Critical Power

Technical Data Sheet Uninterruptible Power Supply

GE Consumer & Industrial SA

General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gecriticalpower.com

g

imagination at work

SGSE_010-040_S1_UPS_GE_01

Page 2: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Critical Power

Modifications reserved Page 2/6

GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1

Model: SG Series 10 – 15 - 20 – 30 - 40 PurePulse™ CE S1

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 03.12.2013

File name: GE_UPS_TDS_SGS_PCE_K10_K40_1GB_V010

Revision: 1.0

Identification No.:

Up-dating

Revision Concern Date

COPYRIGHT © 2013 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE’s Critical Power.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 3: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Critical Power

Modifications reserved Page 3/6

GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1

GENERAL DATA

Topology VFI, static double conversion UPS with integrated transformer

Nominal output apparent power at PF=0.6 lag. to 0.9 leading KVA 10 15 20 30 40

Nominal output active power at PF=1 kW 10 15 20 30 40*

Overall efficiency in VFI mode % Up to 92.3

Heat dissipation at 100% load in VFI mode, PF=0.8 lag. and charged battery

kW 0.65 1.11 1.27 2.18 2.69

Cooling air (25°C ÷ 30°C) m3/h 189 323 371 637 785

Audible noise level dB(A) 58 58 58 65 65

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Operating temperature range UPS: 0°C ÷ 40°C Battery: 20°C ÷ 25°C recommended

Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter

the storage time of the battery)

Storage time of the battery without recharge at 20°C Max. 6 months

Relative humidity Max. 95% (non-condensing)

Max. altitude without power de-rating Power de-rating (according to EN/IEC 62040-3)

1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%

Protection degree IP 20 (IEC 60529)

Standards EN/IEC 62040, CE marking

EMC (Electromagnetic Compatibility) EN/IEC 62040-2

Electrostatic discharge immunity 4kV contact / 8kV air discharge

Internal protection All internal live parts shrouded

Transport Cabinet suitable for handling by forklift

Colour RAL 9003 (white)

Installation Can be positioned against a wall and floor fixed

Service access Access required at front and top

External cable connections Bottom at front of the cabinet (standard)

Cooling Forced bottom to top by internal fans

Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (optional)

RECTIFIER

Rectifier bridge Three phase, IGBT rectifier, PurePulseTM technology, over-temperature protection

Standard input voltage Nominal: 3 x 380V / 400V / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V

Other input voltages On request

Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)

Power factor 0,99

Input current THD 2% at 100% load <5% at 50% load

Inrush current Limited by soft-start circuit

Power walk-in 15 seconds

Output voltage tolerance +/- 1%

DC voltage ripple <1%

Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit Programmable

Input power data kVA 10 15 20 30 40

Input power at inverter nominal load and charged battery

at PF=0.8 lag. at PF=1

kW 8.7

10.9 13.2 16.5

17.4 21.7

26.4 33.0

34.9 43.7

Max. input power at inverter nominal load And max. battery recharge current (programmable)

kW 11.7 16.8 21.8 32.7 43.5

Max. battery charging current (programmable) at the beginning of battery recharge at nominal load

at PF=0.8 lag. at PF=1

A 11 5

13 5

17 6

25 8

33 11

*) at 30°C operating temperature

Page 4: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Critical Power

Modifications reserved Page 4/6

GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1

BATTERY

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Number of 12V blocks, 6 cells/block 30 to 32 (30 blocks can be mounted in the UPS cabinet)

Float voltage at 20°C 405V ÷ 436V (dependent on the number of blocks)

Min. discharge voltage (programmable) 306V

Recharge time <5 hours up to 90% of battery capacity

“Battery to earth” fault detection Standard

Automatic and manual battery test Standard

Manual battery contactor Standard, with automatic safety disconnection

Battery power data kVA 10 15 20 30 40

DC power at full load and PF=0.8 kW 8.4 12.6 16.8 25.3 33.7

DC power at full load and PF=0.9 kW 9.5 14.2 18.9 28.4 37.9

DC power at full load and PF=1.0 kW 10.5 15.8 21.1 31.6 42.1

Matching battery cabinets See table on page 5 and 6

INVERTER

Nominal Total output power 10 – 15 – 20 – 30 – 40 kVA/kW

Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N

Inverter bridge SVM (Space Vector Modulation) and IGBT technology

Output transformer (for galvanic separation) Standard

Output waveform Sine wave

Output voltage tolerance: - static ......................................................................................................... +/- 1% - Dynamic (at load step 0 – 100 – 0%) .......................................... +/- 3% - Dynamic (at load step 0 – 50 – 0%) ............................................ +/- 2% - recovery time to +/-1% .................................................................... 20 ms - output voltage THD for 100% linear load ................................ <2% - output voltage THD for 100% non-linear load (EN 50091) <3%

Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%

Output frequency 50/60 Hz (selectable)

Output frequency tolerance: - free-running .......................................................................................... +/- 0.1% - with mains synchronisation adjustable to .............................. +/- 4%

Phase displacement: - at 100% balanced load .................................................................... 120°: +/- 1% - at 100% unbalanced load ............................................................... 120°: +/- 2%

Overload capability (@25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE

Protection clearance capability (selectivity) 20% In within 5-10 ms (with MCCB class C)

Crest factor >3:1

BYPASS

Input connection Separate (dual input-recommended) or common to the rectifier input

Primary components - Static switch (SCR) on bypass - Electro-mechanic contactor (back-feed protection) - Manual switch for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)

Overload on bypass 200% for 1 minute and 35 times In for 10 ms, non repetitive

INTERFACING

6 programmable signalling voltage-free contacts (available on terminal blocks)

- Standard information for easy integration and signalling - 27 user settable signals

Serial channel RS232 (on Delta 9 pin connector) Standard

Input signals - EPO - Emergency Power Off (n/c contact, customer supplied) - GEN ON(emergency power supply ON, n/o contact, customer supplied) - 1 auxiliary signals with settable functionality

Auxiliary power supply - 24Vdc auxiliary power supply (optional)

Note: all indicated values are typical. Variations may be found from one unit to another.

