BSES Bhawan, Nehru Place, New Delhi- 19 Volume – I Technical Specification For Power Transformer ___________________________________________________________________________ _______________ vi) Stainless steel door handle with lock & additional facility for padlock. vii) Earthing boss 7.11 Hardware, Gasket, Cables and Wires, Terminal blocks, Cable gland, Cable lugs of OLTC Drive mechanism As per Cl. 4.3, 4.4, 4.6, 4.7, 4.8, 4.9 of the specification respectively. 7.12 OLTC and drive mechanism painting As per Cl. 4.10 of the specification 7.13 RTCC Panel Not In the Scope Of Supply 8.0 Approved make of components 8.1 CRGO Nippon/JFE/Posco 8.2 Copper Birla copper/Sterlite 8.3 Pre compressed Pressboard Raman Board, Mysore/ Senapathy Whiteley 8.4 Laminated Wood Permalli Wallance / Rochling Engineers 8.5 Oil Apar/Savita/Raj 8.6 Condensor Bushings (OIP) CGL/BHEL/ABB/ALSTOM 8.7 Porcelain Bushing CJI/Jayshree Insulators/BHEL 8.8 Steel TATA/Jindal/SAIL 8.9 Lugs/Glands Jainson/Dowells/Comet 8.10 Radiators CTR/Hi-Tech Radiators/Tarang Engineers 8.11 Fans Marathon / Khaitan 8.12 Magnetic Oil Level Indicator Sukrut /Yogna 8.13 Pressure relief valve Sukrut / Qualitrol 8.14 Bucchholz Relay Proyog / ATVUS 8.15 Oil surge Relay Proyog / ATVUS 8.16 Winding Temperature Indicator Precimeasure / Perfect Controls / Pradeep sales 8.17 Oil Temperature Indicator Precimeasure / / Perfect Controls/ Pradeep Sales 8.18 Sudden Pressure Relay Sukrut / Qualitrol 8.19 Aircell Sukrut(Unirub)/Pronol / Rubber Product 8.20 Neutral CT Pragati /ECS / KAPPA/ Reputed equivalent 8.21 WCT Pragati / ECS / KAPPA/ Reputed equivalent 8.22 Switch L&T (Salzer) / Siemens 8.23 HRC Fuse Links Siemens / L&T/GE 8.24 Fuse base Siemens / L&T/GE 8.25 AC Contactors & O/L Relay L&T / Siemens / Schneider 296 BSES Bhawan, Nehru Place, New Delhi- 19

Upload: krcdewanew

Post on 04-Feb-2016

244 views

Category:

Documents


0 download

DESCRIPTION

Volume-III

TRANSCRIPT

Page 1: Tech Spec Ss -III

BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________vi) Stainless steel door handle withlock & additional facility for padlock.vii) Earthing boss7.11 Hardware, Gasket, Cables and Wires,Terminal blocks, Cable gland, Cablelugs of OLTC Drive mechanismAs per Cl. 4.3, 4.4, 4.6, 4.7, 4.8, 4.9 of thespecification respectively.7.12 OLTC and drive mechanism painting As per Cl. 4.10 of the specification7.13 RTCC Panel Not In the Scope Of Supply8.0 Approved make of components8.1 CRGO Nippon/JFE/Posco8.2 Copper Birla copper/Sterlite8.3 Pre compressed Pressboard Raman Board, Mysore/ Senapathy Whiteley8.4 Laminated Wood Permalli Wallance / Rochling Engineers8.5 Oil Apar/Savita/Raj8.6 Condensor Bushings (OIP) CGL/BHEL/ABB/ALSTOM8.7 Porcelain Bushing CJI/Jayshree Insulators/BHEL8.8 Steel TATA/Jindal/SAIL8.9 Lugs/Glands Jainson/Dowells/Comet8.10 Radiators CTR/Hi-Tech Radiators/Tarang Engineers8.11 Fans Marathon / Khaitan8.12 Magnetic Oil Level Indicator Sukrut /Yogna8.13 Pressure relief valve Sukrut / Qualitrol8.14 Bucchholz Relay Proyog / ATVUS8.15 Oil surge Relay Proyog / ATVUS8.16 Winding Temperature Indicator Precimeasure / Perfect Controls /Pradeep sales8.17 Oil Temperature Indicator Precimeasure / / Perfect Controls/ PradeepSales8.18 Sudden Pressure Relay Sukrut / Qualitrol8.19 Aircell Sukrut(Unirub)/Pronol / Rubber Product8.20 Neutral CT Pragati /ECS / KAPPA/ Reputed equivalent8.21 WCT Pragati / ECS / KAPPA/ Reputed equivalent8.22 Switch L&T (Salzer) / Siemens8.23 HRC Fuse Links Siemens / L&T/GE8.24 Fuse base Siemens / L&T/GE8.25 AC Contactors & O/L Relay L&T / Siemens / Schneider296BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________8.26 Terminals Connectwell / Elmex8.27 Push buttons / Actuator L&T / Siemens8.28 Thermostat Velco8.29 Heater Velco8.30 Voltmeter Selector Switch Siemens8.31 Control selector switch Siemens8.32 Auxiliary Relays Jyoti / Easun Rayrole8.33 Timers L&T /Siemens8.34 Tap Position Indicator Accord8.35 Annunciator Accord

Page 2: Tech Spec Ss -III

8.36 Digital tap change counter Selectron8.37 LED cluster type indication lamp MIMIC/ Siemens/ BinayNote – Any other make of component to be approved by purchaser9.0 Quality assurance9.1 Quality Assurance Program To be submitted before contract award.Program shall contain followingi) The structure of the organisationii) The duties and responsibilitiesassigned to staff ensuring quality ofworkiii) The system for purchasing, takingdelivery and verification of materialsiv) The system for ensuring quality ofworkmanshipv) The system for control ofdocumentationvi) The system for the retention of recordsvii) The arrangements for the Supplier’sinternal auditingviii) A list of the administration and workprocedures required to achieve andverify Contract’s quality requirements.These procedures shall be madereadily available to the Purchaser forinspection on request.ix) The manufacturers shall havededicated quality personnel at eachstep of manufacturing.x) Manufacturers who are not approvedvendors with BSES / REL can beconsidered after validation of theirfactory for quality processes.297BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________9.2 Quality Plan To be submitted by the successful bidderfor approval. Plan shall contain following asa minimum.i) An outline of the proposed work andprogramme sequencei) The structure of the Supplier’sorganization for the contractii) The duties and responsibilitiesassigned to staff ensuring quality ofwork for the contractiii) Hold and notification pointsiv) Submission of engineering documentsrequired by the specificationv) The inspection of materials andcomponents on receiptvi) Reference to the Supplier’s workprocedures appropriate to eachactivityvii) Inspection during

Page 3: Tech Spec Ss -III

fabrication/constructionviii) Final inspection and testix) Successful bidder shall includesubmittal of Mills invoice, Bill of lading,Mill’s test certificate for grade, physicaltests, dimension and specific watt lossper kG for the core material to thepurchaser for verification in the qualityplan suitably.10.0 Progress Reporting10.1 Outline Document To be submitted for purchaser approval foroutline of production, inspection, testing,inspection,packing,dispatch, documentationprogramme10.2 Detailed Progress report To be submitted to Purchaser once a monthcontainingi) Progress on material procurementii) Progress on fabricationiii) Progress on assemblyiv) Progress on internal stage inspectionv) Reason for any delay in totalprogrammevi) Details of test failures if any inmanufacturing stagesvii) Progress on final box upviii) Constraintsix) Forward path298BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________11.0 Submittals11.1 Submittals required with bid i) Completed technical data schedule;ii) Descriptive literature giving fulltechnical details of equipment offered;iii) Outline dimension drawing for eachmajor component, general arrangementdrawing showing component layout andgeneral schematic diagrams;iv) Type test certificates, where available,and sample routine test reports;v) Detailed reference list of customersalready using equipment offered duringthe last 5 years with particularemphasis on units of similar design andrating;vi) Details of manufacturer's qualityassurance standards and programmeand ISO 9000 series or equivalentnational certification;vii) Deviations from this specification. Onlydeviations approved in writing beforeaward of contract shall be accepted;viii) Recommended spare parts andconsumable items for five years of

Page 4: Tech Spec Ss -III

operation with prices and spare partscatalogue with price list for futurerequirementsix) Transport / Shipping dimension andweights, space required for handlingparts for maintenancex) Write up on oil preservation systemxi) Write up on OLTCxii) Quality Assurance Program11.2 Submittals required after award forApproval (A), Reference (R), andsubsequent distributioni) Programme for production and testing(A)ii) Guaranteed Technical Particulars (A)iii) General description of the equipmentand all components, includingbrochures (R)iv) Calculations to substantiate choice ofelectrical, structural, mechanicalcomponent size/ratings (A)v) Detailed dimension drawing for all299BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________components, general arrangementdrawing showing detailed componentlayout and detailed schematic andwiring drawings for all components likemarshalling box and OLTC drivemechanism boxvi) Detailed loading drawing to enable thePurchaser to design and constructfoundations for the transformer (R)vii) Transport / shipping dimensions withweights, wheel base details, untankingheight etc (R)viii) Terminal arrangements and cable boxdetails (A)ix) Flow diagram of cooling systemshowing no of cooling banks (A)x) Drawings of major components likeBushing , CT etc (A)xi) Valve schedule diagram plate (A)xii) Instruction plate for flexible separator(A)xiii) Rating and diagram plate with OLTCconnection detailsxiv) List of makes of all fittings andaccessories (A)xv) Statement drawing attention to allexposed points in the equipment atwhich contact with or in close proximityto other metals and stating clearly what

Page 5: Tech Spec Ss -III

protection is employed to preventcorrosion at each point (A)xvi) Detailed installation and commissioninginstructionsxvii) Quality Plan11.3 Submittals required at the final holdpoint prior to despatchi) Inspection and test reports carried outin manufacturer’s works (A)ii) Test certificates of all bought out itemsiii) Operation and maintenanceInstructions as well as trouble shootingcharts11.4 Drawing and document sizes Standard size paper A0, A1, A2, A3, A411.5 No of drgs /Documents required atdifferent stagesAs per Annexure A Scope of Supply300BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________12.0 Inspection & Testing12.1 Inspection and Testing duringmanufacture12.1.1 Tank and Conservator i) Check correct dimensions betweenwheels demonstrate turning of wheelsthrough 90 deg and furtherdimensional check.ii) Check for physical properties ofmaterials for lifting lugs, jacking padsetc. All load bearing welds, includinglifting lug welds shall be subjected torequired load tests.iii) Leakage test of the conservator as perCBIP.iv) Certification of all test results.v) Oil leakage test on all tanks at normalhead of oil plus 35 kN/sqm at the baseof the tank for 24 hrsvi) Vacuum and Pressure test on tank astype test as per CBIPvii) Leakage test of radiators as per CBIP12.1.2 Core i) Vendor to submit the documentaryevidence for procurement of CRGOlaminations and prove that they haveprocured / used new core material.During in process inspection atlamination sub vendor , Customer shallrandomly select / seal lamination fortesting at ERDA / CPRI ( AccreditedNABL labs) for Specific core loss ,accelerated ageing test , surfaceinsulation resistivity , AC permeabilityand magnetization , Stacking factor ,ductility etc . This testing shall be in the

Page 6: Tech Spec Ss -III

scope of vendor.ii) Check on the quality of varnish if usedon the stampings.a) Measurement of thickness andhardness of varnish on stampings.b) Solvent resistance test to check thatvarnish does not react in hot oil.c) Check over all quality of varnish bysampling to ensure uniform hippingcolor, no bare spots. No ever burntvarnish layer and no bubbles onvarnished surface.iii) Check on the amount of burrs.iv) Bow check on stampings.v) Check for the overlapping of301BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________stampings. Corners of the sheet areto be apart.vi) Visual and dimensional check duringassembly stage.vii) Check on complete core formeasurements of iron-loss and checkfor any hot spot by exciting the core soas to induce the designed value of fluxdensity in the core.viii) Check for inter laminar insulationbetween core sectors before and afterpressing.ix) Visual and dimensional checks forstraightness and roundness of core,thickness of limbs and suitability ofclamps.x) High voltage test (2 KV for oneminute) between core and clamps.xi) Certification of all test results.12.1.3 Insulating Materials i) Sample check for physical propertiesof materials.ii) Check for dielectric strength.iii) Visual and dimensional checks.iv) Check for the reaction of hot oil oninsulating materials.v) Certification of all test results.12.1.4 Windings i) Sample check on winding conductorfor mechanical properties andelectrical conductivity.ii) Visual and dimensional check onconductor for scratches, dept. marketc.iii) Sample check on insulating paper forPE value, Bursting strength, Electricstrength.iv) Check for the reaction of hot oil on

Page 7: Tech Spec Ss -III

insulating paper.v) Check for the bending of theinsulating paper on conductor.vi) Check and ensure that physicalcondition of all materials taken forwinding is satisfactory and free ofdust.vii) Check for absence of short circuitbetween parallel strands.viii) Check for Brazed joints whereverapplicable.ix) Measurement of voltage ratio to becarried out when core/ yoke is302BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________completely restocked and allconnections are ready.x) Certification of all test results.12.1.4.1 Checks before drying process i) Check conditions of insulation on theconductor and between the windings.ii) Check insulation distance betweenhigh voltage connection distancebetween high voltage connectioncables and earthed and other liveparts.iii) Check insulation distance betweenlow voltage connection and earthedand other parts.iv) Insulation test of core earthing.v) Check for proper cleanlinessvi) Check tightness of coils i.e. no freemovement.vii) Certification of all test results.12.1.4.2 Checks during drying process i) Measurement and recording oftemperature and drying time duringvacuum treatment.ii) Check for completeness of drying.iii) Certification of all test results.12.1.5 Oil As per BSES specification.12.1.6 Test on fittings and accessories As per manufacturer’s standard12.2 Routine / Acceptance tests The sequence of routine testing shall be asfollowsi) Visual and dimension check forcompletely assembled transformerii) Measurements of voltage ratioiii) Measurements of winding resistanceat each taps.iv) Vector Group and polarity testv) *Measurements of insulationresistance and polarization indexvi) Separate sources voltage withstandtest.vii) Measurement of iron losses and

Page 8: Tech Spec Ss -III

exciting current at rated frequencyand 90%, 100% and 110% ratedvoltage.viii) Induced over voltage withstand test.ix) Load losses measurement atprincipal, minimum and maximumtaps.x) Impedance measurement of principal,minimum and maximum taps of thetransformer.303BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________x) Routine test of tanksxi) Induced voltage withstand test (to berepeated if type tests are conducted).xii) Measurement of Iron loss (to berepeated if type test are conducted).xiii) Measurement of capacitance andTan Delta for transformer windingand HV bushing and Tan Delta fortransformer oil (for all transformers).xiv) Phase relation test; Polarity, angulardisplacement and phase sequence.xv) Ratio of HVWTI CT, LV WTI CT andneutral CTxvi) Excitation and Knee point voltage teston class PS core of neutral CT.xvii) Routine Test on on-load tapchanger.xviii) Oil leakage test on assembledtransformerxix) Magnetic balance testxx) Measure the auxiliary loss (Loss offan)xxi) Power frequency voltage withstandtest on all auxiliary circuits.xxii) Certification of all test results.xxiii) Temperature rise test as per IS#Note 1: *Insulation resistancemeasurement shall be carried out at 5kV.Value of IR should not be less than 1000Mohms.Polarisation Index (PI = IR10min/IR1min)should not be less than 1.5 (If one minuteIR value is above 5000 Mohms and it isnot be possible to obtain an accurate 10minutes reading, in such casespolarisation index can be disregarded as ameasure of winding condition.Note 2: #Temperature rise test isnecessary to be carried out on 5% of theorder quantity (subject to minimum 1) atthe manufacturer's works. Purchaser’s

Page 9: Tech Spec Ss -III

engineer, will at his discretion, selecttransformer for temp. rise test atmanufacturer's works and witness thesame for comparison with type test results.12.3 Type Tests Following type test shall be carried out onone transformer of each rating and type (InGovt. recognized independent testlaboratory / Internationally accredited test304BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________lab or at manufacturer’s facility if it isapproved by competent authority) from thelot offered for inspection.i) Impulse withstand test on all three HVand LV limbs of the transformers forchopped wave as per standardii) Temperature rise test as per ISiii) Dissolved gas analysis before andafter Temperature Rise Testiv) Pressure relief device testv) Pressure and Vacuum test on tank*(*stage inspection).12.4 Special Tests Following tests shall be carried out on onetransformer of each rating and typei) Measure of zero seq. impedance (Cl.16.10 IS 2026 Part I).ii) Measurement of acoustic noise level(Cl. 16.12 of IS 2026 Part I).iii) Measurement of harmonic level on noload current.iv) CRGO testing for Specific core loss ,accelerated ageing test , surfaceinsulation resistivity , AC permeabilityand magnetization , Stacking factor ,ductility etc. ( This test to be applicableif total order quantity is equal to ormore than three number)v) Oil testing to be tested at ERDA/CPRIlabs, whose samples shall be selected& sealed by customer inspectionengineer.12.5 Note for Type test and Special test Cost of the above tests, if extra, shall bequoted separately by the Bidder, whichshall be considered in the price evaluation.12.6 Notification to bidders The product offered must be of type testeddesign with valid type test report of notmore than five (5) years.In case the product offered is never typetested for tests as per above list, type teststo be conducted by bidder at his own costat Govt. recognized independent testlaboratory / Internationally accredited testlab or at manufacturer’s facility if it is

Page 10: Tech Spec Ss -III

approved by competent authorityValid Type test reports for Dynamic Shortcircuit test as per IS may be forwarded for305BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________customer’s review and approval.In case the product offered is never testedfor dynamic short circuit the same to beconducted by bidder at his own cost atGovt. recognized independent testlaboratory / Internationally accredited testlab.13.0 Packing , Shipping, Handling and Storage13.1 Packing13.1.1 Packing protection Against corrosion, dampness, heavy rains,breakage and vibration13.1.2 Packing for accessories and spares Robust wooden non returnable packingcase with all the above protection13.1.3 Packing details On each packing case details required asfollowsi) Individual serial number;ii) Purchaser's name;iii) PO number;iv) Destination; ;v) Supplier's name;vi) Name and address of supplier'sagentvii) Description and numbers ofcontents;viii) Manufacturer’s nameix) Country of originx) Case measurementsxi) Gross and net weights in kilogramsxii) All necessary slinging and stackinginstructions.13.2 Shipping The bidder shall ascertain at an early dateand definitely before the commencementof manufacture, any transport limitationssuch as weights, dimensions, road culverts,overhead lines, free access etc. from themanufacturing plant to the project site; andfurnish to the Purchaser confirmation thatthe proposed packages can be safelytransported, as normal or oversizepackages, upto the plant site. Anymodifications required in the infrastructureand cost thereof in this connection shall bebrought to the notice of the Purchaser.306BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________

Page 11: Tech Spec Ss -III

13.3 Handling and Storage As per manufacturer’s instruction14.0 DeviationsDeviations from this Specification shall be stated in writing with the tender by reference to theSpecification clause/GTP/Drawing and a description of the alternative offer. In absence of sucha statement, requirements of the Specification shall be met without exception.307BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure AScope of supply1.0 The scope of supply shall include following1.1 Design, manufacture, assembly, testing at stages of manufacture as per Cl. 12 of thisspecification, final testing at manufacturer works on completely assembled transformerbefore dispatch, packing, transportation, delivery and submission of all documentationfor the Power transformer with all accessories as below and ratings & requirements asspecified in Annex C.Sr. No Description Scope of Supply1.0 Fully assembled transformer with all major parts likeconservator, Radiators, Marshalling box, Protectivedevices as per Clause 5.0 of this specification,Fittings and accessories as per Clause 6.0 of thisspecificationYES1.1 OLTC as per this specification YES1.2 RTCC panel as per this specification No1.3 HV, LV, LV NEUTRAL cable boxes YES1.4 Support steel material for support of cable boxesfrom groundYES1.5 Foundation Bolts for complete transformer YES1.6 Nickel Plated brass double compression weatherproof glands for HV and LV cablesNo1.7 Long barrel medium duty Aluminium lugs for powercablesYES1.8 Nickel Plated brass double compressionweatherproof glands and tinned copper lugs forcontrol cable termination in Marshalling box forvendor’s cablesYES1.9 Cables and wires for transformer accessories andinternal wiring of Marshalling boxYES1.10 Touch up paint, minimum 5 litres YES1.11 Extra Transformer oil 10 % in non returnable drums YES1.12 One spare complete set of gaskets YES308

Page 12: Tech Spec Ss -III

BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________1.13 One set ( 4 nos in a set) of anti rolling clamp for 90lb railYES1.14 Ordinary Thermometers 4 nos YES1.15 Recommended spares as per manufacturer YES1.16 Provision for mounting of NIFPS system YES2.0 Routine testing as per Cl. 12 of this specification YES3.0 Type testing as per Cl. 12 of this specification YES4.0 Special testing as per Cl. 12 of this specification YES5.0 Submission of Documentation as detailed below YES2.0 Submission of documentsSubmission of of drawings , calculations, catalogues, manuals, test reports shall be asfollowsAlong with offer For Approvalafter award ofcontractFinal afterapproval / *Aftercompletion ofdeliveryRemarksDrawings 3 copies (Typicaldrgs)4 copies 12 copies + 1soft copy in CDSee Clause 11for variousdrawingsrequiredCalculations 3 copies(Typical)4 copies 6 copies + 1 softcopy in CDSee Clause 11for detailsCatalogues 1 copy 12 copies + 1soft copy in CDInstructionmanual for thetransformer1 copy 12 copies + 1soft copy in CDType TestReport &Routine TestReport*2 copies (Typetest and sampleRoutine Test )12 copies + 1

Page 13: Tech Spec Ss -III

soft copy in CDRoutine TestReport3.0 Delivery schedule309BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________3.1 Delivery period start date - from date of purchase order3.2 Delivery period end date - as agreed with supplier3.3 Material dispatch clearance - after inspection by purchaser and writtendispatch clearances from purchaser310BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure BService Conditions2.0.0 Delhi Atmospheric conditionsa) Average grade atmosphere : Heavily polluted, dryb) Maximum altitude above sealevel1000 Mc) Ambient Air temperature Highest 50 deg C, Average 40 deg CDesign ambient air temperature 50 deg Cd) Relative Humidity 90 % Maxe) Seismic Zone 4f) Rainfall 750 mm concentrated in four months311BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure - CTechnical particulars (Data by purchaser)Sr No Description Data by purchaser1.0 Location of equipment OUTDOOR2.0 Reference designambient temperature40 deg C3.0 Type Oil immersed, core type, step down4.0 Type of cooling ONAN / ONAF( see note 1)5.0 Reference standard IS: 20266.0 No. of phases 37.0 No. of windings perphase28.0 Rated frequency ( Hz ) 50 Hz9.0 Rated voltage ( kV )9.1 HV winding 33 669.2 LV winding 11 1110.0 Vector Group Reference Dyn11 Dyn1111.0 Nominal ContinuousRating, MVA11.1 ONAN 20 2011.2 ONAF 25 2512.0 Impedance at Principal

Page 14: Tech Spec Ss -III

tap at rated frequencywith IS tolerance12 % (for 20 MVA)15% (for 25MVA)12 % (for 20 MVA)15% (for 25MVA)13.0 Maximum no load loss atrated condition allowedwithout any positivetolerance, kW12kW 12kW14.0 Maximum load loss atrated condition @ 75 degC and principal tapallowed without anypositive tolerance, kW85kW (for 25MVA) 85 kW (for 25MVA)15.0 Terminal connection /Cable / Conductor Size15.1 HV side 33 kV 66 kV312BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________By 2 runs of 3 C x 400 sq.mmA2XFY, 33 kV (E) grade cableBy Single / Double ACSR“ZEBRA” coductor perphase15.2 LV side By 3 runs of 1C x 1000 sqmm perphase A2XY unarmoured cable11 kV (E) grade cable3 runs of 1C x 1000sqmm per phase A2XYunarmoured cable 11 kV(E) grade cable15.3 LV neutral By G.S Strip minimum 2x 75 x 10mm sizeBy G.S Strip minimum 2x75 x 10 mm size16.0 Highest system voltageHV side, kV36 72.517.0 Highest system voltageLV side, kV12 1218.0 Lightning Impulsewithstand voltage , kVpeak18.1 For nominal systemvoltage of 11 kV7518.2 For nominal systemvoltage of 22 kV125

Page 15: Tech Spec Ss -III

18.3 For nominal systemvoltage of 33 kV17018.4 For nominal systemvoltage of 66 kV32518.0 Power FrequencyWithstand Voltage kVrms18.1 For nominal systemvoltage of 11 kV2818.2 For nominal systemvoltage of 22 kV5018.3 For nominal systemvoltage of 33 kV7018.4 For nominal systemvoltage of 66 kV14019.0 Clearances Phase toPhase , mm19.1 For nominal systemvoltage of 11 kV28019.2 For nominal systemvoltage of 22 kV330313BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________19.3 For nominal systemvoltage of 33 kV35019.4 For nominal systemvoltage of 66 kV70020.0 Clearances Phase toEarth , mm20.1 For nominal systemvoltage of 11 kV14020.2 For nominal systemvoltage of 22 kV23020.3 For nominal systemvoltage of 33 kV32020.4 For nominal systemvoltage of 66 kV66020.5 Ground clearance – Livepart to ground for 66kV -

