Summer Indoor Heat Pump Water Heater Evaluation in a Hot-Dry Climate Marc Hoeschele and Matthew Seitzler Alliance for Residential Building Innovation May 2017

Upload: others

Post on 21-Sep-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

Summer Indoor Heat Pump Water Heater Evaluation in a Hot-Dry Climate Marc Hoeschele and Matthew Seitzler Alliance for Residential Building Innovation

May 2017

Page 2: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

NOTICE

This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, subcontractors, or affiliated partners makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof.

This report is available at no cost from the National Renewable Energy Laboratory (NREL) at www.nrel.gov/publications.

Available electronically at SciTech Connect http:/www.osti.gov/scitech

Available for a processing fee to U.S. Department of Energy and its contractors, in paper, from:

U.S. Department of Energy Office of Scientific and Technical Information P.O. Box 62 Oak Ridge, TN 37831-0062 OSTI http://www.osti.gov Phone: 865.576.8401 Fax: 865.576.5728 Email: [email protected]

Available for sale to the public, in paper, from: U.S. Department of Commerce National Technical Information Service 5301 Shawnee Road Alexandria, VA 22312 NTIS http://www.ntis.gov Phone: 800.553.6847 or 703.605.6000 Fax: 703.605.6900 Email: [email protected]

Page 3: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

iii

Summer Indoor Heat Pump Water Heater Evaluation in a Hot-Dry Climate

Prepared for:

The National Renewable Energy Laboratory

On behalf of the U.S. Department of Energy’s Building America Program

Office of Energy Efficiency and Renewable Energy

15013 Denver West Parkway

Golden, CO 80401

NREL Contract No. DE-AC36-08GO28308

Prepared by:

Marc Hoeschele and Matthew Seitzler

Alliance for Residential Building Innovation (ARBI)

Davis Energy Group, Team Lead

123 C Street

Davis, California 95616

NREL Technical Monitor: Stacey Rothgeb

Prepared under Subcontract No. KNDJ-0-40340-00

May 2017

Page 4: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

iv

The work presented in this report does not represent performance of any product relative to regulated minimum efficiency requirements.

The laboratory and/or field sites used for this work are not certified rating test facilities. The conditions and methods under which products were characterized for this work differ from standard rating conditions, as described.

Because the methods and conditions differ, the reported results are not comparable to rated product performance and should only be used to estimate performance under the measured conditions.

Page 5: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

iv

List of Acronyms

ARBI Alliance for Residential Building Innovation

CARB Consortium for Advanced Residential Buildings

COP coefficient of performance

DHW domestic hot water

DOE U.S. Department of Energy

EES Engineering Equation Solver

EF energy factor

gpd gallons per day

HPWH heat pump water heaters

HVAC heating, ventilating, and air conditioning

kBtu Thousand British Thermal Units

kW kilowatt

kWh kilowatt-hour

NEEA Northwest Energy Efficiency Alliance

PNNL Pacific Northwest National Laboratory`

REU Redding Electric Utility

RH resistance heat

Page 6: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

v

Executive Summary

More than 40% of U.S. households heat domestic hot water (DHW) using electric-resistance storage water heaters (DOE 2010). For this group, heat pump water heaters (HPWHs) offer a significant opportunity to improve water heating performance. The HPWH technology is making inroads in some U.S. markets due to aggressive marketing and local utility incentives that often contribute to very favorable economics relative to electric-resistance storage water heating.

As an HPWH operates, it results in air being cooled by the evaporator. This cooled air is either directly exhausted to the surrounding space or, with the advent of ducting kits, delivered to a nearby location in or outside conditioned space. The resulting impact on heating and cooling loads varies considerably based on climate, hot water loads, thermostat setpoints, and the thermal characteristics of the building envelope.

Numerous field studies document performance in a variety of climates and applications. More recent evaluation efforts focus on the performance of units located indoors, as many existing electric water heaters are located in conditioned space. Much of the prior work on ducted HPWHs focuses on cold climates or hot-humid areas. To meet the end-of-year project completion constraints, this study evaluated only summer performance of indoor HPWHs installed in two existing homes in Redding, California. Redding is located in a hot, dry region of the state with more than 2,000 annual cooling degree days and 2,827 heating degree days. The existing electric storage water heaters in the two homes were monitored in detail over a four-week period, followed by the HPWH retrofit in late May. The monitoring included detailed flow and temperature readings at the water heater (at both the water- and air-sides for the HPWH), indoor and outdoor conditions, and space-cooling energy consumption.

Summer results indicated favorable water heating performance—2.60 to 2.85 average coefficient of performance (COP)—and average monitored space cooling delivery from the HPWH in the range of 12,000 to 17,000 Btu/day per day. A combination of high space cooling energy use at the two sites, along with fairly strong variability in cooling usage, made it challenging to resolve the small HPWH cooling benefit from the monitored cooling system energy use. However, given the observed patterns of cooling operation at the two sites and the measured HPWH delivered cooling, annual space cooling energy savings of 121–135 kilowatt-hours (kWh) per year are projected. These savings increase the annual estimated HPWH energy savings by 5-9%.

Customer satisfaction with the installed HPWHs was generally high with both households valuing the cooling delivery indoors. In addition, one site (a six-person household) strongly noted improved hot water delivery characteristics relative to their prior electric-storage water heater. Although this study focused solely on summer impacts, supplemental funding from partners Redding Electric Utility and Pacific Gas and Electric extended the monitoring period through May 2015. Collecting a full year of monitoring data is valuable in developing a better understanding of annual performance characteristics and customer satisfaction with winter HPWH operation.

Page 7: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

vi

Table of Contents List of Acronyms ........................................................................................................................................ iv Executive Summary .................................................................................................................................... v List of Figures ........................................................................................................................................... vii List of Tables ............................................................................................................................................. vii 1 Background and Motivation ................................................................................................................ 1

1.1 Related Research .............................................................................................................................. 2 1.2 Research Questions .......................................................................................................................... 3

2 Methodology ......................................................................................................................................... 4 2.1 Site Selection ................................................................................................................................... 4 2.2 Equipment Selection ........................................................................................................................ 7 2.3 Heat Pump Water Heater Monitoring Approach ............................................................................. 8 2.4 Uncertainty of Calculations ........................................................................................................... 11 2.5 Climate Influences ......................................................................................................................... 13

3 Results ................................................................................................................................................. 15 3.1 Baseline Water Heater Monitoring ................................................................................................ 15 3.2 HPWH System Commissioning and Operational Issues ............................................................... 16 3.3 Monitored HPWH Performance .................................................................................................... 19 3.4 Air Conditioning Impact ................................................................................................................ 23 3.5 Ducting Kit Summer Impact .......................................................................................................... 25 3.6 Preliminary Annual Savings Projections ....................................................................................... 27 3.7 Initial Homeowner Reactions ........................................................................................................ 28

4 Conclusions ........................................................................................................................................ 30 4.1 Level of Cooling Energy Savings that can be Achieved ............................................................... 30 4.2 General Level of Homeowner Satisfaction .................................................................................... 30 4.3 Recommendations to Improve the Ducted HPWH Installability, Operation, and Performance .... 31

References ................................................................................................................................................. 32 Appendix A: Determination of Preliminary Annual Performance Impacts ......................................... 33

Page 8: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

vii

List of Figures Figure 1. Simplified HPWH schematic .......................................................................................................... 1 Figure 2. Street view of Site 1 ....................................................................................................................... 5 Figure 3. Street view of Site 2 ....................................................................................................................... 5 Figure 4. Site 1 water heater location ........................................................................................................... 6 Figure 5. Site 2 water heater location ........................................................................................................... 7 Figure 6. Schematic of ducted HPWH configuration and monitoring points ............................................... 10 Figure 7. Official National Weather Service daily recorded Redding temperatures ................................... 14 Figure 8. Water heater cold water inlet temperatures by site ..................................................................... 14 Figure 9. Sample Site 2 electric water heater baseline monitoring............................................................. 15 Figure 10. Baseline electric water heater energy use vs. load ................................................................... 16 Figure 11. Installed HPWH at Site 1 ........................................................................................................... 17 Figure 12. Site 2 ducting run to outdoors .................................................................................................... 18 Figure 13. Site 2, HPWH evaporator leaving air discharge to kitchen ........................................................ 18 Figure 14. Sample HPWH demand profiles (15 minute interval data) ........................................................ 19 Figure 15. Average summer HPWH demand profile (15-minute interval data) .......................................... 20 Figure 16. Daily HPWH energy use as a function of hot water use ............................................................ 21 Figure 17. Comparison of electric-resistance and HPWH daily energy use ............................................... 22 Figure 18. Daily HPWH COP as a function of recovery load ...................................................................... 22 Figure 19. HPWH evaporator air conditions and delivered cooling ............................................................ 23 Figure 20. Monitored daily cooling energy use as a function of outdoor maximum temperature ............... 24 Figure 21. 15 minute interval indoor temperature data (May 22 – September 14, 2014) ........................... 25 Figure 22. Comparison of average HPWH inlet air conditionson entering wet-bulb temperature .............. 27

Unless otherwise noted, all figures were created by the ARBI team.

