EN 990-5146C 02/2019 User Manual English APC Smart-UPS SUA750I-IN 230 Vac Tower Uninterruptible Power Supply

Upload: others

Post on 27-Oct-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SU UM 990-5146 MN01 EN 08Feb19

EN 990-5146C 02/2019

User Manual English

APC Smart-UPS™

SUA750I-IN 230 Vac

Tower

Uninterruptible Power Supply

Page 2: SU UM 990-5146 MN01 EN 08Feb19
Page 3: SU UM 990-5146 MN01 EN 08Feb19

1

Important Safety Information SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the Smart-UPS and batteries.

Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

Page 4: SU UM 990-5146 MN01 EN 08Feb19

2

Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

Read the Safety Guide supplied with this unit before installing the UPS.

• Adhere to all national and local electrical codes.

• All wiring must be performed by a qualified electrician.

• Changes and modifications to this unit not expressly approved by APC could void the warranty.

• This UPS is for indoor use only.

• Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or high humidity.

• Do not operate the UPS near open windows or doors.

• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.

• Note: Allow 20 cm clearance on both front and rear sides of the UPS.

• Use only the mains and communication cables provided along with the UPS.

• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.

Page 5: SU UM 990-5146 MN01 EN 08Feb19

3

Product Description The APC™ by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to acceptable levels or the batteries are fully discharged.

This user manual is available on the APC by Schneider Electric Web site, www.apc.com.

1: INSTALLATION Package contents Attention: Read the safety instruction sheet before installation.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.

The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents: UPS UPS literature kit containing:

Product documentation, safety and warranty information Serial and USB communication cables Jumper cable (output cable) Input power cord

Note: The UPS is shipped with the battery disconnected.

Position the UPS The UPS is heavy. Select a location sturdy enough to handle the weight. Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits.

0-95% 1 in (2.5 cm)

0-40°C

Page 6: SU UM 990-5146 MN01 EN 08Feb19

4

Connect the Battery The battery connector is located on the rear panel.

For battery connection, push the tethered jumper plug into the corresponding port.

Connect Equipment and Power to the UPS

1. Connect equipment to the UPS.

Note: A laser printer draws significantly more power than other types of equipment and may overload the UPS.

2. Add accessories to the Smart-Slot (optional).

3. Connect ground leads to the TVSS screw (optional). To make the connection, loosen the screw and connect the surge suppression device ground lead. Tighten the screw to secure the lead.

4. Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.

The power cord is supplied in the UPS literature kit. 5. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all

connected equipment is on.

6. Press the button on the front panel to power the UPS.

Note: The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period.

7. For optimal computer system security, install PowerChute Smart-UPS monitoring software.

Page 7: SU UM 990-5146 MN01 EN 08Feb19

5

Rear Panel

Basic Connectors

Serial Port

USB Port

Ground Screw

Use only interface kits approved by APC. Use only the supplied cable to connect to the Serial Port. A standard serial interface cable is incompatible with the UPS. Serial and USB Ports cannot be used simultaneously. The UPS features a ground screw for connecting the ground lead on surge suppression devices such as telephone and network line protectors. When connecting grounding cable, disconnect the unit from the utility power outlet. This is a Class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take corrective actions.

Install PowerChute™ software To install PCPE, connect the supplied USB cable between the data port on the UPS and to a computer with access to the Web.

On the computer, go to www.apc.com/tools/download. Select Software Upgrades - PowerChute Personal Edition and the appropriate operating system. Follow directions to download the software.

Page 8: SU UM 990-5146 MN01 EN 08Feb19

6

2: OPERATION

Front Display Panel

INDICATOR DESCRIPTION Online

The UPS is supplying utility power to the connected equipment.

AVR Trim

The UPS is compensating for a high utility voltage.

AVR Boost

The UPS is compensating for a low utility voltage.

On Battery

The UPS is supplying battery power to the connected equipment.

Overload

The connected loads are drawing more than the UPS power rating.

Replace Battery/ Battery Disconnected

The battery is disconnected or must be replaced.

FEATURE FUNCTION Power On

Press this button to turn on the UPS. (Read on for additional capabilities.)

