submittal guide io series life safety systems

36
Notification Appliances Hazardous Location Devices Door Holders & Relays Initiating Devices iO Series Intelligent Control Submittal Guide iO Series Life Safety Systems Intelligent fire alarm solutions for small buildings iO Series E S T B R A N D L I F E S A F E T Y & C O M M U N I C AT I O N S F R O M E D WA R D S S e e w h a t ' s p o s s i b l e n o w . . .

Upload: others

Post on 15-May-2022

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Submittal Guide iO Series Life Safety Systems

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

Submittal Guide

iO Series Life Safety SystemsIntelligent fire alarm solutions for small buildings

iO S

eries

E S T B R A N D L I F E S A F E T Y & C O M M U N I C A T I O N S F R O M E D W A R D SS

e e w h a t ' s p o s s i b l e n o w . . .

Page 2: Submittal Guide iO Series Life Safety Systems
Page 3: Submittal Guide iO Series Life Safety Systems

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent ControlProject: ___________________________

Contact: ___________________________

Date: ___________________________

Thankyou for giving us the opportunity to provide this submittal for an iO

Series Life Safety System. iO Series combines analog addressable detection

with technologically advanced sensor diagnostic capabilities. Together these

innovations offer unsurpassed stability, reliability, and flexibility.

This guide provides a summary of these innovations and includes a

comprehensive presentation of related system components and devices.

Products we are submitting for your consideration are indicated by a

checkmark in the margins of the pages that follow.

More detailed information can be found in individual data sheets dedicated

to each product. All these sheets, along with guide specifications and other

useful product information, are available electronically on our LifeLines

CD-ROM. This exhaustive collection of life safety related literature is fully

searchable and includes a utility for printing multiple data sheets.

Thank you for giving us the opportunity to provide this submittal. Please do

not hesitate to contact us should you require further information.

_____________________________

Page 4: Submittal Guide iO Series Life Safety Systems
Page 5: Submittal Guide iO Series Life Safety Systems

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

iii

Submittal Guide

iO Series Life Safety SystemsIntelligent fire alarm solutions for small buildings

Page 6: Submittal Guide iO Series Life Safety Systems

iO Series Submittal GuideIntelligent fire alarm solutions for small buildings

Copyright © 2010 UTC Fire and Security All rights reserved.

8985 Town Center Parkway, Bradenton, FL 34202

85010-0132, Issue 1

Wiring diagrams provided herein are for information and reference only and are not to be used for installation pur-poses. Consult the appropriate installation documents for wiring and configuration details.

This guidebook is for information only and is not intended as a substitute for verbatim legislated requirements. For authoritative specifications regarding the application of life safety, security, and access control systems, consult

current editions of applicable codes and standards. For authoritative interpretation of those codes and standards, consult your local authority having jurisdiction.

While every effort has been made to ensure the accuracy and completeness of this guidebook, the authors and publishers assume no responsibility for errors, inaccuracies, omissions, or any inconsistencies herein.

EST, Genesis Series, and Signature Series are trademarks of UTC Fire and Security.

Also from Edwards:

85001-0541: Handbook of Visual Notification Appliances for Fire Alarm ApplicationsA practical guide to regulatory compliance

85001-0542: Glossary of Fire Alarm and Security TerminologyA desk reference for life safety and security professionals

85001-0582: Remote Booster Power Supply Application GuideA summary of typical wiring and configuration for everyday and advanced applications

85010-0139: Installer’s Wire GuideA concise pocket reference to wire and cable requirements for Edwards products and systems

85005-0115: QuickStart Submittal GuideIntelligent/conventional life safety for small to mid-sized applications

85005-0105: EST2 Submittal GuideNetworkable intelligent life safety with voice audio

85010-0099: EST3 Submittal GuideIntelligent control for large and medium sized applications

Page 7: Submittal Guide iO Series Life Safety Systems

Intelligent Analog Initiating Devices 11Detectors and Bases ...................................................... 12

Input/Output Modules .................................................... 14

Manual Pull Stations ....................................................... 18

Accessories .................................................................... 20

Notification Appliances 21Wall Strobes, Horns & Chimes ........................................ 22

Ceiling Speakers, Horns, and Strobes ............................ 23

Wall Speakers and Speaker-strobes ............................... 24

Audible Signals ............................................................... 25

Harsh Environment Signals ............................................. 26

Audio Notification System ............................................... 27

Accessories .................................................................... 28

Hazardous Location Devices 29Initiating Devices............................................................. 30

Notification Appliances ................................................... 31

Door Holders & Relays 32Door Holders .................................................................. 32

Relays ............................................................................ 32

SPDT Relays .................................................................. 33

Index 34

iO Series Analog 1System Specifications ...................................................... 2

Control Panels .................................................................. 3

Option Cards .................................................................... 4

Power Supplies ................................................................ 6

Remote annunciation ....................................................... 8

Accessories .................................................................... 10

v

With control panels, devices, and accessories all

engineered to work in unison, iO Series systems

provide reliable performance and the advanced

features you need for successful installation and

worry-free operation. Best of all, iO Series leaves

you in control – not hemmed in by a limited product

line. EST’s extensive range of fire alarm products

gives you the freedom to tailor each system to the

particular needs of the building – and the budget

of the building owner – while a robust feature set

leaves plenty of room for upgrades, expansions,

and retrofits long into the future.

But innovative features tell only part of the

story: when you specify iO Series you’re getting

more than outstanding value in a fire alarm panel;

you’re benefitting from a whole family of control,

detection, and notification appliances finely tuned

to work together – engineered and tested to func-

tion as a single unified system.

Built on the successes of the past, and meet-

ing the needs of the future, iO Series is the chang-

ing face of small building fire detection today.

Cohesive, comprehensive analog addressable fire alarm for small buildings.

No

tific

atio

n A

pp

liancesH

aza

rdo

us L

oc

atio

n D

evicesD

oo

r Ho

lders

& R

elaysIn

itiatin

g

Devices

iO S

eries Intellig

ent Co

ntrol

iO SeriesLife Safety Systems

Page 8: Submittal Guide iO Series Life Safety Systems
Page 9: Submittal Guide iO Series Life Safety Systems

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

1

iO SeriesIntelligent Control

iO Series life safety systems are a powerful intelligent solu-tion for small to mid-sized buildings. Advanced analog tech-nology delivers the benefits of flexible system installation, while a clean and easy-to-operatate user interface makes panel operation and system maintenance quick and intuitive.

The smart choiceSignature Series electronic addressing eliminates the tedium of setting dipswitches, and automatic device mapping en-sures that each device resides on the system at its correct location. Meanwhile, innovative programming features allow the system designer to customize powerful built-in features to precisely suit the needs of the building owner.

Flexibility built right inTwo fully-programmable front panel switch/LED combi-nations provide an added measure of flexibility. Their slide-in labels take the mystery out of custom applications, and present a clean finished appearance.

Perfect for retrofitsiO Series is particularly well-suited to retrofit applications. All connections are made over standard wiring – no shielded cable required. This means that in most situations existing wiring can be used to upgrade a legacy control panel to iO Series technology without the expense or disruption of rewir-ing the entire building.

Signals with a differenceiO Series NACs are configurable to fully support the ad-vanced signaling technology of Edwards Genesis and En-hanced Integrity notification appliances. These devices offer precision synchronization of strobes to UL 1971 standards. For Genesis devices, enabling this feature allows connected horns to be silenced while strobes on the same two-wire circuit continue to flash until the panel is reset.

Clear-cut remote annunciationRemote annunciation is a strong suit of the iO64. Up to eight annunciators can be installed on a single system. Compat-

ible annunciators include a range of LED and LCD models that provide zone or point annuncia-tion, as well as common control capabilities.

iO Series also supports graphic annunciation with optional RA Graphic Annunicator interface modules. Each interface provides common control, indicators, and 32 LEDS.

A complete line of accessoriesiO Series life safety systems are supported by a complete line of intelligent detectors, modules and related equipment, each of which is fully tuned and tested to oper-ate in concert with one another to provide highly reliable service and years of trouble-free operation.

iO Series Intelligent Control

Specifications p. 2

Control Panels p. 3

Option Cards p. 4

Power Supplies p. 6

Remote annunciation p. 8

Accessories p. 10

Page 10: Submittal Guide iO Series Life Safety Systems

iO SeriesiO

Ser

ies

Inte

lligen

t Con

trol

Intelligent Control

2

Ethernet

DACT/Dialer

RS-232

Relays: Two Form C, one Form A

Any combination of up to eight LCD, LED, and graphic serial annunciators

iO500: 4 Class B or 2 Class A NACs

iO64: 2 Class B or 2 optional Class A NACs

iO500: one loop that supports up to 250 intelligent devices. Can be expanded to two loops. Each loop supports up to 125 detectors and up to 125 modules.

iO64: one loop that supports up to 64 intelligent devices of any type.

Diagram represents an iO500 system wired for Class A operation with

a full complement of option cards.

Up

to 2

0,00

0 fe

et o

f wiri

ng p

er d

ata

loop

!

Specifications

Specifications iO64 iO500Device loops 1 loop Class B, Class A optional,

supports up to 64 devices1 loop, expandable to 2, Class A or B, each loop supports up to 250 devices

Notification appliance circuits

2 Class B, Class A optional, 2.5 amps each

4 Class B or 2 Class A, 2.5 amps each

Power supply 3.75 A FWR total at 120/230 VAC 60 Hz

3.0 A FWR total at 230 VAC 50 Hz 0.5 amps aux power

6.0 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz. 5.0 A total at

230VAC 50 Hz, 2.5 A max. per circuit 0.5 amps aux power

NAC Operating 24 VDC. NAC minimum voltage: 19.5 VDC @ 20.4 V battery voltageSLC Loop operating 20 V peak-to-peakPrimary power 120 VAC, 60 Hz, 230 VAC 50-60 HzAux Power 1 Continuous circuit: 24 VDC nominal at 500 mA. A SMK module is required when

using the SIGA-UM module to support two-wire smoke detectors.Aux Power 2 Resettable circuit: 24 VDC nominal at 500 mA.Auxiliary output 19 to 25.7 VDCBase panel current Standby: 155 mA Alarm: 204 mA Standby: 172 mA, Alarm: 267 mABattery placement Accommodates up to 10 A/H

batteries. Use external cabinet for larger batteries.

