study of conventional roof performance · 3.4.1 long-term displacement 42 ... while insulation...
TRANSCRIPT
Stu
dy o
f Con
ven
tion
al R
oo
f Perfo
rman
ce | P
roje
ct 6
23
0.0
0
Submitted to:
Mr. Blair Bennett
Soprema Inc.
#101 - 18651 52nd Avenue
Surrey BC V3S 8E5
Mr. Dave Lawlor
Roxul Inc.
#105 - 420 Bronte Street South
Milton, ON L9T 0H9
Submitted Sept. 14, 2014 by:
RDH Building Engineering Ltd.
224 W 8th Avenue
Vancouver BC V5Y 1N5
6230_00 2014 12 15 LR GF RPT - Conventional Roof Monitoring Study.docm
Contents
1 Introduction 1
1.1 Background 1
1.1.1 Durability 2
1.1.2 Heat Flow & Energy Consumption 2
1.2 Objectives 3
1.3 Methodology & Scope 4
1.3.1 Laboratory Testing 4
1.3.2 Field Monitoring 5
1.3.3 Energy Modeling 13
2 Laboratory Results 14
3 Field Monitoring Results 17
3.1 Overview of Boundary Conditions 17
3.2 Thermal Performance - Membrane Cap Sheet Colour 19
3.2.1 Membrane In-Service Reflectance 19
3.2.2 Membrane Temperature 24
3.2.3 Membrane Degradation 27
3.2.4 Urban Heat Island 30
3.2.5 Heat Flux 31
3.2.6 Interior Metal Deck Temperature 32
3.3 Thermal Performance - Insulation Arrangement 34
3.3.1 Heat Flux 34
3.3.2 Membrane Temperature 35
3.3.3 Interior Metal Deck Temperature 37
3.3.4 Insulation Thermal Mass 38
3.3.5 Latent Heat Transfer 39
3.4 Dimensional Stability of Insulation 41
3.4.1 Long-term Displacement 42
3.4.2 Short-term Displacement 47
4 Energy Modeling 49
5 Discussion and Conclusions 54
6 Further Research 56
7 References 57
Contents (continued)…
6230_00 2014 12 15 LR GF RPT - Conventional Roof Monitoring Study.docm
Appendices
Appendix A Additional Graphs
6230.00 RDH Building Engineering Ltd. Page 1
1 Introduction
Conventional roof assemblies make-up the majority of low-slope roof assemblies in North
America. The design of these roof assemblies typically considers a variety of factors
including product availability, economics, aesthetics, energy consumption, building type,
local industry familiarity, and compliance with building codes and green building programs;
however, the implications of these selections are often not fully understood. Factors
including membrane colour and insulation type can have significant impacts on the thermal
performance of the roof assembly and consequently on building energy consumption,
occupant comfort, membrane durability, and assembly service life.
This research study analyzes the performance of nine different roof assemblies with
different membrane colour (white, grey, and black) and insulation arrangements
(polyisocyanurate, stone wool, and hybrid) with respect to energy transfer and membrane
durability. This assessment includes consideration of insulation thermal mass, insulation
age, insulation dimensional stability, latent heat transfer, roof membrane reflectance1, roof
membrane soiling, and roof membrane temperatures.
1.1 Background
Conventional roof assemblies, also known as exposed membrane roof assemblies, are roofs
which have the roof membrane on the exterior of the roof insulation and structure.
Typically there is also an air and vapour barrier membrane installed on the underside of the
roof insulation to prevent condensation and associated damaged within the roof assembly.
Various types of insulation are used within conventional roof assemblies including rigid
polyisocyanurate (polyiso, approximately R-5 to R-6 ft²∙°F∙hr/Btu per inch), expanded
polystyrene (EPS, approximately R-4 to R-4.5 ft²∙°F∙hr/Btu per inch), or rigid stone wool
(approximately R-3.7 to R-4.3 ft²∙°F∙hr/Btu per inch). Wood fiberboard, rigid fiberglass,
extruded polystyrene (XPS), and spray polyurethane foam (SPF) insulation are also used in
conventional roofs, but are less common. It is also possible to use a combination of
insulation layers within conventional roofs, thus blending the positive attributes of each
insulation type in “hybrid” systems. One common example of a hybrid system is to use EPS
insulation to achieve the required slope, and then use polyiso insulation for the majority of
the insulation due to its high R-value per inch of thickness.
While insulation products are typically rated based on their thermal resistance at the time
of manufacture according to standardized test procedures, this testing does not consider
in-service temperatures, and potential latent heat transfer. Additionally, the impacts of
insulation thermal mass and roof membrane temperatures on net heat flow, and
subsequently on building energy consumption and membrane durability, are not typically
considered. For the purposes of this study, rated R-value refers to the R-value of the
insulation per the manufacturer’s specifications, and apparent R-value refers to the in-
service R-value of the insulation including the effects of temperature dependent
conductivities and aging.
1 For readability, this report uses the term “reflectance” to refer to the ability of the surface (i.e. membrane) to reflect radiation (i.e. solar radiation) in all directions measured as a fraction of the incident radiation; however, this is more accurately referred to as “albedo” and “reflectance” technically is only for a specific incident angle.
Page 2 RDH Building Engineering Ltd. 6230.00
Different roof membrane colours are also used in conventional roof assemblies. Reflective
roof membranes are typically selected to provide increased reflection of solar radiation
thereby decreasing roof membrane temperature and urban heat island effect, and often this
selection is part of meeting green building program requirements. However, much of the
work with regards to reflective roofs does not consider the effects of soiling as roof
membranes age.
This study addresses durability and thermal performance of conventional roof assemblies
with respect to roof membrane colour and insulation arrangement.
1.1.1 Durability
Conventional roof assemblies (i.e. exposed roof assemblies) expose the waterproof
membrane to exterior conditions including exterior temperature, radiation from the sun
including ultraviolet (UV), precipitation, wind, atmospheric pollution and dirt. All of these
exposures can degrade the roof membrane, and its ability to resist this degradation
determines its durability and service life.
Temperature is of particular importance to roof membrane durability. Increased
temperature can “accelerate deleterious chemical reactions, cause loss of volatile
constituents, and soften some polymers” (pg. 424, Berdahl et al., 2008). Additionally,
thermal expansion and contraction due to changes in temperature can stress roof
membranes and can affect the durability of the membrane. (Berdahl et al., 2008) Typically
faster rates of dimensional change and larger magnitude changes will more rapidly degrade
a roof membrane and shorten its service life. (Dell, 1990)
It is well known that exposed roof membranes can reach temperatures significantly higher
than ambient air temperatures due to absorption of solar radiation. Consequently, the
absorptivity, and reflectivity of the roof can significantly impact of the roof temperatures
and thus roof membrane durability. A more reflective roof may cause a roof membrane to
heat up less quickly, and reduce both average and maximum membrane temperatures
which would likely extend the service life of the roof membrane.
The rate of change and magnitude of exposed roof membrane temperatures may also be
impacted by the thermal mass of the membrane substrate, which in conventional roofs is
provided by the insulation. Insulation with a higher thermal mass per square foot of roof
area may provide a buffer to changes in temperature. This buffer effect could potentially
change the net heat flow through the assembly and could also potentially act to moderate
roof membrane temperatures and extend its service life.
The dimensional stability of the roof membrane substrate (i.e. the insulation) can also
impact roof membrane durability. Typically foam insulations are less dimensionally stable
than mineral fibre insulations and movement of the insulation can potentially cause
creasing of the roof membrane and accelerate degradation due to increased strain induced
in the roof membrane.
1.1.2 Heat Flow & Energy Consumption
Heat flow through conventional assemblies, and consequently building energy
consumption, is also impacted by the combination of the roof membrane colour and the
insulation arrangement. Roof membranes with a higher Solar Reflective Index (SRI) are
commonly used in the Southern United States where regulated by energy standards such as
6230.00 RDH Building Engineering Ltd. Page 3
ASHRAE 90.1, and are also used in other areas as part of green building programs such as
Leadership in Energy and Environmental Design (LEED) which provides credits for use of a
high SRI roof. In northern climates the benefit of using white membrane roofs to achieve
cooling savings is often small and can be offset by higher wintertime heating loads. (DOE
Cool Roof Calculator, 2013; Roof Savings Calculator, 2013; Smith, 2001)
The insulation arrangement in a roof can also impact the heat flow through the assembly
and consequently the building energy consumption. Even for the same rated R-value,
different insulation types have different apparent thermal resistances due to operating
temperatures that are different than test conditions, and latent heat transfer. Additionally,
more thermally massive insulation types (such as stone wool) can buffer changes in a
temperature and consequently affect heat flow through roof assemblies.
In particular, it is generally recognized that the thermal resistance of polyiso insulation (and
some other foam insulations) decreases as it ages, and since circa 2001 most
manufacturers have reported the long-term thermal resistance (LTTR) of polyiso insulation.
(Roe, 2007; Christian et al., 1995) The LTTR is currently determined according to three
standards, the most recent versions of which are CAN/ULC-S770-09 Standard Test Method
for Determination of Long-term Thermal Resistance of Closed-Cell Thermal Insulating
Foams, or ASTM C1303-12 Standard Test Method for Predicting Long-Term Thermal
Resistance of Closed-Cell Foam Insulation. (Graham, 2013; Graham, 2014)
1.2 Objectives
This research study aims to evaluate the impact of roof membrane colour and insulation
type on the performance of conventional roof assemblies. In particular this study aims to
develop understanding in the following areas:
The difference in maximum and average roof membrane temperatures
The difference between rated and apparent in-service R-values for two common roof
insulations (polyiso and stone wool) due to the combination of in-service insulation
temperatures and aging effects
How membrane colour, insulation apparent R-value, and insulation thermal mass affect
net heat flow through different conventional roof assemblies
The potential interior surface temperature and thermal comfort benefits related to
membrane solar reflectance and roof insulation arrangement
The impact of aging and soiling on the reflectance of white SBS roof membranes
The in-service dimensional stability of two common roof insulations (polyiso and stone
wool)
The impact of insulation moisture content on latent heat transfer through conventional
roof assemblies
The impact of roof membrane colour and arrangement on whole building heating and
cooling energy consumption in various North American climates
Page 4 RDH Building Engineering Ltd. 6230.00
1.3 Methodology & Scope
The experimental phase of this project includes three main components: laboratory testing
of insulation samples, field monitoring of roof assembly performance, and energy modeling
of building energy consumption implications.
1.3.1 Laboratory Testing
To determine the thermal resistance (R-value) of the insulation products being used in this
study, a number of polyiso and stone wool insulation samples were tested in general
accordance with ASTM C518 Standard Test Method for Steady-State Thermal Transmission
Properties by Means of Heat Flow Meter Apparatus (ASTM, 2010). This test method applies
a temperature difference across an insulation sample and measures the heat flux through
the sample under these conditions. A picture of the testing apparatus is shown in Figure
1.1.
Figure 1.1 Material conductivity testing machine used to measure insulation conductivity (Photo courtesy of Building Science Consulting Inc.)
Typically this test is performed at a mean temperature of 24°C (75°F) with a temperature
difference of approximately 28°C (50°F) across the insulation sample; however, this study
is also interested in the impact of temperature on the apparent R-value of the insulation
product, so the testing was also conducted at mean temperatures of -4°C, 4.5°C, 24°C, and
43°C (25°F, 40°F, 75°F, 110°F) with the same 28°C (50°F) temperature difference.
To investigate the impact of aging on the apparent R-value of polyiso insulation, three 4-
year-old samples were tested and six un-aged (approximately 2-month-old) samples were
tested. The 4-year-old samples were stored in laboratory conditions during the aging
period, and the six un-aged samples were removed from the same batches of insulation
installed in the test roofs for this research study.
Three stone wool insulation samples were also tested. These samples were removed from
the same batches of insulation installed in the test roofs for this research study.
6230.00 RDH Building Engineering Ltd. Page 5
1.3.2 Field Monitoring
A large-scale field monitoring program was implemented to evaluate the in-service
performance of conventional roof assemblies with three different colour membranes and
three different insulation arrangements for a total of 9 different roof assemblies. The three
roof membranes are all 2-ply SBS roof membranes with the same base sheet and a black,
grey, or white (LEED compliant SRI) granulated cap sheet. The three cap sheet colours are
shown in Figure 1.2, and the solar properties of the sheets as specified by the manufacturer
are provided in Table 1.1.
Figure 1.2 Samples of the three different SBS granulated cap sheet colour used in the field monitoring portion of this study
TABLE 1.1 ROOF MEMBRANE CAP SHEET PROPERTIES SPECIFIED BY MANUFACTURER
Cap Sheet Colour Solar Reflective
Index (SRI) Solar Reflectance
Thermal Emittance (Infrared)
White 70 0.582 0.91
Grey 9 0.138 0.85
Black -4 0.04 0.85
The three different insulation strategies are: all polyiso, all stone wool, and a hybrid roof
assembly with polyiso insulation underneath stone wool insulation. The hybrid system is
intended to optimize the apparent R-value of the polyiso insulation by maintaining it closer
to its optimal performance temperature, and also takes advantage of the dimensional
stability of the stone wool insulation. These three insulation assemblies are shown in Figure
1.3, Figure 1.4, and Figure 1.5 respectively.