List of Tables Table 1. Characteristics of Monitoring Test Sites ......................................................................................... 4 Table 2. Equipment Specifications ................................................................................................................ 8 Table 3. Monitoring Sensor Specifications .................................................................................................... 9 Table 4. Instrument Uncertainties ............................................................................................................... 12 Table 5. Heat Flow Uncertainty Calculations .............................................................................................. 13 Table 6. Impact of Ducting Kit on Summer HPWH Inlet Conditions ........................................................... 26 Table 7. Preliminary Annual Performance Projections ............................................................................... 28 Table A1. Performance Projections for Installed HPWHs ........................................................................... 35

Page 9: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

1

1 Background and Motivation

Quantifying the water heating performance and space conditioning impacts of heat pump water heaters (HPWHs) operating within conditioned space is an important Building America research topic as it provides critical data on a broader systems level. This kind of comprehensive field research is needed in a variety of applications and climates to inform not only on the performance and cost-effectiveness implications, but also on issues such as customer satisfaction primarily related to noise. To date, field studies have been undertaken in many parts of the country; however, in terms of indoor HPWH installations, the major research focus has been on assessing performance impacts on space-heating loads. This study expands the understanding of indoor HPWH performance by focusing hot-dry climate applications where cooling load interactions are the primary concern. Monitoring the space-cooling benefits advances Building America research efforts by quantifying performance impacts in a hot-dry climate. With favorable results, this approach could be promoted as a preferred strategy for specific regional applications in both new construction and retrofit applications.

Figure 1 shows how HPWHs operate by taking surrounding air, passing it over the evaporator coil, and exhausting cooler air to the surrounding air space, or into a ducting kit for delivery away from the unit. (Since typical HPWH installation criteria suggest a 700-1000 ft3 volume of adequate dilution of evaporator leaving air, the ducting kit serves as an approach to allow installations in more confined spaces.) More heat than is removed from the evaporator is rejected to the storage tank, based on the operating efficiency of the unit.

Figure 1. Simplified HPWH schematic

Many HPWHs are installed in unconditioned spaces such as garages and attics, while some are installed in conditioned space such as basements or laundry rooms and interior closets. The units installed in conditioned space impact space conditioning loads to varying extents depending on climate and hot water loads. In heating-dominated climates, the impact is largely negative as additional heat from the space-heating system is needed to offset the evaporator heat removal. In

Page 10: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

2

mixed climates the impact may be neutral. However, in cooling-dominated climates, an indoor HPWH may be able to generate sufficient cooling season benefits to more than offset any winter heating penalty. It should be noted, however, that the heating season penalty is likely to be greater than the cooling season benefit.

The availability of HPWH ducting kits from several manufacturers allow to seasonally control the airflow paths for air entering and leaving the HPWH. During the summer season, either indoor or outdoor air can enter the HPWH evaporator and cooled air can be delivered indoors. Conversely, in the winter season, the exclusive use of outdoor air and leaving air routed outdoors would eliminate any negative impact on space-heating loads. This improved control allows for optimizing space conditioning impact. Any applications whereby the house can be depressurized with HPWH operation should be carefully evaluated in conjunction with indoor combustion appliances.

1.1 Related Research Prior work in this area includes a monitoring study by NRCan at the twin test houses located in Ottawa, Canada. In this test configuration, the two identical “twins” were calibrated against each other, allowing for equipment changes in one house to be compared to a benchmark system in the second house. Martin Thomas presented results from this study (Heat Pump Water Heaters: Whole House Effects –Heating & Cooling Seasons) at the 2013 ACEEE Hot Water Forum1. In this testing project, one house had an electric storage water heater in the basement and the other had an HPWH. Findings for the Ottawa climate suggest that in the heating season, any HPWH energy savings relative to electric-resistance water heating are essentially offset by space-heating system energy use. In the short Canadian summer season, project findings showed a 20% reduction in overall house cooling and water heating energy use, amounting to approximately 7 kWh/day for the “typical” hot water loads used in the study.

The Northwest Energy Efficiency Alliance (NEEA) completed a 30-home field study of HPWHs installed in the Pacific Northwest in late 2013 (Fluid Market Strategies, 2013). Some of the homes included HPWHs with ducting kits, although the focus of that study was on HPWH performance, not on space conditioning impacts. A second ongoing field study of 50 homes is assessing the space conditioning impacts in more detail.

Southface, working under the National Association of Home Builders Research Center IP team, has a project were HPWHs are installed indoors at 15 duplexes in Lafayette, GA. The water heating system is ducted and draws air from, and rejects it to, an encapsulated attic space. Another recent hot/humid project involved the Consortium for Advanced Residential Buildings (CARB) team monitoring a 50-gallon General Electric HPWH installed in the unvented attic of a house in Windmere, FL (Williamson and Puttagunta, 2013). Over a four-month summer period, the unit operated at a COP of 2.2.

NREL completed a detailed Transient System Simulation program modeling study (Maquire et al, 2013) of HPWHs in the seven Building America climate zones to assess both water heating source energy impacts relative to conventional gas and electric storage water heaters, as well as determining both the impact of indoor HPWH operation on space conditioning loads. Detailed

1 http://www.aceee.org/conferences/2013/hwf/program

Page 11: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

3

results are provided in Appendix A. For an indoor 50-gallon HPWH compared to an electric storage water heater in a home conditioned with an air source heat pump, the average annual space cooling source energy benefit was projected to be 41% of the space-heating penalty. The combined annual space conditioning impact resulted in a 14% reduction in the water heating-only savings. In the hot-dry climate, space conditioning is more favorable; however, there is still an overall negative impact on an annual basis (annual space-cooling benefit is 77% of the annual space-heating penalty).

A recent Pacific Northwest National Laboratory (PNNL) study tested HPWHs in various ducting configurations at two PNNL lab homes that were heavily instrumented (Widder et al, 2014). The study found that in the Richland, WA climate, the penalty of installing a HPWH indoors may not be as large as modeling studies indicate. The report suggests that a fully ducted HPWH decreased heating, ventilating, and air conditioning (HVAC) energy use by 7.8% ± 2.3% as compared to a case with an unducted HPWH.

1.2 Research Questions The proposed work expands the geographical and climatic documentation of indoor HPWH performance, as well as evaluating the ducting kit impacts. Findings from this and the other projects could be used in refining performance modeling in the Building Energy Optimization model, which currently assumes the HPWH does not interact with indoor thermal systems.

A key focus of this project is to assess indoor HPWH water heating performance and impact on summer space conditioning energy use under various operating modes. As noted previously, the timeline for this research project required completion in 2014, limiting the assessment to summer testing. In addition, the project team is interested in assessing homeowner satisfaction with the HPWH relative to their experiences with their prior electric storage water heater.

Key research questions include the following:

1. What level of cooling energy savings can be achieved by a ducted HPWH in a hot-dry climate with more than 1,900 cooling degree days?

2. What is the general level of homeowner satisfaction with the indoor HPWH in terms of perceived energy savings, hot water delivery characteristics, noise, and thermal comfort impacts?

3. Based on the field testing results, what recommendations can be made to improve the ducted HPWH installability, operation, and performance?

Project partner Redding Electric Utility (REU)2, who helped identify sites and supported the installation of the HPWH’s for this project, is interested in extending the current Building America-funded effort to continue through the upcoming heating season. Adding the winter performance assessment in a hot-dry climate will help expand the current summer results. Nevertheless, quantifying summer cooling system performance impacts of indoor HPWH’s in a hot-dry climate is a critical step in advancing the understanding of HPWH performance in different climates and applications.

