summary eq engg
DESCRIPTION
SummaryTRANSCRIPT
![Page 1: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/1.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 133
Seismic design principlesBasic principles of conceptual design ndash
1 Structural simplicity Principle Clear and direct load paths so that seismicforces can be transferred from top to bottom Direct load paths from top tobottom can only be assured by regularly arranged structural elements
2
Uniformity symmetry and redundancy Principle The greater the departure from regularity or symmetry the greater theperil to suffer serious damage
During the design process care should be taken with respect to the following rarrsymmetrical arrangement of mass and stiffness in ground plan and elevation rarr
irregularities in the buildings layout will result in eccentricities of mass andstiffness center which will lead to unfavorable torsional effects that are coupledwith large displacements rarr interruptions of lateral stiffness over the buildingsheight will cause weak locations in the structural system
Redundancy means that the building should have more than one single loadpath in order to transfer the forces from top to bottom In case that one load pathis affected by the shaking another load path is taking over Redundant systemsare generally less simple
REGULARITY OF STRUCTURECriteria for structural regularity
A Regularity in plan
Figure 22 opposes the most common regular with irregular plan shapesHowever a regular plan shape cannot always be realized Consequently
measures have to be taken in order to provide that an irregular plan shapelsquobehavesrsquo like a regular one This can be either done by - subdividing the building into separate independent units using seismic joints
(Figure 23)- strengthening those parts of the building that experience largest
displacementsforces (Figure 23)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 333
Plan regularity-symmetrical arrangement of lateral stiffness and mass distributions
- two orthogonal axes ie rectangular buildings with two principal buildingaxes that are orthogonally arranged to each other
- plan configuration is compact able to be delimited by a polygonal convex line(compare withFigure 215)
- if set-backs exist plan can be estimated as compact if the differential area isless than 5 of thetotal floor area (compare with Figure 216 ie A 1 lt 005 A tot and A 2lt 005
A tot )
- slenderness ie ratio between length L max and width L minof the building
shall be smaller than 402
(Figure 217)
B Regularity in elevation
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 533
Figure 26 compares favorable with unfavorable building solutions withrespect to elevation shape
In general the following principles shall be considered -avoid sensitive zones where concentrations of stress or large ductility
demands increase damage susceptibility
- provide either constant or continuously decreasing stiffness with height- avoid buildings with too slender (chimney-style) or inverted pendulumshape (heavy mass on top)-arrange continuous bracings over total building height- arrange seismic (movement) joints of sufficient thickness1 in order todecouple separate building segments from each other
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 2: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/2.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 333
Plan regularity-symmetrical arrangement of lateral stiffness and mass distributions
- two orthogonal axes ie rectangular buildings with two principal buildingaxes that are orthogonally arranged to each other
- plan configuration is compact able to be delimited by a polygonal convex line(compare withFigure 215)
- if set-backs exist plan can be estimated as compact if the differential area isless than 5 of thetotal floor area (compare with Figure 216 ie A 1 lt 005 A tot and A 2lt 005
A tot )
- slenderness ie ratio between length L max and width L minof the building
shall be smaller than 402
(Figure 217)
B Regularity in elevation
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 533
Figure 26 compares favorable with unfavorable building solutions withrespect to elevation shape
In general the following principles shall be considered -avoid sensitive zones where concentrations of stress or large ductility
demands increase damage susceptibility
- provide either constant or continuously decreasing stiffness with height- avoid buildings with too slender (chimney-style) or inverted pendulumshape (heavy mass on top)-arrange continuous bracings over total building height- arrange seismic (movement) joints of sufficient thickness1 in order todecouple separate building segments from each other
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 3: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/3.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 333
Plan regularity-symmetrical arrangement of lateral stiffness and mass distributions
- two orthogonal axes ie rectangular buildings with two principal buildingaxes that are orthogonally arranged to each other
- plan configuration is compact able to be delimited by a polygonal convex line(compare withFigure 215)
- if set-backs exist plan can be estimated as compact if the differential area isless than 5 of thetotal floor area (compare with Figure 216 ie A 1 lt 005 A tot and A 2lt 005
A tot )
- slenderness ie ratio between length L max and width L minof the building
shall be smaller than 402
(Figure 217)
B Regularity in elevation
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 533
Figure 26 compares favorable with unfavorable building solutions withrespect to elevation shape