Page 16: Tech Spec Ss -III

mm400021.0 System Fault Level , HVside1500 MVA for 33 kV3600 MVA for 66 kV22.0 System Fault Level , LVside500 MVA for 11 kV23.0 Short Circuit withstandCapacity of thetransformer23.1 Three phase dead shortcircuit at secondaryterminal with ratedvoltage maintained on theother sideFor 3 secs.23.2 Single phase short circuitat secondary terminalwith rated voltagemaintained on other sideFor 3 secs.24.0 System earthing24.1 HV Solidly earthed24.2 LV Solidly earthed25.0 Overload Capability As per IS 660026.0 Noise Level Shall not exceed limits as per NEMA TR-1 with all accessoriesrunning measured as per IEC 551 / NEMA standard27.0 Radio Influence Voltage Maximum 250 microvolt314BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________28.0 Harmonic suppression Transformer to be designed for suppression of 3rd, 5th, 7th

harmonic voltages and high frequency disturbances.29.0 Partial Discharge Transformer to be free from partial discharge upto 120 % ofrated voltage as the voltage is reduced from 150 % of ratedvoltage i.e. there shall be no significant rise above backgroundlevel30.0 Loss capitalizationformulaeAs per CBIP manual (see not 2)30.1 No load Losscapitalization figureRs. 4,09,979 per KW30.2 Load loss capitalizationfigureRs. 2,26,718 per KW30.3 Cooler Lossescapitalization figureRs. 85,000 per KW31.0 Temperature rise of top

Page 17: Tech Spec Ss -III

oil by thermometer40 deg C32.0 Temperature rise ofwinding by resistance45 deg C33.0 Note for the bidders (left blank)34.0 Tappings to be providedon HV winding for OLTC+ 5 % to –15 % @ step of 1.25 % 16 taps, 17 tap positions,Tap no.5 is principal tap35.0 Maximum flux densityallowed in the core atextreme over excitation /over fluxing1.9 Tesla36.0 Maximum current densityallowed at any tap3.0 A / sqmm.37.0 AVR input voltage / aux.supply( Not applicable )38.0 Bushing Parameters38.1 Rated current 1000A for 33kV bushing2000A for 11kV bushing38.2 Creepage factor for allbushing mm / KV31 mm / kV minimum38.3 Rated thermal short timecurrent for all bushing25 times rated current for 2 secs.38.4 Angle of mounting 0 to 90 degree38.5 Cantilever withstand load 1250N for 33kV bushing2000N for 11kV bushing38.6 Overall Length(Approx) 678mm for 33kV bushing503mm for 11kV bushing38.7 Diameter of base 100mm315BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Note 1 :For ONAN and ONAF rating the temperature rise of the transformer shall be within the valuesspecified at sl. No. 31.0 and 32.0 above. Under ONAF cooling 20% spare cooling fans shall beprovided. Design of cooling equipment and control shall comply to CBIP clause no. 2.1.3 ofSection A (general)Note 2 :The transformers will be evaluated against the losses guaranteed by the bidders withcapitalization of losses as per figures indicated under sl.no. 30.1, 30.2 and 30.3 above.However, the maximum loss figures acceptable are as per cl. 13.0 & 14.0 of Annexure C. In the

Page 18: Tech Spec Ss -III

event of measured loss figures during testing exceeding the guaranteed loss figures of thesuccessful bidder penalty shall be levied at a rate of 1.25 times the figures mentioned above forno load, load losses and cooler loss.316BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure – C1Technical Specification for transformer oilTransformer oil shall be new and conform to the following requirements:1.0 Codes & standardsLatest revision of following codes & standards with all amendments –Standard no Title1.1 IS 335 New insulating oils1.2 IS 1783 Drums for oils2.0 PropertiesThe insulating oil shall have following features:2.1 Appearance Clear, transparent and free from suspendedmatter or sediments2.2 Density at 29.50C Max. 0.89 g/cm3

2.3 Kinematics viscosity Max. 16 cSt at 270C11 cSt at 400C2.4 Interfacial tension at 270C, min 0.04 N/m2.5 Flash point Pensky-Marten (Closed),Min.1400C2.6 Pour Point, Max - 150C2.6 Neutralization valuei) Total acidity, Max. 0.03 mg KOH/gii) Inorganic acidity/ Alkalinity Nil2.7 Corrosive sulfur Non-corrosive2.8 Electric strength breakdown voltage Average value of six samplesi) New unfiltered oil. Min. 30 kV (rms) min.ii) After filtration Min. 60 kV (rms)2.9 Dielectric dissipation factor (tan δ) 0.002 at 90 0C, Max.0.0005 at 27 0C, Max2.10 Specific resistance (resistivity)i) At 900C, Min 150 X 1012 ohm-cmii) At 270C, Min 3000 X 1012 ohm-cm2.11 Oxidation stabilityi) Neutralization value after oxidation,Max.0.15 mg KOH/gii) Total sludge, after oxidation, Max. 0.03 % by weightiii) Max Tan delta at 70 0C 0.12.12 Ageing characteristics after acceleratedageing(open breaker method with copper catalyst)i) Specific resistance (resistivity)a) At 270C Min. 27 X 1012 ohm-cmb) At 900C Min 2 X 1012 ohm-cmii) Dielectric dissipation factor (tan δ) at 0.1317

Page 19: Tech Spec Ss -III

BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________900C Maxiii) Total acidity, Max 0.05 mg KOH/giv) Total sludge, Max 0.05 % by weight2.13 Presence of oxidation inhibitor no antioxidant additives2.14 Water content, Max 40 ppm2.15 Max PCA ( Poly cyclic aromatics)content3%2.16 PCB (Poly chlorinated biphenyl) content Not detectable2.17 Tests As per IS 335318BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure - DGuaranteed Technical Particulars (Data by Seller)Sr. Particulars Specified / Required Offered1.0 General1.1 Make1.2 Type As per Cl. 3.0 of Annexure C2.0 Nominal ContinuousRating, KVA2.1 ONAN As per Cl. 11.1 of Annexure C2.2 ONAF As per Cl. 11.2 of Annexure C3.0 Rated voltage ( kV )3.1 HV Winding As per Cl. 9.1 of Annexure C3.2 LV Winding As per Cl. 9.2 of Annexure C4.0 Rated current (Amps )4.1 HV Winding, ONAN/ ONAF4.2 LV Winding, ONAN /ONAF5.0 Connections5.1 HV Winding As per Cl. 10.0 of Annexure C5.2 LV Winding As per Cl. 10.0 of Annexure C5.3 Vector GroupreferenceAs per Cl. 10.0 of Annexure C6.0 Impedance atprincipal tap ratedcurrent andfrequency, %6.1 Impedance As per Cl. 12.0 of Annexure C6.2 Reactance6.3 Resistance6.4 Impedance at lowesttap rated currentand frequency, %6.5 Impedance athighest tap ratedcurrent and

Page 20: Tech Spec Ss -III

frequency, %7.0 Resistance of thewinding at 750 C ,atprincipal tap, ohm7.1 a) HV319BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________7.2 b) LV8.0 Zero sequenceimpedance, ohm8.1 a) HV8.2 b) LV9.0 Guaranteedmaximum lossesprincipal tap full loadand 75°C withoutany positivetolerance kW9.1 No load losses(max.)As per Cl. 13.0 of Annexure C9.2 Load losses (max.) As per Cl. 14.0 of Annexure C9.3 Cooler fan losses(max.)9.4 Total Isq R losses ofwindings @ 75 degC9.5 Total stray loses @75 deg C9.6 Total losses (max.)9.7 No load loss atmaximumpermissible voltageand frequency(approx.) kW10.0 Temperature riseover referencedesign ambient of40 deg C10.1 Top oil bythermometer 0 C40 0C10.2 Winding byresistance 0 C45 0C10.3 Winding Gradient atrated current , deg C10.3.1 HV10.3.2 LV11.0 Efficiency11.1 Efficiency at 750Cand unity powerfactor %

Page 21: Tech Spec Ss -III

11.1.1 at 110% load320BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________11.1.2 at 100% load11.1.3 at 80% load11.1.4 at 60% load11.1.5 at 40% load11.1.6 at 20% load11.2 Efficiency at 750Cand 0.8 power factorlag %11.2.1 at 110% load11.2.2 at 100% load11.2.3 at 80% load11.2.4 at 60% load11.2.5 at 40% load11.2.6 at 20% load11.3 Maximum efficiency%11.4 Load and powerfactor at which itoccurs12.0 Regulation , (%)12.1 Regulation at fullload at 750 C12.1.1 at unity power factor12.1.2 at 0.8 power factorlagging12.2 Regulation at 110%load at 750 C12.2.1 at unity power factor12.2.2 at 0.8 power factorlagging13.0 Tappings13.1 Type13.2 Capacity13.3 Range-steps x %variationAs per Cl. 34.0 of Annexure C13.3 Taps provided onHV winding (Yes /No)Yes.14.0 OLTC Gear14.1 Make14.2 Type14.3 Reference std14.4 No of compartment321BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________14.5 Mounting

Page 22: Tech Spec Ss -III

arrangementSide mounted14.6 Rated current, Amp 500A minimum for 33kV14.7 Rated step capacity,kVA14.8 Short circuitwithstand for 2 secs, kA14.9 Time required forone stepchange,sec.14.10 Rated voltage formotor, V AC14.11 Rating of motor14.12 Rated voltage forauxiliaries, V14.13 Consumption ofauxiliaries14.14 OLTC features asper specification ,YES/ NO14.15 Does the overloadrating of OLTCmatch with that ofthe transformerunder all conditions,(Yes/No)16.0 Cooling system -16.1 Type of cooling As per Cl. 4.0 of Annexure C16.2 No. of cooling unitGroups16.3 Capacity of coolingunits16.4 Mounting ofradiators16.5 Number of Radiators16.6 Type & size ofradiator headermain valve16.7 Type & size ofindividual radiatorvalve16.8 Total radiatingsurface , sqmm16.9 Thickness ofradiator tubes, mmMinimum 1.2 mm16.10 Schematic flowdiagram of the-322BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________cooling system

Page 23: Tech Spec Ss -III

furnished, (Yes/no)16.11 Number of coolerfans required forrated ONAF rating16.12 Number of standbycooler fansprovided.16.3 Capacity of eachcooler fan - kW16.4 Cooler fans ratedvoltage & variation16.5 Make of cooler fans17.0 Details of Tank17.1 Material Robust mild steel plate without pitting andlow carbon content17.2 Thickness of sidesmm17.3 Thickness of bottommm17.4 Thickness of covermm17.5 Confirmation ofTank designeddesigned and testedfor Vacuum,Pressure ( Ref:CBIP Manual ) ,(Yes/ No)17.5.1 Vacuum mmof Hg. / (kN/m2)As per CBIP17.5.2 Pressure mmof Hg.Twice the normal head of oil / normalpressure + 35kN/m2 whichever is lower,As per CBIP17.6 Is the tank lidsloped?Yes17.7 Inspection coverprovided (Yes / No)as per clause17.8 Location ofinspection cover(Yes / No)as per clause17.9 Min. dimensions ofinspection cover (provide list of allinspection coverwith dimension), mmx mm323BSES Bhawan, Nehru Place, New Delhi- 19

Page 24: Tech Spec Ss -III

Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________18.0 Core18.1 Type: Core18.2 Core material grade Premium grade minimum M4 or better18.3 Thickness oflamination mmMax. 0.27 mm with insulation coating onboth sides.18.4 Insulation oflaminationWith insulation coating on both sides ofthe laminations18.5 Design flux densityin the core at ratedcondition at principaltap, Tesla18.6 Maximum fluxdensity allowed inthe core at extremeoverexcitation/overfluxing, TeslaAs per Cl. 35.0 of Annexure C18.7 Equivalent crosssection area of core,mm²-18.8 Guaranteed NoLoad current at100% / 110 % ratedvoltage , Amps(Max)@ 100% - 0.5% of RFLC@ 110% - 1.0% of RFLC18.8.1 HV18.8.2 LV19.0 Type of Winding19.1 HV19.2 LV19.3 Conductor material Electrolytic Copper as per relevantstandard19.4 Maximum currentdensity allowed ,Amp per sqmmAs per Cl. 36.0 of Annexure C19.5 Gauge/area of crosssection of conductor,sqmm19.5.1 a) HV19.5.2 b) LV19.6 Maximum Currentdensity achieved inwinding, Amp persqmm19.7 Insulating material

Page 25: Tech Spec Ss -III

19.7.1 HV Turn19.7.2 LV Turn19.7.3 LV Core -324BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________19.7.4 HV - LV -19.8 Insulating materialthickness, mm19.8.1 HV Turn19.8.2 LV Turn -19.8.3 LV to Core19.8.4 HV to LV-20.0 Minimum designclearance, mm20.1 HV to earth in Air20.2 HV to earth in oil20.3 LV to earth in Air20.4 LV to earth in oil -20.5 Between HV & LV inAir20.6 Between HV & LV inoil20.7 Top winding andyoke-20.8 Bottom winding andyoke21.0 Insulating oil21.1 Quantity of oilLtrs-21.1.1 In the Transformertank21.1.2 In each radiator21.1.3 In OLTC chamber21.1.4 Total quantity21.2 10% excess oilfurnished?Yes21.3 Type of Oil New insulating oil as per BSESSpecification21.4 Oil preservationsystem provided(Yes / No)As per Clause 4.2.7 of the specification22.0 Bushing22.1 Make -22.2 Type22.3 Reference Standard22.4 Voltage class, kV22.4.1 HV side Bushing22.4.2 LV side line and

Page 26: Tech Spec Ss -III

neutral bushing22.5 Creepage factor forall bushing mm/KVAs per Cl. 38.0 of Annexure C325BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________22.6 Rated current, Amp.22.6.1 HV bushing22.6.2 LV line and neutralbushing22.7 Rated thermal shorttime current22.7.1 HV bushing As per Cl. 38.0 of Annexure C22.7.2 LV line and neutralbushingAs per Cl. 38.0 of Annexure C22.8 Weight, Kg22.8.1 HV bushing22.8.2 LV line and neutralbushing22.9 Free space requiredfor bushing removal,mm22.9.1 HV bushing22.9.2 LV line and neutralbushing23.0 Terminalconnections23.1 HV As per Cl. 15.1 of Annexure C23.2 LV As per Cl. 15.2 of Annexure C23.3 LV Neutral As per Cl. 15.3 of Annexure C24.0 H.V. Cable box /Terminals24.1 Suitable for cable /Conductor type ,sizeAs per Cl. 15.4 of Annexure C24.2 Termination height,mm1000 mm, minimum24.3 Gland Platedimension, mm xmm24.4 Gland Plate material Aluminium24.5 Gland PlateThickness, mm5 mm minimum24.5 Phase to clearanceinside box /terminals, mm24.6 Phase to earthinside box /terminals, mm

Page 27: Tech Spec Ss -III

25.0 L.V line side Cablebox25.1 Suitable for cabletype , sizeAs per Cl. 15.5 of Annexure C25.2 Termination height, 1000 mm, minimum326BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________mm25.3 Gland Platedimension, mm xmm25.4 Gland Plate material Aluminium25.5 Gland PlateThickness, mm5 mm minimum25.6 Phase to clearanceinside box, mm25.7 Phase to earthinside box, mm26.0 L.V neutral Cablebox26.1 Suitable for cabletype , sizeAs per Cl. 15.6 of Annexure C and foraccommodating NCT spec. as per Cl.4.2.9 of spec. and Cl. 28.0 Of AnnexureD26.2 Termination height,mm26.3 Gland Platedimension, mm xmm26.4 Gland Plate material Aluminium26.5 Gland PlateThickness, mm5 mm minimum26.5 Phase to clearanceinside box, mm26.6 Phase to earthinside box, mm27.0 Marshalling boxcubicle provided asper clause no ofspec. (Yes / No)27.1 Mounting ofMarshalling boxProject specific to be filled up ( Separate/tank mounted)28.0 Neutral CurrentTransformer (NCT)28.1 Type28.2 Make

Page 28: Tech Spec Ss -III

28.3 Reference Standard28.4 Neutral CT Ratio 33/11 kV 20/25MVA, Dyn1166/ 11 kV 20/25MVA, Dyn11Core 1 Core 2 Core 1 Core 21600 /1 A1600 /1 A1600 / 1A1600 / 1 A28.5 Burden, VA - 20 - 2028.6 Class of Accuracy PS 5P20 PS 5P20327BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________28.7 KPV, Volts,minimum40(Rct+8- 40(Rct+8-28.8 Resistance, ohm @75 deg C, maximum1.0 - 1.0 -28.9 Magnetizing current@ Vk/4, mA,maximum30 - 30 -28.10 Short time withstandcurrent26.3 kA for 3 sec.29.0 Winding CurrentTransformer (WCT)29.1 Type29.2 Make29.3 Reference Standard29.4 CT RatioHVLV33 / 11 kV,20/25 MVA ,66 / 11 kV, 20/25MVAAs perrequirementAs per requirement29.5 Burden, VA Manufacturer Std.29.6 Class of Accuracy Manufacturer Std.30.0 Pressure releasedevice

Page 29: Tech Spec Ss -III

30.1 Minimum pressurethe device is set torupture30.1.1 For Main Tank30.1.2 For OLTC31.0 Alarm and Tripcontact ratings ofprotective devices31.1 Rated / making/breaking currents ,Amp @ Voltage for31.1.1 PRV for main Tank31.1.2 PRV for OLTC31.1.3 Buchholz Relay31.1.4 Oil Surge relay forOLTC31.1.5 Sudden PressureRelay31.1.6 OTI31.1.7 WTI31.1.8 Magnetic Oil Gauge32.0 Fittings AccessoriesEach Transformer328BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________furnished as perClause No. (Biddershall attach separatesheet giving details,make and bill ofmaterials)33.0 Painting: as perclause for thetransformer, cableboxes, radiator,Marshalling box etc(Yes/No)34.0 Over all transformerdimensions20/25 MVA34.1 Length, mm 6.5 metres maximum34.2 Breadth, mm 5.0 metres maximum34.3 Height, mm 5.0 metres maximum35.0 Transformer TankDimensions35.1 Length, mm35.2 Breadth, mm35.3 Height, mm36.0 Marshalling Boxdimensions36.1 Length, mm36.2 Breadth, mm36.3 Height, mm

Page 30: Tech Spec Ss -III

37.0 Weight data37.1 Core, kG37.2 Frame parts, kG37.3 Core and frame, kG37.4 Total Winding, kG37.5 Core , Frame,Winding, kG37.6 Tank, kG37.7 Tank lid, kG37.8 Empty conservatortank, kG37.9 Each radiator empty,kG37.10 Total weight of allradiators empty, kG37.11 Weight of oil inTank, kG37.12 Weight of oil inConservator, kG329BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________37.13 Weight of oil in eachRadiators, kG37.14 Total weight of oil inRadiators, kG37.15 OLTC gear includingoil, kG-37.16 Total Transportweight of thetransformer, kG37.17 Total weight of thetransformer withOLTC and allaccessories38.0 Volume Data38.1 Volume of oil inmain tank, litres38.2 Volume of oilbetween highest andlowest levels of mainconservator, litres38.3 Volume of oilbetween highest andlowest levels ofOLTC conservator,litres38.4 Volume of oil ineach radiator, litres38.5 Total volume of oil inradiators, litres38.6 Volume of oil inOLTC, litres

Page 31: Tech Spec Ss -III

38.7 Transformer total oilvolume, litres39.0 Shipping Data39.1 Weight of heaviestpackage, kG39.2 Dimensions of thelargest package (L xB x H) mm40.3 Tests40.1 All in process testsconfirmed as per Cl.(Yes/ No)40.2 All Type Testsconfirmed as per Cl.(Yes / No)40.3 All Routine Testsconfirmed as per Cl.330BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________(Yes/ No)40.4 All Special Testsconfirmed as per Cl.(Yes/ No)331BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure E - Guaranteed Technical Particulars of Transformer OilBidder to submit hard copy duly filled & signed along with techno commercial offer.Bidder to submit separate GTP for each type of insulating oil –Sr No Item description Specification requirement Data by Vendor1 Manufacturer Name1.1 Address1.2 Contact person1.3 Contact telephone no2 Appearance of oil Clear, transparent and freefrom suspended matter orsedimentsYes / No3 Density at 29.50C Max. 0.89 g/cm3

4 Kinematics viscosity Max. 16 cSt at 270C11 cSt at 400C5 Interfacial tension at 270C 0.04 N/m min6 Flash point Pensky-Marten(Closed), Min.1400C7 Pour Point, Max - 150C8 Neutralization valuei) Total acidity, Max. 0.03 mg KOH/gii) Inorganic acidity/ Alkalinity Nil9 Corrosive sulfur Non-corrosive10 Electric strength breakdown

Page 32: Tech Spec Ss -III

voltageAverage value of six samplesi) New unfiltered oil. Min. 30 kV (rms) min.ii) After filtration Min. 60 kV (rms)11 Dielectric dissipation factor(tan δ).0.002 at 900C, Max0.0005 at 270C, Max12 Specific resistance (resistivity)i) At 900C, Min 150 X 1012 ohm-cmii) At 270C, Min 3000 X 1012 ohm-cm13 Oxidation stabilityi) Neutralization value afteroxidation, Max.0.15 mg KOH/gii) Total sludge, afteroxidation, Max.0.03 % by weightiii) Max Tan delta 0.1 at 700C14 Ageing characteristics afteraccelerated ageing(open breaker method withcopper catalyst)i) Specific resistance(resistivity)a) At 270C Min. 27 X 1012 ohm-cmb) At 900C Min 2 X 1012 ohm-cmii) Dielectric dissipation factor(tan δ)0.10 at 900C Max332BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Sr No Item description Specification requirement Data by Vendoriii) Total acidity, Max 0.05 mg KOH/giv) Total sludge, Max 0.05 % by weight15 Presence of oxidationinhibitorno antioxidant additives16 Water content, Max 40 ppm17 List of clients To be enclosed18 PCA content 3% max19 PCB content Not detectable333BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification For Power Transformer__________________________________________________________________________________________Annexure FRecommended spares (Data by supplier)List of recommended spares as following –Sr No Description of spare part Unit Quantity1 No2 No3

Page 33: Tech Spec Ss -III

4567334

Specification forLighting High MastSpecification no – GN101-03-SP-33-00Prepared by Reviewed by Approved by Rev No. DateName Sign Name Sign Name SignRishabhLohiyaGauravSharmaDevendraSharma00 04.01.2012335

GN101-03-SP-33-001.0 Scope of supplyThis specification covers the requirement of design, manufacture and testing of 12M, 16M and 20Mhigh mast along with accessories and requisite hardware. The scope also includes erection,installation and associated civil work like foundation etc.2.0 Codes & StandardsAll standards, specifications, and codes of practice referred to herein shall be the latest editionincluding all applicable official amendments and revisions as applicable.IS: 5 1994 Colour for ready mixed paints and enamels.IS:694 1990 PVC insulated cables for working voltages upto and including1100V.IS:800 1984 Code of practice for general construction in steel.IS:8021978Part-2Code of practice for use of structural steel in Overheadtransmission line towers. Part-2 Fabrication, galvanising,inspection and packing.IS: 875 1987Part-3Code of practice for design loads(other than earthquake) forbuildings and structures: Wind loadsIS:2062 1992 Steel for general structural purposes.IS: 2551 1982 Danger notice plates.IS:2629 1985 Recommended practice for hot dip galvanising on iron andsteel.IS :2633 1986 Methods for testing uniformity of coating of zinc coatedarticles.IS :3961 1967Part-2Recommended current ratings for PVC insulated cables. Part-

Page 34: Tech Spec Ss -III

2: PVC insulated and PVC sheathed heavy duty cables.IS :5133 1969Part-1Boxes for enclosure of electrical accessories-Part-1: steel and cast iron boxes.IS: 5831 1984 PVC insulation and sheath of electric cables.IS :8130 1984 Conductors for insulated electric cables and flexible cords.IS :10810 1984 Method of tests for cables.IS:13703 1993Part-1Low voltage fuses for voltages not exceeding 1000V AC or1500V DC .Part-1:General requirementsIS:13703 1993Part-2Low voltage fuses for voltages not exceeding 1000V AC or1500V DC .Part-2:Supplementary requirements for fuses forindustrial applicationsBS EN10-027(part-1)1992 Designation systems for steel: steel names, principal symbolsBS EN10-027(part-2)1992 Designation systems for steel: steel numbersBS 5135 National Electrical Code.BS-EN10-027 Indian Electricity rules(relevant safety regulation of CEA) andacts336

