TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR CONDITIONER INSTALLATION MANUAL © 2005 McQuay International Group: WSHP Part Number: A08019025766 Date: SEPTEMBER 2005 IM-5WST-0905-McQuay

Upload: dinhnhi

Post on 15-Mar-2018

228 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

TANDEM WATER SOURCEHEAT PUMP SPLIT TYPEAIR CONDITIONER

INSTALLATION MANUAL

© 2005 McQuay International

Group: WSHP

Part Number: A08019025766

Date: SEPTEMBER 2005

IM-5WST-0905-McQuay

Page 2: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766
Page 3: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

i

OUTLINE AND DIMENSIONS / DISPOSITION ET DIMENSIONS /AUSLEGUNG UND ADMESSUNG / INGOMBRI E DIMENSIONI / ESQUEMA Y DIMENSIONES /

СХЕМА И РАЗМЕРЫ

Model A B C D E F G H I J K L M N O P (ID)5WST40AR 920 151 692 77 511 549,5 1013,8 440 450 130 61,5 102 100 80 75 175WST50AR / 60AR 920 162 682 76 610 648,5 1014,6 504 550 130 61,5 107 100 80 75 17

5WST 40AR / 50AR / 60AR

All dimensions in mmFigure 1

All dimensions in mm

800

500

800

1200

INSTALLATION LOCATION / SÉLECTION DE L’EMPLACEMENT / INSTALLATION LAGE /POSIZIONAMENTO ED INSTALLAZIONE / UBICACION DE LA UNIDAD /

МЕСТО УСТАНОВКИ

Figure 2

I

J

LM

NO

H

G

E F

ACB D

PK

Page 4: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

ii

! Caution Sharp edges and coil surfaces are potential locations which may causeinjury hazards. Avoid from being in contact with these places.

! Avertissement Les bords coupants et les surfaces du refroidisseur tuulaire présententun risque de blessure. Mieux vaut éviter le contact avec ces endroits.

! Vorsicht Scharfe Kanten und Wärmetauscherflächen stellen eine Gefahrenquelle dar.Jeglicher Kontakt mit diesen Stellen ist zu vermeiden.

! Cautela Per preservarsi da eventuali ferite, evitare di toccare gli spigoli affilali e lasuperficie della serpentina.

! Cuidado Los Bordes afilados y la superficie del serpentín pueden producir lesiones.Evite tocarlos.

This product is subjected to Waste of Electrical and Electronic Equipment Regulations (WEEERegulations). The waste product shall be separately collected by specific collection and treatment centre.Please refer to local authorithy for these centres. This is only applicable to European Union countries.

Ce produit est soumis à la rà érr é é électriques eté éé ê é éé

é éé éé é îître ces centres. Ceciîîest uniquement applicable aux pays de l'Union Européenne.

Questo prodotto è soggetto alle disposizioni RAEE (Rifiuti di apparecchiature elettriche ed elettroniche).à

à locali. Questa disposizioneà è valida solamente i paesidell’U.E.

éctrico y Electrónico en materia deññ á íficoíí

de colecciósolamente aplicable a los países de la Unión Europea.

Dieses Produkt unterliegt den Bestimmungen zur Entsorgung von elektrischen und elektronischenGerää ätesää

üüll bei Ihrer ö ü öändiges Abfall-Amt. Dieserää

Hinweis gilt nur füff r L äischen Union.

Процесс утилизации данного продукта регулируется правилами по утилизацииотходов и (WEEE Regulations).

и, . Эти

правила Европейского .

NOTICE

Page 5: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

iii

Figure 3

5WST 40AR / 50AR / 60AR

BALANCING VALVEROBINET D’EQUILIBRAGEDRUCKAUSGLEICHSVENTILVALVOLA DI BILANCIAMENTOVÁLVULA DE EQUILIBRADOБАЛАНСИРОВОЧНЫЙ КЛАПАН