Page 6 RDH Building Engineering Ltd. 6230.00
Figure 1.3 Polyiso Roof Assembly – Two layers of polyiso insulation
Figure 1.4 Hybrid Roof Assembly – Base layer of polyiso insulation and top layer of stone wool insulation
Figure 1.5 Stone Wool Roof Assembly – Two layers of stone wool insulation
The thickness of the insulation layers in the roof assemblies were varied to achieve similar
rated R-values of approximately R-21.5 hr∙ft²∙°F/Btu based on values of R-6 hr∙ft²∙°F/Btu per
inch for the polyiso and R-3.8 hr∙ft²∙°F/Btu per inch for the stone wool. The layer thicknesses
6230.00 RDH Building Engineering Ltd. Page 7
and assembly rated R-values are provided below. The polyiso R-value (R-6 hr∙ft²∙°F/Btu per
inch) used to calculate the rated thermal performance of these assemblies was standard
practice at the start of the project; however, recently the methods of determination and
reporting of LTTR have been updated and typically lower values (R-5.6 hr∙ft²∙°F/Btu per inch)
are now reported. (Graham, 2014)
The rated R-values of the insulation installed in these assemblies are:
Polyiso = R-21.0 hr∙ft²∙°F/Btu
Lower Layer: 2” polyiso (R-12.0 hr∙ft²∙°F/Btu)
Upper Layer: 1 ½” polyiso (R-9.0 hr∙ft²∙°F/Btu)
Hybrid = R-21.5 hr∙ft²∙°F/Btu
Lower Layer: 2” polyiso (R-12.0 hr∙ft²∙°F/Btu)
Upper Layer: 2 ½” stone wool (R-9.5 hr∙ft²∙°F/Btu)
Stone Wool = R-21.9 hr∙ft²∙°F/Btu
Lower Layer: 2 ½” stone wool (R-9.5 hr∙ft²∙°F/Btu)
Upper Layer: 3 ¼” stone wool (R-12.4 hr∙ft²∙°F/Btu)
The nine roof assemblies created by the three different membrane colours and three
different insulation arrangements were installed on a large roof with relatively few
obstructions located on an industrial building in Chilliwack, within the Lower Mainland of
British Columbia. Each of the roof assemblies covers an area of approximately 150 m².
Figure 1.6 shows the arrangement of the roof assemblies on the building, and Figure 1.7
shows an aerial view of the test roofs.
Figure 1.6 Layout of test roofs on the test building
Polyiso
Hybrid
Stone wool
G-ISO
W-ISO
B-ISO
G-ISO-SW
W-ISO-SW
B-ISO-SW
G-SW
W-SW
B-SW
Page 8 RDH Building Engineering Ltd. 6230.00
Figure 1.7 Layout of test roofs on the test building
Figure 1.8 to Figure 1.13 show images of the test roof assemblies being constructed
including installation of the air and vapour barrier, the insulation layers, and the 2-ply SBS
roof membranes. The insulation layers are adhered to the air and vapour barrier and to
each other with a two component polyurethane foam adhesive to limit the movement of the
insulation withen the assemblies. In the case of the roof assemblies with only polyiso
insulation, an asphaltic protection board is also installed to facilitate installation of the roof
membrane, and this projection board is adhered to the upper polyiso layer. In the stone
wool cases, the top surface of the stone wool is impregnated with asphalt and the
membrane is applied directly to this impregnated surface.
Figure 1.8 Installation of the self-adhered air and vapour barrier membrane on the metal roof deck
Figure 1.9 First layer of the polyiso roof being installed on the self-adhered air and vapour barrier membrane and adhered with pulyurethane foam adhesive
6230.00 RDH Building Engineering Ltd. Page 9
Figure 1.10 Stone wool insulation being installed in the stone wool only roof assembly
Figure 1.11 Stone wool insulation being adhered to bottom layer of polyiso insulation using polyurethan foam in the hybrid roof assembly
Figure 1.12 Bottom layer of polyiso insulation, upper layer of stone wool insulation, and base sheet of the 2-ply SBS membrane during construction
Figure 1.13 Completed roofs showing black, white, and grey SBS cap sheet colours
Various sensors were installed within each of the different roof assemblies to measure
indicators of their performance including material temperatures, relative humidity, heat
flux, and dimensional stability of the insulation. The monitoring equipment and sensors
were supplied and installed by SMT Research Ltd. (SMT) under direction of RDH Building
Engineering Ltd. (RDH) and specifications are available through the SMT website
(http://www.smtresearch.ca/). A schematic roof cross-section is provided in Figure 1.14
which illustrates the typical layout of the sensors in each roof assembly and the naming
convention for the sensors installed in the roof assemblies is provided in Table 1.2. When
sensor names do not follow this convention, appropriate sensor name descriptors were
used.
The heat flux sensors were installed between the insulation layers such that they would be
protected from potential wetting (i.e. not at the bottom of the assembly) and from damage
during the torch application of the roof membrane (i.e. not at the bottom of the assembly).
Due to the difference in the thickness of the insulation layers in the different insulation
arrangements, the heat flux sensors were installed at a different depth for the different roof
assemblies. The heat flux sensors were installed under approximately R-9 hr∙°F∙ft²/Btu, R-
Page 10 RDH Building Engineering Ltd. 6230.00
9.5 hr∙°F∙ft²/Btu, and R-12.4 hr∙°F∙ft²/Btu of rated R-value for the polyiso, hybrid, and stone
wool roof assemblies respectively. These differences in R-values above the heat flux
sensors may potentially affect the non-steady state heat flux measurements due to the
buffering effect of the insulation; however, under relatively steady state conditions, the
relative depth of the heat flux sensors would have no impact on the measurements.
Figure 1.14 Schematic roof cross-section showing typical arrangement of sensors installed in each roof assembly
TABLE 1.2 SENSOR NAMING CONVENTION
Membrane Colour
- Insulation Arrangement - Sensor Type - Optional
Descriptor
B Black ISO Polyisocyanurate T Temperature Additional descriptors of sensor positioning
G Grey ISO-SW Hybrid (stone wool on top of polyiso)
RH Relative Humidity
W White SW Stone Wool HF Heat Flux
Figure 1.15 to Figure 1.19 show how these sensors were installed in to the roof assemblies
during construction.
6230.00 RDH Building Engineering Ltd. Page 11
Figure 1.15 Monitoring unit located under the metal deck of the roof attached to sensor to measure ambient interior conditions and metal deck temperature
Figure 1.16 Temperature and relative humidity sensor installed on top of the air and vapour barrier prior to installation of the insulation boards
Figure 1.17 Series of three images showing the displacement sensor installed within the stone wool insulation (left), a contact plate being installed on the edge of the insulation to ensure solid contact of the displacement sensor (middle), and a deisplacement sensor and contact plate installed in the insulation such that when the insulation sheets are butted against each other the displacement sensor will touch the contact plate (right)
Page 12 RDH Building Engineering Ltd. 6230.00
Figure 1.18 Heat flux sensors are installed between the insulation layers to measure heat flow through the assembly
Figure 1.19 Thermistors installed at the top of the insulation (will be just under the roof membrane once membrane installed) to measure roof membrane temperature
Reflected solar radiation from the roof cap sheets was measured using solar radiation
sensors (pyranometers) mounted approximately 1 m above the roof surface and pointed
downwards as shown in Figure 1.20. Sensors to measure reflected solar radiation were
installed at a high point and low point on the white roof membrane (likely to become less
and more soiled respectively), and also at one location on the roof with a grey cap sheet,
for comparison. The measurements from these sensors can be compared with the
measurements from the solar radiation sensor on the weather station to provide an
indication of in-service reflectance of the roof membranes.
Figure 1.20 Three solar radiation sensors were installed to measure reflected solar radiation from the roof membranes
The exterior conditions were monitored using a weather station located on the building
adjacent to the test roof as shown in Figure 1.21. The weather station includes sensors to
measure ambient temperature, relative humidity, precipitation, wind speed, wind direction,
and total horizontal solar radiation. A camera was also installed to automatically capture
photos of the roof surfaces every hour to allow for study of soiling of the roof membranes.
6230.00 RDH Building Engineering Ltd. Page 13
Figure 1.21 Weather station installed adjacent to test roofs
In some cases the data collection system lost data from the weather station. In these cases
data from the Chilliwack Airport was used to supplement the available monitoring data.
(Environment Canada, 2013)
1.3.3 Energy Modeling
Building energy modeling was performed to assess how the thermal performance of the
roof assemblies, as determined in the laboratory and field testing phases of the study,
affects whole building energy consumption. Additionally, the energy modeling investigates
the optimum roof membrane colour (solar absorptivity) and insulation strategy for
conventional roof assemblies in various North American climates. Simulations were
conducted to compare the same white, grey, and black roof membranes, and the same three
insulation arrangements: polyiso, stone wool, and hybrid.
The building energy modeling was conducted using the U.S. Department of Energy (DOE)
Building Energy Codes Program commercial building prototype model for a stand-alone
retail building designed to meet ASHRAE 90.1-2010 requirements. The building
information files are available online and use the hourly energy modeling program
EnergyPlus. (DOE, 2012) Models were run for one representative city in each of the eight
ASHRAE North American climate zones. A specific goal of the energy modeling was to
investigate the impact of temperature dependant insulation R-values on whole building
energy consumption. This effect is typically not modeled in most whole building simulation
programs, but can be modeled in EnergyPlus.
Page 14 RDH Building Engineering Ltd. 6230.00
2 Laboratory Results
The results of the thermal conductivity laboratory testing of the polyiso (fiberglass facer)
and stone wool insulation samples are provided graphically in Figure 2.1 for a range of
mean temperatures. The maximum, minimum, and average performances are shown for
the polyiso samples to provide an indication of the range of performance in the tested
samples. The stone wool did not show the same variation so only the average is provided.
Figure 2.1 Insulation R-value versus mean temperature for polyiso, aged polyiso, and stone wool insulation
Figure 2.1 illustrates that the R-value of polyiso insulation varies more with temperature
than does the R-value of stone wool insulation. Additionally, aged (4-year-old) polyiso has
a significantly reduced R-value as compared to new polyiso at all temperatures, with the
largest difference in R-value being measured at lower mean temperatures. The aging effects
measured in the polyiso insulation are likely as a result of off-gassing of the insulation
product post-manufacturing. Overall, the results of this testing agree well with published
data for polyiso and stone wool from the National Roofing Contractors Association (Graham,
2010; BSC, 2013) Additional testing would be required to determine the thermal
resistances of these insulation types at higher and lower temperatures.
These laboratory measurements can be applied to the insulation assemblies that were
constructed as part of the field monitoring component of this study. Despite having very
similar rated R-values, the insulation in these roof assemblies likely performs significantly
differently due to temperature and aging effects. The graph shown in Figure 2.2
demonstrates how temperature and aging effects would theoretically impact the apparent
R-value of the insulation in each of the assemblies. The mean insulation temperatures for
each of these cases were calculated using an indoor temperature of 21°C.
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
‐10 0 10 20 30 40 50
R‐value per inch
Mean Temperature of Insulation
Polyiso ‐ Maximum
Polyiso ‐ Average
Polyiso ‐ Minimum
Polyiso ‐ Aged (4 years)
Stone Wool ‐ Average
6230.00 RDH Building Engineering Ltd. Page 15
Figure 2.2 Apparent R-values of roof assemblies used in field monitoring calculated based on insulation conductivity testing.
This figure demonstrates the sensitivity of the apparent R-value of the polyiso roof
assemblies to hot and cold temperatures. The R-value (thermal resistance) of the polyiso
roof assemblies decrease significantly at outdoor temperatures either hotter or colder than
approximately 25°C. The lowest R-value within the tested range was determined at a high
exterior surface temperature of approximately -10°C. At this temperature the R-value was
determined to be approximately 4.8 hr∙ft²∙°F/Btu less than the R-value of this assembly at
25°C, which is approximately at 22% decrease. Temperature of the roof membrane was
measured as part of the field monitoring component of this study and is discussed further
in Section 3.
The polyiso roof also shows significantly reduced apparent R-values due to aging effects.
The 4-year-old polyiso insulation ranges from approximately 9 to 18% less than the un-aged
insulation.
The stone wool insulation assembly also demonstrates temperature dependence; however
the effect is significantly less pronounced than that of the polyiso. Additionally, the R-value
of this assembly does not decrease at both warmer and colder mean temperatures, and
instead actually increases as the mean temperature decreases. The maximum decrease in
the apparent R-value of the stone wool assembly is also at the highest surface temperature
for which conductivities were measured, 60°C. The R-value of the assembly at this
temperature is approximately R-1.0 hr∙ft²∙°F/Btu (5%) lower than the R-value at 25°C (R-21.2
hr∙ft²∙°F/Btu). The R-value at a mean temperature of -10°C is approximately R-1.0
hr∙ft²∙°F/Btu higher than the R-value at 25°C.
The hybrid roof assembly provides a combination of the effects noted for the polyiso and
stone wool roof assemblies. The stone wool insulation buffers the temperatures
experienced by the underlying polyiso consequently allowing the polyiso to operate closer
to its optimum temperature range. This assembly has very similar temperature response
to the stone wool assembly except for at temperatures below 10°C where slightly lower R-
values were determined. The decrease in R-value of the roof assembly due to polyiso aging
effects is also somewhat mitigated by the hybrid roof assembly. While the polyiso insulation
still decreases in R-value, in this assembly it only provides approximately 55% of the rated
R-value, and thus the decrease in apparent R-value is significantly less in this hybrid
assembly that in the polyiso assembly.
14
15
16
17
18
19
20
21
22
23
24
‐10 0 10 20 30 40 50 60
Effective Assembly R‐value
Outdoor Membrane Surface Temperature (Indoor, 21oC)
Stone Wool (Initial or Aged)
Hybrid (Initial Average)
Hybrid (Aged)
Polyiso (Initial Average)
Polyiso (Aged)
Page 16 RDH Building Engineering Ltd. 6230.00
Overall, the R-value of the polyiso was determined to be significantly more sensitive to aging
and temperature affects than is the stone wool insulation. As a result, roofs using
exclusively polyiso insulation may provide significantly less thermal resistance in-service at
temperature extremes (hot or cold) than is indicated by its rated R-value.
6230.00 RDH Building Engineering Ltd. Page 17
3 Field Monitoring Results
This study assesses the effect of two different parameters affecting conventional roof
assembly performance: the cap sheet colour (reflectance), and the insulation arrangements.
These factors are addressed separately in the subsequent sections so that their affects can
be determined independently. To facilitate this independent analysis this results section
has been subdivided into four main sections with subsections:
Overview of Boundary Conditions
Thermal Performance – Membrane Cap Sheet Colour
Membrane In-Service Reflectance
Membrane Temperature
Heat Flux
Interior Metal Deck Temperature
Thermal Performance – Insulation Arrangement
Heat Flux
Membrane Temperature
Interior Metal Deck Temperature
Dimensional Stability of Insulation
Long-term Displacement
Short-term Displacement
In some cases data is not available due to intermittent malfunctioning of the installed
monitoring equipment, but these instances do not significantly affect the findings and are
discussed where appropriate. Annual data in this report is typically presented from May
2013 to April 2014 as this is when the data collection was most consistent. Graphs provided
in this section of the report are supplemented with additional graphs provided in Appendix
A.
