stoughton high school · o chiller plant o chilled water distribution o chilled beam unit chiller...

16
Stoughton High School HVAC System: Basis of Design. 1

Upload: vohanh

Post on 21-Aug-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Stoughton High School

HVAC System: Basis of Design.1

Basis of Design Criteria

2Consulting Engineering Services, Inc.

o Occupant Thermal Comfort

o Indoor Air Quality

o Energy Efficiency / Environmental Impact

o System Noise

o First Cost / Return on Investment

o Maintenance

o Reliability

o LEED

HVAC: Energy Design Criteria

3Consulting Engineering Services, Inc.

• ASHRAE Standard 90.1

o Minimum Energy Criteria for Standard Construction

o ASHRAE Standard establishes a baseline system.

o High Performance and LEED Bldgs:

Design team develops a building which exceeds the

base line by 22%

o Building efficiency is measure with an energy model.

HVAC: System Options

4Consulting Engineering Services, Inc.

• Base Line: Variable Air Volume Air System (VAV)

o ASHRAE 90.1 minimum criteria

• System 1 (SD Basis of Design): Variable Refrigerant Flow System (VRF)

o Typically better than ASHRAE 90.1 by 25%~30%.

• System 2: Chilled Beam System

o Typically better than ASHRAE 90.1 by 25%~30%.

• System 3: High Performance VAV

o Typically better than ASHRAE 90.1 by 18%~23%.

VAV Box

VRF Fan Coil Unit

Chilled Beam Unit

VAV Box

Baseline HVAC System

5Consulting Engineering Services, Inc.

• Minimum Energy Requirement: ASHRAE 90.1

• Classrooms & Offices Heating / Cooling:

o Variable Air Volume Boxes for Zone Control (VAV)

o Package Roof Top Unit (RTU) with Gas Furnace Section.

VRF Description System

6Consulting Engineering Services, Inc.

• Classrooms & Offices Heating & Cooling:

o VRF Indoor Fan Coil Units

o VRF Outdoor Air Cooled Heat Pumps

o Refrigerant Pipe Distribution

o Heat Recovery System

Outdoor Unit

Indoor Unit

(Cooling Mode)

Indoor Unit

(Heating Mode)

Outdoor Unit

Indoor Unit Options

Overall System

VRF System Components

VRF Typical Classroom Layout

Terminal Cooling

Device Supply Air

Filtered Return

Exhaust Air

Outdoor Air

Control Damper

Perimeter Radiation or Radiant Ceiling Heating

7Consulting Engineering Services, Inc.

1

3

4

5

6

2

7

VRF System Summary

8Consulting Engineering Services, Inc.

• Pros:

o Comfort: Individual Room Control.

o Energy Efficient: Heat Recovery. Matches Cooling and Heating

o Quiet. Exceeds stringent noise criteria

o Distribution takes up little space due to minimum ductwork for ventilation

o Indoor Air Quality: Temperature control (VRF) is separated from ventilation air system.

With decoupled ventilation and temperature control, mold issues are minimized.

o Less expensive as compare to chilled beam and high performance VAV.

o Demand control ventilation

• Cons:

o Distributive Filters

o Distributive Condensate piping

Chilled Beam System Description

9Consulting Engineering Services, Inc.

• Classrooms & Offices Heating & Cooling:

o Chiller Plant

o Chilled Water Distribution

o Chilled Beam Unit

Chiller

Chilled

Water and

Hot Water

Distribution

Overall SystemChilled Beam Section

Chilled Beam in Ceiling

Chilled Beam Typical Classroom Layout

10Consulting Engineering Services, Inc.

Chilled Beam

Exhaust Air

Outdoor Air

Perimeter Heating

1

2

3

4

Chilled Beam System Summary

11Consulting Engineering Services, Inc.

• Pros:

o Comfort: Individual Room Control.

o Energy Efficient: Heat Recovery. Matches Cooling and Heating

o Quiet. Exceeds stringent noise criteria

o Distribution takes up little space due to minimum ductwork for ventilation

o Indoor Air Quality: Temperature control (VRF) is separated from ventilation air system.

With decoupled ventilation and temperature control, mold issues are minimized.

• Cons:

o Condensate issue. Tight humidity control required. On humid days, air conditioning will turn off

with open windows or open classroom exterior doors.

o More expensive as compare to VRF.

o Demand control ventilation.

High Performance VAV System

Description System

12Consulting Engineering Services, Inc.

• Classrooms & Offices Heating & Cooling:

o Central Ductwork Distribution with Variable Air Volume Boxes for Zone Control (VAV)

o To achieve High Performance:

• Larger than average ductwork

• Custom Air Handler, AHU (Roof Top or Indoor)

• Optimization Control Strategy

• Water Cooled Chiller

• Cooling Tower

Custom Air Handling Unit Magnetic Bearing Water

Cooled Chiller

Cooling Tower

Overall System

High Performance VAV System Summary

13Consulting Engineering Services, Inc.

VAV Box w/reheat

Supply Air

Return Air

Perimeter Heating

1

2

3

4

High Performance VAV System Summary

14Consulting Engineering Services, Inc.

• Pros:

o Central air filtration and condensate.

o Central compressors

• Cons:

o Comfort / Indoor Air Quality: Temperature control system and ventilation control are from the same

distribution source. Does not provide humidity control or mold control.

o Large than average ductwork required to meet noise criteria energy criteria. Takes up an additional

12” to 18” as compared the VRF and Chilled Beams.

o In order to out-perform ASHRAE 90.1 by 22%, Custom Air Handling Units are required.

o More expensive as compare to VRF. Approximately.

COMMON HVAC Components

15Consulting Engineering Services, Inc.

• Ventilation Source: Dedicated Outdoor Air System (DOA) with Heat Recovery

• Central Boiler Plant: High Efficient Condensing Boilers.

• Perimeter Heating

*Not common for High Performance VAV

DOA Diagram* Condensing Boiler DOA*

Perimeter Heating

Comparison Summary

16Consulting Engineering Services, Inc.

Function System 1 (SD Basis of Design)

Variable Refrigerant Volume (VRF)

System 2

Chilled Beam

System 3

High Performance VAV

Ventilation Ventilation provided by Dedicated Outdoor Air System

(DOA) with energy recovery

Same as System 1 Ventilation provided by mixing outside air and return air in the

VAV air handling unit.

Humidity

Control

Ventilation air pretreated by DOA to conditions that will

handle the moisture added by ventilation

Same as System 1 Humidity loads are addressed at air handler. Humidity

conditions may occur when outside air is cool and damp,

Control

System

A central DDC control system with web based control Same as System 1 Same as System 1

Pros • Comfort

• Energy Efficient:

• Quiet.

• Takes up little space

• Indoor Air Quality. Minimizes any mold issue

• Less expensive Vs. Chilled Beam

• Demand control ventilation

• Comfort

• Energy Efficient:

• Quiet.

• Takes up little space

• Indoor Air Quality. Minimizes any

mold issue

Central air filtration and condensate

Cons • Distributive Filters

• Distributive Condensate piping

• Condensate issue. Tight humidity

control ,Windows remain closed

• More expensive as compare to VRF.

• Demand control ventilation not

feasible

• Comfort / Indoor Air Quality: Temperature control system and

ventilation control are from the same distribution source. Does

not provide humidity control or mold control.

• Large than average ductwork required to meet noise criteria

energy criteria. Takes up an additional 12” to 18” as compared

the VRF and Chilled Beams.

• In order to out-perform ASHRAE 90.1 by 22%, Custom Air

Handling Units is required.

• More expensive as compare to VRF.

• Demand control ventilation not feasible.