static regain
TRANSCRIPT
MAE-403 - AIR CONDITIONING
Static Regain Method: lower the velocity for next section, to “regain” friction andlocalized losses, so that ALL outlets have the SAME STATIC PRESSURE.
This is best accomplished by the use of a computerized spreadsheet.
lossesr
losses
losses
PVCV
PVV
PP
PVPVP
∆+=
∆=−
=
∆++=+
22
:or22
:so
: wantwe22
21
2
21
22
12
21
1
22
2
ρρ
ρρ
ρρ
2/24/2005 1
MAE-403 - AIR CONDITIONING
60
x 1
5
30 x 15
150 l/s 150 l/s
150 l/s 150 l/s
440 cm
170 cm 440 cm
375 cm
40 cm
200 cm
4
56 7 8
215 cm
3
180 cm
2/24/2005 2
MAE-403 - AIR CONDITIONING
STATIC REGAIN METHOD EXAMPLE - uses hydraulic diameterρ = 1.2 kg/m3 Cr = 0.75 ε = 0.09 mm ν = 1.6E-05 m2/s ∆P
Sect. Descr. Air Flow W x H Veloc Dh Re fprime f F.Loss Length Co Pdyn Loss Sum Sect.l/s cm x cm m/s cm Pa/m m Pa Pa Pa
3-4 straight 600 60 x 15 6.67 24.0 1.00E+05 0.01982 0.01982 2.203 2.15 - - -4.74 -4.74 3-44-5 wye-br 300 30 x 15 6.67 - - 0.25 26.67 -6.67 -11.40 4-55-6 straight 300 30 x 15 6.67 20.0 8.33E+04 0.02075 0.02075 2.767 1.80 - - -4.98 -16.38 5-6
Diffuser 150 60 x 60 -20.83 -37.21 Diffuser 0.00%
Section 7-8 is now designed to give the same static pressure at the diffuser (or as close as we can).
7-8 straight 150 15 x 15 6.67 15.0 6.25E+04 0.02230 0.02230 3.964 4.40 - - -17.44 -33.82 11-12Diffuser 150 60 x 60 -20.83 -54.65 Diffuser
ALT to 7-8regain 150 20 x 15 5.00 8.75 -7.63 regain
7-8 straight 150 20 x 15 5.00 17.1 5.36E+04 0.02264 0.02264 1.981 4.40 - - -8.72 -16.35 11-12Diffuser 150 60 x 60 -20.83 -37.18 Diffuser -0.09%
2/24/2005 3
MAE-403 - AIR CONDITIONING
60
x 1
5
30 x 15
150 l/s 150 l/s
150 l/s 150 l/s
440 cm
170 cm 440 cm
375 cm
40 cm
200 cm
4
56 7 8
215 cm
3
180 cm
20 x 15
2/24/2005 4
MAE-403 - AIR CONDITIONING
formulas
Veloc.= (Air Flow)/(WxHx10)Dh=4x(WxH)/(2*(W+H)) Eq. 24 Ch 32Re=VelocxDh/νfprime=0.11x(ε/Dh+68/Re)^0.25 Eq 21 Ch 32f: IF fprime >= 0.018 THEN f=fprime ELSE f=0.85xfprime+0.0028F.Loss=f x r x Veloc^2/(2xDh)Loss=L x F.LossorLoss=Co x PdynPdyn = r x V^2/2Regain = Cr x r x (Vout^2 - Vin^2)/2
2/24/2005 5
MAE-403 - AIR CONDITIONING
A computer program to solve Colebrook's Formula in Excel follows.
2/24/2005 6
MAE-403 - AIR CONDITIONINGOption Explicit'Calculates friction factor using Colebrok's formula'Uses ASHRAE Hndbk of Fundamentals 1997 Ch.2 eq.(29b) corrected'according to Shames, Mechanics of Fluids, 3rd. ed. eq.(9-18)Static Function ffriction#(Vdot As Double, W As Double, _
H As Double, nu As Double, eps As Double)Dim iter As Integer, itlim As Integer, a As IntegerDim Area As Double, Per As Double, Dh As Double, Vel As Double, _
Re As Double, fold As Double, f1 As Double, Df1 As Double, _tol As Double, invsqrtf As Double, conv As Double, _arg As Double, incr As Double, f As Double, _Vdotlocal As Double, Wlocal As Double, _Hlocal As Double, Log10 As Double, _epslocal As Double
Log10 = Log(10#)Vdotlocal = Vdot / 1000# 'l/s -> m3/sWlocal = W / 100# ' cm -> mHlocal = H / 100# ' cm -> mepslocal = eps / 1000# ' mm -> mtol = 0.0000000001itlim = 100Area = Wlocal * HlocalPer = 2# * (Wlocal + Hlocal)
2/24/2005 7
MAE-403 - AIR CONDITIONING
Dh = 4# * Area / PerVel = Vdotlocal / AreaRe = Vel * Dh / nufold = 0.01iter = 0