GN101-03-SP-33-003.0 Service ConditionsEquipment to be supplied against this specification shall be suitable for satisfactory continuousoperation under the following tropical conditions.Maximum Ambient Temperature (Degree C) 50Maximum temperature in shade (Degree C) 45Min. Temperature of Air in Shade (Degree C) -10Relative Humidity (Percent) 10 To 100Maximum annual rain fall (mm) 1450Maximum Wind pressure (Kg/Sq. M.) 150Maximum altitude above mean sea level (Meters) 3000lsoceranic level (days per year) 50Seismic level (Horizontal Acceleration)Moderately hot and humid tropical climateconducive to rust and fungus growth 0.3g4.0 Technical Requirement4.1. StructureThe High mast shall be of continuously tapered, galvanised polygonal cross section, at least20 sided, presenting a good and pleasing appearance, based on proven In-Tension design,conforming to the standards referred to above, to give an assured performance, and reliable

Page 35: Tech Spec Ss -III

service. The structure shall be suitable for wind loading as per IS - 875 Part -III, 1987.4.2. ConstructionThe mast shall be fabricated from special steel plates, conforming to BS-EN10-027, cut andfolded to form a polygonal section and telescopically jointed and welded. The welding shallbe in accordance with BS-5135. The sections are joined together by slip-stressed-fitmethod. No site welding shall be done. Only bolted joint shall be done on the mast at thesite. The minimum over lap distance shall be 1.5 times the diameter at penetration. Thedimensions of the mast shall be decided based on proper design and accordingly designcalculations shall be submitted for review / approval.The mast shall be provided with fully penetrated flange, free from any lamination orincursion. The welded connection of the base flange shall be fully developed to the strength337

GN101-03-SP-33-00of the entire section. The base flange shall be provided with supplementary gussetsbetween the bolt holes to ensure elimination of helical stress concentration. The entirefabricated mast shall be hot dip galvanised both internally and externally.4.3. Door OpeningAn adequate door opening shall be provided at the base of the mast and the opening shallbe such that it permits clear access to equipment like winches, cables, plug and socket, etc.and also facilitate easy removal of the winch. The door opening shall be complete with aclose fitting, vandal resistant, weatherproof door, provided with a heavy-duty double internallock with special paddle key.4.4. Dynamic Loading for the MastThe mast structure shall designed as per TR No-7 of Institutions of lightning engineers ofUK and shall be suitable to sustain maximum reaction arising from a wind speed as per IS-875 (three second gust), and is measured at a height of 10 meters above ground level.4.5. Lantern CarriageA fabricated Lantern Carriage shall be provided for fixing and holding the flood light fittingsand control gear boxes. The lantern Carriage shall be of special design and shall be ofsteel tube construction, the tubes acting as conduits for wires, with holes fully protected bygrommets. (The lantern carriage tube should not be used as conduit. Separate flexible

Page 36: Tech Spec Ss -III

conduits are used from CG Boxes to the Flood Light Fixtures) The Lantern Carriage shallbe designed and fabricated to hold the required number of flood light fittings and the controlgear boxes, and also have a perfect self balance.The Lantern Carriage shall be fabricated in two halves and joined by bolted flanges withstainless steel bolts and plastic lock type stainless steel nuts to enable easy installation orremoval from the erected mast. The inner lining of the carriage shall be provided withprotective PVC arrangement, so that no damage is caused to the surface of the mast duringthe raising and lowering operation of the carriage. The entire Lantern Carriage is hot dipgalvanised after fabrication.4.6. Junction BoxThe junction box shall be cast aluminium or SS, weather proof IP67 junction box. It shall beprovided on the Carriage Assembly as required, from which the inter-connections to thedesigned number of the flood light luminaries and associated control gears fixed on thecarriage, is made.338

GN101-03-SP-33-004.7. Raising and lowering mechanismIt will be necessary to lower and raise the Lantern Carriage Assembly to install and maintainthe luminaries and lamps. To enable this, a suitable Winch Arrangement shall be provided,with the winch fixed at the base of the mast and the specially designed head frameassembly at the top.4.8. WinchThe winch shall be of completely self-sustaining type, without the need for brake, shoe,springs or clutches. Each driving spindle of the winch is positively locked when not in use.Individual drum also should be operated for the fine adjustment of lantern carriage. Thecapacity, operating speed, safe working load, recommended lubrication and serial numberof the winch shall be clearly marked on each winch.The gear ratio of the winch shall be 53 : 1 or as recommended by manufacturer. However,the minimum working load shall not be less than 750 kg. The winch shall be self-lubricatingtype by means of an oil bath and the oil shall be readily available grades of reputedmanufacturers and details of the oil shall be furnished.The winch drums shall be grooved to ensure perfect seat for stable and tidy rope lay, with

Page 37: Tech Spec Ss -III

no chances of rope slippage. The rope termination in the winch shall be such that distortionor twisting is eliminated and at least 5 to 6 turns of rope remains on the drum even when thelantern carriage is fully lowered and rested on the rest pads. It should be possible to operatethe winch manually by a suitable handle and/or by an external power tool. It would bepossible to remove the double drum after dismantling, through the door opening provided atthe base of the mast. Also, a winch gearbox for simultaneous and reversible operation ofthe double drum winch shall be provided as part of the contract.The winch shall be type tested in a reputed test lab/ Institution and the test certificates shallbe furnished before supply of materials. Test certificate shall be furnished by the bidderfrom the original equipment manufacturer, for each winch in support of the maximum loadoperated by the winch.4.9. Head FrameThe head frame, which is to be designed, as a capping unit of the mast, shall be of weldedsteel construction, galvanised both internally and externally after assembly. The top pulleyshall be of appropriate diameter, large enough to accommodate the stainless steel wireropes and the multi-core electric cable. The pulley block shall be made of corrosionresistant material, and is of the cast Aluminium Alloy (LM-6) or SS. Pulley made of339

GN101-03-SP-33-00synthetic materials such as Plastic or PVC is not acceptable. Self-lubricating bearings andstainless steel shaft shall be provided to facilitate smooth and maintenance free operationfor a long period. The pulley assembly shall be fully protected by a canopy galvanisedinternally and externally.Close fitting guides and sleeves shall be provided to ensure that the ropes and cables donot dislodge from their respective position in the grooves. The head frame shall beprovided with guides and stops with PVC buffer for docking the lantern carriage.4.10 Stainless Steel Wire RopesThe suspension system shall essentially be without any intermediate joint and shall consistof only non-corrodable stainless steel of AISI - 316 or better grade.The stainless steel wire ropes shall be of 7/19 construction, the central core being of thesame material. The overall diameter of the rope shall be more than 6 mm keeping in mind

Page 38: Tech Spec Ss -III

contingency. The breaking load of each rope shall not be less than 2350 kg. The designshall have a factor of safety over 5 for the system at full load. The end constructions ofropes to the winch drum shall be fitted with talurit.The thimbles are secured on ropes by compression splices. Two continuous lengths ofstainless steel wire ropes are used in the system and no intermediate joints are acceptablein view of the required safety. No intermediate joints, either bolted or else, shall be providedon the wire ropes between winch and lantern carriage.4.11 Electrical System, Cable and Cable ConnectionsA suitable terminal box shall be provided as part of the supply at the base compartment ofthe high mast for terminating the incoming cable. The electrical connections from thebottom to the top shall be made by special trailing cable. The cable is EPR insulated andPCP sheathed to get flexibility and endurance. Size of the cable is minimum 5 core 2.5 sqmm copper, in case of failure of any core 2 spare cores shall be available. The cable shallbe of reputed make. At the top necessary weatherproof junction box to terminate thetrailing cable shall be provided. Connections from the top junction box to the individualluminaries is made by using 3 core 1.5 sq mm flexible PVC cables of reputed make. Thesystem shall have in built facilities for testing the luminaries while in lowered position.Also, suitable provision shall be made at the base compartment of the mast to facilitate theoperation of externally mounted, electrically operated power tool for raising and lowering ofthe lantern carriage assembly. The trailing cables of the lantern carriage rings shall beterminated by means of specially designed, metal clad, multi pin plug and socket providedin the base compartment to enable easy disconnection when required.340

GN101-03-SP-33-004.12 Power Tool for the WinchA suitable, high-powered, electrically driven, externally mounted power tool, with manualover ride, together with an operating stand shall be supplied for the raising and lowering ofthe lantern carriage for maintenance purposes. The speed of the power tool may preferablyof slow speed, of 1.5 to 1.8 m/minute, so that vibrations associated with high speedoperation are avoided. The power tool shall be single speed, provided with a motor of the

Page 39: Tech Spec Ss -III

required rating, suitable for hand/stand operation. The power tool shall be suppliedcomplete with push button type remote control switch, together with 6 (six) meters of powercable, so that the operations can be carried out from a safe distance of 5 (five) meters. Thecapacity and speed of the electric motor used in the power tool shall be suitable for thelifting of the design load installed on the lantern carriage.The power tool stand shall be so designed that it will not only be self-supporting but alsoaligns the power tool perfectly with respect to the winch spindle during the operations. Also,a handle for the manual operation of the winches in case of problems with the electricallyoperated tool shall be provided and shall incorporate a torque-limiting device.A separate torque-limiting device to protect the wire ropes from over stretching shall beprovided. It shall be mechanical with suitable load adjusting device. The torque limiter is arequirement as per the relevant standards in view of the overall safety of the system.4.13 Lightning FinialOne number heavy-duty hot dip galvanised lightning finial shall be provided for each mast.The lightning finial shall be minimum 1.2 m in length and shall be provided at the centre ofthe head frame. It shall be bolted solidly to the head frame to get a direct conducting pathto the earth through the mast. The lightning finial shall not be provided on the lanterncarriage under any circumstances in view of safety of the system.4.14 Aviation Obstruction Lights:Based on site and project specific requirements, 2 nos. Low Intensity Type-B (as per Table6.3 of Volume-1, Annexure-14 of ICAO Guideline for Aerodrome Design & Operations) LEDtype aviation obstruction lights of reliable design and reputed manufacturer shall beprovided on top of each mast.341

GN101-03-SP-33-004.15 Earthing Terminals:Suitable earth terminal pad using twin 12 mm diameter stainless steel bolts shall beprovided at a convenient location on the base of the Mast, for lighting and electrical earthingof the mast.4.16 Luminaries:The 400 W non-integral floodlight luminaries with HPSV lamp shall be provided with eachmast. Optical compartment of the luminary shall be IP 66 and control gear compartment

Page 40: Tech Spec Ss -III

shall be IP 54 or better. Bajaj, Crompton and Philips make luminaries are approved.Detailed technical brochure shall be provided along with the bid.4.17 Feeder Pillar:Feeder pillar required for feeding power to the Lighting mast shall also be supplied alongwith the mast and its accessories. The feeder pillar is fed from the main switchgear / mainlighting distribution board. The outgoings of this feeder pillar are connected to the MCBs inthe mast. The feeder pillar shall be FLP or WP IP 54 with rain protection canopy ingalvanised CRCA sheet or cast Aluminium body (for FLP) and finished with two coats ofepoxy primer and grey enamel paint of shade 631 of IS-5. The feeder Pillar shall compriseof incoming 32 Amp TPN switch, HRC fuses, outgoing 25 Amp SP MCB, Time switch andcontactor for automatic on & off of circuit with manual override, TP MCB for power toolcontactors for reversing the motor and overload Protection of motor. Feeder pillar shall bemounted on suitable foundation near to the mast.5.0 TestsAll type test certificates for the tests listed in the relevant standards, conducted onidentical masts shall be submitted to BSES for approval. Routine tests & acceptance tests asper relevant IS shall be conducted as per approved Quality Plan.6.0 Marking / Name PlateThe high mast shall be provided with “BSES” insignia with anodized aluminium plate.Anodized plate showing 24X7 customer care number shall also be provided. Name plateshall include manufacturer name, date of manufacturing, warranty period and other detailsas per standards.342

GN101-03-SP-33-00Annexure A: Guaranteed Technical ParametersSl. No. Particulars Data by purchaser Data by seller1 Name and address ofmanufacturer2 Overall height of highmast12 mtrs 16 mtrs 20 mtrs2.1 Make2.2 Material ofconstruction of shaftGrade S355 J O as per BSEN 10025 orequivalent2.2 Cross section of mast 20 sided, regular continuously taperedpolygonal2.3 Number of sections One Two Two2.3

Page 41: Tech Spec Ss -III

Minimum thickness ofshaft (mm)4 mm Bottom section:5 mmTop section:4mmBottomsection: 5mmTop section:4mm2.4 Length of individualsection (mm)12000 mm 10900mm /5850mm10375mm /10375mm2.5Minimum Base and topdiameter340mm (A/F)and 150 mm(A/F)450mm (A/F)and 150 mm(A/F)500mm (A/F)and 150 mm(A/F)2.6Type of joints No sitejoints, mastshould bedelivered ina singlesectionTelescopic slipjoint, stressfittedTelescopicslip joint,stress fitted2.7 Length of overlap N/A 750mm 750mm2.8Metal protectiontreatment of fabricatedmast sectionHot dip galvanization through single dippingprocess2.9 Thickness ofgalvanizationsMinimum 85 microns as per IS:26292.10 Size of opening door atbase

Page 42: Tech Spec Ss -III

Approx. 250 X 1200 mm2.11Type of lockingarrangement and doorconstructionAnti vandal type2.12 Details of struck boardinsideInsulated base board2.13Size , material andthickness of cabletermination box2.14 Minimum size of baseplate diameter540 mm(min.)650 mm (min.) 680 mm(min.)2.15 Minimum size of baseplate thickness25 mm thick2.16 Minimum size ofanchor plate thickness8 mm2.17 Details of template Same as anchor plate but 2 mm thick343

GN101-03-SP-33-00Sl. No. Particulars Data by purchaser Data by seller3 Dynamic loading asprevailing at site3.1maximum windpressure (basic windspeed)47m/s as per IS:875, p-33.2 Maximum gust speedtime3 seconds3.3Height above groundlevel at which windspeed is consider10 mtrs3.4 Factor of safety forwind load1.253.5 Factor of safety forother load1.153.6 Application standardfor mast designTechnical report #7:2000 by ILE, UK4 Foundation details

Page 43: Tech Spec Ss -III

4.1 Type of foundation Open raft shallow footing or pile as applicable4.2 Size of foundation as per design conforming to IS:4564.3 Design safety factor 24.4 Considered windspeed180 m /s4.5 Depth of foundation As per requirement of design4.6 Average soil bearingcapacityAs per site condition4.7 Numbers of foundationbolts6 nos 8 nos4.8 PCD of foundationbolts440 mm (min.) 550 mm(min.)600 mm(min.)4.9 Type of foundation bolt Tor steel4.10 Bolt diameter / length 25mm dia / 750mm32mm dia /1325 mm40mm dia /1375 mm5 Lantern Carriage5.1Diameter of CarriageRingSuitable tocarry up to 4nos. floodlights1200 mm 1200 mm5.2Construction MS Channels /Tube, Hot dipgalvanizedChannels75X40X4mmthickChannels75X40X4mmthick5.3Number of joints As permanufacturer'sstandarddesign(2 segments asper Cl no.4.5)3 segments(2 segmentsas per Cl

Page 44: Tech Spec Ss -III

no.4.5)3 segments(2 segmentsas per Clno.4.5)5.4Buffer arrangementbetween carriage andmastRubber padded guide ring provided344

GN101-03-SP-33-00Sl. No. Particulars Data by purchaser Data by seller5.5 Load carrying capacity 500 kg 750 kg 750 kg5.6 Total weight ofassembly with fittingas per design6Winch6.1Make of winch6.2 Number of drums/winchDouble drum6.5 Gear Ratio6.3 Capacity SWL 500 kg SWL 750 kg6.4 Method of operation Manual / power tool6.6 Operating speed6.7 Lubricant Arrangement Permanent oil bath6.8 Type of lubricant6.9 Material ofconstruction of gearPhosphorus Bronze / EN 196.10 Tested load per drum 500 kg 750 kg6.11 SWL of winch at 410rpm500 kg SWL 750 kg SWL7 Wire rope7.1 Make7.2 Grade AISI 3167.3Number of ropes 3 nos / 5mm(three wirerope)3 nos / 6 mm (three wirerope)7.4 Construction 7./197.5 Diameter of Wire rope 5mm 6mm7.6 Factor of safety Not less than 5 Not less than 67.7 Breaking capacity Minimum 2350Kgs. X 28 Cable8.1 Type EPR coated PCP sheathed8.2 Material Multicore copper conductor8.3 Make Finolex, torrent, Polycab, KEI, Havells

Page 45: Tech Spec Ss -III

8.4 Current carryingcapacityAs per IS 9968 (Part - 1), 19988.5 conductor size 5CX2.5 sqmm.9 Torque limiter9.1 Lifting capacity Upto 500 kg Upto 750 kg9.2 Adjustable / nonadjustableAdjustable10 Lantern and Fixture10.1 Type Of Lamp HPSV, Asymetrical IP65 fitting10.1.1 Wattage 400W10.1.2 Make10.1.3 Model Number10.2 Housing Single piece gravity die-cast10.2.1 Material Aluminium alloy: LM6345

GN101-03-SP-33-00Sl. No. Particulars Data by purchaser Data by seller10.2.2 Ingress protection10.2.3 For opticalcompartmentIP:65/IP:6610.2.4 For control gearcompartmentIP:54 or better10.2.5 Dimensions of lantern As per design standard10.2.6 Weight of lantern withcontrol gearAs per design standard10.3 Lamp Cover Perspex/Toughened glass10.3.1 Toughened glass10.3.2 Class of glass AA/SSQ10.3.3 Nominal thickness 5mm10.3.4 Perspex thickness 2.5mm+/-0.4 mm10.4 Material of gasket Slicon Rubber/ Neoprene10.5 Lamp holder Screw type/three pin type10.5.1 Material Porcelain10.6 Ballast Conventional/Open type/ VI/VPI10.6.1 Ballast voltage 240V AC10.6.2 Minimum open circuitvoltage198V10.6.3 Frequency 50 Hz10.6.4 Current output(A), atrated voltage10.6.5 Voltage to currentratio ( ) +/-0.5%10.6.6 Watt loss ( W ) To be specified10.7 Power factor oflanternMore than 0.95 lag10.7.1 Value of capacitor To be specified10.8 Igniter Three wire

Page 46: Tech Spec Ss -III

10.9 Reflector Anodised/POT10.9.1 Angle of tilt of lamp To be specified10.9.2 Downward light outputratioMore than 70%10.9.3 Angle of throw As per clause 5.12.510.9.4 Angle of spread As per clause 5.12.610.9.5Luminous intensity inC = 0°plane at γ = 90°Less than 10 Cd/klm10.9.6Luminous intensity inC = 0°plane at γ = 80°Less than 30 Cd/klm10.10Make of fixture Bajaj, GE, Philips and CGL10.10.1 Nos of fixture providedwith high mast 4 5 6346

GN101-03-SP-33-00Sl. No. Particulars Data by purchaser Data by seller10.10.2 Type of fixture Weather proof11 Others11.1Make of 24 hourDifferential TimerSwitchLegrand/ GE/ Schnider/ L&T11.2 Make of 32A TPNMCBGE/ Hager/ Legrand/ Schnider11.3 Make of 32A Contactor L&T/ Schnider/ GE11.4 Earth pit Two numbers of treated earth pit with eachmast12 GTP and DrawingSubmittedYes/No13 Type Tests Submitted Yes/ No14 Technical Brochure ofluminaries submittedYES / NO15Operation andmaintenance manualsubmittedYES / NO347BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Tanu Srivastava Rev: 0Reviewed by Meenakshi Date: 07.02.2014Approved by Kiran K Alla

Page 47: Tech Spec Ss -III

TECHNICAL SPECIFICATIONFORNITROGEN INJECTION FIRE PROTECTION348BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection System1.0.0 SUPPLY AND SCOPE WORK1.1.0 Design, manufacture, testing of the assembled system at manufacturer’s works beforedispatch, packing and supply at site, erection and commissioning of the NitrogenInjection Fire Protection system1.2.0 Any modifications if required for installation of Nitrogen Injection Fire Protection systemon existing power transformer of various rating ranging from 10MVA to 25MVA shall be inscope of bidder. All material, tools, tackles, hardware, testing equipments and manpowerrequired for the modification shall be in scope of bidder except for any type of civil work likefire wall, soak pit etc. Bidder if feels shall conduct physical survey of the powertransformer to check feasibility and quantum of work involved.2.0.0 INTRODUCTIONNitrogen Injection Fire Protection System (NIFPS) shall use nitrogen as fire quenchingmedium. The protective system shall prevent transformer / Reactor oil tank explosion andpossible fire in case of internal faults. In the event of fire by external causes such asbushing fire, OLTC fires, fire from surrounding equipment etc, it shall act as a fast andeffective fire fighter without any manual intervention. It shall accomplish its role as firepreventer and extinguisher without employing water and / or carbon dioxide. Fire shall beextinguished within 3 minutes (Maximum) of system activation and within 30 seconds(maximum) of commencement of nitrogen injection.3.0.0 APPLICABLE CODES AND STANDARDSThe design and installation of the complete fire protection system shall comply with the latestapplicable Indian standardsa) IS 10028 (Part II) : Code of practice for selection, installation, and maintenance oftransformerb) Tariff Advisory Committee : Regulations for the electrical equipment of buildingsc) National fire Codes 1993 of National Fire Protection Association (NFPA) USAd) Central Electricity Authority, The Gazette of India, Extraordinary 2010 :Safety provisions for electrical installations and apparatus of voltage exceeding 650V4.0.0 ACTIVATION OF THE FIRE PROTECTIVE SYSTEMMal-functioning of fire prevention / extinguishing system could lead to interruption in powersupply. The supplier shall ensure that the probability of chances of malfunctioning of the fireprotective system is practically zero. To achieve this objective, the supplier shall plan out hisscheme of activating signals which should not be too complicated to make the fire protectivesystem inoperative in case of actual need and should not be dependent on auxiliary power349BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection Systemsource. The system shall be provided with automatic control for fire prevention and fireextinction without any manual intervention. Besides automatic control, remote electrical pushbutton control at Control box and local manual control in the fire extinguishing cubicle shallalso be provided. The following electrical-signals shall be required for activating the fireprotective system under prevention mode / fire extinguishing mode.4.1.0 Auto Mode4.1.1 For prevention of fire :Differential relay operation + Buchholz relay paralleled with pressure relief valve or RPRR(Rapid Pressure Rise Relay) + Tripping of all or one circuit breakers (on HV & LV/IV side)associated with transformer / reactor is the pre-requisite for activation of system. The system

Page 48: Tech Spec Ss -III

shall have sufficient Input modules.4.1.2 For extinguishing fire :Fire detector + Buchholz relay paralleled with pressure relief valve (PRV) or suddenpressure relay (SPR) + tripping of all circuit breakers (on HV & LV/IV side) associated withtransformer / reactor is the pre-requisite for activation of system.4.2.0 Manual Mode (Local / Remote electrical)Tripping of all circuit breakers (on HV & LV/IV side) associated with transformer/reactor is thepre-requisite for activation of system.4.3.0 Manual Mode (Mechanical)Tripping of all circuit breakers (on HV & LV/IV side) associated with transformer /Reactor is the pre-requisite for activation of system.The system shall be designed to be operated manually in case of failure of powersupply to fire protection system.5.0.0 GENERAL DESCRIPTIONNitrogen injection fire protection system should be a dedicated system for eachoil filled transformer / reactor. It should have a Fire Extinguishing Cubicle (FEC)placed on a plinth at 5-7m away (as per statutory requirement) from transformer /reactor or placed next to the fire wall if fire wall exists. The FEC shall be connected to the topof transformer / reactor oil tank for depressurization of tank and to the oilpit as per Indian standard and CBIP from its bottom through oil pipes. The fireextinguishing cubicle should house a pressurized nitrogen cylinder(s) which isconnected to the oil tank of transformer/reactor oil tank at bottom. The TransformerConservator Isolation Valve (TCIV) is fitted between the conservator tank andBuchholz relay.Cable connections are to be provided from signal box to the control box in the control room,control box to fire extinguishing cubicle, TCIV to signal box and any other wiring to ensureproper functioning of the fire protection system. Fire detectors placed on the top of350BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection Systemtransformer/reactor tank are to be connected in parallel to the signal box by Fire survivalcables. Control box is also to be connected to relay panel in control room for receivingsystem activation signals. All panel or control equipments shall be fire proof so as to ensurethat they do not fail themselves in event of fire.6.0.0 OPERATIONOn receipt of all activating signals, the system shall drain pre-determined volume ofhot oil from the top of tank (i.e top oil layer), through outlet valve, to reduce tankpressure by removing top oil and simultaneously injecting nitrogen gas at highpressure for stirring the oil at pre-fixed rate and thus bringing the temperature of topoil layer down. Transformer conservator isolation valve blocks the flow of oil fromconservator tank in case of tank rupture / explosion or bushing bursting. Nitrogenoccupies the space created by oil drained out and acts as an insulating layer over oil in thetank and thus preventing aggravation of fire.7.0.0 SYSTEM COMPONENTSNitrogen injection fire protection system shall broadly consist of the following components.However, all other components which are necessary for fast reliable and effective working ofthe fire protective system shall be deemed to be included in the scope of supply.7.1.0 Fire Extinguishing Cubicle (FEC)The FEC shall be made of CRCA sheet of 3 mm (minimum) thick complete with thebase frame, painted inside and outside with post office red colour (shade 538 of IS-5).It shallhave hinged split doors fitted with high quality tamper proof lock. The degree of protectionshall be IP55. The following items shall be provided in the FEC.a. Nitrogen gas cylinder with regulator and falling pressure electrical contact manometerb. Oil drain pipe with mechanical quick drain valve.