Figure 4

1: SHUT OFF VALVESOUPAPE D’ARRETSPERRVENTILVALVOLA DI CHIUSURALLAVE DE PASOОТСЕЧНОЙ КЛАПАН

2: WATER OUTSORTIE D'EAUWASSERABLAUFACQUA IN USCITAAGUA FUERAВЫХОД ВОДЫ

3: WATER INENTREE D'EAUWASSERZULAUFACQUA IN ENTRATAAGUA ENВХОД ВОДЫ

4: Y-STRAINEREPURATEUR EN YY-SIEBFILTRO A YFILTRO-YУ-ОБРАЗНЫЙ ФИЛЬТР

5: SHUT OFF VALVESOUPAPE D’ARRETSPERRVENTILVALVOLA DI CHIUSURALLAVE DE PASOОТСЕЧНОЙ КЛАПАН

1

2

34

5

THREADED ROD

HEX. NUT

WASHERVIBRATION ISOLATOR

HEX. NUTWASHER

6

6: WATER LOOPWATER LOOPWATER LOOPWATER LOOPWATER LOOPWATER LOOP

Page 6: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

iv

1: VACUUM PUMPPOMPE À VIDEVAKUUMPUMPEPOMPA A VUOTOESTRAER AIREВАКУУМНЫЙ НАСОС

2: LIQUID VALVEROBINET DE LIQUIDEFLÜSSIGKEITSVENTILVALVOLA LIQUIDOVÁLVULA DEL LIQUIDOЖИДКОСТНОЙ ВЕНТИЛЬ

3: GAS VALVE (3-WAY)ROBINET DE GAZ (3 DIRECTIONS)GASVENTIL (3-WEGE)VALVOLA GAS (A TRE VIE)VÁLVULA DE GAS (3-DIRECCIONES)ГАЗОВЫЙ ВЕНТИЛЬ (трехходовой)

=

2

3

HANDLE LoPOIGNÉE LoSCHALTER LoMANOPOLA LoHANDLE LOКЛАПАН Низ

HANDLE Hi (ALWAYS CLOSED)POIGNÉE Hi (TOUJOURS FERMÉE)SCHALTER Hi (STETS GESCHLOSSEN)MANOPOLA Hi (SEMPRE CHIUSA)HANDLE HI (SIEMPRE CERRADO)КЛАПАН Выс. (ВСЕГДА ЗАКРЫТ)

1

RUBBER BUSH

Figure 5

Figure 6

Figure 7

ENSURE WATER VALVE ADAPTORS AREALIGNED TO THE CENTER WITHOUT TOUCHING(min 2mm) THE RUBBER BUSH WHEN MAKINGPIPING CONNECTION.

Page 7: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

v

1

2

3

4

7 ~ 7

599

(

)

-

,

+

%

&

#

$

"

6

!8 ! 8ss

Figure 8

COOLING OPERATION

HEATING OPERATION

SCHEMATIC DIAGRAM

NOTE:

1. GAS PIPING / TUYAUTERIE DU GAZ / GASLEITUNG / TUBATURE DEL GAS / TUBOS DE GAS / ГАЗОВЫЙ ТРУБОПРОВОД2. FAN COIL UNIT / VENTILO-CONVECTEUR / LUFTBEHANDLUNGSAGGREGAT / UNITÀ FAN COIL / VENTILOCONVECTOR /

ФАНКОЙЛ3. FAN MOTOR / MOTEUR DU VENTILATEUR / GEBLÄSEMOTOR / MOTORE VENTOLA / MOTOR DE VENTILADOR /

ДВИГАТЕЛЬ ВЕНТИЛЯТОРА4. LIQUID PIPING / TUYAUTERIE LIQUIDE / FLÜSSIGKEITSLEITUNG / TUBATURE DEL LIQUIDO / TUBOS DE LÍQUIDO /

ЖИДКОСТНЫЙ ТРУБОПРОВОД5. 4 WAY VALVE / ROBINET A 4 VOIES / VIERWEGEVENTIL / VALVOLA A 4 VIE / VÁLVULA DE 4 VÍAS / 4-ХОДОВЫЙ ВЕНТИЛЬ6. COMPRESSOR / COMPRESSEUR / KOMPRESSOR / COMPRESSORE / COMPRESOR / КОМПРЕССОР7. STRAINER / EPURATEUR / SIEB / FILTRO / FILTRO / СЕТЧАТЫЙ ФИЛЬТР8. SOLENOID VALVE / SOLENOID VALVE / SOLENOID VALVE / SOLENOID VALVE / SOLENOID VALVE/SOLENOID VALVE9. OIL RETURN CAP. TUBE / OIL RETURN CAP. TUBE / OIL RETURN CAP. TUBE / OIL RETURN CAP. TUBE /

OIL RETURN CAP. TUBE / OIL RETURN CAP. TUBE10. CHECK VALVE / CLAPET DE NON-RETOUR / ABSPERRVENTIL / VALVOLA DI NON RITORNO / VÁLVULA DE RETENCIÓN /

