tablas ingeniería eléctrica

28
TABLA No. 5 DIMENSIONES DE LOS CONDUCTORES ELECTRICOS DESNUDOS CALIBRE AWG o MCM SECCIÓN DIÁMETRO CIRCULAR MIL Mm2 PULGADAS MILIMETROS 20 1 022 0.518 0.032 0.812 18 1 824 0.823 0.040 1.024 16 2 583 1.309 0.051 1.291 14 4 107 2.080 0.064 1.628 12 6 530 3.310 0.081 2.053 10 10 380 5.260 0.102 2.588 8 16 510 8.370 0.129 3.264 6 26 250 13.300 0.162 4.115 4 41 740 21.150 0.204 5.189 2 66 370 33.630 0.258 6.543 1/0 105 400 53.480 0.325 8.252 2/0 133 100 67.420 0.365 9.266 3/0 167 800 85.030 0.410 10.403 4/0 211 600 107.230 0.460 11.684 250 250 000 126.640 0.575 14.605 300 300 000 152.000 0.630 16.000 350 350 000 177.350 0.681 17.300 400 400 000 202.710 0.728 18.490 500 500 000 253.350 0.814 20.680 600 600 000 304.000 0.893 22.680 700 700 000 354.710 0.964 24.690 750 750 000 379.840 0.998 25.350 800 800 000 405.160 1.031 26.190 900 900 000 455.810 1.093 27.760

Upload: cesar-torres

Post on 13-Jun-2015

74.476 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Tablas ingeniería eléctrica

TABLA No. 5

DIMENSIONES DE LOS CONDUCTORES ELECTRICOS DESNUDOS

CALIBREAWG o MCM

SECCIÓN DIÁMETROCIRCULAR MIL Mm2 PULGADAS MILIMETROS

20 1 022 0.518 0.032 0.81218 1 824 0.823 0.040 1.02416 2 583 1.309 0.051 1.29114 4 107 2.080 0.064 1.62812 6 530 3.310 0.081 2.053

10 10 380 5.260 0.102 2.5888 16 510 8.370 0.129 3.2646 26 250 13.300 0.162 4.1154 41 740 21.150 0.204 5.1892 66 370 33.630 0.258 6.543

1/0 105 400 53.480 0.325 8.2522/0 133 100 67.420 0.365 9.2663/0 167 800 85.030 0.410 10.4034/0 211 600 107.230 0.460 11.684

250 250 000 126.640 0.575 14.605300 300 000 152.000 0.630 16.000350 350 000 177.350 0.681 17.300400 400 000 202.710 0.728 18.490500 500 000 253.350 0.814 20.680

600 600 000 304.000 0.893 22.680700 700 000 354.710 0.964 24.690750 750 000 379.840 0.998 25.350800 800 000 405.160 1.031 26.190900 900 000 455.810 1.093 27.760

1000 1 000 000 506.450 1.152 29.2601250 1 250 000 633.060 1.289 32.7401500 1 500 000 759.680 1.412 35.8701750 1 750 000 886.290 1.526 38.7602000 2 000 000 1 012.900 1.631 41.420

Page 2: Tablas ingeniería eléctrica

TABLA No. 6

CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE, AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30º C.

CALIBREAWG o MCM

TIPOS T, TW, UF (60º C) THW, THWN, RHW, XHW (75º C)TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE

14 15 20 15 2012 20 25 20 2510 30 30 30 408 40 60 50 706 55 80 65 954 70 105 85 1252 95 140 115 170

1/0 125 195 150 2302/0 145 225 175 2653/0 165 260 200 3104/0 195 300 230 360250 215 340 255 405300 240 375 285 445350 260 420 310 505400 280 455 335 545500 320 515 380 620600 355 575 420 690700 385 630 460 755750 400 655 475 785800 410 680 490 815900 435 730 520 8701000 455 780 545 935

FACTORES DE CORRECCIÓN PARA TEMPERATURAS AMBIENTESMAYORES DE 30º C

31 A 35º C 0.91 0.91 0.94 0.9436 A 40º C 0.82 0.82 0.88 0.8841 A 45º C 0.71 0.71 0.82 0.8246 A 50º C 0.58 0.58 0.75 0.7551 A 55º C 0.41 0.41 0.67 0.6756 A 60º C 0.58 0.5861 A 79º C 0.41 0.41

NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras dadas, de 7 a 9 conductores, la ampacidad se reduce al 70% ; al 50% si hay de 10 a 20 conductores y, al 45% si hay de 21 a 30 conductores en un tubo. En un sistema balanceado, el neutro no cuenta como conductor para los efectos de esta nota.