Page 5: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Critical Power

Modifications reserved Page 5/6

GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1

CONTROL PANEL

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements:

Back lit Graphic Display (LCD) with the following characteristics:

Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

Graphic diagram indicating UPS status.

Command keys and parameters setting.

UPS status control LED.

OPTIONS

COMMUNICATION:

1. Additional Customer Interface Card

2. 3-ph SNMP/WEB plug-in Adapter

3. Modbus RTU or Modbus/TCP Interface (only license)

4. GE iUPSGuard

5. GE Data Protection

BUILT-IN UPS OPTIONS: 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA

1. RPA kit

2. Auxiliary Power Supply (APS) 24Vdc

3. Rectifier or bypass or UPS input transformer * * * * *

4. Input / Output cable connection kit

*) Mounted in UPS cabinet battery cavity, instead of battery

OPTIONS IN ADDITIONAL CABINETS:

Dimensions (WxDxH): 750 x 800 x 1450 mm 1100 x 800 x 1450 mm

10 kVA 15 kVA 20 kVA 30 kVA 40 kVA

1. Rectifier or bypass or UPS input transformer On request

2. Special voltages: input and/or output On request

3. Centralized maintenance bypass for RPA configuration On request

4. Empty battery cabinets

Page 6: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Critical Power

Modifications reserved Page 6/6

GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1

TECHNICAL DATA

SG Series 10 – 40 PurePulse™

Dimensions

(Width x Depth x Height):

680 x 800 x 1450 mm

Battery table Dimensions Weights

UPS Autonomy

time Battery

capacity Battery cabinet

Total width

UPS Battery Battery + cabinet

Total Floor

loading (kVA) (Min.) (Ah) (mm) (mm) (Kg) (Kg) (Kg) (Kg) (Kg/m2)

10

10 9Ah HR in UPS 680

285

110 - 395 726

24 2 x 9Ah HR in UPS 680 220 - 505 928

30 22Ah HR in UPS 680 230 - 515 947

51 33Ah HR in UPS 680 335 - 620 1140

80 (estimated) 50Ah HR 750 1430 - 600 885 1000

135 (estimated) 75Ah HR 750 1430 - 900 1185 1500

15

5.5 9Ah HR in UPS 680

335

110 - 445 818

15 2 x 9Ah HR in UPS 680 220 - 555 1020

19 22Ah HR in UPS 680 230 - 565 1038

30 33Ah HR in UPS 680 335 - 670 1232 52 50Ah HR 750 1430 - 600 935 1000

85 (estimated) 75Ah HR 750 1430 - 900 1235 1500

20

10 2 x 9Ah HR in UPS 680

335

220 - 555 1020

13 22Ah HR in UPS 680 230 - 565 1038

22 33Ah HR in UPS 680 335 - 670 1232

35 50Ah HR 750 1430 - 600 935 1000

60 75Ah HR 750 1430 - 900 1235 1500

30

5.5 2 x 9Ah HR in UPS 680

400

220 - 620 1140

7.5 22Ah HR in UPS 680 230 - 630 1158

13 33Ah HR in UPS 680 335 - 735 1351

22 50Ah HR 750 1430 - 600 1000 1000

36.5 75Ah HR 750 1430 - 900 1300 1500

40

5 22Ah HR in UPS 680

400

230 - 630 1158

9 33Ah HR in UPS 680 335 - 735 1351

15.5 50Ah HR 750 1430 - 600 1000 1000

26 75Ah HR 750 1430 - 900 1300 1500

) At full load and PF=0.8 lag. ) Based on BB Battery HR type ) Max. value for battery cabinet only

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Separated input Rectifier & Bypass

1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = Internal Battery

2 = Inverter 4 = Manual Bypass 6 = Load

Line protections and cable sections

Protections for mains voltages Battery protection

Cable sections (mm2) recommended by European Standards

3 x 380V / 400V / 415V Alternatively, local standards to be respected

kVA F1 F2 F3 (if external) A B C & D K (for external battery)

10 3x 20A 3 x 20A 3 x 20A 2 x 40A 4 x 2.5 4 x 2.5 5 x 2.5 3 x 6

15 3 x 25A 3 x 25A 3 x 25A 2 x 63A 4 x 4 4 x 4 5 x 4 3 x 10

20 3 x 35A 3 x 35A 3 x 35A 2 x 63A 4 x 6 4 x 6 5 x 6 3 x 10

30 3 x 50A 3 x 50A 3 x 50A 2 x 100A 4 x 10 4 x 10 5 x 10 2 x 25 + 16

40 3 x 63A 3 x 63A 3 x 63A 2 x 100A 4 x 10 4 x 10 5 x 10 2 x 25 + 16

Cable sections (mm2) recommended in Switzerland

F1, F2, F3, A, B, C, D: supplied by customer kVA A B C & D K (for external battery)

Battery protection: can be supplied by GE’s Critical Power 10 4 x 4 4 x 4 5 x 4 3 x 10

15 4 x 6 4 x 6 5 x 6 3 x 16

20 4 x 10 4 x 10 5 x 10 3 x 16

30 4 x 16 4 x 16 5 x 16 2 x 35 + 25

40 4 x 16 4 x 16 5 x 16 2 x 35 + 25

IMPORTANT NOTE! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 3 pole breakers should be used upstream the UPS input (see also IEC 60364-1, IEC 61140 and IEC 61557).