ОБРАТНЫЙ КЛАПАН11. THERMOSTATIC EXPANSION VALVE / DÉTENDEUR THERMOSTATIQUE / THERMOSTATISCHES EXPANSIONSVENTIL /

VALVOLA DI ESPANSIONE TERMOSTATICA / VÁLVULA TERMOSTÁTICA DE ESPANSIÓN / ТЕРМОРЕГУЛИРУЮЩИЙ ВЕНТИЛЬ12.TUBE IN TUBE HEAT EXCHANGER / TUBE D’ECHANGEUR THERMIQUE / DOPPELROHRWÄRMETAUSCHER /

SCAMBIATORE DI CALORE TUBO IN TUBO / TUBO EN TERMOPERMUTADOR / ТЕПЛООБМЕННИК “ТРУБА В ТРУБЕ”13. WATER INLET / PRISE D’ENTRÉE D’EAU / WASSEREINTRITTSÖFFNUNG / INGRESSO ACQUA / ENTRADA DEL AGUA /

ВОДОПРИЕМНИК14. WATER OUTLET / PRISE DE SORTIE D’EAU / WASSERAUSTRITTSÖFFNUNG / USCITA ACQUA / SALIDA DEL AGUA /

ВОДОВЫПУСК15. WATER SENSOR / CAPTEUR D’EAU / WASSERSENSOR / SENSORE ACQUA / SENSOR DEL AGUA / WATER SENSOR /

ДАТЧИК ВОДЫ16. HIGH PRESSURE SWITCH / PRESSOSTAT HAUTE PRESSION / HOCHDRUCKSCHALTER / INTERRUTTORE ALTA PRESSIONE/

INTERRUPTOR DE ALTA PRESIÓN / ПЕРЕКЛЮЧАТЕЛЬ ВЫСОКОГО ДАВЛЕНИЯ17. LOW PRESSURE SWITCH / PRESSOSTAT BASSE PRESSION / NIEDERDRUCKSCHALTER /

INTERRUTTORE BASSA PRESSIONE / INTERRUPTOR DE BAJA PRESIÓN / ПЕРЕКЛЮЧАТЕЛЬ НИЗКОГО ДАВЛЕНИЯ18. TXV BY PASS CAP. TUBE / CONDENSATEUR DE DÉCOUPLAGE TXV / TXV BYPASS KAPILLARROHR /

TUBO COPERTO BY-PASS TXV / TXV POR PASS CAP. TUBO / TXV ОБХОД ЕМНОСТИ ТРУБКИ19. 4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) / 4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) /

4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) / 4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) /4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) / 4 WAY VALVE (FUNCTIONING AS BI-FLOW SOLENOID VALVE) /

20. ACCUMULATOR / ACCUMULATOR / ACCUMULATOR / ACCUMULATOR / ACCUMULATOR / ACCUMULATOR21. SUCTION CAP. TUBE / SUCTION CAP. TUBE / SUCTION CAP. TUBE / SUCTION CAP. TUBE / SUCTION CAP. TUBE /

SUCTION CAP. TUBE

5WST 40AR / 50AR / 60AR

Page 8: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

vi

5WST 40AR / 50AR / 60AR

Figure 9

POWER SOURCE 380-410V/3PH/50Hz

R S T N

RE

D

WH

ITE

TH

RE

D

WH

ITE

BLU

E

RE

D

WH

ITE

BLU

EB

LUE

REDRED

BROWNK3

41

56

S.V.3

BLUEBLACK

BLUE

4WV

7ABLUE

BLUE

GREEN/YELLOW

BLACK

BLUE

A 4WV COMP 1 COMP 2 L N

G/Y

PUR

PLE

PUR

PLE

RE

D

BLU

E

BLU

E

BLUE

21

43

65

87

BLU

E

BLU

E

HP

LP

BLUE

BLUEBLU

E

S.V.2

RELAY(O.R.)

RELAY(S.V.1)BLUE

S.V.1

BLUE

BLU

E BLUE

BLUE

REDCOMP. 1

S

RCBLUE

REDCOMP. 2

S

RC

K1

1

(TO FAN COIL UNIT)

RED

BLU

E

BLUE

RE

D

RED

3 5 13

2 4 6 14

A1

A2

K2

1 3 5 13

2 4 6 14

A1

A2

RED

RED

RED RED RELAY(S.V.2)

1 23 4

5 67 8

NOTE:1) K1, K2 - MAG. CONTACTOR2) K3 - RELAY

1 23 4

5 67 8

BLU

E

RED REDRED

Page 9: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

En

gli

s h

This manual provides the procedures of installation to ensure a safe and good standard of operation for WaterSource Heat Pump split type unit.Special adjustment may be necessary to suit local requirements.

