technical committee on fire protection for nuclear facilities · technical committee on fire...
TRANSCRIPT
Technical Committee on Fire Protection for Nuclear Facilities
Date: May 1, 2017
To: Technical Committee on Fire Protection for Nuclear Facilities
From: Eric Nette, Staff Liaison/Engineer
Re: Agenda Package – NFPA 801 F2018 First Draft Meeting –May 23-24, 2017
Enclosed is the agenda package for the Tuesday and Wednesday, May 23-24, 2017
NFPA 801 First Draft Meeting. Please ensure that you have reviewed the public input
and the other agenda items in advance to prepare for discussion. The agenda (which
includes the public inputs) will be posted on the document information pages to
www.nfpa.org/801next
Some items to have available during the meeting include:
Agenda package with public input
A copy of NFPA 801 (visit the NFPA 801 Document information pages for your
free committee copy)
Any previous copies of the technical committees standard
A laptop
Optional items that are sometimes useful include:
Review of NFPA’s Process, www.nfpa.org/regs
If you have any questions or comments, please feel free to reach me at (617) 984-7434 or
by e-mail at [email protected]. I look forward to our meeting to begin the revision cycle!
Page 1 of 80
NFPA 801 F2018 First Draft Meeting Tuesday and Wednesday, May 23-24, 2017
Holiday Inn Charleston Historic Downtown
Charleston, SC
8:00 a.m. to 5:00 p.m. (Eastern Time Zone)
Adobe Connect/Teleconference Option
To Join the Meeting: http://nfpa.adobeconnect.com/nette/
US (Toll Free) 1-866-398-2885
(Additional phone numbers will be listed on the forthcoming Adobe Connect
invitation)
Participant Code: 691847
1. Meeting opening, introduction and attendance
2. Approval of Second Draft Meeting Minutes of March 18, 2014 (Attachment A.
March 18, 2014 Meeting Minutes).
3. Chair's remarks, Bernie Till
4. Staff Liaison update:
a. F2018 Schedule (Attachment B. F2018 Revision Cycle)
b. Committee Membership Update (Attachment C. FIF-AAA
Membership)
c. Standards Process Review (Attachment D. NFPA Process – Quick
Reference Guide)
5. Old/New Business
a. Public Input for NFPA 801 (Attachment E. NFPA 801 - F2018 Public
Input) and development of First Revisions (Attachment D. NFPA
Process Quick Reference Guide)
6. Other business
7. Date/Location of Next Meeting. (Second Draft Meeting between December 1,
2018 and May 17, 2018)
8. Adjournment (May 24)
Page 2 of 80
Attachment A:
March 18, 2014 Meeting
Minutes
Page 3 of 80
Page 1 of 2
FIF AAA
Technical Committee on Fire Protection for NuclearFacilities
Second Draft Meeting for NFPA 804/805/806
Web Meeting, Tuesday, March 18, 2014
1 PM 5 PM ET
Members Present Alternate PresentWilliam Till (chair) Yes Eric JohnsonIvan BolligerJames Bouche Yes Christy MarsoloCraig Christenson James Bisker yesStanford Davis Yes Frank Gruscavage retiredRichard Dible Yes Hunter StevenEdgar Dressler Seth BreitmalerDavid EstrellaDaniel Hubert YesNeal Hara Yes James StreitSteven Joseph yesRobert Kalantari yes Paul OuelletteElizabeth Kleinsorg yes Andrew RatchfordNeal Krantz A.M. Fred LeberChristopher Ksobiech yes Jeffery ErtmanPaul Lain Daniel Frumkin yesJohn Lattner yes Joseph WhittCharles March yesAnca McGee yesRobert Richter yes Michael Fletcher yesClifford SinopoliCleveland Skinner yes Arie T.P. GoWayne Sohlman yes Thomas FurlongDonald Struck yes Daniel FinneganWilliam Sullivan yesRonald Woodfin yes David Hope yes
Page 4 of 80
Page 2 of 2
David Sean O’KellyTzu sheng ShenLeonard HathawayWayne Holmes yesSusan Bershad – staffliaison
yes
1.0 Meeting was called to order at 1 PM by the chair, Bernie Till2.0 Roll call was taken and meeting attendance recorded. (see above for attendance list)3.0 Minutes of the last meeting (April 25, 2013) were approved as written.4.0 NFPA staff liaison, Susan Bershad, gave an update on the new NFPA process and an update
on committee membership.5.0 The committee reviewed and took action on public comment for NFPA 804, 805, and 806.6.0 A motion was made and approved for the staff liaison to update all document references to
current revisions as appropriate for the second draft.7.0 The next meeting of the Technical Committee will be for the first draft of NFPA 801, which
will be in the fall 2017 revision cycle. This meeting will take place in the spring of 2016 at alocation to be determined.
8.0 The meeting was adjourned at 4:00 PM ET.
Page 5 of 80
Attachment B:
F2018 Revision Cycle
Page 6 of 80
Fall 2018 Revision Cycle
Process Stage Process Step Dates for TCDates for TC
with CC
Public Input Stage (First Draft)
Public Input Closing Date* 1/05/2017 1/05/2017
Final Date for TC First Draft Meeting 6/15/2017 3/16/2017
Posting of First Draft and TC Ballot 8/03/2017 4/27/2017
Final date for Receipt of TC First Draft ballot 8/24/2017 5/18/2017
Final date for Receipt of TC First Draft ballot ‐ recirc 8/31/2017 5/25/2017
Posting of First Draft for CC Meeting 6/01/2017
Final date for CC First Draft Meeting 7/13/2017
Posting of First Draft and CC Ballot 8/03/2017
Final date for Receipt of CC First Draft ballot 8/24/2017
Final date for Receipt of CC First Draft ballot ‐ recirc 8/31/2017
Post First Draft Report for Public Comment 9/07/2017 9/07/2017
Comment Stage (Second Draft)
Public Comment Closing Date* 11/16/2017 11/16/2017
Notice Published on Consent Standards (Standards that received no Comments)Note: Date varies and determined via TC ballot.
Appeal Closing Date for Consent Standards (Standards that received no Comments)
Final date for TC Second Draft Meeting 5/17/2018 2/08/2018
Posting of Second Draft and TC Ballot 6/28/2018 3/22/2018
Final date for Receipt of TC Second Draft ballot 7/19/2018 4/12/2018
Final date for receipt of TC Second Draft ballot ‐ recirc 7/26/2018 4/19/2018
Posting of Second Draft for CC Meeting 4/26/2018
Final date for CC Second Draft Meeting 6/07/2018
Posting of Second Draft for CC Ballot 6/28/2018
Final date for Receipt of CC Second Draft ballot 7/19/2018
Final date for Receipt of CC Second Draft ballot ‐ recirc 7/26/2018
Post Second Draft Report for NITMAM Review 8/02/2018 8/02/2018
Tech Session Preparation (&
Issuance)
Notice of Intent to Make a Motion (NITMAM) Closing Date 8/30/2018 8/30/2018
Posting of Certified Amending Motions (CAMs) and Consent Standards 10/11/2018 10/11/2018
Appeal Closing Date for Consent Standards 10/26/2018 10/26/2018
SC Issuance Date for Consent Standards 11/05/2018 11/05/2018
Tech Session Association Meeting for Standards with CAMs 6/20/2019 6/20/2019
Appeals and Issuance
Appeal Closing Date for Standards with CAMs 7/10/2019 7/10/2019
SC Issuance Date for Standards with CAMs 8/07/2019 8/07/2019
TC = Technical Committee or PanelCC = Correlating Committee
As of 1/27/2017
Page 1 of 1NFPA
4/26/2017http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and-standa...
Page 7 of 80
NFPA 801 Revision Cycle KEY DATES
Fall 2018
NFPA 801 F2018 [FIF-AAA]
Important Dates For the Cycle:
Public Input Closing January 5, 2017 (DONE)
Posting of First Draft September 7, 2017
Public Comment Closing November 16, 2017
Posting of Second Draft August 2, 2018
Notice of Intent to Make Motion (NITMAM) August 30, 2018
Issuance of Consent Standard November 5, 2018 (published bit later)
NFPA Annual Meeting with CAMs June 20, 2018
Issuance of Standard – with CAMs August 7, 2019 (published bit later)
Page 8 of 80
Attachment C:
FIF-AAA Committee
Membership
Page 9 of 80
Address List No PhoneFire Protection for Nuclear Facilities FIF-AAA
Eric Nette04/28/2017
FIF-AAA
William B. Till, Jr.
