substation

33
Substation switchgears Instructor Engr. Muhammad Yaseen

Upload: muhammad-mohsin-raza

Post on 12-Jan-2017

90 views

Category:

Engineering


0 download

TRANSCRIPT

High Voltage Engineering

Substation switchgearsInstructorEngr. Muhammad Yaseen

Differentiate between substation and grid stationSubstation:An electrical power substation is a conversion point between transmission level voltages (such as 132 KV) and distribution level voltages (such as 11 KV).A substation has one or more step-down transformers and serves a regional area such as part of a city or neighborhood.Substations are connected to each other by the transmission ring circuit.

Differentiate between substation and grid stationGrid Station:An electrical grid station is an interconnection point between two transmission ring circuits, often between two geographic regions.They might have a transformer, depending on the possibly different voltages, so that the voltage levels can be adjusted as needed.The interconnected network of grid stations is called the grid, and may ultimately represent an entire multi-state region.In this configuration, loss of a small section, such as loss of a power station, does not impact the grid as a whole, nor does it impact the more localized neighborhoods, as the grid simply shifts its power flow to compensate, giving the power station operator the opportunity to effect repairs without having a blackout.

Distribution sub-stationIntroduction:It is link between sub-transmission and distribution system. The main function of sub-station is to transform higher voltage (132 kV) to distribution voltage level (11 kV).Power is delivered to high voltage bus through circuit breaker and isolators.High voltage bus bars are then connected to the distribution transformers which further step down the voltage up to the level of 11 kV.The power is transformed to low voltage bus bar which is made of large cross-sectional area.From low voltage bus bars energy is fed to the feeders through circuit breakers.The three phase primary feeders distributes energy from low voltages bus of sub-station to its load centers.Normally 100-500 kVA transformer are connected to each primary feeder or sub-feeders.

Classification of SubstationThere are several ways of classifying substations. However the two most important ways of classifying them are according to (1) Service requirement and (2) constructional features.According to service requirement A substation may be called upon to change voltage level or improve power factor or convert a.c. power in to d.c. power etc. According to the service requirement, substation may be classified into:(a) Transformer Sub-stations.Those substations which change the voltage level of electric supply are called transformer substations.These substations receive power at some voltage and deliver it at some other voltage.Obviously, transformer will be the main component in such substations. Most of the substations in the power system are of this type.

Classification of Substation(b) Switching sub-stations.These substation do not change the voltage level i.e. incoming and outgoing lines have the same voltage. However, they simply perform the switching operations of the power lines.(c) Power factor correction sub-stations.Those substations which improve the power factor of the system are called power factor correction sub-stations.Such sub-stations are generally located at the receiving end of the transmission lines.These sub-stations generally use synchronous condensers at the power factor improvement equipment.(d) Frequency changer sub-stations.Those sub-stations which change the supply frequency are known as frequency changer sub-stations.Such a frequency change may be required for industrial utilization.

Classification of Substation(e) Converting sub-stations.Those sub-stations which change a.c. power in to d.c. power are called converting sub-stations.These sub-stations receive a.c. power and convert it in to d.c. power with suitable apparatus (e.g. ignitron) to supply for such purposes as traction, electroplating, electric welding etc.(f) Industrial sub-stations.Those sub-stations which supply power to individual industrial concerns are known as industrial sub-stations.(2) According to constructional featuresA substation has many components (e.g. circuit breakers, switches, fuses, instruments etc.) which must be cover properly to ensure continuously and reliable service. According to constructional features, the substations are classified as:

Classification of Substation(a) Indoor substations.For voltages up to 11 kV, the equipment of the substation is installed indoor because of economic consideration.However, when the atmosphere is polluted with impurities, these sub-stations can be erected (setup) for voltages up to 66 kV. (b) Outdoor substations.For voltages beyond 66 kV, equipment is invariably (constant) installed outdoor. It is because of such voltages, the clearances between conductors and the space required for switches, circuit breakers and other equipment becomes so great that it is not economical to install the equipment indoor. (c) Underground substations.In thickly populated areas, the space available for equipment and building is limited and the cost of land is high.Under such situations, the sub-station is created underground.

Classification of Substation(d) Pole-mounted substations.This is an outdoor sub-station with equipment installed over-head on H-pole or 4-pole structure.It is the cheapest form of the sub-station for voltages not exceeding 11 kV.Electric power is almost distributed in localities through such sub-stations.For more discussion on pole mounted sub-station please refer the principle of power system by v.k. Mehta.