Before using the Water Source Heat Pump split type unit, please read this instruction manual carefully and keepit for future reference.

INSTALLATION MANUAL

TANDEM WATER SOURCE HEAT PUMP SPLIT TYPEAIR CONDITIONER

Part No.: A08019025766

MODEL

R410A

5WST40AR / M5WST040AR

5WST50AR / M5WST050AR

5WST60AR / M5WST060AR

IM-5WST-0905 (0)-McQuay

! WARNING• Installation and maintenance should be performed by qualified persons who are familiar with local code and

regulation, and experienced with this type of appliance.

Page 10: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-1

! CAUTIONPlease take note of the following important points when installing.

• Do not install the unit where leakage of flammable gas may occur.

If gas leaks and accumulates around the unit, it may cause fire ignition.

• Do not overcharge the unit.

This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.

INDEX- Outline And Dimensions page i- Installation Location page i- Schematic diagram page v- Wiring Diagram page vi- Installation Location page 1- Unit Installation page 1- Physical Data page 1- Water Piping And Fitting page 2- Refrigerant Piping page 2- Flare work page 2- Vacuuming page 3- Tightening Torque page 3

- Vacuuming And Charging page 3- Electrical And Wiring page 4- Electrical Data page 4- Recommended Cable Sizes page 4- Special Precautions When Dealing With R410A Unit page 4- Control Operation Guide page 5- Unit Operation Limits page 5- System Cleaning And Flushing page 5- Unit Start Up And Operation page 6- Service And Maintenance page 6- Troubleshooting page 7

INSTALLATION LOCATION

• This unit is designed for indoor installation only.• Installation work should be done by authorized dealer or qualified contractor.• Install the unit at a suitable minimum distance or shortest path to the coupling fan coil unit.• There should be sufficient space for piping connection, service and maintenance. (Refer to Figure 2)• The area should be isolated from vibration and noise.• Ensure the area is free from water leakage.

UNIT INSTALLATION

• This unit will be mounted on the ceiling by the support of four threaded rods. (Refer to Figure 4)• Ensure that the supports are strong enough and properly anchored to withstand the weight of the unit.• Use isolator rubber (natural rubber) with hardness of 35° for better noise and vibration control.• Do not locate the drainage system at any point above the drain connection.

PHYSICAL DATA

Model 5WST40AR 5WST50AR 5WST60ARNominal Cooling Capacity kW 10.84 13.48 15.53

Nominal Heating Capacity kW 11.72 14.65 16.71

Unit Weight kg 105.0 134.0 134.0

Refrigerant Charge R410A kg 1.925 2.450 3.500

Compressor Rotary Compressor

Refrigerant CircuitLiquid valve connection inches 3/8 3/8 3/8

Gas valve connection inches 5/8 5/8 3/4

Service port connection (UNF-20) inches 1/2 1/2 1/2

Refrigerant - Water Heat Exchanger Tube In Tube

Water inlet (BSP)MALE inches 3/4 3/4 3/4

Water outlet (BSP)MALE inches 3/4 3/4 3/4

Nominal Water pressure drop kPa 12.03 15.50 22.21

Nominal Water flow rate m3/h 2.30 2.90 3.45

Drain Pipe ConnectionSteel Pipe inches 3/4 3/4 3/4

Page 11: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-2

En

gli

s h

WATER PIPING AND FITTING

• Install a 40 – 60 mesh strainer to ensure water quality is good.• Water pipe materials recommended are black steel pipe and copper pipe.• All piping connections must be properly and firmly connected. Do not over-tighten the connections.• Users are recommended to install the pipes as shown in Figure 4 & 5.• The piping need to be cleaned and flushed prior to operation.• Air vents must be installed at the highest position while a drainage system at the lowest position of the water circuit.

REFRIGERANT PIPING

• Do not use contaminated, dented or used copper tubing.• Do not use copper tubes with less than 0.8 mm thickness.• Use a flare tool specially for R410A.• Do not use mineral oil on flare part.• Use proper torque wrench to tight the flare nuts. If the torque strength is weak, gas leakage may occur. If it is too tight, the

flare nut may crack and it may be non-removable.• Use a vacuum pump with a back flow preventing adapter to prevent the vacuum pump oil mix with R410A which will

create sludge and damage the equipment.• Vacuum unit thoroughly to -76cmHg.• Insulate the piping to prevent capacity losses and water condensation.

FLARE WORK• Use either a flare tool specially for R410A or a conventional type. Head project dimension may differ according to type of

flare tool.• Flare end diameter is also different for R410A. Flare section should be uniform or even. Crack on the flare section or burr

on the flare edge is not acceptable. Make new flare tubing again to prevent potential gas leak.