100 iter = iter + 1f = foldinvsqrtf = 1# / Sqr(f)arg = (epslocal / Dh + 9.35 * invsqrtf / Re)f1 = invsqrtf - 1.14 + 2# * Log(arg) / Log10Df1 = -(0.5 + 9.35 / (Re * arg * Log10)) * (invsqrtf ^ 3)incr = f1 / Df1f = f - incrfold = fIf (iter > itlim) Thena = MsgBox("iterations: limit exceeded!", 0, "error!")Return
End IfIf (Abs(incr) > tol) Then GoTo 100ffriction = f
End Function
2/24/2005 8
MAE-403 - AIR CONDITIONING
2/24/2005 9
2/24/2005 10
MAE-403 - AIR CONDITIONING
Neck Ve locity (m /s) 2 2.5 3 3.5 4 4.5 5 6 7 8Velocity Pressure, Pa 2.5 4 5.5 7.75 10 12.5 15.5 22.5 30.4 40
Total Pressure 3.81 5.84 8.64 11.68 15.24 19.30 23.88 34.29 46.48 60.71
6Flow Rate , l/s 37 46 56 65 74 83 93 111 129 148NC -- -- -- -- -- 19 22 28 33 37Throw m .75,.50,.25 0.3/0.6/1.2 0.3/0.6/1.2 0.6/0.9/1.5 0.6/0.9/1.8 0.6/1.2/2.1 0.9/1.2/2.1 0.9/1.2/2.1 1.2/1.5/2.4 1.2/1.8/2.7 1.5/2.1/2.7
Total Pressure 4.064 6.35 9.40 12.70 16.51 20.83 25.91 37.08 50.55 66.04
8Flow Rate , l/s 66 83 99 115 132 148 165 198 231 263NC -- -- -- -- 19 22 26 31 36 40Throw .75,.50,.25 0.6/0.6/1.5 0.6/0.9/1.8 0.6/1.2/2.1 0.9/1.2/2.4 0.9/1.5/2.7 1.2/1.8/2.7 1.2/1.8/3.0 1.5/2.1/3.3 1.8/2.4/3.6 2.1/2.7/3.6
Total Pressure 4.826 7.62 11.18 15.24 19.81 24.89 30.99 44.45 60.45 78.99
10Flow Rate , l/s 103 129 154 180 206 232 257 309 360 412NC -- -- -- 17 21 25 28 34 39 43Throw .75,.50,.25 0.6/0.9/1.8 0.9/1.2/2.4 0.9/1.5/2.7 1.2/1.8/3.0 1.2/1.8/3.3 1.5/2.1/3.6 1.5/2.4/3.6 1.8/2.7/3.9 2.4/3.3/4.2 2.7/3.3/4.5
Performance Data - 24 x 24 / 600 x 600 Face Size - METRIC
Listed Size
Diff
user
Dat
a
MAE-403 - AIR CONDITIONING
2/24/2005 11
60
x 1
5
30 x 15
150 l/s 150 l/s
150 l/s 150 l/s
440 cm
170 cm 440 cm
375 cm
40 cm
200 cm
4
56 7 8
215 cm
3
9
10
11
12 13 14
180 cm
20 x 15
MAE-403 - AIR CONDITIONING
4 wye-st 300 30 x 15 6.67 - - 0.13 26.67 -3.47 -8.20 44-9 straight 300 30 x 15 6.67 20.0 8.33E+04 0.02075 0.02075 2.767 0.40 - - -1.11 -9.31 4-9
9-10 straight 300 30 x 15 6.67 20.0 8.33E+04 0.02075 0.02075 2.767 3.75 - - -10.37 -19.68 9-1010-11 elbow 300 30 x 15 6.67 - - 0.12 26.67 -3.20 -22.88 10-1111-12 straight 300 30 x 15 6.67 20.0 8.33E+04 0.02075 0.02075 2.767 2.00 - - -5.53 -28.42 11-12
Diffuser 150 60 x 60 -20.83 -49.25 Diffuser 32.34%ALT to 4-12
4 wye-st 300 30 x 15 6.67 - - 0.13 26.67 -3.47 -8.20 44-9 straight 300 30 x 15 6.67 20.0 8.33E+04 0.02075 0.02075 2.767 0.40 - - -1.11 -9.31 4-9
regain 300 0 x 15 #DIV/0! #DIV/0! #DIV/0! regain9-10 straight 300 0 x 15 #DIV/0! 0.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! 3.75 - - #DIV/0! #DIV/0! 9-1010-11 elbow 300 0 x 15 #DIV/0! - - 0.12 #DIV/0! #DIV/0! #DIV/0! 10-1111-12 straight 300 0 x 15 #DIV/0! 0.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! 2.00 - - #DIV/0! #DIV/0! 11-12
Diffuser 150 60 x 60 -20.83 #DIV/0! Diffuser #DIV/0!
13-14 straight 150 17.50 x 15 5.71 16.2 5.77E+04 0.02245 0.02245 2.723 4.40 - - -11.98 #DIV/0! 13-14Diffuser 150 60 x 60 -20.83 #DIV/0! Diffuser #DIV/0!
ALT to 13-14regain 150 0 x 15 #DIV/0! #DIV/0! #DIV/0! regain13-14 straight 150 0 x 15 #DIV/0! 0.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! 4.40 - - #DIV/0! #DIV/0! 13-14
Diffuser 150 60 x 60 -20.83 #DIV/0! Diffuser #DIV/0!
2/24/2005 12
MAE-403 - AIR CONDITIONING
Assignment: Use the spreadsheet and the drawing posted, and complete the design of the rest of the duct system using Static Regain.
Due: next class