Page 3: Tablas ingeniería eléctrica

TABLA No. 7

CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE, AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30° C

CALIBREAWG o MCM

THHW, RHH, THHN, XHHW (90º C) VINICON, AVA, AVL (110º C)TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE

14 25 35 30 4012 30 40 35 5010 40 55 45 658 55 80 60 856 75 105 80 1204 95 140 105 1602 130 190 135 210

1/0 170 260 190 2852/0 195 300 215 3303/0 225 350 245 3804/0 260 405 275 445250 290 455 315 495300 320 505 345 555350 350 570 390 610400 380 615 420 665500 430 700 470 765600 475 780 525 855700 500 850 560 940750 535 885 580 980800 550 900 600 1 0201000 615 1 055 680 1 165

FACTORES DE CORRECCION PARA TEMPERATURAS AMBIENTES MAYORES DE 30º C

31 A 35º C 0.96 0.96 0.97 0.9736 A 40º C 0.91 0.91 0.94 0.9441 A 45º C 0.87 0.87 0.90 0.9046 A 50º C 0.82 0.82 0.87 0.8751 A 55º C 0.76 0.76 0.83 0.8356 A 60º C 0.71 0.71 0.79 0.79

NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras dadas. De 7 a 9 conductores, la ampacidad se reduce al 70% ; de 10 a 20 al 50% y de 21 a 30 al 45%. En un sistema balanceado, el neutro no cuenta como conductor para los efectos de esta nota.

Page 4: Tablas ingeniería eléctrica

TABLA No. 8

NUMERO MAXIMO DE CONDUCTORES TIPO T, TW, THW, THHW, XHHW QUE PUEDEN INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE

RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.

CALIBRECONDUCTOR

DIAMETRO NOMINAL DEL TUBO EN MILÍMETROS13 19 25 32 38 51 63 76 89 102 127 152

14 9 15 25 44 60 99 14212 7 12 19 35 47 78 111 17110 5 9 15 26 36 60 85 111 1768 2 4 7 12 17 28 40 62 84 108

6 1 2 4 7 10 16 23 36 48 62 97 1414 1 1 3 5 7 12 17 27 36 47 73 1062 1 1 2 4 5 9 13 20 27 34 54 78

1/0 - 1 1 2 3 5 8 12 16 21 33 492/0 - 1 1 1 3 5 7 10 14 18 29 413/0 - 1 1 1 2 4 6 9 12 15 24 354/0 - - 1 1 1 3 5 7 10 13 20 29

250 1 1 1 2 4 6 8 10 16 23300 1 1 1 2 3 5 7 9 14 20350 1 1 1 3 4 6 8 12 18400 1 1 1 2 4 5 7 11 16500 1 1 1 1 3 4 6 9 14

600 1 1 1 3 3 5 7 11750 1 1 1 2 3 4 6 9800 1 1 1 1 3 4 6 8900 1 1 1 3 3 5 81000 1 1 1 2 3 5 7

Page 5: Tablas ingeniería eléctrica

TABLA No. 9

NUMERO MAXIMO DE CONDUCTORES TIPO THWN Y THHN QUE PUEDEN INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE

RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.

CALIBRECONDUCTOR

DIÁMETRO NOMINAL DEL TUBO EN MILÍMETROS13 19 25 32 38 51 63 76 89 102 127 152

14 13 24 39 69 94 15412 10 18 29 51 70 114 16410 6 11 18 32 44 73 104 1608 3 5 9 16 22 36 51 79 106 136

6 1 4 6 11 15 26 37 57 76 98 1544 1 2 4 7 9 16 22 35 47 60 94 1372 1 1 3 5 7 11 16 25 33 43 67 97

1/0 1 1 3 4 7 10 15 21 27 42 612/0 1 1 2 3 6 8 13 17 22 35 513/0 1 1 1 3 5 7 11 14 18 29 424/0 1 1 1 2 4 6 9 12 15 24 35