3.1 Overview of Boundary Conditions
The test roof assemblies were located in Chilliwack, British Columbia which is located within
the Lower Mainland region surrounding Vancouver. The roofs were monitored from
September 2012 to June 2014, and data is typically presented from May 2013 to April 2014
because data collection was most consistent during this period.
Graphs providing the average exterior and interior conditions for each month are provided
the following figures. The average exterior monthly temperature, exterior dew point
temperature, and interior temperature are provided in Figure 3.1. Monthly heating degree
days (HDD), and cooling degree days (CDD) are provided in Figure 3.2. The average monthly
relative humidity and total daily solar radiation are provide in Figure 3.3 and Figure 3.4
respectively. Figure 3.5 provides the distribution of wind direction and speed during this
period.
Page 18 RDH Building Engineering Ltd. 6230.00
Figure 3.1 Graph of monthly average temperature and dew point temperature during the main monitoring period from May 2013 to April 2014
Figure 3.2 Graph of monthly average HDD (18°C, 64°F) and CDD (10°C, 50°F) during the main monitoring period from May 2013 to April 2014
Figure 3.3 Graph of monthly average relative humidity during the main monitoring period from May 2013 to April 2014
14
23
32
41
50
59
68
77
‐10
‐5
0
5
10
15
20
25
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Temperature [°F]
Temperature [°C]
Exterior Temperature Exterior Dew Point Temperature Interior Temperature
0
180
360
540
720
900
1080
0
100
200
300
400
500
600
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Degree Days [°F∙days]
Degree Days [°C∙days]
HDD (18°C, 64°F) CDD (10°C, 50°F)
0
10
20
30
40
50
60
70
80
90
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Relative
Humidity [%
]
Relative Humidity
6230.00 RDH Building Engineering Ltd. Page 19
Figure 3.4 Graph of monthly average total daily solar radiation during the main monitoring period from May 2013 to April 2014
Figure 3.5 Wind rose indicating the average wind speed and frequency of wind for each direction during the main monitoring period from May 2013 to April 2014
3.2 Thermal Performance - Membrane Cap Sheet Colour
The field monitoring component of this study evaluated the performance of white (W), grey
(G), and black (B) membrane cap sheets. The colour of these membranes primarily affects
their solar reflectance. The subsequent sections assess the in-service solar reflectance of
the membranes and the impact on membrane temperatures, interior metal deck
temperatures, and heat flux through the assemblies. Supplementary graphs are provided
in Appendix A.
3.2.1 Membrane In-Service Reflectance
The different membrane cap sheet colours have different rated solar reflectance values as
previously provided in Table 1.1. As part of this study, the total horizontal solar radiation
from the sun was measured as well as the reflected solar radiation from the white (at a high
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May
Total D
aily Horizontal Solar Rad
iation
[Whr/m²]
Total Daily Solar Radiation
0
1
2
3
4N
NNE
NE
ENE
E
ESE
SE
SSE
S
SSW
SW
WSW
W
WNW
NW
NNW
Average Wind Speed [m/s]
Frequency [%/4]Average Wind Speed = 1.4 m/s
Page 20 RDH Building Engineering Ltd. 6230.00
and a low point on the roof surface) and grey roofs to determine their in-service solar
reflectance. This testing was not performed in accordance with ASTM reflectance
measurements and instead provides a relative measurement intended to facilitate
comparison of the roof membranes. Figure 3.6 shows these measurements for a period
from June 2nd to 8th, 2013 to demonstrate the difference in in-service roof reflectance.
Note that the results for the two white roofs are nearly identical and so overlap almost
exactly on the graph.
Figure 3.6 Graph of total solar radiation and reflected radiation from the roof surface from June 2 to 8, 2013
The preceding figure indicates that for the given period from June 2nd to June 8th, 2013,
approximately 51% of the incident solar radiation is reflected by the white roof (both
locations), and 27% by the grey roof. The white roof and the grey roof have manufacturer
rated solar reflectance values of 58% and 14% respectively, and the difference between these
values and the field measured values is expected due to the difference in measuring
techniques. The technique used in this study is intended to provide a relative measure of
reflectance to allow for comparison of the roofs in the study, but is not intended to provide
a measurement of the actual reflectance of the membranes as would be consistent with the
manufacturer rating. While the in-service reflectance of the white roof was similar to this
rated value, the grey roof reflected significantly more solar radiation in-service. This is
potentially because the reflected solar radiation sensor on the grey roof is located relatively
close to the white roof and may have been measuring some reflected radiation from the
white roof or other adjacent surfaces.
Typically the measured reflectance values were lowest in the summer and highest in the
winter as shown on a monthly average basis in Figure 3.7. During the winter months there
is less direct solar radiation due to cloud cover and consequently diffuse solar radiation is
a larger proportion of the total solar radiation incident on the roof surface. This diffuse
radiation also has a slightly different spectrum than does direct solar radiation. The
reflectance of the roof membrane was measured for the solar spectrum, so the roof
membranes likely have a different reflectance with respect to this diffuse radiation which
may be the cause of the observed seasonal variation in the measured reflectance. It is also
possible that the diffuse radiation is more likely to irradiate the roof and sensor equally and
consequently that a larger proportion of the solar radiation measured by the sensor is not
reflected from the roof which leads to a higher measured reflectance that is not indicative
of the actual reflectance of the roof. The increased measured reflectance in the winter could
0
200
400
600
800
1000
1200
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Solar Rad
iation [W/m
²]
Solar Radiation
Reflected Solar ‐ White (High)
Reflected Solar ‐ White (Low)
Reflected Solar ‐ Grey
Average Incident SolarRadiation Reflected
White (High) = 51%
White (Low) = 51%
Grey = 27%
6230.00 RDH Building Engineering Ltd. Page 21
also be caused by increased moisture on the surface of the roof (water and ice) during the
winter periods due to more precipitation and colder temperatures.
The annual average reflectance shows good correlation between the measured reflectance
of the white membrane and the values provided by the manufacturer. The measurement of
the reflectance of the white membrane at a low point is slightly lower than that of the
membrane at a high point which is likely due to the low point being more likely to collect
dirt and becoming soiled more quickly than the high point. The grey membrane reflectance
is significantly higher than the rated value and is likely due to placement of the sensor near
to the white roofs as discussed earlier with respect to Figure 3.6.
Figure 3.7 Chart of average monthly measured cap sheet membrane reflectances
As noticeable in the reflectance measurements of the two white membrane locations, the
in-service solar reflectance of the roof membrane will be affected by soiling which can
potentially decrease the reflectance of the roof, particularly of the white roof. The effects
of soiling on roof membrane reflectance have previously been studied by Koshiishi et al
(2014) who found a significant reduction in the reflectance of reflective (i.e. white) roof
membranes over the first year of exposure, and limited reductions thereafter. To
qualitatively assess roof membrane soiling for the test roofs in this study, a camera was
installed to periodically take pictures of each of the roofs. Figure 3.8 provides images of
the roof when it was newly installed. Figure 3.9 and Figure 3.10 provide images the roof
after approximately 7 months of service (March 15, 2013) and after approximately 13
months of service (October 21, 2013).
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr Annual Rated
Reflectan
ce
White (high) White (low) Grey
*
*Rated reflectance was measured using a different method than was used in the field study.
Page 22 RDH Building Engineering Ltd. 6230.00
Figure 3.8 Set of three images documenting the condition of the roof membranes shortly after insatllation on August 21, 2012
Figure 3.9 Set of three images documenting the condition of the roof membranes on March 15, 2013 approximately 7 months after installation.
Figure 3.10 Set of three images documenting the condition of the roof membranes on October 21, 2013 approximately 14 months after installation.
These images illustrate that there is significant soiling of the roof membrane in close
proximity to the roof drains, but that in general the roof membranes have not become
significantly visually soiled over the course of approximately a year of service.
Consequently, the reflectance of these roofs has not likely changed significantly since they
were installed. Figure 3.11 provides a chart of average seasonal reflectance of the three
roofs to facilitate comparison of reflectance in Winter 2013 to reflectance in Winter 2014.
6230.00 RDH Building Engineering Ltd. Page 23
Figure 3.11 Chart of seasonal average and annual average (Spring 2013 to Winter 2014) reflectance of roof membranes
This comparison indicates that soiling of the roof membranes has had a small effect on the
white membrane located at a low point on the roof. The limited soiling that is observed
on these test roof may in part be due to the relatively unpolluted atmospheric conditions in
the vicinity of the test building. The test roofs are located in rural semi-industrial area as
shown in Figure 3.12, and airborne particulates are typically found in relatively low
quantities in rural areas as compared to urban centres.
Figure 3.12 Aerial image showing terrain surround the test roof location
There is also limited vegetation in close proximity to the test roofs so leaves and other
debris from vegetation does not typically fall on the test roofs and the absence of this debris
source could also be contributing to the lack of soiling which was observed.
Despite the limited soiling observed to this point, future years of service and associated
continued soiling may gradually degrade the reflectance of the roof membranes, and in
particular of the white roof membrane. Continued monitoring of these membranes would
allow for the evaluation of long-term soiling effects.
After soiling, it may be possible to restore these membranes to their initial reflectance by
cleaning the membrane or recoating. Both Akbari et al (2005) and Koshiishi et al (2014)
found that for most roofs cleaning of the roof membrane using water and wiping
(simulating annual rain) was sufficient to restore the roof membrane reflectance to near its
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Winter2013
Spring2013
Summer2013
Fall2013
Winter2014
Annual
Reflectan
ce
White (high) White (low) Grey
Page 24 RDH Building Engineering Ltd. 6230.00
initial value, but that for membranes with “deep irregularities” (Koshiishi et al, 2014) (such
as those created by granules on SBS cap sheets) or algae growth, additional cleaning
measures are required. Further monitoring and research would be required to evaluate the
long-term impact of soiling of these roof membranes, and the effectiveness of roof cleaning
methods.
3.2.2 Membrane Temperature
It is generally understood within the roof industry that roof membrane temperatures are
largely dependent on absorption of solar radiation; consequently, roof temperatures are
often significantly warmer than ambient air temperatures and largely dependent on roof
membrane reflectance (i.e. colour). The increased solar reflectance of the white membrane
relative to the grey membrane and of the grey membrane relative to black membrane means
that less solar energy is absorbed by these membranes. This difference in the amount of
absorbed radiation causes significant differences in the roof membrane temperatures.
Figure 3.13 to Figure 3.15 provide graphs of the roof membrane temperatures from June
2nd to June 8th, 2013 grouped by insulation type to allow for evaluation of the effect of
membrane reflectance (i.e. colour) on membrane temperature. The effect of membrane
reflectance is most noticeable during sunny summer periods when, in the climate of Lower
Mainland British Columbia where the study was conducted, there is typically more direct
solar radiation. For this reason, the figures provided in this section are primarily during
sunny summer periods, though increased roof temperatures compared to the ambient
exterior temperature are noticeable throughout the year.
Figure 3.13 Graph of roof membrane cap sheet temperature for the three polyiso roof assemblies from June 2 to 8, 2013
32
50
68
86
104
122
140
158
176
0
10
20
30
40
50
60
70
80
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Temperature [°C]
p p
W‐ISO T‐CAP
G‐ISO T‐CAP
B‐ISO T‐CAP
Ambient Exterior
Temperatu
re [°F]
6230.00 RDH Building Engineering Ltd. Page 25
Figure 3.14 Graph of roof membrane cap sheet temperature for the three hybrid roof assemblies from June 2 to 8, 2013
Figure 3.15 Graph of roof membrane cap sheet temperature for the three stone wool roof assemblies from June 2 to 8, 2013
These figures show that maximum roof temperatures are significantly reduced for the more
reflective white roofs than for the other roofs and the temperatures also change more slowly
for the white roofs than for the grey and black roofs. The grey roof also experienced
reduced maximum temperatures and rates of temperature change relative to the black
roofs; however, as one would expect, this effect is not as significant as for the white roofs.
The impact of roof membrane colour on roof membrane temperatures is most significant
during sunny and warm periods when roof membrane temperatures reach their annual
maximums; however, it is noticeable year-round. To illustrate the annual variation in the
impact of membrane colour on peak roof membrane temperatures, the monthly average
daily maximum temperatures and the maximum membrane temperature for each month
are graphed in Figure 3.16. The decreases in maximum membrane temperature of the
white and grey roofs relative to the black roofs are shown in Figure 3.17.
32
50
68
86
104
122
140
158
176
0
10
20
30
40
50
60
70
80
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Temperature [°C]
W‐ISO‐SW T‐CAP
G‐ISO‐SW T‐CAP
B‐ISO‐SW T‐CAP
Ambient Exterior
Temperatu
re [°F]
32
50
68
86
104
122
140
158
176
0
10
20
30
40
50
60
70
80
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Temperature [°C]
W‐SW T‐CAP
G‐SW T‐CAP
B‐SW T‐CAP
Ambient Exterior
Temperatu
re [°F]
Page 26 RDH Building Engineering Ltd. 6230.00
Figure 3.16 Chart of monthly average of the maximum daily membrane temperatures an maximum membrane temperature for each month for the white, grey, and black roofs, averaged for the different insulation arrangements
Figure 3.17 Chart of monthly average reduction in maximum daily membrane temperatures for the roofs with white and grey membrane cap sheets as compared to the roofs with black membrane cap sheets
The effect of membrane colour on the maximum roof membrane temperature can also be
assessed for the different insulation arrangements. Figure 3.18 shows the monthly average
reduction in maximum membrane temperature for the white roofs compared to the black
roof for all of the roofs with white membrane cap sheets. This figure indicates that typically
the reduction in daily maximum membrane temperature created by the use of a more
reflective membrane is largest for the polyiso roof assemblies, though the cause of this
effect is unknown.
