which shall be re-fixed

back in position all at the contractors cost.

26.8. MODE OF MEASUREMENT :

a) Aluminium work: The measurement of aluminium sections shall be taken only

after the frames along with shutters are fixed in its final finished position in

line, level and plumb. Length of each extruded section used for fabrication shall

be measured outer to outer of cut length correct upto 1 mm

b) The weight of material used shall be calculated on the basis of actual weight of

extruded sections used for fabrication and shall be compared with the weights

given in the catalogue of the approved manufacturer subject to the condition that

the variation in actual weight should not exceed (+ / -) 10% than the approved

catalogue weights. The payment shall be made for the actual weight of the

extruded section after anodising. The final weight shall be calculated in kgs

upto two places of decimal.

c) Glazing work: The length and width of opening for glazing inserts shall be

measured correct to a centimetre and area for payment shall be calculated in

square metre nearest to 0.01 sqm.

26.9. RATE :

Unless otherwise specified, Fittings and fixtures such as window handles, hinges,

peg stays, friction stays, concealed window lock, cleat angles, stiffener plates etc.

shall not be measured for payment and rate quoted shall include cost of all such

fittings, accessories and hardware. However, door handles, mortise lock, dead lock,

door closer, floor springs, concealed door tower bolts shall be measured separately

as specified in the item and paid for.

The rate quoted shall include all taxes, duties etc. tools, plants, labour involved in

all the operations described above, fixing in final position including submitting shop

drawings etc. and all incidentals to the job involved.

26.10. TESTING :

Aluminium sections shall be tested for its unit weight, anodic coating etc. as per

relevant IS codes.

26.11. GUARANTEE :

All materials used in above work shall be guaranteed for one year (unless otherwise

specified) from the date of handing over the work. Any defect found in the guarantee

period shall be replaced/repaired to original condition/position entirely at the

contractors cost.

* * *

Page 152: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 152 of 307

27. ALUMINIUM WINDOWS, VENTILATORS, COMPOSITE UNIT ETC. :

27.1. SCOPE OF WORK :

The scope of work in the tender item includes fabrication, supply and installation of

white anodised matt finished aluminium windows, ventilators, composite units,

glazing etc. strictly in accordance with these specifications and relevant detailed

approved shop drawings.

27.2. GENERAL :

The material, fabrication and hardware shall conform to IS 1948 & 1949. The

contractor shall submit six copies of shop drawings covering all types/details of work

as generally shown in Architectural drawing and envisaged under these

specifications before manufacture. The drawing shall show all dimensions, details of

construction, installation, fixtures and relation to adjoining and related works. No

fabrication work shall be under- taken prior to the approval of the shop drgs. from the

Engineer-in-Charge. The tenderer shall intimate at the time of tendering, the types of

sections he proposes to use on the works.

27.3. MATERIALS :

The aluminium alloy used in the manufacture for extruded window section shall

correspond to I.S. 733 (or any further revision thereof). Extruded sections shall

conform to I.S. designation HE9-WP and Hollow sections shall conform to I.S.

Designation HV9-WP. The frame work, stiles, mullions, beadings, transoms, hinges,

pegstays, handles etc. shall be of aluminium anodised sections as shown in the

detailed drawings. All sections and hardware shall have minimum anodic film

thickness of 0.015 mm. All sections shall be of INDAL or other equivalent make as

per drwg. The contractor can also propose nearest alternative sections they

manufacture/posses without changing the elevations and functional requirements.

Department reserves the right to accept the alternative sections or otherwise. The

sections shall be structurally suitable to withstand all the load, the members have

to sustain. Countersunk screws, nuts, bolts, washers, rivets and other

miscellaneous fastening devices shall be of approved cadmium plated or stainless

steel as specified in the approved drawings.

27.4. FABRICATION :

The frames shall be manufactured square and flat. The corners of the frames shall

be fabricated to true right angles. All the fixed, sliding, openable frames shall be

constructed from sections which have been cut to length, mitred and mechanically

jointed or welded at the corners. Where hollow sections are used with welded joints,

argon arc welding or flash butt welding shall be employed (Gas welding or brazing not

to be done). Sub-dividing bars of units shall be tennoned and riveted into the frames.

In case welded joints are used, all welding shall be on unexposed sides in order to

prevent pitting, discolouration and other surface imperfections after finishing. The

dimensions shown in the drawing are overall heights and widths to the outside of

frames of aluminium windows. The side hung shutters shall have projected friction

type hinges of aluminium alloy. Concealed projected hinges having structural

stability and of good quality will also be considered only after the inspection of the

sample submitted by the tenderer. The necessary pegstays, handles, window

fasteners etc. shall be of aluminium. The handle shall be mounted on a handle plate

Page 153: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 153 of 307

riveted to the opening frame. The pegstays shall be 300 mm. long or as required

complete with peg and locking bracket and shall have holes for keeping the shutter

open in three different positions. No field fabrication of frames is permitted. The

complete fabricated assembly shall be anodised in approved satin finish with

minimum film thickness of 0.0 15 mm. for the entire surface. A thick layer of clear

transparent lacquer based on methacrylate or cellulose butyrate shall be applied on

the finished sections of the aluminium windows etc. by the supplier to protect the

surfaces from wet cement, lime, dirt, dust etc. during the installation. This lacquer

coating shall be removed after installation is complete, if approved by the Engineer-

in-Charge and all sections of the windows shall be protected by P.V.C. film covering.

27.5. HARDWARE :

All cut outs, recesses, mortising or milling and operations required for fixing the

hardware shall be accurately made, reinforced with packing plate as required to

ensure adequate strength of the connection. All the hardware, accessories shall be of

best approved type and of anodised finish same as for the frame and other sections.

All hardware shall be free from defects which may affect the appearance and

serviceability. All hardware shall be fixed after obtaining the prior approval of the

Engineer-in-Charge. Approved samples of hardware shall be kept in the custody of

Engineer-in-Charge.

27.6. FIXING :

The window frames shall be accurately fixed in the brick masonry or R.C.C. work.

The fixing of the frame shall be done with cadmium plated brass counter sunk

screws driven on the teak wood rough grounds if required or fixed to the wall with

holdfasts. All aluminium windows shall be fixed in position as per I.S. 1081-1960 (or

any revision thereof): Code of practice for fixing and glazing of aluminium windows.

All joints between metal and masonry/rough ground wooden frame shall be fully

caulked with mastic or polysulphide compound in order to ensure water tight joints.

Joints shall be neatly painted with matching cement and excess materials shall be

removed. Hardware shall be fixed in workman like manner all as directed by the

Engineer-in-Charge.

27.7. SAMPLES :

The samples of different windows shall be submitted to the Engineer-in-charge, for

approval.

27.8. GLAZING :

The glazing shall be of Indian make plain sheet/frosted figured glass of special

selected quality and size as mentioned in item description and drawings and shall be

of M/S. Triveni/Shree Vallabh/I.A.G. or other approved equivalent. The

specifications specified here-in-before shall hold good as far as applicable.

27.9. MODE OF MEASUREMENT :

Similar to as described under chapter “Aluminium Windows, Ventilators, Composite

Unit Etc.”

Page 154: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 154 of 307

27.10. GUARANTEE :

All materials and workmanship in above work shall be guaranteed for a period of

one year (unless otherwise specified) from the date of handing over the work.

Unqualified performance guarantee for smooth operation of the windows, doors, wall

spans and precautionary measures against leakages etc. shall be furnished by the

contractor on stamped paper, if so specified in schedule of quantities. Any defect

found during the guarantee period shall be replaced/made good to the original

conditions/positions entirely at the cost of the contractor.

27.11. TESTING :

All windows shall be tested for water tightness. Any leakage found during testing

shall be rectified by the contractor without any extra charge.

* * *

28. STRUCTURAL GLAZING

28.1. Specification for Materials to be used In Structural Glazing

This shall be same as described for Aluminium Curtain Wall System.

28.2. Specification for Materials to be used In Structural Glazing

Aluminium extruded sections shall be from approved and reputed / renowned

manufacturer. In absence of specific extruded section, sections available conforming

to BIS specification, manufactured by approved reputed companies, shall be used in

the works.

28.3. General Specification and Tolerances for Aluminium Extrusions Dimensions

and weights of the sections shall be as per approved drawings.

Circumscribing Circle Diameter (CCD)

i) The product range shall be broadly as categorized below;

a) For solids upto 190mm.

b) For hollows upto 135mm

ii) Sections with higher CCD, if required, shall be produced from reputed /

renowned manufacturer as approved by the Engineer-in-Charge.

Manufacturing Tolerance: Dimensional extrusions shall be normally as per IS /

BSS. Special tolerances shall be mutually agreed upon.

Tolerance on cut length:

i) The standard cut length is 3.66M the tolerance on cut length shall be as follows:

Length Upto 6 metres Over 6 metres

Tolerance + 5 mm + 7 mm

Page 155: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 155 of 307

ii) Sections shall also be acceptable in random lengths between 1500 to 5000mm

depending upon actual requirements. Tolerance in Weights: A tolerance of ±

10% shall be acceptable on Sectional weight per metre

28.4. Glazing:

Glazing work shall be as specified in the description of the item and / or as described

under chapter : Glass & Glazing.

28.5. Scope of Work

This shall be same as described in the Para “Scope of work” for Aluminium Curtain

Wall System.

28.6. Execution of Work

i. This shall be similar to the Specifications for Aluminium Curtain Wall System as

far as applicable.

Notes on Aluminium Curtain Wall System and structural glazing

1) Though both the systems i.e. curtain wall system and structural glazing are very much similar, still the type and shape of aluminium extruded sections, that are used in this case are totally different.

2) Another noted difference between the two systems is that in elevation the structural glazing looks as total glass surface without any beading visible externally, whereas in case of curtain wall system the cover plate used on the surface is clearly visible in elevation.

3) A large quantity of sealant has to be used for the execution of the work of structural glazing with the result the cost per sqm. of structural glazing works out to be much on higher side.

4) There is also a slight difference in the actual fabrication of the two systems though quantity of materials required for execution in both the cases is same except the quantity of sealant.

28.7. Representative of the

Contractor

These shall be similar to

the

28.8. Performance Guarantee Specifications for Aluminium

Curtain

Wall System as far as

applicable

28.9. Measurements

28.10. Rate

* * *

Page 156: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 156 of 307

29. CEMENT PLASTERING FOR WALLS & CEILINGS AND SAND FACE / ROUGH CAST

PLASTERS :

29.1. SCOPE OF WORK :

The work covered under these specifications consists of supplying all materials and

rendering all types of plaster/pointing finishes strictly in accordance with these

specifications, applicable drawings etc. For all finishing works mentioned above, only

blended cement shall be a used.

29.2. GENERAL :

Blended cement, sand and water required for the work shall conform to

specifications laid down herein before under chapter 4 i.e. Plain and reinforced

cement concrete, except that sand for finishing coat shall be fine sand conforming to

I.S. 1542. The plastering works shall generally conform to I.S. 1661 (Pt. III) (Code of

practice for cement and cement plaster finish on walls and ceilings). All general

precautions as specified in I.S. 1661 (Pt. III) clause-8, shall be taken and

Preparation of the back ground shall be done as laid down in I.S. 1661 clause 12

and I.S. 2402 shall be generally followed for rough cast and sand faced plaster work.

Scaffolding required for facility of working shall be provided by the contractor at his

own cost. This may be double or single according to the requirement and shall be

approved by the Engineer-in-Charge. Stage scaffolding shall be erected when ceiling

plastering is done. The contractor shall be responsible for accidents, if any, take

place. The contractor shall co-operate with the other agencies also. Whenever

electrical contractor/agency has to fix up switch boxes in walls, necessary Thiyyas,

Tapanish or Dhadas shall be arranged to be given in advance of actual plastering

process at these locations so that the boxes are fixed properly in line with finished

plaster surface. All finishing in and around these boxes as also around the conduit

boxes in ceiling shall be done by plastering contractor without any extra cost to the

Department. The decision of the Engineer-in-Charge in this regard shall be final and

binding on the contractor.

29.3. PREPARATION OF SURFACE :

The surface to be plastered shall first be thoroughly cleaned of all muck and cleaned

down. All joints shall be raked out in case of brick work / stone masonry and closely

hacked in case of concrete, under the relevant masonry / concrete items. The

surface to be plastered shall be well wetted for a minimum period of 6 hours before

commencing the work. The mortar for all plaster work shall be blended cement

mortar of mix as specified in the schedule of quantities.

After erection of scaffolding and before commencement of plastering work, top most

junctions/joints/sides with beam/column shall be thoroughly packed with blended

cement mortar to prevent cracks.

Before commencement of plastering operation, the contractor shall ensure that all

the service pipes, electrical conduits, boxes, switch boxes etc. have been installed in

position by other agencies and the plastering surface is duly approved by the

Engineer-in-Charge. In order to enable other service contractors to fix the electrical

conduits, conduit boxes, EDBs, pipes, outlets etc. in proper level and line with

reference to the finished surface of the plaster, Thiyyas and Tapanis i.e. finished

plaster patches shall be given by the main civil contractor on walls, ceiling at

Page 157: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 157 of 307

regular intervals well in advance of his plaster work at no extra cost to the

Department. The entire work of Preparation of surface before plastering shall thus

be co-ordinated by the main civil contractor with all other agencies working at site.

Just before actual plastering work is taken up in hand, all the ceilings and walls etc.

shall be marked with Tapanis or Thiyyas indicating the thickness of plaster required

and which shall be in true line, level and plumb. The contractor shall get these

marks approved by the Engineer-in-Charge before starting the plastering work. The

contractor shall also be responsible to render the final surface true to line, level and

plumb etc.

All building operations like construction of walls, concreting etc. shall have been

completed before plastering is taken up. The plastering operation should be taken

up only after the service pipes etc. that are to be embedded in the wall or ceiling are

completed and suitably protected against erosion by other agencies and Okayed by

the Engineer-in-charge. Damage if caused to any of the existing fittings, fixtures,

including doors and windows etc. during the plastering operation shall be made

good by the contractor at his own cost.

If the surface which is to be plastered either internally or externally is out of plumb

and not in line and level and if the plastering to be done is more than specified

thickness to bring the plastered surface to perfect line and levels, in such specific

cases, chicken wire mesh is to be provided by the contractor at his own cost and the

plaster should be done to required line and level with no extra cost whatsoever.

The finished plastered surface shall be free from cracks, fissures, crevices, hair

cracks, blisterings, local swellings and flakings. The finished surface shall be true to

line, level, plumb & plain and durable. The adhesion of the mortar with the

background surface is of prime importance as this affects durability of plaster.

Preparation of surface which has to take plastering is of great importance. Before

starting the plastering work the surface should be got approved by the Engineer-in-

charge.

In order to avoid the formation of deep and side cracks and for dispersion of cracks

at the junctions between concrete surfaces and brick masonry work as also between

junction of windows/door frames and brick masonry works, cautionary measures

such as fastening and lapping of chicken mesh over the junction areas should be

carried out over which the plastering work has to be taken up as required by the

Engineer-in-charge.

The minute gap between window/door frames with sills and jambs should be filled

up/caulked by plaster of paris/epoxy putty/silicon sealants, Rubber based sealants

(brand name TECHMAT/TECHCOAT) by caulking guns or by approved methods as

instructed/approved by Engineer-in-Charge.

29.4. GROOVES :

The grooves shall be of required dimensions. The same shall be made to turn

wherever necessary. The finish, inside, shall be of the same finish as that of the

plaster. The lines of the grooves shall be well defined and rounded. The grooves are

to be provided in plastering in internal and external surfaces and shall be paid extra

in the rates given in schedule of quantities.

Page 158: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 158 of 307

29.5. MIX PROPORTIONS :

The mortar for plastering shall be of proportion as specified in the item schedule.

The mixes specified in the schedule are volumetric.

29.6. MIXING :

Cement and fine aggregates shall be mixed dry in the required proportions to obtain

a uniform colour. Water shall then be added to get the required consistency for the

plaster.

Mixing shall be done mechanically. However, manual mixing will be allowed only in

exceptional circumstances at the discretion of the Engineer-in-Charge. Manual

mixing, where adopted, shall be carried out on a clean water tight platform. After

water is added during mixing, the mix shall be held back and forth for 10 to 15

minutes.

In machine mixing, the mixer shall run at least five minutes after placing all the

ingredients in the drum. Only so much quantity of mortar which can be used within

half an hour after the addition of water shall be prepared at a time. Any mortar for

plaster which is set or partially set shall be rejected & shall be removed forthwith

from the site.

6 / 12 / 15 MM. PLASTER :

The plaster shall be laid with somewhat more than 12 mm. thickness and pressed and

levelled with wooden ruler to a finished thickness of 12 mm. Straight edges shall be

freely used to ensure a perfectly even surface. All exposed angles and junctions of

walls, doors, windows, beams, slabs etc. shall be carefully finished so as to furnish a

neat and even surface.

Note: For 6mm plaster, approved bonding agent shall be used as per manufacturer’s

specifications, wherever specified in the Schedule of Items.

20 MM PLASTER :

The proportions of sand and cement shall be as specified and shall cover all

irregularities, undulations, depressions due to chasing etc. in the surface to be

plastered. The mortar shall be applied slightly more than 20 mm. thick and pressed

and levelled with wooden ruler or straight edge to finished thickness of 20 mm.

Straight edges shall be freely used to ensure a perfectly even surface. The finished

surface shall be true and even and present uniform texture throughout and all

joining marks shall be eliminated. All corners, edges and angles shall be made

perfectly to line, plane and plumb. All exposed angles and junctions of walls, doors,

windows, beams, slabs etc. shall be carefully finished so as to furnish a neat and

even surface.

Plastering items amongst all other things as described in various items also include:

i) Preparation of surfaces to receive the plaster, providing cement plaster of the

specified average thickness and proportions with specified number of coats.

ii) All labour, materials, scaffolding, use of tools and equipment to complete the

plastering work as per specifications.

Page 159: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 159 of 307

iii) Curing for 10 days.

iv) Cleaning the surface of doors, windows, floors or any other surfaces where

plastering might have splashed.

v) Finishing the portion of plaster left above the terrazzo, plain cement tiles, ironite

or any type of skirting work to be finished rounded or as directed by the

Engineer-in-Charge, in a separate operation after laying of floor tiles skirting.

29.7. (A) NEERU FINISH :

Wherever specified, the surface rendered shall be finished smooth with good quality

lime neeru class ‘C’ conforming to I.S. 712-1956. The lime shall be tested in an

approved testing laboratory for the chemical analysis of the lime and test certificate

submitted regarding suitability of lime for plaster work. The cost of testing shall be

borne by the contractor. Neeru shall be prepared at site out of best quality pure fat

lime slaked at site with fresh water and slaked in accordance with the relevant I.S.

code for slaking of lime. The slaked and sifted lime shall be reduced to a fine paste by

grinding 150 turns in a mortar mill. Sufficient quantity, which can be used within

10 days only shall be prepared at a time. Chopped hessian or jute fibre in the

required quantity may also be added to neeru and properly ground to pure paste as

per directions of the Engineer-in-Charge.

An entire unobstructed area shall be plastered in one operation. Neeru shall be

applied to the prepared and partially set but somewhat plastic surface with steel

trowel to a thickness slightlty exceeding 1.5 mm. (1/16") and rubbed down to 1.5

mm. It shall be polished to perfectly smooth and even finish working from top to

bottom for at least 3 days. All corners shall be truly brought to desired lines and

levels in the base plaster along and the thickness of neeru shall not exceed 1.5 mm.,

at these locations. Moistening shall be commenced as soon as the plaster has

hardened sufficiently and is not susceptable to injury. The surfaces shall be kept

sprinkled with water for 7 days to prevent excessive evaporation. On the sunny or

wind-ward side of the building in hot dry weather, matting or gunny bags may be

hung over on the outside of the plaster and kept them wet. If blow holes are

observed in neeru plaster at any time during the contract period and during the

defect liability period, the contractor will have to rectify the defective neeru plaster

work including redoing of the white washing/colour washing/distempering work etc.

as the case may be, entirely at his own cost.

It shall be the contractors responsibility to ensure that cracks do not develop during

the execution or subsequently during the defect liability period and the cracks if any

observed shall be rectified including finishing, white washing/painting as specified,

without any extra cost to the Department, to the entire satisfaction of the Engineer-

in-charge.

33. (C) PLASTER OF PARIS (POP – CaSO4 , 1 / 2H2O) FINISH :

Wherever specified, the wall / ceiling surfaces shall be finished smooth with

approved quality Plaster of Paris (POP). POP shall be mixed in water for dehydration

at site. Sufficient quantity, which can be used within half an hour only, shall be

prepared at a time.

Page 160: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 160 of 307

POP shall be applied immediately after the under coat of cement plaster has set. An

entire unobstructed area shall be finished in one operation. POP shall be applied on

top of finished coat of plaster which should be levelled without any scratch/key

marks to the prepared and partially set. It shall be ensured that the surface to be

covered is free of loose particles, dust, dirt, grease, oil and paint. It shall be applied

with steel trowel to a thickness slightly exceeding 2 mm and rubbed down to 2 mm. It

shall be polished to perfectly silk smooth and even finish working from top to bottom.

All corners shall be truly brought to desired lines and levels in the base plaster along

and the thickness of POP shall not exceed 2 mm, at these locations.

If blow holes / cracks are observed in POP plaster at any time during the contract

period and during the defects liability period, the contractor will have to rectify the

same including redoing painting to match with the adjacent surface etc., all at his

own cost to the entire satisfaction of the Engineer-in-charge.

34. SAND FACED CEMENT PLASTER:

34.1 GENERAL : Materials and Preparation of surfaces and scaffolding etc. for sand

faced plaster wherever applicable shall conform to specification laid down here-

in-before under section cement plastering and the following specifications are

also to be complied with:

PREPARATION OF SURFACE : The surface to be plastered shall first be

thoroughly cleaned down. All joints shall be raked out in case of brick work /

stone masonry and closely hacked and wire brushed in case of concrete, under

the relevant masonry / concrete items. The surface to be plastered shall be

well wetted for a minimum period of 6 hours before commencing the work. The

mortar for all plaster work shall be cement sand mortar of mix as specified in

the schedule of quantities.

Double scaffoldings required for facility of construction shall be provided by the

contractor at his own expenses wherever directed by the Engineer-in-Charge.

Scaffolding shall be erected with pipes or ballies or bamboos of adequate

strength so as to be safe for all the dead, live and impact loads likely to

sustain by it during construction operations. The contractor shall take all

measures to ensure the safety of the work and workmen. Any instruction of

the Engineer-in-Charge in this respect shall also be complied with. The

contractor shall be entirely responsible for any damage to Government

property or injury to persons, resulting from faulty scaffolding, defective

ladders and materials or otherwise arising out of his default in this respect.

Proper scaffolding shall be provided to allow easy approach for workmen and

supervisory staff to every part of the work. Ballies, bamboos etc. for

scaffolding shall not be tied to the windows, doors, mulliions, ventilators etc.

Any damage done to the windows, doors etc. shall be made good by the

contractor to the original conditions at his own cost. For better safety, steel

pipe scaffolding is preferred.

WORKMANSHIP : The surface to be plastered shall first be dubbed out with

cement mortar to cover all irregularities and faces upto proudest part. The

dubbing coat which shall be of proportion as specified in schedule and a 12

mm. thick (1/2") layer shall then be applied/scored and keys shall be formed

on the surface by thoroughly combing it with heavy horizontal lines about 12

mm. (1/2") apart and about 3 mm. (1/8") deep when mortar has just set.

Page 161: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 161 of 307

The cement mortar for sand faced plaster shall have washed and approved

sand with slightly larger proportions of coarse materials, but not exceeding 3

mm. The proportion of cement to sand shall be as specified in the schedule.

The water is gradually added to make the mixture homogenous. The thickness

of finishing coat excluding key shall be 8mm. (about 5/16"). After application

the surface should be finished with a wooden float lined with cork closely

pricked on with a wet sponge tapped gently to bring sand particles into

prominence.

The chajjas and any other horizontal portions shall be cleaned and set mortar

that might have been fallen at the time of plastering at higher elevation, before

plastering work is taken up. Junction of wall and chajja shall be rounded off

simultaneously as directed by the Engineer-in-Charge.

* * *

35. CEMENT POINTING :

35.1. PREPARATION OF SURFACE :

The joints shall be raked out properly under masonry item. Dust and loose mortar

shall be brushed out. Efflorescence if any, shall also be removed by brushing and

scrapping. The surface shall be thoroughly washed with water, cleaned and kept wet

before pointing is commenced.

35.2. MORTAR :

Mortar mix for pointing shall be as described in the schedule of quantities.

Specifications for cement, sand and water shall be as described herein before for

concrete works.

35.3. APPLICATION OF MORTAR &

FINISHING :

The mortar shall be pressed into the raked out joints with a pointing trowel, either

flush, sunk, ruled or raised according to type of pointing specified in the schedule of

quantities. The mortar shall not spread over the face of brick work or stone work,

corners, edges of the masonry but restricted to the width of joints only.

The super-fluous mortar shall then the struck off and the surface of the masonry

shall be cleaned off completely. The finish shall be such that the pointing is to the

exact size and shape stipulated and the edges are straight, neat and clean. The

pointing lines shall be straight, regular and uniform. No false joints shall be allowed.

35.4. CURING :

The pointing shall be kept wet for at least seven days. During this period it shall be

suitably protected from all damages.

35.5. TYPES :

(a) Raised and Cut Pointing : Raised and cut pointing shall project from the wall

facing with its edges cut Parallel so as to have a uniformly raised band about 6

mm. raised and width 10 mm. or more as directed.

Page 162: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 162 of 307

(b) Flush Pointing : The mortar pressed into the joints shall be finished off flush

and level with the edges of bricks, tiles or stones so as to give a smooth

appearance. The edges shall be neatly trimmed with a trowel and straight edges.

(c) Ruled Pointing : The joints shall be initially formed as for flush pointing and

then while the mortar is still green, a groove of shape and size as directed shall

be formed by running a forming tool straight along the centre line of the joints.

This operation shall be continued till a smooth and hard surface is obtained.

The vertical joints shall also be finished in a similar way. All vertical lines shall

make true right angles at their junctions with horizontal lines and shall not

project beyond the same.

35.6. MODE OF MEASUREMENT:

The area of surface actually pointed will be measured net and shall be paid for. The

measurement of length and height of walls pointed shall be taken correct to a

centimetre. All the openings of doors, windows, ventilators etc. shall be deducted and

jambs, soffits, sills etc. if pointed will be measured to arrive at the net area for the

payment. The rate shall include cost of all materials, labour, transport, scaffolding,

curing etc.

* * * *

Page 163: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 163 of 307

36. WALL CARE PUTTY

36.1. SCOPE OF WORK:

Wall care putty consists of white cement, high quality polymers and specialty

chemicals and mineral fillers and is formulated to make it suitable to apply even on

damp surfaces. Being cement based putty, it has better compatibility with the base

plaster and forms a durable base for paints. It can be applied on both, Interior and

exterior plastered surfaces. It is a water resistant base coating to the plastered

surfaces to provide fine leveling and a protective base for the surfaces to be painted.

36.2. GENERAL:

Wall care putty shall have superior water resisting properties to prevent paint from

flaking even if the walls are damp. It should fill-up fine pores in walls and ceilings to

get the smooth and dry surface for painting. Wall care putty shall have better

properties in terms of water-resistance, adhesive strength and durability as

compared to the ordinary putties. The putty shall provide a breathable surface and

allow any trapped moisture to move out keeping the wall dry and clean.

36.3. MATERIAL:

Wall care Putty shall be in dry free flowing powder form. Required quantity of Wall

care putty shall be procured from the reputed manufacturers like M/s. Birla White

Wall Care Putty / M/s. Wallplast Products Pvt. Ltd. or equivalent approved

manufacturers, or from their authorized dealers. The putty shall conform to the

International standards (viz. HDB-Singapore Standards with Water-resistant

properties).

The putty shall be procured in the form of FINE or COARSE (MATT) finish as

specified in the description of the item.

36.4. PREPARATION OF SURFACE:

• Surface should be clean of loose particles, dirt, grease and traces of foreign

material. Sand papering or chipping shall be done if so required.

• Loose plastered areas/defective materials shall be removed & surface re-

plastered and cracks filled-up properly.

• Uneven ceiling/wall surfaces shall be made even by re-plastering.

• Surface should be pre-wetted prior to application. This helps in providing a

strong bond with substrate.

36.5. MIXING:

• 12 to 16 litres of clean water shall be required for a bag of 40 kg of wall care

putty. Required quantity of putty (which is required to be used at a time) shall

be added to the water in right proportion. (considering pot life of the mix as 60

minutes).

• Mix shall be stirred continuously by using an electric mixer or by hand to

obtain a homogeneous lump-free paste.

Page 164: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 164 of 307

• The paste shall be allowed to stand for about 10 minutes for the additives to

dissolve.

• The paste shall be re-mixed again for about 2 minutes.

• This mix should be used within 60 minutes.

36.6. APPLICATION:

• The plastered surface shall be dampened with clean water and excess water

shall be allowed to be drained-off.

• Using a steel trowel/blade, the above mix shall be applied to a thickness of

about 1 – 2 mm. Then the surface shall be levelled and smoothened. This first

coat shall be cured lightly after it dries-up.

• Then second coat shall be applied after first coat is fully dried and set. Second

coat shall be cured lightly for two days.

• Over plastered / Coarse putty substrate, fine wall care putty of about 1 to 1.5

mm thickness shall be applied, to smoothen the surface with a steel trowel.

Finished surface of wall care putty shall not require any dressing by Emery

Paper but if at all it is done, the paper should not be less than 500 number.

• The thickness of each coat should not exceed 1.5mm and total wall putty

thickness should not exceed 3mm.

• If specified in the description of item, coarse wall care putty of about 6 to 10

mm thickness shall be applied to remove the undulations and level the surface.

More number of coats of coarse putty shall be applied to cover up undulations,

only after approval of the Engineer-in-Charge.

• Coverage of wall care putty depends upon surface quality. However,

approximate coverage for fine wall care putty shall be 20-22 Sqft/kg and for

coarse wall care putty, it shall be 9-10 Sqft/kg.

• Application of primer before painting is not necessary over the surfaces

finished with wall care putty.

36.7. SPECIFICATIONS

Specification of Wall care putty – For smooth Finish

SL.

NO. PROPERTY

AS PER HDB

(HOUSING

DEVELOPMENT

BOARD), SINGAPORE

TEST METHOD

Dry Adhesion >=0.8 N/sqmm EN 1015-12

Wet Adhesion >=0.3 N/sqmm Chinese

Std.

1 Tensile Adhesion Strength

(N/sqmm) @ 28 Days >0.8 N/sqmm EN-1348

2 Compressive Strength (N/sqmm)

@ 28 Days 7-12 N/sqmm EN 1015-11

Page 165: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 165 of 307

3 Setting Time (Minutes) - Initial &

Final <360 <500 EN 196

4 Water Absorption Coefficient -

Kg/M². H1/2

<=0.13 for W2 / <=0.26

for W1

EN 1015-18

5 Water Capillary Absorption (ML)

@ 24 Hrs. Karsten Tube

6 Water Retentivity % >=95% EN 1015-8

PH Alkaline

NOTE:

Putty being white cement based, it is alkaline, and hence direct eye and skin contact

should be avoided. In case of eye contact, flush the same with clean water for 15

minutes and seek medical help.

* * *

37. PAINTING :

37.1. SCOPE OF WORK :

The work covered under these specifications consist of furnishing the various types

of paints and also the workmanship for these items, in strict compliance with these

specifications, which are given in detail here-in-after with the item of schedule of

quantities.

37.2. MATERIALS :

Paints, oils, varnishes etc. of approved brand and manufacture shall be used. Ready

mixed paints as received from the manufacturer without any admixture shall be

used.

If for any reason, thinning is necessary in case of ready mixed paint, the brand of

thinner recommended by the manufacturer or as instructed by the Engineer-in-

Charge shall be used. Approved paints, oils or varnishes shall be brought to the site

of work by the contractor in their original containers in sealed condition. The

materials shall be brought in at a time in adequate quantities to suffice for the whole

work or at least a fortnights work. The materials shall be kept in the joint custody of

the contractor and the Engineer-in-charge. The empties shall not be removed from

the site of work, till the relevant item of work has been completed and permission

obtained from the Engineer-in-Charge.

The contractor shall associate the chemist of paint manufacturers before

commencement of work, during and after the completion of work who shall certify

the suitability of the surface to receive painting and the paint before use etc.

37.3. COMMENCING WORK :

Scaffolding : Wherever scaffolding is necessary, it shall be erected on double

supports tied together by horizontal pieces, over which scaffolding planks shall be

fixed. No ballies, bamboos or planks shall rest on or touch the surface which is

being painted.

Page 166: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 166 of 307

Where ladders are used, pieces of old gunny bags shall be tied on their tops to avoid

damage or scratches to walls.

For painting of the ceiling, proper stage scaffolding shall be erected.

Painting shall not be started until and unless the Engineer-in-Charge has inspected

the items of work to be painted, satisfied himself about their proper quality and

given his approval to commence the painting work.

Painting, except the priming coat, shall generally be taken in hand after all other

builders work, practically finished.

The rooms should be thoroughly swept out and the entire building cleaned up at

least one day in advance of the paint work being started.

37.4. PREPARATION OF SURFACE :

The surface shall be thoroughly cleaned. All dirt, rust, scales, smoke and grease

shall be thoroughly removed before painting is started. Minor patches if any in

plastered/form finished surfaces shall be repaired and finished in line and level in

C.M. 1:1 and cracks & crevices shall be filled with approved filler, by the contractor

at no extra cost to the Department. The prepared surface shall have received the

approval of the Engineer-in-Charge after inspection, before painting is commenced.

37.5. APPLICATION :

Before pouring into smaller containers for use, the paint shall be stirred thoroughly

in its containers. When applying also, the paint shall be continuously stirred in the

smaller containers so that consistency is kept uniform.

The external surfaces of the buildings under reference including the R.C.C. Jalli,

fins and the panels above and below the window etc. shall be finished in different

colours of approved shade. The contractor will make suitable samples at site for

Departments approvel before taking up the work in hand and they will be allowed to

proceed with the work only after getting Departments approval for the same.

The painting shall be laid on evenly and smoothly by means of crossing and laying off,

the later in the direction of the grain in case of wood. The crossing & laying off

consists of covering the area with paint, brushing the surface hard for the first time

and then brushing alternately in opposite directions two or three time and then

finally brushing lightly in direction at right angles to the same. In this process, no

brush marks shall be left after the laying off is finished. The full process of crossing

and laying will constitute one coat.

Where so stipulated, the painting shall be done with spraying. Spray machine used

may be (a) a high pressure (small air aperture) type or (b) a low pressure (large air

gap) type, depending on the nature and location of work to be carried out. Skilled

and experienced workmen shall be employed for this class of work. Paints used shall

be brought to the requisite consistency by adding a suitable thinner. Spraying

should be done only when dry condition prevails.

Each coat shall be allowed to dry out thoroughly and rubbed smooth before the next

coat is applied. This should be facilitated by thorough ventilation.

Page 167: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 167 of 307

Each coat except the last coat, shall be lightly rubbed down with sand paper or fine

pumice stone and cleaned of dust before the next coat is laid.

No left over paint shall be put back into the stock tins. When not in use, containers

shall be kept properly closed.

The final painted surface shall present a uniform appearance and no streaks, blisters,

hair marks from the brush or clogging of paint puddles in the corners of panels,

angles of mouldings etc. shall be left on the work.

In case of cement based paints/primers, the absorbent surfaces shall be evenly

damped so as to give even suction. In any weather, freshly painted surfaces shall be

kept damp for at least two days.

In painting doors and windows, the putty around the glass panes must also be

painted, but care must be taken to see that no paint stains etc. are left on the glass.

Tops of shutters and surfaces in similar hidden locations shall not be left out while

painting. Perspect covers of electrical switch boxes have to be painted from inside by

removing them. Care shall be taken while removing them in position after painting

with respective approved paints. In painting steel work, special care shall be taken

while painting over bolts, nuts, rivets, overlaps etc.

The additional specifications for primer and other coats of paints shall be as in

accordance to the detailed specifications under the respective headings.

Any damage caused during painting work to the existing works/surfaces shall be

made good by the contractor at his own cost.

37.6. BRUSHES AND CONTAINERS :

After work, the brushes shall be completely cleaned off paint and linseed oil by

rinsing with turpentine. A brush in which paint has dried up is ruined and shall on

no account be used for painting work. The containers, when not in use, shall be

closed, kept air tight and shall be kept at a place free from dust. When the paint has

been used, the containers shall be washed with turpentine and wiped dry with soft

clean cloth, so that they are clean & can be used again.

37.7. MEASUREMENT :

a) Painting, unless otherwise stated shall be measured by area in square metre.

Length and breadth shall be measured correct upto two places of decimal of a

metre.

b) No deduction shall be made for opening not exceeding 0.05 sqm. and no addition

shall be made for painting to the beading, moulding edges, jambs, soffits, sills,

architraves etc. of such openings.

c) In measuring painting, varnishing, oiling etc. of joinery and steel work etc., the

co-efficients as in the following table shall be used to obtain the areas payable.

The co-efficients shall be applied to the areas measured flat and not girthed in

all cases.

d) In case of painting of door shutter with push plates in plastic laminate,

deduction will be made for area of such laminations.

Page 168: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 168 of 307

37.7.1. Table of multiplying Co-efficients to be applied over areas of different

surfaces to get equivalent plain areas is given in the Appendix-“C-2” of this

book.

37.7.2. Explanatory notes on the table of Co-efficients.

1. Where doors, window etc. are of composite types other than those included in

Para 47.7 (c), the different portions shall be measured separately with their

appropriate co-efficients, the centre line of the common rail being taken as the

dividing line between the two portions.

2. Measurements for doors, windows etc. shall be taken flat (and not girthed)

over all including chowkhats or frames, where provided. Where chowkhats or

frames are not provided, the shutter measurements shall be taken.

3. Collapsible gates shall be measured for width from outside to outside of gate

in its expanded position and for height from bottom to top of channel

verticals. No separate measurements shall be taken for the top and bottom

guide, rails, rollers, fittings etc.

4. Rolling shutters of interlocked laths shall be measured for the actual shutter

width and the height from bottom of opening to the centre of the shaft. No

separate measurements shall be taken for painting guides and other exposed

features within or outside the shutter area. The painting of top cover or hood

shall however be measured separately.

5. Co-efficients for sliding doors shall be the same as for normal types of doors

as mentioned in the table. Measurements shall be taken outside of shutters,

and no separate measurements shall be taken for painting guides, rollers,

fittings etc.

6. Measurement of painting of doors, windows, collapsible gates, rolling shutters

etc. as above shall be deemed to include painting all iron fittings in the same

or different shade for which no extra will be paid.

7. The measurements as above shall be deemed to include also the painting of

edges, blocks, cleats etc. for which no extra will be paid.

8. The co-efficients for doors and windows shall apply irrespective of the size of

frames and shutter members.

9. When the two faces of a door, window etc. are to be treated with different

specified finishes, measurable under separate items, the edges of frames and

shutters shall be treated with the one or the other type of finish as ordered by

the Engineer-in-Charge, and measurement of this will be deemed to be

included in the measurement of the face treated with that finish.

10. In the case where shutters are fixed on both faces of the frames, the

measurements for the door frame and shutter on one face shall be taken in

the manner already described, while the additional shutter on the other face

will be measured for the shutter area only excluding the frame.

11. Where shutters are provided with clearance at top or/and bottom, such

openings shall be deducted from the overall measurements and relevant co-

Page 169: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 169 of 307

efficients shall be applied to obtain the area payable.

12. In case of trellis (or jaffri) work, the measurements shall include the painting

of the frame member for which no separate measurements shall be taken.

Trellis door or window shutters shall also be measured under terllis work.

13. Wherever air conditioning grill, lighting, fixtures etc. in false ceiling are

painted along with, measurements shall be taken over all without deductions

for opening in grills and no extra shall be paid for the grills. If grills, fixtures

etc. are not painted, area of fixtures or grills as measured flat (not girthed)

shall be deducted when it exceeds 0.05 sqm. Individuals Where walls and

ceilings are painted in separate colours, the junctions of two paints shall be

brought down on the walls in a straight line by about 6mm to 12mm. if so

desired, if the junctions of walls and ceilings are not even. Nothing extra shall

be paid to the contractor on this account. Beading wherever provided shall

not be measured separately but shall be deemed to be included in the area of

false ceiling etc. measured flat (not girthed).

14. For painting open palisade fencing and gates etc., the height shall be

measured from the bottom of the lowest rail, if the palisades do not go below

it, (or from the lower end of the palisades, if they project below the lowest rail),

upto the top of rails or palisades whichever are higher, but not up to the top of

standards when the latter are higher than the top rails or palisades.

15. In the case of asbestos cement corrugated or semi-corrugated sheeting and

iron corrugated sheeting in roofs, side cladding etc., the work shall be

measured flat (not girthed) as fixed.

16. For trusses, compound girders, stanchions, lattice girder and similar work,

actual areas will be measured in sqm and no extra shall be paid for painting

on bolt heads, nuts, washers etc. even when they are picked out in a different

tint to the adjacent work.

17. Painting of rain water, soil, waste, vent and water pipes etc. shall be

measured in running metres of the particular diameter of the pipe concerned.

Painting of specials such as bends, heads, branches, junctions, shoes etc. shall

be included in the length and no separate measurements shall be taken for

these or for painting brackets, clamps etc.