250 1 1 1 3 4 7 10 12 20 28300 1 1 1 3 4 6 8 11 17 24350 1 1 2 3 5 7 9 15 21

400 1 1 1 3 5 6 8 13 19500 1 1 1 2 4 5 7 11 16750 1 1 1 2 3 4 7 11

Page 6: Tablas ingeniería eléctrica

TABLA No. 10

CANTIDAD DE CONDUCTORES QUE PUEDEN ALOJARSE EN UN DUCTO DE LAMINA

CALIBRECONDUCTORAWG o MCM

SECCIÓN CONDUCTOR CON AISLAMIENTO mm2

DUCTOS DE LÁMINA

MEDIDASEN mm

SECCION TRANSVER. mm2THWN,THHN

TW, THWXHW

TOTAL 20% TOTAL

14 5.80 8.30 60 x 60 3 600 72012 7.90 10.64 100 x 100 10 000 2 00010 12.30 13.99 150 x 150 22 500 4 5008 21.10 26.70 200 x 200 40 000 8 000

PARA USAR ESTA TABLA:1.- Determinar cantidad, tipo y calibre de conductores a canalizar.2.- Sumar sus secciones transversales.3.- Escoger el ducto adecuado, utilizando la columna del 20% de su sección - - transversal.

6 34.20 49.294 55.15 65.612 77.00 89.42

1/0 123.50 143.992/0 147.60 169.723/0 176.70 201.064/0 211.20 239.98

250 261.30 298.65300 302.60 343.07350 346.19 386.88400 384.30 430.05

500 463.00 514.72600 572.27 628.70750 673.91 735.04

1000 813.92 934.35

Page 7: Tablas ingeniería eléctrica

TABLA No. 11

RESISTENCIA DE CONDUCTORES CON CORRIENTE DIRECTA, FACTORES DE CORRECCION AL OPERARLOS CON CORRIENTE ALTERNA POR EL EFECTO PIEL Y,

REACTANCIA AL NEUTRO PARA UNA FRECUENCIA DE 60 HERTZ.

CALIBRECONDUCTORAWG o MCM

RESISTENCIAC. DIRECTA

OHMS / 1000’

FACTOR DE CORRECCIÓNPOR EFECTO PIEL

REACTANCIA ENOHMS / 1000 PIES

( 1 ) ( 2 ) MÍNIMA MÁXIMA14 3.0000 1.000 1.00012 1.8700 1.000 1.00010 1.1800 1.000 1.0008 0.7400 1.000 1.000 0.041 0.0456 0.4650 1.000 1.000 0.040 0.0454 0.2920 1.000 1.000 0.037 0.0502 0.1850 1.000 1.010 0.035 0.048

1/0 0.1600 1.000 1.020 0.034 0.0482/0 0.0920 1.000 1.030 0.032 0.0443/0 0.0730 1.000 1.040 0.031 0.0444/0 0.0580 1.000 1.050 0.030 0.045250 0.0490 1.005 1.060 0.030 0.044300 0.0408 1.006 1.070 0.029 0.045350 0.0350 1.009 1.080 0.029 0.044400 0.0306 1.011 1.100 0.029 0.043500 0.0245 1.018 1.130 0.028 0.038600 0.0204 1.025 1.160 0.028 0.038750 0.0163 1.039 1.210 0.028 0.0351000 0.0123 1.067 1.300 0.028 0.0381250 0.0098 1.102 1.410 0.028 0.0381500 0.0082 1.142 1.530 0.028 0.0381750 0.0070 1.185 1.659 0.027 0.0372000 0.0061 1.233 1.800 0.027 0.038

NOTAS: ( 1 ) Conductor en aire o en tubo no magnético. ( 2 ) Conductor en tubo de acero. Los valores de la reactancia mínima se aplican para conductores juntos dentro de un tubo

o de un ducto. Los valores de la reactancia máxima se aplican para conductores separados en

instalaciones aéreas o en ménsulas en galerías de conductores. Para conductores en ductos o tubos de acero o, con armadura de acero, la reactancia

aumenta en un 25%. Por lo tanto, multiplíquense los valores por 1.25.