SGSE_010-040_S1_UPS dimension_GE_01

1'4

50

mm

800mm680mm

Page 7: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

GE Digital Energy Power Quality

Technical Data Sheets Digital Energy™ Uninterruptible Power Supply SG-CE Series 60–80–100–120 kVA PurePulse® 400 Vac CE – Series 1

SG-CE Series 100 - 120 kVA PurePulse ®

SG-CE Series 60 - 80 kVA PurePulse®

SGSE

_060

-120

_S1_

UPS

_GE_

01

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44

www.gedigitalenergy.com

GE imagination at work

Page 8: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Modifications reserved Page 2/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1

Model: SG-CE Series 60 – 80 – 100 – 120 kVA PurePulse® / Series 1

Issued by: Product Document Department – Riazzino - CH

Date of issue: 15.12.2008

File name: TDS_SGS_PCE_60K_M12_1GB_V020

Revision: 2.0

Identification No.

Up-dating

Revision Concern Date

2.0 ECN 1257 (Short-circuit characteristic) + 50Ah battery cabinet 15.12.2008

COPYRIGHT © 2008 by GE Consumer & Industrial SA All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 9: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Modifications reserved Page 3/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1

GENERAL DATA Topology VFI, double conversion with integrated transformer Nominal output power from PF=0.6 lag. to 0.9 leading KVA/kW 60/54 80/72 100/90 120/108

Overall efficiency at 100% load PF=0.9 lag. in VFI mode 91.4 91.4 91.7 91.2 Overall efficiency at 75% load PF=0.9 lag. in VFI mode +/-0.2% 91.8 91.8 92.0 91.8

Overall efficiency at 50% load PF=0.9 lag. in VFI mode

% (guaranteed values) 91.9 91.9 91.9 92.1

Overall efficiency at 100% load in SEM mode +/-0.2% % 97.9 97.9 97.8 97.9 Heat dissipation at 100% load in VFI mode, PF=0.8 lag. & charged battery kW 4.52 6.02 7.24 9.26 Cooling air (25°C ÷ 30°C) m3/h 1320 1760 2115 2710 Audible noise level dB(A) 63 63 63 63 Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd Operating temperature range UPS: 0°C ÷ 40°C Storage temperature range -25°C ÷ +55°C Relative Humidity Max. 95% (non-condensing) Max. altitude without power derating Power derating (according to EN/IEC 62040-3)

1000m 1500m: -5% / 2000m: -9% / 2500m: -14% / 3000m: -18%

Protection degree IP 20 (IEC 60529) Standards EN/IEC 62040, CE marking EMC EN/IEC 62040-2 (Category C2 as option), Burst & Surges 2kV L-L, 4kV L-PE Electrostatic discharge immunity 8kV contact / 15kV air discharge Internal protection All live parts shrouded Transport Cabinet suitable for handling by forklift Colour RAL 9003 (white), bottom air grids RAL 7021 (black) Installation Can be positioned against a wall and floor fixed Service access Front and top access only External cable connections Bottom at front of the cabinet (top as option) Cooling Enforced ventilation with fan speed control

Paralleling (RPA version) Up to 6 units parallelable for redundancy or capacity in RPA configuration (optional).

RECTIFIER

Rectifier bridge Three phase, IGBT rectifier, PurePulse® technology, overtemperature protection

Standard input voltage Nominal: 3 x 380V / 400V / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V

Other input voltages On request Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz) Power factor 0.99 Input current THD 2% at 100% load <2.5% at 75% load <3% at 50% load Inrush current Limited by soft-start circuit Power walk-in 15 seconds Output voltage tolerance +/- 1% DC voltage ripple <1% DC current ripple Max. 5% the battery capacity [Ah], expressed in A Battery charging characteristic IU (DIN 41773), T° compensated floating voltage Battery charging current limit Programmable Input power data kVA 60 80 100 120

at PF=0.8 lag. 52.5 70.0 87.3 105.3 Input power at inverter nominal load and charged battery at PF=0.9 lag. kW 59.1 78.8 98.2 118.5

Max. input power at inverter nominal load and max. battery recharge current (programmable) kW 66.0 87.8 109.5 131.6

at PF=0.8 lag. 33 44 55 65 Max. battery charging current (programmable) at the beginning of battery recharge at nominal load at PF=0.9 lag.