Accommodates up to 18 A/H batteries. Use external cabinet for larger batteries.

Batteries Batteries must be sealed lead acid type only. Maximum charging capacity = 26 Ah.

Loop circuit Maximum loop resistance: 66 Ω. Maximum loop capacitance: 0.7 µF. Style 4, 6, and 7 wiring. 64 isolators

maximum

Maximum loop resistance: 66 Ω. Maximum loop capacitance: 0.5 µF. Style 4, 6, and 7 wiring. 64 isolators

maximum.Loop max detector standby current

1.5 mA (see the UL and ULC compatibility list for your panel for the maximum quantity of detectors per circuit)

Compatibility ID 100Alarm contact Form C 24 VDC @ 1 A (resistive load)Trouble contact Form C 24 VDC @ 1 A (resistive load)Supervisory contact Form A 24 VDC @ 1 A (resistive load)Environmental Temperature: 0 to 49°C (32 to 120°F). Humidity: 0 to 93% RH, noncondensingTerminal rating All terminals rated for 12 to 18 AWG (0.75 to 2.5 sq mm)Serial communications Voltage: 2.55 V. Current: 30 mA maxRemote annunciator 8 drops max, RS-485 Class B, Class AInput zones 16 max. 32 max.Agency Listing UL, CSFM and ULC

Optional second loop (iO500)

Page 11: Submittal Guide iO Series Life Safety Systems

iO SeriesIntelligent Control

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

3

Control Panels

iO500 Intelligent Multi-Loop Systems, Data Sheet 85005-0130iO500G 1 Loop System, 500 analog point capacity, 4 NACs, gray door, surface enclosure, 115VAC, English.

iO500G-2 1 Loop System, 500 analog point capacity, 4 NACs, gray door, surface enclosure, 230VAC, English

iO500GC 1 Loop System, 500 analog point capacity, 4 NACs, gray door, surface enclosure, 115VAC, Canadian English

iO500G-F 1 Loop System, 500 analog point capacity, 4 NACs, gray door, surface enclosure, 115VAC, Canadian French

iO500GD 1 Loop System, 500 analog point capacity, two-line dialer, 4 NACs, Gray door, surface enclosure, 115VAC, English.

iO500R 1 Loop System, 500 analog point capacity, 4 NACs, red Door, surface enclosure, 115VAC, English.

iO500R-2 1 Loop System, 500 analog point capacity, 4 NACs, red door, surface enclosure, 230VAC, English

iO500RD 1 Loop System, 500 analog point capacity, two-line dialer, 4 NACs, Red Door, surface enclosure, 115VAC, English.

D16L-iO-2 LED Annunciator Module, 16 groups, 2 LEDs per group. Mounts in cabinet on iO500 systems. Mounts to right of display.

D16L-iO-1 LED Annunciator Module, 16 groups, 2 LEDs per group. Mounts in cabinet on iO500 systems. Mounts to left of display.

SA-TRIM2 Flush mount trim, black

iO64 Intelligent Single Loop Systems, Data Sheet 85005-0131iO64G 1 Loop System, 64 analog point capacity, 2 Class B NACs, Gray door, surface enclosure, 115VAC, English.

iO64GD 1 Loop System, 64 analog point capacity, 2 Class B NACs, 2 Line Dialer, Gray door, surface enclosure, 115VAC, English.

iO64R 1 Loop System, 64 analog point capacity, 2 Class B NACs, Red Door, surface enclosure, 115VAC, English.

iO64RD 1 Loop System, 64 analog point capacity, 2 Class B NACs, 2 Line Dialer, Red Door, surface enclosure, 115VAC, English.

iO64G-2 1 Loop System, 64 point capacity, 2 Class B NACs, Gray door, surface enclosure, 230VAC, English.

iO64R-2 1 Loop System, 64 point capacity, 2 Class B NACs, Red door, surface enclosure, 230VAC, English.

iO64GL 1 Loop System, 64 point capacity, 2 Class B NACs, Gray door, surface enclosure, 115VAC, English, Canadian.

iO64GL-F 1 Loop System, 64 point capacity, 2 Class B NACs, Gray door, surface enclosure, 115VAC, French, Canadian.

D16L-iO-1 LED Annunciator Module, 16 groups, 2 LEDs per group. Mounts in cabinet on iO500 systems. Mounts to left of display.

SA-TRIM1 Flush mount trim, black

Dimensions

D1

D2 D3

D4

D5

D6

Surface mounting holes

Se

mi-flu

sh

mo

un

tin

gh

ole

s

Surface mounting holes

Panel dimensions, in (cm)Model D1* D2 D3 D4 D5* D6

iO50028.0(71.1)

3.85(9.8)

9.0(22.8)

22.0(55.8)

15.75(40.0)

10.25(26.0)

iO6421.50(54.6)

3.85(9.8)

7.5(19.0)

15.5(39.4)

14.25(36.2)

10.25(26.0)

* Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.

Standard FeaturesAll iO Series life safety systems feature an attractive design that fits with any decor. Its distinctive doorfront offers a contemporary look that’s available with red or silver finishes. All LED indicators and its large backlit display remain easy to see at all times.

• Supports Signature Series intelligent modules and detectors

• Form C contacts for alarm and trouble, Form A for supervisory

• Electronic addressing with automatic device mapping

• Optional Ethernet port for diagnostics, programming and a variety of reports

• Two programmable switches with LEDs and custom labeling

• Supports Genesis horn silence over two wires and UL 1971-compliant strobe synchronization

• Supports up to eight serial annunciators, (LCD, LED-only, and graphic interface).

• Can use existing wiring for most retrofit applications

• Upload/download remotely or locally

• Two-level maintenance alert reporting

• Pre-alarm and alarm verification by point

Page 12: Submittal Guide iO Series Life Safety Systems

iO S

erie

s In

tellig

ent C

ontr

ol

SUBMIT

      

4

iO SeriesIntelligent Control

Option CardsiO-Series panels are supported by a complete line of modules and related equipment that enhance performance and extend system capabilities. Option cards are easy to install and set up. They simply plug directly into the control panel main circuit board or are connected to it with a ribbon cable. After installation, terminals remain easily accessible for quick connection of field wiring. The cabinet provides ample room for wire routing, keeping wiring neat and easy to service at all times.

SA-CLA wiring

Class A card installedon main circuit board

NAC1

NAC2+

NAC2

NAC1++ +

+ +

+

+

TB2 on maincircuit board

SA-CLA Class A Module

The SA-CLA card provides Class A capability for NAC and annuncia-tor wiring. Its terminal block provides the wiring connection for NAC return wiring. The card is required for annunciator Class A wiring even though this wiring does not return to the SA-CLA card. The SA-CLA is compatible with iO64 control panels only. iO500 panels are Class A ready. The SA-CLA is installed directly to the control panel circuit board using its plastic standoffs and plug connection.

SA-CLA Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on main board.

SA-ETH Ethernet Interface Card Network cable

Ethernet card

To networkconnection

SA-ETH wiring

The SA-ETH card provides a standard 10/100 Base T Ethernet network connection for connecting to an intranet, a local network, or the Internet. The card can be used to upload and download panel configuration, history, and current status from the iO-CU to the panel over the network.

The Ethernet card is installed on the plastic assembly and connects to the main circuit board via a ribbon cable.

SA-ETH Ethernet Port, Slave, for Ethernet connection to local area networks. Mounts in cabinet on base plate.

GND (black wire)

TXD (white wire)

RXD (red wire)

SA-232 wiring

SA-232 RS-232 interface

The SA-232 card provides an RS-232 interface with iO-Series panels. It can be used for connecting a printer to the control panel to print system events. The card also can be used for connecting a computer to download a configuration program from the iO-CU to the control panel.

The RS-232 card is installed on the plastic assembly and connects to the main circuit board via a ribbon cable.

SA-232 Serial Port (RS-232), for connection to printers & computers, mounts in cabinet to base plate

Page 13: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

5

iO SeriesIntelligent Control

Phone line 1

Phone line 2To wallphone jack

Phone cables(supplied) RJ31 jacks

SA-DACTwiring

SA-DACT Dialer

The SA-DACT provides communications between the control panel and the central station over a telephone line system. It transmits system status changes (events) to a compatible digital alarm communicator receiver over the public switched tele-phone network. The dialer is capable of single, dual, or split reporting of events to two different account and telephone numbers. The modem feature of the SA-DACT can also be used for uploading and downloading panel configuration, history, and current status to a PC running the iO-CU.

The dialer phone lines connect to connectors on the dialer’s main circuit board. Phone line 1 connects to connector J4 and phone line 2 connects to connector J1.

SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate

SMK Smoke Power Converter

The SMK Smoke Power Converter Module provides a backup power source for two-wire smoke circuits connected to a Signature data circuit. The SMK monitors the operating power from the power supply. When power begins to degrade, the SMK provides the necessary operating voltage to the two-wire smoke detection circuits.

SMK Smoke Power Converter Module

XAL250 Loop Expander Card (iO500 Systems only)

Loop 1 SEC

Loop card

+

Loop 1 PRI+

+ +

Loopdevice

Loopdevice

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI+

+ +

Loopdevice

LoopdeviceLoop card Data Line

-

-

- -

-

-

- -

Loop 1 SEC

Loop card

+

Loop 1 PRI+

+ +

Loopdevice

Loopdevice

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI+

+ +

Loopdevice

LoopdeviceLoop card Data Line

-

-

- -

-

-

- -

Class B Wiring Class A Wiring

The XAL250 Loop Expander Card provides an additional Signature Series device loop on the control panel. The card expands the control panel’s device capacity to 500 total device addresses, 250 per loop. The card is compatible with Class B or Class A wiring. It is compatible with iO500 control panels only. The loop expander card mounts in the cabinet and connects to connector J7 on the main circuit board.

XAL250 Signature Loop Expansion Module. Adds second loop to iO500 systems, 250 point capacity.