Substation equipments and its functions(1) Lightening Arrester.Lightening arrestors are the instrument that are used in the incoming lines so that to prevent the high voltage entering the main station. This high voltage is very dangerous to the instruments used in the substation. Even the instruments are very costly, so to prevent any damage lightening arrestors are used. The lightening arrestors do not let the lightening to fall on the station. If some lightening occurs the arrestors pull the lightening and ground it to the earth.In any substation the main important is of protection which is firstly done by these lightening arrestors. The lightening arrestors are grounded to the earth so that it can pull the lightening to the ground.The lightening arrestor works with an angle of 30 to 45 making a cone.

Substation equipments and its functions(2) Capacitor Voltage Transformer (CVT):A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra high voltage signals and provide low voltage signals either for measurement or to operate a protective relay. In its most basic form the device consists of three parts: two capacitors across which the voltage signal is split, an inductive element used to tune the device to the supply frequency and a transformer used to isolate and further step-down the voltage for the instrumentation or protective relay.The device has at least four terminals, a high-voltage terminal for connection to the high voltage signal, a ground terminal and at least one set of secondary terminals for connection to the instrumentation or protective relay.CVTs are typically single-phase devices used for measuring voltages in excess of one hundred kilovolts where the use of voltage transformers would be uneconomical.

Substation equipments and its functions

220 kV Capacitor Voltage Transformer

Wave Trap

Substation equipments and its functions(3) Wave trap:Wave trapsare used at sub-stations using PowerlineCarrier Communication (PLCC). PLCC is used to transmit communication and control information at a high frequency over the power lines. This reduces need for a separate infra for communication between sub-stations.(4) Instrument Transformers:The line in sub-stations operate at high voltages and carry current of thousand amperes.The measuring instruments and protective devices are designed for low voltages (generally 110 V) and current (about 5 A). Therefore they will not work satisfactorily if mounted directly on the power lines.This difficulty is overcome by installing instrument transformer on the power lines.The function of these instrument transformer is to transfer voltages or currents in the power lines to values which are convenient for the operation of measuring instruments and relays.

Substation equipments and its functionsTheses are two types of instrument transformer(i) Current Transformer (CT)(ii) Potential Transformer (PT)Current Transformer (CT):A current transformer is essentially a step-up transformer which step down the current to a known ratio.The primary of this transformer consists of one or more turns of thick wire connected in series with power line.The secondary consists of large number of turns of fine wire and provides for measuring instruments and relays a current which is a constant fraction of the current in the line.Suppose a current transformer rated at 100/5 A is connected in the line to measure the current .If the current in the line is 100 A . Then current in the secondary will be 5 A .Similarly, if current in the line is 50 A, then secondary of CT will have current of 2.5 A.Thus the CT under consideration will step-down the line current by a factor 20.

Substation equipments and its functions(ii) Potential Transformer (PT)It is essentially a step-down transformer and step down the voltage to a known ratio.The primary of this transformer consists of large number of turns of fine wire connected across the line.The secondary winding consists of a few turns and provides for measuring instruments and relays a voltage which is known fraction of the line voltage.Suppose a potential transformer rated at 66 kV/110 V is connected to power line. If line voltage is 66 kV, then voltage across secondary will be 110 V.(5) Bus-Bars:The bus is a line in which the incoming line come into and get into the instruments for further step up or step down. The first bus is used for putting the incoming line in a single line. There may be double line in the bus so that if any fault occurs in the one the other can still have the current and the supply will not stop.

Substation equipments and its functionsA bus barin electrical power distribution refers to thick strips of copper or aluminum that conduct electricity within a switchboard, distribution board, substation, or other electrical apparatus. The size of the bus bar is important in determining the maximum amount of current that can be safely carried. Bus bars are typically either flat strips or hollow tubes as these shapes allow heat to dissipate more efficiently due to their high surface area to cross sectional area ratio.(6) Circuit Breaker:The circuit breakers are used to break the circuit if any fault occurs in any of the instrument. These circuit breaker breaks for a fault which can damage other instrument in the station. For any unwanted fault over the station we need to break the line current. This is only done automatically by the circuit breaker. There are different types of circuit breakers used for any substations. They area. SF6 circuit breakersb. Oil circuit breakerc. Spring circuit breakers.d. Vacuum circuit breaker

Substation equipments and its functions(7) Power Transformer:A power transformer is used in a sub-station to step-up or step-down the voltage.The modern practice is to use 3-phase transformers in sub-stations; although 3 single phase bank of transformers can also be used.In case of a 220KV or more KV line station auto transformers are used. While in case of lower KV line such as less than 132KV line double winding transformers are used.(8) Isolator:The use of this isolator is to protect the transformer and the other instrument in the line. The isolator isolates the extra voltage to the ground and thus any extra voltage cannot enter the line. Thus an isolator is used after the bus also for protection.Isolator is installed before and after the circuit breaker