In general the following principles shall be considered -avoid sensitive zones where concentrations of stress or large ductility
demands increase damage susceptibility
- provide either constant or continuously decreasing stiffness with height- avoid buildings with too slender (chimney-style) or inverted pendulumshape (heavy mass on top)-arrange continuous bracings over total building height- arrange seismic (movement) joints of sufficient thickness1 in order todecouple separate building segments from each other
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 4: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/4.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 533
Figure 26 compares favorable with unfavorable building solutions withrespect to elevation shape
In general the following principles shall be considered -avoid sensitive zones where concentrations of stress or large ductility
demands increase damage susceptibility
- provide either constant or continuously decreasing stiffness with height- avoid buildings with too slender (chimney-style) or inverted pendulumshape (heavy mass on top)-arrange continuous bracings over total building height- arrange seismic (movement) joints of sufficient thickness1 in order todecouple separate building segments from each other
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 5: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/5.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 533
Figure 26 compares favorable with unfavorable building solutions withrespect to elevation shape
In general the following principles shall be considered -avoid sensitive zones where concentrations of stress or large ductility
demands increase damage susceptibility
- provide either constant or continuously decreasing stiffness with height- avoid buildings with too slender (chimney-style) or inverted pendulumshape (heavy mass on top)-arrange continuous bracings over total building height- arrange seismic (movement) joints of sufficient thickness1 in order todecouple separate building segments from each other
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 6: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/6.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 633
Bi-directional resistance and stiffnessBuildings which are designed to withstand these loads shall possess bi-directional resistance and stiffnessA special case consists in slender plan shapes Please consider that both generalbuilding axes usually possess equal resistance A lsquoweakrsquo axis (as sometimes
reported) does not exist (compare with Figure 29)
Torsional resistance and stiffness Torsional effects generally occur if the center of mass and the center of stiffnessare located in a certain distance (ie eccentricity e) to each other This is caused by symmetricalregular plan shapes where the structuralelements are irregularly distributed (Figure 210)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 7: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/7.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 733
- Unsymmetricalirregular plan shapes where masses and stiffnesses aredisorderly arranged
It should be also considered that slender plan shapes tend more easily totorsional effects (Figure 211) It is therefore advisable to limit the length-to-width
ratio (slenderness) of the plan
Diaphragmatic behavior at storey level
The main role of floor diaphragms is to collect and transmit the inertia forces They further have to ensure that all vertical elements act together (aresynchronous) in resisting the seismic forces and should thus have sufficient in-plane stiffness In order to ensure this large openings or interruptions should
be avoided (Figure 212) Floor diaphragms act as horizontal ties which preventexcessive relative deformations between the vertical elements
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 8: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/8.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 833
Adequate foundation The foundation shall ensure that the whole building is subjected to a uniform
seismic excitation If the superstructure is likely to differ in width and stiffnessa rigid box-type or cellular foundation should be chosen (Figure 213)
Primary and secondary seismic membersWhile primary elements contribute to the seismic resistance secondary elementsresist gravity loads only and have no contribution to the structurersquos seismicresistance (Figure 214) According to EC8 the contribution of all secondaryseismic members should not exceed 15 of that of all primary seismic membersin order to avoid unintentional stiffening by secondary elements (higherfrequencies and inertial loads) as well as to provide flexible joints
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 9: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/9.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 933
EARTHQUAKE-RESISTANT DESIGN CONCEPTS
1 Seismic Design Categories
Factors that affect a structurersquos seismic risk include
bull The intensity of ground shaking and other earthquake effects the structureis likely to experience and
bull The structurersquos use including consideration of the number of people who wouldbe affected by the structurersquos failure and the need to use the struc ture for its
intended purpose after an earthquake
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 10: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/10.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 11: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/11.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1133
The intensity of earthquake shaking and other effects used to assign structures
