Dorman Smith Switchgear

Product Portfolio

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 2/182

How to use this catalogue

This catalogue has been designed to enable users to access the information on the

whole product range in a straight-forward and logical manner. We are conscious

that the needs of our customers vary considerably and that, as our markets

continue to grow, many will be dealing with our systems and products for thefirst time.

Where product codes are already well known, the Product and Parts Locator at the

back of the catalogue will direct you to the pages relevant to each occurrence of a

particular item.

Each main product or system category has its own section. The sections are

arranged such that those detailing the simpler and smaller systems are at the

beginning. Exploded views of typical system configurations are given as a guide,

near to the front of each section.

In order to help you to ‘build’ a system, there are detailed Selection Charts at the

end of each section. Again, these are formatted in a logical manner, from mainhousings to incomers, outgoing devices to their accessories. Once a reasonable

level of familiarity with the TE Connectivity Dorman Smith product range has been

attained, complete circuit distribution systems can be readily configured directly

from the Selection Charts alone.

Following the main products sections, the Technical Data and Applications section

provides a high level of detail on both specific products and the principles of circuit

protection in general.

We trust you will find this catalogue informative, helpful and a quick and easy-to-

use tool whenever you need to configure MCB or MCCB distribution schemes.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 3/182

1

Electrical Distribution and Circuit

Protection Product Catalogue

Contents

SP&N Distribution Systems (A-type) 5-14

TP&N Distribution Systems (B-type) 15-34

MCCB Panel Boards (250A & 400A) 35-44

Fuse Switch Panel Boards (800A) 45-56

MCCB Panel Boards (400A & 800A) 57-80

Fuse Combination Units 81-92

Dorman Smith Circuit Protection and 93-128

Modular Devices

MCB and MCCB General Purpose Enclosures 129-130

Technical Data & Applications 131-174

Products & Parts Locator 175-184

How to use this catalogue

Contents 1

TE Connectivity/Dorman Smith 3

2 0

1 0 1

2 4

1 1 2

2 4

1 1 2

2 4

1 1 2

L M

L M 5 0

L M 6 0

L M 2 P

2 0

L M 3 P

1 0

L M 3 P

2 0

L M 3 P

3 0

L M 3 P

4 0

M B 2

3

1 1 0

1 1 0

1 1 0

1 1

2

123

456

9

8

10

7

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 4/182

2

TE Connectivity provides solutions for easy compliance of current regulations within electrical installationsby utilising products from both the Dorman Smith and Crompton Instruments brand portfolios.

Enhancing the design of Dorman Smith products to incorporate metering and surge protection facilities

has made it easy and more economical to comply with the necessary regulations.

Easy Compliance• 17th Edition IEE Wiring Regulations

• Part L2 Building Regulations

• Protection Against Lightning Electrical and

Electronic Systems with Structures BS EN 62305-4

Solutions for Current Regulations

To find out more, please contact our sales team

Tel: +44 (0) 870 870 7500 Fax: +44 (0) 870 240 5289

Email: [email protected], www.dormansmithswitchgear.com

TE connectivity (logo), TE Connectivity and Dorman Smith are trademarks.

Crompton is a trademark of Crompton Parkinson Ltd., and is used by TE Connectivity under licence.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 5/182

TE Connectivity

With a 50-plus year history of leadership, TE Connectivity is a global, $12.1

billion company that designs and manufactures over 500,000 products

that connect and protect the flow of power and data inside the products

that touch every aspect of peoples’ lives. Our nearly 100,000 employees

partner with customers in virtually every industry – from consumerelectronics, energy and healthcare, to automotive, aerospace and

communication networks – enabling smarter, faster, better technologies to

connect products to possibilities.

TE Energy – connecting the world of power

TE Energy, a global operating unit within TE Connectivity, is focused on providing

products and systems for the electrical power industry. TE Energy products are

extensively used by power utilities, equipment manufacturers, railways and by a

wide range of industries.

Each Business Unit within the TE Energy comes with a specialised product line and

focused set of application skills for its specific market niche. Thus TE Energy is able to

bring innovative and technology driven products efficiently to market by

synchronising the product development and manufacturing facility capabilities.

TE Energy is a global supplier of:

• Cable accessories

• Connectors and fittings

• Insulators and insulation

• Surge arresters

• Switching, protection and lighting

• Power measurement and control

Dorman Smith Switchgear

Dorman Smith Switchgear has been a part of TE Connectivity since 2000.

With over 130 years of experience in switchgear design and production,

Dorman Smith business unit continues to bring high quality electrical

distribution and circuit protection equipment to market.

Dorman Smith business unit's line-up of electrical equipment begins with simple

SP&N distribution boards and extends to custom designed, factory built, low-

voltage switchboards for a broad range of commercial and industrial applications.

Dorman Smith and Crompton Instruments products combine through shared

technologies and close co-operation a complementary portfolio of low voltage

power measurement and protection products for energy applications worldwide.

The extensive array of electrical distribution systems suited to a broad scope of ,

commercial and industrial applications, together with instruments for measurement

of key electrical parameters ensures unrivalled capability to fulfil the most

demanding specifications.

End user applications for the company’s products and systems are found in rail

transportation, building management, utilities and infrastructure, together with

the manufacturing sector and many parts of the process industry.

The Dorman Smith product range includes:

• MCB distribution board systems

• MCCB panel board systems

• Fuse combination switch units

• Modular control devices

• Digital metering panel instruments

3

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 6/182

The range of Modis LV distribution switchboard systems is designed and engineered by Dorman Smith business unitand this range of fully type tested assemblies comprehensively covers all low-voltage switchboard requirements up to

3200 amps!

The Modis range of LV distribution switchboard systems is available as wall-mounted or floor standing with front or

rear access.

Assembled by our trained certified partners, the Modis range of LV distribution switchboards is more than capable of

satisfying individual customer needs, for the control and protection of the power distribution system in commercial

and industrial applications.

Dorman Smith Modis Switchboards

4

To find out more, please contact our sales team

Tel: 01772 325 380 Fax: 01772 325 385

Email: [email protected], www.dormansmithswitchgear.com

TE connectivity (logo), TE Connectivity, Dorman Smith and Modis are trademarks.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 7/182

1Section

SP&N Distribution Systems

Loadlimiter 63 Range of SP&N DistributionSystems (A-type)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 8/182

6

Key Features• Distribution board has 125A

rated busbars• Distribution boards can

be stacked

• Choice of switch disconnectoror RCCB incomer• Boards have standard height

(250mm) and depth (116mm)

Available Options• Distribution boards provide from

6 to 22 outgoing ways• Incomer can be double-pole

switch disconnector up to 125Aor double-pole RCCB up to 100A

• Outgoing ways can beconfigured with 10kA-ratedMCBs or RCBOs

• Matching service centres

equipped with 8 to 24modular ways

Additional Features• Single module shunt trip

and auxiliary contacts easilyfitted to MCBs

• Neutral and earth terminal foreach single-pole way

• IP4X Ingress Protection

ComplianceDistribution boards EN 60439-3MCBs EN 60898Contactors EN 61095

RCBOs EN 61009RCCBs EN 61008

Overview

The Dorman Smith Loadlimiter 63 distribution systemincludes a versatile range of MCB distribution boards

and components for constructing comprehensive SP&Ncircuit management solutions. The system is designedfor applications demanding up to 125A incoming and63A outgoing capacity and the distribution boardexceeds the requirements of EN 60439-3.

The array of circuit devices includes an extensive rangeof MCBs, RCBOs, RCCBs and switch disconnectors.The system ensures simple configuration and quickinstallation as demanded by today’s new and retrofit,

commercial and industrial applications.

The standard finish is epoxy powder coating in lightgrey RAL 7035.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 9/182

7

SP&N Distribution System

Modular Devices

• Surge protection• Metering• Contactors• Timer• Residual current circuit breaker

A-type Distribution Boards

• Service centres• Stacking kits

Circuit Protection Devices

• Miniature circuit breakers• Residual current circuit breaker with

overcurrent protection - RCBO• Residual current circuit breakers - RCCB

Incoming Devices

• Switch disconnectors• Residual current circuit

breakers - RCCB

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 10/182

8

1

3

2

4

A-type Distribution Boards• Exceeds the requirements of EN 60439-1• 125A rated• Neutral and earth terminal for each single-pole way• 6-22 single-pole outgoing ways

• IP4X Ingress Protection

6 270 3.8 DA06X

9 323 4.3 DA09X

12 377 4.8 DA12X

15 430 5.3 DA15X

18 484 6.0 DA18X

22 555 7.0 DA22X

Outgoing Width Weight Cat. no.

1-pole ways (mm) (kg)

A-type Service Centre• Accepts all DIN-rail mounting devices• 8-24 modular ways• IP4X Ingress Protection

8 270 3.8 DAS08X

11 323 4.3 DAS11X

14 377 4.8 DAS14X

17 430 5.3 DAS17X

20 484 6.0 DAS20X

24 555 7.0 DAS24X

Modular ways Width (mm) Weight (kg) Cat. no.

Accessories for A-type Distribution Boards

Vertical stacking kits

Stacking kit for 270mm width 1 DAXSK08

Stacking kit for 323mm width 1 DAXSK11

Stacking kit for 377mm width 1 DAXSK14

Stacking kit for 430mm width 1 DAXSK17

Stacking kit for 484mm width 1 DAXSK20

Stacking kit for 555mm width 1 DAXSK24

Earth bar kits

Earth bar 3 DAXEB

Earth bar isolation kit 3 DBXL

Door lock kits

Cylinder door lock 4 DBXCL

Padlock bracket kit 4 DBXPL

Blanking kits

10 busbar terminal blanks 2 DAXTP

MCB blanks

4xTP MCB + 12 busbar terminal blanks 5 DBXBP

5x1P MCB + 5 busbar terminal blanks 6 DBXBM

5x1 ⁄2 MCB blanks - DBXBH

Description Picture Cat. no.

Loadlimiter 63

A-type Distribution Boards and Accessories

5 6

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 11/182

9

Direct connection 35 1 DBXD0

Direct connection 70 2 DAXD1

Switch Disconnector• Exceeds the requirements of EN 60947-3• 50mm2 cable capacity• Duty category of AC22

Switch disconnector 100 2 50 AV2100

Switch disconnector 125 2 50 AV2125

Incoming Current Poles Max. cable Cat. no.

device type rating (A) (mm2)

RCCB 63 30 AC EE63/30/2

RCCB 63 100 AC EE63/100/2

RCCB 63 300 AC EE63/300/2

RCCB 80 30 AC EE80/30/2

RCCB 100 30 AC EE100/30/2

RCCB 100 100 AC EE100/100/2

RCCB time delay 100 100 AC EES100/100/2

Incoming Current Sensitivity Device Cat. no.

device type rating (A) (mA) type

Double-pole RCCB• Exceeds the requirements of EN 61008• Equipped with transient suppression filter• Voltage 230/400V 50/60 Hz

• Double module for both type AC• Terminal capacity: top 25mm2

• Terminal capacity: bottom 35mm2

Direct Connection

Incoming device type Max. cable (mm2) Pic number Cat. no.

SP + NE surge protection DSPM1PN

MOV replacement plug-in module DSPML

MOV neutral/earth replacement plug-in module DSPMNE

Device type Cat. no.

Surge Protection• Plug-in surge protection modules• Integral protection status indicator

• Operating range 200-300V rms max• ‘Hot working’ replaceable modules• Terminals 35mm2 max

See page 116 for more information.

Note: It is recommended that SPM surge protectors are installed on the loadside of a MCB - type C, MCCB or a fused disconnector 63A to provide isolationand protection.

1

2

Loadlimiter 63

A-type Distribution Boards Incoming Options

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 12/182

10

Single-pole MCBs• Exceeds the requirements of EN 60898• 10kA rated breaking capacity to EN 60898• 15kA rated breaking capacity to EN60947-2• Contact position indicator

• 35mm2

cable capacity

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 -

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 T1PD40*

50 K1PB50 K1PC50 T1PD50*

63 K1PB63 K1PC63 T1PD63*

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

6 30 KR1PB0630 KR1PC063010 30 KR1PB1030 KR1PC1030

16 30 KR1PB1630 KR1PC1630

20 30 KR1PB2030 KR1PC2030

32 30 KR1PB3230 KR1PC3230

40 30 KR1PB4030 KR1PC4030

45 30 KR1PB4530 KR1PC4530

6 100 - KR1PC06100

10 100 - KR1PC10100

16 100 - KR1PC16100

20 100 - KR1PC20100

32 100 - KR1PC32100

40 100 - KR1PC40100

Current rating (A) Sensitivity (mA) B type cat. no. C type cat. no.

Single Module RCBOs• Exceeds the requirements of EN 61009• Single module: type AC• 10kA rated breaking capacity• Terminal capacity: top terminals 10mm2

• Terminal capacity: bottom terminals 35mm2

Double Module RCBOs• Exceeds the requirements of

EN 61009, IEC 61009• SP&SwN configuration• Rated breaking capacity up to 10kA• Contact position indicator• Rated voltage Ue ~230V• Rated frequency 50Hz

• Energy limiting class 3• Type AC• Terminal capacity: outgoing

terminals 35mm2

• Terminal capacity: busbar sideterminals 35mm2

Loadlimiter 63

A-type Outgoing Devices

6 30 KR2PB0630 KR2PC0630

10 30 KR2PB1030 KR2PC103016 30 KR2PB1630 KR2PC1630

20 30 KR2PB2030 KR2PC2030

32 30 KR2PB3230 KR2PC3230

40 30 KR2PB4030 KR2PC4030

Current rating (A) Sensitivity (mA) B type cat. no. C type cat. no.

* 6kA/10kA - EN60898/EN60947-2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 13/182

11

Accessories for MCBs and RCBOs

MCB shunt trip (240V AC) 1 KST240

MCB auxiliary/switching contact KAUX1

Auxiliary equipment Picture Cat. no.

MCB dolly locking device 2 KDL

Padlock for dolly locking device XPL

Padlocking Picture Cat. no.

Measuring Current Transformers• System voltage up to 720V• Secondary output of 5A• Operating temperature range of –20°C to +70°C

Description Cable aperture Height Width Cat. no.(mm) (mm) (mm)

100A current transformer 25 65 45 M53Q-100/5

125A current transformer 25 65 45 M53Q-125/5

DIN-rail clip - - - M30-DINCLIP

DIN-rail Mounted Meters• DIN-rail mountable in Loadlimiter 63 service centres

Device type Outputs Width Cat. no.

(mm)

3-phase analogue 1 pulse 71 DRK-3PCT-415

kWh meter

3-phase digital kWh meter 1 pulse 71 DRK-3PCT-415-LCD

1-phase/3-phase digital 1 pulse & 71 RI3-01

multi-function meter 1 modbus1-phase digital kWh meter 1 pulse 54 DRK-1P-230-D63

with integral 63A

current transformer

Loadlimiter 63

A-type Metering and Accessories

1

2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 14/182

12

Loadlimiter 63 Selection Chart - A-type

Distribution Boards

Busbar rating Outgoing ways Width (mm) Weight (kg) Cat. no.

Service Centres

For DIN-rail modules Modular ways

Stacking kit for 270mm width DAXSK08

Stacking kit for 323mm width DAXSK11

Stacking kit for 377mm width DAXSK14

Stacking kit for 430mm width DAXSK17

Stacking kit for 484mm width DAXSK20

Stacking kit for 555mm width DAXSK24

Blanking kits

Busbar terminal blanks (set of 10) DAXTP

Earth bar kits

Earth bar DAXEB

Earth bar isolation kit DBXL

Door lock kits

Cylinder door lock DBXCL

Padlock bracket kit DBXPL

Accessories for DA Type Distribution Boards

Vertical stacking kits

Surge Protection

125A 6 270 3.8 DA06X

125A 9 323 4.3 DA09X

125A 12 377 4.8 DA12X125A 15 430 5.3 DA15X

125A 18 484 6.0 DA18X

125A 22 555 7.0 DA22X

Service centre 8 270 3.8 DAS08X

Service centre 11 323 4.3 DAS11X

Service centre 14 377 4.8 DAS14X

Service centre 17 430 5.3 DAS17X

Service centre 20 484 6.0 DAS20X

Service centre 24 555 7.0 DAS24X

Switch disconnector 100 - 50 AV2100Switch disconnector 125 - 50 AV2125RCCB, type AC 63 30 35 EE63/30/2RCCB, type AC 63 100 35 EE63/100/2RCCB, type AC 63 300 35 EE63/300/2RCCB, type AC 80 30 35 EE80/30/2RCCB, type AC 100 30 35 EE100/30/2RCCB, type AC 100 100 35 EE100/100/2RCCB type AC time delay 100 100 35 EES100/100/2Direct connection - - 35 DBXD0Direct connection - - 70 DAXD1

Incoming Devices

Device type Current rating (A) Sensitivity (mA) Max. cable (mm2)

SP + NE surge protection DSPM1PN

MOV replacement plug-in module DSPML

MOV neutral/earth replacement plug-in module DSPMNE

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 15/182

13

Loadlimiter 63 Selection Chart - A-type

1-pole 6 K1PB06 K1PC06 K1PD06

1-pole 10 K1PB10 K1PC10 K1PD10

1-pole 13 K1PB13 K1PC13 K1PD131-pole 16 K1PB16 K1PC16 K1PD16

1-pole 20 K1PB20 K1PC20 K1PD20

1-pole 25 K1PB25 K1PC25 K1PD25

1-pole 32 K1PB32 K1PC32 K1PD32

1-pole 40 K1PB40 K1PC40 T1PD40*

1-pole 50 K1PB50 K1PC50 T1PD50*

1-pole 63 K1PB63 K1PC63 T1PD63*

SP&N MCBs – B, C & D types

10kA/15kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Single module, type AC 6 30 KR1PB0630 KR1PC0630

Single module, type AC 10 30 KR1PB1030 KR1PC1030

Single module, type AC 16 30 KR1PB1630 KR1PC1630

Single module, type AC 20 30 KR1PB2030 KR1PC2030

Single module, type AC 32 30 KR1PB3230 KR1PC3230

Single module, type AC 40 30 KR1PB4030 KR1PC4030

Single module, type AC 45 30 KR1PB4530 KR1PC4530

Single module, type AC 6 100 - KR1PC06100

Single module, type AC 10 100 - KR1PC10100

Single module, type AC 16 100 - KR1PC16100

Single module, type AC 20 100 - KR1PC20100

Single module, type AC 32 100 - KR1PC32100Single module, type AC 40 100 - KR1PC40100

SP&N RCBOs – B & C types

10kA breaking capacity Current rating (A) Sensitivity B type C typeDevice type (mA) cat. no. cat. no.

Accessories for MCBs and RCBOs

Description Cat. no.

3-phase analogue kWh meter 1 pulse 71 DRK-3PCT-415

3-phase digital kWh meter 1 pulse 71 DRK-3PCT-415-LCD

1-phase/3-phase digital multi-function meter 1 pulse & 1 modbus 71 RI3-01

1-phase digital kWh meter with integral 63Acurrent transformer 1 pulse 54 DRK-1P-230-D63

Current transformer, 100A - - M53Q-100/5

Current transformer, 125A - - M53Q-125/5

Metering

Description Outputs Width (mm) Cat. no.

Auxiliary equipment

MCB shunt trip (240V ac) KST240

MCB auxiliary/switching contact KAUX1

Padlocking

MCB dolly locking device KDL

Padlock for dolly locking device XPL

Blanking pieces

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1 ⁄2 MCB ways) DBXBH

6kA/10kA - EN60898/EN60947-2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 16/182

14

6 270 3.8 DA06X

9 323 4.3 DA09X

12 377 4.8 DA12X

15 430 5.3 DA15X

18 484 6.0 DA18X

22 555 7.0 DA22X

1-pole ways Width (mm) Weight (kg) Cat. no.

A-type Distribution Boards

8 270 3.8 DAS08X

11 323 4.3 DAS11X

14 377 4.8 DAS14X

17 430 5.3 DAS17X

20 484 6.0 DAS20X

24 555 7.0 DAS24X

Modular ways Width (mm) Weight (kg) Cat. no.

A-type Service Centres

All dimensions in mm

Loadlimiter 63Outline Drawings and Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 17/182

2Section

TP&N Distribution Systems

Loadlimiter 63 Range of TP&N DistributionSystems (B-type)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 18/182

16

Key Features• Conforms to EN 60439-3• ASTA certified busbars rated at

10kA for 250ms• Neutral and earth terminal

25mm2

for each single-pole way• Clean earth facility• Enclosures are 484mm wide x

159 deep• 4 to 24 TP&N outgoing ways• IP4X Ingress Protection• Double earth kits available• Extended service centres with

fitted earth and neutral terminals

Available Options• Incomer can be switch

disconnector, contactor, fuseswitch, MCCB or RCCB

• Outgoing ways can be

configured with 10/15kA-ratedMCBs or RCBOs• Matching service centres

equipped with one or two rowsof 18-pole ways

• Surge protection modules canbe accommodated withinstandard configuration

• Modular DIN-rail meter fitswithin standard configuration

Benefits• Extra spreading room for single

module RCBOs• Multi incoming options• Earth/neutral close to phase

terminal• MCBs with symmetrical dual

terminals• Integral metering options• Exceptional flexibility

Applications• Commercial and industrial final

circuit protection• Part L2 building regulations• 17th edition wiring regulations

ComplianceDistribution boards EN60439-3MCBs EN60898Contactors EN61095RCBOs EN61009RCCBs EN61008

Overview

The Dorman Smith Loadlimiter 63 TP&N distributionboard system excels in providing flexible and cost

effective final circuit management solutions forcommercial and industrial applications.

Featuring a comprehensive range of TP&N distributionboards rated at 250A and a wide array of circuitdevices the system ensures simple configuration as wellas quick assembly for new and retrofit applications.

To suit current industry regulation requirements therange has been extended to offer a vast collection of

metering accessories including fully assembled meteredpower and lighting distribution boards. This range

consists of both stocked and customised optionsproviding an easy and flexible solution to comply withPart L2 Building Regulations and specificationrequirements.

The standard finish is epoxy powder coating in lightgrey RAL 7035.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 19/182

17

TP&N Distribution System

Modular Devices

• Surge protection• Meters, current transformers and

wiring looms• Contactors• Timer• Residual current circuit breaker

B-type Distribution Boards

• Service centres• Stacking kits• Assembled metered boards• Metering enclosures

Circuit Protection Devices

• Miniature circuit breakers• Residual current circuit breaker with

overcurrent protection - RCBO• Residual current circuit breaker - RCCB

Incoming Devices

• Switch disconnectors - modular 125A max• Switch disconnectors - MCCB 250A max• Residual current circuit breakers - RCCB• Fuse switch• Moulded case circuit breakers• Contactors

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 20/182

18

B-type Distribution Boards• Exceeds the requirements of EN 60439-3• ASTA certified busbars rated at 10kA for 250mS• Neutral and earth terminal 25mm2 for each single-pole way• Integral clean earth facility

• Enclosure are 484mm wide x 159mm deep• 4-24 TP&N outgoing ways• IP4X Ingress Protection

4 544 10 DBX04R

6 598 11 DBX06R

8 651 12 DBX08R

12 758 15 DBX12R

16 865 18 DBX16R

20 1025 22 DBX20R

24 1132 27 DBX24R

Outgoing Height Weight Cat. no.

3-pole ways (mm) (kg)

250A Incoming Housing• Enclosure to mount any YA3 Frame MCCB up to 250A• Facility to mount two panel mounted meters (using available knockouts)

3-pole unit 321 8 DBXYA3

4-pole unit 321 8 DBXYA3

Incomer Height (mm) Weight (kg) Cat. no.

Service Centres for all B-type Distribution Boards• Accepts all DIN-rail mounting devices• 18 or 36 modular ways• IP4X Ingress Protection

• General purpose enclosure includes facility to mount two panel mounted metersand DIN-rail for current transformers

• Neutral and earth bars fitted as standard

Double earth bar kits are availableOrder as DBTE**X, where ** = 04 to 24.

Note: Devices to be ordered separately.Triple-pole device requires neutral link YA3NL to be ordered separately.

18 x 1-pole ways(single row) 213 5 DBS18X

36 x 1-pole ways(double row) 427 8 DBS36X

General purposeenclosure 213 3 DBMSB

Modular ways Height (mm) Weight (kg) Cat. no.

Supplied without top or bottom plate. Intended for use with removable plate from

distribution board.

Description Cat. no.

YA3 neutral link YA3NL

Loadlimiter 63B-type Distribution Boards and Enclosures

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 21/182

19

Conversion kits plus spares

TP&N to SP&N conversion kit 1 DBXTS

Spare end plate 2 DBXEP

Fixing kit for 24 way distribution boards DBX24FK

Blank way label for 24 way distribution boards DBX24WL

DA18X to B type board stacking kit DBXSKA

Blanking pieces

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) 8 DBXBP

MCB blanks (5x1P MCB ways + 5 busbar terminal blanks) 9 DBXBM

MCB blanks (5x1 ⁄ 2 MCB Ways) DBXBH

Joining kit

Kit for vertically joining two distribution boards 3 DBXJK

Terminal bars

Terminal bar for 6 ways (6 useable 1P ways) 6 DBXT06

Terminal bar for 12 ways (12 useable 1P ways) 6 DBXT12

Terminal bar for 18 ways (18 useable 1P ways) 6 DBXT18

Terminal bar for 24 ways (24 useable 1P ways) 6 DBXT24Blanking kits

Busbar terminal blanks (set of 10) 4 DAXTP

Earth bar kits

Earth bar 7 DAXEB

Earth bar isolation kit 5 DBXL

Double earth bar facility

Earth bar kit with terminal for each outgoing way(where ** = 04, 06, 08, 12, 16, 20 or 24 ways) DBTE**X

Door lock kits

Cylinder door lock 10 DBXCL

Padlock bracket kit 11 DBXPL

Description Picture Cat. no.

1 2

3

4

5 6

7

Loadlimiter 63B-type Distribution Boards Accessories

8

11

10

9

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 22/182

Switch disconnector

Device type Max. cable Sensitivity Incoming Connection(mm2) (mA) device cat. no. kit cat. no.

100A, 3-pole 50 - AV3100 N/A

100A, 4-pole 50 - AV4100 DBXCKR

125A, 3-pole 50 - AV3125 N/A

125A, 4-pole 50 - AV4125 DBXCKR

4-pole RCCB Cat. no.

40A, type AC 35 30 EE40/30/4 DBXCKR

40A, type AC 35 30 EE40/100/4 DBXCKR

63A, type AC 35 30 EE63/30/4 DBXCKR

63A, type AC 35 100 EE63/100/4 DBXCKR

63A, type AC 35 300 EE63/300/4 DBXCKR

100A, type AC 35 30 EE100/30/4 DBXCKR

100A, type AC 35 100 EE100/100/4 DBXCKR

100A, type AC 35 300 EE100/300/4 DBXCKR

100A, type AC, 35 100 EES100/100/4 DBXCKRtime delay

Contactor Cat. no.

40A, 4-pole - - EE4P40CO DBXCKR

63A, 4-pole - - EE4P63CO DBXCKR

Fuse switch Cat. no.

100A, 3-pole 70 - HBF3P100N DBXLSA1

200A, 3-pole 150 - HBF3P200N DBXLSA2

Switch Disconnector 125A Max• Exceeds the requirements of EN 60947-3• 50mm2 cable capacity• Duty category of AC22

RCCBs• Exceeds the requirements of EN 61008• Double width module, 35mm• Type AC• Terminal capacity: 40A-63A: 25mm2

• Terminal capacity: 100A: 35mm2

Contactors – DIN-rail Mounted• Exceeds the requirements of EN 61095• May require de-rating when used with inductive loads – see Contactor De-rating

table in the Technical Applications section

Loadlimiter 63B-type Incoming Options

20

Fuse Combination Units

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 23/182

21

Surge Protection

Device type Width (mm) Cat. no.

3-phase with neutral/earth surge protection module 54 DSPM3PN

MOV replacement plug-in SPM 17.5 DSPML

MOV neutral/earth replacement plug-in SPM 17.5 DSPMNE

• Plug-in surge protection modules• Integral protection status indicator• Thermal and current overload fusing• Three-phase operating range, 380-515V rms max

• ‘Hot working’ replaceable modules

Note: Connection kit DBXCKR must be ordered to provide the additional DIN-railneeded to mount this device in the distribution enclosure below the incomingdevice (for 125A max only). For 250A applications devices should be mounted in aservice centre.

Device type Max. cable Icu Incoming device

(mm2) cat. no.

63A, 3-pole 150* 25kA YA3N3P63T

63A, 4-pole 150* 25kA YA3N4P63T

100A, 3-pole 150* 25kA YA3N3P100T

100A, 4-pole 150* 25kA YA3N4P100T

125A, 3-pole 150* 25kA YA3N3P125T

125A, 4-pole 150* 25kA YA3N4P125T

160A, 3-pole 150* 25kA YA3N3P160T

160A, 4-pole 150* 25kA YA3N4P160T

200A, 3-pole 150* 25kA YA3N3P200T

200A, 4-pole 150* 25kA YA3N4P200T

250A, 3-pole 150* 25kA YA3N3P250T

250A, 4-pole 150* 25kA YA3N4P250T

250A, 3-pole 150* - YA3B3P250Dswitch disconnector

250A, 4-pole 150* - YA3B4P250Dswitch disconnector

YA3 frame MCCB - 250A Max• Standard cable termination 95mm2

• Cable clamps termination - 120mm2

• Maximum cable termination is 150mm2 using reduced palm width M8 cable lugs• MCCBs have thermal and magnetic overloads except switch disconnector

• To be mounted in incoming housing (DBXYA3)

Loadlimiter 63B-type Incoming Options and Surge Protection

Direct Connection Terminal Kits

Terminals 35 1 DBXD0

Terminals 70 2 DBXD1

Terminals 150 3 DBXD2

Description Max. cable (mm2) Picture Cat. no.

1

2

3

* 150mm2 based on using reduced palm width cable lugs

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 24/182

22

Loadlimiter 63DB-type Outgoing Devices

Current B type C type D typerating (A) cat. no. cat. no. cat no.

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 N/A

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 T1PD40*

50 K1PB50 K1PC50 T1PD50*

63 K1PB63 K1PC63 T1PD63*

Single-pole MCBs• Exceeds the requirements of EN 60898• 10kA rated breaking capacity to EN60898• 15kA rated breaking capacity to EN60947-2• Contact position indicator

• 35mm2

cable capacity

Current B type C type D typerating (A) cat. no. cat. no. cat no.

6 K3PB06 K3PC06 K3PD06

10 K3PB10 K3PC10 K3PD10

13 K3PB13 N/A N/A

16 K3PB16 K3PC16 K3PD16

20 K3PB20 K3PC20 K3PD20

25 K3PB25 K3PC25 K3PD25

32 K3PB32 K3PC32 K3PD32

40 K3PB40 K3PC40 T3PD40*

50 K3PB50 K3PC50 T3PD50*

63 K3PB63 K3PC63 T3PD63*

Triple-pole MCBs

* 6kA/10kA - EN60898/EN60947-2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 25/182

23

Current Sensitivity B type C typerating (A) (mA) cat. no. cat no.

6 30 KR1PB0630 KR1PC0630

10 30 KR1PB1030 KR1PC1030

16 30 KR1PB1630 KR1PC1630

20 30 KR1PB2030 KR1PC2030

32 30 KR1PB3230 KR1PC3230

40 30 KR1PB4030 KR1PC4030

45 30 KR1PB4530 KR1PC4530

6 100 - KR1PC06100

10 100 - KR1PC10100

16 100 - KR1PC16100

20 100 - KR1PC20100

32 100 - KR1PC32100

40 100 - KR1PC40100

Single Module RCBOs• Exceeds the requirements of EN 61009• Single module: Type AC• 10kA rated breaking capacity• Terminal capacity: outgoing terminals 10mm2

• Terminal capacity: busbar side terminals 35mm2

Loadlimiter 63B-type Outgoing Devices and Accessories

Double Module RCBOs• Exceeds the requirements of

EN 61009, IEC 61009• SP&SwN configuration• Rated breaking capacity up to 10kA• Contact position indicator• Rated voltage Ue ~230V• Rated frequency 50Hz

• Energy limiting class 3• Type AC• Terminal capacity: outgoing

terminals 35mm2

• Terminal capacity: busbar sideterminals 35mm2

Current rating (A) Sensitivity (mA) B type cat. no. C type cat. no.

6 30 KR2PB0630 KR2PC0630

10 30 KR2PB1030 KR2PC1030

16 30 KR2PB1630 KR2PC1630

20 30 KR2PB2030 KR2PC2030

32 30 KR2PB3230 KR2PC3230

40 30 KR2PB4030 KR2PC4030

1

2

Accessories for MCBs and RCBOs

Auxiliary equipment Picture Cat. no.

MCB shunt trip (240V AC) 1 KST240

MCB auxiliary/switch contact KAUX1

Padlocking Picture Cat. no.

MCB dolly locking device 2 KDL

Padlock for dolly locking device XPL

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 26/182

24

16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Current rating (A) Function Width (mm) Cat. no.

Programmable Timers – DIN-rail Mounted• 250V ac 50/60Hz• Running reserve of 3 years• Switching capacity 150mA

When controlling highly inductive loads, a suitably rated contactor should beemployed with timers, programmers and relays.

Contactors – DIN-rail Mounted• Exceeds the requirements of EN 61095• May require de-rating when used with inductive loads – see Contactor De-rating

table in the Technical Applications section

Loadlimiter 63B-type Modular Devices

Double-pole RCCBs• Exceeds the requirements of EN 61008• Voltage 230/400V 50/60Hz• Type AC• Terminal capacity: 40A-63A: 25mm2

• Terminal capacity: 100A: 35mm2

Four-pole RCCBs

40 30 AC 70 EE40/30/4

40 100 AC 70 EE40/100/4

40 300 AC 70 EE40/300/4

63 30 AC 70 EE63/30/4

63 100 AC 70 EE63/100/4

63 300 AC 70 EE63/300/4

100 30 AC 70 EE100/30/4

100 100 AC 70 EE100/100/4

100 300 AC 70 EE100/300/4

100, time delay 100 AC 70 EES100/100/4

Current rating (A) Sensitivity (mA) Type Width (mm) Cat. no.

40 30 AC 35 EE40/30/2

40 100 AC 35 EE40/100/2

63 30 AC 35 EE63/30/2

63 100 AC 35 EE63/100/2

63 300 AC 35 EE63/300/2

100 30 AC 35 EE100/30/2

100 100 AC 35 EE100/100/2

100, time delay 100 AC 35 EES100/100/2

Current rating (A) Sensitivity (mA) Type Width (mm) Cat. no.

20A 17.5 2P N/O EE2P20CO20A 35 2P N/C EE2P20CC25A 35 4P N/O EE4P25CO25A 35 4P N/C EE4P25CC40A 54 4P N/O EE4P40CO40A 54 4P N/C EE4P40CC

63A 54 4P N/O EE4P63CO63A 54 4P N/C EE4P63CCVenting kit * 9 - LLMV

Current rating (A) Width (mm) Contacts Cat. no.

* Ventilation module must be fitted between alternate pairs of contactorsto prevent overheating.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 27/182

Loadlimiter 63Meters, Current Transformers and Wiring Looms

DIN-rail Mounted Meters for Incoming Circuits• 4 modules width• Fully programmable CT ratios

Note: Connection kit DBXCKR must be ordered to provide the additional DIN-railneeded to mount these devices integral to distribution board below theincoming disconnector.

Panel Mounted Meters for Incoming Circuits• 96mm x 96mm dimensions• Low profile• Fully programmable CT ratios• Can be configured single or three phase

3-phase analogue kWh meter 1 pulse 71 DRK-3PCT-415

3-phase digital kWh meter 1 pulse 71 DRK-3PCT-415-LCD

1-phase/3-phase digital 1 pulse 71 RI3-01multi-function meter & 1 Modbus

Device type Outputs Width (mm) Cat. no.

DIN-rail Mounted Kilowatt Hour Meters for Outgoing Circuits• In-built current transformers, direct connection• DIN-rail mountable in Loadlimiter 63 service centres• Phase cable hole diameter 12.5mm

25

1-phase/3-phase digital 1 pulse 96 CI1-01-PULkWh meter

1-phase/3-phase digital 1 pulse 96 INT-1630-M-5-M-100multi-function meter

1-phase/3-phase digital 1 pulse & 96 INT-1630-M-5-M-110multi-function meter 1 Modbus

1-phase/3-phase digital 1 pulse 96 CI3-01-PULmulti-function meter

Optional pulse plug-in – – CI-PUL-01module for Ci meter

RS485 Modbus plug-in – – CI-MOD-01module for Ci meter

Device type Outputs Width (mm) Cat. no.

1-phase digital kWh meter 1 pulse 54 DRK-1P-230-D63with integral 63A currenttransformer

3-phase digital kWh meter 1 pulse 126 DRK-3P-400-D100with integral 100A currenttransformers

Device type Outputs Width (mm) Cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 28/182

26

Measuring Current Transformers• Up to Class 0.5 accuracy• System voltage up to 720V• Secondary output of 5A• Operating temperature range of –20°C to +70°C

Wiring Looms for TP&N Applications(refer to page 33 for application details)• 1A fuse (rated 400V) metering harness• Current transformer harness

Wiring loom DBX04R – DBX16R Any Crompton DBXW16for single meter Instruments meter

Wiring loom DBX20R – DBX24R Any Crompton DBXW24for single meter Instruments meter

Wiring loom for DBX04R – DBX16R Any Crompton DBXW16Tsingle meter for Instruments metertop distributionboard (verticalstacking)

Description For use with Suitable meter Cat. no.

distribution boards

Power Loom for Sub-Metered Distribution Boards(refer to page 33 for application details)

• 125A and 250A power loom for joining two distribution boards

Power loom for sub metered 125A max DBXWP125distribution board

Power loom for sub metered 250A max DBXWP250distribution board

Description Current rating Cat. no.

Note: Meters, current transformers and enclosure to be ordered separately.

* 95mm2 using standard cable lugs

**150mm2 using reduced palm width lugs

100A 3-in-1 CT case size 35mm 95*/150** M3N1-35-100/5

125A 3-in-1 CT case size 35mm 95*/150** M3N1-35-125/5

200A 3-in-1 CT case size 35mm 95*/150** M3N1-35-200/5

250A 3-in-1 CT case size 35mm 95*/150** M3N1-35-250/5

Meter spreader box - DBMSB

Description Max Cable mm2 Cat. no.