ChairBernie Till & Associates LLC197 Till Hill RoadOrangeburg, SC 29115-8744Alternate: Jason W. Butler
SE 04/17/1998FIF-AAA
Ivan Bolliger
PrincipalCanadian Nuclear Safety Commission280 Slater StreetOttawa, ON K1P 5S9 Canada
E 8/5/2009
FIF-AAA
James Bouche
PrincipalF. E. Moran, Inc.Special Hazard Systems2265 Carlson DriveNorthbrook, IL 60062National Fire Sprinkler AssociationAlternate: Christy J. Marsolo
M 7/23/2008FIF-AAA
Seth S. Breitmaier
PrincipalAmerican Nuclear Insurers95 Glastonbury BoulevardSuite 300Glastonbury, CT 06033-4453Alternate: Charles S. Logan
I 10/18/2011
FIF-AAA
Craig P. Christenson
PrincipalUS Department of EnergyRichland Operations OfficePO Box 450MSIN: H6-60Richland, WA 99352-0450Alternate: James G. Bisker
E 1/14/2005FIF-AAA
David R. Estrela
PrincipalOrr Protection Systems, Inc.38 Blanchard RoadGrafton, MA 01519
IM 10/28/2008
FIF-AAA
Jack A. Gump
PrincipalConsolidated Nuclear Security260 Hill Top DriveLenoir City, TN 37772Alternate: Timmy Dee
SE 7/23/2008FIF-AAA
Neal T. Hara
PrincipalBattelle-Pacific Northwest National LaboratoryPO Box 999, MSIN J2-38Richland, WA 99352Alternate: James R. Streit
U 03/05/2012
FIF-AAA
Daniel J. Hubert
PrincipalAmerex/Janus Fire Systems1102 Rupcich DriveMillennium ParkCrown Point, IN 46307-7542
M 10/28/2008FIF-AAA
Eric R. Johnson
PrincipalSavannah River Nuclear Solutions, LLCSavannah River SiteBldg. 722-5A, Room 108Aiken, SC 29808Alternate: William V. F. Cosey
U 03/07/2013
FIF-AAA
Steven W. Joseph
PrincipalHoneywell/Xtralis, Inc.11467 SW Foothill DrivePortland, OR 97225-5313
M 10/18/2011FIF-AAA
Robert Kalantari
PrincipalEPM, IncorporatedEngineering Planning & Management959 Concord StreetFramingham, MA 01701Alternate: Paul R. Ouellette
SE 1/15/1999
1Page 10 of 80
Address List No PhoneFire Protection for Nuclear Facilities FIF-AAA
Eric Nette04/28/2017
FIF-AAA
Elizabeth A. Kleinsorg
PrincipalJENSEN HUGHES2001 North Main Street, Suite 510Walnut Creek, CA 94596-7239Alternate: Andrew R. Ratchford
SE 10/10/1997FIF-AAA
Neal W. Krantz, Sr.
PrincipalKrantz Systems & Associates, LLC30126 BrettonLivonia, MI 48152Automatic Fire Alarm Association, Inc.Alternate: A. M. Fred Leber
M 1/1/1992
FIF-AAA
Christopher A. Ksobiech
PrincipalWe Energies231 West Michigan, P378Milwaukee, WI 53203
U 7/17/1998FIF-AAA
John D. Lattner
PrincipalSouthern Nuclear Company40 Inverness Center ParkwayBirmingham, AL 35201
U 8/9/2011
FIF-AAA
Charles J. March
PrincipalDefense Nuclear Facilities Safety Board625 Indiana AvenueWashington, DC 20004
E 10/20/2010FIF-AAA
Anca McGee
PrincipalOntario Power Generation10 Guildwood Parkway, Suite 1229Toronto, ON M1E 5B5 Canada
U 8/9/2011
FIF-AAA
Robert K. Richter, Jr.
PrincipalSouthern California Edison Company17 Firenze StreetLaguna Niguel, CA 92677Nuclear Energy InstituteAlternate: Michael Fletcher
U 4/15/2004FIF-AAA
Cleveland B. Skinker
PrincipalBechtel Infrastructure and Power Corporation12011 Sunset Hills RoadReston, VA 20190Alternate: Arie T. P. Go
SE 1/15/2004
FIF-AAA
Wayne R. Sohlman
PrincipalNuclear Electric Insurance Ltd.1201 Market Street, Suite 1100Wilmington, DE 19801Alternate: Thomas K. Furlong
I 1/1/1993FIF-AAA
Donald Struck
PrincipalSiemens Fire Safety8 Fernwood RoadFlorham Park, NJ 07932-1906National Electrical Manufacturers AssociationAlternate: Daniel P. Finnegan
M 8/5/2009
FIF-AAA
William M. Sullivan
PrincipalContingency Management Associates, Inc.49 Wawela Park RoadWebster, MA 01570
SE 4/17/1998FIF-AAA
Carl N. Sweely
PrincipalAREVA Inc.117 S. Summit AvenueCharlotte, NC 28208
U 04/05/2016
FIF-AAA
Jeffrey S. Tubbs
PrincipalArup60 State StreetBoston, MA 02109
SE 12/08/2015FIF-AAA
Ronald W. Woodfin
PrincipalTetraTek, Inc. Fire Safety Technologies/AESPO Box 1094Brighton, CO 80601Alternate: David M. Hope
SE 1/15/2004
2Page 11 of 80
Address List No PhoneFire Protection for Nuclear Facilities FIF-AAA
Eric Nette04/28/2017
FIF-AAA
Daniel M. Frumkin
Voting AlternateUS Nuclear Regulatory Commission11555 Rockville Pike, MS 011A11Rockville, MD 20852
E 11/2/2006FIF-AAA
James G. Bisker
AlternateUS Department of EnergyNuclear Facility Safety Programs, HS-321000 Independence Avenue, SWWashington, DC 20585-1290Principal: Craig P. Christenson
E 8/2/2010
FIF-AAA
Jason W. Butler
AlternateBernie Till and Associates LLCFire Protection Engineer2520 Beaver Creek LaneAiken, SC 29803Principal: William B. Till, Jr.
U 08/03/2016FIF-AAA
William V. F. Cosey
AlternateSavannah River Nuclear Solutions, LLC118 Beauregard LaneAiken, SC 29803Principal: Eric R. Johnson
U 12/08/2015
FIF-AAA
Timmy Dee
AlternateConsolidated Nuclear Security Y-12, LLC540 Annandale RoadKnoxville, TN 37934Principal: Jack A. Gump
SE 04/05/2016FIF-AAA
Daniel P. Finnegan
AlternateSiemens Industry, Inc.Building Technologies DivisionFire & Security2953 Exeter CourtWest Dundee, IL 60118-1724National Electrical Manufacturers AssociationPrincipal: Donald Struck
M 10/18/2011
FIF-AAA
Michael Fletcher
AlternateAmeren Corporation912 Hickory Hill DriveColumbia, MO 65203Nuclear Energy InstitutePrincipal: Robert K. Richter, Jr.
U 10/29/2012FIF-AAA
Thomas K. Furlong
AlternateNuclear Service Organization1201 North Market Street, Suite 1100Wilmington, DE 19801Principal: Wayne R. Sohlman
I 1/12/2000
FIF-AAA
Arie T. P. Go
AlternateBechtel National, Inc.50 Beale StreetSan Francisco, CA 94105Principal: Cleveland B. Skinker
SE 10/1/1993FIF-AAA
David M. Hope
AlternateTetraTek Inc. Fire Safety Technologies204 Masthead DriveClinton, TN 37716Principal: Ronald W. Woodfin
SE 4/15/2004
FIF-AAA
A. M. Fred Leber
AlternateLRI Engineering, Inc.170 university Avenue, 3rd FloorToronto, ON M5H3B3Automatic Fire Alarm Association, Inc.Principal: Neal W. Krantz, Sr.
M 10/20/2010FIF-AAA
Charles S. Logan
AlternateAmerican Nuclear InsurersSenior Engineer / C.F.P.S.95 Glastonbury Boulevard, Suite 300Glastonbury, CT 06033-4412Principal: Seth S. Breitmaier
I 08/17/2015
3Page 12 of 80
Address List No PhoneFire Protection for Nuclear Facilities FIF-AAA
Eric Nette04/28/2017
FIF-AAA
Christy J. Marsolo
AlternateTyco/SimplexGrinnell13500 Darice Parkway, Suite AStrongville, OH 44149-3840National Fire Sprinkler AssociationPrincipal: James Bouche
M 07/29/2013FIF-AAA
Paul R. Ouellette
AlternateEPM, IncorporatedEngineering Planning & Management959 Concord StreetFramingham, MA 01701Principal: Robert Kalantari
SE 7/19/2002
FIF-AAA
Andrew R. Ratchford
AlternateJENSEN HUGHES2001 North Main Street, Suite 510Walnut Creek, CA 94596JENSEN HUGHESPrincipal: Elizabeth A. Kleinsorg
SE 08/03/2016FIF-AAA
James R. Streit
AlternateLos Alamos National LaboratoryPO Box 1663, Mail Stop K493Los Alamos, NM 87545Principal: Neal T. Hara
U 1/16/1998
FIF-AAA
Tzu-sheng Shen
Nonvoting MemberCentral Police University56 Shu-Jen RoadTa-kan-chun, Kuei-sanTaoyuan, 333 Taiwan
SE 7/29/2005FIF-AAA
Leonard R. Hathaway
Member Emeritus1568 Hartsville TrailThe Villages, FL 32162
I 1/1/1976
FIF-AAA
Wayne D. Holmes
Member EmeritusHSB Professional Loss Control508 Parkview DriveBurlington, NC 27215-5036
I 1/1/1980FIF-AAA
Eric Nette
Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471
04/16/2014
4Page 13 of 80
Attachment D:
NFPA Process – Quick
Reference Guide
Page 14 of 80
New Process – Quick Reference Guide For additional information on the Regulations visit: www.nfpa.org/Regs
There are only three actions a TC can take at the First Draft (ROP)
meeting: 1. Resolve a Public Input (no change to the document) 2. Create a First Revision (change to the document) 3. Create Committee Input
Resolve Public Input (no change to the document)
TC must provide a response (Committee Statement/CS) to ALL Public Input (proposal).
CS for not doing what is suggested
Sample Motion: “I make a motion to resolve PI#_ with the following committee statement__.” Approval by meeting vote (simple majority). Not subject to Ballot.
Create a First Revision (change to the document)
TC must create a First Revision (FR) for each change they wish to make to the document, either using Public Input for the basis of the change or not using a Public Input for the basis. One or more Public Input can be considered for the FR.
All Public Input requires a response
TC can use a Public Input for basis i. Sample Motion: “I make a motion to revise section __ using PI#_ as the
basis for change.” Approval by meeting vote (simple majority) and final approval through ballot.
TC develops revision without a Public Input for basis i. Sample Motion: “I make a motion to revise section __ as follows___.”
Approval by meeting vote (simple majority) and final approval through ballot.
First Revisions require a committee statement
Committee Input
TC may create a Committee Input (CI). This replaces the old system “rejected” Committee Proposals. CIs will get printed in the report but will not be balloted or shown as a change in the draft. CIs are used to solicit public comments and/or as a placeholder for the comment stage.
i. Sample Motion: “I make a motion to create a CI with a proposed revision to section__ as follows___.” Approval by meeting vote (simple majority). Not subject to ballot.