1

1

1

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

7

7

7

8

8

8

11

11

12

12

16

16

15

15

14

14 13

13 9

9

10

103 2 1

3 2 1

+_

24 VDC auxilliary power

(not resettable)

++

++

+

+

+

Power inPower out

SMK

JP1

JP1

Data in

Data out

Terminateor to next

UM

Two-wire smokedetectors

Two-wire smokedetectors

1

1

1

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

7

7

7

8

8

8

11

11

12

12

16

16

15

15

14

14 13

13 9

9

10

103 2 1

3 2 1

+_

24 VDC auxilliary power

(not resettable)

++

++

+

+

+

Power inPower out

SMK

JP1

JP1

Data in

Data out

Terminateor to next

UM

Two-wire smokedetectors

Two-wire smokedetectors

Page 14: Submittal Guide iO Series Life Safety Systems

iO S

erie

s In

tellig

ent C

ontr

ol

SUBMIT

      

6

iO SeriesIntelligent Control

Power SuppliesRemote Booster Power Supply

The Remote Booster Power Supply is a self-contained 24 Vdc power supply designed to augment fire alarm audible and visual power requirements as well as provide power for auxiliary, access control and security applications. The booster contains all of the necessary circuits to monitor and charge batteries, control and supervise four Class B or two Class A NAC circuits and monitor two controlling inputs from external sources.

Simple switch selection provides a wide variety of operational configurations. Each remote booster power supply is supplied with its own enclosure providing ample space for additional interface modules and battery compartment.

When used with Genesis Notification appliances, the booster provides the ability to syn-chronize strobes as well as horn signals. The booster flexibility allows synchronization with upstream devices, or, the booster may be used to synchronize downstream devices, as well as other boosters and their connected devices.

BPS notification appliance circuits easily configure for either of two signaling rates: 3-3-3 temporal or continuous. This makes the BPS ideal for applications requiring signaling rates not available from the main panel. It also allows independent setup of a notification appli-ance circuit without interfering with the main panel and its initiating circuits. In addition to the generated signal rates, the BPS can also be configured to follow the signal rate of the main panel’s notification appliance circuit. This allows seamless expansion of existing NACs.

For comprehensive configuration and wiring details, refer to the BPS Application Guide, 85001-0582.

BPS6A 6.5 Amp Booster Power Supply Data Sheet 85005-0125

BPS6A/230 6.5 Amp Booster Power Supply (220V) Data Sheet 85005-0125

BPS6CAA 6.5 Amp Booster Power Supply with California rate Data Sheet 85005-0125

BPS10A 10 Amp Booster Power Supply Data Sheet 85005-0125

BPS10A/230 10 Amp Booster Power Supply (220V) Data Sheet 85005-0125

BPS10CAA 10 Amp Booster Power Supply with California rate Data Sheet 85005-0125

3-TAMP Tamper switch Data Sheet 85005-0125

BoosterPower Supply

SenseNAC

Parallel ConnectionThe number of boostersthat can be connected

together is limited by wirerun length and available current

Parallel ConnectionThe number of boostersthat can be connected

together is limited by wirerun length and available current

Series ConnectionUp to ten boosterscan be connectedtogether

BoosterPower Supply

SenseNAC

BoosterPower Supply

SenseNACNAC

Circuit

Page 15: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

7

iO SeriesIntelligent Control

Batteries and Battery Cabinets12 Volt Batteries 12V4A (4.5 Ah) 12V6A5 (7.2 Ah) 12V10A (11 Ah) Data Sheet 85005-0127  12V1A2 (1.2 Ah) 12V24A (26 Ah)  12V17A (18 Ah) Data Sheet 85005-0127

6 Volt Batteries 6V8A (8 Ah) 6V10A (12 Ah) Data Sheet 85005-0127 Battery Cabinet BC-1 (holds up to two 40 Ah batteries) Data Sheet 85005-0127   

Auxiliary Power Supply (APS)

Notificationappliancecircuit (NAC)

Notificationappliancecircuit (NAC)

To next signaling device,booster, or NAC returningto existing control panel

++

OUT

OUT

NC

Sense 1

Sense 2

Trouble

COM

COM

COM

IN

IN

NO

NAC1

NAC2

NAC3

NAC4

++

++

TB2

TB1

TB5200 mA AUX

Continuous Input or signaling circuit

NAC

+-

AC power failmonitoring

EOL

[3]

The Auxiliary Power Supply (APS) is a self-contained 24 Vdc power supply designed to augment fire alarm audible and visual power requirements as well as provide auxiliary power for life safety and security applications. The APS contains all of the necessary circuits to monitor and charge batteries, control and supervise four Class B or two Class A NAC circuits and moni-tor two controlling inputs from external sources.

APS6A 6.5 Amp Auxiliary Power Supply Data Sheet 85005-0127 APS6A/230 6.5 Amp Auxiliary Power Supply (220V) Data Sheet 85005-0127 APS10A 10 Amp Auxiliary Power Supply Data Sheet 85005-0127 APS10A/230 10 Amp Auxiliary Power Supply (220V) Data Sheet 85005-0127

Page 16: Submittal Guide iO Series Life Safety Systems

iO S

erie

s In

tellig

ent C

ontr

ol

SUBMIT

      

8

iO SeriesIntelligent Control

Remote annunciation

Edwards R-Series Annunciators are high-performance remote annunciators that provide status indication and common controls for compatible fire alarm control panels, including iO-Series small analog fire alarm systems. This family of annunciators offers LCD or LED annunciation. Models are available with and without common controls.

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLCD-C

Controls Enabled

Ack/Silence

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLCD

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLED-C

RLED24

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLCD-C

Controls Enabled

Ack/Silence

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLCD

Controls Enabled

Ack/Silence

Reset

Signal Silence

Drill

Lamp Test

PowerFire AlarmSupervisoryGround FaultTrouble

RLED-C

RLED24

There are three R-Series annunciator models, plus an LED-based expander. Up to two expanders can be connected to any annun-ciator. The expander includes 24 pairs of LEDs that extend the capabilities of any of the annunciators.

All annunciator models include status LEDs and an internal buzzer. Two models have an LCD text display, and one has 16 pairs of LEDs for zone annunciation. LCD models feature a large back-lit, four by twenty character per line, super-twist liquid crystal display.

R-Series annunciators and expanders are mounted on a standard 4-inch square electrical box, using the included mounting ring. They can also be surface mounted in locking steel enclosures. Three different enclosures are available.

A keyswitch and graphic annunciator interface is available for R-Series annunciator applications. The keyswitch en-ables or disables common controls. The graphic annunicator interface cards supports 32 LEDs and 16 switches on the graphic panel display.

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

24 VDC +

LISTED 24 VDCSUPPLY

24 VDC –

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

CH2 –

CH2 +

CH1 –

CH1 +

FACP

RS-485

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

24 VDC +

LISTED 24 VDCSUPPLY

24 VDC –

FACP Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

RS-485

CH1 +

CH1 –

Annunciator

A

B

C

D

E

F

V ( )–

V (+)

OUT

First Expander

A

B

C

D

E

F

V ( )–

V (+)

IN

A

B

C

D

E

F

V ( )–

V (+)

OUT

Second Expander

A

B

C

D

E

F

V ( )–

V (+)

IN

A

B

C

D

E

F

V ( )–

V (+)

OUT

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

24 VDC +

LISTED 24 VDCSUPPLY

24 VDC –

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

CH2 –

CH2 +

CH1 –

CH1 +

FACP

RS-485

Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

24 VDC +

LISTED 24 VDCSUPPLY

24 VDC –

FACP Annunciator

CH2 (–) OUT

CH2 (+) OUT

CH2 ( ) IN–

CH2 (+) IN

CH1 ( ) OUT–

CH1 (+) OUT

CH1 ( ) IN–

CH1 (+) IN

24V (+) IN

24V ( ) IN–

GROUND

24V (+) OUT

24V ( ) OUT–

RS-485

CH1 +

CH1 –

Annunciator

A

B

C

D

E

F

V ( )–

V (+)

OUT

First Expander

A

B

C

D

E

F

V ( )–

V (+)

IN

A

B

C

D

E

F

V ( )–

V (+)

OUT

Second Expander

A

B

C

D

E

F

V ( )–

V (+)

IN

A

B

C

D

E

F

V ( )–

V (+)

OUT

Wiring, Class A Wiring, Class B

RLCD LCD text annunciator without common controls. English. Data Sheet 85005-0128

RLCD-R LCD text annunciator without common controls. English. Red. Data Sheet 85005-0128

RLCDF LCD text annunciator without common controls. French. Data Sheet 85005-0128

RLCD-C LCD text annunciator with common controls. English. Data Sheet 85005-0128

RLCD-CR LCD text annunciator with common controls. English. Red. Data Sheet 85005-0128

RLCD-CF LCD text annunciator with common controls. French. Data Sheet 85005-0128

RLED-C 16-pair LED zone annunciator with common controls. English. Data Sheet 85005-0128

RLED-CR 16-pair LED zone annunciator with common controls. English. Red. Data Sheet 85005-0128

RLED-CF 16-pair LED zone annunciator with common controls. French. Data Sheet 85005-0128

RLED24 24-pair LED zone expander with expander cable and zone card insert. Data Sheet 85005-0128

RLED24R 24-pair LED zone expander with expander cable and zone card insert. Red. Data Sheet 85005-0128

RKEY Remote key switch on plate for enabling or disabling common controls (Lock/Unlock). Data Sheet 85005-0128

Page 17: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initiating D

evicesiO

Series

Intelligent Control

9

iO SeriesIntelligent Control

Annunciator Enclosures

RA-ENC1

RA-ENC2

RA-ENC3

The RA Remote Annunciator Enclosures provide secure, surface mounted protec-tion for annunciators and extenders. Each consists of a back plate, hinged cover, and key lock. The enclosures are 16-gauge welded steel with a white, painted finish. Each enclosure includes a security lock and two keys. The two- and three-position enclosures have wiring channels for correct routing of interconnections. The enclosures attach to a standard electrical box, and provide a mounting lip that takes the place of the integral mounting ring supplied with the annunciators and expanders.

RA-ENC1 One-position enclosure for Remote Annunciator. Data Sheet 85005-0128

RA-ENC2 Two-position enclosure for Remote Annunciator and one Remote Expander. Data Sheet 85005-0128

RA-ENC3 Three-position enclosure for Remote Annunciator and two Remote Expanders. Data Sheet 85005-0128

Graphic Annunication

The RA Graphic Annunicator is an interface card that connects the iO Series control panel to the display panel of an LED-based graphic annunciator. The annunciator card supports 32 LEDs on the graphic panel display. It includes status LEDs and an internal buzzer. The graphic interface is sup-plied with snap track mounting. It is attached to a plastic mounting rail that requires two EIA panels. The annunciator communicates with the control panel on the RS-485 data riser. This can be configured for Class A or Class B communication. The annunciator does not provide ground fault isolation. It is a stand-alone unit that can be powered by the control panel or by an approved power supply.