18. Measurements of wall surfaces and wood and other works not referred to

already shall be recorded as per actual and opening exceeding 0.05 sqm shall

be deducted to get the net payable area. Length and breadth shall be measured

correct upto two places of decimal of a metre and area so worked out shall be

correct upto two places of decimal of a square metre.

19. In case the items of work requiring painting are inclusive of cost of painting,

the painting carried out shall not be measured separately.

37.8. PRECAUTIONS :

All furnitures, lightings, fixtures, sanitary fittings, glazing, floors etc. shall be

protected by covering and stains, smears, splashings, if any shall be removed and

any damage done shall be made good by the contractor at his cost.

Page 170: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 170 of 307

37.9. RATES:

Rates shall include cost of all labour and materials involved on all the operations

described above and in the particular specifications given under the several items.

37.10. (A) PAINTING PRIMING COAT ON WOOD, IRON OR PLASTERED SURFACES

:

37.10.1. Primer

1. The primer for wood work, iron work or plastered surface shall be as specified

in the description of the item.

2. Primer for Wood work / Iron & Steel / Plastered / Aluminium surfaces

shall be as specified below:

SN SURFACES PRIMER TO BE USED

a Wood work (hard & soft wood): Pink conforming to

b Resinous wood and ply wood: Aluminium primer

c Iron & Steel, Aluminium and

galvanised Steel

Zinc chromate primer

conforming to d Plastered surfaces, cement brick

work, Asbestos

Cement Primer

3. The primer shall be ready mixed primer of approved brand and manufacture.

47.10.2 Preparation of surface :

a) Wood work : The wood work to be painted shall be dry and free from moisture.

The surface shall be thoroughly cleaned. All unevenness shall be rubbed down

smooth with sand paper and shall be well dusted. Knots, if any, shall be

covered with Preparation of red lead made by grinding red lead in water and

mixing with strong glue sized and used hot. Appropriate filler material with

same shade as paint shall be used where so desired by the Engineer-in-

charge.

The surface treated for knotting shall be dry before painting is applied. After

the priming coat is applied, the holes and indentation on the surface shall be

stopped with glaziers putty or wood putty (for specifications for glaziers putty

and wood putty- refer as mentioned here-in-before). Stopping shall not be

done before the priming coat is applied as the wood will absorb the oil in the

stopping and the latter is therefore liable to crack.

b) Iron and Steel Work : All rust and scales shall be removed by scrapping or by

brushing with steel wire brushes. Hard skin of oxide formed on the surface of

wrought iron during rolling which becomes loose by rusting, shall be removed.

All dust and dirt shall be thoroughly wiped away from the surface.

If the surface is wet, it shall be dried before priming coat is undertaken.

c) Plastered Surface : The surface shall ordinarily not be painted until it has

dried completely. Trial patches of primer shall be laid at intervals and where

Page 171: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 171 of 307

drying is satisfactory, painting shall be taken in hand. Before primer is

applied, holes and undulations, shall be filled up with plaster of paris and

rubbed smooth.

37.10.2. Application : The primer shall be applied with brushes, worked well

into the surface and spread even and smooth. The painting shall be done by

crossing and laying off as described here-in-before.

37.10.3. Other Details : The specifications for Painting (General) shall hold good

so far as it is applicable.

37.11. (B): PAINTING WITH SUPERIOR QUALITY & FLAT OIL READY MIXED PAINTS

ON NEW SURFACE :

37.11.1. Paint : Ready mixed paints shall be of approved brand and

manufacture and of the required shades. They shall conform in all respects to

the relevant I.S. specifications.

37.11.2. Preparation of Surface:

(a) Wood work : The surface shall be cleaned and all unevenness removed as in

Para 47.10.2 (a). Knots if visible, shall be covered with a Preparation of red

lead. Holes and indentations on the surface shall be filled in with glaziers

putty or wood putty and rubbed smooth before painting is done. The surface

should be thoroughly dry before painting.

(b) Iron and steel work : The primer coat shall have dried up completely before

painting is started. Rust and scaling shall be carefully removed by scraping or

by brushing with steel wire brushes. All dust and dirt shall be carefully and

thoroughly wiped away.

(c) Plastered surfaces : The priming coat shall have dried up completely before

painting is started. All dust or dirt that has settled on the priming coat shall

be thoroughly wiped before painting is started.

37.11.3. Application : The specifications mentioned here-in-before shall hold

good as far as applicable.

The number of coats to be applied will be as stipulated in the item. The painted

surface shall present a uniform appearance1 and glossy/semiglossy finish,

free from streaks, blisters etc.

37.11.4. Other details : The specifications for Painting (General) specified here-

in-before shall hold good in so far as they are applicable.

37.12. (C) PAINTING WITH SYNTHETIC ENAMEL/SEMI GLOSSY PAINT ON NEW

WORK :

1. Paint : Synthetic enamel/semi glossy paint of approved brand and manufacture

and required shade shall be used for the top coat and an under coat of shade to

match the top coat as recommended by the manufacturer shall be used. The

paint shall be conforming to IS : 1932-1 964.

2. Preparation of Surface : This shall be as per painting with superior quality

Page 172: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 172 of 307

ready mixed paint as mentioned here- in- before.

3. Application : The number of coats including the under coat shall be as

stipulated in the item.

3.1. Under Coat : One coat of the specified paint of shade suited to the

shade of the top coat shall be applied and allowed to dry over night. It shall

be rubbed next day with the finest grade of wet abrasive paper to ensure a

smooth and even surface free from brush marks and all loose particles shall

be dusted off. All the cracks, crevices, roughness etc. will be filled with

approved putty as per manufacturers recommendations.

3.2. Top Coat : Finishing coats of specified paint of the desired colour &

shade shall be applied after the under coat is thoroughly dried. Additional

finishing coats shall be applied if found necessary to ensure a proper and

uniform semi glossy surface.

4. Other Details : The specifications for “Painting (General)” mentioned here-in-

before shall hold good as far as they are applicable.

37.13. (D) PAINTING WITH ACRYLIC EMULSION/PLASTIC EMULSION PAINT.

1. This shall be polyvinyl based Acrylic/plastic emulsion paint of approved

manufacture of the required shade, conforming to I.S.5411-1969.

2. Primer: The primer to be used for the painting with acrylic emulsion on cement

concrete surfaces, plastered surfaces, A.C. sheets, timber and metal surfaces, if

necessary, shall be of approved base and as per recommendations of the

manufacturers.

3. Putty : Plaster filler to be used for filling up (putting) uneven surfaces, small

cracks and holes etc. shall be of approved compound and as per

recommendations of the manufacturers. No oil based putty shall be used. The

putty should be made from a mixture of whiting and plastic emulsion paint or as

per manufacturers recommendations.

4. Finishing coats : All the finishing coats shall be of matt finish or any other finish

as required by the Engineer-in-charge. The number of finishing coats shall be as

specified in the item.

MODE OF MEASUREMENT :

All the measurements for payment shall be taken on net surface area actually

painted, unless otherwise specified. Deduction will be made from the areas for

fixtures, grills, ventilation, outlets, electrical boxes and such obstructions not

painted, if they are individually more than 0.05 sqm.

JOB REQUIREMENTS :

i) Acrylic emulsion paint is required to be provided on plastered and concrete

surfaces in portions of the building. The Department shall reserve the option to

delete or increase quantities in full or part from the scope of contract during

progress of work.

Page 173: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 173 of 307

ii) All wood surfaces are to be painted with semi glossy synthetic enamel paint with

an approved primer.

iii) All shades and colours of paints shall be subjected to review and prior approval

of Engineer-in-Charge shall be taken before the application.

37.14. WHITE WASHING WITH LIME

37.14.1. Preparation of Surface : Before new work is white washed, the surface

shall be thoroughly brushed free from mortar droppings and foreign-matter.

In the case of old work, all loose pieces and scales shall be scrapped off and

holes in plaster as well as patches of less than 0.05 sqm.area each shall be

filled up with mortar of the same mix. Where so specifically ordered by the

Engineer-in-charge, the entire surface of old white wash shall be thoroughly

removed by scrapping and this shall be paid for separately.

37.14.2. Preparation of lime wash : The wash shall be prepared from fresh

stone white lime “Katani” or equivalent. The lime shall be thoroughly slaked

on the spot, mixed and stirred with sufficient water to make a thin cream.

This shall be allowed to stand for a period of 24 hours and then shall be

screened through a clean coarse cloth. 40 gm. of gum dissolved in hot water,

shall be added to each 10 cubic decimetre of the cream. The approximate

quantity of water to be added in making the cream will be 5 litres of water to

one kg. of lime.

Indigo (Neel) up to 3 gm. per kg. of lime dissolved in water, shall then be

added and wash stirred well. Water shall then be added at the rate of about 5

ltrs. per kg. of lime to produce a milky solution.

The lime shall be tested in a chemical laboratory and test certificate

submitted, to conform the quality of lime with regard to its physical and

chemical properties. The cost of testing lime shall be borne by the contractor.

37.14.3. White Washing ``: The white wash shall be applied with brushes or by

spray in the specified number of coats. The operation for each coat in the case

of brush application shall consist of a stroke of the brush given from the top

downwards, another from the bottom upwards over the first stroke, and

similarly one stroke horizontally from the right and another from the left

before it dries.

Each coat shall be allowed to dry before the next one is applied. Further each

coat shall be inspected and approved by the Engineer-in-charge before the

subsequent coat is applied. No portion of the surface shall be left out initially

to be patched up later on.

For new work, three or more coats shall be applied till the surface present a

smooth and uniform finish through which the plaster does not show. The

finished dry surface shall not show any sign of cracking and peeling nor shall

it come off readily on the hand when rubbed.

For old work, after the surface has been prepared as described here-in-before,

a coat of white wash shall be applied over the patches and repairs. Then a

single coat or two or more coats of white wash as stipulated in the description

Page 174: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 174 of 307

of the item shall be applied over the entire surface. The white washed surface

should present a uniform finish through which the plaster patched do not

appear. The washing on ceiling should be done prior to that on walls.

37.14.4. Protective Measures : Doors, windows, floors, articles of furniture etc.

and such other parts of the building not to be white washed shall be protected

from being splashed upon. Splashings and droppings, if any, shall be removed

by the contractor at his own cost and the surfaces cleaned. Damages if any to

painted surfaces, furnitures or fittings and fixtures etc. shall be recoverable

from the contractor.

37.14.5. Measurements : All measurements for payment shall be taken on net

surface areas actually white washed, unless otherwise specified. Deductions

will be made from the areas for fixtures, grills, ventilation, outlets, electrical

boxes and such obstruction not painted if they are individually more than

0.05 sqm. Length and breadth shall be taken correct upto two places of

decimal of a metre and areas so worked out shall be correct upto two places of

decimals of a square metre.

Corrugated surfaces shall be measured flat as fixed and the area so

measured shall be increased by the following percentages to allow for the

girthed area.

Corrugated asbestos cement sheets 20%

Semi-corrugated asbestos cement sheets: 10%

The number of coats of each treatment shall be stated. The item shall

include removing nails, making good holes, cracks, patches etc. not

exceeding 0.05 sqm. each with materials similar in composition to the

surface to be prepared.

37.14.6. Rate : The rate shall include the cost of all materials and labour

involved in all the operations described above.

37.15. COLOUR WASHING:

In the case of colour washing, mineral colours, not affected by lime, shall be added

to white wash with proper glue. No colour wash shall be done until a sample of the

colour wash to the required tint or shade has been got approved from the Engineer-

in-Charge. The colour shall be of even tint or shade over the whole surface. If it is

patchy or otherwise badly applied, it shall be redone by the contractor, at no extra

cost to the Department.

For new work, the priming coat shall be of white wash lime or with whiting as

specified in the description of the item. Two or three coats, shall then be applied as

specified on the entire surface till it represents a smooth and uniform finish. Each

coat after applying shall be got approved from the Engineer-in-Charge.

The finished dry surface shall not be powdery and shall not readily come off on the

hand when rubbed.

Page 175: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 175 of 307

Other specifications as detailed for Whitewashing with lime shall be applicable.

Indigo (Neel) shall however, not be added.

37.16. WATER PROOFING CEMENT BASED PAINT :

a) Material: Cement based paint (IS:541 0-1 969) of approved manufacture,

quality, shade and colour only shall be used.

b) Preparation of surfaces : The surface shall be thoroughly cleaned off all mortar

dropping, dirt, dust, algae, grease and other foreign matter by brushing and

washing the surfaces. The surface shall be thoroughly wetted with clean water

before the water proof cement paint is applied. The prepared surface shall be got

approved before painting is commenced.

The water proof cement paint shall be mixed in such quantities as can be used

up with in an hour of its mixing as otherwise the mixture will set and thicken,

affecting flow and finish.

Water proof cement paint shall be mixed with water in two stages. The first stage

shall comprise of 2 parts of water proof cement paint and one part of water

stirred thoroughly and allowed to stand for 5 minutes. Care shall be taken to

add the water proof cement paint gradually to the water and not vice versa. The

second stage shall comprise of adding further one part of water to the mix and

stirring thoroughly to obtain liquid of workable and uniform consistency. In all

cases the manufacturers instruction shall be followed meticulously.

c) Application: The solution shall be applied on the clean and wetted surface with

brushes or spraying machine. The solution shall be kept well stirred during the

period of application. To avoid direct heat of the sun during painting, the cement

based paint shall be applied on the surface which is on the shady side. Cement

based paint shall not be applied on the surfaces already treated with white

wash, colour wash, dry or oil bound distemper, varnishes, paints etc. It shall not

be applied on gypsum, wood and metal surfaces.

d) Other details : The specifications for Painting (General) mentioned here-in-

before shall hold good as far as they are applicable.

e) Mode of measurement for dry distemper, oil bound distemper and water

proof cement paint : All measurement for payment shall be taken on net

surface area actually painted unless otherwise specified and no co-efficient shall

be applied for working out areas. Deductions will be made from areas for

opening/obstructions not painted, if they are individually more than 0.05 sqm.

Length and breadth shall be taken correct upto two places of decimal of a meter

and areas shall be worked out correct upto two places of decimal of a square

meter.

Corrugated surfaces shall be measured flat as fixed and the area so measured

shall be increased by the following percentage to allow the girthed area: a)

Corrugated asbestos cement sheets - 20%; b) Semi corrugated asbestos cement

sheets - 10%.

The number of coats of each treatment shall be stated in the schedule of

quantities. The whole surface shall be applied with approved putty/filler to get

uniform and smooth surface at no extra cost to the Department.

Page 176: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 176 of 307

Rates : The rate shall include cost of all materials and labour involved in all the

operation described above.

37.17. BEES WAXING OR POLISHING WITH READY MADE WAX POLISH:(NEW

WORK) :

37.17.1. Materials : The polishing shall be done with bees waxing prepared

locally or with readymade wax polish of approved brand and manufacture, as

stipulated in the description of item.

a) Where bees waxing is to be prepared locally, the following specifications for

the same shall apply:

Pure bees wax free from Paraffin or stearing adulterants shall be used. Its

specific gravity shall be 0.965 to 0.969 and melting point shall be 63o C. The

polish shall be prepared from a mixture of bees wax, linseed oil, turpentine

and varnish in the ratio of 2: 1 .5: 1: 0.5 by weight.

The bees wax and boiled linseed oil shall be heated over a slow fire. When the

wax is completely dissolved, the mixture shall be cooled till it is just warm and

turpentine and varnish added to it in the required proportions and the entire

mixture shall be well stirred.

37.17.2. Preparation of surface : Preparation of surface will be as mentioned

here-in-under Para 47.20.2 with the exception that knotting, holes and cracks

shall be stopped with a mixture of fine saw dust formed of the wood being

treated, beaten up with sufficient bees wax to enhance cohesion.

37.17.3. Application : The polish shall be applied evenly with a clean soft pad of

cotton cloth in such a way that the surface is completely and fully covered.

The surface is then rubbed continuously for half an hour.

When the surface is quite dry, a second coat shall be applied in the same

manner and rubbed continuously for one hour or until the surface is dry.

The final coat shall then be applied and rubbed for two hours (more if

necessary) until the surface has assumed a uniform gloss and is dry showing

no sign of stickiness.

The final polish depends largely on the amount of rubbing which should be

continuous and with uniform pressure, with frequent changes in the direction.

37.17.4. Other details : The specifications for painting (General) as mentioned

here-in-before shall hold good as for as they are applicable.

37.18. FRENCH SPIRIT POLISHING: (ON NEW WORK WITH A COAT OF WOOD

FILLER) :

37.18.1. Polish : Pure shellac varying from pale orange to lemon yellow colour,

free from resin or dirt shall be dissolved in methylated spirit at the rate of 140

gm. of shellac to 1 litre of spirit. Suitable pigment shall be added to get the

required shade.

37.18.2. Preparation of surface : The surface shall be cleaned. All unevenness

Page 177: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 177 of 307

shall be rubbed down smooth with sand paper and well dusted off. Knots if

visible shall be covered with a Preparation of red lead and glue size laid on

while hot. Holes and indentations on the surface shall be stopped with glaziers

putty. The surface shall then be given a coat of wood filler made by mixing

whiting (ground chalk) in methylated spirit at the rate of 1 .5 kg. of whiting per

litre of spirit. The surface shall again be rubbed down perfectly smooth with

glass paper and wiped clean.

37.18.3. Application : The number of coats of polish to be applied shall be as

described in the item.

A pad of woolen cloth covered by fine cloth shall be used to apply the polish.

The pad shall be moistened with the polish and rubbed hard on the wood, in a

series of overlapping circles applying the mixture sparingly but uniformly

over the entire area to give an even level surface. A trace of linseed oil on the

face of the pad facilitates this operation. The surface shall be allowed to dry

and the remaining coats applied in the same way. To finish off, the pad shall

be covered with a fresh piece of clean fine cotton cloth, slightly damped with

methylated spirit and rubbed lightly and quickly with circular motions. The

finished surface shall have a uniform texture and high gloss.

37.18.4. Measurement, Rate and other Details : These shall be as for Painting

(General) mentioned here-inbefore as far as they are applicable.

NOTE: Consumption of paint for some painting items is given in Appendix

– “C-1”.

* * *

38. VINERATEX OR VITROBRITE DECORATIVE TEXTURE COAT :

38.1. GENERAL :

Vineratex or vitrobrite decorative treatment/coating consisting of coating the plaster

finished surfaces with decorative texured coat of ready mixed mixture of approved

aggregate with bonding compound/synthetic adhesive manufactured by M/s. Vinera

Industries & Co. or other approved manufacturer. The vineratex or vitrobrite

treatment coating shall be got done through approved agency as per manufacturers

recommendations.

The vineratex or vitrobrite treatment shall be applied/coated directly over the sub-

base of reasonably smooth/levelled and clean surface like plastered brick work

(plaster not being raked or scratched) in-situ concrete, precast concrete units, light

weight blocks, asbestos cement sheet etc. as specified.

38.2. MATERIAL :

The various aggregate and special bonding media/synthetic resin shall be strictly as

per manufacturers recommendations. Only such aggregates shall be used, which are

weather and corrosion resistant viz. glass, ceramic marble, chips, granite, quartz and

flint, hametites, pyrites or one in natural vitrified, coloined or other processed forms

as specified. The aggregate shall vary in sizes from 0.5 mm. to 2.5 mm. and shall be

applied in shades as specified. The finish shall have a film thickness of 3 mm.

average.

Page 178: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 178 of 307

38.3. SURFACE PREPARATION :

Before commencing, the surfaces should be cleaned thoroughly to remove any grease,

dirt, dust or loose particle and should be free from surface water. Extremely porous

surfaces should be pre-sealed with a thin coat of suitable primer. Previous painted

surfaces if any, should be prepared by thoroughly scrapping off all loose flaking paint

film, washing down with a suitable detergent and rinsing thoroughly with clean

water and allowed to dry.

38.4. APPLICATION :

Vineratex or vitrobrite shall be brought to site in sealed containers. Addition of

thinner at site will not be permitted. The material in the containers shall be mixed

thoroughly before use, to off-set the settlement occurred due to heavy vibration while

transporting and during storage.

A small amount of Vineratex or vitrobrite mixture shall be placed on a spot board. The

spot board shall be held against the surface on which the treatment/coating is to be

applied. The mixture shall be applied to the surface evenly with the help of laying on

trowel to uniform thickness of about 3 mm. on an area of about 0.18 sqm. Scrap off

the excess material with the help of the steel float to obtain an even film thickness of

3 mm. This shall be achieved by using the steel float held slightly on the trailing

edge, putting an even pressure and scrapping off the excess material/mixture, left

on the spot board shall be immediately put back into drum and shall be mixed well

before reuse.

Level of the vineratex or vitrobrite film to a smooth and even finish using the flat

edge of steel float. It is important that only small areas of about 0.18 sqm. shall be

treated at a time. Wherever possible, whole work should be completed without stop

in one operation by engaging sufficient number of workers, so that flowing edge may

be maintained without forming any joint. If this is unavoidable, a suitable natural

break in the application should be chosen and the joint shall be made using a

straight edge, which can be continued when application is resumed the following

day. Over lap or over troweling at joints shall be avoided. This treatment shall

always be carried out in shade, away from full effect of hot sun.

At all times the completed work of vineratex or vitrobrite shall be protected against

rain fall until complete hardness has been obtained which takes about 24 hours.

Once the treatment/coating is completed and set hard, no other treatment like

polishing, cleaning, washing with acid etc. shall be resorted to in this area. The

treatment/coating shall be taken up in hand when all other construction works viz.

plastering, electrical wiring, plumbing, painting etc. have been completed.

After the whole work is completed, the vineratex/vitrobrite shall be given a coat of

anti-fungus gel to avoid fungus growth on surfaces. The contractor shall be

responsible to protect the finished surface from any damages for whatever reason

whatsoever.

38.5. MODE OF MEASUREMENT :

Mode of measurement shall be similar to sand faced/roughcast plaster items.

* * *

Page 179: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 179 of 307

39. TUBULAR TRUSSES, PURLINS ETC. :

39.1. Structural Steel Tubes : These shall

be of :

i) hot finished welded (HFW) type, or

ii) hot finished seamless (HFS) type, or

iii) electric resistance or induction butt welded (ERW), having carbon content less

than 0.03%, yield stress of 21.5 kg./mm. (YST 22) type, conforming to the

requirement of I.S. 1161-63. The steel tubes when analysed in accordance with

the method specified in I.S. 226-1959.

Tubes shall be designated by their nominal bore. These shall be light, medium or

heavy as specified, depending on the wall thickness.

Tubes shall be cleanly finished and reasonably free from scale. They shall be free

from cracks, surface flaws, laminations and other defects. The ends shall be cut

cleanly and square with the axis of tube, unless otherwise specified.

39.2. MINIMUM THICKNESS OF METALS : The tubular steel work shall be painted

with one coat of approved steel primer after fabrication. Wall thickness of tubes used

for construction exposed to weather shall be not less than 4 mm. and for construction

not exposed to weather, it shall be not less than 3.2 mm., where structures are not

readily accessible for maintenance, the minimum thickness shall be 5 mm.

39.3. FABRICATION :

39.3.1. The component parts of the structure shall be assembled in such a

manner that they are neither twisted nor otherwise damaged and be so

prepared that the specified cambers, if any, are maintained.

39.3.2. Straightening : All material before being assembled shall be

straightened, if necessary, unless required to be of a curvilinear form and

shall be free from twist.

39.3.3. Bolting : Washers shall be specially shaped where necessary, or other

means used, to give the nuts and the heads of bolts a satisfactory bearing.

In all cases where the full bearing area of the bolt is to be developed, the

threaded portion of the bolt shall not be within the thickness of the parts

bolted together, and washers of appropriate thickness shall be provided to

allow the nut to be completely tightened.

39.3.4. Welding : Where welding is adopted, it shall be done as per relevant I.S.

820.

39.3.5. Caps and Bases for Columns : The ends of all the tubes for columns,

transmitting loads through the ends, should be true and square to the axis of

the tube and should be provided with a cap or base accurately fitted to the

end of the tube and screwed, welded or shrunk on. The cap or base plate

should be true and square to the axis of the column.

Page 180: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 180 of 307

39.3.6. Sealing of Tubes : When the end of a tube is not automatically sealed

by virtue of its connection by welding to another member, the end shall be

properly and completely sealed. Before sealing, the inside of the tube should

be dry and free from loose scale.

39.3.7. Flattened Ends : In tubular construction the ends of tubes may be

flattened or otherwise formed to provide for welded, rivetted or bolted

connections, provided that the methods adopted for such flattening do not

injure the material. The change of sections shall be gradual.

39.4. HOISTING AND ERECTION :

Tubular trusses shall be hoisted and erected in position carefully, without damage

to themselves, other structure, equipment and injury to workmen. The method of

hoisting and erection proposed to be adopted shall be got approved from the

Engineer-in-charge. The contractor shall however be fully responsible, for the work

being carried out in a safe and proper manner without unduly stressing the various

members. The contractor shall have to grout the bolts in column tops to receive the

truss wall plates, hoist the trusses in position, erect it in a perfect line, level and

plumb, fix it in position with nuts, bolts etc., cure the grouted portion and paint the

truss with two coats of paint of approved colour and shade over a coat of approved

steel primer. Proper equipment such as derricks, lifting tackles, winches,

scaffolding, propping, ropes etc. shall be used.

39.5. MODE OF MEASUREMENT : The work as fixed in place shall be measured in

running metres correct to a centimetre and their weights calculated on the basis of

standard tables correct to the nearest kilogram, unless otherwise specified.

Weight of cleats, brackets, packing pieces, bolts , nuts, washers, distance pieces,

seParators diaphragm gussets (taking overall square dimensions) fish plates etc.

shall be added to the weight of respective items unless otherwise specified. No

deduction shall be made for skew cuts.

39.6. RATE : The rate shall include the cost of labour and materials involved in all

the operations described above including one coat of approved steel primer and

painting as specified in the item.

* * *

40. FALSE CEILING WITH FLEXO BOARDS / A.C. SHEETS :

40.1. SCOPE OF WORK :

The work envisaged under these specifications refer to supplying and fixing in

position false ceiling at any floor, any location and at any height.

40.2. MATERIAL :

The plain A.C. sheet or flexo board shall be of the thickness as mentioned in the

relevant items of the schedule of quantities and the size of panels and the

arrangement of panels etc. for different area of the building shall be as indicated by

the Engineer-in-Charge. Plain A.C. sheet or flexo board shall be of approved quality

and shall be free from cracks, bends and other defects. Samples of materials to be

used on the work shall first be furnished by the contractor and got approved by the

Page 181: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 181 of 307

Engineer-in-Charge. All materials which are used on the works shall strictly conform

to the samples, other-wise the materials shall be summarily rejected.

The plain A.C. sheet or flexo board shall be fixed to the angle iron frames (frame

work paid separately) work by means of suitable counter sunk brass self tapping

screws not more than 200 mm. centre to centre or as directed, and all holes after

fixing the screws be filled with approved filler. Necessary openings in the ceiling

shall be left for trap doors, ducts etc.

40.3. ERECTION :

The flexo boards/A.C. sheets when brought to site shall be stacked carefully on floor

over wooden sleeper supports. The boards shall be cut to required sizes either by

sawing or by score and snap method. The edges shall be smoothened by wood rasp

file or with emery paper. Wherever required the edges of each panel may require

bevelling which also shall be done carefully to the correct line and dimensions.

The flexo boards/A.C. sheets shall be fixed to ridge frames either wooden or metallic

or mentioned in the item description. In case of metallic frame, the flexo boards are

held to the frame by means of self tapping screws or by the ordinary machine screws

and nuts, as directed by the Engineer-in-Charge.

Teak wood or aluminium beadings if required to be fixed shall be as mentioned in

the item description and shall be carried out in best workman-like manner.

Any other treatment for finishing such as gluing of wall papers, cement or oil based

paint etc. shall be as specified in the item description and shall be done as per

relevant specifications.

40.4. MODE OF MEASUREMENT :

Unless otherwise mentioned, the wooden or metallic-frame work shall be separately

measured and paid for. The flexo board/A.C. sheet false ceiling shall be measured in

square metre as actually laid over the frame work. The area being worked out correct

to two places of decimal with length and breadth measured correct to a centimeter.

The rates shall include the cost of all materials, labour, scaffolding etc. as

mentioned above and in item description, unless otherwise specified.

41 TRAP DOORS :

The materials viz. M.S. frame, aluminium frame and A.C. sheet and fabrications

shall conform to the relevant specification given in this tender.

The trap doors shall be fixed in position with necessary M.S. angle frame out of

M.S. angle of size 40 x 40 x 6mm. for the shutter and fixed to M.S. wall angle of

size 40 x 25 x 6 mm. which is to be fixed by means of 40 x 25 x 6 mm. M.S. angle

cleats, fixed to wall by means of M.S. hold fasts out of M.S. flats of size 40 x

6mm., 150 mm. long and grouted with cement concrete 1:2:4 in case of brick

wall and with 100 mm. long M.S. coach screws and rawl plugs in case R.C.

columns etc. M.S. angle of size 40 x 25 x 5 mm. shall be provided for receiving

the lever of the locking arrangement. This angle shall be supported by 40 x 6

mm. M.S. flat suspenders from ceiling fixed with 3/8" diameter metal

fasteners/expansion bolts. This angle, meant to receive the lever of the lock,

shall be supported by two numbers of M.S. angle of size 40 x 25 x 5 mm. on

Page 182: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 182 of 307

either side. The two angles also shall be provided with M.S. flat (40 x 6 mm.)

suspenders @ 800 mm. centers at all other convenient spacing as per drawing

and as approved by the Engineer-in-Charge.

Sample of trap doors of single, double and multi panels shall be fabricated and

fixed in position and got approved before taking up fabrication of trap doors on

large scale.

All the exposed surfaces of M.S. work including the suspenders shall be painted

with two coats of synthetic enamel paint of approved make and shade over a

coat of approved primer.

MODE OF MEASUREMENT :

The area of trap door visible from underside of the false ceiling only shall be

measured in square metres for payment. The m.s. angles to be provided for

locking arrangements and supporting M.S. angles which shall not be seen from

underneath shall not be measured for payment and are supposed to be included

in the rate quoted for trap door, unless otherwise specified in the schedule of

work.

42. METAL FALSE CEILING SYSTEM & THERMAL INSULATION :

METAL FALSE CEILING SYSTEM (LUXALON 150 C / EQUIVQLENT):

42.1. MATERIALS

Manufacturing and Product: Hunter Douglas India Private Ltd. or equivalent

a) PRODUCT : Luxalon 150 C lineal aluminium false ceiling or equivalent

b) COLOUR : As specified or as approved by the Engineer-in-Charge

Material Description: All components shall be made of aluminium and manufactured

by M/s. Hunter Douglas India Private Limited OR Equivalent and as per

manufacturer's specification.

LUXALON 150 C METAL CEILING :

i) PANEL: The panel shall be cold roll formed panels 150mm wide and 15,5mm

deep with a 5mm beveled edge creating an 8mm V groove made from corrosion

resistant Al.-Mg. Alloy AA5050, The length of each panel shall be upto 6000mm.

The aluminium panels shall be chromatised for maximum bond between metal

and paint enameled twice under high temperature, one side with a full primer

and finish coat in a polyester paint for a dry film thickness of 20 microns, the

other side (inner side) with a primer coating and skin coat on a Continuous

Paint Line.

ii) CARRIER : The carrier on which the panels shall be clipped on to will be 32mm

wide, 39mm deep, made of black stove enameled 0.95mm thick aluminium alloy

AA5050. When two or more carriers are to be joined, they shall be joined together

by means of splices, which will clip on to holes provided for the same.

iii) WALL TRIM : The wall trim shall be 15mm deep x 30mm wide x 15mm deep x

Page 183: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 183 of 307

0.4mm thick Aluminium Alloy AA5050 with square edges and length of 5 mtr.

iv) ROD HANGER : The rod hanger of suitable length shall be made of 4mm dia.

galvanised steel (Zinc coating 120 gms/Sqm.)

v) SUSPENSION CLIP : The adjustment suspension clip shall be made of

galvanised spring steel V shaped with two holes to accommodate the rod hanger.

vi) ANCHOR FASTNERS : The single piece sleeve anchor with assembled hanger

taper bolt and nut which has smaller driller dia. Anchor fastener shall be of

arrow make or equivalent with thread size 5mm.

vii) SUSPENSION SYSTEM : The carriers would be suspended from the roof by 4mm

dia galvanised (Zinc coating 120gms/Sqm.) steel wire rod hangers with height

adjustment springs out of galvanised spring steel. Hangers shall be fixed to roof

by 'J' hooks and Anchor Fasteners

42.2. FINISHING OF SURFACE OF STRIPS FOR INTERNAL USE (ALUMINIUM)

The coils from which aluminium panels are made shall be cold roll formed & stove

enameled on a continuous coil coating paint line with dried in place roller coated

application for pre-treatment. The coils to go through four stages of pre-treatment,

three times oven baked through conversion coating, priming and finished coat,

ensuring superior adhesion, high corrosion resistance and good colour retention. The

coils shall be painted on both sides after being degreased. Prime coat of at least 5

microns to be applied on both sides and a back coat of 5 micron of neutral colour to

be applied on the inside surface and 5 micron of binder and 15 microns of top coat of

desired colour shall be additionally provided on the exposed surface.

Pencil Hardness. : phh > F

Light Fastness. : Light fastness of at least 6 according to international wool

scale.

Colour Fastness : All finishes shall have a colour fastness of at least 6.

Colour Variation. : Colour diff, Bet batches + 4 units Colour diff. Within one

batch + 2 units.

Colour Uniformity : Maximum allowable deviation is 2 NBS units.

Specular Glose. : 10 deg/00 (matt) ; 25 deg/00 (satin)

Resistance to Salt Spray : After 100 hrs testing under creep from the edges

or the Cross, shall Test exceed 2mm. Blistering shall not exceed F 8.

Impact resistance : To withstand an impact test of 5mN/mm metal

thickness Without loss of adhesion.

Paint adhesion. : Better than or equal rating 1

Humidity Resistance. : No formation of blister.

Chemical Resistance. : No loss of adhesion or gloss and no colour change or

Staining.

Page 184: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 184 of 307

42.3. FIXING : The panels shall be clipped on to a carrier. The carriers to be

suspended with an adjustment spring of galvanised spring steel, V shaped with two

holes to accommodate the rod hanger. The rod hanger to be made of 4mm dia,

galvanised steel and suspended form the ceiling by J hooks fixed at 1.5mm centre to

centre.

42.4. WORKMANSHIP : The ceiling shall be erected in continuous sequence. Spans

would not exceed those recommended by M/s. Hunter Douglas India Pvt. Ltd. All work

in this section shall be performed in an efficient manner by the installing agency

approved by the manufacturers and as per manufacturer's recommended procedures.

42.5. FIRE RESISTANCE : The false ceiling including the paint shall be fire

resistant as per DIN 4102.Class A2. It should also be classified as P-NOT EASILY

IGNITABLE - AS PER BS 476. Part 6 and should have a fire propagation classification

of Class as per BS 476. Part 6.

43. FALSE CEILING WITH GYPBOARD AND G.I. FRAMEWORK Scope of work :

The work envisaged under these specifications refer to supplying and fixing in

position false ceiling at any floor, any location and at any height.

a) Providing and fixing suspended G.I frame work

b) Providing and fixing one layer of 12 mm gypboard over

this frame work

c) Jointing the board flush, applying two coats of primer

suitable for gypsum board and two coats of acrylic

emultion matt finish paint of approved shade and make.

d)

Making necessary cut outs for light fitting, A.C grills

diffusers and other necessities. The work shall include

horizontal, vertical and inclined surfaces depending

upon the various requirements

e) The item includes p/f all necessary t.w. frame work

for A/C grills,electric fittings etc.complete all as directed

by consultant.

Material :

G.I Frame work:

The system consists of G.I frame work suspended from the soffit of the RCC ceiling.

The following G.I components shall be used for grid work:

a) Ceiling section of 80 x 26 x 0.5 mm

b) Perimeter channel of 20 x 27 x 30 x 0.5mm

c) Intermediate channels of 15 x 45 x 0.9 mm

d) Ceiling angle of 25 x 10 x 0.55 mm

e) Connecting clips of 2.64 mm dia.

f) Soffit cleat 22 x 37 mm

g) Anchor fasteners 6 mm

All the G I components shall be of M/s. India Gypsum Limited make and bear the

embossing of “GYPSTEEL’ in each length.

Page 185: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 185 of 307

The G.I grid work system shall be suspended from the soffit of RCC ceiling using

anchor fasteners of 6 mm of approved type and make and connected to soffit cleats

and ceiling angle by means of necessary nuts, bolts and washers etc.

Gyp Board

Gyp Board of plain series 12 mm manufactured by India gypsum shall be used. The

Gyp board shall conforms to Is 2095. The longitudinal edge of the Gyp board shall

be of tapered / square edges, so as to have flush joints while fixing.

Handling and transporting of Gyp board shall be done carefully and as recommended

by the manufacturer. The board should always be kept in a dry and covered place

sheltered from rain and to avoid dampness from flow, they should be supported on

wooden battens which should not be more than 45 cm apart on a flat surface. The

material shall be stacked in piles of smaller heights and should not be stacked on

edges. Gyp board which have deformed due to poor stacking should not be used.

Cutting of board should be made in faced side of the board by means of retractable

knife or by using a normal saw and the edges of the boards shall be planed using

proper files.

Finishing materials:

All jointing compounds, paper tapes, primer and paints shall be with materials

manufactured / recommended by India Gypsum.

Installation :

Perimeter channels are leveled at the required position of the finished ceiling line and

fixed to the wall at 610 mm center with the screws and nylon plugs. The remaining

G.I gird component are installed to form a regular grid suspended from the soffit of

RCC slab using soffit cleats ceiling angle and anchor fasteners as specified. Extra

frame for various cutouts of different shapes, light fittings, AC grills, diffusers,

smoke detectors and other necessities have to be provided wherever required and is

included in the scope of the work at no extra cost. This frame work has to be made

with perimeter channel of specified size and shall be suitably supported. The line

and level of the grid work has to be checked for perfection and prior clearance of the

grid work has to be obtained from the Engineer-in-Charge before the placement of

Gyp board.

The Gyp board are fixed with bound edges at right angles to ceiling section with all

joints staggered. All joints of Gyp board have to be fixed on ceiling section. The Gyp

boards are screwed to the ceiling section and perimeter channels with Gyp board dry

wall screws with joints staggered. Spotting of screws and jointing are then carried

out according to India Gypsum recommendations to give a flush and smooth joint.

Necessary door openings of hinged type of suitable sizes have to be provided with a

suitable framework for control valves and for access above false ceiling / AC duct

boxing at no extra cost.

Joints at horizontal, vertical and inclined surfaces shall be suitably strengthened

with additional G.I frame work as required.

Finally the boards are jointed and finished so as to have a flush look which includes

filling and finishing the tapered and square edges of the board with a jointing

compound, paper tape and two coats of primer suitable for gyp board (all as per

recommended practices of Indian Gypsum). Then, the finished Gyp board has to be

Page 186: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 186 of 307

painted with 2 coats of acrylic emulsion matt finish paint of approved color and

make.

The rate shall includes providing all material, erecting, suspending, G.I grid work,

jointing the boards, providing required cutouts and openable doors and painting

including providing necessary fittings and fixtures etc. complete as per the

specifications and all other activities related to the completion of the above job.

Details of A.C grills, diffusers, recessed type electrical fittings to be erected in false

ceiling will be as per specifications and as shown in drawings.

The quantities indicated are approximate and is likely to vary depending upon the

site conditions.

The scope of works includes fixing with screws, fixtures etc. the recessed electrical

light fittings in the grid work of false ceiling / boxing. Marine plywood ( 6 mm thick)

/ special G.I sections, if required, shall also be provided at no extra cost. The rate

quoted shall include all the above mentioned activities related to the completion of

the above job.

Mode of measurement :

Measurements will be made on flat plan area basis in Sq.M calculated to 2 places of

decimal. Length and breadth shall be measured corrected to a cm. No deduction

shall be made for cutouts made for A.C. grills, diffusers, electrical fittings, smoke

detectors etc.

44. Modular false ceiling Modular False Ceiling : Armstrong Modular ceiling grid(hot dipped galvanized steel

section) shall have 595 x 595 mm x 15mm fine fissured tiles(lay-in type) in true

horizontal level using a 15mm T bar section suspended from the ceiling slab using 2

mm wire at every 1200mm interval. And shall have fire rating of 60 minutes as per

BS 476/23 of 1987, Noise reduction Coefficient (NRC) of 0.50-0.60, to resist

temperature and humidity conditions up to 40 degree (104deg. F) and humidity of

99% RH.

* * *

45. WATER PROOFING :

GENERAL : The guarantee for waterproofing treatment in prescribed proforma must

be given by the specialised agency which shall be countersigned by the contractor in

token of his overall responsibility. The guarantee for waterproofing treatment in the

prescribed proforma shall also cover Horizontal expansion joint and Vertical

expansion joint.

45.1. WATER PROOFING PLASTER IN TOILET AREA :

The following specification shall be followed unless otherwise stated in schedule of

quantities. This shall be 15 mm. thick plaster including an under coat not

exceeding 8 mm. thick. Approved water proofing compound like CICO No. 1 or other

approved equivalent shall be added @ 3% by weight of cement in cement mortar or

as per manufacturers specifications in both the coats. The workmanship and material

shall be same as described in plaster work in general. All exposed surfaces shall be

finished smooth with a coat of neat cement as directed, except areas where tiling

work is to be done, where the plaster shall be left rough / float finish.