Power Off

Press this button to turn off the UPS.

Page 9: SU UM 990-5146 MN01 EN 08Feb19

7

FEATURE FUNCTION Self-Test Automatic: The UPS performs a self-test automatically when turned on, and

every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.

Manual: Press and hold the button for a few seconds to initiate the self-test.

Cold Start Supply battery power to the UPS and connected equipment in the absence of

utility voltage (see Troubleshooting). Press the button for one second and release. The UPS will beep briefly and go quiet. Press and hold the button again, but for approximately three seconds. The unit will emit a sustained beep. Release the button during this beep.

Diagnostic Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display.

Press and hold the button to view the utility voltage bar graph display. After a few seconds, this five-LED battery charge display on the right of the front panel will show the utility input voltage. Refer to the figure at left for the voltage reading (values are not listed on the UPS). The display indicates the voltage is between the displayed value on the list and the next higher value (see Troubleshooting).

Battery Operation The UPS switches to battery operation automatically if the utility power is not available. While running on battery, an audible alarm beeps four times every 30 seconds.

Press the button to silence this audible alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully discharges the battery.

Refer to www.apc.com for on battery runtimes.

Page 10: SU UM 990-5146 MN01 EN 08Feb19

8

3: USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT ACCESSORY CARDS.

FUNCTION FACTORY DEFAULT

USER SELECTABLE CHOICES DESCRIPTION

Automatic Self-Test

Every 14 days (336 hours)

Every 7 days (168 hours), On Startup Only, No Self-Test

Set the interval at which the UPS will execute a self-test.

UPS ID UPS_IDEN Up to eight characters (alphanumeric)

Uniquely identify the UPS, (i.e. server name or location) for network management purposes.

Date of Last Battery Replacement

Manufacture Date mm/dd/yy Reset this date when you replace the battery module.

Minimum Capacity Before Return from Shutdown

0 percent 0, 15, 30, 45, 50, 60, 75, 90 percent

Specify the percentage to which batteries will be charged following a low-battery shutdown before powering connected equipment.

Voltage Sensitivity

The UPS detects and reacts to line voltage distortions by transferring to battery operation to protect connected equipment.

High High sensitivity, Medium sensitivity, Low sensitivity

Note: In situations of poor power quality, the UPS may frequently transfer to battery operation. If the connected equipment can operate normally under such conditions, reduce the sensitivity setting to conserve battery capacity and service life.

Alarm Delay Control

Enable Enable, Mute, Disable

Mute ongoing audible alarms or disable all audible alarms permanently.

Shutdown Delay 90 seconds 0, 90, 180, 270, 360, 450, 540, 630 seconds

Set the interval between the time when the UPS receives a shutdown command and the actual shutdown.

Low Battery Alert

2 minutes

PowerChute software provides automatic, unattended shutdown when approximately 2 minutes of battery operated runtime remains.

2, 5, 8, 11, 14, 17, 20, 23 minutes

(Times are approximate.)

The UPS will beep when 2 minutes of battery runtime remains.

Change the low battery alert interval setting to the time that the operating system or system software requires to shut down.

Page 11: SU UM 990-5146 MN01 EN 08Feb19

9

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT ACCESSORY CARDS.

FUNCTION FACTORY DEFAULT

USER SELECTABLE CHOICES DESCRIPTION

Synchronized Turn-on Delay

0 seconds 0, 60, 120, 180, 240, 300, 360, 420 seconds

Specify the time the UPS will wait after the return of utility power before turn-on (to avoid branch circuit overload).

High Transfer Point

253 Vac 253, 257, 261, 265 Vac

Set the high transfer point higher to avoid unnecessary battery usage when the utility voltage is usually high and the connected equipment is specified to operate with input voltages this high.

Low Transfer Point 208 Vac 196, 200, 204, 208 Vac

Set the low transfer point lower when the utility voltage is usually low and the connected equipment is specified to operate with input voltages this low.

Output Voltage 230 Vac 220, 230, 240 Vac Select the output voltage.

