study and analysis of distribution equipment reliability data...equipment reliability data can be...

106
Study and Analysis of Distribution Equipment Reliability Data Datastudier och analys av tillförlitlighetsdata på komponentnivå för eldistributionsnät Elforsk rapport 10:33 Ying He Mars 2010

Upload: others

Post on 27-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

Study and Analysis of Distribution Equipment Reliability Data

Datastudier och analys av tillförlitlighetsdata på komponentnivå för eldistributionsnät Elforsk rapport 10:33

Ying He Mars 2010

Page 2: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

Study and Analysis of Distribution Equipment Reliability Data

Datastudier och analys av tillförlitlighetsdata på komponentnivå för eldistributionsnät

Elforsk rapport 10:33 Ying He Mars 2010

Page 3: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Förord Denna rapport är framtagen av projektet ”Tillförlitlighets data på komponentnivå för riskanalys på eldistributionsnät - Del 2: Data studier och analys’’, som är en fortsättning av det tidigare utfört projektet ”Tillförlitlighets data på komponentnivå för riskanalys på eldistributionsnät’’ inom FoU-programmet Riskanalys 06-10 som drivs av Elforsk. Projektet har genomförts av Ying He, Vattenfall Research and Development AB.

Syftet med projektet är att utföra fördjupande studier och analys av felstatistiken på komponentnivå, jämföra befintlig statistik, undersöka felkällor och faktorer som påverkar felstatistiken, och analysera uppdelningen av statistiken med avseende på felorsaker, samt ge ett branschgemensamt underlag till dataanvändningen för riskanalys på eldistributionsnät.

Programmets styrgrupp består av följande ledamöter:

Arne Bergström, Vattenfall Eldistribution AB

Horst Blüchert, Elsäkerhetsverket

Mikael Bohjort, E.ON Elnät Sverige AB

Leif Boström, Fortum Distribution

Håkan Jarer, Svenska Kraftnät

Sven-Åke Polfjärd, Föreningen Industriell Elteknik, FIE

Sven Jansson, Elforsk AB

Bertil Wahlund, Elforsk AB.

Finansiärer i programmet är:

Vattenfall Eldistribution AB

E.ON Elnät Sverige AB

Fortum Distribution AB

Svenska Kraftnät

Göteborg Energi AB

Skellefteå Kraft AB

Mälarenergi Elnät AB

Tekniska Verken i Linköping AB

Öresundskraft AB

Jämtkraft AB

Umeå Energi Elnät AB

Jönköping Energi Nät AB

Page 4: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Eskilstuna Energi & Miljö AB

Gävle Energi AB

Energiverken i Halmstad

Sundsvall Elnät AB

Växjö Energi Elnät AB

Borlänge Energi AB

Nacka Energi AB

Föreningen Industriell Elteknik, FIE

Elsäkerhetsverket

Lunds Energi AB.

Projektet har genomförts i huvudsak av Vattenfall Research and Development AB med medverkan av Svensk Energi och hjälp av följande personer:

Matz Tapper, Svensk Energi

Gerd Kjølle, SINTEF, Norway

Jørn Heggset, SINTEF, Norway

Peter Hansen, Danish Energy Association

Morten Møller, Danish Energy Association

Lisbeth Petersson, Danish Energy Association

Elina Lehtomäki, Finnish Energy Industries

Przemysław Karaś, Vattenfall Distribution Poland S.A.

Anders Holm, granskning, Vattenfall Research and Development AB.

Bertil Wahlund

Överföring & Distribution

Elforsk AB

Page 5: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Sammanfattning Kvantitativ riskanalys kräver tillförlitlighetsdata för olika elektriska komponenter. Trovärdiga data har en fundamental betydelse för riskanalys. Utan trovärdiga data kommer resultaten av riskanalys att vara meningslös.

I del 1 av projektet genomfördes grundläggande arbete. Arbetet fokuserades på förbättringar av befintligt dataunderlag med datainsamling och kompletteringar från ett antal nätbolag. Det visade sig att det fanns stora variationer och spridningar i datastatistiken. Det var oklart varför och vad som orsakade sådana variationer och det saknas analys av statistiken och jämförande studier.

För att få bättre förståelse i tillförlitlighetsdata, har projektet utfört fördjupande studier och analyser kring befintlig statistik. Arbetet har fokuserats på jämförande studier, felorsak, analys och kartläggning av underliggande faktorer som påverkar statistiken.

Studierna visar att ett stort antal företag och organisationer världen över har etablerat datorsystem och databaser för felrapporteringar, störningsanalys och bearbetning av statistiken. Det finns dock inga standarder generellt accepterade för datainsamlingar och behandlingar. Undersökningen tyder på att betydande inkonsekvenser och skillnader finns i datakategorisering och insamlingar i olika länder och organisationer.

Trots svårigheter i datajämförelser på grund av skillnaderna i datainsamlingar, skillnaderna i system- och statistikklassificeringar, har projektet försökt identifiera gemensamma data och kategorier för att möjliggöra jämförelserna. Projektet studerade den befintliga statistiken på komponentnivå från olika aspekter, inklusive systemkarakterisering, datastruktur, metod för datainsamlingar, klassificering av felstatistik, typiska parametrar och värde som beskriver tillförlitlighet hos komponenter, felorsakskategorier och anläggningsklassificeringar.

Resultatet från de jämförande studierna beskrivs i rapporten. Jämförelser av statistiken från olika dataskällor med avseende på datastruktur och komponentklassificering presenteras också i rapporten. Värden av anläggningsstatistiken från del 1 av projektet har jämförts med statistik från ett antal länder. Sammanställningar av dess värde för olika typer av anläggningar presenteras i bilaga till rapporten.

Tillförlitlighetsdata hos elnätkomponenter reflekterar stokastiska egenskaper hos komponentfel. Resultaten av projektet visar att betydande skillnader finns i statistik i olika länder. Det är viktigt att förstå denna dynamiska karaktär hos tillförlitlighetsdata. Om möjligt bör felstatistik hos anläggningar studeras regelbundet.

Uppdelning på felorsaker till komponentfel har analyserats i projektet utgående från felrapporteringar i DARWin hos Svensk Energi. Analyserna utfördes både på nationell nivå och på enskilda företag. Analyserna visar att felorsaker kan vara olika för olika typer av elnätkomponenter. Huvudorsaker till fel på luftledningar är väder- och omgivningsrelaterade fel, medan dominerande fel på jordkablar är material- och grävningsrelaterade. Det visar

Page 6: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

sig att åska, materialfel, och bristande underhåll är huvudorsaker till fel på distributionstransformatorer.

Tillförlitlighetsdata kan påverkas av olika faktorer. För att ge en bild på felkällor och inverkande faktorer, har projektet studerat olika påverkande faktorer. Resultatet visar att tillförlitlighetsdata kan påverkas av ett antal faktorer, t.ex. tidsperiod, geografi, underhåll, anläggningsålder, tillverkning, spänningsnivå, konstruktion och storlek. En kartläggning av påverkande faktorer bakom statistiken presenteras i rapporten. Hur dessa faktorer kan påverka tillförlitlighetsdata hos olika typer av elnätkomponenter beskrivs också i rapporten.

Extrema händelser, t.ex. stormen Gudrun, kan ha förödande effekter på elnät och drabba nätkunder mycket negativt. För att modellera och analysera risker relaterade till Gudrun-stormen krävs tillförlitlighetsdata för elektriska komponenter. Den här typen av statistik har också analyserats i projektet. Projektresultatet visar att felfrekvensen för elnätkomponenter som utsätts för väder kan dramatiskt öka med upp till 80 gånger av det genomsnittliga värdet under extremt väder. Denna dramatiska förändring av tillförlitlighetsdata för komponenter bör tas hänsyn till vid riskanalys av distributionssystem.

Page 7: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Summary

Meaningful risk and reliability analysis requires reasonable and acceptable component reliability data. The quality of the data has fundamental importance for the risk analysis of a system. If the quality of the data cannot be guaranteed, the results of the reliability analysis will not make sense.

In the project performed previously, “Component Reliability Data for Risk Analysis of Distribution Systems’’ within the Elforsk R&D program Risk Analysis 06-10, main effort has been expended in developing component reliability data and fundamental work with data collection and data processing. However, the component reliability data produced show that the significant variations in data statistics exist. It was unclear why and by what these data variations were caused, and the statistics needs to be further analyzed.

In order to better understand reliability data and get confidence in data use, the project performed detailed study and analysis of existing component failure statistics. The main activities of the project were focused on comparative data study and failure cause and influencing factor analyses.

The studies shows that many utilities and organizations throughout the world have established systems and procedures for collecting data and assessing the performance of their electric power equipment. Failure statistics have been topics for many years and failure and interruption data have been collected in various countries.

However, there are currently no standards generally accepted for data recording and collections. The survey of recorded information and data scheme used for deducing reliability data indicates that significant inconsistencies exist in the data categorization and collection processes in different countries and organizations.

Despite the fact that the comparisons may be difficult to make due to the differences in data collection methods employed, differences in system design and operation, and differences in the environments, the project tried to identify common data set and categories necessary to allow the comparison. In the comparative studies of the project, the differences between the collection methods and the differences in system and data items were studied. The issues and items studied include power system characterization, data categorization structures, data collection methods, classification of failure statistics and outage events, typical parameters and key figures calculated to describe component reliability, definitions of interruptions and outages, failure cause categories, and component classifications.

The results of the comparative studies are described in the report. The comparative overviews of data scheme characteristics and structures are provided in the report. The values of failure statistics from different data sources were also compared in the project. The comparative data studies are made on major categories of distribution equipment, and the comparison of the Swedish statistics with the data from other sources are presented in the report and the detailed values are summarized in the Appendix of the report.

Page 8: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Component reliability data reflects stochastic nature of component failures and impact of influencing factors. The results of project show that the reliability data can vary widely from system to system, from year to year, and from area to area. It is important to recognize this dynamic feature of reliability data. If possible, study and analyze component failure statistics regularly and produce confident data for risk analysis.

To understand the causes of component failures the cause analyses were carried out in the project. The analyses were based on the data from the DARWin database of Svensk Energi. In addition to the nationwide analyses the study of faults reported at individual companies was also performed in the project.

The analyses show that the failure causes were different for different types of power components. The analyses confirm that the dominant causes for faults on overhead network components are weather and environment related, while faults on underground distribution equipment are mainly material defect and digging related. The results of analysis indicate that thunderstorm, manufacturer and material defects, and inadequate maintenance were responsible for the majority of distribution transformer failures.

The reliability of distribution equipment can be influenced by various factors. In order to understand this influence the project work is devoted to studying and analyzing these factors. The report describes and illustrates how equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography, age, operation condition and maintenance. It is shown by the project that due to different influencing factors, component reliability data can exhibit significant variations. It is therefore important to understand this influence and to consider the influencing factors when estimating and using the reliability statistics.

In the extreme weather condition, distribution systems could be affected very negative. For this reason, this effect should be considered in the risk analysis, and the project studied how extreme weather affects component reliability. The project analyzed the statistics of component failures during the hurricane Gudrun in January 2005 based on the fault reports from all Sweden and from the power company, E:ON Elnät Sverige AB.

The results indicate that the failure rate of distribution equipment exposed to weather could dramatically increase by up to 80 times of the average value during extreme weather condition. This dramatic change of the component reliability data should therefore be taken into account in risk analysis of distribution systems.

Page 9: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

Innehåll

1 Introduction 11.1 Background ...................................................................................... 11.2 Purpose ........................................................................................... 1

2 Data Sources and Collection 32.1 Data Sources .................................................................................... 32.2 Norwegian Fault Statistics .................................................................. 52.3 Danish Fault Statistics ....................................................................... 62.4 Finnish Fault Statistics ....................................................................... 72.5 Norstat Statistics .............................................................................. 82.6 Fault Statistics from Other Data Sources .............................................. 9

3 Data Structure and Categorization 123.1 System Characterization .................................................................. 123.2 Equipment Classification .................................................................. 133.3 Measures of Component Reliability .................................................... 153.4 Data Collected and Data Processing ................................................... 163.5 Interruption Causes ......................................................................... 17

4 Comparison of Reliability Data 214.1 Distribution Lines ............................................................................ 214.2 Distribution Cables .......................................................................... 264.3 Transformers .................................................................................. 304.4 Distribution Substations ................................................................... 334.5 Circuit Breakers, Switches, and Other Devices .................................... 34

5 Failure Cause Analysis 385.1 Overhead Lines ............................................................................... 385.2 Underground Cables ........................................................................ 415.3 Distribution Substations ................................................................... 445.4 Distribution Transformers and Devices ............................................... 47

6 Influencing Factors 516.1 Manufacture, Voltage Level, and Construction ..................................... 516.2 Time Period .................................................................................... 526.3 Geographical Location ...................................................................... 566.4 Age ............................................................................................... 586.5 Other Factors ................................................................................. 61

7 Impact of Extreme Weather 63

8 Conclusions 70

9 References 73

10 Appendix 1: Summary of Data Comparison 75Table A1-1: Comparison of Failure Rates for Overhead Lines .......................... 76Table A1-2: Comparison of Failure Rates for Underground Cables. .................. 77Table A1-3: Comparison of Failure Rates for Transformers. ............................ 78Table A1-4: Comparison of Failure Rates of Substation. ................................. 79Table A1-5: Comparison of Failure Rates for Circuit Breakers, Switches and

Other Devices. ................................................................................ 80

Page 10: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

11 Appendix 2: Failure Causes for Distribution Equipment 81Table A2-1: Failure Causes for Overhead Lines, All Sweden. ........................... 81Table A2-2: Failure Causes for MV Underground Cables, All Sweden. ............... 82Table A2-3: Failure Causes for Primary Substation, All Sweden. ...................... 83Table A2-4: Failure Causes for Secondary Substation, All Sweden. .................. 84Table A2-5: Failure Causes for Distribution Transformers, All Sweden. ............. 85Table A2-6: Failure Causes for Fuse or Apparatus Boxes, All Sweden. .............. 86

12 Appendix 3: Summary of Swedish Distribution Equipment Reliability Data on Hurricane Gudrun Day 87Table A3-1: Failure Rate of 10-20 kV Network Components on January 8,

2005, All Sweden. ........................................................................... 87Table A3-2: Failure Rate of 10-20 kV Network Equipment on Jan. 9, 2005, All

Sweden. ........................................................................................ 88Table A3-3: Number of Outages > 3 Minutes During Jan. 2005 on 10-20 kV

Networks, All Sweden. ..................................................................... 89Table A3-4: Variation of Failure Rate of 10 – 20 kV Bare Overhead Lines on

Jan. 8, 2005, All Sweden. ................................................................. 90Table A3-5: Variation of Failure Rate of 10–20 kV Insulated Lines in Air on

Jan. 8, 2005, All Sweden. ................................................................. 91

13 Appendix 4: Summary of Statistics on Hurricane Gudrun Day of E.ON Elnät Sverige AB 92Table A4-1: Failure Statistics of 10-20 kV Network Equipment on Jan. 8, 2005,

E.ON Elnät Sverige AB. .................................................................... 92Table A4-2: Number of Outages > 3 minutes During January 2005 on 10-20

kV Networks, E.ON Elnät Sverige AB. ................................................. 93Table A4-3: Variation of Failure Rate of 10–20 kV Bare Overhead Lines on Jan.

8, 2005, E.ON Elnät Sverige AB. ....................................................... 94Table A4-4: Variation of Failure Rate of 10–20 kV Aerial Insulated Lines on

Jan. 8, 2005, E.ON Elnät Sverige AB. ................................................. 95

Page 11: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

1

1 Introduction

1.1 Background

A distribution system consists of network components. Failures of the components can lead to a system failure. The component outages are the root cause of a system failure. In the risk analysis of a distribution system, the system performance can be estimated from the knowledge of the reliability data of individual system components. These data describe the component reliability and serve as input data for risk analysis of distribution systems. These data are valuable because they establish the feedback of data from the network operation field, help to identify network weak areas, and allow this feedback information to be used in system analysis and predicting the values in future.

Meaningful risk analysis requires reasonable and acceptable reliability data at component level. The quality of the data has fundamental importance for the risk analysis of a system. If the quality of the data cannot be guaranteed, the results of the reliability analysis will not make sense.