A 17 22 27 32

UPS OUTPUT POWER CAPABILITY

Output UPS power versus power factor for: − Inductive loads − Resistive loads − Capacitive loads

Page 10: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Modifications reserved Page 4/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1

BATTERY

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)

Number of cells

VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells

Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells) Recharge time <5 hours up to 90% of battery capacity “Battery to earth” fault detection Standard Automatic and manual battery test Standard Automatic battery contactor Standard Battery power data kVA 60 80 100 120 DC power at full load and PF=0.8 lag. kW 50.8 67.8 84.7 101.6 DC power at full load and PF=0.9 lag. kW 57.2 76.2 95.3 114.3 DC power at full typical computer load (PF=0.66 lag.) kW 41.9 55.9 69.9 83.8 Matching battery cabinets See optional features on page 5

INVERTER Nominal output power at PF=0.6 ... 0.9 lag. 60 – 80 – 100 - 120 kVA Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N Inverter bridge SVM (Space Vector Modulation) and IGBT technology Output transformer (for galvanic separation) Standard Output waveform Sine wave Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ........................................ +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3% Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3% Output frequency 50/60 Hz (selectable) Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to .......................... +/- 4% Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load .......................................................... 120°: +/- 3% Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE

MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB class C or magn. trip at max. 10In) Crest factor >3:1

BYPASS Input connection Separate (dual input-recommended) or common to the rectifier input

Primary components

- Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and

inverter - 2 manual switches for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable) Overload on bypass 200% for 5 minutes & 45 times In for 10 ms, non repetitive

INTERFACING 6 programmable signalling voltage-free contacts (available on Delta and block terminals)

- Standard information for easy integration and signalling - 27 user settable signals

Serial channel RS232 (on Delta 9 pin connector) Standard

Input signals - EMERGENCY POWER OFF (n/c contact, customer supplied) - GEN ON (emergency power supply ON, n/o contact, customer supplied) - 1 auxiliary signal, with settable functionality

Note: all indicated values are typical. Variations may be found from one unit to another.

Page 11: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Modifications reserved Page 5/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: • Back lit Graphic Display (LCD) with the

following characteristics: − Multilanguage communication

interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

− Graphic diagram indicating UPS status.

• Command keys and parameters setting.

• UPS status control LED.

OPTIONS

COMMUNICATION: 1. Additional Customer Interface Card 2. Advanced SNMP Card 3. GE Power Diagnostics 4. GE Data Protection 5. RSB - Remote Signalling Box (cable for connection to UPS not included)

BUILT-IN UPS OPTIONS: 1. RPA kit 2. Auxiliary Power Supply (APS) 24Vdc

OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH): 350x850x1900mm 500x850x1900mm 850x850x1900mm 1500x850x1900mm

1. Rectifier or bypass or UPS input transformer 2. EMC filter EN/IEC 62040-2 Category C2 (Class A) 3. Top entry cables cabinet

4. Special voltages: input and/or output On request 5. Empty battery cabinets 6. Battery cabinet 50Ah (without fuses) 7. Battery cabinet 75Ah (without fuses) BATTERY TABLE 8. Battery cabinet 2x50Ah (without fuses) At 75% load PF 0.8 At 100% load PF 0.8

9. Battery cabinet 2x75Ah (without fuses) UPS (kVA) 50Ah 75Ah 2x50Ah 2x75Ah 4x50Ah 4x75Ah 50Ah 75Ah 2x50Ah2x75Ah4x50Ah4x75Ah

60 13 min. 22 min. 31 min. 53 min. 77 min. 139 min. 9 min. 16 min. 22 min. 36 min. 53 min. 95 min.

80 9 min. 15 min. 22 min. 36 min. 52 min. 95 min. 6 min. 11 min. 16 min. 26 min. 36 min. 70 min.

100 _ 12 min. 17 min. 27 min. 37 min. 65 min. _ 8 min. 12 min. 20 min. 28 min. 45 min.

SGSE_060-120_S1_OPT_cabinet 500_01

50Ah

670 kg

SGSE_160-300_OPT_B1 cabinet_01

75Ah 1000 kg

2x50Ah 1170 kg

SGSE_160-300_OPT_B2 cabinet_01

2x75Ah

1800 kg

120 _ 9 min. 13 min. 22 min. 32 min. 51 min. _ 6 min. 9 min. 16 min. 22 min. 36 min.

500x850x1900mm 850x850x1900mm 1500x850x1900mm These runtimes can be achieved only with our High Rate batteries.

EXTERNAL ACCESSORIES: 1. ISM - Intelligent Synchronization Module 350mm x 190mm x 584mm 2. Parallel output cabinet with centralized maintenance bypass On request 3. Battery fuses box On request

Page 12: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Modifications reserved Page 6/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1

TECHNICAL DATA

WEIGHTS (kg) UPS cabinet Additional cabinet

UPS

Rat

ing

(kVA

)

UPS

sta

ndar

d (k

g)

Floo

r loa

ding

U

PS s

tand

ard

(kg/

m2 )

Rect

ifier

or

bypa

ss tr

ansf

orm

er

(500

x850

x190

0mm

)

EMC

filte

r EN

/IEC

6204

0-Ca

t. C2

(3

50x8

50x1

900m

m)

Top

entr

y ca

bles

ca

bine

t (3

50x8

50x1

900m

m)

60 550 kg 995 340 kg 110 kg 70 kg

80 630 kg 1140 380 kg 110 kg 70 kg

100 860 kg 1212 450 kg 125 kg 75 kg

SG-CE Series 60 & 80 kVA SGSE_060-080_S1_UPS dimensions_GE_01

850mm650mm

1'90

0mm

Dimensions (WxDxH): 650mm x 850mm x 1900mm

120 860 kg 1212 450 kg 125 kg 75 kg

SG-CE Series 100 & 120 kVA

SGSE_100-120_S1_UPS dimensions_GE_01

835mm850mm

1'90

0mm

Dimensions (WxDxH): 835mm x 850mm x 1900mm

Note: Single weights have to be added up for system configuration to get the total weight!