to a Seismic Design Category is determined using the national seismic maps
In general sites that have deep deposits of soft soils will have larger values of
the design acceleration parameters than sites with shallow deposits of firm soils
or near-surface rock
2 Site Class
Site soil conditions are important in determining Seismic Design Category Hard
competent rock materials efficiently transmit shaking with high-frequency
(short-period) energy content but tend to attenuate (filter out) shaking with low-
frequency (long-period) energy content Deep deposits of soft soil transmit high-
frequency motion less efficiently but tend to amplify the low-frequency energy
content
3 Design Ground Motion
In order to determine the Seismic Design Category for a structure it is first
necessary to determine the design ground motion which is one of the primary
factors used to determine the required seismic resistance (strength) of structures
and supported nonstructural components
4 Structural System Selection
selecting an appropriate seismic-force-resisting system (SFRS) the seismic-
force-resisting systems for building structures and nonbuilding structures with
structural systems like buildings are categorized by construction material (eg
concrete masonry steel or wood) type of system (bearing wall braced frame
moment frame dual or cantilever column) and level of seismic detailing (special
intermediate ordinary or not detailed for seismic resistance)
three design coefficients used to determine the required strength and
stiffness of a structurersquos seismic-force-resisting system
a R is a response modification factor that accounts for the ability of some
seismic-force-resisting systems to respond to earthquake shaking in aductile manner without loss of load-carrying capacity R values generally
range from 1 for systems that have no ability to provide ductile response
to 8 for systems that are capable of highly ductile response The R factor
is used to reduce the required design strength for a structure
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 12: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/12.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1233
5 Configuration and Regularity
structures have nonuniform distribution of strength or stiffness and discontinu-
ous structural systems are termed ldquoirregular structures
two basic categories of irregularity horizontal or plan irregularity and vertical
irregularity
a Horizontal irregularities include
Torsional irregularity- when the distribution of vertical elements of
the seismic-force-resisting system within a story including braced
frames moment frames and walls such that when the building is
pushed to the side by earthquake forces it will tend to twist as well
as deflect horizontally
Extreme torsional irregularity-twisting that occurs as the structure
is displaced laterally becomes very large
Re-entrant corner irregularity
Diaphragm discontinuity irregularity ndash This occurs when a
structurersquos floor or roof has a large open area
Out-of-plane offset irregularity-when braced frames or shear walls
are not aligned vertically from story to story
Nonparallel systems irregularity
Vertical irregularities include the following
Stiffness soft-story irregularity ndash This occurs when the stiffness of
one story is substantially less than that of the stories above
Extreme stiffness soft-story irregularity
Weightmass irregularity ndash This exists when the weight of the
structure at one level is substantially in excess of that at the levels
immediately above or below it
In-plane discontinuity irregularity-when walls or braced frames do
not align vertically within a given line of framing
Weak-story irregularity ndash This occurs when the strength of the
walls or frames that provide lateral resistance in one story is
substantially less than that of the walls or frames in the adjacent
stories
Extreme weak-story irregularity
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 13: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/13.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1333
Seismic action and performance requirements
EC8 provides for a two-level seismic design
Protection of life under a rare seismic action by prevention of collapse of the
structure
Reduction of property loss due to a frequent even
For structures of ordinary importance the recommendation of EC8 is for bull A 10
exceedance probability in 50 years (ldquodesignrdquo) seismic action for collapse
prevention (mean return period 475 years) The ldquodesignrdquo seismic action for
structures of ordinary importance over rock is termed ldquoreferencerdquo seismic action
bull A 10 in 10 years ldquoserviceabilityrdquo action for damage limitation (mean return
period 95 years)
Enhanced performance of essential or large occupancy facilities is achieved not
by upgrading the performance level for given earthquake level as US codes do
but by modifying the hazard level (the mean return period) for which collapseprevention or damage limitation is pursued
Behaviour factor
The majority of structures designed with EC8 are expected to be designed for
ldquoenergy dissipationrdquo Medium (M) and High (H) ductility DC M and H buildings
are entitled to values of the force reduction or behaviour factor q well above the
minimum value of q=15 attributed to overstrength
Availability of the global energy dissipation and ductility capacity needed for
values of q (much) higher than 15 is ensured throughbull Measures to control the inelastic response mechanism so that concentration
of inelastic deformations in a part of the structure (mainly a soft storey
mechanism) and brittle failure modes are avoided