32
50
68
86
104
122
140
158
176
194
0
10
20
30
40
50
60
70
80
90
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Temperature [°F]
Temperature [°C]
White Grey Black White ‐ Maximum Grey ‐ Maximum Black ‐ Maximum
* *
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
0
9
18
27
36
45
0
5
10
15
20
25
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr Annual
Decrease in
Temperature [°F]
Decrease in
Temperature [°C]
White Grey
* *
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
6230.00 RDH Building Engineering Ltd. Page 27
Figure 3.18 Chart of monthly average reduction in maximum daily membrane temperatures for the roofs with white membrane cap sheets as compared to the roofs with the same insulation arrangements and black membrane cap sheets
While more reflective roof membranes were found to reduce the maximum membrane
temperature and consequently to likely extend the service life of the roof membrane, there
was no noticeable effect of roof membrane colour on the minimum night-time
temperatures. This finding is likely because while night sky radiation can frequently cause
roofs to cool below ambient outdoor temperatures, this radiation is primarily in the infrared
spectrum (not solar spectrum) and consequently the infrared (i.e. thermal) absorption and
emittance of the membranes are of most importance. As shown previously in Table 1.1,
the thermal emittances (and consequently absorptance) of the three tested membranes are
very similar, and consequently the reduction in temperature due to night sky radiation
would be expected to be similar for all of the tested membrane colours.
3.2.3 Membrane Degradation
The degradation of roof membranes often occurs as the result of chemical reactions and
most chemical reactions happen faster at higher temperatures. In many cases the
relationship between temperature and reaction rate is described using the Arrhenius
equation as shown in Equation 3-1.
∙ ∙ Equation 3-1
k = Reaction Rate Constant [units vary]
C1 = Constant Depending on the Reaction [units vary]
Ea = Activation Energy [J/mol]
R = Universal Gas Constant [8.314 J/mol∙K]
T = Absolute Temperature [K]
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
0
5
10
15
20
25
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Decrease in
Temperature [°C]
Monthly Average Decrease in Daily Maximum Membrane Temperature Compared to Black for White Membrane
W‐ISO W‐ISO‐SW W‐SW
* *
Page 28 RDH Building Engineering Ltd. 6230.00
Importantly this equation indicates that for a given increase in temperature, the increase in
the reaction rate can be significantly greater. A rule of thumb is that the increase in the
oxidation rate of roof membranes roughly doubles for every 10°C increase in temperature.
(Docent n.d.) Using this rule of thumb and Equation 3-1, the relative rate of reaction, and
consequently of membrane degradation, was calculated over a range of membrane
temperatures and graphed in Figure 3.19. The degradation rate was set at 1 for a
temperature of 20°C and all other reaction rates are relative to the rate at this temperature.
Figure 3.19 Graph of reaction rate relative to reaction rate at 20°C versus temperature assuming that reaction rate doubles from 20°C to 30°C
Using the relationship shown in Figure 3.19, the relative degradation rates of the roof
membrane cap sheets were determined and are plotted in Figure 3.20, Figure 3.21, and
Figure 3.22 for the polyiso, hybrid, and stone wool roof assemblies respectively. These
figures show a similar relationship to the membrane temperature graphs provided earlier
(Figure 3.13 to Figure 3.15), but the difference in degradation rate is exaggerated compared
to the difference in temperature due to the governing Arrhenius equation. Consequently,
a relatively small reduction in the maximum membrane temperature as a result of the use
of a more reflective roof membrane could potentially significantly extend the service life of
the membrane. For example, during the maximum temperature on June 4th, 2013 the black
polyiso roof was calculated to be aging due to chemical reactions approximately 12 times
faster than the white roof.
Figure 3.20 Graph of relative degradation due to chemical reactions assuming the Arrhenius equation describes relationship of reaction rate to temperature for polyiso roofs
0
50
100
150
200
250
300
350
400
450
500
‐20 ‐10 0 10 20 30 40 50 60 70 80 90 100
Reaction Rate Relative to Rate at 20°C
Temperature [°C]
0
20
40
60
80
100
120
140
160
180
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Reaction Rate Relative to Rate at 20°C
W‐ISO
G‐ISO
B‐ISO
Ambient Exterior
x12
x5.5
6230.00 RDH Building Engineering Ltd. Page 29
Figure 3.21 Graph of relative degradation due to chemical reactions assuming the Arrhenius equation describes relationship of reaction rate to temperature for hybrid roofs
Figure 3.22 Graph of relative degradation due to chemical reactions assuming the Arrhenius equation describes relationship of reaction rate to temperature for stone wool roofs
To examine the relative amounts of degradation that the roof membranes undergo as a
result of the differences in temperatures created by the white, grey, and black roof
membrane colours, the cumulative degradation (degradation integrated over the operating
time period) for each of the roof assemblies was calculated and are plotted in Figure 3.23.
The amount of relative degradation was only summed for hours in which all roof
membranes had data to avoid a misleading comparison due to one roof having more or less
data than another.
0
20
40
60
80
100
120
140
160
180
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Reaction Rate Relative to Rate at 20°C
W‐ISO‐SW
G‐ISO‐SW
B‐ISO‐SW
Ambient Exterior
0
20
40
60
80
100
120
140
160
180
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Reaction Rate Relative
to Rate at 20°C
W‐SW
G‐SW
B‐SW
Ambient Exterior
x11x6
x9 x5
Page 30 RDH Building Engineering Ltd. 6230.00
Figure 3.23 Graph of cumulative relative degradation due to chemical reactions assuming Arrhenius equation describes relationship of reaction rate to temperature
This figures clearly illustrates the decrease in membrane degradation due to chemical
reactions as a result of the use of a reflective membrane. For example, according to the
Arrhenius equation, the white roof membrane and the grey roof membrane on polyiso
underwent approximately 5 times and 3 times less aging due to chemical reactions than
did the black membrane on polyiso for the same one year period. Consequently, the use
of more reflective roof membranes can potentially significantly extended roof membrane
service-life. There is also a noticeable difference in the calculated weathering for the
different insulation arrangements with black membrane; however, this difference is small
compared to the difference created by membrane colour.
This extension of service-life of the roof membrane does not account for the potential
additional benefits associated with more reflective roof membranes moderating membrane
temperatures including less thermal expansion and contraction. That said, it is likely that
in-service roof membrane service-life would not be extended by the same amount as
indicated by these results because of weathering of the roof membranes by other factors.
Overall, the reduction of both temperature magnitude and rate of temperature change
caused by the increased reflectance of the white and grey membranes is likely to improve
roof membrane durability and extend the roof service-life by: reducing the maximum strain
magnitudes and rates on the roof membrane caused by thermal expansion and contraction;
reducing the rate of deleterious chemical reactions; and by reducing the loss of volatile
membrane constituents. This effect is likely to be more pronounced in the white membrane
than the grey as it is more reflective and consequently experiences lower peak temperatures
and slower rates of temperature change than does the grey membrane.
Further research and testing could be performed in a few years to confirm and evaluate the
effect of this calculated increased aging rate on the membrane performance. This work
could include testing of the physical properties of the membrane including evaluation of
the stress-strain relationship of the membrane samples.
3.2.4 Urban Heat Island
Reduced membrane temperatures can also have positive implications with respect to urban
heat island effect. Urban heat island is an affect by which the more solar absorptive roofs,
walls, and pavement of urban areas increases in heat more relative to the surface in rural
areas and consequently causes the average temperature in urban areas to be higher than
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May
Relative
Degradation
W‐ISO
W‐ISO‐SW
W‐SW
G‐ISO
G‐ISO‐SW
G‐SW
B‐ISO
B‐ISO‐SW
B‐SW
x5
x3
6230.00 RDH Building Engineering Ltd. Page 31
in rural areas. It is also attributed to less evapotransporative cooling and less efficient
transport of heat energy by convection. (Hewitt et al., 2014; Zhao et al, 2014) Increased
temperatures, in particular in urban areas, have been correlated with health issues, and
increased peak electricity use. Reflective roofs have been found to reduce summertime air
temperatures of the surrounding area by approximately 1 to 2°C. (Sproul et al, 2014; Akbari
et al, 2005) Large scale evaluation of the urban heat island implications of reflective roof
membranes is beyond the scope of this study.
3.2.5 Heat Flux
The difference in roof membrane temperatures as a result of roof membrane reflectance
also affects the heat flux through the roof assembly. The measured heat flux through the
polyiso roof assemblies during the same period from June 2nd to 8th, 2013 is shown in
Figure 3.24. Note that in this figure and all subsequent heat flux graphs, positive heat flux
is heat flow out of the building and negative heat flux is heat flow in to the building.
Figure 3.24 Graph of heat flux through the three polyiso roofs from June 2 to 8, 2013
The effect of roof membrane reflectance (i.e. colour) on the net heat flux into or out of the
building through the roof assembly is also apparent on an annual basis. Figure 3.25
provides monthly average heat flux out of the building through the roof (outward heat flow
is positive) from May 2013 to April 2014.
‐25
‐20
‐15
‐10
‐5
0
5
10
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Heat Flux [W
/m²]
Heat Flux Sensors
W‐ISO HF
G‐ISO HF
B‐ISO HF
Outw
ardHeat Flo
wInward
Heat Flo
w
Page 32 RDH Building Engineering Ltd. 6230.00
Figure 3.25 Chart of monthly average daily heat flow through the roof assemblies averaged for each roof membrane colour
It is apparent from this figure that the black roofs on average transfer more heat in to the
building during relatively warm periods of the year than do the white and grey roofs. The
heat transfer out through roofs during the colder months is slightly higher for the black
roofs, but this difference is less significant than the difference during warm periods.
Important to note from this figure is that over the course of the year there is more heat gain
in to the building through the roofs than there is heat loss. This was initially a surprising
finding given that the test roofs are located in a heating dominated climate (ASHRAE Climate
Zone 5).
The difference in heat flux caused by the difference in reflectance of the roof membranes
likely has implications with respect to building energy consumption. This potential impact
is analysed in Section 4.
3.2.6 Interior Metal Deck Temperature
The interior metal deck temperature influences the thermal comfort of building occupants
as it composes part of the mean radiant temperature for the interior space. The
temperature of the metal deck is potentially impacted by the roof membrane colour, and to
examine this potential impact the interior metal deck surface temperatures were plotted for
a warm day, June 30th, 2013, in Figure 3.26, Figure 3.27, and Figure 3.28 for the polyiso,
hybrid, and stone wool roof assemblies respectively. It is important to note that interior
metal deck temperatures are also significantly impacted by interior temperature
fluctuations and given that the test roofs are installed on a manufacturing facility,
fluctuations in interior temperature due to manufacturing operations could potentially
impact the measured interior metal deck temperatures; however, this was not noted to be
a significant factor. The average monthly interior temperatures were provided in Section
3.1.
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr Annual
Daily Energy Tran
sfer [W
∙hr/m² per day]
White Grey Black
Outw
ardHeat Flo
wInward
Heat Flo
w
6230.00 RDH Building Engineering Ltd. Page 33
Figure 3.26 Graph of interior metal deck temperature on June 30th, 2013 for the polyiso roof assemblies
Figure 3.27 Graph of interior metal deck temperature on June 30th, 2013 for the hybrid roof assemblies
Figure 3.28 Graph of interior metal deck temperature on June 30th, 2013 for the stone wool roof assemblies
The preceding figures indicate that typically the interior metal deck temperature is more
stable (less extreme minimum and maximum temperatures) for the white roofs than for the
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°C]
W‐ISO TEMP‐DECK
G‐ISO TEMP‐DECK
B‐ISO TEMP‐DECK
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Tem
perature [°C]
W‐ISO‐SW TEMP‐DECK
G‐ISO‐SW TEMP‐DECK
B‐ISO‐SW TEMP‐DECK
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°C]
W‐SW TEMP‐DECK
G‐SW TEMP‐DECK
B‐SW TEMP‐DECK
Page 34 RDH Building Engineering Ltd. 6230.00
grey roofs, and more stable for the grey roofs than for the black roofs. This improved
stability for the more reflective roofs would likely result in improved thermal comfort for
the building occupants as the metal deck temperature stays closer to the ambient interior
air temperature. The differences in metal deck temperatures based on insulation
arrangement are discussed in later sections of this report.
3.3 Thermal Performance - Insulation Arrangement
The field monitoring evaluated the performance of three different insulation arrangements:
polyisocyanurate (polyiso or ISO), stone wool (SW), and a hybrid (ISO-SW) assembly with a
lower layer of polyiso and an upper layer of stone wool. As discussed in Section 2,
laboratory testing indicates that the R-value of these insulation arrangements vary with
temperature, and in particular that the polyiso insulation becomes significantly less
insolative at both high and low temperatures. The field monitoring of these different
assemblies analyses the impact of this varying R-value on the performance of the roof
assemblies. The impact of the difference in thermal mass between the assemblies and of
potential latent heat transfer are also assessed.
Supplementary graphs are provided in Appendix A.
3.3.1 Heat Flux
To assess the impact of the insulation arrangement on the heat flux through the roof
assemblies, the heat flux measurements have been averaged on a monthly basis for each
insulation arrangement and are provided in Figure 3.29. The heat flux measurements for
each of the roof insulation arrangements are presented separately in Appendix A.
Figure 3.29 Chart of monthly average daily heat flow through the roof assemblies averaged for each insulation arrangement
The monitoring results presented in Figure 3.29 indicate that on average the heat flow both
in to and out of the building through the roof assembly is of largest magnitude for the
polyiso (ISO) insulation arrangement, followed by the hybrid (ISO-SW) insulation
arrangement, and then the stone wool (SW) insulation arrangement. This finding is in
0
100
200
300
400
500
600
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr Annual
Degree Days [°C∙days]
Daily Energy Tran
sfer [W∙hr/m² per day]
ISO ISO‐SW SW Heating Degree Days (18°C)
Outw
ardHeat Flow
InwardHeat Flow
6230.00 RDH Building Engineering Ltd. Page 35
contrast to the similar rated R-value of the three different roof assembly insulation
arrangements and indicates that heat flow through the roof assemblies is impacted by the
apparent in-service thermal performance of the insulation which is consistent with the
laboratory measurements of insulation conductivity presented in Section 1.3.1. In other
words, despite the similar rated R-values of these roof assemblies, the polyiso roof
assemblies allow noticeably more heat flow through the assembly than do the stone wool
insulation assemblies for the same rated R-value. The whole building energy consumption
implications of this finding are assessed in Section 4.