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Separated input Rectifier & Bypass

1 = Rectifier 3 = Electronic Bypass 5 = Mains 7 = External Battery 2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses

Protections and cable sections

Protections for mains voltages

3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards

Alternatively, local standards to be respected

Fuses AgL or equivalent MTCB Cable sections (mm2)

kVA

F1 F2 F3 F4 A B C & D & E K

60 3x100A 3x100A 3x100A 2x160A 3 x 25 + 16 4 x 25 4 x 25 + 16 2 x 50 + 25

80 3x125A 3x125A 3x125A 2x250A 3 x 35 + 25 4 x 35 4 x 35 + 25 2 x 120 + 70

100 3x160A 3x160A 3x160A 2x315A 3 x 50 + 25 4 x 50 4 x 50 + 25 2 x 150 + 95

120 3x200A 3x200A 3x200A 2x355A 3 x 70 + 35 4 x 70 4 x 70 + 35 2 x 185 + 95

Cable sections recommended in Switzerland (mm2)

F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & D & E K

K: supplied by GE only with battery 60 3 x 35 + 25 4 x 35 4 x 35 + 25 2 x 70 + 35

F4: can be supplied by GE. 80 3 x 50 + 25 4 x 50 4 x 50 + 25 2 x 150 + 95

100 3 x 70 + 35 4 x 70 4 x 70 + 35 2 x 185 + 95

120 3 x 95 + 50 4 x 95 4 x 95 + 50 2 x 240 + 120

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557).

Page 13: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Technical Data Sheet Uninterruptible Power Supply

SG Series 160 PurePulse™ SG Series 200 - 250 - 300 PurePulse™

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gepowerquality.com

g

imagination at work

SGSE_160_S3_UPS_01

SGSE_200-300_S3_UPS_01

Page 14: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 2/6

GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3

Model: SG Series 160 – 200 – 250 - 300 PurePulse™ CE S3

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 25.04.2012

File name: GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010

Revision: 1.0

Identification No.:

Up-dating

Revision Concern Date

COPYRIGHT © 2012 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE Digital Energy.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 15: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 3/6

GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3

GENERAL DATA Topology VFI, double conversion with integrated transformer

Nominal output apparent power from PF=0.6 lag. to 0.9 lag. and at 0.9 leading KVA 160 200 250 300

Nominal output active power from PF=0.9 lag. to 0.9 leading kW 144 180 225 270

Efficiency at 100% load PF=1 in VFI / eBoost Operation Modes %

93.6/98.4 93.7/98.4 93.4/98.4 93.5/98.5 Efficiency at 75% load PF=1 in VFI / eBoost Operation Modes 93.9/98.3 94.3/98.3 94.0/98.3 94.0/98.5 Efficiency at 50% load PF=1 in VFI / eBoost Operation Modes 94.2/98.1 94.6/98.1 94.1/98.1 94.2/98.3

Heat dissipation at 100% load, PF=0.8 lag. & charged battery (VFI) kW 8.2 10.1 13.2 15.6

Heat dissipation at 100% load, PF=0.9 lag. & charged battery (VFI) kW 9.2 11.3 14.9 17.6

Cooling air at PF=0.8 (25°C ÷ 30°C) m3/h 2389 2940 3850 4550

Cooling air at PF=0.9 (25°C ÷ 30°C) m3/h 2688 3308 4331 5119

Audible noise level dB(A) 69

Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd

Operating temperature range UPS: 0°C ÷ 40°C

Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the

storage time of the battery)

Relative Humidity Max. 95% (non-condensing)

Max. altitude without power derating Power derating (according to EN/IEC 62040-3)

1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%

Protection degree IP 20 (IEC 60529

Standards EN/IEC 62040, CE marking

EMC (Electromagnetic Compatibility) EN/IEC 62040-2 (Category C2 as option)

Electrostatic discharge immunity 4kV contact / 8kV air discharge

Internal protection All internal live parts shrouded

Transport Cabinet suitable for handling by forklift

Colour RAL 9005 (black)

Installation Can be positioned against a wall and floor fixed

Service access Front and top access only

External cable connections Bottom at front of the cabinet (top as option)

Cooling Enforced ventilation with fan failure detection

Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)

RECTIFIER Rectifier bridge Three phase, IGBT rectifier, PurePulse™ technology, overtemperature protection

Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V

Other input voltages On request

Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)

Power factor 0.99

Input current THD 2% at 100% load <2.5% at 75% load <3% at 50% load

Inrush current Limited by soft-start circuit

Power walk-in 15 seconds

Output voltage tolerance +/- 1%

DC voltage ripple <1%

DC current ripple Max. 5% the battery capacity [Ah], expressed in A

Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit Programmable

Input power data kVA 160 200 250 300

Input power at inverter nominal load and charged battery at PF=0.8 lag.

kW 136.8 170.8 214.1 256.7

at PF=0.9 lag. 153.9 192.1 240.9 288.8

Max. input power at inverter nominal load and max. battery recharge current (programmable)

kW 170.5 212.7 267.8 321.1

Max. battery charging current (programmable) at the beginning of battery recharge at nominal load

at PF=0.8 lag. A

85 105 130 160

at PF=0.9 lag. 40 50 70 80

UPS OUTPUT POWER CAPABILITY

Output UPS power versus power factor for:

Inductive loads

Resistive loads

Capacitive loads

Page 16: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 4/6

GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3

BATTERY Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)

Number of cells

VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells

Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells)

Recharge time <5 hours up to 90% of battery capacity

“Battery to earth” fault detection Standard

Automatic and manual battery test Standard

Battery power data kVA 160 200 250 300

DC power at full load and PF=0.8 lag. / PF=0.9 lag. kW 134.7 / 151.6 168.4 / 189.5 210.5 / 236.8 252.6 / 284.2