2 REU serves 86,000 residential and commercial customers in Northern California.

Page 12: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

4

2 Methodology

2.1 Site Selection The Alliance for Residential Building Innovation ARBI team approached REU in the summer of 2013 to assess their interest in participating in a HPWH field monitoring project focused on both water heating performance and impacts on summer cooling load. REU, an all-electric utility located in Northern California, serves approximately 86,000 residential and commercial customers. Although natural gas is available in much of the area, electric storage water heaters are fairly common in their service territory. ARBI, REU, and local high-performance building contractor, The Energy Docs, identified a short list of candidate sites that met the following criteria:

Existing indoor electric storage water heater

Interest in participating in the project

Stable and consistent home occupancy during the 2014 summer. To encourage participation in the project, REU agreed to cover the cost of installation of the HPWHs for each of the homeowners. The utility is particularly interested in gaining firsthand experience with monitored HPWH locations in their service territory. In addition to understanding summer performance of the HPWHs, they are also interested in funding ongoing monitoring through the winter season.

Two sites were identified that met these criteria. Basic characteristics of the two sites are identified in Table 1.

Table 1. Characteristics of Monitoring Test Sites

Parameter Site 1 Site 2

House floor area (ft2) 2,037 (3 story) 2,740 (2 story) Year constructed ~1980 1987 Occupants Two adults Six (2 adults, one child < 10,

three 10-20 year olds) Existing electric storage water heater

50-gallon Bradford, White 50-gallon Bradford, White

HVAC system description

Two packaged heat pumps (age estimated at 20+ years)

1. BDP 542D032HP 2. No nameplate on

unit

Two split-system heat pumps (both original equipment)

1. Bryant 663CJ036 2. No nameplate on unit

Page 13: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

5

Figure 2. Street view of Site 1

Figure 3. Street view of Site 2

Figure 4 shows the location of the existing electric water heater (within the music studio) at Site 1. The lower floor of the house shown has two floors of living space above. The downstairs is largely built with masonry block wall construction. Although within the thermal envelope, the

Page 14: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

6

music studio does not have direct space conditioning. At the time of installation, the owners were indirectly cooling the music studio area by opening the door to the wine room. The owners expressed strong interest in adding cooling to the space to supplement the use of fans during hot summer nights. They were also concerned about coring through the block walls to accommodate the ducting as they would likely abandon it at the end of the project. As a result, the HPWH unit was installed in the space without any ducting of air entering or leaving the evaporator. The thermostat controlling the first floor HVAC unit was located on the floor above the water heater location.

Figure 4. Site 1 water heater location

Figure 5 shows the configuration of the first floor at Site 2. The existing electric water heater is located in the laundry room. This house presented much more flexibility at integrating ducting on the supply and return sides of the HPWH. Approximately 10 feet of six-inch flex duct was added and ducted to the outdoors and to the kitchen register location3. As shown in the figure, the concept was to run an inlet duct from outdoors to the unit and a duct leaving the unit to outdoors (via the attic) or to the kitchen area, where additional cooling is often desired in hot climates like Redding. The first floor HVAC unit thermostat is located in the living room area and is far enough removed from the HPWH kitchen supply register as to not be directly impacted by the unit’s operation.

3 The manufacturer states that “maximum duct length shall not exceed 25 feet in length and shall not have more than three 90°elbows”… and for “duct lengths longer than 10 feet, but not exceeding 25 feet, rigid ducting with a smooth inner surface is recommended.”

Page 15: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

7

Figure 5. Site 2 water heater location

2.2 Equipment Selection The goal of this project was to install a fully ducted HPWH (both inlet and outlet ducted to conditioned space and outside) in both field sites to be able to test the unit by varying the source of evaporator air and controlling the leaving air delivery to either indoors or outdoors. Several manufacturers provide the capability to fully duct their units including General Electric, A.O. Smith, and Air Generate. In discussions with staff at NEEA, the team selected the Air Generate brand as the preferred choice for this project due primarily to their favorable experiences with the unit in terms of low noise levels4. As noted, noise levels are critical to ensuring customer satisfaction.

The ARBI team and The Energy Docs reviewed the household size and demographic information with Air Generate support engineers and determined that appropriate sizing for the two units would be a 66-gallon ATI66 model for Site 1 and an 80-gallon ATI80 for Site 2. Specifications for the two units can be found in Table 2. Typical evaporator airflows are in the range of 250 to 275 cfm unducted, with reduced airflow with the installation of a ducting kit and ductwork.

4 NEEA has had several larger detailed field monitoring studies over the past few years with tens of units being monitored. The observed lower noise levels within this unit were a key factor in selecting this brand versus competing brands.

Page 16: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

8

Table 2. Equipment Specifications

Parameter ATI66 ATI80

Tank volume 66 gallons 80 gallons EF (hybrid mode) 2.35 2.2 First Hour Rating (hybrid mode) 70 gallons 80 gallons Heat Pump Btu Rating 2.5 kW 2.5 kW Backup Electric Element 4.0 kW 4.0 kW Refrigerant R410A R410A Tank Height 70.5” 75.5” Weight (dry) 243 lbs 254 lbs Duct Kit Connection Diameter 6” 6” Decibel Rating 48 db 48 db

2.3 Heat Pump Water Heater Monitoring Approach The experimental design focused on testing the two installed HPWHs to monitor HPWH performance, as well as to determine resulting summer space cooling energy impacts. The expectation in a hot climate like Redding is that it should be easier to resolve space cooling impacts as the cooling system operates on most of summer days5.

The two sites were equipped with Data Electronics DT50 data loggers and modems for collecting, storing, and transferring data on a daily basis to the ARBI host computer at the Davis Energy Group offices. Table 3 summarizes the installed data points and sensors. The “ID” column in the table correlates the sensors to their installation location on the water schematic heater shown in Figure 6. Manual dampers are shown, depicting the dual flow paths on both the evaporator inlet and outlet sides. On the inlet side, air from either outdoors or the interior space can be selected. On the outlet side, the cooled air can either be directed indoors (during the summer season) or direct outdoors (during the winter season6). The indoor temperature/resistance heat (RH) sensor was located adjacent to the first floor indoor HVAC thermostat and the outdoor sensor with gill radiation shield was located on the north side of each home. In addition to installing power monitors to record total water heater energy use (and backup electric-resistance energy use for the HPWH), power monitors were installed on the two AC condensing units (or packaged heat pumps) at each site.

The programmable data logger was configured to capture data at multiple logging intervals, as described below. Onboard data logger memory is sufficient to store more than one week of data, so any short-term communication losses do not interrupt the data stream. Data storage cards were also installed in the data logger to provide added data backup capability.

The flow meter was scanned continuously to detect the initiation of a hot water draw event. Once flow is detected, the data logger initiates 4-second interval logging of water flow, as well as water heater inlet and outlet water temperatures. Equation 1 describes the energy calculation performed on the 4-second interval when flow is occurring. This high-resolution logging

5 In milder climates, the HPWH benefit on space cooling energy use is harder to determine as the occupant’s variable use of natural ventilation impacts how much benefit actually offsets space cooling usage. 6 This study was limited to summer-only monitoring, but additional utility funding allowed the work to continue through the 2014-15 winter.

Page 17: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

9

continues for the duration of the hot water draw event. In addition, a second logging schedule was programmed to occur on a fixed 15-minute interval. This fixed interval logging included:

Average indoor and outdoor dry bulb temperature and RH

Average HPWH inlet and leaving air temperature and RH during operation

HPWH electrical energy consumption (total unit and electric resistance only)

AC (or packaged heat pump) average demand during the 15-minute interval

HPWH and cooling system run fraction during the 15-minute interval

Total volume of hot water flow and energy delivered (as defined in Equation 1).

Equation 1: = . . °

( ) . )

where,

Qi = energy content of water flow during four second interval “i” (kBtu/4 seconds)

Vi = hot water flow volume during four second interval “i” (gallons/4 seconds)

THi = temperature leaving the water heater in (ºF) during interval “i”

TLi = temperature entering the water heater in (ºF) during interval “i”

Table 3. Monitoring Sensor Specifications

Type Application ID Mfg/Model Signal Span Accuracy Duct temp./RH

HPWH inlet and outlet air

5,6 7,8

Vaisala HMD42 4-20 mA -4 to 140oF

0 – 100% ±0.54 oF @ 68°F ±3% RH (30-70%)

Wall mount temp./RH

Indoor air temperature and RH

n/a Vaisala HMW82 4-20 mA -4 to 140oF

0 – 100% ±0.54 oF @ 68°F ±3% RH (30-70%)

Outdoor air temp./RH

Shielded outdoor sensor n/a RM Young

model 41372 4-20 mA 14 to 140oF 0 – 100%

±0.54 oF ±3% RH (10-90%)

Power monitors

HPWH and AC power

11, 12

Wattnode/ WNA-1-P-240-P

pulse 0-30A ±1.5% of reading

Flow meter

Flow to water heater (cold) 15 Onicon F-

1300 Frequency output n/a ±2% of reading

from .8 to 38 gpm Immersion thermocouple

Hot and cold side temps 9,10 Gordon

20CTOUH mV n/a ±0.9°F

Page 18: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

10

Figure 6. Schematic of ducted HPWH configuration and monitoring points

HPWH efficiency calculations were completed on a daily basis. Although these calculations could be completed on either shorter or longer time scales, the daily COP calculation was chosen as a reasonable performance metric to document performance and influences due to hot water load variations. A shorter COP calculation procedure is challenging as HPWH operation is largely disconnected from many hot water load events. For example, a two-hour COP calculation metric may exhibit hot water loads, but no HPWH heating operation, or vice versa. Longer intervals would smooth out any effects that may influence system performance, but also tend to smooth out any performance variability. Equation 2 presents the daily COP calculation used in this study. Note that the calculated COP is based on the sum of the daily energy leaving the hot

Page 19: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

11

water tank (i.e., recovery load), not the input to the tank. In a lab setting, a vertical stalk of thermocouples is commonly installed in the tank to record tank temperature at different points in the tank, allowing for calculation of an average tank temperature.