Page 49: Tech Spec Ss -III

c. Control equipment for draining of oil of pre-determined volume and injecting regulatedvolume of nitrogen gasd. Pressure monitoring switch for back-up protection for nitrogen releasee. Limit switches for monitoring of the systemf. Butterfly valve with flanges on the top of panel for connecting oil drain pipe and nitrogeninjection pipes for transformer/reactorsg. Panel lighting (CFL Type)h. Oil drain pipe extension of suitable sizes for connecting pipes to oil pit.7.2.0 Control boxControl box is to be placed in the control room for monitoring system operation,automatic control and remote operation. Control supply will be 50/220VDC (15%tolerance) based on site requirement. The following alarms, indications, switches,351BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection Systempush buttons, audio signal etc. shall be provided.a. System onb. TCIV openc. Oil drain valve closedd. Gas inlet valve closede. TCIV closed*f. Fire detector trip *g. Buchholz relay triph. Oil drain valve open*i. Extinction in progress *j. Cylinder pressure low *k. Differential relay tripl. PRV / SPR tripm . Master relay of Transformer/reactor tripn. System out of service *o. Fault in cable connecting fault fire detectorp. Fault in cable connecting differential relayq. Fault in cable connecting Buchholz relayr. Fault in cable connecting PRV / SPRs. Fault in cable connecting transformer /reactor tript. Fault in cable connecting TCIVu. Auto/ Manual / Offv. Extinction release on / offw. Lamp testx. Visual/ Audio alarm*y. Visual/ Audio alarm for DC supply fail *Suitable provision shall be made in the control box, for monitoring of the system fromremote substation using the substation automation system.7.3.0 Transformer Conservator Isolation ValveTransformer conservator isolation valve (TCIV) to be fitted in the conservator pipeline,between conservator and buchholz relay which shall operate for isolating the conservatorduring abnormal flow of oil due to rupture / explosion of tank or bursting of bushing. Thevalve shall not isolate conservator during normal flow of oil during filtration or filling orrefilling, locking plates to be provided with handle for pad locking. It shall have proximityswitch for remote alarm and indication glass window for visual inspection for physicalchecking of the status of valve.The TCIV should be of the best quality as malfunctioning of TCIV could lead to seriousconsequence. The closing of TCIV means stoppage of breathing of transformer/reactor. Firesurvival cable connecting TCIV shall be terminated in transformer marshalling box.

Page 50: Tech Spec Ss -III

7.4.0 Fire detectors352BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection SystemThe system shall be complete with adequate number of fire detectors (quartz bulb)fitted on the top cover of the transformer / reactor oil tank. The system generates signal aftersensing higher temperature. The placing of fire detectors and numbers shall be designedand finalized by bidder as per requirement.7.5.0 Signal boxIt shall be mounted away from transformer / reactor main tank, preferably near thetransformer marshalling box, for terminating cable connections from TCIV & firedetectors and for further connection to the control box. The degree of protection shallbe IP55.7.6.0 CablesFire survival cables (capable to withstand 750° C.) of 4 core x 1.5 sq. mm size forconnection of fire detectors in parallel shall be used. The fire survival cable shallconform to BS 7629-1,BS 8434-1, BS 7629-1 and BS 5839-1,BS EN 50267-2-1 orrelevant Indian standards.Fire Retardant Low Smoke (FRLS) cable of 12 core x 1.5 sq. mm size shall be usedfor connection of signal box / marshalling box near transformer/reactor and FECmounted near transformer/reactor with control box mounted in control room.Fire Retardant Low Smoke (FRLS) cable of 4 core x 1.5 sq. mm size shall be used forconnection between control box to DC and AC supply source, fire extinguishingcubicle to AC supply source, signal box/ marshalling box to transformer conservator isolationvalve connection on transformer/reactor.7.7.0 PipesHeavy duty pipe connecting the transformer/reactor tank for oil rain, and for nitrogeninjection shall be provided. Pipes connecting oil tank laid underground, shall bepreferably be used for interconnection. Pipes, complete with connections, flanges,bends and tees etc. shall be supplied along with the system.7.8.0 Other items7.8.1 Oil drain and nitrogen injection openings with gate valves on transformer / reactor tank atsuitable locations.7.8.2 Flanges with dummy piece in conservator pipe between Buchholz relay and conservatorTank for fixing TCIV.7.8.3 Fire detector brackets on transformer / reactor tank top cover.7.8.4 Spare potential free contacts for activating the system i.e. in differential relay, Buchholzrelay, Pressure Relief Device / RPRR, Circuit Breaker of transformer/reactor7.8.5 Pipe connections between transformer / reactor and FEC and between FEC and oil pitrequired for collecting top oil.7.8.6 Cabling for fire detectors mounted on transformer /reactor top cover7.8.7 Inter cabling between signal box, control box and Fire Extinguishing Cubicle (FEC).353BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection SystemAll external cables from / to the system i.e. signal box to control box and control box to FECshall be provided by the purchaser. All internal cables within the system i.e.between detectors / signal box / marshalling box / FEC / TCIV shall be in the scope of NIFPSsupplier.7.8.8 Butterfly valves /Gate valves on oil drain pipe and nitrogen injection pipe which should beable to withstand full vacuum.7.8.9 Supports, signal box etc. which are to be painted with enamelled paint.

Page 51: Tech Spec Ss -III

The doors, removable covers and panels shall be gasketted all round with neoprenegaskets.8.0.0 MANDATORY SPARESCylinder filled with Nitrogen of requiredcapacity per substation1 No.Fire Detectors per transformer 3 No’s.Regulator assembly per sub-station 1 No.9.0.0 TESTSReports of all type test conducted as per relevant IS/IEC standards in respect ofvarious bought out items including test reports for degree of protection for FEC /control box / signal box shall be submitted by the supplier.The supplier shall demonstrate the functional test associated with the following:• Fire Extinguishing Cubicle, Control Box.• Fire Detector.• Transformer Conservator Isolation ValveThe performance test of the complete system shall be carried out after erection of the system withtransformer at site.10.0.0 DOCUMENTS TO BE SUBMITTED10.1.0 To be submitted along with offer10.1.1 General outline of the system.10.1.2 Detailed write-up on operation of the offered protection system including maintenanceand testing aspects / schedules.10.1.3 Technical Data particulars (GTP), the format of which is attached in Annexure A of thespecification10.1.4 Data regarding previous supplies, date of commissioning, performance feedback etc.10.1.5 Document related to Type test / proof of design as required by statutory body /electrical inspector10.2.0 To be submitted after award of contract:354BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Nitrogen Injection Fire Protection SystemDetailed dimensional layout drawing of the system with complete bill of materials,clearances from ground and other live points, details of detectors, equipment layoutdrawings, detailed drawings pertaining to signal box, control box, FEC equipment,wiring and schemes, 4 sets of testing, commissioning, Operation and Maintenancemanual along with soft copies (in CDs) shall be submitted by the supplier.11.0.0 PACKING, SHIPPING, HANDLING & SITE SUPPORT11.1.0Packing ProtectionThe packing shall be fit to withstand roughhandling during transit and storage atdestination. The test set should beproperly protected against corrosion,dampness & damage.11.2.0Packing for accessories andsparesRobust non-returnable packing case withall the above protection & identificationLabel. Thebidder should get the packinglist approved before dispatching thematerial.

Page 52: Tech Spec Ss -III

11.3.0 Packing Identification Label On each packing case, following detailsare required:11.3.1 Individual serial number11.3.2 Purchaser's name11.3.3 PO number (along with SAP item code, if any) & date11.3.4 Equipment Tag no. (if any)11.3.5 Destination11.3.6 Manufacturer / Supplier's name11.3.7 Address of Manufacturer / Supplier / it’s agent11.3.8 Description11.3.9 Country of origin11.3.10 Month & year of Manufacturing11.3.11 Case measurements11.3.12 Gross and net weight11.3.13 All necessary slinging and stacking instructions11.4.0ShippingThe seller shall be responsible for alltransit damage due to improper packing.11.5.0 Handling and Storage Manufacturer instruction shall befollowed.11.6.0 Detail handling & storage instruction sheet / manual to be furnished beforecommencement of supply.12.0.0 DEVIATIONSList of deviations shall be stated in writing with the tender by reference to theSpecification clause / GTP/ Drawing. In absence of such a statement, requirements of theSpecification shall be assumed to be met without exception by the bidder.355BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Rev: 0Reviewed by Date:Approved by

TECHNICAL SPECIFICATIONFORPACKING & TRANSPORTATION356BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Packing and Transportation1.0 PACKING AND TRANSPORTATION1.1 Packing shall be sturdy and adequate to protect all assemblies, components and accessoriesfrom injury by corrosion, dampness, heavy rains, breakage and vibration encountered duringtransportation, handling and storage at the plant site. All accessories, which are likely to getdamaged during transit if transported mounted on the equipment, shall be removed,adequately packed and shipped separately. All openings shall be sealed. Spare parts shallbe packed separately and clearly marked. They shall be specially packed for long storagewithout injury.1.2 The bidder shall after proper painting, pack and crate all plant equipment for sea shipment/airfreight in a manner suitable for export to a tropical humid and saline air borne climate regionas per Internationally accepted export practice in such a manner so as to protect it fromdamage and deterioration in transit by road, rail and/or sea and during storage at site till thetime of erection. The bidder shall be held responsible for all damages due to improperpacking.1.3 The bidder shall give complete shipping information concerning the weight, size, contents ofeach package including any other information the Owner may require. The weight and size ofthe package shall be such that they can be easily transported from the maker's works to the

Page 53: Tech Spec Ss -III

plant site by ship/air, road ways and railways.1.4 The bidder shall ascertain at an early date and definitely before the commencement ofmanufacture, any transport limitations such as weights, dimensions, road culverts, overheadlines, free access etc. from the manufacturing plant to the project site; and furnish to theOwner confirmation that the proposed packages can be safely transported, as normal oroversize packages, upto the plant site. Any modifications required in the infrastructure andcost thereof in this connection shall be done and borne by the bidder.1.5 The bidder shall prepare detailed packing list of all packages and containers, bundles andloose materials forming each and every consignment dispatched to 'site'. The bidder shallfurther be responsible, for making all necessary arrangements for loading, unloading andother handling right from his works; and from Indian port for equipment under the Off-shoreSupply till the 'site' and also till the equipment is erected, tested and commissioned. Thebidder shall be solely responsible for proper storage and safe custody of all equipment.1.6 All packages must be marked consecutively from number one upwards covering allshipments until completion of the plant equipment execution without repeating the samenumber. Each box, crate, case bundle or each piece of lose material shall be painted with acombination of one white band and one yellow band of a least 4 cm wide each, round thebody of the box, crates, etc as the case be for easy identification.357BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Packing and Transportation2.0 DEVIATIONSDeviation from this specification, if any, shall be clearly brought out in the offer. Unless ownerexplicitly accepts such deviations, it shall be considered that the offer fully complies with thespecification.358BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Rev: 0Reviewed by Date:Approved by

TECHNICAL SPECIFICATIONFORMATERIALS WORKMANSHIP & TEST359BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Materials Workmanship and Tests1.0 MATERIAL, WORKMANSHIP & TESTS1.1 GeneralAll materials used in the manufacture of the offered plant equipment shall be of high grade,free from defects and imperfections, of recent manufacture and unused. Materials notspecifically described elsewhere, shall as far as applicable and practicable conform to thelatest specification of ISS where applicable and equivalent International Standards. Liberalfactors of safety shall be used throughout the design for all parts of plant equipment whensubjected to the most severe operating conditions. The working stress in all parts of the plantequipment shall be bestowed with ample margins for possible overstressing due to shock.All work shall be performed and completed in accordance with the best modern shop practicein manufacture of high grade equipment.Castings shall be free from blow-holes, flaws, cracks or other defects; and shall be smooth,close-grained and of true form and dimensions. No plugged or filled-up holes or other defectswill be accepted. No casting shall be burned, plugged, patched or welded; and no repairs ordefects will be accepted.All materials, supplies, parts and assemblies supplied under this specification shall be testedas far as reasonably practical.All welded joints shall be free from defects such as blow-holes, slag inclusions, lack ofpenetrations, under-cuts, cracks etc; and shall be made by qualified and tested welders. Slagshall be ground after joint completion; and well reinforced smooth welds shall be made.1.2 Inspection, Testing program and Notification

Page 54: Tech Spec Ss -III

Before manufacture commences, the contractor shall submit an outline of the proposedinspection and testing programmes (Quality Assurance Programme - QAP) for all majorstages during manufacturing of major equipment. This inspection and testing programmeshall include for the various items, the designation number, the kind of test, test standard andthe extent of witness by the Owner/Engineer or third party.The notification of the individual witness inspections made by the Owner/Engineer or the thirdparty, shall be given by the contractor using facsimile or telex or e-mail in a format to beagreed upon. The contractor shall notify the Owner/Engineer within 21 days prior to the dateon and the place at which item shall be ready for testing. If any postponement becomesnecessary, the contractor shall provide written notification of same at least 72 hours prior tothe originally scheduled date.If the Owner/Engineer does not attend the test at the place and at the date which thecontractor has stated in his notification, the contractor shall proceed with the test, which shall360BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Materials Workmanship and Testsbe deemed to have been made in their presence and shall forthwith forward to them dulycertified copies of the test readings.Before erection commences, the contractor shall submit an outline of the proposed erectioninspection and test programme during the erection of major systems. The individual testingprocedure shall be submitted as progress of erection work of the equipment, systems and/orunits, coordinated with relevant work of the complete plant.Before commissioning commences, the contractor shall submit an outline of the proposedcommissioning test procedure. The test programmes shall be maintained by the contractorduring erection and commissioning.1.3 Test : GeneralDuring manufacture, the Owner's representative shall have the right to expedite and/orinspect design, materials, workmanship and progress of manufacture of the contractor's andhis sub-contractor's plant system equipment and may reject any defective materialsconsidered unsuitable for the intended purpose or which does not comply with the intent ofthis specification. The contractor, upon any such rejection by the Owner or his representative,shall rectify or replace the defective or unsuitable material. The contractor shall provide everyreasonable inspection facility to the Owner's inspector or representative at his own and hissub-contractor's works.Material being furnished against this order shall only be shipped when factory inspectionsatisfactory to the Owner and/or his representative has been conducted. Such inspection andacceptance for shipment shall not however, relieve the contractor from entire responsibilityfor furnishing the plant system equipment conforming to the requirement of this specificationnor shall prejudice any claim, right or privilege which the Owner may have, because of theuse or supply of defective or unsatisfactory materials for the plant system equipment. Shouldthe inspection be waived by the Owner, such waiver shall not also relieve the contractor inany way, from his entire obligations under this order.The plant system equipment shall at factory or after installation be demonstrated capable ofperforming satisfactorily upto the contractor's guaranteed performance. All tests required bythis specification, including retests and inspection, that may be necessary owing to failure tomeet any tests specified, shall be made at the contractor's expense. Additional tests, asnecessary, shall be made to locate any such failure and after determining the causes offailure and rectifying it, specified tests shall be repeated to establish that the rebuilt plantsystem equipment meets with the specification in every respect. Should the equipmentultimately fail to pass the tests specified, the Owner will have the option to reject the unit.The bidder shall state in the proposal, the shop testing facilities available. Should full capacitytesting equipment be not available, the bidder shall state the method proposed to be adoptedwith detailed computations and justification for adopting such a method to reliably ascertainthe equipment characteristics corresponding to full capacity testing.1.4 Test Certificate361BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Materials Workmanship and TestsIn accordance with approved QCP, the results of the tests shall be certified by theOwner/Engineer or independent agency as applicable. As and when the item of the plant

Page 55: Tech Spec Ss -III

equipment has passed the tests, the Owner/Engineer shall furnish to the contractor acertificate in writing to that effect. The Quality Control Plan (QCP) shall be issued by thecontractor within 1 months after NTP. Document files containing material certificates, testreports, etc shall be compiled for each QCP item of plant equipment; and shall be suitablyidentified (including equipment classification reference) and bound. Copies of compiled fileshall be submitted as per distribution schedule1.5 Tests at Manufacturers WorksThe major equipment of the plant to be supplied under this contract shall be subjected toshop inspection and tests. After NTP, the contractor shall issue within 1 months a QCPindicating the kind and extent of inspection and tests to be carried out on the offered plantequipment components to prove whether the equipment fulfills the requirement of thecontract in view of:• Safety Conditions• Consideration of the applied standards and regulations• Execution of workmanshipSITE TESTSTests conducted at sites shall be indicated by bidder.2.0 DEVIATIONSDeviation from this specification, if any, shall be clearly brought out in the offer. Unless ownerexplicitly accepts such deviations, it shall be considered that the offer fully complies with thespecification.362BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Rev: 0Reviewed by Date:Approved by

TECHNICAL SPECIFICATIONFORMISCELLANEOUS ACTIVITIES363BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc Activities1.0 SERVICE AFTER SALES1.1 The bidder shall furnish in detail about his organization for rendering service after sales,covering deployment of personnel and supply of spares, for ensuring efficient operation andmaintenance of the offered plant equipment. The details of spares and service facilitiespossessed by them should be elaborated.1.2 The bidder shall guarantee furnishing of the following in respect of after sales servicesincluding spares:-i) Providing services of his specialists on indent from the Owner for periodical orspecial maintenance of the plant; as well as for identifying sources of trouble, ifany, reported and measures for immediate rectification.ii) The bidder shall guarantee maintenance of adequate spares at his works to besupplied on indent from the Owner at short notice during the life of the plant.2.0 BID DATA, DRAWINGS AND INFORMATION REQUIRED2.1 Technical data sheets, drawings, schedules with supporting information incorporating thedetails in compliance to spec but not limited to the following shall be furnished along with theproposal:2.2 Duly filled in 'Schedule of Guaranteed and other Technical Particulars Schedules ‘C’ exceptfor data which cannot be finally furnished with the Bid. The Price and Delivery Schedule-Bduly filled in.2.3 Dimensioned outline drawings of the offered overall plant and separately for equipmentincluding cross-sectional drawings showing dimensions, net weights, shipping weights andsuggested arrangement layout of proposed plant & equipment with auxiliaries etc. TechnicalLiterature/leaflets of the above plant equipment.2.4 Manufacturers' catalogues showing the construction details of various equipments should befurnished indicating clearly the technical preference of the offered equipment over the

Page 56: Tech Spec Ss -III

specified equipment.2.5 List of users of comparable plant equipment with the year in which the Diesel plant and othercritical plant equipment was put actually into service. For technical acceptability of the bid,proven experience of the bidder in manufacture and satisfactory and trouble freeperformance of the critical plant equipment for at least three (3) years is essential for whichthe bidder shall furnish necessary documents in support of the above.2.6 A bar chart of design, engineering, procurement, manufacture, testing, delivery, installation,commissioning and site testing including civil structural and architectural works of theproposed plant equipment.364BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc Activities2.7 Technical description of the proposed plant equipment and materials particularly outlining anyadditional list out features proposed for safety & reliability. List out items of work & servicesnot included and which has to be provided by the Owner for satisfactory commissioning of theoffered plant equipment supplied.2.8 The bid shall not be considered if the bidder fails to submit all the details asked for. Proposalshould be complete without ambiguity and should be clearly written against each item.2.9 Bidder shall furnish Quality Assurance Programme for design, manufacture, assembly,erection, testing & commissioning including civil, structural and architectural works along withthe proposal for all equipment covered under this specification whether manufactured by thebidder or procured from other sources.2.10 Technical deviations from the specification, if any, shall be clearly listed in the Schedule-E. Inabsence of any deviation given in Schedule-E and accepted by Owner, it will be bidder'sresponsibility and his contractual obligation to supply the Plant equipment as per specificationto Owner/Engineer's approval.2.11 List of shop and site tests, the bidder proposes to carry out including those pertaining to theirsub-suppliers works shall be clearly brought out in Schedule – G. In addition to above tests,the bidder shall conduct any other tests, to Owner/Engineer's approval, which are consideredimportant for satisfactory operation of plant equipment.2.12 Bidder shall furnish all required mandatory and startup commissioning spare parts as well asmaintenance tools and tackles with unit prices for the offered plant equipment.3.0 POST CONTRACT DATA AND DRAWINGS3.1 The contractor shall submit within thirty (30) days from the date of the order and Notice toProceed (NTP) certified dimensioned drawings and technical schedules giving every detail ofthe offered plant equipment particularly the following:3.2 Completely filled in schedule of guaranteed particulars and other technical particulars.3.3 Single line diagrams; logic diagrams, dimensioned general arrangement and equipmentlayout drawings showing front and side elevations, plan and sectional views of the offeredequipment forming part of the contractor's supply; The drawings should also indicatestructures & supporting details including foundation outline and loading data etc.3.4 Final version of all drawings and data submitted along in the proposal mentioned above.3.5 Structural, thermodynamic and pressure part calculations showing compliance withspecifications and codes as and when required.3.6 Any other drawings/details not specified herein and required by the Owner/Engineer tocorrectly coordinate the offered plant equipment with other contractor's work.365BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc Activities3.7 Civil design calculations.3.8 Detailed specifications and data sheets of the plant equipment with auxiliaries.3.9 Detail drawings of critical equipment units, assemblies, parts etc. as deemed necessary.3.10 Design calculations of conductor sizing, cable sizing, main equipment sizing etc.3.11 Schematic wiring diagrams along with write-ups for control, interlocks, instrumentation,protection, circuits. Terminal blocks and terminals arrangement drawings showing power &control cable connections.3.12 Owner/Engineer will return to the contractor one (1) print of each drawing either.(a) stamped approved or (b) marked up with the comments. In case of (a), no furthersubmission of a drawing will be required. In case of (b), the contractor shall correct hisoriginal drawings to conform to comments made by the Owner/Engineer and resubmit within

Page 57: Tech Spec Ss -III

two (2) weeks of receipt of comments in the same manner as stated in the DistributionSchedule. The Owner/Engineer's approval shall not relieve the contractor from any of hisobligation and responsibility to manufacture and supply equipment conforming to thisspecification, unless a written amendment to the specification is issued by the Owner.3.13 After approval of the drawings, reproducible of each drawing shall be supplied. Finaldrawings shall be certified as Approved for Construction. Should any minor revision be madeafter approval the contractor shall re-distribute prints and reproducible as per the DistributionSchedule. Every revision shall be marked by a number, date and subject in a revision blockprovided in the drawing.3.14 Reproducible shall be of quality to produce clear and legible prints and any inferiorreproducible will be returned by the Owner for replacement with suitable reproducible. Allreproducible shall be mailed rolled (not folded) on the outside of regular mailing tubes exceptfor small sizes which can be mailed unfolded in envelope with a cardboard backing. Theprints and reproducible shall be mailed in the most expeditious manner and shall beaccompanied with a letter of transmittal.4.0 INSTRUCTION MANUAL4.1 At least one (1) month prior to the dispatch of the plant equipment, fifteen (15) copies ofinstallation, testing and adjustments after installation, operation and maintenance manualsshall be furnished. These manuals shall be sturdily bound volumes and shall contain everydrawings and information required for installation, testing, setting and adjustment of allcomponents after installation, operation and maintenance of the equipment and all itscomponents. Separate tabs shall be used for such instructions concerning each equipmentcontrol components, electrical and other accessories. The other data needed for servicing thecomponents and ordering their spare parts.366BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc Activities4.2 Marked erection prints identifying the components parts of the equipment, as transported,with its assembly drawings.4.3 Detailed dimensioned assembly and cross sectional drawings and description of all the plantsystem equipment with auxiliaries and drawings identifying all spare parts for re-order.4.4 DocumentationCorrespondence, drawings, progress reports, schedules, tests reports and instructionmanuals shall be mailed in requisite copies in accordance with Distribution Schedule.5.0 WORK SCHEDULE5.1 Time being the essence of the proposal, preference will be given for the offers quoting earlierdeliveries. The bidder shall include in his proposal his programme for furnishing and erectingthe offered plant & equipment.5.2 The programme shall be in the form of master network identifying the key phases in variousareas of total plant work, such as design work, procurement of raw materials, manufacture ofcomponents & subassemblies; complete erection of equipment and all other field activities.The master network shall conform to completion of trial operation from the date of Letter ofAward within a period of 4 months. The trial operations shall commence any day within 15days prior to the date of completion indicated above.5.3 This master network shall be discussed and agreed before the issue of letter of award.Engineering drawings as well as technical data sheets submission schedule shall also bediscussed and finalized before the issue of letter of award. Provisions of the liquidateddamages leviable for delays in completion of trial operation shall become effective after theabove mentioned date.5.4 After the contract award, the contractor shall plan the sequence of work of manufacture anderection including associated civil works to meet the Owner's power plant commissioningrequirements; and shall ensure that all work/manufacture, shop testing, inspection &shipment of the equipment in accordance with the required construction/erection sequence.5.5 Within seven (7) days of acceptance of the letter of award, the contractor shall submit, forreview and approval, two copies (1 reproducible and 1 print) of Detailed Network schedules,based on the Master Network (mutually agreed by the Owner & contractor) to theOwner/Engineer showing the logic & duration of the activities in the following areasi) Engineering, Procurement, Manufacturing & Supply Detailed engineering activitiesin regard to procurement of raw materials including bought out items, manufacture,dispatch/ shipment & receipt at site.