Loadlimiter 63Meters, Current Transformers and Wiring Looms

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 29/182

Loadlimiter 63B-type Assembled Boards Range

125A - Horizontal Arrangement with Two Multi-function Meters

• Two 125A switch disconnectors fitted:One for isolation of whole arrangementOne for isolation of lighting circuits only

• Two meter displays for separate readings of power and lighting consumption

• All power and control wiring fully tested and fitted

• Multi-function meter with pulse output for connection to a compatible BMS system

6 6 811 x 968 x 160 DBXC06NAH06CA

12 12 971 x 968 x 160 DBXC12NAH12CA

No. of power No. of TP Dimensions Cat. no.TP ways lighting ways H x W x D

125A - Vertical Arrangement with One Multi-function Meter (Lighting Only)

• Two 125A switch disconnectors fitted:One for Isolation of whole arrangementOne for isolation of lighting circuits only

• One meter display for readings of lighting consumption only

• All power and control wiring fully tested and fitted• Multi-function meter with pulse output for connection to a compatible BMS system

8 6 1452 x 484 x 160 DBXC08NNV06CA

12 8 1612 x 484 x 160 DBXC12NNV08CA

No. of power No. of TP Dimensions Cat. no.TP ways lighting ways H x W x D

8 8 972 x 968 x 160 DBXE08NAH08NA

No. of power No. of TP Dimensions Cat. no.TP ways lighting ways H x W x D

125A - Vertical Arrangement with Two Meters (kWh or Multi-function)

• Two 125A switch disconnectors fitted:One for Isolation of whole arrangementOne for isolation of lighting circuits only

• Two meter displays for separate readings of power and lighting consumption

• All power and control wiring fully tested and fitted

• Both meters have a pulse output for connection to a compatible BMS system

Multi-function 6 4 1345 x 484 x 160 DBXC06NAV04CA

Multi-function 8 6 1452 x 484 x 160 DBXC08NAV06CA

Multi-function 12 8 1612 x 484 x 160 DBXC12NAV08CA

kWh 8 6 1452 x 484 x 160 DBXC08NJV06CJ

kWh 12 8 1612 x 484 x 160 DBXC12NJV08CJ

Meter No of power No of TP Dimensions Cat. no.type TP ways lighting ways H x W x D

250A - Vertical Arrangement with Two Meters (kWh or Multi-function)

• One 250A switch disconnector fitted providing isolation for whole arrangement

• Two meter displays for separate readings of power and lighting consumption

• All power and control wiring fully tested and fitted• Both kWh and multi-function meters have a pulse output for connection to a

compatible BMS system

Multi-function 8 6 1570 x 484 x 160 DBXE08NAV06NA

Multi-function 12 8 1730 x 484 x 160 DBXE12NAV08NA

kWh 8 6 1570 x 484 x 160 DBXE08NJV06NJ

kWh 12 8 1730 x 484 x 160 DBXE12NJV08NJ

Meter No. of power No. of TP Dimensions Cat. no.type TP ways lighting ways H x W x D

250A - Horizontal Arrangement with Two Multi-function Meters

• One 250A switch disconnector fitted providing isolation for whole arrangement

• Two meter displays for separate readings of power and lighting consumption

• All power and control wiring fully tested and fitted

• Both kWh and multi-function meters have a pulse output for connection to acompatible BMS system

Customised assembled boards available

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 30/182

28

18 x 1-pole ways (single row) 213 5 DBS18X

36 x 1-pole ways (double row) 427 8 DBS36XCable spreader box 213 3 DBMSB

B-type Service Centres

For use with DIN-rail modules Height (mm) Weight (kg) Cat. no.

3-pole housing 321 8 DBXYA34-pole housing 321 8 DBXYA3

B-type Incoming YA3 MCCB Enclosure

Height (mm) Weight (kg) Cat. no.

Loadlimiter 63 Selection Chart - B-type

250A 4 544 10 DBX04R

250A 6 598 11 DBX06R

250A 8 651 12 DBX08R250A 12 758 15 DBX12R250A 16 865 18 DBX16R250A 20 1025 22 DBX20R250A 24 1132 27 DBX24R

B-type Distribution Boards (without incoming device)

Busbar rating TP outgoing ways Height (mm) Weight (kg) Cat. no.

Accessories for all B-type Distribution Boards

Description Cat. no.

Conversion kits plus spares

TP&N to SP&N conversion kit DBXTS

Spare end plate DBXEP

RCCB, Contactor, 4-pole switch disconnector connection kit DBXCKR

Fixing kit for 24 way distribution boards DBX24FK

Blank way label for 24 way distribution boards DBX24WL

Blanking pieces

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1 ⁄ 2 MCB Ways) DBXBH

Joining kit

Mechanical joining kit (For joining two distribution boards vertically) DBXJK

Terminal bars

Terminal bar for 6 ways DBXT06

Terminal bar for 12 ways DBXT12

Terminal bar for 18 ways DBXT18

Terminal bar for 24 ways DBXT24

Blanking kits

Busbar terminal blanks (set of 10) DAXTP

Earth bar kits

Earth bar DAXEB

Earth bar isolation kit DBXL

Double earth bar facility

Earth bar kit with terminal for each outgoing way(where ** = 04, 06, 08, 12, 16, 20 or 24 ways) DBTE**X

Door lock kits

Cylinder door lock DBXCL

Padlock bracket kit DBXPL

125 6/6 811 968 Horizontal 2 x MF DBXC06NAH06CA

125 12/12 971 968 Horizontal 2 x MF DBXC12NAH12CA125 8/6 1452 484 Vertical 1 x MF DBXC08NNV06CA125 12/8 1612 484 Vertical 1 x MF DBXC12NNV08CA125 6/4 1345 484 Vertical 2 x MF DBXC06NAV04CA125 8/6 1452 484 Vertical 2 x MF DBXC08NAV06CA

125 12/8 1612 484 Vertical 2 x MF DBXC12NAV08CA125 8/6 1452 484 Vertical 2 x kWh DBXC08NJV06CJ125 12/8 1612 484 Vertical 2 x kWh DBXC12NJV08CJ

250 8/6 1570 484 Vertical 2 x MF DBXE08NAV06NA250 12/8 1730 484 Vertical 2 x MF DBXE12NAV08NA

250 8/6 1570 484 Vertical 2 x MF DBXE08NJV06NJ250 12/8 1730 484 Vertical 2 x MF DBXE12NJV08NJ250 8/8 972 968 Horizontal 15 x MF DBXE08NAH08NA

B-type Distribution Boards (complete with incoming device/s)

Busbar rating TP outgoing ways Height (mm) Width (mm) Arrangement Meters Cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 31/182

29

Connection kit for surge suppression DBXCKR

3-phase with neutral/earth surge protection module DSPM3PN

MOV replacement plug-in SPM DSPML

MOV neutral/earth replacement plug-in SPM DSPMNE

Surge suppression Cat. no.

Loadlimiter 63 Selection Chart - B-type

Terminals 35 DBXD0

Terminals 70 DBXD1

Terminals 150 DBXD2

Direct connection Max. cable (mm2) Cat. no.

Incoming Devices

Device type Max. cable Sensitivity Incoming device Connection kit

(mm2) (mA) cat. no. cat. no.

Switch disconnector

100A, 3-pole 50 - AV3100 N/A

100A, 4-pole 50 - AV4100 DBXCKR

125A, 3-pole 50 - AV3125 N/A

125A, 4-pole 50 - AV4125 DBXCKR

250A, 3-pole 150 - YA3B3P250D DBXYA3

250A, 4-pole 150 - YA3B4P250D DBXYA3

4-pole RCCB40A, type AC 35 30 EE40/30/2 DBXCKR

40A, type AC 35 100 EE40/100/2 DBXCKR

63A, type AC 35 30 EE63/30/4 DBXCKR

63A, type AC 35 100 EE63/100/4 DBXCKR

63A, type AC 35 300 EE63/300/4 DBXCKR

100A, type AC 35 30 EE100/30/4 DBXCKR

100A, type AC 35 100 EE100/100/4 DBXCKR100A, type AC 35 300 EE100/300/4 DBXCKR

Contactor

40A, 4-pole - - EE4P40CO DBXCKR

63A, 4-pole - - EE4P63CO DBXCKR

Fuse switch

100A, 3-pole 70 - HBF3P100N DBXLSA1

200A, 3-pole 150 - HBF3P200N DBXLSA2

100A current transformer 25 80 <1 M3N1-35-100/5125A current transformer 25 80 <1 M3N1-35-125/5

200A current transformer 25 80 <1 M3N1-35-200/5

250A current transformer 25 80 <1 M3N1-35-250/5

Current Transformers

Description Cable Height Weight Cat. no.

aperture (mm) (mm) (kg)

B-type Metering

Device type Outputs Width (mm) Cat. no.

3-phase DIN-rail mounting analogue kWh meter 1 pulse 71 DRK-3PCT-415

3-phase DIN-rail mounting digital kWh meter 1 pulse 71 DRK-3PCT-415-LCD

1-phase/3-phase DIN-rail mounting digitalmulti-function meter 1 pulse & 1 Modbus 71 RI3-01

1-phase/3-phase digital kWh meter 1 pulse 96 CI1-01-PUL

1-phase/3-phase digital multi-function meter 1 pulse 96 INT-1630-M-5-M-100

1-phase/3-phase digital multi-function meter 1 pulse & 1 Modbus 96 INT-1630-M-5-M-1101-phase/3-phase digital multi-function meter 1 pulse 96 CI3-01-PUL

Optional pulse plug-in module for Ci meter – – CI-PUL-01

RS485 Modbus plug-in module for Ci meter – – CI-MOD-01

1-phase DIN-rail mounting digital kWh meter 1 pulse 54 DRK-1P-230-D63with integral 63A current transformer

3-phase DIN-rail mounting digital kWh meter 1 pulse 126 DRK-3P-400-D100with integral 100A current transformers

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 32/182

30

MCB shunt trip (240V AC) KST240

MCB auxiliary/switch contact KAUX1

Padlocking

MCB dolly locking device KDL

Padlock for dolly locking device XPL

Blanking pieces

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBMMCB blanks (5x1 ⁄ 2 MCB ways) DBXBH

1-pole 6 30 KR1PB0630 KR1PC0630

1-pole 10 30 KR1PB1030 KR1PC1030

1-pole 16 30 KR1PB1630 KR1PC1630

1-pole 20 30 KR1PB2030 KR1PC2030

1-pole 32 30 KR1PB3230 KR1PC3230

1-pole 40 30 KR1PB4030 KR1PC4030

1-pole 45 30 KR1PB4530 KR1PC4530

1-pole 6 100 - KR1PC06100

1-pole 10 100 - KR1PC10100

1-pole 16 100 - KR1PC16100

1-pole 20 100 - KR1PC20100

1-pole 32 100 - KR1PC32100

1-pole 40 100 - KR1PC40100

RCBOs

10kA breaking Current Sensitivity B type C type

capacity, AC type rating (A) (mA) cat. no. cat. no.

Loadlimiter 63 Selection Chart - B-type

1-pole

1-pole 6 K1PB06 K1PC06 K1PD06

1-pole 10 K1PB10 K1PC10 K1PD101-pole 13 K1PB13 K1PC13 N/A

1-pole 16 K1PB16 K1PC16 K1PD16

1-pole 20 K1PB20 K1PC20 K1PD20

1-pole 25 K1PB25 K1PC25 K1PD25

1-pole 32 K1PB32 K1PC32 K1PD32

1-pole 40 K1PB40 K1PC40 T1PD40*

1-pole 50 K1PB50 K1PC50 T1PD50*

1-pole 63 K1PB63 K1PC63 T1PD63*

3-pole

3-pole 6 K3PB06 K3PC06 K3PD06

3-pole 10 K3PB10 K3PC10 K3PD10

3-pole 13 K3PB13 N/A N/A3-pole 16 K3PB16 K3PC16 K3PD16

3-pole 20 K3PB20 K3PC20 K3PD20

3-pole 25 K3PB25 K3PC25 K3PD25

3-pole 32 K3PB32 K3PC32 K3PD32

3-pole 40 K3PB40 K3PC40 T3PD40*

3-pole 50 K3PB50 K3PC50 T3PD50*

3-pole 63 K3PB63 K3PC63 T3PD63*

TP&N – B, C & D types

10kA/15kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Accessories for MCBs and RCBOs

Auxiliary equipment Cat. no.

* 6kA/10kA - EN60898/EN60947-2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 33/182

31

Modular contactor, 20 2P N/O 17.5 EE2P20COAC1 230V

Modular contactor, 20 2P N/C 17.5 EE2P20CCAC1 230V

Modular contactor, 25 4P N/O 35 EE4P25COAC1 400V

Modular contactor, 25 4P N/C 35 EE4P25CCAC1 400V

Modular contactor, 40 4P N/O 35 EE4P25CCAC1 400V

Modular contactor, 40 4P N/C 35 EE4P40CCAC1 400V

Modular contactor, 63 4P N/O 54 EE4P63COAC1 400V

Modular contactor, 63 4P N/C 54 EE4P63CCAC1 400V

Venting kit 9 LLMV

Contactor Current Rating (A) Contacts Width (mm) Cat. no.

Timer 16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Programmable Timer

Loadlimiter 63 Selection Chart - B-type

Type AC 40 30mA 35 EE40/30/2Type AC 40 100mA 35 EE40/100/2Type AC 63 30mA 35 EE63/30/2Type AC 63 100mA 35 EE63/100/2Type AC 63 300mA 35 EE63/300/2Type AC 80 30mA 35 EE80/30/2Type AC 100 30mA 35 EE100/30/2Type AC 100 100mA 35 EE100/100/2Type AC time delay 100 100mA 35 EES100/100/2

2-pole RCCB

Description Current rating (A) Function Width (mm) Cat. no.

Type AC 40 30mA 70 EE40/30/4Type AC 40 100mA 70 EE40/100/4Type AC 63 30mA 70 EE63/30/4Type AC 63 100mA 70 EE63/100/4

Type AC 63 300mA 70 EE63/300/4Type AC 80 30mA 70 EE80/30/4Type AC 100 30mA 70 EE100/30/4Type AC 100 100mA 70 EE100/100/4Type AC time delay 100 100mA 70 EES100/100/4

4-pole RCCB

Description Current rating (A) Sensitivity Width (mm) Cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 34/182

32

B-type Distribution Boards (without incoming device)

4 1 544 10 DBX04R6 1 598 11 DBX06R

8 1 651 12 DBX08R

12 1 758 15 DBX12R

16 1 865 18 DBX16R

20 1 1025 22 DBX20R

24 1 1132 27 DBX24R

3-pole ways Drawing Height Weight Cat. no.

no. (mm) (kg)

YA3 Frame MCCB Enclosure for B-type Distribution Boards

3-pole MCCB 2 321 8 DBXYA3

4-pole MCCB 2 321 8 DBXYA3

Incomer Drawing Height Weight Cat. no.

no. (mm) (kg)

1

2

3

All dimensions in mm

18 x 1-pole ways(single row) 213 5 DBS18X

36 x 1-pole ways(double row) 427 8 DBS36X

General purposeenclosure 213 3 DBMSB

Modular ways Height (mm) Weight (kg) Cat. no.

Supplied without top or bottom plate. Intended for use with removable plate fromdistribution board.

Loadlimiter 63Outline Drawings and Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 35/182

Loadlimiter 63 Metering Selection Chart

Split Metered Power & Lighting Board Single Board

125A 250A

YA3B3P250D

YA3B4P250D

Or any YA3 MCCB

AV3125

AV3100

AV4125

AV4100

125A Incomer 250A Incomer

AV3100

AV3125

AV4100

AV4125

Integral

DBXW16

OR

DBXW24

DBXW16T*

DBXW16

OR

DBXW24

Select meter wiring loom

x1 for bottom board

Select meter wiringloom x1 for top board

Select meterwiring loom x2

Vertical Arrg’t Horizontal Arrg’t

DBMSBDBXJK

YA3B3P250D

YA3B4P250D

Or Any YA3

MCCB

Spreader box

Select dist board x2

DBX04RDBX06R

DBX08R

DBX12R

DBX16R

DBX20R

DBX24R

Select incomer

M3N1-35-100/5

M3N1-35-125/5

M3N1-35-200/5

M3N1-35-250/5

DBXD0

see table 1

DBXD0

see table 1

DBXWP125 x1 DBXWP250 x1

DBMSB x1 DBXYA3 x1 DBXYA3

Select meter x2

INT-1630-M-5-M-100

(Multi-function)

CI3-01-PUL

CI1-01-PUL

Select outgoing devices

* Top board max size 16 way (vertical arrangement only)

Select dist board x1

DBX04RDBX06R

DBX08R

DBX12R

DBX16R

DBX20R

DBX24R

Select incomer

Select meter

** Meter RI3-01 only

Select CT x3

M3N1-35-100/5

M3N1-35-125/5

M3N1-35-200/5

M3N1-35-250/5

DBXW16

OR

DBXW24

Select meter wiringloom x1

Cable connection terminals

DBXD0

see table 2

INT-1630-M-5-M-100

CI1-01-PUL

RI3-01

CI3-01-PUL

Select outgoing devices

Switch disconnectors (125A max)

Meter enclosure (125A)

Meter enclosure

(125A)

DIN-rail

mounting kit

Meter enclosure (250A) Meter enclosure (250A)

Power loom (125A) Power loom (250A)

Cable connection terminals Cable connection terminals

Current transformers (125A) Current transformers (250A)

Current transformers

Vertical joining kit Meter enclosure (DB 2)

Switch disconnectors (250A max) Switch disconnectors Switch disconnectors

DBMSB DBXCK **

1 5 3 02 4 2 02 3 N/A 1

Quantity of AV DBXD0's DBXD0'S DBXCK(switch disconnectors) required (125A) required (250A) required

Main incomer 2 1 1mounted in DBMSBMain incomer mounted 0 0 -in standard position

DBXD0’s DBXD0 DBXWP125required 125A required 250A (125A rated only)

Table 1 Table 2

33

Modbus available

Modbus available

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 36/182

34

Example 1 Requirement – Vertically stacked, 125A split meteredpower and lighting distribution board• 8 way TP&N power board• 6 TP&N lighting board• Multi-function meters

DBX08R 1 8 way TP&N distribution board

DBX06R 1 6 way TP&N distribution board

AV3125 1 125A – 3P switch disconnector

DBMSB 1 Spreader box with facility to mount 2 panelmounted meters

DBXJK 1 Mechanical joining kit for joining twovertically stacked distribution boards

DBXWP125 1 Power loom for split metered distributionboard (125A)

INT-1630-M-5-M-100 2 3-Phase Integra 1630 multi-function meterwith 1 pulse output

DBXW16 1 Wiring loom for single meter

DBXW16T 1 Wiring loom for single meter for topdistribution board when vertically stacked

DBXD0 5 Cable joining terminal kit

M3N1-35-125/5 2 125A 3-in-1 current transformers

Cat. no. Quantity Description

Flow Chart Examples

Example 1: Bill of Material List

Example 2: Bill of Material List

Example 2 Requirement – Single Metered Distribution Board (250A)• 24 way TP&N distribution board• KWh meter

DBX24R 1 24 way TP&N distribution board

YA3B3P250D 1 250A–3P MCCB switch disconnector

DBXYA3 1 250A incoming enclosure with facility tomount 2 panel mounted meters

CI1-01-PUL 1 3-phase Kilowatt hour meter with 1 pulseoutput (panel mounted)

DBXW24 1 Wiring loom for single meter

DBXD0 1 Cable joining terminal kit

M3N1-35-250/5 1 250A current transformers

Cat. no. Quantity Description

Split metered 125A

Split metered 250A

Single metered 125A & 250A

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 37/182

3Section

MCCB Panel Boards

Loadbank 125 Range (250A and 400A Ratings)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 38/182

36

Key Features• ASTA certified busbars with a

short circuit rating of 25kA for1 second (250A) and 25kA for 3seconds (400A)

• Shunts, UVRs and auxiliariesare common for YA2, YA3 andYA5 MCCBs

• Single frame size outgoingMCCBs from 16A to 125A

• Generous cable-spreadingspace for incoming andoutgoing cables

• Common width (700mm) anddepth (190mm) for all enclosures

• A single part number identifiesthe complete main enclosure

Available Options• 250A panel boards with 6, 8 or

12 triple-pole outgoing ways canchoose incoming devices fromthe YA3 MCCB range or adirect connection

• 400A panel boards with 6, 8, 12or 16 triple-pole outgoing wayscan choose incoming devicesfrom the YA5 MCCB range or adirect connection

• Panel build options include:• Cable spreader box• Service centre with 24

single-pole ways• Integra metering housing• YA3 frame outgoing housing

Additional Features• Neutral and earth terminal for

each single-pole way• Clean earth facility• 250A panels use YA3 MCCBs for

incoming devices• 400A panels use YA5 MCCBs

for incoming devices• All versions use YA2 MCCBs for

outgoing devices• All triple-pole MCCBs have

adjustable overload andinstantaneous trips

Compliance

Panel boards EN 60439-1MCCBs EN 60947-2

Overview

Featuring busbar ratings of 250A and 400A with sevenMCCB panel board designs Loadbank 125 system offers

an uncomplicated solution for power distribution incommercial and industrial applications. Outgoing devicesconsist of a single frame size utilising the Loadline YA2frame as a cost effective option for circuit protection.

New developments include ASTA certified busbars with ashort-circuit withstand rating of 25kA-3sec (400Abusbars only) and Form 3 separation is now as standard.

Available options now include a versatile range of

accessories for both incoming and outgoing metering forcompliance with Part L2 Building Regulations. A

multitude of add-on enclosures, including service centresand a unique outgoing housing for 160A to 250A YA3frame MCCB matching the dimensional profile of thestandard enclosure.

The standard finish is epoxy powder coating in light greyRAL 7035.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 39/182

37

MCCB Panel Boards (250A and 400A Rating)

Modular Devices

• Surge protection• Meters, current transformers and

wiring looms• Contactors• Timer• Earth leakage device

MCCB Panel Boards

• Service centres• Metering enclosures

Circuit Protection Devices

• Moulded case circuit breakers (125A max)

Incoming Devices

• Switch disconnector• Moulded case circuit breakers

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 40/182

38

250A Panel Board Enclosures• ASTA certified busbars rated 25kA-1sec• Form 3 with outgoing terminals shields fitted• IP4X protection rating• Optional incoming terminal shield available

• Accepts single frame size YA2 MCCB (Max 125A) outgoing devices

No. of TP Incoming device Height Width Depth Cat. no.

outgoing ways type (mm) (mm) (mm)

6 YA3 frame 904 700 190 PB206YA

8 YA3 frame 994 700 190 PB208YA

12 YA3 frame 1174 700 190 PB212YA

Incoming Current rating No. of poles Cat. no.

device type (A)

Switch disconnector 250 3 YA3B3P250D

MCCB 160 3 YA3N3P160TMCCB 200 3 YA3N3P200T

MCCB 250 3 YA3N3P250T

Switch disconnector 250 4 YA3B4P250D

MCCB 160 4 YA3N4P160T

MCCB 200 4 YA3N4P200T

MCCB 250 4 YA3N4P250T

Description Cat. no.

3-pole incoming terminal shroud YA3TS3P

4-pole incoming terminal shroud YA3TS4P

Door cylinder lock DBXCL

Door padlock device DBXPL

3-pole blanking piece LBYA2BP3P

4-pole incoming connection kit PB4PNC250

250A Panel Board Accessories

250A and 400A Panel Board Accessories Add-on Units

• Cable spreader box• 24 way service centre• Housing to accommodate outgoing YA3 MCCB

250A Panel Board Incoming Devices• Standard cable termination 95mm2

• Maximum cable termination is 150mm2 using reduced palm width M8 cable lugs• MCCBs have thermal and magnetic overloads except switch disconnector• Four-pole incoming devices require adapter kit• YA3 cable clamp termination 120mm2 (sold separately)

Description Height (mm) Cat. no.

Cable spreader box 270 PBYA2CSB

Service centre with 24-1 pole ways 270 PBYA2SC24

160A–250A YA3 outgoing housing 450 PBYA2OG

Loadbank 125250A Panel Board Enclosures Form 3 25kA-1sec

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 41/182

39

Loadbank 125400A Panel Board Enclosures Form 3 25kA-3secs

400A Panel Board Enclosures• ASTA certified busbars rated 25kA-3secs• Form 3 as standard• IP4X protection rating• Optional incoming terminal shield available

• Accepts single frame size YA2 MCCB (Max 125A) outgoing devices

No. of TP Incoming device Height Width Depth Cat. no.

outgoing ways type (mm) (mm) (mm)

6 YA5 frame 1084 700 190 PB406YA

8 YA5 frame 1174 700 190 PB408YA

12 YA5 frame 1354 700 190 PB412YA

16 YA5 frame 1534 700 190 PB416YA

Description Picture number Cat. no.

3-pole incoming terminal shroud 1 YA5TS3P

4-pole incoming terminal shroud – YA5TS4P

Door cylinder lock 2 DBXCL

Door padlock device 3 DBXPL

3-pole blanking piece – LBYA2BP3P

4-pole incoming connection kit – PB4PNC400

400A Panel Board Accessories

Incoming Current rating No. of poles Cat. no.

device type (A)

Switch disconnector 400 3 YA5B3P400D

MCCB 250 3 YA5N3P250T

MCCB 400 3 YA5N3P400T

Switch disconnector 400 4 YA5B4P400D

MCCB 250 4 YA5N4P250T

MCCB 400 4 YA5N4P400T

Direct connection 400 3/4 PBYA2DC4

400A Panel Board Incoming Devices• Standard cable termination 95mm2

• Maximum cable termination is 185mm2 using reduced palm width M8 cable lugs• MCCBs have thermal and magnetic overloads except switch disconnector• Four-pole incoming devices require adapter kit

1

2

3

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 42/182

40

Metering Housing• New stackable meter housing for incoming and outgoing metering• Designed to fit up to six DIN-rail mounted meters (4 mod max)• Can be mounted top or bottom

• Includes DIN-rail for facility to mount current transformers and fuses

Metering Harnesses• A collection of meter harnesses for metering incoming and outgoing circuits• Please refer to page 44 for easy selection chart

Description Cat. no.

Incoming meter loom PBWI

Voltage tap off loom for outgoing metering PBWP

CT harness for 1 meter PBWCT

Power loom for 6 outgoing meters PBWM6

Description Cat. no.

Digital multi-function meter with 1 pulse and RI3-01

1 RS485 Modbus ouputAnalogue kWh meter with 1 pulse DRK-3PCT-415

Description Height (mm) Weight Cat. no.

Meter housing 450 - PBYA2MB

Four Module DIN-rail Meter

Description Max cable size mm2 Cat. no.

250A 3-in-1 CT case size 3 150 M3N1-45-250/5

400A 3-in-1 CT case size 3 150 M3N1-45-400/5

Incoming Current Transformers

Description Max cable size mm2 Cat. no.

60A 3-in-1 current transformer 50 M3N1-25-60/5Case size 25mm

100A 3-in-1 current transformer 50 M3N1-25-100/5Case size 25mm

125A 3-in-1 current transformer 50 M3N1-25-125/5Case size 25mm

Outgoing Current Transformers

Loadbank 125250A/400A Surge Protection and Metering Accessories

Surge Protection Mounting Kits• Easily installed inside panelboard closely located to incoming device• DIN-rail mounting for triple-pole MCB• C/W 30kA three-phase surge protector• Remote status indication

• Site fault indication

Surge protection Loadbank 125 mounting kitc/w surge protector and remote indicator 435 PBSM

Description Height (mm) Cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 43/182

41

Loadbank 125250A/400A Outgoing Devices and Accessories

Outgoing Devices• Standard cable termination 35mm2

• Maximum cable termination is 70mm2 using reduced palm width M8 cable lugs• 3-pole MCCBs have thermal and magnetic overloads• 1-pole MCCBs have fixed thermal and magnetic overloads

Device type Current rating 1-pole cat. no. 3-pole cat. no.

(A) (fixed overloads) (adjustable)

YA2 frame 16 YA2N1P16T N/A

YA2 frame 20 YA2N1P20T YA2N3P20T

YA2 frame 32 YA2N1P32T YA2N3P32T

YA2 frame 40 YA2N1P40T -

YA2 frame 50 YA2N1P50T YA2N3P50T

YA2 frame 63 YA2N1P63T YA2N3P63T

YA2 frame 80 YA2N1P80T -

YA2 frame 100 YA2N1P100T YA2N3P100T

YA2 frame 125 YA2N1P125T YA2N3P125T

Accessories

Description Cat. no.

Panel board 3P blanking piece LBYA2BP3P

YA3 4-pole MCCB incoming kit PB4PNC250

YA5 4-pole MCCB incoming kit (pic 2) PB4PNC400

YA2 cable clamps (1.5-50mm2) YA2CC3P

YA3 cable clamps (35-120mm2) YA3CC3P

YA5 cable clamps (95-240mm2) YA5CC3P

YA2 1-pole terminal shroud YA2TS1P

YA2 3-pole terminal shroud YA2TS3P

YA3 1-pole terminal shroud YA3TS1P

YA3 3-pole terminal shroud (pic 1) YA3TS3PYA5 3-pole terminal shroud YA5TS3P

YA3 4-pole terminal shroud YA3TS4P

YA5 4-pole terminal shroud YA5TS4P

Door cylinder lock DBXCL

Door padlock device lock DBXPL

YA2 1-pole dolly lock Y2DL

YA2 3-pole dolly lock YADL1

Shunt trips

YA frame shunt trip 100-120V AC YAST115AC

YA frame shunt trip 200-240V AC YAST240AC

YA frame shunt trip 380-450V AC YAST450AC

YA frame shunt trip 24V DC YAST24DC

Under-voltage release

YA frame under-voltage release 100-120V AC YAUVR120AC

YA frame under-voltage release 200-240V AC YAUVR240AC

YA frame under-voltage release 380-450V AC YAUVR450AC

YA frame under-voltage release 24V DC YAUVR24DC

1

2

YADL1 fitted without padlock

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 44/182

Surge protection Loadbank 125 mounting kit c/w surge protector & remote indicator 435 PBSM

Surge Protection Mounting Kits for 250A and 400A Panelboards

Description Height (mm) Cat. no.

42

Auxiliary Units for both 250A & 400A Panel BoardsDescription Cat. no.

SwitchDisconnector 400 YA5 3 N/A YA5B3P400D

MCCB 250 YA5 3 25kA YA3N3P250T

MCCB 400 YA5 3 25kA YA3N3P400T

SwitchDisconnector 400 YA5 4 N/A YA5B4P400D

MCCB 250 YA5 4 25kA YA3N4P250T

MCCB 400 YA5 4 25kA YA3N4P400T

Incoming Devices for 400A Panel Boards

Device type Current rating (A) Frame size No. of poles MCCB Icu Cat. no.

400A 25kA for 3 seconds YA5 MCCB/switch disconnector 6 PB406YA

400A 25kA for 3 seconds YA5 MCCB/switch disconnector 8 PB408YA

400A 25kA for 3 seconds YA5 MCCB/switch disconnector 12 PB412YA

400A 25kA for 3 seconds YA5 MCCB/switch disconnector 16 PB416YA

400A Panel Boards

Busbar rating ASTA busbar Incoming device Outgoing ways Cat. no.

short circuit rating

SwitchDisconnector 250 YA3 4 N/A YA3B3P250D

MCCB 125 YA3 4 25kA YA3N3P125T

MCCB 160 YA3 4 25kA YA3N3P160T

MCCB 200 YA3 4 25kA YA3N3P200T

MCCB 250 YA3 4 25kA YA3N3P250T

SwitchDisconnector 250 YA3 4 N/A YA3B4P250D

MCCB 125 YA3 4 25kA YA3N4P125TMCCB 160 YA3 4 25kA YA3N4P160T

MCCB 200 YA3 4 25kA YA3N4P200T

MCCB 250 YA3 4 25kA YA3N4P250T

400A - - - - PBYA2DC4

Incoming Devices for 250A Panel Boards

Device type Current rating (A) Frame size No. of poles MCCB Icu Cat. no.

Loadbank 125 Selection Chart - Panel Boards

250A 25kA for 1 second YA3 MCCB/switch disconnector 6 PB206YA

250A 25kA for 1 second YA3 MCCB/switch disconnector 8 PB208YA250A 25kA for 1 second YA3 MCCB/switch disconnector 12 PB212YA

250A Panel Boards

Busbar rating ASTA busbar Incoming device Outgoing ways Cat. no.

short circuit rating

Cable spreader box PBYA2CSB

Service centre with 24 1-pole ways PBYA2SC24

YA3 MCCB outgoing housing PBYA2OG

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 45/182

43

Loadbank 125 Selection Chart - Panel Boards

Selection Chart - Accessories

Description Cat. no.

Panel board 3-pole blanking piece LBYA2BP3P

YA3 4-pole MCCB kit PB4PNC250

YA5 4-pole MCCB kit PB4PNC400

YA2 cable clamps (1.5-50mm2) YA2CC3P

YA3 cable clamps (35-120mm2) YA3CC3P

YA5 cable clamps (95-240mm2) YA5CC3P

YA2 1-pole terminal shroud YA2TS1P

YA2 3-pole terminal shroud YA2TS3P

YA3 1-pole terminal shroud YA3TS1P

YA3 3-pole terminal shroud YA3TS3P

YA5 3-pole terminal shroud YA5TS3P

70mm2 outgoing cable clamps for neutral earth PBYA2NA

YA3 4-pole terminal shroud YA3TS4P

YA5 4-pole terminal shroud YA5TS4P

Door cylinder lock DBXCLDoor padlock device lock DBXPL

YA2 1-pole dolly locking device Y2DL

YA2 3-pole dolly locking device YADL1

Shunt trips

YA frame shunt trip 100-120V AC YAST115AC

YA frame shunt trip 200-240V AC YAST240AC

YA frame shunt trip 380-450V AC YAST450AC

YA frame shunt trip 24V DC YAST24DC

Under-voltage release

YA frame under-voltage release 100-120V AC YAUVR120AC

YA frame under-voltage release 200-240V AC YAUVR240AC

YA frame under-voltage release 380-450V AC YAUVR450ACYA frame under-voltage release 24V DC YAUVR24DC

Metering Accessories

Description Cat. no.

Metering enclosure for upto 6 meters PBYA2MB

Incoming meter loom PBWI

Voltage tap off loom PBWP

CT harness for 1 meter PBWCT

Power loom for 6 outgoing meters PBWM6

250A 3-in-1 CT case size 3 M3N1-45-250/5

400A 3-in-1 CT case size 3 M3N1-45-400/5

60A 3-in-1 current transformer case size 25mm M3N1-25-60/5100A 3-in-1 current transformer case size 25mm M3N1-25-100/5

125A 3-in-1 current transformer case size 25mm M3N1-25-125/5

Digital multi-function meter with 1 pulse and 1 RS485 Modbus ouput RI3-01

Analogue kWh meter with 1 pulse output DRK-3PCT-415

MCCB 16 YA2 25kA YA2N1P16T N/A

MCCB 20 YA2 25kA YA2N1P20T YA2N3P20T

MCCB 32 YA2 25kA YA2N1P32T YA2N3P32TMCCB 40 YA2 25kA YA2N1P40T N/A

MCCB 50 YA2 25kA YA2N1P50T YA2N3P50T

MCCB 63 YA2 25kA YA2N1P63T YA2N3P63T

MCCB 80 YA2 25kA YA2N1P80T N/A

MCCB 100 YA2 25kA YA2N1P100T YA2N3P100T

MCCB 125 YA2 25kA YA2N1P125T YA2N3P125T

Outgoing Devices for 250A & 400A Panel Boards

Device type Current rating (A) Frame size MCCB Icu 1-pole cat. no. 3-pole cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 46/182

PanelBoard

PB206YAPB208YA

PB212YA

PB406YA

PB408YA

PB412YA

PB416YA

Meter Box

Outgoing:PBYA2MB

Incoming:

PBYA2MB

Outgoing:

PBYA2MB

Incoming:PBYA2MB

PBWP 1 Off

Outgoing Meter

Arrangement

PBWI 1 Off

Incoming Meter

Arrangement

Power Tap Off Harness

Incomer Harness

Up to 6 Meters:

PBWM6 1 OffAbove 6 Meters:

PBWM6 2 Off

Meter PowerHarness

DRK-3PCT-415

Ri3-01DRK-3PCT-415

Ri3-01Meters

PBWCT 1per Meter

CT Harness

M3N1-25-60/5M3N1-25-100/5

M3N1-25-100/5

M3N1-35-200/5

M3N1-35-250/5M3N1-45-400/5

CurrentTransformers

For single phase metering use:

1 CT per phase

INT-1630-M-5-M-100 Integra meter only

44

Panel-board enclosures

Description Cat. no.

250A, 6 TP way PB206YA

250A, 8 TP way PB208YA

250A, 12 way PB212YA

400A, 6 way PB406YA

400A, 8 way PB408YA

400A, 12 way PB412YA

400A, 16 way PB416YA

Loadbank 125 MCCB Panel Board System

The Loadbank 125 metering facilities consist of DIN-railmounted meters used within a housing which can fit up

to 6 meters of four modules. The meter housing can bestacked top or bottom with facility to mount currenttransformers and fuses. We recommend that forapplications with more than 6 outgoing meters theLoadbank 250 system with metering accessories shouldbe used. For applications which require single phasemetering please contact the sales office.

Description Cat. no.

Meter housing for up to 6 meters PBYA2MB

Description Cat. no.

Incoming meter loom PBWI

Voltage tap off loom for outgoing metering PBWP

CT harness for 6 outgoing meters PBWCT

Power loom for 6 outgoing meters PBWM6

Description Cat. no.

Digital Multi-function meter with 1 pulseoutput and 1 Modbus output RI3-01

Analogue kilowatt hour meter withone pulse output DRK-3PCT-415

Description Cat. no.

3-in-1 60A current transformers M3N1-25-60/5

3-in-1 100A current transformers M3N1-25-100/5

3-in-1 125A current transformers M3N1-25-125/5

3-in-1 200A current transformers M3N1-35-200/5

3-in-1 250A current transformers M3N1-35-250/5

3-in-1 400A current transformers M3N1-45-400/5

Loadbank 125 Meter Selection Process

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 47/182

4Section

Fuse Switch Panel Boards

Loadbank 200 Range (800A Rating)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 48/182

46

Key Features• ASTA certified short circuit

withstand rating• Allows inclusion of TP&N

and four-pole fuse

switch distribution• Generous cable-spreadingspace for incoming andoutgoing cables

• Common width (750mm)and depth (200mm) forall enclosures

Available Options• 800A panel boards with 6 or 10

outgoing fuse switch ways• 400A, 630A or 800A fuse

switch incomers• Panel build options include:

• SP&N MCB distribution

board for 17 ways• TP&N distribution boardwith 6 and 12 ways

• TP&N distribution board withdouble banks of 12 ways

• General purpose enclosureswith uncut front plates

• Metering housings andservice centres

• Current transformers

Additional Features• Add-on incomer units include

all copper connections andincoming cable shrouds

• Panel and distribution boardsexceed EN 60439-1requirements

• Fully shielded busbars andinterconnections ondistribution boards

• Various locking options• IP4X Ingress Protection

ComplianceSwitch fuse panelboards EN 60439-1Skeleton switches EN 60947-3

Overview

Based on the modular system employed withinLoadbank 250 panel board, Loadbank 200 panel board

is designed to fulfil the need for fuse switchpanelboards upto 800A. Panel board enclosures areavailable in either 6 or 10 TP&N outgoing waysfeaturing devices from 63A to 200A. Form 2 separationis provided as standard, with Form 4 shielding as anavailable option.

Several incoming options can be selected from 200A to800A and a comprehensive range of metering facilitiesfor compliance with Building Regulations Part L2

completes this versatile panel board system.

The standard finish is epoxy powder coating in lightgrey RAL 7035.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 49/182

47

Fuse Switch Panel Board System (800A)

Modular Devices

• Surge protection• Meters, current transformers and

wiring looms• Contactors• Timer• Residual current circuit breaker

Fuse Switch Panel Boards

• General purpose enclosures• Cableway extention enclosures• Stacking kits

Circuit Protection Devices

• Fuse switches (63A-200A)

Incoming Devices

• Fuse switches (200A-800A)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 50/182

400A Fuse Switch IncomingDevices• 400A incoming devices for LF1F4A

enclosure• Standard cable termination 300mm2

• Exceeds the requirements ofEN 60947-3

• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage

630A/800A Fuse Switch Incoming Devices• 630A/800A incoming devices for LF1F8A enclosure• Standard cable termination 630mm2

Incoming Current No. of poles Max cable Cat. no.device type rating (A) termination

(mm2

)

L frame fuse switch 400 TP&N 300 SL3P400N

L frame fuse switch 400 4 300 SL4P400

Incoming Current No. of Max cable Cat. no. Cabledevice type rating poles termination terminals

(A) (mm2)

N frame fuse switch 630 TP&N 630 SN3P630N SNCET

N frame fuse switch 800 TP&N 630 SN3P800N SNCET

N frame fuse switch 630 4 630 SN4P630 SNCET

N frame fuse switch 800 4 630 SN4P800 SNCET

48

800A Panel Board Enclosures• Form 2 as standard• Form 4 with optional shielding• IP3X (IP4X with door kit fitted) Ingress Protection• 750mm wide x 200mm deep

• Integral incoming option available using 200A fuse switchin available outgoing way

No of TP Modular Height Weight Cat. no. Optionaloutgoing ways height (mm) (kg) door kit

6 5 760 59 LF806A MXD06

10 8 1216 98 LF810A MXD10

Description Cat. no.