ENVOY graphic annunciators and smoke control panels are designed to present complex status and control information in an easy to understand package. The design of ENVOY products permits users to rapidly determine system status and easily operate associated system controls.

GCI Graphic Annunciator Driver Data Sheet 85005-0128

EV1 Envoy Graphic Annunciator (maximum 96 LEDs) Data Sheet 85006-0037

EV1B EV1 Wallbox: textured black finish Data Sheet 85006-0037

EV1T EV1 Semi-Flush Trim: textured black finish Data Sheet 85006-0037

EV2 Envoy Graphic Annunciator (maximum 160 LEDs) Data Sheet 85006-0037

EV2B EV2 Wallbox: textured black finish Data Sheet 85006-0037

EV2T EV2 Semi-Flush Trim: textured black finish Data Sheet 85006-0037

EV3 Envoy Graphic Annunciator (maximum 256 LEDs) Data Sheet 85006-0037

EV3B EV3 Wallbox: textured black finish Data Sheet 85006-0037

EV3T EV3 Semi-Flush Trim: textured black finish Data Sheet 85006-0037

Page 18: Submittal Guide iO Series Life Safety Systems

iO S

erie

s In

tellig

ent C

ontr

ol

SUBMIT

      

10

iO SeriesIntelligent Control

City Tie Module Alarm/Supervisory Wiring

Riser out to next deviceor EOL Relay

Riser infromPanel

Data in

Data out

Master Box

MunicipalCircuit

CC1/MCC1

CTMThe City Tie Module provides a simple way of connecting iO Series to a local energy fire alarm box or City Master Box. One 2-CTM provides either supervisory or alarm signaling. To config-ure both supervisory and alarm signaling, two City Tie modules are required.

CTM City Tie Module Data Sheet 85005-0097

Reverse Polarity Module

Provides three reverse polarity transmitters: one for system common alarm; one for system common trouble; and, one for system common supervisory.

RPM Reverse Polarity Module Data Sheet 85005-0097

Desktop Serial Printer

The PT-1 series printers are high-speed, nine-pin dot matrix type. It is used to permanently record life safety system changes of state. All printed entries contain the date, time, event type and a user-defined message for each printed event. The printer is required in propri-etary systems and requires a backup UPS power source. In auxiliary, local, or remote station systems, the printer is optional.

PT-1S Serial Printer Data Sheet 270020

PT-1S/220 Serial Printer — 220/240Vac Data Sheet 270020

Accessories

Page 19: Submittal Guide iO Series Life Safety Systems

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initia

ting

D

evices

11

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Signature Series intelligent analog addressable devices represent an entire family of fire alarm and security detectors as well as mounting bases, multiple-function input and output modules, and user-friendly maintenance and service tools.

Analog information from equipment connected to Signature devices is gathered and converted into digital signals. At the heart of each Signature Series device is an on-board micro-processor that analyses these signals and decides whether or not to input an alarm. The power of this approach, known as distributed intelligence, provides four important benefits: self-diagnostics and history logging; au-tomatic device mapping; stand-alone operation; and, fast, stable communication.

Self-diagnostics and His-tory Log – Signature Series devices constantly run self-checks to provide important maintenance information. The results of these checks are automatically updated and permanently stored in the device’s non-volatile memory. This information is accessible for review using the System Definition Util-ity. The information stored in device memory includes:

• device serial number, address, and type;

• date of manufacture, hours of operation, and last mainte-nance date;

• number of recorded alarms and troubles; and,

• up to 32 possible trouble codes which may be used to specifically diagnose faults.

Automatic Device Mapping – The Signature Loop Controller learns where each device’s serial number address is installed relative to other devices on the circuit. The controller keeps a map of all Signature Series devices connected to it. This allows the Signature Loop Controller to discover:

• unexpected additional device addresses;

• missing device addresses; and,

• changes to the wiring in the circuit.

Most Signature modules use a personality code selected by the installer to determine their actual function. Personal-ity codes are downloaded from the controller during system configuration and are indicated during device mapping.

Fast Stable Communica-tion – Built-in intelligence means less information needs to be sent between the device and the Signa-ture Loop Controller. Other than routine supervisory polling responses, Signa-ture devices only need to communicate with the controller when they have something new to report. This provides very fast con-trol panel response and al-

lows a lower baud rate (speed) to be used for communication on the circuit. The lower baud rate offers several advantages including:

• less sensitivity to circuit wire characteristics;• less sensitivity to noise glitches on the cable;• less emitted noise from the analog wiring; and,• twisted or shielded wiring is not required.

Detectors and Bases p. 12

Input/Output Modules p. 14

Manual Pull Stations p. 18

Accessories p. 20

Signature Series

Intelligent Analog Initiating Devices

iO Series Signature Device loop

iO Series control panels provide one device loop circuit that can be used with any mix of Signature Series detectors and modules. The iO500 panel can be expanded to provide a second loop. All loop

circuits are supervised for opens, shorts, and grounds.

Circuit specificationsDevice loops 1 loop, expandable to 2, Class A or B, each loop

supporting up to 250 device addressesCom. line voltage Maximum 20 V peek-to-peekCircuit current 0.5 A maxCircuit impedance 66Ω total, 0.5 µF, maxIsolators 64 maximum

Typical Wiring

Loop 1 SEC

Loop card

+

Loop 1 PRI+

+ +

Loopdevice

Loopdevice

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI+

+ +

Loopdevice

LoopdeviceLoop card Data Line

-

-

- -

-

-

- -

Loop 1 SEC

Loop card

+

Loop 1 PRI+

+ +

Loopdevice

Loopdevice

Data Line

Class B wiring

Class A wiring

Loop 1 SEC+

Loop 1 PRI+

+ +

Loopdevice

LoopdeviceLoop card Data Line

-

-

- -

-

-

- -

Class B Class A

Page 20: Submittal Guide iO Series Life Safety Systems

Init

iati

ng

D

evic

es

SUBMIT

      

iO S

erie

s

Inte

lligen

t Con

trol

12

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Intelligent 4D Multisensor Detector

Integrates three sensing technologies — Ionization, Photoelectric, and Heat — into one detector. Select alarm point for any one of five sensitivity settings between 0.67 to 3.70% per foot. Heat detector alarms when it sees a 65° F (35° C) increase in ambient temperature. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

SIGA-IPHS Intelligent 4D Multisensor Detector, White Data Sheet 85001-0245

SIGA-IPHSB Intelligent 4D Multisensor Detector, Black Data Sheet 85001-0245

Intelligent 3D Multisensor Detector

Integrates two sensing technologies — Photoelectric and Heat — into one detector. Select alarm point for any one of five sensitivity settings between 0.67 to 3.77% per foot. Heat detector alarms at 135° F (57° C) ambient temperature. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

SIGA-PHS Intelligent 3D Multisensor Detector, White Data Sheet 85001-0247

Intelligent Photoelectric Detector

Select alarm point for any one of five sensitivity settings between 0.67 to 3.77% per foot. Mounts to separate Stan-dard, Relay, Isolator, or Sounder detector base.

SIGA-PS Intelligent Photoelectric Detector, White Data Sheet 85001-0269

Intelligent Ionization Detector

Select alarm point for any one of five sensitivity settings between 0.61 to 1.91% per foot. Mounts to separate Stan-dard, Relay, Isolator, or Sounder detector base.

SIGA-IS Intelligent Ionization Detector, White Data Sheet 85001-0291

Intelligent Rate-of-Rise/Fixed Temperature Heat Detector

Includes 15° F (9° C) per minute rate-of-rise and 135° F (57° C) fixed temperature sensor. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

SIGA-HRS Intelligent Rate-of-Rise/Fixed Temperature Heat Detector, White Data Sheet 85001-0243

Intelligent Fixed Temperature Heat Detector

Includes 135° F (57° C) fixed temperature sensor. Mounts to separate Standard, Relay, Isolator, or Sounder base. SIGA-HFS Intelligent Fixed Temperature Heat Detector, White Data Sheet 85001-0243

Signature Series

Detectors and BasesSignature Series products are intelligent devices that have significantly lower communications requirements than those of sensor type devices. Because of the low Signature communica-tions rate there are no special wiring requirements for Signature circuits. This permits Signature devices to use existing wiring, as long as the wiring is in good shape, free of electrical noise, When existing wiring is used, the Signature devices will properly map the circuit, function as designed, and provide overall network response time of less than three seconds. For new installations, twisted-pair wiring is all that is recommended.

Page 21: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initia

ting

D

evices

13

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

SIG+ SIG-

DATA-OUT

DATA-IN

DATA+IN/OUT

+

-

+

-

+

-

+

-

Volume setting

24 Vdc inFrom power supply

or previous base

Data inFrom Signature controller

or previous device

Tone setting

24 Vdc outTo next baseor EOL relay

Data outTo next Signaturedevice

Audible (Sounder) Detector Base

The Signature Series AB4G sounder base adds an audible output function to any Signature Series detector. The base can operate as an independent local alarm, or as part of a zone or system alarm with synchronized audible output. The AB4G may be configured in the field for either steady or temporal output and either high or low dB output.

SIGA-AB4G Audible (Sounder) Base Data Sheet 85001-0581

Standard Detector Base

Signature detector base provides roomside wiring terminals. Mounts to North American one-gang box, 3½ or 4-inch octagon boxes, or 4-inch square electric box. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electric box and provide a finished appearance.

SIGA-SB SIGA-SB4 (with trim skirt) Standard Detector Base Data Sheet 85001-0245

Isolator Detector Base

Signature detector base provides room-side wiring terminals and includes a built-in line fault isolator. Models with integral switches allow the detector to be removed from its base without causing the isolator to operate. Mounts to North American one-gang box, 3½ or 4-inch octagon boxes, or 4-inch square electrical boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electrical box and provide a finished appearance.

SIGA-IB SIGA-IB4 (with trim skirt) Isolator Detector Base Data Sheet 85001-0245

Relay Detector Base

This base includes a relay. Normally-open or closed operation is selected dur-ing installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s position is supervised to avoid accidentally jarring it out of position. The relay base does not support the SIGA-LED remote LED. It mounts to North American one-gang boxes, 3½ or 4-inch octagon boxes, or 4-inch square electrical boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electrical box and provide a finished appearance.