DC power at full typical computer load (PF=0.66 lag.) kW 111.2 138.9 173.7 208.4

Matching battery cabinets See option features on page 5

INVERTER Nominal output apparent power from PF=0.6 lag. to 0.9 lag. & at 0.9 leading 160 – 200 – 250 - 300 kVA

Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N

Inverter bridge SVM (Space Vector Modulation) and IGBT technology

Output transformer (for galvanic separation) Standard

Output waveform Sine wave

Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3%

Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%

Output frequency 50/60 Hz (selectable)

Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%

Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load ........................................................... 120°: +/- 3%

Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE

MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB class C or magn. trip at max. 10In)

Crest factor >3:1

eBoost™ OPERATION MODE (OPTION) eBoost Operation Mode characteristics (option)

Output waveform Continuously monitored

Inverter reaction time ms <2 (typical)

Transfer limits in eBoost Operation Mode (option)

Steady-State RMS tolerance Vrms +/- 10

Instantaneous voltage distortion (w.r.t. normal sine wave)

Magnitude Vp +/- 50

Duration us 500

Steady-State frequency tolerance Hz +/- 3

Instantaneous phase shift rad 0.15

BYPASS Input connection Separate for rectifier and bypass input or common to the rectifier input (option)

Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and inverter - 2 manual switches for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)

Overload on bypass 150% for 1 minute & 45 times In for 10 ms, non repetitive

INTERFACING RS232 serial port Standard

EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard

Customer Interface board Standard 6 programmable signalling voltage-free contacts .............. (available on block terminals)

- Standard information for easy integration and signalling - 27 user settable signals

Connector RJ45 .................................................................................... With adaptation cable for a serial port RS232 / sub DB9 connection Input signals .......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)

- 1 auxiliary signal, with settable functionality Note: all indicated values are typical. Variations may be found from one unit to another.

Page 17: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 5/6

GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) with the following

characteristics:

Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

Graphic diagram indicating UPS status.

Command keys and parameters setting.

UPS status control LED.

OPTIONS

COMMUNICATION:

1. Additional Customer Interface Card

2. 3-ph SNMP/WEB plug-in Adapter

3. GE Power Diagnostics

4. GE Data Protection

5. RSB - Remote Signalling Box (cable for connection to UPS not included)

BUILT-IN UPS OPTIONS:

1. eBoost™ Operation Mode

2. RPA kit (Redundant Parallel Architecture)

3. Kit for common input mains

4. Auxiliary Power Supply (APS) 24VDC

5. Surge suppressors

OPTIONS IN ADDITIONAL CABINETS:

Dimensions (WxDxH): 500x850x1900mm 850x850x1900mm 1000x850x1900mm 1500x850x1900mm

1. Rectifier or bypass or UPS input transformer 160 & 200 kVA / 250 & 300 kVA

2. EMC filter EN/IEC 62040-2 Category C2 (Class A)

3. Top entry cables cabinet

4. Special voltages: input and/or output On request

5. Empty battery cabinets

6. Battery cabinet 2x50Ah (without fuses) BATTERY TABLE

7. Battery cabinet 2x75Ah (without fuses) UPS At 75% load PF 0.8 At 100% load PF 0.8

2x50Ah

1170 Kg

2x75Ah

1800 Kg

2x50Ah 2x75Ah 4x50Ah 4x75Ah 2x50Ah 2x75Ah 4x50Ah 4x75Ah

160 9 min. 15 min. 22 min. 36 min. 6 min. 11 min. 16 min. 25 min.

200 6 min. 12 min. 17 min. 27 min. _ 8 min. 12 min. 19 min.

250 _ 8 min. 13 min. 21 min. _ 6 min. 8 min. 15 min.

300 _ _ 10 min. 17 min. _ _ 6 min. 12 min.

These runtimes can be achieved only with our High Rate batteries

EXTERNAL ACCESSORIES:

1. Parallel output cabinet with centralized maintenance bypass On request

2. Battery fuses box On request

SGSE_160-300_OPT_B1 cabinet_01

SGSE_160-300_OPT_B2 cabinet_01

Page 18: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 6/6

GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3

TECHNICAL DATA

SG Series 160 PurePulse™

Dimensions (WxDxH): 900mm x 850mm x 1900mm

WEIGHTS (kg) SG Series 200 - 250 - 300 PurePulse™

Dimensions (WxDxH): 1300mm x 850mm x 1900mm

UP

S R

ati

ng

(kV

A)

UPS cabinet Built-in UPS

options Options in additional

cabinet

UP

S s

tan

da

rd

(kg

)

Flo

or

loa

din

g

UP

S s

tan

da

rd (k

g/m

2)

eB

oo

st™

O

pe

rati

on

Mo

de

(k

g)

Re

ctif

ier

or

by

pa

ss t

ran

sfo

rme

r (8

50

/10

00

x85

0x1

90

0m

m)

EM

C f

ilte

r E

N/I

EC

62

04

0-C

at.

C2

(5

00

x85

0x1

90

0m

m)

Top

en

try

ca

ble

s c

ab

ine

t (5

00

x85

0x1

90

0m

m)

160 1050 1373 20 800 230 125

200 1220 1105

30

800 230 125

250 1470 1331 900 230 125

300 1560 1412 900 230 125

Note: Single weights have to be added up for system configuration to get the total weight!