Theoretically it is possible to determine in-service R-values of each assembly based on a
measurement of the heat flux through the insulation and of the temperature difference
across the insulation; however, it was not possible to determine consistent in-service R-
values using this method due to a combination of factors including in particular the non-
steady state nature of the exterior conditions created in part by solar heat gains and night
sky cooling effects.
3.3.2 Membrane Temperature
The different characteristics of the insulation arrangements may have an impact on
membrane cap sheet temperatures. To evaluate this potential impact, the cap sheet
temperatures for each of the white, grey, and black roof assemblies are graphed in Figure
3.30, Figure 3.31, and Figure 3.32 respectively.
Figure 3.30 Graph of roof membrane temperatures for roof assemblies with a white cap sheet on June 30, 2013
32
50
68
86
104
122
140
158
176
194
0
10
20
30
40
50
60
70
80
90
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°C]
W‐ISO T‐CAP
W‐ISO‐SW T‐CAP
W‐SW T‐CAP
Ambient Exterior
Temperatu
re [°F]
56°C at 13:00
55°C at 13:0055°C at 15:00
Page 36 RDH Building Engineering Ltd. 6230.00
Figure 3.31 Graph of roof membrane temperatures for roof assemblies with a grey cap sheet on June 30, 2013
Figure 3.32 Graph of roof membrane temperatures for roof assemblies with a black cap sheet on June 30, 2013
Each of the preceding figures clearly indicates a lag of approximately 1 to 2 hours in the
membrane cap sheet temperature for the hybrid (ISO-SW) assemblies as compared to both
the polyiso (ISO) and the stone wool (SW) assemblies. While figures illustrating this affect
are only provided for June 30th, 2013, the affect is consistently noticeable during the
monitoring period. In addition to this lag, there is also a noticeable reduction in the daily
maximum membrane temperature for the hybrid roof assemblies as compared to the other
two assembly types. There are a number of possible explanation for this lag and reduction
in peak temperatures including temperature dependent R-values, and potentially also
thermal mass and latent heat transfer affects (Hedline, 1988; Hedlin, 1987).
The minimum daily temperature of the roof membranes was also assessed for the different
insulation arrangements. Figure 3.33 shows the monthly average minimum daily
temperature for each of the insulation arrangements and clearly demonstrates that polyiso
insulation roof typically has the coldest temperatures, followed by the stone wool insulation
and hybrid insulation assemblies. This finding likely indicates either less heat loss through
the polyiso insulation compared to the hybrid or stone wool under these conditions, or
consistently less heat gain for these assemblies. Neither of these potential causes is
32
50
68
86
104
122
140
158
176
194
0
10
20
30
40
50
60
70
80
90
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°C]
G‐ISO T‐CAP
G‐ISO‐SW T‐CAP
G‐SW T‐CAP
Ambient Exterior
Temperatu
re [°F]
74°C at 14:00 73°C at 14:00
71°C at 14:00
32
50
68
86
104
122
140
158
176
194
0
10
20
30
40
50
60
70
80
90
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°C]
B‐ISO T‐CAP
B‐ISO‐SW T‐CAP
B‐SW T‐CAP
Ambient Exterior
Temperatu
re [°F]
84°C at 13:00
81°C at 13:0080°C at 14:00
6230.00 RDH Building Engineering Ltd. Page 37
consistent with the other findings presented in this report. Further research is required to
determine the cause of this finding.
Figure 3.33 Graph of monthly average minimum daily roof membrane temperatures
3.3.3 Interior Metal Deck Temperature
As discussed with respect to roof membrane colour, the interior metal deck temperature
influences the thermal comfort of building occupants. The metal deck temperature is
potentially affected by the roof insulation arrangement, and to examine this potential effect
the interior metal deck surface temperatures were plotted for a warm day, June 30th, 2013,
for the black, grey, and white roof assemblies respectively.
Figure 3.34 Graph of interior metal deck temperature on June 30th, 2013 for the white roof assemblies
23
32
41
50
59
‐5
0
5
10
15
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Temperature [°F]
Temperature [°C]
ISO ISO‐SW SW
* *
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
68
77
86
95
104
20
25
30
35
40
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°F]
Temperature [°C]
W‐ISO TEMP‐DECK
W‐ISO‐SW TEMP‐DECK
W‐SW TEMP‐DECK
33°C at 19:0033°C at 17:00
32°C at 19:00
Page 38 RDH Building Engineering Ltd. 6230.00
Figure 3.35 Graph of interior metal deck temperature on June 30th, 2013 for the grey roof assemblies
Figure 3.36 Graph of interior metal deck temperature on June 30th, 2013 for the black roof assemblies
The preceding figures indicate that similarly to the roof membrane temperatures, there is
a lag in the maximum metal deck temperature experienced by the hybrid roof assemblies
as compared to the polyiso roof assembly. There is also a lag in the temperature of the
hybrid roof assemblies, which is less than the lag for the stone wool assemblies for the
white and grey roofs, but more for the black roofs. The cause of this discrepancy is
unknown. Overall, the hybrid roof provides the most stable interior metal deck temperature
for the white and grey roofs, and the stone wool insulation provides the most stable metal
deck temperature for the black roofs. These more stable temperatures would likely result
in improved thermal comfort for the building occupants.
Further research is required to determine the optimal hybrid insulation split between
polyiso and stone wool insulation.
3.3.4 Insulation Thermal Mass
Lags and associated reductions in peak temperatures are commonly created by thermal
mass affects which moderate temperature changes by absorbing and releasing relatively
large amount of thermal energy for a given change in temperature. (Siplast, 2010) In these
68
77
86
95
104
20
25
30
35
40
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°F]
Temperature [°C]
G‐ISO TEMP‐DECK
G‐ISO‐SW TEMP‐DECK
G‐SW TEMP‐DECK
35°C at 17:00
34°C at 19:00
32°C at 18:00
68
77
86
95
104
20
25
30
35
40
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Temperature [°F]
Temperature [°C]
B‐ISO TEMP‐DECK
B‐ISO‐SW TEMP‐DECK
B‐SW TEMP‐DECK
36°C at 17:00
34°C at 19:00
35°C at 18:00
6230.00 RDH Building Engineering Ltd. Page 39
roof assemblies the thermal mass most directly connected to the roof membrane is the
insulation. The approximate density, specific heat capacity, volumetric heat capacity, and
thermal diffusivity for the polyiso, stone wool, and SBS membrane products used in the test
roofs are provided in Table 3.1.
TABLE 3.1 INSULATION PROPERTIES RELEVANT TO THERMAL MASS
Insulation Type Density [kg/m³]
Specific Heat Capacity [J/kg∙K]
Volumetric Heat
Capacity [kJ/m³∙K]
Thermal Diffusivity [m²/s 10-7]
Polyiso 32 1500 48 3.3
Stone Wool 176 800 141 2.4
SBS Membrane 1250 1510 1882 47.8
These values were then used to calculate the thermal mass of the insulation per square
meter of roof area for each of the insulation arrangements. The thermal mass of each of
the roof assemblies per square meter of roof area were determined to be 4.6, 11.4, and
20.6 kJ/m²•K for the polyiso, hybrid, and stone wool roof assemblies respectively which is
in addition to approximately 12.2 kJ/m² provided by the SBS roof membrane. These values
clearly illustrate that there is significantly more thermal mass in the assemblies which
include stone wool than in the assemblies with only polyiso; however, there is more thermal
mass in the only stone wool assembly than in the hybrid assembly, so the thermal mass
affect does not fully explain the measured membrane temperatures.
3.3.5 Latent Heat Transfer
Another potential cause of the lag in the roof membrane and metal deck temperatures is
latent heat transfer within the assembly. Latent heat transfer is the movement of energy as
a result of the movement of moisture within the assembly. (Hedlin, 1988; Hedlin, 1987)
In these roof assemblies the heating during the day and cooling at night of the roof
membrane creates the potential for cyclically driving moisture inward and then outward
over the course of each day. This cyclical moisture movement could potentially transfer
significant amounts of energy through the roof assembly and influence the membrane
temperatures. Evaporation of moisture below the roof membrane as it heats up would
decrease the membrane temperature (or slow the heating), and condensation of moisture
under the roof membrane would increase the roof membrane temperature (or slow cooling).
To assess the movement of moisture within the roof assemblies, the relative humidity
measured below the insulation is graphed for each of the roof membrane colours in Figure
3.37, Figure 3.38, and Figure 3.39. These figures are for June 30th, 2013 which is the same
time period as for the roof membrane cap sheet and metal deck temperature graphs
presented in Section 3.3.2 and Section 3.3.3.
Page 40 RDH Building Engineering Ltd. 6230.00
Figure 3.37 Graph of relative humidity below the insulation for assemblies with a white cap sheet on June 30, 2013
Figure 3.38 Graph of relative humidity below the insulation for assemblies with a grey cap sheet on June 30, 2013
Figure 3.39 Graph of relative humidity below the insulation for assemblies with a black cap sheet on June 30, 2013
Each of the preceding three figures indicates the daily cycle of moisture movement within
the roof assemblies. As the temperature of the roof membrane increases during the day,
moisture is driven inwards and the relative humidity below the insulation increases. As the
0
10
20
30
40
50
60
70
80
90
100
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Relative Humidity [%
] W‐ISO RH‐B‐INS
W‐ISO‐SW RH‐B‐INS
W‐SW RH‐B‐INS
0
10
20
30
40
50
60
70
80
90
100
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Relative
Humidity [%
]
G‐ISO‐SW RH‐B‐INS
G‐SW RH‐B‐INS
G‐ISO RH‐B‐INS was damaged during installation; conseuqently, data is unavailable.
0
10
20
30
40
50
60
70
80
90
100
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Relative
Humidity [%
]
B‐ISO RH‐B‐INS
B‐ISO‐SW RH‐B‐INS
B‐SW RH‐B‐INS
6230.00 RDH Building Engineering Ltd. Page 41
temperature of the roof membrane decreases at night, the moisture is then driven outward
and the relative humidity below the insulation decreases. This movement is noticeable in
all of the roof assemblies, and it is most significant for the stone wool assemblies and least
significant for the polyiso roof assemblies which is likely due to the stone wool being
significantly more vapour permeable than the polyiso. It is not readily apparent why the
white hybrid (W-ISO-SW) assembly demonstrates such large changes in relative humidity
compared to the grey and black ISO-SW roofs, but it is possible that a small quantity of
moisture entered the roof assembly during construction.
Cut tests were performed on September 26th, 2013 to assess the amount of moisture that
was present within the roof assemblies. These cut tests were performed in four different
locations including locations with different membrane colours and different insulation
arrangements. The cut tests were performed in the morning when frost was still present
on the membrane surface which is when the maximum amount of moisture would be
present on the underside of the roof membrane. Images of two of these cut tests are
provided in Figure 3.40 to Figure 3.41. All of these cut tests found no visible indications
of moisture within the roof assemblies.
Figure 3.40 Photo of cut test of stone wool insulation under white roof membrane cap sheet indicating no visible signs of moisture within the roof assembly
Figure 3.41 Photo of cut test of polyiso insulation under black roof membrane cap sheet indicating no visible signs of moisture within the roof assembly
Despite the extensive monitoring conducted for this study, it is not possible to quantify the
impact of the latent heat transfer that is occurring in the tested roof assemblies based on
the available information. Further research involving more detailed laboratory testing
would be required to quantify this effect. This research could also investigate the impact
of different amount of water being incorporated into the assembly to simulate rain events
and night sky condensation on exposed insulation which occur during construction and
then subsequently can be included within the assembly if not permitted to dry prior to
installation of the roofing membrane. Further research could also be performed to calibrate
the relative humidity levels measured within the assemblies with the associated moisture
content that would occur in the different materials (i.e. insulation types).
3.4 Dimensional Stability of Insulation
Previous investigation by RDH has indicated that shrinkage of polyiso roof insulation over
time can potentially negatively affect roof performance. While the roof membrane is
typically protected from damage due to shrinkage of the insulation boards by protection
boards installed over the insulation and under the roof membrane, gaps that can open up
Page 42 RDH Building Engineering Ltd. 6230.00
between insulation boards can create thermal bypasses which potentially compromise the
thermal performance of the roofing assembly. These gaps could potentially be substantial
in size as the specification of polyiso insulation board which is provided by ASTM C1289
allows for 2% to 4% dimensional change (depending on the exposure conditions) which for
a 48” by 48” board could be as much as almost 2 inches. (NRCA, 1999)
3.4.1 Long-term Displacement
To investigate the relative dimensional stability and potential shrinkage of the polyiso and
stone wool insulation products used in this study, displacement sensors were installed in
the edges of the insulation boards along both the north-south and east-west axes in both
the lower layer of insulation and the upper layer for the white and black roofs. Figure 3.42
illustrates the arrangement of the insulation boards, adhesive, metal deck, open-web steel
joists, and displacement sensors.
Figure 3.42 Graph of relative humidity below the insulation for assemblies with a black cap sheet on June 30, 2013
It is important to note that the displacement sensors installed in the test roofs measure the
size of the gap between the boards, and that changes in this gap size could be the result
of insulation expansion or contraction, insulation shrinkage (permanent contraction) or
could alternatively be caused by movement of the insulation boards. Movement of the
insulation boards could potentially be driven by thermal expansion and contraction of the
roof membrane or by movement of the roof structure. Figure 3.43 illustrates how deflection
of the steel roof structure could manifest as changes in the gap size between insulation
boards.
Displacement sensor will be sandwiched against adjacent insulation board once installed.
6230.00 RDH Building Engineering Ltd. Page 43
Figure 3.43 Schematic cross-section of the roof assemblies showing how deflection of the structural steel trusses can cause changes in the gap size between the insulation boards
The effectiveness of the polyurethane foam adhesive used to adhere the insulation boards
could also have bearing on the measured changes in the size of the gap between the
insulation boards. Different insulation attachment strategies could provide substantially
different responses to movement of the insulation boards. While an adhered system would
likely provide a relatively stiff response until failure of the adhesive, and mechanically
fastened system would likely allow significantly more movement of the insulation boards.