Page 8: Tablas ingeniería eléctrica

TABLA No. 12

CAPACIDADES Y DIMENSIONES DE CARTUCHOS FUSIBLES

CAPACIDAD EN AMPERES

250 VOLTS 600 VOLTSLARGO (mm) DIÁMETRO(mm) LARGO (mm) DIÁMETRO(mm)

FUSIBLES TIPO TAPÓN10, 15, 20, 25 Y

30 - - - - - - - - - - - -FUSIBLES TIPO CASQUILLO

3, 5, 6, 10, 15, 20, 25 Y 30 53 14 125 19

35, 40, 45, 50 Y 60 76 21 139 26

FUSIBLES TIPO NAVAJA75, 90, 100 151 30 200 35

125, 150, 175, 200 181 42 244 47

225, 250, 300 219 56 295 65500, 600 263 67 340 76

Page 9: Tablas ingeniería eléctrica

TABLA No. 13

CAPACIDAD Y DIMENSIONES DE LOS INTERRUPTORES TERMOMAGNETICOS

MARCO CAPACIDAD ENAMPERES

CAPACIDADINTERRUPTIVA

No. DE

POLOS

DIMENSIONES ENCENTIMETROS

240V 480V 600V ALTO ANCHO FONDO

QL15, 20, 30, 40, 50,

70, 100 10000 - - - - - -123

7.57.57.5

2.55.07.5

7.37.37.3

FA15, 20, 30, 40, 50,

70, 100 10000 - - - - - -123

15.315.315.3

3.57.0

10.5

8.68.68.6

FB15, 20, 30, 40, 50, 70, 100, 125, 150 18000 14000 14000 2

315.315.3

7.010.5

8.68.6

HFB15, 20, 30, 40, 50, 70, 100, 125, 150 65000 25000 18000 2

315.315.3

7.010.5

8.68.6

LB 125, 150, 175, 200, 225 25000 22000 22000 3 25.7 14.0 10.3

LB 250, 300, 350, 400 42000 30000 22000 3 25.7 14.0 10.3

HLB125, 150, 175, 200, 225, 250, 300, 350, 400

65000 35000 25000 3 25.7 14.0 10.3

LA 500, 600 42000 30000 22000 3 27.6 21.0 10.3NB 700, 800, 1000,

1200 42000 30000 22000 3 41.2 21.0 14.0PB 1400, 1600, 1800

2000, 2500, 3000 125000 100000 100000 3 56.2 30.5 22.9NC (+) 800, 900, 1000,

1200 42000 30000 22000 3

PC (+)1000, 1200, 14001600, 1800, 2000

2500, 3000125000 100000 100000 3

MPC 3, 7, 15, 30, 50, 100, 150 25000 22000 22000 3 15.3 10.5 8.6

NOTAS: (+) Interruptores con protección electrónica. MPC: Interruptor magnético instantáneo.

Page 10: Tablas ingeniería eléctrica

TABLA No. 14

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE DIRECTA

POTENCIA EN HP

VOLTAJE115 VOLTS 230 VOLTS 550 VOLTS

0.50 4.6 2.3 - -0.75 6.6 3.3 1.41.00 8.6 4.3 1.81.50 12.6 6.3 2.52.00 16.4 8.2 3.43.00 24.0 12.0 5.0

5.0 40.0 20.0 8.37.5 58.0 29.0 12.0

10.0 76.0 38.0 16.015.0 112.0 56.0 23.020.0 148.0 74.0 31.0

25.0 184.0 92.0 38.030.0 220.0 110.0 46.040.0 292.0 146.0 61.050.0 360.0 180.0 75.060.0 430.0 215.0 90.0

75.0 536.0 268.0 111.0100.0 - - - 355.0 148.0125.0 - - - 443.0 184.0150.0 - - - 534.0 220.0200.0 - - - 712.0 295.0

Page 11: Tablas ingeniería eléctrica

TABLA No. 15

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA MONOFASICOS

POTENCIA ENHP

VOLTAJES115 VOLTS 230 VOLTS 440 VOLTS

1/6 3.2 1.6 - - -

¼ 4.6 2.3 - - -

½ 7.4 3.7 - - -

¾ 10.2 5.1 - - -

1.0 13.0 6.5 - - -

1.5 18.4 9.2 - - -2.0 24.0 12.0 - - -3.0 34.0 17.0 - - -5.0 56.0 28.0 - - -7.5 80.0 40.0 21.0

