synchronous generator transient analysis
DESCRIPTION
observations and graphsTRANSCRIPT
SYNCHRONOUS GENERATOR TRANSIENT ANALYSIS
OBSERVATION SHEET
a) Obtaining of short circuit armature current oscillogram Pre –short circuit line voltage = 104.3 V Steady short circuit current = 5.77 AGenerator speed = 1500 rpmNumber of generator pole pairs = 2
Oscillogram 1b) Obtaining of field current oscillogram
Steady state field current = 0.3 A
Oscillogram 2
c) Obtaining of open circuit armature voltage waveform.
Minimum phase current = 4.8 A
Maximum phase current = 5.4 A
Minimum line voltage = 47.5 V
Maximum line voltage = 48.3 V
Generator speed = 1475 rpm
Oscillogram 3
d) Obtaining supply voltage waveform at slip test.
Oscillogram 3
Calculations
1.
STEP 1 From short circuit armature current wave form using oscillogram 1, computation for X d & X’’d
Time(ms) Half of peak to peak value. Ia (A) Log (Ia)0 27 1.43136376410 20.5 1.31175386120 18 1.25527250530 15 1.17609125940 14 1.14612803650 13.5 1.13033376860 12.5 1.09691001370 11.5 1.0606978480 11 1.04139268590 10 1100 9.5 0.977723605110 9.5 0.977723605120 9 0.954242509130 9 0.954242509140 9 0.954242509
Using the graph the calculated values of A & B in the ampere units
A = antilog (1.431363764) =27
B = antilog (0.954242509) = 9
According to the theory
X d=√2VsB
where Vs isthe rms pahse voltagebefor the S/C
= √2×104.39×√3
=9.462Ω
X ’’d=√2VsA
¿ √2×104.527×√3
=3.154Ω
Time(ms) vs Log (Ia)
STEP 2 From short circuit armature current wave form using oscillogram 1, computation for X’ d & T’d
Time(ms) Δx (A) log Δx0 17.838 1.2513461610 11.778 1.0710715520 8.318 0.92001891630 6.278 0.79782131140 5.078 0.70569269750 4.168 0.6199277160 3.348 0.52478544970 2.498 0.39759243480 1.728 0.23754373890 1.048 0.020361283100 0.539 -0.268411235110 0.172 -0.764471553120 0130 0140 0
Using the graph the calculated values of C & D in the ampere and ms units.
C = antilog (1.30044) =19.97
So C/e = 7.3469 so the log value of this is 0.866 hence correscopnding value obtained for D using the figure is 25 ms
According to the theory
X ’d=
11Xd
+C
√2V s
X ’d=
11
9.462+ 19.97×√3
√2×104.3
=2.93Ω
T ’d=D=25ms
Time(ms) vs log Δx
STEP 3 From short circuit armature current wave form using oscillogram 1, computation for T’’d & T’do
Time(ms) Δy (A) Log Δy0 14.24005858 1.15351177610 7.209749896 0.85792019920 3.704663695 0.56874878930 1.879807084 0.27411328240 0.910019998 -0.04094906450 0.398075891 -0.40003412460 0.140719611 -0.85164537470 0.028503233 -1.54510588280 0
Using the graph the calculated values of E & F in the ampere and ms units.
E = antilog (1.27955) =19.0348
So E/e = 7.0025 so the log value of this is 0.845 hence corresponding value obtained for F using the figure is 12 ms.
T ’ ’d=12ms
T ’do=T ’d×Xd
X 'd
T ’do=25×9.4622.93
=80.73ms
T ’ ’do=T ’’d×X ' dX ' ' d
T ’ ’do=12×2.933.154
=11.1477ms
Time(ms) vs log Δy
STEP 4 Graph between time vs Ia,(+ve peak + -ve peak)
Time(ms) Ia,(+ve peak + -ve peak)0 5410 4120 3630 3040 2850 2760 2570 2380 2290 20100 19110 19120 18130 18140 18
Using the graph the calculated values of G & H in the ampere and ms units.