Substation equipments and its functions(9) Protective Relaying:Protective relays are used to detect defective lines or apparatus and to initiate the operation of circuit interrupting devices to isolate the defective equipment. Relays are also used to detect abnormal or undesirable operating conditions other than those caused by defective equipment and either operate an alarm or initiate operation of circuit interrupting devices.There are different types of relays.i. Over current relayii. Distance relayiii. Differential relayiv. Directional over current relay

Substation equipments and its functions(10) D.C. Power Supply (D.C. Battery and Charger):All but the smallest substations include auxiliary power supplies. AC power is required for substation building small power, lighting, heating and ventilation, some communications equipment, switchgear operating mechanisms, anti-condensation heaters and motors. DC power is used to feed essential services such as circuit breaker trip coils and associated relays, supervisory control and data acquisition (SCADA) and communications equipment.

Substation equipments and its functions

Potential Transformer (PT)Current Transformer (CT)

Substation equipments and its functions

Oil Circuit Breaker

Substation equipments and its functions

SF6 Circuit BreakerIsolator

Substation Bus SchemesThe selection of bus schemes is based upon safety, reliability, economy, simplicity and other considerations.The most commonly sub-station schemes used at are given as under 5 schemesSingle Bus Single Breaker SchemeDouble Bus Double Breaker SchemeMain Transfer Bus SchemeRing Main Arrangement SchemeOne and Half Breaker Scheme

Substation Bus SchemesSingle Bus Single Breaker Scheme

Substation Bus SchemesAdvantagesDisadvantagesLowest costFailure of bus or any C.B results shutdown (power outage) in entire sub-station.Difficult to do maintenance.Bus can not be extended without its de-energising.This can be used where loads have other supply arrangements if bus looses supply.

Substation Bus SchemesDouble Bus Double Breaker Scheme

Substation Bus SchemesAdvantagesDisadvantagesEach circuit has two breakers.It allows feeder circuits to be connected to be either bus.Any breaker can be taken out from service for maintenance.High reliability.Most costly or expensive.Would loose half of the circuit for breaker failure. If circuits are not connected to both buses.

Substation Bus SchemesMain and Transfer Bus Scheme

Substation Bus SchemesAdvantagesDisadvantagesLow initial cost.Any breaker can be taken out from service for maintenance.Potential device may be used on the main bus for relaying.It requires one extra breaker for bus tie.Switching is complicated when breaker maintenance.Failure of bus or any of the breaker results in shutdown of entire sub-station.

Substation Bus SchemesRing Main Arrangement Scheme

Substation Bus SchemesAdvantagesDisadvantagesSeparation of ring if fault occurs.It requires potential devices on all circuits.Automatic reclosing.

Low initial cost.Flexible operation.Any of the breaker can be taken out of service.It requires one C.B per circuit.Does not use main bus.Each circuit is fed from two circuit breakers.

Substation Bus SchemesOne and half breaker Scheme

Substation Bus SchemesAdvantagesDisadvantages1 and breaker per circuit.Relaying and automatic reclosing are somewhat involved since the middle breaker must be responsive to either of its associated circuits.High flexibility operation.High reliability.Very simple in operation.Breaker failure of bus side breaker removes only one circuit from serviceAll switching is done by breakers.Bus failure does not remove any feeder circuits from service.

Line (OH/UG)

Bus

Isolator

C.B

C.B

C.B

C.B

C.B

Isolator

Isolator

Isolator

Isolator

Bus 1

Isolator

C.B

C.B

C.B

C.B

Isolator

Isolator

C.B

C.B

C.B

C.B

Isolator

Bus 2

Common point

Line

Line

Line

Line

Isolator

Main Bus

Incoming line 1

Incoming line 2

C.B

Here, OR logic is used

Transfer Bus

Isolator

Bus Coupler

Out going 11 kV feeder

Incoming line

C.B

C.B

Isolator

Out going

Incoming line

Incoming line

Out going

Out going

Isolator

Isolator

C.B

C.B

C.B

C.B

C.B

C.B

C.B

C.B

C.B

C.B

Incoming line 2

Ckt 1

Ckt 2

C.B

Main Bus

Isolator

C.B

Transfer Bus

Isolator

Isolator

Out going

Incoming line 1

Out going

Isolator

C.B