10.0 100.0 50.0 26.0

Page 12: Tablas ingeniería eléctrica

TABLA No. 16

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA TRIFASICOS

POTENCIAHP

MOTORES DE INDUCCIÓN MOTORES SÍNCRONOS220 V 440 V 550 V 2400 V 220 V 440 V 550 V 2300 V

1/2 2.0 1.0 0.8 - - - - - - - - - - - - - - -3/4 2.8 1.4 1.1 - - - - - - - - - - - - - - -1.0 3.5 1.8 1.4 - - - - - - - - - - - - - - -1.5 5.0 2.5 2.0 - - - - - - - - - - - - - - -2.0 6.5 3.3 2.6 - - - - - - - - - - - - - - -

3.0 9.0 4.5 4.0 - - - - - - - - - - - - - - -5.0 15.0 7.5 6.0 - - - - - - - - - - - - - - -7.5 22.0 11.0 9.0 - - - - - - - - - - - - - - -10.0 27.0 14.0 11.0 - - - - - - - - - - - - - - -15.0 40.0 20.0 16.0 - - - - - - - - - - - - - - -

20.0 52.0 26.0 21.0 - - - - - - - - - - - - - - -25.0 64.0 32.0 26.0 7.0 54.0 27.0 22.0 5.430.0 78.0 39.0 31.0 8.5 65.0 33.0 26.0 6.540.0 104.0 52.0 41.0 10.5 86.0 43.0 35.0 8.050.0 125.0 63.0 50.0 13.0 108.0 54.0 44.0 10.0

60.0 150.0 75.0 60.0 16.9 128.0 64.0 51.0 12.075.0 185.0 93.0 74.0 19.0 161.0 81.0 65.0 15.0

100.0 246.0 123.0 98.0 25.0 211.0 106.0 85.0 20.0125.0 310.0 155.0 124.0 31.0 264.0 132.0 106.0 25.0150.0 360.0 180.0 144.0 37.0 - - - 158.0 127.0 30.0

200.0 480.0 240.0 192.0 48.0 - - - 210.0 168.0 40.0250.0 - - - 300.0300.0 - - - 345.0350.0 - - - 406.0400.0 - - - 475.0

Page 13: Tablas ingeniería eléctrica

TABLA No. 17

CAPACIDAD O AJUSTE MAXIMO DEL DISPOSITIVO DE PROTECCION PARA LOS CIRCUITOS DERIVADOS DE LOS MOTORES

TIPO DE MOTORPOR CIENTO DE LA CORRIENTE A PLENA CARGA

FUSIBLES INT. TERMOMAGNÉTICONORMAL ACC. RET. INSTANT. TIEMPO INV.

Todos los motores monofásicos o trifásicos, jaula de ardilla, con arranque a tensión plena o con resistencias o reactancias:LETRA DE CÓDIGO “A” 150 150 700 150LETRA DE CÓDIGO “B a E” 250 175 700 200LETRA DE CÓDIGO “F a V” 300 175 700 250SIN LETRA CÓDIGO 300 175 700 250

Todos los motores jaula de ardilla y síncronos con arranque por autotransformador:LETRA DE CÓDIGO “A” 150 150 700 150LETRA DE CÓDIGO “B a E” 200 175 700 200LETRA DE CÓDIGO “F a V” 250 175 700 200SIN LETRA DE CÓDIGO 250 175 700 200

Motores jaula de ardilla de alta reactancia y no mayores de 30 A. 250 175 700 250

Motores jaula de ardilla de alta reactancia y mayores de 30 A. 200 175 700 200

Motores de rotor devanado 150 150 700 150

Page 14: Tablas ingeniería eléctrica

TABLA No. 18

RELACION QUE MUESTRA ALGUNAS DE LAS CAPACIDADES DE LOS ELEMENTOS TERMICOS UTILIZADOS PARA LA PROTECCION CONTRA SOBRECARGA DE LOS