Form 4 shielding for cable up to 70mm2 (1 per device required) LFS41A

Form 4 shielding for outgoing cables to 150mm2

(1 per device required) LFS42AVertical stacking connection kit LCFVK

Blank cover for fuse switch handle LFXHBA

Current Modular Height Weight Device type Cat. no.rating height (mm) (kg)(A)

400 5 762 50 L frame fuse switch LF1F4A

630/800 6 914 67 N frame fuse switch LF1F8A

Add-on Incoming Enclosures• Excludes incoming device (to be ordered separately)• Supplied with all necessary copper connections• Incoming terminations fully shrouded• Supplied with two side plates only• IP4X Ingress Protection

Fuse Switch Panel Board Accessories

Loadbank 200Fuse Switch Panel Board System Form 2 and 4 50kA-1sec

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 51/182

49

Loadbank 200Outgoing Devices

63/125A Skeleton Switches• Exceeds the requirements of

EN 60947-3• 80kA rms fused short-circuit capacity

• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage

Current rating (A) 1-pole+N cat. no. 3-pole+N cat. no. 4-pole cat. no.

63 - SF3P63N SF4P63

100 - SF3P100N SF4P100

125 - SF3P125N SF4P125

160/200A Skeleton Switches• Exceeds the requirements of

EN 60947-3• 80kA rms fused short-circuit capacity

• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage

Current rating (A) 1-pole+N cat. no. 3-pole+N cat. no. 4-pole cat. no.

160 - SF3P160N SF4P160200 - SF3P200N SF4P200

Accessories for Outgoing/Incoming Skeleton Switches

Description Current rating (A) Picture Cat. no.

Solid links (set of 1) 63 1 HFL63

Solid links (set of 1) 100/200 1 HFL200A

2-bank auxiliary switch 63/200 2 SAUX2F

4-bank auxiliary switch 63/200 2 SAUX4F

Terminal shrouds and barriers 63/200 – SFTSS

Terminal barriers (set of 3) 63/200 – SFTB

Cable extension terminals 630/800 – SNCET(set of 8)

Solid links (set of 1) 400 1 HLL400

Solid links (set of 1) 630/800 1 HNL800

2-bank auxiliary switch 400/630/800 2 SAUX2N

4-bank auxiliary switch 400/630/800 2 SAUX4N6-bank auxiliary switch 400/630/800 2 SAUX6N

Terminal shrouds and barriers 400 – SLTS

Terminal shrouds and barriers 630/800 – SNTS

Terminal barriers (set of 3) 400 – SLTB

Terminal barriers (set of 3) 630/800 – Supplied

1

2

Loadbank 200Outgoing Devices Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 52/182

50

Loadbank 200Add-on Enclosures

General Purpose Enclosures• IP4X Ingress Protection• Enclosures are 750mm wide x 200 deep• No top or bottom plates supplied (supplied with panel board)

Description Modular height Height (mm) Cat. no.

General purpose enclosure 1 152 LEBM1

General purpose enclosure 2 305 LEBM2

General purpose enclosure 3 457 LEBM3

General purpose enclosure 4 609 LEBM4

General purpose enclosure 5 762 LEBM5

General purpose enclosure 6 914 LEBM6

Cableway Extension Enclosures• IP4X Ingress Protection• Recommend for cables above 70mm2

• 250mm wide x 200mm deep• No side plates supplied (supplied with panel board)

Description Modular height Height (mm) Cat. no.

Cableway 1 152 LECM1

Cableway 2 305 LECM2

Cableway 3 457 LECM3

Cableway 4 609 LECM4

Cableway 5 762 LECM5

Cableway 6 914 LECM6

Cableway 8 1219 LECM8

MCB Distribution Board and Service Centre• IP3X (IP4X with door fitted) Ingress Protection• MCB distribution boards have fully shielded busbars and interconnections• Space saving twin option TP&N distribution board option

*Only double module RCBOs can be fitted in this enclosure.

Description Modular Height Cat. no. Door kitheight (mm) cat. no.

17 MCB way SP&N distribution board 1 152 LDS17 LD1DS

6 TP way TP&N distribution board 2 305 LDT106X LD1D06X

12 TP way TP&N distribution board 3 457 LDT112X LD1D12X

2 x 12 TP way TP&N distribution board 4 609 LDT212X* LD2D12X

24 way modular service centre 1 152 LDS24 LD1DS

Transient Voltage Surge Protector Cableway Mounting Kits• Easily installed within a standard cableway (2 modules onward)• DIN-rail mounting for triple-pole MCB• C/W 30Ka three-phase surge protector• Remote status indication• Site fault indication

Cableway mounting frame c/w surge protector

& remote indicator (1) 304 LECK2SM2 module enclosure c/w surge protector& remote indicator (2) 304 LECK2SP

Description Height (mm) Cat. no.

1

2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 53/182

51

Loadbank 200Metering Accessories

Description Height Cat. no.

2 module metering door kit, excluding CTs and control wiring 2 LECMD2

3 module metering door kit, excluding CTs and control wiring 3 LECMD3

4 module metering door kit, excluding CTs and control wiring 4 LECMD4

5 module metering door kit, excluding CTs and control wiring 5 LECMD5

6 module metering door kit, excluding CTs and control wiring 6 LECMD6

8 module metering door kit, excluding CTs and control wiring 8 LECMD8

*Using standard lugs**Using reduced palm width lugs

For easy selection of metering please refer to the charts on pages 56.

Cableway Metering Door Kits• Incoming and outgoing metering utilises cableway extension boxes• Metering door kits are available sized to the cableway extension boxes and are

designed for panel mounted meters• Includes DIN-rail for facility to mount current transformers and fuses

Description Cat. no.

Incoming meter loom LBWI

Voltage tap off loom for outgoing metering LBWP

CT harness for 1 outgoing meters LBWCT

Power loom for 6 outgoing meters LBWM6

Metering Harnesses

Description Cat. no.

Digital multi-function meter with one pulse output INT-1630-M-5-M-100

Digital multi-function meter with one pulse output and INT-1630-M-5-M-110one RS485 output

Digital kilowatt hour meter with pulse output CI1-01-PUL

Digital multi-function meter with pulse output CI3-01-PUL

Pulse Output for Ci meter CI-PUL-01

RS485 Modbus Output for Ci meter CI-MOD-01

Description Max cable size mm2 Cat. no.

100A 3-in-1 CT Case size 35mm 95*/150** M3N1-35-100/5

125A 3-in-1 CT Case size 35mm 95*/150** M3N1-35-125/5

200A 3-in-1 CT Case size 35mm 95*/150** M3N1-35-200/5250A 3-in-1 CT Case size 35mm 95*/150** M3N1-35-250/5

Outgoing Current Transformers

Description Max cable size mm2 Cat. no.

400A current transformer (sold singular) 185*/240** M63N-400/5

600A current transformer (sold singular) 185*/240** M63N-600/5

800A current transformer (sold singular) 240 M93L-800/5

Incoming Current Transformers

Metering

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 54/182

Service Centres

Type Outgoing ways Height Weight (kg) Cat. no. Door kit

Service centre (DIN units) 24 DIN 1 module 10 LDS24 LD1DS

General Purpose Enclosures

Height Weight (kg) Cat. no.

1 module 4 LEBM1

2 modules 10 LEBM2

3 modules 16 LEBM3

4 modules 22 LEBM4

5 modules 28 LEBM5

6 modules 34 LEBM6

Cableways

Height Weight (kg) Cat. no.

1 module 2 LECM1

2 modules 4 LECM2

3 modules 6 LECM3

4 modules 8 LECM4

5 modules 8 LECM5

6 modules 12 LECM6

8 modules 14 LECM8

Incoming Units

Device type Current Height Weight (kg) Cat. no.

housing rating (A)

Fuse switch 400 5 modules 48.5 LF1F4A

Fuse switch 630/800 6 modules 66.5 LF1F8A

800A Panel Boards - Form 4 Conversion Cat. no.

Form 4 shields for outgoing cables up to 70mm2 LFS41A

Form 4 shields for outgoing cables up to 150mm 2 LFS42A

Vertical connection kit for 800A panelboard LCFVK

Blank cover plate for fuse switch handle LFXHBA

52

800A Panel Boards - Form 2

Outgoing device Outgoing ways Height (mm) Weight (kg) Cat. no.

Fuse switch 6 5 modules 59 LF806A

Fuse switch 10 8 modules 98 LF810A

MCB Distribution Boards

Surge Protection Cableway Mounting Kits

Description Height (mm) Cat. no.

Cableway mounting frame c/w surge protector & remote indicator 304 LECK2SM

2 module enclosure c/w surge protector & remote indicator 304 LECK2SP

SP&N

Outgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no.

17 1 module 15 LDS17 LD1DS

TP&N

Outgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no.

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

Loadbank 200 Selection Chart - Enclosures

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 55/182

53

Loadbank 200 Selection Chart - IncomingDevices and Accessories

Fuse Switches

Device type Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Skeleton switch 200 SF3P200N SF4P200

Skeleton switch 400 SL3P400N SL4P400

Skeleton switch 630 SN3P630N SN4P630

Skeleton switch 800 SN3P800N SN4P800

Loadbank 200 Incoming Devices

Description Current rating (A) Picture Cat. no.

Cable extension terminals (set of 8) 630/800 – SNCET

Solid links (set of 1) 400 1 HLL400Solid links (set of 1) 630/800 1 HNL800

2-bank auxiliary switch 400/630/800 2 SAUX2N

4-bank auxiliary switch 400/630/800 2 SAUX4N

6-bank auxiliary switch 400/630/800 2 SAUX6N

Terminal shrouds and barriers 400 – SLTS

Terminal shrouds and barriers 630/800 – SNTS

Terminal barriers (set of 3) 400 – SLTB

Terminal barriers (set of 3) 630/800 – Supplied

Accessories for Incoming Skeleton Switches

Metering

Description Height Height Current rating Cable size Cat. no.(modules) (mm) (A) (mm)

Metering door kit 2 304 - - LECMD2Metering door kit 3 456 - - LECMD3Metering door kit 4 608 - - LECMD4Metering door kit 5 760 - - LECMD5Metering door kit 6 912 - - LECMD6Metering door kit 8 1216 - - LECMD8Incoming meter loom - - - - LBWIVoltage tap off for outgoing meter - - - - LBWPCT harness for 1 outgoing meter - - - - LBWCTMeter power loom for 1 outgoing meter - - - - LBWM63-in-1 current transformers - - 100 95 M3N1-35-100/5

3-in-1 current transformers - - 125 95 M3N1-35-125/53-in-1 current transformers - - 150 95 M3N1-35-150/53-in-1 current transformers - - 200 95 M3N1-35-200/53-in-1 current transformers - - 250 95 M3N1-35-250/5Current transformer - - - 185 M63N-400/5Current transformer - - - 185 M63N-600/5Current transformer - - - 240 M93L-800/51-phase/3phase kWh meter with pulse - - - - CI1-01-PUL1-phase/3phase MF meter with pulse - - - - INT-1630-M-5-M-1001-phase/3phase MF meter with pulse and Modbus - - - - INT-1630-M-5-M-1101-phase/3phase MF meter with pulse - - - - CI3-01-PULOptional pulse plug in module for Ci meter - - - - CI-PUL-01Optional RS485 Modbus plug in module - - - - CI-MOD-01for Ci meter

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 56/182

54

Loadbank 200 Selection Chart - Outgoing FuseSwitches and Accessories

Accessories

Description Current rating (A) Cat. no.

Solid links (set of 1) 63 HFL63

Solid links (set of 1) 100/200 HFL200A

2-bank auxiliary switch 63/200 SAUX2F

4-bank auxiliary switch 63/200 SAUX4F

Terminal shrouds and barriers 63/200 SFTSS

Terminal barriers (set of 3) 63/200 SFTB

Door Locking

Door lock/key kit DBXCL

Padlocking kit for door kits DBXPL

800A Panelboard

Description Cat. no.

Vertical connection kit LCFVK

Blank cover plate for fuse switch handle LFXHBA

Main Enclosures - Insulation & Plates

Horizontal insulation kit MXEPF

Steel end plate LGES

Outgoing Fuse Switches

Device Current rating (A) 1-pole+N cat.no. 3-pole+N cat. no. 4-pole cat. no.

Skeleton switch 63 - SF3P63N SF4P63

Skeleton switch 100 SF1P100N SF3P100N SF4P100

Skeleton switch 125 - SF3P125N SF4P125

Skeleton switch 160 - SF3P160N SF4P160

Skeleton switch 200 - SF3P200N SF4P200

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 57/182

55

Loadbank 200Dimensions and Outline Drawings

LEBM66 modules

LEBM55 modules

LEBM44 modules

LEBM33 modules

LEBM22 modules

LEBM11 module

LECM8

8 modules

LECM6

6 LECM55 LECM4

4 LECM3

3 LECM2

2 LECM11

LF810A

8 modules

LF806A

5 modules

LF1F8A

6 modules

LF1F4A

5 modules

8 Module Height-1219mm

6 Module Height-914mm

5 Module Height-762mm

4 Module Height-609mm

3 Module Height-457mm

2 Module Height-304mm

1 Module Height-152mm

Cableway250mm

Main Enclosure750mm

Depth of all enclosures–200mm

Standard Cableways

14kg 12kg 10kg 8kg 6kg 4kg 2kg

400A Switch48.5kg*

630A/800A Switch66.5kg*

34kg 28kg 22kg 16kg 10kg 4kg

10/6 Outgoing Ways 200A Max.98kg 59kg

200mm

200mm

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 58/182

56

Loadbank 200 Metering Selection

Panel-board enclosures

Description Cat. no.

800A, 6 way, Form 4 LF806A

800A, 10 way, Form 4 LF806A

Loadbank 200The Loadbank 200 metering facilities utilisestandard cableway extension enclosures with

optional door kits designed for panel mountedmeters. The size of the cableway will determine thecorresponding metering door kit. Where cable sizesexceed 70mm a recommendation would be toinclude two cableway extension enclosures tofacilitate easy wiring. The same could be advisedwhen fully populating an 18 way panel board withmeters. Current transformers and fuses can be DIN-rail mounted within the cableways using thefacilities provided within the optional door kits.

Description Cat. no.

2 module metering mounting kit,(2 meter positions) LECMD2

3 module metering mounting kit,(3 meter positions) LECMD3

4 module metering mounting kit,(4 meter positions) LECMD4

5 module metering mounting kit,(6 meter positions) LECMD5

6 module metering mounting kit,(6 meter positions) LECMD6

8 module metering mounting kit,(9 meter positions) LECMD8

Description Cat. no.

3-in-1 100A current transformers M3N1-35-100/5

3-in-1 125A current transformers M3N1-35-125/5

3-in-1 200A current transformers M3N1-35-200/5

3-in-1 250A current transformers M3N1-35-250/5400A current transformer(sold singular) M63N-400/5D

630A current transformer(sold singular) M63N-600/5D

800A current transformer(sold singular) M93L-800/5D

Description Cat. no.

Digital multi-function meterwith one pulse outputs INT-1630-M-5-M-100

Digital multi-function meterwith one pulse output andone RS485 output INT-1630-M-5-M-110

Digital kilowatt hour meterwith one pulse output CI1-01-PUL

Digital multi-function meterwith one pulse output CI3-01-PUL

Cableway Door

LF806ALF810A

LF806A:-LECMD5 x 2LF810A:-LECMD8 x 2

LF1F4A:-LECMD5 x 1LF1F8A:-LECMD6 x 1

LBWP 1 Off LBWP 1 Off

Left Side Outgoing

Meter Arrangement

Right Side Outgoing

Meter Arrangement

Incoming Meter

Arrangement

LBWI 1 Off

Up to 6 Meters:LBWM6 1 Off

Above 6 Meters:LBWM6 2 Off

Up to 6 Meters:LBWM6 1 Off

Above 6 Meters:LBWM6 2 Off

CI1-01-PULCI3-01-PUL

INT-1630-M-5-M-***

CI1-01-PULCI3-01-PUL

INT-1630-M-5-M-***

CI3-01CI1-01

INT-1630-M-5-M-***

LBWCT 1 perMeter

LBWCT 1 perMeter

M3N1-35-100/5M3N1-35-125/5M3N1-35-200/5M3N1-35-250/5

M3N1-35-100/5M3N1-35-125/5M3N1-35-200/5M3N1-35-250/5

M53J-200/5D3 per Meter

M53J-250/5D3 per Meter

M63N-400/5D3 per Meter

M63N-600/5D3 per Meter

M63N-800/5D3 per Meter

M93L-600/5D3 per Meter

M93L-800/5D3 per Meter

LBWP 1 Off

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 59/182

5Section

MCCB Panel Boards

Loadbank 250 Range (400A and 800A Ratings)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 60/182

58

Key Features• ASTA certified busbars with a

short-circuit withstand rating of36kA for 1 second (400A)

• ASTA certified busbars with a

short-circuit rating of 50kA for1 second (800A)• Allows mounting of YA3, Y5, Y6

or Y7 MCCBs and switchdisconnectors

• Single frame size for outgoing16A to 250A MCCBs

• Generous cable-spreadingspace for incoming andoutgoing cables

• Common width (750mm) anddepth (200mm) for allenclosures

Available Options• 400A and 800A panel boards

with 6, 12 or 18 triple-poleoutgoing ways with Y6/Y7 orYA3 incoming devices, withForm 3 separation

• 800A panel boards with 6 or 10TP&N or four-pole outgoingways with fuse switch/MCCBincomer, with Form 4separation

• Panel build options include:

• Range of MCBdistribution boards

• General purposeenclosures with uncut

front plates• Metering housings and

service centres

• Current transformers

• Cableway enclosures

CompliancePanel boards EN 61439-2MCCBs EN 60947-2MCBs EN 60898RCCBs EN 61008RCBOs EN 61009Skeleton Switches 60947-3

Overview

Loadbank 250 modular enclosure system is engineeredto provide unrivalled flexibility and build simplicity

needed to produce a wide range of power distributionsolutions. TP&N busbars of 400A and 800A comprisingof three sizes of 6, 12, 18 TP outgoing ways allowinstallers to cover a multitude of commercial andindustrial applications.

Featuring circuit breakers from 16A to 400A to befitted as outgoing circuits, integral MCB distributionboards, contactors, timers complemented by a newrange of incoming and outgoing metering facilities

completes the Loadbank 250 panel board range.

Loadbank 250 panel boards house the incomer andoutgoing units in separate, adjoining enclosures toallow the widest range of possible circuit permutations,including oversized outgoing circuits, to beaccommodated within a common format. The standardfinish is epoxy powder coating in light grey RAL 7035.

Loadbank 250 single module is 152mm high.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 61/182

59

MCCB Panel Boards (400A and 800A Rating)

Modular Devices

• Surge protection• Meters, current transformers and

wiring looms• Contactors• Timer• Earth leakage device

MCCB Panel Boards

• Service centres

• Cableway extension chambers• General purpose enclosures• TP&N distribution boards

Circuit Protection Devices

• Moulded case circuit breakers (upto 250Aor 400A max)

Incoming Devices

• Switch disconnector• Moulded case circuit breakers• Fuse combination units

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 62/182

60

400A Panel Board Enclosures• Form 3 as standard• Incoming enclosures and devices to be ordered separately• ASTA certified busbars rated at 36kA-1sec

250A/400A Add-on Incoming Enclosures• Supplied with all necessary connections• Incoming devices to be ordered separately

400A Panel Board Accessories

Description Cat. no.

Door cylinder lock DBXCLDoor padlock device DBXPL

3-pole blanking piece LBBP3PYA3

Steel end plate LGES

Panel board stacking kit LBCK4

Busbar extension terminals with shields to connectto top of panel board LBSKE

Current rating Device type Modular Height Cat. Neutralheight (mm) no. link

250 YA3 MCCB 3 457 LB1YA3 YA3NL

400 Y6 MCCB 5 762 LB1Y6 Standard

400 Direct connection 2 305 LBDR4 Standard

200 F frame fuse switch 3 457 LB1F2A Standard

400 L frame fuse switch 5 762 LB1F4A Standard

250A Max Incoming Devices• Up to 250A Incoming devices for LB1YA3• Standard cable termination 95mm2

• Maximum cable termination is 150mm2 using reduced palm width M8 cable lugs• MCCBs have thermal and magnetic overloads except switch disconnector

Incoming device type Current rating (A) No. of poles Cat. no.

Switch disconnector 250 3 YA3B3P250D

MCCB 160 3 YA3N3P160T

MCCB 200 3 YA3N3P200T

MCCB 250 3 YA3N3P250T

Switch disconnector 250 4 YA3B4P250D

MCCB 160 4 YA3N4P160T

MCCB 200 4 YA3N4P200T

MCCB 250 4 YA3N4P250T

No of TP Modular Height Width Depth Cat. no. Door kitoutgoing ways height (mm) (mm) (mm) cat. no.

6 4 609 750 200 LB406YA3 LBDD06

12 6 914 750 200 LB412YA3 LBDD12

18 8 1219 750 200 LB418YA3 LBDD18

400A Incoming Devices• 400A Incoming devices for LB1Y6• Standard cable termination 240mm2

200/400 Fuse Switch Devices• 200A Incoming devices for LB1F2A

• 400A Incoming devices for LB1F4A

Incoming device type Current rating (A) No. of poles Cat. no.

Switch disconnector 400 3 Y6B3P400D

MCCB 400 3 Y6H3P400T5

Switch disconnector 400 4 Y6B4P400D

MCCB 400 4 Y6H4P400T5

Incoming device type Current rating (A) No. of poles Cat. no.

F frame fuse switch ex fuses 200A 3 SF3P200N

F frame fuse switch ex fuses 200A 4 SF4P200

L frame fuse switch ex fuses 400A 3 SL3P400N

L frame fuse switch ex fuses 400A 4 SL4P400

Loadbank 250250A/400A Panel Board Form 3 36kA-1sec

Fitted with incoming housingand metering

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 63/182

61

* MCCB must be set for 800A maximum.

Loadbank 250800A Panel Board Form 3 50kA-1sec

630A Incoming Devices• 630A Incoming devices for LB1Y6• Standard cable termination 240mm2

• Upto 250A or 400A

Incoming Current rating No. of poles Cat. no.device type (A)

Switch disconnector 630 3 Y6B3P630D

MCCB 630 3 Y6H3P630T5

Switch disconnector 630 4 Y6B4P630D

MCCB 630 4 Y6H4P630T5

800A Incoming Devices• 800A Incoming devices for LB1Y7• Standard cable termination 300mm2

• LB1Y7 Neutral link supplied

Incoming Current rating No. of poles Cat. no.device type (A)

Switch disconnector 800 3 Y7B3P800DMCCB 800 3 Y7J3P1000E*

Switch disconnector 800 4 Y7B4P800D

MCCB 800 4 Y7J4P1000E*

No of TP Modular Height Width Depth Cat. no. Door kitoutgoing ways height (mm) (mm) (mm) (mm) cat. no.

6 4 609 750 200 LB806YA3 LBDD06

12 6 914 750 200 LB812YA3 LBDD12

18 8 1219 750 200 LB818YA3 LBDD18

800A Panel Board Enclosures• Form 3 as standard

• Incoming enclosures and devices to be ordered separately

• ASTA certified busbars rated at 50kA-1sec

400A/800A Add-on Incoming Enclosures• Supplied with all necessary connections• Incoming devices to be order separately

Current rating Device type Modular Height Cat. no. Neutralheight (mm) link

800A Panel boards

400/630A Y6 MCCB 5 762 LB1Y6 Standard800A Direct connection 3 457 LBDR8 Standard

800A Y7 MCCB 6 912 LB1Y7 Standard

800A Panel Board Accessories

Description Cat. no.

Door cylinder lock DBXCL

Door padlock device DBXPL

3-pole blanking piece LBBP3PYA3

Panel board stacking kit LBCK8Busbar extension terminals with shields to connectto top of panel board LBSKE

Steel end plate LGES

Horizontal insulation kit MXEPF

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 64/182

62

Outgoing YA3 MCCB Devices• Standard cable termination 95mm2

• Maximum cable termination is 150mm2 using reduced palm width M8 cable lugs• Triple-pole MCCBs have thermal and magnetic overloads• Single-pole MCCBs have fixed thermal and magnetic overloads

Device Current 1-pole 3-pole, 25kA 3-pole, 36kA 3-pole, 65kAtype rating cat. no. cat. no. cat. no. cat. no.

(A) (fixed (adjustable (adjustable (adjustableoverloads) overloads) overloads) overloads)

YA3 frame 16 YA3N1P16T - - -

YA3 frame 20 YA3N1P20T YA3N3P20T YA3S3P20T YA3J3P20T

YA3 frame 32 YA3N1P32T YA3N3P32T YA3S3P32T YA3J3P32T

YA3 frame 40 YA3N1P40T - - -

YA3 frame 50 YA3N1P50T YA3N3P50T YA3S3P50T YA3J3P50T

YA3 frame 63 YA3N1P63T YA3N3P63T YA3S3P63T YA3J3P63T

YA3 frame 80 YA3N1P80T - - -

YA3 frame 100 YA3N1P100T YA3N3P100T YA3S3P100T YA3J3P100T

YA3 frame 125 YA3N1P125T YA3N3P125T YA3S3P125T YA3J3P125TYA3 frame 160 YA3N1P125T YA3N3P160T YA3S3P160T YA3J3P160T

YA3 frame 200 - YA3N3P200T YA3S3P200T YA3J3P200T

YA3 frame 250 - YA3N3P250T YA3S3P250T YA3J3P250T

Outgoing YA5 MCCB Devices• Standard cable termination 95mm2

• Maximum cable termination 185mm2 using reduced palm width M8 cable lugs• MCCBs have adjustable overloads• For use with LB802YA5 (twin YA5 outgoing housing - page 66)

Description Cat. no.

YA3 3P cable clamps (35-120mm2) YA3CC3P

YA3 4P cable clamps (35-120mm2) YA3CC4P

YA5 3P cable clamps (95-240mm2) YA5CC3P

YA5 4P cable clamps (95-240mm2) YA5CC4P

Dolly locking device YADL1100-120V AC shunt trip YAST115AC

200-240V AC shunt trip YAST240AC

380-450V AC shunt trip YAST450AC

24V DC shunt trip YAST24DC

100-120V AC under-voltage release YAUVR120AC

200-240V AC under-voltage release YAUVR240AC

380-450V AC under-voltage release YAUVR450AC

24V DC under-voltage release YAUVR24DC

YA3 3P terminal shield YA3TS3P

YA3 4P terminal shield YA3TS4P

YA5 3P terminal shield YA5TS3P

YA5 4P terminal shield YA5TS4P

YA3 and YA5 MCCB Accessories

Device type Current rating (A) 25kA cat. no. 50kA cat. no.

YA5 Frame 160A-250A YA5N3P250T YA5H3P250T

YA5 Frame 250A-400A YA5N3P400T YA5H3P400T

Loadbank 250400A and 800A, Form 3 Outgoing Devices and Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 65/182

Loadbank 250800A Form 4 MCCB Panel Board

63

The Form 4 panel board range features a 800A TP&Nfour-pole busbar assembly comprises of two stackable

designs of 6 and 10 TP&N ways. Three incomingenclosures are available with MCCB or fuse switchincoming options offering a cost effective, off the shelfsolution for projects which require Form 4 separation.

A comprehensive range of general purpose add-onunits and cableways with metering options completethis versatile range.

Features• Exceeds EN60439-1• ASTA certified busbars with a

short-circuit withstand rating of50kA-1sec

• Form 3 as standard• Form 4 with Form 4 shielding

fitted• IP4X Ingress Protection• Single frame size outgoing

triple-pole MCCBs from 16A-250A• Common width (750mm) and

depth (200mm) for all enclosures• Fully rated neutrals• Does not accept 1-pole outgoing

devices

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 66/182

64

800A Panel Boards - Form 4• No provision for 1-pole MCCBs• Form 3 as standard• Form 4 with optional shielding• IP3X (IP4X with door kit fitted) Ingress Protection

• 750mm wide x 200mm deep• Spare busbar terminal covers/blanking plates are to be ordered separately

Add-on Incoming Enclosures• Form 4 as standard• IP4X Ingress Protection

No of TP Modular Height Weight Cat. no. Optionaloutgoing ways height (mm) (kg) door kit

6 5 760 59 LF806YA MXD06

10 8 1216 98 LF810YA MXD10

Description Cat. no.

Form 4 shielding for cable up to 70mm2 LFS41YA

Form 4 shielding for outgoing cables to 150mm2 LFS42YA

Vertical stacking connection kit LCFVKBlanking plate for unused way YA3F4BP

Current Modular Height Weight Device Cat. no. Connectionrating height (mm) (kg) type kit required(A)

400 5 762 98 L frame fuse LF1F4A -switch

630/800 8 1216 66.5 N frame fuse LF1F8A -switch

400-800 5 762 45.2 Y6 MCCB/ MMS15Y* MCFMY6MCCB switchdisconnector

400A Fuse Switch Incoming Devices• 400A Incoming devices for LF1F4A enclosure

• Standard cable termination 240mm2

Incoming device type Current rating (A) No. of poles Cat. no.

L frame fuse switch 400 TP&N SL3P400N

L frame fuse switch 400 4 SL4P400N

800A Panel Board Accessories

Loadbank 250800A Panel Board Form 4 50kA-1sec

*Neutral link supplied

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 67/182

65

Incoming Current No. of Max cable Cat. no.device type rating (A) poles termination

(mm2)

Y6 frame switch disconnector 400 3 240 Y6B3P400D

Y6 frame MCCB 400 3 240 Y6H3P400T5

Y6 frame MCCB 630 3 240 Y6H3P630T5

Y6 frame MCCB 800 3 240 Y6H3P800T5

Y6 frame switch disconnector 400 4 240 Y6B4P400D

Y6 frame MCCB 400 4 240 Y6H4P400T5Y6 frame MCCB 630 4 240 Y6H4P630T5

Y6 frame MCCB 800 4 240 Y6H4P800T5

Incoming Current No. of Max cable Cat. no. Cabledevice type rating poles termination terminals

(A) (mm2)

N frame fuse switch 630 TP&N 630 SN3P630N SNCET

N frame fuse switch 800 TP&N 630 SN3P800N SNCET

N frame fuse switch 630 4 630 SN4P630N SNCET

N frame fuse switch 800 4 630 SN4P800N SNCET

630A/800A Fuse Switch Incoming Devices• 630A/800A Incoming devices for LF1F8A enclosure• Standard cable termination 630mm2

Incoming MCCB Devices

• 400A-800A Incoming devices for MMS15Y enclosure• Standard cable termination 240mm2

• Triple-pole and four-pole MCCBs have adjustable thermal and magneticoverloads

Outgoing MCCB Devices• Standard cable termination 95mm2

• Maximum cable termination is 150mm2 using reduced palm width M8 cable lugs• Triple-pole MCCBs have adjustable thermal and magnetic overloads

Device type Current 3-pole, 25kA 3-pole, 36kA 3-pole, 65kArating (A) cat. no. cat. no. cat. no.

(adjustable (adjustable (adjustableoverloads) overloads) overloads)

YA3 frame 16 - - -

YA3 frame 20 YA3N3P20T YA3S3P20T YA3J3P20T

YA3 frame 32 YA3N3P32T YA3S3P32T YA3J3P32T

YA3 frame 40 - - -

YA3 frame 50 YA3N3P50T YA3S3P50T YA3J3P50T

YA3 frame 63 YA3N3P63T YA3S3P63T YA3J3P63T

YA3 frame 80 - - -

YA3 frame 100 YA3N3P100T YA3S3P100T YA3J3P100T

YA3 frame 125 YA3N3P125T YA3S3P125T YA3J3P125T

YA3 frame 160 YA3N3P160T YA3S3P160T YA3J3P160T

YA3 frame 200 YA3N3P200T YA3S3P200T YA3J3P200T

YA3 frame 250 YA3N3P250T YA3S3P250T YA3J3P250T

Loadbank 250800A Panel Board Incoming and Outgoing Devices

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 68/182

66

General Purpose Enclosures• IP4X Ingress Protection• Enclosures are 750mm wide x 200 deep• No top or bottom plates supplied (supplied with panel board)

Description Modular height Height (mm) Cat. no.

General purpose enclosure 1 152 LEBM1

General purpose enclosure 2 305 LEBM2

General purpose enclosure 3 457 LEBM3

General purpose enclosure 4 609 LEBM4

General purpose enclosure 5 762 LEBM5

General purpose enclosure 6 914 LEBM6

Cableway Extension Enclosures

• IP4X Ingress Protection• Recommend for cables above 70mm2

• 250mm wide x 200mm deep• No side plates supplied (supplied with panel board)

Description Modular height Height (mm) Cat. no.

Cableway 1 152 LECM1

Cableway 2 305 LECM2

Cableway 3 457 LECM3

Cableway 4 609 LECM4

Cableway 5 762 LECM5

Cableway 6 914 LECM6

Cableway 8 1219 LECM8

MCB Distribution Board and Service Centre• IP3X (IP4X with door fitted) Ingress Protection• MCB distribution boards have fully shielded busbars and interconnections• Space saving twin option TP&N distribution board option

*Only double module RCBOs can be fitted in this enclosure.

Description Modular Height Cat. no. Door kitheight (mm) cat. no.

17 MCB way SP&N distribution board 1 152 LDS17 LD1DS

6 TP way TP&N distribution board 2 305 LDT106X LD1D06X

12 TP way TP&N distribution board 3 457 LDT112X LD1D12X

2 x 12 TP way TP&N distribution board 4 609 LDT212X* LD2D12X24 way modular service centre 1 152 LDS24 LD1DS

Twin YA5 Outgoing Housing (not design for use with Form 4 panelboards)• Can be mounted direct to incoming enclosure without connection kit• When mounting to 800A panelboard connection kits are required

(LBSKE and LBCK8)• Cableway extension enclosures are necessary to assist with cabling• Terminal shields required per MCCB (YA5TC3P)• Devices to be ordered separately (page 62)

Description Modular Height Weight Cat. no. Door kitheight (mm) (kg) cat. no.

Twin YA5 (400A max each) 3 modules 456 35 LB802YA5 LBDD02

Loadbank 250400A and 800A, Form 3 and 4, Panel Board Add-on Enclosures

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 69/182

67

Loadbank 250400A and 800A, Form 3 and 4, Panel Board Metering Accessories

Description Height Cat. no

2 module metering door kit, excluding CTs and control wiring 2 LECMD2

3 module metering door kit, excluding CTs and control wiring 3 LECMD3

4 module metering door kit, excluding CTs and control wiring 4 LECMD4

5 module metering door kit, excluding CTs and control wiring 5 LECMD5

6 module metering door kit, excluding CTs and control wiring 6 LECMD6

8 module metering door kit, excluding CTs and control wiring 8 LECMD8

* Using standard cable lugs.**Using reduced palm width cable lugs.

For easy selection of metering please refer to the chart on pages 80.

Cableway Metering Door Kits• Incoming and outgoing metering utilises cableway extension boxes

• Metering door kits are available sized to the cableway extension boxes and aredesigned for panel mounted meters• Includes DIN-rail for facility to mount current transformers and fuses

Device type Outputs Width (mm) Cat. no.

1-phase/3-phase digital kWh meter 1 pulse 96 CI1-01-PUL

1-phase/3-phase digital 1 pulse 96 INT-1630-M-5-M-100multi-function meter

1-phase/3-phase digital 1 pulse & 96 INT-1630-M-5-110multi-function meter 1 Modbus

1-phase/3-phase digital 1 pulse 96 CI3-01-PULmulti-function meter

Optional pulse plug-in module – – CI-PULfor Ci1 meter

Optional RS485 Modbus plug-in – – CI-MOD-01

module for Ci meter

Description Cat. no.

Incoming meter loom LBWI

Voltage tap off loom for outgoing metering LBWP

CT harness for 1 outgoing meters LBWCT

Power loom for 6 outgoing meters LBWM6

Metering Harnesses

Description Max cable size mm2 Cat. no.

100A current transformer (sold singular) 95*/150** M3N1-35-100/5

125A current transformer (sold singular) 95*/150** M3N1-35-125/5

200A current transformer (sold singular) 95*/150** M3N1-35-200/5

250A current transformer (sold singular) 95*/150** M3N1-35-250/5

400A current transformer (sold singular) 185*/240** M63N-400/5D

630A current transformer (sold singular) 240 M63N-600/5D

800A current transformer (sold singular) 240 M93L-800/5D

3-in-1 Current Transformers

Panel Mounted Meters for Incoming Circuits• 93mm x 96mm dimensions• Low profile• Fully progammable CT ratios• Can be configured SP or TP

Surge Protection Cableway Mounting Kits• Optional Modbus plug-in module for Ci meter• Easily installed within a standard cableway (2 modules onward)• DIN-rail mounting for triple-pole MCB• C/W 30Ka three-phase surge protector• Remote status indication• Site fault indication

Cableway mounting frame c/w surge protector 304 LECK2SM& remote indicator (1)

2 module enclosure c/w surge protector 304 LECK2SP

& remote indicator (2)

Description Height (mm) Cat. no.

1

2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 70/182

68

Loadbank 250 Selection Chart - 400A PanelBoards and Incomer Housings

400A Panel Boards - Form 3

Incomer Housings - Form 3

Incoming device type Current Height Weight (kg) Cat. no.rating (A)

MCCB/YA3 250 3 modules 26 LB1YA3

MCCB/Y6 400 5 modules 45 LB1Y6

Direct connection 400 2 modules 18 LBDR4

Fuse switch 200 3 modules 37.5 LB1F2A

Fuse switch 400 5 modules 48.5 LB1F4A

Housed Fuse Switch

Adaptor kits Current rating (A) Cat. no.

Kit for HBF3P200N, incl. connections 200 LBSK2B

Kit for HBF3P400N, incl. connections 400 LBSK4B

Cableways - Form 2/3

Housing type Standard Height Weight (kg) Cat. no.apertures

Cableway Yes 1 module 2 LECM1

Cableway Yes 2 modules 4 LECM2

Cableway Yes 3 modules 6 LECM3

Cableway Yes 4 modules 8 LECM4

Cableway 5 modules 8 LECM5

Cableway Yes 6 modules 12 LECM6

Cableway 8 modules 14 LECM8

General Purpose Enclosures

Housing type Height Weight (kg) Cat. no.

General purpose – uncut front plate 1 module 4 LEBM1

General purpose – uncut front plate 2 modules 10 LEBM2

General purpose – uncut front plate 3 modules 16 LEBM3

General purpose – uncut front plate 4 modules 22 LEBM4

General purpose – uncut front plate 5 modules 28 LEBM5

General purpose – uncut front plate 6 modules 34 LEBM6

Surge Protection Cableway Mounting Kits

Description Height (mm) Cat. no.

Cableway mounting frame c/w surge protector and remote indicator 304 LECK2SM

2 module enclosure c/w surge protector and remote indicator 304 LECK2SP

ASTA busbar short circuit Outgoing Outgoing Height Weight Panel Door kit

rating of 36kA for 1 second device ways (kg) cat. no. cat. no.

Rating

250A outgoing MCCB/YA3 6 4 modules 36 LB406YA3 LBDD06

250A outgoing MCCB/YA3 12 6 modules 52 LB412YA3 LBDD12

250A outgoing MCCB/YA3 18 8 modules 66 LB418YA3 LBDD18

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 71/182

69

Metering

Description Height Height Current rating Cable size Cat. no.