Page 187: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 187 of 307

45.2. BRICK BAT COBA WATERPROOFING ON TERRACE :

45.2.1. Materials : The aggregate for brick bat coba shall be broken from good

and thoroughly well burnt bricks. These shall be strong, durable, clean and

free from impurities. They shall not contain any soft or powdering materials.

The aggregate shall be 20 mm. to 10 mm. size and shall be approved by the

Engineer-in-Charge before use.

Lime to be used for preparing brick bat coba shall be of lime class B,

conforming to I.S. 712-1959. Lime burnt from lime stone shall be used. All

impurities, ashes or pieces improperly burnt shall be screened or picked out

before slaking. It shall be in the form of lumps when brought to site of work

and not in powder form. The lime shall not be slaked with water less than one

week or more than two weeks before use.

45.2.2. Storage : The slaked lime if stored, shall be kept in a weather proof and

damp proof closed shed with impervious floor and sides to protect it against

rain, moisture, weather and extraneous materials mixing with it, and shall be

approved by the Engineer-in-Charge.

45.2.3. Proportion : The proportion for brick bat coba shall be 0.906 cum.

(about 32cft.) of brick bat to 0.34 cum. (about 12 cft.) of slaked lime.

45.2.4. Laying : The concrete surface shall be thoroughly rubbed, cleaned of all

set mortar, all dirt and dust and slightly wetted. The brick aggregate shall be

soaked in water before mixing with lime. The brick bat coba shall be laid in an

even layer and to the required thickness and slope so as to form ridge, hip or

valley line as may be necessary and as indicated in the drawing or as directed

by the Engineer-in-Charge. The compaction shall be started immediately with

wooden beaters and during the above process, the surface shall be constantly

kept wet by sprinkling water observing the following precautions:

a) Brick bat coba shall not be rammed with heavy iron rammers as brick

aggregates are likely to be crushed into powder thereby, but shall be beaten

lightly and rapidly with wooden beaters to get the required compaction and to

obtain complete integration of brick bats and lime.

b) While beating, fresh fracture may take place which may cause absorption of

water from the mortar. Additional water may be sprinkled with beating in

such cases as considered necessary by the Engineer-in-Charge. The beating

work shall continue for at least 7 days.

c) The average thickness of coba shall be as specified in the items and the top of

the coba shall be given slope or made level and edges taken into the brick

masonry Parapet or rounded off at junctions as shown in the drawing and as

directed by the Engineer-in-Charge.

45.2.5. MODE OF MEASUREMENT :

The length and breadth of the surface area shall be measured to two places of

decimals of a metre from the finished surface of wall and Parapet and cubic

contents to be worked out with average thickness of coba provided. Rate shall

include cost of Preparation of surface, cost of materials, labour, rounding of

junctions etc. complete.

Page 188: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 188 of 307

45.3. CHINA MOSAIC WATER PROOFING :

45.3.1. General : This type of water proofing shall consist of setting in thick

cement slurry selected colour/white glazed tile broken pieces of approved make

and size over 20mm. thick bedding of cement mortar 1:4 with approved

waterproofing agent or as specified in schedule of work, to the required slope

and level, over brick bat coba and finishing with neat cement and cleaning to

the required degree of fineness and evenness.

The different materials and workmanship shall conform to the relevant I.S.

specifications and shall be got approved before incorporating in the work.

The surface of brick bat coba shall be thoroughly cleaned of dust, dirt and

loose particles removed and adequately watered. Thick coat of cement slurry

of the honey like consistency shall be sprayed on the base before lime mortar

screening of specified thickness is laid.

45.3.2. Laying : Over the prepared surface of brick bat coba, a layer of cement

mortar, 20 mm. thick or as specified, shall be laid and cement slurry of

consistency of honey, shall be spread over it using cement at a rate of not less

than 0.01 cum. per 10 sqm. While the bed is fresh, broken pieces of 6 mm.

thick selected white/colour glazed tiles not less than 25 mm. and not more

than 50 mm. in any direction shall be set closely by hand at random. The

glazed tile pieces shall be soaked in water before setting in position. The glazed

surfaces shall be kept exposed and pressed with wooden mallet. Over the

glazed tile pieces a neat cement slurry, using cement not less than 0.01 cum.

per 10 sqm. shall be spread and the surface brushed in and lightly rolled with

wooden roller, taking care that no air pocket is left between brick bat coba

and china mosaic flooring.

The top surfaces shall be cleaned with saw dust and cotton waste. Finally the

surface shall be cleaned with weak acid solution to remove cement marks over

the white glazed tile pieces. The finished work shall be cured for at least 7 days.

Care shall be taken to see that cement in joints does not get dissolved due to

acid washing. At corners and junctions with Parapet, the water proofing

course shall be rounded off with cement mortar as per drawing and shall be

included in the quoted rate.

45.3.3. MODE OF MEASUREMENT :

The length and breadth shall be measured to two places of decimal of a metre,

alongside the surface including rounding of junctions of walls and wall & slab

etc. and area worked out in square metre. The rain water out-lets shall be

finished as directed and no deduction shall be made for the same (area upto

0.02 sqm.) while arriving at the net area for payment.

45.4. CEMENT BASED WATER PROOFING OF W.C. AND BATHS AREAS :

45.4.1. General : The water proofing treatment for the Bath and W.C. shall be

essentially of cement based water proofing treatment with admixture of

proprietary water proofing compound similar to M/s. India water proofing

companies treatment or any other equivalent approved cement based water

proofing treatment. The waterproofing treatment shall consist of providing

Page 189: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 189 of 307

cement slurry mixed with proprietary water proofing compound after

Preparation of surfaces, providing water proofing cement plaster, finishing

smooth/rough as required to the required line, level, curing, finishing,

guarantee for the water tightness of the water proofing treatment etc.

45.4.2. Preparation of Surface : The surface to receive water proofing

treatment shall be thoroughly cleaned of scales, laitance, set mortar etc. for

receiving water proofing treatment, and necessary Preparation of the surface

for providing water proofing treatment shall be done by the contractor. If any

honey combs are observed in beams and slabs of Bath and W.C., the same

shall be grouted with cement slurry mixed with water proofing compound and

the cracks and crevices, filled with injection method.

45.4.3. Sequence of Treatment : All cutting and chasing in the floor and walls

for plumbing work shall be done by the plumbing agency. Water proofing

agency shall then provide CETROOF or equivalent approved cement based

water proofing treatment consisting of cement plaster treatment mixed with

the water proofing compound according to the recommended specifications of

the waterproofing agency. The thickness of water proof plaster shall be about

35 mm. on floor area of the depression and about 25 mm. thick on the vertical

surface of walls/concrete surface in case of sunken slabs, upto the finished

floor level. The thickness shall be about 18 mm. for the remaining wall height

upto 600 mm. from finished floor level.

The plumbing agency shall then lay and fix the pipes, W.C. pans, traps etc.

without disturbing the water proofing treatment. However, the joints of water

supply and waste connections including holes drilled for clamps shall be

treated by water proofing agency.

Waterproofing agency shall then fill-in the depression in the floor with their

‘CETROOF’ or equivalent approved waterproof brick bat coba with the

admixture of waterproofing compound according to waterproofing agency’s

specification and process, which should be furnished in writing to the

Engineer-in-Charge for effective supervision of completeness of the process

while executing the works.

45.4.4. Finishing : The surface of the exposed plaster shall be finished smooth

with neat cement. The plaster surface where tiling is to be provided as well as

brick bat coba filling where flooring to be provided, shall be finished to proper

line, level, plane and plumb to receive the floor/dado finish. Curing of the

waterproofing treatment shall be carried out for 14 days.

45.4.5. Testing and Guarantee : The contractor shall test the surface where

waterproofing treatment is provided for the bone dry condition by filling with

water inside the depressed plastered portion. No wet patches or leaks shall

appear on he surrounding plastered walls or at the underside of the slabs.

The testing shall be carried out to the entire satisfaction of the Engineer-in-

Charge. The contractor shall furnish guarantee in the Proforma as per

Appendix D for the waterproofing treatment for maintaining the underside of

the waterproofed surface in bone dry condition for a period of minimum ten

years. During this period, contractor shall attend to all leakages, defects etc.

if noticed, free of cost, starting his work of checking up and rectification with

in a weeks time from the date of receipt of information about such leakages

Page 190: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 190 of 307

etc. by him.

The contractor shall submit the guarantee bond on appropriate stamp paper

and as per the enclosed proforma.

45.4.6. MODE OF MEASUREMENT :

i. Waterproof plaster shall be computed by taking the length and breadth of the

area actually plastered correct upto two decimal places of a metre. No

deduction shall be made for W.C. pans, pipes etc. in the measurement.

ii. The filling with waterproof brick bat coba shall be computed by noting the

levels and dimensions of the filled up depression before and after the filling,

upto two decimal places of a metre and also no deductions shall be made for

W.C. pans, pipes etc.

45.5. CEMENT BASED WATERPROOFING OF ROOF TERRACES :

45.5.1. General : The waterproofing treatment shall be essentially a cement

based waterproofing treatment similar to that of M/s. India Waterproofing

Companies CETROOF or any other equivalent approved waterproofing

treatment. The waterproofing treatment shall consist of providing cement

slurry mixed with waterproofing compound, at desired proportions including

grouting the cracks and crevices with cement slurry mixed with waterproofing

compound, laying brick bats over cement mortar bedding to the required

slopes for roof drainage, filling and grouting the joints with cement mortar,

finishing the surface smooth/chequered with cement plaster mixed with

waterproofing compound etc. as directed.

45.5.2. Preparation of Surfaces : All the rubbish, debris and other materials left

over by other agencies will be got removed by the Department through other

agencies. After removal of this rubbish, debris etc., the surface to receive the

waterproofing treatments shall be thoroughly cleaned with wire brushes

including removing of scales and laitance, set mortar etc. by the waterproofing

contractors. If any honey combing including cracks and crevices are observed

at column junctions/and elsewhere, the same shall be grouted with cement

slurry mixed with approved waterproofing compound.

45.5.3. Treatment : The waterproofing treatment shall be generally as per

manufacturers own specifications, method and procedure. A typical cross

section of the waterproofing treatment shall generally consist of the following:

i) Applying cement slurry mixed with waterproofing compound for the entire

surface to be treated.

ii) Laying of broken brick bat of required thickness over cement mortar bedding

to give proper roof drainage, grouted with cement mortar with waterproofing

compound.

iii) Laying of jointless cement based waterproofing cement mortar layer of average

thickness as specified in the item.

iv) Final rendering to give a smooth finish of cement colour with false lines at 300

x 300 mm. or nearer convenient dimensions. Tenderer shall give complete

Page 191: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 191 of 307

details of waterproofing treatment proposed by him, in writing viz. details

including roof fill material, waterproofing compound, minimum and maximum

thickness etc. for effective supervision of the departmental Engineers, while

the work is executed at site.

The contractor shall ensure that sufficient slope for effective roof drainage is

provided within the average thickness of waterproofing treatment proposed by

the contractor. In case the average specified thickness of treatment exceeds,

the fact shall be specifically brought to the notice of the Engineer-in-Charge,

before adopting the extra thickness.

The rain water down take pipes if any, shall be fixed by the other agency prior

to commencement of waterproofing operation. Curing of the finished surface

by ponding shall be done for 7 days at least.

45.5.4. Testing and Guarantee :

The contractor shall test the surface for the bone dry condition by ponding

water over roof for minimum seven days period to the entire satisfaction of the

Engineer-in-Charge. Alternately, the curing of the finished surface done by

ponding of water on the entire surface for seven days, can also be used for

testing water tightness. After a period of two months, once again the roof

should be ponded with water to check its efficiency of waterproofing treatment

against leakage. The contractor shall furnish guarantee in the proforma as per

Appendix D for the waterproofing treatment provided by them, for maintaining

the under side of the roof in bone dry condition for a minimum period of ten

years.

During this period, the contractor shall be liable to attend all the leakages,

defects etc. if noticed, free of cost, starting his work of checking and

rectifications within a weeks time from the date of receipt of intimation of such

leakages etc. by him.

45.5.5. MODE OF MEASUREMENT :

Net area in square metre of the roof measured in between the side walls, i.e.

plan dimensions including rounded junctions, kerbs, Parapets where

waterproofing treatment provided etc. shall be measured for payment. No

deduction shall be made for openings upto 0.02 sqm such as rain water outlets

etc., but the same shall be finished as directed by the Engineer-in-Charge. The

rate shall include the cost of labour, materials, scaffolding etc. and shall cover

the cost of rounding of junctions etc. which will not be measured separately.

Brick bat filling done under this item will not be measured separately and is

deemed to be included in the waterproofing treatment for roof with an average

thickness of 115 mm.

* * *

46. RAILING, BALUSTERS AND NEWELS :

46.1. SCOPE OF WORK AND GENERAL : The item refers to supplying and fixing in

position composite hand railing for staircase, open area, balcony, corridor etc. at

different floors, levels and locations.

Page 192: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 192 of 307

46.2. MATERIALS : The class and quality of wood to be used for hand railing and

workmanship shall comply with the requirements specified in wood work wrought

and put up and also comply with the I.S. specifications. M.S. balusters, grills, M.S.

flat frame work and runners to be used in hand railing, their quality, workmanship

etc. shall comply with requirements specified in manufacture of M.S. grills, and

standard practice adopted in fabrication of structural steel work and also comply

with I.S. specification.

46.3. SAMPLES : Before taking up fabrication and erection on mass scale, the

sample of railing materials being used etc. shall be got approved by the Engineer-in-

charge.

46.4. FABRICATION : The fabrication of wooden hand rail shall follow the standard

specification for wood work. The wooden handrail shall be in single piece per flight

panel, moulded, shaped and finished to required dimensions as shown in drawing

and as directed by the Engineer-in-charge. The hand railing shall be secured

perfectly to line, slope and level to M.S. flat runners, balusters, newels and posts.

M.S. grill, balusters, M.S. flat frame work fabricated as per the drawing and shall be

strictly according to the specifications specified in manufacturing of M.S. grills and

structural steel work. M.S. balusters, newels, M.S. flat frame work and posts as the

case may be, shall be fabricated in a workman like manner.

46.5. FIXING/ERECTION : M.S. Balusters, newels, posts, M.S. flat frame work

manufactured as per drawing and as per approved sample, shall be firmly fixed in

the pockets left for fixing of balusters or weld to main steel of waist slab or landing

slab or weld to the inserts left for fixing of balusters, posts etc. as shown in the

drawing. Necessary cover plates at the base of the balusters shall be provided after

grouting the balusters duly kept in position. The hand railing shall follow the

inclination of stair in case of stair-case and shall be perfectly in line, level and

plumb for all other railings. Any damage caused to treads/risers while fixing of

balusters, posts, railings etc., the damaged tread and riser shall be removed and

replaced by new ones at no extra cost. Railing shall be joined in lengths with plain

butt joints, dowelled and held together by hand rails, bolts, clamps and M.S. frame

work.

46.6. MODE OF MEASUREMENT : Hand railing shall be measured for payment in

running meters. The length shall be measured along the top centre line of the hand

rail and shall be measured between ends of balusters, newels posts as the case may

be upto two places of a decimal. Rate to include fabrication, leaving suitable

pockets, grouting the same, fixing, all labour, materials, transporting, painting,

polishing, finishing, scaffolding if necessary and as described in the schedule of

quantities.

* * *

47. DISMANTLING AND DEMOLITION :

47.1. SCOPE OF WORK :

The work envisaged under this sub-head is for dismantling and demolition of brick

masonry in cement/lime mortar, reinforced cement concrete works, removing

wooden chowkhats of doors, wooden or steel windows.

Page 193: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 193 of 307

47.2. GENERAL :

The term Dismantling implies carefully taking up or down and removing without

damage. This shall consist of dismantling one or more parts of the building as

specified or shown on the drawings.

The term Demolition implies taking up or down or breaking up. This shall consist of

demolishing whole or part of work including all relevant items as specified or shown

on drawings.

47.3. PRECAUTIONS :

Necessary propping, shoring and/or underpinning shall be provided for the safety of

the adjoining work or property, which is to be left in tact, before dismantling and

demolishing is taken up and the work shall be carried out in such a way that no

damage is caused to the adjoining work or property.

Wherever required, temporary enclosures or partitions shall also be provided.

Necessary precautions shall be taken to keep the dust- nuisance down as and when

necessary.

Dismantling shall be commenced in a systematic manner. All materials which are

likely to be damaged by dropping from a height or demolishing roofs, masonry etc.,

shall be carefully dismantled first. The dismantled articles shall be passed by hand

where necessary and lowered to the ground and not thrown. The materials then be

properly stacked as directed by the Engineer-in-charge.

All materials obtained from dismantling or demolition shall be the property of the

Government unless otherwise specified and shall be kept in safe custody until

handed over to the Engineer-in-charge.

Any serviceable material, obtained during dismantling or demolition shall be

separated out and stacked properly as indicated by the Engineer-in-charge within a

lead of 150 m. or as specified in the item. All under serviceable materials, rubbish

etc. shall be disposed off as directed by the Engineer-in-charge.

47.4. TREATMENT :

All the dismantled area shall be rendered clean off all debris, dust etc. The sides of

jambs, sills, soffits etc. of the openings if any, after taking out doors and window

chowkhats, unless and otherwise to be treated, shall be plastered in C.M. 1:3 with

neeru finish to render true sides, corners, edges etc.

47.5. MODE OF MEASUREMENT :

47.5.1. Brick Masonry & R.C.C. Works : The measurement of brick masonry

with or without plaster/painting shall be taken correct to a centimeter and

volume calculated in cubic metres upto two places of decimal.

47.5.2. Doors and Windows : Dismantling of doors and windows (wooden or

steel) shall be enumerated. Removal of chowkhats (frame works) shall include

(unless otherwise separately mentioned for removing shutters only), the

removal of shutters along with architraves, beadings, fittings and fastenings

Page 194: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 194 of 307

along with frames.

47.5.3. Roof Terracing : Dismantling of roof waterproofing treatment shall be

measured in square metre area. .Length and breadth shall be measured

correct to a centimeter between Parapets. No separate measurement shall be

taken for gola and khurrah etc.

47.6. RATES :

The rate shall include cost of all such operations mentioned above including

necessary labour, materials, transport, scaffolding, stacking the serviceable

materials, disposing the unserviceable materials within the lead specified, all as

directed by the Engineer-in-charge.

48. Providing and fixing in position UV resistant X-structure/multiwall/multicell

Polycarbonate sheet (Lexan Thermoclear of GE Plastics or equivalent 1200 mm width

and max length upto 12.0 m, including UV resistant coating on both sides, providing

specially designed serrated polycarbonate clamping section at all longitudinal joints

(Parallel to span) on supporting member, fixing to box purlins/runner using specially

designed stainless steel clamps and fasteners SS304 grade,(or) specially designed

anodised aluminium clamping section with EPDM/Neo prene gaskets to be located

on supporting member, the fasteners to be fixed on pre drilled or self drilled hole, all

fixing to be completely water tight. etc. complete as per manufacturer specifications.

* * * *

49. AUTOCLAVED CELLULAR (AREATED) CONCRETE BLOCK MASONRY

Scope of Work : The work covered under this specifications pertains to procurement

of best quality locally available or locally manufactured precast AAC concrete solid

block and workmanship in building walls of various thickness in strict compliance

with the specifications and applicable drawings.

Material: Precast cement concrete solid blocks shall be of best quality locally

available/ manufactured at factory and should be approved by the Engineer-in-

Charge before incorporation in the work. The ingredient and the cement concrete

used shall confirm to relevant I.S. as stipulated in specification for cement concrete

works herein before.

Minimum crushing strength of the AAC blocks shall be 5 N/ sqmm. at 28th day after

curing and dry density shall be not less than 651-750 kg/cum. The type of the bond

to be adopted will be decided by the Engineer-in-Charge but vertical joints shall be

staggered. The thickness of the blocks shall be 100 mm, 150 mm & 200 mm and the

proportion used in making the blocks shall be as per IS code. The blocks shall be

cured well at least for 14 days before incorporation in to the work. The cement

mortar for concrete blocks masonry shall be 1:4 and joints shall not be more than

10 mm. thick.

Workmanship and Mode of Measurement: The workmanship and mode of

measurement shall be as stipulated in the specification for brick work as applicable

stated earlier and AAC block masonry with 140 mm. thick block shall be measured

in sqm. nearest to two places of decimals of a meter. The rate quoted shall include

Page 195: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 195 of 307

cost of all materials, labour including form work in casting the blocks, curing,

transporting, handling, hoisting the blocks to proper level, curing masonry etc.

complete.

Mode of measurement: All AAC blocks masonry walls shall be measured in Sqm.

All opening in AAC block work for doors, windows and ventilators shall be deducted

to get the net quantity of actual work done. Opening or chases required for P.H. or

electrical inserts less than 0.1 sqm. And bearing of precast concrete members shall

not be deducted. No extra payment shall be made for extra work involved in making

the above opening or placement.

50. KALZIP ROOFING

The roofing system manufacturers shall be certified with Under Writer Laboratories (UL-

90) for wind uplift & ISO Certificate (ISO 9001) . Installer to submit the above alongwith

the Offer.

Installer must submit Certificate from manufacturer as authorised installer of the roofing

system.

Installer must submit Certificate from manufacturer as authorised installer of the roofing

system. And must submit list of such similar Aluminum standing seam roofs for

minimum 5 projects in India having roof area more than 3,000 m2 each.

Installer should submit necessary documents, like photographs & completion

certificates, TDS certificate of the earlier projects as proof for qualification.

Installer should offer a 15 years warranty for material and leakage warranty of 10 years.

Installer must have carried out aluminium welding for openings in aluminium standing

seam roofing systems and should submit photographs & certificate as a proof of

expertise.

Installer should submit all detailed drawings required for the project.

Installer to submit certificates of training from the Manufacturer's training facility for its

key personnel in - Project execution, Quality, Design & General management.

Supply and fixing of KingZip SF, 65/400 Self Supported Secret Fix ROOFING SYSTEM in

0.9 mm thick in Marine Grade AA 3004 Aluminium Alloy comprising of the following

layers:

1. Top Layer - The topmost profiled sheeting of aluminium KingZip SF 65/400 self

supported roof system manufactured from Aluminium alloy AlMnlMg1 Quality AA 3004,

in accordance with B209M/ BS-EN-485-2:1995 minimum material thickness of 0.90mm

with 60µm Durobond finish in accordance with BS-EN-1396: 2007 finish including

Accessories. Colour as per Architect`s choice. The profile should have Architectural micro

ribs between every 24 mini ribs of 1.5 mm to provide additional strength at the pan. The

support halters shall be manufactured from extruded aluminium alloy 6082 T6 in

accordance with BSEN 755 part 2. Each aluminium halter shall be coupled with a 6mm

thick black polyamide thermal barrier base pad. The material properties shall be as

follows:

Page 196: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 196 of 307

Ultimate tensile strength: minimum 200 N/mm2, 0.2% Proof Stress: min 185 N/mm2,

Modulus of elasticity: 70,000 N/mm2. King Zip SF to be laid in Single Length to meet the

requirements of the building geometry (straight sheet) and fixed on Aluminum Clip/

Halter and which is fixed to steel top hat through with SS-304 screws. 1) Detail

structural load calculation report to be submitted by the manufacturer based on wind

load as per IS 875 and screw pull out force. Approved Makes : KINGSPAN / BEMO /

SANKYO.

2. Insulation Layer - Rockwool Insulation of 100 mm thickness x 60kg/m3 density. K-

value 0.038 W/mK as per standard ASTM C-518. Fire classification as per BS 476: Part

6&7 / EN-1350-1 / UL-273. MAKE- ROXUL / ROCKWOOL.

3. Vapour Control Layer – Double sided aluminium foil with 170 microns thickness.

4. Bottom Sheet – Supply & Fixing of bare Galvalume profile sheet of 1000-1015 mm

effective cover width and 28-35 mm height ribs with subtle square fluting in the five pan

at 200-250 mm centre-to-centre. The feed material is manufactured out of nominal 0.47

mm Total Coated Thickness (TMT), Hi-strength steel with min. 550 MPa yield strength,

metallic hot dip coated with Aluminium-Zinc alloy (55% Aluminium, 45% Zinc) as per AS

1397 - Zincalume/ Galvalume (Make- Tata bluescope / Jindal) AZ150 (Min. 150

gms/sq.mt total on both sides) Fixed to the purlins with steel screws (Make- Buildex /

Corroshiled) at 500mm spacing.

51. Steam Bath:

Machine - Highly durable enclosure with argon gas welded stainless steel boiler with

slopped bottom, tested at 5 Kg/ sq. cm, Steam Boiler Insulation in 50mm thick LRB

mineral wool Boiler Enclosure made in 16 SWG MS in exclusively chosen powder coated

shades with proper lowers for free air circulation, Long life Low Watt Density stainless

steel 316 Industrial immersion heaters with faster & more efficient heating systems.,

Electronically Micro based controlled automatic water feed with “LOW “or “NO WATER”

cut-off systems. ,Pressure relief valve set at 3 kg /cm2, Built in water filter, Failsafe

Imported thermostatic with high limit control inside the boiler. All SS / Brass / Chrome

fittings. ,Exclusive control panel with a higher safety factor, greater reliability and lesser

maintenance using colored conductors and silver tipped Siemens contactors for years of

trouble free “ ON-OFF” operations, Automatically pressure flushes tank every time unit is

shut off (Auto Servicing)

Control panel - Personalized Control Panel, Digital Control Steam Function With

Temperature and time setting, Reliable Anti-Interference Circuit Design, Feather Touch

membrane switch Control, lluminated Timer easy to use, Digital Timer display preset 0

to 99 mint, Highly Processed Circuit Design, Digital Steam Room Thermostatic Controller

range 25° deg to 68° deg, High Limit Controller systems, Illuminated System Function

Indication, Auto Flush Facility Powered Drain, Auto Service, Abs Body

Plumbing & Electrical - Supply and fixing of G.I. „C‟ Class pipes and fittings for Main

water supply to the boiler, steam boiler to steam room and from steam boiler to nearest

nhani trap or galli trap. Supply and fixing of Main Switch (Through ELCB + MCB) and

armored cable. Installation of above equipment, testing and commissioning.

Page 197: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 197 of 307

LIST OF MATERIALS OF APPROVED BRAND AND/OR MANUFACTURER

Sr.n

o

Description Approved make

1 Cement 53 Grade / 43 Grade

Gujarat Ambuja (Silicate), ACC

(Suraksha), Ultra-tech, Birla Plus

(Grasim), Vasavadatta (Birla Shakti)

2 White Cement Birla / J.K. or equivalent

3 Mild & TOR Steel Sail, Tisco, Rashtriya Ispat Nigam or

equivalent

4 Structural steel SAIL/TATA/JRINL/IISCO/ Vizag

5 AAC blocks Ultratech/ Ascolite/ Siporex/Godrej &

Boycee

6 Synthetic plaster Renovo, Ruff & Tuff, Spectrum, Oikos

7 Lustre oil paint Nerolac / ICI/ Asian.

8 Emulsion paint Nerolac/ ICI/ Asian make.

9 Apex Ultima Nerolac/ ICI/ Asian make.

Apex ultima protek Nerolac/ ICI/ Asian make.

10 Texture paint Ruff & Tuff – Verticle Asian Paint –

Rough Tex – Verticle Scratch

11 PU paint Nerolac/ ICI/ Asian make.

12 Epoxy paint Epoxy/Dulux/Berger

13 Vermiculite spray Proma spray

14 Vitrified tiles Matt or polished RAK /

Euro/KAJARIA/Somany/Jhonson

15 Granite First quality ruby red / jet black / light

grey Galaxy granite of approved quality

and

Colour ( SOUTH INDIA )

16 Agglomerate Composite Euro/Nitco/Classic/CMC/Asian/Johns

Page 198: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 198 of 307

Marble on

17 Italian Marble classic/ nitco/ elegance

18 Rubber flooring Sandick

19 GRC (Glass Reinforced

Concrete)

Birla

20 Timber C.P seasoned teakwood of approved

quality for lipping, beading, framing

etc.

21 Laminated sheet Formica/Decolam/ Greenlam/

Neoluxe/ /Marino

22 Plywood Anchor / Green ply /Century

23 Veneer Anchor / Green ply / Century / Euro

24 Melamine polish Asian paint / ICI/ NEROLAC/

25 Duco paint MRF / ICI / ASIAN

26 Adhesive Fevicol

27 Modular doors & partitions Greenlam/Merino

28 Corian Dupont

29 Glass wool Rockwool/Twiga

30 Blinds Hunter Douglas, Mac, Vista, Technifab,

Ferrari

31 Wallpaper Arte/Marshall /ego /softek/Elementi

32 Frosted film 3M

33 Hardware fittings

i) Hinges Butt

Stainless Steel (14g) powder

coated hinges with screw

Nettle fold screws/palladium

size 5" x 11/4'' or as specified

Jyoti / Palladium/Haffle/Kich

ii) Mortise lock - Brass or

Stainless steel mortise

lock of 6 lever 75mm width,

all

Hafele / Yale / Dorset / Godrej/Euro

Page 199: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 199 of 307

locks to be provided in one

cabin shall be of common key

and 5 such common keys

shall

be provided to the client.

iii) Tower bolts - Stainless steel

and brass

Jyoti / Palladium/Haffle/Kich

iv) Door closers Efficient gadget dc 2000 model /

DORMA /Sevax (black anodised)/Steel

finish/Haffle/Hettich

v) Floor spring Dorma/Sevex/Ozone

vi) Panic handle DORMA/Haffle

viii) Patch fittings Dorma/kich/Haffle/Hettich

ix) Floor spring Dorma / Ozone

x) Door handle Kich/Neki/Haffle/Hettich/Ozone

34 Movable panels DORMA & Doors & doors

35 Flush doors Century/Anchor or equivalent

36 Aluminium windows Jindal, Hindalco,

37 DGU Glass Saint gobain/Asahi/Modi

38 Stainless Steel Kich

39 Polycarbonate sheets GE, Lexan, Danpalon, polygal

40 Gypsum India gypsum

41 Water proofing chemicals CICOP no.1, Sunanda, CET proof

42 Polymer Sunanada/ROFF/Basf

43 False ceiling Fibre-Indian

Gypsum/Armstrong/Nitoobo

Gypsum–India Gypsum/Boral

44 Aluminium perforated ceiling Hunter Douglas

45 Flagstone Vyara

46 Lift Hyundai/Kone

47 Chairs Godrej, Durian, Wipro

Page 200: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 200 of 307

48 Dining set Urban ladder

49 Coffee table Godrej

50 Sofa Urban ladder, Godrej, Durian

51 Steam generator Maverick/Maitreyee

52 Gym Equipment Life fitness/Precore/Proline fitness

Page 201: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 201 of 307

TECHNICAL SPECIFICATION FOR PLUMBING WORKS

SECTION-01: BASIS OF DESIGN

BASIS OF DESIGN

The Plumbing, Sanitary & Drainage System for the project is designed keeping in view the

Technical aspects below.

CONCEPT OF THE SYSTEM

The following services are envisaged for the complex:

Domestic water supply through Gravity system for making water available at the

residual pressure 0.5 to 2.0 kg / sq.cm. The pressure at the inlet of fixture shall be

limited to 2.5 Kg/cm2.

Sewage and Sullage collection system based on IS:1742 and ASPE standards for

domestic drainage.

Sewage / Effluent Treatment Plant comprising of preliminary, primary, biological and

tertiary treatment for recycling of the effluent. The treated effluent shall be used for

flushing water required and for make-up to the cooling tower for air conditioning and of

DG sets, for gardening / irrigation purpose.

Storm / Rain water drainage system from various levels of the building and

disposal to available municipal storm water drain.

Separate and independent garden hydrant for horticulture operation, using treated

effluent recycled for external / non-guest areas, and use of domestic water for internal

courtyard and water bodies, etc.

Rainwater harvesting including Recharging ground water and storing roof top rain

water. Reuse of stored rain water for Domestic or flushing consumption as per Consultant

guidelines.

WATER STORAGE & DISTRIBUTION SYSTEM

Water Requirement

The water requirement for the project is proposed to be based on the provisions of IS:1172

and prevalent practice. The estimated requirement of water per day for the Complex is

based on the number of users and other services.

Source of Water

It is expected that part of the daily domestic water requirement for

the Complex shall be through municipal mains supply. Provision of

tanker water fill feasibility shall also be made.

Water Distribution

The water distribution for cold water supply for the Complex shall be

designed on principle of zoning to ensure availability of adequate

residual head at user outlet. Provision of pressure reducing station

and non-return valve shall be made for effective and efficient water

distribution in the Complex.

Appurtenant

Page 202: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 202 of 307

Following components shall be included in the water supply system for efficient

functioning:

Isolation valves at strategic points.

Non Return valves for backflow prevention.

Automatic air vent at each of the high point.

Drain valve at each of the low point.

Strainer.

Cross connection.

vii. Pressure Reducing valve where abnormally high pressure is to be reduced.

xi. Pressure Gauge.

xii. Anchor block / thrust block.

SEWAGE, SULLAGE AND STORM WATER

The soil and waste shall be carried down in separate independently vented pipes.

Two pipe drainage systems shall be adopted as per NBC (Part-IX). Provision of vertical

vent shall also be made for hygiene, safety consideration and to avoid foul smell entering

through trapped gully in WC and Urinal trap. Provision of grease trap shall be made for

waste water from Kitchen.

Design Limitations

The system is designed considering the following:

a. High thrust developed at soil & waste pipe connections.

b. Termination of vent cowl at terrace level.

c. Provision of adequate slope for horizontal header pipes for achieving self-cleansing

velocity in the pipes.

d. Provision of cleanout plug and Rodding eye.

e. Minimum diameter of Soil pipe as 110 mm and Waste pipe as 75mm.

WORKMANSHIP

The workmanship shall be best of its kind and shall conform to the specifications,

as below or Indian Standard Specifications in every respect or latest trade practices and

shall be subject to approval of the Owner’s Site Representative. All materials and/or

Workmanship which in the opinion of the Owner’s Site Representative / Architect /

Consultant is defective or unsuitable shall be removed immediately from the site and

shall be substituted with proper materials and/or workmanship forthwith.

MATERIALS

All materials shall be best of their kind and shall conform to the latest Indian

Standards.

Page 203: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 203 of 307

All materials shall be of approved quality as per samples and origins approved by

the Owner’s Site Representative / Architect / Consultants.

As and when required by the Owner’s Site Representative / Consultant, the

contractor shall arrange to test the materials and/or portions of works at his own cost to

prove their soundness and efficiency. If after tests any materials, work or portions or work

are found defective or unsound by the Owner’s Site Representative / Consultant, the

contractor shall remove the defective material from the site, pull down and re-execute the

works at his own cost to the satisfaction of the Owner’s Site Representative / Consultant.

To prove that the materials used are as specified the contractor shall furnish the Owner’s

Site Representative with original vouchers on demand.

SECTION-02 : SANITARY FIXTURES

SCOPE

The scope of this section consists of but is not necessarily limited to supply, installation,

testing and commissioning of following items:

a. Sanitary appliances and fixtures for toilets.

b. Chromium plated brass fittings

c. Stainless steel sinks

d. Accessories e.g. towel rods, toilet paper holders, soap dish, liquid soap dispensers,

towel rails, coat hooks etc.

e. Hand driers, drinking water fountains etc.

Whether specifically mentioned or not the Contractor shall provide for all appliances and

fixtures all fixing devices, nuts, bolts, screws, hangers as required.

GENERAL REQUIREMENT

Sanitary appliances and fixtures for toilets, chromium plated brass fittings, stainless steel

sinks, bathroom accessories like towel rods, toilet paper holders, soap dish, liquid soap

dispensers, towel rails coat hooks etc and mirrors, hand driers, drinking water fountains

etc as listed in the relevant items in the Schedule of. All sanitary fixtures and fittings

shall be stored under covered roof and handled carefully to prevent any damage.

All appliances, fixtures and fittings shall be provided with all such accessories as are

required to complete the item in working condition whether specifically mentioned or not

in the Schedule of Quantities, specifications, drawings. Accessories shall include proper

fixing arrangements, brackets, nuts, bolts, washers, screws and required connection

pieces.

The sanitary fixtures and fittings shall be installed at the correct assigned position as

shown on the drawings and as directed by the Architect / Owner’s Site Representative

and shall fully meet with the aesthetic and symmetrical requirements as demanded by the

Architect / Interior Designer

All fixtures and accessories shall be fixed in accordance with a set pattern matching the

tiles or interior finish as per Architect requirements. Wherever necessary, the fittings shall

be centered to dimensions and pattern as called for.

Page 204: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 204 of 307

All appliances, fittings and fixtures shall be fixed in a neat workmanlike manner true to

level and to heights shown on the drawings and in accordance with the manufacturers

recommendations. Care shall be taken to fix all inlet and outlet pipes at correct positions.

Faulty locations shall be made good and any damage to the finished floor, tiling, plaster,

paint, insulation or terrace shall be made good by the Contractor at his own cost.

Fixtures shall be mounted rigid, plumb and true to alignment.

All materials shall be rust proofed; materials in direct or indirect contact shall be

compatible to prevent electrolytic or chemical (bimetallic) corrosion.

Wall flanges shall be provided on all walls, floors, columns etc. wherever supply and

disposal pipes pierce through them. These wall caps shall be or chromium plated brass

fittings and the receiving pipes and shall be large enough to cover the punctures properly.

Sanitary appliances, subject to the type of appliance and specific requirements, shall be

fixed in accordance with the relevant standards and the following:

i. Contractor shall, during the entire period of installation and afterwards protect the

appliances by providing suitable cover or any other protection so as to absolutely prevent

any damage to the appliances until handing over (The original protective wrapping shall

be left in position for as long as possible)

ii. The appliances shall be placed in correct position or marked out in order that pipe

work can be fixed or partially fixed first.

iii. The appliance shall be fixed in a manner such that it will facilitate subsequent

removal if necessary.

iv. The appliance shall be securely fixed. Manufacturer's brackets and fixing methods

shall be used wherever possible. Compatible rust-proofed fixings shall be used. Fixing

shall be done in a manner that minimize noise transmission.

v. Appliances shall not be bedded (e.g. WC pans, pedestal units) in thick strong

mortar that could crack the unit (e.g. ceramic unit)

vi. Pipe connections shall be made with demountable unions. Pipe work shall not be

fixed in a manner that it supports or partially supports and appliance.

vii. Appliances shall be fixed true to level firmly fixed to anchor or supports provided

by the manufacturer and additional anchors or supports where necessary.

Sizes of sanitary fixtures given in the Specifications or in the Schedule of Quantities are

for identification with reference to the catalogues of make considered. Dimensions of

similar models of other makes may very within + 10% and the same shall be provided and

no claim for extra payment shall be entertained NOR shall any payment be deducted on

this account.

The contractor shall fix all plumbing fittings such as water faucets, shower fittings,

mixing valves etc. in accordance with manufacturer’s instructions and connect to piping

system. The contractor shall supply all fixing materials such as screws, rawl plugs,

unions, collars, compression fittings etc., as required.

Page 205: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 205 of 307

Joints / gaps between all sanitary appliances / fixtures and the floor / walls shall be

caulked with an approved mildew resistant sealant, having antifungal properties, of

colour and shade to match that of the appliances / fixture and the floor / wall to the

extent possible.

Water Closet

Providing and fixing in position white vitreous china pedestal type water closet

(European type) single piece with integrated cistern of "Jaquar" make model no. VGS-

WHT-0207P of size 840x390x720 (mm) with seat and lid, integrated flushing cistern with

manually controlled device (push type flush valve), with all fittings and fixtures

Each WC shall be provided with 110 mm dia (OD) PVC Pan Connector connecting

the ceramic outlet of WC to downtake pipe. As per MSR 100-390.

Wash Basin

Providing and fixing under Counter washbasin of Rectangular shape & size 200 x

490 x 375 mm of Jaquar make, model no.-CNS-WHT-WB01 with C.I. brackets, 32mm

C.P. brass waste of standard pattern, including painting of fittings and brackets. As per

MSR 100-410.

Sinks

Providing and fixing in position Stainless steel kitchen sink without drain board A

ISI 304 (18/8) as per IS 13983 610mm x 510mm depth 200mm with cast iron brackets

and stainless steel plug 40mm in painting of fittings and brackets. As per MSR 90-460

MOCKUP AND TRIAL ASSEMBLY

The installation of the Sanitary fixtures and fittings shall be as per the shop

drawings approved by the Architect/Consultant.

The contractor shall have to assemble at least one set of each type of sanitary

fixtures and fittings in order to determine precisely the required supply and disposal

connections. Relevant instructions from manufacturers shall be followed as applicable.

This trial assembly shall be developed to determine the location of puncture holes,

holding devices etc. which will be required for final installation of all sanitary fixtures and

fittings. The above assembly shall be subject to final approval by the Architect / Interior

Designer.

The fixtures in the trial assembly can be re-used for final installation without any

additional payments for fixing or dismantling of the fixtures.

SUPPORTING AND FIXING DEVICES

The contractor shall provide all the necessary supporting and fixing devices to

install the sanitary fixtures and fittings securely in position. The fixing devices shall be

rigidly anchored into the building structure. The devices shall be rust resistant and shall

be so fixed that they do not present an unsightly appearance in the final assembly. Where

the location demands, the Architect may instruct the contractor to provide chromium

plated or other similarly finished fixing devices. In such circumstances the contractor

Page 206: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 206 of 307

shall arrange to supply the fixing devices and shall be installed complete with appropriate

vibration isolating pads, washers and gaskets.