Page 12: SU UM 990-5146 MN01 EN 08Feb19

10

4: STORAGE, MAINTENANCE, AND SHIPPING Storage Store the UPS covered in a cool, dry location, with the battery fully charged.

At -15 to +30 °C (+5 to +86 °F), charge the UPS battery every six months. At +30 to +45 °C (+86 to +113 °F), charge the UPS battery every three months.

Battery Module Maintenance The UPS battery life differs based on usage and environment. Consider replacing the battery every five years.

This UPS has an easy to replace, swappable battery. See your dealer or contact APC by Schneider Electric (see Contact Information) for information on replacement batteries.

Note: Upon battery disconnection, equipment is not protected from power outages.

Removing the Front Bezel and Battery Module

Page 13: SU UM 990-5146 MN01 EN 08Feb19

11

Replacing the Battery Module

*Contact APC by Schneider Electric Customer Support India to determine the age of the installed battery modules. Reverse the instructions for Removing the Front Bezel and Battery Module. Note: To close the battery door, ensure the plungers are in the extended position, push the door shut, and push the plungers into the locked position.

Be sure to deliver the spent battery to a recycling facility or ship it to APC in the replacement battery packing material.

Shipping 1. Shut down and disconnect any equipment attached to the UPS. 2. Shut down the UPS, and disconnect the UPS from the utility power outlet. 3. Unplug the battery connector, located on the rear panel. For further shipping instructions and to obtain appropriate packing materials, contact APC (see Contact Information).

Page 14: SU UM 990-5146 MN01 EN 08Feb19

12

5: TROUBLESHOOTING Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with complex UPS problems.

PROBLEM AND/OR POSSIBLE CAUSE

SOLUTION

UPS WILL NOT TURN ON UPS not connected to utility power supply.

Check that the power cord from the UPS to the utility power supply is securely connected at both ends.

Battery not connected properly.

Check that battery connector on the rear panel is fully snapped into position.

Very low or no utility voltage. Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, have the utility voltage checked.

UPS WILL NOT TURN OFF UPS has detected an internal fault.

Do not attempt to use the UPS. Unplug the UPS, unplug the battery connector on the rear panel, and have it serviced immediately.

UPS BEEPS OCCASIONALLY Normal operating UPS beeps when running on battery.

None. The UPS is protecting the connected equipment from occasional utility power irregularities.

UPS IS NOT PROVIDING EXPECTED BACKUP TIME The UPS battery is weak due to a recent outage or is near the end of the service life.

Charge the battery. Batteries require recharging after extended outages, and wear faster when frequently put into service or when operated at elevated temperatures. If the battery is near the end of the service life, consider replacing even if the replace battery LED is not yet illuminated.

LEFT HALF, RIGHT HALF, OR CENTER SECTION OF FRONT PANEL LEDS ARE FLASHING UPS has detected an internal fault. The UPS has shut down.

Do not attempt to use the UPS. Turn off the UPS, unplug the battery connector on the rear panel, and have it serviced immediately.

FRONT PANEL LEDS FLASH SEQUENTIALLY The UPS has been shut down remotely through software or an optional accessory card.

None. The UPS will restart automatically when utility power returns.

ALL LEDS ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET The UPS is shut down or the battery is discharged from an extended outage.

None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.

THE INPUT CIRCUIT BREAKER HAS TRIPPED The UPS is overloaded. The plunger on the circuit breaker has popped out.

Reduce the load on the UPS by unplugging equipment. Press in the plunger on the circuit breaker.

THE AVR BOOST OR AVR TRIM LEDS ARE ILLUMINATED The system is experiencing excessive periods of low or high voltage.

Seek qualified service personnel to check your facility for electrical problems. If the problem continues, contact the utility company for further assistance.

Page 15: SU UM 990-5146 MN01 EN 08Feb19

13

PROBLEM AND/OR POSSIBLE CAUSE

SOLUTION

THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SUSTAINED ALARM TONE The UPS is overloaded. The connected equipment is drawing more VA than the UPS can sustain.

The connected equipment exceeds the specified “maximum load.” The audible alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload. The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a utility voltage interruption. If a continuous overload occurs while the UPS is on battery, the unit turns off output in order to protect the UPS from possible damage.