Requires a committee statement to explain the intent of making a CI.
Page 15 of 80
Comparison to Previous Process:
PREVIOUS ACTIONS CURRENT PROCESS ACTIONS SAMPLE MOTION
Accept or any variation of Accept
(APA, APR, APP) on a public
proposal
1) Committee generates a First
Revision and Substantiation (CS)
for change
2) Committee provides response (CS)
to each PI that is associated with the
revision
1) “I make a motion to revise section __ using PI#_ as the basis for change.”
2) “ I make a motion to resolve PIs#_ through ## with the following statement__”
Rejected Public Proposal Committee provides response (CS)
to PI
“I make a motion to resolve
PI#_ with the following
committee statement__.”
Accepted Committee Proposal Committee generates a First Revision
and Substantiation (CS) for change
“I make a motion to revise
section __ as follows___.”
Committee generates a
statement for reason for change.
Rejected Committee Proposal Committee generates a Committee
Input (CI) and reason (CS) for
proposed change
“I make a motion to create a CI
with a proposed revision to
section__ as follows___.”
Committee generates a
statement for reason for CI.
Notes:
1) All meeting actions require a favorable vote of a simple majority of the members present. 2) All First Revisions will be contained in the ballot and will require a 2/3 affirmative vote to
confirm the meeting action. 3) Only the First Revisions will be balloted. PIs and CIs will be contained in the report but will
not be balloted. 4) Comments may be submitted on all PIs, FRs and CIs
Page 16 of 80
Term Comparison between Current and Old:
CURRENT TERM OLD TERM
Input Stage ROP Stage
Public Input (PI) Proposal
First Draft Meeting ROP Meeting
Committee Input Committee Proposal that Fail
Ballot
Committee Statement
(CS) Committee Statement
First Revision (FR) Committee Proposal or Accepted
Public Proposal
First Draft Report ROP
First Draft ROP Draft
Comment Stage ROC Stage
Public Comment Public Comment
Second Draft Meeting ROC Meeting
Committee Comment Committee Comment that Fail
Ballot
Committee Action Committee Action
Second Revision Committee Comment or Accepted
Public Comment
Second Draft Report ROC
Second Draft ROC Draft
Note: The highlighted terms are the ones that will be most applicable at the First Draft Meeting.
Page 17 of 80
Attachment E:
NFPA 801 – F2018 Public
Input
Page 18 of 80
Public Input No. 2-NFPA 801-2015 [ Chapter 2 ]
Chapter 2 Referenced Publications
2.1 General.
The documents or portions thereof listed in this chapter are referenced within this standard andshall be considered part of the requirements of this document.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 62 1/20/2017 2:04 PM
Page 19 of 80
2.2 NFPA Publications.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 62 1/20/2017 2:04 PM
Page 20 of 80
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.
NFPA 10, Standard for Portable Fire Extinguishers, 2013 edition.
NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 edition.
NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 edition.
NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 edition.
NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 edition.
NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 edition.
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 edition.
NFPA 16, Standard for the Installation of Foam-Water Sprinkler and Foam-Water SpraySystems, 2011 edition.
NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2013 edition.
NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2013 edition.
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 edition.
NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 edition.
NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances,2013 edition.
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based FireProtection Systems, 2014 edition.
NFPA 30, Flammable and Combustible Liquids Code, 2012 edition.
NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.
NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2014edition.
NFPA 54, National Fuel Gas Code, 2012 edition.
NFPA 55, Compressed Gases and Cryogenic Fluids Code, 2013 edition.
NFPA 58, Liquefied Petroleum Gas Code, 2014 edition.
NFPA 70® , National Electrical Code®, 2014 edition.
NFPA 72® , National Fire Alarm and Signaling Code, 2013 edition.
NFPA 75, Standard for the Fire Protection of Information Technology Equipment, 2013 edition.
NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2013 edition.
NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment,2009 edition.
NFPA 86, Standard for Ovens and Furnaces, 2011 edition.
NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012edition.
NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems,2012 edition.
NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, andNoncombustible Particulate Solids, 2010 edition.
NFPA 101® , Life Safety Code®, 2012 edition.
NFPA 115, Standard for Laser Fire Protection, 2012 edition.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 62 1/20/2017 2:04 PM
Page 21 of 80
NFPA 204, Standard for Smoke and Heat Venting, 2012 edition.
NFPA 220, Standard on Types of Building Construction, 2012 edition.
NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations,2013 edition.
NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using aRadiant Heat Energy Source, 2011 edition.
NFPA 400, Hazardous Materials Code, 2013 edition.
NFPA 484, Standard for Combustible Metals, 2012 edition.
NFPA 600, Standard on Industrial Fire Brigades, 2010 edition.
NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 2010edition.
NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 edition.
NFPA 780, Standard for the Installation of Lightning Protection Systems, 2014 edition.
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric GeneratingPlants, 2010 edition.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor ElectricGenerating Plants, 2010 edition.
NFPA 806, Performance-Based Standard for Fire Protection for Advanced Nuclear ReactorElectric Generating Plants Change Process, 2010 edition.
NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, 2013edition.
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 edition.
2.3 Other Publications.
2.3.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials, 2012 2015a .
ASTM E 648 E648 , Standard Test Method for Critical Radiant Flux of Floor-Covering SystemsUsing a Radiant Heat Energy Source, 2010 2015 .
ASTM E 814 E814 , Standard Test Method for Fire Tests of Penetration Firestop Systems,2011a 2013 a .
2.3.2 UL Publications.
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.
ANSI/ UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008,revised 2010 2013 .
ANSI/ UL 900, Standard for Air Filter Units, 2004, revised 2009 2015 .
ANSI/ UL 1479, Fire Tests of Through-Penetration Fire Stops, 2003, revised 2010 2015 .
2.3.3 Other Publications.
Merriam-Webster's Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA,2003.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 62 1/20/2017 2:04 PM
Page 22 of 80
2.4 References for Extracts in Mandatory Sections.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor ElectricGenerating Plants, 2010 edition.
NFPA 850, Recommended Practice for Fire Protection for Electric Generating Plants and HighVoltage Direct Current Converter Stations, 2010 edition.
NFPA 5000® , Building Construction and Safety Code®, 2012 edition.
Statement of Problem and Substantiation for Public Input
Referenced current editions.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 3-NFPA 801-2015 [Chapter D]
Submitter Information Verification
Submitter Full Name: Aaron Adamczyk
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Sun Dec 06 21:18:17 EST 2015
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5 of 62 1/20/2017 2:04 PM
Page 23 of 80
Public Input No. 59-NFPA 801-2017 [ Section No. 2.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 62 1/20/2017 2:04 PM
Page 24 of 80
2.2 NFPA Publications.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 62 1/20/2017 2:04 PM
Page 25 of 80
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.
NFPA 10, Standard for Portable Fire Extinguishers, 2013 edition.
NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 edition.
NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 edition.
NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 edition.
NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 edition.
NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 edition.
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 edition.
NFPA 16, Standard for the Installation of Foam-Water Sprinkler and Foam-Water SpraySystems, 2011 edition.
NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2013 edition.
NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2013 edition.
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 edition.
NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 edition.
NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances,2013 edition.
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based FireProtection Systems, 2014 edition.
NFPA 30, Flammable and Combustible Liquids Code, 2012 edition.
NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.
NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2014edition.
NFPA 54, National Fuel Gas Code, 2012 edition.
NFPA 55, Compressed Gases and Cryogenic Fluids Code, 2013 edition.
NFPA 58, Liquefied Petroleum Gas Code, 2014 edition.
NFPA 70® , National Electrical Code®, 2014 edition.
NFPA 72® , National Fire Alarm and Signaling Code, 2013 edition.
NFPA 75, Standard for the Fire Protection of Information Technology Equipment, 2013 edition.
NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2013 edition.
NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment,2009 edition.
NFPA 86, Standard for Ovens and Furnaces, 2011 edition.
NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012edition.
NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems,2012 edition.
NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, andNoncombustible Particulate Solids, 2010 edition.
NFPA 101® , Life Safety Code®, 2012 edition.
NFPA 115, Standard for Laser Fire Protection, 2012 edition.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
8 of 62 1/20/2017 2:04 PM
Page 26 of 80
NFPA 204, Standard for Smoke and Heat Venting, 2012 edition.
NFPA 220, Standard on Types of Building Construction, 2012 edition.
NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations,2013 edition.
NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using aRadiant Heat Energy Source, 2011 edition.
NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and CeilingInterior Finish to Room Fire Growth , 2015 edition
NFPA 400, Hazardous Materials Code, 2013 edition.
NFPA 484, Standard for Combustible Metals, 2012 edition.
NFPA 600, Standard on Industrial Fire Brigades, 2010 edition.
NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 2010edition.
NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 edition.
NFPA 780, Standard for the Installation of Lightning Protection Systems, 2014 edition.
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric GeneratingPlants, 2010 edition.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor ElectricGenerating Plants, 2010 edition.
NFPA 806, Performance-Based Standard for Fire Protection for Advanced Nuclear ReactorElectric Generating Plants Change Process, 2010 edition.
NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, 2013edition.
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 edition.
Statement of Problem and Substantiation for Public Input
adds standard added to section 5.8.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 57-NFPA 801-2017 [Section No. 5.8]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:39:56 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
9 of 62 1/20/2017 2:04 PM
Page 27 of 80
Public Input No. 4-NFPA 801-2016 [ Section No. 2.3.1 ]
2.3.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials,2012 2015 .
ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Usinga Radiant Heat Energy Source, 2010 2015 .
ASTM E 814, Standard Test Method for Fire Tests of Penetration Firestop Systems, 2011a2013 .
Statement of Problem and Substantiation for Public Input
Date updates.