FINAL INSTALLATION

The contractor shall install all sanitary fixtures and fittings in their final position in

accordance with approved trial assemblies and as shown on drawings. The installation

shall be complete with all supply and waste connections. The connection between

building and piping system and the sanitary fixtures shall be through proper unions and

flanges to facilitate removal/replacement of sanitary fixtures without disturbing the built

in piping system. All unions and flanges shall match in appearance with other exposed

fittings.

Fixtures shall be mounted rigid, plumb and to alignment. The outlets of water

closet pans and similar appliances shall be examined to ensure that outlet ends are

butting on the receiving pipes before making the joints. It shall be ensured that the

receiving pipes are clear of obstruction. When fixtures are being mounted, attention shall

be paid to the possibility of movement and settlement by other causes. Overflows shall be

made to ensure that necessary anchoring devices have been provided for supporting water

closets, wash basins, sinks and other appliances.

PROTECTION AGAINST DAMAGE

The contractor shall take every precaution to protect all sanitary fixtures against

damage, misuse, cracking, staining, breakage and pilferage by providing proper wrapping

and locking arrangement till the completion of the installation. At the time of handing

over, the contractor shall clean, disinfect and polish all the fixtures and fittings. Any

fixtures and fittings found damaged, cracked chipped stained or scratched shall be

removed and new fixtures and fittings free from defects shall be installed at his own cost

to complete the work.

MEASUREMENT

Rate for fixing only of sanitary fixtures accessories, CP fittings shall etc. include all items,

and operations stated in the respective specifications and bill of quantities and nothing

extra is payable.

Rates for all items under specifications Para above shall be inclusive of cutting holes and

chases and making good the same, CP screws, nuts, bolts and any fixing arrangements

required and recommended by manufacturers, testing and commissioning and making

good to the satisfaction of the Owner’s Site Representative.

TESTING AND ACCEPTANCE

All appliances, fixtures and fittings shall be tested before and after installation. Water

seals of all appliances shall be tested. The contractor shall block the ends of waste and

ventilation pipes and shall conduct an air test.

The sanitary fixtures form the final terminal units of the water supply and drainage

system and should meet the performance needs as a terminal unit. Each fixture shall be

inspected for scratches or chippings and alignment before acceptance.

Page 207: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 207 of 307

All tests shall be conducted at each and every fixture except for flush valves which shall

be at the lowest and highest test connections to be made on each riser/downtake. The

contractor shall make the temporary valve connections which shall be plugged with a

brass plug after validation.

SECTION-03 : WATER SUPPLY

SCOPE

The scope of this section comprises the supply, installation, testing and

commissioning of piping network for water supply for internal & external services as

follows:

a Bore well / Municipal / Tanker Water supply.

b. Drinking Water Supply.

c. Flushing Water Supply

d. Washing

f. Connection to various mechanical equipments to be supplied and installed by the

other specialist contractors.

The Contractor shall make all necessary application and arrangements for his work

to be inspected by the Local Authorities.

The Contractor shall be solely responsible for obtaining the Authorities approval of

his works prior to the handing over of the complete water supply / distribution

installation to the Owner.

PIPING MATERIALS

The piping system shall consist of:

CPVC CTS SDR 11.0 as per ASTM D 2846 piping from 15 mm to 50 mm & Schedule 40

as per ASTM F441 from 65 mm to 100 mm for cold & hot water supply. The sizes are

specified in the Schedule of Quantities and the makes are specified in Special Conditions

of Contract. Pipes shall include GI pipe fittings wherever required as stated by

Consultant.

Unplasticised Polyvinyl Chloride pipes and Specials conforming to Sch 40 & Sch 80 as per

ASTM D-1785. The sizes are specified in the Schedule of Quantities and the makes are

specified in Special Conditions of Contract.

For any internal works, the CPVC pipes / galvanized iron / UPVC pipes and fittings shall

be embedded in the wall chase or run on the floor/ceiling unless otherwise specified. No

unsightly exposed runs shall be permitted. The sizes are specified in the Schedule of

Quantities and the makes are specified in Special conditions of contract.

Page 208: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 208 of 307

CPVC Pipes & Fittings

The pipes shall be CPVC (Chlorinated Poly Vinyl Chloride) material for hot & cold

water supply piping system with pipes as per CTs SDR -11 at a working pressure of 320

PSI at 23 deg C and 80 PSI at 82 deg.C, using G.I fittings i.e. Tees, Elbows, Couples,

Unions, Reducers, Brushing etc. including transition fittings (connection between CPVC &

Metal pipes / GI) i.e. Brass adapters (both Male & Female threaded and all conforming to

ASTM D-2846 with only CPVC solvent cement conforming to ASTM F-493, with clamps /

structural metal supports as required /directed at site including cutting chases & fitting

the same with cement concrete / cement mortar as required, including painting of the

exposed pipes with one coat of desired shade of enamel paint. All termination points for

installation of faucets shall have brass termination fittings. Installation shall be to the

satisfaction of manufacturer & Project Manager. Pipes from 65 mm to 150 mm dia shall

be Schedule 40 for CWC & Schedule 80 for HWS / HWR.

i. Joining Pipes & Fittings

a. Cutting:

Pipes shall be cut either with a wheel type plastic pipe cutting or hacksaw blade and care

shall be taken to make a square cut which provides optimal bonding area within a joint.

b. Deburring / Beveling:

Burrs and fittings should be removed from the outside and inside of pipe with a pocket

knife or file otherwise burrs and fittings may prevent proper contact between pipe and

fittings during assembly.

c. Fitting Preparation:

A clean dry rag/cloth should be used to wipe dirt and moisture from the fitting sockets

and tubing end. The tubing should make contact with the socket wall 1/3 or 2/3 of the

way into the fitting socket.

d. Solvent Welded Application:

Only CPVC solvent cement confirming to ASTM-F493 should be used for joining pipe with

fittings. An even coat of solvent cement should be applied on the pipe end and a thin coat

inside the fitting socket, otherwise too much of cement solvent can cause clogged water

ways.

e. Assembly:

After applying the solvent cement on both pipe and fitting socket, pipe should be inserted

into the fitting socket within 30 seconds, and rotating the pipe ¼ to ½ turn while

inserting so as to ensure even distribution of solvent cement with the joint. The

assembled system should be held for 10 seconds (approximately) in order to allow the

joint to set up.

An even bead of cement should be evident around the joint and if this bead is not

continues remake the joint to avoid potential leaks.

Set & Cure times:

Solvent cement set and cure times shall be strictly adhered to as per the below mentioned

table.

Minimum Core prior to pressure testing at 150 PSI

Page 209: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 209 of 307

Ambient Temperature during

Core period

Pipe Size

½ " - 1" 1.¼" - 2"

Above 15 deg. C 1 Hr 2 Hrs

2 Hrs 4 Hrs

Below 4 deg C 4 Hrs 8 Hrs

Special care shall be exercised when assembling flow guard systems in extremely

low temperature (below 4°C) or extremely high temperature (above 45°C) In extremely hot

temperatures, make sure that both surfaces to be joined are till wet with cement solvent

when putting them together.

f. Testing

Once an installation is completed and cored as per above mentioned

recommendations, the system should be hydrostatically pressure tested at 150 psi (10

Bar) for one hour. During pressure testing, the system should be fitted with water and if a

leak is found, the joint should be cut out and replacing the same with new one by using

couplers.

ii. Transition of Flow guard CPVC to Metals

When making a transition connection to metal threads, special Brass / plastic transition

fitting (Male and female adapters) should be used. Plastic threaded connections should

not be over torqued Hard tight puts one half turn should be adequate.

iii. Threaded Sealants

Teflon tape shall be used to make threaded connections leak proof.

iv. Solvent Cement

CPVC solvent cement conforming to ASTMF 493 should be used for joining pipe with

fittings and valves. Flow guard CPVC cement solvent have a minimum shelf life of 1 year.

Aged cement solvent will often change colour or being to thicken and become gelatinous

or jelly like and when this happens, the cement should not be used. The cement solvent

should be used within 30 days after opening the company’s seal and tightly close the seal

after using in order to avoid its freezing. The freezed cement solvent should be discarded

immediately and fresh one should be used. The CPVC solvent cement usage should be

adhered to as given in table below

v. Hangers and supports

For Horizontal runs, support should be given at 3 foot (90 cm) intervals for diameters of

one inch and below and at 4 foot (1.2m) intervals for larger sizes.

Hangers should not have rough or sharp edges which come in contact with the tubing.

Supports should be as per the below mentioned table:

Size of Pipe 21°C 49°C 71°C 82°C

Inch Ft. Ft. Ft. Ft.

½” 5.5 4.5 3.0 2.5

¾” 5.5 5.0 3.0 2.5

1” 6.0 5.5 3.5 3.0

1¼” 6.5 6.0 3.5 3.5

Page 210: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 210 of 307

1½” 7.0 6.0 3.5 3.5

2” 7.0 6.5 4.0 3.5

SCHEDULE – 40

Recommended Support spacing (in feet)

Nom. Pipe Size Temperature oC

(In) (mm) 23 38 49 60 71 82

2 ½ 65 7 ½ 7 7 6 ½ 6 3 ½

3 80 8 7 7 7 6 3 ½

4 100 8 ½ 7 ½ 7 ½ 7 6 ½ 4

6 150 9 ½ 8 8 7 ½ 7 4 ½

8 200 9 ½ 8 8 7 ½ 7 5

SCHEDULE - 80

Recommended Support spacing (in feet)

Nom. Pipe Size Temperature oC

(In) (mm) 23 38 49 60 71 82

2 ½ 65 8 7 ½ 7 ½ 6 ½ 4 ½ 4

3 80 8 8 7 ½ 7 4 ½ 4

4 100 9 9 8 ½ 7 ½ 5 4 ½

6 150 10 9 ½ 9 8 5 ½ 5

Galvanised Iron Pipes & Fittings

The pipes shall be galvanised mild steel welded (HFS), (ERW) or and (HFW) screwed

and socketed conforming to the requirements of IS:1239.

The pipes under this standard are designated by their nominal bore and are further

classified as Light, Medium and Heavy depending upon their wall thickness. All the three

categories of pipes may be used for conveying water depending upon pressure conditions.

Sockets of these pipes are designated by respective nominal bore of the pipe.

Joints: The threads of all screwed and socket pipes shall conform to IS:554. The

minimum length of thread in Light pipes shall be 80 percent of that specified in IS:554.

Each pipe shall be supplied with one socket.

Galvanising: The Galvanising shall conform to IS:4736, the hot dip zinc coating shall be

uniform, adherent reasonably smooth and free from such imperfections as flux, ash and

drop inclusions, bare patches, black spots, pimples, lumpiness, runs, rust strains, bulky

white deposits and blisters. The pipes and sockets shall be cleanly finished, well

galvanised in and out and free from cracks, surface flaws laminations and other defects.

All screw threads shall be clean and well cut. The ends shall be cut cleanly, and square

with the axis of the pipe.

Hydraulic test: Each pipe shall be hydraulically tested at manufacturer’s work to

withstand a test of

Pressure of 5 Mpa.

Page 211: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 211 of 307

Marking: The different classes of pipes shall have 75mm colour bands when arrived

on site. The following colour bands shall be provided.

Light ------------- Yellow

Medium ------------- Blue

Heavy ------------- Red

Fittings: The fittings shall be malleable iron screwed fittings and shall conform to

IS:1879. comply with all the requirements of the pipes . The fittings are classified as

Light, Medium and Heavy. The sizes of pipes and fitting is specified in the schedule of

quantities

Laying And Jointing Of GI Pipes

The galvanised pipes and fittings shall run in wall chase or ceiling or as specified.

The fixing shall be done by means of standard pattern holder bat clamps keeping the

pipes about 1.5 cm clear of the wall where to be laid on surface. Where it is specified to

conceal the pipes, chasing may be adopted for pipes fixed in the shafts, ducts etc. there

should be sufficient space to work on the pipes with the usual tools. As far as possible,

pipes may be buried for short distances provided adequate protection is given against

damage and where so required special care to be taken at joints. Where directed by the

Owner’s Site Representative, pipe sleeves shall be fixed at a place the pipe is passing

through a wall or floor for reception of the pipe and allow freedom for expansion and

contraction and other movements. In case of pipe is embedded in walls or floors it shall be

painted with anticorrosive bitumastic paints of approved quality. Under the floors the

pipes shall be laid in layer of sand filling.

Galvanised iron pipes shall be jointed with threaded and socket joints, using threaded

fittings. Care shall be taken to remove any burr from the end of the pipes after threading.

Teflon tape, White lead or an equivalent jointing compound of proprietary make shall be

used, according to the manufacturer’s instructions, with a grommet of a few strands of

fine yarn while tightening. Compounds containing red lead shall not be used because of

the danger of contamination of water. Any threads exposed after jointing shall be painted

with bituminous paint to prevent corrosion.

Electric Welded steel pipes conforming to IS:3589 for 150mm to 2000mm Nominal

Diameter:

The pipes shall be made from Steel plates or strips by butt welding longitudinally

or spirally. The pipes shall be butt welded by employing any of the methods such as a)

Electric Resistance Welding and b) Electric Fusion Arc welding.

Minimum specified thickness of pipes as per IS:3589:

Nominal diameter Minimum specified thickness of

pipes (mm)

150 to 300 4.0

Above 300 to 500 5.0

Above 500 to 600 6.0

Above 600 to 850 7.0

Above 850 to 1200 8.0

Above 1200 to 2000 10.0

Page 212: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 212 of 307

Joints: The Joints shall be a) Plain or bevelled ends for field butt welding and b)

Joints with sleeve joints or swelled and plain ends for welding.

PIPING INSTALLATION SUPPORT (VALID FOR GI PIPING )

Tender drawings indicate schematically the size and location of pipes. The

Contractor, on the award of the work, shall prepare detailed working drawings, showing

the cross-sections, longitudinal sections, details of fittings, locations of isolating and

control valves, drain and air valves, and all pipe supports. He must keep in view the

specific openings in buildings and other structure through which pipes are designed to

pass.

Piping shall be properly supported on , or suspended from , on stands, clamps,

hangers as specified and as required. The Contractor shall adequately design all the

brackets, saddles, anchor, clamps and hangers, and be responsible for their structural

stability.

Pipe work and fittings shall be supported by hangers or brackets so as to permit

free expansion and contraction. All accessories and ancillaries of support system such as

brackets, saddles, clamps, hangers etc. shall be hot dip galvanized after fabrication.

Further to permit free movement of common piping, support shall be from a common

hanger bar, fabricated from galvanised steel sections.

Pipe hangers shall be provided at the following maximum spacings:

Pipe Dia

(mm)

Hanger Rod Dia

(mm)

Spacing between Supports

(m)

Up to 25

6

2

32 to 50

8

2.7

65

10 2.7

80 to 100

12

2.7

125 to 150

16

3.6

200 to 300

19

5.3

Insulated piping shall be supported in such a manner as not to put undue pressure on

the insulation. 14 gauge metal sheet shall be provided between the insulation and the

clamp, saddle or roller, extending at least 15 cm. on both sides of the clamps, saddles or

roller.

All pipe work shall be carried out in a proper workman like manner, causing

minimum disturbance to the existing services, buildings, roads and structure. The entire

piping work shall be organized in consultation with other agencies work, so that area can

be carried out in one stretch.

Page 213: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 213 of 307

Cut-outs in the floor slab for installing the various pipes area are indicated in the

drawings. Contractor shall carefully examine the cut-outs provided and clearly point out

wherever the cut-outs shown in the drawings, do not meet with the requirements.

Pipe sleeves, larger diameter than pipes, shall be provided wherever pipes pass

through walls and slab and annular space filled with fiberglass and finished with retainer

rings.

The contractor shall make sure that the clamps, brackets, saddles and hangers

provided for pipe supports are adequate or as specified / approved by Consultants. Piping

layout shall take due care for expansion and contraction in pipes and include expansion

joints where required.

All pipes shall be accurately cut to the required sizes in accordance with relevant

BIS codes and burrs removed before laying. Open ends of the piping shall be closed as the

pipe is installed to avoid entrance of foreign matter. Where reducers are to be made in

horizontal runs, eccentric reduces shall be used for the piping to drain freely. In other

locations, concentric reduces may be used.

All buried pipes for CWS shall be cleaned and coated with two coats of bitumen

and then wrapped with two layers of 400 micron polythene sheet coating.

Automatic air valves shall be provided at all high points in the piping system for

venting. All valves shall be of 15mm pipe size and shall be associated with an equal size

isolation ball valve. Automatic air valves shall also be provided on hot water risers.

Discharge from the air valves shall be piped through a galvanized steel pipe to the nearest

drain or sump. All pipes shall be pitched towards drain points.

Pressure gauges shall be provided as shown on the approved drawings and include in Bill

of Quantities. Care shall be taken to protect pressure gauges during pressure testing.

Temperature gauge as specified shall be provided at the hot water supply and return and

as shown on drawings and included in Bill of Quantities.

These gauges are available in dials 50 mm, 63 mm, 101 mm, 203 mm, 254 mm and 304

mm upto 10,000 lbs. per square inch or equivalent Kg/cm2 in imported and indigenous

makes.

Equilibrium Ball Valves or Ball (Float) Valves: These valves are required to

maintain a constant level in service reservoirs and steel storage tanks. The float follows

the water level in the reservoir and permits the valve to admit additional water on a falling

level and less water on rising level and when the over flow level is reaches, the valve

closes itself completely. In addition to small size of the valves ranging from 15 mm dia,

these are available upto 450 mm dia with cast iron body, with bronze liner and gun metal

seat ring. These are available for static pressure of 5 lbs to 100 lbs per square inch,

flanges faced and drilled to BS 10, table C, tested to 250 pounds per square inch. These

are manufactured to BS-1212 Part-2 and IS 1703 (Also refer under chapter 17 for more

details).

The expansion joints are made of grey cast iron fitted with brass bushes, grease packing,

flanges drilled to BS or IS Specifications, tested to 250 PSI to various pipe sizes.

Page 214: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 214 of 307

Gunmetal Gate Valves (Peet Valves)-IS 778 : The use of gun metal gate valves or

peet valves in the mild steel pipes is the same as the use of sluice valves in cast iron

pipes. Generally manufactured sizes correspond to mild steel pipe sizes, i.c. 15mm,

20mm, 25mm, 32mm, 40mm, 50mm, 65mm, 80mm and 100mm.

Gun metal gate valves are of solid wedge type screwed bonnet, integral seat, inside screw,

non rising stem, provided with a sturdy hand wheel for operation. These conform to

Indian Standard 778. The gate valves to this Indian Standard are available in all three

classes of IS 778, both screwed female and flanged ends. Screwed end valves are in the

form of hexagon to facilitate wrenching. Flanged valves have their flanges machined flat

faced, drilled or undrilled as specified (Also refer under Clause 17.10(3), for weights and

other details).

The testing of these vales is done as per clause 10 of IS 778 for hydraulic test pressures

as indicated in table 281.

Test Records : Records must be made of tests including date of test, identification of

piping tested, test pressure and approval of the testing authority. These records need not

be retained after completion of the piping installation if the testing authority certifies that

the piping has been pressure tested as require

TESTING

The Contractor shall notify the Architect three days in advance of any test so that

the Architect can witness the tests if he so wishes.

All water supply system shall be tested to hydrostatic pressure test of at least one and a

half (1.5) times the maximum pressure but not less than 10Kg/Sq.cm for a period of not

less than 8 hours. All leaks and defects in joints revealed during the testing shall be

rectified and got approved at site by retest. Piping required subsequent to the above

pressure test shall be retested in the same manner.

System may be tested in sections and such sections shall be entirely retested on

completion.

The Contractor shall make sure that proper noiseless circulation of fluid is achieved

through the entire piping network of the system concerned. In case of improper

circulation, the contractor shall rectify the defective connections. He shall bear all

expenses for carrying out the above rectifications including the tearing up and refinishing

of floors and walls as required.

In addition to the sectional testing carried out during the construction, contractor shall

test the entire installation after connections to the overhead tanks or pumping system or

mains. He shall rectify all leakages and shall replace all defective materials in the system.

Any damage done due to carelessness, open or burst pipes or failure of fittings, to the

building, furniture and fixtures shall be made good by the contractor during the defects

liability period without any cost.

After commissioning of the water supply system, contractor shall test each valve by

closing and opening it a number of times to observe if it is working efficiently. Valves

Page 215: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 215 of 307

which do not effectively operate shall be replaced by new ones at no extra cost and the

same shall be tested as above.

A test register shall be maintained and all entries shall be signed and dated by

Contractor(s) and Owner’s site representative.

DISINFECTION OF PIPING SYSTEM AND STORAGE TANKS

Before commissioning the water supply system, the contractor shall arrange to disinfect

the entire system as described in the succeeding Paragraph.

The water storage tanks and pipes shall first be filled with water and thoroughly flushed

out. The storage tanks shall then be filled with water again and disinfecting chemical

containing chlorine added gradually while tanks are being filled to ensure thorough

mixing. Sufficient chemical shall be used to give water a dose of 50 parts of chlorine to

one million parts of water.

If ordinary bleaching powder is used, the proportions will be 150 gm of power to 1000

liters of water. The power shall be mixed with water in the storage tank. If a proprietary

brand of chemical is used, the proportions shall be specified by the manufacturer. When

the storage tanks is full, the supply shall be stopped and all the taps on the distributing

pipes are opened successively working progressively away from the storage tank. Each tap

shall be closed when the water discharged begins to smell of chlorine. The storage tank

shall then be filled up with water from supply pipe and added with more disinfecting

chemical in the recommended proportions. The storage tank and pipe shall then remain

charged at least for three hours. Finally the tank and pipes shall be thoroughly flushed

out before any water is used for domestic purpose.

The pipe work shall be thoroughly flushed before supply is restored.

STERILIZATION OF MAINS

After the pipe work has been tested and approved, but before it is coupled, it shall

be sterilized with a solution of chloride of lime.

CUTTING CHASES IN MASONARY WALLS

Cold water distribution pipes to fixtures and equipment exposed to view in the

bathrooms, kitchens, and sanitary compartments shall be chased into walls or floors or

placed in wall cavities. The Contractor shall be responsible for cutting all notches, chases,

and recesses in walls and floors and only a diamond cutter shall be used. The maximum

size of conduit or pipe permitted to be concealed in floor slabs shall be 32 mm diameter

unless otherwise approved by the Architect.

The chases upto 7.5 x 7.5 cm shall be made in the walls for housing GI pipes etc. These

shall be provided in correct positions as shown in the drawings or directed by the

Architects. Chases shall be made by chiseling out the masonry to proper line and depth.

After the pipes etc are fixed in chases, the chases shall be filled with cement mortar 1:2:4

or as may be specified, and made flush with the masonry surface. The concrete surface

shall be roughened with wire brush to provide a key for plastering.

Page 216: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 216 of 307

Where pipes pass through beams or structural walls, subject to the approval of the

Structural Consulting Engineer, the Contractor shall ensure that sizes and locations of

openings required are formed in when the relevant beams or walls are cast.

VALVE CHAMBERS

Provision of suitable brick masonry chambers in cement mortar 1:5 (1 cement : 5

coarse sand) on cement concrete foundations 150 mm thick 1:5:10 mix (1 cement:5 fine

sand : 10 graded stone aggregate 20 mm nominal size ) with 15 mm thick cement plaster

inside and outside finished with a plaster inside and outside finished with a floated coat

of neat cement inside with cast iron surface box approved by fire brigade including

excavation, back-filling complete shall be made.

VALVES

All valves (gate, globe, check, safety) shall be of gun metal suitable for the

particular service as specified. All valves shall be of the particular duty and design as

specified. Valves shall either be of screwed type or flanged type, as specified, with suitable

flanges and non-corrosive bolts and gaskets. Tail pieces as required shall be supplied

along with valves. Gate, globe and check valves shall conform to Indian Standard IS:776

and non-return valves and swing check type reflux to IS:5312.

Butterfly valve

The butterfly valve shall be suitable for waterworks and rated for Pressure

requirement as mentioned in the Schedule of quantities.

The body shall be of cast iron to IS:210 in circular shape and of high strength to

take the water pressure . The disc shall be heavy duty cast iron with anti corrosive epoxy

or nickel coating.

The valve seat shall be of high grade elastomer or nitrile rubber. The valve is closed

position shall have complete contact between the seat and the disc throughout the

perimeter. The elastomer rubber shall have a long life and shall not give away on

continuous applied water pressure. The shaft shall be EN 8 grade carbon steel.

The valve shall be fitted between two flanges on either side of pipe flanges. The

valve edge rubber shall be projected outside such that they are wedged within the pipe

flanges to prevent leakages.

Ball valve

The ball valve shall be of floating ball design with PN 16 bar rating. The body shall

be of Died nickel plated Brass with ends screwed to BSP. suitable for test pressure of pipe

line. The valve shall be internally threaded to receive pipe connections.

The ball shall be made from brass and machined to perfect round shape and

subsequently chrome plated. The seat of the valve body-bonnet gasket and gland packing

shall be of Teflon.

Page 217: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 217 of 307

The handle shall be provided with PVC jacket. The handle shall also indicate the

direction of ‘open’ and ‘closed’ situations. The gap between the ball and the teflon packing

shall be sealed to prevent water seeping.

The handle shall also be provided with a lug to keep the movement of the ball valve

within 90°. The lever shall be operated smoothly and without application of any

unnecessary force.

Ball float valve

Ball valves with floats to be fixed in storage tanks shall consist of cast brass lever arm

having copper balls (26 SWG) screwed to the arm integrally. The copper ball shall have

bronze welded seams. The closing/opening mechanism incorporating the piston and

cylinder shall be non-corrosive metal and include washers. The size and construction of

ball valves and float shall be suitable for desired working pressure operating the supply

system. Where called for brass valves shall be supplied with brass hexagonal back nuts to

secure them to the tanks and a socket to connect to supply pipe.

Gun metal valve

Gun metal Valves shall be used for smaller dia pipes, and for threaded

connections. The Valves shall bear certification as per IS:778

Non-return valve

Non-Return valves shall be cast iron double flanged with cast iron body and

gunmetal internal parts conforming to IS:5312.

Pressure Gauge

The pressure gauge shall be constructed of die cast aluminium and stove

enamelled. It shall be weather proof with an IP 55 enclosure. It shall be a stainless steel

Bourden tube type pressure gauge with a scale range from 0 to 16 Kg / cm square and

shall be constructed as per IS:3524. Each pressure gauge shall have a siphon tube

connection. The shut off arrangement shall be by Ball Valve.

Calibration certificate shall be obtained and submitted for each pressure gauge.

CONNECTIONS TO VARIOUS MECHANICAL EQUIPMENT SUPPLIED BY OTHER

AGENCIES

All inlets, outlets, valves, piping and other incidental work connected with

installation of mechanical equipment supplied by other agencies all be carried out by the

contractor in accordance with the drawings, requirements for proper performance of

equipment, manufacturers instructions and the directions of the Owner’s site

representative / Architect. The equipments to be supplied by the other agencies consist

mainly for Kitchen, Back-of-the-House area and other similar areas. The work of

connections to the various equipments shall be effected through proper unions and

isolating valves. The work of effecting connections shall be executed in consultation with

and according to the requirement of equipment suppliers, under the directions of the

Owner’s site representative / Architect. The various aspects of connection work shall be

executed in a similar way to the work of respective trade mentioned elsewhere in these

specifications.

Page 218: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 218 of 307

MEASUREMENTS

The length above ground shall be measured in running meter correct to a cm for

the finished work, which shall include pipe and fittings such as coupling, bends, tees,

elbows, reducers, crosses, plugs, sockets, nipples and nuts, unions. Deductions for length

of valves shall be made. Rate quoted shall be inclusive of all fittings, clamps, cutting holes

chased and making good the same and all items mentioned in the specifications and Bill

of Quantities.

All pipes below ground shall be measured per linear meters (to the nearest cm) and

shall be inclusive of all fittings e.g. coupling, tees, bends, elbows, unions, deduction for

valves shall be made rate quoted shall be inclusive of all fittings, excavation, back filling

and disposal of surplus earth, cutting holes and chase and making good all item

mentioned in Bill of Quantities.

THRUST BLOCKS

In case of bigger pipes (80 mm dia and above), thrust blocks of cement concrete

1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate of 20 mm nominal size) shall be

constructed on all bends as directed by the Owner’s site representative.

MASONRY CHAMBER

i. All masonry chambers for stop cocks, sluice valves and meter etc. shall be built as

per supplied drawings.

ii. The excavation for chambers shall be done true to dimension and level indicated on

plans or as directed by the Owner’s site representative.

iii. Concrete shall be of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded

stone aggregate 40 mm nominal size.

iv. Brick shall be of class designation 75 in cement mortar 1:5 (1 cement : 5 fine sand)

v. Inside Plastering not less than 12 mm thick shall be done in cement mortar 1:3 (1

cement : 3 fine sand) finished with a floating coat of neat cement.

SHIFTING OF EXCAVATED SURPLUS MATERIAL

Contractor shall make his own arrangement to shift the surplus excavated material

within the site limits as directed by Owner’s site representative at free of cost within time

limit.

Page 219: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 219 of 307

SECTION-04: INTERNAL DRAINAGE (SOIL, WASTE, VENT & RAIN WATER PIPES)

SCOPE

The scope of this section comprises the supply, installation, testing and

commissioning of internal drainage services.

Work under this section shall consist of furnishing all labour, materials,

equipments and appliances necessary and required to completely install all soil, waste,

vent and rainwater pipes and fittings as required by the drawings, and given in the

schedule of quantities.

BASIC PIPING SYSTEM

The UPVC soil pipes shall be circular with a minimum diameter of 110mm for

Internal & 150/200 as per drawing for external. Pipes shall be fixed by means of stout GI

clamps in two sections, bolted together, built into the walls, wedged and neatly jointed as

directed and approved by the Owner’s site representative / Architect. All bends, branches,

swan neck and other parts shall conform to the requirement and standards as described

for the pipes. Pipes shall be rested against the walls on suitable wooden cradles. Local

authority regulations applicable to the installations shall be strictly followed.

Where indicated, the soil pipes shall be continued upwards without any diminution

in its diameter, without any bend or angle to the height shown in the drawings. Joints

throughout shall be made with molten lead as described under jointing of cast iron pipes.

Soil pipes shall be painted as provided under `painting'. The soil pipes shall be covered on

top with cast iron terminal outlets as directed and approved. All vertical soil pipes shall be

firmly fixed to the walls with properly fixed clamps, and shall as far as possible be kept

50mm clear of wall. Pipes shall be fixed, jointed and painted as described in installation of

soil, waste & vent pipes.

Every waste pipe shall discharge above the grating of properly trapped gully. The

contractor will ensure that this requirement is adequately met with. Wherever floor traps

are provided, it shall be ensured that atleast one wash is connected to such floor traps to

avoid drying of water seal in the trap. Ventilating pipes shall be UPVC, conforming to the

requirements laid down earlier. Anti-syphon vent pipes/relief vent pipes where called for

on the drawings shall be of cast iron or galvanised mild steel pipes as specified. The pipes

shall be of the diameter shown on the drawings.

All traps on branch soil and waste pipes shall also be ventilated at a point not less

than 300mm from their highest part and on the side nearest to the soil pipe or waste

pipes.

Access doors for fittings and clean outs shall be so located that they are easily

accessible for repair and maintenance. Any access panel required in the civil structure,

false ceiling or marble cladding etc. shall be clearly reported to the Owner in the form of

shop drawings so that other agencies are instructed to provide the same.

All the fittings used for connections between soil, waste and ventilation pipes and

branch pipes shall be made by using pipe fittings with inspection doors for cleaning. The

doors shall be provided with 3mm thick rubber insertion packing and when closed and

bolted shall be air and water tight.

Page 220: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 220 of 307

Where soil, waste and ventilating pipes are accommodated in shafts ducts,

adequate access to cleaning eyes shall be provided.

Head (starting point) of drains and sewage / waste water sumps (as and where

applicable) having a length of greater than 4 m upto it connection to the main drain or

manhole shall be provided with a 80 / 100 mm vent pipe.

PIPING MATERIALS ( Internal Drainage)

UPVC Pipes and Fittings

The pipes shall be round and shall be supplied in straight lengths with socketed

ends. The internal and external surfaces of pipes shall be smooth, clean, free from

groovings and other defects. The ends shall be cleanly cut and square with the axis of the

pipe. The pipes shall be designed by nominal diameter and shall confirming to IS:13592

Type B.

Fittings

Fittings shall be of the same make as that of pipes, injection moulded and shall

conform to Indian Standard.

Laying and Jointing

The pipes shall be laid and clamped to wooden plugs fixed above the surface of the

wall. Alternatively, plastic clamps of suitable designs shall be preferred. Provision shall be

made for the effect of thermal movement by not gripping or disturbing the pipe at

supports between the anchors for suspended pipes. The supports shall allow the repeated

movements to take place without abrasion.

Jointing for UPVC pipes shall be made by means of solvent cement for horizontal

lines and ‘O’ rubber ring for vertical line. The type of joint shall be used as per site

conditions / direction of the Owner’s site representative. Where UPVC pipes are to be

used for rain water pipes, the pipe shall be finished with GI adopter for insertion in the

RCC slab for a water proof joint complete as directed by Owner’s site representative.

Supports

UPVC pipes require supports at close intervals. Recommended support spacing for

unplasticised PVC pipes is 1500 mm for pipes 50 mm dia and above. Pipes shall be

aligned properly before fixing them on the wooden plugs with clamps. Even if the wooden

plugs are fixed using a plumb line, pipe shall also be checked for its alignment before

clamping, piping shall be properly supported on, or suspended from clamps, hangers as

specified and as required. The Contractor shall adequately design all the brackets,

saddles, anchors, clamps and hangers and be responsible for their structural sufficiency.

Pipe supports shall be primer coated with rust preventive paint.

Page 221: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 221 of 307

Repairs

While temporary or emergency repairs may be made to the damaged pipes,

permanent repairs shall be made by replacement of the damaged section. If any split or

chip out occur in the wall of the pipe, a short piece of pipe of sufficient length to cover the

damaged portion of the pipe is cut. The sleeve is cut longitudinally and heated sufficiently

to soften it so that it may be slipped over the damaged hard pipe.

PIPES HANGERS, SUPPORTS, CLAMPS ETC.

All vertical pipes shall be fixed by galvanized clamps and galvanized angle brackets

truly vertical. Branch pipes shall be connected to the stack at the same angle as that of

the fittings. No collars shall be used on vertical stacks. Each stack shall be terminated at

top with a cowl (terminal guard).

Horizontal pipes running along ceiling shall be fixed on galvanized structural

adjustable clamps of special design shown on the drawings or as directed. Horizontal

pipes shall be laid to uniform slope and the clamps adjusted to the proper levels so that

the pipes fully reset on them.

Contractor shall provide all sleeves, openings, hangers, inserts during the

construction. He shall provide all necessary information to the building contractor for

making such provisions in the structure as necessary. All damages shall be made good to

restore the surfaces.

All pipes clamps, supports and hangers shall be galvanized. Factory made

prefabricated clamps shall be preferred. Contractor may fabricate the clamps of special

nature and galvanize them after fabrication but before installation. All nuts, bolts,

washers and other fasteners shall be factory galvanized.

Clamps shall be of approved design and fabricated from MS flats (which shall be

galvanized after fabrication) of thickness and sizes as per drawings or contractor’s shop

drawings. Clamps shall be fixed in accordance to manufacturer’s details/shop drawings

to be submitted by the contractors.

When required to be fixed on RCC columns, walls or beam they shall be fixed with

approved type of galvanized expansion anchor fasteners (Dash fasteners) of approved

design and size according to load.

Structural clamps e.g.. trapeze or cluster hangers shall be fabricated by electro-

welding from MS structural members e.g. rods, angles, channels flats as per contractors

shop drawings shall be galvanized after fabrication. All nuts, bolts and washers shall be

galvanized.

Galvanized slotted angle/channel of approved sizes supports on walls shall be

provided wherever shown on shop drawings. Angles/channels shall be fixed to brick walls

with bolts embedded in cement concrete blocks and to RCC walls with anchor fasteners

mentioned above. The spacing of support bolts on support members fixed horizontally

shall not exceed 1 m.

Page 222: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 222 of 307

INSTALLATION OF SOIL, WASTE & VENT PIPES

Soil, waste & vent pipes in shafts under the floors / suspended below slab shall

consist of cast iron pipes as described earlier. Waste pipes from bottle trap to floor/urinal

traps for wash basin, urinal and sink shall be GI pipes and fittings.

All Horizontal pipes running below the slab and along the ceiling, shall be fixed on

structural adjustable clamps, sturdy hangers of the design as called for in the drawings.

The pipes shall be laid in uniform slope and proper levels. All vertical pipes shall be truly

vertical fixed by means of stout clamps in two sections, bolted together, built into the

walls, wedged and neatly jointed. The branch pipes shall be connected to the stack at the

same angle as that of fittings. All connections between soil, waste and ventilating pipes

and branch pipes shall be made by using pipe fittings with inspection doors for cleaning.

Pipes shall be fixed in a manner as to provide easy accessibility for repair and

maintenance and shall not cause obstruction in shafts. Where the horizontal run off the

pipe is long or where the pipes cross over building expansion joints etc. suitable

allowance shall be provided for any movements in the pipes by means of expansion joint

etc. such that any such movement does not damage the installation in any way.

All cast iron pipes and fittings shall be jointed with drip seal / Best Quality pig lead

free from impurities conforming to standards.

Before jointing, the interior of the socket and exterior of the spigots shall be

thoroughly cleaned and dried. The spigot end shall be inserted into the socket right up to

the back of the socket and carefully centered by two or three laps of threaded spun yarn,

twisted into ropes of uniform thickness, well caulked into the back of the socket. No piece

of yarn shall be shorter than the circumference of the pipe. The jointed pipe line shall be

at required levels and alignment. The reminder of the socket is left for the lead caulking.

Where the gasket has been tightly held, a jointing ring shall be placed round the barrel

against the face of the socket. Molten Lead shall be poured to the remainder of the socket.

The depth of the lead joints for the cast iron pipes shall be 45mm for the pipes

upto 100mm dia and 50mm for the pipes beyond 100mm dia respectively.

The joint shall not be covered till the pipe line has been tested under pressure.

Rest of pipe line shall be covered so as to prevent the expansion and contraction due to

variation in temperature.

Rainwater Pipes

All open terraces shall be drained by rain water down takes with SWR pipes

conforming to IS:13985 Type A category.

Rainwater down takes are separate and independent of the soil and waste system

and will discharge into the underground storm water drainage system of the complex.

Rainwater in open courtyards shall be collected in catch basins and connected to

the Storm Water Drains.

Any dry weather flow from waste appliances, e.g. AHU’s pump rooms, waste water

sumps shall connected to sewers after traps and not in the storm water drainage systems.

Page 223: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 223 of 307

Balcony / Planter drainage

Wherever required, all balconies, terraces, planters and other frontal landscape

areas will be drained by vertical down takes or other type of drainage system shown on

the drawings and directed by the Project Manager.

TRAPS

Floor Traps

Floor traps where specified shall be siphon type full before P or S type having a

minimum 50 mm deep seal. The trap and waste pipes when buried below ground shall be

set and encased in cement concrete blocks firmly supported on firm ground or when

installed on a sunken RCC structural slab. The blocks shall be in 1:2:4 mix (1 cement : 2

coarse sand : 4 stone aggregate 20 mm nominal size).

Contractor shall provide all necessary shuttering and centering for the blocks. Size of the

block shall be 30 x 30 cms of the required depth.

Floor Trap Inlet /Hopper

Bath room traps and connection shall ensure free and silent flow of discharging water.

Where specified, contractor shall provide a special type of floor inlet fitting fabricated from

GI pipe, with one, two or three inlet sockets welded on side to connect the waste pipe. All

joint between waste hopper and CI inlet socket shall be drip seal/Lead Caulked. Inlet

shall be connected to a “P” trap. Floor trap inlet and the traps shall be set in cement

concrete blocks where burried in floors without extra charge. Floor trap for the shower

cubicle shall suit site and as per the approval of Owner’s site representative. All fabricated

hopper shall be hot dip galvanized.

Floor Trap Grating

Floor and urinal traps shall be provided with 100 – 150 mm square or round stainless

steel gratings, with frame and rim of approved design and shape or as specified in the

schedule of quantities approved by the Owner’s site representative.

Cleanout Plugs

Floor Clean Out Plug

Clean out plug for soil, waste or rain water pipes laid under floors shall be provided

near pipe junctions bends, tees, “Y” and on straight runs at such intervals as required as

per site conditions. Cleanout plugs shall terminate flush with the floor level. They shall be

threaded and provided with key holes for opening. Cleanout plugs shall be cast brass

suitable for the pipe dia. With screwed to a GI socket. The socket shall be drip seal

joined/ Lead Caulked to the drain pipes.

Cleanout on Drainage Pipes

Cleanout plugs shall be provided on head of each drain and in between at locations

indicated on plans or directed by Owner’s site representative. Cleanout plugs shall be of

Page 224: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 224 of 307

size matching the full bore of the pipe but no exceeding 150 mm dia CO plugs on drains

of greater diameters shall be 150 mm dia. Fixed with a suitable reducing adapter.

Floor cleanout plugs shall be cast brass.