HEAD PROJECTION DIMENSION Diameter A(mm)

in mmClutch Type ConventionalFor R410A Clutch type

1/4 6.35 0 – 0.5 0.7 – 1.33/8 9.52 0 – 0.5 0.7 – 1.31/2 12.7 0 – 0.5 0.7 – 1.35/8 15.88 0 – 0.5 0.7 – 1.33/4 19.05 0 – 0.5 0.7 – 1.3

FLARE DIE

COPPER TUBE

COPPER TUBE

FLARE NUT

B

D

Diameter, D Flare End Diameter, Bin mm

1/4 6.35 9.13/8 9.52 13.21/2 12.7 16.65/8 15.88 19.73/4 19.05 24.0

Refrigerant Piping Length, Elevation And Bends• When piping length becomes too long, both the capacity and compressor reliability drop.• As the number of bends increases, system-piping resistance to the refrigerant flow increase thus lowering the capacity of the

unit and as a result the compressor may become defective.• Always choose the shortest path and follow the recommendation as tabulated below.

5WST40AR 5WST50AR 5WST60ARMax. Length, L 35 m 35 m 35 mMax. Elevation, H 10 m 10 m 10 mMax. No. of bends 10 10 10Liquid Valve Size 9.52 mm (3/8") 9.52 mm (3/8") 9.52 mm (3/8")Gas Valve Size 15.88 mm (5/8") 15.88 mm (5/8") 19.05 mm (3/4")

!!!!! CAUTION• Connection service port at the gas valve is 1/2" UNF-20. It is different from the conventional R22 or R407C connec-

tion. This is to prevent wrong refrigerant charging into the system.• Beware that R410A standard operating pressure is about 1.6 times higher than R22.

Page 12: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-3

Models gram/meter 5WST40AR 47.5 5WST50AR 47.5 5WST60AR 47.5

Additional Charge• The pre-charged of R410A in the Water Source Heat Pump unit is suitable for standard pipe of length:-

a) 5 meter for 5WST40AR/50AR/60ARWhen the piping is more than the above stated standard pipe length, kindly add additional charge referring to the table below.

TIGHTENING TORQUE

Use proper torque wrench to tight the flare nuts. If the torque strength is weak, gas leakage may occur. If it is too tight, the flarenut may crack and it may be non-removable.

Diameter Torque (Nm)in mm

1/4 6.35 18

3/8 9.52 421/2 12.7 55

5/8 15.88 65

3/4 19.05 100

Unit has to be sufficiently vacuumed to -0.1MPa (-76cmHg). Leave the vacuum for 5 minutes to ascertain the gauge pointerdo not raise again. (Refer to Figure 6 & 7)

VACUUMING

VACUUMING AND CHARGINGUse a vacuum pump with a back flow preventing adapter to prevent the vacuum pump oil mix with R410A which willcreate sludge and damage the equipment. Use only gauge manifold exclusive for R410A for vacuuming and charging.

a) Gauge Manifold

Gauge Manifold (R410A) Connection Port SizeHigh Pressure Gauge (Red) -0.1 ~ 5.3 MPa-76 cmHg ~ 53 kgf/cm2

1/2 UNF -20

Low Pressure Gauge (Blue) -0.1 ~ 3.8 MPa thread per inch

-76 cmHg ~ 38 kgf/cm2

Charge Hose (R410A)

Operating Pressure 5.1 MPa (51 kgf/cm2)

Burst Pressure 27.4 MPa (274 kgf/cm2)

Connection size 1/2 UNF -20 thread per inch

b) Charge Hose

The different size of connection port from the conventional is to prevent wrong refrigerant charging instead of R410A.

c) Refrigerant CylinderA typical R410A charging cylinder will be identified with the refrigerant name and is coated with pink in colour as designatedby ARI.

R410A is mixture of refrigerant which have different evaporating temperature. So when charging, make sure only liquid isbeing withdrawn from the charging cylinder. Charging gas refrigerant R410A in state will affect the performance and operat-ing condition of the system. Invert the cylinder that does not come with dip pipe during charging.

Additional Charge OperationThis operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is topped-up intothe outdoor unit using the suction valve via service port.

- Remove the service port cap.- Connect the low pressure side of the charging gauge to the suction service port, center of the cylinder tank and close the

high pressure side of the gauge. Purge the air from the service hose.- Start the air conditioner unit.- Open the gas cylinder and low pressure charging valve.- When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve.- Disconnect the service hose from service port. Put back the service port cap.