SIGA-RB SIGA-RB4 (with trim skirt) Relay Detector Base Data Sheet 85001-0245

Page 22: Submittal Guide iO Series Life Safety Systems

Init

iati

ng

D

evic

es

SUBMIT

      

iO S

erie

s

Inte

lligen

t Con

trol

14

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Module mounting and installation options

Signature Series input/output modules are available in models that feature two mounting options: standard mount and plug-in.

Standard mount models are installed to North American two-gang or one-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module.

Plug-in UIO modules mount to UIO motherboards. Two- and six-module UIO motherboards are available, making them ideal for instal-lations where more than one module is required. Motherboards can accommodate individual risers for each on-board module, or shared risers in any combination with their UIO modules. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in either cabinets, or standard electrical enclosures.

Signature Series input/output modules are extremely flexible and power-ful devices that gather analog information from the slave devices connected to them and convert this data into digital signals. They are available in models that mount in standard one- or two-gang electrical boxes, as well as versions that plug into UIO motherboards. The actual function of each module is determined by its installer-selected personality code. This is downloaded to the module from the Signature Loop Controller during system configuration. Because they are intelligent devices, all decisions are made at the module. This allows lower communication speed but very fast control panel response time and less sensitivity to line noise and loop wiring properties. As a result, twisted or shielded wire is not required.

Signature Series

Input/Output Modules

Standard two-gang mount

Plug-in UIOs with motherboard

SIGA-SD Intelligent SuperDuct Detector Data Sheet 85001-0584

Sampling Tubes SD-T8 (8”) SD-T18 (18”) SD-T24 (24”) SD-T36 (36”) SD-T42 (42”) SD-T60 (60”) SD-T78 (78”) SD-T120 (120”)

Remote Test Stations SD-TRM (magnetic) SD-TRM (keyed) SIGA-LED (Remote alarm LED)

Accessories SD-GSK (cover gasket kit) SD-MAG (Test magnet kit) SD-VTK (Air velocity test kit, stoppers only) SIGA-SDPCB (PCB/Signature sensor kit)

SuperDuct Duct Detectors

Less than two inches deep, SuperDuct intelligent smoke detectors are ideal for installation in ductwork, where space is always at a premium. Offering the most advanced and most reliable performance in its class, SuperDuct represents the perfect balance of practical design and ad-vanced technology.

SuperDuct detectors feature a unique design that speeds installation and simplifies maintenance. Removable dust filters, conformally coated circuit boards, and optional water-resistant gaskets keep contaminants away from components, ensuring years of trouble-free service. When cleaning is required, the assemblies come apart easily and snap back together in seconds.

Returnair

Duct smokedetector

Supplyair

Duct smokedetector

Remotetest station

FACP

HVACunit

Alarm relay output

Alarm relay output

Remotetest station

Standard mount (one- or two-gang)

FIRE ALARM

MODULE

UIO Motherboard

Plug-in (UIO)Module

Cabinet or electrical enclosure

Plug-in UIO

Page 23: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initia

ting

D

evices

15

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Universal Class A/B Module

The Universal Class A/B Module is used to connect initiating, appliance, or two-wire smoke circuits in either Class A or Class B configurations. The plug-in version can also be used as a Class A dry contact initiating device circuit. The actual function of this module is determined by the “personality code” selected by the installer. Up to fifteen personalities are available.

SIGA-UM Universal Class A/B Module (Two-gang standard mount) Data Sheet 85001-0275

SIGA-MAB Universal Class A/B UIO (Plug-in) Module Data Sheet 85001-0275

SIGA-UM

Class B Input Module

The Class B Input Module is used to connect Class B normally-open Alarm, Supervisory, or Monitor type dry contact initiating device circuits. The standard-mount version is available with either one or two input connections. The plug-in version accepts two input connections. The actual function of this module is determined by the “personality code” selected by the installer. A total of four personalities are available.

SIGA-CT1 Single Input Module (One-gang standard mount) Data Sheet 85001-0241

SIGA-CT2 Dual Input Module (One-gang standard mount) Data Sheet 85001-0241

SIGA-MCT2 Dual Input UIO (Plug-in) Module Data Sheet 85001-0241

SIGA-CT1/CT2

SIGA-MCT2

SIGA-MAB

Waterflow/Tamper Module

The SIGA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class B normally-open waterflow alarm switches. When the input contact is closed for approximately 16 seconds, an “alarm” signal is sent to the loop controller. Circuit 2 is for Class B normally open dry contact supervisory and tamper switches. When the input contact is closed, an “active” signal is sent to the loop controller. Conditions on both circuits are latched at the module.

SIGA-WTM Waterflow/Tamper Module (One-gang standard mount) Data Sheet 85001-0297

Isolator Module

The SIGA-IM Isolator Module is an intelligent device that allows part of the Signature data loop to continue operating in the event of a short circuit. The module can be wired into a Class A data loop at any point. A maximum of 96 isolator modules can be installed on one circuit. If a fault occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once activated, the line fault isolator continuously checks the faulted side of the loop to determine if the short still exists. When the fault is cleared, the module automatically restores the entire data loop to its normal condition.

SIGA-IM Fault Isolator Module (Two-gang standard mount) Data Sheet 85001-0271

Monitor Module

The SIGA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry contact. This is used for monitoring input from devices such as fans, dampers, and doors. When the input contact is closed, an “active” signal is sent to the loop controller. The active condition is not latched at the module.

SIGA-MM1 Monitor Module (One-gang standard mount) Data Sheet 85001-0297

SIGA-IM

SIGA-WTM

SIGA-MM1

Page 24: Submittal Guide iO Series Life Safety Systems

Init

iati

ng

D

evic

es

SUBMIT

      

iO S

erie

s

Inte

lligen

t Con

trol

16

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Signal ModuleThe Signal Module is used to connect, upon command from the loop controller, supervised Class B signal or telephone circuits to their respective power inputs. Models are available with one or two power inputs. These may be either polarized 24 Vdc to operate audible and visual signal appliances, or 25 and 70Vrms to operate audio evacuation speakers and firefighter’s telephones. The actual function of this module is determined by the “personality code” selected by the installer. A total of three personalities are available.

SIGA-CC1 Single Input Signal Module (Two-gang standard mount) Data Sheet 85001-0237

SIGA-MCC1 Single Input Signal UIO (Plug-in) Module Data Sheet 85001-0237

SIGA-CC2 Dual Input Signal Module (Two-gang standard mount) Data Sheet 85001-0237

SIGA-MCC2 Dual Input Signal UIO (Plug-in) Module Data Sheet 85001-0237

Control Relay ModuleThe Control Relay Module provides a Form C dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon command from the loop controller, the relay activates the normally open or normally-closed contact. This module supports only one personality: no user configuration is required.

SIGA-CR Control Relay Module (One-gang standard mount) Data Sheet 85001-0239

SIGA-MCR Control Relay UIO (Plug-in) Module Data Sheet 85001-0239

Polarity Reversal Relay ModuleThe Polarity Reversal Relay Module provides a Form C dry relay contact to power and activate a series of SIGA-AB4 Audible Sounder Bases. Upon command from the Signature loop controller, the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. This module supports only one personality: no user configuration is required.

SIGA-CRR Polarity Reversal Relay Module (One-gang standard mount) Data Sheet 85001-0239

SIGA-MCRR Polarity Reversal Relay UIO (Plug-in) Module Data Sheet 85001-0239

Synchronization Output Module

The Synchronization Output Module is an intelligent device that connects a supervised output circuit to a 24 Vdc riser. The output wiring is monitored for open circuits and short circuits. A short circuit will cause the fire alarm control panel to inhibit the activation of the audible/visual signal circuit so the riser is not connected to the wiring fault. Upon command from the Signature loop controller, the Auto-Sync Output Module connects the output circuit to the riser input.

SIGA-CC1S Synchronization Output Module (One-gang standard mount) Data Sheet 85001-0543

SIGA-MCC1S Synchronization Output UIO (Plug-in) Module Data Sheet 85001-0543

Input/Output Module

The Input/Output Module is an intelligent device that provides• Output with monitor input• Input/programmable output• Input/direct output

SIGA-IO Input/Output Module (One-gang standard mount) Data Sheet 85001-0533

SIGA-MIO Input/Output UIO (Plug-in) Module Data Sheet 85001-0533

SIGA-CC1/CC2

SIGA-MCC1/MCC2

SIGA-CR

SIGA-MCR

SIGA-CRR

SIGA-MCRR

SIGA-IO

SIGA-MMIO

SIGA-CC1S

SIGA-MCC1S

Page 25: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initia

ting

D

evices

17

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Universal Input/Output (UIO) Motherboards

Signature Series Universal Input/Output Module Motherboards provide mounting and wiring termi-nations for up to six Signature Series plug-in UIO (SIGA-“M” series) modules. UIO motherboards snap into a rigid extruded track (included) with mounting pads for convenient mounting into a variety of equip-ment enclosures. UIO modules plug into the board and are held securely in place with captive machine screws. All field wiring connects to terminal blocks on the motherboard, which permits rapid removal and replacement of modules for troubleshooting.

The SIGA-UIO2R provides mounting and wiring terminations for up to two UIO modules, and the SIGA-UIO6R provides mounting and wiring terminations for up to six UIO modules. Both motherboards feature a riser #1 input and a riser #2 input bus. Jumpers on riser #1 input (between modules), facilitate sharing a single riser among more than one module. This significantly reduces wiring requirements. Removing the jumpers provides separate riser inputs to each adjacent module. Riser #2 input is fixed to each module position and cannot be split. UIO motherboards mount inside the MFC-A cabinet or other suitable UL-listed electrical enclosure. Each MFC-A will hold one UIO2R motherboard or one UIO6 or UIO6R motherboard complete with their full complement of modules.