MOTORES

CAPACIDAD EN AMPERES CAPACIDAD EN AMPERES CAPACIDAD EN AMPERES

TAMAÑOS 0 Y 1 TAMAÑOS 0 Y 1 TAMAÑOS 2 A 8

0.167 - 0.187 5.040 - 5.590 91.80 - 105.00.188 - 0.210 5.600 - 6.250 106.0 - 121.00.211 - 0.237 6.260 - 6.920 122.0 - 135.00.238 - 0.266 6.930 - 7.750 126.0 - 139.00.267 - 0.298 7.760 - 8.630 140.0 - 157.00.299 - 0.334 8.640 - 9.590 158.0 - 175.00.335 - 0.376 9.600 - 10.60 176.0 - 196.00.377 - 0.422 10.70 - 11.90 197.0 - 218.00.423 - 0.474 12.00 - 13.30 219.0 - 243.00.475 - 0.532 13.40 - 14.70 244.0 - 270.00.533 - 0.598 14.80 - 16.60 264.0 - 295.00.599 - 0.672 16.70 - 18.80 296.0 - 330.00.673 - 0.757 18.90 - 21.20 331.0 - 369.00.758 - 0.855 21.30 - 23.90 370.0 - 410.00.856 - 0.959 24.00 - 27.00 411.0 - 458.00.969 - 1.070 459.0 - 512.01.080 - 1.210 TAMAÑOS 2 A 8 513.0 - 574.01.220 - 1.350 550.0 - 607.01.360 - 1.520 24.60 - 27.90 608.0 - 685.01.530 - 1.700 28.00 - 32.00 686.0 - 763.01.710 - 1.900 32.10 - 36.60 764.0 - 855.01.910 - 2.100 36.70 - 41.80 828.0 - 924.02.110 - 2.330 41.90 - 45.00 925.0 - 1 0272.340 - 2.620 42.90 - 48.50 1 028 - 1 1472.630 - 2.930 48.60 - 55.10 1 148 - 1 2852.940 - 3.270 55.20 - 62.303.280 - 3.640 62.40 - 69.503.650 - 4.060 69.60 - 79.104.070 - 4.550 79.20 - 90.004.560 - 5.030 80.00 - 91.70

Page 15: Tablas ingeniería eléctrica

TABLA 19

POTENCIA MAXIMA DEL BANCO DE CAPACITORES PARA COMPENSAR FACTORES DE POTENCIA DE MOTORES TRIFASICOS DE INDUCCION, LIMITANDO EL FENOMENO

DE AUTOINDUCCION.

POTENCIAMOTOR EN HP

VELOCIDAD DE SINCRONISMO DEL MOTOR EN R. P. M.3 600 1 800 1 200 900 720 600

10 2.5 4.0 4.0 5.0 5.0 6.515 2.5 5.0 5.0 7.5 7.5 10.020 5.0 5.0 5.0 7.5 10.0 12.525 5.0 7.5 7.5 10.0 10.0 15.0

30 7.5 10.0 10.0 10.0 12.5 15.040 10.0 10.0 10.0 12.5 15.0 17.550 12.5 12.5 12.5 15.0 20.0 22.560 15.0 15.0 15.0 17.5 22.5 25.075 17.5 17.5 17.5 20.0 27.5 30.0

100 22.5 22.5 22.5 25.0 35.0 37.5125 25.0 27.5 27.5 30.0 40.0 47.5150 32.5 32.5 35.0 37.5 47.5 55.0200 42.5 42.5 42.5 45.0 60.0 67.5

Page 16: Tablas ingeniería eléctrica

TABLA No. 20

MULTIPLICADORES DE KW PARA DETERMINAR LOS KVAR EN CAPACITORES, REQUERIDOS PARA CORREGIR EL FACTOR DE POTENCIA

F. P.ORIGINA

L

FACTOR DE POTENCIA CORREGIDO0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.98 1.00

0.56 0.996 1.024 1.054 1.085 1.117 1.151 1.188 1.277 1.4800.58 0.921 0.949 0.979 1.010 1.042 1.076 1.113 1.202 1.4050.60 0.849 0.877 0.907 0.938 0.970 1.004 1.041 1.130 1.3330.62 0.782 0.810 0.840 0.871 0.903 0.937 0.974 1.063 1.2660.64 0.717 0.745 0.775 0.806 0.838 0.872 0.909 0.998 1.2010.66 0.654 0.682 0.712 0.743 0.775 0.809 0.846 0.935 1.1380.68 0.594 0.622 0.652 0.683 0.715 0.749 0.786 0.875 1.0780.70 0.536 0.564 0.594 0.625 0.657 0.691 0.728 0.817 1.020

0.72 0.480 0.508 0.538 0.569 0.601 0.635 0.672 0.761 0.9640.74 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.706 0.9090.76 0.371 0.399 0.429 0.460 0.492 0.526 0.563 0.652 0.8550.78 0.318 0.346 0.376 0.407 0.439 0.473 0.510 0.599 0.8020.80 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.547 0.7500.81 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.521 0.7240.82 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.495 0.6980.83 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.469 0.6720.84 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.443 0.6460.85 0.136 0.164 0.194 0.225 0.257 0.291 0.328 0.417 0.620