(modules) (mm) (A) (mm)

Metering door kit 2 304 - - LECMD2Metering door kit 3 456 - - LECMD3Metering door kit 4 608 - - LECMD4Metering door kit 5 760 - - LECMD5Metering door kit 6 912 - - LECMD6Metering door kit 8 1216 - - LECMD8Incoming meter loom - - - - LBWIVoltage tap off for outgoing meter - - - - LBWPCT harness for 1 outgoing meter - - - - LBWCTMeter power loom for 1 outgoing meter - - - - LBWM63-in-1 current transformers - - 100 95 M3N1-35-100/53-in-1 current transformers - - 125 95 M3N1-35-125/53-in-1 current transformers - - 150 95 M3N1-35-150/53-in-1 current transformers - - 200 95 M3N1-35-200/5

3-in-1 current transformers - - 250 95 M3N1-35-250/5Current transformer - - - 185 M63N-400/5Current transformer - - - 185 M63N-600/5Current transformer - - - 240 M93L-800/51-phase/3phase kWh meter with pulse - - - - CI1-01-PUL1-phase/3phase MF meter with pulse - - - - INT-1630-M-5-M-1001-phase/3phase MF meter with pulse and Modbus - - - - INT-1630-M-5-M-1101-phase/3phase MF meter with pulse - - - - CI3-01-PULOptional pulse plug in module for Ci - - - - CI-PUL-01Optional RS485 Modbus plug in module for Ci - - - - CI-MOD-01

Loadbank 250 Selection Chart - 400A PanelBoards Add-on Enclosure and Accessories

Outgoing ways

SP&N Height Weight Enclosure Door kit

(kg) cat. no. cat. no.

17 1 module 15 LDS17 LD1DS

Service Centres

Type Height Weight Cat. no. Door kit

(kg) cat. no.

Service centre (24 DIN units) 1 module 10 LDS24 LD1DS

TP&N

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

Description Cat. no.

Loadbank 250/distribution boards/service centres

Blanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3

Vertical connection kit (400A) LBCK4

Busbar terminals - extensions with shield, to connect both ends of busbar LBSKE

Adaptor kit for 200A housed fuse switch LBSK2B

Adaptor kit for 400A housed fuse switch LBSK4B

Horizontal insulation kit MXEPF

Steel end plate LGES

MCB Distribution Boards

Door Locking Cat. no.

Door lock/key kit DBXCL

Padlocking kit for door kits DBXPL

Accessories for 400A Panel Board Systems

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 72/182

Loadbank 250 Selection Chart - 400APanel Board Circuit Protection Devices

Incoming Devices

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.YA3 switch disconnector

250 – YA3B3P250D YA3B4P250D

YA3 frame MCCB - 25kA

250 160 YA3N3P250T YA3N4P250T

YA3 frame MCCB - 36kA

250 160 YA3S3P250T YA3S4P250T

Y6 switch disconnector

400 – Y6B3P400D Y6B4P400D

Y6 frame MCCB - 50kA400 250 Y6H3P400T5 Y6H4P400T5

200A skeleton switches

200 – SF3P200N SF4P200

400A skeleton switches

400 – SL3P400N SL4P400

400A direct connection

400 – – LBDR4

Outgoing Devices for Form 2 Panel Boards

Current rating (A) 1-pole cat. no. 3-pole cat. no.

Max.

YA3 MCCB – 25kA

16 YA3N1P16T –

20 YA3N1P20T YA3N3P20T

32 YA3N1P32T YA3N3P32T

40 YA3N1P40T –

50 YA3N1P50T YA3N3P50T

63 YA3N1P63T YA3N3P63T

80 YA3N1P80T –

100 YA3N1P100T YA3N3P100T

125 YA3N1P125T YA3N3P125T160 YA3N1P160T YA3N3P160T

200 – YA3N3P200T

250 – YA3N3P250T

YA3 MCCB - 36kA

20 – YA3S3P20T

32 – YA3S3P32T

50 – YA3S3P50T

63 – YA3S3P63T

100 – YA3S3P100T

125 – YA3S3P125T

160 – YA3S3P160T

200 – YA3S3P200T

250 – YA3S3P250T

70

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 73/182

71

Loadbank 250 Selection Chart - 400A PanelBoard and Incoming Devices Accessories

Description Cat. no.

Solid links (set of 1) HLL400

Terminal barriers (set of 3) SLTB

Fuse shrouds SLFS

Terminal shrouds and barriers SLTS

2-blank auxiliary switch SAUX2N

4-blank auxiliary switch SAUX4N

6-blank auxiliary switch SAUX6N

Y6 Frame Accessories

Description Cat. no.

Terminal covers 3-poleInterphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Interphase barriers (set of 3) Y5TB4P

Terminations 4-pole

Extension terminal bars Y6XT4P

Locking devices

Dolly padlock device Y6DL

Shunt trips

Shunt 100-115V AC Y6ST115AC

Shunt 200-450V AC Y6ST450AC

Shunt 24V DC Y6ST24DC

Under-voltage release

UVR 100-120V AC Y6UVR120AC

UVR 200-240V AC Y6UVR240AC

UVR 380-450V AC Y6UVR450AC

UVR 24V DC Y6UVR24DC

Auxiliary switches

1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Accessories for 400A Skeleton Switches

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 74/182

72

Loadbank 250 Selection Chart - 400A PanelBoard Outgoing Devices Accessories

Description Cat. no.

Terminal covers 3-poleYA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3TB

YA3 frame long terminal shroud (set of 1) YA3TS3P

YA3 frame short terminal shroud (set of 1) YA3TS3PS

Terminations 3-pole

YA3 frame cable clamps 35-120mm2 (set of 3) YA3CC3P

Terminal covers 4-pole

YA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3TB

YA3 frame long terminal shroud (set of 1) YA3TS4P

YA3 frame short terminal shroud (set of 1) YA3TS4PS

Terminations 4-pole

YA3 frame cable clamps 35-120mm2 (set of 4) YA3CC4P

Shunt trips

YA frame shunt trip 100-120V AC YAST115AC

YA frame shunt trip 200-240V AC YAST240AC

YA frame shunt trip 380-450V AC YAST450AC

YA frame shunt trip 24V DC YAST24DC

Auxiliary and alarm switches

YA frame 1AB auxiliary switch YAAUX1

YA frame alarm switch YAAL

Under-voltage release

YA frame under-voltage release 100-120V AC YAUVR120AC

YA frame under-voltage release 200-240V AC YAUVR240AC

YA frame under-voltage release 380-450V AC YAUVR450AC

YA frame under-voltage release 24V DC YAUVR24DC

Locking devices

YA frame dolly padlock device YADL1

YA frame Castell* (DS1) lock direct mtg. trapped ‘on’ YACL

*Castell is a trademark of Castell Safety International Limited.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 75/182

73

800A Panel Boards – Form 3

ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kit

of 50kA for 1 second device ways (kg) cat. no. cat no.

250A outgoing MCCB/YA3 6 4 modules 42 LB806YA3 LBDD06

250A outgoing MCCB/YA3 12 6 modules 62 LB812YA3 LBDD12

250A outgoing MCCB/YA3 18 8 modules 78 LB818YA3 LBDD18

800A Panel Boards – Form 4

ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kit

of 50kA for 1 second device ways (kg) cat. no. cat no.

250A outgoing MCCB/YA3 6 5 modules 59 LF806YA MXD06

250A outgoing MCCB/YA3 10 8 modules 98 LF810YA MXD10

Incomer Housings – Form 3

Incomer device type Current Height Weight Cat. no.

rating (A) (kg)

MCCB/Y6 630 5 modules 45 LB1Y6

MCCB/Y7 800 6 modules 69 LB1Y7

Direct connection 800 3 modules 23 LBDR8

Outgoing Housings – Form 3

Incomer device type Current Outgoing Height Weight Panel Door kit

rating (A) ways (kg) cat. no. cat. no.

2x YA5 MCCB 400 2 3 modules 25 LB802YA5 LBDD02

Incomer Housings – Form 4

Device type housing Current Height Weight Cat. no.

rating (A) (kg)

Fuse switch 630/800 6 modules 67 LF1F8A

Y6 frame MCCB 800 5 modules 59 MMS15Y

Y6 connection kit MCFMY6

Shielding – Form 4

Description Additional Cat. no.

housing

70mm2 cables LFS41YA

150mm2 cables Cableway LFS42YA

Loadbank 250 Selection Chart - 800A PanelBoards and Incomer Housings

Description Height (mm) Cat. no.

Cableway mounting frame c/w surge protector and remote indicator 304 LECK2SM2 module enclosure c/w surge protector and remote indicator 304 LECK2SP

Surge Protection Cableway Mounting Kits

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 76/182

74

Loadbank 250 Selection Chart - 800A PanelBoards Add-on Enclosures and Accessories

Metering

Description Height Height Current rating Cable size Cat. no.

(modules) (mm) (A) (mm)

Metering door kit 2 304 - - LECMD2Metering door kit 3 456 - - LECMD3Metering door kit 4 608 - - LECMD4Metering door kit 5 760 - - LECMD5Metering door kit 6 912 - - LECMD6Metering door kit 8 1216 - - LECMD8Incoming meter loom - - - - LBWIVoltage tap off for outgoing meter - - - - LBWPCT harness for 1 outgoing meter - - - - LBWCTMeter power loom for 1 outgoing meter - - - - LBWM63-in-1 current transformers - - 100 95 M3N1-35-100/53-in-1 current transformers - - 125 95 M3N1-35-100/53-in-1 current transformers - - 150 95 M3N1-35-100/53-in-1 current transformers - - 200 95 M3N1-35-100/5

3-in-1 current transformers - - 250 95 M3N1-35-100/5Current transformer - - - 185 M63N-400/5Current transformer - - - 185 M63N-600/5Current transformer - - - 240 M93L-800/51-phase/3phase kWh meter with pulse output - - - - CI1-01-PUL1-phase/3phase MF meter with pulse output - - - - INT-1630-M-5-M-1001-phase/3phase MF meter with pulse - - - - INT-1630-M-5-M-110and Modbus output1-phase/3phase MF meter with pulse output - - - - CI3-01-PULOptional pulse plug in module for Ci meter - - - - CI-PUL-01Optional RS485 Modbus plug in module for - - - - CI-MOD-01Ci meter -

Outgoing waysSP&N Height Weight Enclosure Door kit

(kg) cat. no. cat. no.

17 1 module 15 LDS17 LD1DS

Description Cat. no.

Loadbank 250/distribution boards/service centres

Blanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3

Vertical connection kit (800A) LBCK8

Busbar terminals - extensions with shield, to connect both ends of busbar LBSKE

Adaptor kit for 200A housed fuse switch LBSK2B

Adaptor kit for 400A housed fuse switch LBSK4B

Horizontal insulation kit MXEPF

Steel end plate LGES

MCB Distribution Boards

Door Locking Cat. no.

Door lock/key kit DBXCL

Padlocking kit for door kits DBXPL

Accessories for 400A Panel Board Systems

Service Centres

Type Height Weight Cat. no. Door kit

(kg) cat. no.

Service centre (24 DIN units) 1 module 10 LDS24 LD1DS

TP&N

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 77/182

75

Loadbank 250 Selection Chart - 800A PanelBoards Incoming Devices

Incoming Devices – Form 3 Panel Boards

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.Y6 Frame Switch Disconnector

630 - Y6B3P630D Y6B4P630D

Y6 Frame MCCB Thermal/Magnetic –Icu 50 kA

630 400 Y6H3P630T5 Y6H4P630T5

Y6 Frame MCCB Electronic – Icu 50kA

630 315 Y6H3P630E Y6H4P630E

Y7 Frame Switch Disconnector

800 - Y7B3P800D Y7B4P800D*

Y7 Frame MCCB Electronic – Icu 65kA

1000 500 Y7J3P1000E Y7J4P1000E*

Incoming Devices – Form 4 Panel Boards

Fuse Switch 3-pole+N cat. no. 4-pole+N cat. no.

Current rating (A)

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Y6 Frame MCCB Thermal/Magnetic

Current rating (A)

Max. Min.

800 500 Y6H3P800T5 Y6H4P800T5

Y6 Frame MCCB Electronic

Current rating (A)

Max. Min.

800 400 Y6H3P800E Y6H4P800E

Y6 Switch Disconnector Panel Boards

Current rating (A) 3-pole cat. no. 4-pole cat. no.

800 Y6B3P800D Y6B4P800D

*This MCCB must be set at 800A maximum.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 78/182

76

630/800A Skeleton Switches Accessories

Description Cat. no.

Cable extension terminals (set of 8) SNCETSolid links (set of 1) HNL800

Terminal barriers (set of 3) Supplied

Fuse shrouds SNFS

Y6 Frame Accessories

Description Cat. no.

Terminal covers 3-pole

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Interphase barriers (set of 3) Y5TB4P

Terminations 4-pole

Extension terminal bars Y6XT4P

Locking devices

Dolly padlock device Y6DL

Shunt trips

Shunt 100-120V AC Y6ST115AC

Shunt 200-450V AC Y6ST450AC

Shunt 24V DC Y6ST24DC

Under-voltage releaseUVR 100-120V AC Y6UVR120AC

UVR 200-240V AC Y6UVR240AC

UVR 380-450V AC Y6UVR450AC

UVR 24V DC Y6UVR24DC

Auxiliary switches

1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Loadbank 250 Selection Chart - 800A PanelBoard Incoming Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 79/182

77

Y7 Frame Accessories

Description Cat. no.

Terminal covers 3-poleInterphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Interphase barriers (set of 3) Y5TB4P

Locking devices

Dolly padlock device Y7DL

Shunt trips

Shunt 100-120V AC Y7ST115AC

Shunt 200-450V AC Y7ST450AC

Shunt 24V DC Y7ST24DC

Under-voltage release

UVR 100-120V AC Y7UVR120AC

UVR 200-240V AC Y7UVR240AC

UVR 380-450V AC Y7UVR450AC

UVR 24V DC Y7UVR24DC

Auxiliary switches 3-pole MCCB

1AB auxiliary switch Y7AUX3P1

2AB auxiliary switch Y7AUX3P2

Alarm switch + 1 auxiliary Y7AUX3PAL

Auxiliary switches 4-pole MCCB

1AB auxiliary switch Y7AUX4P1

2AB auxiliary switch Y7AUX4P2Alarm switch + 1 auxiliary Y7AUX4PAL

Loadbank 250 Selection Chart - 800A PanelBoard Incoming Device Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 80/182

78

Loadbank 250 Selection Chart - 800A PanelBoards Outgoing Devices

Outgoing Devices for Form 3 Panel Boards

Current rating (A) 1-pole cat. no. 3-pole cat. no.

Max. Min.YA3 frame MCCB - 25kA

16 - YA3N1P16T -

20 - YA3N1P20T YA3N3P20T

32 - YA3N1P32T YA3N3P32T

40 - YA3N1P40T -

50 - YA3N1P50T YA3N3P50T

63 - YA3N1P63T YA3N3P63T

80 - YA3N1P80T -

100 - YA3N1P100T YA3N3P100T

125 - YA3N1P125T YA3N3P125T

160 - YA3N1P160T YA3N3P160T

200 - - YA3N3P200T

250 - - YA3N3P250T

YA3 frame MCCB - 36kA

50 32 - YA3S3P50T

63 40 - YA3S3P63T

100 63 - YA3S3P100T

125 80 - YA3S3P125T

160 100 - YA3S3P160T

200 125 - YA3S3P200T

250 160 - YA3S3P250T

Outgoing Devices for Form 4 Panel Boards

Current rating (A) 4-pole 25kA 4-pole 36kA 4-pole 65kA

Max. Min. cat. no. cat. no. cat. no.

YA3 frame MCCB

20 13 YA3N4P20T - -

32 20 YA3N4P32T - -

50 32 YA3N4P50T YA3S4P50T YA3J4P50T

63 40 YA3N4P63T YA3S4P63T YA3J4P63T

100 63 YA3N4P100T YA3S4P100T YA3J4P100T

125 80 YA3N4P125T YA3S4P125T YA3J4P125T

160 100 YA3N4P160T YA3S4P160T YA3J4P160T

200 125 YA3N4P200T YA3S4P200T YA3J4P200T

250 160 YA3N4P250T YA3S4P250T YA3J4P250T

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 81/182

79

Loadbank 250 Selection Chart 800A PanelBoard Outgoing Device Accessories

Description Cat. no.

Terminal covers 3-pole

YA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3TB

YA3 frame long terminal shroud (set of 1) YA3TS3P

YA3 frame short terminal shroud (set of 1) YA3TS3PS

Terminations 3-pole

YA3 frame cable clamps 35-120mm2 (set of 3) YA3CC3P

Terminal covers 4-pole

YA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3TB

YA3 frame long terminal shroud (set of 1) YA3TS4P

YA3 frame short terminal shroud (set of 1) YA3TS4PS

Terminations 4-pole

YA3 frame cable clamps 35-120mm2 (set of 4) YA3CC4P

Shunt trips

YA frame shunt trip 100-120V AC YAST115AC

YA frame shunt trip 200-240V AC YAST240AC

YA frame shunt trip 380-450V AC YAST450AC

YA frame shunt trip 24V DC YAST24DC

Auxiliary and alarm switches

YA frame 1AB auxiliary switch YAAUX1

YA frame alarm switch YAAL

Under-voltage release

YA frame under-voltage release 100-120V AC YAUVR120AC

YA frame under-voltage release 200-240V AC YAUVR240AC

YA frame under-voltage release 380-450V AC YAUVR450AC

YA frame under-voltage release 24V DC YAUVR24DC

Locking devices

YA frame dolly padlock device YADL1

YA frame Castell* (DS1) lock to be ordered separately YACL

Motor actuator

YA3 motor actuator AC 100-110V YA3MA110

YA3 motor actuator AC 230-240V YA3MA240

*Castell is a trademark of Castell Safety International Limited.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 82/182

Panel-board enclosures

Description Cat. no.

400A, 6 way, Form 3 LB406YA3

400A, 8 way, Form 3 LB412YA3400A, 12 way, Form 3 LB418YA3

800A, 6 way, Form 3 LB806YA3

800A, 12 way, Form 3 LB812YA3

800A, 18 way, Form 3 LB818YA3

800A, 6 way, Form 4 LF806YA

800A, 10 way, Form 4 LF810YA

Loadbank 200/250The Loadbank 200/250 metering facilities utilisestandard cableway extension enclosures with

optional door kits designed for panel mountedmeters. The size of the cableway will determine thecorresponding metering door kit. Where cable sizesexceed 70mm a recommendation would be toinclude two cableway extension enclosures tofacilitate easy wiring. The same could be advisedwhen fully populating an 18 way panel board withmeters. Current transformers and fuses can be DIN-rail mounted within the cableways using thefacilities provided within the optional door kits.

Description Cat. no.

2 module metering mounting kit,(2 meter positions) LECMD2

3 module metering mounting kit,(3 meter positions) LECMD3

4 module metering mounting kit,(4 meter positions) LECMD4

5 module metering mounting kit,(6 meter positions) LECMD5

6 module metering mounting kit,(6 meter positions) LECMD6

8 module metering mounting kit,(9 meter positions) LECMD8

Description Cat. no.

3-in-1 100A current transformers M3N1-35-100/5

3-in-1 125A current transformers M3N1-35-125/5

3-in-1 200A current transformers M3N1-35-200/5

3-in-1 250A current transformers M3N1-35-250/5400A current transformer M63N-400/5D(sold singular)

630A current transformer M63N-600/5D(sold singular)

800A current transformer M93L-800/5D(sold singular)

Description Cat. no.

Digital multi-function meter INT-1630-M-5-M-100with one pulse outputs

Digital multi-function meter INT-1630-M-5-M-110with one pulse output andone RS485 output

Digital kilowatt hour meter CI1-01-PULwith one pulse output

Digital multi-function meter CI3-01-PULwith one pulse output

80

Loadbank 250 Meter Selection Process

Cableway Door

LBWP 1 Off LBWP 1 Off

Left Side Outgoing

Meter Arrangement

Right Side Outgoing

Meter Arrangement

Incoming Meter

Arrangement

LBWI 1 Off

Up to 6 Meters:

LBWM6 1 Off

Above 6 Meters:

LBWM6 2 Off

Up to 6 Meters:

LBWM6 1 Off

Above 6 Meters:

LBWM6 2 Off

CI1-01-PUL

CI3-01-PULINT-1630-M-5-M-***

CI1-01-PUL

CI3-01-PULINT-1630-M-5-M-***

CI3-01

CI1-01INT-1630-M-5-M-***

LBWCT 1 perMeter

LBWCT 1 perMeter

M3N1-35-100/5M3N1-35-125/5

M3N1-35-200/5M3N1-35-250/5

M3N1-35-100/5M3N1-35-125/5

M3N1-35-200/5M3N1-35-250/5

M53J-200/5D3 per Meter

M53J-250/5D3 per Meter

M63N-400/5D3 per Meter

M63N-600/5D3 per Meter

M63N-800/5D3 per Meter

M93L-600/5D3 per Meter

M93L-800/5D3 per Meter

LB406YA3

LB412YA3LB418YA3

LB806YA3

LB812YA3LB818YA3

LB802YA5

LF806YALF810YA

LB406YA3:-LECMD4 x 2

LB412YA3:-LECMD6 x 2LB418YA3:-LECMD8 x 2

LB1YA3:-LECMD3 x 1LB1Y6:-LECMD5 x 1LBDR4:-LECMD2 x 1LB1F2A:-LECMD3 x 1LB1F4A:-LECMD5 x 1

LB806YA3:-LECMD4 x 2LB812YA3:-LECMD6 x 2LB818YA3:-LECMD8 x 2LB802YA5:-LECMD3 x 2

LB1Y6:-LECMD5 x 1LB1Y7:-LECMD6 x 1LBDR8:-LECMD3 x 1

LF806YA:-LECMD5 x 2LF810YA:-LECMD8 x 2

LF1F8A:-LECMD5 x 1MMS15Y:-LECMD6 x 1

LF1F4A

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 83/182

6Section

Fuse Combination Units

Loadswitch Range (Housed SkeletonDisconnectors 16-800A)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 84/182

82

Key Features• 80kA short-circuit capacity• Housed or skeleton versions• Integral cable spreading facility

with choice of position

• AC23A utilisation category• IP rated switch disconnectors• Switch disconnectors in sheet

steel enclosures

Benefits• Ease of installation• Accepts large cables• Rated for continuous

full-rated load

ComplianceFuse switches EN 60947-3

Overview

The Dorman Smith Loadswitch fuse combination rangeincludes skeleton switches, housed switches and switch

disconnectors. All Loadswitch fuse combination unitsexceed EN 60947-3 requirements and amply meetspecifications for full uninterrupted duty to ensure thatswitches will maintain the maximum rated loadindefinitely. Given their utilisation category of AC23Aand a short-circuit capacity of 80kA, Loadswitch fusecombination devices provide complete confidencewhen installed in any resistive or inductive loadapplication. Housed switches are supplied in sheet steelboxes with integral cable spreading space that can

be positioned above or below the switch to suit easeof installation.

The switch disconnector units are supplied in eitherIP65 insulated enclosures or sheet steel boxes.

The robust steel enclosures are finished in light greyRAL 7035 epoxy powder coating and have doors thatopen 180° for ease of access. Padlocking is arranged tobe ’off‘ as standard and up to three padlocks can be

attached with ease.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 85/182

83

Housed Switches

Skeleton Switches

32A

63/125A

160/200A

315/400A

630/800A

160/200A

63/125A

315/400A

630/800A

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 86/182

Housed Switches – 32A Completewith Fuses• Exceeds the requirements of EN

60947-3• All terminals supplied with cable

clamps• Full withstand duty

• 80kA rms fused short-circuit capacity• 415V AC rated voltage• Supplied with fuse links, solid links are

an optional accessory• AC23A utilisation category

• IP4X Ingress Protection• Not supplied with fuse links• For fuse links see page 89

Housed Switches – 63/125AComplete with Fuses• Exceeds the requirements of EN

60947-3• All terminals supplied with lug-fixing

screws

• Full withstand duty

• 80kA rms fused short-circuit capacity• 415V AC rated voltage• Supplied with fuse links, solid links are

an optional accessory• AC23A utilisation category• IP4X Ingress Protection

• Not supplied with fuse links• For fuse links see page 89

Housed Switches – 160/200A• Exceeds the requirements of EN

60947-3• All terminals supplied with lug-fixing

screws• Full withstand duty

• 80kA rms fused short-circuit capacity• 415V AC rated voltage• AC23A utilisation category• IP4X Ingress Protection• Not supplied with fuse links• For fuse links see page 89

32 – HBE3P32N –

Current rating (A) 3-pole cat. no. 3-pole+N cat. no. 4-pole cat. no.

63 HBF3P63N -100 HBF3P100N HBF4P100125 HBF3P125N -

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

160 HBF3P160N -200 HBF3P200N HBF4P200

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

315 HBK3P315N -400 HBL3P400N HBL4P400

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

630 HBN3P630N -800 HBN3P800N HBN4P800

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Housed Switches – 315/400A• Exceeds the requirements of EN

60947-3• All terminals supplied with lug-fixing

screws• Full withstand duty

• 80kA rms fused short-circuit capacity• 415V AC rated voltage• AC23A utilisation category• IP4X Ingress Protection• Not supplied with fuse links• For fuse links see page 89

Housed Switches – 630/800A• Exceeds the requirements of EN

60947-3• All terminals supplied with lug-fixing

screws• Full withstand duty

• 80kA rms fused short-circuit capacity• 415V AC rated voltage• AC23A utilisation category• IP4X Ingress Protection• Not supplied with fuse links• For fuse links see page 89

LoadswitchEnclosed Fuse Switch Combination Units 32A-800A

84

For solid isolator links see page 85.

For solid isolator links see page 85.

For solid isolator links see page 85.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 87/182

85

Accessories for Housed Switches

Cable spreader box 63/125 1 HB125CSB

160/200 1 HB200CSB315/400 1 HB400CSB630/800 1 HB800CSB

Solid links (set of 1) 32 2 HEL3263 2 HFL63

125-200 2 HFL200A315/400 2 HLL400630/800 2 HNL800

Castell* lock mounting kit All – SCLKCastell* lock with key (see note) All 3 FS22-bank auxiliary switch 63/200 4 SAUX2F

315/800 4 SAUX2N4-bank auxiliary switch 63/200 4 SAUX4F

315/800 4 SAUX4N6-bank auxiliary switch 315/800 4 SAUX6N

Description Current Picture Cat. no.rating (A)

Note: Standard symbol DS1, special symbols are available direct from Castell. Quotereference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65˚ anti-clockwise to trap key

*Castell is a trademark of Castell Safety International Limited.

1

2

4

3

Housed Switches Technical Data

Max. current rating (A) = 32 125 200

Rated current (A) 315 400 630 800Frame size K L N NMechanical endurance 8,000 5,000 5,000 3,000

Fused s/c current kA rms 80 80 80 80kW @ 415V AC 160 230 330 450Max. cable (mm2)* 185** 300 630 630Terminals M10 M10 4xM8 4xM8

M10 M10 1xM16 1xM16

Max cable lug palm width 35 50 80 80Weight (kg) 21 21 37 37

Max. current rating (A) = 400 800

* These figures are for guidance only and are dependent upon lug palm width.** 240mm2 with terminal barriers

Housed Switches Dimensions

32 210 210 220 363 420 263 273 6100 420 263 273 6125 420 263 273 6

160 525 315 325 12200 525 315 325 12315 735 420 325 21400 735 420 325 21630 840 630 378 37800 840 630 378 37

Current Height Width Depth over Weightrating (A) (mm) (mm) handle (mm) (kg)

Spreader Box Dimensions

63A-125A 105 263 183 HB125CSB200A 105 315 235 HB200CSB315-400A 210 420 235 HB400CSB630-800A 210 630 288 HB800CSB

Current Height Width Depth over Weightrating (A) (mm) (mm) handle (mm) (kg)

All dimensions in mm

Rated current (A) 32 63 100 125 160 200Frame size E F FMechanical endurance 10,000 10,000 10,000 8,000 8,000 8,000

Fused s/c current kA rms 80 80 80 80 80 80kW @ 415V AC 15 30 55 75 90 110Max. cable (mm2)* 10 70 70 70 150 150Terminals Clamp type M8 M8 M8 M8 M8Max cable lug palm width – 22 22 22 22 22

Weight (kg) 3 6 6 6 12 12

32A Top and Bottom KnockOut Dimensions

63 - 125A Top and BottomKnock Out Dimensions

630-800A Loadswitch Terminal

LoadswitchEnclosed Fuse Switch Combination Units Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 88/182

86

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

63 SF3P63N SF4P63

100 SF3P100N SF4P100

125 SF3P125N SF4P125

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

160 SF3P160N SF4P160

200 SF3P200N SF4P200

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

315 SK3P315N SK4P315

400 SL3P400N SL4P400

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Skeleton Switches – 63/125A• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty

• 415V AC rated voltage• Lug fixings not supplied

Skeleton Switches – 160/200A• Exceeds the requirements of EN 60947-3

• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage• Lug fixings not supplied

Skeleton Switches – 315/400A• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage• Lug fixings not supplied

Skeleton Switches – 630/800A• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V AC rated voltage• Lug fixings not supplied

LoadswitchSkeleton Switches (Without Fuses)

For fuse links see page 89.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 89/182

87

2

1

3 4

5

6

Accessories for Skeleton Switches

Description Current Picture Cat. no.

rating (A)

Cable extension terminals (set of 8) 630/800 – SNCETSolid links (set of 1) 63 1 HFL63

100/200 1 HFL200A

315/400 1 HLL400

630/800 1 HNL800

2-bank auxiliary switch 63/200 3 SAUX2F

315/800 3 SAUX2N

4-bank auxiliary switch 63/200 3 SAUX4F

315/800 3 SAUX4N

6-bank auxiliary switch 315/800 3 SAUX6N

Castell* lock mounting kit

(standard symbol DS1 – see note) All – SCLK

Castell* lock with key 32/800 2 FS2

Handle assembly for:

E frame - standard size – 5 SHA1F frame - standard size – 5 SHA2

K + L frame - special reduced size – 5 SHA3

KL+N frame - standard size – 5 SHA4

Shaft extensions 63A - 200A 4 SXT127for panel depth 270mm 315A - 800A 4 SXT227

Shaft extensions 63A - 200A 4 SXT160for panel depth 600mm 315A - 800A 4 SXT260

Terminal shrouds 160/200 – SFTSL(recommended for cable sizes above 70mm)

63/200 – SFTSS

315 – SKTS

400 – SLTS630/800 – SNTS

Terminal barriers (set of 3) 63/200 – SFTB

315 – SKTB

400 – SLTB

630/800 – Supplied

Fuse shrouds (set of 3) 63/125 – SFFS125

160/200 – SFFS200

315 – SKFS

400 – SLFS

630/800 – SNFS

Rating label (strip of 8) 63 6 SRLB63

100 6 SRLB100

125 6 SRLB125

160 6 SRLB160

200 6 SRLB200

315 6 SRLB315

400 6 SRLB400

630 6 SRLB630

800 6 SRLB800

Note: Special symbols are available direct from Castell.Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65˚ anti clockwiseto trap key.

*Castell is a trademark of Castell Safety International Ltd.

LoadswitchSkeleton Switch Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 90/182

88

* These figures are for guidance only and are dependent upon lug palm width** 240mm2 with terminal barriers*** Only with cable extension terminals (SNCET)

Dimensions

Frame A B C D E F G H I J K L M N O P Q W X Y Z

F 63A 80 135 170 186 270 35 140 150 165 50 73 N/A 30 80 160 161 3 M5 170* M8 20F100-125A 80 135 170 186 270 35 140 150 165 50 94 N/A 30 80 160 161 3 M5 170* M8 20

F 160-200A 80 135 170 186 300 35 140 150 165 50 94 N/A 30 80 196 197 3 M5 220 M8 20

K 315A 60 180 220 250 384 52.5 210 225 235 90 111 N/A 45 87 210 212 5 M5 220 M12 35

L 400A 60 180 220 250 414 70 280 295 305 125 111 N/A 45 87 210 212 5 M5 220 M12 50N 630-800A 100 180 235 255 534 105 420 460 475 195 133 184 60 129 240 242 5 M6 270 M12 80

Skeleton Switches Dimensions 630/800A Standard Terminal

* Supplied suitable for an ‘X’ dimension of 220mm, the drive shaft can be cut to give a minimum ‘X’ dimension of 170mm.

630/800A extensionterminal (accessory)

Max. current rating (A) = 400 800

Rated current (A) 315 400 630 800

Frame size K L N N

Mechanical endurance 8,000 5,000 5,000 3,000

Fused s/c current kA rms 80 80 80 80

kW @ 415V AC 160 230 330 450

Max. cable (mm2)* 185** 300 630 630

Terminals M12 M12 4xM8*** 4xM8***

M12 M12 1xM16*** 1xM16***

Max cable lug palm width 35 50 80 80

Weight (kg) 21 21 37 37

LoadswitchTechnical Data

Skeleton Switches Technical Data

Max. current rating (A) = 125 200

Rated current (A) 63 100 125 160 200

Frame size F F F F F

Mechanical endurance 10,000 10,000 8,000 8,000 8,000

Fused s/c current kA rms 80 80 80 80 80

kW @ 415V AC 30 55 75 90 110

Max. cable (mm2)* 70 70 70 150 150

Terminals M8 M8 M8 M8 M8Max cable lug palm width 22 22 22 22 22

Weight (kg) 6 6 6 12 12

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 91/182

89

NOTE:1. The comparative types are a guide to interchangeability, with regard to dimensions and current rating only. It is essential

that rated voltage and other electrical characteristics are checked to ensure compatability.2. Please check maximum barrel size prior to fitting.3. *Lawson fuse reference only.

LoadswitchFuse Comparison Chart - 415V

Standard Bussman GEC/ MEM Tag type BS88 ref Fuse fixing Insertedswitch Lawson centres (mm) switch

NITD2 NIT2 2SA2

NITD4 NIT4 4SA2

NITD6 NIT6 6SA2

HBE3P32N NITD10 NIT10 10SA2 OFFSET A1 44.5

NITD16 NIT16 16SA2

NITD20 NIT20 20SA2

NITD25 NIT25* 25SA2

NITD32 NIT32* 32SA2

AAO2 TIA2 2SB3

AAO4 TIA4 4SB3

AAO6 TIA6 6SB3

AAO10 TIA10 10SB3

HBF/SF3P63 AAO16 TIA16 16SB3 OFFSET A2 73.0 SFT3P63

HBF/SF3P63N AAO20 TIA20 20SB3 SFT3P63N

HBF/SF4P63 AAO25 TIA25 25SB3 SFT4P63

AAO32 TIA32 32SB3BAO40 TIS40 40SB4

BAO50 TIS50 50SB4 OFFSET A3 73.0

BAO63 TIS63 63SB4

– TCP6* –

– TCP10* –

– TCP16* –

– TCP20* –

HBF/SF3P100 – TCP25* – SFT3P100

HBF/SF3P100N CEO32 TCP32* – OFFSET A4 (dia 33 max) 94.0 SFT3P100N

HBF/SF4P100 CEO40 TCP40* – SFT4P100

CEO50 TCP50* –

CEO63 TCP63* –

CE080 TCP80 80SD5

CEO100 TCP100 100SD5

HBF/SF3P125 SFT3P125

HBF/SF3P125N DEO125 TFP125 125SD6 OFFSET A4 94.0 SFT3P125N

HBF/SF4P125 SFT4P125

HBF/SF3P160 SFT3P160

HBF/SF3P160N DEO160 TFP160 160SD6 OFFSET A4 (dia 38 max) 94.0 SFT3P160N

HBF/SF4P160 SFT4P160

HBF/SF3P200 SFT3P200

HBF/SF3P200N DEO200 TFP200 200SD6 OFFSET A4 (dia 38 max) 94.0 SFT3P200N

HBF/SF4P200 SFT4P200

CD80 TC80 80SF5

CD100 TC100 100SF5 CENTRE B1 111.0 SKT3P315

HBK/SK3P315 DD125 TF125 125SF6 SKT3P315N

HBK/SK3P315N DD160 TF160 160SF6 CENTRE B2 111.0 SKT4P315HBK/SK4P315 DD200 TF200 200SF6

HBL/SL3P400 ED250 TKF250 250SF7 SLT3P400

HBL/SL3P400N ED315 TKF315 315SF7 CENTRE B3 (dia 50 max) 111.0 SLT3P400N

HBL/SL4P400 SLT4P400

EF355 TM355 355SH8

EF400 TM400 400SH8 CENTRE C1 133.0 SNT3P630

HBN/SN3P630 FF450 TTM450 450SH9 SNT3P630N

HBN/SN3P630N FF500 TTM500 500SH9 SNT4P630

HBN/SN4P630 FF560 TTM560 560SH9 CENTRE C2 133.0

FF630 TTM630 630SH9

HBN/SN3P800 – TLM670 – SNT3P800

HBN/SN3P800N GF710 TLM710 710SH10 SNT3P800N

HBN/SN4P800 – TLM750 – CENTRE C3 133.0 SNT4P800

GF800 TLM800 800SH10

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 92/182

Current rating (A) 3-pole cat. no.

16 PS16NY25 PS25NY32 PS32NY40 PS40NY63 PS63NY80 PS80NY100 PS100NY125 PS125NY

Dimensions

Current Height Width Depth over Weight

rating (A) (mm) (mm) handle (mm) (kg)

16 133 86 104 0.36

25 133 86 104 0.36

32 175 125 136 0.75

40 175 125 136 0.75

63 300 200 168 1.82

80 400 300 168 2.74

100 400 300 168 2.74

125 400 300 168 2.74

Switch Disconnectors in IP65 Insulated Enclosures• Conforms to EN 60947-3• Padlockable handle• Rotary handle accepts three padlocks• Terminals accept large cables

• Includes earth and neutral terminals• IP65 ingress protection

Current rating (A) 16 25 32 40 63 80 100 125

Rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800

Dielectric strength (kV) 50 Hz 1 min 3 3 3 3 3 3 3 3

Shock resistance Uimp (kV) 8 8 8 8 8 8 8 8

Operational current Ie (A)

415V AC – AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 125

AC23A/AC23B 16 25 32 40 63 80 80 80

500V AC – AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 125

AC23A/AC23B 16 25 32 40 40 63 63 63

690V AC – AC20A/AC20B 16 25 32 40 63 80 100 125

AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 100AC23A/AC23B 16 25 25 25 25 50 50 50

Motor power (kW) AC23

415V AC 7.5 9 11 11 15 22 37 40

500V AC 7.5 9 11 15 18.5 30 37 37

690V AC 11 11 11 18.5 18.5 30 30 30

Overload capacity at 415V AC

Fuse rating 16 25 32 40 63/40 80 100 125

Short-circuit current with fuses (kA rms) 50 50 50 50 20/50 25 25 11

Asymmetric short time ratingcurrent (kA peak) 6 6 6 6 6 9 9 9

Admissible short time current 1s (kA rms) 1.26 1.26 1.26 1.26 1.26 1.5 1.5 1.5

Making and breaking characteristics

Breaking capacity (A rms) 415V AC23A 128 200 256 320 504 640 640 640

Making capacity (A rms) 415V AC23A 160 250 320 400 630 800 800 800

WithstandMechanical (number of operations) x 1000 100 100 100 100 100 30 30 30

Electrical (no. of operations at 415VAC23A) x 1000 3 3 3 3 3 1.5 1.5 1.5

Connection

Maximum Cu cable section (mm2) 16 16 16 16 16 50 50 50

Using stranded cable (mm2) 25 25 25 25 25 – – –

Technical Data for Disconnectors in IP65 Insulated Enclosures

LoadswitchSwitch Disconnectors in IP rated Enclosures

90

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 93/182

91

Current rating (A) 16 25 32 40 63 80 100 125

Rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800

Dielectric strength (kV) 50 Hz 1 min 3 3 3 3 3 3 3 3

Shock resistance Uimp (kV) 8 8 8 8 8 8 8 8

Operational current Ie (A)

415V AC – AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 125

AC23A/AC23B 16 25 32 40 63 80 80 80

500V AC – AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 125

AC23A/AC23B 16 25 32 40 40 63 63 63

690V AC – AC20A/AC20B 16 25 32 40 63 80 100 125

AC21A/AC21B 16 25 32 40 63 80 100 125

AC22A/AC22B 16 25 32 40 63 80 100 100

AC23A/AC23B 16 25 25 25 25 50 50 50Motor power (kW) AC23

415V AC 7.5 9 11 11 15 22 37 40

500V AC 7.5 9 11 15 18.5 30 37 37

690V AC 11 11 11 18.5 18.5 30 30 30

Overload capacity at 415V AC

Fuse rating 16 25 32 40 63/40 80 100 125

Short-circuit current with fuses (kA rms) 50 50 50 50 20/50 25 25 11

Asymmetric short time ratingcurrent (kA peak) 6 6 6 6 6 9 9 9

Admissible short time current 1s (kA rms) 1.26 1.26 1.26 1.26 1.26 1.5 1.5 1.5

Making and breaking characteristics

Breaking capacity (A rms) 415V AC23A 128 200 256 320 504 640 640 640

Making capacity (A rms) 415V AC23A 160 250 320 400 630 800 800 800

Withstand

Mechanical (number of operations) x 1000 100 100 100 100 100 30 30 30

Electrical (no. of operations at 415VAC23A) x 1000 3 3 3 3 3 1.5 1.5 1.5

Connection

Maximum Cu cable section (mm2) 16 16 16 16 16 50 50 50

Using stranded cable (mm2) 25 25 25 25 25 – – –

Technical Data for Disconnectors in IP65 Insulated Enclosures

Switch Disconnectors in Sheet Steel Enclosures• Conforms to EN 60947-3• Padlockable handle• Rotary handle accepts three padlocks• Terminals accept large cables

• IP4X ingress protection

Current rating (A) 3-pole cat. no. 3-pole+N cat. no.