SIGA-UIO2R Universal Input/Output Module Board with Riser Inputs — 2 Module Positions Data Sheet 85001-0365

SIGA-UIO6R Universal Input/Output Module Board with Riser Inputs — 6 Module Positions Data Sheet 85001-0365

SIGA-UIO6 Universal Input/Output Module Board — 6 Module Positions Data Sheet 85001-0365

Riser 2 Inputcommon toall SIGA-UIOModules

Jumpers ConnectRiser Input #1

Between Modules

Individual Riser 1 Input to each SIGA-UIO module

Module Input/Output Wiring

SignatureDataCircuit

Data In

Data Out

Related Equipment

MFC-A Multi-function Cabinet (for UIO and Releasing modules)

27193-11 Surface Mount Box - Red, One-gang

27193-16 Surface Mount Box - White, One-gang

27193-21 Surface Mount Box - Red, Two-gang

27193-26 Surface Mount Box - White, Two-gang

235196P Bi-polar Transient Protector (use with all Signal Modules)

SIGA-MP1 Signature Module Mounting Plate, 1 footprint

SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint

SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint

Page 26: Submittal Guide iO Series Life Safety Systems

Init

iati

ng

D

evic

es

SUBMIT

      

iO S

erie

s

Inte

lligen

t Con

trol

18

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

LIFT

NORMAL

8

4

7

3 2 1

DATA OUT (+)DATA IN (+)

DATA OUT (-)DATA IN (-)

To Next DeviceFrom Signature Controlleror Previous Device

Green LED(Normal)

Red LED(Alarm/Active)

REAR VIEW

TB1

TB2

8

4

7

3 2 1

DATA OUT (+)DATA IN (+)

DATA OUT (-)DATA IN (-)

To Next DeviceFrom Signature Controlleror Previous Device

Green LED(Normal)

Red LED(Alarm/Active)

REAR VIEW

TB1

TB2

Signature Series manual pull stations are configured for Class B IDC operation. When the station’s pull lever is operated, an

alarm signal is sent to the loop controller. The alarm condition is latched at the station.

Single Action Pull Stations

SIGA-270 series manual pull stations are made from die-cast zinc and finished with red epoxy powder-coat paint. With positive pull-lever operation, one pull on the station handle breaks the rod and turns in a positive alarm. Where two-stage operation is re-quired, SIGA-270P pre-signal models are equipped with a general alarm (GA) keyswitch.

SIGA-270 One Stage Fire Alarm Station, English Markings Data Sheet 85001-0279

SIGA-270P Two Stage (Pre-signal) Fire Alarm Station, English Markings Data Sheet 85001-0279

276-K2 GA Key — for pre-signal station Data Sheet 85001-0279

270-GLR 20 Break-rods — for SIGA-270 series Data Sheet 85001-0279

276B-RSB Surface Mount Box, Red — for SIGA-270 series Data Sheet 85001-0279

Double Action Pull Stations

The double action, single stage SIGA-278 station is a contemporary style manual station made from durable red LEXAN. To initiate an alarm, first lift the upper door, then pull the alarm handle.

SIGA-278 Double Action (One Stage) Fire Alarm Station, English Markings Data Sheet 85001-0279

276B-RSB Surface Mount Box, Red — for SIGA-278 series Data Sheet 85001-0279

276-GLR 20 Break-rods — for SIGA-278 series Data Sheet 85001-0279

Signature Series

Manual Pull Stations

Page 27: Submittal Guide iO Series Life Safety Systems

SUBMIT

      

Notification

Appliances

Hazard

ous Lo

cation

Devices

Do

or H

olders &

Relays

Initia

ting

D

evices

19

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Manual Station Relocator

The Manual Station Relocator is designed to lower the height of a fire alarm pull station to meet ADA requirements. Most existing pull stations are mounted 60 inches (1524mm) or higher above the floor. The Relocator lowers the height to 48 inches (1220mm) without the need for pulling new wires or moving the existing electrical box.

RR-32RL Pull Station Relocator Data Sheet 85001-0351

Stopper II

This unique device helps prevent false alarms without restricting legitimate ones. It consists of a tamper-proof clear LEXAN polycarbonate shield and frame that fits easily over manual pull stations. When lifted, it sounds a piercing warning horn.

STI-1100 (Flush) STI-1130 (Surface) Stopper II with Horn Data Sheet 85001-0491

STI-1200 (Flush) STI-1230 (Surface) Stopper II without Horn Data Sheet 85001-0491

STI-3100 (2" Spacer) STI-3004 (Conduit Insert) Spacers Data Sheet 85001-0491

STI-3002 (Gasket) STI-3003 (Conduit Gasket) Weatherproofing Data Sheet 85001-0491

Page 28: Submittal Guide iO Series Life Safety Systems

Init

iati

ng

D

evic

es

SUBMIT

      

iO S

erie

s

Inte

lligen

t Con

trol

20

iO SeriesI n t e l l i g e n t I n i t i a t i n g D e v i c e s

Signature Detector Guard

Constructed of sturdy 16-guage steel, the SIGA-DG Smoke Detector Guard is designed to protect SIGA-IPHS 4D and SIGA-PS smoke detectors from damage or tamper-ing. The advanced computer-designed louver system allows smoke detectors to be installed at their listed spacing and has no effect on operating sensitivity.

SIGA-DG Smoke Detector Guard Data Sheet 85001-0359

SIGA-DGSB Detector Guard Surface Mount Accessory Data Sheet 85001-0359

Detector Mounting Plate

The SIGA-DMP Detector Mounting Plate is a 7-inch (178mm) square mounting plate designed to provide convenient mounting of Signature Series intelligent smoke detectors in raised floor or plenum applications. The detector mounting plate may also be installed in low velocity ducts that have a maximum width of up to 36-inches (915mm) and a maximum height of up to 36-inches (915mm).

SIGA-DMP Detector Mounting Plate Data Sheet 85001-0255

Remote LED

The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base. It features a North American size one-gang plastic faceplate with a white finish and red alarm LED.

SIGA-LED Remote Alarm LED Data Sheet 85001-0245

Trim Skirt

Use the SIGA-TS Trim Skirt to give Signature detectors a finished look and hide surface imperfections around the detector’s base. Supplied with all four-inch detector bases, the SIGA-TS4 can also be ordered separately. Use the black model with SIGA-IPHSB.

SIGA-TS Detector Trim Skirt (white) Data Sheet 85001-0245

SIGA-TSB Detector Trim Skirt (black) Data Sheet 85001-0245

SIGA-TS4 Detector Trim Skirt (white) – for 4-inch box Data Sheet 85001-0245

Signature Series

Accessories

Page 29: Submittal Guide iO Series Life Safety Systems

Hazardous Location Devices

HeatDetectors p.30

FireAlarmStation p.30

Strobes,BellsandHorns p.31

Classes

Class I - Hazardous Gases.ClassIlocationsareareasinwhichflam-mablegasesorvaporsareormaybepresentintheairinquantitiessufficienttoproduceexplosiveorignitablemixtures.

Typical Class I Hazardous Areas•Spraypaintingandfinishingareas•Utilitygasplants•Petroleumrefiningproductionplants•Petroleumdispensinglocations•Drycleaningfacilities•Diptankscontainingcombustiblesorflammableliquids•Plantfacilitiesextractingsolvents•Inhalationanestheticsareas•Processfacilitiesmanufacturingpyroxylintypeplastics

Class II - Hazardous Dusts.ClassIIlocationsrepresentareasthatarehazardousduetothepresenceofcombustibledust.

Typical Class II Hazardous Areas•Flourmills•Feedmills•Grainelevatorsandgrainhandlingfacilities•Aluminummanufacturingandstorageareas•Magnesiummanufacturingandstorageareas•Coalpreparationandhandlingfacilities•Starchmanufacturingandstorageareas•Confectioneryplants•Pulverizersugarandcocoamanufacturing,andstorageplants•Spicegrindingandstorageplants

Class III - Hazardous Fibers. ClassIIIlocationshaveeasilyignitablefibersorflyingspresent,butnotlikelytobesuspendedinairinquantitiessufficienttoproduceignitablemixturesintheatmosphere.

Typical Class III Hazardous Areas•Textilemills•Woodworkingplants*•Furnituremanufacturers*•Cottongins•Cottonseedmillingplants•Flaxplants•Carpetmanufacturers

* Except if wood flour (dust), which is Class II Group G, is present

DivisionsTheLocationClassesarebrokendownbytheNFPAintoDivisions1and2,definingdifferentlevelsofrisk.Ingeneral,theriskoftherebeingahazardouspresenceofflammable/combustible/ignitablematerialsishigherforDivision1thanforDivision2.Thespecificsdifferbetweenthethreeclasses(I,IIandIII).EquipmentsuitableforDivision1isalsosuitableforDivision2locations.

GroupsClassIandIIlocationsaredividedbytheNFPAintoGroupdesignationsidentifyingspecificgases,vaporsanddustsbycharacteristicsimilaritiesthatrelatetospecificequipmentconstructionrequirements.ClassIIIlocationsarenotdividedintoseparategroupdesignations.

Class I Groups Group A.Atmospherescontainingacetylene.

Group B. Atmospherescontaininghydrogen,fuelandcombustibleprocessgasescontainingmorethan30percenthydrogenbyvolume,orgasesorvaporsofequivalenthazardsuchasbutadiene,ethyleneoxide,propyleneoxide,andacrolein.

Group C. Atmospheressuchasethylether,ethylene,orothergasesorvaporsofequivalenthazard.

Group D.Atmospherescontainingacetone,ammonia,benzene,butane,cyclopropane,ethanol,gasoline,hexane,methanol,methane,naturalgas,naphtha(petroleum),pro-pane,orgasesorvaporsofequivalenthazard.

Class II GroupsGroup E. Atmospherescontainingcombustiblemetaldusts,includingaluminum,magnesium,andtheircommercialalloys,orothercombustibledustswhoseparticlesize,abra-sivenessandconductivitypresentsimilarhazardsintheuseofelectricalequipment.

Group F.Atmospherescontainingcombustiblecarbona-ceousdusts,includingcarbonblack,charcoal,coal,orduststhathavebeensensitizedbyothermaterialssothattheypresentanexplosionhazard.

Group G. AtmospherescontainingcombustibledustsnotincludedinGroupEorF,includingflour,grain,wood,plastic,andchemicals.

Edwardshazardouslocationdevicesprovidereliablelifesafetyprotectionandemergencysignalinginareaswhereatmospherescouldbecomeharshorexplosive.AllhazardouslocationdevicesareULratedunderthefullrangeofclassificationssetoutintheNationalElectricalCode.

Thefollowingclassificationdefinitionsareaninterpretivesummarybasedonthe1996editionoftheNationalElec-tricalCode(NEC,NFPA70).RefertothelatesteditionsofNFPA497M,NFPA70andtheULHazardousLocationEquipmentDirectoryforcurrentandmoredetailedinformation.FormoreinformationonNEMAclassifications,refertoNEMAStandardsPublicationNo.250.