Equation 2: ( ) = ( ÷ ) ÷ .

where,

Qi = water heater energy delivered for interval “i”

EWHj (kWh) = water heater energy electrical consumed for interval “j”

“i = 1 to m” = “m” is the number of four second intervals/day with flow

“j = 1 to 96” = 96 fifteen minute interval data records per day

2.4 Uncertainty of Calculations Uncertainties7 in the measured variables are published in instrument technical specifications and are presented below in Table 4. Assuming the uncertainties of the measured variables are not correlated, the total uncertainty (UR) in the system variable can be approximated using the delta method, as shown below.

Equation 3:

Where:

is the sensitivity coefficient [partial derivative of Performance Metric, in this case R, with respect to measured variable (xi)]8 and is the uncertainty of the measured variable.

7 As used in this analysis “uncertainty” is defined as half the width of a confidence interval or a standard deviation around a measurement value. 8 The partial derivatives depend on the values of the lower level variables and so (typically) unlike the uncertainties of the lower level measurements, it depends on the value of “x.” The resulting sensitivity coefficient can change over the range encountered. This can result in situations in which one of the measured variables is the critical one within part of the operating range; however, another becomes more critical in another range.

Page 20: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

12

Table 4. Instrument Uncertainties

Instrument Uncertainty (uXi) Immersion Thermocouple ± 0.9ºF

Immersion Flowmeter ± 2.0%

Power Transducer ± 1.5%

In this study, uncertainty is determined via the Engineering Equation Solver (EES)9. The EES helps determine an error percentage for the metric of interest over a known range of values. This maximum percentage of error at the smaller timescale was then applied to the larger daily sums.

The DHW heat flow relationship, as defined in Equation 1, results in the “Q” uncertainty as shown in Equation 4.

Equation 4. = ± + +

Normal DHW events represent a range of flow rates, inlet and outlet water conditions, and Table 5 characterizes the uncertainty for a range of temperature conditions and flow rates. Hot water temperature, Th, is normally in the 125ºF range, although lower temperatures occur under short-duration, high-load events. Cold water temperature, Tl, varies seasonally, with much of California conditions falling in the 55–75ºF range. Flow rates depend on a wide range of factors and vary from less than one tenth of a gallon per minute to 3 to 4 gpm. The vast majority of hot water events over the course of a year will fall in a 1.0 to 1.5 gpm window.

In the case of heat flow, the uncertainties over the range of expected values indicate a maximum uncertainty of 4.1%.

COP calculations were completed on a daily basis. This involved the summation of the water heater energy flows over the course of the day, divided by the HPWH energy input (as defined in Equation 2). Equation 5 reflects the COP uncertainty in terms of energy flow (Q) and the electrical energy uncertainty (W).

Equation 5. = ± +

To assess typical COP uncertainties, two representative cases were evaluated based on ranges identified from the monitoring data. A low-usage day with a recovery load of 10,000 Btu/day and 1.24 kWh consumption and a high-usage day with a recovery load of 50,000 Btu/day and 6.37 kWh consumption. The resulting COP uncertainty ranged from 3.9–4.3% for the two cases.

9 http://www.fchart.com/ees/

Page 21: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

13

Table 5. Heat Flow Uncertainty Calculations

Th Tl gpm Q (Btu) uQ (±Btu) uQ%/Q

130 55 0.5 312.4 8.6 2.7% 130 55 1.5 937.1 25.8 2.7% 130 55 2.5 1562.0 42.9 2.7% 130 65 0.5 270.7 8.0 3.0% 130 65 1.5 812.2 24.0 3.0% 130 65 2.5 1354.0 40.1 3.0% 130 75 0.5 229.0 7.5 3.3% 130 75 1.5 687.2 22.4 3.3% 130 75 2.5 1144.9 37.3 3.3% 115 55 0.5 249.9 7.7 3.1% 115 55 1.5 749.7 23.2 3.1% 115 55 2.5 1250.0 38.6 3.1% 115 65 0.5 208.3 7.2 3.5% 115 65 1.5 624.8 21.6 3.5% 115 65 2.5 1041.0 36.1 3.5% 115 75 0.5 166.6 6.8 4.1% 115 75 1.5 499.8 20.3 4.1% 115 75 2.5 832.9 33.8 4.1%

2.5 Climate Influences The Redding location was selected as a preferred field test location for two primary reasons: A local utility with significant electric-resistance water heating market share, and a very hot climate (2003 cooling degree days at base 65) that provides for a more suitable testing location to assess summer space-cooling benefits derived from utilizing the HPWH cooled evaporator leaving air. Redding is located 160 miles north of Sacramento near the northern end of the Central Valley of California. Summer weather conditions in this area are more extreme than the Sacramento area, since any moderating coastal influence is mitigated. Figure 7 presents daily maximum, minimum, and average outdoor temperatures during the period of monitoring from May 1, 2014, through September 14, 2014. Extended periods with high temperatures exceeding 95ºF and lows exceeding 65ºF provide a good testing framework for consistent cooling operation and ability to utilize HPWH evaporator leaving air.

The City of Redding has both surface water and groundwater as part of its municipal water service. The Sacramento River (fed by upstream Lake Shasta) and nearby Whiskeytown Lake provide 74% of the Redding municipal water supply, while the remaining 26% is groundwater that comes from 16 city wells. Both surface water sources provide relatively cold water supplies generated largely from snowmelt. This combination of surface and ground water resulted in interesting monitored cold water temperature variations at the two sites. Figure 8 plots monthly average recorded temperatures during periods when cold water is flowing into the water heater. Site 1 shows average monthly cold water temperatures, as much as 15ºF cooler than Site 2, likely due to the local source of potable water. Site 2 also demonstrated an interesting solar heating effect. On summer days with both early morning hot water draws and draws around 5 p.m.,

Page 22: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

14

monitored cold water temperatures during the later hours would average 7–8ºF higher than in the morning. Our hypothesis is that the cold water supply line to the house is under the driveway, which heats up considerably in the hot Redding summer climate.

Figure 7. Official National Weather Service daily recorded Redding temperatures

Figure 8. Water heater cold water inlet temperatures by site

30

40

50

60

70

80

90

100

110

120

1-M

ay

8-M

ay

15-M

ay

22-M

ay

29-M

ay

5-Ju

n

12-Ju

n

19-Ju

n

26-Ju

n

3-Ju

l

10-Ju

l

17-Ju

l

24-Ju

l

31-Ju

l

7-Au

g

14-A

ug

21-A

ug

28-A

ug

4-Se

p

11-S

ep

Out

door

Tem

pera

ture

(deg

rees

F)

Dry Bulb Max (Avg June 1 to Sept 14 = 97.4F)

Dry Bulb Min (Avg June 1 to Sept 14 = 64.6F)

Dry Bulb Avg (Avg June 1 to Sept 14 = 81.3F)

50

55

60

65

70

75

80

April May June July August Sept

Cold

Wat

er In

let T

empe

ratu

re D

urin

g Fl

ow (d

egre

es F

)

Site 1

Site 2

Page 23: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

15

3 Results

3.1 Baseline Water Heater Monitoring Monitoring equipment was installed on April 23 and April 24, 2014, at the two sites. Baseline electric storage water heating data were desired to document the performance and energy usage of the conventional system type, as well as to troubleshoot any startup issues with the monitoring system. At Site 2 (with six residents), the inability of the existing 50-gallon storage water heater to consistently satisfy the hot water loads was immediately confirmed by monitoring data. Figure 9 plots 4-second interval hot water temperatures and hot water flow rates over a day-and-a-half period10. The number of hot water tank “run outs” is evident on several occasions over this period of time, with the lowest observed hot water supply temperature under 90ºF. Figure 10 plots daily electric water heater energy use versus gallon-per-day consumption for the two sites. Both sites shows the anticipated well-correlated hot water energy use versus load, with Site 2 showing distinctly lower electrical consumption per gallon of hot water, likely due to a combination of warmer inlet (cold) water temperatures and the common hot water tank run outs.