20 HS13P20 HS13P20N32 HS13P32 HS13P32N40 HS13P40 HS13P40N63 HS13P63 HS13P63N63 HS23P63 HS23P63N100 HS23P100 HS23P100N125 HS23P125 HS23P125N

LoadswitchSwitch Disconnectors in Sheet Steel Enclosures

Current Height Width Depth over Weight

rating (A) (mm) (mm) handle (mm) (kg)

3-pole 4-pole

20 210 158 173 2.0 2.232 210 158 173 2.0 2.2

40 210 158 173 2.0 2.2

63 210 158 173 2.0 2.2

63 315 158 173 2.5 2.7

100 315 158 173 2.5 2.7

125 315 158 173 2.5 2.7

DimensionsDisconnectors

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 94/182

92

Accessories for Switch Disconnectors

Description Current rating (A) Cat. no.

63A neutral link All HSNL63125A neutral link All HSNL12510A auxiliary switch All HSAUXTerminal shroud (set of 2):1-pole 16/63 HSTS1633-pole 16/63 HSTS3631-pole 63/125 HSTS11253-pole 63/125 HSTS3125

LoadswitchSwitch Disconnectors Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 95/182

7Section

Dorman Smith Circuit Protection

and Modular Devices

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 96/182

94

Circuit Protection DevicesLoadlimiter 63 Miniature Circuit Breakers 10/15kA

10kA/15kA MCBs• Exceeds the requirements of EN 60898• Contact position indicator• 35mm2 cable capacity• Multiples of 17.5mm width

• 10kA rated to the requirements of EN60898• 15kA rated to the requirements EN60947

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Single-pole MCBs

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 N/A

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 T1PD40*

50 K1PB50 K1PC50 T1PD50*

63 K1PB63 K1PC63 T1PD63*

Double-pole MCBs

6 K2PB06 K2PC06 K2PD06

10 K2PB10 K2PC10 K2PD10

13 N/A N/A N/A

16 K2PB16 K2PC16 K2PD16

20 K2PB20 K2PC20 K2PD20

25 K2PB25 X2PC25 K2PD25

32 K2PB32 K2PC32 K2PD32

40 K2PB40 K2PC40 T2PD40*

50 K2PB50 K2PC50 T2PD50*

63 K2PB63 K2PC63 T2PD63*

Triple-pole MCBs6 K3PB06 K3PC06 K3PD06

10 K3PB10 K3PC10 K3PD10

13 N/A N/A N/A

16 K3PB16 K3PC16 K3PD16

20 K3PB20 K3PC20 K3PD20

25 K3PB25 K3PC25 K3PD25

32 K3PB32 K3PC32 K3PD32

40 K3PB40 K3PC40 T3PD40*

50 K3PB50 K3PC50 T3PD50*

63 K3PB63 K3PC63 T3PD63*

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 97/182

Circuit Protection DevicesLoadlimiter 63 Residual Current Circuit Breaker with Overload

Current rating (A) Sensitivity B type cat. no. C type cat. no.

6 30 KR1PB0630 KR1PC063010 30 KR1PB1030 KR1PC103016 30 KR1PB1630 KR1PC163020 30 KR1PB2030 KR1PC203032 30 KR1PB3230 KR1PC323040 30 KR1PB4030 KR1PC403045 30 KR1PB4530 KR1PC45306 100 - KR1PC0610010 100 - KR1PC1010016 100 - KR1PC1610020 100 - KR1PC2010032 100 - KR1PC3210040 100 - KR1PC40100

10kA RCBOs• Exceeds the requirements of EN 61009• Single module: Type AC• 10kA rated breaking capacity• Terminal capacity: outgoing terminals 10mm2

• Terminal capacity: busbar side terminals 35mm2

Double Module RCBOs• Exceeds the requirements of

EN 61009, IEC 61009• SP&SwN configuration• Rated breaking capacity up to 10kA• Contact position indicator• Rated voltage Ue ~230V• Rated frequency 50Hz

• Energy limiting class 3• Type AC• Terminal capacity: outgoing

terminals 35mm2

• Terminal capacity: busbar sideterminals 35mm2

Current rating (A) 30m/A cat. no.

6 KR2PB063010 KR2PB103016 KR2PB163020 KR2PB203032 KR2PB323040 KR2PB4030

MCB shunt trip (240V AC) KST240

MCB auxiliary/switch contact KAUX1

Padlocking

MCB dolly locking device KDL

Padlock for dolly locking device XPL

Auxiliary equipment Cat. no.

Accessories for 10kA MCBs and RCBOs

95

126.4

45

34.5

98.2

109

4 . 3

6 .

8 6 .

6

4 3 . 1

6 9 . 5

1 7 .

4

Dimensions

Single Module Double Module

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 98/182

96

Circuit Protection DevicesLoadlimiter 63 Miniature Circuit Breakers 6kA/10kA

6kA/10kA – MCBs• Exceeds the requirements of EN 60898• 6kA rated breaking capacity to EN 60898• Contact position indicator• 25mm2 cable capacity

• 10kA rated breaking capacity to EN 60947-2

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Single-pole MCBs6 S1PB06 S1PC06 S1PD0610 S1PB10 S1PC10 S1PD1016 S1PB16 S1PC16 S1PD1620 S1PB20 S1PC20 S1PD2025 S1PB25 S1PC25 S1PD2532 S1PB32 S1PC32 S1PD3240 S1PB40 S1PC40 S1PD4050 S1PB50 S1PC50 S1PD5063 S1PB63 S1PC63 S1PD63Double-pole MCBs

6 S2PB06 S2PC06 S2PD0610 S2PB10 S2PC10 S2PD1016 S2PB16 S2PC16 S2PD1620 S2PB20 S2PC20 S2PD2025 S2PB25 S2PC25 S2PD2532 S2PB32 S2PC32 S2PD3240 S2PB40 S2PC40 S2PD4050 S2PB50 S2PC50 S2PD5063 S2PB63 S2PC63 S2PD63Triple-pole MCBs6 S3PB06 S3PC06 S3PD0610 S3PB10 S3PC10 S3PD1016 S3PB16 S3PC16 S3PD1620 S3PB20 S3PC20 S3PD2025 S3PB25 S3PC25 S3PD25

32 S3PB32 S3PC32 S3PD3240 S3PB40 S3PC40 S3PD4050 S3PB50 S3PC50 S3PD5063 S3PB63 S3PC63 S3PD63

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 99/182

97

Circuit Protection DevicesLoadlimiter 63 Residual Current Circuit Breakers

RCCBs• Exceeds the requirements of EN 61008• Voltage 230/400V 50/60Hz• Type AC• Terminal capacity: top 25mm2

• Terminal capacity: bottom 35mm2

Four-pole RCCBs

40 30 AC 35 EE40/30/2

40 100 AC 35 EE40/100/2

63 30 AC 35 EE63/30/2

63 100 AC 35 EE63/100/2

63 300 AC 35 EE63/300/2

80 30 AC 35 EE80/30/2

100 30 AC 35 EE100/30/2

100 100 AC 35 EE100/100/2

100, time delay 100 AC 35 EES100/100/2

Current rating (A) Sensitivity (mA) Type Width (mm) Cat. no.

40 30 AC 70 EE40/30/4

40 100 AC 70 EE40/100/4

40 300 AC 70 EE40/300/4

63 30 AC 70 EE63/30/4

63 100 AC 70 EE63/100/463 300 AC 70 EE63/300/4

100 30 AC 70 EE100/30/4

100 100 AC 70 EE100/100/4

100 300 AC 70 EE100/300/4

100, time delay 100 AC 70 EES100/100/4

Current rating (A) Sensitivity (mA) Type Width (mm) Cat. no.

Double-pole RCCBs

Dimensions

4-pole 2-pole

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 100/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 101/182

99

Circuit Protection DevicesLoadline Moulded Case Circuit Breakers

Frame YA3N YA3S YA3J YA5N YA5H

Maximum amps 250 250 250 400 400

No. of poles 1 3 4 3 4 3 4 3 4 3 4

Adjustable thermal N Y Y Y Y Y

Adjustable magnetics N N Y Y Y N

Rated current Nom Adj Adj Adj Adj Adj Adj Adj Adj Adj(A). [In] min max min max min max min max min max

16 16 – – – – – – – – – –

20 20 13 20 13 20 – – – – – –

25 25 – – – – – – – – – –

32 32 20 32 20 32 20 32 – – – –

40 40 – – – – – – – – – –

50 50 32 50 32 50 32 50 – – – –

63 63 40 63 40 63 40 63 – – – –

80 80 – – – – – – – – – –

100 100 63 100 63 100 63 100 – – – –

125 125 80 125 80 125 80 125 – – – –

160 160 100 160 100 160 100 160 – – – –

200 – 125 200 125 200 125 200 – – – –

250 – 160 250 160 250 160 250 160 250 160 250

400 – – – – – – – 250 400 250 400

Rated impulse withstand 8 8 8 8 8

voltage Uimp[kV]

AC rated insulation 800 800 800 800 800

voltage [Ui]

AC rated breaking capacity Icu Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

IEC 947-2 690V – – – 7.5 7.5 7.5 7.5 – – 20 15

EN 60947-2 525V – 10 7.5 25 25 25 25 15 15 30 30

CEI EN 60947-2 440V – 15 12 25 25 25 25 22 22 45 45

415V – 25 19 36*** 36*** 65 65 25 25 50 50

400V – 25 19 36*** 36*** 65 65 25 25 50 50

380V – 25 19 36*** 36*** 65 65 25 25 50 50

240V 25 35 27 65 65 85 85 35 35 35 85

220V 25 35 27 65 65 85 85 35 35 35 85

NEMA AB-1 600V – – – – – – – – – – –

480V – 10 – 22 – 22 – 15 – 22 –

240V – 35 – 65 – 85 – 35 – 50 –

Without

instantaneous

240-690V – – – – – – – – – – –DC rated 250V 19 25 25 40 40 40 40 25 25 40 40

breaking 125V

capacity

[kA]

Rated short time – – – – –

current r.m.s.

[kA] [Icw]

Utilisation category A A A A A

Notes: *Value at1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown. ***20A and 32A only rated at 30kA at this voltage.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 102/182

100

Circuit Protection DevicesLoadline Moulded Case Circuit Breakers

Frame YA5H YA5K Y6H Y6K

Electronic Electronic Thermal/ Thermal/

Magnetic and Magnetic

Generator

Maximum 400 400 800A 800A

ampsNo. of poles 3 4 3 4 3 4 3 4

Adjustable Y Y Y Y

thermal

Adjustable Y Y Y Y

magnetics

Rated current Adj Adj Adj Adj Nom Adj Nom Adj

(A). [In] min max min max min max min max

50 – – – – – – – – – –

63 – – – – – – – – – –

80 – – – – – – – – – –

100 – – – – – – – – – –

125 – – – – – – – – – –

160 – – – – – – – – – –

200 – – – – – – – – – –

250 100 250 100 250 – – – – – –

400 160 400 160 400 400 250 400 400 250 400

630 – – – – 630 400 630 630 400 630

800 – – – – 800 500 800 800 500 800

1000 – – – – – – – – – –

1250 – – – – – – – – – –

1600 – – – – – – – – – –

Rated impulse 8 8 8 8

withstand

voltage Uimp

[kV]

AC rated 800 800 690 690

insulation

voltage [Ui]

AC rated Icu Ics Icu Ics Icu Ics Icu Ics

breaking

symmetrical

r.m.s. [kA]

IEC 947-2 690V 20 15 20 15 20 10** 45 23**

EN 60947-2 525V 30 30 30 30 – – – –

BS EN 60947-2 500V – – – – 35 18** 65 33**415V 50 50 70 50 50 25 85 50

400V 50 50 70 50 65 33 100 50

380V 50 50 70 50 65 33 100 50

240V 85 85 100 85 85 43 125 63

220V 85 35 100 85 85 43 125 63

NEMA AB-1 600V – – 30 –

480V 25 30 – –

400V – – 50 –

240V 85 100 85 –

Without

instantaneous

240-690V – – – –

DC rated 250V – – 50 50

breaking 125V – – 50 50

capacity

[kA]

Rated short time 5 5 – –

current r.m.s. [kA]

[Icw]

Utilisation category B B A A

Notes: *Value at1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 103/182

101

Circuit Protection DevicesLoadline Moulded Case Circuit Breakers

Frame Y6H-E Y6J-E Y7J-E Y8K-E

Electronic Electronic Electronic Electronic

Maximum 800A 800A 1250A 1600A

amps

No. of poles 3 4 3 4 3 4 3 4

Adjustable – – – –thermal

Adjustable – – – –

magnetics

Rated current Nom Adj Nom Adj Nom Adj Nom Adj

(A). [In] min max min max min max min max

50 – – – – – – – – – – – –

63 – – – – – – – – – – – –

80 – – – – – – – – – – – –

100 – – – – – – – – – – – –

125 – – – – – – – – – – – –

160 – – – – – – – – – – – –

200 – – – – – – – – – – – –

250 – – – – – – – – – – – –

400 – – – – – – – – – – – –

630 630 315 630 630 315 630 – – – – – –

800 800 400 800 800 400 800 – – – – – –

1000 – – – – – – 1000 500 1000 – – –

1250 – – – – – – 1250 630 1250 – – –

1600 – – – – – – – – – 1600 800 1600

Rated impulse 8 8 8 8

withstand

voltage Uimp

[kV]

AC rated 690 690 690 690

insulation

voltage [Ui]

AC rated Icu Ics Icu Ics Icu Ics Icu Ics

breaking

symmetrical

r.m.s. [kA]

IEC 947-2 690V 20 10** 20 10** 25 19** 35 35**

EN 60947-2 500V 35 18** 42 21** 45 34** 65 49**

BS EN 400V 50 25 65 50 65 49 85 64

60947-2

415V 50 25 65 50 65 49 85 64400V 50 25 65 50 85 64 100 75

380V 50 25 65 50 85 64 100 75

240V 85 43 100 50 100 75 125 94

220V 85 43 100 50 100 75 125 94

NEMA AB-1 600V 30 – 42 –

400V 50 – 65 –

240V 85 – 85 –

Without

instantaneous

240-690V 10 10 15 20

DC rated 250V – – – –

breaking 125V – – – –

capacity

[kA]

Rated short time 10 (0.3 sec) 10 (0.3 sec) 15 (0.3 sec) 20 (0.3 sec)

current r.m.s. [kA] [Icw]

Utilisation category B B B B

Notes: *Value at 1/ 3 times stated voltage. ** Not applicable to IT systems at voltage shown.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 104/182

102

Circuit Protection DevicesLoadline YB1 and YB3 Frame Moulded Circuit Case Breakers

YB1 Frame MCCBs (Available 2012)• Standard cable termination = 50mm2

• Triple-pole and four-pole have adjustable thermal overloads only• Single-pole devices have fixed thermal and magnetic overloads

Current rating (A) 1-pole Cat no. 3-pole Cat No. 4-pole Cat no

YB1 Frame Switch Disconnector

160 - YB1B3P160D YB1B4P160D

YB1 Frame MCCB Thermal/Magnetic -Icu 25kA

16 YB1N1P16T - -

20 YB1N1P20T - -

25 YB1N1P25T YB1N3P25T YB1N4P25T

32 YB1N1P32T YB1N3P32T YB1N4P32T

40 YB1N1P40T YB1N3P40T YB1N4P40T

50 YB1N1P50T - -

63 YB1N1P63T YB1N3P63T YB1N4P63T

80 YB1N1P80T YB1N3P80T YB1N4P80T

100 YB1N1P100T YB1N3P100T YB1N4P100T125 YB1N1P125T YB1N3P125T YB1N4P125T

160 - YB1N3P160T YB1N4P160T

YB3 Frame MCCBs• Standard cable termination = 95mm2

• Maximum cable termination using M8 reduced palm width cable lugs = 150mm2

• Triple-pole and four-pole have adjustable thermal overloads only

Current rating (A) 1-pole Cat no. 3-pole Cat No. 4-pole Cat no

YB3 Frame Switch Disconnector

250 - YB3B3P250D YB3B4P250D

YB3 Frame MCCB Thermal/Magnetic -Icu 25kA50 YB3N3P50T YB3N4P50T

63 YB3N3P63T YB3N4P63T

100 YB3N3P100T YB3N4P100T

125 YB3N3P125T YB3N4P125T

160 - YB3N3P160T YB3N4P160T

200 YB3N3P200T YB3N4P200T

250 YB3N3P250T YB3N4P250T

Dimensions

YB1 1-pole YB1 3-pole and 4-pole YB3 3-pole and 4-pole

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 105/182

103

Circuit Protection DevicesLoadline YA2 Frame Moulded Case Circuit Breakers

YA2 Frame MCCBs• Exceeds EN60947-2• Rated insulation voltage is 800V AC (U i)• Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Standard M8 cable lug termination = 35mm2

• Maximum cable termination = 95mm2

(using M8 reduced palm width lugs)

YA2 Frame MCCB Thermal/Magnetic – Icu 25kA

16 YA2N1P16T N/A N/A20 YA2N1P20T YA2N3P20T YA2N4P20T32 YA2N1P32T YA2N3P32T YA2N4P32T50 YA2N1P50T YA2N3P50T YA2N4P50T63 YA2N1P63T YA2N3P63T YA2N4P63T80 YA2N1P80T - -100 YA2N1P100T YA2N3P100T YA2N4P100T125 YA2N1P125T YA2N3P125T YA2N4P125T

YA2 Frame MCCB Thermal/Magnetic – Icu 36kA

50 YA2S3P50T YA2S4P50T63 YA2S3P63T YA2S4P63T100 YA2S3P100T YA2S4P100T125 YA2S3P125T YA2S4P125T

YA2 Frame MCCB Thermal/Magnetic – Icu 65kA

20 YA2J3P20T YA2J4P20T32 YA2J3P32T YA2J4P32T50 YA2J3P50T YA2J4P50T63 YA2J3P63T YA2J4P63T100 YA2J3P100T YA2J4P100T125 YA2J3P125T YA2J4P125T

Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no.

YA2 3 and 4-pole

Dimensions

YA2 1-pole

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 106/182

104

** Common to all YA2, YA3, YA5 MCCBs.

Circuit Protection DevicesLoadline YA2 Frame Accessories

Cable clamps

YA2 cable clamps (set of 3) YA2CC3PYA2 cable clamps (set of 4) YA2CC4PTerminals and protectionYA2 1-pole terminal shroud YA2TS1PYA2 3-pole terminal shroud YA2TS3PYA2 4-pole terminal shroud YA2TS4PYA2 terminal barrier YA2TBYA2 3-pole terminal cover YA2TS3P3YA2 4-pole terminal cover YA2TS4PSYA2 3-pole rear terminals YA2RT3PYA2 4-pole rear terminals YA2RT4PYA2 3-pole extension terminals YA2XT3PYA2 4-pole extension terminals YA2XT4PPlug-in unitsYA2 3-pole plug-in terminals YA2PT3PYA2 4-pole plug-in terminals YA2PT4P

YA2 3-pole plug-in base YA2PB3PYA2 4-pole plug-in base YA2PB4PYA2 3-pole plug-in base extension terminals YA2PXT3PYA2 4-pole plug-in base extension terminals YA2PXT4PYA2 3-pole right angle terminals YA2PRA3PYA2 4-pole right angle terminals YA2PRA4PMotors and interlocksYA2 motor actuator, 100-110V ac YA2MA110YA2 motor actuator, 200-240V ac YA2MA240YA2 mechanical changeover, link type YA2MLYA2 mechanical changeover, manual slide type YA2MMSYA2 mechanical changeover, wire type with 1 metre cable YA2MW10YA2 mechanical changeover, wire type with 1.5 metre cable YA2MW15AuxiliariesYA2 dolly lock YADL1

YA2 neutral link YA2NLYA2 rotary handle standard length YA2R1YA2 rotary handle long length YA2R2Shunt trips**YA frame shunt trip 100-120V AC YAST115AC**YA frame shunt trip 200-240V AC YAST240AC**YA frame shunt trip 380-450V AC YAST450AC**YA frame shunt trip 24V DC YAST24DCAuxiliary and alarm switches**YA frame 1AB auxiliary switch YAAUX1**YA frame alarm switch YAALUnder-voltage release**YA frame under-voltage release 100-120V AC YAUVR120AC**YA frame under-voltage release 200-240V AC YAUVR240AC**YA frame under-voltage release 380-450V AC YAUVR450AC**YA frame under-voltage release 24V DC YAUVR24DC

Description Cat. no.

YA2 Frame Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 107/182

105

YA3 Frame MCCBs• Exceeds EN 60947-2 requirements• Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V AC (U i)• Standard M8 cable lug termination = 95mm 2

• Maximum cable termination = 150mm2

(using M8 reduced palm width lugs)

YA3 Switch Disconnector250 YA3B3P250D YA3B4P250DYA3 Frame MCCB Thermal/Magnetic - Icu 25kA

16 16 YA3N1P16T - -

20 13 YA3N1P20T YA3N3P20T YA3N4P20T

32 20 YA3N1P32T YA3N3P32T YA3N4P32T

40 25 YA3N1P40T - -

50 32 YA3N1P50T YA3N3P50T YA3N4P50T

63 40 YA3N1P63T YA3N3P63T YA3N4P63T

80 50 YA3N1P80T - -100 63 YA3N1P100T YA3N3P100T YA3N4P100T

125 80 YA3N1P125T YA3N3P125T YA3N4P125T

160 100 YA3N1P160T YA3N3P160T YA3N4P160T

200 125 - YA3N3P200T YA3N4P200T

250 160 - YA3N3P250T YA3N4P250T

YA3 Frame MCCB Thermal/Magnetic – Icu 36kA

50 32 YA3S3P50T YA3S4P50T

63 40 YA3S3P63T YA3S4P63T

100 63 YA3S3P100T YA3S4P100T

125 80 YA3S3P125T YA3S4P125T

160 100 YA3S3P160T YA3S4P160T

200 125 YA3S3P200T YA3S4P200T

250 160 YA3S3P250T YA3S4P250T

YA3 Frame MCCB Thermal/Magnetic – Icu 65kA

50 32 YA3J3P50T YA3JP50T

63 40 YA3J3P63T YA34J63T

100 63 YA3J3P100T YA34J100T

125 80 YA3J3P125T YA34J125T

160 100 YA3J3P160T YA34J160T

200 125 YA3J3P200T YA34J200T

250 160 YA3J3P250T YA34J250T

Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no.

Max. Min.

Circuit Protection DevicesLoadline YA3 Frame Moulded Case Circuit Breakers

Dimensions

YA3 1-pole

YA3 3 and 4-pole

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 108/182

106

Circuit Protection DevicesLoadline YA3 Frame Accessories

Cable clampsYA3 cable clamps (set of 3) YA3CC3PYA3 cable clamps (set of 4) YA3CC4P

Terminals and protectionYA3 1-pole terminal shroud YA3TS1PYA3 3-pole terminal shroud YA3TS3PYA3 4-pole terminal shroud YA3TS4PYA3 terminal barrier YA3TBYA3 3-pole terminal cover YA3TS3PSYA3 4-pole terminal cover YA3TS3P3YA3 3-pole rear terminals YA3RT3PYA3 4-pole rear terminals YA3RT4PYA3 3-pole extension terminals YA3XT3PYA3 4-pole extension terminals YA3XT4PPlug-in unitsYA3 3-pole plug-in terminals YA3PT3PYA3 4-pole plug-in terminals YA3PT4PYA3 3-pole plug-in base YA3PB3PYA3 4-pole plug-in base YA3PB4PYA3 3-pole plug-in base extension terminals YA3PXT3PYA3 4-pole plug-in base extension terminals YA3PXT4PYA3 3-pole right angle terminals YA3PRA3PYA3 4-pole right angle terminals YA3PRA4PMotors and interlocksYA3 motor actuator, 100-110V AC YA3MA110YA3 motor actuator, 200-240V AC YA3MA240YA3 mechanical changeover, link type YA3MLYA3 mechanical changeover, manual slide type YA3MMSYA3 mechanical changeover, wire type with 1 metre cable YA3MW10YA3 mechanical changeover, wire type with 1.5 metre cable YA3MW15Castell* mounting kit (lock to be ordered separately) YACLAuxiliariesYA3 dolly lock YADL1YA3 rotary handle standard length YA3R1

YA3 rotary handle long length YA3R2

Description Cat. no.

Adapter Kit AA Frame to YA3 FrameFor use when replacing existing AA frame with YA3 MCCBs.

Loadbank panel board 1 YAA1PLB

Loadbank panel board 3 YAA3PLB

Type 2 Loadframe switchboard 3 YAA3PLFT2

Description – for AA frame kit Poles Cat. no.

*Castell is a trademark of Castell Safety International Limited.

Note: Shunt trips, UVT, auxiliaries switches, alarm switches - see commonaccessories page 104.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 109/182

107

YA5 Frame MCCBs

• Exceeds EN60947-2 requirements• Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V AC (U i)• Electronic MCCBs are Category B rated for discrimination

• No extension terminal bars supplied, see ‘Accessories’ if required• Standard M10 cable lug termination = 95mm2

• Maximum cable termination = 185mm2 (using M10 reduced palm width lugs)

YA5 Switch Disconnector

400 YA5B3P400D YA5B4P400D

YA5 Frame MCCB Thermal/Magnetic – Icu 25kA

250 157 YA5N3P250T YA5N4P250T

400 252 YA5N3P400T YA5N4P400T

YA5 Frame MCCB Thermal/Magnetic – Icu 50kA

250 157 YA5H3P250T YA5H4P250T400 252 YA5H3P400T YA5H4P400T

YA5 Frame MCCB Thermal/Magnetic – Icu 65kA

250 157 YA5J3P250T YA5J4P250T

400 252 YA5J3P400T YA5J4P400T

YA5 Frame MCCB Electronic – Icu 70kA

250 125 YA5K3P250E YA5K4P250E

400 200 YA5K3P400E YA5K4P400E

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Circuit Protection DevicesLoadline YA5 Frame Moulded Case Circuit Breakers

Dimensions

YA5 3 and 4-pole

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 110/182

108

YA5 Frame MCCB Accessories

Cable clamps

YA5 cable clamps (set of 3) YA5CC3P

YA5 cable clamps (set of 4) YA5CC4P

Terminals and protection

YA5 3-pole terminal shroud YA5TS3P

YA5 4-pole terminal shroud YA5TS4P

YA5 terminal barrier YA5TB

YA5 3-pole terminal cover YA5TC3P

YA5 4-pole terminal cover YA5TC4P

YA5 3-pole rear terminals YA5RT3P

YA5 4-pole rear terminals YA5RT4P

YA5 3-pole extension terminals YA5XT3P

YA5 4-pole extension terminals YA5XT4P

Plug-in units

YA5 3-pole plug-in terminals YA5PT3P

YA5 4-pole plug-in terminals YA5PT4PYA5 3-pole plug-in base YA5PB3P

YA5 4-pole plug-in base YA5PB4P

YA5 3-pole plug-in base extension terminals YA5PXT3P

YA5 4-pole plug-in base extension terminals YA5PXT4P

YA5 3-pole right angle terminals YA5PRA3P

YA5 4-pole right angle terminals YA5PRA4P

Motors and interlocks

YA5 motor actuator, 100-110V ac YA5MA110

YA5 motor actuator, 200-240V ac YA5MA240

YA5 mechanical changeover, link type YA5ML

YA5 mechanical changeover, manual slide type YA5MMS

YA5 mechanical changeover, wire type with 1 metre cable YA5MW10

YA5 mechanical changeover, wire type with 1.5 metre cable YA5MW15

Auxiliaries

YA5 dolly lock YA5DL

YA5 neutral link YA5NL

YA5 rotary handle standard length YA5R1

YA5 rotary handle long length YA5R2

Description Cat. no.

Note: Shunt trips, UVT and auxiliaries - see common accessories page 104.

Circuit Protection DevicesLoadline YA5 Frame Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 111/182

109

Circuit Protection DevicesLoadline Y6 Frame Moulded Case Circuit Breakers

Y6 Frame MCCBs

• Exceeds the requirements of EN 60947-2• Rated insulation voltage 690V AC (U i)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination

• Standard M12 cable termination = 240mm2

• Extension terminal bars to be ordered separately when not used in conjunctionwith Dorman Smith steel work - Y6XT4P (2 required)

Y6 Frame Switch Disconnector630 Y6B3P630D Y6B4P630D

800 Y6B3P800D Y6B4P800DY6 Frame MCCB Thermal/Magnetic – Icu 50kA

400 250 Y6H3P400T5 Y6H4P400T5

630 400 Y6H3P630T5 Y6H4P630T5

800 500 Y6H3P800T5 Y6H4P800T5

Y6 Frame MCCB Thermal/Magnetic – Icu 85kA

400 250 Y6K3P400T5 Y6K4P400T5

630 400 Y6K3P630T5 Y6K4P630T5

800 500 Y6K3P800T5 Y6K4P800T5

Y6 Frame MCCB Electronic – Icu 50kA

630 315 Y6H3P630E Y6H4P630E

800 400 Y6H3P800E Y6H4P800E

Y6 Frame MCCB Electronic – Icu 65kA

630 315 Y6J3P630E Y6J4P630E

800 400 Y6J3P800E Y6J4P800E

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Dimensions

Y6

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 112/182

110

Terminal covers 3-pole

Terminal shroud (set of 1) Y6TS3P

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Terminal shroud (set of 1) Y6TS4P

Interphase barriers (set of 3) Y5TB4P

Terminations 3/4-pole

Cable clamps 2 x 185mm2 only Y6CC4P

Locking devices

Dolly padlock device Y6DL

Castell* lock (DS1 direct mounting) Y6CLDS1

Castell* lock (DS2 direct mounting) Y6CLDS2

Castell* lock door-mounted cam for shaft only Y5DCLCAM

Shunt trips

Shunt 24V dc Y6ST24DC

Shunt 100-115V ac Y6ST115AC

Shunt 200-480V ac Y6ST480ACUndervoltage release

UVR 24V dc Y6UVR24DC

UVR 100-120V ac Y6UVR120AC

UVR 200-240V ac Y6UVR240AC

UVR 380-450V ac Y6UVR450AC

Motors and interlocks

Motor actuator, 100-110V ac Y6MA110

Motor actuator, 200-240V ac Y6MA240

Changeover, rocker type Y6MR

Changeover, manual slide type Y6MMS

Changeover, wire type with 1 metre cable Y6MW10

Changeover, wire type with 1.5 metre cable Y6MW15

Auxiliary switches

1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Neutral link

Y6 Neutral link Y6NL

Rotary handles

Standard length Y6RH1

Long length Y6RH2

Cover flange Y5CF

Handle extension Y6HE

Description Cat. no.

*Castell is a trademark of Castell Safety International Limited.

Circuit Protection DevicesLoadline Y6 Frame Accessories

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 113/182

111

Circuit Protection DevicesLoadline Y6 Frame Moulded Case Circuit Breakers

Changeover UnitsThe changeover pairs are four-pole units fitted with mechanical and electricalinterlocking mounted on a back plate. Both devices have a motor actuator and areterminated for front access. All changeover pairs utilise the Y6 range of breakers.Each breaker is fitted with:

1 - Shunt trip 240V AC - Electrical interlock1 - AB auxiliary switch - to indicate MCCB status1 - Alarm switch - for auto reset1 - Motor operator spring charged 240V AC - to drive MCCB1 - Mechanical interlock (rear)

400A Y6AC400

630A Y6AC630

800A Y6AC800

Rating (A) Cat. no.

Remote Operation

Changeover Unit Dimensions (mm)

Y Frame Changeover Unit

Remote Operation

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 114/182

112

Circuit Protection DevicesLoadline Y7 Frame Moulded Case Circuit Breakers

Y7 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y7TS3P

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Terminal shroud (set of 1) Y7TS4P

Interphase barriers (set of 3) Y5TB4P

Locking devices

Dolly padlock device Y7DL

Castell* lock (DS1 direct mounting) Y7CLDS1

Castell* lock (DS2 direct mounting) Y7CLDS2

Castell* lock door-mounted cam for shaft only Y5DCLCAM

Shunt trips

Shunt 100-120V AC Y7ST115AC

Shunt 200-480V AC Y7ST480AC

Shunt 24V DC Y7ST24DC

Under-voltage releaseUVR 100-120V AC Y7UVR120AC

UVR 200-240V AC Y7UVR240AC

UVR 380-450V AC Y7UVR450AC

UVR 24V DC Y7UVR24DC

Motor actuators

Motor actuator 100-110V AC Y7MA110

Motor actuator 200-240V AC Y7MA240

Auxiliary switches 3-pole MCCB

1AB auxiliary switch Y7AUX3P1

2AB auxiliary switch Y7AUX3P2

Alarm switch + 1 auxiliary Y7AUX3PAL

Auxiliary switches 4-pole MCCB

1AB auxiliary switch Y7AUX4P1

2AB auxiliary switch Y7AUX4P2

Alarm switch + 1 auxiliary Y7AUX4PALNeutral link

Y7 neutral link Y7NL

Description Cat. no.

Y7 Frame MCCBs

• Exceeds EN 60947-2 requirements• Rated insulation voltage 690V AC (U i)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination

Y7 Frame Switch Disconnector

1250 Y7B3P1250D Y7B4P1250DY7 Frame MCCB Electronic – Icu 65kA

1000 500 Y7J3P1000E Y7J4P1000E

1250 630 Y7J3P1250E Y7J4P1250E

*Castell is a trademark of Castell Safety International Limited.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Dimensions

Y7

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 115/182

113

Circuit Protection DevicesLoadline Y8 Frame Moulded Case Circuit Breakers

Y8 Frame MCCBs

• Exceeds EN 60947-2 requirements• Rated insulation voltage 690V AC (U i)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination

Y8 Frame Switch Disconnectors1600 Front terminals Y8B3P1600D Y8B4P1600D1600 Rear terminals Y8B3P1600DR -1600 Draw out Y8B3P1600DDO -Y8 Frame MCCB Electronic – Icu 85kA

1600 Front terminals Y8K3P1600E Y8K4P1600E1600 Rear terminals Y8K3P1600ER N/A1600 Ground fault Y8K3P1600EG N/A

Current rating (A) Type 3-pole cat. no. 4-pole cat. no.

Y8 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y7TS3PInterphase barriers (set of 2) Y5TB3PTerminal covers 4-poleTerminal shroud (set of 1) Y7TS4PInterphase barriers (set of 3) Y5TB4PLocking devicesDolly padlock device Y7DLCastell* lock (DS1 direct mounting) Y7CL

Castell* lock (DS2 direct mounting) Y7CLDS2Castell* lock door-mounted cam for shaft only Y5DCLCAMShunt tripsShunt 100-120V AC Y7ST115ACShunt 200-480V AC Y7ST480AC

Shunt 24V DC Y7ST24DCUnder-voltage releaseUVR 100-120V AC Y7UVR120ACUVR 200-240V AC Y7UVR240ACUVR 380-450V AC Y7UVR450ACUVR 24V DC Y7UVR24DCMotor actuatorsMotor actuator 100-110V AC Y7MA110Motor actuator 200-240V AC Y7MA240Auxiliary switches 3-pole MCCB1AB auxiliary switch Y7AUX3P12AB auxiliary switch Y7AUX3P2Alarm switch + 1 auxiliary Y7AUX3PALAuxiliary switches 4-pole MCCB1AB auxiliary switch Y7AUX4P12AB auxiliary switch Y7AUX4P2

Alarm switch + 1 auxiliary Y7AUX4PALNeutral linkY7 neutral link Y7NL

Description Cat. no.

*Castell is a trademark of Castell Safety International Limited.

Dimensions

Y8

Mounting hole

Conductoroverlapmax.

o13

Extension handle(removable)

Insulator

Mounting angle

M8 Mounting screw

Mounting angle

ø970

4P

3P

HL

1 8 4

1 5 m a x

1 5 m a x

1 5 4

1 7 0

1 4 0

3 7 0

1 0 0

1 0 0

3 0

188

20

17

80 191

20 11

28

46

140

70

105

280

175

70 70

210

70 70

45

2 0

3 2

1 5

2 0 0

1 7

0

4P3P HL HL

ASLASL ASL

N

o12

3 0

6 5 1 0 0

6 0

70

85

115

130

15

15

MIN EARTHED BOUNDARY MIN EARTHED BOUNDARY

7 0 . 0

0

4 0 . 0

0

30.00 30.00

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 116/182

114

Circuit Protection DevicesLoadmaster Miniature Circuit Breakers

10 LM10 -

20 LM20 LM3P2030 LM30 LM3P30

40 LM40 -

50 - -

60 LM60 -

Current rating (A) 1-pole cat. no. 3-pole cat. no.

Loadmaster MCBs

100 - LW3

Current rating (A) 1-pole cat. no. 3-pole cat. no.

Loadmaster Isolators

Loadmaster Accessories

Mounting bracket for MCB/isolator 2-pole LMMB2

Mounting bracket for MCB/isolator 3-pole LMMB3

Description Cat. no.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 117/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 118/182

116

Modular DevicesDSPE Range Surge Protector Series

DSPE 600 Series• Low “let through” voltage of 600 volts• Two stage (redundant) protection, with pre-failure indication• Site fault condition indicator• Remote Monitoring Unit is provided with a 1 metre cable and appropriate plug

and socket connectors (other lengths are available on request)• Easy installation and field serviceability• Compact size and small footprint

Dimensions

70,00

1 6 5

, 0 0

10,00

1 7 7

, 0 0

1 8 6

, 5 0

Specification and Dimensions

Voltage rating (Nominal), Un 400V rms

Max. continuous operating voltage, Uc L-N 300V rms

L-L 500V rms

Maximum load current rating Unlimited (parallel connection)

Maximum surge current (8/20µs), Imax 30kA per phase

Response time <10 ns

Power consumption (nominal) 18mA per phase

Leakage current to earth 600µA

Terminals 16mm2 max - line, neutral, earth

2.5mm2 max - remote signalling

Remote signalling terminals Rated at 230V rms 0.2A or30V DC 2A

Operating temperature -40° to +70° Celsius

Light emitting diodes status indication Green: full protection

Red & green: reduced protection

Red - no protection

Case Steel - epoxy paint

Type (EN 61643-11) 2

Dimensions (mm) L 176

W 110

D 72

Weight (g) 1110

DSPM Surge Protectors Cat. no.