To date, no significant difference in the gap between the insulation boards between the
north-south and east-west directions has been noticed. One example is provided in Figure
3.44 which compares the movement of the lower layer of the hybrid roof assemblies
(polyiso) in each direction and shows similar trends for each. Graphs for each roof type are
provided in Appendix A. Displacement is provided both in millimetres and in % change in
length of the board (change in length divided by length of insulation board, length of
insulation boards is 1219 mm (4 ft)), and negative displacement corresponds with an
increase in the gap between the boards, and potentially with shrinkage of the insulation
boards.
Deflection of steel deck
Deflection causing opening of joint between insulation boards
Potential compression of insulation due to deflection of steel deck
Page 44 RDH Building Engineering Ltd. 6230.00
Figure 3.44 Graph of displacement of lower layer of insulation in hybrid roof assemblies (parenthesis indicate insulation type)
Given that there is no significant difference based on direction, north-south and east-west
displacements were averaged for the upper and lower layers of insulation in each roof
assembly. Figure 3.45 and Figure 3.46 provide graphs of these averages for comparing the
roofs with white and black cap sheets. These two figures indicate that there is no significant
correlation between the roof membrane colour and the insulation displacement.
Figure 3.45 Graph of insulation displacement averaged for both north-south and east-west direction for upper insulation layers
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐SW‐Lower‐W (ISO) B‐ISO‐SW‐Lower‐W (ISO)
W‐ISO‐SW‐Lower‐N (ISO) B‐ISO‐SW‐Lower‐N (ISO)
‐0.2
‐0.16
‐0.12
‐0.08
‐0.04
0
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacemen
t [%
]
Displacement [m
m]
W‐ISO‐Upper (ISO) W‐ISO‐SW‐Upper (SW) W‐SW‐Upper (SW)
B‐ISO‐Upper (ISO) B‐ISO‐SW‐Upper (SW) B‐SW‐Upper (SW)
6230.00 RDH Building Engineering Ltd. Page 45
Figure 3.46 Graph of insulation displacement averaged for both north-south and east-west direction for lower insulation layers
To evaluate the potential correlation between displacement and the insulation arrangement,
the displacement data was averaged for the lower and upper layers of each of the three
insulation arrangements and is plotted in Figure 3.47 and Figure 3.48 for the upper and
lower insulation layers respectively.
Figure 3.47 Graph of insulation displacement averaged for the upper insulation layer of each of the roof insulation arrangements
‐0.2
‐0.16
‐0.12
‐0.08
‐0.04
0
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐Lower (ISO) W‐ISO‐SW‐Lower (ISO) W‐SW‐Lower (SW)
B‐ISO‐Lower (ISO) B‐ISO‐SW‐Lower (ISO) B‐SW‐Lower (SW)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacemen
t [%
]
Displacemen
t [m
m]
ISO‐Upper (ISO) ISO‐SW‐Upper (ISO) SW‐Upper (SW)
Page 46 RDH Building Engineering Ltd. 6230.00
Figure 3.48 Graph of insulation displacement averaged for the lower insulation layer of each of the roof insulation arrangements
These figures indicate that the lower layer of the hybrid roofs, which is polyiso, has
significantly more movement than the lower layers in either of the polyiso only or stone
wool only roof assemblies. This movement corresponds with the gap between the
insulation boards increasing, potentially due to shrinkage of the insulation boards. The
upper layers of insulation all show similar amounts of displacement over the course of the
monitoring period.
To facilitate the comparison of displacement of the lower layers versus displacement of the
upper layers, the data in Figure 3.47 and Figure 3.48 have been combined into Figure 3.49.
This graph illustrates that with the exception of the hybrid roof assembly, the upper
insulation layer typically has more displacement than the lower insulation layer.
Figure 3.49 Graph of insulation displacement averaged for the upper and lower insulation layer of each of the roof insulation arrangements
Overall, nearly all of the insulation has measured displacement of between 0.4 mm and 2.6
mm (0.03% to 0.20%) which corresponds with an increase in the size of the gap between
the insulation boards which could potentially be a result of shrinkage of the insulation
boards. No correlation was found between the amount of displacement and direction (i.e.
north-south or east-west) and roof membrane colour; however, the insulation arrangement
and the location of the insulation (lower or upper layer) did correlate with the measured
displacements. The gap in the polyiso layer in the hybrid roof assemblies was found to
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
ISO‐Lower (ISO) ISO‐SW‐Lower (ISO) SW‐Lower (SW)
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [m
m]
ISO‐Lower (ISO) ISO‐SW‐Lower (ISO) SW‐Lower (SW)
ISO‐Upper (ISO) ISO‐SW‐Upper (ISO) SW‐Upper (SW)
6230.00 RDH Building Engineering Ltd. Page 47
increase in size more than in the other lower layers of insulation, and in general the upper
layers were found to have displaced more than the lower layers.
Further research and continued monitoring of these insulation boards is necessary to
confirm these longer-term displacement trends. This could potentially include making
exploratory openings in the roof assemblies to confirm the size of the gaps between the
insulation boards. Work could also be carried out to investigate the potential driver of these
gaps between the insulation boards including deflection of the roof structure, thermal
expansion and contraction of the roof membrane, and potentially shrinkage of the
insulation boards.
3.4.2 Short-term Displacement
Changes in the size of the gap between the insulation boards is also noticeable over the
short-term. Figure 3.50 and Figure 3.51 show an example of this for June 30th, 2013 for
the upper and lower insulation layers in the black roofs. These figures show that in some
cases the upper layer of stone wool insulation shows significant movement which is
correlated with the temperature of the cap sheet; however this does not occur for all of the
stone wool roofs. The lower layer of insulation shows no displacement in relation to the
cap sheet temperature because it is separated from this change in temperature by the upper
layer of insulation. A similar trend was also determined for the white roofs and these graphs
are provided in Appendix A.
Figure 3.50 Graph of insulation displacement for the upper layer of insulation in the black roofs
0
10
20
30
40
50
60
70
80
90
100
‐2
‐1.5
‐1
‐0.5
0
0.5
1
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Cap
Sheet Temperature [°C]
Displacement [m
m]
B‐ISO Upper N
B‐ISO‐SW Upper N
B‐SW Upper N
B‐ISO Upper W
B‐ISO‐SW Upper W
B‐SW Upper W
B‐SW T‐CAP
Page 48 RDH Building Engineering Ltd. 6230.00
Figure 3.51 Graph of insulation displacement for the lower layer of insulation in the black roofs
0
10
20
30
40
50
60
70
80
90
100
‐2
‐1.5
‐1
‐0.5
0
0.5
1
Jun 30 00:00 Jun 30 06:00 Jun 30 12:00 Jun 30 18:00 Jul 1 00:00
Cap
Sheet Temperature [°C]
Displacement [m
m]
B‐ISO Lower N
B‐ISO‐SW Lower N
B‐SW Lower N
B‐ISO Lower W
B‐ISO‐SW Lower W
B‐SW Lower W
B‐SW T‐CAP
6230.00 RDH Building Engineering Ltd. Page 49
4 Energy Modeling
Whole building energy modeling was performed to assess how the thermal performance of
the roof assemblies, as determined in the laboratory and field testing phases of the study,
affects whole building energy consumption in various North American climates.
Additionally, the energy modeling investigates the optimum roof membrane colour (solar
absorptivity) and insulation strategy for conventional roof assemblies in each of these
climates. Simulations were conducted to compare the same white, grey, and black roof
membranes, and the same polyiso, stone wool, and hybrid insulation arrangements as were
examined in the field monitoring component of this project.
The building energy modeling was conducted using the U.S. Department of Energy (DOE)
Building Energy Codes Program commercial building prototype model for a stand-alone
retail building designed to meet ASHRAE 90.1-2010 requirements. The building
information files are available online and use the hourly energy modeling program
EnergyPlus. (DOE, 2012)
One goal of the energy modeling was to investigate the impact of temperature dependant
insulation R-values on whole building energy consumption. This effect is typically not
modeled in most whole building simulation programs, but can be modeled in EnergyPlus
by making the conductivity of the insulation a function of temperature. Figure 4.1 shows
charts of the modeled energy consumption of the commercial retail building located in
Vancouver, BC first using constant conductivity values for the roof insulation based on the
rated thermal resistance, and then using temperature dependent insulation conductivities
based on the laboratory testing. Though the overall difference in heating consumption
between the two cases in this climate is low (typically within 1 kWh/m², 2%), these results
indicate that the polyiso has the lowest heating energy consumption when constant
conductivities are used, but stone wool insulation has the lowest heating energy
consumption when temperature dependent conductivities more consistent with field and
laboratory findings are used.
It is also important to note that the graphs in this section present totally building energy
consumption; however, the percent change in the heat flow through the roofs is much larger
than the percent change in the total building energy consumption. For example, in
Vancouver heat flow through the roof of the commercial retail building represents between
15% and 36% of the heat flow through the building enclosure depending on the insulation
and roof membrane scenario. Consequently, a 2% change in the overall energy
consumption of the building would correspond with approximately a 6% to 14% change in
the heat flow through the roof.
Page 50 RDH Building Engineering Ltd. 6230.00
Figure 4.1 Chart of annual heating energy consumption for a commercial retail building located in Vancouver, BC using constant conductivites and temperature dependent conductivities for the roof insulation
The impact of insulation aging on building energy consumption was also assessed using
the commercial retail building energy model. The building was modeled using insulation
conductivities consistent with the initial thermal performance of the insulation, and then it
was modeled using conductivities consistent with the aged performance measured in the
laboratory. The results of this modeling are provided in Figure 4.2 and demonstrate a clear
increase in the energy consumption of the building using polyiso insulation between the
initially installed and aged cases. This effect is largest in the polyiso roof, making it the
case with the most annual heating energy use. The difference in heating energy between
the un-aged and aged cases would increase in more extreme climates than Vancouver.
Figure 4.2 Chart of annual heating energy consumption for a commercial retail building located in Vancouver, BC showing the differnce between the initial and aged insulation cases
To evaluate the impact of roof membrane colour and insulation arrangement on building
energy consumption throughout North America, energy models were developed for one
representative city in each of the eight ASHRAE climate zones. The climate zones and the
cities used for the modeling are illustrated in Figure 4.3.
35
36
37
38
39
40
41
42
43
44
45
Black Grey White Average
Annual Heating En
ergy
[kWh/m
²]
Black Grey White Average
ISO
ISO‐SW
SW
35
36
37
38
39
40
41
42
43
44
45
Black Grey White Average
Annual Heating En
ergy
[kWh/m
²]
ISO
ISO (Aged)
ISO‐SW
ISO‐SW (Aged)
SW
Constant Conductivity (Default)
Temperature Dependent Conductivity (Adjusted to match lab data)
5%2%
6230.00 RDH Building Engineering Ltd. Page 51
Figure 4.3 Map of ASHRAE Climate zones indicating the cities selected for the energy modeling
Figure 4.4, Figure 4.5, and Figure 4.6 show the annual heating, cooling, and total heating
and cooling energy consumption, respectively, for the commercial retail building in each of
the eight ASHRAE climate zones with black, grey, and white roof membranes, and aged
polyiso, stone wool, or hybrid insulation. The numerical results of this analysis are
tabulated in Appendix A.
Houston Miami
San Francisco Baltimore
Burlington Vancouver
Duluth
Fairbanks
Page 52 RDH Building Engineering Ltd. 6230.00
Figure 4.4 Chart of annual heating energy use intensity for a commercial retail building in each of the eight ASHRAE climate zones
Figure 4.5 Chart of annual cooling energy use intensity for a commercial retail building in each of the eight ASHRAE climate zones
0
20
40
60
80
100
120
140
1Miami
2Houston
3San Francisco
4Baltimore
5Vancouver
6Burlington, V
T
7Duluth
8Fairbanks
Average
Annual Heating En
ergy [kWh/m
²]
B‐ISO (Aged) B‐ISO‐SW (Aged) B‐SW
G‐ISO (Aged) G‐ISO‐SW (Aged) G‐SW
W‐ISO (Aged) W‐ISO‐SW (Aged) W‐SW
0
20
40
60
80
100
120
140
1Miami
2Houston
3San Francisco
4Baltimore
5Vancouver
6Burlington, V
T
7Duluth
8Fairbanks
Average
Annual Coolin
g En
ergy [kWh/m
²]
B‐ISO (Aged) B‐ISO‐SW (Aged) B‐SW
G‐ISO (Aged) G‐ISO‐SW (Aged) G‐SW
W‐ISO (Aged) W‐ISO‐SW (Aged) W‐SW
6230.00 RDH Building Engineering Ltd. Page 53
Figure 4.6 Chart of annual heating & cooling energy use intensity for a commercial retail building in each of the eight ASHRAE climate zones
Comparing roof membrane colour, the buildings with black membranes use less heating
energy but more cooling energy, while the buildings with white roofs use more cooling
energy but less heating energy. The total heating and cooling plot (Figure 4.6) shows that
overall energy use is lower for white roofs in cooling dominated climate zones, and lower
for black roofs in heating dominated climate zones. This finding also suggests that in some
temperate climates there could theoretically be an optimal grey roof membrane colour for
energy efficiency. Across all climate zones, stone wool insulation results in the lowest
heating and cooling energy consumption, while aged polyiso insulation has the highest
energy consumption.
0
20
40
60
80
100
120
140
1Miami
2Houston
3San Francisco
4Baltimore
5Vancouver
6Burlington, V
T
7Duluth
8Fairbanks
Average
Annual Heating & Coolin
g En
ergy [kWh/m
²]
B‐ISO (Aged) B‐ISO‐SW (Aged) B‐SW
G‐ISO (Aged) G‐ISO‐SW (Aged) G‐SW
W‐ISO (Aged) W‐ISO‐SW (Aged) W‐SW
Page 54 RDH Building Engineering Ltd. 6230.00
5 Discussion and Conclusions
A large-scale study incorporating a combination of laboratory testing, field monitoring, and
energy modelling was implemented to measure the impacts and benefits of roof membrane
color and insulation strategy on the long-term thermal and hygrothermal performance of
conventional roofing assemblies. At the study building in the Lower Mainland of British
Columbia, Canada, three different 2-ply SBS membrane cap sheet colors (white, grey, black)
were placed over three different conventional insulation strategies (polyiso, stone wool, and
a hybrid combination of both) creating a total of nine unique conventional roofing
assemblies. Sensors were installed within each of the roof assemblies to measure material
and surface temperatures, relative humidity, moisture content, heat flux, and dimensional
stability of the insulation.