In the project performed previously, “Component Reliability Data for Risk Analysis of Distribution Systems’’ within the Elforsk R&D program “Risk Analysis 06-10’’, main effort has been expended in developing component reliability data and fundamental work with data collection and data processing of a large sample size of distribution outages reported by more than a hundred power utilities in Sweden during 2004 – 2005, [1]. However, the results of the component reliability data produced indicate that the significant variations in data statistics exist from company to company and from year to year. There was no detail analysis of this statistics and it was unclear why and by what these data variations were caused.

In order to aid in using the statistics and to understand the influencing factors behind the statistics, it needs analysis of the statistics and comparative studies. It is therefore intended that this project carries out such analysis and investigates differences in existing statistics from different data sources.

1.2 Purpose

The overall purpose of this project is to perform detailed study and analysis of existing component failure statistics, compare the results obtained from the previous project with the existing statistics in other countries, examine the influence factors, and analyze the major causes of component failures.

In order to gain better understanding and achieve a certain level of confidence in the use of component reliability data, it is expected that through the in-depth data analyses this project could provide more knowledge about

Page 12: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

2

component failure statistics and the relevant issues as influence factors, data variances, and causes of failures.

The objectives of the project are:

• Perform comparative study. Compare component failure statistics from different countries, such as Norway, Denmark, Finland, and Germany, as well as from IEEE publications. Compare the data with respect to data structure, component classification, and values of the statistics.

• Investigate influential factors. Study what factors that may affect the statistics and how. Identify failure sources that exist in the data.

• Deduce failure statistics of extreme events. Deduce component failure statistics of hurricane Gudrun based on outage reports from 2004-2005.

• Analyze major causes of component failures. Analyze failure distributions with respect to failure causes.

Page 13: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

3

2 Data Sources and Collection

Meaningful component performance statistics are en essential part of risk analysis of distribution systems. Many utilities and organizations throughout the world have established systems and procedures for collecting data and assessing the performance of their electric power equipment. Failure statistics have been topics for many years and failure and interruption data have been collected in various countries.

However, there are currently no standards generally accepted for data recording and collections. The survey of recorded information and data scheme used for deducing reliability data indicates that significant inconsistencies exist in the data categorization and collection processes in different countries and organizations.

Despite the fact that the comparisons may be difficult to make due to the differences in data collection methods employed, differences in system design and operation, and differences in the environments, the project tried to identify common data set and categories necessary to allow the comparison. When performing comparative studies, the differences between the collection methods and the differences in system and data items were studied. The issues and items studies are listed below:

• Power system characterization and voltage levels;

• Data categorization structures;

• Data collection methods and data collected;

• Classification of failure statistics and outage events;

• Typical parameters and key figures calculated to describe component reliability;

• Definitions of interruptions and outages;

• Interruption cause categories;

• Component classifications.

2.1 Data Sources

Electrical component reliability data are normally obtained from field outage records and equipment failure reports. The field data are first collected by operational and maintenance personnel together with the associated outage details. The field data are then analysed to create the statistical reliability data. Most utilities store interruption data in large computer databases. These databases normally have different functions for data processing. Some databases may be better organized than others for analyzing reliability data.

Some countries have established comprehensive computer systems for recording and assessing the performance of their power systems and have

Page 14: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

4

created national organizations for facilitating data exchanging. These organizations formulate procedures and manage centralized data collection and processing, and reporting reliability and outage statistics for electric networks and equipment.

In Sweden power utilities record and document the outages together with the associated details. Their outage statistics are annually reported to the national database, DARWin, maintained by Swedish energy industry organization (Svensk Energi AB). The DARWin is a comprehensive operation interruption and outage reporting computer system. This database is used to generate the national outage statistics, and gives annual reliability indices such as SAIFI, SAIDI for Sweden as a whole. Over a hundred electrical power utilities in Sweden participate in the data collection and reporting of the national interruption and outage statistics. The database covers all system voltages, and for distribution systems includes voltages of 0.4 - 24 kV. The data identify the major distribution equipment categories, including distribution lines and cables, transformers, fuse boxes, apparatus cabinets, and stations. The database provides fundamental statistics for the practical measure of the equipment performance. It is therefore used as an important Swedish data source in the comparative studies of the project.

An overview on the data sources is presented in Figure 2-1. Table 2-1 summaries outage occurrences and records collected in different sources.

More details about other individual data sources are described in the subsequent subsections.

Figure 2-1: Overview of the data sources.

Svensk Energi, EMI

Norway

Finland

Project data-base

Vattenfall

Fortum

E.ON Elnät

BCP

Denmark

IEEE, USAPoland

Svensk Energi, EMI

Norway

Finland

Project data-base

Vattenfall

Fortum

E.ON Elnät

BCP

Denmark

IEEE, USAPoland

Page 15: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

5

Table 2-1: Summary of data sources and outage records.

2.2 Norwegian Fault Statistics

The Norwegian power industry has long traditions in recording and utilisation of fault and interruption data. The need for national co-ordination of this work was early put into focus. To meet the quality requirements a concept for national collection and reporting of component fault and delivery point interruption data was developed in the 1990’s. This concept is denoted as FASIT (Fault And Supply Interruption information Tool) and has been in use since 1995. This system has become a national standard for collection, calculation and reporting of reliability data for all voltage levels above 1 kV and is in use by all network companies in Norway.

The main purpose of FASIT is to establish a nation-wide coordinated and standardized system for registration, reporting and analysis of failure and interruption data on all voltage levels. It consists of basic requirements, guidelines for data collection, and reporting schemes divided in three voltage levels (< 1 kV, 1-22 kV and > 33 kV). FASIT is mainly designed for collecting power system performance, but it is coordinated with a component-oriented system. Information stored about components and delivery point records can be used together with the FASIT reports to generate useful statistics.

The FASIT system enables to record information about:

• Faults on electric equipment and related information about the failure events (date, type, fault description, component, cause etc.).

• Delivery point interruptions.

• Restoration times.

Sustained outages > 3min Outage occurrencesSouce 2004 2005 2006 2007

Svensk Energi DARWin 42 152 59 296 48 162 52 951Fortum Distribution 8 373 8 096Vattenfall Eldistribution AB 11 390 14 850Eon Elnät Sverige AB 11 674 23 096Norwegian FACIT system: outage statistics 1 - 22 kV, 1996 - 2007Danish national outage statistics 6 - 22 kV, 1998 - 2007Finnish national statistics 2005Vattenfall Distribution Poland, transformer statistics 2007 - 2008 BCP data: based on statistics in Germany and Switzerland before 2006IEEE equipment surveys from 1976 - 1989 USA data: based on average statistics before 1998

Page 16: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

6

• Fault consequences (affected delivery points, ENS etc.)

Various time intervals during the restoration procedure following an outage can be recorded in FASIT. From 2006 reporting of short interruptions (≤ 3 minutes) became mandatory in Norway. Typical statistics related to restoration times comprise distribution of turnout times for different events and districts, average sectioning time per outage, distribution of fault localisation times for different component types, and average repair time per component.

Typical fault statistics produced by the FACIT are the number of faults on various components per year, distribution of fault causes, the number of faults on different sub-components, types, manufacturers, etc, and distribution of fault detection methods.

The FASIT system has provided the Norwegian power industry with a practical tool for recording and reporting faults on both power systems and network components. It supports various analyses related to planning and operation of the power system. This standardized system makes it possible for all Norwegian power utilities to collect data on the same basis and facilitates centralized data processing and reporting. The registered interruption and failure data in FACIT serve as foundation for deducing component statistics and calculating key figures.

2.3 Danish Fault Statistics

The Danish Regulatory Authority pays great attention to the quality of supply and has thus implemented a reporting scheme. Most Danish DNO’s have reported faults and outages to the DEFU for more than 30 years. All customer interruptions caused by incidents are registered from high voltage down to 10 kV. This registered information can be combined with similar information for the low voltage networks and hence make it possible to estimate fault statistics.

In order to provide statistical figures and descriptions to illustrate the structure and most recent development in Danish electricity supply, statistical reports on performance of power networks and equipment are regularly published in Denmark. The predominant part of the data basis was collected and processed by Danish Energy Association from the energy companies.

According to the general principles in the guidelines for recording interruptions to supply of the Danish Energy Regulatory Authority, every DNO must record information about interruptions to supply lasting one minute or longer. All voltage levels are to be included. From 1st of January 2006 every fault in the high voltage grid must be recorded, and this is extended to include the low voltage grid from 1st of January 2007. Once a year the DNO’s must report network performance key figures to the Danish Regulatory Authority. For each fault that causes an interruption of supply to one or more customers for one minute or longer the DNO has to register the following as a minimum:

Page 17: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

7

• Date and time;

• Duration;

• Number of disconnected customers;

• Disconnected HV points;

• Voltage level;

• Whether the interruption was a planned or forced;

• Cause of the fault.

At low voltage level outages causes by faults are registered at feeder level. In case of a fault that results in disconnection of the low voltage feeder, the feeder designation, the outage duration and the number of customers must be recorded.

In Demark the network operators record information about every fault that causes interruption to supply. Since the middle of 60ies faults and interruptions in the Danish networks have been subject to statistical treatment. Distribution and transmission network companies carry out statistical survey on a voluntary basis and most of the companies have actually participated in this survey since the very beginning. From the early 70ies interruptions and failures in the 10-400 kV networks have been treated statistically. In the year 2004, about 80% of the 10-20 kV networks were represented in the statistical survey.

Danish power utilities update continuously their data collection and failure statistics. All voltage levels (i.e. 0.4, 10-20, 30-60, 132-150 and 400 kV) are now included. In the end of 2007 the statistics cover nearly 90% of the country’s electric supply on 6-25 kV networks. This results in significant data material for various statistical analyses. At component level the failure statistics can be deduced for 10 year’s periods. The two types of statistics are generated and reported regularly:

• Component failure statistics, including main causes of the recorded component failures and the number of faults in various types of components.

• Interruption statistics, which describes the number and duration of customer outages at various power delivery points.

2.4 Finnish Fault Statistics

The electricity distribution utilities in Finland have collected national interruption statistics from the beginning of the 70’s and an annual summary report has been published by the Finnish Energy Industries association(ET). The network companies deliver annually to the Energy Market Authority ten key indicators of interruptions. These indicators relate to the reliability of electricity distribution and include the duration and number of unexpected and planned interruptions as well as a number of auto-reclosings and interruptions

Page 18: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

8

on low-voltage networks. Some of the key indicators are weighted with the annual energy fed from secondary substations.

In order to produce more detailed data and enable better classification of interruption causes, from 2005 the publications of interruption statistics have changed quite radically. The new method for fault reporting is based on the examination of interruptions in medium voltage networks. The network utilities register and report to ET about information of each individual interruptions. Special attention has been focused on which kind of network components (overhead line, cable etc.) the interruption has occurred on. This makes the information about networks types, and the number and duration of interruptions to be obtained in more detail.

In Finland the fault statistics concentrate on the interruptions experienced by the customers. Attention has been paid to the network structures, i.e. overhead line or cable networks, and to the causes of the interruptions.

Finnish distribution networks consist mainly of overhead lines. At 0,4 kV level about 4% of the lines are overhead lines, 66% aerial cables and 30% underground cables. At 1–45 kV level 84,6% of the lines are overhead lines, of which 5,4% with covered conductors, 0,4% aerial cables, and 9,6% underground cables. The Finnish fault statistics are based on the reports from 59 (out of 90) distribution network companies, which cover approximately about 82% of the whole networks in proportion to the total length of the medium voltage networks.

2.5 Norstat Statistics

In the Nordic countries there has been a co-operation on the transmission level for many years to standardise fault statistics. On the distribution level there is work going on to standardise the fault collection and reporting as well. A joint Nordic working group, named Norstat, was established in 2005 to maintain the guidelines and to publish annual interruption statistics of each country.

The published Norstat statistics cover a significant part of the 1-70 kV networks in he Nordic countries. The figures are broken down into two intervals, 1-39 kV and 40-70 kV. However the fault and interruption statistics published in the Norstat report are for very limited time of periods. Only the data for the year 2005 are available.

The Norstat statistics cover approximately 80-90% the Nordic 1-39 kV networks and 80-95% the 40-70 kV networks in Denmark and Norway. Due to limited data comparability the data are used at a more aggregated level than actually described in the guidelines.

Fault frequencies are deduced for the selected major components. The fault frequencies are at a comparable level in the four countries, but some minor differences can be observed. The Norstat component failure statistics for a single year must be used with great caution.

Page 19: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

9

The Norstat report [22], which is the first annual statistics published by the working group, presents some of the available statistical figures, these statistics are used as a data source for the project.

2.6 Fault Statistics from Other Data Sources

IN 1975, the Canadian Electrical Association (CEA) created a facility for centralized collection, processing and reporting of reliability and outage statistics for electrical generation, transmission and distribution equipment. To coordinate the development of this Equipment Reliability Information System CEA constituted the Consultative Committee on Outage Statistics. The outage statistics made available through this collection and analysis process are sufficient for evaluating the reliability of generation, transmission and distribution systems.

Canadian Fault Statistics

All the major electric power utilities in Canada participate in a single data collection and analysis system called the Equipment Reliability Information System (ERIS). CEA started firstly collecting data on generation equipment in 1977. The second stage was on transmission equipment in 1978. The third stage, dealing with distribution equipment, was completed in 1993, and Canadian utilities are now supplying data based on agreed procedures.

The ERIS system identifies the states of power equipment and provides continuous records of the operating and outage history of power equipment. The ERIS database contains over hundreds of thousand components and consists of six related entities: utility, manufacturer, outage cause, equipment, configuration and event. One can gain access to the database by utility or manufacturer or equipment or cause and of course retrieve events according to these parameters.

Distribution equipment reporting system deals with seven major components of distribution equipment: lines, cables, power and distribution transformers, switching devices, regulators and capacitors. The database contains design information for all components as well as details on all forced outages that occurred. This is collected for each participating utility. Every change in the equipment state is monitored and thus a wealth of statistics can be produced. The following statistics can be determined for each component and for each voltage classification:

• Number of outages (incl. number of forced outages);

• Equipment failure rate (incl. forced outage rate);

• Total outage time;

• Mean duration;

• Unavailability.

The top causes of outages are identified in each equipment categories. The above statistics can be compiled by primary cause, failure mode, interruption

Page 20: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

10

medium, and system structure. The equipment status report containing the failure statistics is published annually.

The IEEE Society conducts surveys on the reliability of electrical equipment in industrial and commercial installations. Each survey has a defined objective of obtaining field data on electrical equipment failure characteristics. The failure characteristics of individual pieces of electrical equipment are described by the following basic reliability statistics:

Fault Statistics from IEEE and USA

• Failure rate, expressed as failures per year per component (failures per unit-year).

• Downtime to repair and replace a component after it has failed in service, expressed in hours per failure.

• In some cases, probability of operating.

The statistics from IEEE publications and reports available for the project consist of two parts, Part 1, most recent equipment reliability surveys conducted between 1976 and 1989 and Part 2, equipment surveys conducted prior to 1976. The reliability data collected by the IEEE surveys cover the data for major equipment categories of lines and cables, transformers, motors, circuit breakers, generators, switchgear bus, switches, bus ducts, cable joints, cable terminations, inverters, rectifiers.

The equipment reliability data from USA are mainly based on the publications of the results of nationwide surveys of recorded information and equipment failure statistics. The reliability data presented and suggested for use in reliability analysis in some papers from USA are also used for the comparative studies of the project.

Vattenfall Distribution Poland collects data on equipment performance. The data contains interruptions that occur on distribution networks due to failures on, among other equipment, distribution lines and cables, as well as power and distribution transformers.

Fault Statistics from Vattenfall Distribution Poland

The company has performed a number of studies on equipment reliability. Associated with these studies, the characteristics and variations of the reliability data were examined. The significant results obtained from the data studies were used in the project.

Over recent years, there has been a significant development in software for reliability analysis of power systems. Busarello Cott Partner Inc. (BCP) in Switzerland is one of the developers of such computer programs. NEPLAN,

BCP Fault Statistics

Page 21: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

11

developed by BCP has become one of the important tools for power network reliability analysis.

In order to provide the NEPLAN program with the default reliability input data, BCP studied and collected equipment failure statistics required for reliability assessment mainly from European countries. The BCP databank contains fault statistics for MV networks including major component categories: station, transformer, overhead-line, cable, and switch devices. Since the BCP statistics are based on equipment performance records in European countries and are relevant for the comparison. They are therefore used as a data source in the project.