30kA 2-stage, 3-pole surge protector DSPE60030kA 2-stage, 3-pole surge protector, remote terms & monitoring DSPE600R30kA 2-stage, 3-pole surge protector with aux contact DSPE600NEnclosure for DSP3 surge protection units 2IP-7-0244(240mm (h) x 190mm (w) x 90mm (d))

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 119/182

117

Modular DevicesDSPT Range Surge Protector Type 1

DSPT Type 1• Class 1; Type I device• Tested to withstand 10/350µs waveforms

Dimensions

Specification and Dimensions

Max. continuous operating voltage (Uc) 275V ac rms

Temporary overvoltage (Ut), L-N 335V/5s

Temporary overvoltage (Ut), N-PE 1200V/0.2s

Response time L-N <25ns

Response time N-PE <100ns

Max. backup fuse 315A gL/gG

Max. backup fuse when ‘V’ connected 63A gL/gG

Short-circuit withstand capability 80ka rmsat max backup fuse (Ip)

Lightning impulse current, 25kA10/350µs, L-N (Iimp)

- Charge (Q) 12.5As

- Specific energy (W/R) 156kJ/Ω

Lightning impulse current, 100kA10/350µs, N-PE (Iimp)

- Charge (Q) 50As

- Specific energy (W/R) 2500kJ/Ω

Total lightning current, 10/350µs 100kA(Itotal), L1,L2,L3,N-PE

Max. discharge current, 8/20µs (Imax), L-N 120kA

Max. discharge current, 8/20µs (Imax), N-PE 120kA

Nominal discharge current, 8/20µs (In) 50kAVoltage protection level at Iimp (Up) <1.3kV

Weight (g) 1125

Description Cat. no.

3-phase & neutral, 25kA L-N, 100kA surge protector DSPT3PN

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 120/182

118

Modular DevicesSwitch Disconnectors, Timers, Modular Contactors

63 2 50 AV26363 3 50 AV36363 4 50 AV463100 2 50 AV2100100 3 50 AV3100100 4 50 AV4100125 2 50 AV2125125 3 50 AV3125125 4 50 AV4125

Current rating (A) Poles Max. cable (mm) Cat. no.

• Exceeds the requirements of EN 60947-3• 50mm2 cable capacity• Duty category of AC22

Modular Contactors• Exceeds the requirements of EN 61095• May require de-rating when used with inductive loads

– see Contactor De-rating table in the Technical Applications section

Modular Programmable Timers• Daily/weekly• 2 relays• 16A

16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Current rating (A) Width (mm) Function Cat. no.

20A 17.5 2P N/O EE2P20CO20A 35 2P N/C EE2P20CC25A 35 4P N/O EE4P25CO25A 35 4P N/C EE4P25CC40A 54 4P N/O EE4P40CO40A 54 4P N/C EE4P40CC63A 54 4P N/O EE4P63CO63A 54 4P N/C EE4P63CCVenting kit * 9 - LLMV

Current rating (A) Width (mm) Contacts Cat. no.

* Ventilation module must be fitted between alternate pairs of contactorsto prevent overheating.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 121/182

Modular DevicesCurrent Transformers

Measuring Current Transformers• For use with kilowatt hour metering• Up to Class 0.5 accuracy• System voltage up to 720V• Secondary output 5A

• Operating temperatures from –20°C to +70°C

100 25 65 45 M53Q-100/5

125 25 65 45 M53Q-125/5

30 0.68 80 50 M55E-30/5

60 0.68 80 50 M55E-60-5

100 25 80 50 M53J-100/5D

125 25 80 50 M53J-125/5D

200 25 80 50 M53J-200/5D

250 25 80 50 M53J-250/5D

400 32 94 60 M63N-400/5

600 42 131 90 M93L-600/5

800 63 156 134 MB5D-800/5

Current Cable aperture Height Width Cat. no.

rating (A) (mm) (mm) (mm)

M30-DINCLIP DIN-rail mounting option for M63N/M93L current transformers(2 required)

M50-DINCLIP DIN-rail mounting option for MB5D current transformers(2 required)

Dimensions

M55EM53Q M53J

M63NMBD5 M93L

119

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 122/182

M3N1-25 M3N1-45

Dimensions

M3N1-35

3-in-1 Current Transformers• For use with metering• Space saving 3-in-1 design• Up to 5A class• Secondary output 5A

• Plug-in metal feet, DIN-rail clips and busbar mounting options supplied as standard

Part number Ratio Burden VA against Aperture

class index (mm)

Class Class Class

0.5 1 3

M3N1-25-60/5 60/5 - 1 2 3@15 x 25mm

M3N1-25-100/5 100/5 - 1.5 2.5 3@15 x 25mm

M3N1-25-125/5 125/5 - 1.5 2.5 3@15 x 25mm

M3N1-25-160/5 160/5 1.5 1.5 2.5 3@15 x 25mm

Part number Ratio Burden VA against Aperture

class index (mm)

Class Class Class

0.5 1 3

M3N1-35-100/5 100/5 - 1.5 2 3@21 x 25mm

M3N1-35-125/5 125/5 - 1.5 2.5 3@21 x 25mm

M3N1-35-160/5 160/5 1.5 1.5 2.5 3@21 x 25mm

M3N1-35-200/5 200/5 1.5 1.5 2.5 3@21 x 25mm

M3N1-35-250/5 250/5 1.5 1.5 2.5 3@21 x 25mm

Part number Ratio Burden VA against Aperture

class index (mm)Class Class Class

0.5 1 3

M3N1-45-250/5 250/5 1.5 1.5 2.5 3@31 x 31mm

M3N1-45-300/5 300/5 2.5 2.5 3.75 3@31 x 31mm

M3N1-45-400/5 400/5 2.5 2.5 3.75 3@31 x 31mm

M3N1-45-500/5 500/5 2.5 2.5 3.75 3@31 x 31mm

M3N1-45-630/5 630/5 2.5 2.5 3.75 3@31 x 31mm

Modular Devices3-in-1 Current Transformers

120

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 123/182

121

A range of split core current transformers that offers a costeffective and efficient method by which the current can bemeasured without the need to break the conductor, therebyreducing installation and commissioning time.

Accuracy Class

Dimension Case 1 Case 2 Case 3 Case 4

A 20 50 80 80

B 30 80 80 120

C 51 78 108 108

D 89 114 144 144

E 111 145 145 185

F 34 32 32 32G 47 32 32 32

H 40 32 32 32

I 32 33 33 33

Weight (Kg) 0.75 0.90 1.05 1.25

Units of measurement – mm

Part number Ratio Burden VA against class index Aperture

(mm)

0.5 1 3

SC1-100/5A 100/5A - - 1.5 20 x 30

SC1-150/5A 150/5A - - 2 20 x 30

SC1-200/5A 200/5A - 1.5 2.5 20 x 30

SC1-250/5A 250/5A - 2 4 20 x 30

SC1-300/5A 300/5A 1.5 4 6 20 x 30

SC1-400/5A 400/5A 2.5 6 10 20 x 30

SC2-250/5A 250/5A 1 2 4 50 x 80

SC2-300/5A 300/5A 1.5 3 6 50 x 80

SC2-400/5A 400/5A 1.5 3 10 50 x 80SC3-250/5A 250/5A 1 2 4 80 x 80

SC3-300/5A 300/5A 1.5 3 6 80 x 80

SC3-400/5A 400/5A 1.5 3 10 80 x 80

SC3-500/5A 500/5A 2.5 5 15 80 x 80

SC3-600/5A 600/5A 2.5 5 15 80 x 80

SC3-750/5A 750/5A 3 6 20 80 x 80

SC3-800/5A 800/5A 3 7.5 20 80 x 80

SC3-1000/5A 1000/5A 5 10 20 80 x 80

SC4-500/5A 500/5A - 4 12.5 80 x 120

SC4-600/5A 600/5A - 5 15 80 x 120

SC4-750/5A 750/5A 2.5 6 17.5 80 x 120

SC4-800/5A 800/5A 3 7.5 20 80 x 120

SC4-1000/5A 1000/5A 5 10 20 80 x 120

SC4-1200/5A 1200/5A 6 12.5 25 80 x 120

SC4-1250/5A 1250/5A 7.5 15 30 80 x 120

SC4-1500/5A 1500/5A 8 17 30 80 x 120

SC4-1600/5A 1600/5A 8 17 30 80 x 120

C a s e 1

C

a s e 2

C a s e 3

C a

s e 4

Modular DevicesSplit Core Current Transformers

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 124/182

122

• Precision digital protection relay• Adjustable sensitivity of 30mA to 10A• Adjustable time delay from 0 to 10 seconds• Double-pole relay contacts 8A, 250V• Supply voltage 100-250V AC/DC (50/100Hz)

50 100-250 AC/DC ELR1

Frequency (Hz) Auxiliary supply (V) Cat. no.

Earth Leakage RelayDIN-rail Mounted

110.0mm 4.32"

73.0mm 2.87"

33.0mm 1.3"

48.0mm 1.89"

71.0mm

2.79"

6 2 . 5 m m

2 . 4

6 "

9 0 . 5 m m

3 . 5

6 "

4 6 . 0 m m

1 . 8 7 "

Remoteresetswitch

FusedAuxiliarysupply

The equipment groundingconductor must bypass the CT

CommissioningMeter

Link to energiseon trip

GND

Relay 1 Relay 2

Connections

Specification

Measuring input From core balanced current transformer

Overload 20 x nominal for 1 second

Frequency 50Hz or 60Hz ±10%

Auxiliary voltage 100-250V ac and dc

Auxiliary burden Less than 1.5 Watts

Trip current settings Selectable 30mA, 100mA, 200mA, 300mA, 500mA,

1A, 2A, 3A, 5A, 10ATrip accuracy 50% <trip point current

<100% in accordance with IEC 1543

Trip response time <40ms (at 5 x rated trip current, ignoring theselected time delay)

Time delay set points Selectable 0ms, 50ms, 100ms, 150ms, 200ms,300ms, 400ms, 500ms, 600ms, 700ms, 800ms,900ms, 1 second, 2 seconds, 5 seconds, 10 seconds.When 30mA leakage is selected, the time delay isdisabled

Indication 5 yellow LED bar graph for leakage levelsRed LED indicated trip functionGreen LED indicated auxiliary power presenceRed LED pre-alarm indication (SPCO version only)

Relay contacts Standard: 2-pole change over

Option: 2 1-pole change over (pre-alarm andmain alarm)

Relay contact rating 8 amps at 250V ac8 amps at 30V dc resistive

Relay mechanical life >100,000 operations

Analogue output 0 to 1mA = 0 to 100% of selected tripping level.Compliance 1V, accuracy 10%

Enclosure style DIN 43880, rail width 70mm

Compliant with EMC and LVD, UL 3111-1 File No: E203000, CSA22.2/1010.1-92 BSEN 50081-1, BSEN 50082-2, IEC60255-22-1 (BS5992), IEC 60255-11, BSEN 61543 (IEC1543), BSEN 61010 (IEC 1010), EN 60068 (IEC 68)

Material Flame retardant UL94V0

Terminals 1 to 4mm2 solid or stranded conductors.IP20 protection

Operating temperature –10°C to +60°C

Storage temperature –20°C to +70°C

Relative humidity <95% non condensing

Weight <250g

Dimensions 71mm wide x 90.5mm high x 73mm deep 2.79" widex 3.56" high x 2.87" deep

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 125/182

123

Modular DevicesCore Balance Current Transformers

Core Balanced Current Transformers• For use with ELR1 earth leakage protection relay• Leakage measurement range 0 to 10A• Integral wire-sealable terminal cover• Flame retardant, high impact moulded case

250 35 100 79 26 48.5 CBT-94F-035

630 70 130 110 32 66 CBT-94F-070

1000 105 170 146 38 94 CBT-94F-105

1000 140 220 196 49 123 CBT-94F-140

Current Dim E Dim A Dim B Dim C Dim D Cat. no.rating Aperture Width Height Depth(A) (mm) (mm) (mm) (mm)

Specification

System voltage 720V maximum

Test voltage 3kV ac for 1 minute

System frequency 50Hz or 60Hz

Primary ratings From 30mA to 10A

Secondary terminals Protected to IP20

Operating temperature –10°C to +50°C

Enclosure UL94V0 flame retardant plastic

Compliant with IEC185, VDE 0414

Mounting hardware Steel mounting feet for wall or base mounting

A

ø E B

33

DC

4 6

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 126/182

124

Modular DevicesIntegra Ci1 Energy Meter

The Integra Ci1 energy meter is specially designed and developedas a cost effective Watt hour and VAr hour meter to complementthe current Integra Ci digital metering system (dms). The IntegraCi1 self-contained 96mm DIN panel mounted Watt hour, VAr hour

meter measures the real consumption of active and reactiveenergy to Class 1.0 accuracy.

The backlit LCD screen displays 8 character counter indicating Watt hour or VArhour units. The optional modules enables transfer of energy measurements tobuilding management systems (BMS) via pulsed or digital communication options.

Programmable FunctionsIntegra Ci1 meter provides simple programming to suit single phase 2-wire, three-phase three wire and three-phase four-wire un-balanced system configurations,CT ratio settings and configuration of selected communication options. To preventunauthorised access to the product configuration settings, all set-up screensoffer password protection.

DisplayDirect access to display the programmed set CT ratio, Watt hours import andexport, VAr hours import and export and the phase sequence test routine for bothvoltage and current phases. During the accumulation of the Wh or VArh therunning icon will flash at a rate dependant on the displayed parameter.

Plug-in ModulesPlug-in modules allow to fit either maximum of two isolated pulsed output relaysor a RS485 communication module and one isolated pulsed output relay. Thecommunication output module can be programmed internally to respond either toModbus® RTU or Johnson Controls protocols.

Panel MountingIntegral retention clips allow fast, safe and secure panel mounting in variousmaterial thicknesses without the need for external screws or clips.

Description Part number

Integra Ci1 base unit with pulse output CI1-01-PUL

Options

Optional plug-in pulse output module CI-PUL-01

Optional RS485 Modbus plug-in module CI-MOD-01

Accessories

IP65 protective cover 3G36502

IP54 panel gasket 3C34501

Product Code

Parameters

Button Screen Parameters

CT 1 CT ratio

Wh 2 IMPORT Wh3 EXPORT Wh

VArh 4 IMPORT VArh5 EXPORT VArh

TEST 6 Phase sequencediagnostic

Running icon indicates Whand VAhr accumulation.

53.00

77.50

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 127/182

125

The Integra Ci3 digital metering system (dms) represents the firstmodel of a new generation of digital metering systems designedto complement the current Crompton Instruments Integra series.

The Integra Ci3 meter is an accurate and cost effective solutionfor measurement and display of all major electrical and powerquality parameters.

Designed, developed and manufactured in the UK, the Integra Ci3dms builds on Crompton Instruments’ long established reputationfor metering product quality.

The product features a DIN 96 panel mounted enclosure, backlit LCD screen anduser programmable CT ratios, all accessible via an intuitive user interface. IntegraCi3 dms measures 17 electrical parameters including total harmonic distortion(THD) up to the 31st harmonic.

Programmable FunctionsIntegra Ci3 dms is programmable to suit single-phase two-wire, three-phasethree-wire and three-phase four-wire system configurations. Programmable CTratios enable to display any current range.

DisplayThe parameters can be viewed on a backlit LCD screen. The 15 screens areaccessible via four buttons on the front panel allowing to scroll between variousscreens making the navigation very user-friendly, intuitive and above all – simple.

Plug-in ModulesIntegra Ci3 dms offers two output ports at the rear of the product, to allow thefitting of either two isolated pulsed output relays or a RS485 communicationmodule such as Modbus® or Johnson Controls communication output. These areconfigurable via internal settings.

Panel MountingIntegral retention clips allow fast, safe and secure panel mounting in variousmaterial thicknesses without the need for external screws or clips.

Description Part number

Integra Ci3 base unit with pulse output CI3-01-PUL

Options

Optional plug-in pulse output module CI-PUL-01

Optional RS485 Modbus plug-in module CI-MOD-01

AccessoriesIP65 protective cover 3 G365 02IP54 panel gasket 3 C345 01

Product Code

Modular DevicesIntegra Ci3 Digital Metering System

Parameters

Button Screen Parameters

V/Hz 1 Volts L1 - N

Volts L2 - NVolts L3 - N

2 Volts L1 - L2

Volts L2 - L3Volts L3 - L1

3 Frequency4 Volts L1 - N THD%

Volts L2 - N THD%

Volts L3 - N THD%5 Volts L1 - L2 THD%

Volts L2 - L3 THD%Volts L3 - L1 THD%

A 1 Current L1Current L2Current L3

2 Neutral current3 L1 Current max

DemandL2 Current maxDemand

L3 Current maxDemand

4 Neutral current maxdemand

5 Current L1 THD%Current L2 THD%

Current L3 THD%

P/PF 1 kW

kVArkVA

2 kW Max demand3 Power factor

E 1 kWh2 kVArh

53.00

77.50

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 128/182

126

Modular DevicesIntegra 1630 Digital Metering System

Multi-function Integra 1630 digital metering system provides highaccuracy 0.2% measurement, display and communication of allmajor electrical and power quality parameters including totalharmonic distortion (THD) up to the 31st harmonic. To suit user

requirements, the range includes single-phase, three-phasethree-wire and three-phase four-wire capability, all selectableat the point of installation.

Features• Auxiliaries: 100/250V ac/dc (12/48V dc optional)• Options: ProfibusTM, Modbus® TCP, Bacnet IP, RS485, Pulsed output

Product Description and Order Codes

Description Cat. no.

1-phase, 3-phase 3/4-wire, INT-1630-M-5-M-option241-480V L-L, 5A CT input, Aux.

100-250V ac/dcOptions

No options 000

1 pulsed output 100

RS485 interface Modbus® + 1101kWhr pulsed output

Extended collar OPT-1630-collar

Dimensions

Modbus®, ProfibusTM and Bacnet aretrademarks

Measured Parameters

• System (average) voltsSystem (average) current

System (total) kW• System volts (average) THD%

System current (average) THD%• Phase – neutral

Voltage (VL-N)(4 wire only)Phase – phaseVoltage (L-L)(3 wire only)

• Voltage THD%(4 wire only)

• Phase current• Current THD %

• Neutral current

(4 wire only)FrequencyPower factor (overall)

• kVAr kVA kW• kWh import (7-digit resolution)

• kVArh import (7-digit resolution)• kWh export (7-digit resolution)• kVArh export (7-digit resolution)• kW demand

Current demand

• Maximum kW demandMaximum current demand

• Hours run

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 129/182

DRK-3PCT-400-D90

127

Self-contained energy metering system which is ideal forswitchgear, plant instrumentation and process control. The rangehas significant advantages over the traditional energy meters withpulsed outputs, communications and direct connection all

available as options.

Single-phase: 230V – CT Connected 5A

1-phase CT 5A – pulse output DRK-1PCT-240Pulsed output (Opto),Mechanical counter

Three-phase: 400V (+N) CT Connected 5A

3-phase 3 or 4-wire system, DRK-3PCT-4155A CT connected, pulsed output(Opto), mechanical counter

3-phase 3 or 4-wire system, DRK-3PCT-415-LCD5A CT connected, pulsed output(Opto), LCD screen

Single-phase: 230V – Direct Connected 63A

1-phase 230V–63A direct DRK-1P-230-D63connected, pulsed output (Opto)LCD screen

Three-phase: 230V (400V) – Direct Connected 100A

3-phase 230V L-N (400V L-L) DRK-3P-400-D100– 100A direct connected,

pulsed output (Opto), LCD screen

Description Cat. no.

Modular DevicesModular Devices Kilowatt Hour Energy Meters DIN-rail

Dimensions

DRK-1PCT-240 DRK-3PCT-415/ DRK-3PCT-415-LCD

DRK-1PCT-230-D63

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 130/182

128

Modular DevicesIntegra Ri3 Digital Metering System

The product features a DIN-rail enclosure, backlit LCD display anduser programmable CT ratios, all accessible via an intuitive userinterface. Integra Ri3 dms measures 17 electrical parametersincluding total harmonic distortion (THD) measurement up to the

31st harmonic.

Specifications

InputNominal input voltage 100-289V AC L-N (173-500V AC L-L)Max. continuous input 120% of nominaloverload voltageMax. short duration input voltage 2 x range maximum (1 second application

repeated 5 times at 5 minute intervals)Nominal input voltage burden < 0.2VA per phaseNominal input current 5A AC rmsMax. continuous input 120% of nominaloverload currentMax. short duration input current 10 x nominal (1 second application repeated

5 times at 5 minute intervals)

Nominal input current burden < 0.6VA per phaseFrequency 45-66HzSystem CT primary values 1 to 9999AuxiliaryOperating range 110-400V AC nominal +/-10% (99-440V AC

absolute limits) or 120-350V DC +/-20%(96-420V DC absolute limits)

Burden < 10VA/5WAccuracyVoltage (V) 0.5%Current (A) 0.5%Neutral current calculated (A) 4%Frequency (Hz) 0.1 HzPower factor (PF) 1% of unityActive power (W) +/- 1% of rangeReactive power (VAr) +/- 1% of rangeApparent power (VA) +/- 1% of range

Active energy (kWh) Class 1 (IEC 62053-21)Reactive energy (kVArh) +/- 1% of rangeTHD 1% up to 31st harmonicResponse time 1secOutputPulse output relay 1Contact rating 50mA max at 250V ACType Solid state relayRS485 Modbus output module 1 Modbus channelType 2-wire half duplexBaud rate 2400, 4800, 9600, 19200, 38400EnclosureEnclosure style DIN-railDimensions 72x90mm (width x height) as per

DIN 43880Front protection rating IP52Case protection rating IP30Material Polycarbonate to UL94V0

Weight 300gTerminals Shrouded screw-clamp 0.05-4mm wireEnvironmentOperating temperature -10°C to +55°CStorage temperature -20°C to +70°CRelative humidity 0-90% non-condensingShock 30g in 3 planesVibration 10Hz to 50HzDielectric voltage Withstand test 3.25kV rms 50Hz for 1

minute between comms and measuringinputs, comm and aux, aux and measuringinputs

Features

• DIN-rail enclosure DIN 43880• Backlit LCD screen

• Programmable CT ratio

• True rms measurement

• User programmablesystem configuration

• Pulsed output and Modbusas standard

Benefits

• Cost effective

• Simple navigation

• Crompton renowned quality

• UK manufactured

48.30

62.00

4 5 . 0

0

6 2 . 0

0

3 5 . 0

0

32.40

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 131/182

8Section

MCB and MCCB General

Purpose Enclosures

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 132/182

General Purpose Enclosures

Sheet steel 1 6 225x134x73 1.0 LLMGPS6S

Insulated, IP4X 2 2 130x50x60 0.1 LLMGPI2

Insulated, IP4X 4 130x86x60 0.2 LLMGPI4

Insulated, IP4X 3 8 162x214x92 0.6 LLMGPI8

Insulated, IP55 5 175x125x115 0.5 LLMGPW5

Insulated, IP55 4 8 175x214x115 0.8 LLMGPW8

Construction Picture Number HxWxD Weight Cat. no.

of ways (mm) (kg)

General Purpose MCB/Modular Units Enclosures

Sheet steel - surface YA3 687x263x120 16 LLGPYA3

Construction Device HxWxD Weight Cat. no.

type (mm) (kg)

General Purpose MCCB Enclosures 16-250A• Accepts all YA3 devices up-to 250A (as per page 107)• IP4X rated

• Spreading room for 150mm2

Note: LLGPYA3 requires neutral link YA3NL to be ordered separately.

Note: For terminating two parallel cables with YA5 frame please order extensionterminals (YA5XT3P) separately.

Sheet steel YA5/6 1060x420x175 16 LLGPYA56

Construction Device HxWxD Weight Cat. no.

type (mm) (kg)

General Purpose MCCB Enclosures 400A-800A• Accepts all YA5 & Y6 devices up-to 800A (pages 109 and 111)• IP4X• Neutral link included• Spreading room for 240mm2

1 2

3 4

130

Dimensions

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 133/182

9Section

Technical Data & Applications

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 134/182

132

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 135/182

133

Technical Data & Applications

Index

Compliance with International Standards 134

Standard Terminology 135

Current Carrying and Switching Devices 137

Miniature Circuit Breakers (MCBs) 140

Residual Current Circuit Breakers (RCCBs) 145

Modular Contactors 147

Moulded Case Circuit Breakers (MCCBs) 151

Motor Starting Applications (MCCBs) 152

Discrimination and Cascading 153

System Sizing and Diversity 160

Prospective Short-circuit Current 161

Earth Fault Protection including MCCB Max Zs 164

Forms of Separation 167

Ingress Protection 169

Loadline MCCB Insulation Data 170

Loadline YA2 Frame MCCB Characteristics 171

Loadline YA3 Frame MCCB Characteristics 172

Loadline YA5 and Y6 Frame MCCB Characteristics 173

Loadline Y7 and Y8 Frame MCCB Characteristics 174

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 136/182

134

Compliance with InternationalStandards

Dorman Smith branded products comply with internationally recognised technicaland quality standards to ensure that each product is fully capable of meeting therelevant standard requirements for its intended use.

The design, manufacture, procurement, supply and servicing of Dorman Smith

branded products is also governed by compliance to an international standardthrough the operation of a Quality Management System.

• Quality Management System BS EN ISO 9001:2008

The Institute of Electrical Engineers (IEE) British Standard BS 7671 addressesRequirements for Electrical Installations and dictates that all relevant products mustcomply with applicable British, International or Harmonised Standards according tothe intended installation and application of the equipment. The BS 7671 documentis commonly referred to as ‘The Wiring Regulations’.

Products are type tested, manufactured, routinely tested and assembled inaccordance and compliance with a number of relevant Harmonised Standardsrecognised by the electrical industry.

A Harmonised Standard is a European Standard formally presented by theEuropean Committee for Electrotechnical Standardisation, CENELEC, to theEuropean Commission and published in its official journal. These documents aredenoted by the prefix EN (European Norm).

The products listed within this catalogue conform to appropriate electrical andmechanical standards as follows:

• MCB Distribution Boards EN 60439-3• Panel Boards EN 61439-2• MCBs EN 60898• MCCBs EN 60947-2• Switches EN 60947-3• RCCBs EN 61008• RCBOs EN 61009• Contactors EN 61095

In addition to the above, and where appropriate, Dorman Smith branded productsalso comply with the relevant requirements of the standard for protection againstphysical, mechanical and liquid ingress as follows:

• Ingress Protection EN 60529

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 137/182

135

Standard Terminology

The Harmonised Standard EN 60898 and the IEE Wiring Regulations BS 7671:2008contain references to a set of adopted standard terminology for the principaldevice parameters with regard to MCBs. This terminology is also embraced byother standards with regard to MCCBs and switches (EN60947-2 and EN 60947-3).

The standard terminology relates to the following parameters:

Rated Operational Voltage, Ue

Rated Insulation Voltage, Ui

Rated Current, InRated Short Circuit Capacity, Icn

Rated Service Short Circuit Breaking Capacity, Ics

Rated Ultimate Breaking capacity, Icu

Rated Voltage and Current

Rated Operational Voltage, Ue

The nominal voltage of the system should not exceed the stated value of Ue.For example: single-pole Ue = 230/400V, three-pole Ue = 400V.

The standardised values of 230V and 230/400V will progressively replace 240V,220/380V and 240/415V.

Rated Insulation Voltage, Ui

This is the voltage upon which the dielectric properties are based, using tests athigh voltage and mains frequency.

Unless otherwise stated, the rated insulation voltage is the value of the maximumrated voltage of the circuit breaker.

In no case shall the maximum rated voltage exceed the rated insulation voltage.

Rated Current, InThis is the current that the circuit breaker will carry continuously under specifiedconditions and upon which the time/current characteristics are based.

Unless otherwise stated, this value is based upon a reference ambient temperatureof 30 degrees Celsius.

EN 60898 Standard refers to the following terms:

Short Circuit Capacity

Rated Short Circuit Capacity, Icn

The calculated prospective fault current at the incoming terminals of thecircuit breaker should not exceed the stated value. For example: Icn = 10kA(marked 10000).

Service Short Circuit Breaking Capacity, Ics

This value is the maximum level of fault current operation, after which furtherservice of the device is assured without loss of performance. Note that there is norequirement for Ics to be marked on the device.

There is a proscribed relationship between Ics and Icn, as follows:For values of Icn up to 6000A Ics = Icn

For values of Icn 6000A to 10000A Ics = 0.75Icn (but with a minimum value of Ics = 6000A)For values of Icn above 10000A Ics = 0.5Icn (but with a minimum value of Ics = 7500A)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 138/182

136

The EN 60947-2 and EN 60947-3 Standards also refer to the following terms.

Isolation SuitabilityThese define the requirements for the suitability of circuit breakers to performisolation duty by defining tests to which such units must comply. Conformingdevices must carry a standard symbol mark to show that they are suitable forisolation duty. For example, all Dorman Smith circuit breakers are so marked.

Utilisation CategoriesThe utilisation category of a circuit breaker is stated with reference to whetheror not it is specifically intended for discrimination by means of an intentional time

delay with respect to other circuit breakers in series on the load side undershort-circuit conditions.

Category AThis designates circuit breakers not specifically intended for selectivity with deviceson the load side. Circuit breakers will discriminate only up to certain fault levels,above which discrimination with devices on the load side cannot be guaranteed.

Category BThis designates circuit breakers specifically intended for selectivity with devices onthe load side. Such circuit breakers will incorporate some form of time delay.

EN 60947-2 recognises both a rated service and a rated ultimate short circuitbreaking capacity for both Category A and Category B circuit breakers.

Rated Service Breaking Capacity, Ics

In order to define this value, the circuit breakers under test must be subjected to atest sequence of:

Ics = o – t – co - t – co, where:o = opening time under fault conditionst = time interval before re-closing (not more than 3 minutes)c = closing operation on to a fault

After this test sequence, dielectric, terminal temperature and over-current tests areto be applied. The circuit breaker must meet certain test parameters to ensure thatthe device has not deteriorated in performance and can be put back into service.

Rated Ultimate Breaking capacity, Icu

In order to define this value, the circuit breakers under test must be subjected to a

test sequence of:

Icu = o – t– co.

After this test sequence, dielectric and over-current tests are to be applied.

The rated service breaking capacity (Ics) applies to short circuit faults that couldoccur in practice; whereas the ultimate short circuit capacity (Icu) is the maximumtheoretical fault value of the installation at the point of connection.

The standard defines the ratio between the two values. Ics will be shown as 25%,50%, 75% or 100% of its Icu value for Category A devices and 50%, 75% or 100% ofIcu for Category B devices.

A circuit breaker can remain in service after interrupting a short circuit up to its

rated value of Ics. However, where two or more faults occur between the Ics and Icuvalues, the capability of the device for continued operation must be verified.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 139/182

137

Current Carrying andSwitching Devices

SwitchA switch is a mechanical device capable of making, carrying and breaking currentunder normal circuit conditions.

Disconnector (Isolator)A disconnector is a mechanical switching device that provides the function ofcircuit isolation.

Switch DisconnectorThis device combines the functionality of the two foregoing devices; it providesmaking, carrying, breaking and isolation of current within a circuit.

FusesFuses can be combined with any of the above devices in any physical order. Theinclusion of a fuse will add the functionality of short circuit protection, breaking thecircuit when the current flow is higher than that for which the circuit is rated.

Combination DevicesIn order to enhance circuit protection, switches and fuses are often combined

within a single device. The physical composition of the device can be identified bythe literal position of the words in its description. For example, the word ‘fuse’ atthe beginning of the device description identifies the fuse as forming part of themoving contact system, whereas placing it at the end of the description identifiesthe fuse as a static link.

Functional Summary

Switch Current rating Isolation

Operational and insulation voltage Protection

Making and breaking of load

Short time current rating

Disconnector Current rating Protection

Isolation Making/breaking capability

Operational and insulation voltage

Short time current rating

Fuse Overload protection Switching

Short circuit protection

Term Features Features

provided not provided

Suitability for PurposeAll of these devices have the ability to carry rated current either continuously orfor a period of eight hours under defined conditions. Selection and specification ofa specific device depends upon the circuit application.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 140/182

138

Function

Fuse Combination Unit

Switching ApplicationsFor switching applications, the principal functions and capabilities include:

• Making and breaking operation

A switch must have the ability to make or break defined load and overloadcurrents at a rated operational voltage, for the useful life of the device.

• Short circuit action

The device must have the capability of handling short circuit current and/orthrough fault and/or fault making.

• Protection

The device must interrupt the circuit under overload and/or short circuitconditions.

• Isolation

To meet this requirement, the device must ensure disconnection of the supply forsafe downstream working. Facilities must be included for safety padlocking in the‘off’ position, together with positive indication of the contact position.

• Neutral switching

Where the neutral is reliably earthed, it is accepted that the neutral need not beswitched except in defined circumstances (e.g. the incoming switch disconnectorin a consumer unit) even though the Wiring Regulations (BS 7671:2008) class theneutral as a current carrying conductor.

In applications where the neutral cannot be confirmed as reliably earthed, the

neutral should be switched simultaneously with the phase(s) or alternativelyarranged to make before and break after the phase(s).

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 141/182

139

Utilisation CategoryThe utilisation category defines the basic circuit conditions and the switchingcapability of the device.

AC20/DC20 Connecting and disconnecting under ‘no load’.

Assumes all switching operations are carried out by othercapable devices before this device is operated.

AC21/DC21 Switching of resistive loads including moderate overloads. Suitable for purely resistive type loads.

Device can switch 150% of its rated current underfault conditions.

AC22/DC22 Switching of mixed resistive/inductive loads, including moderate overloads.

Suitable for mixed resistive/inductive loads.

Device can switch 300% of its rated current underfault conditions.

AC23/DC23 Switching of highly inductive loads.

These devices are provided principally as back-up to othermeans of switching, e.g. contactors. In the event of failure ofthe functional device, the AC23/DC23 device can safelyinterrupt a stalled motor current. Where devices are the

only means of controlling individual motors they shouldcomply with the requirements of Appendix A of theEN 60947-3 standard.

Category Circuit/application

Note: Switch disconnectors for AC21/DC21, AC22/DC22 and AC23/DC23 categoriesalso have to meet the requirements of AC20/DC20.

For specific and special applications such as switching of capacitors and tungstenlamps not covered by the EN 60947-3 standard, the manufacturer’s advice shouldbe sought.

Frequent and Infrequent UseThe designation ‘A’ or ‘B’ should be appended to utilisation categories to indicatethe suitability for frequent or infrequent use in service. The ‘Rule of Thumb’definition for full load current switching duty is:

Frequent (A): Up to five times a day for small devices, say up to 100 amps, andonce per week for larger devices.

Infrequent (B): One per week for the smaller devices and once per month for thelarger devices.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 142/182

140

Miniature Circuit Breakers (MCBs)

In general terms, circuit breakers are thermal/magnetic electromechanical devicesthat provide current making, carrying and breaking functions and will ‘trip’ tointerrupt a circuit under abnormal conditions. MCBs are equipped with positivecontact indication flags: red indicates that the contact(s) are closed, greenindicates the open state. The contact(s) will open when tripped due to abnormalcircuit conditions or can be manually put into the open state by use of a handle.

These devices are used to provide protection and control of circuits againstoverload and short circuit conditions. Dorman Smith MCBs are supplied withvarious breaking capacities, particularly for ratings of 6kA and 10kA. The lowerrated devices are used typically in domestic installations, e.g. in consumer units,whereas the higher rated devices are suitable for a range of commercial andindustrial circuit protection applications.

The thermal and magnetic trip functions cater for different circuit abnormalities andoperate as follows:

Thermal Trip FunctionThe purpose of this form of protection is to interrupt the circuit upon sensing anoverload current. Typically, a bi-metallic strip is used such that it will deflect due todifferential expansion of the dissimilar metals in response to the heating effectcaused by the passage of current through it. The higher the current, the greater willbe the heating effect and the more the deflection. At a preset point the physicaldeflection will be sufficient to actuate the tripping mechanism, opening thecontact(s) and interrupting the circuit.

Magnetic Trip FunctionThe purpose of this form of tripping is to protect against the effects of short circuitfault currents. A wire coil or solenoid is used to provide this function, operating thetrip mechanism when the over-current reaches a preset magnitude. As the faultcurrent rapidly increases, the magnetic field also increases, energising the coil andmoving a cam that is part of the contact assembly to fully open the contact(s)thereby interrupting the circuit.

CharacteristicsMCBs are designed according to one of three distinct tripping characteristicsdesignated B, C or D. These designations relate to the magnetic trip setting and

indicate the multiple of nominal current that will be tolerated by the device beforetripping. The following table illustrates these characteristics with typical duties and

applications. The nominal rated current is denoted by the symbol In.

B 3-5 In Light duty, resistive loads

C 5-10 In Fluorescent lights, small motors, inductive loads

D 10-20 In Sodium lights, large motors (>3kW), largeinductive loads

Type Magnetic Application

trip

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 143/182

141

MCB Tripping Characteristics – B, C and D Types

MCB Add-on Functions

Various accessories can be added to MCBs to enable remote access and signalling.For example, the contact status could be relayed to an alarm annunciator panelor SCADA system; the circuit breaker could be controlled also from theSCADA system.

Auxiliary ContactsRelaying of contact status can be achieved by the addition of an auxiliary contactand the contact form selected to suit the remote system input requirements.

Shunt TripThe addition of a shunt trip allows remote access to the breaker operation,permitting the supervisory system to manually trip the breaker. The shunt tripactuator is a coil that is normally de-energised in the closed (on) state. Whenactivated, the shunt trip will force the breaker to its ‘off’ state and the togglehandle and indicator flag will move to this corresponding position. Since the

‘fail-safe’ (i.e. non-powered) state of a shunt coil is with the breaker remainingclosed, this precludes its use for emergency stop purposes. The interconnectingwiring could be open-circuit, for example, and would therefore not allow the shuntto open the breaker when the remote emergency switch is closed.

Under-voltage ReleaseIf the supply voltage dropped to a low level and devices tripped, a dangeroussituation could exist if the devices were automatically reset. For example, motorscould suddenly restart or other operating machinery set in motion without warning.In the event that the mains voltage should drop significantly below its normaloperating range, typically to less than 50%, an under-voltage release will force thebreaker to its ‘off’ state and the toggle handle and indicator flag will move to thiscorresponding position. Only when the supply has returned to, typically, at least85% of normal operating voltage will the under-voltage release allow the breaker tobe closed.

If a break occurred in the interconnecting wiring in this case, the breaker would betripped, just as if the voltage had fallen below the threshold value. For this reason,it is advisable to include an alarm function when using a UVR function.

The tripping time for the thermal release is defined according to specific values ofapplied overload current, as follows:

1.13In >1h (In < 63A) >2h (In > 63A)

1.45In <1h (In < 63A) <2h (In > 63A)

2.55In 1s<t<60s (In < 32A) 1s<t<120s (In > 32A)

Text current Tripping time

B

C

D

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 144/182

142

Energy Let-throughAn important facet of circuit protection devices is the extent to which they limit theamount of electrical energy they allow to pass through them. This applies to fusesas well as to circuit breakers.

When an electric current flows through a resistance for a certain time, energyis produced in the form of heat. This thermal effect can be measured usingthe formula:

I2 x R x t, to give a quantity in ‘Watt seconds’. The unit of measurement for energyis the Joule, which is equivalent to one Watt second.

For all practical purposes, the resistance is treated as constant and negligible;therefore the commonly accepted term for energy let-through of a device is I2tsince this will always be proportional to the true thermal effect. The I 2t term isreferred to as the Joule Integral since the results are expressed in integral form.

Under short-circuit fault conditions there is the potential for considerable energyto be let through by a circuit protection device. Knowledge of the energy let-through characteristics of circuit protection devices is useful for comparisonbetween different devices and also with regard to the selection of devices that arerequired to act in co-ordination to produce the levels of discrimination required forfault clearance.

The I2t characteristics of circuit breakers are depicted as curves, graphed againstvalues of prospective short-circuit current. These characteristics are relevant toboth MCBs and MCCBs as depicted in the following graphs.