Submitter Information Verification
Submitter Full Name: Timothy Earl
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jan 05 10:04:27 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10 of 62 1/20/2017 2:04 PM
Page 28 of 80
Public Input No. 55-NFPA 801-2017 [ Section No. 2.3.1 ]
2.3.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials, 2012 2016 .
ASTM E 648 E648 , Standard Test Method for Critical Radiant Flux of Floor-Covering SystemsUsing a Radiant Heat Energy Source, 2010 2015 e1 .
ASTM E 814 E814 , Standard Test Method for Fire Tests of Penetration Firestop Systems,2011a 2013a .
Statement of Problem and Substantiation for Public Input
updates
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:21:51 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
11 of 62 1/20/2017 2:04 PM
Page 29 of 80
Public Input No. 37-NFPA 801-2017 [ Section No. 2.3.2 ]
2.3.2 UL Publications.
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.
ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008,revised 2010 2013 .
ANSI/UL 900, Standard for Air Filter Units, 2004, revised 2009 2015 .
ANSI/UL 1479, Fire Tests of Through-Penetration Fire Stops, 2003, revised 2010 2015 .
Statement of Problem and Substantiation for Public Input
Update revised editions
Submitter Information Verification
Submitter Full Name: Kelly Nicolello
Organization: UL LLC
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jan 03 12:04:48 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
12 of 62 1/20/2017 2:04 PM
Page 30 of 80
Public Input No. 6-NFPA 801-2016 [ Section No. 2.3.2 ]
2.3.2 UL Publications.
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.
ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008,revised 2010 2013 .
ANSI/UL 900, Standard for Air Filter Units, 2004, revised 2009 2015 .
ANSI/UL 1479, Fire Tests of Through-Penetration Fire Stops, 2003, revised 2010 2015 .
Statement of Problem and Substantiation for Public Input
This proposal updates the UL Standards to the current referenced edition.
Submitter Information Verification
Submitter Full Name: Ronald Farr
Organization: UL LLC
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jun 28 10:26:55 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
13 of 62 1/20/2017 2:04 PM
Page 31 of 80
Public Input No. 21-NFPA 801-2016 [ New Section after 3.3.27 ]
3.3.28* Qualified Fire Protection Engineer.
A fire protection engineer with a combination of one or more of the following minimum education,experiences, or professional registration/license, plus three years of responsible in charge experience inthe field of fire protection specific to the types of facilities within the scope of this standard: 1) A graduateof an approved fire protection engineering curriculum, or 2) Be registered or licensed by a state or localauthority in fire protection engineering, or 3) Demonstrate fire protection engineering knowledge andexperiences and provide evidence of qualifications acceptable to the authority having jurisdiction.
Statement of Problem and Substantiation for Public Input
A fire hazard analysis is required by Section 4.2.6 to be prepared or under the supervision of a qualified fire protection engineer. However, the standard does not define what a qualified fire protection engineer is and the result could be of disastrous consequences when considering the seriousness of fire involving facilities handing radioactive materials. Defining what constitutes a qualified fire protection engineer will result in safer accomplishment of the standards objectives when a qualified fire protection engineer is specified by the standard.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 14:49:24 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
14 of 62 1/20/2017 2:04 PM
Page 32 of 80
Public Input No. 22-NFPA 801-2016 [ Sections 3.3.28, 3.3.29, 3.3.30 ]
Sections 3.3.28, 3.3.29, 3.3.30
3.3. 28 29 * Radiation.
The emission and propagation of energy through matter or space by means of electromagneticdisturbances that display both wave-like and particle-like behavior.
3.3. 28 29 .1 Nuclear Radiation.
The emission from atomic nuclei in various nuclear reactions including alpha, beta, and gammaradiation and neutrons.
3.3. 29 30 Radiation Area.
An area, accessible to personnel, in which radiation exists, originating in whole or in part withinradioactive material, at such levels that a major portion of the body could receive a dose in
excess of 5 millirems (5 × 10-5 sievert) during any single hour or a dose in excess of
100 millirems (100 × 10-5 sievert) during any five consecutive days.
3.3. 30 31 Radioactivity.
The spontaneous decay or disintegration of an unstable atomic nucleus accompanied by theemission of radiation.
Statement of Problem and Substantiation for Public Input
Revision of paragraph numbers for addition of new 3.3.28 definition of Qualified Fire Protection Engineer
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 14:52:23 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
15 of 62 1/20/2017 2:04 PM
Page 33 of 80
Public Input No. 35-NFPA 801-2016 [ Section No. 4.2 ]
4.2 * Fire Hazards Analysis.
(See also Annex B.)
4.2.1
A documented fire hazards analysis shall be initiated at the beginning of the design process orwhen configuration and other facility changes are made to ensure that the to ascertainwhether the fire prevention and fire protection requirements of this standard have beenevaluated acheived .
4.2.1.1
The fire hazards analysis shall be updated as necessary to reflect facility modifications,changes in fire hazards, and operating experience.
4.2.1.2
The completed fire hazards analysis shall be reviewed at least every three years and modified,when necessary, in order to ensure the analysis remains current.
4.2. 1.3
The fire hazard analysis shall assess the hazards from fire (direct flame impingement, hot gases, smokemitigation, firefighting water damage, fire exposure to structural members, etc.) in relationship toexisting or proposed fire safety features to ensure that the facility can be safely controlled and stabilizedduring and after a fire.
4. 2 .2
The evaluation shall The fire hazard analysis shall consider the facility's specific design, layout,and anticipated operating needs.
4.2.3
The evaluation fire hazard analysis shall consider acceptable means for separation or controlof hazards, the control or elimination of ignition sources, and the suppression of fires.
4.2.4 *
For existing facilities, a documented fire hazards analysis shall be performed for all areas of thefacility.
4.2.5
The evaluation shall The fire hazard analysis shall consider the storage and use of radioactiveand other hazardous materials, since their release under fire or explosion conditions can resultin a severe hazard.
4.2.6 *
The fire hazards analysis shall be prepared by or under the supervision of a qualified fireprotection engineer.
Statement of Problem and Substantiation for Public Input
Changes proposed to clarify to why a fire hazard analysis is required to determine whether or not fire prevention and protection requirements are being achieved in relationship to the hazards and existing
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
16 of 62 1/20/2017 2:04 PM
Page 34 of 80
or proposed fire safety features
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:57:43 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
17 of 62 1/20/2017 2:04 PM
Page 35 of 80
Public Input No. 26-NFPA 801-2016 [ Section No. 4.2.6 ]
4.2.6 *
The fire hazards analysis shall be prepared by or under the supervision of a qualified fireprotection engineer.
Statement of Problem and Substantiation for Public Input
Deletion due addition of definition from comments in Public Input No. 21-NFPA 801-2016 and No. 23-NFPA 801-2016
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:06:37 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
18 of 62 1/20/2017 2:04 PM
Page 36 of 80
Public Input No. 63-NFPA 801-2017 [ Section No. 5.5 [Excluding any
Sub-Sections] ]
Buildings in which radioactive materials are to be used, handled, or stored shall be fire-resistantor noncombustible Type I or Type II construction in accordance with NFPA 220, Standard onTypes of Building Construction, Type I or Type II construction .
Statement of Problem and Substantiation for Public Input
NFPA 220 does not contain requirements for "fire resistant" construction or "noncombustible: construction. The criteria are fir Type I through Type V construction and include requirements for the materials of construction associated with them. Fire resistant construction is no longer a valid term.
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 15:41:41 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
19 of 62 1/20/2017 2:04 PM
Page 37 of 80
Public Input No. 20-NFPA 801-2016 [ Section No. 5.5.1 ]
5.5.1
Limited-combustible construction shall not be permitted for structural elements .
Statement of Problem and Substantiation for Public Input
Sheetrock and roofing materials (for example an FM approved roof) are of limited combustibility and would be prohibited by the current section 5.5.1. The intent of this requirement should prevent construction of wood platforms and wood roof structures (trusses and girders) in radiological facilities. NFPA 220 would allow both in type I and II facilities.
Submitter Information Verification
Submitter Full Name: Neal Hara
Organization: Battelle-Pacific Northwest National Laboratory
Street Address:
City:
State:
Zip:
Submittal Date: Wed Dec 14 14:51:10 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
20 of 62 1/20/2017 2:04 PM
Page 38 of 80
Public Input No. 57-NFPA 801-2017 [ Section No. 5.8 ]
5.8* Interior Finish.
5.8.1 *
Interior wall and ceiling finish in areas processing or storing radioactive materials shall have aflame spread index of not more than 25 and a smoke development index of not more than 450,in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials or shall coimply with 5 .8.2.
5.8.2
Interior wall and finish shall comply with all of the following when tested using the test protocolof NFPA 286:
(1) During the 40 kW exposure, flames shall not spread to the ceiling.
(2) The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
(3) Flashover, as described in NFPA 286, shall not occur.
(4) The peak heat release rate throughout the test shall not exceed 800 kW.
(5) The total smoke released throughout the test shall not exceed 10,764 ft 2 (1000 m 2 ).
5.8.3
Interior floor finish in areas processing or storing radioactive materials shall be characterized by
a critical radiant flux not less than 0.45 W/cm2 in accordance with NFPA 253, Standard Methodof Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat EnergySource, or ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor-CoveringSystems Using a Radiant Heat Energy Source.
Statement of Problem and Substantiation for Public Input
The revision provides an alternate method for approval of interior wall and ceiling materials. The alternate method (NFPA 286) is a room-corner fire test and has been shown to be able to adequately assess the fire performance of many more interior finish materials than ASTM E84, the Steiner tunnel test. When interior finish materials are appropriately tested using ASTM E84, the results of both tests correlate well in terms of pass or fail criteria. The proposed new annex note explains this also.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 58-NFPA 801-2017 [New Section after A.5.8]
Public Input No. 59-NFPA 801-2017 [Section No. 2.2]
Submitter Information Verification
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
21 of 62 1/20/2017 2:04 PM
Page 39 of 80
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:27:25 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
22 of 62 1/20/2017 2:04 PM
Page 40 of 80
Public Input No. 14-NFPA 801-2016 [ Chapter 6 ]
Chapter 6 General Fire Protection Systems and Equipment
6.1 * General Considerations.