Hazardous Location Classifications

Hazardous Location Devices

Ha

zard

ou

s Lo

ca

tion

Devices

Do

orH

olders&

Relays

29

iO SeriesH a z a r d o u s L o c a t i o n D e v i c e s

Page 30: Submittal Guide iO Series Life Safety Systems

iOS

erie

s

Inte

lligen

tCon

trol

Initi

atin

gD

evic

esN

otifi

catio

nA

pplia

nces

Ha

zard

ou

s L

oc

ati

on

Dev

ices

SUBMIT

      

30

iO SeriesH a z a r d o u s L o c a t i o n D e v i c e s

Rate Compensation Heat Detectors

Series302heatdetectorsaredesignedforuseinnormalenvironmentsaswellasenvironmentswherethedetectorsaresubjecttoweather,moisture(internalcondensation),andexplosiveatmospheres.Theyarenormally-opendevicesdesignedtocloseanelectricalcircuituponactivation.Allmodelsfeatureratecompensationandareavailablewitheither135°F(57.2°C)or194°F(90°C)ratings.Theyareselfrestoring,hermeticallysealed,shockandcorrosionresistant,andaretamperproof.

Sensorsratedat135°F(57.2°C)willnotrespondtomomentarytemperaturefluctuationslessthan30°F/minutebetween60°F(16°C)and100°F(38°C).Sensorsratedat194°F(90°C)willnotrespondtomomentarytemperaturefluctuationslessthan50°F/minutebetween60°F(16°C)and150°F(66°C).302Seriessensorsshouldnotbeusedinenvironmentswhereconditionsexceedtheseparameters.Donotinstalltheminhotairducts,infrontofheaters,inpaintboothsthatuseheattocurepaint,oranyotherlocationsubjecttotem-peraturefluctuation.

Sensor’s Rated Temperature

Minimum Ambient Air Temperature

Maximum Ceiling Temperature

135°F(57.2°C) -40°F(-40°C) 100°F(38°C)194°F(90°C) -40°F(-40°C) 150°F(66°C)

Thesensor'saluminumtubeactsasaheatcollectorwhensourcesofheatradiatedirectlyonthetube.Installthesesensorsoutofdirectsunlightandawayfromradiatingheatsourcesincludingthedirectflowfromheatersandheatducts.

302-AW-135 All-weather Heat Detector - Vertical Mounting FM & UL, 135 °F (57.2 °C) Data Sheet 85001-0589

302-AW-194 All-weather Heat Detector - Vertical Mounting FM & UL, 194°F (90 °C) Data Sheet 85001-0589

302-ET-135 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C) Data Sheet 85001-0589

302-ET-194 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C) Data Sheet 85001-0589

302-EPM-135 Heat Detector - Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C) Data Sheet 85001-0589

302-EPM-194 Heat Detector - Explosionproof Mounting UL (not FM approved), 194°F (90 °C) Data Sheet 85001-0589

AP-P Adaptor plate for mounting 302 and 302-AW to any 3" box or 4" octagon outlet box Data Sheet 85001-0589

STONCO27 3 ½" Weatherproof, round backbox and cover Data Sheet 85001-0589

JALX11 Explosion proof outlet body with cover - Killark Data Sheet 85001-0589

Hazardous location fire alarm station

TheXAL-53isanextremelyruggeddouble-actionfirealarmstationsuitableforhazardouslocations.Thedeviceisactivatedbyliftingthefrontcoverandpullingdownthering.Thistwo-stepprocesspreventsunintentionaloperation.

XAL-53 Hazardous Location Fire Alarm Station Data Sheet 85001-0371

Initiating Devices

Surface Mount

Box mount

Page 31: Submittal Guide iO Series Life Safety Systems

Ha

zard

ou

s Lo

ca

tion

Devices

Do

orH

olders&

Relays

31

SUBMIT

      

iO SeriesH a z a r d o u s L o c a t i o n D e v i c e s

Hazardous Location Strobes

•ClassI,II,orIIIlocations

116DEXSTC-FJhazardouslocationstrobesarein-rushcurrentlimitedlifesafetysignalingappliancesde-signedforinstallationinhazardousenvironments.Rigidspecificationsandstate-of-the-arttechnologypro-videforhighvisualoutputandlowmaintenance.Whenpendant,wallorceilingmounted,the116DEXSTC-FJmeetsorexceedstherequirementsofUL1971SignalingAppliancefortheHearingImpaired.StanchionmountmodelsareUL1638Listedforprivatemodeemergencysignaling.AllmodelsareCSFMListed.

116DEXSTC-FJ Explosionproof Strobe, Diode Polarized Data Sheet 85001-0586

Wall Mount Elbow Ceiling/wall Module Pendant Module Stanchion Module Data Sheet 85001-0586

Hazardous Location Bells

•ClassIgroupsB,CandDlocations •ClassIIIhazardouslocations,forDivisions1and2•ClassIIgroupsE,FandGlocations

430Dseriesofhazardouslocationbellsarediode-polarized,heavydutyfirebellsforuseinlifesafetyapplicationswhereadiodesupervisedsignalisrequired.Theycanbemountedtoanysolidsurfaceusingtwo3/8inch(10mm)boltsandthesuppliedmountingbracketsortoarigidconduit.Theintegralexplosion-proofhousingismechanicallyterminatedtoacceptastandard3/4inch-14NationalPipeTaper(NPT)nipple.

439DEX-6AW (6”) 439DEX-8AW (8”) 439DEX-10AW (10”) Bell – 24 Vdc Data Sheet 85001-0399

438DEX-6N5 (6") 438DEX-8N5 (8") 438DEX-10N5 (10") Bell – 120 Vac Data Sheet 85001-0399

Hazardous Location Horns

•ClassIgroupsB,CandDlocations •ClassIIIhazardouslocations,forDivisions1and2•ClassIIgroupsE,FandGlocations

888Dand889Dhazardouslocationhornsarediode-polarized,heavyduty,highdecibelvibratinghornsintendedforuseinlifesafetysystemsinhazardous(classified)locations.Thesehornsmaybemountedtoanysolidsurfaceusingtwobolts.Eachunitissuppliedwithasealingfittingfora3/4inch-14NationalPipeTaper(NPT)nipple,andwireleadsfortheelectricalconnectiontothelifesafetysystemnotificationappliancecircuit.

888D-N5 (120 Vac) 889D-AW (24 Vdc) Horn – 120 Vac Data Sheet 85001-0397

Notification Appliances

Page 32: Submittal Guide iO Series Life Safety Systems

Do

or

Ho

lder

s

& R

elay

s

32

iO S

erie

s

Inte

lligen

t Con

trol

Initi

atin

g D

evic

esN

otifi

catio

n A

pplia

nces

Haz

ard

ous

Lo

catio

n D

evic

es

SUBMIT

      

iO SeriesD o o r H o l d e r s & R e l a y s

Door Holders Electromagnetic Door Holders

Edwards electromagnetic door holders keep doors open until signaled by the fire alarm system, a heat detector, a smoke detector, or an electrical switch. Door holders should be installed wherever doors may be effectively used to confine smoke and fire, or where the release of a self-closing door from a remote location is required. Fail-safe operation is an inherent feature of these door holders. If power fails, doors are released automatically, but may be opened or closed manually at any time. All units are free of moving parts, are self-contained, and require no maintenance. Door holders have a holding force of approximately 15-25 Lbf (66-111N).

1501-AQN5 (Single Door) 1502-AQN5 (Double Door) Floor Mounted Data Sheet 85001-0421

1504-AQN5 (Long Catch Plate) 1505-AQN5 (Short Catch Plate) Flush Wall Mounted Data Sheet 85001-0421

1508-AQN5 (Surface) 1505-AQN9 (Completely flush) Wall Mounted Data Sheet 85001-0421

1500-1 (1.5” Extension) 1500-2 (2.5” Extension) Catch Plate Data Sheet 85001-0421

1500-7 (5.25 to 7.5” Extension) 1500-12 (7.5 to 12” Extension) Catch Plate Data Sheet 85001-0421

CS2595-5 (short) CS2598-5 (long) Replacement Armature Data Sheet 85001-0421

Relays Four-Voltage SPDT/DPDT Control Relays

MR Series multi-voltage control relays are ideal for applications where local contacts are required for system status, remote contacts, or for control of electrical loads and general pur-pose switching. They are suitable for use with HVAC temperature control, fire alarm, security, energy management, and lighting control systems. Relays provide 10-Amp contacts, which may be operated by one of four input control voltages. Each relay position contains a red LED that indicates the relay coil is energized. Relays may be snapped apart from a standard four-module assembly and used independently.

MR-101/T (with mounting hardware) MR-101/C (in metal enclosure) Single SPDT relay Data Sheet 270062

MR-104/T (with mounting hardware) MR-104/C (in metal enclosure) 4-position SPDT relay Data Sheet 270062

MR-201/T (with mounting hardware) MR-201/C (in metal enclosure) Single DPDT relay Data Sheet 270062

MR-204/T (with mounting hardware) MR-204/C (in metal enclosure) 4-position DPDT relay Data Sheet 270062

Heavy Duty DPDT Power Relays

MR-199 heavy duty power relays are designed for control applications where 30-Amp DPDT contacts are required. Two models are available: a 115Vac coil and a 24Vdc coil, each of which may be mounted in a rugged steel enclosure.

MR-199X-13 (relay only) MR-199X-13/C (in metal enclosure) Power Relay — 24 VDC Data Sheet 270065

MR-199AX-14 (relay only) MR-199AX-14/C (in metal enclosure) Power Relay — 120 VDC Data Sheet 270065

24 Vac 60 Hz

24 Vdc

120 Vac 60 Hz

Page 33: Submittal Guide iO Series Life Safety Systems

Do

or H

old

ers &

Relays

33

SUBMIT

      

iO SeriesD o o r H o l d e r s & R e l a y s

SPDT RelaysSingle-pull/double-throw relays are ideal for applications where local or remote con-tacts are required for control of electrical loads. They are suitable for use with HVAC, temperature control, fire alarm, security, energy management, and lighting control systems. Each relay position contains a high-intensity LED which, when illuminated, indicates the relay coil is energized. Individual relay circuits may be snapped apart from standard four- or eight-position modules, and are also available in a single-circuit configuration. The common power to each relay position is bussed on the printed wiring board, which permits power to be connected only once per multi-position module.