Cleanouts provided at ceiling level pipe shall be fixed to a CI flanged tail piece. The

cleanout doors shall be specially fabricated from light weight galvanized sheets and angles

with hinged type doors with fly nuts, gasket etc. as per drawing.

PIPE SLEEVES

Pipe sleeves, next larger diameter than pipes shall be provided wherever pipes pass

through walls & slabs and annular space filled with fiberglass & finished with retainer

rings. All pipes shall be accurately cut to the required sizes in accordance with relevant

BIS codes and burrs removed before laying. Open ends of the pipe shall be closed as the

pipe is installed to avoid entrance of foreign matter.

PIPE PROTECTION

Cast iron soil and waste pipes under floor in sunken slabs and in wall chases

(when cut specially for the pipe) shall be encased in cement concrete 1:2:4 mix (1 cement

: 2 coarse sand : 4 stone aggregate of 12 mm size) 10 cm bed and around. When pipes are

running well above the structural slabs, the encased pipes shall be supported with

suitable cement concrete pillars of required height and size at intervals directed by the

Project Manager.

CUTTING AND MAKING GOOD

Pipes shall be fixed and tested as building proceeds. The contractor shall provide

all necessary holes, cutouts and chases in structural members as building work proceeds.

Wherever holes are cut or left originally they shall be made good with cement concrete

1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 20 mm nominal size) or cement

mortar 1:2 (1 cement : 2 coarse sand). Cured and the surface restored to original

condition.

PAINTING

Soil, waste, vent and rain water pipes in exposed location, in shafts and pipe space shall

be painted with two or more coats of ready mix oil paint to give an even shade. Before

painting all dust and extraneous matter shall be removed

Paint shall be of approved quality and shade. Where directed by the Owner’s site

representative pipes shall be painted in accordance with approved pipe colour code.

Pipe in chase shall be painted with two coats of bitumen paint, covered with polythene

tape and a final coat of bitumen paint. Exposed pipes shall be painted with synthetic

enamel paint after removing dust and extraneous matter.

C.I. Soil and waste pipes below ground and covered in cement concrete shall not be

painted.

TESTING

Testing shall be done in accordance with IS:1172 and IS:5329 except as may be modified

herein under.

Page 225: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 225 of 307

Entire drainage system shall be tested for water tightness and smoke tightness during

and after completion of the installation. No portion of the system shall remain untested.

Contractor must have adequate number of expandable rubber bellow plugs, manometers,

smoke testing machines, pipe and fitting work tests.

All materials obtained and used on site must have manufacturer’s hydraulic test

certificate for each batch of materials used on the site.

Before use at site all CI pipes shall be tested by filling up with water for at least 30

minutes. After filling, pipes shall be struck with a hammer and inspected for blow holes

and cracks. All defective pipes shall be rejected and removed from the site within 48

hours. Pipes with minor sweating may be accepted at the discretion of the Project

Manager.

Soil and waste pipes shall be tested in sections after installation, by filling up the stack

with water. All openings and connections shall be suitably plugged as approved by the

Project Manager. The total head in the stack shall be 4.5 m at the highest point of the

section under test. The period of test shall be minimum for 30 minutes or as directed by

the Project Manager. If any leakage is visible, the defective part of the work shall be cut

out and made good.

On completion of the work the entire installation shall be tested by smoke testing

machine. The test shall be conducted after the plumbing fixtures are installed and all

traps have water seal or by plugging the outlets with bellow plugs. Apply dense smoke

keeping the top of stack open and observe for leakages. Rectify or replace defective

sections.

After the installation is fully complete, it should be tested by flushing the toilets, running

atleast 20% of all taps simultaneously and ensuring that the entire system is self

draining, has no leakages, blockages etc. rectify and replace where required.

A test register shall be maintained and all entries shall be signed and dated by the

Contractor and the Project Manager or his representative.

All pipes in wall chase or meant to be encased or burried shall be hydro tested

before the chase in plastered or the pipe encased or burried.

LIST OF APPROVED MAKES

(Note: - Fittings with IS mark preferred)

S.

No.

Item IS Code & Type Manufacturer

1 GM gate, check,

globe valves

IS 778, Cl Danfoss, kirloskar, Audco

2 CI foot valve &

Strainer

IS 4038,single disc

lift type

NECO

3 CI NR valves IS 5312, single door,

swing check

NECO

4 Ball / Butterfly

Valve

IS 13095 Danfoss, Audco, C & R,

Kirloskar,Zoloto

5 ARV Jain, crispin,

Valmatics,Anergy,

6 Ceramic fittings Parryware,Kohler,Jaquar

7 CP brass ware

fittings (Cocks,

mixers etc)

Parryware,Kohler,Jaquar

Page 226: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 226 of 307

NOTE : Other materials should be of good quality, with IS mark if available, to be got

approved beforehand or shall be as per Client requirements. Sanitary Fixtures brands

may be as per Architect/Client choice.

8 CP Flush valve Nelson,

Jaquar,Kohler,Handware

9 CPVC / UPVC/PPR

/SWR pipes &

fittings

Astral, Supreme,

Prince(SMARTFIT,EASYFIT),

Finolex.

10 G.I ,C class heavy

duty pipes

IS :1239 TATA,Jindal

Page 227: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 227 of 307

TECHNICAL SPECIFICATIONS

ELECTRICAL WORK

Page 228: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 228 of 307

TECHNICAL SPECIFICATIONS

1 SCOPE:

The specifications given below pertain to the entire electrical installation work to be

carried out in the proposed Angre House (17th & 18th Floor) at Mazagon Dock shipbuilders

limited. The project comprises 17th & 18th floor House interior.

During normal times the power flowing through all the L.T Power cables will be the

normal power from the supply company.

Cables are also to be laid to general DBs (for lighting and Power loads). From Main L.T

panel cable shall be laid to Main Panel for A.C. to be located in terrace Area. This panel is

in the scope of this tender. From the said AC Panels power and control cables shall be

laid on suitable cable trays to respective Outdoor unit by the electrical contractor. The

cables shall then be terminated into the Outdoor unit installed by the A.C. contractor.

The outgoing cabling from the Main Panel for AC and from the outdoor unit is not in the

scope of this contract.

Point wiring is to be provided to all points in the Banquet Hall Area, VIP & VVIP rooms,

toilet blocks, Veg & Non Veg Pantry and Reception areas. Besides all of the above, this

tender covers providing wiring to outdoor lighting, earthing system and lightning

protection system.

Environmental Conditions:

• Maximum Temperature : 35° C

• Minimum Temperature : 18° C

• Humidity : 60%

• Height : MSL

1.0 Codes and Standards:

The design, manufacture and performance of equipment shall be as per all current

statutory regulations and safety codes in the locality where the equipment will be

installed. Nothing in these specifications shall be construed to relieve the vendor of

this responsibility.

1.1 General specification for Panels. 1.2 Construction:

The panel board shall be made from M.S. sheet steel 1.6 mm thick and shall be

folded and braced as necessary to provide a rigid support for all components. All

panels and covers shall be properly fitted and square with frames, and holds in the

panels correctly positioned. Self-threading screws shall not be used in the

construction of switchboard. The panel board shall be of totally enclosed design,

dust tight and vermin proof and extensible type. The circuit breaker shall be

mounted on a separate carriage arranged for horizontal isolation and horizontal

withdrawal. The bus bar shall be made of Aluminum flats and supported on rigid

epoxy support insulator and insulated. Two independent earth connections shall

be provided. The circuit breaker shall be provided with the necessary auxiliary

contacts for indication, control, interlocking or other purposes. Excluding the

Page 229: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 229 of 307

auxiliary contacts already used for the circuits, six spare sets of contacts with

three ‘NO’ and three ‘NC’ shall be left free in each unit. The equipment when

assembled shall form a neat and compact unit and shall be completed with all

supporting frame work, mounting channels, foundation bolts etc. and shall be

designed so as to insure complete inter-changeability of components from one

panel to another.

The design, manufacturing process and all the equipment & instruments

incorporated in the same shall comply with the latest Indian Standards set by

B.I.S. and particularly to the following:

BRIEF DESCRIPTION REFERENCE STAND

Switch gear General Requirements IS : 13947-1993

Factory Built Assemblies of Switch gear

and Control gear

IS : 8623

Miniature Circuit Breaker IS : 8828

HRC Cartridge fuse IS : 9224 (Part 2)

Current Transformers IS : 2705

Indicating Instruments IS : 1248

Bus bar Connections and Accessories IS : 5578, 11353

Code of Practice for Phosphate Iron & Steel IS : 6005

PVC Wires IS : 694

The above are minimum standards expected. The technical specifications

to follow and those given in schedule of quantities, if found to be more stringent as

compared to those listed above, then the more stringent specifications shall prevail.

1.3 SHEET METAL WORK

1.3.1 The panel boards frame shall be fabricated using suitable mild steel structural sections or pressed and shaped cold rolled sheet steel of thickness not less than 2.5 mm.

1.3.2 Frames shall be enclosed by cold rolled sheet steel of thickness not less than 2.0 mm. smoothly finished, leveled and free from flaws. Doors, top covers and partitions shall be made of cold rolled sheet steel of thickness not less than 1.6 mm. Stiffeners shall be provided wherever necessary.

1.3.3 As far as wall mountable panels incorporating only Miniature Circuit Breakers and R.C.C.B. & starters are concerned, the thickness of sheet still shall be 1.6 mm for enclosure and door

1.3.4 All panel edges and door edges shall be reinforced against distortion by rolling, bending or by the addition of welded reinforced members. Cut-outs shall be

Page 230: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 230 of 307

true in shape and devoid of sharp edges. The complete structure shall be rigid, self-supporting and free from vibration, twists and bends. Counter sunk screw shall be used for jointing.

1.4 PAINTING The panel manufacturer shall have in-house 7 tank process facility. The type

of painting will be as per the direction given in the preamble to the relevant

section of the schedule of quantities

(i) Sheet pretreatment (. phosphate coating) IS: 3618/1991/6005/1991. (ii) Preparing the surface. (iii) Applying the final paint (iv) Curing the paint (v) Testing the painted surface (vi) Providing peal able coating compound (vii) Effluent treatment and discharge of waste water

1.5 CONSTRUCTIONAL FEATURES

1.5.1 Switch gear shall be:

a) Indoor, floor mounted modular type (wall mounted wherever so

specified in schedule of quantities), Of vermin proof construction.

b) Provided with a metal still frame made of structural steel channel

section properly drilled for mounting the switch gear along with

necessary mounting hardware (hardware shall be zinc plated and

passivated).

c) Provided with gaskets all-round the perimeter of removable covers

and doors.

d) Provided with bus bar of adequate rating.

1.5.2 No equipment needing manual operation shall be located at a height less than 250 mm above floor level and exceed 2,100mm from floor level.

1.5.3 Cable alleys shall be provided with suitably hinged doors/cover. It shall be possible to safely carry out maintenance work on cable connections to any one circuit with the bus bar and adjacent circuits live. Adequate number of slotted cable support arms shall be provided for cleating the cables.

1.5.4 All doors shall be folded type. All covers and doors shall be provided with rubber gaskets.

1.5.5 Provision shall be made for insulating covers on outgoing terminals for protection against accidental touch.

1.5.6 Base Channel of ISMC-75 shall be provided in case of free floor standing panels.

1.5.7 Four Lifting Lugs per each shipping section shall be provided.

Page 231: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 231 of 307

1.5.8 Cable entry for all the panel will be at the bottom & cable outlet will be adequately provided.

1.6 DISTRIBUTION BOARDS 1.6.1 Scope

The scope of work shall cover the supply, installation, testing and

commissioning of lighting and power distribution boards including cable

sleeves, anchor fasteners etc. Associated minor civil works required for the

erection of the DB’s such as opening in wall etc. are also included in the scope

of this contract.

1.6.2 The Distribution Board shall comply with the latest edition of relevant Indian Standards and Indian Electricity Rules and Regulations. The following Indian standards shall be complied with:

Sr. Item Relevant IS Relevant IEC

1 General requirements for switchgear

and control gear for voltages not

exceeding 1000 V AC or 1200 V DC

IS: 4237

2 Switchgear bus bars, main connection

and auxiliary wiring, marking and

arrangement.

IS: 375

3 Terminal marking for electrical

measuring instrument

and their accessories.

IS: 8197

4 Miniature circuit breakers.

IS: 8828

1.6.3 Distribution Boards Distributions boards along with the controlling MCB’s or Isolator as shown

shall be fixed in a mild steel Box with hinged lockable door suitable for recessed

mounting in wall. Distribution boards shall be made of 18 SWG sheet steel with

hinged lockable spring loaded cover duly rust inhibited through a process of

degreasing, acid pickling, phosphating and powder coated to an approved

colour over a red oxide primer. The enclosure shall meet IP 43 rating.

All components shall be mounted on DIN rails and covered totally with a sheet

steel cover rendering it finger-safe. Access to the internal connections shall be

only through removing the cover sheet.

Three phase boards shall have phase to phase barriers and a wire channel

for internal wiring. All DB’s shall be internally prewired using copper

insulated high temperature PVC wires brought to a terminal strip of

appropriate rating for outgoing feeders.

Page 232: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 232 of 307

Conduit knockouts shall be provided as required/shown on drawings and

the entire board shall be rendered dust and vermin proof with necessary

sealing gaskets.

The distribution board shall have one main neutral and 3 separate sub -

neutral links, one for each phase of adequate capacity as per number of

outgoings per phase. The DB shall have earth bar(s) of adequate capacity as per

total numbers of outgoings of DBs. Two numbers separate earth terminals, (one

on each side) shall be provided on the outer body of DB for its body earthing.

The DB shall be supplied complete with cable ties, circuit identification labels

and few spare blanking plates.

1.6.4 DB Technical Specifications

No. of Ways: 4, 6, 8 & 12 ways

Type of Installation: Surface & Flush mounting

Colour/ Finish: RAL Grey (Semi Glossy)

Door Options: Reversible

Door Locking Options: Sliding Lock

Removable Gland Plates: Top & Bottom

Protection Level of Distribution Board: Advanced

Distribution Technique: Insulated Bus bar

Bus Bar Rating: up to 125A

Provision for Incomer slots: 8 Slots

Voltage Rating: 240/415V-,3 Phase/4 Wire

Incoming Options: Three Phase MCCB, MCB or RCCB or ISOLATOR

Outgoing Options: SP or TP or Both MCB

Neutral Bar Terminal Capacity: 25 mm2, Split on both sides

Earthing Bar Terminal Capacity: 25 mm2, Split on both sides

Ingress Protection (IP): IP43

Insulation Voltage(Ui): 690V

Frequency: 50Hz

Dielectric Strength: 2.5KV

Ambient Temperature: -5 °C to 40 °C

Distribution Board- Reference Standards: IS 8623; IS 13032

Page 233: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 233 of 307

1.7 BUSBARS

1.7.1 Switch gear shall be provided with three phase and neutral bus bar. Bus bar shall be of uniform cross section throughout their length and up to the incoming terminals of the incoming feeder circuit breaker.

1.7.2 Bus bars shall be made of high conductivity tinned Aluminum/copper. (as shall be stated in the respective item of the bill of quantities) and shall be provided with at-least the minimum clearances in air as per applicable standards for a 500 V, 3 phase system.

1.7.3 All bus bar and bus-taps shall be insulated with close fitting sleeve of hard, smooth, dust and dirt free plastic insulation of high dielectric strength (450 V/mil) to provide a permanent high dielectric non-aging and non-tracking protection; impervious to water, tropical conditions and fungi. The insulation shall be non-inflammable and self-extinguishing and in fast colours to indicate phases. The joints shall be insulated in such a way as to provide for accessibility of contact bolts for maintenance. The di-electric strength and properties shall hold good for the temperature up to 900 C. If the insulating sleeve should be coloured, bus bar shall be color-coded throughout the length and not with coloured bands.

1.7.4 Bus bar shall be adequately supported and braced to withstand the stresses due to the specified short circuit currents. Bus bar supports shall be made of Hylam sheets, glass reinforced moulded plastic material, Permali wood or cast resin.

1.7.5 Separate supports shall be provided for each phase of the bus bars. If a common support is provided for all three phases, ant tracking barriers shall be incorporated.

1.7.6 Bus bar joints shall be complete with high tensile steel bolts and Belleville washers and nuts. Bus bars shall be thoroughly cleaned at the joint locations and a suitable contact grease shall be applied just before making a joint.

1.7.7 The Bus bars shall have uniform cross section with 30ºC rise above ambient and with color coded PVC sleeves. The maximum current density for copper bus bar shall be 1.6amp/mm² in case of all Panels. The maximum current density for aluminum bus bar shall be 0.8amp/mm² in case of all Panels. The Branch bus bars shall have 75% of aggregate capacity of feeder connected. The Neutral and Earthing Bars shall have cross-sectional areas not less than 50% of Phase Bus bar. In case bus bars are mentioned as 4 pole then the neutral bus bar shall have same cross section as that of phase bus bar.

1.8 MCCB’s

The MCCB’s shall conform to the latest applicable standards (IS: 13947)

MCCBs in AC circuits shall be of TP/TPN/FP construction arranged for

simultaneous manual closing and opening. Operating mechanism shall be

quick-make, quick-break and trip-free type. The ON, OFF and TRIP positions

Page 234: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 234 of 307

of the MCCB shall be clearly indicated and visible to the operator. Operating

handle for operating MCCBs from door of board shall be provided.

The instantaneous short circuit release shall be so chosen by the Contractor as

to operate at a current in excess of the peak motor inrush current and a range

of settings shall be provided for the Employer ‘S / Engineer’s selection.

MCCB terminals shall be shrouded and designed to receive cable lugs for cable

sizes relevant to circuit ratings.

MCCB’s shall incorporate time delay devices to ensure that it will tolerate

harmless transient overload unless this is well in excess of 25% of its rated

value for a sustained period.

1.8.1 The MCCBs shall be provided with the following features:

a) Inverse-time-current tripping characteristics under sustained

overload.

b) Instantaneous tripping on short circuit.

c) MCCBs shall be of current limiting type only.

d) MCCBs must have its rated service breaking capacity (Ics) equal to or

greater than its specified fault level.

e) Variable Thermal setting shall be provided in all MCCB s with thermal

Magnetic releases.

1.9 Miniature Circuit Breaker (MCBs)

Miniature Circuit Breaker shall comply with relevant IS / IEC standard i.e. IS-

8828-1996 & IEC – 60898 and ISI marked on each MCB. MCBs shall be quick

make and quick break type, suitable for 230 / 415V AC 50 Hz, breaking

capacity should be 10kA and marked on MCB. MCB shall be classified as B, C,

D curve type suitable marked on MCB. MCB’s for Lighting & power sockets

shall be C-curve, all MCBs used on UPS circuit shall be D-Curve only. MCB’s

shall have quick make can break non welding self-wiping silver alloy contacts.

The housing shall be made from heat resistant thermoplastic material and

shall have high impact strength. All 2P, 3P and 4P miniature circuit breakers

shall have a common trip bar independent to the external.

1.10 RESIDUAL CURRENT CIRCUIT BREAKER (300mA): -

Characteristics: -

• Phase (line) and Neutral both wires connected through RCD.

• It trips the circuit when there is earth fault current.

• The amount of current flows through the phase (line) should return through neutral.

• It detects by RCD. any mismatch between two currents flowing through phase and neutral detect by -RCD and trip the circuit within 30Miliseconed.

• If a house has an earth system connected to an earth rod and not the main incoming cable, then it must have all circuits protected by an RCD

Page 235: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 235 of 307

(because you might not be able to get enough fault current to trip a MCB)

• RCDs are an extremely effective form of shock protection.

• Protection of installations against the risk of fire (300 mA).

1.11 INDICATING INSTRUMENTS AND METERS Electrical indicating instruments (Digital type) shall be of minimum 96 mm

square size and with a class of accuracy of 1.0 and shall have provision for zero

adjustment outside the cover. Digital meters should have red colored readout.

The size of the meters to be provided on outgoing feeders and in wall mounted

panels shall be 96mm x 48mm.

1.12 CABLE TERMINATIONS Suitable double compression type, brass cable glands with check nuts, rubber

sealing ring and brass washers mounted on a removable gland plate shall be

provided to support all cables entering the switchgear. Cable Termination will

be measured under separate item in the schedule of quantities.

1.13 INTERNAL WIRING Wiring inside the switchgear shall be carried out with 1100 V grade,

single core, PVC insulated, stranded copper conductor wires made to

IS:694. Minimum size of conductor for power circuits is 4 mm². Not more

than two connections shall be made on incoming side. The outgoing side

of connector shall have only a single connection. Spare connectors to be

provided for BMS & other uses

1.14 TERMINAL BLOCKS

1.14.1 Terminal blocks shall comprise finely threaded pairs of brass studs of at least 6 mm diameter, links between each pair of studs, washers, nuts and locknuts. The studs shall be securely locked within the mounting base to prevent their turning. Insulated barriers shall be provided between adjacent terminals.

1.14.2 Terminals shall be shrouded. Terminal blocks shall be adequately rated to carry the current of the associated circuit. Minimum rating of the terminal block shall be 10 A.

1.15 LABELS: All labels shall comprise white letters on a black background and shall be made of non-rusting metal or 3-ply lamicoid or engraved PVC. Size of lettering shall be 6.0 mm.

1.16 EARTHING

1.16.1 Earth bus bars shall be supported at suitable intervals. Positive connection between all the frames of equipment mounted in the switchboard and earth bus bar shall be provided by using insulated copper wires/bare bus bars of cross section equal to that of the bus bar or equal to half the size of circuit load current carrying conductor, whichever is smaller.

Page 236: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 236 of 307

1.16.2 All instrument cases shall be connected to the earth bus bar using 1100 V grade, single core 2.5 mm² stranded, copper earthing conductor.

1.16.3 All non-current carrying metal and hinged doors shall be earthed to the earth bar.

1.17 TESTS Switchgear shall be subjected to following tests as per relevant standards along

with following tests:

a) Mechanical operation test.

b) H. V. test for 1 minute.

c) Insulation resistance at 1000 V D.C. before & after 1 minute H.V.

test.

1.18 TECHNICAL SPECIFICATIONS FOR HVAC PANEL (IP65)

1.18.1 SCOPE The scope of work shall cover design, manufacture, check test, Installation and

supply of medium and low voltage motor/power control Panel boards, MCB

distribution boards etc. as described in this specification, as per drawings and

schedule of quantities.

1.18.2 CODES & STANDARDS

The Panels shall comply with the latest edition of relevant Indian Standards and

Indian Electricity Rules and Regulations. The following Indian standards shall be

complied with:

Sr. Item Relevant IS Relevan

t IEC

1 General requirements for switchgear and control

gear for voltages not exceeding 1000 V AC or

1200 V DC

IS: 4237

2 Switchgear bus bars, main connection and

auxiliary wiring, marking and arrangement.

IS: 375

3 Degree of protection provided by enclosures for

Low voltage switch gear and control gear.

IS: 2147

4 Terminal marking for electrical measuring

instrument and their accessories.

IS: 8197

5 Danger notice plates IS: 2551

6 Code of Practice for selection, installation and

maintenance of switchgear and control gear.

IS: 10118

7 Specification for factory built assemblies of

switchgear and control gear for voltage up to and

including 1000 V AC and 1200 V D.C.

IS: 8623

8 Miniature circuit breakers. IS: 8828

Page 237: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 237 of 307

9 Current transformers IS: 2705

10 Voltage transformer IS: 3155

11 Electrical relay for protection IS: 3231

12 Indicating instruments IS: 1248

13 Integrating instruments IS: 722

14 Control switches and push buttons IS: 6875

15 AC motor starters of voltage not exceeding 1000

V

IS: 1822

The Panels also require approval of the MDL Executive/consultant at

various stage of their manufacture such as design, selection, construction,

testing, shipping etc.

1.18.3 DESIGN BASIS & SITE CONDITIONS

All the equipment and components provided in the panels and

accessories shall be suitably designed for installation and satisfactory

operation as specified below.

Site conditions

Location Mumbai, Maharashtra Site altitude 560M-800M above mean sea

level

Ambient temperature Relative humidity

Maximum 41 0 C Maximum 85 %

Minimum 05 0 C Minimum 35 %

Design 45 0 C Design 90 % at 45 0 C

Seismic factor Zone IV as per

IS:1893 Rainfall 722 mm/year

Environmental Tropical/wet & Dry

Climate

Location of Equipment Outdoor

Wind speed Annual average 4.35

Electrical system data:

Power supply for Equipment

Voltage 415 V ± 5 % Frequency 50 Hz ± 3 %

Permissible combined

voltage & frequency

variation

± 6 % System design faults

level (Symmetrical)

10 kA for 1 sec.

max.

Page 238: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 238 of 307

System earthing LV side neutral

solidly earthed

Wiring 3 phase, 4 wire on 415V system

Auxiliary power supply :

Power supply 240V AC, 1-Ph, 50Hz

Control Supply -----

Space heater power supply 240V AC, 1-Ph, 50Hz

Illumination power supply 240V AC, 1-Ph, 50Hz

Plug-socket power supply 240V AC, 1-Ph, 50Hz

1.18.4 TECHNICAL REQUIREMENTS:-

The Panel shall be metal clad, totally enclosed, rigid, floor mounting,

air insulated, cubicle type suitable for operation on three phase/single

phase, 415 V/240 V, 50 Hz., neutral effectively grounded at

transformer and short circuit level as mentioned in the drawings.

All the outdoor panel shall be double door type with IP65 protection

class construction.

The painting of all the metal part shall be as per the painting

specification defined in the datasheet.

The Panels shall be designed to withstand heaviest condition at site,

with maximum expected ambient temperature of 45°c, 90% humidity

and salty, dusty weather.

1.18.5 CUBICAL TYPE PANELS:

STRUCTURE

The Panels shall be metal clad enclosed and be fabricated out of high

quality CRCA sheet, suitable for indoor installation having dead front

operated and floor mounting type.

All CRCA sheet steel used in the construction of Panels shall be 2 mm.

thick and shall be folded and braced as necessary to provide a rigid

support for all components. Joints of any kind in sheet steel shall be

seam welded, all welding slag grounded off and welding pits wiped

smooth with plumber metal.

The Panels shall be totally enclosed, completely dust and vermin proof

and degree of protection being not less than IP: 65. Gaskets between

all adjacent units and beneath all covers shall be provided to render

the joints dust proof. All doors and covers shall be fully gasketed with

foam rubber and/or rubber strips and shall be lockable.

All panels and covers shall be properly fitted and secured with the

frame and holds in the panel correctly positioned. Fixing screws shall

Page 239: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 239 of 307

enter into holes, taped into an adequate thickness of metal or provided

with bolts and nuts. Self-threading screws shall not be used in the

construction of Panels.

A base channel of 100 mm. x 50 mm. shall be provided at the bottom.

A clearance of 300 mm. between the floor of the Panels and the bottom

of the lower most units shall be provided.

Panels shall be preferably arranged in multi-tier formation. The Panels

shall be of adequate size with a provision of 20% spare space to

accommodate possible future additional switchgear. The size of the

Panels shall be designed in such a way that the internal space is

sufficient for hot air movement and the electrical component does not

attain temperature more than 450c. The entire electrical component

shall be derated for 500c. The ratings indicated in the drawing are de-

rated for 500c.

Knock out holes of appropriate size and number shall be provided in

the Panels in conformity with the number, and the size of incoming

and outgoing conduits/cables.

Alternately, the Panels shall be provided with removable sheet steel

plates at top and bottom to drill holes for cable/conduit entry at site.

The Panels shall be designed to facilitate easy inspection, maintenance

and repair.

The Panels shall be sufficiently rigid to support the equipment without

distortion under normal and under short circuit condition. They shall

be suitably braced for short circuit duty.

1.18.6 PROTECTION CLASS:

All the outdoor Panels shall have protection class of IP 65 for outdoor

installation.

1.18.7 PAINTING:

The painting shall be with 2 coats of epoxy primer along with two coats

of PU paint [Anti-corrosive paint]. Paint shade shall be confirmed with

the client.

1.18.8 CIRCUIT COMPARTMENTS:

Each circuit breaker and switch fuse unit shall be housed in separate

compartments and shall be enclosed on all sides. Sheet steel hinged

lockable door shall be duly interlocked with the breaker/switch fuse

unit in `ON’ and `OFF’ position. Safety interlocks shall be provided for

air circuit breaker to prevent the breaker from being drawn out when

the breaker is in `ON’ position.

The door shall not form an integral part of draw out position of the

circuit breaker. All instruments and indicating lamp shall be mounted

on the compartment door. Sheet steel barriers shall be provided

between the tiers in a vertical section.

1.18.9 INSTRUMENT COMPARTMENTS:

Page 240: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 240 of 307

Separate adequate compartment shall be provided for accommodating

instruments, indicating lamps, control contactors/relays and control

fuses etc. These components shall be accessible for testing and

maintenance without any danger of accidental contact with live parts

of the circuit breaker/switch fuse unit, busbar and connections.

1.18.10 DRAWINGS & DATA

As part of the technical bid, tenderer shall furnish the

following data:

1.18.11 DATA SHEET FOR HVAC Panel(IP65)

a. Incomer : 250A,TPN MCCB,35kA,Adjustable thermomagnetic

1 Set - Ammeter/ Voltmeter selector switch

b. Busbar : 250A, TPN, Aluminum, 35kA

c. Indicator : LED type RYB phase indicators, MCB type

d. Outgoings :

63A, TPN, MCB - 2 Nos. (For outdoor Unit 1&2)

100A, TPN, MCCB - 2 Nos. (For Standby Unit 1&2)

2.0 CABLES:

2.1 The design, manufacture, testing and supply and installation of 11KV grade HT cables & 1.1KV grade LT cables. PVC insulated and sheathed SWA power cable for LT supply. All cables shall have Flame Retardant (FR) and meet, ASTM norms for the smoke density and Oxygen Index norms. Cables shall have high conductivity stranded aluminium or copper conductors and cores color coded to the Indian Standards.

2.2 General Conditions:

a. The quantities given in the schedule are indicative and contractor shall arrange for the actual requirement.

b. The manufacturer should have in house testing facilities as per IS as well as special tests pertaining to PVC (FRLS) cables like 'Oxygen and Temperature Index Test', 'Smoke Generation test to measure and record smoke density over fixed time interval', HCl gas 'Emission Test' and 'Flammability Tests as per IEC, IEEE and Swedish Standards'.

2.3 Inspection: All cables shall be inspected by the contractor upon receipt at site and checked

for any damage during transit.

Page 241: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 241 of 307

2.4 Joint in Cables: The Contractor shall take care to see all the cables received at site are

apportioned to various location in such a manner as to ensure maximum

utilization and avoidance of jointing cables. This apportioning shall be got

approved by the Owner before the cables are cut to lengths. Straight joints are

prohibited. It is the contractor’s responsibility to arrange the cable lengths to

suit site requirements. Neither the owner nor their representive are responsible

for approving the length for cable.

2.5 Excavation and Backfill All excavation and backfill including timbering, shoring and pumping required

for the installation of the cables shall be carried out by the contractor in

accordance with the drawings and requirements laid down elsewhere. Trenches

shall be dug true to line and grades. Backfill for trenches shall be filled in layer

not exceeding 150mm. Each layer shall be properly rammed and consolidated

before laying the next layer. The Contractor shall restore all surface, roadways,

sidewalks, curbs, walls or other works out by excavation to their original

condition, satisfactory to the Architects. Back filling shall be done with soft

earth only.

2.6 Cable Termination of Cables and Joints:

(a) For termination of cables of size 16 sq.mm. and above, suitable copper

cable sockets of appropriate size and capacity shall be provided at

terminal ends. This condition is applicable to single PVC insulated wires

of 16 sq.mm. and above also.

(b) Generally, Tubular sockets shall be used where grub screw/ clamp type

fixing arrangement is available at the terminating end. Reducer / spade

type sockets shall be used where bolt and nut arrangement is available

at terminating end.

(c) The cable socket shall generally be fixed to the cable cores by crimping

process.

(d) Irrespective of the size of the cable and the method of termination, the

core end shall be cleaned and immediately covered with an oxide

inhibiting/ corrosion inhibiting compound before termination.

(e) The tail end wires shall be finished in an appropriate colour by using

PVC insulating sleeve.

Page 242: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 242 of 307

2.7 DATA SHEET FOR CABLES (Must be furnished along with the quotation for all cable of conductor size 50 Sq.mm and above).

Sr

No.

DESCRIPTION GUARANTEED

PARTICULARS

1.0 Name of Manufacturer

2.0 Conductor

2.1 Form - circular/ segmented

2.2 Cross sectional area mm²

3.0 Whether cores identified by colours

Yes/No

4.0 Overall dia. of finished cable

5.0

Critical Oxygen Index Value at 750oC

when tested for temperature index

test as per ASTMD-2863

6.0

Total acid gas generation by weight

when tested as per IEC 7541

%

7.0 Percentage of light transmission

under fire for assessment of smoke

generation when tested as per ASTM-

D-2843.

%

8.0 Will cables offered pass the

flammability tests as per:

a) Class-F3-Swedish Standard S5-

424-1475

b) IEC 332-1

c) IEC 331-1

Yes/No

Yes/No

Yes/No

3.0 POINT WIRING: 3.1 SCOPE: The scope of this part comprises the supply, delivery, storing, erection, testing

and commissioning of electrical wiring installation.

3.2 CONDUIT: a) The conduit shall be Rigid PVC and black enameled screwed mild steel (as

specified in the scheduled of quantity), manufactured to IS:9537 Part III including latest amendments, if any, and in accordance with the requirement set out in the schedule of quantities.

Page 243: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 243 of 307

b) The conduit accessories should be compatible to the conduit installed. PVC in case of PVC conduit and Black enameled steel in case of Black enameled conduit

c) Conduits shall be provided with couplers for straight joints.

3.3 CONDUIT CAPACITY:

The maximum capacity of a conduit for drawing in PVC insulated copper

conductor wires shall be in accordance with the following table.No conduit shall

be used having its diameter less than 20 mm. Not more than two circuits shall

be bunched in one conduit.

Size of Wire (Made to

IS:694)

Capacity of Conduit

20 mm. dia. 25 mm. dia.

1.5 Sq. mm. 5 10

2.5 Sq. mm. 5 8

4 Sq. mm. 3 6

6 Sq. mm. 2 5

10 Sq. mm. - 4

3.4 POINT WIRING (FOR LIGHT POINTS, SOCKETS, ETC.):

The wiring shall be of the looping in system as different from the tree system.

Connectors should not be used without specific prior approval. Loop in on the

phase side shall be at the switches and that on the neutral side shall be at the

connector inside the lighting fitting or ceiling roses. All ceiling roses shall be 3-

plate type. Every fan point and socket point shall have individual control switch

unless stated otherwise. Light points may be group controlled by one switch as

shown on drawings or as directed at site by the Architects/Consultants. Such a

group will be called a set and will consist of one to up to six light points e.g. a set

of three light points controlled by one switch.

Earthing shall be provided for all points according to the specification of the

tender. The number of points in any circuit shall not exceed 9 in any case

(unless otherwise stated) with load not exceeding 1000watts.

a) The point wiring in conduit consists of wiring from the distribution board in

conduit with Earthing and its ancillary work such as bends, couplers,

junction boxes, PVC insulated wires up to the fixed terminals of ceiling

roses, connectors of fixtures, etc. via switch whenever called for. The bidder

should carefully study all the tender drawings to arrive at estimated length

of circuit and point conduit length. Circuit wiring cost is to be included in

the point wiring rates and no separate payment will be made for circuit

wiring.

Page 244: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 244 of 307

b) For easy identification, wires with different colours shall be used (e.g. Red,

Yellow, Blue - for Phases, Black for neutral), Green for running Earth.

4.0 LIGHTING FIXTURES

4.1 General requirements: 4.1.1 All Lighting Fittings shall be complete with Accessories and Fixtures necessary

for installation whether so detailed under item description or not.

4.1.2 Fixture housing, frame or canopy shall provide a suitable cover for the fixture outlet box or fixture opening.

4.1.3 Fixtures shall be installed at mounting heights as detailed on the drawings or as instructed on site by the Architect/Consultants.

4.1.4 Fixtures and/or fixture outlet boxes shall be provided with hangers to adequately support the complete weight of the fixture. Design of the hangers and method of fastening other than shown on the drawings or herein specified shall be submitted to the Architects for approval prior to execution at site.

4.1.5 Pendant fixtures within the same room area shall be installed plumb and at a uniform height from the finished floor. Adjustment of height shall be made during installation as per instructions of Architects.

4.1.6 Flush mounted recessed fixtures shall be installed so as to completely eliminate leakage of light between the fixture and adjacent finished surface.

4.1.7 Fixture mounted on outlet boxes shall be rigidly secured to a fixture stud in the outlet box. Extension pieces shall be installed where required to facilitate proper installation.

4.1.8 Fixture shall be completely wired and constructed to comply with the "regulations" and "Standards" for Electric Lighting fixtures, unless otherwise specified. Fixtures shall bear manufacturer's name and factory inspection label unless otherwise approved.

4.1.9 Wiring within the fixture and for connection to the branch circuit wiring shall be not less than 1.5 sq. mm. copper for 250 Volt applications. Wire insulation shall suit the temperature conditions inside the fixture

4.1.10 Metal used in lighting fixtures shall be not less than 22 swg. or heavier if so required to comply with specification of standards. Sheet steel reflectors shall have a thickness of not less than 20 swg. The metal parts of the fixtures shall be completely free from burns and tool marks. Solder shall not be used as mechanical fastening device on any part of the fixture

4.1.11 Ferrous metal shall be bonderized and given a corrosion resistance phosphate treatment or other approved rust inhibiting prime coat to provide a rust-proof base before application of finish.

4.1.12 Non-reflecting surfaces such as fixture frames and trim shall be finished in a baked enamel paint.

4.1.13 Finish shall be capable of withstanding 72 hours’ exposure to an ultraviolet sun lamp placed 10 cm. from the surface without discoloration factor after exposure. Test results shall be furnished for each lot of fixtures.

Page 245: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 245 of 307

4.1.14 Fixture with visible frames shall have concealed hinges and catches. Pendant fixtures and lamp holders shall be provided with ball type aligners or similar approved means. Recessed fixtures shall be constructed as to fit into an acoustic tile ceiling or plaster ceiling. Plaster rings shall be provided for plastered ceiling. Fixtures with hinged diffuser doors shall be provided with spring clips or other retaining devices to prevent the diffuser from moving.

4.1.15 Detailed catalogue for all fixtures or, if so required by the Architects, sample fixtures shall be submitted for approval to the Architect before orders for the fixtures are placed. Shop drawings for non-standard fixture types shall be submitted for approval to the Architects.

4.1.16 Recessed fixtures shall be constructed so that all components are replaceable without removing housing from the ceiling. � Lamps shall be supplied and installed in all lighting fixtures furnished

under this contract. � Lamps used for temporary lighting service shall not be used in the final lamping of fixture units.

� Lamps shall be of wattage and type as shown on the drawings. Where not shown, the details shall be ascertained from Architect before procurement.

� Lamps for permanent installation shall not be placed in the fixtures until so directed by the Architect and this shall be accomplished directly before the building portions are ready for occupation.

4.2 LED Lamps:

lamp is a light-emitting diode (LED) product which is assembled into

a lamp (or light bulb) for use in lighting fixtures. LED lamps have a lifespan

and electrical efficiency which are several times longer than incandescent

lamps, and significantly more efficient than most fluorescent lamps. LEDs come

to full brightness without need for a warm-up time; the life of fluorescent

lighting is also reduced by frequent switching on and off.

LEDs are “directional” light sources, which means they emit light in a specific

direction, unlike incandescent and compact fluorescent bulbs, which emit light

and heat in all directions.

The chart below shows the amount of brightness in lumen you can expect from

different wattage light bulbs. The LED bulbs require much less wattage than

the CFL or Incandescent light bulbs.

Incandescent Watt CFL Watts LED Watts Lumens (Brightness)

40 8 - 12 6 - 9

400 - 500

60 13 - 18

8 - 12.5

650 - 900

75 - 100 18 - 22

13+

1100 - 1750

100

23 -30

16 - 20

1800+

Page 246: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 246 of 307

150

30 - 55

25 - 28

2780

16-20 W ROUND LED DOWNLIGHT

Features

• Aluminum pressure die cast (PDC) body with decorative trim

• Industry best light output with LM80 tested SMD LEDs

• Effective thermal management with aluminum PDC heat sink

• Robust driver with wide voltage range 100-240VAC and inbuilt protection

• Recessed mount, protected from dust and insects

Specifications

Code D521665 D522065

Wattage 16 20

Colour Temp. (K) 6500 6500

Lumens (lm) 1200 1450

Voltage (VAC) 240 240

Cut Out Φ (mm) 140 140

5W-9W LED BULB

Features

• Saves 80% energy with life up to 10 years

• Industry best light output with wide light distribution > 200°

• Robust driver with wide voltage range 100-240VAC and inbuilt protection

• Light weight and decorative look fits in CFL sockets

Specifications

• Code N50001 N90002

Page 247: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 247 of 307

• Wattage 5 5

• Colour Temp. (K)

6500 6500

• Lumens (lm) 450 840

• Voltage (VAC) 240 240

• Beam Angle 240° 220°

5W LED Mirror Light

Features

• Slim LED Batten in Aluminum housing and decorative end caps

• Industry best light output, with spot free illumination

• Effective heat dissipation with extruded aluminum heat sink

• Robust driver with wide voltage range 100-240VAC and inbuilt protection

• Wall mounted, protected from dust and insects

Specifications

Code D530565 D530527

Wattage 5 5

Colour Temp. (K) 6500 2700

Lumens (lm) 380 360

Voltage (VAC) 240 240

LED Strip Light

An LED Strip Light (also known as an LED tape or ribbon light) is a flexible

circuit board populated by surface mounted light-emitting diodes (SMD LEDs)

and other components that usually comes with an adhesive backing.