6.1.1 *
Automatic sprinkler protection shall be provided unless the fire hazards analysis in Section 4.2dictates otherwise.
6.1.2 *
As determined by the fire hazards analysis, special hazards shall be provided with additionalfixed fire protection systems.
6.1.3 *
For locations where fissile materials might be present and could create a potential criticalityhazard, combustible materials shall be excluded.
6.1.4
If combustible materials are unavoidably present in a quantity sufficient to constitute a firehazard, water or another suitable extinguishing agent shall be provided for fire-fightingpurposes.
6.1.5
Fissile materials shall be arranged such that neutron moderation and reflection by water shallnot present a criticality hazard.
6.2 Water Supply.
6.2.1 * General.
6.2.1.1
The water supply for the permanent fire protection installation shall be based on the largestfixed fire suppression system(s) demand, including the hose-stream allowance, in accordancewith NFPA 13, Standard for the Installation of Sprinkler Systems.
6.2.1.2
For common service water/fire protection systems, the maximum anticipated service waterdemand shall be added to the fire protection demand.
6.2.1.3
The fire protection water supply system shall be arranged in conformance with NFPA 20,Standard for the Installation of Stationary Pumps for Fire Protection; NFPA 22, Standard forWater Tanks for Private Fire Protection; and NFPA 24, Standard for the Installation of PrivateFire Service Mains and Their Appurtenances, as applicable.
6.2.2 Water Tanks and Pumps.
Where an auxiliary supply is required by the fire hazards analysis, each supply shall be capableof meeting the requirements of 6.2.1.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
23 of 62 1/20/2017 2:04 PM
Page 41 of 80
6.2.2.1
Where multiple fire pumps are required, the pumps shall not be subject to a common failure,electrical or mechanical, and shall have capacity to meet the fire flow requirements determinedby 6.2.1 with the largest pump out of service.
6.2.2.2 *
Fire pumps shall be automatic-starting with manual shutdown.
6.2.2.3
The manual shutdown shall be only at the pump controllers.
6.2.2.4 *
If tanks are for dual-purpose use, they shall be arranged to provide the water supplyrequirements as determined by 6.2.1 for fire protection use only.
6.2.2.5 *
Where water tanks are used, they shall be capable of being replenished for fire protectionneeds in an 8-hour period.
6.2.2.5.1
The tank refilling method shall be automatic.
6.2.3 Multiple Water Supplies.
If multiple water supplies are used, each water supply shall be connected to the fire main by aseparate connection that is arranged and valve-controlled to minimize the possibility of multiplesupplies being impaired simultaneously.
6.3 * Valve Supervision.
All fire protection water system control valves shall be monitored under a periodic inspectionprogram (see Chapter 4) and shall be supervised in accordance with NFPA 13, Standard for theInstallation of Sprinkler Systems; NFPA 16, Standard for the Installation of Foam-WaterSprinkler and Foam-Water Spray Systems; NFPA 24, Standard for the Installation of PrivateFire Service Mains and Their Appurtenances; NFPA 25, Standard for the Inspection, Testing,and Maintenance of Water-Based Fire Protection Systems; or NFPA 72, National Fire Alarmand Signaling Code, as applicable.
6.4 Supply Mains and Hydrants.
6.4.1
Supply mains and fire hydrants as required by the fire hazards analysis shall be installed on thefacility site in accordance with NFPA 24, Standard for the Installation of Private Fire ServiceMains and Their Appurtenances.
6.4.2
Where required by the fire hazards analysis, the supply mains shall be looped and sized tosupply the flow requirements as determined by 6.2.1.
6.5 Standpipe and Hose Systems.
6.5.1
Standpipe and hose systems as required by the fire hazards analysis shall be installed inaccordance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems.
6.5.2
Spray nozzles having shutoff capability and listed for use on electrical equipment shall beprovided on hose located in areas near energized electrical equipment.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
24 of 62 1/20/2017 2:04 PM
Page 42 of 80
6.6 Portable Fire Extinguishers.
Fire extinguishers shall be installed in accordance with NFPA 10, Standard for Portable FireExtinguishers.
6.7 Fire Suppression Systems and Equipment.
6.7.1
Fire suppression systems and equipment shall be provided in all areas of a facility asdetermined by the fire hazards analysis.
6.7.2
Where fire suppression systems are required, the design, installation, maintenance, and testingof such systems shall be in accordance with the following NFPA standards, as applicable:NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam; NFPA 12, Standard onCarbon Dioxide Extinguishing Systems; NFPA 12A, Standard on Halon 1301 Fire ExtinguishingSystems; NFPA 13, Standard for the Installation of Sprinkler Systems; NFPA 14, Standard forthe Installation of Standpipe and Hose Systems; NFPA 15, Standard for Water Spray FixedSystems for Fire Protection; NFPA 16, Standard for the Installation of Foam-Water Sprinklerand Foam-Water Spray Systems; NFPA 17, Standard for Dry Chemical Extinguishing Systems;NFPA 17A, Standard for Wet Chemical Extinguishing Systems; NFPA 25, Standard for theInspection, Testing, and Maintenance of Water-Based Fire Protection Systems; NFPA 750,Standard on Water Mist Fire Protection Systems; and NFPA 2001, Standard on Clean AgentFire Extinguishing Systems.
6.7.3
The selection of the extinguishing agent system shall be based upon the following:
(1) Type of hazard
(2) Effect of agent discharge on equipment
(3) Health hazards
(4) Cleanup after agent discharge
(5) Effectiveness of agent in suppressing fire
(6) Cost of agent, including life-cycle costs
(7) Availability of agent
(8) Criticality safety
(9) Environmental impact
6.8 Fire Alarm Systems.
6.8.1
Fire detection and automatic fixed fire suppression systems shall be equipped with local audibleand visual notification appliances with annunciation on the main fire control panel or at anotherconstantly attended location in accordance with NFPA 72, National Fire Alarm and SignalingCode.
6.8.2 *
Where automatic fire detectors are required, the design, installation, testing, inspection, andmaintenance shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code.
6.8.3
Means shall be provided to allow a person observing a fire at any location in the plant tocommunicate to a constantly attended location.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
25 of 62 1/20/2017 2:04 PM
Page 43 of 80
6.8.4
Means shall be provided to notify the following of any fire emergency in such a way as to allowthem to determine a course of action:
(1) Affected site population
(2) Members of the site fire department, industrial fire brigade, and other groups supportingfire emergency response
(3) Off-site fire emergency response agencies
6.9 * The safety and seismic classification of fire protection systems
Statement of Problem and Substantiation for Public Input
Small imptrovements involving applied scope and grammar for better understanding, when being read by not fluent in english engineers.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: Fennovoima
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 09:19:40 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
26 of 62 1/20/2017 2:04 PM
Page 44 of 80
Public Input No. 9-NFPA 801-2016 [ Section No. 6.1.2 ]
6.1.2 *
As determined by the fire hazards analysis, special hazards shall be provided with additionalfixed local fixed fire protection systems.
Statement of Problem and Substantiation for Public Input
It is just a case I am having right now with outside EU supplier for fire protection of NPP inside EU, that has its own codes, standards and practice. I recommend using NFPA, which are the highest in details source of requirements, but yet not precise enough to persuade specialists who know better. Fixed fire protection systems are not eaual to local fixed fire extinguishing, which does not have to be connected to supply network.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: Fennovoima
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 08:53:02 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
27 of 62 1/20/2017 2:04 PM
Page 45 of 80
Public Input No. 8-NFPA 801-2016 [ Section No. 6.1.4 ]
6.1.4
If combustible materials are unavoidably present in a quantity sufficient to constitute a firehazard, water or clean agent, spray water or another suitable extinguishing agent shall beprovided for fire-fighting purposes.
Statement of Problem and Substantiation for Public Input
At present times the water is not recommended agent for any radioactive related areas.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: [ Fennovoima ]
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 08:46:50 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
28 of 62 1/20/2017 2:04 PM
Page 46 of 80
Public Input No. 10-NFPA 801-2016 [ Section No. 6.1.5 ]
6.1.5
Fissile materials shall be arranged such that in such order that neutron moderation andreflection by water shall or any other extinguishing agent shall not present a criticality hazard.
Statement of Problem and Substantiation for Public Input
The improvement toutches the case of fire protection market rapid changing - and now since a few years it turns out that the fog systems will be in charge in some areas insead of water. For international projects outside US with engineers like me-using NFPA as an important source- it is crucial during negotiations with technology supplier to demand the best technology available. I can sell my knowledge and demand the solutions but I always need to support it with some precise number inside a code or standard.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: Fennovoima
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 08:53:58 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
29 of 62 1/20/2017 2:04 PM
Page 47 of 80
Public Input No. 11-NFPA 801-2016 [ Section No. 6.2.2.1 ]
6.2.2.1
Where multiple fire pumps are required, the pumps shall not be subject to a common failure,electrical or mechanical, and shall have enough capacity to meet the fire flow requirementsdetermined by 6.2.1 with the largest pump out of service.
Statement of Problem and Substantiation for Public Input
This input is of no particular importance, just requires the wording typically liked/accepted by the suppliers-a minimum neccesary for good operation. I think it will (from human psycho point of view) work better than overall requirement.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 09:00:07 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
30 of 62 1/20/2017 2:04 PM
Page 48 of 80
Public Input No. 16-NFPA 801-2016 [ Section No. 6.4.2 ]
6.4.2
Where required by Regardless the requirements of fire hazards analysis, the supply mainsshall be looped and sized to supply the flow requirements as determined by 6.2.1.