Page 58: Tech Spec Ss -III

ii) Civil, Structural & Architectural Works:Detailed engineering activities in regard to civil & structural works execution basedon the offered equipment and approved drawings including detailed execution ofexecution activities covering the complete scope of work.iii) Erection, Testing and Commissioning:367BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc ActivitiesDetailed erection, testing and commissioning activities, covering the completescope of work of the offered plant equipment coordinated with the civil andstructural works executed.5.6 Detailed Manufacturing ProgramDetailed manufacturing PERT/PRIMAVERA programme for all the manufacturing activities ofthe offered plant equipment at contractor's/subcontractor's works shall be furnished within 7days of letter of award.The manufacturing network shall be supported by detailed procurement programme forcritical bought out items/raw materialsPre-erection Activity ProgrammeA) Manpower DeploymentB) Tools and plant mobilization planC) Detailed Site Mobilization Plan5.7 Within a week of approval of the Network schedule, the contractor shall forward to theowner/Engineer copies of the Computer initial run data in an acceptable manner5.8 The network shall be updated every month; or as frequency as possible to mutual agreement.Within seven (7) days following the monthly review, a progress meeting shall be held at thework (possible) wherein the major items of the plant or equipment are being produced. Themeeting will be attended by the Owner/Engineer and responsible representatives of thecontractor. The contractor shall be responsible for minuting the proceedings of the meeting, areport of which shall reach the Owner or the Owner/Engineer not later than 7 days followingthe meeting.5.9 Access to the contractor's and/or sub-contractor's work shall be granted to theOwner/Engineer at all reasonable times for the purpose of ascertaining the progress6.0 PROGRESS REPORTSDuring execution of the contract either in manufacture or erection/commissioning, thecontractor shall furnish monthly progress report to the Owner or the Owner/Engineer in aformat as specified indicating the progress achieved during the month, and total progressupto the month as against scheduled and anticipated completion dates in respect of keyphase of work or manufacture and shipment such as release of drawings for fabrication,procurement of raw materials, inspection and testing. If called for by the Owner/Engineer, thecontractor shall also furnish to the Owner or the Owner/Engineer resources data in aspecified format and time schedule. The contractor shall also furnish any other informationnecessary to ascertain progress if called for by the Owner/Engineer368BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification Misc Activities7.0 DEVIATIONSDeviation from this specification, if any, shall be clearly brought out in the offer. Unless ownerexplicitly accepts such deviations, it shall be considered that the offer fully complies with thespecification.369BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Javed Ahmed Rev: 0Reviewed by Meenakshi Date: 05.08.2015Approved by Kiran Kumar Alla

TECHNICAL SPECIFICATIONEOT (ELECTRICAL OVERHEADTRAVELLING) CRANE

Page 59: Tech Spec Ss -III

370BSES Bhawan, Nehru Place, New Delhi- 19Volume-I Technical Specification for EOT (Electrical Overhead Travelling) CraneScope:This specification applies to the design, engineering, manufacturing/fabrication, assembly,inspection, testing before dispatch, packing, forwarding, supply and delivery at destinationby suitable transport, unloading at site, installation and commissioning of indoor EOTcrane on Turnkey basis and as specified in the following sections of this document.Reference Standards:1IS:325-19783-Phase induction motors (fourth revision2IS:807-2006Code of practice for design, manufacture, erection andtesting (structural portion) of cranes and hoists.3IS: 2062-1992Specification for structural steel (fusion welding quality)4IS:2266-1989Steel wire ropes for general engineering purposes5IS:3177- 1999Code of practice for electric overhead travelling cranes andgantry cranes other than steel work cranes.6IS:l3947(Part-1)-1993Low voltage switches and control gear PI-general rules7IS:l3947(Part-4,Section-1) -1993Low voltage switchgear and control gear P-4 - contactorsand indoor starters sec 1, electromechanical contactors andmotor starters (superseding IS:2959 and IS:8544 – all parts)Introduction:The EOT cranes will consist of the following major components:• Double girder.• Trolley frame.• Brakes.• Wheels and rails.• Hooks (main/auxiliary) and hoist rope.• Operator’s cabin/radio control.• Conductors.• AC motor.• Shrouded down shop leads (DSL) with maintenance cage.• Control panel.371BSES Bhawan, Nehru Place, New Delhi- 19Volume-I Technical Specification for EOT (Electrical Overhead Travelling) CraneTechnical Details:The girder will be of box type construction and will ensure that water/oil do not accumulateinside the box. The trolley frame will be fabricated from rolled sections/steel plates. Themain hoist, auxiliary hoist, cross travel trolley, and long travel trolley of the crane will be

Page 60: Tech Spec Ss -III

motor driven. The structural portion of the EOT crane will be designed to meet therequirements of Class II of IS 807 (Indian Standard). The EOT crane will be designed(other than the structural steel portion) to meet the requirements of Class M5 of IS 3177.Sideward approaches from the operating floor level to the rail level will be provided in bothrows for access to the bridge. Safe means of access will be provided in the cabin andother areas of the crane where maintenance of any equipment or component is involved.A platform will extend the full length of the crane bridge on both sides of the bridge girderThe EOT crane will have a permanent inscription in English and Hindi on each side,readily visible from the operating floor level, stating the safe working loads in metric tonsfor both the hooks, the year of manufacture, crane serial number, and manufacturer’sname.Features:• The EOT crane will be of double girder, bridge type.• The EOT crane shall be designed for lifting 25% more than the heaviest piece ofequipment (detailed calculation shall be submitted by Vendor for approval)• Steel will be of tested quality steel conforming to IS 2062 (Grade B).• Handrails will be of galvanized steel pipe of flush welded construction, groundsmooth using 32 mm.Nominal bore medium class pipe conforming to IS 1239 (PartII).• The wheels and rails act as a guide for EOT cranes to provide smooth and linearmotion.• The crane panel will have two incoming supplies. The two isolators will havemechanical interlock(through Castell key) to prevent simultaneous closing of thetwo isolators.• Electrical motors will be selected with an S4 duty, a 25 percent cycle duty factor,and 150 starts per hour.• Speed of the hoist shall be 3-4 meter per min and the creep speed through DCEMclutch and pony geared motor shall be maximum 0.5 meter per min.• The height of lift and length of long travel shall be in accordance to the GIS room.• The end carriage & Trolley frame shall be fabricated with MS Rolled channels andMS plates, suitable stiffeners and diaphragms shall also be provided.• Antiskid skid chequered plate with suitable maintenance platform for Hoist Blockand long travel drive shall be provided. Sufficiently wide full length walk way withhand railing should be provided on the girder. Drawing &all other related documentare to be approved from the user Dept.372BSES Bhawan, Nehru Place, New Delhi- 19Volume-I Technical Specification for EOT (Electrical Overhead Travelling) Crane• Totally enclosed helical splashed oil bath lubricated gear box shall be used for allmotion. All gear & pinion shall be hardened and tempered alloy steel having metricmodule machine cut teeth. The housing shall be graded cast iron / cast steel orfabricated from steel plates. Fabricated housing shall be stress relieved before themachining. The gear box shall be oil tight and fitted with oil level indicator, breatherplug, inspection cover and oil drain out plug. The internal surface of gearbox shallbe painted with oil resistant type paint.• Rope drum shall be fabricated form rolled steel plates or seamless tube.Fabricated rope drum shall be stress relieved before machining. The rope drumshall be designed for single layer of rope; the helical groove shall be smoothfinished.• Wire rope shall be regular right hand lay fiber core as per IS: 2266. Theconstruction of wire rope shall be 6X36 constructions. The factor of safety shall be6 minimum. Rope sheaves shall be graded cast iron. The rope sheaves shall bemounted on anti friction bearing.• Lifting hook shall be single point with shank as per IS: 3815. The hook shall bemounted on anti friction thrust bearing which shall be enclosed by protective skirt

Page 61: Tech Spec Ss -III

for360° smooth swivelling of the load on the hook. The block sheaves · shall befully encased in close fitting guards fabricated out of steel plate. Smooth openingshall be provided in the guard to allow free movement of rope. Hook block shouldbe tested and certified with proof load from Govt. accredited testing authorities.Test certificates for lifting hook shall be furnished during the supply.• All electrical motors shall be totally enclosed fan cooled, S4 Duty, Squirrel CageInduction Motor. The starting motion of all travel shall be jerking free. Suitablestarting arrangement shall be provided for all LT motor to reduce the startingcurrent to achieve smooth starting and thereby jerk free operation in all motions ofthe crane. Motor shaft shall be connected to the gear box through gear type flexiblecoupling.• Pendent push button shall be suspended from crane by link chain so that no unduestress can come on the cables. · The Push button station shall be independentlymovable. Separate cable track with cable trolley etc. shall be provided for the pushbutton station. The unit shall comprise of push button marked as follows and 1no.Indication lamp for control of indication:(1)Start (2) Emergency stop (3) Up (hoist) (4) Down (lower) (5) Slow down (6) SlowUP (7) Left -CT (8) Right- CT (9) Forward - LT (10) Reverse –LT• The unit shall comprise incoming ACB / MCCB with positive isolation contactor,line chock, three phase diode bridge rectifier acting as line converter and threephase inverter as load converter interconnected through DC link reactor andcapacitor unit.373BSES Bhawan, Nehru Place, New Delhi- 19Volume-I Technical Specification for EOT (Electrical Overhead Travelling) CraneInspection and Testing: The crane supplier shall put up the crane for inspection at hisWorks as well as at site and the following tests shall be carried out by him in the presenceof the Purchaser or his authorised representatives• All the dimensions of the crane shall be checked as per the approved generalarrangement drawings. Diagonal measurement of the crane and trolley shall alsobe carried out in the fabrication shops before despatch to site.• The deflection of the bridge girders shall not exceed 1/1000 of span with the fullyloaded trolley stationed at mid-span with safe working load at rest. Themeasurement shall not be taken on the first application of the load. The datum linefor measuring the deflection should be obtained by placing the unloaded trolley atthe extreme end of the crane span• The girders shall be tested for permanent set by applying 125% of the safe workingload when the trolley is stationed at mid-span. At the end of the test there shall beno sign of permanent set of the girders• Height of lift shall be checked by measuring the length of hook travel from itstopmost position to the bottom-most position and this shall not be less than the liftspecified• All the motions of the crane shall be tested with rated load and the rated speedsshall be attained within the tolerance limits• All the motions of the crane shall be tested with 25% overload in which case therated speeds need not be attained but the crane shall show itself capable ofdealing with the overload without difficulty.• For checking the performance of the hoist motion the speed at each notch of themaster controller with different loads both during hoisting and lowering shall befound out and the load/ speed characteristics shall tally with the speed/torquesgraph submitted.• For the performance of long travel and cross travel motions, the crane shall betested with rated load and the running time for a particular distance shall be as perthe acceleration values specified.• The hoist brakes shall be tested so as to enable to brake the movement under all

Page 62: Tech Spec Ss -III

conditions without any jerk on the load . The brakes shall also be tested withoverload condition.• The long and cross travel brakes shall be capable of arresting the motion within adistance in metres equal to 10% of the rated speed in metres/minute.• Limit switches for all the motions shall be tested for their proper operation and shallbe set right so as to obtain the required hook approaches and lifting height.• Insulation and other tests as per applicable codes shall be carried out.• Trolley frames shall be designed in accordance with applicable sections of IS2062/IS 12075.374BSES Bhawan, Nehru Place, New Delhi- 19Volume-I Technical Specification for EOT (Electrical Overhead Travelling) Crane• The main function of the trolley frames is to provide rigid support and strength tothe EOT cranes to carry a load from one place to another.• The trolley frame will be fabricated from rolled sections/steel plates. End carriageswill be of welded Construction. Mountings will be designed to facilitate easyremoval of the wheels, bearings, and journals for quick and easy maintenance.Wheel or wheel end carriage mountings will be complete with safety pads toprevent an accidental drop of more than 25 mm. Jack pads will also be provided onthe trolley and bridge wheel mounting structural frames for the removal of wheels.Drawing and Documents: Following drawings are to be submitted for scrutiny andapproval• The detailed general arrangement drawing containing all basic dimensions andvital particulars of the crane. These drawings should indicate the mainspecification, number and location of joints provided on the girder plates, CT railsetc. structural calculation, drawings of main load carrying members, if asked for byPurchaser• General arrangement drawing of the trolley.• Motor power &brake selection calculation.• Cabin layout drawing showing location and mounting of all equipment.• Control equipment supplier's schematic control circuit diagrams for individual drivesalong with speed-torque characteristics and explanatory notes.• General arrangement drawing for control panel with sections.Transportation of Equipment at Site:The contractor shall be responsible for the loading, transport, handling and offloading of allequipment and materials from the place of manufacture or supply to site. The contractorshall be responsible to select and verify the route, mode of transportation and make allnecessary arrangement with the appropriate authorities as well as determining anytransport restrictions and regulations imposed by the government and other localauthorities.Packing , Storing and Unpacking:All the equipment shall be carefully packed for transport in such a manner that it isprotected against the climatic conditions and the variations in such conditions that will beencountered enroute from the manufacturer’s works to the site.375BSES Bhawan, Nehru Place, New Delhi- 19Prepared by Meenakshi Rev: 1Reviewed by Kiran Kumar Alla Date: 21.11.2013Approved by Kiran Kumar Alla

TECHNICAL SPECIFICATIONAPPROVED MAKES & VENDERS376BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Approved Makes & Vendors

Page 63: Tech Spec Ss -III

1.0 APPROVED MAKES & VENDORSS NO. Vendors1.0 Power Transformer1.1 BHARAT BIJLEE LIMITED1.2 ABB LIMITED1.3 SCHNEIDER ELECTRIC LIMITED.1.4 BHEL2.0 Station Transformers2.1 VOLTAMP TRANSFORMER LIMITED2.2 SHILCHAR TECHNOLOGIES LIMITED2.3 ABB LIMITED2.4 SCHNEIDER ELECTRIC LIMITED.2.5 CROMPTON GREAVES LIMITED2.6 EMCO LIMITED3.0 LT Control, Communication and special cables3.1 POLYCAB3.2 PARAMOUNT COMMUNICATIONS LIMITED3.3 TARUNA METALS PVT. LIMITED.3.4 ALPHA COMMUNICATION3.5 KEI INDUSTRIES LIMITED.4.0 LT(1.1 KV grade) XLPE Insulated Power Cables4.1 PARAMOUNT COMMUNICATIONS LIMITED4.2 KEI INDUSTRIES LIMITED.4.3 HINDUSTAN VIDYUT PRODUCTS LIMITED4.4 GEMSCAB INDUSTRIES LIMITED4.5 KRISHNA ELECTRICAL INDUSTRIES LIMITED4.6 POLYCAB WIRES PRIVATE LIMITED4.8 KEC INTERNATIONAL LIMITED (RPG CABLES LIMITED )4.9 HAVELLS5.0 11KV 500MVA Indoor Switchboard5.1 SIEMENS LIMITED5.2 ABB LIMITED5.3 SCHNEIDER ELECTRIC LIMITED.6.0 66KV Outdoor Circuit Breakers6.1 ABB LIMITED6.2 SIEMENS LIMITED6.3 ALSTOM INDIA LIMITED7.0 66KV & 11KV Outdoor CT/PT7.1 CROMPTON GREAVES LIMITED377BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Approved Makes & Vendors7.2 KAPCO ELECTRIC PVT. LIMITED.7.3 ALSTOM7.4 MEHRU ELECTRICAL & MECHANICAL ENGINEERS P LIMITED.7.5 ABB LIMITED7.6 BHEL8.0 CVT8.1 CROMPTON GREAVES LIMITED8.2 ABB LIMITED8.3 ALSTOM INDIA LIMITED8.0 66KV Lightening Arrestor8.1 ALSTOM8.2 OBLUM ELECTRICAL INDUSTRIES PVT. LIMITED.8.3 LAMCO INDUSTRIES PVT. LIMITED.8.4 ABB LIMITED8.5 CROMPTON GREAVES LIMITED.9.0 66KV Isolators9.1 ABB LIMITED.9.2 SIEMENS LIMITED.

Page 64: Tech Spec Ss -III

9.3 CROMPTON GREAVES LIMITED.10.0 66KV Control & Relay Panel10.1 ABB LIMITED.10.2 SCHNEIDER ECLECTRIC LIMITED.10.3 SIEMENS LIMITED.11.0 11KV Capacitor Bank11.1 UNIVERSAL CABLES LIMITED.11.2 SHREEM ELECTRIC LIMITED11.3 ABB LIMITED11.4 LARSEN & TOUBRO LIMITED11.5 EPCOS INDIA PVT. LIMITED12.0 ACDB12.1 NEPTUNE12.2 KAY BEE ELECTRICALS12.3 MK ENGINEER12.4 SHRIRAM SWITCHGEAR LIMITED12.5 POPULAR SWITCHGEAR13.0 St. through jointing and Termination Kits - 1.1KV,11KV13.1 RAYCHEM RPG LIMITED13.2 3M ELECTRO & COMM. INDIA (P) LIMITED.13.3 DENSON378BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Approved Makes & Vendors14.0 St. through jointing and Termination Kits - 66KV14.1 RAYCHEM RPG LIMITED14.2 3M ELECTRO & COMM. INDIA (P) LIMITED.15.0 HPSV/Fluorescent Lamps, Ballasts, Starters / Igniters, Fittings, Lamp Holder,High Mast15.1 PHILIPS ELECTRONICS INDIA LIMITED15.2 CROMPTON GREAVES LIMITED15.3 BAJAJ ELECTRICALS LIMITED15.4 SURYA ROSHNI LIMITED16.0 Transformer oil16.1 APAR INDUSTRIES LIMITED16.2 SAVITA OIL TECHNOLOGIES LIMITED16.3 RAJ PETRO SPECIALITIES PVT. LIMITED.17.0 Protective Relays17.1 SIEMENS LIMITED17.2 EASUN REY ROLLE LIMITED17.4 A-EBERLE17.5 ABB LIMITED18.0 Overhead Line accessories e.g. Clamps, Connectors, Line Hardware fitting18.1 RAYCHEM RPG PVT.LIMITED18.2 EXALT ENGINEERING INDUSTRIES18.3 RASHTRA UDHYOG LIMITED.18.4 KLEMMEN ENGINEERING19.0 Disc and Pin Insulators19.1 ADITYA BIRLA INSULATORS19.2 MORDEN INSULATORS LIMITED.19.3 BHEL19.4 W.S. INDUSTRIES20.0 STEEL TUBULAR POLES20.1 FABRICO (INDIA) PVT. LIMITED.20.2 ADVANCE STEEL TUBES LIMITED.20.3 GOOD LUCK STEEL TUBES LIMITED.20.4 RAMA STEEL TUBES LIMITED.21.0 ACSR Conductors21.1 HINDUSTAN VIDYUT PRODUCTS LIMITED21.3 LUMINO INDUSTRIES LIMITED21.5 POLYCAB WIRES PRIVATE LIMITED

Page 65: Tech Spec Ss -III

379BSES Bhawan, Nehru Place, New Delhi- 19Volume – I Technical Specification for Approved Makes & Vendors22.0 NI-Cd Battery Bank22.1 HBL POWER SYSTEMS LIMITED22.2 AMCO SAFT INDIA LIMITED22.3 AMARAJA23.0 Battery Charger cum DC DB23.1 MASS-TECH CONTROLS PRIVATE LIMITED23.2 CALDYNE AUTOMATICS LIMITED.23.3 CHABI ELECTRICALS24.0 PAINTS & CHEMICALS24.1 BERGER PAINTS INDIA LIMITED BRITISH PAINTS DIVISION24.2 SHALIMAR PAINTS LIMITED.24.3 NEROLAC PAINTS LIMITED.24.4 ASIAN PAINTS LIMITED.25.0 CEMENT25.1 ACC25.2 ULTRA TECH26.0 STEEL26.1 TATA26.2 SAIL380BSES Bhawan, Nehru Place, New Delhi- 19

VOLUME – IISCHEDULE AND ANNEXURE381BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule ASCHEDULE – AGENERAL PARTICULARS(This shall from part of Technical Bid)1.0 Bidder1.1 Name :1.2 Postal Address :1.3 Telegraphic Address :1.4 Telex number / Answer back code :1.5 Phone(s) :1.6 Name and Designation of the person who :should be contacted in case of clarifications /details etc. not received expeditiously formthe officer mentioned in item 1.6 above1.7 Brief write-up giving details of the :organization, years of establishment andand commercial production activities,manufacturing, fabrication, shop testing,erection, testing, commissioning andafter-sales service facilities, key personnel withtheir qualifications and experience,collaboration agreements, if any number ofemployees in various categories and last three(3) years turn over2.0 Bid Validity :3.0 All the Schedules filled-in : Yes4.0 All the Deviations brought out in : YesSchedule – E1and E25.0 All the drawings, write-ups, literature, : Yesleaflets, calculations, details, etc as

Page 66: Tech Spec Ss -III

called for in the specification attached6.0 Is the Bidder agreeable to undertake this : Yes/Nocontract, if deviations stipulated by himare not acceptable to the Purchaser382BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule ABidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________383BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule BSCHEDULE – BTRANSFORMER OILS.No Item Description Specification requirement Data by Vendor1 Manufacturer Name Name1.1 Address Address1.2 Contact person Contact person1.3 Contact no. Contact telephone no2 Appearance of oil Clear, transparent and freefrom suspended matter orsedimentsYes / No3 Density at 29.50C Max. 0.89 g/cm34 Kinematics viscosity Max. 16 cSt at 270C11 cSt at 400C5 Interfacial tension at 270C 0.04 N/m min6 Flash point Pensky-Marten(Closed), Min.1400C7 Pour Point, Max - 150C8 Neutralization value8.1 Total acidity, Max 0.03 mg KOH/g8.2 Inorganic acidity/AlkalinityNil9 Corrosive sulfur Non-corrosive10 Electric strengthbreakdown voltageAverage value of sixsamples10.1 New unfiltered oil. Min. 30 kV (rms) min.10.2 After filtration Min. 60 kV (rms)11 Dielectric dissipation factor(tan δ).0.002 at 900C, Max0.0005 at 270C, Max12 Specific resistance (resistivity)12.1 At 900C, Min 150 X 1012 ohm-cm12.2 At 270C, Min 3000 X 1012 ohm-cm13 Oxidation stability13.1 Neutralization value afteroxidation, Max.0.15 mg KOH/g13.2 Total sludge, afteroxidation, Max.