As part of the study, thermal resistance testing of the polyiso and stone wool insulation
was performed using ASTM C518 procedures. The insulation products were tested at a
range of in-service temperatures, and a relationship between R-value and temperature was
developed. The results were then applied to the three insulation arrangements monitored
within this study to determine in-service apparent R-values based on exterior membrane
temperature. The findings show that the stone wool and hybrid roofs will maintain apparent
R-values close to rated values, whereas the apparent R-value in the polyiso roofs decreases
significantly when exposed to either extreme of cold or hot outdoor (and solar radiation
induced) temperatures. This is an important consideration when designing roof assemblies.
The difference in performance between the roofs with black, grey, and white membrane cap
sheets was examined using the field monitoring data. The in-service reflectance of these
roofs was measured and determined to be relatively similar to the rated reflectance and
also to not have significantly changed due to soiling of the roof membrane over the course
of the monitoring period except around drain locations. However, with continued exposure,
soiling of the roof membrane may worsen and affect the reflectance. Generally, the more
reflective the roof membrane, the lower the daily maximum membrane temperature and
the more moderate the fluctuations in interior metal deck temperature which will likely
extend the service life of the membranes, reduce heat gain in to the building through the
roof assembly, and improve the thermal comfort of the building occupants.
The relative performance of the three different roof insulation arrangements was also
evaluated using the field monitoring data. The heat flow (flux) and temperature
measurements show a difference in behaviour between the polyiso, stone wool, and hybrid
insulation strategies. The peak membrane temperature was reduced and offset for the
hybrid roof assemblies which is likely due to a combination of temperature dependent
thermal conductivity, thermal mass, and latent heat transfer effects; however, it was not
possible to fully determine the cause of this effect as part of this study. This reduction in
peak roof membrane temperatures positively affects the longevity of the membrane as it
reduces the rate of various weathering mechanisms. An offset was also noted in the
maximum metal deck temperatures, though the measured effect was different for the white
and grey roofs as compared to the black roofs. In all cases the hybrid and stone wool
insulation arrangements provided more stable interior metal deck temperatures and
consequently would likely provide improved thermal comfort for the building occupants.
6230.00 RDH Building Engineering Ltd. Page 55
Whole building energy modeling was performed to investigate the optimum roof membrane
color (solar absorptivity) and insulation strategy for a conventional roof with respect to
building energy consumption. Simulation runs were used to compare the same white, gray,
and black roof membranes, and polyiso, stone wool and hybrid insulation strategies as used
in the monitoring study, and accounted for the temperature dependence of the insulation
thermal resistance. Energy modeling of these variables was performed using the U.S.
Department of Energy (DOE) Building Energy Codes Program commercial building prototype
model for a stand-alone retail building designed to meet ASHRAE 90.1-2010 requirements.
Models were run for one representative city in each of the eight ASHRAE North American
climate zones.
Comparing roof membrane color across each climate zone, the black membrane uses less
heating energy but more cooling energy, while the white roof uses more heating energy but
less cooling energy. Overall energy use is lower for white roofs in cooling dominated climate
zones (zones 1 and 2), and lower for black roofs in heating dominated climate zones (zones
5 through 8). In mixed heating and cooling climate zones (zone 3 and 4), the differences
are very small between light and dark colored roof membranes. With membrane aging and
soiling, the cooling savings of white membranes will likely be reduced as the surface
reflectivity decreases; however, cleaning or recoating of the roof could potentially help to
maintain the roof reflectance.
Across all climate zones, the energy modeling indicates that the stone wool insulation
results in the lowest heating and cooling energy consumption for the same rated R-value,
while aged polyiso insulation has the highest energy consumption due to the loss of its
initial R-value. The hybrid approach of stone wool over polyiso results in a good compromise
of performance and maintains the higher R-value of the polyiso insulation by buffering it
from the exterior temperature.
Overall this study provides insight into the performance of conventional roof assemblies
depending on insulation arrangement and roof membrane solar reflectance (i.e. colour).
The findings of this study can be used to guide the design of conventional roof assemblies
to optimize both roof membrane durability and building energy performance.
Page 56 RDH Building Engineering Ltd. 6230.00
6 Further Research
This study has identified a number of areas for potential further research that could be
pursued to continue to develop the understanding of conventional roof performance.
Potential further research areas include:
Continued monitoring and research to evaluate the long-term impact of roof
membrane soiling and potentially also of the effectiveness of cleaning and
recoating methods at restoring membrane reflectance.
Testing of samples of the aged roof membrane samples after additional years of
exposure to evaluate the effect of the roof membrane colour on the deterioration
of the membrane. This testing would likely include testing of the physical
properties of the aged membrane and comparison of the performance based on
the insulation arrangement on which it was placed and based on membrane colour.
Research to determine the optimal hybrid insulation split between polyiso and
stone wool insulation.
Laboratory testing to quantify the impact of latent heat transfer and thermal mass
on net heat transfer through the roof assemblies, roof membrane temperatures,
and interior metal deck temperatures. This research could include the intentional
introduction of water in to roof assemblies and could also work to calibrate the
relative humidity levels measured in the roof assemblies with the associated
moisture content of the different insulation products.
Continued monitoring and research to evaluate long-term displacement trends and
the impact on membrane durability and effective thermal performance. This
analysis could include the evaluation of potential drivers of these gaps including
roof membrane thermal expansion and contraction, roof deflection, and insulation
shrinkage.
Research to assess the performance of hybrid roof with different insulation types
including extruded polystyrene (XPS) and expanded polystyrene (EPS).
Research to assess the performance of different membrane types.
Similar field studies to evaluate the performance of conventional roof assemblies
in different climate zones.
Additional energy modeling to evaluate the impact of different roof colours and
insulation arrangements for building types including multi-unit residential,
commercial office towers, etc.
Monitoring of energy consumption of a building with different insulation
arrangements and/or insulation colours by monitoring it with one roof assembly
and then with an alternate roof assembly.
6230.00 RDH Building Engineering Ltd. Page 57
7 References
Akbari, H., Berhe, A., Levinson, R., Graveline, S., Foley, K., Delgado, A., & Paroli, R. 2005. Aging and Weathering of Cool Roofing Membranes. (LBNL-58055)
ASTM Standard C518, 2010, “Standard Test Method for Steady-State Thermal
Transmission Properties by Means of the Heat Flow Meter Apparatus” ASTM International, West Conshohocken, PA, 2010. Available at http://www.astm.org/Standards/C518.htm.
ASHRAE Standard 90.1 “Energy Standard for Buildings except Low-Rise Residential
Buildings” I-P and S-I Editions. 2007, 2010. ANSI/ASHRAE/IESNA. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Available at: http://www.ashrae.org.
Berdahl et al. (2008) Weathering of Roofing Materials - An Overview. Construction and
Building Materials, vol. 22, pg. 423-433. Building Science Corporation (BSC). 2013a. BSC Information Sheet 502: Understanding the
Temperature Dependence of R-values for Polyisocyanurate Roof Insulation. Available at: http://www.buildingscience.com.
Christian, J., Desjarlais, A., Graves, R., Smith, T. 1995. Five-Year Field Study Confirms the
PIMA Standard fro Estimating Polyisocyanurate Insulation Long-Term Thermal Performance. Proceedings of the 11th Conference on Roofing Technology, September 1995, Gaithersburg, MD.
DOE. 2012. Building Energy Codes Program – Commercial Prototype Building Models.
Available at: http://www.energycodes.gov/development/commercial/90.1_models DOE Cool Roof Calculator. 2013. Oak Ridge National Laboratory. Software Version 1.2.
Available online: http://web.ornl.gov/sci/roofs+walls/facts/CoolCalcEnergy.htm. Dell, M. 1990. Behavioral characteristics of fully adhered modified bitumen roof
membranes when subjected to in-plane loads. University of Waterloo, 1990. Waterloo, Ontario.
Dell, M., and Finch, G., 2013. Monitored Field Performance of Conventional Roofing
Assemblies – Measuring the Benefits of Insulation Strategy. Proceedings from the 2013 RCI Symposium on Building Envelope Technology, November 13-14, 2013, Minneapolis, Minnesota.
Dell, M., Finch, G., Ricketts, L, and Hanam, B. 2014. Conventional Roofing Assemblies:
Measured Thermal Benefits of Light to Dark Roof Membranes and Alternate Insulation Strategies. Proceedings from the 2014 RCI Symposium on Building Envelope Technology, March 20-25, 2014, Anaheim, California.
Environment Canada. 2013. Canadian Climate Normals, Chilliwack Airport. Available at:
http://climate.weather.gc.ca/climate_normals/ Graham, M., 2010. Revised R-values, Professional Roofing, May 2010. Available at:
http://www.professionalroofing.net/. Graham, M., 2013. New LTTR values: PIMA updates its QualityMark Program. Professional
Roofing, vol. 42, issue 8, p 12, August 2013. Available at: http://www.professionalroofing.net/.
Graham, M., 2014. Polyiso’s R-value: NRCA recommends Polyisocyanurate insulation be
specified by its desired thickness. NRCA Industry Issue Update, January 2014. National Roofing Contractors Association, Rosemont, Illinois.
Page 58 RDH Building Engineering Ltd. 6230.00
Hedlin, C.P., 1987. Seasonal Variations in the Modes of Heat Transfer in Moisture Porous Thermal Insulation in a Flat Roof. Journal of Thermal Insulation, Vol. 11, p 54-66, July 1987, (IRC Paper No. 1496).
Hedlin, C. 1988. Heat Flow Through a Roof Insulation Having Moisture Contents Between
0 and 1% by Volume, in Summer. ASHRAE Transactions 1988, Part 2, p 1579-1594. (IRC Paper No. 1636.)
Hewitt, V., Mackres, E., Shickman, K. 2014. Cool Policies for Cool Cities: Best Practices for
Mitigating urban Heat Islands in North American Cities. American Council for an Energy-Efficient Economy and Global Cool Cities Alliance, Washington, DC. (Report Number U1405)
Koshiishi, N., Shoji, T., Shimizu, I., Tanaka, K. 2014. Changes in the solar reflectance of
membrane waterproofing materials exposed to different atmospheric conditions. Proceedings from the International Conference on Building Envelope Systems and Technologies (ICBEST) 2014, June 9-12, 2014, Aachen, Germany.
NRCA, 2011. Special Report: Considerations Pertaining to Polyisocyanurate Insulation.
Accessed August 18, 2014 at http://www.nrca.net/roofing/-Special-Report-Considerations-Pertaining-to-Polyisocyanurate-Insulation-May-1999-263.
Roe, R. 2007. Long-Term Thermal Resistance (LTTR): 5 Years Later. Interface Technical
Journal, March 2007, p 12-15. Roof Savings Calculator (RSC). 2013. Oak Ridge National Laboratory and Lawrence
Berkeley National Laboratory. Software Version v0.92. Available online: http://www.roofcalc.com/index.shtml.
Siplast. 2010. Mass Effect – Substrate Influences on Modified Bitumen Roof Membrane
Longevity. North Vancouver, British Columbia, Canada. Smith, T.L., 2001. Benefits of Reflective Roofs in Northern Areas of the U.S.. Proceedings
of the 16th International Convention & Trade Show, April 20-24, 2001, Baltimore, Maryland.
Sproul, J., Pun Wan, M., Mandel, B. H., Rosenfeld, A. H. 2014. Economic comparison of
white, green, and black flat roofs in the United States. Energy and Buildings 71 (2014), p 20-27.
Zhao, L., Lee, X., Smith, R., Oleson, K. 2014. Strong contributions of local background
climate to urban heat islands – abstract. Accessed July 22, 2014 to http://www.nature.com/nature/journal/v511/n7508/full/nature13462.html
6230.00 RDH Building Engineering Ltd. Page 59
We trust that this report meets your needs at this time. Please contact the undersigned
with any questions or concerns.
Yours truly,
Lorne Ricketts | MASc, EIT Building Science Research Engineer (EIT) [email protected] RDH Building Engineering Ltd.
Graham Finch | MASc, P.Eng Principal, Building Science Research Specialist [email protected] RDH Building Engineering Ltd.
Marcus Dell | MASc, P.Eng. Managing Principal, Senior Building Science Specialist [email protected] RDH Building Engineering Ltd.
Ap
pen
dix
A
Ad
ditio
nal G
rap
hs
6230.00 RDH Building Engineering Ltd. Page 1
Additional graphs and data are provided in this appendix to supplement the main body of
the report. In some cases graphs are repeated here from the main body of the report for
completeness.
Maximum and Minimum Daily Membrane Temperatures
Figure A.1 Chart of monthly average peak daily membrane temperatures from May 2013 to April 2014
Figure A.2 Chart of monthly average reduction in peak daily membrane temperatures for the roofs with white membrane cap sheets as compared to the roofs with black membrane cap sheets
0
10
20
30
40
50
60
70
80
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Temperature [°C]
W‐ISO
W‐ISO‐SW
W‐SW
G‐ISO
G‐ISO‐SW
G‐SW
B‐ISO
B‐ISO‐SW
B‐SW
* *
*W‐ISO‐SW had significant data loss in August and September which is likely the cause of colder than typical temperatures.