Statement of Problem and Substantiation for Public Input
The form of fiire mains underground system for either nuclear or any non nuclear power plants is always looped/ring type and regardless any probabilistic or deterministic accident analysis results-fire water mains in a ring form is a must.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: [ Fennovoima ]
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 09:28:36 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
31 of 62 1/20/2017 2:04 PM
Page 49 of 80
Public Input No. 17-NFPA 801-2016 [ Section No. 6.7.1 ]
6.7.1
Fire suppression systems and equipment shall be provided in all provided to cover all areas ofa facility as determined by the fire hazards analysis.
Statement of Problem and Substantiation for Public Input
It is very important to say that all areas of the plant must be covered by manual fire fighting. In potenttial international supplier point of view a current 801 standard wording means to cover with some fire means all types of areas of the plant.For design engineers who know how it should be-it means to cover all areas of the plant with water coming from manual fire fighting (respective hydrant hose distance with water streems/hoses lenght overlapping) without any exceptions.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: [ Fennovoima ]
Affilliation: BAT
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 09:30:42 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
32 of 62 1/20/2017 2:04 PM
Page 50 of 80
Public Input No. 18-NFPA 801-2016 [ Section No. 6.7.3 ]
6.7.3
The selection of the extinguishing agent system shall be based upon the following:
(1) Type of hazard
(2) Criticality safety
(3) Effect of agent discharge on equipment
(4) Effectiveness of agent in suppressing fire
(5) Health hazards
(6) Cleanup after agent discharge
(7) Effectiveness of agent in suppressing fire Environmental impact
(8) Cost of agent, including life-cycle costs
(9) Availability of agent
(10) Criticality safety
(11) Environmental impact
(12) Monitoring availability
(13) Fire brigade plan
(14) Availability of anual fire protection means
Statement of Problem and Substantiation for Public Input
Here is how I see the selection of extingushing agent and what is more or less importanta from fire safety sake point of view in my opinion.
Submitter Information Verification
Submitter Full Name: Katarzyna Zasadni
Organization: [ Fennovoima]
Street Address:
City:
State:
Zip:
Submittal Date: Tue Oct 04 09:32:25 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
33 of 62 1/20/2017 2:04 PM
Page 51 of 80
Public Input No. 28-NFPA 801-2016 [ Section No. 7.1.1.3 ]
7.1.1.3 *
As determined by fire hazards analysis, combustible gas analyzers shall be installed inenclosed spaces with the potential for accumulation of combustible gases outside In enclosedspaces in which combustible gas could accumulate outside of the storage vessels, piping, andutilization equipment, combustible gas analyzers that are designed for the specific gas shall beinstalled .
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer writing a fire hazard analysis could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is proposed in Public Input No. 27-NFPA 801-2016.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:26:14 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
34 of 62 1/20/2017 2:04 PM
Page 52 of 80
Public Input No. 29-NFPA 801-2016 [ Section No. 7.1.1.4 ]
7.1.1.4 *
As determined by fire hazards analysis, flammable Flammable and combustible liquids inenclosed spaces in which vapors have the potential to accumulate outside of the storagevessels, piping, and utilization equipment shall be installed with combustible-vapor analyzersappropriate for the vapors generated.
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer writing a fire hazard analysis could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is proposed in Public Input No. 27-NFPA 801-2016.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:36:47 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
35 of 62 1/20/2017 2:04 PM
Page 53 of 80
Public Input No. 30-NFPA 801-2016 [ Section No. 7.1.1.8.2 ]
7.1.1.8.2
Operating controls and limits appropriate for solvent hazards, as determined by the fire hazardanalysis, specified in 4.2, shall be established and approved .
Statement of Problem and Substantiation for Public Input
As the standard currently reads there is no establishment of controls and limits, which should be done by the fire hazard analysis. Furthermore, no authority having jurisdiction is required to approve the controls and limits established for solvents which could result in in catastrophic consequences to the public.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:39:03 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
36 of 62 1/20/2017 2:04 PM
Page 54 of 80
Public Input No. 31-NFPA 801-2016 [ Section No. 7.1.1.8.3 ]
7.1.1.8.3
An approved fixed fire-extinguishing system shall be installed or its absence justified by firehazards analysis to the authority having jurisdiction .
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer writing a fire hazard analysis could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is also proposed in Public Input No. 27-NFPA 801-2016
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:48:31 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
37 of 62 1/20/2017 2:04 PM
Page 55 of 80
Public Input No. 32-NFPA 801-2016 [ Section No. 7.1.1.8.4 ]
7.1.1.8.4 *
Solvent distillation and recovery equipment for flammable or combustible liquids shall beisolated from areas of use by by 3-hour fire barriers of appropriate rating for the hazard .
Statement of Problem and Substantiation for Public Input
The current requirement is too vague and is undetermined what is 'appropriate' and could result in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is proposed in Public Input No. 27-NFPA 801-2016.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:52:11 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
38 of 62 1/20/2017 2:04 PM
Page 56 of 80
Public Input No. 33-NFPA 801-2016 [ Section No. 7.1.4 ]
7.1.4 Hot Cells, Caves, and and Glove Boxes.
7.1.4.1 *
As determined by fire hazards analysis, hot Hot cells, caves, and glove boxes shall beprovided with fire detection in accordance with NFPA 72, National Fire Alarm and SignalingCode.
7.1.4.2 *
As determined by fire hazards analysis, fire Fire suppression shall be provided in hot cells,caves, and and glove boxes.
7.1.4.3 Hot Cells and Caves.
7.1.4.3.1
Hot cells and caves shall be of noncombustible construction.
7.1.4.3.2
Where combustible shielding is necessary for the radiation hazard, appropriate fire protectionfeatures shall be installed as determined by fire hazards analysis .
7.1.4.3.3
Where hydraulic fluids are used in master slave manipulators, fire-resistant fluids shall be used.
7.1.4.3.4
Combustible materials inside the cells and caves shall be kept to a minimum.
7.1.4.3.5
If explosive concentrations of gases or vapors are present, an inert atmosphere shall beprovided, or the cell or cave and its ventilation system shall be designed to withstand pressureexcursions.
7.1.4.4 * Glove Boxes and Windows .
7.1.4.4.1
The glove boxes , including windows, and windows shall be of noncombustible construction.
7.1.4.4.2
Where combustible shielding is necessary for the radiation hazard, appropriate fire protectionfeatures shall be installed as determined by fire hazards analysis .
7.1.4.4.3 *
When the gloves are not being used, they shall be withdrawn and secured outside the box if firehazards are present inside the box.
7.1.4.4.4 *
When the gloves are no longer needed for operations, they shall be removed and glove portcovers installed if fire hazards are present inside the box.
7.1.4.4.5
Doors shall remain closed when not in use.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
39 of 62 1/20/2017 2:04 PM
Page 57 of 80
7.1.4.4.6
The concentration of combustibles shall be limited to the quantity necessary to perform theimmediate task.
7.1.4.4.7 *
Fixed inerting systems shall not be utilized in lieu of a fire suppression system.
7.1.4.4.8
If fixed extinguishing systems are utilized, the effects of system discharge on glove box integrityshall be considered in evaluating the design of the system.
7.1.4.4.9 *
As determined by fire hazards analysis, a means A means shall be provided to restrict thepassage of flame between glove boxes that are connected.
7.1.4.5 Hoods.
7.1.4.5.1 *
Fume hoods containing radioactive materials shall be of noncombustible construction and meetthe requirements of NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals.
7.1.4.5.2
Lining materials shall be compatible with the chemical environment and capable ofdecontamination.
7.1.4.5.3
Combustible materials shall not be stored in fume hoods and should be the minimum necessaryto support the work activity.
7.1.4.5.4
Radioactive contaminated combustible waste shall not be stored or allowed to accumulate infume hoods.
7.1.4.5.5
Procedures for timely waste characterization and removal shall be established.
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer writing a fire hazard analysis could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is proposed in Public Input No. 27-NFPA 801-2016.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
40 of 62 1/20/2017 2:04 PM
Page 58 of 80
Zip:
Submittal Date: Thu Dec 15 16:00:55 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
41 of 62 1/20/2017 2:04 PM
Page 59 of 80
Public Input No. 34-NFPA 801-2016 [ Section No. 7.4.2 ]
7.4.2
Laboratory enclosures shall comply with the requirements for hot cells, glove boxes, and hoodsunless otherwise justified in a fire hazards analysis .
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer writing a fire hazard analysis could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Chapter 7 should specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials. The addition of alternative methods using the fire hazard analysis written by a qualified fire protection engineer with authority having jurisdiction approval is proposed in Public Input No. 27-NFPA 801-2016.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 16:14:15 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
42 of 62 1/20/2017 2:04 PM
Page 60 of 80
Public Input No. 27-NFPA 801-2016 [ New Section after 7.9 ]
7.10 Alternative Methods
7.10.1 Alternative methods to address specific facility, process, and special hazards addressedby this chapter are permitted when justified by a comprehensive fire hazards analysis asspecified in 4.2 and approved by the authority having jurisdiction.
Statement of Problem and Substantiation for Public Input
As the standard currently reads, anyone who claims to be a qualified fire protection engineer could determine the safety controls for facilities, processes and special hazards handling radioactive materials without AHJ concurrence resulting in catastrophic consequences to the public. Consistent with other comments made for Chapter 7 (specifying the minimum requirements and safety controls for facilities, processes and special hazards handling radioactive materials), this proposed section would permit alternative fire protection methods when justified by a fire hazard analysis prepared by a qualified fire protection engineer that is approved by the authority having jurisdiction.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:07:43 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
43 of 62 1/20/2017 2:04 PM
Page 61 of 80
Public Input No. 62-NFPA 801-2017 [ Section No. A.3.3.25 ]
A.3.3.25 Noncombustible Material.