Page 67: Tech Spec Ss -III

0.03 % by weight13.3 Max Tan delta 0.1 at 700C14 Ageing characteristicsafteraccelerated ageing(open breaker method withcopper catalyst)14.1 Specific resistance14.1(a) At 270C Min. 27 X 1012 ohm-cm14.1(b) At 900C Min 2 X 1012 ohm-cm14.2 Dielectric dissipationfactor (tan δ)0.10 at 900C Max14.3 Total acidity, Max 0.05 mg KOH/g14.4 Total sludge, Max 0.05 % by weight15 Presence of oxidation no antioxidant additives384BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule Binhibitor16 Water content, Max 40 ppm17 List of clients To be enclosed18 PCA content 3% max19 PCB content Not detectableBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________385BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1SCHEDULE – C111KV INDOOR SWITCHGEARSr. No. Description Incomer Buscoupler Outgoing Capacitor Transformer1 Switchgear assembly1.1 Make1.2 Type1.3 Reference standard1.4 Voltage (normal / Max.KV)1.5 Frequency (HZ)1.6 Short circuit rating1.7 Short time current anddurationA Impulse withstand (KVpeak)B 1min. Power freq.withstand test(KV rms)2 Construction2.1 Metal clad construction(Yes / No)2.2 Degree of Portion2.3 Minimum thickness ofsheet metal used (mm)2.4 Draw out feature providedforA

Page 68: Tech Spec Ss -III

Breaker with service, test& isolated position - Yes/NoB Voltage Transformer- Yes/ NoC Protection relays -Yes /No2.5 Breaker cubicleACubical door can beclosed with breaker in testand isolated position -Yes/ NoB Working zone units fromfloor level (mm)2.6All meters, switchgear &relays flush mounted type-Yes /No2.7 Minimum clear spacerequiredA Front for breakerwithdrawal (mm)386BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B Rear (mm)2.8 Typical vertical sectionA Overall dimensionsi. Length (mm)ii. Breath (mm)iii. Height (mm)B Weight (Kg)3 Bus Bar3.1 Make3.2 Material & grade3.3 Reference standard3.4 Cross section area (mm2)3.5 Bus connection (joints)A Silver plated -Yes /NoB Conventional made withanti oxide grease -Yes /No3.6 Rated continuous currentamps3.7Maximum temp. rise atrated continuous currentDFG C3.8 Short time current andduration KA … secs3.9 DC resistance at 85 DEGC (Ω/m/Ø)3.10 Minimum clearance of busbar and connectionA Phase to phase (mm)B Phase to earth (mm)3.11 Bus bar provided withA Insulation sleeveB Phase barriersC Cast resin shrouds forjoint

Page 69: Tech Spec Ss -III

3.12 Bus bar supportedspacing (mm)3.13 Bus bar insulatorsA MakeB TypeC Reference standardD Voltage class (KV)E Min. creepage distance(mm)F Cantilever strengthKg/mm2G Net weight (Kg)387BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14 Circuit Breaker4.1 Make4.2 Type4.3 Reference standard4.4 Related Voltage4.5 Related frequency4.6 Related current and itsreference ambient tempAContinuous current to limitthe max. temp. rise to55DEG C for silver platedconnections and 40DEG Cfor conventionalconnections4.7 Related operating duty4.8Symmetrical breakingcapacity at rated voltage &operating duty KA rms.4.9 Rated making current(Kap)4.10 Short time current andduration KA … secs4.11 Insulation levelA Impulse voltage withstandon 1/50 full waveA 1min. Power freq.withstand test(KV rms)4.12 Maximum overvoltagefactor while switching offA Un loaded transformerB Loaded transformerC Un loaded CABLESD CapacitorE Motors4.13 Opening time max. Noload condition (ms)4.14Number of permissiblebreaker operation undervacuum loss4.15 At 100% breaking capacityA Opening time Max. (ms)B Arcing time max (ms)

Page 70: Tech Spec Ss -III

C Total break time (ms)4.16A Make time (Max) (ms)B Total closing time (ms)388BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14.17 Total length of contacttravel (mm)4.18No. of breaker operationpermission withoutrequiring inspection,replacement of contactsand other main parts.A At 100% rated currentB At 100% rated breakingcurrent4.19 Types of contents4.20 Maximum clearance in air(mm) from live part4.21 Between phasesA Between live parts andgroundB Type of arc control deviceprovided4.22 Operating mechanismclosing4.23 TypeA No. of breaker operationsstoredB Trip free or fixed tripC Anti pumping featuresprovided4.24 Operating mechanismtrippingA TypeB No. of breaker operationsstoredC Trip free or fixed tripD Anti pumping featuresprovided4.25 Spring charging motorA RatingB MakeC Voltage and permissiblevariation(%)4.26 Closing coilA Voltage (V)B Permissible voltagevariation (%)C Closing current at ratedvoltage (A)D Power at rated voltage (w)4.27 Trapping Coil389BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A Voltage (V)B Permissible voltage

Page 71: Tech Spec Ss -III

variation (%)C Tripping current ratedvoltage (A)D Power at rated voltage (w)4.28Breaker / AccessoriesAccessories such ascontrol switch indicationlamps etc. furnished asspecified.(Please attach separatesheet giving details of allAccessories, inter locksand safety shutters)A Mechanical safetyinterlockB Automatic safety interlockC Operational interlockD Emergency manual tripE Operation counterF Change / dischargeindicatorG Manual spring chargingfacilityH Auxiliary switch with 6 No+ 6 NC for owner's useI Contacts wear indicator4.29 Auxiliary SwitchA Switch contacts typeB Contacts rating at1) Make & Continuous(Amps)2) Break (Inductive)(Amps)4.30 Net weighting of thebreaker (Kg)4.31Impact load foundationdesign ( to include deadload plus impact value onopening at maximuminterrupting rating) (Kg)4.32 On vacuum loss (Amps)A Possible load currentbreaker (Amps)B Possible fault currentbreaker (Amps)4.33 Overall dimensions390BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A Length (mm)B Breath (mm)C Height (mm)4.34Type test reportomidentical breakerfurnished5 Control & Indications5.1 Push Button Make

Page 72: Tech Spec Ss -III

A Type & Catalog No.B Contact rating at110V/220V.D.CC Make & continuous(Amps)5.2 LED lamps: Make:A Type & Catalog No.B Watts /VoltageC Lamps & lens replaceablefrom front with glass cover5.3 Selector switch: Make:A Type & Catalog No.B Contact ratingC Make & continuous(Amps)D Break (Inductive)(Amps)6 Current Transformer6.1 Make6.2 Types & Voltage Level6.3 Reference standard6.4 C.T ratio as specified6.5Short circuit withstandshort time current for 1sec. - KA rms Dynamiccurrent -KA peak6.6 Class of insulation6.7 Temperature rise6.8 Basic insulation level6.9 For metering & protectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmp6.10 For differential & restrictedearth fault protection391BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1A CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmp6.11 For restricted earth faultprotectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpG Secondary resistance (Ω)6.12 For stand by earth fault

Page 73: Tech Spec Ss -III

protectionA CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpGOver current ratingcontinuous % over load(%)6.13 For sensitive by earth faultprotection (CBCT)A CT ratioB Class of accuracyC Rated burden VAD Knee point voltage VE Excitation current at VK / 4F Rated saturating currentAmpGOver current ratingcontinuous % over load(%)7 Potential Transformer7.1 Make7.2 Types & Voltage Level7.3 Reference standard392BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C17.4 Voltage ratio7.5 AccuracyA Corer-1B Corer-27.6 Rated burdenA Corer-1B Corer-27.7 Over voltage factorA ContinuousB 30 Seconds7.8 Class of insulation7.9 Temperature rise overambient ( 0 C)7.10 Basic impulse level (KVpeak)7.11 Winding connectionA PrimaryB Secondary7.12 FusesA Continuous rating HV / LV(Amp)B Symmetrical fault ratingHV /LV KA rmsC Make7.13 Maximum ratio error atA90% to 100% of ratedvoltage and 25% to 100%

Page 74: Tech Spec Ss -III

of rated secondary burdenat unity power factorB90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.7.14 Maximum Phasedifference atA90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.B90% to 106% of ratedvoltage and 10% to 50%of rated secondary burdenat 0.2 p.f.7.15 E=Weight (Kg)8 Relay8.1 Manufacture8.2 Model Type393BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C18.3 Draw out type with built intest facilities. Yes/ No8.4 Built in test facility Yes /No8.5 Type of mounting8.6 Reference standard8.7 All relays furnished as perdrawing and specification8.8 All relevant relay leafletsand catalogue furnished8.9 Communication port type8.10 Auxiliary Supply8.11 Measurement and dataacquisition feature8.12 Control and supervisionA IEC protocolB Open protocol featureC Programming facilityD Separate output forindividual elementE Event recording facilitynumber of eventsF Required software offered8.13 C.T.secondary current8.14 Self diagnostic feature8.15 Modular design8.16 Relay details8.16.1 Over currentA MakeB TypeC Characteristic availableDRange of settingi. Currentii. Time

Page 75: Tech Spec Ss -III

ERange of settingi. Currentii. TimeF Rated burden8.16.2 Synchronizing check relayA MakeB TypeC Setting range8.16.3 Earth faultA MakeB TypeC Characteristic available394BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1DRange of settingi. Currentii. TimeE Rated burden8.16.4 Over current (Directional)A MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeE Rated burden8.16.5 Earth fault (Directional) ifapplicableA MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeE Rated burden8.16.6 Neutral unbalance relayA MakeB TypeC Characteristic availableDRange of settingi. Currentii. TimeE Rated burden8.16.7 Under voltage relayA MakeB TypeCRange of settingi. Currentii. TimeD Rated burden8.16.8 Over voltage relayA MakeB Type

Page 76: Tech Spec Ss -III

CRange of settingi. Currentii. TimeD Rated burden8.16.9 Busbar differential relayA Make395BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B TypeC High impedance / lowimpedanceDFacility of CT radioadjustment possiblethrough software. Yes / NoE CT supervision facilityavailable. Yes /No8.16.10 Transformer differentialrelayA MakeB TypeC High impedance / lowimpedanceDFacility of CT radioadjustment possiblethrough software. Yes / NoEFacility of transformervector group adjustmentpossible through software.Yes/ NoF Setting rangeG Rated burden8.16.11 Restricted earth fault relayA MakeB TypeC Combined with differentialrelay. Yes / NoD Setting rangeE Rated burden8.16.12 Stand by earth fault relayA MakeB TypeC CharacteristicsD Setting rangeE Rated burden9 Meters9.1 ammeterA MakeB TypeC Reference standardD SizeE ScaleF Accuracy class9.2 VoltmeterA Make396

Page 77: Tech Spec Ss -III

BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1B TypeC Reference standardD SizeE ScaleF Accuracy class9.3 Energy MeterA MakeB TypeC Reference standardD SizeE ScaleF Accuracy classG MeasurementH kWhI kVARhJ kVAHK Any OtherL Data stored capabilityM Pulse output facilityN Data down loading facility10 Secondary Wiring10.1 Type of insulation10.2 Voltage grade10.3 Conductor material10.4 Conductor Size (minimum)and insulation wiringA Potential circuitB Control & current circuit11 Terminal Block11.1 Make11.2 Type11.3 Catalog No.11.4 20% spare terminalfurnished12 Cable Termination12.1 Clearance for power cabletermination12.2 Removable gland plateA Material for multicorecableB Material for single corecableC Thickness of plate13 Name Plate13.1 Material397BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C113.2 Thickness13.3 Size forA Breaker cubicleB Instrument / devices14 Space heater / plugsocket14.1 Cubicle heaterA Thermostat controlledB WattageC Voltage

Page 78: Tech Spec Ss -III

D Resistance (ohms)E Thermostat range14.2 Plug SocketA TypeB Rating14.3Cubical heater & plugsocket circuit providedwith MCB's15 A.C. /D.C. Supply15.1 Isolated switches forincoming supplyA A.C. Type & ratingB D.C. Type & rating15.2 Isolated switches at eachcubicleA A.C. Supply type & ratingB D.C. Supply type & rating16 Tropical Protection16.1 Any Special treatment fortropical protection17 Painting17.1 Finish of switchgearA InsideB Outside18 No. of AccessoriesfurnishedA Breaker lifting & handlingtrolleyB Any other19 Tests19.1 Reference standard19.2 Routine test to beperformed on switchgear19.3 Type test certificatessubmitted20 Drawing / Data398BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C120.1 General arrangement forpanel board20.2 Foundation Panel20.3 Bill of material20.4Cross sectional drawingfor every type ofswitchgear (Add sheets ifnecessary)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________399BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C10SCHEDULE – C10AC DISTRIBUTION BOARDS

Page 79: Tech Spec Ss -III

S.No Description Buyers Requirement Sellers Data1 Panel Construction1.1 Enclosure Type Free standing, indoor, Fullycompartmentalized, Metal clad,Vermin Proof1.2 Enclosure degree of protection IP 5X1.3 Enclosure Material CRCA steel1.4 Load bearing members Minimum 2.5 mm thick1.5 Doors and covers Minimum 2.0 mm thick1.6 Gland Plate (detachable type) 3.0mm MS detachable type orAluminum 5.0mm for singlecore cables1.7 Separate compartment for Bus bar, circuit breaker,incoming cable, outgoing cablePT, LV instruments.1.8 Breaker compartment door Separate with lockable handle1.9 Fixing arrangementi. Doorsii. Coversiii. GasketConcealed hingedBolted with SS boltsNeoprene1.10 Panel Base Frame Steel base frame as permanufacturer’s standard.1.11 Handle Removable bolted covers forcable chamber and busbarchamber shall be provided with“C” type handles1.12 Space Heater Required1.13 Panel extension possibility Required2 MCCB2.1 Mounting Flush Mounted2.2 Rated Operational Voltage(V) 415 volt2.3 Ultimate breaking Capacity2.3.1 630A MCCB As per requirement2.3.2 100A MCCB As per requirement2.4 Rated Service breakingcapacity at rated voltage IcsIcs =100% Icu2.5 Rotary handle Required2.6 Interlocking arrangement Between Incomer MCCBs2.7 Trip time As per requirement2.8 Test Certificates Should have test certificates forbreaking capacities fromindependent test authorities400BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C10CPRI / ERDA or equivalent3 MCB3.1 Rated Operational Voltage(V) 415 VAC 50 Hz3.2 Protection relay/Release Magnetic thermal release forover current and short circuitprotection3.3 Breaking capacity Shall not be less than 10 KA at415 VAC3.4 Mounting Din mounted3.5 MCB classification As required3.6 ISI Marked The complete range shall be

Page 80: Tech Spec Ss -III

ISI markedBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________401BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C2SCHEDULE – C266 kV CONTROL & RELAY PANELParameter Technical Particulars1.00.00 CONTROL PANEL BOARD1.01.00 Make1.02.00 Type1.03.00 Reference Standard1.04.00 Construction1.04.01 Degree of protection1.04.02 Sheet metal thickness mm1.04.03 Floor channel sills, vibration damping padsand kick plate furnished?1.05.00 Equipment Mounting1.05.01 All relays, meters and switches are flushmounted?1.05.02 Relays furnished in draw out cases withbuilt in test facilitate?1.06.00 Name plate1.06.01 Material1.06.02 Thickness1.06.03 Size for:-EquipmentPanels1.07.00 Mimic1.07.01 Material1.07.02 Width1.08.00 Internal Illumination1.08.01 Volt1.08.02 Watt1.08.03 Door switched controlled1.09.00 Space Heater1.09.01 Volt1.09.02 Watt1.09.03 Thermostat Controlled?1.10.00 Plug Socket1.10.01 Type1.10.02 Rating1.11.00Panel Illumination, space heater & plugsocket circuits provided with individualswitch fuse units?1.12.00 AC/DC Supply - Type & rating of isolatingswitch fuse units for1.12.01 Incoming AC Supply1.12.02 Incoming DC Supply1.13.00 Internal Wiring1.13.01 Wire Type1.13.02 Voltage Grade402BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C2

Page 81: Tech Spec Ss -III

1.13.03 Conductor Material1.13.04 Conductor Size fori) Current / control circuitii) Voltage Circuit1.13.05 Wires identified at both ends with ferrules?1.14.00 Terminal block1.14.01 Make1.14.02 Type / Catalogue No1.14.03 20% spare terminals furnished?1.15.00 Ground Bus1.15.01 Materials1.15.02 Size (mm)1.16.00 Painting1.16.01 Type of finish1.16.02 Colour Shade - Inside/Outside1.16.03 Details of Painting procedure finished?2.00.00 BREAKER CONTROL SWITCH2.01.00 Make2.02.00 Type2.03.00 Reference Standard2.04.00 Contact Rating 220V DC 240V AC2.04.01 Make & Continuous (A)2.04.02 Break (inductive) (A)3.00.00 ISOLATING CONTROL SWITCH3.01.00 Make3.02.00 Type3.03.00 Reference Standard3.04.00 Contact Rating 220V DC 240V AC3.04.01 Make & Continuous (A)3.04.02 Break (inductive) (A)4.00.00 METER SELECTOR SWITCH4.01.00 Make4.02.00 Type4.03.00 Reference Standard4.04.00 Contact Rating 220V DC 240V AC4.04.01 Make & Continuous (A)4.04.02 Break (inductive) (A)5.00.00 PUSH BUTTON5.01.00 Make5.02.00 Type5.03.00 Reference Standard5.04.00 Contact Rating5.04.01 Make & Continuous (A)5.04.02 Break (inductive) (A)5.05.00 NO & type of Contacts provided per button6.00.00 LAMPS6.01.00 Make6.02.00 Type6.03.00 Reference Standard6.04.00 Rating:403BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C26.04.01 Volt6.04.02 Watt6.04.03 Series Resistance6.05.00 10 % Extra lamps furnished?6.06.00 Size of lens7.00.00 SEMAPHORE INDICATORS7.01.00 Make

Page 82: Tech Spec Ss -III

7.02.00 Type7.03.00 Diameter of the Disc7.04.00 Operating voltage7.05.00 Burden (Watt DC)7.06.00 Whether latch in type or supply Failuretype8.00.00 INDICATING INSTRUMENT Ammeter Voltmeter8.01.00 Make8.02.00 Type8.03.00 Reference Standard8.04.00 Type of Movement8.05.00 Accuracy Class8.06.00 Scale in Degrees8.07.00 VA Burden9.00.00 MULTIFUNCTION METER9.01.00 Make9.02.00 Type9.03.00 Reference Standard9.04.00 Furnished in Draw out Case or not9.05.00 Type of Register9.06.00 Accuracy Class9.07.00 VA Burden9.07.01 Current Coil9.07.02 Voltage Coil10.00.00 ANNUNCIATOR10.01.00 Make10.02.00 Type10..03.00 Reference Standard10.04.00 No. of Annunciator groups furnished?10.05.00 No. of Windows per group10.06.00 Overall Dimension of a group (mm)10.07.00 Detailed Write-up on Scheme furnished?11.00.00 TRANCDUCERS11.01.00 Whether provided as per specification11.02.00 Make11.03.00 Type11.04.00 Output11.05.00 Accuracy11.06.00 Response Time11.07.00 Power Supply11.08.00 Isolation11.09.00 Catalogue furnished404BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C212.00.00 RELAYS Make Type12.01.00 Relays furnished in draw out cases withbuilt in test facilitates?12.02.00 Line Protection Panel12.03.00 Transformer Panel12.04.00 Bus coupler Panel12.05.00 Miscellaneous Auxiliary Relays12.06.00 Auxiliary Relay, Voltage Operated with4 pair of contacts8 pair of contacts12.07.00 Auxiliary Relay, Current Operated with4 pair of contacts12.08.00 Catalogue of all relays submitted with bidBidders Name : ____________________Signature : ____________________

Page 83: Tech Spec Ss -III

Name : ____________________Designation : ____________________Seal of Company Date : ____________________405BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C3SCHEDULE – C3BATTERY CHARGERSr.No. Description Data to be filled by manufacturer1 Manufacturer equipment type2 Conformance to design standards as perspecification Yes / No3 Conformance to design features as perspecification Yes / No4 Submitted to deviation sheet for eachspecification clause no - Yes / No5 Panel dimension in mm ( length x depth x height)6 Panel weight in kg7 Panel enclosure protection offered8 Voltage regulation as per specification ( value tobe specified)9 Boost charging DC current adjustment range(Value to be specified)10Amount of Ripple in DC in %- output with battery- without battery11 Charger efficiency offered12 Max temperature rise above ambient13 Power factor at rated load14 Rectifier bridge as per specification15 Heat generated by the panel in Kw16 AC MCCB - Make , rating17 DC MCCB - Make , rating18 Rectifier transformer - Make , rating19 Semiconductor rectifier - Make , rating20 DC conductor - Make , rating21.1 DCDB integral part of charger or separate?21.2 MCB for DC distribution boards - Make, rating22 Conformance to metering & indication as perspecification23 Conformance to make of component as perspecification24 Conformance to mimic diagram, labels & finishas per specification25 Submission of component catalogue - Yes / No26 DC charger nominal output current - ( batterytrickle charge + DC load)27 DC charger boost charge current406BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C328 DC battery29 DC battery duty cycle30 DC distribution board output DP MCB feedersrequired30.1 63 amp DP MCB30.2 40 amp DP MCB

Page 84: Tech Spec Ss -III

30.3 25 amp DP MCB30.4 16 amp DP MCB30.5 10 amp DP MCBBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________407BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C4SCHEDULE – C4Ni – Cd BATTERYS.NO. Description Data to be filledby Manufacturer1 Battery ( as per scope of supply annexure A) - Yes / No2 Manufacturing battery type3 Conformance to design standards as per specificationclause no. 2.0 - Yes / No4 Conformance to design feature as per specificationclause no. 3.0 & 4.0 - Yes / No5 Submitted of deviation sheet for each specificationclause no - Yes / No6 Battery GA drawing submitted - Yes / No6.1 Battery selection / sizing calculation submitted - Yes /No7 Battery rating (C5) offered in Ahr7.1 Rating at temperature 27 deg C as per IS7.2 Rating at temperature 20 deg C as per IEC8 Battery race type offered -steel or FRP8.1 Number of steps in a tire8.2 Number of tires in a rack9 Battery bank dimensions in mm ( length x depth xheight)10 Battery cell weight in kg11 Battery cell anode --- no. of plates & thickness in mm12 Battery cell cathode --- no. of plates & thickness in mm13 Battery cell nominal voltage13.1 Battery cell float charge voltage14 Battery cell maximum boost charge voltage15 Battery cell end cell voltage16 Total battery bank float charging voltage required involts17 Total battery bank boost charging voltage required volts17.1 Total time required for boost charging from and cellvoltage to rated voltage /capacity.18 Battery internal resistance ( in Ohms ) at fully chargedcondition19 Heat generated by battery at rated full load (in Kw)20 Electrolyte chemical name21 Electrolyte specific gravity at 27 deg C22 Recommended topping up frequency (in weeks ormonths)23 Amount of gas evolution in one full charge dischargecycle (in liter / Ahr)24 Type of separators used in battery cell408BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C425 Shelf life period ( to retain 90% of energy from full

Page 85: Tech Spec Ss -III

charge condition at 27 deg C)26 Total battery bank short circuit fault level ( in KA)27 Battery bank terminal bus bar with insulating shrouds -Yes /NoBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________409BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C5SCHEDULE – C5STATION AUXILIARY TRANSFORMERSr. Particulars Specified / Required Offered1.0 General1.1 Make1.2 Type Oil immersed, core type, step downlocated generally outdoor but maybe located indoor also with poorventilation. Bidder shall confirm fullrating available in indoor locationalso2.0 Nominal Continuous Rating, KVA2.1 HV winding 400kVA2.2 LV winding 400kVA3.0 Rated voltage ( kV )3.1 HV Winding 11 kv3.2 LV Winding 433 volt4.0 Rated current ( Amps )4.1 HV Winding4.2 LV Winding5.0 Connections5.1 HV Winding Delta5.2 LV Winding Star with neutral5.3 Vector Group reference Dyn116.0 Impedance at principal tap ratedcurrent and frequency, ohm @75 degC6.1 Impedance 5.0 % with IS tolerance410BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C56.2 Reactance6.3 Resistance6.4 Impedance at lowest tap at ratedcurrent and frequency6.5 Impedance at highest tap at ratedcurrent and frequency7.0 Resistance of the winding at 750 C inohm7.1 a) HV7.2 b) LV8.0 Zero sequence impedance in ohm8.1 a) HV8.2 b) LV9.0 Guaranteed maximum losses atprincipal tap full load and 75°Cwithout any positive tolerance,kW

Page 86: Tech Spec Ss -III

9.1 No load losses (max.) 0.79.2 Load losses (max.) 5.19.4 Total I2R losses of windings @ 75deg C, KW9.5 Total stray loses @ 75 deg C, KW9.6 Total losses (max.), KW 5.89.7 No load loss at maximum permissiblevoltage and frequency (approx.),kW10.0 Temperature rise over referenceambient of 50 0C10.1 Top oil by thermometer 0 C 40 0C10.2 Winding by resistance 0 C 45 0C411BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C511.0 Efficiency11.1 Efficiency at 750C and unity powerfactor %11.1.1 at 110% load11.1.2 at 100% load11.1.3 at 80% load11.1.4 at 60% load11.1.5 at 40% load11.1.6 at 20% load11.2 Efficiency at 750C and 0.8 powerfactor lag %11.2.1 at 110% load11.2.2 at 100% load11.2.3 at 80% load11.2.4 at 60% load11.2.5 at 40% load11.2.6 at 20% load11.3 Maximum efficiency at 750C %11.4 Load and power factor at which itoccurs12.0 Regulation , (%)12.1 Regulation at full load at 750 C12.1.1 at unity power factor12.1.2 at 0.8 power factor lagging12.2 Regulation at 110% load at 750 C12.2.1 at unity power factor12.2.2 at 0.8 power factor lagging13.0 Tappings412BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C513.1 Type Off Circuit taps on HV winding13.2 Capacity Full capacity13.3 Range-steps x % variation +5% to -5% @ 2.5%13.4 Taps provided on HV winding (Yes /No)Yes.13.5 Rated current of rotary switch 60 A14.0 Cooling system -14.1 Type of cooling ONAN14.2 No. of cooling unit Groups14.3 Capacity of cooling units14.4 Mounting of radiators14.5 Number of Radiators14.8 Total radiating surface , sqmm