Page 22: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

12

3 Data Structure and Categorization

Reliability of electric power systems is an important issue for the society. Security and service interruptions at the distribution level are the primary concern of the end-use customers. Much effort has been expended in developing procedures and methods in order to assess uniformly and consistently the reliability of distribution systems based on past performance. However, the results of survey of recorded information used for deducing equipment failure statistics and for calculating distribution reliability in different countries indicate that significant inconsistencies exist in the data, in the collection processes, and in the data categorization.

Although many questions have been answered about the component reliability, there are still no generally accepted standards for recording or measuring interruptions and component failure events. Presently there are no standardized ways to compare and track component reliability among different utilities and different countries.

This Chapter gives an overview of data characteristics and categorization structures in different data sources necessary for data comparison. The similarities and consistence that exist among different data sources are given in the subsequent sub-sections. The characteristics of overall data scheme and structure presented include:

• System characteristics;

• Equipment categories;

• Reliability data measurement;

• Data collected and process;

• Interruption causes and durations;

• Restoration methods.

3.1 System Characterization

Network categorization is necessary for data comparison of distribution equipment and is an important issue for data collection system. The characterizations of utility distribution systems are usually categorized by voltage level, customer density or type of distribution lines.

IEEE Task Force on Interruption Reporting Practices defined the characterizations of the utility system by the customer density per kilometre [2]. The networks are broken into the three categories as below:

• Rural networks (less than 31 customers/km);

• Suburban networks (31 though 93 customer/km);

• Urban (greater than 93 customers/km).

Page 23: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

13

In Norwegian fault reporting system FACIT, the distribution networks are classified into three groups for calculation of key figures:

• Overhead line distribution network (with more than 90% overhead line length);

• Cable distribution network (with more than 90% cable length);

• Mixed distribution network (with less than 90% overhead line and cable length).

Voltage level is generally used to categorize the networks. Two voltage levels are normally utilized: low-voltage (LV) (0,4 kV, < 1kV), and medium-voltage (MV). Table 3-1 summarizes the network categorizations used in different countries.

Table 3-1: Network categorizations used in different countries.

3.2 Equipment Classification

In order to provide the means for recording the outages, distribution equipment are divided into a number of component categories, thus the distribution systems can be treated as component-oriented. Several major component categories are normally used for this purpose, each of which is

Sweden Norway Finland

Distribution LV network: 0,4 - 1 kV; Distribution MV network: 10 - 24 kV.

Distribution overhead line network (with more than 90% overhead line). Cable network (with more than 90% cable), Mixed network (with less than 90% overhead line and cable). < 1kV, 1 - 22 kV.

Distribution LV network: < 1 kV; Distribution MV network: 1 - 35 kV.

Denmark BCP IEEE Task Force suggestion

Distribution LV network: 0,4 kV; Distribution MV network: 6-25kV.

Distribution network: 10 kV, 20kV

Rural system (less than 31 customers/km), Suburban system (31 - 93 customer/km), Urban system (more than 93 customers/km). LV, 5 kV; 15 kV; 25 kV; 35 kV.

Page 24: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

14

further divided into sub-categories in order to identify more precisely which part of the major component was involved or damaged in the outage. From fault data, outage statistics can be calculated and the reliability data for each type of component can be made.

In most of the data collection systems the following distribution equipment are selected as major components:

• Distribution line;

• Distribution cable;

• Power and distribution transformer;

• Switching device;

• Protection device.

All major components may be classified according to their distinguishing characteristics, such as voltage class, manufacturer and rating, so that each major component is grouped sufficiently well for describing its performance.

Two kinds of sub-components are generally recognized: those that are integral to the major component and those that are peripheral subcomponents. The peripheral subcomponents may cover such items as control and protection equipment, surge arrester, busbar, voltage and current transformer.

In 2006 IEEE Task Force on Interruption Reporting Practices provided a recommended list of equipment classification for examining equipment performance [2]. This equipment is usually failed network component that initiated the customer interruption.

• Cable;

• Wire;

• Control;

• Interrupting device;

• Lightning/surge arrester;

• Other equipment;

• Structural support;

• Switch;

• Transformer.

In this IEEE classification, the cable category includes all cable that is direct buried or encased in pipe or conduit. Wire refers to overhead strung conductors and jumpers. The control category contains control equipment. The interrupting device category consists of circuit breakers, re-closers, and fused equipment. The structural support category includes poles, etc. The switch category contains disconnect or isolation device, load break switch, etc.

Page 25: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

15

The category transformer can include current, distribution, grounding, voltage and power transformers.

In Norway the equipment is structured in a three level hierarchy: unit, major component and sub-component. The unit is highest level in the hierarchy and may contain a group of component as transformer station.

Table 3-2 gives an overview of the component categories used in different countries and databases. It can be seen that some use broad categories only, and some classifications contain more items for fault reporting.

Table 3-2: Overview of equipment classification.

3.3 Measures of Component Reliability

Component reliability data describe reliability of distribution equipment. The reliability data have been defined to monitor frequency and duration of component failures. There are two basic categories of the reliability data: frequency-oriented data and duration-oriented data.

From component outage data collected the statistics can be calculated to provide both a measure of component past performance and a forecast of

Sweden Norway Finland Denmark

Open wire bare conductor line; Open wire insulated line; Aerial cable; Aerial spiral cable; Underground cable; Distribution transformer; Circuit breaker (indoors, outdoors); Switch (indoors, outdoors); Load switch; Fuse and apparatus box; T-junction cable cabiet; Secondary substation; Unknown.

Line; Cable; Power transformer; Distribution transformer; Circuit breaker; Load-switch; Fuse; Busbar; Secondary substation; Surge arrester; Voltage transformer; Current transformer; Control; Others.

Bare conductor line; Covered conductor line; Underground cable; Transformer station; Circuit breaker; Disconnector.

Overheadline; Surge arrester; Underground cable; Cable equipment; Circuit breaker; Switch devices; Transformer.

Norstat BCP Canada IEEE Task Force suggestion

Overhead line (uninsulated, insulated); Cable (underground cable, oil-paper cable, XLPE cable); Secondary substation; Power transformer; Circuit breaker; Load break switch; Disconnectors; Unknown.

Overheadline; Cable; Transformer; Circult breaker; Disconnector switch; Busbar; Compact station; Inhouse station; Tower station.

Distribution line; Distribution cable; Distribution transformer; Power transformer; Switching device.

Cable; Wire; Connector; Control; Interrupting device; Lightning/surge arrester; Other equipment; Structural support; Switch; Transformer.

Page 26: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

16

expected performance in the future. Equipment failure rate and repair time are the two main categories of parameters that would be calculated from the collected data. By combining a wide variety of information on the performance of distribution equipment, various parameters may be deduced to describe component reliability, which include:

• Momentary component failure rate: the frequency of faults that will clear themselves if the fault site is de-energized and then re-energized.

• Sustained failure rate: the frequency of faults that requires repair.

• Repair time/outage time/downtime: the time it takes to repair a component outage/failure.

• Unavailability: the production of failure rate and downtime in year expressed as a percentage.

The statistics are normally calculated on the basis of component unit-years or kilometre-years. Since the major components are classified into types, it will be possible to obtain these statistics for each classification.

Almost all the countries consider sustained outages. Some of them consider also transient or momentary outages. However the definition of a sustained outage may vary from country to country. Many power utilities consider any outage longer than one minute to be permanent while many define outages longer than three or five minutes as sustained. In practice, there may be little difference in the results because of the different durations used for deducing statistics.

In Norway and Finland several interruption durations are considered in deducing failure statistics, including transient outages of 0-3 minutes, and sustained outages longer than three minutes.

3.4 Data Collected and Data Processing

The reliability data are basically calculated from historical statistics of component performance. Collecting suitable data is therefore essential for deducing failure statistics. The data collected must be sufficiently completed to ensure to produce desired statistics, but restrictive enough to ensure no to collect unnecessary data items.

The basic information collected is data items related to system failure events, which are component outages or customer interruptions. Each failure event is taken into consideration and recorded according to causes of failure, duration of outage, and area of the system affected, etc. The Data collected are normally by number of interruption events, number of customers affected, or by duration of the interruption. Results from this data may reveal rates of failure for various types of equipment.

The completeness of data items collected varies from country to country. However most of the countries established the basic form as standard for

Page 27: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

17

utilities to collect failure data. In their data base the emphasis is on system and component failures. For every failure the data collected in the basic form generally include:

• Date of fault occurrence;

• Fault start time and end time;

• Total time (in minutes or hours) until the last customers are restored;

• Number of MV/LV power stations involved;

• Cause of the fault;

• On what equipment did the fault occur;

• Components affected;

• Maximum unavailable power;

• Description of the event in order to understand what happened.

Data collection systems range from manual collection system to computer based outage management system. Typically, majority of power utilities and most of countries have implemented computer outage management system for data collection and processing.

The various types of computer software for the processing of the data collected on power equipment were developed. In some countries the software developed for processing of the data collected on distribution equipment uses the transmission system software as a model and meet the same basic system requirements.

For data processing the computer database normally contain several related entities, such as utility, manufacturer, outage code (cause, time duration, etc.), equipment, network configuration, etc. One can gain access to the database by utility or manufacturer or equipment or outage code to generate relevant statistics.

Although there are similarities among the data processing systems, the differences exist between the data collection methods and in system design that could make the comparison difficult. Examples of the types of items that may be relevant are ability to collect interruption data, use of step restoration when collecting interruption data, determination of the start time and end time, definition of sustained interruption (may ranging from greater than 1 minute to greater than 5 minutes), definition of a customer, etc.

3.5 Interruption Causes

The historical data is very useful when analyze failure statistics to ascertain what went wrong in the past. To increase distribution reliability it is necessary to understand the causes of outages. Knowing the cause of an outage can help to reduce the number of specific types of outages. For example, if lightning is a major cause of outages, then lightning arresters can be installed. Tracking outage causes allows power utilities to correct a known

Page 28: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

18

problem. When recording failure events, it is useful to record some specific causes.

Classification of interruption causes has been an important issue in data collection. A component forced outage has been defined in terms of the following primary causes in some data collection systems:

• Defective equipment;

• Adverse weather;

• Adverse environment;

• Human factors;

• Foreign interference;

• Unknown.

The IEEE Task Force on Interruption Reporting Practices suggested ten general interruption cause categories for comparison in benchmarking studies [2]. These are intentionally broad categories that will make possible more precise comparisons between different distribution utilities. There are numerous categories that could be chosen, but with the goal of uniformity for comparison purposes, the Task Force recommended the following categories:

• Equipment;

• Lightning;

• Planned;

• Power supply;

• Public;

• Vegetation;

• Weather (other than lightning);

• Wildlife;

• Unknown;

• Other.

The IEEE Working Group on System Design conducted three surveys on distribution reliability index usage. The surveys gave the most commonly used cause codes [3], and the top ten of them are listed below:

• Tree;

• Animal;

• Unknown;

• Lighting;

• Equipment;

• Error;

Page 29: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

19

• Overload;

• Storm;

• Dig in;

• Vandalism.

The IEEE Interruption Reporting Practices Task Force suggested weather related sub-cause as below, and recommended to include interruptions due directly to a weather phenomenon where the weather caused the interruption.

• Wind;

• Snow;

• Ice;

• Hail;

• Rain.

Table 3-3: Overview of cause classification.

Sweden Norway Denmark

Weather related (tree falls, snow, wind, ice, thunder, rain); External influences (environment related, animal, digging, sabotage, salt, traffic); Material defect; Technique related; Dimensioning failure; Operation and people related (lack of maintenance, overloading, improper method, improper montage, faulted operation).

Environment related (thunderstorm, vegetation, wind, snow, salt, animal); Human being related; Operating stress; Construction/montage; Technical equipment, Not classified cause, Others.

Weather related (thunder, wind, storm, ice, salt, and rain); Other outside influence; Operation and maintenance; Staff error; Montage fault; Equipment failure; Material, construction and dimensioning failure; Others; Unknown.

Norstat Canada IEEE Task Force suggestion

Wind, storm; Ice, snow; Lightning; Other nature related; Animals; Digging/excavations; Work/testing; Fire/explosion; Staff; Maloperation; Other people/extenal; Insufficient maintenance; Construction error; Ageing; Wear and tear; Corrosion; Leakage; Other technical equipment; Impact due to other faults; Unknown.

Defective equipment, Weather; Adverse environment; Human element; Foreign interference; Tree contacts; Personnel error; Unknown.

Equipment; Lightning; Power supply; Public; Vegetation; Weather (other than lightning); Wildlife; Unknown; Other.

Page 30: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

20

Table 3-3 gives an overview of interruption causes used by different countries and organizations. In Denmark the failure causes include both immediate causes and underlying causes [4]. The immediate causes include thunderstorms, other nature-related events, other external influences, staff fault, operating, and unknown. The underlying causes include material failure, montage failure, operation and maintenance, and others. The weather related outages are classified further to sub-causes: thunder, wind, storm, ice, salt, and rain.

In Norway the outage causes are divided into environment related, human being, operating stress, construction/montage, technical equipment, not classified cause, others [5]. The major part of the outages was normally environment related. The sub-causes for environment related outages include thunderstorm, vegetation, wind, snow, salt, animal, not specified, and others.

Page 31: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

21

4 Comparison of Reliability Data

Tracking information about equipment failure can allow utilities to monitor equipment performance and improve system reliability. In order to supply detailed information about component failure statistics, this Chapter give a comparative overview of the statistics from different sources available to the project.

Although there is a considerable variance in statistics and in the way to produce the statistics among the different databases, the project attempts the comparison based on the similarities and consistency existing in the different data sources. The comparative studies are made on major categories of distribution equipment including:

• Distribution lines;

• Distribution cables;

• Transformers;

• Sub-stations;

• Circuit breakers, switch devices, and other devices.

The subsequent sub-sections describe the studies of each type of components.

4.1 Distribution Lines

Distribution lines are important distribution equipment. Because this type of equipment is directly exposed to weather, vegetation, and animals, it typically has higher failure rates than distribution underground cables. Failure rates of distribution lines are normally very system specific due to their dependence on environment, and therefore could vary considerably.

Figure 4-1 and 4-2 show the average reliability values of all Sweden for LV and MV overhead lines. It is seen that the values of the failure rates have large variations and the values of 2005 are very high.

Figures 4-3, 4-4, and 4-5 show the data from Norway. Figures 4-3 and 4-4 show the development of the average fault rates for MV overhead lines in the period 1989 – 2005.

Figure 4-6 presents the interruptions caused by failures on overhead lines in Denmark. The failures were from reports registered on overhead lines and associated construction equipment, as insulators. As the figure indicates, the number of interruptions due to failures on the overhead line construction in 2005-2007 is above the average of 10-year period. The number of failures on the overhead line network is heavily dependent on the weather.

Page 32: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

22

Failure rates of LV overhead lines (sustained outages), Sweden

010203040506070

2004 2005 2006 2007 Ave 2004-2007

Fa

ilure

rate

s (f

/100

km.y

r) Bare conductor

Inslulated

Overhead lines

Figure 4-1: Failure rates of LV overhead lines, Sweden.

Failure rates of MV overhead lines (sustained outages), Sweden

0

5

10

15

20

2004 2005 2006 2007 Ave 2004-2007

Fa

ilure

rate

s (f

/100

km.y

r)

Bare conductor

Inslulated

Overhead lines

Figure 4-2: Failure rates of MV overhead lines, Sweden.

Page 33: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

23

Figure 4-3: Failure rates of MV overhead lines, Norway. From [6].

Figure 4-4: Failure rates of MV overhead lines, Norway. From [5].

Page 34: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

24

Figure 4-5: Average reliability values of distribution networks, From [8].

Figure 4-7 compares the values of Sweden with the statistics of Norway and Denmark. It is seen that the average values of Sweden is approximately twice as high as the values of Norway and Denmark. Table A1-1 in Appendix 1 summarizes the statistics from all the sources. The comparison of the statistics shows that there are large variations in failure rates reported from different sources. This may be due to that the failure rates of overhead lines are very dependence on weather and environment.

An important reliability parameter of overhead distribution systems is the temporary failure rates of overhead lines. Unfortunately available data are scare. The number of observed failures was relatively too small in Sweden to allow acceptable estimations of transient failure rate to be made. The project could not therefore make comparison of reliability data for transient failures.