Traditionally, strip lights had been used solely in accent lighting, backlighting,

task lighting, and decorative lighting applications. Increased luminous

efficacy and higher-power SMDs have allowed LED strip lights to be used in

applications such as high brightness task lighting, fluorescent and halogen

lighting fixture replacements, indirect lighting applications, Ultra

Violet inspection during manufacturing processes, set and costume design, and

even growing plan

Application: -

Strip lights are designed for both indoor and outdoor use depending on whether

they’re water resistant. Since the strip is flexible and can be divided at any

point between LEDs, it is extremely versatile and can be used in a number of

Page 248: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 248 of 307

installations. Outside of traditional lighting, strip lighting is extensively used in

DIY projects or lighted clothing.

4.3 Wall-mounted PIR Occupancy Sensor for A.C

Wall-mounted PIR Occupancy Sensor employs passive infrared (PIR)technology

will scan the room for occupancy using Passive Infra-Red (PIR) technology to

accurately detect occupancy. As the sensor will only detect body heat it will not

therefore be affected by items such as ceiling fans, or curtains. When no

occupancy has been detected, after a preset time delay (either 15, 30 or

45 minutes), a signal will be transmitted to the AC to switch it off. On re-

entering the room, if air conditioning is required, the occupant simply turns the

air conditioner back on using the normal remote control.

After the occupant has left the room, Sensor will continue to scan the room for

a preset time - 15.30 or 45 mins before sending the signal to turn off the Air

Conditioner

4.4 Rodent Repellent System The powerful sound waves generated by the transducers of the repellers are

within the hearing range of many pests, and cause them pain and discomfort.

The transducers are quiet. If you cannot hear them, do not think that the unit

is not working. You cannot hear ultrasound. The Ultrasound emitted by the

machine becomes unbearable to the rodents and they try to run away. Rodents

get irritated and look out for quiet safer areas

Rodents stop entering the areas being protected by us, because the ultrasonic

sound waves hit their eardrums and cause them considerable pain and

discomfort. They do not get immune since the sound output is at varying

frequencies. They do not die unless they get trapped in a particular place for

days together or are under consistent exposure to ultrasonic sound

Effects of ULTRASOUND On Rodents:

The high pressure ultrasound waves have a very adverse effect on the ear

drums of the rodents and is unbearable to them. They eventually leave the area

after initial resistance.

Ultrasonic sound waves have a very bad effect on the nervous system of

Rodents and make them sluggish.

Ultrasonic sound waves reduce the very desire for sex in rodents and this in

turn helps in controlling rodent population.

If they stay in contact with the Ultrasonic sound waves for more than 3 or 4

days, possibility is that their eating habits get affected and mobility is reduced.

Rodents Repellent System model with high frequency random signal

generator which drives up to 20 transducers.

The signal is fed to each transducers (up to 20 transducers) from the main

Master Unit. These signals are converted as high frequency sound waves that

are audible to rats and very painful for them tolerate. The rats usually leave the

Page 249: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 249 of 307

protected area within 2 – 3 weeks, but you can see the gradual decrease of

rodent infestation on installing the unit.

The transducers does not make any human audible noise, it is not harmful to

human beings or pet animals at home.

4.5 Wireless Call Bell System. wireless call system is an innovative and simple solution. It helps to summon a

peon or attendant from a distant location, with mere press of a remote. The call

system works on latest wireless technology and needs no installation. User

needs to press a remote controller to call the attendant. The range of

communication is 20-30 meters indoors, and around 100-120 meters outdoors.

Every remote has a number that is displays on the receiver when pressed. The

call bell system comes in numbers of 2 to 10 remotes. The system is simple to

use and easy to understand.

Every remote has a CALL and CANCEL button. The receiver has 2 to 10

indicators (depending on various models). To call the attendant simply press

the CALL button on the remote controller. This will send a wireless signal to

the receiver unit. The respective indicator on the receiver will start to blink.

Along with a beeping sound to alert the attendant or peon.

Advantages of wireless call bell system:

• Absolutely no wiring needed

• Ready to use system (just out of the box, plug and play)

• No hassles of installation (plug in the receiver to the adapter and distribute the remotes)

• Each remote has a separate indicator on the receiver to allow the attendant to know exact room location

• System needs no line of sight communication. Remote controller signals can penetrate through walls as well

• System operates on cutting edge wireless RF technology

• The battery life of the remotes is around 1 year (operates on 23A batteries)

• Each indicator glows along with a beep sound to alert the attendant.

4.6 Mobile Charging Station.

Mobile Charging Station is free standing charging station with 10 different

Charging Port to charge up to 10 devices at a time.

4.7 UV Mosquito Lamp. Mosquito Lamp, more formally called an electrical discharge insect control

system, electric insect killer or (insect) electrocutor trap, is a device that

attracts and kills flying insects that are attracted by light. A light source

attracts insects to an electrical grid, where they are electrocuted by touching

two wires with a high voltage between them. The name comes from the

characteristic onomatopoeic zap sound produced when an insect is

electrocuted.

4.8 Ceiling Fans

Page 250: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 250 of 307

TS-4.5.8.1. Electric Ceiling fan capacitor type with double ball bearing complete

with capacitor, 300 mm down rod, canopies, shackles, reel insulator, half

threaded bolts of 9.53 mm (3/8”) dia 62.5 mm (2-1/2”) to 88 mm (3-1/2”) long

and 7.94 mm (5/16”) dia 44.5 mm (1-3/4”) to 57 mm (2- 1/4”) long with nuts,

with lock type split pin, spring & plate washers, etc.; three number blade made

of Aluminum alloy, suitable for single phase, AC 210 volts, 50 Hz supply and

conforming to class I of IS : 374/1979 with amendment no 1 to 6 except for

performance Parameters to the extent modified as details in general

requirements. The down rod shall be capable to withstand a tensile load of

1000 kg without breakdown and a torsion load of 500 kg.cm without breakage

as per Clause 10.14.1 of IS: 374/1979 with amendment no.1 to 6. Electrical

motor should be single phase permanent capacitor type with no. of poles

12/14/16/18 (As per sweep), Class-I with basic insulation. Class of insulation

shall be B class. The winding wire used for fan should be synthetic enamelled of

30 to 38 SWG. Connection wire: Flat / round Two core flexible stranded copper

wire cord 24/0.2mm ISI marked.

Paint: Superior quality enamel paint of specified colour for marking Sr. No and

date of erection.

4.9 Exhaust Fans Scope:

Supplying and erecting Exhaust fan of specified sweep and speed, with all

accessories and necessary materials, suitable to work on 230 V / 415 V, AC

Supply 50 Hz, erected in position.

Material:

ISI marked Exhaust fan suitable for Single/Three phase AC 230/415 Volts 50

Hz, capacitor run with mounting ring, four numbers of fixing hole without

regulator and louvers. The sweep and speed shall be as per table below. Fan

motor with moisture proof treatment and E class insulation, ISI marked,

conforming to IS: 2312/67 with amendments 1 to 8. The fan mounting rings

shall be proper pretreatment followed with at least two coats of primer; final

finish shall be with two coats of grey colour paint duly baked. The connecting

leads shall be brought out for making connections.

Paint: Superior quality enamel paint of specified colour.

4.9.1 Corresponding Speed with Sweep

Sr.No Sweep Speed in RPM Voltage level CFM in m3/hr

1 375mm 900 230 2460

2 375mm 1400 230 4000

3 450mm 1400 230 6800

4 450mm 900 230 4350

5 375mm 900 415 2460

Page 251: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 251 of 307

4.9.2 Method of Construction: The Exhaust fan complete with all above accessories and duly wired shall be

erected at specified position, connected to the supply and tested.

Testing:

After erection fan shall be tested by connecting to supply. Also steadiness and

Vibrations if any, of fan shall be checked at full speed, so that there is no

wobbling. Mode of Measurement: Executed quantity shall be counted on

number basis. (i.e each)

4.10 TECHNICAL SPECIFICATIONS FOR INVERTER SYSTEM: -

SCOPE OF WORK

The scope of work for Inverter system to be furnished in accordance with

this specification, shall include design, manufacture, fabrication, assembly,

pre – shipment, testing at manufacturer’s works, proper packing for

transportation, delivery at site, unloading, storage, erection, interconnection

of related equipment’s, calibration, commissioning, testing and putting the

Inverter system together with all accessories and auxiliaries as specified

hereinafter in a fully operational condition acceptable to the Owner. The

systems shall be furnished, erected and commissioned and all other services

shall be performed by the vendor as covered under this specification and this

work shall be fully in compliance with the requirements stated herein.

CODES & STANDARDS

IEEE Standard 446—

1987

Emergency and standby power systems.

IEEE Standard 450 –

1975

IEEE Paper 4-177 Some discharge characteristics of lead acid

batteries.

IEC 146 Performance testing of UPS

ANSI C37.90a,

IEEE Standard 472

Surge withstand capability test.

ANSI C 34.2 Practices and requirements for semiconductor

power rectifiers.

ANSI C 37.90 Relays and relay system associated with

electrical power apParatus.

NEMA PE-1983 Uninterrupted Power System Standard

IS 2208 & IS 9224 Cartridge fuses for voltages upto and

including

650V (Part 1 & Part 2 ) (I.E.C. 269)

IS 9224 (Part – 4) Fuses for protection of semiconductors.

BS 2709 (I.E.C 119) The Electrical Performance of Semiconductor

Rectifiers. (Metal Rectifiers)

BS 4417 (I.E.C 146) Semi-conductor Rectifier Equipments.

Page 252: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 252 of 307

IS 8623 (I.E.C 439) Factory – built Assemblies of switchgear and

Control gear for voltages upto and including 1

KV and 1200V DC

IS 694 (I.E.C 228) PVC insulated Cables for switchgear and

Control gear wiring.

IS 1652 & IS1652 Lead-acid stationary cells and batteries.

BD 9720 Custom-built transformers and inductors of

assessed quality.

IP20 Degree of protection.

IEC Semi-Conductor Convertor Standards.

ISO 9001certified

The requirements of Inverter systems are specified herein on system basis.

The vendor shall be responsible for engineering and providing all materials,

equipment’s and services specified or otherwise, which are required to

fulfill the intent of ensuring operability, maintainability, completeness and

reliability of the total work covered under this specification within his

quoted price.

Following general requirements shall be met for ensuring proper circuit

protection.

For circuit with transformers, if secondary fuse protection is not provided

then the primary fuses must not be sized larger than 125% of the

transformer primary full-load amperes.

If secondary fuses are sized not greater than 125% of transformer

secondary current, individual transformer fuses are not required in the

primary provided the primary feeder fuses are not larger than 250% of the

transformer rated primary current.

All the neutral conductors used in three phase UPS systems are to be sized

equal to take at least 150% of the maximum phase current. In addition, all

the isolators and circuit breakers used in three phase UPS system are to

be rated such that the neutral poles will take at least 150% of the

maximum phase current.

All control shall be designed and positioned such that, possibility of

inadvertent or accidental operations are eliminated.

All Inverter system cabinets, frames and power transmission circuits are to

be double earthed.

The Inverter design philosophy shall ensure that a single component /

device failure shall not result in failure of the entire UPS system. i.e the

design of UPS System shall be modular to permit easy removal of any unit

without affecting other units.

The various overload capacities of inverters, static switch, step down

transformer/voltage stabilizer as specified herein are the minimum

requirements. However, if the Vendor’s offered system has better overload

capacities for the above devices, the same shall be highlighted by the

vendor in his offer.

The Inverter system offered by the vendor shall be suitable for operating

continuously at the rated capacity indicated in tender with in ambient

Page 253: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 253 of 307

temperature 5- 45 deg. C and relative humidity of 30 to 98%. Also the

Inverter system shall be suitable for operation as per full rating up to 1000

meters above sea level without derating. The Vendor shall furnish a

certificate towards compliance on ambient conditions permissible.

The Inverter system to be supplied by the vendor shall have maximum

humming noise level of 75 DB at 3 meter from the surface of the UPS

cabinets.

Suppression of Radio Interference shall be provided to meet statutory

requirements.

Detailed literature should be provided showing Quality Assurance

Procedure.

The vendor shall submit along with the tender detailed item by item

compliance statement along with the tender.

The vendor shall submit along with the tender Credential certificates for

satisfactory completion of minimum five (5) Inverter installation of similar

magnitude, capacity, application and operational philosophy. Vendor

Noncompliance with above requirement shall be outright rejected.

All the equipment and components provided in the transformer and

accessories shall be suitably designed for installation and satisfactory

operation as specified below.

TECHNICAL REQUIREMENTS

Static Converter

The static converter shall be fully microprocessor controlled full wave

controlled rectifier which shall include drive circuitry, over current

protection, over temperature protection, control voltage drops protection

and short circuit protection.

The converter shall be capable of the following:

During any step-load change the Converter shall only supply 100% current

to the Inverter without cycling the battery any time during step-load

change and provide power to the fully loaded inverter to the rated capacity

while simultaneously recharging the system battery to 95% of the full

capacity within 10 times the discharge time.

The Converter shall provide a battery charge current limit of 10% of battery

Ah rate to prevent any damage to the battery.

The Converter system shall be capable of achieving 0.95 or above power

factor limiting KVA input to the system to be the rated KVA of the UPS

system.

The Converter shall limit input harmonic current THD to maximum of 4%

under 100% load condition and 10 % under 33 % load condition. If the

manufacturer’s standard equipment does not achieve this, the bidder

should add for necessary filters to limit input harmonic current THD as

indicated above.

The Converter logic shall have walk in function to allow a delay and time

ramping of input current. On energizing the Converter input, the ramping

of current shall be delayed by a maximum of 3 seconds. During walk in

process ramping current shall be timed to assume the load gradually

Page 254: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 254 of 307

within 1 to 60 seconds selectable 1 second interval.

The Converter shall meet the following performance requirements:

Nominal Voltage 415V + 5% AC Input 3 Phase

Normal frequency 50 Hz + 3%

Input harmonic Less than 5% typical at 100% load

current

Input power factor 0.95 or above lagging or more at 50

% load (PF improvement)

Duty Continuous at 50 deg. C

Cooling using fans Natural convection or forced

cooling

Ambient Temperature 45oC maximum

Relative Humidity 0-95% non-condensing

Magnetized sub-cycle Typically 8 times normal full load

current in rush current

Converter walk-in time 1 through 60 seconds

(every one second selectable, 0 to

100% rated load)

Input Vendor shall provide suitable

terminals for termination of cables

for connecting to the converter

from the AC distribution board to

be sup[plied by owner.

Static Inverter

The static Inverter shall have utilizing high speed switching Insulated Gate Bipolar

Transistor which shall include drive circuitry and devices to control

requirements including voltage regulation, current limiting, wave shaping,

transient recovery, automatic synchronization etc.

The static Inverter shall be use appropriate control circuitry to perform as

a constant voltage and constant current source to enable adapting its

performance for changing loads.

Inverter capacity

Each static inverter shall have the following minimum capacities without

causing any damage to the components and with current limiting function

not operating

Continuous full load

rating

The Inverter should be rated to deliver full

rated 1400 VA at any load power factor

Overload capacity 125% for 30minutes minimum at all

specified input voltages and 150% for

minimum 60 seconds.

The Inverter should be designed to meet the following.

Earth leak capacity

Page 255: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 255 of 307

200% for 10 minutes minimum at all specified input.

Step load pick up

Upon transfer of the full load the inverter output voltage shall not drop

below 95% of nominal voltage. The recovery to within +/-1% of the voltage

shall be 20 milliseconds maximum.

Overloads short circuits and load loss

The Inverter should be capable of clearing an output fault of 1000% of the

rated capacity in 40 milliseconds.

Nonlinear loading

The Inverter shall be capable of operation with 100% nonlinear loads. The

bidder shall assume a nonlinear wave form providing a crest factor of

greater than 3.0 occurring coincident with the voltage peak.

The output wave form of the Inverter shall remain within the specified

tolerance when operating with these nonlinear loads at 100 percent rated

load. For 3 Phase UPS, the load carrying neutral conductors and

components throughout the UPS shall be rated for continuous operation

at a minimum of 150% of the phase ratings.

The Inverter shall be self-protecting against all AC and DC transients,

voltage surges and steady state abnormal voltages and currents likely to

be encountered. The inverter shall be protected against high and low input

DC voltage.

Supply Voltage Variation and Loss

The Inverter shall include equipment necessary to protect itself from

damage resulting from excursion loss or restoration of DC input and

synchronizing voltage.

The Inverter also should be designed to supply the rated load at 40°C

ambient temperature continuously.

The Inverter shall comply with the following performance specifications in

addition to those described above :

Nominal output voltage 230 +/- 1% AC, 1 Phase 2 Wire.

Nominal input voltage To suit output requirement.

Details to be given by the bidder.

Inverter capacity As per schedule of quantities.

Voltage regulation The bidder should furnish compliance of

voltage regulation of less than +/- 1%

under all conditions including 0-100%

loading, the Inverter DC input voltage

when fed from battery system varies from

maximum to minimum.

All bidders to provide voltage fluctuation limitation under transient

condition for the following :

Page 256: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 256 of 307

100% step load change at loss or return of AC input, on load transfer

from bypass to Inverter.

This figure should be less than +/- 3% and the recovery time from

transient

to normal voltage should be less than 20 milli seconds.

The Inverter should have phase displacement limitation as

120 deg. +/- 1

deg. For balanced load and 120 deg +/- 2 deg. For unbalanced load. It

should also have an output fault clearing capacity as 1000% of the

current for 20 milli seconds.

By-Pass and Static Transfer Switch

When the Inverter output under voltage or over voltage, overload

beyond the specified limits of the Inverter, at final end voltage of

system battery, total system failure, PC circuit under voltage or over

voltage condition, the UPS system logics and the static switch should

transfer the load to bypass source within 150 micro seconds providing

an uninterrupted transfer

When the critical load has been transferred to bypass source due to

an overload condition, the system logic shall constantly monitor the

condition and upon the overload being cleared, perform an automatic

re-transfer to the Inverter output. The UPS system logic should allow

re-transfer to occur 3 times within a 10 minute period and shall

prohibit re-transfer on the 4th transfer. The automatic re-transfer

from standby source to Inverter should occur only when the Inverter

output is in synchronization with standby source.

The UPS control system through the operating panel should have

capability to initiate manual transfer. During manual transfer or

automatic re-trasfer, the UPS system logic shall force the Inverter

output voltage to match the bypass input voltage to achieve no-break

transfer along with controlled walk in load current to the Inverter.

Maintenance bypass switch :

The UPS shall be provided with, as an integral part of the system, a

zero energy maintenance bypass switch with lock and key

arrangement of adequate capacity and specification, the use of which

by authorized personnel using the key shall enable bypass of the

entire UPS system, including the static bypass switch, and connect

the load to standby AC source enabling maintenance personnel to

work on the UPS system.

Inverter Battery System

The Inverter system shall, as an integral part, provide battery system

for 30 minutes standby capacity.

The latest state of the art Valve Regulated Sealed Maintenance Free

Lead Acid Batteries should be used with a 10 minute discharge rating.

The battery system shall be sized to provide30 minutes back up time

when the UPS is supplying 100% rated load at 0.8 load power factor.

Page 257: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 257 of 307

An ageing factor of 15% should be applied to the capacity arrived at,

to allow for compensation against capacity loss during float operation.

The battery system design should be provided with necessary devices

to prevent deep discharge beyond recommended limits to prevent the

batteries discharging beyond end cell voltage specified by the battery

maker. The connections from battery to battery shall be using copper

bus bar strips and the entire battery system shall be used in IP20

steel cabinet enclosure and shall be similar to the UPS enclosure.

All batteries should be clearly identified and identification numbers

marked on the batteries and a schematic diagram along with the

complete calculations, including manufacturers supporting curves,

should be submitted with the tender.

OPERATION

Under normal operation, the UPS load will be fed from the Inverter

with the bypass switch inhibited. The Converter, apart from providing

DC power to the Inverter, also charges the battery under the float

charge mode. The battery charge system shall have float charge,

equalizing charge the recovery charge modes, to replenish the

batteries self-discharging part while the battery is fully charged,

equalizing the battery cell voltage to a constant value forcibly, and

recharging the battery system to the required values when the

batteries have been used, respectively.

The Inverter shall constantly monitor the AC source frequency and

shall be in synchronization with the AC input source till the frequency

of the AC input source is within synchronizing limit and if the

frequency of the standby source exceeds the synchronizing limit the

Inverter will work on its own internal oscillator maintaining an output

frequency of 50Hz +/- 0.01% under all conditions of load. When the

Inverter operates on its internal oscillator, it shall continuously

monitor the frequency of the input source and when the input source

frequency returns to within synchronization limit, the Inverter shall

automatically synchronize itself with the input A/C source frequency

and use it as a signal for Inverter output frequency control.

Battery Operation :

When the A/C input voltage drops below specified limits or in case of

a power failure the Inverter continues to supply AC power of constant

voltage and constant frequency utilizing the battery system as a power

source until the input voltage returns to normal requirement. When

the power supply is resumed or the input voltage returns to limits, the

Converter shall automatically start and the load fed for normal

operation status.

If the power failure continues beyond battery backup time or the

battery voltage drops to the final discharge voltage, the Inverter

should automatically stop and at the same time transferring the load

to the bypass circuit. On resumption of power supply, the Converter

shall automatically re-start the operations and charge the batteries

whereas the Inverter should inhibit automatic start and should be

started manually.

Page 258: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 258 of 307

Bypass Operation:

When power is supplied from the Inverter in synchronization with the

bypass, it shall accomplish the following :

When the UPS output current reaches overload status it shall

automatically transfer the load to bypass circuit with no interruption

and when the overload status is cleared it automatically the load to

Inverter.

When the battery final discharge condition is reached, the load shall

automatically be transferred to the bypass circuit without

interruption.

In case of failure of the UPS, the load shall be automatically

transferred to the bypass circuit with no interruption and when the

failure is cleared, re-transfer the load to the Inverter shall be done

manually.

There should be provision made in the system to prevent, when

necessary, asynchronous transfer.

When the UPS goes on bypass mode in any of the conditions

described above and it at that time there is no bypass power supply

available due to power failure, the UPS shall remain in standby mode

and as soon as the bypass power supply is available will transfer the

load to bypass.

A maintenance bypass transfer switch shall be provided with lock and

key arrangement and should be manually done by authorized

personnel only.

INSPECTION & TESTING

The Vendor shall perform the routine tests at works, whereas full load

and THD measurement at site prior to handing over, to confirm the

functional and the performance specification of the UPS as specified.

All required test equipment like Digital Oscilloscope, Voltage

Regulator, and Measurement Meters etc. shall be the responsibility of

the Vendor without any additional cost.

The Vendor shall demonstrate as a minimum the following features on

site by providing all required test equipment, such as power factor

improvement, input current THD, output voltage THD, output

frequency and all other performance monitoring requirements detailed

before as required by the Owner.

CONSTRUCTIONAL FEATURES FOR CABINETS / ENCLOSURE

The UPS system shall be installed indoors. The inverters, static

switches, chargers, batteries and manual by pass switches shall be

located in cabinets to be installed in UPS room. Voltage stabilizer and

isolation transformers shall also be located in individual enclosures if

provided along with UPS.

The construction details for UPS system cabinets / enclosures shall

conform to the requirements of the following Paragraphs.

Page 259: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 259 of 307

Enclosure

Equipment enclosures shall match and line up in similar assemblies

of free-standing floor mounted cabinets designed for indoor service.

The degree of protection shall conform to IP-20.

All enclosures shall be in approved color finish.

METHOD OF MEASUREMENT

Supply of the products including transport to site, loading and

unloading etc. as specified will be treated as one unit for measurement

and payment after successful commissioning.

GUARANTEE & WARRENTY

The Bidder shall stand guarantee for the performance of entire

equipment and components for twelve (12) months from the date of

commissioning or eighteen (18) months from the date of dispatch,

whichever is earlier, as agreed up on and as reproduced in the

purchase order within the tolerance specified or as permitted by the

relevant standards for the equipment in his scope of supply. The

Purchaser also reserves the right to use the rejected equipment or

part thereof until the new equipment meeting the guaranteed

performance is supplied by the Bidder.

ATTACHMENTS

Data sheet

TECHNICAL DATA SHEET FOR INVERTER SYSTEM

NO. PARTICULAR DESCRIPTION

1.0 KVA rating 1400 VA

2.0 Quantity 1 Nos.

3.0 Technology IGBT (Insulated Gate Bipolar Transistor) PWM

technology True ON-LINE. Capable of high

frequency application, high switching speed.

4.0 Inversion Frequency Above 16 KHz.

5.0 Input Voltage Range 230 - 240 V Single Phase

6.0 Input Frequency 48 Hz. To 53 Hz.

7.0 Output Voltage 230 V +/- 1% 3 phase & Neutral OR 230V+/- 1 %

8.0 Output Frequency 50 Hz. +/- 0.1%

9.0 Load capacity Full resistive Load as per KVA rating

10.0 Total Harmonic Distortion in

output

Less than 4% for 100% Non Linear Load.

11.0 Output Waveform Sine Wave - on mains

Sine Wave - on battery

12.0 Efficiency Inverter above 85%

Over all above 90%

13.0 Inverter Type High Frequency switching sinusoidal multiple

pulse with modulation. If six pulse consider

Page 260: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 260 of 307

NO. PARTICULAR DESCRIPTION

provide extra AHF and if 12 pulse consider provide

double wound transformer at the input.

14.0 Transient response < 5% Recover with in 20ms.

15.0 Over load capacity 110% for 1 Hr., 125% for 8 Min., and 150 % for 10

sec

16.0 Bypass line Stabilized

17.0 Transfer time In Sync mode – less than 4 millisecond

In Async. mode – less than 20 millisecond

18.0 Cooling Air cooling

19.0 Noise Level Except for Crest factor which is a characteristic

respect to load and not a Monitoring device.

20.0 Protections Input / Output low & high Voltage protection

Battery low voltage

Battery MCB

21.0 Monitoring / Metering

( Digital type )

Output Voltage

Digital Frequency meter

Ammeter

D.C. Battery Voltmeter and current

22.0 Display Input Voltage (Phase to Phase). Input Current per

phase. Bypass Input Voltage (Ph/Ph And Ph/N ).

By pass input Frequency, Inv. Output Voltage

(Ph/Ph & Ph/N) ,Inv. Output current per phase

,Input output and bypass frequency, % load at the

inverter output ,Inverter output power factor.

Inverter output in KVA and KW,DC voltage, battery

current(charge/discharge),Battery Back uptime

and remaining services life Temperature in the

Battery clubicle.

23.0 Remote Indication Potential free change over contacts to be provided

for fault identification & indication.

24.0 Audible Alarm Mains Fail

Battery Low

25.0 Cooling Forced Air-cooled ( by cooling fan)

26.0 Switch Gear MCB, Inverter On-Off switch, Manually By Pass

Switch.

27.0 Temperature 0-40 deg. Cen. At 95% relative humidity ( non-

condensing )

28.0 Type of Battery Sealed Maintenance Free (SMF) batteries

29.0 Back up 30 Minute.

30.0 Testing Load test on site should be provided

31.0 Enclosure Battery housed in large cubicle or in separate

matching cubicle made out of 14 SWG CRCA

sheet.

Page 261: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 261 of 307

NO. PARTICULAR DESCRIPTION

32.0 EMI / RFI Filters Metallic case double stage

Response time – 20/8 micro second

Surge withstand – 12 KV

Attenuation – More then 40 Db

Bandwidth – 40 MHz to 100 MHz.

Common mode – Return through earth

Voltage – 250 v +/- 10 % per phase, 433 v +/- 10

% Line voltage

Ampere capacity – 200 amps. Per phase

5.0 EARTHING AND LIGHTNING PROTECTION:

Supply of Earthing and Lightning Protection System:

5.1 Scope:

(a) Earthing System to be provided shall comprise of earth electrode in earth

pits, earth bus/ grid of copper/GI flats and bare copper/GI wires as

earth continuity conductor.

(b) Lightning Protection System shall comprise of early streamer emission

type air terminal system, earth electrode of G.I. plate in earth pits, earth

bus of down conductors of G.I. flats.

(c) Entire earth system shall conform to the Code of Practice as per IS with

its latest amendments.

5.2 General Requirements:

(a) Enclosures and frame work of all current carrying equipment and

accessories, structural steel/ columns shall be adequately earthed to a

single earthing system, unless separate earthing systems are specifically

stipulated. All three phase electrical equipment shall be earthed at two

distinct points.

(b) Earth leads and risers shall follow as directed and as short a path as

possible. Suitable risers shall be provided as directed if equipment is not

available when earthing is installed.

(c) Terminations at equipment like motors shall have flexibility for

movement of equipment.

5.3 Earth Bus and Earth Continuity Conductor:

(a) Earth bus is a Copper/ G.I. strip or flat of specified size interconnecting

all earth electrodes. This will be laid throughout the length of electrical

shaft.

(b) Fused DBs, MCB DBs and motors up to 30 kW rating shall be earthed by

a G.I continuity conductor, as specified. Minimum size of continuity

conductor shall be 8 SWG bare G.I., soft drawn. All power panels shall

Page 262: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 262 of 307

be earthed by G.I. Strip. Dedicated copper earthing for UPS & Server

room.

5.4 Lightning Protection System:

(a) The air terminal shall be early streamer emission type, which shall be

equipped with a lower series of energy collecting electrodes and an upper

series of spark generating electrodes.

(b) Earth electrodes for lightning protection system shall be G.I. plate

installed in earth pits as per I.S.

(c) The down conductors from air terminals shall be galvanized iron flat

strips, hot dipped of size 32mm.x 6mm. as required. The down

conductor shall follow a direct path to the earth electrode without any

sharp bend, turn or kinks. These down conductors shall not be

connected to earthing conductors above ground level but the metallic

parts in the vicinity of lightning protection conductors such as ladders,

pipes etc. shall be effectively connected and bonded.

(d) A test joint as per IS shall be provided for every down conductor within

1500mm. above ground level.

(e) Hardware and clamps shall be similar as used for the Earthing systems.

5.5 Artificial Treatment of Soil:

If the earth resistance is too high and the multiple electrode earthing does not

give adequate low resistance to earth, then the soil resistivity immediately

surrounding the earth electrodes shall be reduced by adding sodium chloride,

sodium carbonate, copper sulfate, salt and soft coke or charcoal in suitable

proportions.

5.6 Resistance to Earth: The resistance to each earthing system shall not exceed 1.0 ohm.

5.7 TESTING, MANUFACTURER’S TESTS, PRE-COMMISSIONING TESTS AND COMPLETE COMMISSIONING

The General intent of this specification is to mention the relevant tests to be

done and furnished to the Employer by the Contractor. These are guidelines.

However, the Contractor shall carry out all such tests and complete all

formalities as per relevant Indian Standard Specifications, Tariff Advisory

Committee's rules and Fire Insurance Requirements and/or Electricity Rules

and Regulations as per Government Gazette and Publications.

5.8 Testing of Equipment:

All equipment before installing on the site work shall be tested and all such

results produced to the Employer. Nothing shall absolve the Contractor from re-

performing any tests that the Contractor may be called upon specifically by the

Architects/PMC/Employer or supply company or electrical inspector. All

equipment shall be tested jointly with the Consultants/ PMC/ Employer as

Page 263: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 263 of 307

required by various sections of the specifications and test data shall be

furnished as required.

5.9 Pre-commissioning Tests:

All rules, regulations and requirements of Electrical, Government or Local

Authorities and of Indian Standard Specifications and/or Rules and

Regulations stated in Indian Electricity Act shall be strictly complied.

On completion of erection the contractor shall clean all the equipment

thoroughly and inspect the entire installation for correctness and shall furnish

a report of completion to the Consultant/ PMC. Pre-commissioning tests shall

commence only on approval of this report by the Consultant/ PMC/ Employer.

All tests and the certification thereof shall only be carried out by those

authorized, skilled, experienced and certified permit holders of the Supervisor

Category of State Government’s Industries and Labour Department. No

unauthorized personnel shall ever carry out any such tests as stated herein

under.

i) Phantom load tests for Protective Relays.

ii) Insulation tests at the following points by 1000 Volts and/or 500 Volts

megger.

Between phase and phase and neutral and phase and earth at Bus bars, all

outgoings, cables, distribution Boards, Sub-Distribution Boards etc.

Capacitor terminals between phases.

iii) Mechanical Operational tests for all movable parts of switchgears, breakers

tripping devices etc.

iv) Phase sequence tests at all the relevant points for connecting correct R, Y

and B as per the supply authority’s positions.

v) All Panels to be tested for interlocks, control tripping and breakers to be

tested for sequential trippings.

vi) Capacitors banks shall be tested for all residual voltages on the terminal of

the units and it should not exceed 50 V after one minute.

vii) For point wiring insulation resistance tests for all wiring, with switchgear in

closed positions and loads connected.

viii) Continuity tests shall be done for noting any short circuits and/or earthing

of phases.

ix) Earthing tests for continuity of Earth by earth megger, on L.V. side the

reading shall not exceed 5 ohm and Computer dedicated earth reading shall

not exceed 1 ohm.

5.10 Commissioning:

a) Prior to commencement of installation work the Contractor shall obtain the

approval of the sub-station drawings, if any, and electrical layouts prepared

by him from the Electrical Inspector (or any other statutory authority

Page 264: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 264 of 307

including supply company). The time involved in this is included in the

overall completion period of the contract.

b) The Contractor shall obtain the written permission and sanction of

commissioning the equipment and sub-station (if applicable) from

Electrical Inspector and from Consultants/ PMC.

c) All costs, incidental to obtaining such sanctions shall be to the Contractors'

account.

d) Contractor shall furnish all the necessary tests and test-reports to the

Electrical Supply Authorities and complete all formalities required to comply

as per the Rules and Regulations laid down for release of Electric Supply. If

called on, the Contractor shall carry out all such tests and prove the results

to the entire satisfaction of the local and Electric Supply Authorities.

All costs and expenses incidental to the release of Electric Supply shall be to

the Contractor's account and no demand whatsoever shall be to the Employer,

except for any Security Deposits that the Supply Authorities would deem

necessary for charging of the line, except as may be provided for in the

schedule of quantities.

All such documents forwarded and / or letters and/or correspondence

exchanged in this regard shall be made available for inspection and the

Contractor shall furnish 3 sets of such documents and drawings for the

Employer's records.

After release of Electric Supply to Employer's premises, the Contractor shall

furnish six sets of all tests declared to the Supply Co. Authorities and shall

furnish all such documents, officially exchanged between the Contractor and

Supply Co. Authorities for the record of employers.

Contractor shall also obtain and furnish the relevant completion certificate

from the Electrical Inspector, Fire Officer and/or any other Authority thereof

whichever may be applicable.

The scope of the contractor under commissioning also includes for doing relay

settings so as to achieve proper discrimination and an installation free of

nuisance trippings.

6.0 DOCUMENTS, CERTIFICATES, DRAWINGS AND SPARE REQUIREMENTS:

The intent of this specification is to give a guideline to the Contractor to furnish

in reproducible all sets of relevant papers and lists of spares for the continuous

performance of the electrical installation. Nothing shall absolve the Contractor

from furnishing any information document and/or papers that have not

been specifically stated herein.

6.1 Documents: All relevant maintenance and operation manuals and dates of all Electrical

Equipment supplied and erected by the Contractor on the site shall be bound

and furnished to the Employer

Page 265: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 265 of 307

6.2 Certificate:

All relevant test certificates etc. and as more specifically stated in clause, shall

be furnished. Contractor shall also furnish all such certificates issued by the

original manufacture towards guarantee of performance of all equipment

supplied.

6.3 Drawings:

All working and erection drawings of the final erected plan of all electrical

installation work in reproducible of equipment such as Breakers, L.T. Panels,

Distribution Boards, Cable routing, sizing, connection diagrams, circuits, wiring

diagrams and conductor sizes, lengths, termination details, operational charts,

recorded readings, conduit, light fittings, socket outlet layout drawings etc.

shall be furnished to the Employer. The employer reserves the right to the

mode of submission of such details being furnished by the Contractor.

All colored drawing shall be providing by contractor in A2 Print.

6.4 Spare Requirements:

The Contractor shall, notwithstanding anything stated otherwise, furnish lists

of recommended maintenance tools, spares, fuses, sets, codes, catalogues,

appropriate pricing, original equipment manufacturers' addresses, etc. to the

Employer. Prior to such furnishing Contractor shall make a proper assessment

of all such requirements and then proceed to make lists. The Contractor shall

also be deemed to have understood the requirements, in such a way that it

ensures a continuous operation and functioning of the Electrical Equipment

under the stated ratings conditions and specifications.

7.0 CODES AND STANDARDS APPLICABLE

7.1 Codes & Standards

The entire electrical system shall comply with the latest versions of IS. Codes and IEC

guidelines as detailed under various Equipment’s, Items & Systems, above that it shall

also comply with:

• Code of Practice of Electrical Wiring : IS 732

• Code of Practice for fire safety of buildings

(General) Electrical Installation

: IS 1646

• Specification of conduits for electrical

installation

: IS 8130

• Danger Notice Boards : IS 2557 / IS 5-1978 /

IS 2551-1982

• Earthing : IS 3043

• Installation of switch gear : IS 3072

• Ingress Protection of Enclosures : IS 2147

Page 266: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 266 of 307

• Meters : IS 1248

• General requirement for switchgear and

control gear for voltage not exceeding 1000V

: IS 4237

• Marking and arrangement for switchgear

busbars, main connection, and aux. Wiring

: IS 375

• Code of Practice for installation and

maintenance of switch gear

: IS 10118

• Specifications for factory built assemblies of

Switchgear

: IS 8623

• Indian Electricity Act and Rules

Regulations for Electrical equipment and buildings issued by Bombay Regional Council of

Fire Insurance Association of India.

8.0 Fire Alarm System

8.1 Scope of Work and Exclusions

The work shall comprise entire labour including supervision and all materials necessary

to make a complete installation to the entire satisfaction of the Client /Consultant. The

term complete installation shall mean, not only major items of equipment covered by

these specifications, but also incidental sundry components necessary for complete

execution and satisfactory performance of the installation, with all labour charges,

whether or not these have been mentioned in detail in the tender documents. The work

shall include data entry, programming, start-up test and demonstration, training of

personnel for maintenance and operation, submission of construction and installation

drawings and wiring diagrams, as built documents and system guarantee and for

approval by the Statutory Authorities.

The Contractors’ scope of work will include all items of work as per these

specifications, drawings, terms and conditions of contract etc. and briefly described

in schedule of quantities. This shall include, but not be restricted to the following: -

� Intelligent Addressable Optical Smoke & Heat Detectors

� Manual Call Points

� Microprocessor Based Intelligent Addressable Main Fire Alarm Control Panel

for connecting and monitoring the Fire Detectors and other devices.

� Low and High Intensity Hooters activated from the Panel.

� Providing suitable compatibility in the Main Fire Alarm Control Panel for the

Public Address System, audio Amplifiers, speakers & required wiring.

� Providing suitable compatibility in the Main Fire Alarm Control Panel with

inbuilt Talk Back System having loop connection with jacks with compatible

to portable Handset at each floor and Exist & required wiring.

� Electrical works, including Cabling, Earthing etc. for the installation.

Page 267: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 267 of 307

� All other works associated with above items as per specifications, drawings

and conditions of contract and the Mumbai Fire Brigade requirements

except those specifically excluded in Schedule of Quantities.

Unless otherwise indicated in Schedule of Quantities and drawings, the

Contractor's scope of work will exclude only the following items of work and

services, which will be arranged by the Engineer-In-charge through other

contractors, if required: -

Provisions of adequate AC, single/ three phase, 230/415 V, 50 HZ supply with earthing

for Fire Control Panels etc.

8.2 General Description of Intelligent Fire Alarm System

The detectors shall be Addressable Intelligent optical detectors.

• The number of detectors and location shall confirm to relevant standards but not

less than one detector per 49-sq. meter area. Addressable intelligent optical

detectors shall be used. The detectors shall give the visual and audible alarm at the

respective control Panel. The panels shall be located in the respective ground floor

control rooms.

• The fire alarm panel shall operate 240V+ 10% 50Hz. The FDAS shall also be

provided with a dedicated standby power supply system (battery and charger)

capable of maintaining the system for a period of not less than 24 hours after

failure of ac power supply after which sufficient battery shall remain to provide full

load operation for at least 30 minutes in line with IS 2189.

• Armoured FRLS cables shall be used from detectors to the alarm panel confirming

to the relevant IS and from reputed manufacture.

The system should be able to detect any type of smoke, fire and heat in the respective

site/area.

8.3 Detailed Description of the System Components:

Basis of Design

� An Intelligent Modular/ Expandable Fire Alarm System (IFAS) shall be provided to

effect total control over the life safety services required in the building.

� The system shall be provided with Addressable fire alarm initiating, annunciating

and control devices.

� The addressable and intelligent system shall be such that smoke sensors, thermal

sensors, manual call points, etc., can be identified with point address.

� The FAS shall be able to recognize normal and alarm conditions, below normal

sensor values that reveal trouble condition, and above normal values that indicate

either a alarm condition or the need of maintenance.