Page 87: Tech Spec Ss -III

14.9 Thickness of radiator tubes, mm Minimum 1.2 mm15.0 Details of Tank15.1 Material Robust mild steel plate withoutpitting and low carbon content15.2 Thickness of sides mm15.3 Thickness of bottom mm15.4 Thickness of cover mm15.5 Confirmation of Tank designed andtested for Vacuum, Pressure ( Ref:CBIP Manual ) , (Yes/ No)15.5.1 Vacuum mm of Hg. / (kN/m2) As per CBIP15.5.2 Pressure mm of Hg. Twice the normal head of oil /normal pressure + 35kN/m2

whichever is lower, As per CBIP15.6 Is the tank lid sloped? Yes15.7 Inspection cover provided (Yes / No) as per clause 4.2.1.515.8 Location of inspection cover (Yes /No)15.9 Min. dimensions of inspection cover (413BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C5provide list of all inspection cover withdimension), mm x mm16.0 Core16.1 Type: Core16.2 Core material grade Premium grade minimum M416.3 Core lamination thickness in mm 0.27 Max16.4 Insulation of lamination With insulation coating on bothsides16.5 Design flux density at rated conditionat principal tap, Tesla16.6 Maximum flux density at 10 %overexcitation /overfluxing, Tesla1.9 Tesla16.7 Equivalent cross section area mm²16.8 Guaranteed No Load current at 100%rated voltage , Amps16.8.1 HV16.8.2 LV16.9 Guaranteed No Load current At 110%rated voltage, Amps16.9.1 HV16.9.2 LV17.0 Type of Winding17.1 HV17.2 LV17.3 Conductor material Electrolytic Copper17.4 Current density (HV/LV) Maximum allowed 3.0 A per sqmm.At any tap17.5 Gauge/area of cross section ofconductor17.5.1 a) HV17.5.1 b) LV414BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C517.6 Insulating material17.6.1 HV Turn17.6.2 LV Turn

Page 88: Tech Spec Ss -III

17.6.3 LV Core -17.6.4 HV - LV -17.7 Insulating material thickness, mm17.7.1 HV Turn17.7.2 LV Turn -17.7.3 LV to Core17.7.4 HV to LV-18.0 Minimum design clearance, mm18.1 HV to earth in Air18.2 HV to earth in oil18.3 LV to earth in Air18.4 LV to earth in oil18.5 Between HV & LV in Air18.6 Between HV & LV in oil18.7 Top winding and yoke18.8 Bottom winding and yoke19.0 Insulating oil19.1 Quantity of oil Ltrs19.1.1 In the Transformer tank19.1.2 In each radiator19.1.4 Total quantity19.2 10% excess oil furnished? Yes19.3 Type of Oil As per BSES Spec Annex -C20.0 Bushing / Support Insulator20.1 Make -20.2 Type415BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C520.2.1 HV side As per Cl. 3.2.7.1 of the spec20.2.2 LV side As per Cl. 3.2.7.2 of the spec20.3 Reference Standard20.4 Voltage class, kV20.4.1 HV side Bushing/ Support Insulator 12 kV20.4.2 LV side line and neutral bushing/Support Insulator1.1 kV20.5 Creepage factor for all bushing /Support Insulator mm/KV31 mm / kV20.6 Rated thermal short time current20.6.1 HV bushing 25 times rated current for 2 secs.20.6.2 LV line and neutral bushing 25 times rated current for 2 secs.20.7 Weight, Kg20.7.1 HV bushing20.7.2 LV line and neutral bushing20.8 Free space required for bushingremoval, mm20.8.1 HV bushing20.8.2 LV line and neutral bushing21.0 Terminal connections21.1 HV Cable size as per annexure A 22.021.2 LV Cable size as per annexure A 23.021.3 LV Neutral Cable size as per annexure A 23.022.0 H.V. Cable box Required22.1 Suitable for cable type , size As per annexure A cl. 22.022.2 Termination height, mm 750 mm, minimum22.3 Gland Plate dimension, mm x mm22.4 Gland Plate material Aluminium

Page 89: Tech Spec Ss -III

22.5 Gland Plate Thickness, mm 5 mm minimum22.5 Phase to phase clearance inside box,mm180 mm22.6 Phase to earth inside box, mm 120 mm416BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C522.7 HV Cable Box Protection Class IP 5523.0 L.V Cable termination arrangement With cable box23.1 Suitable for cable type , size Cable size as per annexure A cl.23.023.2 Termination height, mm 1000 mm, minimum23.3 Gland Plate dimension, mm x mm23.4 Gland Plate material Aluminium23.5 Gland Plate Thickness, mm 5 mm minimum23.5 Phase to clearance inside box, mm 25 mm minimum23.6 Phase to earth inside box, mm 25 mm minimum23.7 LV Cable Box Protection Class IP 5524.0 L.V neutral Cable terminationarrangementSeparate cable box not required25.0 Current Transformer on LV phases25.1 Type25.2 Make25.3 Reference Standard25.4 CT Ratio As per annexure C cl 21.025.5 Burden, VA As per Cl. 3.2.9.5 of the spec.25.6 Class of Accuracy As per Cl. 3.2.9.4 of the spec.25.7 CT terminal box size As per Cl. 3.2.9.8.1 of the spec.26.0 Pressure release device26.1 Minimum pressure the device is set torupture26.1.1 For Main Tank27.0 Fittings Accessories EachTransformer furnished as per ClauseNo 5. (Bidder shall attach separatesheet giving details, make and bill ofmaterials)417BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C528.0 Painting: as per clause for thetransformer, cable boxes, radiator,Marshalling box (Yes/No)29.0 Over all transformer dimensions29.1 Length, mm 170029.2 Breadth, mm 150029.3 Height, mm 170030.0 Transformer Tank Dimensions30.1 Length, mm30.2 Breadth, mm30.3 Height, mm31.0 Weight data31.1 Core, kG31.2 Frame parts, kG31.3 Core and frame, kG31.4 Total Winding, kG31.5 Core , Frame, Winding, kG31.6 Tank, kG

Page 90: Tech Spec Ss -III

31.7 Tank lid, kG31.8 Empty conservator tank, kG31.9 Each radiator empty, kG31.10 Total weight of all radiators empty, kG31.11 Weight of oil in Tank, kG31.12 Weight of oil in Conservator, kG41.13 Weight of oil in each Radiators, kG31.14 Total weight of oil in Radiators, kG31.16 Total Transport weight of thetransformer, kG32.0 Volume Data418BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C532.1 Volume of oil in main tank, litres32.2 Volume of oil between highest andlowest levels of main conservator,litres32.4 Volume of oil in each radiator, litres32.5 Total volume of oil in radiators, litres32.7 Transformer total oil volume, litres33.0 Shipping Data33.1 Weight of heaviest package, kG33.2 Dimensions of the largest package (Lx B x H) mm34.3 Tests34.1 All in process tests confirmed as perCl. (Yes/ No)34.2 All Type Tests confirmed as per Cl.(Yes / No)34.3 All Routine Tests confirmed as per Cl.(Yes/ No)34.4 All Special Tests confirmed as per Cl.(Yes/ No)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________419BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C6SCHEDULE – C611kV CAPACITOR BANKSr. No. Description Data to be filled by Manufacturer2.0 Manufacturer equipment type/make3.0 Conformance to design standards as perspecification clause no. 2.0- Yes/No- Capacitor Unit- Series Reactor- LA- Isolator4.0Conformance to capacitor designrequirements as per specification clause no.4.0 to 7.0 - Yes/No5.0 Submission of deviation sheet for eachspecification clause no. -Yes/No6.0 Capacitor single phase unit6.1 Enclosure sheet metal thickness in mm

Page 91: Tech Spec Ss -III

6.2Hermetic sealing method (pressurewelding/gas welding/sealant/ if any other pl.specify)6.3 No. of series group/unit6.4 No. of parallel elements/ series group6.5 No. of APP layers -double/triple6.6 Thickness of APP film6.7 Thickness of Al foil6.8 Maximum voltage stress per APP layer6.9 Rated capacitance in micro farad6.10 Output at rated system voltage (in kVAR)6.11 Rated current in Amp.7.0 Overall capacitor bank rating7.1At rated system voltage(in kVAR)(requirement is 5.4 MVAR at 11kV with subbank rating of 3.6 & 408 MVAR7.2 Rated current in Ampere7.3 Connection in double star?- Yes/No7.4 Space provided for future capacity addition asper Annexure B clause 9.0? -Yes/No7.5 Accessories provided for future capacityaddition as per Annexure B cl:9.0? -Yes/No7.6 Spare capacitor unit offered? Yes/No420BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C67.7 Series Reactor rating details(bank rating ≥22kV)8.0 Capacitor bank insulation level8.1 Impulse withstand voltage (kV peak)8.2 One minute power frequency withstandvoltage (kV rms)9.1 Bus bar cross-section in sq. mm9.2 Bus bar short time withstand capacity in kAfor 3sec10.1 Bus bar support insulator make & type10.2 Bus bar support insulator voltage class11 Capacitor unit maximum temperature riseabove ambient in Deg. Celsius12 Capacitor unit power loss in kilowatt13 Capacitor bank total power loss in kilowatt14.1 Discharge device type & material14.2Minimum time gap required betweencapacitor switching OFF & ON operation (insec.)15.0 Dimension in mm15.1 Capacitor unit -width x breadth x height15.2 Capacitor bank -width x breadth x height15.3 Enclosure -width x breadth x height16.0 Weight in kg16.1 Capacitor single phase unit16.2 Steel enclosure & rack/structure16.3 Total assembly17.0 Neutral Current Transformer as per clause no.4.20 -Yes/No18.0 Conformance to label & finish as perspecification clause no. 7 -Yes/No

Page 92: Tech Spec Ss -III

19.0 Copy of type test certificate submitted? -Yes/No20.0 Submission of GA drawing/documentation asper Annexure A clause 2.0 -yes/NoBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________421BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C7SCHEDULE – C7LT POWER CABLESFor each size / rating separate GTP need to be furnished.S.No. Description Buyer's requirement Seller's Data1 Make ………………2 Type (AS PER IS) A2XFY (Multicore)3 Voltage Grade (KV) 1.14 Maximum conductor temperatureA Continuous ( 0 C) 90 0CB Short time ( 0 C) 250 0C5 ConductorA Size (mm2) 4CX300,4CX50, 4CX25,4CX10 & 2CX10 SqmmB No. of wire in each conductors Nos. As per ManufacturerstandardC Dia of wires in each conductorsbefore compaction (mm)As per ManufacturerstandardD Shape of conductor As per specificationE Diameter over conductor (mm) ……………F Maximum conductor resistance at 200

C (ohm / km)As per table 2 of IS -7098Part -16 InsulationA Nominal thickness (mm) As per table 3 of IS -7098Part -1B Minimum thickness (mm) ……………C Diameter over insulation (mm)Approx ……………7 Inner SheathA Minimum thickness As per table 5 of IS -7098Part -1B Approx dia over sheath (mm) Approx ……………8 Galvanized steel Armour As per table 6 of IS -7098Part -1A Number of strips As per manufacturer Std.B Size (Thickness X width ) in mm 0.8 x 4C Dia of wire for 2CX10sqmm 1.4mm MinD Dia over Armour -Approx ……………9 Outer Sheath As per table 8 of IS -7098Part -1A Thickness (Minimum)B Colour YellowC Weather proof paint (applicable for 2cx 10 sqmm and 4c x 10 sqmm only) ……………10 Approx. overall dia (mm) ……………

Page 93: Tech Spec Ss -III

11 End Cap Required12 Continuous current rating forstandard I.S. condition laid Direct422BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C7a. In ground 30 0C Amps ……………a. In duct 30 0C Amps ……………a. In air 40 0C Amps ……………13 Short circuit current for 1 sec ofconductor (KAmp) ………………14 Electrical Parameters at Maximumoperating temperatureA Resistance (Ohm / Km) (ACResistance) ……………B Resistance AT 50 C/s (Ohm / Km) ……………C Impedance (Ohm / Km) ………….D Capacitance (Micro farad /Km) …………15 Recommended minimum bendingradius …………….. X O/D16 De-rating factor for following AmbientTemperature in Ground /Aira. At 30 OCa. At 35 OCa. At 40 OCa. At 45 OCa. At 50 OC17 Group factor for following Nos. ofcables laid Touching TrefoilA 3 Nos.B 4 Nos.C 5 Nos.D 6 Nos.18 Process of cross linking ofpolyethylene Dry cureBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________423BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C8SCHEDULE – C8CONTROL CABLESSr. Description Buyers's requirement Seller's Data1.0 Make2.0 Type (As per IS-1554 part-1) YWY3.0 Voltage Grade (kV) 1.14.0 Maximum conductor temperatureA Continuous (°C) 70°CB Short time (°C) 160°C5.0 ConductorA Size (mm2) 10CX2.5, 6CX2.5SqmmB No. of wire in each conductor Nos. As per Manufacturer standardC Dia. of wires in each conductorsbefore compaction (mm) As per Manufacturer standardD Shape of conductor As per the specificationE Maximum conductor resistance at20°C (Ω/Km.) As per Table 2 of IS 8130

Page 94: Tech Spec Ss -III

F Number of conductor core6.0 InsulationA Nominal thickness (mm) As per CI & table 2 of IS-1554Part-1B Minimum thickness (mm)C Diameter over insulation (mm)approx.7.0 Inner SheathA Minimum thickness As per Table 4 of IS-1554Part-1B Approx. dia Over sheath (mm)approx.8.0 Galvanized steel armoura) As per Cl 13.2 of IS 1554Part-1: Galvanized steelround wire armour.b) Minimum area of coverageof armouring shall be 90%.A Number of wire/strip As per Manufacturer standardB Size (Dia/thickness x width) in mmC Dia over Armour -Approx9.0 Outer SheathA Thickness (Minimum) As per Table 7 of IS-1554Part-1B Colour Black10.0 Approx overall dia (mm)11.0 End Cap Required12.0 Drums provide with MS Spindleplate & nut bolts arrangement Required424BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C813.0 Continuous current rating forstandard I.S. condition laid Directa) In ground 30°C Ampsb) In duct 30°C Ampsc) In air 40°C Amps14.0 Recommended minimum bendingradius 12 x O/D15 Minimum Armour Coverage 90% minimum16 Lay Ratios16.1 Main Conductor16.2 ArmourBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________425BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C9SCHEDULE – C9ILLUMINATION SYSTEM1 General+1.01 Make*1.02 Applicable Standards*1.03 Degree of protection2Lighting Panel /Feeder Pillarm Box

Page 95: Tech Spec Ss -III

(LP/ELP/DLP/FPB/EPB/LDB/ELDB/Construction Features)2.01 Make2.02 Rated Value (V)*2.03 Busbar continuous current rating (A)*2.04 Busbar material and cross section 1 2 33 Minimum current breakers :+3.01 Service3.02 Make+3.03 Type*3.04 No. of poles*3.05 Rated continuous current (A)*3.06 Short time current rating (Ka)*3.07 Related Voltage (V)*3.08 Breaking Current (Ka)4 Load Breaking Switches4.01 Service+4.02 Make+4.03 Type*4.04 No. of poles*4.05 Related Voltage (V)*4.06 Rated continuous current (A)*4.07 Rated making current (Ka peak)*4.08 Rated breaking current (Ka)*4.09 Rated short time one (1) second current(Ka)*4.10 Rated dynamic current (kApeak)5 Fuses5.01 Service+5.02 Make*5.03 Type*5.04 Standard applicable*5.05 Related Voltage (V)*5.06 Rated current (A)*5.07 Fusing factor426BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C9*5.08 Category of duty*5.09 Rupturing capacity (prospective current)(Ka)6 Earth Leakage current Breaker+6.01 Make+6.02 Type*6.03 No. of poles*6.04 Rated continuous current (A)6.05 Short time current rating (Ka)6.06 Rated Tripping current7 Lighting Fixtures Type A B C+7.01 Manufacturer+7.02 Type7.03 Description of different types*7.04 Type and wattage of lamp*7.05 Rated life of the lamp*7.06 Applicable standardsNote:- In case luminaries other than the ones specified in specification are offered, allthe deviations shall be listed out otherwise these shall be considered as being fully inline with luminaries specified.8 Receptacles with Switches 1 2 3+8.01 Make

Page 96: Tech Spec Ss -III

+8.02 Type+8.03 Related Voltage (V)*8.04 Rated current (A)8.05 Technical brochures (Attach brochuresand state brochure Nos.)9 Cables / Wire 1 2 39.01 Service+9.02 Make+9.03 Type*9.04 Voltage Grade (V)*9.05 Conductor Material*9.06 Size of conductors (mm2)*9.07 Current rating of conductors (A)9.08 Applicable Standards10 Conduits and Accessories10.01 Make10.02 Type10.03 Material10.04 Applicable Standards11 Lamp and Luminaries IncandescentLampsFluorescentTubesHPSVLamps11.01 Make427BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C911.02 Type*11.03 Lumen output throughout life (Lumen)*11.04 Derating factor due to temperature*11.05 Derating factor due to aging12 Lighting Poles / Towers12.01 Manufacturer12.02 Applicable Standards12.03 Material and Painting12.04 HeightNotes :1. Single asterisk (*) marked particulars are guaranteed.2. Other particulars are bonafide and may vary slightly upon completion of detailed design.3. Particulars against items marked * and + shall be furnished with the Bid.Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________428BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C11SCHEDULE – C11CABLE TRAYS, ACCESSORIES AND TRAY SUPPORT, CONDUITS, PIPESAND DUCTS1 Generala Name of the Contractorb Name of sub contractors, if anyc Applicable standards2 Cable Trays and Fittingsa Cable Trays and Fittingsi. Make

Page 97: Tech Spec Ss -III

ii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)3. Zinc coating per sq meter (gms)3 Conduits , Fitting and Accessoriesa Pipes with fittingi. Makeii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)b Flexible conduits with fittings and accessoriesi. Makeii. Typeiii. Material1. Thickness (mm)2. Thickness of galvanization (microns)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________429BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C12SCHEDULE – C12GROUNDING & LIGHTNING PROTECTION SYSTEMS.No. Description Unit Data by vendor1 Earth mata Materialb Size of conductorc Fault withstand current & duration2 Equipment Earthinga Materialb Size of conductor3 Earth Electrodea Materialb Sizec Length4 Lightning Protection SystemaMaterial and size of horizontal airterminationb Material and size of vertical air terminationc Material and size of down conductord Size of test linke Material of enclosure for test linkf Material and size of earth electrodeBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________430BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C13SCHEDULE – C13CABLE ACCESSORIES1 Cable Accessories

Page 98: Tech Spec Ss -III

1.01 Makes1.02 Termination kits1.03 Straight through joint kits1.04 Cable glands1.05 Cable lugs1.06 Termination blocks1.07 Types1.08 Termination kits1.09 Straight through joints1.1 Cable glands1.11 Cable lugs1.12 Terminal blocksBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________431BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14SCHEDULE – C1466 KV OUT DOOR LIGHTNING ARRESTER432BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14Corporate office: BSES Bhawan, Nehru Place, New Delhi- 19433BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C14Corporate office: BSES Bhawan, Nehru Place, New Delhi- 19Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________434BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15SCHEDULE – C16GAS INSULATED SWITCHGEARProposed Technical data 66 / 11k V Gas insulated switchgearSr.No. Description Proposed Data1.0 Manufacturer2.0 Country of origin3.0 Type designation4.0 Indoor or outdoor5.0Applied standard,publication number andyear6.0 Segregated phase type or‐common enclosure type7.0 Rate voltage kV rms8.0 Number of phase

Page 99: Tech Spec Ss -III

9.0 Rated lightning impulsewithstand voltage kV peak9.1 phase to earth9.2 phase to phase9.3 across open contact10.0 Rated 1 min powerfrequencywithstand voltage kV rms11.0 Auxiliary circuit 50HZ, 1 minwithstand voltage12.0 Rated frequency Hz13.0 Rated short time withstandcurrent kA14.0 Rated peak withstandcurrent kA15.0 Degree of protection forauxiliary and control circuit16.0 Rated supply voltage ofclosing and opening device Vdc17.0 Permissible ambienttemperature 0C435BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1518.0 Maximum temperature riseat..................A19.0 Material of enclosure Al/alloy/steeI20.0 Average Thickness mm21.0 Guarantee SF6 gas lossesper compartment per year %22.0 Design Maintenance period23.0 Rated SF6 gas pressure at 200C24.0Minimum safe gas pressureat 200C required for safeoperation25.0 Setting of pressure reliefdevice ( 20 0C)26.0 Emergency operation atrated voltage and yes/no27.0 No. of Gas Compartment27.1 Bus Bar27.2 Feeder28.0 Heat losses per feeder atrated power KW29.0 Bay width mm30.0 Volume of gas contained ineach compartment M3

Page 100: Tech Spec Ss -III

31.0Burn through time ofenclosure for internal faultof 31.5KASec32.0 Weight per bay ( ready foroperation ) Sec33.0 Heaviest part Kg34.0 Net total weight Kg35.0 Packing detailed drawingnumber ( to be attached ) KgCIRCUIT BREAKER1.0 Manufacturer436BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C152.0 Country of manufacture3.0 Type designation, numberof pole4.0 Indoor or outdoor5.0Applied standard,publication number andyear6.0 Catalog number (to beattached)7.0 Outline drawing number (tobe attached)8.0 Rated voltage kV9.0 Rated lightning impulsewithstand voltage kV peak10.0 Rated 1 min powerfrequencywithstand voltage kV rms11.0 Rated frequency Hz12.0 Rated normal current A13.0 Rated short circuit breaking‐current kA14.0 Rated short circuit making‐current kA15.0 Rated duration of shortcircuits16.0 Rated operating sequence17.0 Short time withstand‐current, 3 sec kA18.0 Total break time ms19.0 Rated capacitive breakingcurrent A20.0 Rated small inductive

Page 101: Tech Spec Ss -III

breaking current A21.0 Rated out of phase breaking‐ ‐current A22.0 Switching over currentfactor pu23.0 Rated characteristics of437BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15short line faults23.1 TRV of supply circuit23.2 TRV peak value uc23.3time delay td24.0 Opening time24.1 Maximum25.0 Maximum closing time26.0 Maximum make time27.0 Minimum dead time28.0 Gas operating pressure28.1 Rated pressureat................... 0C Kg/cm28.2 Alarm pressureat................... 0C Kg/cm28.3 Lock out pressureat................... 0C Kg/cm29.0 Contacts29.1 Type of contact29.2 Material29.3 Surface treatment29.4 Maximum temperature riseat.......A 0C30.0Guaranteed contact life interms of number ofoperation31.0 Operating mechanism31.1 Type31.2Method of operation(hydraulic, pneumatic ormotor operated springcharging)438BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1531.3 Mechanical life in terms ofnumber of operation31.4 Method of interlocking

Page 102: Tech Spec Ss -III

31.5 Number of auxiliarycontacts, NO/NC31.6 Rated voltage of tripping,closing and31.7 interlocking coil vdc31.8 Method of interlocking32.0 Motor32.1 Rated voltage32.2 Voltage range in % of rated32.3 Number of phase32.4 Frequency32.5 Power33.0Number of operationswithin one maintenanceperiod33.1At rated normal currentRecommended33.2 Maximum33.3 At Rated Breaking capacityRecommended33.4 Maximum33.5 Accumulated current perone set KA33.6 Static weight complete set Kg33.7 Dynamic weight completeset Kg33.8 Detailed complete set ofdrawing to be attachedCONDUCTOR439BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15S.No. Description Proposed DataLine & Buscoupler BaysTransformerBays1.0 Manufacturer2.0 Country of manufacture k V3.0 Type designation, numberof poleK V peak4.0 Indoor or outdoor kV rms5.0

Page 103: Tech Spec Ss -III

Applied standard,publication number andyearHz6.0 Catalog number (to beattached)A7.0 Outline drawing number (tobe attached)8.0 Material9.0 Rated voltage10.0 Rated lightning impulsewithstand voltage11.0 Rated 1 min powerfrequencywithstand voltage12.0 Voltage13.0 Rated normal current14.0 Rated short time withstandcurrent, 1sec. kA15.0 Rated Peak withstandcurrent Amp16.0 Rated capacitive current Amp17.0 Gas operating pressure18.0 Rated pressureat................... 0Ckg/cm19.0 First stage alarm pressureat................... 0C20.0 Second stage alarmpressure at................... 0C21.0 Material ( Copper oraluminum)440BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1522.0 Packing detailed drawingnumber( to be attached)DISCONNECTORS.NO. Description Proposed DataBus OtherDisconnectorDisconnector1.0 Manufacturer2.0 Country of manufacturer3.0 Type designation, numberof poles, indoor or outdoor4.0

Page 104: Tech Spec Ss -III

Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0 Rated voltage kV8.0 Rated lightning impulsewithstand voltage8.1 To earth and betweenpole kV peak8.2 Across isolating distance kV peak9.0 Rated power frequencywithstand voltage, 1 min9.1 To earth and between pole kV rms9.2 Across isolating distance kV rms10.0 Rated frequency11.0 Rated normal current12.0 Rated short time withstandcurrent , 3 sec. kA13.0 Rated duration of shortcircuit s441BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1514.0 Rated peak withstandcurrent kA peak15.0Rated capacitive breakingcurrent and recoveryvoltage A, kV16.0Rated inductive breakingcurrent and recoveryvoltage A, kV17.0 Closed loop currentswitching A, V18.0 Gas operating pressure kA18.1 Rated pressureat................. 0C kg/cm18.2 First stage alarm pressureat................. 0C kg/cm18.3 Second stage alarmpressure at............... 0C kg/cm19.0 Contact19.1 Type19.2 Material19.3 Surface treatment