Annual number and duration of interruptions at the distribution level, 1995 - 2000

012345678

Number of interruptions Annual interruption duration

Num

ber

or h

ours

per

yea

r

Overhead networkCable network

Norway

Annual number and duration of interruptions at the distribution level, 1995 - 2000

012345678

Number of interruptions Annual interruption duration

Num

ber

or h

ours

per

yea

r

Overhead networkCable network

Norway

Page 35: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

25

Figure 4-6: Failure rates of overhead lines, Denmark. From [4].

Failure rates of distribution overhead lines (sustained outages)

0

5

10

15

20

2004 2005 2006 2007 Ave 2004-2007

Fa

ilure

rate

s (f

/100

km.y

r)

10-20 kV lines, Sw eden 1-22 kV lines, Norw ay

6-25 kV lines, Denmark

Figure 4-7: Comparison of failure rates of overhead lines.

Page 36: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

26

4.2 Distribution Cables

Although the majority of distribution systems are overhead, underground distribution networks are steadily increasing in population. Underground equipment is sheltered from weather and vegetation, and usually has lower failure rates than corresponding overhead equipment.

Figure 4-8 gives an overview of Swedish statistics of underground cables. The values were quite stable during 2004-2007 and are less than one fifth of the failure rates of overhead lines in average.

Failure rates of underground cables (sustained outages) Sweden

0

1

2

3

4

2004 2005 2006 2007 Ave 2004-2007

Failu

re ra

tes

(f/1

00km

.yr)

LV underground cablesMV underground cables

Figure 4-8: Failure rates of distribution cables of Sweden.

Figures 4-9 and 4-10 present an overview of the statistics from Norway. The failure rates for the cables have been deduced for both permanent and transient failures. In annual average of the period of 1996-2005, approximate 96% of all registered cable faults are permanent, while transient faults are only 4%.

The data of Denmark are shown in Figures 4-11, 4-12, and 4-13. As Norwegian statistics, very little bit of total cable faults is transient. The number of interruptions caused by failure of oil/paper-insulated APB-cables is shown in Figure 4-11. The statistics are expressed in per 100 km APB cable and include only faults on the cable itself. The number of disruptions caused by failures of PEX-cables is shown in Figure 4-12, and has remained at the same level as the 10-year’s average during the last three years. Historically, the failures of per 100 km PEX-cable are 4-5 times lower than the number of failures per 100 km APB-cable. The faults caused by defects in the cable equipment are calculated for two common types of cables. The failures on the cable equipment, including cable joints, etc. are compiled together for both APB and PEX cables and are summarized in Figure 4-13. The failure rates of cable equipment were recorded per 100 km cable due to that the number of the equipment is usually not fully known.

Page 37: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

27

Figure 4-9: Failure rates of underground cables, Norway. From [5].

Figure 4-10: Failure rates of underground cables, Norway, From [7].

Page 38: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

28

Figure 4-11: Failure rates of distribution cables, Denmark. From [4].

Figure 4-12: Failure rates of distribution cables, Denmark. From [4].

Page 39: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

29

Figure 4-13: Failure rates of cable equipment, Denmark. From [4].

The Swedish values are compared with the data from other sources. Table A1-2 in Appendix 1 summarizes the results. Compared the Swedish data with the statistics from Norway and Denmark in Figures 4-14 and 4-15, it is seen that the failure frequencies of all types of cables are in principle at the same level in the three countries. The PEX-cables however show a significantly lower failure rate. The analysis of the data in the table A1-2 reveals that the variations in the data collected from different sources exist, but they are not as large as that in the data of overhead lines.

Page 40: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

30

Failure rates of underground cables (sustained outages)

0,00,51,01,52,02,53,0

2004 2005 2006 2007 Average2004-2007

Failu

re ra

tes

(f/1

00km

.yr)

Cables, 10-20 kV, Sweden Cables, 1-22 kV, NorwayAPB-cables, 6-25 kV, Denmark PEX-cables, 6-25 kV, Denmark

Figure 4-14: Comparison of failure rates of underground cables.

Failure rates of underground cables (sustained outages)

0,00,51,01,52,02,53,0

2004 2005 2006 2007 Ave 2004-2007

Fai

lure

rate

s (f/

100k

m.y

r)

Cables, 10-20 kV, Sw eden Cables, 1-22 kV, Norw ay

Cables (APB+PEX), 6 - 25 kV, Denmark

Figure 4-15: Comparison of failure rates of underground cables.

4.3 Transformers

Reliability data on transformers are necessary for risk analysis of power system reliability. Results of studying transformer failure statistics are presented in Figures from 4-16 to 4-19 and Table A1-3 in Appendix 1.

The Norwegian statistics are shown in Figure 4-16 where both transient and permanent faults are included. The statistics confirm the fact that most of transformer failures have long durations.

Page 41: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

31

Figure 4-16: Failure rates of distribution transformers, Norway. From [5].

Figure 4-17: Failure rates of distribution transformers, Denmark. From [4].

Page 42: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

32

The number of faults per 100 distribution transformers at 6-25 kV from Denmark can be seen in Figure 4-17. The failure rate of transformers for 2007 is slightly below the average for the latest ten-year’s period. Transformer faults, however, like the failures of disconnectors and switches, are relatively rare.

Vattenfall Distribution Poland studied the faults on their MV transformers recorded during the period 2004-2009. The results of the study are given in Figure 4-18. The failure rates vary within 0,5-0,8 failure/100unit.month.

Failure rates of VDP

0,73

0,80

0,59

0,64

0,55

0,64

0,68

0,0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1,0

Jan-

04

Feb-

04

Mar

ch-0

4

Apr-

04

May

-04

June

-04

July

-04

Aug-

04

Sep-

04

Oct

-04

Nov

-04

Dec

-04

Jan-

05

Feb-

05

Mar

ch-0

5

Apr-

05

May

-05

June

-05

July

-05

Aug-

05

Sep-

05

Oct

-05

Nov

-05

Dec

-05

Jan-

06

Feb-

06

Mar

ch-0

6

Apr-

06

May

-06

June

-06

July

-06

Aug-

06

Sep-

06

Oct

-06

Nov

-06

Dec

-06

Jan-

07

Feb-

07

Mar

ch-0

7

Apr-

07

May

-07

June

-07

July

-07

Aug-

07

Sep-

07

Oct

-07

Nov

-07

Dec

-07

Jan-

08

Feb-

08

Mar

ch-0

8

Apr-

08

May

-08

June

-08

July

-08

Aug-

08

Sep-

08

Oct

-08

Nov

-08

Dec

-08

Jan-

09

Feb-

09

Mar

ch-0

9

Apr-

09

May

-09

June

-09

July

-09

Aug-

09

Sep-

09

Oct

-09

Nov

-09

Dec

-09

failu

res

/ 100

* pcs

MV transformers failure rate

Figure 4-18: Failure rates of MV distribution transformers during

2004-2009, Vattenfall Distribution Poland.

Lund University in Sweden conducted a study of “Distribution System Component Failure Rates and Repair Times’’ [10]. The study presents the results of a literature search for reported failure rates and repair times, based on operational experience, for distribution system components. As important observations it was concluded that the sustained failure rates for MV/MV transformers published during the recent decade indicate a variation of the average transformer failure rates in the range of 0.4-1 failures/100units.year.

As a comparison, Figure 4-19 and Table A1-3 in Appendix 1 give an overview of the statistics from different sources. It is observed that the statistics from major sources indicate the failure rates of distribution transformers lower than 1 failure/100units.year.

Page 43: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

33

Failure rates of distribution transformers (sustained outages)

0,960,79

0,12

0,63

0,29

0,0

0,2

0,4

0,6

0,8

1,0

1,2

1

Fai

lure

rate

s (f

/100

units

.yr)

Sweden, 2004-2005 All Norway, 1997-2006 All Denmark, 1998-2007 Poland, 2005-2007Germany, Switzerland, before 2006

Figure 4-19: Comparison of average failure rates of distribution transformers.

4.4 Distribution Substations

Distribution stations like other network components may experience reliability problems associated with weather and environment. Vattenfall Distribution Sweden estimated the reliability of their substations based on the failure statistics before 2006. These data are given in Table 4-1 below.

Table 4-1: Failure rates of substations, Vattenfall Distribution Sweden.

Figure 4-20 shows the trend in the number of faults on the 6-22 kV distribution delivery and customer connection points of Danish power systems in the period of 1998-2007. As an average in Denmark, 2,85 sustained interruptions occur per 100 stations per year.

A comparison of Swedish data with Danish statistics is made in Table A1-4 in Appendix 1. Since there is a lack of the statistics of substations from other sources, the comparison of Swedish data with other statistics cannot be conducted.

Station Failure rates (f/100units.yr)

Pole station 10 - 20 kV 2,00Metal-plate station 10 - 20 kV 1,60Concrete station 10 - 20 kV 1,50Cable cabinet 0,4 kV 0,60

Page 44: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

34

Figure 4-20: Failure rates of 6-25 kV stations, Denmark. From [4].

4.5 Circuit Breakers, Switches, and Other Devices

In Sweden there are not so much statistics available for describing reliability of circuit breakers and switch devices. Some data from Swedish power utilities are therefore used in the comparative study.

In Norway a comprehensive data basis on component faults is established continuously over the years from 1989 for all network voltage levels. Through the database it is possible to extract fault statistics for individual types of components and to produce the distributions of failure rates over the years. Figures 4-21 and 4-22 present the Norwegian failure statistics for circuit breakers, load-disconnectors, and switch devices over ten-year’s period.

Figure 4-23 shows the development of frequencies caused by failures on the circuit breakers and load disconnectors in Denmark. The number of faults on the circuit breakers is stable in the 10-year’s period. Only minor variations from year to year were observed. During the latest three years, the number of permanent faults has been roughly constant with approximately 0.1 failures per 100 units per year.

To maintain the quality level of power supply, Denmark has put continuously efforts on monitoring the continuity of supply. In their power system outage data collection and reporting database the distribution equipment units were defined to include even the disconnectors, switch devices, and surge arresters. This allows good statistics in ten-year’s period for these devices produced. Figures 4-24 and 4-25 summarize the values for these components.

Page 45: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

35

Figure 4-21: Failure rates of circuit breakers, Norway. From [6].

Figure 4-22: Failure rates of load-disconnectors and switch devices, Norway. From [6].

Page 46: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

36

Figure 4-23: Failure rates of circuit breakers and load-disconnectors, Denmark. From [4].

Figure 4-24: Failure rates of disconnectors and switch devices, Denmark. From [4].

Page 47: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

37

As indicated in Figure 4-24 that the number of faults on switch devices is quite small in normal years, giving the frequencies approximately 0,2 failures/100units.year. The number of outages caused by failures of surge arresters can be seen in Figure 4-25, which shows an average rate of 0,2-0,25 failures/100units.year. It is important to note that not all power companies are completely clear about their number of installed surge arresters. The failure rates should be treated with care. Generally, there is very limited number of events with failures on surge arresters nationwide.

Table A1-5 in Appendix 1 summarizes the values from all the data sources for the comparison of failure rates for circuit breakers, switches and other devices. Although the differences in values can be observed, the variations are not so significant.

Figure 4-25: Failure rates of surge arresters, Denmark. From [4].

Page 48: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

38

5 Failure Cause Analysis

Outages in distribution systems caused by different factors significantly impact the reliability of the systems. It is important to investigate these outages. Specifically, analysis of reliability performance of the distribution system over the past year related to outages caused by different factors is very useful for the utilities. Significant rise from the trend in outages caused by a specific factor would help the utility to take remedial actions.

Power utilities use normally a computerized system to record the outages. The “cause codes” are then used to classify interruptions. Tree interruptions, lighting, wind, animal, and unknown are some of the typical codes used. This coded information makes analysis of root causes possible. However it should be aware that the variability in the data source and quality of data collected based upon field experience may affect the accuracy of the analysis.

In the following sub-sections the cause analyses rely on the data collected in the computerized database systems. For analyzing nationwide outages in Sweden the data from the Darwin database of Svensk Energi were used. In addition to the analysis by primary causes nationwide, analysis of failures reported at individual companies that fail on the distribution equipment was also performed.

Historical data summarize the actual performance of a distribution system. The basic data item is a system failure, which is a component outage or a customer interruption. The customer interruption has been defined and recorded in terms of the primary causes of the interruption. In the outage cause analysis each failure event recorded was taken into consideration and sorted according to causes of failure and duration of outage.

In the analysis the contributions of the dominant causes to the equipment failures are calculated and compared between different years. The results for different types of equipment are presented in the subsequent subsections.

5.1 Overhead Lines

Overhead distribution lines constitute a very large part of distribution grids. This type of equipment is directly exposed to weather, vegetation, and animals. It typically has failure rates that are higher than corresponding underground cables. Major failures of overhead distribution lines are normally due to environment and weather they are exposed to.

Figure 5-1 and Table A2-1 in Appendix 2 show the division of faults by causes on overhead lines reported in whole Sweden during 2004-2005. The customer interruptions resulting from overhead line failures confirm by the figure that the dominant causes are weather and environment related.

Page 49: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

39

Figures 5-2 and 5-3 present the results of analysing the data from Vattenfall Distribution Sweden and Fortum Distribution AB. These figures give similar dominant causes as those shown in Figure 5-1.

Failure causes of overhead distribution lines, Sweden

010203040506070

Tree fall

, wind

Thunde

rstrom Wind

Tree fall

, sno

w

Tree fell

ing

Snow, ic

e loa

d

Animal

Materia

l failu

re

Lack

of m

aintena

nce

Fuse b

low

Unknown

Other

Perc

enta

ge (%

) 200520042005: 81%

2004: 70%

Figure 5-1: Failure causes for overhead lines, Sweden.

Failure causes of overhead distribution lines, Vattenfall

010203040506070

Tree fall

, wind

Wind

Tree fell

ing

Tree fall

, sno

w

Thunde

rstrom

Animal

Snow, ic

e loa

d

Materia

l failu

re

Fuse b

low

Lack

of m

aintena

nce

Dig inOthe

r

Perc

enta

ge (%

) 200520042005: 84%

2004: 76%

Figure 5-2: Failure causes for overhead lines, Vattenfall Distribution Sweden.

Page 50: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

40

Failure causes of overhead distribution lines, Fortum

010203040506070

Unknown

Tree fall

, wind

Thunde

rstrom Wind

Animal

Tree fall

, sno

w

Tree fell

ing

Lack

of m

aintena

nce

Traffic Salt

Faulte

d opera

tion

Other

Perc

enta

ge (%

) 200520042005: 75%

2004: 62%

Figure 5-3: Failure causes for overhead lines, Fortum Distribution.

Figure 5-4: Failure causes for distribution equipment, Norway. From [5].

Page 51: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

41

The major causes indicated in these figures reflect the customer interruptions resulting from extreme weather conditions, as the hurricane Gudrun in January 2005, as well as from winds, lightning, rain, snow, and storms.

Comparing the Swedish statistics with Norwegian data shown in Figure 5-4 and Table A2-7 in Appendix 2, it is seen that environment related faults on distribution lines were dominant in both countries. As shown in figures the majority of the causes have weather and environment related characteristics.

5.2 Underground Cables

Outage data collected for cable failures over a period of 2004-2005 were analyzed both nation-wide and company-wide. Figures from 5-5 to 5-7 and Table A2-2 in Appendix 2 present the results. It is noted that underground cables have much less weather related faults compared with overhead lines.

The factors that cause the cable failures, as shown in the figures, are mainly material defects, digging, and inadequate maintenance. Swedish power utilities use the same classification of interruption causes as that defined in Svensk Energi DARWin for outage data collection and reporting. The analysis of the cable faults of Vattenfall Distribution gives the similar results to that from analyzing the data Sweden-wide. However the statistics of Fortum Distribution show that the approximate 30-50% cable faults were due to lack of maintenance during 2004-2005.

Failure causes of underground cables, Sweden

05

10152025303540

Materia

l defe

cts

Digging

Lack

of m

aintena

nce

Unknown

Fuse b

low

Tree fall

, wind

Traffic

Thunde

rstrom

Faulte

d opera

tion

Overlo

ading

Sabota

geOthe

r

Perc

enta

ge (%

) 20052004

2005: 67%2004: 63%

Figure 5-5: Failure causes for underground cables, all Sweden.