The three terms used to describe the combustibility of materials — noncombustible, limited-combustible, and combustible — have are based on specific definitions criteria . Whenattempting to classify the combustibility of a material, ensure that the definitions of all criteriafor classifying a material based on any of the three terms are thoroughly understood. (SeeNFPA 220, Standard on Types of Building Construction.
Materials that do not comply with the criteria for either noncombustible materials or for limitedcombustible materials are considered combustible.
Materials that are reported as passing ASTM E 136 E136 , Standard Test Method for Behaviorof Materials in a Vertical Tube Furnace at 750°C, are considered noncombustible materials.
The following are the criteria used in NFPA 101, Life Safety Code and in NFPA 220,Standardon Types of Building Construction, for a material to be classified as a limited-combustiblematerial. A limitedd combustible material is a material not complying with the definition ofnoncombustible material that, in the form in which it is used, has a potential heat value notexceeding 8141 kJ/kg (3500 Btu/lb) where tested in accordance with NFPA 259, Standard TestMethod for Potential Heat of Building Materials, and complies with (1) or (2):
(1) Materials having a structural base of noncombustible material, with a surfacing notexceeding a thickness of 3.2 mm (1⁄8 in.) that have a flame spread index not greater than 50,when tested in accordance with ASTM E84;
(2) Materials that, in the form and thickness used, other than described in (1), have neither aflame spread index greater than 25, when tested in accordance with ASTM E84, nor exhibitevidence of continued progressive combustion and are of such composition that surfaces thatwould be exposed by cutting through the material on any plane would have neither a flamespread index greater than 25 nor exhibit evidence of continued progressive combustion, whentested in accordance with ASTM E84 or UL 723.
Materials subject to increase in combustibility or flame spread index beyond the limitsestablished above through the effects of age, moisture, or other atmospheric condition areconsidered combustible.
Statement of Problem and Substantiation for Public Input
This public input proposes to move all the information regarding limited combustible materials from section A.5.8 to the section (A.3.3.25) which discusses noncombustible materials and limited combustible materials instead of section 5.8 where simply flame spread or similar properties is being discussed and not whether a material is or is not combustible, limited combustible or noncombustible. The criteria proposed to be added are the same as those originally in A.5.8. The slight changes in language are simply to clarify that this is not a definition for limited combustible but the criteria contained in the 2015 edition of NFPA 101 and to make the language more consistent with NFPA 101 or NFPA 220.The public input also makes slight changes to the existing language so as to make it clear that these are issues of criteria for classification and adds a sentence regarding combustible materials.
Just for information, the 2018 edition of NFPA 101 will most likely contain an additional option to determine what is a limited combustible material (based on ASTM E2965) and that may be proposed in a public comment after NFPA 101-2018 is approved later this year.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
44 of 62 1/20/2017 2:04 PM
Page 62 of 80
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 61-NFPA 801-2017 [Section No. A.5.8]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 14:29:19 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
45 of 62 1/20/2017 2:04 PM
Page 63 of 80
Public Input No. 23-NFPA 801-2016 [ New Section after A.3.3.27.2 ]
A.3.3.28
Examples of a qualified fire protection engineer includes a person who has a minimum of three yearsresponsible in charge involving facilities covered by this standard and is either a graduate of a recognizedfire protection engineering curriculum, a licensed professional engineer though a state administeredNational Council of Examiners for Engineering and Surveying in fire protection engineering, or meets therequirements as a professional member of the Society of Fire Protection Engineers (SFPE), whichrecognizes various other education, knowledge and experiences levels as a basis for recognizing fireprotection engineering standing.
Statement of Problem and Substantiation for Public Input
Explanatory information provided to accompany definition of qualified fire protection engineer from Public Input No. 21-NFPA 801-2016
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 14:55:46 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
46 of 62 1/20/2017 2:04 PM
Page 64 of 80
Public Input No. 24-NFPA 801-2016 [ Section No. A.3.3.28 ]
A.3.3. 28 29 Radiation.
The term includes streams of fast-moving particles, such as alpha and beta particles, freeneutrons, and cosmic radiation.
Statement of Problem and Substantiation for Public Input
Revision of Section number consistent with comment in Public Input No. 22-NFPA 801-2016
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:00:39 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
47 of 62 1/20/2017 2:04 PM
Page 65 of 80
Public Input No. 36-NFPA 801-2016 [ Section No. A.4.2 ]
A.4.2
A fire hazards analysis, in the context used in this standard, should serve as an evaluation toolfor design and therefore should include a goal-oriented approach, particularly when discussingtopics when there are no deterministic requirements in this standard. The evaluation shouldaddress goals and objectives that include the following:
(1) Nuclear safety goal. The nuclear safety goal should be to provide assurance thatradioactive materials be maintained in a safe and stable condition in the event of a fire.
(2) Radioactive and hazardous material release goal. The radioactive and hazardous materialrelease goal should be to provide reasonable assurance that a fire will not result in therelease of radiological or hazardous material that adversely affects the public, plantpersonnel, or the environment.
(3) Life safety goal. The life safety goal should be to provide reasonable assurance that lossof life in the event of fire will be prevented for facility occupants.
(4) Nuclear safety objectives. In the event of a fire during any operational mode and processconfiguration, the nuclear safety objectives should be as follows:
(5) Reactivity control — capable of achieving and maintaining subcritical conditions
(6) Cooling — capable of achieving and maintaining decay heat removal
(7) Fission product boundary — capable of maintaining fundamental fuel geometry
(8) Heat transfer medium inventory control — capable of maintaining the necessaryquantity of heat transfer medium
(9) Prevent subcritical fissionable material from becoming critical by the introduction ofwater and concurrent violation, with safe separation of subcritical masses
(10) Maintain monitoring of safety functions
(11) Radioactive and hazardous material release objective. The radiological and hazardousmaterial release objective should be to prevent exposure, uncontrolled release, orunacceptable dispersion of hazardous substances, nuclear material, or radioactivematerial, due to fires.
(12) Life safety objectives. The life safety objectives should be to protect occupants not intimatewith the initial fire development from loss of life, improve the survivability of those who areintimate with the fire development, and provide protection for emergency personnel and thepersonnel required to carry out manual actions to achieve the nuclear safety objectives.
(13) Objectives to address the Purpose. The fire hazard analysis should arrive at a conclusion thateither the facility meets fire protection objectives necessary to address this standards purpose or itdoes not meet the objectives with implementation of actions necessary to meet fire protectionobjectives.
(14) Individual Fire Areas . The premise of the fire hazard analysis should be that fire wouldbe contained within individual fire areas of the facility consisting of areas bounded by firerated construction, unless analytical deterministic modeling methods or calculations,recognized by the authority having jurisdiction, can demonstrate a less or greater firepotential.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
48 of 62 1/20/2017 2:04 PM
Page 66 of 80
Statement of Problem and Substantiation for Public Input
Proposed is to add additional explanatory material focusing on the fire hazard analysis to address the purpose of the standard to protect the safety of the public, facility personnel, and the environment from the effects of fire or explosions on radiological and other hazardous materials at facilities handling radioactive materials with a premise of fire containment within rated construction unless the fire hazard analysis demonstrates a lessor or greater fire. This is not currently conveyed in the standard.
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 17:06:11 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
49 of 62 1/20/2017 2:04 PM
Page 67 of 80
Public Input No. 25-NFPA 801-2016 [ Section No. A.4.2.6 ]
A.4.2.6
A qualified fire protection engineer responsible for the preparation of a fire hazards analysisshould have a combination of education and experience in the field of fire protection specific tothese types of facilities. Examples of a qualified fire protection engineer can include a licensedprofessional engineer specializing in the field of fire protection or qualified to be a professionalmember of the Society of Fire Protection Engineers (SFPE).
Statement of Problem and Substantiation for Public Input
Deletion due addition of definition from comments added in Public Input No. 21-NFPA 801-2016 and No. 23-NFPA 801-2016
Submitter Information Verification
Submitter Full Name: Craig Christenson
Organization: Us Department Of Energy
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 15 15:05:09 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
50 of 62 1/20/2017 2:04 PM
Page 68 of 80
Public Input No. 58-NFPA 801-2017 [ New Section after A.5.8 ]
A.5.8.2 The alternate fire test method in this section (NFPA 286) is a room-corner fire test and ithas been shown to be applicable to many more interior finish materials than ASTM E84, theSteiner tunnel test, for assessing their fire performance. When interior finish materials areappropriately tested using ASTM E84, the results of both tests correlate well in terms of pass orfail criteria.
Statement of Problem and Substantiation for Public Input
Explains the added section
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 57-NFPA 801-2017 [Section No. 5.8]
Public Input No. 56-NFPA 801-2017 [Section No. D.1.2.1]
Public Input No. 60-NFPA 801-2017 [Section No. D.1.1]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:35:43 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
51 of 62 1/20/2017 2:04 PM
Page 69 of 80
Public Input No. 61-NFPA 801-2017 [ Section No. A.5.8 ]
A.5.8
Limited-combustible is defined as follows: A material not complying with the definition ofnoncombustible material that, in the form in which it is used, has a potential heat value notexceeding 8141 kJ/kg (3500 Btu/lb) where tested in accordance with NFPA 259, Standard TestMethod for Potential Heat of Building Materials , and complies with (1) or (2): (1) Materialshaving a structural base of noncombustible material, with a surfacing not exceeding a thickness
of 3.2 mm ( 1 ⁄ 8 in.) that have a flame spread index not greater than 50; (2) materials, in theform and thickness used, other than described in (1), having neither a flame spread indexgreater than 25 nor evidence of continued progressive combustion and of such compositionthat surfaces that would be exposed by cutting through the material on any plane would haveneither a flame spread index greater than 25 nor evidence of continued progressivecombustion. (Materials subject to increase in combustibility or flame spread index beyond thelimits herein established through the effects of age, moisture, or other atmospheric conditionare considered combustible.)