bull Detailing of the plastic hinge regions for inelastic deformations expected to
develop there under the design seismic action
Concentration of inelastic deformations and soft storey mechanisms are avoided
by configuring and dimensioning the lateral-force resisting system so that vertical
members( column walls) remain practically straight ndash ie elastic ndash above their
base and designed to be stronger than the beams
Analysis procedures and modelsEC8 provides the following analysis options for design and for evaluation of the
performance of buildings
bull Linear static (termed ldquolateral forcerdquo method)
bull Linear modal response spectrum analysis
bull Nonlinear static analysis (ldquopushoverrdquo)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 14: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/14.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1433
bull Nonlinear dynamic (response time-history) Linear time-history analysis is not
explicitly mentioned In US codes linear static analysis is the reference in EC8 the linear
modal response spectrum method is the standard procedure applicable
to all types of buildings
The lateral force procedure(US code) may be applied if the effects of
higher modes are not significant ie only when
bull In both horizontal directions the fundamental period is less than 2sec
and 4 times the transition period Tc between the constant-acceleration
and the constant-velocity regions of the spectrum
bull There are no significant irregularities in elevation
In the response spectrum analysis(EC8 code) modal contributions are
combined by rigorous application of the SRSS or CQC rules ie at the
level of the final seismic action effects of interest (internal forces
displacements etc)
Behaviour factor q for reduction of elastic
forces
For structures designed for energy dissipation the behaviour factor q
by which the elastic spectrum for use in linear analysis is reduced is
linked directly or indirectly to the ductility and deformation demands
the type of lateral-force-resisting-system and on the ductility classselected for the design System overstrength is explicitly included in the value of the q-factor
through the ratio αuα1 (denoted here for convenience αR) of the seismic
action that causes development of a full plastic mechanism (ie for fully
yielded structure) q=3αR for DC M and 45αR for DC H
Soil-structure interaction
Two types of SSI are commonly referred to in the literature
1
ldquoKinematicrdquo interaction is caused by inability of a foundation to follow
ground motion due to greater foundation stiffness in comparison with
ground stiffness
2 ldquoInertialrdquo interaction is caused by the existence of structural and
foundation masses Seismic energy transferred into a structure is
dissipated by material damping and radiation back into ground
causing superposition of incoming and outgoing ground waves As a
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 15: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/15.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1533
result the ground motion around a foundation can be attenuated or
amplified depending on a variety of factors
The most important factor in determining the response is the ratio between the
fundamental period of a foundation and the fundamental period of the adjacent ground
in the free-field The ratio of unity indicates resonance condition between foundation
and its adjacent ground which is to be avoided
Section 6 of EN1998-12004 states that the effects of dynamic soil-structure interaction
shall be taken into account in the case of
bull structures where Pndash effects play a significant role
structures with massive or deep seated foundations
bull slender tall structures
bull structures supported on very soft soils with average shear wave velocity less than 100
ms
bull The effects of soil-structure interaction on piles shall be assessed
EN1998-12004 is the only code which recognizes the importance of kinematic
interaction for piled foundations as it is stated in clause 542(6) of EN1998-52004
Bending moments developing due to kinematic interaction shall be computed only
when two or more of the following conditions occur simultaneously
bull the subsoil profile is of class C (soft soil) or worse and contains consecutive layers
with sharply differing stiffness
bull the zone is of moderate or high seismicity S ag gt 01 g
bull the supported structure is of importance category III or IV
SSI is motivated not only by the need to satisfy geotechnical requirement related to
foundation response to earthquake loading (eg bearing capacity assessment
settlement calculation) but also by the necessity of computing the ldquoeffectiverdquo earthquake
excitation to a structure with respect to the free-field ground motion (which is also called
Foundation Input Motion or FIM)
There are three primary categories of soil-structure interaction (SSI) effects These
include bull filtering of the ground motions transmitted to the structure (kinematic effects)bull introduction of flexibility to the soil-foundation system (flexible foundation effects) bull
dissipation of energy from the soil-structure system through radiation and hysteretic
soil damping (foundation damping effects)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 16: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/16.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1633
Behavior factor Vs Design Spectrum relationship
The Behavior factor is a reduction factor of the design response spectrum in
relation to the elastic response spectrum You can edit its value after selecting
the Design spectrum option Note The behavior factor q reduces
