tank cooling calculation

2
Calculation for 9000 Gallons Roof Tank Cooling System Description In Summer Tank Volume, Gallons 9000 (34,000 lits) Water Temperature Required 28 deg C/ Incoming Water Temperature 43 deg C Desired Temperature Difference 15 o C Formulae Q = m x Cp x (T2-T1) Cooling Capacity kW = Volume of Water lits x Sp x (T2-T1) o C / 860 x T Sp, Specific heat of water = 1.0 Kcal / Kg. x o C T, initial cooling period = 6 hours COOLING LOAD T2 (Incoming water temp.) = 43 o C T1 (reqd. water temp.) = 28 o C T2-T1 = 15 o C Therefore, kW = 34,000 x 1 x 15/ 860 x 6 = 98.85 kW To cool in 6 hour, TR = 28.25 Tons (98.85 kW) Note: Total water flow rate can be calculated by = Total tank volume / cooling time i.e. 34000/6 = 5667 Lit/hr Units suggested 2 units of 50 kW each with flow 2.9 m3/hr and ∆T 15°C.

Upload: karthy-ganesan

Post on 19-Oct-2015

871 views

Category:

Documents


62 download

DESCRIPTION

cooling capacity calculation

TRANSCRIPT

  • Calculation for 9000 Gallons Roof Tank Cooling System

    Description

    In Summer

    Tank Volume, Gallons 9000 (34,000 lits)

    Water Temperature Required 28 deg C/

    Incoming Water Temperature 43 deg C

    Desired Temperature Difference 15 oC

    Formulae

    Q = m x Cp x (T2-T1)

    Cooling Capacity kW = Volume of Water lits x Sp x (T2-T1) oC / 860 x T

    Sp, Specific heat of water = 1.0 Kcal / Kg. x oC

    T, initial cooling period = 6 hours

    COOLING LOAD

    T2 (Incoming water temp.) = 43 o C

    T1 (reqd. water temp.) = 28 o C

    T2-T1 = 15o C

    Therefore, kW = 34,000 x 1 x 15/ 860 x 6

    = 98.85 kW

    To cool in 6 hour, TR = 28.25 Tons (98.85 kW)

    Note:

    Total water flow rate can be calculated by = Total tank volume / cooling time i.e. 34000/6 = 5667 Lit/hr

    Units suggested 2 units of 50 kW each with flow 2.9 m3/hr and T 15C.

  • Calculation for 16000 Gallons Roof Tank Cooling System

    Description

    In Summer

    Tank Volume, Gallons 16000 (60,600 lits)

    Water Temperature Required 28 deg C/

    Incoming Water Temperature 43 deg C

    Desired Temperature Difference 15 oC

    Formulae

    Q = m x Cp x (T2-T1)

    Cooling Capacity kW = Volume of Water lits x Sp x (T2-T1) oC / 860 x T

    Sp, Specific heat of water = 1.0 Kcal / Kg. x oC

    T, initial cooling period = 6 hours

    COOLING LOAD

    T2 (Incoming water temp.) = 43 o C

    T1 (reqd. water temp.) = 28 o C

    T2-T1 = 15o C

    Therefore, kW = 60,600 x 1 x 15/ 860 x 6

    = 176.20 kW

    To cool in 6 hour, TR = 50.50 Tons (176.50 kW)

    Note:

    Total water flow rate can be calculated by = Total tank volume / cooling time i.e. 60,600/6 = 10,100 Lit/hr

    Units suggested 2 units of 80 kW each with flow 4.6 m3/hr and T 15C.