Statement of Problem and Substantiation for Public Input
The information on limited combustible material is not appropriate here and should be added to the annex note to A.3.3.25, which is where limited combustible material is being discussed.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 62-NFPA 801-2017 [Section No. A.3.3.25]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 14:26:46 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
52 of 62 1/20/2017 2:04 PM
Page 70 of 80
Public Input No. 3-NFPA 801-2015 [ Chapter D ]
Annex D Informational References
This annex is not a part of the requirements of this NFPA document but is included forinformational purposes only.
D.1 Referenced Publications.
The documents or portions thereof listed in this annex are referenced within the informationalsections of this standard and are not part of the requirements of this document unless alsolisted in Chapter 2 for other reasons.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
53 of 62 1/20/2017 2:04 PM
Page 71 of 80
D.1.1 NFPA Publications.
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 edition.
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 edition.
NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 edition.
NFPA 30, Flammable and Combustible Liquids Code, 2012 edition.
NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.
NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2014edition.
NFPA 72 ®, National Fire Alarm and Signaling Code, 2013 edition.
NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2013 edition.
NFPA 80A, Recommended Practice for Protection of Buildings from Exterior Fire Exposures,2012 edition.
NFPA 92, Standard for Smoke Control Systems, 2012 edition.
NFPA 99, Health Care Facilities Code, 2012 edition.
NFPA 101 ®, Life Safety Code ®, 2012 edition.
NFPA 204, Standard for Smoke and Heat Venting, 2012 edition.
NFPA 220, Standard on Types of Building Construction, 2012 edition.
NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2012 edition.
NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2013 edition.
NFPA 484, Standard for Combustible Metals, 2012 edition.
NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2013 edition.
NFPA 600, Standard on Industrial Fire Brigades, 2010 edition.
NFPA 601, Standard for Security Services in Fire Loss Prevention, 2010 edition.
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric GeneratingPlants, 2010 edition.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor ElectricGenerating Plants, 2010 edition.
NFPA 901, Standard Classifications for Incident Reporting and Fire Protection Data, 2011edition.
NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, 2013edition.
NFPA 1600 ®, Standard on Disaster/Emergency Management and Business ContinuityPrograms, 2013 edition.
NFPA 1620, Standard for Pre-Incident Planning, 2010 edition.
D.1.2 Other Publications.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
54 of 62 1/20/2017 2:04 PM
Page 72 of 80
D.1.2.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 119 E119 , Standard Test Methods for Fire Tests of Building Construction andMaterials, 2011 2015 .
ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical Tube Furnaceat 750°C, 2011 2012 .
IEEE/ASTM SI 10, American National Standard for Metric Practice , 2010.
D.1.2.2 EPA Publications.
Environmental Protection Agency, Ariel Rios Building, 1200 Pennsylvania Avenue, NW,Washington, DC 20460.
EPA 520/1-75-001, Manual of Protective Action Guide and Protective Actions for NuclearIncidents.
D.1.2.3 FPRF Publications.
Fire Protection Research Foundation, 1 Batterymarch Park, Quincy, MA 02169.
“Glovebox Fire Protection: A Literature Review,” September 2010.
D.1.2.4 IEEE Publications.
Institute of Electrical and Electronics Engineers, Three Park Avenue, 17th Floor, New York, NY10016-5997.
IEEE 383, Standard for Type of Class IE Electric Cables, Field Splices and Connections forNuclear Power Generating Stations, 1974 Qualifing Electric Cables and Splices forNuclear Facilities , 2015 .
IEEE SI 10, American National Standard for Metric Practice , 2010 .
D.1.2.5 OSHA Publications.
Occupational Safety and Health Administration, 200 Constitution Avenue, NW, Washington, DC20210.
OSHA Title 29, Code of Federal Regulations, Part 1910.38, Employee Emergency Plans andFire Prevention, 2002.
OSHA Title 29, Code of Federal Regulations, Part 1910.156, Fire Brigades, 1981 2008 .
D.1.2.6 UL Publications.
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062–2096.
ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, revised2015 .
D.2 Informational References.
The following documents or portions thereof are listed here as informational resources only.They are not a part of the requirements of this document.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
55 of 62 1/20/2017 2:04 PM
Page 73 of 80
D.2.1
The National Council on Radiation Protection and Measurement has issued a number of reportson specific radiation protection subjects. These reports are available from NCRP Publications,P.O. Box 4867, Washington, DC 20008, , 7910 Woodmont Avenue, Suite 400, Bethesda,MD 20814-3095 , or from the U.S. Government Printing Government Publishing Office,Washington, DC 20402 732 North Capitol Street, NW, Washington, DC 20401-0001 .Applicable publications include the following:
NCRP 30, Safe Handling of Radioactive Materials-NBS Handbook 92, 1964.
NCRP 38, Protection Against Neutron Radiation, 1971.
D.2.2
Standards of the U.S. Nuclear Regulatory Commission for protection against radiation arepublished in the Code of Federal Regulations, Part 20, Chapter 1, Title 10, available at mostlibraries. Revisions are printed in the Federal Register, available at subscribing libraries or bysubscription from the U.S. Government Printing Office Government Publishing Office .
D.2.3
Nuclear Safety, a bimonthly magazine, is available from the U.S. Government PrintingGovernment Publishing Office. It covers many areas of interest, including general safety,accident analysis, operating experiences, and current events.
D.2.4
Specific requirements for facilities handling radioactive materials have been issued by theAmerican Nuclear Insurers, Town Center 95 Glastonbury Boulevard , Suite 300S, 29 SouthMain Street, West Hartford, CT 06107-2445 300, Glastonbury, CT 06033-4453 , and theMAERP Reinsurance Association, 1151 Boston-Providence Turnpike, Norwood, MA 020621400 Rniilance Dr., Suite 208, Park Ridge, IL 60068 .
D.3 References for Extracts in Informational Sections. (Reserved)
Statement of Problem and Substantiation for Public Input
Referenced current SDO names, addresses, standard names, numbers, and editions.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 2-NFPA801-2015 [Chapter 2]
Referenced current SDO names, addresses, standardnames, numbers, and editions.
Submitter Information Verification
Submitter Full Name: Aaron Adamczyk
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Sun Dec 06 21:30:31 EST 2015
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
56 of 62 1/20/2017 2:04 PM
Page 74 of 80
Public Input No. 60-NFPA 801-2017 [ Section No. D.1.1 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
57 of 62 1/20/2017 2:04 PM
Page 75 of 80
D.1.1 NFPA Publications.
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 edition.
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 edition.
NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 edition.
NFPA 30, Flammable and Combustible Liquids Code, 2012 edition.
NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.
NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2014edition.
NFPA 72 ®, National Fire Alarm and Signaling Code, 2013 edition.
NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2013 edition.
NFPA 80A, Recommended Practice for Protection of Buildings from Exterior Fire Exposures,2012 edition.
NFPA 92, Standard for Smoke Control Systems, 2012 edition.
NFPA 99, Health Care Facilities Code, 2012 edition.
NFPA 101 ®, Life Safety Code ®, 2012 edition.
NFPA 204, Standard for Smoke and Heat Venting, 2012 edition.
NFPA 220, Standard on Types of Building Construction, 2012 edition.
NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2012 edition.
NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2013 edition.
NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and CeilingInterior Finish to Room Fire Growth, 2015 edition.
NFPA 484, Standard for Combustible Metals, 2012 edition.
NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2013 edition.
NFPA 600, Standard on Industrial Fire Brigades, 2010 edition.
NFPA 601, Standard for Security Services in Fire Loss Prevention, 2010 edition.
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric GeneratingPlants, 2010 edition.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor ElectricGenerating Plants, 2010 edition.
NFPA 901, Standard Classifications for Incident Reporting and Fire Protection Data, 2011edition.
NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, 2013edition.
NFPA 1600 ®, Standard on Disaster/Emergency Management and Business ContinuityPrograms, 2013 edition.
NFPA 1620, Standard for Pre-Incident Planning, 2010 edition.
Statement of Problem and Substantiation for Public Input
adds standard added in A.5.8.2.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
58 of 62 1/20/2017 2:04 PM
Page 76 of 80
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 58-NFPA 801-2017 [New Section after A.5.8]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:41:52 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
59 of 62 1/20/2017 2:04 PM
Page 77 of 80
Public Input No. 5-NFPA 801-2016 [ Section No. D.1.2.1 ]
D.1.2.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials,2011 2015 .
ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at750°C, 2011 2015 .
IEEE/ASTM SI 10, American National Standard for Metric Practice, 2010.
Statement of Problem and Substantiation for Public Input
Date updates.
Submitter Information Verification
Submitter Full Name: Timothy Earl
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jan 05 10:05:28 EST 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
60 of 62 1/20/2017 2:04 PM
Page 78 of 80
Public Input No. 56-NFPA 801-2017 [ Section No. D.1.2.1 ]
D.1.2.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.
ASTM E 119 E84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials, 2016.
ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials,2011 2016a .
ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical Tube Furnaceat 750°C, 2011 2016a .
IEEE/ASTM SI 10, American National Standard for Metric Practice, 2010.
Statement of Problem and Substantiation for Public Input
updates - also adds standard from annex A.5.8.2.
Related Public Inputs for This Document
Related Input Relationship
Public Input No. 58-NFPA 801-2017 [New Section after A.5.8]
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jan 05 13:23:17 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
61 of 62 1/20/2017 2:04 PM
Page 79 of 80
Public Input No. 7-NFPA 801-2016 [ Section No. D.1.2.6 ]
D.1.2.6 UL Publications.
Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062–2096.
ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011 2015 .
Statement of Problem and Substantiation for Public Input
This proposal updates the UL Standards to the current referenced edition.
Submitter Information Verification
Submitter Full Name: Ronald Farr
Organization: UL LLC
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jun 28 10:28:39 EDT 2016
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
62 of 62 1/20/2017 2:04 PM
Page 80 of 80