Figure 9. Sample Site 2 electric water heater baseline monitoring

10 Note: Only data with flow is show.

0.00.51.01.52.02.53.03.54.04.55.05.56.06.57.07.58.0

0

20

40

60

80

100

120

140

160

4/24

/14

14:2

9

4/24

/14

17:2

0

4/24

/14

17:2

7

4/24

/14

19:2

0

4/24

/14

19:4

4

4/24

/14

20:3

3

4/24

/14

20:4

0

4/24

/14

23:0

4

4/25

/14

6:05

4/25

/14

6:35

4/25

/14

7:03

4/25

/14

7:42

4/25

/14

7:48

Hot W

ater

Flo

w R

ate

(gpm

)

Wat

er H

eate

r O

utle

t Tem

pera

ture

(F)

Water heater outlet temperature

Hot Water flow rate

Page 24: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

16

Figure 10. Baseline electric water heater energy use vs. load

3.2 HPWH System Commissioning and Operational Issues The HPWHs, minus the ducting kits, were installed on May 22 at Site 1 and May 23 at Site 2. After repeated interactions with the homeowners and the installing contractor (Energy Docs), the decision was made to not install a ducting kit at Site 1 since the only aesthetically feasible approach to running ducting from the water heater location to both outdoors and a central interior location would have required penetrating masonry block walls at two locations. From the viewpoint of the homeowner, this approach was not acceptable, since they were uncertain whether they would want the ducting to remain after the end of monitoring. Based on the owner’s input, the decision was made to drop the ducting kit implementation at Site 1.

After installation, the units were immediately operated in HPWH “Auto” mode11 for initial shakedown monitoring at a setpoint of 125°F12. The ducting kit for Site 2 was not originally in stock with the manufacturer and had to be shipped as part of a larger order from China. The kits did not arrive until late-June and was installed on June 30. The ducting at Site 2 was configured to provide HPWH evaporator entering air from either the laundry room or outdoors, and exhaust evaporator leaving air to the kitchen area or outdoors.

Another minor issue occurred related to the HPWH control boards. During the course of the summer monitoring, the intent was to collect a period of electric-resistance-only operating data

11 Auto mode provides for heat pump priority with electric-resistance backup when the unit cannot adequately maintain tank conditions. 12 125°F setpoint was maintained throughout the summer monitoring at both sites.

y = 0.137x + 0.7469R² = 0.9871

y = 0.1179x + 0.0236R² = 0.8752

0

2

4

6

8

10

12

14

16

18

0 20 40 60 80 100 120 140

Daily

Ele

ctric

Sto

rage

Wat

er H

eate

r Usa

ge (k

Wh/

day)

Daily Hot Water Usage (gal/day)

Site 1- Existing WH

Site 2- Existing WH

Page 25: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

17

with the HPWH13 to provide mid-summer documentation of performance to supplement the late-April to mid-May existing water heater monitoring. During the implementation of the resistance-only mode of operation on the Site 1 unit, monitoring indicated that the control change did not affect operation. The manufacturer contact was notified and reported that there was apparently a control issue that required a new control board. The boards were shipped from China, causing an additional delay in testing this mode. Once resolved, a 10-day testing period in electric-resistance mode was completed at Site 1; however, no testing was completed at Site 2. With the exception of this identified issue, both units operated reliably for the duration of the summer.

Figure 11 documents the installed unit at Site 1. Figure 12 shows the Site 2 unit installed in the laundry room with horizontal ducting penetrating the laundry room cabinet (to the left) to outdoors, and vertical ducting entering the attic to serve either the new kitchen duct (see new supply grille on the upper right of Figure 13) or dump evaporator leaving air into the attic.

Figure 11. Installed HPWH at Site 1

Photo credit: M. MacFarland, reprinted with permission

13 The unit’s manual indicates the capability to set electric-resistance operation for up to 999 hours, at which time the unit will revert to heat pump operation.

Page 26: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

18

Figure 12. Site 2 ducting run to outdoors

Photo credit: M. MacFarland, reprinted with permission

Figure 13. Site 2, HPWH evaporator leaving air discharge to kitchen

Photo credit: M. MacFarland, reprinted with permission

New register

Page 27: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

19

3.3 Monitored HPWH Performance The HPWHs were installed without ducting kits on May 22 at Site 1 and on May 23 at Site 2. The units were set up in “hybrid” mode, allowing for simultaneous compressor and back-up electric element operation, if the controls determined that the tank setpoint was not being adequately met by the compressor operation. Figure 14 plots five sample water heating cycles to characterize the timing, duration, and profile of individual days of water heating operation at the two sites. As one would expect with a compressor-based system, the demand is generally lowest at the start of the cycle and increases as the tank temperature increases during the typical 2.5- to 4-hour heating cycle. The red line shows a dip shortly before midnight as hot water loads during the recovery cycle drive the tank temperature down, reducing the system condensing temperature. The purple line shows a rare summer case where electric-resistance operation is required to maintain adequate tank temperatures during the recovery cycle. Over the full summer monitoring period, the electric-resistance heating represented only 4–7% of total unit consumption, with the higher value associated with Site 1 (smaller 66-gallon tank) where hot water loads for the two person household appeared to be more variable day-to-day, as well as more intense in duration.

Figure 14. Sample HPWH demand profiles (15 minute interval data)

Figure 15 plots the observed average HPWH demand profile during the June 6 through September 23 period. With peak observed “compressor-only” unit demands in the 0.9 kW range, the data suggests the maximum peak summer operating demand at a level ~ 2/3 lower than 0.9 kW. Due to their relatively low early morning hot water consumption, Site 1 operation shifted to later in the day than Site 2. The shape of the profile provides a direct representation of when cooling is being provided to conditioned space and also contributing to peak air conditioning load reduction. With typical California electric utility peak demand periods in the 4 to 7 p.m.

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

0:00

:00

2:00

:00

4:00

:00

6:00

:00

8:00

:00

10:0

0:00

12:0

0:00

14:0

0:00

16:0

0:00

18:0

0:00

20:0

0:00

22:0

0:00

0:00

:00

HPW

H To

tal U

nit D

eman

d (k

W)

Page 28: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

20

window, neither of the two sites demonstrated an optimal alignment with that time period in terms of cooling delivery to offset peak space cooling demand.

Average hot water consumption from May 23 through September 14 averaged 44.4 gallons per day (gpd) for Site 1 and 66.9 gpd for Site 2. Although Site 2 has higher usage, Site 1 consumption (nominaly two occupants) is roughly double that of Site 2 (nominally six occupants) on a per-capita basis. The 11.1 to 22.2 gpd per-person consumption reflects not only the colder inlet water temperatures at Site 1, but also the level of variability that one can expect among households14.

Figure 16 plots daily HPWH energy use (excluding any resistance only modes of operation) as a function of daily hot water load. There are two points of interest: (1) the linear regression offset between Site 1 and 2 is consistent with that shown in the baseline monitoring (Figure 10) and likely due to consistently colder inlet water temperatures, and (2) the daily data are not as well correlated as Figure 10 due to occasional resistance heating usage spikes and end-of-day carryover effects that are more pronounced with the larger storage tank systems.

Figure 15. Average summer HPWH demand profile (15-minute interval data)

14 Interestingly, the average of the two sites is very close to the 15.6 gpd/person monitored hot water consumption documented in an 18-home California hot water monitoring study (Hoeschele and Weitzel 2013).

-

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0:00

:00

2:00

:00

4:00

:00

6:00

:00

8:00

:00

10:0

0:00

12:0

0:00

14:0

0:00

16:0

0:00

18:0

0:00

20:0

0:00

22:0

0:00

0:00

:00

HPW

H Av

erag

e U

nit D

eman

d (k

W) Site 1

Site 2

Page 29: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

21

Figure 16. Daily HPWH energy use as a function of hot water use

Figure 17 plots both the electric RH and HPWH mode data that is shown in Figure 10 and Figure 16, as well as the Site 1 “HPWH (RH mode)” data for August 14–27. Slightly warmer cold water inlet temperatures and possibly reduced tank thermal losses contribute to the improved performance relative to the Site 1 “Existing WH” data. The performance advantage of the HPWH is clear at both sites, with typical daily energy savings in the 50–70% range for a given daily hot water consumption.