THE REPLACE BATTERY/BATTERY DISCONNECTED LED IS ILLUMINATED This LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected.

Check that the battery connector on the rear panel is fully engaged.

Weak battery. Allow the battery to recharge for 24 hours. Then, perform a self-test. If the problem persists after recharging, replace the battery.

Battery self-test has not passed. The UPS emits short beeps for one minute and the replace battery LED illuminates. The UPS repeats the audible alarm every five hours. Perform the self-test procedure after the battery has charged for 24 hours to confirm the replace battery condition. The audible alarm stops and the LED clears if the battery passes the self-test.

UPS OPERATES ON BATTERY ALTHOUGH UTILITY VOLTAGE EXISTS The UPS input circuit breaker has tripped.

To reduce the load on the UPS, unplug equipment and press in the plunger on the circuit breaker.

The line voltage is very high, low or distorted.

Move the UPS to a different outlet on a different circuit, as inexpensive fuel powered generators may distort the voltage. Test the input voltage with the utility voltage display (see Operation). If acceptable to the connected equipment, reduce the UPS sensitivity (see User Configurable Items).

BATTERY CHARGE AND LOAD LED BAR GRAPHS FLASH SIMULTANEOUSLY The UPS has shutdown. The internal temperature of the UPS has exceeded the allowable threshold for operation.

Check that the room temperature is within the specified limits for operation.

Check that the UPS is properly installed, allowing for adequate ventilation (see Position the UPS).

Allow the UPS to cool down. Restart the UPS. If the problem continues, contact APC by Schneider Electric (see Contact Information).

Page 16: SU UM 990-5146 MN01 EN 08Feb19

14

PROBLEM AND/OR POSSIBLE CAUSE

SOLUTION

DIAGNOSTIC UTILITY VOLTAGE All five LEDs are illuminated. The line voltage is extremely high and should be checked by an electrician.

There is no LED illumination. If the UPS is plugged into a properly functioning utility power outlet, the line voltage is extremely low.

ONLINE LED

There is no illumination. The UPS is running on battery, or it must be turned on.

The LED is blinking. The UPS is running an internal self-test.

Page 17: SU UM 990-5146 MN01 EN 08Feb19

15

6: SERVICE If the unit requires service, do not return it to the dealer. Follow these steps:

1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact APC by Schneider Electric Customer Support.

Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.

Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Service Request Number.

If the unit is under warranty, the repairs are free. 3. An Authorised Service Representative will visit your location and try to resolve the issue.

Page 18: SU UM 990-5146 MN01 EN 08Feb19

16

7: WARRANTY INFORMATION

Two Year Limited Factory Warranty Schneider Electric IT Business India Private Ltd. (SEITBIPL), warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase. The SEITBIPL obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products or parts there of. Repair or replacement of a defective product or part thereof does not extend the original warranty period.

This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com or by mailing in the completed warranty registration card that is included with the documentation.

SEITBIPL shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation, testing, operation or use of the product contrary to SEITBIPL’s recommendations or specifications. Further, SEITBIPL shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, 6) theft. In no event shall SEITBIPL have any liability under this warranty for any product where the serial number has been altered, defaced, or removed, 7) normal wear resulting from frequent use.

EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.

SEITBIPL DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.

SEITBIPL EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEITBIPL’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.

THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEITBIPL’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEITBIPL WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.

IN NO EVENT SHALL SEITBIPL, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEITBIPL HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEITBIPL IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.

To obtain service under warranty you must call customer support. Customers with warranty claims issues may access the SEITBIPL worldwide customer support network through the SEITBIPL Web site: support.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Refer to the product user manual for more information on how to contact customer support.

Page 19: SU UM 990-5146 MN01 EN 08Feb19
Page 20: SU UM 990-5146 MN01 EN 08Feb19

APC by Schneider Electric Customer Support IndiaInternet http://www.apc.com/support

Toll Free 18001030011/18004194272

E-mail [email protected]

02/2019EN 990-5146C

© 2019 APC by Schneider Electric. APC, the APC logo, PowerChute and Smart-UPS are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.