Page 52: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

42

Failure causes of underground cables, Vattenfall

0102030

405060

Unknown

Materia

l defe

cts

Digging

Lack

of m

aintena

nce

Tree fall

, wind

Fuse b

low

Thunde

rstrom

Tree fell

ingTraffic

Animal

WindOthe

r

Perc

enta

ge (%

) 200520042005: 71%

2004: 56%

Figure 5-6: Failure causes for underground cables, Vattenfall Distribution Sweden.

Failure causes of underground cables, Fortum

0102030405060

Unknown

Lack

of m

aintena

nce

Digging

Materia

l defe

cts

Dimen

sionin

g fail

ure

Animal

Thunde

rstrom

Tree fall

, wind

TrafficWind

Overlo

ading

Other

Perc

enta

ge (%

) 200520042005: 66%

2004: 65%

Figure 5-7: Failure causes for underground cables, Fortum Distribution.

Figures 5-8 and 5-9 present the results of interesting studies in Denmark reported in [4], where the distributions of faults on underground APB- and PEX-cables by deterioration from age and excavation were calculated.

Page 53: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

43

Figure 5-8: Major failure causes for APB-cables, Denmark. From [4].

Figure 5-9: Major failure causes for PEX-cables, Denmark. From [4].

Page 54: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

44

The Danish studies indicate that main causes of cable failures are due to deterioration from age and excavation. For APB-cables, the ten-year’s average value shows that the aging-related faults are at almost the same level as the faults caused by excavation, i.e. 50% and 50% division. However for PEX-cables, much more faults were due to underground work. From Figure 5-8 it is seen that the aging-related failure rates of APB-cables were about 1-1,4 failures per 100 km per year during a five-year’s period.

5.3 Distribution Substations

Figures from 5-10 to 5-13 summarize the causes which initiate and contribute to the failures of distribution substations both Sweden nation-wide and at an individual power company. Tables A2-3 and A2-4 in Appendix 2 list the values of the calculations.

The figures 5-10 and 5-11 reveal that a large percentage of primary substation failures was initiated by weather and manufacturer and material defects. A comparison of the cause distributions shown in these two figures reveals the similar major causes both at the national level and at a company level.

For secondary substations it is shown that thunderstorm and manufacturer and material defects were responsible for the majority of failures (i.e., about 53-81%) both the nation-wide and company-wide. Thunderstorm was a more significant cause of secondary substation failures than material defects.

In Denmark from the early 1970 interruptions and failures in the distribution networks have been subject to statistical treatment. Distribution network companies carry out the statistical survey. In the year 2004, about 80% of the 10-25 kV networks were included in the statistics. Based on the central statistical analyses the development in interruptions at distribution stations is reported in [4] with regard to interruption causes. This is shown again in Figure 5-14. The figure presents an overview of causal distribution of the power outages on 6-25 kV networks. It can be seen that the particularly causes "other natural" and "external influence" were historically significant influential factors and contributed to approximately 50% of the substation failures according to ten-year’s statistics. “Other natural cause’’ has influenced the substations especially by heavy snowfall and hurricanes in Dec. 1999 and Jan. 2005.

Page 55: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

45

Failure causes of primary substations, Sweden

0

5

10

15

20

25

Unknown

Materia

l defe

cts

Thunde

rstrom

Tree fall

, wind

Animal

Wind

Fuse b

low

Lack

of m

aintena

nce

Faulte

d opera

tion

Overlo

ading

Test

Other

Perc

enta

ge (%

) 200520042005: 61%

2004: 56%

Figure 5-10: Failure causes for primary substations, all Sweden.

Failure causes of primary substations, Vattenfall

05

101520253035

Materia

l defe

cts

Thunde

rstrom

Tree fall

, wind

Animal

Wind

Unknown

Lack

of m

aintena

nce

Fuse b

lowTraffic

Snow, ic

e loa

d

Dimen

sionin

g fail

ureOthe

r

Perc

enta

ge (%

) 20052004

2005: 83%2004: 72%

Figure 5-11: Failure causes for primary substations, Vattenfall

Distribution Sweden.

Page 56: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

46

Failure causes of 2:nd substations, Sweden

05

1015202530354045

Unknown

Thunde

rstrom

Materia

l defe

cts

Animal

Fuse b

low Wind

Overlo

ading

Lack

of m

aintena

nce

Tree fall

, wind

Rain, w

ater

Faulte

d opera

tion

Other

Perc

enta

ge (%

) 200520042005: 53%

2004: 56%

Figure 5-12: Failure causes for secondary substations, all Sweden.

Failure causes of 2:nd substations, Vattenfall

010203040506070

Materia

l defe

cts

Thunde

rstrom

Lack

of m

aintena

nce

Animal

Wind

Overlo

ading

Tree fall

, wind

Dimen

sionin

g fail

ure

Faulte

d meth

od

Improp

er mon

tage

TrafficOthe

r

Perc

enta

ge (%

) 20052004

2005: 71%2004: 81%

Figure 5-13: Failure causes for secondary substations, Vattenfall

Distribution Sweden.

Page 57: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

47

Figure 5-14: Outage causes for distribution power delivery stations,

Denmark. From [4].

5.4 Distribution Transformers and Devices

Table A2-5 in Appendix 2 and Figure 5-15 summarize the results of cause analysis of distribution transformer failures nation-wide. These failures were registered as “kapslad transformator fel’’ in the Darwin database.

The analysis indicates that thunderstorm, manufacturer and material defects, and inadequate maintenance were responsible for the majority of distribution transformer failures (i.e., 59-66%).

Figures from 5-16 to 5-19 and Table A2-6 in Appendix 2 summarize the failure-contributing causes for fuse or apparatus boxes based on the faults reported nationwide and at the distribution utilities, Vattenfall and Fortum.

Thunderstorm, manufacturer and material defects, inadequate maintenance, and wind caused tree falls were reported to have contributed to a large number of fuse or apparatus box failures according to the national statistics.

The analysis at company level confirms that a large percentage of fuse or apparatus box failures was initiated by either thunderstorm or wind caused tree falls. However Vattenfall’s statistics indicate manufacturer and material defects being one of dominant causes, while Fortum’s data show inadequate maintenance being one of major causes.

Page 58: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

48

An examination of the results of Fortum’s statistics shown in Figures 5-18 and 5-19 reveals that the causes for MV fuse or apparatus box failures were almost the same as for LV fuse or apparatus box failures during 2004-2005.

Failure causes of distribution transformers, Sweden

05

1015202530354045

Unknown

Thunde

rstrom

Materia

l defe

cts

Lack

of m

aintena

nce

Animal

Fuse b

low

Tree fall

, wind

Revert l

oad

Sabota

geWind

Dimen

sionin

g fail

ureOthe

r

Perc

enta

ge (%

) 200520042005: 66%

2004: 59%

Figure 5-15: Failure causes for distribution transformers, all Sweden.

Failure causes of MV fuse or apparatus boxes, Sweden

05

101520253035

Unknown

Thunde

rstrom

Materia

l defe

cts

Lack

of m

aintena

nce

Tree fall

, wind

Fuse b

lowAnim

alWind

Overlo

ading

Snow, ic

e loa

d

Tree fall

, sno

wOthe

r

Perc

enta

ge (%

) 200520042005: 69%

2004: 67%

Figure 5-16: Failure causes for fuse or apparatus boxes, all Sweden.

Page 59: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

49

Failure causes of MV fuse or apparatus boxes, Vattenfall

05

10152025303540

Unknown

Thunde

rstrom

Materia

l defe

cts

Tree fall

, wind

Fuse b

lowAnim

alWind

Snow, ic

e loa

d

Overlo

ading

Lack

of m

aintena

nce

Tree fall

, sno

wOthe

r

Perc

enta

ge (%

) 20052004

2005: 87%2004: 84%

Figure 5-17: Failure causes for fuse or apparatus boxes, Vattenfall Distribution Sweden.

Failure causes of MV fuse or apparatus boxes, Fortum

0102030405060

Unknown

Lack

of m

aintena

nce

Thunde

rstrom

Tree fall

, wind

Wind

Animal

Salt

Materia

l defe

cts

Faulte

d meth

od

Sabota

geTraffic

Other

Perc

enta

ge (%

) 200520042005: 84%

2004: 74%

Figure 5-18: Failure causes for MV fuse or apparatus boxes, Fortum Distribution.

Page 60: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

50

Failure causes of LV fuse or apparatus boxes, Fortum

05

101520253035404550

Unknown

Lack

of m

aintena

nce

Thunde

rstrom

Tree fall

, wind

Wind

Animal

Overlo

ading

Digging

Traffic

Dimen

sionin

g fail

ure

Improp

er mon

tage

Other

Perc

enta

ge (%

) 200520042005: 65%

2004: 47%

Figure 5-19: Failure causes for LV fuse or apparatus boxes, Fortum Distribution.

Page 61: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

51

6 Influencing Factors

The reliability of distribution equipment can be influenced by various factors. These include environmental conditions, operating conditions, maintenance, material, construction and design, etc. Table 6-1 gives an overview of the influencing factors.

Due to these influencing factors, component reliability data can exhibit significant variations. It is therefore important to understand this influence and to consider the influencing factors when estimating and using the reliability statistics.

This Chapter is devoted to explaining some of these factors for the variance in the statistics. In the subsequent subsections some of the influencing factors are illustrated by statistics either deduced from the fault records or obtained from available publications.

Table 6-1: Overview of influencing factors.

6.1 Manufacture, Voltage Level, and Construction

Equipment reliability data can be affected by its design, manufacture, voltage level, construction, and size. Products from different manufacturers may differ in their inherent characteristics, and these variations may make the reliability of the products different. The reliability data for the same type of products by different manufacturers, different sizes, and different voltage levels can have significant variations. These influences need to be considered in use of equipment reliability data.

Vattenfall Distribution Poland analyzed how failure rates of the distribution transformers of the company vary with voltage and size (in power rating

Influencing factors

• Voltage • Manufacture, construction• Time period• Age, deterioration• Geography, area• Maintenance• Operational environment• Loading• Inaccuracy in data

reporting• …

Page 62: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

52

kVA). Figure 6-1 presents the results of the analyses. It was observed that the small transformers (<= 100 kVA) have much higher failure rates than large ones with power rating of 400 kVA.

Figure 6-1: Influence of voltage and size on failure rates of distribution transformers, Vattenfall Distribution Poland.

6.2 Time Period

A notable character of component reliability data is its variation with time. Power network component behaviour is stochastic in nature. Component failures occur randomly. The reliability data of the components reflect this stochastic behaviour and have dynamic feature. The average failure frequency and repair time for a piece of equipment change from year to year.

Figures from 6-2 to 6-5 show the variations of fault occurrences on distribution equipment over a year as well as from a year to another in Sweden and Norway. The statistics confirm the high variation for overhead lines that are more easily affected by environment and weather they are exposed to.

Norwegian statistics in Figures 6-3 and 6-4 show that fault occurrences on all types of equipment vary more or less over time. The variation for overhead lines is much more larger than that for underground cables.

Figures 6-2 and 6-5 reflect the nature of the failure occurrence’s changing over years. In 2005 the largest portion of line-related outages occurred in

<=100 160 200 250 400 630

6kV15kV

21kV0,000

0,005

0,010

0,015

0,020

0,025

0,030

Failu

re ra

te (f

/100

units

, yr)

Power [kVA]

Voltage

Distribution transformer failur rates regarding to power and voltages, Vattenfall Poland

6kV

15kV

21kV

Page 63: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

53

January, while in 2004 occurred in November. However in a similar fashion, in both years the variation for overhead lines is larger than that for underground cables.

Distribution of equipment failures over year 2005, Sweden

0

510

15

2025

30

3540

45

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Equi

pmen

t fai

lure

s (%

)

Overhead linesPrimary substations Underground cables

Figure 6-2: Fault occurrences on distribution equipment over the year 2005, all Sweden.

Figure 6-3: Fault occurrences on distribution equipment over the year 2005, Norway. From [5].

Page 64: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

54

Fordeling av antall feil over året

0

5

10

15

20

25

Jan Feb Mar Apr Mai Jun Jul Aug Sep Okt Nov Des

Anta

ll fe

il (%

)Lastskillebryter SkillebryterSiklastbryter Sikring Nettstasjon

Figure 6-4: Fault occurrences on distribution equipment over the year 2005, Norway. From [5].

Distribution of equipment failures over year 2004, Sweden

02468

101214161820

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Equi

pmen

t fai

lure

s (%

) Overhead linesPrimary substations Underground cables

Figure 6-5: Fault occurrences on distribution equipment over the year 2004, all Sweden.

Page 65: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

55

Outage duration of MV distribution equipment over year 2005, Sweden

0

20

40

60

80

100

Out

age

dura

tion

(h/f)

Overhead lines 45,1 102,3 17,11 7,65 5,48 4,15 2,30 4,93 3,28 3,21 3,29 5,97 3,07

Prim. substations 6,57 31,74 2,67 1,71 0,89 2,66 2,54 3,63 2,83 2,38 3,66 2,82 3,5

Underg. cables 5,44 8,32 13,5 4,98 3,1 5,48 4,48 5,83 2,8 5,14 3,24 8,36 3,11

Ave Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Figure 6-6: Outage durations of distribution equipment over the year 2005, all Sweden.

Variasjon i midlere reparasjonstid over året (varige feil) [min]

0100200300400500600700800900

1000

Jan Feb Mar Apr Mai Jun Jul Aug Sep Okt Nov Des

Mid

lere

repa

rasj

onst

id (m

in)

Kraftledning Fordelingstransf. Kabel

Figure 6-7: Outage durations for distribution equipment over the year 2005, Norway. From [5].

Figures 6-6 and 6-7 show the monthly variation effect on the outage durations of equipment failures. A considerable variation over a year in both Sweden and Norway can be observed. This variation could be due to several factors, such as operation and restoration conditions, and repair staff resource problems associated with a large number of simultaneous fault occurrences in an extreme weather condition. From these graphs, the outage durations were quite short during summer. For overhead lines the repair time was higher in winter months.

Page 66: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

56

6.3 Geographical Location

The geographical location of distribution equipment is another factor that could influence the reliability data of the equipment. Figures 6-8 and 6-9 show the geographical effect on the number of fault events on distribution equipment of Vattenfall Distribution Sweden during the years 2005 and 2006.

It is shown by the figures that there were more fault events on overhead lines in the west region during the years 2005-2006. The failure rate of overhead lines was high in the east region in 2005, but was much lower in 2006 compared with the year 2005.

Failure rates of MV distribution equipment, Vattenfall Distribution Sweden, 2005, (sustained outages)

0

5

10

15

20

Reg. Middle Reg. North Reg. West Reg. East

Failu

re ra

te (f

/yr.1

00km

)

Overhead lines Aerial cables Underground cables

Figure 6-8: Failure rates of distribution equipment by regions, 2005, Vattenfall Distribution Sweden.

Failure rates of MV distribution equipment, Vattenfall Distribution Sweden, 2006, (sustained outages)

02

46

810

Reg. Middle Reg. North Reg. West Reg. East

Failu

re ra

te (f

/yr.1

00km

)

Overhead lines Aerial cables Underground cables

Figure 6-9: Failure rates of distribution equipment by regions, 2006, Vattenfall Distribution Sweden.

Page 67: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

57

Figure 6-10: Failure rates of overhead lines by areas of the country, Norway. From [5].

Figure 6-11: Failure rates of underground cables by areas of the country, Norway. From [5].

Page 68: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

58

Figure 6-12: Failure rates of distribution transformers by areas of the country, Norway. From [5].

Comparing the Swedish data with Norwegian statistics, the variations of failure events on distribution equipment by geographical location can also be observed. Figures 6-10, 6-11, and 6-12 from Norway illustrate the variations of failure frequencies for distribution equipment with areas. It is noted that the fault occurrences on cables were also influenced by geography. However, the geographical variation effect on the failure rates of underground cables was lower than that for overhead lines.

6.4 Age

Age is generally considered to be an important factor that influences the failure frequency of distribution equipment. During equipment’s entire lifetime, when in operating condition, the equipment underlies electrical, mechanical and thermal stresses, which may lead to a deterioration of its functionality. Furthermore, the deterioration also occurs due to the environment of the equipment operation. This deterioration occurs over time and causes the equipment ageing and decrease in reliability and functional ability.

The failure rates of almost all types of power components increase with age, but the degree of increase may be low for certain types of components and high for others. Figure 6-13, from a study in Siemens AG, Germany, gives an age model of failure rate for MV oil cables. The characteristic of the age model is adjusted to the failure statistic for oil cables. This statistical model is believed giving a better representation of general reliability of MV oil cables due to its large database.