Single-Voltage Manual Override Relays

MR-600 series relays provide SPDT, 10-Amp contacts with manual override capability by means of an ON-AUTO-OFF switch. The relay requires a 24Vac or 24Vdc power source supplied by the controlling system. With the switch in the ON position the power relay is energized. With the switch in the AUTO position the relay is allowed to operate as signaled by the controlling system. With the switch in the OFF position the relay cannot be energized.

MR-601/T (with mounting track) MR-601/S (with mounting spacers) Single SPDT relay Data Sheet 270061

MR-604/T (with mounting track) MR-604/S (with mounting spacers) 4-position SPDT relay Data Sheet 270061

MR-608/T (with mounting track) MR-608/S (with mounting spacers) 8-position SPDT relay Data Sheet 270061

Three-Voltage Control Relays

MR-800 Series relays provide SPDT 10-Amp contacts that may be operated by one of three input control voltages: 24Vdc, 24Vac or 115Vac.

MR-801/T (with mounting track) MR-801/S (with mounting spacers) Single SPDT relay Data Sheet 270063

MR-804/T (with mounting track) MR-804/S (with mounting spacers) 4-position SPDT relay Data Sheet 270063

MR-808/T (with mounting track) MR-808/S (with mounting spacers) 8-position SPDT relay Data Sheet 270063

Four-Voltage Control Relays

MR-700 Series relays provide SPDT 10-Amp contacts that may be operated by one of four input control voltages: 12Vdc, 12Vac, 24Vdc, or 24Vac.

MR-701/T (with mounting track) MR-701/S (with mounting spacers) Single SPDT relay Data Sheet 270064

MR-704/T (with mounting track) MR-704/S (with mounting spacers) 4-position SPDT relay Data Sheet 270064

MR-708/T (with mounting track) MR-708/S (with mounting spacers) 8-position SPDT relay Data Sheet 270064

Three-Voltage Encapsulated Control Relays

PAM-1 relays provide 10-Amp Form C contacts. The relay may be energized by one of three input voltages: 24Vac, 24Vdc, or 115Vac. The PAM-1 may be mounted with double-sided adhesive tape, a self-tapping screw, or loosely placed in a backbox.

PAM-1 Encapsulated SPDT relay Data Sheet 270066

Page 34: Submittal Guide iO Series Life Safety Systems

34

Do

or

Hol

ders

&

Rel

ays

iO S

erie

s

Ana

log

Initi

atin

g D

evic

esN

otifi

catio

n A

pplia

nces

Haz

ard

ous

Lo

catio

n D

evic

esLife Safety System

Index

Control PanelsiO500G 500-point Systems 85005-0130 3iO64G 64-point Systems 85005-0131 3D16L-iO LED Annunciator Modules 85005-0130 3SA-TRIM Flush mount trim 85005-0130 3

Option CardsSA-CLA Class A adapter module 85005-0130 4SA-ETH Ethernet Port 85005-0130 4SA-232 Serial Port (RS-232) 85005-0130 4SA-DACT Dual Line Dialer/Modem 85005-0130 5SMK Smoke Power Converter Module 85005-0130 5XAL250 Signature Loop Expansion Module 85005-0130 5

Power SuppliesBPS Booster Power Supplies 85005-0125 6APS Auxiliary Power Supplies 85005-0127 712/6V Batteries 85010-0127 7

Remote annunciationRLCD LCD text annunciators 85005-0128 8RLED-C LED zone annunciators 85005-0128 8RKEY Remote key switch on plate 85005-0128 8RA-ENC Remote Annunciator Enclosures 85005-0128 9GCI Graphic Annunciator Driver 85005-0128 9EV Envoy Graphic Annunciators 85006-0037 9

System AccessoriesCTM City Tie Module 85005-0097 10RPM Reverse Polarity Module 85005-0097 10PT-1S Serial Printer 270020 10

DetectorsSIGA-IPHS Intelligent 4D Multisensor Detector 85001-0245 12SIGA-IPHSB Intelligent 4D Multisensor Detector, Black 85001-0245 12SIGA-PHS Intelligent 3D Multisensor Detector 85001-0247 12SIGA-PS Intelligent Photoelectric Detector 85001-0269 12SIGA-IS Intelligent Ionization Detector 85001-0291 12SIGA-HRS Intelligent Rate-of-Rise/Fixed Temp. Heat 85001-0243 12SIGA-HFS Intelligent Fixed Temperature Heat 85001-0243 12SIGA-AB4G Audible (Sounder) Base 85001-0581 13SIGA-SD Intelligent SuperDuct Detector 85001-0584 14

Input/Output ModulesSIGA-UM Universal Class A/B Module 85001-0275 15SIGA-CT1 Single Input Module 85001-0241 15SIGA-CT2 Dual Input Module 85001-0241 15SIGA-WTM Waterflow/Tamper Module 85001-0297 15SIGA-IM Fault Isolator Module 85001-0271 15SIGA-MM1 Monitor Module 85001-0297 15SIGA-CC1 Single Input Signal Module 85001-0237 16SIGA-CC2 Dual Input Signal Module 85001-0237 16SIGA-CR Control Relay Module 85001-0239 16SIGA-CRR Polarity Reversal Relay Module 85001-0239 16SIGA-CC1S Synchronization Output Module 85001-0543 16SIGA-IO Input/Output Module 85001-0533 16SIGA-UIO Input/Output Module Boards 85001-0365 17

Manual Pull StationsSIGA-270 One Stage Fire Alarm Station 85001-0279 18SIGA-270P Two Stage Fire Alarm Station 85001-0279 18SIGA-278 Double Action Fire Alarm Station 85001-0279 18RR-32RL Pull Station Relocator 85001-0351 19STI Pull Station Guard 85001-0491 19

Initiating Device AccessoriesSIGA-DG Smoke Detector Guard 85001-0359 20SIGA-DMP Detector Mounting Plate 85001-0255 20SIGA-LED Remote Alarm LED 85001-0245 20SIGA-TS Detector Trim Skirt 85001-0245 20

Wall Strobes, Horns & ChimesG1-VM Wall Strobes 85001-0573 22G1-HD Wall Horn-Strobes 85001-0573 22G1-P Wall Horns, Steady 85001-0573 22G1R-CVM Wall Chime-Strobes 85001-0574 22G1-C Wall Chimes 22G1T Genesis Trim Plates 85001-0573 22G1M Genesis Signal Master 85001-0545 23G4 Wall Speakers 85001-0549 24403 Bell Strobe Plate 85001-0441 28

Ceiling Speakers, Horns, and StrobesGC Ceiling Speakers 85001-0558 23GC-SxVM Ceiling Speaker-Strobes 85001-0558 23GC-VM Ceiling Strobes 85001-0558 23GC-H Ceiling Horn-Strobes 85001-0558 23

Audible Signals5530MD-24AW27-Tone Selectable Signal — 24Vdc 85001-0415 25HPSA15R2570 15-watt loudspeaker, red 85001-0591 25HPSA15G257015-watt loudspeaker, gray 85001-0591 25

Audio Notification SystemANS Audio Notification Panels 85001-0587 27

Harsh Environment Signals757-1A-T Temporal Horn 85001-0341 26757-7A-T Temporal Horn-Strobe 85001-0341 26405-5A-T Outdoor Strobe 85001-0305 26757-1A-R25 Re-entrant Speaker 85001-0317 26757-7A-RS25 Re-entrant Speaker-Strobe 85001-0317 26

Hazardous Location Devices302Series All-weather Heat Detectors 85001-0589 30XAL-53 Hazardous Location Fire Alarm Station 85001-0371 30116DEXSTC-FJExplosionproof Strobe 85001-0586 31

Door Holders & Relays1500 Series Electromagnetic Door Holders 85001-0421 44MR-199 Heavy Duty Power Relays 270065 44MR-700 MR-700 Multi-Voltage Control Relays 270064 45MR-800 MR-800 Multi-Voltage Control Relays 270063 45MR Series MR-100 & 200 Multi-Voltage Control Relays 270062 44MR-600 Manual Override Relays 270061 45PAM-1 Encapsulated SPDT relay 270066 33

Model Description Lit#/Guide p. # Model Description Lit#/Guide p. #

Page 35: Submittal Guide iO Series Life Safety Systems
Page 36: Submittal Guide iO Series Life Safety Systems

85005-0132

Innovation, leadership, and a rich tradition of excellence

Whether EST life safety systems are protecting the lives and livelihoods of the

people who make businesses run, or the lives entrusted to the care of public

institutions; whether they’re charged with protecting the guests of the world’s

finest hotels, or preserving irreplaceable artifacts that bring history to life; EST

stands alone as the brand closely associated with some of the most important

and far-reaching developments in the life safety industry today.

Our strength is in our Strategic Partners — the people and organizations

we entrust with the technology that has charted the course of life safety protec-

tion for decades. Strategic Partners are not middlemen or go-betweens. They

are independent contractors that form an integral part of the Edwards marketing

and support organization. As insiders, they enjoy exclusive access to products,

custom design innovations, specialized training, and pricing privileges. Yet

as successful independent contractors, they are adept at ensuring that each

submittal is strong and competitive, and that each bid is locally relevant to your

installation. As local businesses they not only have to earn your trust — they

have to keep it.

Together these strengths set EST installations apart, and have earned this

brand a special place among life safety and security solutions available today.

Perhaps that’s why EST products and systems have become the choice of

building owners, architects and engineers around the globe. And why many of

the world’s most cherished landmarks are protected by Edwards products that

bear the EST mark. From the Bibliotheca Alexandrina Museum in Egypt, to the

modern-day sphinx at the Luxor Hotel in Las Vegas, professionals who design,

own and occupy the world’s most impressive structures have come to know

that the safest and most survivable solution today is an EST solution.

See what’s possible now.

Contact your EST Strategic

Partner today.

Detection & alarm since 1872

U.S.T 888-378-2329F 866-503-3996

CanadaChubb-EdwardsT 519 376 2430F 519 376 7258

Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 AustraliaT +61 3 9239 1200F +61 3 9239 1299

EuropeT +32 2 725 11 20F +32 2 721 86 13

Latin AmericaT 305 593 4301F 305 593 4300

utcfireandsecurity.com

© 2010 UTC Fire & Security. All rights reserved. 06-21-10