Figure 18 plots daily COP for both sites while the system was operating in the heat pump mode. A few daily COP values with no compressor operation and small amounts of energy delivered (i.e., recovery load on the water heater) generated high COPs that are not presented in the graph. Significant variations in daily COP are evident due to the timing of both hot water draws and heat pump operating cycles around the end of a day. For the time period monitored, recovery load weighted average COPs ranged from 2.60 at Site 1 to 2.85 at Site 2. The Site 1 performance is slightly lower due to the greater use of electric-resistance heating (7% of summer consumption at Site 1 vs. only 4% at Site 2). The smaller 66-gallon unit at Site 1 also exhibits a trend of decreasing efficiency at higher recovery loads, consistent with findings presented in the “CARB HPWH Measure and Strategy Guide” (Shapiro et al 2012). The few Site 2 (80-gallon HPWH) data points at higher loads appear less definitive in suggesting this trend.

y = 0.0431x + 0.3942R² = 0.6094

y = 0.0425x - 0.1911R² = 0.6898

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

0 10 20 30 40 50 60 70 80 90 100 110 120

Daily

Tota

l HPW

H Co

nsum

ptio

n (k

Wh/

day)

Daily Hot Water Consumption (gallons/day)

Site 1

Site 2

Page 30: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

22

Figure 17. Comparison of electric-resistance and HPWH daily energy use

Figure 18. Daily HPWH COP as a function of recovery load

y = 0.137x + 0.7469R² = 0.9871

y = 0.1179x + 0.0236R² = 0.8752

y = 0.0431x + 0.3942R² = 0.6094

y = 0.0405x - 0.0886R² = 0.6988

0

2

4

6

8

10

12

14

16

18

0 20 40 60 80 100 120 140

Daily

Ele

ctric

Sto

rage

Wat

er H

eate

r Usa

ge (k

Wh/

day)

Daily Hot Water Usage (gal/day)

Site 1 - Existing WH

Site 1 - HPWH (RH mode)

Site 2 - Existing WH

Site 1 - HPWH

Site 2 - HPWH

0.0

1.0

2.0

3.0

4.0

5.0

6.0

0 10000 20000 30000 40000 50000 60000

Daily

CO

P (B

tu/B

tu)

Daily Water Heater Recovery Load (Btu/day)

Site 1

Site 2

Page 31: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

23

3.4 Air Conditioning Impact An important goal in this project in addition to documenting HPWH field performance and operating characteristics is to try to quantify the cooling benefit that can be realized in a hot-dry climate. The recent PNNL HPWH report indicated a space-cooling benefit equivalent of approximately 1.5 kWh/day at a hot water usage level of 78.51 gallons per day (Widder et al, 2014). By measuring HPWH inlet and outlet air temperature and RH conditions and airflow rate15, one can calculate the sensible and latent cooling delivered by the unit. Figure 19 plots a 36-hour period at Site 2 with two HPWH cycles, both approximately 2.5 hours long. The lower portion of the graph plots evaporator entering and leaving air conditions during the cycles, and the upper portion of the graph plots the delivered cooling to the indoors. Leaving air temperatures are typically 25–30ºF cooler than entering air, and leaving RH is 40–50% higher than the dry indoor inlet conditions. Given the different hot water loads and operating efficiencies at each site, the full-summer average daily delivered cooling varies from 12,000 Btu/hr at Site 1 to 17,000 Btu/hr at Site 2. Although Site 2 had a higher daily HPWH space-cooling benefit, the duration of the cooling season impacts the length of time the cooling benefit actually offsets space cooling energy use.

Figure 19. HPWH evaporator air conditions and delivered cooling

15 Using the TEC Flow Blaster device

-2000-1800-1600-1400-1200-1000-800-600-400-2000200400600800100012001400160018002000

0102030405060708090

100110120130140150160170180190200

0:00

:00

2:00

:00

4:00

:00

6:00

:00

8:00

:00

10:0

0:00

12:0

0:00

14:0

0:00

16:0

0:00

18:0

0:00

20:0

0:00

22:0

0:00

0:00

:00

2:00

:00

4:00

:00

6:00

:00

8:00

:00

10:0

0:00

12:0

0:00

HPW

H C

oolin

g (Bt

u/15

min

utes

)

HPW

H Ai

r (de

g F,

RH%

)

HPWH Entering Air T

HPWH Entering Air RH

HPWH Leaving Air T

HPWH Leaving Air RH

HPWH Qsensible

HPWH Qtotal

Page 32: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

24

Monitoring air conditioner energy consumption at each of the two systems installed at both sites allowed characterization of cooling consumption as a function of outdoor temperature. Figure 20 plots total daily space cooling energy use as a function of maximum outdoor temperature. The difference between the two sites is surprisingly significant, as is the lower-than-expected correlation of cooling energy use with outdoor temperature. For the full monitored summer period (May 22 to September 14), Site 1 cooling energy use totaled 7,427 kWh, while Site 2 recorded a much more moderate consumption level of 2,330 kWh. The Site 1 consumption is very high (even by California standards for a very hot climate region) and can likely be attributed to poor equipment efficiencies, high duct losses, and extensive south facing glazing16. A significant driver on consumption is thermostat setpoint. Figure 21 plots monitored first-floor indoor temperatures as a proxy for the indoor setpoint. Site 2 occupants tolerate much warmer and more variable indoor temperatures, as well as warmer conditions during the middle of the summer, as evidenced by the shape of second order curve fits to the data.

Figure 20. Monitored daily cooling energy use as a function of outdoor maximum temperature

16 This house would make an interesting case study for a deep energy retrofit. This project scope was limited to the HPWH monitoring, otherwise all the identified issues could have been explored in more detail.

y = 2.6216x - 189.71R² = 0.5566

y = 2.7447x - 249.43R² = 0.5152

0

20

40

60

80

100

120

60 70 80 90 100 110 120

Daily

Coo

ling

kWh

Outdoor Maximum Daily Temperature (F)

Site 1

Site 2

Page 33: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

25

Figure 21. 15 minute interval indoor temperature data (May 22 – September 14, 2014)

3.5 Ducting Kit Summer Impact The HPWH ducting kit provides the ability to optimize system performance seasonally by controlling where evaporator inlet air is coming from (indoors or outdoors) and where the evaporator leaving air is directed (indoors or outdoors). In the heating season, it is preferable to eliminate the HPWH space cooling effect by directing evaporator leaving air outside of the conditioned envelope and using either outdoor or indoor air as the source for evaporator inlet air17. In the summer season, the cooling benefit of directing the HPWH leaving air indoors reduces cooling energy use, provided the air conditioner is being operated. Otherwise, the cooling benefit only serves to improve comfort. As shown in Figure 20, where Site 1 initiates cooling at maximum outdoor temperatures ~10°F lower than Site 2, variations in house load and comfort expectations have significant impact on the number of days the HPWH provides a space-cooling benefit that offsets a portion of the air conditioning system energy use. Using outdoor air as the evaporator inlet air in a hot climate such as Redding also provides the benefit of reducing the heat pump lift, increasing operating efficiency.

To try to quantify the summer impact of the ducting kit, data were collected from Site 2 in two operating modes: 1) evaporator inlet air from laundry room source (July 1–15), and 2) evaporator inlet air fed by outdoor air duct (August 30–September 14). Table 6 summarizes average outdoor and indoor conditions during that time period, as well as the HPWH evaporator inlet conditions during only the 15-minute logging intervals when the HPWH was operating. The Mode 1 period (using indoor air as the HPWH source) was mid-summer with outdoor temperature averaging

17 If there are indoor combustion appliances or wood burning stoves, depressurizing the house by using indoor air should be discouraged.

70

72

74

76

78

80

82

84

86

88

90

Firs

t Flo

or In

door

Tem

pera

ture

(deg

F)

Site 1

Site 2

Page 34: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

26

90°F and inlet air conditions to the HPWH during operation averaging 83.2°F (~7 degrees cooler than outdoors) and 32.9% relative humidity. Later in the summer in Mode 2, average outdoor air conditions were milder (80°F) and the resulting evaporator inlet air conditions during HPWH operation were slightly warmer (2°F warmer than outdoors) and dryer at an average condition of 81.9°F and 24.0%.