A study of how failure rates of distribution transformers vary with age was performed recently at Vattenfall Distribution Poland. The result is presents in Figure 6-14. The failure data were broken down into several age groups. The groups of the transformers over 40 years have much higher failure rates than the other groups. The failure rates for transformers were approximately in

Page 69: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

59

same level for the age groups of less than 40 years old. A slightly higher failure rates were observed for the units aged greater than 40 years in 2007 than in 2008, but slightly lower for the unit groups aged between 11-30 years in 2007 compared with 2008.

Figure 6-13: Failure rate for MV oil cables Vs age. From [11].

In Norway the failure rate of PEX-cables as a function of age has been investigated in order to support decision making for cable replacement. The study indicates that cables in certain age groups have considerable higher values than the rest of the population. As shown in Figure 6-15 there is a quite noticeable difference in failure frequency. The cables used before 1979 have considerable increase in failure frequency and these cable groups become candidates for replacements.

Another study of how component failure rates vary with age was carried out for distribution transformers in Norway. The results of the study shown in Figure 6-16 reveals that the breakdown frequency began increasing when the transformers became more than 20 years old. The transformer units approach the end of their life when they are greater than 40 years.

Page 70: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

60

>50

41-5

0

31-4

0

21-3

0

11-2

0

<10

Aver

age

2007 20

08

0

1

2

3

4

5

6

7

8Fa

ilure

rate

(f/1

00un

its.y

r)

Age

Failure rates of distribution transformers, Vattenfall Poland

2007

2008

Figure 6-14: Failure rates of distribution transformers Vs age, Vattenfall Distribution Poland.

Figure 6-15: Failure frequency of PEX-cables as function of age, Norway. From [12].

Page 71: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

61

Figure 6-16: Breakdown frequency of distribution transformers as function of age, Norway. From [12].

6.5 Other Factors

Another relevant influencing factor on component reliability is the applied maintenance. Maintenance plays a vital role in extending lifetime of a repairable network component. It affects the component's reliability and cost of operation. There are two different kinds of maintenance: corrective maintenance and preventive maintenance.

Operation condition and maintenance

Preventive maintenance, unlike the corrective maintenance, means the care and servicing for the purpose of maintaining equipment and facilities in satisfactory operating condition. It provides, in an early stage, systematic inspection, detection, and correction of incipient failures before they occur or develop into major defects, and hence reduces the failure rates of components.

Preventive maintenance consists of the actions including tests, measurements, adjustments, and parts replacement performed specifically to prevent faults from occurring. Its schedule is based on observation of past system behaviour, component wear-out mechanisms and knowledge of component’s importance.

Page 72: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

62

Environmental factors may have a major contribution to equipment reliability. Bad environment may accelerate equipment deterioration and shorten its life span and hence cause higher failure rate of the equipment.

Operation environment

In the case of transformers, for cooling purposes, they are usually installed outside the substation. This makes them subject to heat, cold, rain and wind. Heat and humidity are especially hazardous as they can cause the degradation of transformer’s insulation layer and slowly turn transformer’s oil tank into rust and consequently making leakages. All external parts of the transformer are affected. The tap changer will corrode leading to corrosion of the contacts that in turn causes jamming. Variations of environmental temperature may cause moisture level of a transformer to go up. With frequent fluctuations, the transformer paper’s ability to reabsorb the moisture decreases. Over time, the permanent moisture level will increase that can lead to transformer breakdown and result in higher failure occurrences.

Inaccuracy in fault reporting may be another influencing factor. Most of power utilities use computerized systems to register equipment failures. The input codes, such as “cause codes”, used to record details of the interruptions by utilities may be a major source of uncertainty. The variability and inaccuracy in the data source as well as quality of the data may in practical affect the qualitative analysis of component failures and thus influence reliability statistics based upon field experience.

Inaccuracy in data reporting

Page 73: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

63

7 Impact of Extreme Weather

Distribution networks are exposed to varying weather conditions. The failure statistics show that the failure rates of most power network components vary with weather conditions. In bad weather conditions, the failure rate of a network component can be many times greater than that found in the favourable weather condition. During extreme adverse weather period the failure rate can be very large, much greater than the average value, and would significantly increase the probability of simultaneous failures.

In 2005 the extreme weather, as hurricane Gudrun in January, hit Sweden and had a very negative local impact and caused a lot of faults on power networks. The Gudrun storm was assumed to be the worst natural catastrophe and caused many very long outages up to more than one month for the worst affected customers.

Although such a situation is rare, but has high negative impact on power systems. For this reason, its effect should be considered in the risk analysis, and corresponding reliability data need to be studied.

Figure 7-1: Impact of Gudrun storm in Jan. 2005.

In order to analyze the outages caused by extreme-weather, the distribution outage data collected in 2005 Sweden-wide and at the company E.ON Elnät Sverige AB were studied. Tables 7-1 and 7-2 and Figures 7-2 and 7-3 present monthly outage occurrences on MV distribution networks of Sweden and at the company. It is clear from the figures that a large portion of outages, approximately 30% of total outages in 2005, occurred during January.

Page 74: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

64

Table 7-1: Sustained outage occurrences

on MV networks, 2005, all Sweden.

Month Number of outages Jan. 7344 Feb. 2463 March 1201 April 1018 May 1355 June 1769 July 2839 Aug. 1595 Sep. 1193 Oct. 1390 Nov. 1801 Dec. 1202 Total 25170

Table 7-2: Sustained outage occurrences on

MV networks, 2005, E.ON Elnät Sverige AB.

Month Number of outages Jan 3634 Feb. 1826 March 606 April 467 May 616 June 817 July 1000 Aug. 406 Sep. 363 Oct. 350 Nov. 609 Dec. 290 Total 10984

Page 75: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

65

Number of outages > 3min on 10-20 kV networks, 2005, Sweden

010002000300040005000600070008000

Jan

Feb.

March

April

MayJu

ne July

Aug.

Sep.

Oct. Nov.Dec.

Figure 7-2: Number of outages (>3 minutes) on MV networks, 2005, Sweden.

Number of sustained outages > 3 min on 10-20 kV networks, 2005, E.ON Elnät Sverige

0

1000

2000

3000

4000

Jan

Feb.

March

April

MayJu

ne July

Aug.

Sep.

Oct. Nov.Dec.

Num

ber

of fa

ilure

s

Figure 7-3: Number of outages (>3 minutes) on MV networks, 2005, E.ON Elnät Sverige AB.

Page 76: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

66

The outage records in Jan. 2005 were further examined and counted by each day. Figures 7-4 and 7-5, Table A3-3 in Appendix 3, and Table A4-2 in Appendix 4 present the results. The analysis reveals that 48% of all the outages in January in Sweden occurred on 8-9 January. The similar situation can be observed with the fault data from E:ON Elnät Sverige AB. 1479 of total 3634 outages in January occurred on 8-9 January.

Number of outages on 10-20 kV networks, Jan. 2005, Sweden

0500

10001500200025003000

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31

Date

Num

ber o

f fai

lure

s

Figure 7-4 : Number of outages on MV networks, in January 2005, Sweden.

Number of sustained outages > 3 min on 10-20 kV networks, Jan. 2005, E.ON Elnät Sverige

0

500

1000

1500

1 4 7 10 13 16 19 22 25 28 31

Date

Num

ber

of fa

ilure

s

Figure 7-5: Number of outages on MV networks, in January 2005, E:ON Elnät Sverige AB.

Page 77: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

67

The failure intensity of the hurricane Gudrun event affecting distribution equipment on Jan. 8 2005 was analyzed both nationwide and for the company E.ON Elnät Sverige AB. Tables A3-1 and A3-2 in Appendix 3 and Table A4-1 in Appendix 4 summarize the values. Figures from 7-6 to 7-9 show the hourly variation of failure intensity for overhead lines. The hourly extreme failure intensity for bare overhead lines could go up to as high as 0,5-2 failures per 100 km as shown in Figures 7-6 and 7-7. Figures 7-8 and 7-9 expresses the same kind of variation for aerial insulated lines, which show hourly extreme value of about 0,3-0,6 failures per 100 km.

Failure rate of 10-20 kV bare overhead lines , Sweden, on Jan 8, 2005

0,00,10,20,30,40,50,6

00:0

0

02:0

0

04:0

0

06:0

0

08:0

0

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Time

Failu

re ra

te

(f/h

our.1

00km

)

Figure 7-6: Failure rate of MV bare overhead lines on Jan. 8, 2005, Sweden.

Failure rate of 10-20 kV bare overhead line, on Jan 8, 2005, E.ON Elnät

0,000,501,001,502,002,50

00:0

0

02:0

0

04:0

0

06:0

0

08:0

0

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Time

Failu

re ra

te

(f/ho

ur.1

00km

)

Figure 7-7: Failure rate of MV bare overhead lines on Jan. 8, 2005, E.ON Elnät Sverige AB.

Page 78: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

68

Failure rate of 10-20 kV insulated lines in air, Sweden, on Jan 8, 2005,

0,000,050,100,150,200,250,300,35

00:00

02:00

04:00

06:00

08:00

10:00

12:00

14:00

16:00

18:00

20:00

22:00

Time

Failu

re r

ate

(f/ho

ur.1

00 k

m)

Figure 7-8: Failure rate of MV insulated lines on Jan. 8, 2005, Sweden.

Failure rate of 10-20 kV insulated lines in air, on Jan 8, 2005, E:ON Elnät

0,00,20,40,60,8

00:00

02:00

04:00

06:00

08:00

10:00

12:00

14:00

16:00

18:00

20:00

22:00

Time

Failu

re ra

te

(f/ho

ur.1

00 k

m)

Figure 7-9: Failure rate of MV insulated lines on Jan. 8, 2005, E.ON Elnät

Sverige AB.

Page 79: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

69

The failure rates caused by adverse weather are compared with the average values deduced in the report [1], and the results are summarized in Figure 7-10. It is important to note that the failure frequency in extreme weather condition is very significantly different with the average value. The hurricane Gudrun could drive the failure intensities up to approximately 50-80 times high as the average values for overhead lines. This emphasizes the need to consider this effect when doing risk analysis.

Figure 7-10: Comparison of the failure rates in extreme weather condition with the average values.

Overhead lines, 10-20 kV:

Bare conductor lines: 0.0248 f/km.day = 73 * 0.00034 f/km.day

Aerial inslulated lines: 0.012 f/km.day = 50 * 0.00024 f/km.day

Underground cables, 10-20 kV : 0.0001 f/km.day = 2 * 0.00005 f/km.day

Overhead lines, 10-20 kV:

Bare conductor lines: 0.123 f/km.yr 0.00034 f/km.day

Aerial inslulated lines: 0.088 f/km.yr 0.00024 f/km.day

Underground cables, 10-20 kV: 0.019 f/km.yr 0.00005 f/km.day

Average value, (outage > 3 min)All Sweden

Jan. 8, 2005, (outage > 3 min)All Sweden

Bare conductor lines: 0.083 f/km.day = 64 * 0.0013 f/km.day

Aerial inslulated lines : 0.0165 f/km.day = 83 * 0.0002 f/km.day

Underground cables: 0.0 f/km.day = 0 * 0.00006 f/km.day

Bare conductor lines: 0.471 f/km.yr 0.0013 f/km.day

Aerial inslulated lines: 0.072 f/km.yr 0.0002 f/km.day

Underground cables:0.021 f/km.yr 0.00006 f/km.day

E.ON E.ON

Overhead lines, 10-20 kV:

Bare conductor lines: 0.0248 f/km.day = 73 * 0.00034 f/km.day

Aerial inslulated lines: 0.012 f/km.day = 50 * 0.00024 f/km.day

Underground cables, 10-20 kV : 0.0001 f/km.day = 2 * 0.00005 f/km.day

Overhead lines, 10-20 kV:

Bare conductor lines: 0.123 f/km.yr 0.00034 f/km.day

Aerial inslulated lines: 0.088 f/km.yr 0.00024 f/km.day

Underground cables, 10-20 kV: 0.019 f/km.yr 0.00005 f/km.day

Average value, (outage > 3 min)All Sweden

Jan. 8, 2005, (outage > 3 min)All Sweden

Bare conductor lines: 0.083 f/km.day = 64 * 0.0013 f/km.day

Aerial inslulated lines : 0.0165 f/km.day = 83 * 0.0002 f/km.day

Underground cables: 0.0 f/km.day = 0 * 0.00006 f/km.day

Bare conductor lines: 0.471 f/km.yr 0.0013 f/km.day

Aerial inslulated lines: 0.072 f/km.yr 0.0002 f/km.day

Underground cables:0.021 f/km.yr 0.00006 f/km.day

E.ON E.ON

Page 80: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

70

8 Conclusions

This project performed distribution reliability data related studies and analyses. The conclusions from the project work are summarized as follows:

Component reliability data has fundamental importance for distribution system risk and reliability analysis. Without good such data the risk analysis would be baseless. In order to better understand component reliability data and get confidence in data use, the project performed detailed study and analysis of existing component failure statistics. The project activities were focused on:

Project performance

• Comparative study. The component failure statistics from different sources and different countries, such as Norway, Denmark, Finland, and Germany, are studied and compared with respect to data structure, component classification, and values of the statistics.

• Major cause analyses for component failures.

• Influential factor analyses. The different factors and failure sources that may affect the statistics were studied and analysed.

• Failure statistics analyses for extreme events. The component failure statistics of hurricane Gudrun based on outage reports from 2004-2005 were deduced in the project.

The project studied the data characteristics and categorization structures in different data sources. The overview of similarities and consistence in data structure and categorizations that exist among different data sources are given in the report. The comparison of data scheme characteristics and structures are summarized in the report with respect to system characteristics, equipment categories, and interruption causes.

Comparative study

The values of failure statistics from different data sources were collected and compared. The comparative data studies are made on major categories of distribution equipment including:

• Distribution lines;

• Distribution cables;

• Transformers;

• Sub-stations;

• Circuit breakers, switch devices, and other devices.

Page 81: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

71

The comparative overviews of the Swedish statistics with the data from other sources are presented in the report and the detailed values for different types of components are summarized in the Appendix of the report.

The project shows that much effort in many countries has been expended in developing methods and computer programs to uniformly and consistently quantify the reliability of distribution equipment based on electric system performance. However, the results of the worldwide study in the project indicate that significant inconsistencies exist in the data, in the data categorization, and in the data collection processes in different countries. A set of differences found in data categorization and structure among different data sources is also presented in the report.

Component reliability data reflects stochastic nature of component failures and impact of influencing factors. The results of project show that the reliability data can vary widely from system to system, from year to year, and from area to area. It is important to recognize this dynamic feature of reliability data. If possible, study and analyze component failure statistics regularly and produce confident data for risk analysis.

To understand the causes of component failures the cause analyses were carried out in the project. The analyses were based on the data from the DARWin database of Svensk Energi. In addition to the nationwide analyses the study of faults reported at individual companies was also performed in the project.

Failure cause analyses

In the analysis the contributions of the dominant causes to the failures of major categories of distribution equipment were calculated and compared between different years. The distribution of component failures over different causes is presented in the report.

The analyses show that the failure causes were different for different types of power components. The analyses confirm that the dominant causes for faults on overhead network components are weather and environment related, while faults on underground distribution equipment are mainly material defect and digging related. The results of analysis indicate that thunderstorm, manufacturer and material defects, and inadequate maintenance were responsible for the majority of distribution transformer failures (approximately 59-66%).

The reliability of distribution equipment can be influenced by various factors. These include environmental conditions, operating conditions, maintenance, material, construction and design, etc.

Influential factor analyses

In order to understand this influence the project work is devoted to studying and analyzing these factors. The report describes and illustrates how equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography, age, operation condition and maintenance.

Page 82: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

72

The results of the study show that due to different influencing factors, component reliability data can exhibit significant variations. It is therefore important to understand this influence and to consider the influencing factors when estimating and using the reliability statistics.

Distribution networks are exposed to varying weather conditions. The failure rates of most power network components vary with weather conditions. In the extreme weather condition, distribution systems could be affected very negative. For this reason, this effect should be considered in the risk analysis, and corresponding reliability data need to be studied.

Failure statistics analyses for extreme events

In order to understand how extreme weather affects component reliability data, the project analyzed the statistics of component failures during the hurricane Gudrun in January 2005 based on the fault reports from all Sweden and from the power company, E:ON Elnät Sverige AB.