Energy Let-through Characteristics –

C6

C13

C16

C10

C20

C25

C32

C40

C50

C63

3

10

10 31.5 2 2.5 3 4 5 6 87 109

4

3

2

5

4

6

8

104

2

3

4

5

6

8

105

2I t/As

2

3

6

4

5

10

8

Ip/A

6

2

2 A ( t I g n i t a r e p o . x a M

s )

Prospective current I (A)p

2

D6D13

D16

D10

D20

D25

D32

B32

3

10

103

1.5 2 2.5 3 4 5 6 87 109 4

3

2

5

4

6

8

104

2

3

4

5

6

8

105

B13

B6

B16

B10

B20

B25

2I t/As

2

3

6

4

5

10

8

Ip/A

6

B40

B50

B63

2

2 A ( t I g n i t a r e p o . x a M

s )

Prospective current I (A)p

2

3

10

103

1.5 2 2.5 3 4 5 6 87 109 4

3

2

5

4

6

8

104

2

3

4

5

6

8

105

2I t/As

2

3

6

4

5

10

8

Ip/A

6

2

2 A ( t I g n i t a r e p o . x a M

s )

Prospective current I (A)p

2

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 145/182

143

Within the EN 60898 standard, circuit breakers with ‘B’ and ‘C’ characteristics arecategorised into energy limiting classes 1, 2 and 3, with Class 3 denoting deviceshaving the lowest energy let-through. The appropriate energy class is markedwithin a square box on conforming devices. Dorman Smith MCBs are categorisedwithin Class 3.

The following table indicates the maximum energy let-through values permissible ineach class, stated in Watt-seconds. In practice, compliance with the standard ischecked on the circuit breakers with the highest applicable rated current within therange, normally 40A.

6kA 1-16 100,000 120,000 35,000 42,000

20-32 No 130,000 160,000 45,000 55,000

40 limits 156,000 192,000 54,000 66,000

10kA 1-16 specified 240,000 290,000 70,000 84,000

20-32 310,000 370,000 90,000 110,000

40 372,000 444,000 108,000 132,000

Rated Current Class 1 Class 2 Class 3short- rating (A) I2t max. I2t max. I2t max.

circuit B type and B type C type B type C type

capacity C type

70

60

50

40

30

20

10

0

-10

-20

-30

-40

0 .5 0 .6 0 .7 0 .8 0 .9 1 .0 1 .1 1 .2 1 . 3 1 .4 1 . 5

T/°C

Correction factor is valid for current with times over 30 s

I(x°C) - test current at x ambient temperature

I(30°C) - test current at 30°C ambient temperature

In

Ambient temperature T/ OC

[A] -40 -30 -20 -10 0 10 20 30 40 50 60 70

0,5 0,61 0,6 0,59 0,57 0,56 0,54 0,52 0,5 0,47 0,44 0,41 0,38

1 1,22 1,2 1,18 1,15 1,12 1,09 1,05 1 0,94 0,88 0,82 0,75

1,6 1,95 1,92 1,89 1,84 1,79 1,74 1,68 1,6 1,51 1,42 1,32 1,2

2 2,44 2,4 2,36 2,30 2,24 2,18 2,1 2 1,88 1,77 1,65 1,5

4 4,88 4,8 4,72 4,61 4,49 4,36 4,20 4 3,77 3,55 3,29 3

6 7,32 7,2 7,09 6,91 6,73 6,54 6,31 6 5,66 5,33 4,94 4,5

10 12,2 12 11,8 11,5 11,2 10,9 10,5 10 9,44 8,89 8,23 7,5

13 15,9 15,6 15,4 14,9 14,5 14,1 13,6 13 12,2 11,5 10,7 9,75

16 19,5 19,2 18,9 18,4 17,9 17,4 16,8 16 15,1 14,2 13,2 12

20 24,4 24 23,6 23 22,4 21,8 21 21 18,8 17,7 16,5 15

25 30,5 30 2,5 28,8 28 27,2 26,3 25 23,6 22,2 20,6 18,8

32 39 38,4 37,8 36,9 35,9 34,9 33,6 32 30,2 28,4 26,3 24

40 48,8 48 47,8 46,1 44,9 43,6 42 40 37,7 35,5 32,9 30

50 61 60 59,1 57,6 56,1 54,5 52,6 50 47,2 44,4 41,2 37,5

63 76,9 75,6 74,4 72,6 70,7 68,7 66,2 63 59,4 56 51,9 47,3

I(x°C)

I(30°C) k= -----------------

Effect of the ambient temperature on the tripping characteristic

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 146/182

144

Current B type C type D type

rating (A) 0.4s 5s 0.4s 5s 0.4s 5s

6 7.6 7.6 3.8 5.9 2.7 3.6

10 4.6 4.6 2.3 3.5 1.6 2.9

13 3.7 3.7 1.8 2.8 1.3 2.3

16 2.9 2.9 1.4 2.2 1.0 1.8

20 2.3 2.3 1.1 1.7 0.8 1.4

25 1.8 1.8 0.9 1.4 0.6 1.1 32 1.4 1.4 0.7 1.1 0.5 0.9

40 1.1 1.1 0.6 0.9 0.4 0.7

50 0.9 0.9 0.5 0.7 0.3 0.6

63 0.7 0.7 0.4 0.6 0.3 0.5

Maximum Zs for Loadlimiter MCBs

The above table is based on 230V rated voltage to earth.

Current B type C type D type

rating (A) Fuse link rating (A)

6 20 32 25

10 20 32 40

13 20 32 40

16 32 50 63

20 40 63 63

25 50 80 80

32 63 100 100

40 80 100 125

50 100 125 125

63 125 125 125

Minimum Fuse Rating for Discrimination

Current B type C type D type

rating (A) Fuse link rating (A)

6 63 40 40

10 80 63 63

13 80 63 63

16 80 80 80

20 80 80 80

25 100 100 100

32 100 100 100

40 125 125 125

50 160 160 160 63 160 160 160

Maximum Back-up Fuse Rating for Protection

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 147/182

145

Currents of low magnitude caused by unintentional ‘leakage’ paths to earth can causedeterioration within circuit wiring and components with the potential to create arapidly escalating situation that will permit the current to reach dangerous levels.

Special forms of circuit breakers are designed to use the detection of earth leakageor ‘residual’ current to limit the effects of this type of fault.

The generic term ‘residual current device’ is used to describe a range of circuitprotection devices that include the functions of sensing and measurement of aleakage current, with subsequent tripping when the magnitude of the residualcurrent reaches a preset level. The purpose of these devices is to protect humanlife, livestock, property and equipment against the escalation of earth fault currentsto destructive magnitudes.

Two forms of technology are commonly employed in the design of residual currentdevices; electromagnetic and electronic. In both cases, a current transformer isused and is arranged such that normal current flows in the phase and neutralconductors cancel each other to produce a zero balance. The presence of anyresidual current will create an out-of-balance that can be used to signal theactuation of a mechanism for circuit interruption.

In the electromagnetic type, a trip relay is used as the actuation device. The relay ispowered by the fault current and therefore requires no external power source.

With electronic devices internal signal amplification allows a much smaller currenttransformer to be used, reducing the physical size of the circuit breaker. In thiscase, however, the actuation power is derived from both the fault current and themains power. Also, a separate earth reference connection may be required toensure continuity of operation in the event that the mains neutral is lost.

Residual current devices are accorded a ‘sensitivity’ coding that indicates the levelof residual current that would cause a trip action. Commonly, the availablesensitivity ranges are 10mA, 30mA, 100mA and 300mA. In general, the 10mA and30mA devices are used to protect human life, the 100mA and 300mA devicesbeing applied to protect wiring, cabling and equipment.

The degree of electrocution that could take place when a fault arises depends uponthe combined effects of the magnitude and duration of current flow. For sensitivity

levels of 30mA and below, tripping must be instantaneous to protect human life.Longer periods of residual current flow can be tolerated by equipment and the tripaction may not necessarily be required to interrupt the circuit instantaneously.

Residual Current Circuit BreakerThe RCCB device combines the functions of a switch with those of a residualcurrent device. It is often used in place of an incoming switch disconnector withthe advantage that it functions also as a residual current protection device. Thedisadvantage, however, is that a residual fault will cause the device to operateinterrupting ALL downstream circuits even when these circuits remain in ahealthy state.

Note that an RCCB should not be used as the sole means to provide completeprotection. It has no overload or short circuit protection and must therefore befurther protected by an upstream device having these capabilities. Frequently, theRCCB is used in consumer units and distribution boards to protect sub-circuits in asplit load configuration. In these applications, the upstream back-up is provided bythe Regional Electricity Company’s local fuse.

Residual Current Breaker with Overload ProtectionThe RCBO combines the functions of an MCB with those of a residual currentdevice. It will therefore provide protection against overload, short circuit andearth leakage.

Residual Current Circuit Breakers

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 148/182

146

RCBOs and RCCBs – GeneralThese devices are furnished with a test pushbutton on the front face of themodule. Operation of this button will simulate the presence of a residual fault andthe test should be made frequently, say once per month, to assure continuedcorrect functionality of the device.

In addition to the range of sensitivities, RCBOs and RCCBs are available in twotypes, type AC and type A. These refer to the types of circuit for which thedevices are suitable.

Type AC: for use with residual sinusoidal ac, whether applied as a step or ramp.

Type A: for use with either residual sinusoidal ac or residual chopped (pulsating)dc, whether applied as a step or ramp.

A time delay facility may also be included, adjustable up to, typically, 50-70mS.This is denoted by ‘S’ included within the description and also marked on thedevice. This function is included in order to enable the device to be used aspart of a circuit device discrimination (or selectivity) arrangement. Without thetime delay, residual current circuit breakers cannot be easily used within adiscrimination scenario due to their inherent rapid tripping in response to residualcurrent detection.

Whereas RCBOs are single module width devices used in place of or alongsideMCBs in outgoing circuits, RCCBs are available in 2-pole and 4-pole forms and arereadily used in single phase and three phase distribution systems where they canfunction as either incoming or outgoing ways.

Due to their low levels of sensitivity RCCBs are generally equipped withsuppression filtering to avoid nuisance tripping that could be induced fromdisturbances in external or incoming circuits.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 149/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 150/182

148

Modular Contactor Technical Data

Type EE2P20 EE4P25 EE4P40 EE4P63

Standards IEC/EN 61095 , IEC/EN 60947-4-1, IEC/EN 60947-5-1

Module width 1 2 3

Mechanical op. c. 3 x 106endurance

Ambient temp. °C -5 … +55

Storage temp. °C -30 … +80

No. of contactors ≤ 40 °C max. 3 no limitation max. 3

(side-by-side) 40 - 55 °C max. 2 max. 2

Contact reliability 17 V; ≥50 mA

Min. distance of mm 3.6

open contacts

Power dissipation W 1.7 1.7 4 8

per pole

Overload current A 72 68 176 240

withstand

capability

Max. back-up fuse Iv A 20 25 63 80

for short-circuitprotection gL

Coordination

type 2

DC-1 300

Max. operating AC-1/AC-3/ op. c./h 600

frequency AC-5b/AC-6b

AC-15 1,200no load 3,000

Weight kg 0.13 0.24 0.42 0.42

Rated insulation Ui V 230 440 400

voltage

Rated impulse Uimp kV 4withstand voltage

Thermal current Ith A 20 25 40 63

Rated operational Ue V 230 400

voltage

Rated frequency f Hz 50/60

Rated operational AC-1/AC-7a Ie A 20 25 40 63

current

Operational power 1-pole 230 V 4 5.4 8.7 13.3

AC-1/AC-7a

3-pole 230 V Pe kW - 9 16 24

3-pole 400 V - 16 26 40

Electrical endurance AC-1/AC-7a op. c. 200,000 100,000

Rated operational AC-3/AC-7b Ie A 9 8.5 22 30

current

Operational power 1-phase 230 V 1.3 only for NO1) 1.32) 3.72) 52)

motor

AC-3/AC-7b 3-phase 230 V Pe kW - 2,2 5.5 8.5motor

3-phase 400 V - 4 11 15motor

Electrical endurance AC-3/AC-7b op. c. 300,000 500,000 150,000 150,000

Switching of AC-6b 230 V C µF 30 36 220 330

capacitors

Electrical endurance AC-6b op. c. 200,000 100,000

Rated operational DC-1

current

1-pole U e = 24 V DC 20 25 40 63

U e = 110 V DC Ie A 6 6 4 4

U e = 220 V DC 0.6 0.6 1.2 1.2

2-poles connected U e = 24 V DC 20 25 40 63in series

U e = 110 V DC Ie A 10 10 10 10

U e = 220 V DC 6 6 8 8

3-poles connected U e = 24 V DC - 25 40 63

in series

U e = 110 V DC Ie A - 20 30 35

U e = 220 V DC - 15 20 30

4-poles connected U e = 24 V DC - 25 40

in series

U e = 110 V DC Ie A - 20 40 63

U e = 220 V DC - 15 40 63

Electrical endurance DC-1 op. c. 100000

Terminal capacity rigid mm2 1.5 … 25

flexible 1.5 … 25

Screw M3,5 M5

Screw head PZ1 PZ2

Tightening torque Nm 1.2 3.5

M A I N C I R C U I T

G E N E R A L

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 151/182

149

Switching of Lamps

Max. number of lamps per pole at 230 V 50 Hz

Type Power (W) Current (A) C (µF) EE2P20 EE4P25 EE4P40 EE4P63

Incandescent lamps 60 0.26 – 33 33 65 85

(tungsten filament) 100 0.44 – 20 20 40 50

200 0.87 – 10 10 20 25

500 2.17 – 3 3 8 10

1000 4.35 – 1 1 4 5Incandescent lamps 18 0.37 2.7 22 24 90 140

uncompensated or series 24 0.35 2.5 22 24 90 140

compensated 36 0.43 3.4 17 20 65 95

58 0.67 5.3 14 17 45 70

Incandescent lamps 2 x 18 0.11 – 2 x 30 2 x 40 2 x 100 2 x 150

lead-lag circuit 2 x 24 0.14 – 2 x 24 2 x 31 2 x 78 2 x 118

2 x 36 0.22 – 2 x 17 2 x 24 2 x 65 2 x 95

2 x 58 0.35 – 2 x 10 2 x 14 2 x 40 2 x 60

Incandescent lamps 18 0.12 4.5 7 8 48 73

parallel compensated 24 0.15 4.5 7 8 48 73

36 000 4.5 7 8 48 73

58 0.32 7 4 5 31 47

Fluorescent lamps with 18 0.09 – 25 35 100 140

electronic ballast units (EVG) 36 0.16 – 15 20 52 75

58 0.25 – 14 19 50 722 x 18 0.17 – 2 x 12 2 x 17 2 x 50 2 x 70

2 x 36 0.32 – 2 x 7 2 x 10 2 x 26 2 x 38

2 x 58 0.49 – 2 x 7 2 x 9 2 x 25 2 x 36

High-pressure 50 0.61 – 14 18 38 55

mercury-vapour lamps. 80 001 – 10 13 29 42

Uncompensated 125 1.15 – 7 9 20 29

250 2.15 – 4 5 10 15

400 3.25 – 2 3 7 10

700 005 – 1 2 4 6

1000 008 – 1 1 3 4

High-pressure 50 0.28 7 4 5 31 47

mercury-vapour lamps. 80 0.41 8 4 5 27 41

Parallel compensated 125 0.65 10 3 4 22 33

250 1.22 18 1 2 12 18

400 1.95 25 1 1 9 13700 3.45 45 _ _ 5 7

1000 005 60 _ _ 4 5

Modular Contactor Technical Data continued

Type EE2P20 EE4P25 EE4P40 EE4P63

Rated operational Ue V 230 400

voltage

Rated insulation Ui V 230 440

voltage

Rated impulse Uimp kV 4

withstand voltage

Thermal current Ith A 20 25 40 63

AC-15 Rated 1-phase 230 V Ie A 6 6 6

operational current 1-phase 400 V - 4 4Electrical endurance AC-15 op. c. 300,000 500,000 150,000 150,000

Range of Uc % 85 … 110

control voltage

Control voltages Uc V 230

Surge immunity test kV 2

(1.2/50 µs), acc. to

IEC/EN 61000-4-5

Coil consumptionswitch-on

VA/W12/10 33/25 5/5 5/5

operation 2.8/1.2 5.5/1.6 5/5 5/5

Make/break delaysmake

ms15 _ 25 10 _ 30 15 _ 20 15 _ 20

break 10 _ 30 10 _ 30 35 _ 45 35 _ 45

Terminal capacityrigid

S1 … 2.5

flexible 1 … 2.5

Screw M3,5 M3

Screw head PZ1

Tightening torque Nm 0.6

C O N T R O L C I R C U I T

A U X I L I A R Y C O N T A C T S

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 152/182

150

Modular Contactor Switching of Lamps continued

Type Power (W) Current (A) C (µF) EE2P20 EE4P25 EE4P40 EE4P63

Halogen metal-vapour lamps. 35 0.53 – 18 22 43 60

Uncompensated 70 001 – 10 12 23 32

150 002 – 5 7 12 18

250 003 – 3 4 7 10

400 004 – 3 3 6 9

1000 010 – 1 1 2 3

2000 16.5 – – – 1 1

Halogen metal-vapour lamps, 35 0.25 6 5 6 36 50

parallel compensated 70 0.45 12 2 3 18 25

150 0.75 20 1 1 11 15

250 002 33 _ 1 6 9

400 003 35 _ 1 6 8

1000 006 95 _ _ 2 3

2000 012 148 _ _ 1 2

Halogen metal-vapour lamps, 20 000 integrated 9 9 18 20

with electronic ballast unit PCI 35 000 integrated 6 6 11 13

50-125 x In lamp for 0.6 ms 70 0.36 integrated 5 5 10 12

150 001 integrated 4 4 8 10

Transformers for halogen 20 _ _ 40 52 110 174

metal-vapour lamps 50 _ _ 20 24 50 80

75 _ _ 13 16 35 54

100 _ _ 10 12 27 43

150 _ _ 7 9 19 29

200 _ _ 5 6 14 23

300 _ _ 3 4 9 14

High-pressure 150 002 _ 5 6 17 22

sodium-vapour lamps. 250 003 _ 3 4 10 13

Uncompensated 400 005 _ 2 2 6 8

1000 10.3 _ _ 1 3 3

High-pressure 150 0.83 20 1 1 11 16

sodium-vapour lamps. 250 002 33 _ 1 6 10

Parallel compensated 400 002 48 _ _ 4 6

1000 006 106 _ _ 2 3

Halogen metal-vapour lamps 20 000 integrated 9 9 18 20

with electronic ballast unit PCI 35 000 integrated 6 6 11 13

50-125 x In lamp for 0.6 ms 70 0.36 integrated 5 5 10 12

150 001 integrated 4 4 8 10

Low-pressure sodium-vapour 18 0.35 _ 22 27 71 90

lamps. Uncompensated 35 002 _ 7 9 23 3055 002 _ 7 9 23 30

90 002 _ 4 5 14 19

135 004 _ 3 4 10 13

180 003 _ 3 4 10 13

Low-pressure sodium-vapour 18 0.35 5 6 7 44 66

lamps. Compensated 35 0.31 20 1 1 11 16

55 0.42 20 1 1 11 16

90 0.63 26 1 1 8 12

135 0.94 45 _ _ 5 8

180 1.16 40 _ _ 4 7

Lumilux T5

LUMILUX* Fluorescent lamps 22 0,11 22 30 80 110

T5 with electronic ballast unit 40 0,21 FC 12 15 40 60

(EVG) 55 0,28 8 12 30 45

14 0,08 30 40 105 15021 0,11

HE22 30 80 115

28 0,14 18 22 60 90

35 0,18 14 18 48 70

24 0,12 20 26 70 100

39 0,20 12 16 42 62

49 0,24 HO 10 14 35 52

54 0,27 9 13 32 47

80 0,39 6 8 22 32

2 x 22 0,23 2 x 11 2 x 15 2 x 40 2 x 55

2 x 40 0,42 2 x FC 2 x 6 2 x 7 2 x 20 2 x 30

2 x 55 0,55 2 x 4 2 x 6 2 x 15 2 x 22

2 x 14 0,15 2 x 15 2 x 20 2 x 52 2 x 75

2 x 21 0,222 x HE

2 x 11 2 x 15 2 x 40 2 x 57

2 x 28 0,28 2 x 9 2 x 11 2 x 20 2 x 45

2 x 35 0,36 2 x 7 2 x 9 2 x 24 2 x 35

2 x 24 0,24 2 x 10 2 x 13 2 x 35 2 x 50

2 x 39 0,39 2 x 6 2 x 8 2 x 21 2 x 31

2 x 49 0,48 2 x HO 2 x 5 2 x 7 2 x 17 2 x 26

2 x 54 0,54 2 x 4 2 x 6 2 x 16 2 x 23

2 x 80 0,74 2 x 3 2 x 4 2 x 11 2 x 16

*LUMILUX is a trademark of OSRAM GmbH

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 153/182

151

The operation and application of the MCCB is similar to that of the MCB, howeverthis device has the air-break mechanism contained within a moulded case housingmade from a very robust non-conducting material. Generally, MCCBs exhibit muchhigher breaking capacities and rated current than their smaller counterparts andcan be used to perform full isolation duty. Consequently, MCCBs are employed inboth incoming and outgoing circuits. MCCBs are constructed to a particular framesize and typically provide rated current in the range 16-1600A.

These devices can be equipped with adjustable thermal and magnetic trippingmechanisms to cater for overload and short circuit protection to meet therequirements for isolation and Category A discrimination duty. Dorman Smithelectronic MCCBs provide adjustable long, short and instantaneous trip functions,allowing more complex overall tripping characteristics to be configured, allowingthese devices to be used for isolation and Category B discrimination requirements.(Refer to page 136 for Category definitions).

Devices equipped with the full range of adjustable trips for long, short andinstantaneous durations are generally referred to as ‘LSI-MCCBs’ to distinguishthem from the L and I only versions employed for Category A devices.

The range of accessories that can be added to MCCBs is similar to that given in thesection dealing with MCBs, including shunt trips, under-voltage releases and variousforms of auxiliary contacts. The physical size of triple-pole and four-pole MCCBs

allows these accessories to be internally mounted, although there are somerestrictions with regard to combinations of these that can be co-mounted. Forexample, either a shunt trip or under-voltage release can be incorporated, but notboth. Also, due to the much larger physical size of these devices compared withMCBs, additional safety features normally include interphase barriers and terminalshrouds to provide IP2X ingress protection at the terminals.

The tripping operation of some MCCBs is different from that of MCBs in that there arethree distinct positions of the toggle or handle. Whereas MCBs are either ‘on’ or ‘off’,MCCBs have a central position when they are tripped. As a further safety feature, thecoloured flags indicating the ‘on’ and ‘off’ states are masked in the tripped state. Thebreaker can be reset only after it has been set into the fully ‘off’ state.

MCCBs are equipped with a test pushbutton that allows periodic testing of themechanical tripping mechanism. As in the case of a fault trip, the device must be

moved into the ‘off’ position before it can be reset following a test.

These devices conform to EN 60947-2 therefore the definitions that apply to someparameters differ from those of EN 60898 that apply to miniature circuit breakers.These differences are explained in the section covering Standard Terminology.

Motor Control ApplicationsThe MCCB is a viable means of providing motor control switching. However,MCCBs used for this type of application are often required to provide only shortcircuit protection, with the overload protection catered for by a separate thermalor electronic overload relay. For this reason, specifically designed ‘motor control’MCCBs are available upon request, with only the single tripping mechanism.

The range of circuit breakers for each frame size includes a basic switchdisconnector version, generally in both triple-pole and four-pole variants. Devices ofthis type are sometimes referred to as ‘non-auto MCCBs’.

Moulded Case Circuit Breakers

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 154/182

152

Loadline YA Frame MCCBs for Motor Starting (415 V ac)

P(Kw) Ie(A) Id"(A) In(A) Ii (lowertolerance) (A)

0.37 1.2 14 YA2/YA3 20 192

0.55 1.6 19 YA2/YA3 20 192

0.75 2 24 YA2/YA3 20 192

1.10 2.8 34 YA2/YA3 20 192

1.50 3.7 44 YA2/YA3 20 192

2.20 5.3 64 YA2/YA3 20 192

3.00 7 84 YA2/YA3 20 192

4.00 9 108 YA2/YA3 20 192

5.50 12 144 YA2/YA3 20 192

7.50 16 192 YA2/YA3 32 307

9.00 20 240 YA2/YA3 32 307

11.00 23 276 YA2/YA3 50 480

15.00 30 360 YA2/YA3 50 480

18.50 37 444 YA2/YA3 50 480

22.00 43 516 YA2/YA3 63 605

30.00 59 708 YA2/YA3 100 960

37.00 72 864 YA2/YA3 125 1200

45.00 85 1020 YA2/YA3 125 1200

55.00 105 1260 YA3 160 1664

75.00 140 1680 YA3 250 2600

90.00 170 2040 YA3 250 2600

110.00 210 2520 YA5 400 3840

132.00 224 2688 YA5 400 3840

150.00 255 3060 YA5 400 3840

Motor Motor full Sub-transient Breaker Breaker Breakerrating load starting frame rated instantaneous current current current trip threshold (set on max.)

Notes

1 In>le2 li/lower > ld"

The above table is suitable for DOL and Star Delta starting.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 155/182

153

In the context of power distribution schemes, the term ‘discrimination’ (sometimesreferred to as ‘selectivity’) describes a hierarchy of circuit devices that are arrangedsuch that a single upstream circuit breaker can fan out to several downstreamdevices to act in a co-ordinated fashion should a fault occur. Under fault conditions,only the upstream protective device closest to the fault should operate to clear thefault, leaving all other healthy circuits operable. This is especially important ininstallations where circuit failures could be life-threatening, such as in hospitals.

The concept of discrimination is similar to that of cascading, the prime differencebeing in the objectives of the application. Whereas discrimination is used to ensurecontinuity of supply to sub-circuits by limiting the disconnection to the faultedsub-circuit alone, cascading is used to buffer downstream protective devicesagainst the effects of high prospective short circuit currents.

In both cases, the protective devices are specifically selected to meet the criteriafor the type of co-ordination required.

When the selected devices are properly matched to fulfil the ideal discriminationprinciple described above, the co-ordinating devices are said to achieve ‘total’discrimination. In many practical installations, however, a partial discrimination maybe satisfactory for safe continuity of supply, with an added advantage of costsavings due to selecting a lower rated upstream circuit breaker.

Discrimination between two circuit breakers arranged in series may be based oneither current or time. Where the magnitude of the fault current is to be used asthe critical factor for selection, the co-ordination in this case is termed ‘currentdiscrimination’. Where the basis for selection is the duration over which theupstream device can withstand the fault current, the selection is to achieve ‘timediscrimination’. In some cases, time discrimination can be achieved by using anupstream device that has a built-in time delay.

Current Discrimination

In general, the basis for current discrimination is that the downstream protectivedevice will have a lower current rating than the upstream device. It should alsohave a lower instantaneous tripping point. The discrimination tables that followhighlight the consequential increase in discrimination level as the differential incurrent ratings between the devices increases.

Time DiscriminationDiscriminating by time between two devices in series relies on the operation of theupstream device being delayed at least until the downstream circuit breaker hastripped to clear the fault. The clearing time of the downstream device must be lessthan the time setting of the upstream device and the upstream device must also becapable of withstanding the fault current for the full duration of its time setting.There is generally no problem in achieving these conditions where the upstreamdevice is a Category B circuit breaker specifically designed for this type ofco-ordination duty.

Time/Current Characteristics

Comparison of the time/current characteristic graphs of the two devices proposedcan give a quick check on their suitability for co-ordination in both current and timediscrimination cases. Ideally, there should be no overlap of the respective curves toachieve total discrimination. If, however, the instantaneous portion of the curves do

intersect, a partial discrimination will be achieved at the current level projectedfrom the intersect point.

In the tables that follow, total discrimination is indicated by the letter ‘T’ inappropriate boxes. Total discrimination applies for all fault levels up to the lowerbreaking capacity of the two devices in co-ordination. Where a value is containedin any of the boxes, this indicates a partial discrimination of that value of currentlimit. If no discrimination is possible, this is shown by a dash symbol.

Discrimination

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 156/182

154

Note that ‘partial discrimination’ infers that, above the current limit value indicated, it is possible that both devices could trip,resulting in disconnection of other sub-circuits and loss of supply continuity to those areas of the distribution system.

Discrimination Tables

FrameRating

Model STD HIGH STD HIGH STD HIGH STD HIGH STD HIGH STD HIGH STDCapacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

Breaking 65kA 80kA 65kA 80kA 65kA 80kA 65kA 80kA 85kA 100kA 85kA 100kA 100kA

Capacity

YA2N 25kA T T T T T T T T T T T T T

Thermal/Mag

YA2S 36kA T T T T T T T T T T T T T

Thermal/Mag

YA2J 65kA T T T T T T T T T T T T TThermal/

Mag

YA3N 25kA T T T T T T T T T T T T T

Thermal/Mag

YA3S 36kA T T T T T T T T T T T T T

Thermal/Mag

YA3J 65kA T T T T T T T T T T T T TThermal/

Mag

YA5N 25kA T T T T T T T T T T T T T

Thermal/Mag

YA5H 50kA T T T T T T T T T T T T TThermal/

Mag

YA5H 50kA T T T T T T T T T T T T T

Electronic

YA5J 65kA T T T T T T T T T T T T TThermal/

Mag

YA5K 70kA T T T T T T T T T T T T T

Electronic

Y6H 50kA T T T T T T T T T T T T T

Thermal/

Mag

Y6H 50kA T T T T T T T T T T T T TElectronic

Y6J 65kA T T T T T T T T T T T T T

Electronic

Y6K 85kA T T T T T T T T T T T T T

Thermal/Mag

Y7J 65kA - - T T T T T T T T T T TElectronic

Y8K 85kA - - - - T T T T T T T T T

Electronic

UPSTREAM ELECTRONIC ACB

Z2 800A Z2 1250A Z2 1600A Z2 2000A Z3 2500A Z3 3200A Z3 4000A

125A

250A

400A

800A

1250A

D O W N S T R E A M M C C B

1600A

T= Total Selectivity

Notes: All ACBs have instantaneous trip set to NON and the MCR set to ON.Assumes all ACB time settings are greater than MCCB.

The above table is in accordance with IEC 60947-2, Annex A.

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 157/182

155

FrameRating

Model YA5H- YA5K- Y6H- Y6J- Y7J- Y8K-Electronic Electronic Electronic Electronic Electronic Electronic

Breaking 50kA 70kA 50kA 65kA 65kA 85kACapacity

YA2N 25kA T T T T T TThermal/

Mag

YA2S 36kA T T T T T T

Thermal/Mag

YA2J 65kA 50 T T T T TThermal/

Mag

YA3N 25kA T T T T T TThermal/

Mag

YA3S 36kA T T T T T T

Thermal/Mag

YA3J 65kA 50 T T 50 T TThermal/

Mag

YA5N 25kA - - T T T T

Thermal/

Mag

YA5H 50kA - - 25 25 T T

Thermal/

Mag

YA5H 50kA - - 25 25 T TElectronic

YA5J 65kA - - 25 25 T TThermal/

Mag

YA5K 70kA - - 25 25 T T

Electronic

In 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 160A 200A250A250A400A

6A 260 T T T T T 260 T T T T T T T T T T

10A 260 420 T T T T 260 420 T T T T T T T T T

16A 260 420 650 T T T 260 420 650 T T T T T T T T

20A 260 420 650 1000 T T 260 420 650 1000 T T T T T T T

25A 260 420 650 1000 T T 260 420 650 1000 T T T T T T T

32A 260 420 650 1000 1500 T 260 420 650 1000 1500 T T T T T T

40A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 T T T T T

50A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 T T T T

63A 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 2600 T T T

UPSTREAM ELECTRONIC MCCB

UPSTREAM THERMAL MAGNETIC MCCB

400A 800A 1250A 1600A

125A

250A

400A

D

O W N S T R E A M M C C B

D O W N S T R E A M

K S E R I E S M C B

T= Total Selectivity

Notes: All pick-up current and time delay settings to be set at maximum onupstream MCCBs.

Partial discrimination level is in kA. The above table is in accordance with IEC 60947-2, Annex A.

T= Total Selectivity

Notes: MCBs can be of any manufacture as long as they are Energy Class 3 asdefined in EN 60898.

Table based on Type B & C characteristic MCBs. MCBs can be 6kA or 10kA at 400V ac. Partial discrimination level is in amps. The above table is in accordance with IEC 60947-2, Annex A.

YA2N (25kA) or YA2S (36kA) YA3N (25kA) or YA3S (36kA) YA5H(50kA)

Discrimination Tables

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 158/182

156

UPSTREAM THERMAL MAGNETIC MCCB

T= Total Selectivity

Notes: Table based on Type D characteristic MCBs.

MCBs can be 6kA or 10kA at 400V ac.Partial discrimination level is in amps.

6A 166 192 307 480 605 832 960 1200 166 192 307 480 605 832 960 1200 1664 2080 2000 2400 3840

10A - - 307 480 605 832 960 1200 - - 307 480 605 832 960 1200 1664 2080 2000 2400 3840

16A - - - 480 605 832 960 1200 - - - 480 605 832 960 1200 1664 2080 2000 2400 3840

20A - - - 480 605 832 960 1200 - - - 480 605 832 960 1200 1664 2080 2000 2400 3840

25A - - - - 605 832 960 1200 - - - - 605 832 960 1200 1664 2080 2000 2400 3840

32A - - - - - 832 960 1200 - - - - - 832 960 1200 1664 2080 2000 2400 3840

40A - - - - - - 960 1200 - - - - - - 960 1200 1664 2080 2000 2400 3840

50A - - - - - - - 1200 - - - - - - - 1200 1664 2080 2000 2400 3840

63A - - - - - - - - - - - - - - - - 1664 2080 2000 2400 3840

D O W N S T R E A M

K S E R I E S D T Y P E M C B

YA2N (25kA) or YA2S (36kA) YA3N (25kA) or YA3S (36kA) YA5H (50kA)

In 16A 20A 32A 50A 63A 80A 100A 125A 16A 20A 32A 50A 63A 80A 100A 125A 160A 200A 250A 250A 400A

Discrimination Table

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 159/182

157

Cascading is sometimes referred to as ‘back-up protection’. The technique ofcascading is used to allow circuit breakers with a breaking capacity lower than thevalue of prospective short-circuit current at the connection point to be used whenthese are positioned downstream of a current-limiting circuit breaker of higherbreaking capacity. The net result of this arrangement is that the downstreamdevice acquires an enhanced ’installed‘ breaking capacity, therefore a lessexpensive, lower breaking capacity breaker can be used.

The upstream circuit breaker must have the normally required breaking capacityfor its point of installation however, when combined with another circuit breakerdownstream, the two devices in series will be able to clear a larger fault. Forexample: if a 10A, 6kA MCB is place downstream of a YA frame MCCB rated at125A and 25kA, the MCB will have an installed breaking capacity of 14kA. Similarly,a 10A, 10kA MCB downstream of a YA frame MCCB rated at 250A and 25kA willhave an installed breaking capacity of 25kA.

It should be noted that the cascading technique is not limited to only two devicesin series. The important point is that it is the upstream device that is limiting thecurrent to a value that can be interrupted by the following device, so that thepattern of paired devices can be repeated many times in an hierarchy of devices.

The following tables give ‘installed breaking capacity’ values of downstream circuitbreakers for both the MCCB/MCB and MCCB/MCCB pairings of cascaded devices.

Note that all values shown are at 400V ac. The values for the installed breakingcapacities are given in kA.

Upstream YA frame MCCB with downstream S-series MCB –

Cascading

MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCB YA2N YA2S YA2J YA3S YA3J YA3N YA3S YA3J (6kA) (25kA) (36kA) (65kA) (36kA) (65kA) (25kA) (36kA) (65kA) 125A 125A 125A 160A 160A 250A 250A 250A

6 14 14 14 12 12 12 12 12

10 14 14 14 12 12 12 12 12

16 14 14 14 12 12 12 12 12

20 14 14 14 12 12 12 12 12 32 14 14 14 12 12 12 12 12

40 12 12 12 10 10 10 10 10

50 12 12 12 10 10 10 10 10

63 12 12 12 10 10 10 10 10

Frame

Rating

Model YA2N T/Mag YA2S T/Mag YA2J T/Mag YA3N T/Mag YA3S T/Mag YA3J T/Mag

Current Breaking 25kA 36kA 65kA 25kA 36kA 65kARating Capacity

6A 10kA 25 30 30 25 25 25

10A 10kA 25 30 30 25 25 25

16A 10kA 25 30 30 25 25 25

20A 10kA 25 30 30 25 25 25

25A 10kA 25 30 30 25 25 25

32A 10kA 25 30 30 25 25 25

40A 10kA 25 30 30 23 23 23

50A 10kA 25 30 30 23 23 23

63A 10kA 25 30 30 23 23 23

UPSTREAM MCCB

125A 250A

D O W N S T R E A M M C B

Upstream YA frame MCCB with downstream K-series MCB –

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 160/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 161/182

159

MCB, type B Fuse Current sizes rating (A) 20 25 35 50 63 80 100 125 160

6 0.5 0.8 1.7 3.1 7.0 10.0 10.0 10.0 10.0

10 0.4 0.7 1.4 2.3 3.4 4.8 7.5 10.0 10.0

13 0.7 1.4 2.3 3.4 4.8 7.5 10.0 10.0

16 1.3 2.0 2.9 4.2 6.0 9.5 10.0

20 1.9 2.7 3.8 5.6 8.5 10.0

25 1.8 2.6 3.6 5.4 8.0 10.0

32 2.4 3.2 4.2 6.8 10.0

40 3.2 4.2 6.8 9.5

50 3.8 5.7 8.5

63 3.8 5.7 8.5

Short-circuit Discrimination LevelsWhere a high prospective fault level exists at the MCB distribution point,discrimination at short-circuit levels should be considered. This will requirecomparison of the device I2t characteristics at the relevant prospective fault level.

Discrimination will be obtained at all fault levels for which the MCB total operatingI2t is lower than the pre-arcing I2t of the device closer to the supply.

The data for typical cartridge fuses can be extracted from graphs and is presentedin the following tables.

MCB, type C Current rating (A)

6 0.5 0.8 1.7 3.1 7.0 10.0 10.0 10.0 10.0

10 1.4 2.3 3.4 4.8 7.5 10.0 10.0

13 2.3 3.4 4.8 7.5 10.0 10.0

16 2.0 2.9 4.2 6.0 9.5 10.0

20 2.7 3.8 5.6 8.5 10.0

25 3.6 5.4 8.0 10.0

32 4.2 6.8 10.0

40 4.2 6.8 9.5

50 5.7 8.5

63 5.7 8.5

MCB, type D Current rating (A)

6 0.7 1.7 3.0 5.9 6.0 6.0 6.0 6.0 6.0

10 1.3 2.2 3.6 6.0 6.0 6.0 6.0

13 1.7 2.5 4.0 6.0 6.0 6.0

16 1.6 2.2 3.1 4.6 6.0 6.0

20 2.2 3.1 4.6 6.0 6.0

25 3.1 4.6 6.0 6.0

32 2.6 3.5 6.0 6.0

40 3.5 6.0 6.0

50 5.5 6.0

63

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 162/182

160

Number MCCB panel boards MCB distribution boards of circuits to EN 61439-2 to EN 60439-3

2-3 0.9 0.8

4-5 0.8 0.7

6-9 0.7 0.6

10+ 0.6 0.5

The adequacy of sizing and rating of power distribution systems is important toensure supply continuity and safety in operation. A number of design parametersmust be taken into account in order to ensure that the supply and safetyrequirements are met. These include busbar ratings, short-circuit fault levels andcircuit utilisation.

Once the overall loading requirements have been established, and the supply

transformer selected, consideration of the circuit distribution systems follows.Distribution enclosures and their busbar systems are pre-tested to accepted normsof through-fault levels, typically 16kA, 25kA, 35kA, 50kA and 80kA. These short-circuit ratings alone will limit the choice of switchboard, panel board or distributionboard. The selection of the type and size of enclosure to be used will then dependupon the busbar current rating needed, together with availability of sufficientcircuit ways of the correct type for the circuits and sub-circuits to be supplied.

The busbar current rating is generally chosen to be sufficient to supply full load,plus some safety factor. For example, if the full load is expected to be 750 amps,an enclosure with a busbar rating of 800 amps may be selected. Once the busbarcurrent rating has been nominated, the incoming device for that group of circuitswill be matched to the rating. In the example cited, the incoming device wouldbe rated at 800 amps. More than one incoming device may be required to effectproper circuit protection and isolation, such as a switch disconnector in serieswith a thermal fuse. In this case, the fuse link will provide the protection and

the disconnector will permit isolation. Alternatively, a moulded case circuitbreaker (MCCB) employed as the incoming device will provide both protectionand isolation.