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Separated input Rectifier & Bypass

1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = External Battery

2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses

Protections and cable sections

Protections for mains voltages

3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards

Alternatively, local standards to be respected

kVA Fuses AgL or equivalent MTCB Cable sections (mm

2)

F1 F2 F3 F4 A B C & E & D K

160 3x250A 3x250A 3x250A 2x400A 3x120+70 4x120 4x120+70 2x240+120

200 3x315A 3x315A 3x315A 2x500A 3x150+95 4x150 4x150+95 2x(2x120)+120

250 3x400A 3x400A 3x400A 2x630A 3x240+120 4x240 4x240+120 2x(2x150)+150

300 3x500A 3x500A 3x500A 2x800A 3x(2x120)+120 4x(2x120) 4x(2x120)+120 2x(2x240)+240

Cable sections recommended in Switzerland (mm2)

F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & E & D K

K: supplied by GE only with battery 160 3x150+95 4x150 4x150+95 2x(2x95)+95

F4 and Q3: can be supplied by GE. 200 3x185+95 4x185 4x185+95 2x(2x150)+150

250 3x(2x95)+95 4x(2x95) 4x(2x95)+95 2x(2x185)+185

300 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(3x185)+2x150

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557).

SGSE_160_S3_UPS dimension_01

1'9

00

mm

900mm850mm

SGSE_200-300_S3_UPS dimension_01

1'300mm850mm

1'9

00

mm

Page 19: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Technical Data Sheet Uninterruptible Power Supply

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gepowerquality.com

g

imagination at work

SGSE_400-500_S3_UPS_01

Page 20: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 2/6

GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3

Model: SG Series 400 & 500 PurePulse™ CE S3

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 25.04.2012

File name: GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010

Revision: 1.0

Identification No.:

Up-dating

Revision Concern Date

COPYRIGHT © 2012 by GE Consumer & Industrial SA All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE Digital Energy.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 21: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 3/6

GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3

GENERAL DATA

Topology VFI, double conversion with integrated transformer

Nominal output apparent power from PF=0.6 lag. to 0.9 lag. and at 0.9 leading KVA 400 500

Nominal output power from PF=0.9 lag. to 0.9 leading kW 360 450

Overall efficiency at 100% load PF=1 in VFI Operation Mode / eBoost Operation Mode %

93.3 / 98.5% 93.2 / 98.7% Overall efficiency at 75% load PF=1 in VFI Operation Mode / eBoost Operation Mode 93.8 / 98.5% 93.7 / 98.7% Overall efficiency at 50% load PF=1 in VFI Operation Mode / eBoost Operation Mode 94.2 / 98.3% 94.2 / 98.6%

Heat dissipation at 100% load in VFI Operation Mode, PF=0.8 lag. and charged battery kW 21.4 27.2

Heat dissipation at 100% load in VFI Operation Mode, PF=0.9 lag. and charged battery kW 24.1 30.6

Cooling air at PF=0.8 (25°C ÷ 30°C) m3/h 6253 7933

Cooling air at PF=0.9 (25°C ÷ 30°C) m3/h 7035 8925

Audible noise level dB(A) 72

Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd

Operating temperature range UPS: 0°C ÷ 40°C

Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the

storage time of the battery)

Relative Humidity Max. 95% (non-condensing)

Max. altitude without power derating Power derating (according to EN/IEC 62040-3)

1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%

Protection degree IP 20 (IEC 60529)

Standards EN/IEC 62040, CE marking

EMC (Electromagnetic Compatibility) EN/IEC 62040-2

Electrostatic discharge immunity 4kV contact / 8kV air discharge

Internal protection All internal live parts shrouded

Transport Cabinet suitable for handling by forklift

Colour RAL 9005 (black)

Installation Can be positioned against a wall and floor fixed

Service access Front and top access only

External cable connections Bottom at front of the cabinet (top as option)

Cooling Enforced ventilation with fan failure detection and fan speed regulation

Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)

RECTIFIER

Rectifier bridge Three phase, IGBT rectifier, PurePulse™ technology, overtemperature protection

Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V

Other input voltages On request

Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)

Power factor 0.99

Input current THD 2% at 100% and 75% load <3% at 50% load <4.5% at 25% load

Inrush current Limited by soft-start circuit

Power walk-in 15 seconds

Output voltage tolerance +/- 1%

DC voltage ripple <1%

DC current ripple Max. 5% the battery capacity [Ah], expressed in A

Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit Programmable

Input power data kVA 400 500

Input power at inverter nominal load and charged battery at PF=0.8 lag.

kW 343.0 429.2

at PF=0.9 lag. 385.9 482.8

Max. input power at inverter nominal load and max. battery recharge current (programmable)

kW 430 539

Max. battery charging current (programmable) at the beginning of battery recharge at nominal load

at PF=0.8 lag. A

215 270 at PF=0.9 lag. 110 140

UPS OUTPUT POWER CAPABILITY

Output UPS power versus power factor for:

Inductive loads

Resistive loads

Capacitive loads

Page 22: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 4/6

GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3

BATTERY

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)

Number of cells

VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells

Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells)

Recharge time <5 hours up to 90% of battery capacity

“Battery to earth” fault detection Standard

Automatic and manual battery test Standard

Battery power data kVA 400 500

DC power at full load and PF=0.8 / PF=0.9 kW 336.8 / 378.9 421.0 / 473.7

DC power at full typical computer load (PF=0.66) kW 277.9 347.4

INVERTER

Nominal output apparent power from PF=0.6 lag. to 0.9 lag. & at 0.9 leading 400 & 500 kVA

Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N

Inverter bridge SVM (Space Vector Modulation) and IGBT technology

Output transformer (for galvanic separation) Standard

Output waveform Sine wave

Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3%

Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%

Output frequency 50/60 Hz (selectable)

Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%

Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load ........................................................... 120°: +/- 3%

Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE

MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB with magnetic trip at max. 10In)

Crest factor >3:1

eBoost™ OPERATION MODE (OPTION)

eBoost Operation Mode characteristics (option)

Output waveform Continuously monitored

Inverter reaction time ms <2 (typical)

Transfer limits in eBoost Operation Mode (option)

Steady-State RMS tolerance Vrms +/- 10

Instantaneous voltage distortion (w.r.t. normal sine wave)

Magnitude Vp +/- 50

Duration us 500

Steady-State frequency tolerance Hz +/- 3

Instantaneous phase shift rad 0.15

BYPASS

Input connection Separate for rectifier and bypass input or common to the rectifier input (option)

Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass & inverter - 2 manual switches for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)

Overload on bypass 150% for 1 minute & 45 times In for 10 ms, non repetitive

INTERFACING

RS232 serial port Standard

EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard

Customer Interface board Standard 6 programmable signalling voltage-free contacts .............. (available on block terminals)

- Standard information for easy integration and signalling - 27 user settable signals

Connector RJ45 .................................................................................... With adaptation cable for a serial port RS232 / sub DB9 connection Input signals .......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)

- 1 auxiliary signal, with settable functionality

Note: all indicated values are typical. Variations may be found from one unit to another.

Page 23: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 5/6

GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) with the

following characteristics:

Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

Graphic diagram indicating UPS status.

Command keys and parameters setting.

UPS status control LED.

OPTIONS

COMMUNICATION:

1. Additional Customer Interface Card

2. 3-ph SNMP/WEB plug-in Adapter

3. GE Power Diagnostics

4. GE Data Protection

5. RSB - Remote Signalling Box (cable for connection to UPS not included)

BUILT-IN UPS OPTIONS:

1. eBoost™ Operation Mode

2. RPA kit (Redundant Parallel Architecture)

3. Kit for common input mains

4. Auxiliary Power Supply (APS) 24Vdc

5. Surge suppressors

OPTIONS IN ADDITIONAL CABINETS:

1. Rectifier or bypass or UPS input transformer Dimensions (WxDxH): 1300 x 950 x 1900mm

2. Battery isolator switch Q3 cabinet

3. Top entry cable cabinet

4. Battery isolator switch Q3 and Top entry cable cabinet

Dimensions (WxDxH): 570 x 950 x 1900mm

EXTERNAL ACCESSORIES:

1. Parallel output cabinet with centralized maintenance bypass On request

2. Battery fuses box On request

SGSE_400-500_S1_Transformer cabinet_01SGSE_400-500_S1_Q3 cabinet_01

Page 24: Technical Data Sheet - Business Critical Engineering · 2017. 2. 4. · *) Mounted in UPS cabinet battery cavity, instead of battery OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH):

Digital Energy

Modifications reserved Page 6/6

GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3

TECHNICAL DATA

SG Series 400 & 500 PurePulse™ SG Series 400 & 500 PurePulse™ with Battery isolator switch Q3 cabinet and/or Top entry cable cabinet (option)

Dimensions (WxDxH): 1800 x 950 x 1900 mm Dimensions (WxDxH): 2370 x 950 x 1900 mm

WEIGHTS

UPS model

UPS cabinet Built-in UPS options Options in additional cabinet

UP

S

sta

nd

ard

Flo

or

loa

din

g

UP

S

sta

nd

ard

eB

oo

st™

O

pe

rati

on

Mo

de

Ba

tte

ry Is

ola

tor

swit

ch

Q3

c

ab

ine

t

Top

en

try

ca

ble

c

ab

ine

t

Ba

tte

ry Is

ola

tor

Sw

itc

h Q

3 a

nd

To

p e

ntr

y c

ab

le

ca

bin

et

Re

ctif

ier

or

by

pa

ss o

r

UP

S in

pu

t tr

an

sfo

rme

r

SG Series 400 PurePulse™ 2190 kg 1281 kg/m2 75 kg 180 kg 200 kg 220 kg 1350 kg

SG Series 500 PurePulse™ 2470 kg 1445 kg/m2 75 kg 180 kg 200 kg 220 kg 1600 kg

Note: Single weights have to be added up for system configuration to get the total weight!

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Separated input Rectifier & Bypass

1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = External Battery

2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses

Protections and cable sections

Protections for mains voltages

3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards

Alternatively, local standards to be respected

kVA Fuses AgL or equivalent MTCB Cable sections (mm

2)

F1 F2 F3 F4 A B C & E & D K

400 3x630A 3x630A 3x630A 2x1000A 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(4x120)+2x120

500 3x800A 3x800A 3x800A 2x1250A 3x(2x240)+240 4x(2x240) 4x(2x240)+240 2x(3x240)+2x185

Cable sections recommended in Switzerland (mm2)

F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & E & D K

K: supplied by GE only with battery 400 3x(2x185)+185 4x(2x185) 4x(2x185)+185 2x(4x150)+2x150

F4 and Q3: can be supplied by GE 500 3x(3x150)+240 4x(3x150) 4x(3x150)+240 2x(4x185)+2x185

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60364, IEC 61140, IEC 61557).

SGSE_400-500_S3_UPS dimension_01

1'9

00

mm

1'800mm950mm

SGSE_400-500_S3_UPS+Q3 dimension_01

1'9

00

mm

1800mm950mm

570mm

2370mm