The results indicate that the failure rate of equipment exposed to weather could dramatically increase by up to 80 times of the average value during extreme weather condition. This dramatic change of the component reliability data should therefore be taken into account in risk analysis of distribution systems.

Page 83: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

73

9 References

[1] Y. He, “Distribution Equipment Reliability Data’’, Elforsk rapport 07:59, Sep. 2007.

[2] V. G. Werner, et al., “Collecting and Categorizing Information Related to

Electric Power Distribution Interruption Events: Data Consistency and Categorization for Benchmarking Surveys’’, IEEE Transactions on Power Delivery, vol. 21, no. 1, January 2006.

[3] IEEE Power Engineering Society, “1366 IEEE Guide for Electric Power Distribution Reliability Indices’’, IEEE Std 1366™-2003, 14 May 2004.

[4] R. Olsen og P. Hansen, Dansk Energi, ”Rapport 547, Fejl- og afbrudsstatistik, Dansk landsstatistik for årene 1998-2007 for statistikområdet 6-25 kV ’’, September 2008.

[5] J. Heggset, et al., ”FASIT 2005 Feil og avbrudd i høyspennings fordelingsnett tom 22 kV’’, Publikasjon nr.: 220-2006. SINTEF Energiforskning AS.

[6] G. Kjølle, et al., ”Analyser av feil og avbrudd i kraftnettet 1989-2005’’, SINTEF Energiforskning AS.

[7] Statnett, “Årsstatistikk 2007 Feil og avbrudd i 1-22 kV nettet.

[8] G. Kjølle, ”Fault statistics in distribution network’’, SINTEF Energy Research.

[9] J. Heggset, et al., ”FASIT 2006 Feil og avbrudd i høyspennings fordelingsnett tom 22 kV’’, SINTEF Energiforskning AS.

[10] F. Roos and S. Lindahl, “Distribution System Component Failure Rates and Repair Times – An Overview’’, Lund University, Sweden.

[11] M. Schwan, et al., ”Reliability Centered Asset Management in Distribution Networks - Process and Application Examples’’, CIRED 2007.

[12] J. Heggset, ”Bedre utnyttelse av feil-ogavbruddsdata’’, SINTEF Energiforskning AS.

[13] G. Kjølle, et al., “Incorporating Short Interruptions and Time Dependency of Interruption Costs in Continuity of Supply Regulation’’, CIRED paper 0494, Prague, June 2009.

[14] J. Heggset, G. H Kjølle, and Olve Mogstad “Fasit – the Norwegian Standard for Collection, Calculation and Reporting of Reliability Data’’.

[15] Danish Energy Association, “Danish Electricity Supply 2008, Statistical Survey’’, ISSN 0907-5259, April 2009.

[16] Association of Danish Energy Companies, “Danish electricity Supply Statistical Survey 2004’’, ISSN 0907-5259.

[17] M. M. Jensen, DEFU, ”Rapport 520, Indsamling af leveringssikkerhedsdata’’, December 2005.

Page 84: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

74

[18] Dansk Energi, ”Dansk Elforsyning Statistik 2004’’, ISSN 0907-5259, Juni 2005.

[19] Dansk Energi, ”Rapport 525, Indsamling af leveringssikkerhedsdata’’, Juni 2006.

[20] J. Heggset and G. H Kjølle, “Experiences with the FASIT Reliability Data Collection System’’, SINTEF Energy Research, Norway.

[21] J. Heggset, et al., ”Fasit – A Tool for Collection, Calculation and Reporting of Reliability Data’’, CIRED paper 0716, Prague, June 2009.

[22] Norstat working group, “Faults and Interruptions in the Nordic 1-70 kV Network, Ststistics 2005’’, Report 530, December 2006.

[23] C. A. Warren, et al., “A Nationwide Survey of Recorded Information Used for Calculating Distribution Reliability Indices’’, IEEE Transactions on Power Delivery, vol. 18, no. 2, April 2003.

[24] Publications at the following Web-sites:

http://www.nordel.org/

http://www.ntnu.no/ross/info/data

http://www.danskenergi.dk/

http://www.ebr.nu/

http://www.fasit.no/

http://www.statnett.no/no/Kraftsystemet/Systemansvaret-FOS-SAKS/Feilstatistikk/

http://www.energy.sintef.no/prosjekt/OPAL

http://www.danskenergi.dk/energiital.aspx

Page 85: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

75

10 Appendix 1: Summary of Data Comparison

Page 86: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

76

Table A1-1: Comparison of Failure Rates for Overhead Lines

Failure rates of overhead lines (f/100km.yr) (sustained outages)For data from Equipment 2004 2005 2006 2007 Average

Friledning oisolerad 0,4 - 1 kV

9,63 67,1 15,72 40,57 33,25 (2004 - 2007)

Luftledning isolerad 0,4 - 1 kV

3,56 5,68 2,61 4,24 4,02 (2004 - 2007)

All Sweden Luftledning 0,4 - 1 kV 5,43 15,81 4,78 9,99 9,00

(2004 - 2007) Friledning oisolerad 10 - 20 kV 8,06 16,53 8,51 12,88 11,49

(2004 - 2005)Luftledning isolerad 10 - 20 kV 7,57 9,55 7,65 12,35 9,28

(2004 - 2005)Luftledning 10 - 20 kV 8,00 15,45 8,38 12,79 11,15

(2004 - 2005)Kraftledning blank 1 - 22 kV 7,00 8,40 5,50 5,90

(1996-2005)All Norway Kraftledning belagt

(BLX), 1 - 22 kV 2,30 2,20 1,90 1,90 (1996-2005)

Kraftledning 1 - 22 kV 3,63 4,13 2,85 4,00 3,72

(1996-2005)All Denmark Luftledningsanlæg

6 - 25 kV 2,15 5,76 4,54 4,41 3,79 (1998 - 2007)

Based on average statistics to 2005All Finland Overhead lines, uninsulated, 1 - 39 kV 4,77

Overhead lines, insulated, 1 - 39 kV 0,21Based on average statistics in Germany and Switzerland before 2006.Overhead line, compensation (earthing), 10 kV 2,56

BCP Overhead line, compensation (earthing), 20 kV 12,42Overhead line, low impedance earthing, 10 kV 11,48Overhead line, low impedance earthing, 20 kV 19,99Based on average statistics before 1998Overhead 11 kV feeders 13,00

USA Overhead lines 5 - 35 kV, primary trunk: low value = 1,24 typical value = 6,22, high value = 18,65

Overhead lines 5 - 35 kV, lateral tap: low value = 1,24 typical value = 9,94, high value = 18,65

Based on equipment surveys from 1976 - 1989IEEE Open wire < 15 kV 6,20

Open wire > 15 kV 2,46

Page 87: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

77

Table A1-2: Comparison of Failure Rates for Underground Cables.

Failure rates of underground cables (f/100km.yr) (sustained outages)For data from Equipment 2004 2005 2006 2007 Average

All Sweden Jordkabel 0,4 - 1 kV

3,11 2,82 3,22 2,89 3,01 (2004 - 2007)

Jordkabel 10 - 20 kV 1,96 1,78 2,22 1,92 1,97

(2004 - 2007)

All Norway kabel (alle typer) 1 - 22 kV 2,34 2,19 1,9 1,7 2,44

(1996-2005)PEX-kabel 1 - 22 kV 2,1 2,1

(1996-2005)

All Denmark APB-kabler 6 - 25 kV 2,3 2,52 2,68 2,67 2,38

(1998 - 2007)PEX-kabler 6 - 25 kV 0,48 0,64 0,66 0,66 0,63

(1998 - 2007)All Finland Based on average statistics to 2005

Underground cables (all types), 1 - 39 kV 0,85Based on average statistics in Germany and Switzerland before 2006.XLPE cables, compensation (earthing), 10 kV 0,76XLPE cables, compensation (earthing), 20 kV 0,65

BCP XLPE cables, low impedance earthing, 10 kV 4,90XLPE cables, low impedance earthing, 20 kV 0,90PE cables, compensation (earthing), 10 kV 2,69PE cables, compensation (earthing), 20 kV 3,50PE cables, low impedance earthing, MV 3,83Based on average statistics before 1998

USA Underground distribution cable, primary cable: low value = 1,86, typical value = 4,35

Underground distribution cable, secondary cable: low value = 0,31typical value = 6,22, high value = 9,32

Based on equipment surveys from 1976 - 1989IEEE Underground cables, < 0,6 kV 1,28

Underground cables, 0,6 - 15 kV 1,97Underground cables, > 15 kV 0,98

Page 88: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

78

Table A1-3: Comparison of Failure Rates for Transformers.

Failure rates of transformers (f/100units.yr) (sustained outages)For data from Equipment 2004 2005 2006 2007 Average

Utility average, 2004 - 2005 Sweden Distributions transformator 0,4/10-24 kV 0,96

(2004 - 2005)

Krafttransformator 10-20/44-135 KV 0,30 (2004 - 2005)

All Norway Fordelingstransfo-rmator 0,23-0,4/1-22 kV

0,76 0,54 0,85 0,61 0,79 (1997-2006)

All DenmarkDistributionstransf-ormere 6 - 25 kV

0,12 0,09 0,13 0,10 0,12 (1998 - 2007)

Poland Based on average statistics from Vattenfall Distribution Poland

MV transformers 0,7 0,6 0,60 0,63 (2005-2007)

Based on average statistics in Germany and Switzerland before 2006.Transformer, compensation (earthing), 10 kV 0,12Transformer, compensation (earthing), 20 kV 0,35

BCP Transformer, low impedance (earthing), 10 kV 0,31Transformer, low impedance (earthing), 20 kV 0,18Transformer, underground system, 10/0,4 kV 0,48Transformer, underground system, 20/0,4 kV 6,76LV/MV transformers 0,1 - 0,2

Study in [10] MV/MV transformers 1,0 - 1,3

MV/HV transformers 1,4 - 2,5Based on average statistics before 1998Pole mounted transformers 5 - 35 kV: low value = 0,4

USA typical value = 1,00, high value = 1,50Pole mounted distribution transformers:

low value = 0,10, typical value = 1,00Based on equipment surveys from 1976 - 1989

IEEE Power transformators, liquid filled, all 0,62Power transformators, liquid filled, 0,3 - 10 MVA 0,59Power transformators, liquid filled, > 10 MVA 1,53

Page 89: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

79

Table A1-4: Comparison of Failure Rates of Substation.

Failure rates of distribution substation (f/100units.yr) (sustained outages)For data from Equipment 2004 2005 2006 2007 Average

Based on statistics from Vattenfall Distribution AB before 2006Stolpstation 10 - 20 kV 2,00

Sweden Plåtstation 10 - 20 kV 1,60

Betongstation 10 - 20 kV 1,50Kabelskåp 0,4 kV 0,60

All Denmark Leveringspunkter 6 - 25 kV 2,26 2,79 2,71 2,6 2,85

(1998-2007)

Page 90: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

80

Table A1-5: Comparison of Failure Rates for Circuit Breakers, Switches and Other Devices.

Failure rates of circuit breakers, switches, and other devices (f/100units.yr)(sustained outages)For data from Equipment 2004 2005 2006 2007 Average

Based on statistics from Swedish utilities before 2006 Sweden Effektbrytare inomhus 1,10

Frånskiljare 10 - 20 kV utomhus 1,30Frånskiljare 10 - 20 kV inomhus 0,50Effektbryter 1 - 22 kV 0,19 0,21 0,18 0,28 0,25

(1997-2006)

All Norway

Lastskillebryter, Skillebryter, Siklastbryter, 1 - 22 kV

0,17 0,16 0,18 0,17 0,15 (1997-2006)

Overspændingsafledere 1 - 22 kV 0,19 0,22 0,13 0,24 0,22

(1997-2006)

All Denmark Afbrydere 6 - 25 kV 0,1 0,09 0,09 0,09 0,10 (1998 - 2007)

Adskillere 6 - 25 kV 0,09 0,06 0,13 0,13 0,13 (1998 - 2007)

Based on average statistics in Germany and Switzerland before 2006.BCP Circuit breakers 10 kV 0,04

Circuit breakers 20 kV 0,18Based on average statistics before 1998Switch 11 kV 1,00Disconnect switch 5 - 35 kV: low value = 0,40

USA typical value = 1,40, high value = 14,00Padmount switch: low value = 0,10

typical value = 0,30, high value = 0,50Reclosers 11 kV 1,00Fuse cutout 5 - 35 kV: low value = 0,40

typical value = 0,90, high value = 3,00Based on equipment surveys from 1976 - 1989Circuit breakers, fixed type, all 0,50Circuit breakers, fixed type, < 0.6 kV 0,40

IEEE Circuit breakers, fixed type, > 0.6 kV 1,76Circuit breakers, metalclad drawout type 0,30Disconnect switches, enclosed 0,61Disconnect switches, open 0,29

Page 91: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

81

11 Appendix 2: Failure Causes for Distribution Equipment

Table A2-1: Failure Causes for Overhead Lines, All Sweden.

2005 2004 Cause Number Percentage (%) Number Percentage (%) Bristande underhåll 237 1,50 251 3,12 Dimensioneringsfel 5 0,03 8 0,10 Djur 251 1,59 242 3,01 Fabr- eller mtrlfel 903 5,71 709 8,82 Felaktig metod/instruktion 26 0,16 27 0,34 Felaktig mont/förläggning 21 0,13 31 0,39 Felmanöver 27 0,17 13 0,16 Grävning 34 0,21 27 0,34 Okänd 1354 8,56 910 11,32 Provning 8 0,05 8 0,10 Regn, vatten 52 0,33 66 0,82 Sabotage 9 0,06 7 0,09 Salt 19 0,12 10 0,12 Snö, islast 257 1,62 290 3,61 Säkringsbrott 165 1,04 256 3,18 Trafik 116 0,73 81 1,01 Trädfall, snö 568 3,59 785 9,76 Trädfall, vind 9704 61,34 2287 28,45 Trädfällning 310 1,96 333 4,14 Vind 745 4,71 621 7,72 Åska 971 6,14 1043 12,97 Återvändande last 2 0,01 3 0,04 Överbelastning 36 0,23 31 0,39 Total 15820 100 8039 100

Page 92: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

82

Table A2-2: Failure Causes for MV Underground Cables, All Sweden.

Cause 2005 2004 Number Percentage (%) Number Percentage (%) Bristande underhåll 83 7,44 74 6,80 Dimensioneringsfel 7 0,63 15 1,38 Djur 6 0,54 4 0,37 Fabr- eller mtrlfel 414 37,10 378 34,74 Felaktig metod/instruktion 7 0,63 3 0,28 Felaktig mont/förläggning 7 0,63 8 0,74 Felmanöver 13 1,16 6 0,55 Grävning 250 22,40 234 21,51 Okänd 154 13,80 187 17,19 Provning 1 0,09 6 0,55 Regn, vatten 2 0,18 2 0,18 Sabotage 10 0,90 4 0,37 Salt 0 0,00 0 0,00 Snö, islast 2 0,18 9 0,83 Säkringsbrott 46 4,12 84 7,72 Trafik 28 2,51 5 0,46 Trädfall, snö 0 0,00 6 0,55 Trädfall, vind 31 2,78 9 0,83 Trädfällning 8 0,72 6 0,55 Vind 10 0,90 5 0,46 Åska 26 2,33 28 2,57 Återvändande last 0 0,00 0 0,00 Överbelastning 11 0,99 15 1,38 Total 1116 100 1088 100

Page 93: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

83

Table A2-3: Failure Causes for Primary Substation, All Sweden.

Cause 2005 2004 Number Percentage (%) Number Percentage (%) Bristande underhåll 14 1,86 9 1,43 Dimensioneringsfel 6 0,80 4 0,64 Djur 61 8,09 48 7,63 Fabr- eller mtrlfel 145 19,23 121 19,24 Felaktig metod/instruktion 3 0,40 6 0,95 Felaktig mont/förläggning 5 0,66 3 0,48 Felmanöver 14 1,86 7 1,11 Grävning 5 0,66 4 0,64 Okänd 170 22,55 134 21,30 Provning 12 1,59 16 2,54 Regn, vatten 2 0,27 4 0,64 Sabotage 0 0,00 1 0,16 Salt 0 0,00 0 0,00 Snö, islast 7 0,93 6 0,95 Säkringsbrott 28 3,71 53 8,43 Trafik 4 0,53 3 0,48 Trädfall, snö 1 0,13 7 1,11 Trädfall, vind 106 14,06 34 5,41 Trädfällning 7 0,93 7 1,11 Vind 34 4,51 18 2,86 Åska 116 15,38 131 20,83 Återvändande last 1 0,13 0 0,00 Överbelastning 13 1,72 13 2,07 Total 754 100 629 100

Page 94: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

84

Table A2-4: Failure Causes for Secondary Substation, All Sweden.