The size and type of circuits to be supplied will further refine the eventual choiceof distribution system. Automatic or manual circuit disconnection will point toan enclosure suitable for either circuit breakers or switch-fuse devices. If therequirement is for automatic disconnection, prospective fault levels at theconnection point may dictate that an MCCB must be used, rather than an MCB ofthe same current rating.

Finally, consideration is given to the degree of circuit utilisation capacity, oftenreferred to as ‘diversity’. Notwithstanding the limitations of the busbar system andthe matched protection provided by the incoming device, the outgoing circuit waysmay be configured with individual circuit protection devices having an aggregate

rated current capacity in excess of the rating of the incomer.

The basis for this approach is that it is often reasonable to assume that not allcircuits will be supplying their rated current at the same time. In this case, a‘diversity factor’ is applied during the design stage to give an overall servicecapacity for the outgoing circuits. The maximum current rating divided by thediversity factor will give the maximum aggregate ‘fitted’ current allowed. Thefollowing table lists the factors that may be applied subject to the number ofoutgoing circuits to be supplied.

Taking the example of a 400A panel board with 400A MCCB incomer and 6outgoing circuits, a diversity factor of 0.7 would allow outgoing MCCBs with anaggregate of 570A capacity to be installed. The individual circuits would beprotected at the level of current rating of each MCCB, with the incomer providingultimate protection at 400A. To allow for the possibility of future expansion of adistribution system, an allowance for 25% spare capacity is often included when

applying a diversity factor to the initial design.

System Sizing and Diversity

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 163/182

161

The Prospective Short-circuit Current, or PSC, is the theoretical maximum faultcurrent that could exist at any point within a complete circuit distribution system.

The magnitude of the fault current at any particular point is calculated on the basis ofa ‘bolted’ (virtually permanent) fault path at that point and therefore assumes aconstant voltage, continuous current supply feeding the fault. Using this assumption,the PSC that could possibly exist at the bolted fault path would be limited only by the

sum of the circuit impedances of the complete current path, from high voltage feedto the supply transformer through to the bolted connection point. Since thisassumption cannot be fulfilled in practice (for example, the voltage will not remainconstant) the value of calculated PSC can never be exceeded in a practical scheme.

The foregoing commentary is particularly relevant to larger commercial and industrialnetworks, where many sub-systems are present and often, many sub-circuits withinthese. For more compact arrangements, such as domestic installations, where thedistribution scheme is contained within one or more consumer units, the situation ismuch simpler. The Regional Electricity Companies generally agree on a fixed faultlevel of 16kA at the local zone supply distribution point to one or more dwellings.Those dwellings that lie some distance from the zone origin point of the distributedsupply will have reduced PSC due to the higher impedance of the longer run ofservice cable. Consumer units should therefore have a minimum short-circuit rating of16kA. When an MCB trips, the combination of forced contact separation and rapid arcextinction produces a limiting effect on the fault current such that it will be

adequately handled within the normal 6kA breaking capacity of MCBs fitted todomestic installations.

PSC at the origin point –

In practice and with consideration of the total distribution network; the breakingcapacity of an individual circuit device would normally be less than that calculated forthe origin point of the scheme.

PSC at the connection point –

The breaking capacity of individual devices must be greater than (or at least equal to)the PSC at the specific point of their connection within a scheme. Conversely, wherethe circuit device breaking capacity is greater than the PSC at origin, there is no needfor further measurement or calculation in this regard.

The PSC at any particular connection point can be estimated, calculated, or

determined by measurement of the circuit impedance at that point. Measurement ofthe circuit impedances at all relevant connection points can be a laborious exercise;the calculation method is generally used since this can be readily carried out usingone of a number of available computer software packages.

PSC by calculation –The magnitude of the short-circuit current (rms value of the ac component) at theconnection point will depend upon:

• the PSC at the origin point.

• the total resistance in the circuit between the origin point and the relevant circuitreference point.

• whether the short-circuit condition is considered as phase-phase, phase-neutral orphase-earth.

The maximum PSC at the origin can be calculated from the following formula:

Supply transformer rating (kVA) x 100

√3 x secondary voltage x % transformer reactance

PSC by estimation –

To estimate the PSC, first calculate the total resistance in the LV circuit bydetermining the sizes and lengths of cables between the supply source and the pointunder consideration. Next, use the following table to find the cable resistances andsummate these to obtain the total resistance. Finally, use this value to read off theestimated PSC from the following graph.

Prospective Short-circuit Current

PSC (kA) =

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 164/182

162

Nominal Cable length (m)

crosssectionalarea (mm2) 5 10 15 20 30 40 50 60 70 80 90 100

1 90.50 181.00

1.5 60.50 121.00 182.00

2.5 37.10 74.10 111.00 148.00

4 23.10 46.10 69.20 92.20 138.00 6 15.40 30.80 46.20 61.60 92.40 123.00

10 9.15 18.30 27.50 36.60 54.90 73.20 91.50 110.00

16 5.75 11.50 17.30 23.00 34.50 46.00 57.20 69.00 80.50 92.00

25 3.64 7.27 10.90 14.50 21.80 29.10 36.40 43.60 50.90 58.20 65.40 72.70

35 2.62 5.24 7.86 10.48 15.70 21.00 26.20 31.40 36.70 41.90 47.20 52.40

50 1.94 3.87 5.81 7.74 11.60 15.50 19.40 23.20 27.10 31.00 34.80 38.70

70 1.34 2.68 4.02 5.36 8.04 10.70 13.40 16.10 18.80 21.40 24.10 26.80

95 0.96 1.93 2.88 3.86 5.79 7.72 9.65 11.60 13.50 15.40 17.40 19.30

120 0.77 1.53 2.30 3.06 4.59 6.12 7.65 9.18 10.70 12.20 13.80 15.30

150 0.62 1.24 1.86 2.48 3.72 4.96 6.20 7.44 8.68 9.92 11.20 12.40

185 0.49 1.00 1.49 1.98 2.97 3.96 4.96 5.96 6.94 7.93 8.92 9.91

240 0.38 0.75 1.13 1.51 2.26 3.02 3.77 4.52 5.28 6.03 6.79 7.54

300 0.30 0.60 0.90 1.20 1.80 2.40 3.00 3.60 4.20 4.80 5.40 6.00

400 0.23 0.47 0.70 0.94 1.41 1.88 2.35 2.85 3.29 3.76 4.23 4.70

500 0.18 0.37 0.55 0.73 1.10 1.46 1.83 2.20 2.56 2.93 3.29 3.66

630 0.14 0.28 0.42 0.57 0.85 1.13 1.42 1.78 2.15 2.51 2.88 3.25

Maximum Resistance of Copper Conductors at 20°C (milli ohms)

Total Circuit Resistance (mΩ)

F a u l t C u r r e n t ( k A )

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 165/182

163

PSC in a typical installation

Note that the values on the graph assume a symmetrical fault across the threephases. In a single circuit, for line-neutral faults, the cable resistance value given inthe table should be doubled.

The following values of PSC would be obtained at the various circuit points markedin the above diagram:

Point ‘A’ PSC = approximately 27kA

Point ‘B’ Two cables per phase, therefore halve the value.

Resistance from ‘A’ to ‘B’ = 0.3 Milli ohms

With reference to the graph PSC

can be assumed to be 25kA

Point ‘C’ Resistance from ‘A’ to ‘B’ = 0.3 Milli ohms

Resistance from ‘B’ to ‘C’ = 10.7 Milli ohms

Total circuit resistance ‘A’ to ‘C’ = 11.0 Milli ohms

With reference to the graph PSC

can be assumed to be 12kA

Point ‘D’ Resistance from ‘A’ to ‘B’ = 0.3 Milli ohms

Resistance from ‘B’ to ‘C’ = 10.7 Milli ohms

Resistance from ‘C’ to ‘D’ = 46.0 Milli ohms (Double the value for the 2-core cable)

Total circuit resistance ‘A’ to ‘D’ = 57.0 Milli ohms

With reference to the graph PSCcan be assumed to be 3kA

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 166/182

164

One of the most common means of protecting persons against the effects of highvoltages and currents is by insulating the wiring and components. Most earth faults occurwhen some part of the insulation has broken down, creating the possibility of causingelectric shock through indirect contact with the faulty circuit. The breakdown of insulationcan often cause all or part of an enclosure or frame to become ‘live’ by raising conductiveparts to a hazardous voltage level. Touching any of the exposed parts of the enclosure orframe would then be highly dangerous and would most likely cause an electric shock.

Whilst protective devices may open quickly to minimise the possibility of high currentsflowing for any significant length of time, additional measures are necessary to limit thepotential earth fault current at source. In some cases fault current limiting resistors orinductors may be installed at the transformer star point however, in all cases, it isimportant to ensure that the impedance of circuit conductors is kept to a minimum sothat the voltage developed under fault conditions will be restricted. The earth fault loopimpedance is denoted Zs and is an important circuit design parameter.

Circuit designs must always ensure that the magnitude of the fault current will besufficient to trip the over-current protective devices within acceptable times as stated inthe IEE Wiring Regulations. Circuit breakers are designed to trip and therefore disconnectfaulted circuits very quickly. The design value of tripping time is generally expressed in theform of a graph that maps current against time and any practical scheme can be checkedagainst this value to ascertain conformance with the requirements.

The fault current can be established very simply using Ohm’s law, as follows:

Fault current = Phase-to-earth voltage

Zs

Once this value is known, the corresponding tripping time can be read from the relevantdevice’s time/current characteristic graph and the result compared with that given withinthe Wiring Regulations. In general, the higher the nominal voltage of an installation, theshorter will be the required disconnection time. For fixed equipment installations, themaximum disconnection time is stated as 5 seconds, whereas it is 0.4 seconds forportable equipment. The Regulations define ‘portable’ as including fixed outlet socketsthat may be used to supply apparatus that is movable or portable when in use.

The following table illustrates the maximum Zs allowable for MCBs to achieve thespecified disconnection times.

Since the complete loop impedance is the sum of the individual impedances of thesupply transformer winding, circuit phase conductor and protective circuitconductor, the total may be higher than that specified for in-time disconnection forthe protection device proposed. In these cases, several solutions may be possibleto overcome or at least assist in achieving compliance.

• The supply cable may be replaced by one with greater cross sectional area

• The short-circuit tripping threshold of the device may be set to a lower value(if it is adjustable)

• A Residual Current Device could be used to replace the circuit breaker in question

The following tables indicate the maximum Zs for Dorman Smith’s range ofMCCBs. Using these tables obviates the need to determine the suitability of adevice by reference to its time/current characteristic graph.

Earth Fault Protection

Current 6 10 16 20 25 32 40 50 63rating (A)

Type Bmax. Zs 8.00 4.80 3.00 2.40 1.92 1.50 1.20 0.96 0.76(ohms)

Type Cmax. Zs 4.00 2.40 1.50 1.20 0.96 0.75 0.60 0.48 0.38(ohms)

Type D

max. Zs 2.00 1.20 0.75 0.60 0.48 0.38 0.30 0.24 0.19(ohms)

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 167/182

165

Zs Values for YA2, YA3 and YA5 MCCBs

Maximum Allowable Earth Loop Impedance Values, in accordance with BS7671

MCCB Reference S/C Protection Zs values @ 230 Volts

Setting In 0.4 sec 5 sec

YA2 1P Fixed Mags 16 0.92 1.31

20 0.74 1.00

25 0.59 0.8232 0.46 0.62

YA2N, 25kA 40 0.37 0.51

50 0.29 0.42

63 0.23 0.33

80 0.18 0.26

100 0.15 0.20

125 0.12 0.16

YA2 3P & 4P MIN 20 1.60 1.64Thermal Magnetic MAX 20 0.80 1.64

MIN 32 1.00 1.00MAX 32 0.50 1.05

MIN 50 0.64 0.64

MAX 50 0.32 0.37MIN 63 0.51 0.51MAX 63 0.25 0.29

MIN 100 0.32 0.32MAX 100 0.16 0.19

MIN 125 0.26 0.26MAX 125 0.13 0.15

YA3 1P Fixed Mags 16 1.20 1.28

20 0.96 1.05

25 0.77 0.82

32 0.60 0.62

40 0.48 0.50

YA3N, 25kA 50 0.38 0.41

63 0.30 0.33

80 0.24 0.26

100 0.19 0.21

125 0.15 0.17

160 0.12 0.13

YA3 3P & 4P MIN 20 1.60 1.60Thermal Magnetic MAX 20 0.80 0.88

MIN 32 1.00 1.00MAX 32 0.50 0.58

MIN 50 0.64 0.64MAX 50 0.32 0.37

MIN 63 0.51 0.51MAX 63 0.25 0.29

MIN 100 0.32 0.32

MAX 100 0.16 0.18MIN 125 0.26 0.26MAX 125 0.13 0.14

MIN 160 0.20 0.20MAX 160 0.09 0.11

MIN 200 0.16 0.16MAX 200 0.07 0.09

MIN 250 0.13 0.13MAX 250 0.06 0.06

YA2N, 25kA

YA2S, 36kA

YA2J, 65kA

YA3N, 25kA

YA3S, 36kA

YA3J, 65kA

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 168/182

166

Loadline MCCBs Magnetic Breaking Max Zs values

adjustment In capacity

(kA) 0.4 sec 5 sec

Y6 Frame

Y6HJK Set at maximum 400 50 0.05 0.05

Thermal magnetic Set at minimum 400 50 0.10 0.10

Y6HJK Set at maximum 630 50 0.03 0.03

Thermal magnetic Set at minimum 630 50 0.07 0.07

Y6HJK Set at maximum 800 50 0.03 0.03

Thermal magnetic Set at minimum 800 50 0.05 0.05

Y6HJK Set at maximum 630 50 0.03 0.03Electronic "INST/STD" Set at minimum 630 50 0.17 0.17

Y6HKJ Set at maximum 800 50 0.13 0.13Electronic "INST/STD" Set at minimum 800 50 0.03 0.03

Y7 Frame

Y7JK Set at minimum 1000 65 0.02 0.02Electronic "INST/STD" Set at minimum 1000 65 0.10 0.1

Y7JK Set at minimum 1250 65 0.08 0.08Electronic "INST/STD" Set at maximum 1250 65 0.02 0.02

Y8 Frame

Y8JK Set at minimum 1600 85 0.07 0.07Electronic "INST/STD" Set at maximum 1600 85 0.01 0.01

Zs values for Y6, Y7 and Y8 MCCBs

Maximum Allowable Earth Loop Impedance Values, in accordance with BS7671

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 169/182

167

The principle of separation applied to multi-cubicle switchboards and panel boardsis the achievement of a high degree of safety for equipment and people duringnormal operation and to promote safe working during commissioning and service.The resulting concept is one of functional separation and segregation of live partsof the system into sub-units by the use of barriers or partitions.

In general, separation should provide enhanced safety by:

• Protecting against contact with the live parts of adjacent functional units

• Preventing the passage of solid foreign bodies from one section of an assemblyto an adjacent one

Various elements of an assembly must be considered for separation fromneighbouring live sections, such as busbars, terminals and functional units. Thespecific form of their separation can be achieved in several ways according to theparticular application and the requirements for access for maintenance. Theminimum degree of protection to be achieved at each barrier or partition is to IP2Xas specified in the Ingress Protection standard EN 60529. Typically, this may include:

• PVC sleeving, wrapping or plastic coating of conductors

• Insulated terminal shrouds or PVC ‘boots’

• Rigid insulated barriers or partitions

• Compartments formed from earthed metal

• A device’s integral housing

There are several forms of separation, indicated by numbered category and sub-category; however the requirements for the degree of separation need to becarefully considered since the cost increases significantly with increased degree.

The principal categories are:

Form 1 – no separation

Typical applications are where the assembly is to be placed in a secure locationand where failure will cause little or no additional disruption to other areas beingsupplied by that particular assembly.

Form 2 – separation of busbars from functional units

Applications may be similar to those of Form 1 but where it is important that a faultneed not affect all functional units being supplied by the same busbar system.

Form 3 – separation of busbars from functional units and the functional units

from one another, but not their terminations

This form should be applied where it is important to provide protection frominternal live parts and where failure of functional units being supplied from thesame busbar would cause unacceptable disruption.

Form 4 – separation of busbars from functional units and the functional units

from one another, including their terminals

This form should be applied where it is important to provide protection frominternal live parts and where failure of functional units being supplied from the

same busbar would cause unacceptable disruption. Because all the terminations areseparated, it is possible to isolate and work on a single functional unit.

Dorman Smith ‘LF-type’ panel board systems are supplied in Form 2 as standard,with Form 4 versions achieved with simple conversion kits. However, otherseparation forms can be provided in special cases.

With the exception of Form 1, the other separation forms have sub-categories thatpermit permutations of the general form to be configured according to therequirements for specific applications and to allow the accommodation of differenttypes of protection method. The exact form of separation provided on an assemblyis a matter for agreement between the manufacturer and the end user.

Forms of Separation

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 170/182

168

Sub-categories of Separation Forms

Main criteria Sub criteria Form Type Construction

No separation 1

Separation of Terminals for externalbusbars from conductors not 2athe functional separated fromunits busbars

Terminals for external 1 Busbar separation byconductors separated 2b insulated coveringsfrom busbars 2 Busbar separation by

rigid barriers

Terminals for externalconductors not 3a

separated from busbars

Terminals for external 1 Busbar separation byconductors separated 3b insulated coveringsfrom busbars 2 Busbar separation by

rigid barriers

Terminals for externalconductors in thesame compartmentas the associatedfunctional unit

Busbar separation by insulatedcoveringsCables may be glanded elsewhere

Busbar separation by rigid barriersCables may be glanded elsewhere

All separation by rigid barriersThe termination for eachfunctional unit has its own integralglanding facility

Busbar separation by insulatedcoveringsCables may be glanded elsewhere

Busbar separation by rigid barriersTerminals may be separated byinsulated coverings and glandedin common cabling chambers

All separation by rigid barriersCables are glanded in commoncabling chambers

All separation by rigid barriersThe termination for eachfunctional unit has its own integralglanding facility

1

2

3

4

5

6

7

4a

4bTerminals for externalconductors not in thesame compartment asthe associatedfunctional unit but inindividual, separate,enclosed protectedspaces orcompartments

Separation ofbusbars from thefunctional unitsand separation ofall functional unitsfrom one another.Separation of theterminals for externalconductors from

functional units butnot from each other

Separation ofbusbars from thefunctional units andseparation of allfunctional unitsfrom one anotherincluding terminalsfor externalconductors whichare an integralpart of the

functional unit

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 171/182

169

The EN 60529 standard describes a system for classifying degrees of protectionagainst the ingress of foreign bodies and harmful liquids. It is intended that thisstandard is applied to enclosures of low voltage (LV) electrical equipment. Theclassification scheme comprises a designation prefixed by the upper case letters’IP‘, followed by two numerals.

The first numeral designates the degree of protection with regard to solid objects;

the second numeral indicates the degree of protection against the ingress of liquid.Compliance to the standard is intended to:

• protect persons against access to hazardous parts inside enclosures and protectthe equipment inside the enclosure against the ingress of solid foreign objects.

• protect the equipment inside the enclosure against harmful ingress of liquids.

For assemblies for indoor use where there is no requirement for the protectionagainst ingress of water, the following IP codes are preferred: IP00, IP2X, IP3X,IP4X, IP5X, IP6X.

Ingress Protection

IP Protection Equivalent

0 No protection

1 Full entry of 50mm Back of sphere, but no hand contact with

hazardous parts

2 Full entry of 12.5mm Finger sphere not allowed, but no contact with hazardous parts with jointed test finger

3 2.5mm diameter Tool access probe shall

not enter

4 1mm diameter access Wire probe shall not enter

5 Limited ingress of Wire dust (no harmful

deposit)

6 Total protection Wire against dust ingress

X Not tested -

IP Protection Equivalent

0 No protection

1 Against vertically Verticalfalling water drops drips

2 As in 1, but with Slanted

enclosure tilted 15 drippingdegrees from vertical to 15

degrees from

vertical

3 Against spray to 60 Limiteddegrees from spray

vertical – limitedingress permitted

4 Against splashing Splashing from any direction – from any limited ingress direction permitted

5 Against low pressure Hosingjets from any jets fromdirection – limited anyingress permitted direction

6 Against strong jets Power from any direction hosing

from anydirection

7 Against immersion Temporary up to one metre immersion

8 Against prolonged Continuous immersion under immersion pressure

X Not tested -

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 172/182

170

The insulation distances between an MCCB and adjacent earthed metal parts andinsulators shown in the diagram below must be maintained to prevent arcing faultsoccurring due to conductive ionised gases. In cases where requirements differ fromthose illustrated here, the greater distance must be maintained. Where twodifferent YA frame devices are installed one above the other, the insulationdistance between the two should be as for the lower size of MCCB.

Exposed conductors must be insulated up to the barrier terminals. Interphasebarriers or terminal covers are recommended. However, if terminal covers are used,the exposed conductor must be insulated until it overlaps the terminal cover.

1. Insulation plate

2. Top plate (earthed metal)

3. Interphase barriers4. Front connected MCCB

5. Front connected MCCB withterminal bar

6. Rear connected type orplug-in type

7. Side panel (earthed metal)

*Note: (1) Insulate the exposed conductor until it overlaps the moulded case at theterminal or terminal cover.

A. Distance from lower breaker to exposedlive part of upper breaker terminal (frontconnected type) or from lower breaker to

end face of upper breaker (rear connectedor plug-in type)

B1. Distance from end face of breaker totop plate

B2. Distance from end face of breaker toinsulation plate

C. Gap between breakers

D. Distance from side of breaker to side panel

E. Dimensions of insulation over exposedconductors

MCCB Distances

Frame Poles A B1 B2 C D ESize

YA2N 1 50 10 10 0 25 *(1)

YA2N 3/4 50 10 10 0 25 *(1)

YA2S 3/4 50 10 10 0 25 *(1)

YA2J 3/4 75 45 25 0 25 *(1)

YA3N 1 50 40 40 0 50 *(1)

YA3N 3/4 50 40 40 0 50 *(1)

YA3S 3/4 50 40 40 0 50 *(1)

YA3J 3/4 100 80 60 0 50 *(1)

YA5N 3/4 100 80 60 0 80 *(1)

YA5H 3/4 100 80 60 0 80 *(1)

Insulation Distances for Loadline YAFrame MCCBs

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 173/182

171

YA2 1-pole Time/Current Characteristic

Loadline YA2 Frame MCCB Characteristics

YA2 1-pole Energy Let-throughYA2 3 and 4-pole Energy Let-through

YA2 3 and 4-pole Time/Current Characteristic

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 174/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 175/182

173

Loadline YA5 and Y6 Frame MCCB Characteristics

YA5 3 and 4-pole Time/Current Characteristic

YA5 3 and 4-pole Energy Let-through

Y6 Time/Current Characteristic

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 176/182

174

Loadline Y7 and Y8 Frame MCCBCharacteristics

Y7 Time/Current Characteristic

43

2

15040

30

20

108

6

54

3

2

15040

30

20

10

8

6

5

4

3

2

1

0.8

0.6

0.5

0.4

0.3

0.2

0.1

0.08

0.06

0.05

0.04

0.03

0.02

0.01

0.008

0.006

0.005

8 0

9 0

1 0 0

1 2 5

1 5

0

2 0 0

2 5

0

3 0 0

4 0 0

5 0 0

6 0 0

7 0 0

8 0 0

9 0 0

1 0 0 0

1 5

0 0

2 0 0 0

2 5

0 0

3 0 0 0 8 9

1 0

1 2

. 5

1 5

2 0

4 0

5 0

Curves based on standard settings

T

I

IG

I1

T1

I2 T2

I3TG

IP

Percent rated current of base current (I0)

Y8 Time/Current Characteristic

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 177/182

10Section

Products & Parts Locator

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 178/182

176

2IP-7-0244 116

3C345 01 124, 125

3G365 02 124, 125

AV2100 9, 118

AV2125 9, 118

AV3100 20, 118

AV3125 20, 118AV363 118

AV4100 20, 118

AV4125 20, 118

AV463 118

CBT-94F-035 123

CBT-94F-070 123

CBT-94F-105 123

CBT-94F-140 123

CI1-01-PUL 25, 51, 67, 124

CI3-01-PUL 25, 51, 67, 124

CI-MOD-01 25, 51, 67, 124, 125

CI-PUL-01 25, 51, 67, 124, 125

DA06X 8

DA09X 8

DA12X 8

DA15X 8

DA18X 8

DA22X 8

DAS08X 8

DAS11X 8

DAS14X 8

DAS17X 8

DAS20X 8

DAS24X 8

DAXD1 9

DAXEB 8

DAXEB 19

DAXSK08 8

DAXSK11 8

DAXSK14 8

DAXSK17 8

DAXSK20 8

DAXSK24 8

DAXTP 19

DBMSB 18, 26

DBS18X 18

DBS36X 18

DBTE04X 19

DBTE06X 19

DBTE08X 19

DBTE12X 19

DBTE16X 19

DBTE20X 19

DBTE24X 19

DBX04R 18

DBX06R 18

DBX08R 18

DBX12R 18

DBX16R 18

DBX20R 18

DBX24FK 19

DBX24R 18

DBX24WL 19

DBXBH 8, 11, 19

DBXBM 8, 11, 19

DBXBP 8, 11, 19

DBXC06NAH06CA 27

DBXC06NAV04CA 27DBXC08NAV06CA 27

DBXC08NJV06CJ 27

DBXC08NNV06CA 27

DBXC12NAH12CA 27

DBXC12NAV08CA 27

DBXC12NJV08CJ 27

DBXC12NNV08CA 27

DBXCKR 20

DBXCL 8, 19, 38, 39, 41, 60

DBXD0 9, 21

DBXD1 21

DBXD2 21

DBXE08NAH08NA 27

DBXE08NAV06NA 27

DBXE08NJV06NJ 27

DBXE12NAV08NA 27

DBXE12NJV08NJ 27

DBXEP 19

DBXJK 19

DBXL 8, 19

DBXLSA1 20

DBXLSA2 20

DBXPL 8, 19, 38, 39, 41, 60

DBXSKA 19

DBXT06 19

DBXT12 19

DBXT18 19

DBXT24 19

DBXTS 19

DBXW16 26

DBXW16T 26

DBXW24 26

DBXWP125 26

DBXWP250 26

DBXYA3 18

DRK-1P-230-D63 25, 127

DRK-1PCT-240 127

DRK-3P-400-D100 25, 127

DRK-3PCT-415 11, 25, 40, 127

DRK-3PCT-415-LCD 11, 25, 127

DRT-DW2R 24, 118

DSPE600 116

DSPE600N 116

DSPE600R 116

DSPM1P 115

DSPM1PN 9, 115

DSPM1PNR 115

DSPM3P 115

DSPM3PN 21, 115

DSPM3PNR 115

DSPML 9, 21, 115

DSPMNE 9, 21, 115

DSPT3PN 117

EE100/100/2 9, 24, 97

EE100/100/4 20, 24, 97

EE100/30/2 9, 24, 97

EE100/30/4 20, 24, 97

EE100/300/4 20, 24, 97

EE2P20CC 24, 118EE2P20CO 24, 118

EE40/100/2 97

EE40/100/4 20, 24, 97

EE40/30/2 24, 97

EE40/30/4 20, 24, 97

EE40/300/4 97

EE4P25CC 24, 118

EE4P25CO 24, 118

EE4P40CC 24, 118

EE4P40CO 24, 118

EE4P63CC 24, 118

EE4P63CO 20, 24, 118

EE63/100/2 9, 24, 97

EE63/100/4 20, 24, 97

EE63/30/2 9, 24, 97

EE63/30/4 20, 24, 97

EE63/300/2 9, 24, 97

EE63/300/4 20, 24, 97

EE80/30/2 9, 24, 97

EES100/100/2 9, 24, 97

EES100/100/4 20, 24, 97

EES63/100/4 20, 24

ELR1 122

FS2 85, 87

HB125CSB 85

HB200CSB 85

HB400CSB 85

HB800CSB 85

HBE3P32N 84

HBF3P100N 84

HBF3P100N 20

HBF3P125N 84

HBF3P160N 84

HBF3P200N 84

HBF3P200N 20

HBF3P63N 84

HBF4P100 84

HBF4P200 84

HBK3P315N 84

HBL3P400N 84

HBL4P400 84

HBN3P630N 84

HBN3P800N 84

HBN4P800 84

HEL32 85

HFL200A 49, 85, 87

HFL63 49, 85, 87

HLL400 49, 85, 87

HNL800 49, 85, 87

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 179/182

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 180/182

178

LEBM6 50, 66

LECK2SM 50, 67

LECK2SP 50, 67

LECM1 50, 67

LECM2 50, 67

LECM3 50, 67

LECM4 50, 67

LECM5 50, 67

LECM6 50, 67LECM8 50, 67

LECMD2 51, 67

LECMD3 51, 67

LECMD4 51, 67

LECMD5 51, 67

LECMD6 51, 67

LECMD8 51, 67

LF1F4A 48, 64

LF1F8A 48, 64

LF806A 48

LF806YA 64

LF810A 48

LF810YA 64

LFS41A 48

LFS41YA 64

LFS42A 48

LFS42YA 64

LFXHBA 48

LGES 60

LGES 61

LLMV 24, 118

LM10 114

LM20 114

LM30 114

LM3P20 114

LM3P30 114

LM40 114

LM50 114

LM60 114

LMMB2 114

LMMB3 114

LW3 114

M30-DINCLIP 11

M30-DINCLIP 119

M3N1-25-100/5 40, 120

M3N1-25-125/5 40, 120

M3N1-25-160/5 120

M3N1-25-60/5 40, 120

M3N1-35-100/5 26, 51, 67, 120

M3N1-35-125/5 26, 51, 67, 120

M3N1-35-160/5 120

M3N1-35-200/5 26

M3N1-35-250/5 26

M3N1-45-250/5 40

M3N1-45-250/5 120

M3N1-45-300/5 120

M3N1-45-400/5 40

M3N1-45-400/5 120

M3N1-45-500/5 120

M3N1-45-630/5 120

M50-DINCLIP 119

M53J-100/5D 119

M53J-125/5D 119

M53J-200/5D 119

M53J-250/5D 119

M53Q-100/5 11, 119

M53Q-125/5 11, 119

M55E-30/5 119

M55E-60/5 119M63N-400/5 51, 67, 119

M63N-600/5 51, 67

M93L-600/5 119

M93L-800/5 51, 67

MB5D-800/5 119

MCFMY6 64

MMS15Y 64

MXD06 48, 64

MXD10 48, 64

MXEPF 60

PB206YA 38

PB208YA 38

PB212YA 38

PB406YA 39

PB408YA 39

PB412YA 39

PB416YA 39

PB4PNC250 38, 41

PB4PNC400 39, 41

PBSM 40

PBWCT 40

PBWI 40

PBWM6 40

PBWP 40

PBYA2CSB 38

PBYA2MB 40

PBYA2OG 38

PBYA2SC24 38

PS100NY 90

PS125NY 90

PS16NY 90

PS25NY 90

PS32NY 90

PS40NY 90

PS63NY 90

PS80NY 90

RI3-01 11, 25, 40, 128

S1PB06 96

S1PB10 96

S1PB16 96

S1PB20 96

S1PB25 96

S1PB32 96

S1PB40 96

S1PB50 96

S1PB63 96

S1PC06 96

S1PC10 96

S1PC16 96

S1PC20 96

S1PC25 96

S1PC32 96

S1PC40 96

S1PC50 96

S1PC63 96

S1PD06 96

S1PD10 96S1PD16 96

S1PD20 96

S1PD25 96

S1PD32 96

S1PD40 96

S1PD50 96

S1PD63 96

S2PB06 96

S2PB10 96

S2PB16 96

S2PB20 96

S2PB25 96

S2PB32 96

S2PB40 96

S2PB50 96

S2PB63 96

S2PC06 96

S2PC10 96

S2PC16 96

S2PC20 96

S2PC25 96

S2PC32 96

S2PC40 96

S2PC50 96

S2PC63 96

S2PD06 96

S2PD10 96

S2PD16 96

S2PD20 96

S2PD25 96

S2PD32 96

S2PD40 96

S2PD50 96

S2PD63 96

S3PB06 96

S3PB10 96

S3PB16 96

S3PB20 96

S3PB25 96

S3PB32 96

S3PB40 96

S3PB50 96

S3PB63 96

S3PC06 96

S3PC10 96

S3PC16 96

S3PC20 96

S3PC25 96

S3PC32 96

S3PC40 96

S3PC50 96

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 181/182

179

S3PC63 96

S3PD06 96

S3PD10 96

S3PD16 96

S3PD20 96

S3PD25 96

S3PD32 96

S3PD40 96

S3PD50 96S3PD63 96

SAUX2F 49, 85, 87

SAUX2N 49, 85, 87

SAUX4F 49, 85, 87

SAUX4N 49, 85, 87

SAUX6N 49, 85, 87

SC1-100/5A 121

SC1-150/5A 121

SC1-200/5A 121

SC1-250/5A 121

SC1-300/5A 121

SC1-400/5A 121

SC2-250/5A 121

SC2-300/5A 121

SC2-400/5A 121

SC3-1000/5A 121

SC3-250/5A 121

SC3-300/5A 121

SC3-400/5A 121

SC3-500/5A 121

SC3-600/5A 121

SC3-750/5A 121

SC3-800/5A 121

SC4-1000/5A 121

SC4-1200/5A 121

SC4-1250/5A 121

SC4-1500/5A 121

SC4-1600/5A 121

SC4-500/5A 121

SC4-600/5A 121

SC4-750/5A 121

SC4-800/5A 121

SCLK 85, 87

SF1P100N 49

SF1P125N 49

SF1P160N 49

SF1P200N 49

SF3P100N 49, 86

SF3P125N 49, 86

SF3P160N 49, 86

SF3P200N 49, 60, 86

SF3P63N 49, 86

SF4P100 49, 86

SF4P125 49, 86

SF4P160 49, 86

SF4P200 49, 60, 86

SF4P63 49, 86

SFFS125 87

SFFS200 87

SFTB 49, 87

SFTSL 87

SFTSS 49, 87

SHA1 87

SHA2 87

SHA3 87

SHA4 87

SK3P315N 86

SK4P315 86

SKFS 87

SKTB 87SKTS 87

SL3P400N 48, 60, 64, 86

SL4P400 48, 60, 86

SL4P400N 64

SLFS 87

SLTB 49, 87

SLTS 49, 87

SN3P630N 48, 66, 86

SN3P800N 48, 66, 86

SN4P630 48, 86

SN4P630N 66

SN4P800 48, 86

SN4P800N 66

SNCET 48, 49, 66, 87

SNFS 87

SNTS 49, 87

SRLB100 87

SRLB125 87

SRLB160 87

SRLB200 87

SRLB315 87

SRLB400 87

SRLB63 87

SRLB630 87

SRLB800 87

SXT127 87

SXT160 87

SXT227 87

SXT260 87

T1PD40 10, 22, 94

T1PD50 10, 22, 94

T1PD63 10, 22, 94

T2PD40 94

T2PD50 94

T2PD63 94

T3PD40 22, 94

T3PD50 22, 94

T3PD63 22, 94

XPL 11, 23, 95

Y2DL 41

Y5CF 110

Y5DCLCAM 110, 112, 113

Y5TB3P 110, 112, 113

Y5TB4P 110, 112, 113

Y6AC400 111

Y6AC630 111

Y6AC800 111

Y6AUX1 110

Y6AUX2 110

Y6AUXAL 110

Y6B3P400D 60, 66

Y6B3P630D 60, 109

Y6B3P800D 109

Y6B4P400D 60, 66

Y6B4P630D 60, 109

Y6B4P800D 109

Y6CC4P 110Y6CLDS1 110

Y6CLDS2 110

Y6DL 110

Y6H3P400T5 60, 66, 109

Y6H3P630E 109

Y6H3P630T5 60

Y6H3P800E 109

Y6H3P800T5 66, 109

Y6H4P400T5 60, 66, 109

Y6H4P630E 109

Y6H4P630T5 60

Y6H4P630T5 66, 109

Y6H4P800E 109

Y6H4P800T5 66, 109

Y6HE 110

Y6J3P630E 109

Y6J3P800E 109

Y6J4P630E 109

Y6J4P800E 109

Y6K3P400T5 109

Y6K3P630T5 109

Y6K3P800T5 109

Y6K4P400T5 109

Y6K4P630T5 109

Y6K4P800T5 109

Y6MA110 110

Y6MA240 110

Y6MMS 110

Y6MR 110

Y6MW10 110

Y6MW15 110

Y6NL 110

Y6RH1 110

Y6RH2 110

Y6ST115AC 110

Y6ST24DC 110

Y6ST480AC 110

Y6TS3P 110

Y6TS4P 110

Y6UVR120AC 110

Y6UVR240AC 110

Y6UVR24DC 110

Y6UVR450AC 110

Y7AUX3P1 112, 113

Y7AUX3P2 112, 113

Y7AUX3PAL 112, 113

Y7AUX4P1 112, 113

Y7AUX4P2 112, 113

Y7AUX4PAL 112, 113

Y7B3P1250D 112

Y7B3P800D 60

7/21/2019 TE Dorman Smith Product Portofolio 2011

http://slidepdf.com/reader/full/te-dorman-smith-product-portofolio-2011 182/182

Y7B4P1250D 112

Y7B4P800D 60

Y7CL 112, 113

Y7DL 112, 113

Y7J3P1000E 60, 112

Y7J3P1250E 112

Y7J4P1000E 60, 112

Y7J4P1250E 112

Y7MA110 112, 113Y7MA240 112, 113

Y7NL 112, 113

Y7ST115AC 112, 113

Y7ST24DC 112, 113

Y7ST480AC 112, 113

Y7TS3P 112, 113

Y7TS4P 112, 113

Y7UVR120AC 112, 113

Y7UVR240AC 112, 113

Y7UVR24DC 112, 113

Y7UVR450AC 112, 113

Y8B3P1600D 113

Y8B3P1600DDO - 113

Y8B3P1600DR - 113

Y8B4P1600D 113

Y8K3P1600E 113

Y8K3P1600EG 113

Y8K3P1600ER 113

Y8K4P1600E 113

YA2N4P50T 103

YA2N4P63T 103

YA2S3P100T 103

YA2S3P125T 103

YA2S3P50T 103

YA2S3P63T 103

YA2S4P100T 103

YA2S4P125T 103

YA2S4P50T 103YA2S4P63T 103

YA2TS1P 41

YA2TS3P 41

YA34J100T 105

YA34J125T 105

YA34J160T 105

YA34J200T 105

YA34J250T 105

YA34J63T 105

YA3B3P250D 21, 38, 60, 105

YA3B4P250D 21, 38, 60, 105

YA3CC3P 41, 62, 106

YA3CC4P 62, 106

YA3F4BP 64

YA3J3P100T 62, 65, 105

YA3J3P125T 62, 65, 105

YA3J3P160T 62, 65, 105

YA3J3P200T 62, 65, 105

YA3J3P250T 62 65 105

YA3N4P160T 21, 38, 60, 105

YA3N4P200T 21, 38, 60, 105

YA3N4P20T 105

YA3N4P250T 21, 38, 60, 105

YA3N4P32T 105

YA3N4P50T 63, 105

YA3N4P63T 21, 105

YA3NL 18, 60

YA3PB3P 106YA3PB4P 106

YA3PRA3P 106

YA3PRA4P 106

YA3PT3P 106

YA3PT4P 106

YA3PXT3P 106

YA3PXT4P 106

YA3R1 106

YA3R2 106

YA3RT3P 106

YA3RT4P 106

YA3S3P100T 62, 65, 105

YA3S3P125T 62, 65, 105

YA3S3P160T 62, 65, 105

YA3S3P200T 62, 65, 105

YA3S3P250T 62, 65, 105

YA3S3P50T 62, 65, 105

YA3S3P63T 62, 65, 105

YA3S4P100T 105