Page 268: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 268 of 307

� Read-out or address an actual detector location. The operator shall also be able to

adjust alarm and alarm thresholds and other Parameters for the smoke sensors.

� Provide a maintenance/pre-alert alarm capability at smoke sensors to prevent the

detectors from indicating a false alarm due to dust, dirt etc.

� Provide alarm verification of individual smoke sensors. Systems that performs

alarm verification on a zone basis shall not be acceptable. Alarm verification shall

be printed on the printer at the Control Station’s printer to enhance system

maintenance and identify possible problem areas.

� Provide local numeric point address and LED display of device and current

condition of the point.

� Each detector shall use state-of-the-art Microprocessor Circuitry with error,

detector self-diagnostics and supervision programs.

� The detection of the fire shall be taken at the detector level.

� Multi-Criteria Detectors shall be offered whereby the system logic activation is

based on any three inputs from the detector i.e. smoke, heat or neural network.

� Provide outputs that are addressable, i.e. outputs shall have point address. The

operator shall be able to command such points manually or assign the points to

Logical Point Groups (Software Zones) for pre-programmed operation.

� In the event of a fire alarm, but not in a fault condition, the following action shall

be performed automatically.

� The System Alarm LED on the main fire alarm control panel shall flash.

� A local sounder shall be sounded.

� The LCD display on the main fire alarm control panel shall indicate all information

associated with Fire Alarm condition including the type of alarm point and its

location within the premises.

� Printing and history storage equipment shall log the information associated with

the Fire Alarm Control Panel condition, along with the time and date of occurrence.

� All system output programs assigned via control-by-event programs that are to be

activated by a particular point in alarm shall be executed, and the associated

system outputs (alarm notification appliances and/or relays) shall be activated.

9.0 FIRE ALARM CONTROL PANEL (FACP)

� The Addressable Fire Alarm Control Panel (FACP) shall function as fully stand-

alone panel as well as providing a communication interface to the central station

where many such panels will be in a network. FACP shall has its own

microprocessor, software and memory. In the event of failure of the central or

communication breakdown between the central station and the FACP, the FACP

shall automatically operate on stand-alone mode without sacrificing any functions.

Page 269: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 269 of 307

� The panel should be modular microprocessor based in nature and should be 4 loop

or Mention in the Bill of Quantity & expandable upto 32 loops (4000 devices –

addresses).

� FACP shall supervise detection circuits and shall generate an alarm in case of

abnormal conditions.

� FACP shall provide general purpose inputs for monitoring such functions as low

battery or AC power failure. FACP shall have tamper protection and programmable

outputs, which can operate relays or logic level devices.

� Smoke detectors / Multi-Criteria Detectors shall be powered using the FACP-based

smoke detection circuits. FACPs shall provide for resetting smoke detectors, fault-

isolation and sensor loop operation. It shall be possible to mix different fire devices

within the same FACP to optimize field wiring.

� It shall be possible for the panel to have a minimum loop length of 1 km of length

of devices from the panel.

� FACPs shall provide monitoring and control of one floor or area or for multiple

floors or areas. FACPs shall meet the following requirements to assure the integrity

and reliability of the system:

� The FACP shall be UL /VDS listed independently as a fire alarm control panel.

� The FACP should have integrated power distribution module and fixed cabling

done internally to guarantee a clear and tidy cable feed.

� The panel should preferably have a LCD touch screen of 5/7 inches size (320 x

240 dpi) is used as display and keypad. The touch display should enable a flexible

design of the operating menu with variable keys and message windows. 23 fixed

keys should be used for standard operating steps. The current status of the system

should be displayed by 11 LEDs. 3 interfaces (RS232,) enable the connection to a

PC.

� All materials and components used in the panel are specified as per UL94 V- 0 or

higher.

� The panel should have a 240 V AC power supply unit in plug-in design with rack

and panel connector is a 24V DC/6A single output power supply. The module

should be protected against over=voltage and reverse polarity. The output voltage is

monitored and regulated externally.

� LCD display at the FACP shall be provided to indicate point in alarm or trouble. In

such systems, means for manually scanning the points in trouble shall be provided

and a trouble and alarm LED shall be used to indicate that there are points in

alarm/trouble. The alarm/trouble LED shall only extinguish when all

alarm/troubles are cleared from the loop.

� It shall be possible to command test, reset and alarm silence from the FACP.

� FACP switches shall allow authorized personnel to accomplish the following,

independent of the central console:

Page 270: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 270 of 307

� Acknowledge a general alarm condition.

� Silence the local audible alarm.

� It shall be possible to Silence the alarm indicating devices (hooters).

� Reset all zones (Logical Point Group) / points, after all initiating devices have

returned to normal.

� Perform a complete operational test of the memory with a visual indication.

� Test all panel LEDs for proper operation without causing a change in the condition

of any zone (Logical Point Group)

9.1 Walk Test

� Software zones/loops shall be circuited and protected by Fault Isolation Modules

such that in the event of a zone/loop short-circuit, Intelligent Smoke and thermal

sensors shall be located as shown and shall report alarm

� Monitoring modules shall be provided to monitor and address contact-type input

devices. The monitor module shall be housed in the FACP supervised by FACP.

� The FACP detectors shall have Drift Compensation facility to compensate for

environment.

� The FACP should be UL / EN / Vds listed approved to provide the sensitivity

measurement and documentation required. FACP shall be backed up with its built

in UPS power.

� The display on FACP shall provide indication for AC Power, System Alarm, System

Trouble/Security Alarm, Display Trouble and Signal Silence. This would mean that

in the event of change of any logic, detector / zone sequence alteration, the

operator can initiate these by use of the LCD touch pad & alpha-numeric keys on

the FACP panel to reconfigure the above Parameters.

� Power supply unit of FACP shall have following characters:

� The main power supply shall be 230 VAC±10%, 50 Hz±3% and shall in turn

provide all necessary power of the FACP.

� It shall provide a separate battery control module with charger.

� For ease of service, all wiring terminal blocks shall be plug-in type.

� The Fire Alarm Panels shall have a possibility of being interlinked either by direct

connectivity or an optical cable link between the various locations and should

further have connectivity to the main control centre.

10.0 MANUAL CALL POINT: -

Each manual call point unit shall comprise of a push button of reputed make enclosed in

box. The push button shall have minimum 1 NC and NO contacts. The push button

assembly is enclosed in the M.S. box enclosure with all sides covered except the front

side. The front side shall be sealed with breakable glass cover using neoprene or

equivalent gasket. In case of fire, when the glass cover is broken to give the fire warming

Page 271: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 271 of 307

the push button will be released due to spring action hence giving remote fire alarm

through the NC contact. Call points can be reset with the test key & then by replacing the

glass.

The box enclosure shall be completely dust, vermin damp and weather proof. They shall

be made of steel sheet of 16 swg. The complete unit shall be suitable for wall mounting

with necessary mounting Accessories. The complete unit and the push button shall be

painted signal red. The internal surface of the enclosure of the box shall be painted of

white colour. The external painting shall be synthetic enamel.

Break Glass in case of Fire shall be written on each MCP unit, either on the enclosure or

on a separate metal plate mounted behind the glass cover. Each unit shall be equipped

with an iron hammer with a hook fixed to the external enclosure.

10.1 HOOTER:

Two different types of hooters have been provided on the installation.

a. Simple 24 volt D.C. operated Electronic Hooter. This are connected directly to the main

control panel by switch twin wires, if desired in a ring circuit. This can be activated

automatically or manually, as desired by the switches provided at additional control panel

for P.A. system etc.

b. P.A. Speaker cum Hooter, working on 0 – 100-volt line through a suitable line matching

transformer. This will automatically give the evacuation alarm in case of fire condition

and can subsequently be used for public announcements through the P.A. system when

provided. These are also connected directly to the Main Control Panel preferably by the

ring circuit.

10.2 SMOKE DETECTOR:

Two major types of Smoke Detectors are available.

One is an ionization device that contains a small radioactive source (AM 241 less than 1

micro curie) for ionizing the air molecules between a pair of electrodes, permitting a very

small current to flow between the pair. If smoke particles from a fire enter this space, they

reduce the flow of current by adhering to the ionized molecules. The drop in current sets

off a buzzer or other alarm.

The second type of smoke detector uses a photoelectric cell. In some of these detectors,

smoke that enters obscures a steady beam of light; in others, the smoke scatters a light

ray from a diode so that the cell can detect it. In either case the change sets off an alarm.

The alarm may sound locally, or it may be designed to alert a central station with

notification of fire department.

Photoelectric detectors are slower than ionization detectors, and sometimes both

principles are combined.

10.3 HEAT DETECTOR:

Rate of rise / fixed temperature rating detector are designated for applications where a

rapid rise in temperature may be expected during and outbreak of fire. The detector

should incorporate both the rate of rise / fixed temperature operating principles. The

detector will react quickly to a rapid rise in temperature, but even if the increase is very

slow, signal will be transmitted to the control panel when the maximum temperature

Page 272: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 272 of 307

sensors gets actuated. The rate of rise sensor shall get actuated when the rate of rise in

temperature exceeds the rate of 150 F per minute the detector should sense the fire and

transmit a signal to the control panel. The fixed temperature element should sense the

fire when the temperature reaches 680 C.

10.4 FAULT ISOLATOR MODULE: - Designed to be used in addressable system communication loop to create a segment. It

detects the short circuit and isolates the segment where short circuit exists enabling all

other segment to work without interruption. This addressable unit also communicates the

location of fault to the control panel for audio-visual indication. The unit checks the

status every 5 seconds. If the fault is rectified automatically, it resets the segment back to

operation.

10.5 MONITOR MODULE: -

Module shall analyze ‘open’ or ‘close’ status. Module shall have integrated buzzer.

10.6 CONTROL MODULE: -

Control Modules conveniently distributed, providing signals for future building

automation requirements as well as output control modules to activate hoot.

10.7 BATTERY & BATTERY CHARGER:

Adequately rated batteries shall be connected via mains failure relay contact across 24

volts regulated D.C. supply. In normal condition, battery shall be kept on constant trickle

charge. Battery can be boost charged by manually operating trickle/boost toggle switch

when battery low indication is observed on the control panel. In case of mains failure,

battery shall automatically feed full supply load of the entire system consisting of fire

alarm and exit signs etc. Battery capacity shall fully meet the requirements of CI.5.2.IS

2189.

10.8 CABLE:

Cables required for complete fire alarm system for interconnecting fire alarm panels,

detectors, manual call points, other field devices, repeater panel, etc., shall be 1100V

grade, multicore, annealed, high conductivity stranded copper conductor, extruded PVC

insulated, laid up inner sheathed, galvanized steel strip / wire armored, outer FRLS

extruded PVC sheathed cable as per IS-1554-Part - I, 1988.

The Contractor shall supply and install all cables required for looping between detectors

and Manual call points and wiring out of connections to a marshalling / junction box in

each zone

As required

11.0 P.A. SYSTEM:

The main control panel, should contain an amplifier of suitable capacity, to activate the

Public Address System.

The Public Address System to be hooked to the Detection circuits. Provision for an alarm

to trigger the amplifier. The evacuation tone can be silenced from the switch marked

Page 273: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 273 of 307

‘siren off’ on the P.A. Panel and the announcement on the affected zone can be made

straight away from the microphone provided without pressing any buttons. On completion

of announcement the system should be able to be reset by the reset button on the panel.

Alternatively, an arrangement for announcement to be made on a desired zone should be

available by pressing the switch provided on a P.A. Panel. This will again switch on the

amplifier. The all call or Master Control switch can make the Announcement

simultaneously on all the floors.

The VU meter provided indicates the volume. The Amplifier should have the requisite

controls for the desired tonal quality.

11.1 AMPLIFIER All amplifiers shall be mixing type for combining speech and music.

The power amplifiers shall have adequate continuous (RMS) power output

to meet the requirement of the configuration. The unit shall be capable of

delivering the rated output watts with less than 0.05% harmonic

distortion in the design bandwidth. The amplifier shall have a broad band

frequency response of 20 Hz to 20 KHz. The output voltage and

impedance shall meet with the system requirements.

The distributed audio amplifiers shall be magnetically coupled switch

mode type with two input signal sources selectable manually or

automatically by the fire alarm system. Output wattage shall be as shown

in the schedule of work or as required to meet the needs of the PA System.

Power as well as audio amplifiers shall be mounted in suitable wall

mounted/floor standing enclosures.

11.2 Booster Amplifier: a) Rated Output Voltage(RMS) :120/240/480 W as per wattage

b) Class : Class-D Digital

c) Battery Voltage : 24VDC(max 10% deviation)

d) Frequency Response : 50Hz to 15KHz

e) Impedance : 10KOhm

f) S/N Ratio : >82 dB

g) Sensitivity : Max 300mV(set at 1V)

h) Total Harmonic Distortion : Less than 0.5% @ 1kHz

11.3 SPEAKERS

Speakers shall be especially designed for broadcasting high quality,

integrated emergency fire alarm signals and voice communications.

Speakers shall be ceiling or Column mounted as shown in the

schedule of work and shall be completed with mounting brackets

accessories etc. Speakers shall be in wooden or metal enclosures.

Speakers shall be of high efficiency yielding maximum output at

minimum power across 200 – 12000 Hz frequency ranges. Speakers

shall have a line-matching transformer for direct connection to

Page 274: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 274 of 307

amplifiers with multiple taps. Speakers shall be mounted in a

rugged metal housing with vandal resistant grille if specified.

Speakers shall be interconnected in the zone configuration.

11.4 Ceiling Loudspeaker a) Max. Power – 9 W

b) Rated Power - 6 Watts

c) SPL at 1kHz, 1m, 1w: 98dB/90 (SPL)

d) Rated Voltage: 100 volts

e) Impedance: 8 ohms

f) Effective frequency range (-10dB) :(80 Hz to 16000 Hz)

g) Size: (H) in mm: 70

h) Weight: 800 g.

11.5 Call station

The call station can make manual or pre-recorded announcements to any pre-

assigned zones. The call station basic a microphone on a flexible stem, a push to-

talk button, a speaker, and a headset socket

The call station has a cardioid, supervised microphone on a gooseneck stem with

good speech intelligibility. A limiter and a speech filter improve intelligibility and

prevent clipping of the audio. It has a volume control for the monitoring speaker and

the headset. When it plays a chime or a pre-recorded message, the call station

activates its speaker. When a headset is connected, it replaces the microphone and

speaker. The call station has its own DSP, and converts between analog and digital

audio. The audio processing can include sensitivity adjustment, limiting, and

Parametric equalization.

Up to 16 call station keypads can connect to the station via a serial communication

link. The station provides the power for the keypads. Up to 224 priorities can be

assigned to the call station. The call station is fully supervised and supports fail-

safe operation.

11.6 Call station a) Output – 2W (Max.) in each amplifier

b) Protections- AC Fuse 1 × 0.5A

c) Power requirement: AC: 220-240V,50/60Hz

d) Weight: Attendant Unit: 1.3kg, Customer Unit: 0.55kg, Power Supply Unit:

0.93kg

11.7 P A SYSTEM WIRING

PA system wiring shall be done with cable in minimum 20 mm dia

PVC conduit including termination complete as required.

The speakers in each zone are connected in Parallel and are

connected to the respective output. The cables from each zone are

separately routed and terminated in the Panel.

12.0 PREMABLE TO BILL OF QUANTITIES 12.1 The Bill of Quantities must be read with the scope of work, Conditions of

Contract, Drawings and the Specifications and the Contractor shall be deemed to

have examined the Scope of Work, Drawings, Specifications, Conditions of Contract

Page 275: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 275 of 307

and to have visited the Site and acquainted himself with the Works to be done and

the way in which they are to be carried out and all factors affecting the execution of

the Works and the Costs thereof including temporary works if required to complete

the works.

12.2 All work shall be measured net as it is finished and/or fixed in the Works

and no allowance shall be made for wastage notwithstanding any general or local

custom. Any items of work not covered in the Preamble shall be measured as per

specifications for works methods laid down in relevant Indian Standards or as

decided by the MDL Engineer.

12.3 The quantities set down against the items in this Bill of Quantities are an

approximate estimate of the quantity of each kind of work included in the Contract

and are given for the convenience of forming a common basis for tendering. They

are not to be taken as a guarantee that the quantities scheduled will be carried out

or required or that they will not be exceeded. The MDL reserves the right to delete

any item indicated in the bill of quantities at any time.

12.4 The quantities shall therefore not be considered as representing the final

measurements, it being the intention of the Contract (except where otherwise

specifically stated) that the actual quantities of work ordered and carried out shall

be jointly measured on completion by the MDL Engineer or his authorized

representative and the Contractor and valued and paid for at such prices and rates

entered by the Contractor in the Bill of Quantities.

12.5 The rates and prices set down against the items are to be the full inclusive

value of the finished work shown on the Drawing and/or described in the

Specifications or which can reasonably be inferred there from and to cover the cost

of every description of Temporary Works executed or used in connection therewith

(except those items in respect of which specific provision has been separately made

in this Bill of Quantities) and all the Contractor's obligations under the Contract

including testing, giving samples and all matters and things necessary for the

proper execution, completion and maintenance of the Works. No claim for

additional payment shall be allowed for any error or misunderstanding by the

Contractor of the work involved.

12.6 The Specifications and the various Sections in the Bill of Quantities are

intended to cover the supply of all the materials and the execution of all works

necessary to complete the Works. Should there be any details of Materials or

Construction which have not been referred to in the scope of work, specifications,

Bill of Quantities or the Tender Drawings, but the necessity for which may

reasonably be implied or inferred there from, or which are usual, or essential to the

completion of all works in all trades, the same shall be deemed to be included in

the rates and prices within in the Bill of Quantities. The rates and prices shall

cover the items as described in the scope of work, Bill of Quantities, tender

drawings and other terms and conditions of the contract.

12.7 The Contractor's unit rates and prices in the BOQ shall include all

equipment, apparatus, material, indicated in the BOQ, Scope of Work, Drawings,

Specifications in connection with the item in question and also associated labour

as well as all additional equipment, apparatus, material, consumables usually

necessary to complete the system even though not specifically shown, described or

otherwise referred to and also associated labour.

Page 276: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 276 of 307

It also includes delivering the material, item to the specified storage area at Site.

Installation of the same in the specified location as per Drawing & as specified,

testing and commissioning as per Specification and direction of the Engineer' at

Site.

The unit price shall be deemed to include everything necessary to complete the

work covered by this item in accordance with the scope of work, BOQ description,

Specifications and Drawings.

The sum total of all the individual item prices shall represent the total price of the

installation ready to be handed over.

Use of any tools, equipment, machinery, lifting tackle, ladders consumables etc.

required by the Contractor to carry out his work.

All the necessary measures to prevent the transmission of vibration. Storage and

insurance of all plant and equipment, apparatus and materials.

13.0 LIST OF APPROVED MAKES

The schedule of quantities may specify for some items the make of materials to

be quoted for. The list of makes given below is for materials other than those

mentioned in the schedule of quantities. In case, for any material, different

makes are listed below from that mentioned in the schedule of quantities then

the make mentioned in the schedule of quantities will only prevail and the

contractor will have to supply only that make mentioned in schedule of

quantities.

DESCRIPTION

MAKE

1 Cable Sockets/ Lugs Dowells

2 L.T. Switchgear GE/ Siemens/ L & T/ ABB/ Schneider

3 Selector Switches L & T / Kaycee/ Siemens/ Cutler

Hammer/ Schneider

4 MCBs/ ELCBs Siemens/ Schneider / Legrand (Lexic) /

L&T (Hager)/ GE / HPL Moeller/ABB

5. Ammeter/Voltmeter/P.F. Meter

(Analog)

Automatic Electric/ Rishab

6 Indicating Lamps 22.5mm dia.

(LED type)

Teknic/ Siemens/ Schneider/

L & T/ Schneider

7 L.T. Power Capacitors Universal/ L & T/ Crompton Greaves/

EPCOS

8 Connectors/ Terminal Blocks Elmex/ Essen

9 Energy Meters (Analog) Enercon/ Jaipur/ Universal/

Securemeters/ IMP

Page 277: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 277 of 307

DESCRIPTION

MAKE

10 Moulded Case Circuit Breakers ABB / L & T/ Siemens / GE/ Legrand /

Schneider

11 PVC Insulated Copper Wires

(including Panel Wires)

KEI / Policab/ Finolex

12 PVC conduit and accessories Precision / Circle Arc / Diamond

13 Switches /Sockets MK Honeywell/ Clipsal / Anchor

(Roma)/ Legrand (Mosaic)/ Siemens

/ABB

14 LED Lighting Fixtures (for

9W/12W/18W/36 tube lights,

flood lights

Phillips / GE Lighting/ Thorn/ Havells/

Wipro/ Bajaj/G.E

15 Lighting Fixtures (for CFL/ GLS

lamps)

Philips/ Tulip/ Crompton Greaves/

GE Lighting/ Thorn/ Wipro/ Bajaj

16 Lamps Philips/ Osram/ G.E.

17 Digital Panel Meters AE / Enercon/ Secure Meters/ HPL

18 Hot Dip G.I. Conduit BEC / VIMCO

19 Exhaust Fan Crompton Greaves/ Alstom/ approved

equivalent

20 Black Enamelled M.S. Conduit BEC/ NIC/ VIMCO

21 Industrial sockets & plugs Legrand / Clipsal

22 Storage Battery Exide/ Standard/ AMCO/ Amar Raja

23 Manufacturers of L.T. Panels Scoot Engg. Pvt. Ltd./ L & T/ Siemens/

Manshu Comtel Pvt. Ltd./ Arrow /

G.E.(Vivid Electromech Pvt. Ltd.)

24 Telephone Cables Delton/ Finolex

25 Battery Charger Excide/ Standard Batteries/ Sherene

Electro Control/ Argo/ AE.

26 Ceiling Rose & Batten Holder M.K. Electric/ CPL/ CrabTree

27 Cable Tray Sadhana/ Profab/ Indiana/ approved

equivalent/Puspak/Indiana/OM

28 SMF Battery Yuasa / Global Yuasa / Hitachi / Exide

Powersafe / Panasonic / China Storage

Battery (CSB)

29 H.T.Cable KEI/POLYCAB/UNIVERSAL/HAVELLS

Page 278: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 278 of 307

DESCRIPTION

MAKE

30 HT Panel ABB/SIEMENS/SCHNEIDER/MEGAWIN

31 L.T.Cables KEL/POLYCAB/UNIVERSAL/HAVELLS/

JEMSCAB/RR

32 End Termination Material Comet/Dowells/Jainson

33 RCCBs (Si Type) Legrand/SIEMENS/ Schneider /ABB

34 Distribution Boards Legrand/SIEMENS/ Schneider /ABB

35 Cable Trays & Raceways Profab / Paifab / Pushpak / Indiana

/OM

36 Conduits-PVC VIP/Precision/AKG/BEC

37

.

Conduits-M.S VIP/Precision/AKG/BEC

38 PVC insulated multistrand Copper

Conductors Wire-FRLS

Ploycab/ FINOLEX/RR/ANCHOR

39 Light Fixture internal Wipro/Philips/Havells

40 Light Fixture External Wipro/Philips/Havells

41 Occupancy Sensor Honeywell/wipro/philips

42 Switch Socket out-let Anchor Roma/ North

West/MK/Legrand/Clipsal/ HAVELLS

43 Inverters APC/Megatech/true power

44 Industrial power Sockets with

enclosures

Neptune / Datar

45 Lighting Arrestors Indelec/LPI/ Ingesco

46 Maintenance Free Earth Electrodes ASHLOK/GALAXY/JUM GATHARING

47 Ultrasonic RAT & Rodent Repellent

System

Maser/Sk vision/Casal

48 Call Bell System Forbixsemicon/SBI/NN

49 Mobile Charging Station GD/ACD

50 UV Mosquito Lamp Balaji/Super trap

51 Sandwitch Raising Main bus Duct C & S / Goderj/GE/Schneider

Page 279: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 279 of 307

DESCRIPTION

MAKE

52 PA SYSTEM Bosch /Boss

53 FIRE ALARM SYSTEM

Schreck/ Notifier / Simplex / Fire finder

/ Bosch / L&T

54 Armoured / Unarmoured FRLS

cables for FAS ,PAS & TBS

RR Kabel / Poliplast / Kenter / Havells /

Lapp

55 Cable glands Commet / Braco / HMI

56 Lugs, crimping type, tinned copper Dowell's /Axis

57 GI /MS Conduits BEC / Vimco / AKG

58 PVC Conduits Precision / Press Fit / Circle Arc

/Dimand

59 Any other Item Sample For Approval Of Engineer-In-

Charge / Consultants

Page 280: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 280 of 307

TECHNICAL SPECIFICATION

HVAC WORKS

Page 281: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 281 of 307

TECHNICAL SPECIFICATIONS FOR VARIABLE REFERIGERANT FLOW (VRF/VRV)

SYSTEMS

Scope of Work for HVAC System

1. Description of the Project The Angre House building is located in Mazagon Dock Shipbuilders Ltd, Mumbai. The Angre House building floor no. 17 & 18 which serves as Guest House, to have the new centralized VRF / VRV air conditioning system to ensure flexibility of operation, installation and maintenance of the HVAC system using latest state of the art technology and also the energy efficient one. 2. General Scope of Work

2.1 The scope of work comprises supply, installation, testing and commissioning of the

V.R.F./V.R.V. system as follows:

a) Indoor units as per the drawings with mounting brackets/supports.

b) Air-cooled outdoor condensing units with structural support. Supporting structure

shall be painted with 2 coats of epoxy and one coat of primer.

c) Treated Fresh Air unit.

d) Electrical panels with starters etc., for compressors motors, condenser fan motor and evaporator fan motors.

e) Digital thermostats and safety controls.

f) Installation accessories, mounting brackets, refrigerant piping, filter, drier etc.

g) First charge of eco-friendly refrigerant gas (R410A/407C) and oil.

h) Refrigerant piping with insulation-

Copper refrigerant piping inclusive of all valves and fittings of suitable diameter

compatible with the refrigerant gas & air conditioner model with insulation/nitrile

rubber sleeves, end connections to be installed true to line and level, jointing by

brazing & adequately supported intermittently at uniform distance with appropriate

clamps / support arrangement including making precise holes in walls with core

cutting m/c, providing sleeves & proper finishing for connectivity from indoor to

outdoor unit etc all complete as directed by MDL engineer. The alignment of copper

piping in horizontal and vertical direction to be maintained.

i) Ducting with insulation and air terminal devices as specified elsewhere.

j) Condensate drain piping for evaporator units inclusive of all valves and fittings.

k) Insulation of refrigerant piping and drain piping.

l) Electrical wiring from power supply.

m) Cable Tray work for External Refrigeration Piping work

Page 282: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 282 of 307

n) Control cabling between Indoor & Outdoor unit

o) Air Flow Controller

p) Automatic controls and instruments.

q) Vibration isolators for all HVAC equipment.

r) Testing and commissioning of the entire HVAC system at site. Contractor to note that all the equipments / materials shall be supplied with relevant quality / conformance / factory inspection documents.

2.2 The contractor shall arrange free of cost quarterly servicing of the entire HVAC

system during Defect liability period to keep the system in good and trouble free operating conditions. The servicing shall be carried out by OEM or authorized agency of OEM. It is preferred to appoint the AMC Contractor as a servicing agency/Contractor.

2.3 All the works under or in course of execution or executed in pursuance of the contract shall at all times be open to inspection & supervision of the MDL engineer / executives & the contractor at all times during the usual working hours offer assistance for the inspection of work.

2.4 The contractor shall raise inspection call to MDL in the agreed format for the works undertaken at below mentioned stages – a. After delivery of material at site before starting of installation works

b. Testing & commissioning of the completed works

2.5 The contractor shall submit supporting documents such as delivery challan(s), packing lists, Factory Test reports for the HVAC items in requisite sets as relevant along with the invoice for the purpose of certification by MDL engineer.

2.6 The general character and the scope of work to be carried out under this contract is illustrated in Drawings, Specifications and Schedule of Quantities. The Contractor shall carry out and complete the said work under this contract in every respect in conformity with the contract documents and with the direction of and to the satisfaction of the Consultant / Architect/ Client.

2.7 The contractor shall furnish all labour, materials and equipment as listed under Schedule of Quantities and specified otherwise, transportation and incidental necessary for supply, installation, testing and commissioning of the complete air conditioning system as described in the Specifications and as shown on the drawings.

2.8 Upon completion of all work and all tests, the Contractor shall depute necessary operators, labor and helpers for operating the entire HVAC installation for a period of ten (10) working days, to enable the Client’s personnel to get acquainted with the operation of the system. During this period, the contractor shall train the Client’s nominated personnel in the operation, adjustment and maintenance of all equipment installed.

2.9 The scope of work also includes Comprehensive all inclusive Annual Maintenance Contract (AMC) for 3 years after completion of defect liability period.

2.10 Scope also includes any material, equipment, appliances and incidental work not

specifically mentioned herein or noted on the Drawings / Documents as being furnished or installed, but which are necessary and customary to be performed under this contract for completion of entire work.

Page 283: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 283 of 307

2.11 At the time of execution, area shall be provided taking into consideration the space available at site, for storage of delivered material/equipment upon request of contractor. Contractor has to make his own arrangement for storage, safety & security of the material delivered at site.

2.12 Buy-Back of existing Air Conditioning Units

As per the list given in the tender documents, some of the existing old AC units (Split) along with copper tubing & its accessories are to be taken out of MDL by Contractor under buy-back arrangement (as is where is condition) as per BOQ.

Some of the AC units as per the list given in the tender documents are to be dismantled by the Contractor and to be handed over to MDL as per BOQ. These ACs are not to be taken out by the Contractor under buy-back scheme.

3. General Conditions & requirements - 3.1 Program of dispatch of material shall be framed keeping in view the progress of the

building renovation work. Safe custody of all machinery and equipment supplied by the contractor shall be the responsibility of the contractor.

3.2 Coordination with Other Agencies -

The contractor shall co-ordinate with all other agencies involved in the work so that the work of other agencies is not hampered due to his work. Ducting, piping, cabling or any other work, which directly affect the progress of building work, shall be given priority.

3.3 Quality of Materials & Workmanship

i) The components of the installation shall be of such design so as to satisfactorily function under all conditions of operation.

ii) The entire work of manufacture/fabrication, assembly and installation shall conform to sound engineering practice. The entire installation shall be such as to cause minimum transmission of noise and vibration to the building structure.

iii) All equipment’s and materials to be used in work shall be manufactured in factories of good repute having excellent track record of quality manufacturing, performance and proper after sales service.

3.4 PROTECTION OF WORK & MATERIAL i) Copper tubes stored on site shall be supported clear of the ground and kept

separate from all other stored ferrous materials & shall be suitably protected against the weather.

ii) All equipments and materials, fixed or unfixed shall be protected against ingress of dirt or moisture into working parts by means of Polythene covers or other equivalent measures.

iii) Precautions against mechanical damage by other trades shall be provided. iv) Precautions shall be taken and all necessary protection provided to safeguard the

work during bad weather. v) The inlet and discharges of all units shall be kept covered until all local Plastering,

Purging, etc. is completed and the units are ready to run. vi) Equipment and material damaged shall be replaced by contractor at the discretion

of the Consultant/MDL engineer. Equipment and materials are subject to rejection and replacement, if in the opinion of the Consultant/MDL Engineer, or in the opinion of the manufacturer's engineering department, the equipment has deteriorated or been damaged to the extent that its immediate use is questionable,

Page 284: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 284 of 307

or that its normal life expectancy has been curtailed. The contractor shall be solely responsible to protect all the delivered materials from

the time of delivery at site till satisfactory completion & handing over of the

completed works from any mode/type of damage/loss that may occur during this

period.

3.5 Care of the Building

Care shall be taken by the contractor during execution of the work to avoid damage to the building. He shall be responsible for repairing all such damages and restoring the same to the original finish at his cost. He shall also remove all unwanted and waste materials arising out of the installation from the site of work from time to time.

3.6 Project Execution Team

The Contractor shall ensure that senior planning and erection personnel from his organization are assigned exclusively for this project. The Contractor shall appoint one Project manager. He shall be assisted on full time basis by erection engineers & supervisors. The entire staff shall be posted at site on full time basis.

The Contractor shall arrange to have mechanized & modern facilities of transporting material to place of installation for speedy execution of work.

3.7 Performance Guarantee The contractor shall carry out the work in accordance with the Drawings, Specifications, Schedule of Quantities and other documents forming part of the Contract.

The contractor shall be fully responsible for the performance of the selected equipment (installed by him) at the specified parameters and for the efficiency of the installation to deliver the required result.

Complete set of drawings is appended with this tender and reference may be made to same for any details or information. The contractor shall also guarantee that the performance of various equipments individually, shall not be less than the quoted capacity; also, actual power consumption shall not exceed the quoted rating, during testing and commissioning, handing over and guarantee period.

3.8 Quiet Operation and Vibration Isolation All equipment shall operate under all conditions of load without any sound or vibration

which is objectionable in the opinion of the Client – MDL / Architect / Consultant. In case of rotating machinery sound or vibration noticeable outside the room in which it is installed, or annoyingly noticeable inside its own room, shall be considered objectionable. Such conditions shall be corrected by the Contractor at his own expense. The contractor shall guarantee that the equipment installed shall maintain the specified NC levels. Further, any noise & vibration above specified industrial Standards / values shall not be accepted.

3.9 Accessibility

The Contractor shall verify the sufficiency of the size of the shaft openings, clearances in cavity walls and suspended ceilings for proper installation of his ducting and piping.

His failure to communicate insufficiency of any of the above, shall constitute his acceptance of sufficiency of the same.

Page 285: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 285 of 307

The Contractor shall locate all equipment which must be serviced, operated or maintained in fully accessible positions. The exact location and size of all access panels, required for each concealed control damper, valve or other devices requiring attendance, shall be finalized and communicated in sufficient time, to be provided in the normal course of work.

Failing this, the Contractor shall make all the necessary repairs and changes at his own expense. Access panel shall be standardized for each piece of equipment / device / accessory and shall be clearly marked.

3.10 Materials and Equipment

All materials and equipment shall conform to the relevant Indian / International Standards and shall be of the approved make and design. Makes shall be strictly in conformity with list of preferred makes/manufacturers as per BOQ & attached list.

3.11 Electrical Installation

The electrical work related to air conditioning services, shall be carried out in full knowledge of, and with the complete coordination of the contractor. The electrical installation shall be in total conformity with the control wiring drawings prepared by the contractor and approved by the Consultant/Client – MDL.

All air conditioning equipment shall be connected and tested in the presence of an authorized representative of the Contractor, Consultant & MDL.

The system shall be commissioned only after the contractor has certified in writing that the electrical installation work for air cooling services has been thoroughly checked, tested and found to be totally satisfactory and in full conformity with the contract Drawings, Specifications and manufacturer’s instructions. It is to be clearly understood that the final responsibility for the sufficiency, adequacy and conformity to the contract requirements, of the electrical installation work for air conditioning services, lies solely with the contractor.

3.12 Testing & Commissioning

The performance, testing & commissioning of the complete HVAC system is required to

be carried out by the HVAC Contractor to comply with the various parameters specified

in the tender documents. Contractor shall submit Testing & Commissioning

methodology for complete HVAC system for review & approval of Client / Consultant.

Testing & commissioning of HVAC system shall be done strictly in accordance with

approved methodology which shall include, but will not be limited to, leak Testing of

copper tubing with nitrogen at suitable pressure to ensure appropriate system

functioning.

All instruments, services needed for the tests shall be furnished by the Contractor

themselves. All testing instruments shall be calibrated and the Contractor shall produce

calibration certificates in support.

Contractor shall also provide four copies of record of all safety and automatic control settings for the entire installation. The installation shall be tested again after removal of defects and shall be commissioned only after approval by the Client – MDL/ Architect / Consultant. All tests shall be carried out for satisfactory performance in the presence of the representatives of the Client – MDL / Architect / Consultant.

Page 286: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 286 of 307

Contractor shall raise call for inspection sufficiently in advance for witness by Consultant /MDL via officially acceptable means such as e-mail & letters.

4.0 GENERAL FEATURES: - Following features shall be provided for all VRV/VRF systems. ON / OFF Control ON / OFF control for each individual indoor unit.

Mode Selection Simulated COOL/FAN operation.

Temperature setting range

Temperature selection from minimum -18 Deg to 30 Deg.C in cooling mode.

Fan Speed Setting

HIGH-MEDIUM-LOW.

Timer Multiple daily time ON/OFF settings where temperature, fan speeds can be selected.

Remote Controller Group

Indoor units with remote controller.

Filter Maintenance

An indication shall appear, at selected time intervals, when it is necessary to

inspect the filter.

5 Documentation – 5.1 Submission of program Contractor is required to submit planned detailed execution methodology & schedule for

review / approval by consultant / Client within 14 days of placement of order. 5.2 Drawings

The HVAC Drawings issued with tenders, are diagrammatic only and indicate arrangement of various systems and the extent of work covered in the contract.

These Drawings indicate the points of supply and of termination of services and broadly suggest the routes to be followed. Under no circumstances shall dimensions be scaled from these Drawings. Shop drawings to be prepared by the Contractor based on the HVAC system configuration offered by them. The interiors drawings and details shall be examined for exact location of equipment, controls, grilles and diffusers. The contractor shall follow the tender drawings in preparation of his shop drawings, and for subsequent installation work. He shall check the drawings of other trades to verify spaces in which his work will be installed.

Maximum headroom and space conditions shall be maintained at all points. Where headroom appears inadequate, the contractor shall notify the Client – MDL/ Architect / Consultant before proceeding with the installation. In case installation is carried out without notifying, the work shall be rejected and contractor shall rectify the same at his own cost. The contractor shall examine all interior, structural, plumbing, and electrical and other services drawings and check the existing works. Before starting the work, Contractor shall report to the Client / Architect / Consultant about any discrepancies and obtain clarification. Any changes found essential to coordinate installation of his work with other services and trades, shall be made with prior approval of the Client – MDL / Architect / consultant without additional cost to the Client – MDL.

5.3 Technical Data Sheet Contractor shall submit the technical data sheet for all items after award of Contract and before procurement of the items. Technical datasheet of Indoor & outdoor units to have parameters mentioned but not limited to those listed at Annexure ‘A’.

Page 287: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 287 of 307

5.4 Shop Drawings

All the shop drawings shall be prepared on computer through AutoCAD System based on Drawings, site measurements and Interior Designer’s Drawings. Contractor to design & select various refrigerant piping sizes based on HVAC system configuration offered by them & accordingly incorporate in the shop drawings. Within two week of the award of the contract, contractor shall furnish, for the approval of the Client – MDL / Architect / Consultant, three sets of detailed shop drawings in A1 color printout of all equipment and materials including detailed ducting drawings showing exact location of supports, flanges, bends, tee connections, reducers, guide vanes, silencers, distribution grids, volume control dampers, collars, grilles, diffusers; detailed piping drawings showing exact location and type of supports, valves, fittings etc. Acoustic lining and external insulation details for ducts, pipe insulation etc; electrical panels inside / outside views, power and control wiring schematics, cable trays, supports and terminations. These shop drawings shall contain all information required to complete the Project as per specifications and as required by the Client – MDL/ Architect / consultant. These Drawings shall contain details of construction, size, arrangement, operating clearances, and capacity of all items of equipment, also the details of all related items of work by other contractors. Each shop drawing shall contain tabulation of all measurable items of equipment / materials / works and progressive cumulative totals from other related drawings to arrive at a variation-in-quantity statement at the completion of all shop drawings. Minimum 4 sets of drawings ‘A1’ size color printout shall be submitted after final approval along with softcopy. Each item of equipment / material proposed shall be a standard catalogue product of an established manufacturer strictly from the manufacturers given in list of makes and quoted by the tenderer in technical data part. When the Client – MDL / Architect / Consultant makes any amendments in the above drawings, the contractor shall supply three fresh sets of drawings with the amendments duly incorporated along with check prints, for approval. No material or equipment may be delivered or installed at the job site until the contractor has in his possession, the approved shop drawing for the material / equipment / installation. No claims for extension of time shall be entertained because of any delay in the work due to his failure to produce shop drawings at the right time, in accordance with the approved program. Manufacturer’s drawings, catalogues, pamphlets and other documents submitted for approval shall be in four sets. Each item in each set shall be properly labeled, indicating the specific services for which material or equipment is to be used, giving reference to the governing section and clause number and clearly identifying in ink the items and the operating characteristics. Data of general nature shall not be accepted. Also, wherever directed a mockup or sample installation shall be carried out for approval before proceeding for further installation. Approval of shop drawings shall not be considered as a guarantee of measurements or of building dimensions. Where drawings are approved, said approval does not mean that the drawings supersede the contract requirements, nor does it in any way relieve the contractor of the responsibility or requirement to furnish material and perform work as required by the contract.

Page 288: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 288 of 307

Where the contractor proposes to use an item of equipment, other than that specified or detailed on the drawings, which requires any redesign of the structure, partitions, foundation, piping, wiring or any other part of the mechanical, electrical layouts; all such re-design, and all new drawings and detailing required therefore, shall be prepared by the contractor at his own expense and gotten approved by the Client – MDL / Architect / Consultant. Any delay on such account shall be at the cost of and consequence of the Contractor. Where the work of the contractor has to be installed in close proximity to, or will interfere with work of other trades, he shall assist in working out space conditions to make a satisfactory adjustment. If so directed by the Client – MDL/Architect/Consultant, the contractor shall prepare composite working drawings and sections at a suitable scale, not less than 1:100, clearly showing how his work is to be installed in relation to the work of other trades. Within two weeks of approval of all the relevant shop drawings, the contractor shall submit four copies of a comprehensive anticipated variation in quantity statement to Consultant/MDL.