Page 13: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-4

En

gli

s h

RECOMMENDED CABLE SIZES

ELECTRICAL DATA

!!!!! CAUTION• Ensure the rated voltage and phase of the unit corresponds to the unit name plate before carrying out wiring work.• The unit must be GROUNDED to prevent hazards due to insulation failures.• Do not ground any electrical equipment to the water piping.• Ensure all electrical wiring do not touch the refrigerant piping, compressor, pump or any moving parts.• Do not operate unit with wet hand(s). It will result in electrical shock.

Model 5WST40AR 5WST50AR 5WST60ARRated Voltage Range** 380 - 415V / 3Ph / 50HzRecommended Fuse/MCB* A 45 45 45Supply Cable Size mm2 8.4 8.4 8.4Number of Cables 5 5 5Interconnection Cable Size* mm2 2.1 2.1 2.1

Number of Cables 7 7 7

ELECTRICAL AND WIRING• Refer to the wiring diagram provided on the unit when making electrical wiring connection. (Refer to Figure 9)• Power supply is from fan coil unit connection.• All field wiring must comply with your national or local wiring regulation.• All terminal wiring must be firmly connected. Improper connection can cause electric shock, short circuit or fire breakout.• A circuit breaker must be provided for over current protection.• All safety precautions need to be strictly adhere.

Model 5WST40AR 5WST50AR 5WST60ARPower Supply V/Ph/Hz 380-415/3/50Nominal Power Input Comp 1/Comp 2 (Cooling) W 1478/1478 1995/1995 1857/2272Nominal Power Input Comp 1/Comp 2 (Heating) W 1583/1583 1820/1820 1798/2231Nominal Current Comp 1/Comp 2 (Cooling) A 6.6/6.6 8.8/8.8 8.5/10.4

Nominal Current Comp 1/Comp 2 (Heating) A 7.1/7.1 8.0/8.0 8.3/10.3

Capacitor µf 50/50 60/60 60/45

Fuse Amp 7 7 7

SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT• R410A is a near azeotrope refrigerant mixture of hydro fluorocarbon (HFC) which is environmental friendly. It has Zero

Ozone Depletion Potential (ODP=0) and this conform to Montreal Protocol regulations.• R410A system has a operating pressure of about 1.6 times higher than R22 at the same temperature.• Never use copper tubes thinner than 0.8mm.• R410A compressor uses polyol-ester oil (POE) as lubricant which is prone to moisture contamination (hydroscopic).

Hydrolysis may occur that will generate acid when mix with moisture or water and will damage the compressor winding.• It has to be treated in a more cautiously manner than other conventional mineral oil.• Do not expose the system for too long. POE oil will absorb moisture into the system that will generate acid and cause

capillary clogging or compressor motor winding damage. Cover temporary the refrigerant valve or copper tube openingwhen performing installation or servicing. Install a bi-flow filter dryer (two-way) along the liquid piping to absorb theunwanted moisture. Residue POE oil in the piping and components can absorb moisture from the air.

• Do not mix R410A with other refrigerant into the system.• Identified refrigerant before charging. R410A refrigerant cylinder is pink coated. Charge only R410A liquid phase into the units.• Do not add any additional oil into the compressor.• Use only exclusive tools and equipment for R410A:

i) Manifold gauge and charging hoseii) Gas leak detectoriii) Refrigerant cylinder (usually pink coated)iv) Vacuum pump c/w adaptorv) Flare toolsvi) Refrigerant recovery machine

!!!!! CAUTION• R410A must be charged in liquid phase. Usually R410A cylinder is equipped with a dip pipe for liquid withdrawal. If

there is no dip pipe, invert the cylinder to withdraw R410A liquid.• If leak occurs, do not top-up any additional R410A refrigerant as this will reduce the unit performance. Instead

evacuate the refrigerant and fix the leakage before vacuuming it thoroughly. Then charge with new R410A refriger-ant according to the recommended specification.

• If refrigerant gas leak occurs during installation / servicing, make sure the area is ventilate fully.• Do not allow the piping and unit exposed to air or moisture.• Install a bi-flow filter dryer (two way) along the liquid line.

Page 14: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-5

UNIT OPERATION LIMITSEnvironmentThis unit is designed for indoor installation and operation only. This unit also limited to water loop application only as the heatexchanger can only cater for this application.

Power SupplyA voltage variation of +/- 10% of rated voltage stated in the unit label is acceptable.