G = 40.73 A from the graph
H = 130.1 ms from the graph
So T a=H=130.1ms
Time(ms) vs Ia,(+ve peak + -ve peak)
2. Field current variation fallowing a sudden three phase short circuit
I f=I f 0+ I f 0Xd−X 'd
Xd
¿
Ifo is the field current before the short circuit which observed as 0.3 ATkd is the direct axis damper time constant and assuming no damper sField current variation
I f=I f 0+ I f 0Xd−X 'd
Xd
¿
I f=0.3+0.3(9.462−2.93)
9.462[e−t25−e
−t11.1477 ]
I f=0.3+0.2071 [e−t25−e
−t11.1477 ]
Field current variation
Field current variation
3) Armature line voltage on sudden open circuit
V a=√2V s cos (ωt+θ0 )−√2V s
[Xd−X 'd ]X ' ' d
e−tT do cos (ωt+θ0 )−¿√2V s
[Xd−X ' ' d ]X ' ' d
e−tT ' do cos (ωt+θ0 )¿
Assuming θ0=0 ;
V a=√2V s cos (ωt )−√2V s
[Xd−X ' d ]X ' ' d
e−tT ' do cos (ωt )−¿√2V s
[ X ' d−X ' 'd ]Xd
e−tT ' ' do cos (ωt ) ¿
V a=√2104.3√3
cos (2 πft )−√2 104.3√3[9.462−2.93 ]3.154
e−t80.73 cos (ωt )−¿√2 104.3√3
[2.93−3.154 ]9.462
e−t
11.1477 cos (2 πft )¿
V a=85.16cos (314.16 t )−176.37 e−t80.73 cos (314.16 t )+2.016 e
−t30.172 cos (314.16 t )
Armature line voltag
4) Value of Xd and XQ from the slip test,
From the graphs of armature current and armature voltage of the slip test,
X d=(Va (pk−pk )max)(Ia( pk−pk )min)
=18V9 A
=2Ω
XQ=(Va( pk−pk )min)(Ia (pk−pk )max)
= 12V12.8 A
=0.9378Ω
Discussion
Compare the parameter values computed using Short circuit current oscillogram, open circuit voltage
oscillogram and slip test
Since the two methods to find the parameter values of the generator use graphical decomposition methods,
and each method having certain assumptions, which introduces to neglect some transient components like
double frequency component and displaced angle, there should be some deviation between the parameter
values obtained by the two methods.
And the graphical approach having more than one step leads to some inherent error in interpolating and curve
fitting.
Compare the agreement of theoretical and observed oscillogram, of short circuit field current and open
circuit line voltage
When we compare the theoretical and practical graph of the variation of field current at short circuit test, it
seems both are having same shape. But the practical curve takes more time to acquire the steady state,
compare with theoretical curve. This may occur due to the effect of damping effect in real situation.
Features of Short Circuit Oscillogram
In short circuit oscillogram we can identify 4 components in the transient behaviour.
(1) Transient component
(2) Sub transient component
(3) DC offset component
(4) Steady state component
Transient and sub transient components occure for very short period of time and transient
component takes much time to decay than sub transient component
When we observe the short circuit oscillogram , four components in field current can be
noticed. They are sub transient , transient , DC offset and steady state componenets. Generally sub
transient period lasts for 3-4 cycles of current. However transient period is long and lasts for some
hundreds of cycles.
DC offset current is caused due to the armature reaction. Before the short circuit, armature
flux is zero. With the short circuit, armature reaction flux ?a is forced to be established. i.e. sudden
armature current tends to be established. Depending on the field flux, the phase 'a' winding is
receiving at the instant of the short circuit, phase 'a' coil establishes a DC current to maintain the
same flux following the short circuit causing the DC offset term.
Importance of short circuit study on synchronous generators.
To apply necessary protection schemes in synchronous generators, generator parameters such as
synchronous reactance, transient reactance , sub transient reactance and etc. should be known. By
performing sudden open short circuit test only, these parameters can be determine. Therefore it is
important to do short circuit test.