Ideally, with a vertical thermocouple stalk installed in the storage tank, field data could be used to calculate a 15-minute COP based on the energy added to the tank allowing for direct measurement of the energy input to the storage tank. However, within the scope and practical realities of this field monitoring effort, thermal monitoring was limited to the immersion thermocouple sensors on the water heater inlet and outlet. Performance maps generated during NREL laboratory testing of various HPWHs (Sparn et al, 2014) resulted in a series of plots characterizing HPWH COP variations as a function of evaporator entering air wet-bulb temperature and average tank temperature. These data were reviewed in conjunction with the observed inlet air temperature and RH data to approximate the magnitude of COP impacts due to varying the source of the inlet air. The NREL performance plots suggest a typical increase in COP due to a 4°F increase in wet-bulb temperature was on the order of 0.1 to 0.2. To get a handle on the expected performance impact of a change in wet-bulb temperature due to the ducting, wet-bulb temperatures were calculated based on a “typical” mid-summer indoor air source condition of 80°F and 32.9% RH, and a corresponding outdoor source air condition of 90°F and 24.0% RH. The resulting calculated 3.5°F increase in wet-bulb temperature shown in Figure 22 results in about a 0.1 to 0.2 COP improvement. Based on the conditions observed in this hot-dry climate, the COP impact is fairly small due to the dryer outdoor air partially countering the warmer air temperature; however, in a more humid climate, the benefit may be greater.

Table 6. Impact of Ducting Kit on Summer HPWH Inlet Conditions

HPWH Outdoor Indoor HPWH Inlet Air

Time Period

Inlet Air Source

Temperature (deg F)

RH (%)

Temperature (deg F)

Temperature (deg F)

RH (%)

Mode 1: July 1-15

Indoors (Laundry) 89.9° 45.9% 81.6° 83.2° 32.9%

Mode 2: Aug 30- Sept 14 Outdoors 80.1° 40.6% 78.0° 81.9° 24.0%

Page 35: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

27

Figure 22. Comparison of average HPWH inlet air conditions on entering wet-bulb temperature

3.6 Preliminary Annual Savings Projections Since heating season monitoring was not feasible within the project completion timeline, only preliminary estimates of annual performance can be developed at this time based on the summer monitoring results and other available data. The field monitoring project continued through the winter with support from utility partners Redding Electric and Pacific Gas and Electric.

The following simplified analysis provides a preliminary indication of full-season impacts in the Redding area. The extrapolations were developed taking into account observed hot water loads and space-cooling benefits, as well as other performance relationships and assumptions that are outlined in full detail in Appendix A. Modeled results presented in NREL’s assessment of HPWH performance throughout the United States (Maguire et al, 2013) are relied on heavily in this report as heating season impacts were not monitored. In the NREL study, the impact of an indoor HPWH on an air source heat pump heated home in the hot-dry climate region was estimated at 260 kWh/year.

Table 7 summarizes the key findings from this initial evaluation. Based on the hot water usage estimation from the summer monitoring, base case annual electric storage water heater energy use is determined to be 2,393 kWh for Site 1 and 3,923 kWh for Site 2. Although summer in-situ COPs were higher than the equipment nominal rated energy factor (EFs) since operating conditions were more favorable, an annual operating COP equal to the EF was used as a full-year estimate of annual HPWH performance. HPWH annual water heating savings relative to electric-resistance storage water heater are projected to range from 59–61%. Space-conditioning impacts

-

0.005

0.010

0.015

0.020

30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

Hum

idity

Rat

io (l

bs/lb

)

Dry Bulb Temperature (degrees F)

Relative Humidity (%)100 90 80 70 60 50 30

20

10

40

Twb = 61.0 F @ T = 80 F, 32.9% RH

Twb = 64.5 F @ T= 90 F, 24.0% RH

Page 36: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

28

ranged from an increase in energy usage at Site 1 (135 kWh cooling savings offset by added 260 kWh heating energy use) to a 121 kWh cooling energy savings at Site 2 (with the ducting kit installed). Applying the fixed Redding Electric utility rate of $0.1528 per kWh, the annual kWh cost savings are projected to range from $205 to $370. A $1,800 incremental cost for a HPWH installation over a standard electric water heater replacement was provided by Mike MacFarland of The Energy Docs. An additional $500 was assumed for installation of the ducting kit and associated duct work, grilles, and required detailing work at Site 2. The resulting preliminary simple paybacks for the two installations are in the 6.2–8.8 year range, before any potential incentives are applied18.

Table 7. Preliminary Annual Performance Projections

Parameter Site 1 Site 2

Monitored gallons/day 44.4 66.9

Estimated Base Electric Storage Water Heater Electrical Consumption, kWh/year 2,393 3,923

Estimated Annual HPWH Electrical Consumption, kWh/year 927 1,623

DHW Savings, kWh/year 1,466 2,300

Space Conditioning Savings (kWh/year) -125 121

Total Savings, kWh/year 1,341 2,421

Annual Savings, $/year $205 $370

Simple Payback, years 8.8 6.2

3.7 Initial Homeowner Reactions Informal communications with the homeowners at each site provided some feedback on performance and satisfaction issues related to the installation of the HPWHs.

Site 1:

On a 1-5 satisfaction level (5 being highest), the occupant gave the new unit a 3. They would have given it a 4, but the control problems (no hot water) when switching to electric-resistance-only mode was a major discomfort over a two-day period. In terms of what they like best, “…the look and the option of the cold air for cooling the space.” The unit “seems to be providing enough hot water” and “the noise levels have not been an issue”. The key benefit for the occupant is the cool air the unit provides and the feeling is that the ducting kit is not necessary for the homeowner’s application.

18 http://www.dsireusa.org/ provides information for the entire United States on available incentives and rebates.

Page 37: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

29

Site 2:

On the 1-5 satisfaction level, the occupant gave the new unit a 4. “The only reason it’s not a 5 is our electric bill has gone up significantly since we have had the HPWH”19. In terms of best aspects of the unit, they identified three: “more hot water…. Can take two showers at a time…. and, the cold air delivered to the kitchen.” What they didn’t like pertains to the perceived higher energy bills. The hot water delivery performance is “way better,” they have yet to run out of hot water with the new unit, and they have no concerns with noise with the laundry room location.

19 This comment was of particular interest as the monitoring data characterizing daily water heating electrical use before and after the HPWH retrofit clearly suggests the opposite effect. Higher 2014 utility bills may well be due to higher cooling energy consumption versus 2013. Homeowner perceptions, whether right or wrong, are important.

Page 38: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

30

4 Conclusions

This project was valuable in extending indoor HPWH field data monitoring and evaluation efforts into hot-dry climate regions, complementing research that has been completed or is underway in other parts of the United States and Canada. The hot-dry region, with its long and hot summers, offers an ideal opportunity for delivering enhanced energy savings and improved comfort to many U.S. households. Although Redding is a hot climate with many days exceeding 100ºF each year, other parts of the desert Southwest have longer and hotter summers where space-cooling benefits will be greater.

Monitored performance during the late-May to mid-September monitoring period suggested good HPWH performance with in-situ COPs ranging from 2.60 to 2.85. Other than a period of short experimentation with electric-resistance water heating at one site, monitored backup electric element operation contributed only 4–7% of the total monitored HPWH energy use. As the weather turns to fall and winter, and cold water inlet temperatures and HPWH entering air temperatures fall, the expectation is that backup electrical usage will increase.

The three primary research questions addressed include:

1. What level of cooling energy savings can be achieved by a ducted HPWH in a hot-dry climate with more than 1,900 cooling degree days?

2. What is the general level of homeowner satisfaction with the indoor HPWH in terms of perceived energy savings, hot water delivery characteristics, noise, and thermal comfort impacts?

3. Based on the field testing results, what recommendations can be made to improve the ducted HPWH installability, operation, and performance?

4.1 Level of Cooling Energy Savings that can be Achieved The expectation entering the project was that a consistently hot climate might provide a stable testing environment to facilitate statistically determining the benefit of HPWH space-cooling benefit relative to the whole-house cooling energy requirements. This was not proven out in this testing as the daily cooling energy usage was much more variable between comparable days than anticipated. In addition, the cooling loads at the two houses (Site 1 in particular) dwarfed any contribution from the HPWH. The monitoring approach for this study allowed for calculating the Btus of cooling energy the unit delivered to the indoor space. Extrapolating these data at each site over a full cooling period indicated projected space cooling reductions of 121–135 kwh/year. These results were generated in older homes with less efficient envelopes and dated HVAC systems. Whereas these results may be representative of a Redding retrofit application, impacts in a thermally improved new construction house in this climate will likely be lower due to a shorter cooling season.