Allowable Operation ConditionsEnsure the operating temperature and condition are in allowable range. Extreme variations in temperature, humidity andcorrosive water or air will adversely affect unit performance, reliability and service life.

CONTROL OPERATION GUIDE• Controller of water source heat pump split type unit is located in the fan coil unit.• Refer to fan coil unit installation manual for control guide operation.

Heat Pump

Wat

er E

nter

ing

Tem

p. (

o C)

Wat

er E

nter

ing

Tem

p. (

o C)

32

20

12

45

30

13

STD

Heating Cooling

Indoor Temp. (oC DB)15 20 27 15 19 24

STD

Indoor Temp. (oC WB)

Water Pressure Drop Table

Model Water Flow Rate Pressure Drop2.1 9.49

5WST40AR 2.3 12.032.5 14.502.7 11.83

5WST50AR 2.9 15.503.1 17.003.2 19.28

5WST60AR 3.4 22.213.6 25.59

The water circulating loop system must be cleaned and flushed to remove all construction debris and dirts before operating the units.1. If the connection is equipped with water shut-off valve, either electric or pressure operated, the individual supply and

return pipes must be connected together first. This will prevent the introduction of dirt into the unit.2. Fill the water loop system with your local water supply with all air vents open. After filling, close all air vents. The

contractor should start the main circulator pump with the pressure reducing valve open. Check all vents in sequence tobleed off any trapped air, ensuring circulation through all components of the system. Power to the heat rejector unit shouldbe off and the supplementary heat control set at 27oC (80oF).

3. While the water is circulating, the contractor should check and repair any leaks in the piping. Drains at the lowest point(s)in the system should be opened for initial flush and blow down. Make sure the local supply water valves are set to make upfor the required flow rate. Check the pressure gauge at the pump suction and manually adjust the make up to hold the samepositive steady pressure both before and after opening the drain valves. Flush should be continuously for two hours orlonger if required to obtain a clean and clear drain water.

4. Shut off all supplemental heater and circulator pump and open all drains and vents to complete drain down the system.Now, the short-circuited water connection to the supply and return pipes should be removed and connected to the indi-vidual water inlet and outlet of the unit. Use proper tape to seal off at the valve connection. Do not use sealant at the valvesconnection.

SYSTEM CLEANING AND FLUSHING

Page 15: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-6

En

gli

s h

5. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, some of the local authori-ties ban the usage of the phosphate into the sewage systems. The current recommendation is to simply flush longer withwarm at 27oC (80oF) water.

6. Refill the water loop system with clean water. Test the water for acidity by using a litmus paper. Treat the water if requiredto obtain the pH level between 7.5 to 8.5 (slightly alkaline). If antifreeze is required, use only antifreeze designed forHVAC. Do not use automotive grade antifreeze.

7. Once the water system is ready, ensure at all times only clean water is supply to the system. Dirty water will result in widedegradation of performance and solids may clog valves, strainers, flow regulator, etc. Pump work will increase and maydamage the pumps. The heat exchanger may become clogged as well which will reduce the compressor service life orcauses premature failure.

8. Finally set the loop water controller heat addition point to 21oC (70oF) and the heat rejection set point to 29oC (85oF).Supply power to all motors and start the circulating pumps. After full flow has been established through all componentsincluding heat rejector (regardless of season) and air vented and loop temperature stabilized, each of the air conditionerswill be ready for check, test and start up, air balancing and water balancing.

1. Make sure all wiring connection is correct and power supply is compatible to the rated voltage.2. Open all valves in full open position and start the circulating pump. Make sure there is water running through the water

loop before operating the unit.3. Set to mode ‘Cool’. Then set the temperature to the coolest. The unit has time delay which protects the compressor for

short cycling. Wait for a few minutes before check on the air discharge for cool air delivery.4. Measure the temperature difference between entering and leaving water. It should before approximately 1.3 to 1.5 times

greater than the heating mode temperature difference. Example: If water temperature difference in cooling mode is 5°C (9°F), the heating mode difference should be 3.3°C (6°F).5. If without automatic flow control valves, target the cooling mode water temperature difference between 5°C (9°F) to 8°C

(14.4°F). This can be achieved by adjusting shut-off / balancing valve in the return piping to a suitable water flow rate toachieve the desire temperature difference.

6. Set to mode ‘Heat’. Set the temperature to the warmest. Again the air conditioner has built in time delay that prevents thecompressor to start immediately. The fan will start first before the compressor. Check for warm air discharge. If it is a ‘coldbuilding’ start-up, leave the unit running until return air to the unit is at least 18°C (65°F).