Cause 2005 2004 Number Percentage (%) Number Percentage (%) Bristande underhåll 70 3,58 56 2,57 Dimensioneringsfel 2 0,10 5 0,23 Djur 125 6,40 114 5,22 Fabr- eller mtrlfel 339 17,35 354 16,22 Felaktig metod/instruktion 5 0,26 5 0,23 Felaktig mont/förläggning 5 0,26 9 0,41 Felmanöver 10 0,51 13 0,60 Grävning 3 0,15 3 0,14 Okänd 340 17,40 342 15,67 Provning 1 0,05 1 0,05 Regn, vatten 11 0,56 19 0,87 Sabotage 1 0,05 7 0,32 Salt 1 0,05 0 0,00 Snö, islast 7 0,36 14 0,64 Säkringsbrott 96 4,91 137 6,28 Trafik 8 0,41 6 0,27 Trädfall, snö 3 0,15 14 0,64 Trädfall, vind 66 3,38 80 3,66 Trädfällning 5 0,26 4 0,18 Vind 89 4,55 66 3,02 Åska 693 35,47 872 39,95 Återvändande last 1 0,05 2 0,09 Överbelastning 73 3,74 60 2,75 Total 1954 100 2183 100

Page 95: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

85

Table A2-5: Failure Causes for Distribution Transformers, All Sweden.

Cause 2005 2004 Number Percentage (%) Number Percentage (%) Bristande underhåll 17 8,29 28 18,67 Dimensioneringsfel 1 0,49 2 1,33 Djur 16 7,80 6 4,00 Fabr- eller mtrlfel 37 18,05 21 14,00 Felaktig metod/instruktion 1 0,49 1 0,67 Felaktig mont/förläggning 0 0,00 1 0,67 Felmanöver 0 0,00 4 2,67 Grävning 0 0,00 0 0,00 Okänd 21 10,24 26 17,33 Provning 1 0,49 0 0,00 Regn, vatten 0 0,00 0 0,00 Sabotage 2 0,98 0 0,00 Salt 0 0,00 0 0,00 Snö, islast 1 0,49 0 0,00 Säkringsbrott 12 5,85 12 8,00 Trafik 1 0,49 0 0,00 Trädfall, snö 0 0,00 0 0,00 Trädfall, vind 9 4,39 2 1,33 Trädfällning 0 0,00 0 0,00 Vind 2 0,98 0 0,00 Åska 81 39,51 39 26,00 Återvändande last 3 1,46 1 0,67 Överbelastning 0 0,00 7 4,67 Total 205 100 150 100

Page 96: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

86

Table A2-6: Failure Causes for Fuse or Apparatus Boxes, All Sweden.

Cause 2005 2004 Number Percentage (%) Number Percentage (%) Bristande underhåll 131 10,05 101 8,10 Dimensioneringsfel 0 0,00 4 0,32 Djur 51 3,91 65 5,21 Fabr- eller mtrlfel 212 16,26 178 14,27 Felaktig metod/instruktion 2 0,15 0 0,00 Felaktig mont/förläggning 3 0,23 9 0,72 Felmanöver 4 0,31 2 0,16 Grävning 2 0,15 5 0,40 Okänd 239 18,33 187 15,00 Provning 0 0,00 0 0,00 Regn, vatten 6 0,46 5 0,40 Sabotage 4 0,31 0 0,00 Salt 4 0,31 0 0,00 Snö, islast 12 0,92 24 1,92 Säkringsbrott 51 3,91 138 11,07 Trafik 2 0,15 3 0,24 Trädfall, snö 7 0,54 12 0,96 Trädfall, vind 108 8,28 41 3,29 Trädfällning 3 0,23 9 0,72 Vind 40 3,07 40 3,21 Åska 394 30,21 382 30,63 Återvändande last 0 0,00 1 0,08 Överbelastning 29 2,22 41 3,29 Total 1304 100 1247 100

Page 97: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

87

12 Appendix 3: Summary of Swedish Distribution Equipment Reliability Data on Hurricane Gudrun Day

Table A3-1: Failure Rate of 10-20 kV Network Components on January 8, 2005, All Sweden. Sustained outage > 3 minutes, on 8 Jan. 2005, Sweden

Equipment, station Number of units or km, 2005

Number of failures, 2005

Number of failures, on 8 Jan. 2005

Failure rate (f/day.unit), (f/day.km), on 8 Jan. 2005

ANNAN LEDNING 134 2 ANNAN STATIONSTYP 48 0 AVGRENINGS- / KABELSKÅP 26 0 BETONGSTN INOMHUSMAN 66 0 BETONGSTN. UTOMHUSMAN 35 0 FRILEDNING, ISOLERAD 1425 187 FRILEDNING, OISOLERAD 86526 14307 2142 0,0248 FÖRDELNINGSSTATION 754 8 HÄNGKABELLEDNING 66 3 HÄNGSPIRALKABELLEDNING 22 1 INHYST STATION 7 0 KABEL I MARK 62829 1117 8 0,0001 KABEL I VATTEN 9 0 KAPSLAD TRANSFORMATOR 205 0 KOPPLINGSSTATION 25 0 LUFTLEDNING ISOLERADE 15851 1513 191 0,0120 OKÄND 3766 133 PLÅTSTATION 179 15 SATELLITSTATION 22 0 STOLPSTATION 1597 17 SÄKRINGS- ELLER APPARATLÅDA 1304 7 UTGÅTT ANNAN LEDNING MARK 16 0 UTGÅTT AVGRENINGSSKÅP HSP 2 0 UTGÅTT MARKSTATION 38 0 Total

25170 2523

Page 98: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

88

Table A3-2: Failure Rate of 10-20 kV Network Equipment on Jan. 9, 2005, All Sweden. Sustained outage > 3 minutes, on 9 Jan. 2005, Sweden

Equipment, station Number of units or km, 2005

Number of failures, 2005

Number of failures, on 9 Jan. 2005

Failure rate (f/day.unit), (f/day.km), on 9 Jan. 2005

ANNAN LEDNING 134 2 ANNAN STATIONSTYP 48 0 AVGRENINGS- / KABELSKÅP 26 0 BETONGSTN INOMHUSMAN 66 0 BETONGSTN. UTOMHUSMAN 35 1 FRILEDNING, ISOLERAD 1425 83 FRILEDNING, OISOLERAD 86526 14307 728 0,0084 FÖRDELNINGSSTATION 754 12 HÄNGKABELLEDNING 66 4 HÄNGSPIRALKABELLEDNING 22 2 INHYST STATION 7 0 KABEL I MARK 62829 1117 12 0,0002 KABEL I VATTEN 9 0 KAPSLAD TRANSFORMATOR 205 4 KOPPLINGSSTATION 25 0 LUFTLEDNING ISOLERADE 15851 1513 89 0,0056 OKÄND 3766 132 PLÅTSTATION 179 3 SATELLITSTATION 22 0 STOLPSTATION 1597 6 SÄKRINGS- ELLER APPARATLÅDA 1304 35 UTGÅTT ANNAN LEDNING MARK 16 0 UTGÅTT AVGRENINGSSKÅP HSP 2 0 UTGÅTT MARKSTATION 38 0 Total

25170 1024

Page 99: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

89

Table A3-3: Number of Outages > 3 Minutes During Jan. 2005 on 10-20 kV Networks, All Sweden. Date Number of Outages 2005-01-01 19 2005-01-02 91 2005-01-03 38 2005-01-04 21 2005-01-05 36 2005-01-06 19 2005-01-07 138 2005-01-08 2523 2005-01-09 1024 2005-01-10 423 2005-01-11 321 2005-01-12 458 2005-01-13 302 2005-01-14 133 2005-01-15 110 2005-01-16 115 2005-01-17 171 2005-01-18 197 2005-01-19 174 2005-01-20 182 2005-01-21 138 2005-01-22 65 2005-01-23 42 2005-01-24 114 2005-01-25 87 2005-01-26 85 2005-01-27 72 2005-01-28 48 2005-01-29 48 2005-01-30 51 2005-01-31 99 Total 7344

Page 100: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

90

Table A3-4: Variation of Failure Rate of 10 – 20 kV Bare Overhead Lines on Jan. 8, 2005, All Sweden. Sustained outage > 3 minutes on 8 Jan. 2005, Sweden

Time Number of failures

Failure rate (f/hour.100km)

00:00 - 01:00 3 0,0035 01:00 - 02:00 1 0,0012 02:00 - 03:00 4 0,0046 03:00 - 04:00 0 0,0000 04:00 - 05:00 2 0,0023 05:00 - 06:00 2 0,0023 06:00 - 07:00 4 0,0046 07:00 - 08:00 2 0,0023 08:00 - 09:00 9 0,0104 09:00 - 10:00 7 0,0081 10:00 - 11:00 4 0,0046 11:00 - 12:00 14 0,0162 12:00 - 13:00 22 0,0254 13:00 - 14.00 52 0,0601 14:00 - 15:00 66 0,0763 15:00 - 16:00 167 0,1930 16:00 -17:00 416 0,4808 17:00 - 18:00 340 0,3929 18:00 - 19:00 155 0,1791 19:00 -20:00 176 0,2034 20:00 - 21:00 193 0,2231 21:00 - 22:00 248 0,2866 22:00 -23:00 114 0,1318 23:00 - 24:00 141 0,1630 Total 2142

Page 101: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

91

Table A3-5: Variation of Failure Rate of 10–20 kV Insulated Lines in Air on Jan. 8, 2005, All Sweden. Sustained outage > 3 minutes on 8 Jan. 2005, Sweden

Time Number of failures

Failure rate (f/hour.100km)

00:00 - 01:00 0 0,0000 01:00 - 02:00 0 0,0000 02:00 - 03:00 0 0,0000 03:00 - 04:00 0 0,0000 04:00 - 05:00 0 0,0000 05:00 - 06:00 0 0,0000 06:00 - 07:00 0 0,0000 07:00 - 08:00 0 0,0000 08:00 - 09:00 2 0,0126 09:00 - 10:00 0 0,0000 10:00 - 11:00 0 0,0000 11:00 - 12:00 1 0,0063 12:00 - 13:00 3 0,0189 13:00 - 14.00 2 0,0126 14:00 - 15:00 6 0,0379 15:00 - 16:00 17 0,1072 16:00 -17:00 52 0,3281 17:00 - 18:00 28 0,1766 18:00 - 19:00 6 0,0379 19:00 -20:00 14 0,0883 20:00 - 21:00 18 0,1136 21:00 - 22:00 9 0,0568 22:00 -23:00 15 0,0946 23:00 - 24:00 18 0,1136 Total 191

Page 102: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

92

13 Appendix 4: Summary of Statistics on Hurricane Gudrun Day of E.ON Elnät Sverige AB

Table A4-1: Failure Statistics of 10-20 kV Network Equipment on Jan. 8, 2005, E.ON Elnät Sverige AB.

Sustained outage > 3 minutes, on Jan. 8, 2005, E.ON Elnät

Equipment, station Number of units or km, 2005

Number of failures, 2005

Number of failures, on 8 Jan. 2005

Failure rate (f/day.unit), (f/day.km), on 8 Jan. 2005

ANNAN LEDNING 62 1 ANNAN STATIONSTYP 41 0 AVGRENINGS- / KABELSKÅP 10 0 BETONGSTN INOMHUSMAN 16 0 BETONGSTN. UTOMHUSMAN 17 0 FRILEDNING ISOLERAD (inkl. hängkabelledning, hängspiralkabelledning) 5766 570 95

0,0165

FRILEDNING, OISOLERAD 13538 8912 1123 0,0830 FÖRDELNINGSSTATION 135 0 HÄNGKABELLEDNING 22 0 HÄNGSPIRALKABELLEDNING 4 0 INHYST STATION 2 0 KABEL I MARK 9564 229 0 KABEL I VATTEN 3 0 KAPSLAD TRANSFORMATOR 37 0 KOPPLINGSSTATION 9 0 OKÄND 60 0 PLÅTSTATION 41 0 SATELLITSTATION 1 0 STOLPSTATION 707 0 SÄKRINGS- ELLER APPARATLÅDA 102 1 UTGÅTT ANNAN LEDNING MARK 14 0 UTGÅTT AVGRENINGSSKÅP HSP 16 0 UTGÅTT MARKSTATION 0 Total 10984 1220

Page 103: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

93

Table A4-2: Number of Outages > 3 minutes During January 2005 on 10-20 kV Networks, E.ON Elnät Sverige AB. Date Number of Outages 2005-01-01 3 2005-01-02 22 2005-01-03 13 2005-01-04 12 2005-01-05 13 2005-01-06 7 2005-01-07 53 2005-01-08 1220 2005-01-09 259 2005-01-10 211 2005-01-11 208 2005-01-12 157 2005-01-13 124 2005-01-14 95 2005-01-15 73 2005-01-16 78 2005-01-17 122 2005-01-18 126 2005-01-19 111 2005-01-20 132 2005-01-21 104 2005-01-22 46 2005-01-23 32 2005-01-24 83 2005-01-25 61 2005-01-26 68 2005-01-27 55 2005-01-28 32 2005-01-29 32 2005-01-30 26 2005-01-31 56 Total 3634

Page 104: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

94

Table A4-3: Variation of Failure Rate of 10–20 kV Bare Overhead Lines on Jan. 8, 2005, E.ON Elnät Sverige AB. Sustained outage > 3 minutes on 8 Jan. 2005, E.ON Elnät

Time Number of failures

Failure rate (f/hour.100km)

00:00 - 01:00 1 0,0074 01:00 - 02:00 1 0,0074 02:00 - 03:00 4 0,0295 03:00 - 04:00 0 0,0000 04:00 - 05:00 2 0,0148 05:00 - 06:00 2 0,0148 06:00 - 07:00 4 0,0295 07:00 - 08:00 2 0,0148 08:00 - 09:00 7 0,0517 09:00 - 10:00 3 0,0222 10:00 - 11:00 4 0,0295 11:00 - 12:00 9 0,0665 12:00 - 13:00 16 0,1182 13:00 - 14.00 18 0,1330 14:00 - 15:00 39 0,2881 15:00 - 16:00 95 0,7017 16:00 -17:00 290 2,1421 17:00 - 18:00 243 1,7949 18:00 - 19:00 108 0,7978 19:00 -20:00 86 0,6352 20:00 - 21:00 63 0,4654 21:00 - 22:00 45 0,3324 22:00 -23:00 28 0,2068 23:00 - 24:00 53 0,3915 Total 1123

Page 105: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

95

Table A4-4: Variation of Failure Rate of 10–20 kV Aerial Insulated Lines on Jan. 8, 2005, E.ON Elnät Sverige AB. Sustained outage > 3 minutes on 8 Jan. 2005, E.ON Elnät

Time Number of failures

Failure rate (f/hour.100km)

00:00 - 01:00 0 0,0000 01:00 - 02:00 0 0,0000 02:00 - 03:00 0 0,0000 03:00 - 04:00 0 0,0000 04:00 - 05:00 0 0,0000 05:00 - 06:00 0 0,0000 06:00 - 07:00 0 0,0000 07:00 - 08:00 0 0,0000 08:00 - 09:00 2 0,0347 09:00 - 10:00 0 0,0000 10:00 - 11:00 0 0,0000 11:00 - 12:00 1 0,0173 12:00 - 13:00 2 0,0347 13:00 - 14.00 1 0,0173 14:00 - 15:00 6 0,1041 15:00 - 16:00 9 0,1561 16:00 -17:00 37 0,6417 17:00 - 18:00 21 0,3642 18:00 - 19:00 3 0,0520 19:00 -20:00 3 0,0520 20:00 - 21:00 6 0,1041 21:00 - 22:00 3 0,0520 22:00 -23:00 1 0,0173 23:00 - 24:00 0,0000 Total 95

Page 106: Study and Analysis of Distribution Equipment Reliability Data...equipment reliability data can be affected by manufacture, voltage level, construction, size, time period, geography,

ELFORSK

2