4.2 General Level of Homeowner Satisfaction The two households were generally pleased with the installed HPWH. Key benefits identified were improved hot water delivery and system heating capacity, beneficial space cooling, and low noise. Site 2 with the six-person household noted immediate and significant improvement in the

Page 39: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

31

unit’s ability to provide hot water compared to their prior electric storage water heater. Ongoing monitoring through the winter will be valuable in terms of assessing winter impacts on energy savings, hot water delivery, and thermal comfort. Site 1 experienced some dissatisfaction when testing in electric-resistance mode as the unit stopped operating, leading to two days without hot water.

4.3 Recommendations to Improve the Ducted HPWH Installability, Operation, and Performance

The installer indicated no significant issues with installing the unit at either site. The 80-gallon unit may provide some challenges in some applications due to its larger size. Installation of the ducting is a site-dependent issue and there may be situations where the 25-foot length limit may make installations challenging.

With the exception of the control board problem at Site 1, the installed units operated reliably and efficiently. The appearance and control panel of the unit provide for a quality customer aesthetic. The control board issue at Site 1, as well as the associated delay in procuring a new board, were the only negative experiences encountered to date.

As with all HPWHs, the control sequence as it relates to resistance heat operation plays a significant role in determining system efficiency. During the summer months, resistance heating represented 4–7% of total unit consumption. Although relatively small, the impact will grow as the inlet water gets colder and hot water consumption increases in winter. Optimizing the control sequence for HPWHs represents an ongoing effort for the industry.

Page 40: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

32

References

Department of Energy. 2010. EnergyStar™ Water Heater Market Profile. Prepared for Oak Ridge National Laboratory under contract BOA#4200000327.

Fluid Market Strategies. 2013. NEEA Heat Pump Water Heater Field Study Report. NEEA Report #E13-266, Northwest Energy Efficiency Alliance, Portland, OR. Available at: http://neea.org/docs/default-source/reports/heat-pump-water-heater-field-study-report.pdf?sfvrsn=5

Hoeschele, M.; Weitzel, E. 2013. “Monitored Performance of Advanced Gas Water Heaters in California Homes”, ASHRAE Transactions, Vol. 119, Part 1, p 214-225.

Maguire, J.; Burch, J.; Merrigan, T.; Ong, S. 2013. Energy Savings and Breakeven Cost for Residential Heat Pump Water Heaters in the United States. NREL/TP-5500-58594, National Renewable Energy Laboratory, Golden, CO. Available at: http://techportal.eere.energy.gov/techpdfs/HPWH_mapping.pdf

Shapiro, C.; Puttagunta, S.; Owens, D. 2012. Measure Guideline: Heat Pump Water Heaters in New and Existing Homes. DOE/GO- 102012-3456. Available at: http://www.nrel.gov/docs/fy12osti/53184.pdf

Sparn, B.; Hudon, K.; Christensen, D. 2014. Laboratory Performance Evaluation of Residential Integrated Heat Pump Water Heaters. NREL/TP-5500-52635, National Renewable Energy Laboratory, Golden, CO. Available at: http://www.nrel.gov/docs/fy14osti/52635.pdf

Widder, S.; Peterson, J.; Parker, G.; Baechler, M. 2014. Impact of Ducting on Heat Pump Water Heater Space Conditioning Energy Use and Comfort. PNNL-23526. Pacific Northwest National Laboratory, Richland, WA. Available at: http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-23526.pdf

Williamson, J.; Puttagunta, S. 2013. “Systems Evaluation at the Cool Energy House.” Golden, CO: National Renewable Energy Laboratory. DOE/GO -102013-3942. Available at: http://apps1.eere.energy.gov/buildings/publications/pdfs/building_america/systems_eval_cool_energy_house.pdf.

Page 41: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

33

Appendix A: Determination of Preliminary Annual Performance Impacts

It was necessary to extrapolate from the available summer-only field data available to develop an initial performance projection for the installed HPWHs. The methodology used to arrive at an annual electric and cost savings is documented here and will be refined when full-season field performance is available. The applied method is simplified, but provides for a first-cut performance estimation.

Step 1: Develop annual hot water load estimate Based on field monitoring data, hot water loads for Site 1 equaled 44.4 gpd and 66.9 gpd for Site 2. This was used to represent annual hot water usage, although one would expect usage to increase during the winter months.

Step 2: Estimate base case electric storage water heater energy use Figure 17 provides linear curve fits for electric storage water heater daily energy use as a function of load. Three seasons were identified to reflect varying hot water usage to inlet water temperature effects, and to lesser extent changing storage losses. Winter was expected to encompass four months (December – March), spring/fall two months (April, November), and summer the remaining six months. Daily energy use for the loads identified in Step 1 was calculated according to the following equation:

Daily electric storage kWh = 0.75 + gpd x A

(where A= .117 for summer, .137 for spring/fall, and .157 for winter)

Determine seasonal energy use by summing number of days in each season; sum for annual

Step 3: Estimate HPWH energy use HPWH annual energy use = electric storage annual kWh * 0.91 / HPWH EF

0.91 is applied as a representative electric water heater annual performance value

Step 4: Determine space-cooling benefits Annual space cooling impacts were estimated based on the 1.0- and 1.4-ton-hour/day benefits monitored for Sites 1 and 2, respectively. To translate this to annual impacts, one needs to a reasonable cooling system efficiency, as well as an estimate of the number of days that the space-cooling benefit is directly contributing to a reduction in cooling energy. To get a conservative estimate of energy savings, the applied efficiency (i.e., full-season energy efficiency rating) of 12.0 was assumed, resulting in 1 kWh/ton-hour delivered. This results in daily savings of 1.0 and 1.4 kWh/day (Sites 1 and 2, respectively). Based on the space cooling day as a function of outdoor maximum temperature (Figure 20) and the 2014 Redding summer weather, a total of 135 days of cooling reduction benefit was estimated for Site 1 and 86 days for Site 2. Multiplying the daily benefit by the number of days generates the 121 to 135 kWh annual space-cooling benefit, equal to 2–5% of the monitored space cooling usage.

Page 42: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

34

Step 5: Estimate space-heating impacts Site 1 has an indoor HPWH without ducting kit, while Site 2 has a ducting kit and is therefore presumed to be operated with the manual dampers positioned to obtain the full summer benefit and avoid any heating season penalty. Without any monitored based for heating season impacts for Site 1, projections were used from an NREL modeling study entitled “Energy Savings and Breakeven Cost for Residential Heat Pump Water Heaters in the United States” (Maguire et al, 2013). In Table 2 of Appendix C from that study, the source energy impact of an indoor HPWH operating in a hot-dry climate with an air source heat pump was projected to be an increase in heating energy use of 2.79 MMBtu/year. Converting source energy to kWh using the NREL source energy multiplier of 3.15 results in an added 260 kWh of space heating usage.

Step 6: Calculate total energy savings HPWH water heating and space heating and cooling impacts are summed.

Step 7: Calculate total operating cost savings Electrical savings are converted to dollars at the fixed electric rate of $.1528/kWh.

Step 8: Calculate simple payback Mike MacFarland of The Energy Docs estimated a typical HPWH replacement of an existing electric storage water heater costs ~$3,000 vs. $1,200 for a direct electric storage replacement. The $1,800 incremental cost for the HPWH installation increases to approximately $2,300 at Site 2 for adding the ducting kit, added duct work, and other installation detailing. Resulting simple paybacks for the two installations are in the 6.2- to 8.8-year range, before any potential incentives are applied.

Preliminary economic evaluation of the ducting kit suggests an annual energy savings of 381 kWh (260 kWh heating plus 121 kWh cooling). Under the Redding Electric utility rates and a cost of $500, the simple payback is a projected at 8.6 years.

Page 43: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

35

Table A1. Performance Projections for Installed HPWHs

Parameter Site 1 Site 2

Monitored gallons/day 44.4 66.9

Estimated Base Electric Storage WH kWh/year 2,393 3,923

Assumed Annual COP 2.35 2.20

Estimated Annual HPWH kWh/year 927 1,623

DHW Savings, kWh/year 1,466 2,300

Cooling Savings, kWh/year 135 121

Cooling Savings as a % of Annual Space Cooling kWh 2% 5%

Heating Savings, kWh/year -260 0 Total Savings, kWh/year 1,341 2,421

Installed Incremental Cost $1,800 $2,300

Annual Savings, $/year $205 $370

Simple Payback, years 8.8 6.2

Page 44: Summer Indoor Heat Pump Water Heater Evaluation in a Hot ... · 1 Background and Motivation Quantifying the water heating performance and space conditioning impacts of heat pump water

DOE/GO-102017-4648 May 2017

For more information, visit buildingamerica.gov