Page 105: Tech Spec Ss -III

19.4 Temperature riseat............................... 0C20.0 Operating mechanism20.1 Type20.2 Method of operation20.3 Method of interlocking20.4 Operating time, close/open s20.5 Number of auxiliary contact,NO/NC20.6 Power requirement W20.7 Rated supply voltage Vac/phaseRated supply frequency HzRecommendedmaintenance period YearPacking detailed drawingnumber( to be attached )442BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Earthing SwitchS.No. Description Proposed DataHigh Speed Slow Acting1.0 Operating speed2.0 Manufacturer3.0 Country of manufacturer4.0 Type designation, numberof poles, indoor or outdoor5.0Applied standard,publication number andyear6.0 Catalog number( to beattached)7.0 Outline drawing number( tobe attached)8.0 Rated voltage k V9.0 Rated lightning impulsewithstand voltage k Vpeak10.0 Rated power frequencywithstand voltage, 1 min. k Vrms11.0 Rated frequency Hz12.0 Rated short circuit making‐current A13.0 Guranteed number of shortcircuitmaking operation14.0 Rated short time withstand‐current15.0 Rated duration of short

Page 106: Tech Spec Ss -III

circuit16.0 Rated peak withstandcurrent17.0 Gas operating pressure17.1 Rated pressure at.................0C17.2 First stage alarm pressureat.................. 0C17.3 Second stage alarmpressure at............. 0C443BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1518.0 Contact18.1 Type18.2 Material18.3 Surface treatment18.4 Temperature riseat................................A19.0 Operating mechanism19.1 Type19.2 Method of operation19.3 Method of interlocking19.4 Operating time, close/open19.5 Number of auxiliary contact,NO/NC19.6 Power requirement W20.0Rated supply voltageVac /Phase20.1 Vdc20.2 Rated supply frequency Hz21.0 Interrupting capability21.1 Inductive current21.2 Interrupting current21.3 Recovery voltage22.0 Capacitive current22.1 Interrupting current22.2 Recovery voltage22.3 Recommendedmaintenance period23.0 Packing detailed drawingnumber ( to be attached )24.0 Interrupting capabilityVOLTAGE TRANSFORMERS.NO. DescriptionProposed Data1.0 Manufacturer

Page 107: Tech Spec Ss -III

444BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C152.0Country3.0 Type designation, numberof phases4.0Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0 Rated voltage k V8.0 Rated Lightning impulsewithstand voltage k V peak9.0 Rated power frequencywithstand voltage, 1 min kV rms10.0 Rated frequency Hz11.0 Rated burden VA12.0 Rated second voltage V13.0 Metering core13.1 Rated output and accuracyclass13.2 Rated transformation ratio13.3 Rated voltage factor14.0 Protective core14.1 Rated output and accuracyclass14.2 Rated transformation ratio14.3 Rated voltage factor15.0 Class of insulation andmaterial 0C16.0 Maximum temperature riseat...........................A kg17.0 Net weight18.0 Packing detailed drawing (to be attached )445BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Current TransformerS.No. Description Proposed DataLine BusCouplerTransformer

Page 108: Tech Spec Ss -III

Bay Bay Bay1.0 Manufacturer2.0Country of manufacturer3.0 Type designation, numberof phases4.0Applied standard,publication number andyear5.0 Catalog number (to beattached)6.0 Outline drawing number (tobe attached)7.0Mounted inside GISenclosure or on powercables8.0 Ring type or bushing type9.0 Rated voltage kV10.0 Rated lightning impulsewithstand voltagekV peak11.0 Rated power frequencywithstand voltage, 1 minkV rms12.0Rated frequency Hz13.0 Rated primary current A14.0 Rated short time thermalcurrent(3s) kA15.0 Rated dynamic current kA peak16.0Rated continuous thermalcurrent in percentage ofrated primary current %17.0 Class of insulation &446BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15material18.0Maximum temperature riseat......................A19.0 Metering core19.1 Rated transformation ratio19.2 Rated output and accuracyclass

Page 109: Tech Spec Ss -III

19.3 Instrument security factor20.0 Protection core20.1Rated transformation ratio20.2 Rated output and accuracyclass20.3 Accuracy limit factor21.0 Net weight22.0 Packing detailed drawingnumber ( to be attached )Sealing EndS.No. Description Proposed Data1.0 Manufacturer2.0 Standards3.0 Material4.0 Rated power frequencyvoltageYes / no4.1 ( 1 min/20 _C ) k V5.0 Breakdown dielectric stress k V /mm6.0 Maximum working dielectricstress k V /mm7.0 Impulse withstand voltage k V8.0 Creepage distance (minimum )mm9.0 Expansion devices Yes / no10.0 Splicing method ofconductor447BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1511.0 Compound for internalinsulation12.0 Nominal weight Kg /pcBay BoardS.No Description Proposed Data1.0 Manufacturer2.0 Type3.0Applied standard,publication number andyear4.0 Confirm to be suppliedaccording to specification Yes /no5.0Material5.1

Page 110: Tech Spec Ss -III

Steel thickness ( minimum )5.2 door Mm‐5.3 side/top/near panels Mm‐6.0 Surface finish k V /mm6.1 Total Paintthickness(Minimum)7.0 Dimension7.1 Length7.2 Width7.3 Height8.0 Total net weight9.0 Packing detailed drawingnumber( to be attached)Type test certificationType test made on identical design of equipment tothose offeredProposed Data448BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15a Circuit breakersTerminal faults: ( Test duties1,2,3,4 and 5to IEC 56 ) ( with a firstphase to clear factor of 1.5 )Making currentShort time current‐DielectricTemperature riseMechanical enduranceShort line faults ( 60%, 75%,‐90% )Out of Phase tests‐ ‐Capacitance switchingLow inductive switchingSpecial tests : ParallelswitchingPartial dischargesb) DisconnectorsShort time current One second‐ThreesecondPeak currentDielectric withstandTemperature enduranceCapacitance switchingPeak currentc) Busbars and Connections

Page 111: Tech Spec Ss -III

Short time current One second‐Threesecondd) Earthing switchesShort time current One second‐Threesecond449BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C15Peak currentMaking current capabilityDielectric withstandDielectric withstandMechanical enduranceType Tests Made onIdentical Designs ofEquipment to ThoseOfferedInterrupting capability forline coupling currents : capacitive currents‐ inductive currents‐

Peak currentMaking current capabilityDielectric withstandBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________450BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16SCHEDULE – C16POWER TRANSFORMERSr.No. Particular Specified / Required Offered1.0 General1.1 Make1.2 Type As per Annexure C ofspecification2.0 Nominal continuous rating, KVA2.1 HV winding As per Annexure C ofspecification2.2 LV winding As per Annexure C ofspecification2.3 Type of Cooling ONAN/ONAF2.4 Rating available at different cooling ONAN - 80%ONAF-100%3.0 Rated voltage (KV)3.1 HV winding As per Annexure C ofspecification3.2 LV winding As per Annexure C ofspecification

Page 112: Tech Spec Ss -III

4.0 Rated current (Amps)4.1 HV winding4.2 LV winding5.0 Connections5.1 HV winding As per Annexure C ofspecification5.2 LV winding As per Annexure C ofspecification5.3 Vector group reference As per Annexure C ofspecification6.0 Impedance at principal tap ratedcurrent and frequency at 75 °C with 100% Rating (% )6.1 Impedance (% ) As per Annexure C ofspecification6.2 Reactance (% )6.3 Resistance (% )6.4 Impedance at lowest tap rated currentand frequency at 75 °C with 100 %Rating (% )6.5 Impedance at highest tap rated currentand frequency at 75 °C with 100 %Rating (% )7.0 Resistance of the winding at 750Catprincipal tap (ohm)7.1 a) HV451BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C167.2 b)LV8.0 Zero sequence impedance ( ohm )8.1 a) HV8.2 b) LV9.0 Guaranteed maximum losses atprincipal tap at full load and 750 Cwithout any positive tolerance kW9.1 No load losses (max.) As per Annexure C ofspecification9.2 Load losses (max.) As per Annexure C ofspecification9.3 Cooler fan losses (max.)9.4 Total I2R losses of winding @ 75 deg C9.5 Total stray losses @ 75 deg C9.6 Total Load losses (max.)9.7 No load loss at maximum permissiblevoltage and frequency (approx.) kW10.0 Temperature rise over reference designambient of 40 0C10.1 Top oil by thermometer 0C 400 C10.2 Winding by thermometer 0C 450 C10.3 Winding gradient at rated current 0C10.3.1 HV10.3.2 LV11.0 Efficiency11.1 Efficiency at 750 C and unity powerfactor %11.1.1 At 110% load11.1.2 At 100% load11.1.3 At 80% load11.1.4 At 60% load

Page 113: Tech Spec Ss -III

11.1.5 At 40% load11.1.6 At 20% load11.2 Efficiency at 750 C and 0.8 power factorlag %11.2.1 At 110% load11.2.2 At 100% load11.2.3 At 80% load11.2.4 At 60% load11.2.5 At 40% load11.2.6 At 20% load11.3 Maximum efficiency %11.4 Load and power factor at which Maxefficiency occurs12.0 Regulation (%)12.1 Regulation at full load at 750 C12.1.1 At unity power factor12.1.2 At 0.8 power factor lagging12.2 Regulation at 110% load at 750 C12.2.1 At unity power factor12.2.2 At 0.8 power factor lagging452BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1613.0 Tapping13.1 Type13.2 Capacity13.3 Range-steps x % variation As per Annexure C ofspecification13.4 Taps provided on HV winding (Yes/No)14.0 OLTC gear14.1 Make14.2 Type14.3 Reference std14.4 No of compartment14.5 Mounting arrangement Side mounted14.6 Rated current Amp14.7 Rated step capacity, kVA14.8 Short circuit withstand for 2 secs, kA14.9 Time required for one step change sec.14.10 Rated voltage for motor, V AC14.11 Rating of motor14.12 Rated voltage for auxiliaries V14.13 Consumption of auxiliaries14.14 OLTC features as per specification,Yes/No14.15 Does the overload rating of OLTCmatch with that of the transformer underall conditions Yes/No15.0 Transformer Monitoring relay – REGDA15.1 Make15.2 Reference standard15.3 Overall dimensions, mm16.0 Cooling system16.1 Type of cooling As per Annexure C ofspecification16.2 No. of cooling unit groups16.3 Capacity of cooling units16.4 Mounting of radiators16.5 Number of radiators and Size16.6 Type & size of radiator header main

Page 114: Tech Spec Ss -III

valve16.7 Type & size of individual radiator valve16.8 Total radiating surface, sq mm16.9 Thickness of radiator tubes, mm Minimum 1.2 mm16.10 Schematic flow diagram of the coolingsystem furnished (Yes/No)16.11 Type and make of Fan motor16.12 No. of fan motor per bank (Working +Standby )16.13 Rated Power Input ( kW)16.14 Rated Voltage, Speed of Motor16.15 Efficiency of motor at Full load(%)16.16 Locked Rotor current(Amps)17.0 Details of tank453BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1617.1 Material Robust mild steel platewithout pitting and lowcarbon content17.2 Thickness of sides mm17.3 Thickness of bottom mm17.4 Thickness of cover mm17.5 Confirmation of tank designed andtested for vacuum pressure (Ref: CBIPmanual ) (Yes/No)17.5.1 Vacuum mm of Hg. / (kN/m2) As per CBIP17.5.2 Pressure mm of Hg Twice the normal head ofoil / normal pressure + 35kN/m2 whichever is lower ,As per CBIP17.6 Is the tank lid slopped? Yes17.7 Inspection cover provided (Yes/No) As per clause No 3.2.1.517.8 Location of inspection cover (Yes/No) As per clause No 3.2.1.517.9 Min. dimensions of inspection cover(provide list of all inspection cover withdimension), mm x mm18.0 Core18.1 Type: Core18.2 Core material grade Premium grade minimumM4 or better18.3 Thickness of lamination mm Max. 0.27 mm withinsulating coating on bothsides18.4 Insulation between core lamination18.5 Design flux density of the core at ratedcondition at principal tap, Tesla18.6 Maximum flux density allowed in thecore at extreme over excitation / overfluxing , Tesla18.7 Equivalent cross section area of core,mm2

18.8 Guaranteed No load current at 90% /100% / 110% rated voltage & frequency( Amp )18.8.1 HV18.8.2 LV19.0 Type of winding19.1 HV19.2 LV

Page 115: Tech Spec Ss -III

19.3 Conductor material Electrolytic copper as perrelevant standard19.4 Maximum current density allowed, Ampper mm2

3.0 A/ mm2

19.5 Gauge/area of cross section ofconductor, mm2

19.5.1 HV19.5.2 LV454BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C1619.6 Maximum current density achieved inwinding (LV/HV/HVT) – Amps/mm2

19.7 Insulating material19.7.1 HV turn19.7.2 LV turn19.7.3 LV- core19.7.4 HV-LV19.8 Insulating material thickness, mm19.8.1 HV turn19.8.2 LV turn -19.8.3 LV to core19.8.4 HV to LV20.0 Minimum design clearance , mm20.1 HV to earth in air20.2 HV to earth in oil20.3 LV to earth in air20.4 LV to earth in oil -20.5 Between HV & LV in Air20.6 Between HV & LV in oil20.7 Top winding and yoke -20.8 Bottom winding and yoke21.0 Insulating oil21.1 Quantity of oil Ltrs -21.1.1 In the transformer tank21.1.2 In each radiator21.1.3 In OLTC chamber21.1.4 Total quantity21.2 10% excess oil furnished? Yes21.3 Type of oil New insulating oil as per IS:335, and CI. 4.2.7 of thespecification21.4 Oil preservation system provided(Yes/No)As per Annexure C ofspecification22.0 Bushing22.1 Make22.2 Type22.3 Reference standard22.4 Voltage class, kV22.4.1 HV side bushing22.4.2 LV side line and neutral bushing22.5 Creepage factor for all bushing mm / kV As per Annexure C ofspecification22.6 Rated current , Amp22.6.1 HV bushing22.6.2 LV line and neutral bushing

Page 116: Tech Spec Ss -III

22.7 Rated thermal shortcurrent22.7.1 HV bushing As per Annexure C ofspecification22.7.2 LV line and neutral bushing As per Annexure C of455BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16specification22.8 Weight Kg22.8.1 HV bushing22.8.2 LV line and neutral bushing22.9 Free space required for bushingremoval, mm22.9.1 HV bushing22.9.2 LV line and neutral bushing23.0 Terminal connections23.1 HV As per Annexure C ofspecification23.2 LV As per Annexure C ofspecification23.3 LV Neutral As per Annexure C ofspecification24.0 H.V. Cable box/Terminals24.1 Suitable for cable/conductor type size As per Annexure C ofspecification24.2 Termination height , mm 1000 mm , minimum24.3 Gland plate dimension mm x mm24.4 Gland plate material Aluminum24.5 Gland plate thickness , mm 5 mm minimum24.5 Phase to clearance inside box /terminals , mm24.6 Phase to earth inside box / terminals ,mm25.0 L.V line side cable box25.1 Suitable for cable type , size As per Annexure C ofspecification25.2 Termination height , mm 1000 mm , minimum25.3 Gland plate dimension mm x mm25.4 Gland plate material Aluminum25.5 Gland plate thickness , mm 5 mm minimum25.6 Phase to clearance inside box /terminals , mm25.7 Phase to earth inside box , mm26.0 LV Neutral cable box26.1 Suitable for cable type , size As per Annexure C ofspecification26.2 Termination height , mm26.3 Gland plate dimension mm x mm26.4 Gland plate material Aluminum26.5 Gland plate thickness , mm 5 mm minimum26.6 Phase to clearance inside box , mm26.7 Phase to earth inside box , mm27.0 Marshalling box cubical provided as perclause no. of spec. (Yes / no)27.1 Mounting of marshalling box Project specific to be filledup (Separate / tankmounted )456BSES Bhawan, Nehru Place, New Delhi- 19

Page 117: Tech Spec Ss -III

Volume – 2 Schedules & Annexure Schedule C1628.0 Neutral Current Transformer (NCT)28.1 Type28.2 Make28.3 Reference standard28.4 CT Ratios28.5 Burden ,VA28.6 Class of Accuracy PS 5P2028.7 KPV , volts , minimum28.8 Resistance, ohm @ 75 deg C,maximum28.9 Magnetizing current @ Vk/4 , mA ,maximum28.10 Short time withstand current 26.3 kA for 3 sec.29.0 Winding current transformer (WCT)29.1 Type29.2 Make29.3 Reference standard29.4 CT ratio29.5 Burden ,VA Manufacturer Std.29.6 Class of accuracy Manufacturer Std.30.0 Pressure release device30.1 Minimum pressure the device is set torupture30.1.1 For main tank30.1.2 For OLTC31.0 Alarm and trip contact ratings ofprotective devices31.1 Rated/making/ breaking currents , Amp@ voltage for31.1.1 PRV for main tank31.1.2 PRV for OLTC31.1.3 Buchholz relay31.1.4 Oil surge relay for OLTC31.1.5 Sudden pressure relay31.1.6 OTI31.1.7 WTI31.1.8 Magnetic oil gauge32.0 Fittings accessories each transformerfurnished as per clause No. (Biddershall attach separate sheet givingdetails, make and bill of materials)33.0 Painting: as per clause for thetransformer , cable boxes, radiator,marshalling box, RTCC etc (Yes/No)34.0 Over all transformer dimensions34.1 Length , mm 6.5 meters maximumallowed34.2 Breadth , mm 5.0 meters maximumallowed34.3 Height , mm 5.0 meters maximum457BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16allowed35.0 Transformer tank dimensions35.1 Length , mm35.2 Breadth , mm35.3 Height , mm36.0 Marshalling box dimensions

Page 118: Tech Spec Ss -III

36.1 Length , mm36.2 Breadth , mm36.3 Height , mm37.0 Weight data37.1 Core, kG37.2 Frame parts, kG37.3 Core and frame, kG37.4 Total winding, kG37.5 Core and frame winding, kG37.6 Tank, kG37.7 Tank lid, kG37.8 Empty conservator tank , kG37.9 Each radiator empty , kG37.10 Total weight of all radiator empty , kG37.11 Weight of oil in tank , kG37.12 Weight of oil in each conservator , kG37.13 Weight of oil in each radiators , kG37.14 Total weight of oil in radiator , kG37.15 OLTC gear including oil , kG37.16 Total transport weight of the transformer, kG37.17 Total transport weight of the transformerwith OLTC and all accessories38.0 Volume data38.1 Volume of oil in main tank , liters38.2 Volume of oil between highest andlowest levels of main conservator ,liters38.3 Volume of oil between highest andlowest levels of OLTC conservator,liters38.4 Volume of oil in each radiator , liters38.5 Total volume of oil in radiators , liters38.6 Volume of oil in OLTC , liters38.7 Transformer total oil volume , liters39.0 Shipping data39.1 Weight of heaviest package, kG39.2 Dimensions of the largest package (L xB x H) mm40.0 Tests40.1 All in process tests confirmed as per Cl.(Yes /No)40.2 All types tests confirmed as per Cl.(Yes /No)40.3 All in routine tests confirmed as per Cl.458BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule C16(Yes /No)40.4 All in special tests confirmed as per Cl.(Yes /No)Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________459BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule E1SCHEDULE – E1TECHNICAL DEVIATIONS FROM THE SPECIFICATION

Page 119: Tech Spec Ss -III

(This shall form part of Technical Bid)All the technical deviation from the tender specification shall be listed out by the Bidder, para bypara in this schedule. Deviation taken in covering letter, standard terms and/or body of the Bid butnot listed herein will make the Bid liable for rejection as ‘Irresponsive’S.No. Section/Sub-Section Part Para Deviation Justification1 2 3 4 5 6Certified that above are the only technical deviations from the tender SpecificationName of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company460BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule E2SCHEDULE – E2COMMERCIAL DEVIATIONS FROM THE SPECIFICATION(This shall form part of Technical Bid)All the commercial deviation from the tender specification shall be listed out by the Bidder, para bypara in this schedule. Deviation taken in covering letter, standard terms and/or body of the Bid butnot listed herein will make the Bid liable for rejection as ‘Irresponsive’.S.No. Section/Sub-Section Part Para Deviation Justification1 2 3 4 5 6Certified that above are the only technical deviations from the tender SpecificationName of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company461BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule FSCHEDULE – FLIST OF DRAWINGS ENCLOSED WITH BID(This shall form part of Technical Bid)S.No. Drawing No Title1 2 3Name of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company462BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & AnnexureSCHEDULE – GSCHEDULE OF TEST(This shall form part of Technical Bid)Tests as per the relevant Indian Standard except as modified and/or as additionally called for in thetender specification shall be performed. Detailed list of the type test certificates enclosed for thevarious equipments offered shall be listed in the schedule.S.No. Type of test Equipment Description1 2 3 41.0 TYPE TESTS2.0 TESTS– DURING MANUFACTURE3.0 ROUTINE TESTS– ON COMPLETION OF MANUFACTURE

Page 120: Tech Spec Ss -III

Name of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company463BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & AnnexureSCHEDULE – HLIST OF INSTRUMENTS, TESTING EQUIPMENTS, TOOLS AND TACKLESFOR ERECTION AND MAINTANANCE(This shall form part of Technical Bid)S.No. Description Capacity Quantity Delivery(1) (2) (3) (4) (5)1.0 INSTRUMENTS, TESTING EQUIPMENT, TOLLS & TACKLES FOR ERECTION(To be taken back by the Bidder after completion of job)2.0 INSTRUMENTS, TESTING EQUIPMENT, TOOLS & TACKLES FOR MAINTENANCE(To be taken back by the Bidder after completion of job)3.0 SPECIAL INSTRUMENTS, TSTING EQUIPMENT, TOOLS & TACKLES FOR ERECTION(To be taken back by the Bidder after completion of job)4.0 SPECIAL INSTRUMENTS, TSTING EQUIPMENT, TOOLS & TACKLES FOR MAINTENANCE(To be taken back by the Bidder after completion of job)Name of Firm : ____________________Signature of Bidder : ____________________Designation : ____________________Date : ____________________Seal of Company464BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule ISCHEDULE – ILIST OF INSTALLATIONSS.No. Purchaser Project PFRef.BriefDescription Value TargetCommissioning Commissioned PerformancePerson to whomreference maybe madeRemarks1 2 3 4 5 6 7 8 9 10 11Bidders Name : ____________________Signature : ____________________Name : ____________________Seal of Company Designation : ____________________Date : ____________________465BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule JSCHEDULE – JDELIVERY TERMS AND CONDITIONS1 Quoted for all the items & in the manner as calledfor in Specification *Yes/No1.1 If not, furnish details of deviations2 Price FOR site delivery basis2.1 Freight:1 Applicable rate * Not included/included

Page 121: Tech Spec Ss -III

2.2 Transit Insurance including forty five(45) daysstorage1 Applicable rate * Not included/included2.3 Excise duty1 Applicable rate * Not included/included2.4 Sales tax1 Applicable rate * Not included/included2.5 Are quoted price firm *Yes/No3 Delivery from LOI3.1 Supply3.2 Erection3.3 Testing & commissioning3.4 Whether penalty clause acceptable *Yes/No4 Validity5 Terms of payment5.1 As per tender specification *Yes/No5.2 If not, give details6 Guarantee period6.1 Is it as per the tender specification *Yes/No6.2 If not, state alternative guarantee period acceptable7 Earnest money furnished *Yes/No8 Agreeable to furnish security deposit as per thetender specification *Yes/No8.1 *Yes/No9 Agreeable to furnish performance Bank as per thetender specification *Yes/No10Correspondence, drawings, test certificates,instruction manuals, BAR/PERT charts progressreports etc. shall be furnished in number of copiesas per distribution schedule attachedto the tender specification*Yes11Agreeable to approval of above documents in our(4) weeks from date of receipt as per tenderspecificationYes12Agreeable to commercial as well as technical terms& conditions of the tender specification, unless listeddeviations are acceptedYes13 Commencing & completion of submission ofdrawings from LOI466BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule JBidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________467BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule KSCHEDULE – KSCHEDULE OF RECOMMENDED SPARESBidder shall offer the prices for spares for destination, rate of taxes & duties to beconsidered shall be indicated.

Page 122: Tech Spec Ss -III

S.No. Description Quantity Unit Price Total Price1 2 3 4 5Bidders Name : ____________________Signature : ____________________Name : ____________________Designation : ____________________Seal of Company Date : ____________________468BSES Bhawan, Nehru Place, New Delhi- 19Volume – 2 Schedules & Annexure Schedule LSCHEDULE – LDECLARATION(This shall form part of Technical Bid)I, ________________________ certify that all the typed data & information pertaining to thesubject tender specification are correct & are true representation of the equipment covered by ourformal Bid No_________________dated________________.I hereby, certify that I am duly authorized representative of the Bidder whose name appears abovemy signature.Bidders Name : ____________________Authorized RepresentativeSignature : ____________________Authorized RepresentativeName (Typed) : ____________________Authorized RepresentativeDesignation : ____________________Seal of Company Date : ____________________Bidder’s Intent : The bidder hereby agrees to fully comply with the requirements& intents of the subject tender specification for the price(s)indicatedAuthorized RepresentativeSignature : ____________________469470471