0.86 0.109 0.137 0.167 0.198 0.230 0.264 0.301 0.390 0.5930.87 0.083 0.111 0.141 0.172 0.204 0.238 0.275 0.364 0.5670.88 0.056 0.084 0.114 0.145 0.177 0.211 0.248 0.337 0.5400.89 0.028 0.056 0.086 0.117 0.149 0.183 0.220 0.309 0.5120.90 0.028 0.058 0.089 0.121 0.155 0.192 0.281 0.484

0.91 0.030 0.061 0.093 0.127 0.164 0.253 0.4560.92 0.031 0.063 0.097 0.134 0.223 0.4260.93 0.032 0.066 0.103 0.192 0.3950.94 0.034 0.071 0.160 0.3630.95 0.037 0.126 0.329

0.96 0.089 0.2920.97 0.048 0.2510.98 0.2030.99 0.143

Page 17: Tablas ingeniería eléctrica

EJEMPLO:

Se tiene una carga de 600 kilowatts con un factor de potencia de 0.80, que se desea corregir

a 0.92. Se entra a la columna de “factor de potencia original” con el dato de 0.80 y, en el

mismo renglón , se busca la constante para corregir el factor de potencia a 0.92,

encontrándose que es 0.324, el cual se multiplica por los 600 kilowatts de demanda. Se

tendrá así:

600 * 0.324 = 194.4

siendo el resultado así obtenido, la capacidad del banco de capacitores en KVAR.

Page 18: Tablas ingeniería eléctrica

TABLA No. 21

FACTORES DE DEMANDA PROMEDIO

TIPO DE SERVICIO F. DEMANDA TIPO DE SERVICIO F. DEMANDA

Alumbrado público 1.00 Fábricas de cigarros 0.60Apartamentos 0.35 Fábricas de dulces 0.45Bancos 0.70 Talleres de fundición 0.70Bodegas 0.50 Fábricas de galletas 0.55Casinos 0.85 Fábricas de hielo 0.90Correos 0.30 Talleres de herrería 0.50Escuelas 0.70 Imprentas 0.60Garages 0.60 Fábricas de jabón 0.60Hospitales 0.40 Fáb. artículos de lámina 0.70Hoteles chicos 0.50 Talleres de niquelado 0.75Hoteles grandes 0.40 Madererías 0.65Iglesias 0.60 Talleres de marmolería 0.70Mercados 0.80 Talleres mecánicos 0.75Multifamiliares 0.25 Fábricas de muebles 0.65Oficinas 0.65 Fábricas de pan 0.55Restaurantes 0.65 Fábricas de papel 0.75Teatros 0.60 Periódicos 0.75Tiendas 0.65 Fábricas de pinturas 0.70Fábricas de acetileno 0.70 Industria química 0.50Industria automotriz 0.70 Refinerías 0.60Talleres de carpintería 0.65 Fábricas de refrescos 0.55Empacadoras de carne 0.80 Industria textil 0.65Fábricas de cartón 0.50 Fábricas de ropa 0.45Fábricas de cemento 0.65 Fábricas de zapatos 0.45

Page 19: Tablas ingeniería eléctrica

TABLA NO. 22

TABLA 250-95 SECCIÓN TRANSVERSAL MÍNIMA DE LOS CONDUCTORES DE PUESTA A TIERRA PARA CANALIZACIONES Y EQUIPOS

CAPACIDAD DEL DISPOSITIVO SECCIÓN TRANSVERSAL SECCIÓN TRANSVERSALAUTOMÁTICO DE SOBRE COBRE ALUMINIO

CORRIENTE ANTES DEL EQUIPO mm2 AWG mm2 AWG15 2.082 14 3.307 1220 3.307 12 5.260 1030 5.260 10 8.367 840 5.260 10 8.367 860 5.260 10 8.367 8

100 8.367 8 13.300 6200 13.300 6 21.150 4300 21.150 4 33.620 2400 27.670 3 42.410 1500 33.620 2 53.480 1/0600 42.410 1 67.430 2/0800 53.480 1/0 85.010 3/0

1000 67.430 2/0 107.200 4/0