7. Measure the temperature difference between entering and leaving water. With entering water temperature of 16°C to 27°C(60°F to 80°F), leaving water temperature should be 3.3°C to 6°C (6°F to 12°F) cooler and the air temperature rise throughthe machine should not exceed 19°C (35°F). If the air temperature exceeds 19°C (35°F), then the water flow rate isinadequate.

8. Check for vibration refrigerant piping, fan wheels, etc.

NOTE• Water source heat pump split type unit is controlled by fan coil unit.• The controller is located on the fan coil unit.

!!!!! CAUTION• Ensure there is water supply into the unit at all times before operating.

UNIT START UP AND OPERATION

SERVICE AND MAINTENANCE

• Service and maintenance should be performed by authorized dealer or qualified contractor.• Internal components can be accessed through two service panels (front and back). External control box for easy access of

electrical components.• Regular checks on the water strainer are recommended. Clean the strainer if dirty or clogged.• Maintain a log data on measurement of volts, amps, and water temperature difference (heating & cooling) is recommended.

A comparison of the data during start-up and periodic data is useful as indicator of general condition of equipment.

!!!!! CAUTION• Do not attempt to do any service or maintenance when the unit is operating.• Unauthorized modification of the unit is not allowed.

Page 16: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

1-7

TROUBLESHOOTING

• Troubleshooting must be performed by authorized dealer or qualified contractor.

Fault Cause / Check Point

Unit cannot start 1. Power supply plug disconnected.

2. Circuit breaker or fuse tripped / blown.3. Wiring connection

4. If fault persist, contact your installer.

Neither fan coil unit and 1. The fuse may be blown or circuit breaker opened.

compressor run 2. Check electrical circuit or motor winding for shorts or grounds. Investigate forpossible over loading. Replace fuse if necessary.

3. Check wiring connections. Wire may be loosening. Replace or tighten.

4. Control system may be faulty.

Compressor does not 1. Check capacitor if available. Replace capacitor if faulty.operate. 2. Check wiring connection. Wire may be loosening. Replace or tighten.

3. The high pressure switch may tripped due to:

a) No or insufficient water flows into and leaves heat exchanger. May be clogged.b) Water entering temperature higher than the maximum operating conditions.

c) Not enough air flow into fan coil unit. May be due to dirty filter or block by object,

cardboard and etc (heating mode).d) Fan coil motor failure (heating mode).

e) Unit over-charged. Release some of the refrigerant charge.

4. The compressor internal/external overload protection is opened. If the compressor bodyis extremely hot, the overload will not reset until it cooled down.

5. The compressor winding may be grounded to the compressor shell. If so, replace

the compressor.

Insufficient cooling 1. Check controller temperature setting.or heating. 2. Filter may be clogged. Check and clean the filter.

3. Check capillary tube for possible restriction of refrigerant flow. Replace capillary tube

if proven so.4. The reversing valve may be defective (valve position is not shifted properly), creating

a bypass of refrigerant. Check the reversing valve coil connection.

5. Check for restriction of air and water flow.6. Refrigerant leakage. Check all piping bends and connection for leakage. Repair the

leakage area or replace with new piping.

7. Window or door wide open.8. Unit may be under-sized.

Insufficient water flow 1. Valves are not opened fully.

through heat exchanger 2. Circulating water pump is faulty.

3. Water pipes or strainers are clogged.

Noisy operation 1. Check for loose bolts or screws.2. Make sure rubber isolators are used for installation.

3. Check for water balance to unit for proper water flow rate.

4. Check for tubing touching compressor or other surface. Readjust tubing by bendingit slightly.

5. Fan (fan coil unit) knocking / hitting on its housing.

6. May be due to worn compressor bearing.

Page 17: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

MEMO

Page 18: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

MEMO

Page 19: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766
Page 20: TANDEM WATER SOURCE HEAT PUMP SPLIT TYPE AIR · PDF filetandem water source heat pump split type ... tandem water source heat pump split type air conditioner part no.: a08019025766

• In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language,the English version of this manual shall prevail.

• The manufacturer reserves the right to revise any of the specification and design contain herein at any time without priornotification.

• En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité.

• Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniquesdes appareils présentés dans ce manuel.

• Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführungin Englisch.

• Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Herstellerjederzeit vorbehalten.

• Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versionein lingua inglese prevale.

• Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica.

• En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versióninglesa.

• El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presentemanual en cualquier momento y sin notificación previa.

• В случае противоречия перевода данного руководства с другими переводами одного и того же текста,английский вариант рассматривается как приоритетный.

• Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое времябез предварительного уведомления.