the design spectrum this way it also decreasesseismic loads and the resulting
internal forces
The starting point is an elastic response spectrum which is reduced with factors
that take into consideration the ability of the structure to absorb seismic energy
through rigid deformations The design acceleration spectrum comes from the
elasticity spectrum with a depreciation of 5 by dividing the spectral
accelerations by the behavior factor q
The elastic acceleration spectrum with a damping of 5 of Eurocode 8is given
graphically below It contains an area of fixed spectral acceleration between the
periods Τ Β and Τ C with a value 25 times the maximum soil acceleration agS that
is followed from an area of fixed spectral velocity between the periods Τ C and Τ D
where the spectral acceleration is proportional to 1Τ and an area of fixed
spectral displacement where the spectral acceleration is proportional to 1Τ 2
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 17: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/17.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1733
Figure 2 Elastic spectrum EC in the horizontal direction for a damping of 5
(Fardis 2009a)
In the areas of fixed spectral acceleration velocity and displacement the design
spectrum originates from an elastic response with a 5 damping divided by q
Exceptionally the increasing part for a vibration period from Τ up to ΤleΤ Β comes
from the linear interpolation between (α) the maximum ground acceleration Sag
divided by 15 that expresses overstrength compared with the design capacity
and the fixed design acceleration for Τ=0 and (β) 25 agq for Τ=Τ Β Moreover
there is a lower limit in the design spectral acceleration equal to the 20 of the
maximum acceleration on the rock ag (Fardis 2009a)
dependence of the importance factor on the mean return period chosen fordesign
Buildings in EN 1998-1 are classified in 4 importance classes depending ono the consequences of collapse for human lifeo their importance for public safety and civil protection in the immediate post-earthquake period ando the social and economic consequences of collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 18: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/18.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 19: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/19.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 1933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 20: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/20.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2033
INSTRUMENTED BUILDING USING RECORDED
RESPONSE MOTION
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 21: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/21.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2133
Conclusion
Drift is defined as the lateral displacement Storey drift is the drift of one level of
a multistorey building relative to the level below Interstory drift is the difference
between the roof and floor displacements of any given story as the building sways
during the earthquake normalized by the story height For example for a 10-foot high story an interstory drift of 010 indicates that the roof is displaced one
foot in relation to the floor below
The greater the drift the greater the likelihood of damage Peak interstory drift
values larger than 006 indicate severe damage while values larger than 0025
indicate that the damage could be serious enough to pose a serious threat to
human safety Values in excess of 010 indicate probable building collapse
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 22: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/22.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 23: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/23.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2333
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 24: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/24.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2433
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 25: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/25.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2533
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 26: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/26.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2633
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 27: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/27.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2733
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 28: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/28.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2833
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 29: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/29.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 2933
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 30: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/30.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3033
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 31: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/31.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3133
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 32: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/32.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3233
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333
![Page 33: Summary Eq Engg](https://reader033.vdocuments.mx/reader033/viewer/2022051214/563dba30550346aa9aa37156/html5/thumbnails/33.jpg)
7182019 Summary Eq Engg
httpslidepdfcomreaderfullsummary-eq-engg 3333