    Hydrostatic Test in Steam Boiler

    Hydrostatic test in steam boiler is one of non destructive examinations which should be

    performed for new steam boiler or steam boiler which has been repaired such as replace water

    wall, superheater, reheater, economizer and so on to. Hydrostatic test must be done to make

    sure that steam boiler is free from leakage before start up is performed. Before hydrostatic test

    s executed, inspection for all welds and installation of pressure parts should be done. Moreover

    nside and outside of steam boiler and pressure part shall be free from all dirt, scale, paint,

    debris, dirt, weld slag, rust, oil, spatter and all other foreign matter.

    Before perform hydrostatic test (hydrotest) in steam boiler, the following matter should be

    prepared as follow:

    Non-destructive examination shall be verified to confirm acceptance as per Code and

    specification.

    1.

    Dimensional inspection.2.

    Full visual inspection for all welds.3.

    Boiler pressure part installation is completed.4.

    No painting work on pressure part before hydrostatic test.5.

    Inside and outside of boiler and pressure part shall be free from all dirt, debris, weld slag

    and spatter, oil, rust, scale, paint and all other foreign matter.

    6.

    Prepare and check valve line-up.7.

    All gags shall be installed on safety valve.8.

    Vent and drain are to be provided for the system before commence of hydrostatic test.9.

    All temporary fitting, blind flange shall be suitable for the test procedure and should not

    have defect that may cause failure during hydrostatic test.

    10.

    Fill boiler with treated water and free from mineral or other suspended matter

    (Demineralized water).

    11.

    Requirement of gauge and record during hydrostatic test in steam boiler (hydro test):

    A minimum of 2 (two) pressure gauge shall be used for pressure tests. One shall be a

    pressure temperature recorder with a range suitable for recording of the test pressure.

    The full scale of the other pressure gauge shall preferably 1 to 4 times of test pressure.

    1.

    The test pump and the line to be tested shall be provided with the separate indicating

    test gauges. In case of testing between a high and low point of the module, gauges shall

    be placed one at the top and one at the bottom to measure the pressured drop.

    2.

    The pressure gauge shall be calibrated and still valid before used. Any gauges showing

    incorrect zero error more than + 1% of full-scale range shall not be used without repair

    and recalibrate.

    3.

    Hydrostatic test must follow the determined procedure which is generally a s follows:

    Install suitable temporary fitting such as blind flange or end plate to close opening and1.

    Beauty & Fashion

    Cosmetics

    Cosmetic Surgery

    Designer Footwear

    Perfume

    Sunglasses

    Computers

    Computer Games

    Domain Hosting

    Domain Registration

    Free Internet

    Firewall

    Electronics

    DVDs

    Digital Cameras

    Laptops

    Mobile Phones

    MP3 Players

    Entertainment

    Books

    Concert Tickets

    Games

    Fantasy Football

    MP3 Download

    Finance

    Credit Card Help

    Debt Consolidation

    Financial Adviser

    InvestingLoans

    Travel

    Airline Tickets

    Car Rental

    Cruises

    Golf Vacation

    Romantic Getaways

    Chitika | Select

    Performance Testing of Boiler

    Performance Assessment of Boiler

    Hydrostatic Test in Steam Boiler

    Boiling Out in Steam Boiler

    Chemical Cleaning in Steam Boiler

    Boiler Evaluation

    Related Post

    steam boiler update

  • 7/28/2019 Steam Boiler_ Hydrostatic Test in Steam Boiler

    2/2

    Newer Post Older PostHome

    Subscribe to: Post Comments (Atom)

    Labels: Steam Boiler Testing

    ensure all of openings are closed except venting valve.

    Fill the steam boiler with treated water, free from mineral or other suspended matter at

    temperature not under 70 F or ambient temperature.

    2.

    Inspect leakage when steam boiler is being filled, remove air through venting valve, close

    it if there is not leakage and air is totally removed.

    3.

    Increase pressure gradually with maximum pressure rate 5 kg/cm2 until 1.5 times of

    maximum allowable working pressure for new boiler and 1.2 times for repaired boiler.

    4.

    Record pressure, time and temperature during test and inspect all of pressure parts of

    steam boiler at holding time of hydrostatic test approximately 10 minutes. 6. After

    hydrostatic test, the pressure should be release in a manner and at rate so as not to

    endanger personnel or damage equipment.

    5.

    Recommend this on Google

    Post a Comment

    0 comments:

    Server not found

    Firefox can't find the

    server at

    r1rk9np7bpcsfoeekl0k

    a-fc-opensocial.google

    Check the

    address for

    typing errors

    such as

    ww.example.com

    instead of

    www.example.com

    l

    Travel template. Powered by Blogger.