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
0
5
10
15
20
25
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Decrease in
Temperature [°C]
W‐ISO W‐ISO‐SW W‐SW
* *
Figure A.3 Chart of monthly average reduction in peak daily membrane temperatures for the roofs with grey membrane cap sheets as compared to the roofs with black membrane cap sheets
Figure A.4 Chart of monthly average reduction in peak daily membrane temperatures for the roofs with white and grey membrane cap sheets as compared to the roofs with black membrane cap sheets for each of the insulation arrangements
0
5
10
15
20
25
30
35
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Decrease in
Tem
perature [°C]
G‐ISO G‐ISO‐SW G‐SW
0
9
18
27
36
45
0
2
4
6
8
10
12
14
16
18
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr Annual
Decrease in
Temperature [°F]
Decrease in
Tem
perature [°C]
ISO ISO‐SW SW
*W‐ISO‐SW had significant data loss in August and September and is removed from the average for those months.
6230.00 RDH Building Engineering Ltd. Page 3
Figure A.5 Chart of monthly average minimum daily membrane temperatures from May 2013 to April 2014
Heat Flux
Figure A.6 Graph of heat flux through the three polyiso roofs from June 2 to 8, 2013
Figure A.7 Graph of heat flux through the three hybrid roofs from June 2 to 8, 2013
‐5
0
5
10
15
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Temperature [°C]
W‐ISO
W‐ISO‐SW
W‐SW
G‐ISO
G‐ISO‐SW
G‐SW
B‐ISO
B‐ISO‐SW
B‐SW
*W‐ISO‐SW had significant data loss in August and September which is likely the cause of colder than typical temperatures.
‐25
‐20
‐15
‐10
‐5
0
5
10
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Heat Flux [W
/m²]
W‐ISO HF
G‐ISO HF
B‐ISO HF
Outw
ardHeat Flo
wInward
Heat Flo
w
‐25
‐20
‐15
‐10
‐5
0
5
10
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Heat Flux [W
/m²]
W‐ISO‐SW HF
G‐ISO‐SW HF
B‐ISO‐SW HF
Outw
ardHeat Flo
wInward
Heat Flo
w
Figure A.8 Graph of heat flux through the three stone wool roofs from June 2 to 8, 2013
Figure A.9 Chart of monthly average daily heat flow through the roof assemblies for polyiso insulation arrangements
Figure A.10 Chart of monthly average daily heat flow through the roof assemblies for hybrid insulation arrangements
‐25
‐20
‐15
‐10
‐5
0
5
10
Jun 2 Jun 3 Jun 4 Jun 5 Jun 6 Jun 7 Jun 8
Heat Flux [W
/m²]
W‐SW HF
G‐SW HF
B‐SW HF
Outw
ardHeat Flo
wInward
Heat Flo
w
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Tran
sfer [W
∙hr/m² per day]
W‐ISO G‐ISO B‐ISO
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Tran
sfer [W
∙hr/m² per day]
W‐ISO‐SW G‐ISO‐SW B‐ISO‐SW
6230.00 RDH Building Engineering Ltd. Page 5
Figure A.11 Chart of monthly average daily heat flow through the roof assemblies for stone wool insulation arrangements
Figure A.12 Chart of monthly average daily heat flow through the roof assemblies for roofs with white cap sheet membrane
Figure A.13 Chart of monthly average daily heat flow through the roof assemblies for roofs with grey cap sheet membrane
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Transfer [W
∙hr/m² per day]
W‐SW G‐SW B‐SW
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Tran
sfer [W∙hr/m² per day]
W‐ISO W‐ISO‐SW W‐SW
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Transfer [W∙hr/m² per day]
G‐ISO G‐ISO‐SW G‐SW
Figure A.14 Chart of monthly average daily heat flow through the roof assemblies for roofs with black cap sheet membrane
Figure A.15 Chart of monthly average daily heat flow through the roof assemblies averaged for each roof membrane cap sheet colour and showing percent of the data points that are missing in each month due to failure of the data collection equipement
Figure A.16 Chart of monthly average daily heat flow through the roof assemblies averaged for each insulation arrangement and showing percent of the data points that are missing in each month due to failure of the data collection equipement
‐200
‐150
‐100
‐50
0
50
100
May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr
Daily Energy Transfer [W
∙hr/m² per day]
B‐ISO B‐ISO‐SW B‐SW
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
‐200
‐150
‐100
‐50
0
50
100
150
Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Daily Energy Tran
sfer [W
∙hr/m² per day]
White Grey Black % Data Missing
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
‐150
‐100
‐50
0
50
100
Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May JunDaily Energy Transfer [W∙hr/m² per day]
ISO ISO‐SW SW % Data Missing
6230.00 RDH Building Engineering Ltd. Page 7
Dimensional Stability
Figure A.17 Graph of displacement of lower layer of insulatoin in polyiso roof assemblies (parenthesis indicate insulation type)
Figure A.18 Graph of displacement of lower layer of insulatoin in hybrid roof assemblies (parenthesis indicate insulation type)
Figure A.19 Graph of displacement of lower layer of insulatoin in stone wool roof assemblies (parenthesis indicate insulation type)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐Lower‐W (ISO) B‐ISO‐Lower‐W (ISO) W‐ISO‐Lower‐N (ISO) B‐ISO‐Lower‐N (ISO)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐SW‐Lower‐W (ISO) B‐ISO‐SW‐Lower‐W (ISO)
W‐ISO‐SW‐Lower‐N (ISO) B‐ISO‐SW‐Lower‐N (ISO)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐SW‐Lower‐W (SW) B‐SW‐Lower‐W (SW) W‐SW‐Lower‐N (SW) B‐SW‐Lower‐N (SW)
Figure A.20 Graph of displacement of upper layer of insulatoin in polyiso roof assemblies (parenthesis indicate insulation type)
Figure A.21 Graph of displacement of upper layer of insulatoin in hybrid roof assemblies (parenthesis indicate insulation type)
Figure A.22 Graph of displacement of upper layer of insulatoin in stone wool roof assemblies (parenthesis indicate insulation type)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐Upper‐W (ISO) B‐ISO‐Upper‐W (ISO) W‐ISO‐Upper‐N (ISO) B‐ISO‐Upper‐N (ISO)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐SW‐Upper‐W (SW) B‐ISO‐SW‐Upper‐W (SW)
W‐ISO‐SW‐Upper‐N (SW) B‐ISO‐SW‐Upper‐N (SW)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐SW‐Upper‐W (SW) B‐SW‐Upper‐W (SW) W‐SW‐Upper‐N (SW) B‐SW‐Upper‐N (SW)
6230.00 RDH Building Engineering Ltd. Page 9
Figure A.23 Graph of displacement of insulation for roof with white membrane cap sheet (parenthesis indicate insulation type)
Figure A.24 Graph of displacement of insulation for roof with black membrane cap sheet (parenthesis indicate insulation type)
Figure A.25 Graph of insulation displacement for the upper layer of insulation in the white roofs
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
W‐ISO‐Lower (ISO) W‐ISO‐SW‐Lower (ISO) W‐SW‐Lower (SW)
W‐ISO‐Upper (ISO) W‐ISO‐SW‐Upper (SW) W‐SW‐Upper (SW)
‐0.20
‐0.16
‐0.12
‐0.08
‐0.04
0.00
0.04
‐2.5
‐2.0
‐1.5
‐1.0
‐0.5
0.0
0.5
Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec Jan Feb Mar Apr May Jun
Displacement [%
]
Displacement [m
m]
B‐ISO‐Lower (ISO) B‐ISO‐SW‐Lower (ISO) B‐SW‐Lower (SW)
B‐ISO‐Upper (ISO) B‐ISO‐SW‐Upper (SW) B‐SW‐Upper (SW)
0
10
20
30
40
50
60
70
80
90
100
‐2
‐1.5
‐1
‐0.5
0
0.5
1
Jun 30 Jun 30 Jun 30 Jun 30 Jul 1
Cap
Sheet Temperature [°C]
Displacement [m
m] W‐ISO Upper N
W‐ISO‐SW Upper N
W‐SW Upper N
W‐ISO Upper W
W‐ISO‐SW Upper W
W‐SW Upper W
W‐ISO T‐CAP
Figure A.26 Graph of insulation displacement for the lower layer of insulation in the white roofs (data unavailable for ISO roofs)
Whole Building Energy Consumption Modeling Data
ANNUAL HEATING ENERGY [kWh/m² (% savings compared to maximum]
1
Mia
mi
2
Houst
on
3
San F
ranci
sco
4
Balt
imore
5
Van
couve
r
6
Burl
ingto
n, V
T
7
Dulu
th
8
Fair
ban
ks
Ave
rage
B-ISO (aged) 0
(22%) 4
(9%) 6
(20%) 18
(13%) 40
(10%) 38
(9%) 54
(8%) 114 (3%)
34 (7%)
B-ISO-SW (aged) 0 (21%)
4 (11%)
6 (20%)
16 (20%)
39 (13%)
35 (18%)
49 (18%)
102 (13%)
31 (15%)
B-SW 0 (23%)
3 (13%)
6 (20%)
15 (26%)
39 (14%)
33 (23%)
46 (22%)
99 (16%)
30 (19%)
G-ISO (aged) 0
(20%) 4
(8%) 7
(16%) 18
(11%) 41
(9%) 39
(8%) 55
(7%) 115 (3%)
35 (6%)
G-ISO-SW (aged) 0 (19%)
4 (10%)
7 (18%)
17 (18%)
40 (11%)
35 (17%)
49 (17%)
103 (13%)
32 (14%)
G-SW 0
(21%) 3
(12%) 7
(19%) 15
(25%) 39
(13%) 33
(21%) 47
(21%) 99
(16%) 30
(18%)
W-ISO (aged) 0 (max)
4 (max)
8 (max)
20 (max)
45 (max)
42 (max)
59 (max)
118 (max)
37 (max)
W-ISO-SW (aged) 0 (2%)
4 (4%)
8 (4%)
19 (9%)
43 (4%)
38 (10%)
52 (12%)
106 (11%)
34 (9%)
W-SW 0
(6%) 4
(7%) 8
(6%) 17
(17%) 42
(7%) 36
(16%) 50
(16%) 102
(14%) 32
(13%)
0
10
20
30
40
50
60
70
80
90
100
‐2
‐1.5
‐1
‐0.5
0
0.5
1
Jun 30 Jun 30 Jun 30 Jun 30 Jul 1
Cap
Sheet Temperature [°C]
Displacement [m
m]
Insualation Displacement ‐White Lower
W‐ISO Lower N
W‐ISO‐SW Lower N
W‐SW Lower N
W‐ISO‐SW Lower W
W‐ISO‐SW Lower W
W‐SW Lower W
W‐ISO T‐CAP
6230.00 RDH Building Engineering Ltd. Page 11
ANNUAL COOLING ENERGY [kWh/m² (% savings compared to maximum]
1
Mia
mi
2
Houst
on
3
San F
ranci
sco
4
Balt
imore
5
Van
couve
r
6
Burl
ingto
n, V
T
7
Dulu
th
8
Fair
ban
ks
Ave
rage
B-ISO (aged) 61 (max)
36 (max)
4 (max)
20 (max)
2 (max)
9 (max)
6 (max)
3 (max)
18 (max)
B-ISO-SW (aged) 59 (4%)
35 (4%)
4 (6%)
19 (4%)
2 (7%)
9 (5%)
6 (4%)
3 (1%)
17 (4%)
B-SW 58 (5%)
34 (5%)
3 (8%)
18 (6%)
2 (9%)
9 (6%)
5 (6%)
3 (1%)
17 (5%)
G-ISO (aged) 60 (2%)
36 (2%)
4 (4%)
19 (2%)
2 (5%)
9 (3%)
6 (4%)
3 (3%)
17 (3%)
G-ISO-SW (aged) 58 (6%)
34 (6%)
3 (9%)
18 (7%)
2 (10%)
9 (7%)
5 (7%)
3 (3%)
17 (6%)
G-SW 57 (6%)
34 (7%)
3 (11%)
18 (8%)
2 (13%)
9 (9%)
5 (8%)
3 (3%)
16 (7%)
W-ISO (aged) 53 (13%)
32 (13%)
3 (26%)
16 (17%)
1 (28%)
7 (20%)
5 (21%)
3 (16%)
15 (15%)
W-ISO-SW (aged) 53 (14%)
32 (13%)
3 (25%)
16 (17%)
1 (27%)
8 (19%)
5 (20%)
3 (15%)
15 (15%)
W-SW 53 (14%)
32 (13%)
3 (25%)
16 (17%)
1 (28%)
8 (19%)
5 (20%)
3 (14%)
15 (15%)
ANNUAL HEATING & COOLING ENERGY [kWh/m² (% savings compared to maximum]
1
Mia
mi
2
Houst
on
3
San F
ranci
sco
4
Balt
imore
5
Van
couve
r
6
Burl
ingto
n, V
T
7
Dulu
th
8
Fair
ban
ks
Ave
rage
B-ISO (aged) 62 (max)
40 (max)
10 (6%)
37 (max)
42 (9%)
48 (4%)
60 (6%)
117 (3%)
52 (0%)
B-ISO-SW (aged) 59 (4%)
38 (4%)
10 (8%)
35 (6%)
41 (11%)
44 (12%)
54 (15%)
106 (13%)
48 (7%)
B-SW 58 (5%)
38 (5%)
10 (9%)
34 (10%)
40 (13%)
41 (17%)
52 (19%)
102 (16%)
47 (10%)
G-ISO (aged) 60 (2%)
39 (2%)
10 (4%)
37 (0%)
43 (7%)
48 (4%)
61 (5%)
118 (2%)
52 (0%)
G-ISO-SW (aged) 58 (6%)
38 (6%)
10 (8%)
35 (6%)
42 (10%)
44 (12%)
54 (14%)
106 (12%)
48 (7%)
G-SW 58 (6%)
37 (7%)
10 (9%)
33 (11%)
41 (12%)
42 (16%)
52 (18%)
102 (15%)
47 (10%)
W-ISO (aged) 53 (13%)
36 (11%)
11 (max)
37 (2%)
46 (max)
50 (max)
64 (max)
121 (max)
52 (max)
W-ISO-SW (aged) 53 (14%)
35 (11%)
11 (3%)
35 (7%)
44 (4%)
45 (9%)
57 (11%)
108 (10%)
49 (7%)
W-SW 53 (14%)
35 (12%)
10 (4%)
33 (11%)
43 (6%)
43 (13%)
55 (14%)
104 (14%)
47 (10%)