5.5 Completion Certificate:

On completion of the Electrical installation for air conditioning, a certificate shall be furnished by the contractor, counter signed by the licensed supervisor, under whose direct supervision the installation was carried out.

5.6 As Built Drawings Contractor shall submit as built drawings as and when work in all respects is completed in a particular area. These drawings shall be submitted in the form of two sets of CD’s and four set of Hard copy – ‘A1’ Size color printout. These drawings shall clearly indicate complete HVAC system Equipment layouts, ducting and piping layouts, location of wiring and sequencing of automatic controls, location of all concealed piping, valves, controls, dampers, wiring and other services.

5.7 Operating Instruction & Maintenance Manual

Upon satisfactory completion and commissioning of system the contractor shall submit a

draft copy of comprehensive operating instructions, maintenance schedule and log sheets

for all systems and equipment included in this contract.

This shall be supplementary to manufacturer’s operating and maintenance manuals.

Upon approval of the draft, the contractor shall submit four (4) complete bound sets of

type written operating instructions and maintenance manuals; one each for retention by

Consultant and Client – MDL / Architect / Consultant and two for Client – MDL’s

Operating Personnel.

These manuals shall also include basis of design, detailed technical data for each piece of

equipment as installed, spare parts manual and recommended spares for period of

maintenance of each equipment.

6. SPECIFICATION OF VRF EQUIPMENT / MATERIAL AND INSTALLATION STANDARDS

6.1 Variable Refrigerant Flow System.

Page 289: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 289 of 307

The system selected is a modular system, with number of indoors connected to centrally

located outdoor units, as per detail designing given in the tender. The outdoor units for all

the system shall be air cooled type and mounted on terrace of the building. Indoor units

in various areas shall be as per enclosed drawings/ Bill of Quantities. All the VRF air

conditioners shall be fully factory assembled, wired, internally piped & tested. The

outdoor unit shall be pre charged with first charge of Eco-friendly refrigerant gas R 410A

/ 407C. Additional charge shall be added as per refrigerant piping at site. All the units

shall be suitable for operation with 415 V + 10%, 50 Hz + 3%, 3 Phase supply for outdoor

units & 220 V + 10%, 50 Hz + 3%, 1 Phase supply for indoor units.

The VRF system shall provide stable, trouble free & safe operation, with flexibility of

operating desired indoor units. The outdoor units must be capable of delivering exact

capacity proportional to the number of indoor units switched on & the heat load in the air

conditioned area. The proportional operation shall be achieved by varying speed of the

compressor in the outdoor units. Electronic expansion valves shall be provided in the

system.

The operation of the VRF system shall be through independent wireless remote controllers

as specified. The entire system shall be provided with BMS connectivity with

MODBUS/BACNET protocol and shall be provided with connectivity port ready to be

integral with intelligent building management system in future.

6.2 Outdoor units.

Outdoors units of the VRF system shall be compact air cooled type.

All the compressors of the outdoor units must be hermetically sealed scroll type. Each

module of outdoor unit shall have combination of Inverter Scroll Compressors suitable to

operate at heat load proportional to indoor requirement. Each compressor shall have in-

built overloads, HP and LP controllers and mounted on vibration isolators. Minimum

Capacity of single module shall be 12 HP. Also, each Outdoor unit shall have

minimum 2 or more number of Modules.

Coated Hydrophilic/PE Fins (with special acryl pre-treatment) for Aluminum fins of

Condenser Coils is mandatory for increased durability to salt corrosion. The system shall

be air-cooled, direct expansion type central air conditioning system consisting of one or

more Variable Refrigerant Flow Condensing unit (Outdoor Unit) and connected to one or

more Evaporator (Indoor Units) for cooling operation. Each having the capability of

individual set point control & the condensing unit should incorporate multiple scroll

compressors. Set of Outdoor Unit should be able to connect up to 64 Indoor Units.

The condensing unit shall be modular type, designed as per Indian atmospheric

conditions and should be capable to perform for outside ambient 43 Deg. C. Outdoor

Units should be modular in type and should be equipped with high efficiency DC inverter

compressor, Wide Range of Capacity Control (15 to 100Hz) with minimum Steps of 1Hz , 2

Stage Oil separating for improving reliability of system.

Each outdoor unit should have Inverter with variable speed compressor, capable of

changing the capacity in accordance to the cooling load requirement with highest

COP/EER. Also, the unit shall be capable of setting External Static Pressure up to 60Pa

on site.

Outdoor unit should consists of DC variable speed motor for condenser fan with

minimum 25 steps speed control to reduce input power, auto check function for

connection error, auto address setting. Unit should be equipped with a double stage

Page 290: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 290 of 307

highly efficient oil separation management system to ensure minimum oil entrenchment

and proper lubrication with high reliability and stable operation with long refrigerant

piping.

The noise level of the base unit shall be less than 60dB (A) when measured horizontally

1m away from cover surface and 1.5 m above floor level during night shift. Unit should

assess demand function automatically and perform with the help of Central Station. Units

having Noise reduction mode will be preferred but must be having back up operation

function for emergency to avoid complete stop. Outdoor unit should have feature of

Rotation Operation function of Compressor to distribute load. The condenser coil should

be with AL-Cu internally grooved Cu tubes, mechanically bonded to super slit aluminum

fins. The surface of the condenser coil shall be coated with suitable chemical coating to

prevent deterioration due to climate.

Outdoor unit must have automatic judgment function to check whether or not the

refrigerant amount is sufficient in one refrigerant cycle. Reliable Transmission system

should be used between outdoor and indoor units. All necessary safety devices shall be

provided to ensure safe operation of the system.

In VRF system, maximum allowable approximate piping length between outdoor unit & its

farthest connected indoor unit is 150 mtr & total approximate piping length for all indoor

units connected to same outdoor unit is 500 mtr. Allowable level difference between

outdoor unit & indoor units shall be 50m in case of outdoor unit on top & 40m in case of

outdoor unit at bottom. Allowable level difference between various indoor units connected

to one out door unit shall be up to 15m.

Back up operation, in case of failure of one of the compressors of outdoor unit, for single

module outdoor units or failure of one of the modules in case of multiple module outdoor

units shall be possible. Vendor to select unit standby capacity with configuration

equivalent to the highest installed compressor capacity inside the unit or 30% of

total unit TR; whichever is higher. Vendor to select ODU MODULES as per best

Available Configuration.

Capacities mentioned in BOQ are minimum cooling requirements. Standby capacity

shall be over and above these capacities.

The outdoor unit shall employ system of equal run time for all the compressors, inverter

or on/ off type, within each out door unit – Single Module or Multi Module.

The outdoor units shall be suitable to operate within an ambient temperature range of – 5

Deg C to 43 Deg C, in cooling mode.

Air cooled condenser shall have Axial Flow, upward throw fan, directly coupled to fan

motors with minimum IP 65 protection. The outdoor unit condenser fan shall be able to

develop external static pressure up to 6 mm of H2O.

The entire operation of outdoor units shall be through independent remotes of indoor

units. No separate Start/ Stop function shall be required.

Soft Starters shall be provided for the Outdoor Unit compressors. Inverter compressor of

the unit shall start first & at the minimum frequency, to reduce the inrush current during

starting.

Page 291: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 291 of 307

Refrigerant control in the outdoor unit shall be through Electronic Expansion Valve.

Complete refrigerant circuit, oil balancing/ equalizing circuit shall be factory assembled &

tested.

Outdoor units shall be complete with following safety devices:

• High pressure switch

• Fan driver overload protector

• Over current relay

• Inverter Overload Protector

• Fusible Plug

Unit shall be supplied with

• Installation manual

• Operation Manual

• Connection Pipes

• Clamps

• Paper pattern for installation.

• Clamp metal/ washer fixing plate/ sealing pads/ clamps/ screws/ washer for

hanging bracket/ insulation for fitting

• Electrical cable & accessories

6.3 Indoor Units

6.3.1 Cassette type indoor units.

These units shall be installed between the bottom of finished slab & top of false ceiling.

The unit must have in built drain pump, suitable for vertical lift of minimum 750 mm.

The unit must have 3 – Speed fan motor

The unit casing shall be Galvanized Steel Plate.

The noise level of unit at the highest operating level shall not exceed 44 dB(A), at a

vertical distance of 1.5 m from the grille of the unit.

Unit shall have provision of connecting fresh air without any special chamber & without

increasing the total height of the unit.

The unit shall be supplied with suitable decorative panel. Decorative panel shall have

coating that repels dirt.

The unit shall be supplied with anti-mould and antibacterial treatment filter. The filter

shall be easy to remove, clean & re install.

The unit will be connected in series to a suitable outdoor unit & it must be possible to

operate the unit independently, through cordless remote specified in the “Bill of

quantities”. The unit to have provision for further connecting to Intelligent Building

Management System & it shall be possible to operate the unit through this IBMS system.

6.3.2 Ceiling Mounted Treated Fresh Air units.

These units shall be installed between the bottom of finished slab & top of false ceiling.

The unit shall have in built drain pump, suitable for minimum vertical lift of 750 mm.

Page 292: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 292 of 307

The unit casing shall be Galvanized Steel Plate.

Unit shall be insulated with sound absorbing thermal insulation material, Polyurethane foam.

The noise level of unit at the highest operating level shall not exceed 55 dB (A), at a vertical distance of 1.5 m from the grille of the unit.

Treated Fresh air unit operates at outdoor ambient up to 43 deg. C in cooling mode.

The External static pressure of TFA unit allows the use of extensive ducting work.

The unit shall be supplied with High Efficiency Filter with dust collection efficiencies of 90%, Filter chamber & Drain Pump Kit.

The unit will be connected in series to a suitable out door unit & it must be possible to

operate the unit independently, through corded/ cordless remote specified in the bill of

quantities.

The unit to have provision for further connecting to Intelligent Building Management

System it shall be possible to operate the unit through this IBMS system.

All units shall be supplied with the following from the factory

a) Operation Manual. b) Installation Manual. c) Paper pattern for Installation.

d) Drain hose/ clamp metal/ washer fixing plate/ sealing pads/

clamps/ screws/ washer for hanging bracket/ insulation for fitting.

e) Wireless Remote controls f) Electrical Cables & accessories

6.4 Constant Volume Air Flow Controller

Mechanical system-powered controllers are an economic solution for the control of

constant air flows. Constant Volume Air Flow Controller work without an external power

supply, no wiring or commissioning is necessary.

The controller contains a control damper supported by bearings. The aerodynamic forces

of the air flow cause the damper to close. These forces are amplified by bellows. A

mechanical unit consisting of a leaf spring and cam plate acts against the closure force

keeping the flow rate constant as the duct pressure varies. The bellows also has the

function of acting as an oscillation damper.

Systems operated with constant air flow offer energy savings potential if the air flow is

reduced at unoccupied times.

6.5 Refrigerant Piping

The indoor and outdoor units shall be connected with refrigerant copper piping. All piping

connections for the units should be performed inside the unit. The refrigerant copper

piping should be insulated with nitrile foam. All refrigerant piping to be done with hard

copper pipes only.

Mode of Measurement - Copper piping work for refrigerant would be measured in running meters excluding the length of copper pipe supplied by the Air conditioner manufacturer as part of the AC unit package. Cost towards insulation to be incorporated by the bidder

Page 293: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 293 of 307

in unit rate of copper tubing in the BOQ. No separate payment shall be made for insulation work.

a) The linear rate per meter for each nominal diameter shall include all pipe fittings, flanges, unions, gaskets for joints, bolts and nuts, pipes support and hangers, vibration isolation devices or suspenders, flexible connections and any other item required to complete the pipe installation.

b) For fittings like bends, elbows, branches, tees, etc. the same principle of linear

measurement as for pipe sections will be adopted except for bends, the length of

which will be the average of the lengths of inner and outer periphery along the

curvature.

6.6 Drain Piping

Condensate from the evaporator unit shall be drained through properly installed drain

piping designed to prevent any accumulation of condensate in the drain pan. Drain piping

of specified sizes and suitable of 6 Kg/Sq cm. pressure rating with water tight

connections, leading from the room unit to a suitable drain point. Complete drain piping

shall be made leak proof and water tight by means of precise installation and the use of

leak proof sealant/adhesives. Drain piping shall be UPVC type as per relevant IS standard

and insulated with 6 mm nitrile foam insulation throughout the length. UPVC pipelines to

be adequately supported intermittently at uniform distance with clamps, pipe supports

with proper alignment in horizontal and vertical direction. The joints shall be properly

sealed so that there is no water leakage. Proper grouping of condensate drain pipes &

gradient to be maintained for the easy flow of condensate drain water.

6.7 Controls System

Wireless Remote Controller - Wireless remote controller shall be supplied as specified in

the “Bill of Quantities”.

The controller must have large crystal display screen, which displays complete operating

status.The digital display must allow setting of temperature with 1 Deg C interval.

Remote shall be able to individually program by timer the respective times for operation

start and stop within a maximum of 24 hours. Remote must be equipped with thermostat

sensor in the remote controller that will make possible more comfortable room

temperature control

The remote shall be able to monitor room temperature & preset temperature & can select

cool/ heat operation mode automatically.

Compact light receiving unit to be mounted into wall or ceiling shall be included.

7.0 AIR DISTRIBUTION SYSTEM

7.1.1 SHEET METAL WORK-

Ducts shall be made of galvanized steel sheet as specified in the BOQ and confirm to IS-

655. The galvanized steel sheet shall confirm to IS-277 grade 120 gsm or better. The duct

construction shall be as follows.

Page 294: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 294 of 307

RECTANGULAR DUCT CONSTRUCTION-For low pressure System (Upto static

pressure of +/- 75mm wc)

Max.Size Min.thick Trans joints Reinforcement Hanger

Up to 750 24 G 25x3

eq.angle

Cross Breaking 10mm

751 to 1500 22 G 25x3

eq.angle

25x3 girth angle at

1250mm centre

10mm

1501 to

2250

20G 37x3

eq.angle

37x3 girth angle at

750

12mm

Above 2250 18g 40x6

eq.angle

40x6 girth angle at 600 12mm

For High pressure System (static pressure of more than+/- 75mm wc)

Max.Size Min.thick Trans joints Reinforcement Hanger

Up to 750 22 G 37x3 eq.angle 37x3 girth angle

at 1250mm

centre

10mm

751 to 1500 20 G 40x6 eq.angle 40x6 girth angle

at 1250mm

centre

10mm

1501 to 2250 18G 50x6 eq.angle 50x6 girth angle

at 750

12mm

Above 2250 16g ISMC 75x40 50x6 girth angle

at 600

12mm

Note: The gasket used for the kitchen/Pantry Exhaust Ducting shall be fire

retardant type.

Ducts shall be fabricated using lock forming machine. Longitudinal seams shall be of lock

type. Flanges used for transverse joints shall be joined with each other with Galvanized

Steel Bolts, washer and nuts. The bolts shall be of minimum M8 size and spacing

between bolts shall be maximum 150 mm for low pressure ducting and 100mm for high

pressure ducting.

For transverse angle flanged joints, neoprene gasket (3mm uncompressed thickness and

width equal to flange face) adhered to the flange face shall be used. The bolt holes in the

gasket shall be the same as bolt diameter and shall be punched prior to insertion of

gaskets.

Angle shall have welded corners and shall be riveted to the ducts at 300 mm centers

maximum.

Page 295: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 295 of 307

If specified in Schedule of Quantities, sealing of the longitudinal and spiral seams shall be

accomplished using RTV 732 sealants.

Rectangular duct shall be supported from ceiling using trapeze hangers. Ducts shall rest

on supporting angle or channel and this supporting angle or channel shall be supported

by CS rods or angles or channels on the both the side of the ducts with weld or bolts.

Zinc Coated anchor fasteners or embedded plates shall be provided for upper attachment

to the building. The Successful Bidder shall provide the anchor fasteners. Bidder shall

provide the embedded plates if marked in the drawings before casting of slabs. The

Successful Bidder shall provide the duct supports from angle cleats welded to the

embedded plates. Anchor fasteners shall be loaded to maximum 20% of the rated capacity

specified by the manufacturer.

Wherever sheet metal duct connects to the intake or discharge of fan units, a flexible

connection of fire retarding double layer of at least 150mm width shall be provided. The

material shall be attached to the angle frames by means of steel band over the end of the

flexible connections. The material shall be secured between the band and the angle frame

by bolting. Sleeve shall be made smooth and the connecting duct work rigidly held by

independent supports on both the ends. The flexible connections shall be suitable for fan

intake and outlet pressures.

All bends, offset and branch connections shall be made for smooth and noiseless flow of

air and minimum pressure drop. The Successful Bidder shall furnish the details of guide

vanes i.e. number of vanes and locations etc. in the construction drawings. The flow of air

to the branch duct shall be regulated by a splitter damper or volume control damper.

7.1.2 DAMPERS-

All dampers shall be of 18 S.W.G. G.I sheets louver dampers of robust construction and

tight fitting. The design, method of handling and control, shall be suitable for the location

and service required. Dampers shall be provided with suitable links, levers and quadrants

as required for their proper operation, control or setting in any desired position. Dampers

and their operating devices shall be made robust, easily operable and accessible through

suitable access door. Every damper shall have indication device clearly showing the

damper position at all times. All the bushing will be of brass only.

7.1.3 GRILLES AND DIFFUSERS-

All grilles (SA & RA), diffusers (SA & RA) will be made from heavy gauge extruded

Aluminum sections / M.S. (As specified in the BOQ) duly powder coated to match the

interior requirements. All the supply air grilles/diffusers will be provided with opposed

blade dampers fabricated from Al. The damper should be suitable for operation from front

face of grille/diffuser.

7.1.4 INSULATION FOR G.I. DUCTING- (THERMAL INSUALTION-WITH NITRILE

RUBBER

The supply air duct shall be insulated with 19 mm thick Elastomeric Nitrile Rubber as

specified in bill of quantities.

Method of applying insulation-

a) Clean the duct surface to be insulated.

Page 296: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 296 of 307

b) Apply a thin layer of tar paints.

c) Apply a thin coat of rubber solution to stick the insulation.

d) Fix the insulation of specified thickness over the surface of the duct tightly and

seal all the joints using BOPP tape. Secure the insulation with 16 Gauge G. I.

wire or 10 mm wire PVC box strapping at a distance of 300 mm.

7.2 INSTALLATION-

a. All ducts shall be rigid and shall be adequately supported and braced where

required with standing seams, tees or angles of ample size to keep the ducts true to shape

and to prevent buckling, vibration or breathing. All the joints shall be made tight and all

interior surfaces shall be smooth. Bends shall be made with radius not less than one half

the width of the duct or with properly designed interior curved vanes where metal ducts

or

sleeves terminate in woodwork, brick or masonry openings, tight-flanged collars. Ducting

over false ceiling shall be supported from the slab above or from beams. In no case a duct

shall be supported from the false ceiling hangers or to be permitted to rest on a hung

ceiling.

b. All holes in concrete, masonry etc. made by Successful Bidder for fixing supports &

also for all refrigerant piping etc. shall be made good and restored to original finish by the

civil contractor.

7.3 TESTING-

a. After completion, complete system shall be tested for leakage.

b. The entire air distribution system shall be balanced to supply the air quantities as

required in various zones and rooms to maintain the specified room conditions.

The final shall be recorded and submitted to the Consultant for approval before

acceptance and taking over of the entire system by the Employer.

c. Functioning of Exhaust fans shall be verified by examining CFM / CMH.

8.0 Commissioning Standards- VRF Systems

8.1 Refrigerant pipe work

• Pressure test

Good Practice; 5 Steps Strength and Leak Test.

1) 3 bar (N2) Minimum of 3 minutes.

2) 15 bar (N2) Minimum of 3 minutes.

3) 32 bar (N2) Minimum of 15 minutes.

4) 41.5 bar (N2) Strength test for a period of time that is acceptable to show any signs

of deformation to the pipework.

5) 33 bar (N2) after step 4, drop pressure to 33 bar for final leak test for minimum 24

hours. Pressure testing signage will be clearly visible on site during testing periods.

Page 297: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 297 of 307

• Steps Evacuation.

On completion of strength/leak testing an evacuation is to be carried out to 2mm Hg (2

Torr).

This will eliminate the risk of any moisture being present within the pipework installation.

It is recommended that a triple evacuation process be carried as below. This should then

be followed by a pressure rise test.

1) Evacuate the system to 10 Torr from both service valves. System manifold gauges

“must not” be used to measure a vacuum. A Torr gauge must be used at all times.

2) Break the vacuum with OFN (N2) into “suction” service valve to 1 bar.

3) Evacuate to 5 Torr from “discharge valve”.

4) Repeat step 2.

5) Evacuate to lowest pressure vacuum pump will achieve (2 Torr for 1 hour minimum).

6) Pressure rise test to be carried for a minimum of 30 minutes.

• Electrical Work

Appropriate glands will be fitted to each item of equipment in accordance with

environmental conditions.

When running interconnecting control wiring it is essential to avoid the risk of electronic

control signals being corrupted. Care should therefore be taken to avoid running control

cables too close to power cables.

• Pre-commissioning.

The following items must be checked prior to any systems being switched on.

1. A marked up scale site drawing showing all units and refrigeration pipework, address

settings (for units and remote controllers and model/serial numbers will be produced.

2. Indoor units, Outdoor Units addressing and screened wiring (greater than 1.25 mm2)

as per the specifications.

3. All control wiring and remote controllers will be complete and connected but final

connection shall be made by the Installation Engineer in charge from the manufacturer.

4. Before the Power Supply to outdoor unit is turned on, the mains wiring must be

checked phase to neutral, neutral to earth. Once this is complete the mains isolator can

be switched on to allow the crankcase heater to warm up the oil (minimum 24 hours).

5. Pressure test system refrigerant pipework will be completed.

6. Evacuation of the system refrigerant pipework will be completed as above.

7. Condensate pipework will be completed and leak tightness to be demonstrated.

8. Totals lengths of liquid line pipework installed, will be confirmed by installation

Engineers and marked on drawings for additional refrigerant charge calculation.

Page 298: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 298 of 307

9. Sufficient supply of refrigerant R410A / R407C in dumpy cylinders will be on site

adjacent to the Outdoor.

Units ready for use.

10. Now charge refrigerant into pipework based upon the additional refrigerant charge

calculation.

11. Outdoor Unit service valves will now be opened.

• Commissioning

1. Connect monitor tool and check system connect information is correct i.e. Outdoor

Unit, BC port, Indoor Unit and Remote controller addresses.

2. Start up the system and run each Indoor Unit one by one in cooling mode to confirm

correct operation.

3. Set up and configure all controllers/time clocks/centralized controllers.

4. Check operation of any accessory interlocks i.e. time clocks, centralized controllers etc.

5. Check operation of all condensate pumps if fitted.

6. Monitor operation for at least 1 hour. Observe and save all data.

7. Complete Commissioning Log Book.

8. Record all refrigerant usage in total compliance with F Gas.

Checklist / proper register to be maintained at site for physical witnessing & ensuring

that the laid down procedure are followed properly. The register to be signed by contractor

& consultant for every activity.

9.0 PAINTING-

Angle iron flanges, stiffeners, hangers and supports shall be painted with 2 coats of anti

rust primer and those remaining uncovered shall be further painted with 2 coats of

synthetic enamel paints of black color.

10.0 HVAC – PREFERRED MAKE LIST

Sr ITEMS PREFERRED MAKES

1 Nitrile Rubber Insulation Armacell/K- Flex/ Superlon

2 UPVC Pipe Finolex/Supreme/Prince/Astral

3 Heavy duty pipe support

clamp

Hi-Tech / Diamond pipe

4 VRV Systems Daikin / Mitsubishi Electric / Toshiba/ Hitachi

5 Sheet Metal Ducting Tata/Jindal

6 Air flow Controller Troxs, Ruskin, Aldes

Page 299: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 299 of 307

ANNEXURE A

DOCUMENT : TECHNICAL DATA SHEET

VRF SYSTEM_OUTDOOR UNIT

(Technical information to be furnished in following format by Bidder after award of contract & before procurement.)

SR. NO. SPECIFICATION

TO BE FILLED IN BY BIDDER

OUTDOOR UNIT :

1.1 COMPRESSOR

Make

Type

Model no.

Max. Speed (rpm)

No. of Inverter / digital type compressor

% of full load capacity

% of Power consumption

Type of drive

List of safety device provided on compressor

Test pressure of compressor (kg./sq.cm.)

Refrigerant

Design conditions (at peak load)

i) Suction temperature(°C)

ii) Discharge temperature(°C)

iii) Suction Pressure (kg./sq.cm.)

Iv) Discharge Pressure (kg./sq.cm.)

Capacity of compressor at design conditions at full load (TR)

BKW at design conditions

Recommended motor HP

Overall dimensions of Outdoor Unit (mm) (Height, Width & Depth)

Weight of the Units

1.2 FAN SECTION :

Fan dia. (mm)

No.of fans

Fan speed (rpm)

Type of drive

Design air quantity (cu.m./hr.)

KW at full load

Motor HP

1.3 CONDENSER COIL :

Tube material

Fin material

No.of rows

Design heat rejection capacity (TR)

1.4 ELECTRIC MOTOR FOR CONDENSER FAN :

Make

Type

Method of starting

Rated output (HP)

Range of working voltage (volts)

Rated frequency (Hz)

Page 300: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 300 of 307

Rated speed (rpm)

Full load current (Amps.)

Starting current (Amps.)

Class of insulation

Efficiency and power factor at full load

1.5 COP

COP of ODU capacity at 125% Diversity

COP of ODU capacity at 100% Diversity

COP of ODU capacity at 75% Diversity

COP of ODU capacity at 50% Diversity

1.6 DERATION CAPACITY in BTU / HR

Actual Deration Capacity of ODU at 40 °C

Actual Deration Capacity of ODU at 43.5 °C

VRF SYSTEM_INDOOR UNIT

(Technical information to be furnished in following format by Bidder after award of contract & before procurement.)

SR. NO. SPECIFICATION

TO BE FILLED IN BY BIDDER

INDOOR UNIT :

1.1 COOLING COIL :

Tube material

Fin material

Overall dimensions of Indoor Unit (mm) (Height, Width & Depth)

Weight of the Units

1.2 EVAPORATOR FAN SECTION :

Maximum air discharge capacity (cu.m./hr.)

1.3 ELECTRIC MOTOR FOR EVAPORATOR FAN :

Make

Type

Method of starting

Rated output (HP)

Range of working voltage (volts)

Rated frequency (Hz)

Rated speed (rpm)

Full load current (Amps.)

Starting current (Amps.)

Class of insulation

Efficiency and power factor at full load

AIR CURTAIN

Air curtains provide environmental separation at openings by reducing the infiltration of unconditioned air, fumes, dust, and humidity. At exterior openings, they can resist winds up and are generally mounted inside the building. Air curtain shall be horizontally mounted above the entrance door of kitchen on the wall.

Page 301: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 301 of 307

A. Construction: Provide factory-assembled units of sufficient structural strength to be supported from ends without intermediate support. Ship units completely assembled.

B. Cabinet:

1. Material and Finish: Aluminum base frame with stainless steel riveted construction and powder coated aluminum cover.

2. Mounting: Provide for wall suspended mounting.

3. Service Access: Removable screen

C. Motors: As per manufacturer suitable to deliver 1100 cfm, single phase, variable speed, ODP, direct driven, resilient mounted, continuous duty with internal thermal-overload protection and permanently lubricated sealed ball bearing.

D. Fans: Balanced forward curved cross flow tangential type, made of aluminum with flexible hubs and mounted in matched fan scroll made of aluminized steel.

E. Discharge Nozzles:

Provide uniform velocity across width of air curtain.

F. Inlet:

1. Location: Front.

2. Screen: Perforated aluminum and extruded aluminum frame with same finish used for the cabinet.

G. Air Inlet Filter: Flat faced fire-rated re-cleanable aluminum with integral filter clips.

H. Remote Control: Infra-red controller for On/Off and control Fan speeds.

J. Preferred Makes: Russell / Ruskin / Euronics / Boss PREMABLE TO BILL OF QUANTITIES

The Bill of Quantities must be read with the scope of work, Conditions of Contract, Drawings and the Specifications and the Contractor shall be deemed to have examined the Scope of Work, Drawings, Specifications, Conditions of Contract and to have visited the Site and acquainted himself with the Works to be done and the way in which they are to be carried out and all factors affecting the execution of the Works and the Costs thereof including temporary works if required to complete the works.

All work shall be measured net as it is finished and/or fixed in the Works and no allowance shall be made for wastage notwithstanding any general or local custom. Any items of work not covered in the Preamble shall be measured as per specifications for works methods laid down in relevant Indian Standards or as decided by the Consultant/MDL Engineer.

The quantities set down against the items in this Bill of Quantities are an approximate estimate of the quantity of each kind of work included in the Contract and are given for the convenience of forming a common basis for tendering. They are not to be taken as a guarantee that the quantities scheduled will be carried out or required or that they will not be exceeded. The MDL reserves the right to delete any item indicated in the bill of quantities at any time.

Page 302: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 302 of 307

The quantities shall therefore not be considered as representing the final measurements, it being the intention of the Contract (except where otherwise specifically stated) that the actual quantities of work ordered and carried out shall be jointly measured on completion by the MDL Engineer or his authorized representative and the Contractor and valued and paid for at such prices and rates entered by the Contractor in the Bill of Quantities.

The rates and prices set down against the items are to be the full inclusive value of the finished work shown on the Drawing and/or described in the Specifications or which can reasonably be inferred there from and to cover the cost of every description of Temporary Works executed or used in connection therewith (except those items in respect of which specific provision has been separately made in this Bill of Quantities) and all the Contractor's obligations under the Contract including testing, giving samples and all matters and things necessary for the proper execution, completion and maintenance of the Works. No claim for additional payment shall be allowed for any error or misunderstanding by the Contractor of the work involved.

The Specifications and the various Sections in the Bill of Quantities are intended to cover the supply of all the materials and the execution of all works necessary to complete the Works. Should there be any details of Materials or Construction which have not been referred to in the scope of work, specifications, Bill of Quantities or the Tender Drawings, but the necessity for which may reasonably be implied or inferred there from, or which are usual, or essential to the completion of all works in all trades, the same shall be deemed to be included in the rates and prices within in the Bill of Quantities. The rates and prices shall cover the items as described in the scope of work, Bill of Quantities, tender drawings and other terms and conditions of the contract.

The Contractor's unit rates and prices in the BOQ shall include

a) all equipment, apparatus, material, indicated in the BOQ, Scope of Work, Drawings, Specifications in connection with the item in question and also associated labour as well as all additional equipment, apparatus, material, consumables usually necessary to complete the system even though not specifically shown, described or otherwise referred to and also associated labour.

b) It also includes delivering the material, item to the specified storage area at Site. Installation of the same in the specified location as per Drawing & as specified, testing and commissioning as per Specification and direction of the Engineer' at Site.

c) The unit price shall be deemed to include everything necessary to complete the work covered by this item in accordance with the scope of work, BOQ description, Specifications and Drawings.

d) The sum total of all the individual item prices shall represent the total price of the installation ready to be handed over.

e) All equipment, machinery, apparatus and materials required as well as the cost of any tests which the Engineer may request in addition to the tests generally required to prove quality and performance of HVAC system. Further, if any equipment, machinery, apparatus and materials found to not comply/fulfill satisfactory performance/duty during such testing, then cost of replacing such materials.

f) Use of any tools, equipment, machinery, lifting tackle, ladders consumables etc. required by the Contractor to carry out his work.

All the necessary measures to prevent the transmission of vibration. Storage and insurance of all plant and equipment, apparatus and materials

Page 303: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 303 of 307

DESCRIPTION OF COMPLETE SYSTEMS FOR COMPREHENSIVE MAINTENANCE OF HVAC (VRV/VRF ACs) SYSTEM SCOPE OF WORK: The scope of work as mentioned below are the minimum expected from the firm / agency / contractor apart from break down maintenance and any other work required for maintenance in proper way as per the operation & maintenance manuals of respective equipment and as per good engineering practices will be required to be done under this scope of work. Successful bidder will make Proforma for recording the following minimum work schedule/parameters and show to the employer to ensure proper accomplishment of these tasks. 1) Attending complaints of systems which include routine as well as breakdown maintenance of all the system. 2) Vendor shall supply minimum following consumables & general spares / items for smooth operation of all the system and the rates quoted by them should be inclusive of following items :- a) Refrigerant Gas b) Lubricating oil for compressor systems c) Packing / Couplings / gaskets / insulation material / other general spares. d) All electrical spares e.g. Fuses / Relays, contactors, Condensers etc. e) Indoor units Filter /Belts / Bearings / Valves / Other spares etc. 3) All tools & tackles, manpower, transportation and other resources required for executing the job shall be in the scope of the contractor. No extra charges will be paid by MDL regarding tools & tackles, manpower, transportation etc. 4) Spares of compressor, control panel card, Software etc. which may be required during maintenance of the system will have to be supplied by the contractor as per instruction of MDL. 5) The Vendor has to maintain a maintenance register during each visit mentioning what kind of job has been done during that visit. Contractor also has to provide maintenance report. Also, before commencement of the AMC, the contractor shall provide schedule of preventive maintenance visits to be carried out for that year. These dates of visits as per schedule to be adhered & contractor’s rep / technician to report on site without delay or requirement of any follow-up from client side. Failure to adhere to the schedule shall attract penalty in accordance to clause 3.1 of this document. Contractor to arrange manpower/material entry passes well in advance in compliance to MDL’s security procedures to avoid any delay. 6) The vendor shall depute his authorized person, who will control this Annual maintenance work, so that authority can contact him for any kinds of problem of the complete system.

Monthly Maintenance:- 1) Maintenance of all filters, fans, diffusers, cooling coils, Refrigerant Gas make up etc. 2) Tightening of belts, foundation bolts of equipment, alignment of belt pulleys and couplings. 3) Examining indoor/outdoor units & operating linkage for smoothness.

Page 304: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 304 of 307

4) To check the gland /seal, coupling of units. 5) To check the safety controls mechanical, Electrical/ Electronics and inter-locking of the

various equipment’s. 6) To check all piping/insulation/proper positioning/damage and rectifying the same where ever required. 7) Inspect/check entire line for leakage and rectification of leakage, if any. 8) To check and lubricant (if required) the bearing of the fans/motors and keep the proper record. 9) To check the foundation bolts of the units/motors and to take the necessary action if required. 10) Check the quantity of Air flow from various out lets in each room/ Area as per

drawings and do adjustment as and when required. 11) Check the performance of equipment for proper functioning 12) Any other job required to be attended during course of Checking and to keep the plant

in perfectly working conditions. Quarterly Maintenance: 1) Checking / setting / rectification of all safety and automatic controls. 2) Complete Overhauling of indoor/outdoor units, FCU, Fans. 3) Maintenance of Fresh Air & Exhaust Air Fans and their Balancing, if required. Observe the operation of all the dampers and make necessary adjustment in linkage and blade orientation for proper operation. 4) Functional checks & calibration of all switches, thermostats, humidistat and other instruments rectification of the same if required. 5) Any other job required to be attended during course of checking / as per OEM and to keep the plant in perfectly working conditions. 6) Maintenance of all Electrical equipment Feeders, Panels, Bus Bars, Cubicles, Motors, Heaters, Circuit Breakers, Power Points, etc. pertaining to HVAC as per standard electrical maintenance practice and as directed by concerned maintenance engineer. The maintenance and repairing of motors, Software re-installation (if required) etc. are also within the Vendor’s scope of work. 7) The gas charging in HVAC system will be executed by vendor, whenever required. NOTE: All the equipment’s/installations shall always be kept in good and trouble free operating conditions. All the required record for break-downs/repairs and maintenance etc. shall be maintained in the form of history books and logbooks etc. as per directions. All the maintenance works shall be carried out in accordance with the manufacturer’s specifications and instructions of the Administrative Officer (PA&F) or his representative.

1. TOOLS & PLANTS All the general & special tools, tackles required for proper maintenance and repairs/break down etc, shall be arranged by the contractor at his own cost.

Page 305: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 305 of 307

2. CONSUMABLES The rates shall be all inclusive of establishment as well as spares and consumables as per schedule of work. The contractor is required to assess the probable quantity of all types of spares and consumables likely to be required for replacement for keeping all the installations in good working conditions and include the lump sum cost of these spares & consumables. Nothing extra on any account shall be payable over and above the approved all-inclusive comprehensive rates of the contract. The consumables and spares shall be of best standard quality purchased from the original manufactures or authorized dealers only and shall be approved by the Client’s Officer. All related documents to be provided by contactor. Client’s office may direct the contractor to use consumables of its choice from the listed/approved vendors. All spares and consumables shall be arranged by the contractor for which nothing extra shall be payable. A list shall be prepared by the Contractor for major & minor spares consumables. Replaced parts/ spares, used brunt oil etc will be property of vendor. It is his responsibility to dispose it off immediately.

3. PENALTY CLAUSE 3.1. If work is not done as per above schedule or any system is not functioning then a penalty @ rate of Rs.1000 /- per day shall be imposed on contractor and will be deducted from the AMC amount due to the contractor and if unsatisfactory performance is continued for more than two days as felt by the client and AMC is liable to be terminated and final decision for this shall rest with Client. 3.2. If the contractor is NOT able to locate and rectify the fault and the reasons attributable to non performance of contractor as assessed by officials nominated by Client, the penalty clause is applicable as System remained non-functional for 1 day or more. The penalty will be Rs.1000/- per day. There will be 24 X 7 support on telephone during the AMC period. For any fault, onsite response time will be of 6 hours and resolution time will be of 24 hours. 3.3. If contractor is not able to rectify the fault then the same may be got done through some other agency at the risk and cost of contractor failing which the same amount will be deducted from AMC bill in addition to the penalty as stipulated above will also be imposed. However, the decision of the Client in this regard shall be final and binding.

4. Detailed Terms and Conditions for providing AMC & All Inclusive maintenance of HVAC systems includes following: 4.1. The contractors shall be responsible for the safety of his/her man power, all the items of furniture, plants, office equipment and other fittings provided in the premises and shall be liable to make good any loss to the same if damaged during the execution of their duties which shall be recoverable from their bill or other dues payable to the contractors by the company. 4.2. The contractor shall raise their invoice for AMC on quarterly basis only. This quarterly invoice will be submitted by the contractor after satisfactory completion of monthly & quarterly maintenance and the same will be settled by Client after due scrutiny only.

Page 306: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 306 of 307

4.3. The contractors should deploy the personnel after screening/approval from Client. 4.4. The contractor shall be responsible for the good conduct and behavior of his employees. If any employee of the contractor is found misbehaving with the supervisory staff or any other staff member, the contractor shall terminate the services of such employees at their own risk. The contractor shall issue necessary instruction to his/its employees to act upon the instructions given by the Client’s supervisory staff of office building.

5. SPECIAL TERMS AND CONDITIONS (STC) 5.1. Corrupt or Fraudulent Practices: 5.1.1 Bidders & Suppliers shall observe the highest standard of ethics during the procurement and execution of the contract. 5.2. Any material required for making good the damages will be brought by the contractor at his own cost and risk, and such material should be of proper brand and of good quality. 5.3. The firm will be responsible for the security/insurance of their staff working at site and Client will not be responsible in any manner in case of any accident / miss-happenings. 5.4. The successful bidder is required to appoint OEM or authorized agency of OEM as HVAC AMC contractor and should submit the credentials & past experience of the HVAC AMC contractor before his appointment.

6. Additional Terms and Conditions 6.1. The HVAC contractors should visit the site and acquaint themselves of the conditions existing, restrictions in movements / working hour’s security aspects, Condition of the plant equipment to be maintained / operated, before quoting for the job. No complaint of loss of labour, items of work not included, scope of work variation etc. will be entertained in handling similar works and should attach copies of cases handled by them along with performance certificate. 6.2. The contractor should submit list of spare parts required to carry out repairs and maintenance works well in advance to Client. 6.3. They shall be responsible for any periodic statutory inspection to be carried out on the equipment necessary test report and certificate rectification of defects, pointed during such inspection etc. 6.4. Contractors should follow all safety norms and provide necessary safety equipment at their own cost. In case of any accident during the maintenance of the equipment leading to injuries / damages to human beings equipment and / or loss of life, the contractor shall be fully responsible for settling all claims and indemnify the Centre against any claims arising out of such accidents. Consequent damages to other systems will however be recoverable from the contractor. 7. Payment terms of AMC charges

1) AMC charges quoted in the price bid will be divided proportionately floor wise (17th floor & 18th floor) and also according to the total TR rating of ODU of each floor.

Page 307: mazagondock.inmazagondock.in/writereaddata/tenders/146978105201751229PMTEF_V… · Tender No: 1800000049 Page 3 of 307 TECHNICAL SPECIFICATIONS GENERAL i. The detailed specifications

Tender No: 1800000047

Page 307 of 307

2) The AMC charges calculated floor wise and according to the total TR rating of ODU of each floor, will be paid quarterly after the monthly and quarterly maintenance programme against the submitted invoice.

The methodology of the above is explained as below.

Say, total AMC charges for 1st year – Rs. “A”

Total TR rating of all the ODUs of all the floors – “B”

Therefore AMC charges per TR = Rs. A / B = “C”

Hence floor wise AMC charges

= (Total TR rating of ODU of particular floor) x (AMC charges per TR = “C”)

The above calculated floor wise AMC charges will be paid quarterly as mentioned above

with supporting documents along with the invoice.