static and dynamic approaches for analyzing voltage stability
TRANSCRIPT
![Page 1: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/1.jpg)
EUROPEAN TRANSACTIONS ON ELECTRICAL POWEREuro. Trans. Electr. Power 2006; 16:277–296Published online 2 February 2006 in Wiley InterScience (www.interscience.wiley.com). DOI: 10.1002/etep.87
Static and dynamic approaches for analyzing voltage stability
X. Lei*,y and D. Retzmann
Bijing XuJi Co. Xinxi Road 5, Shagdi, Beijing, 100085, China
SUMMARY
Voltage stability analysis always involves a large number of devices with various dynamic characteristics in powersystem. For properly capturing static and dynamic behaviors providing insights into characteristics of the voltagestability of the system, different system models are established for different time-scale studies. In this paper,relevant system models are discussed taking into account load characteristics. Based on these models, differentapproaches such as static analysis, time-domain simulation and quasi-steady state (QSS) approximation areimplemented into a simulation program, which is used as a comprehensive tool for analyzing voltage stability. Bycomplementary use of these approaches with the simulation program, voltage collapse stresses of the systemunder a critical operating condition can be analysed in steady state, and impacts of special events on the voltagestability can also be simulated with time-domain simulations. For time-domain simulations, a full system modeland a QSS approximation can be adopted for capturing different forms of instability mechanisms. A test system isused to demonstrate the feasibility and effectiveness of the approaches implemented. Copyright # 2006 JohnWiley & Sons, Ltd.
key words: voltage stability; static analysis; short-term and long-term dynamics approximation; quasi-steadystate approximation (QSS); time-domain simulation and modelling of load characteristics
1. INTRODUCTION
Dynamic phenomena causing voltage instability, occurring in electric power system subjected to
strong load demands, lead to a progressive decrease or, sometimes, fast drop of the voltage magnitude
at one or more busses, resulting sometimes in network islanding, thus leading to local or global
blackout.
Since environmental and economic constraints limit the construction of new generation and
transmission systems, and power demands are predicted to increase, the voltage instability problem
appears to be more and more topical and concerns about voltages instability risks are also rapidly
growing on.
Typical slowness of the voltage instability processes suggests treating the problem as steady-state
one. However, dynamic aspects cannot be neglected in the framework for voltage collapse analysis and
accurate mathematical model of the network components is required, if large perturbations occur and
Copyright # 2006 John Wiley & Sons, Ltd.
*Correspondence to: Xianzhang Lei, Bijing XuJi Co. Xinxi Road 5, Shagdi, Beijing, 100085, China.yE-mail: [email protected]
![Page 2: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/2.jpg)
short-medium term transients become topical. As a consequence, to accurately simulate the system
voltage dynamics, overall system should be modeled by a set of differential and algebraic equations, in
which load flow equations are included as constraints.
Some new tools especially for voltage stability analysis have been developed. While developing
news tools, it is possible to exploit and extend conventional tools into this area. In this paper, the
authors introduce a comprehensive simulation program, and attempt to use this program for analyzing
voltage stability both in static and dynamic manner. With the program, components, which can
significantly affect voltage stability, can be modeled in detail. This also includes induction motors,
load with different dynamics and control systems, even such as AVR or over-excitation limiters
(OXLs) on synchronous generators, etc. By establishing adequate system models, voltage collapse
stresses of the system under a critical operating condition can be analyzed in steady state, and impacts
of special events (e.g., faults, motor starting, transformer’s tap changing, load varying) on the voltage
stability can also be simulated with time-domain simulations. For time-domain simulations, a full
system model and a quasi steady-state (QSS) approximation can be adopted for capturing different
forms of instability mechanisms.
This paper is organized as follows: in Section 2, static and dynamic models of a power system are
discussed, while modeling characteristics of some load and generator that appropriately represent the
system for the subsequent voltage collapse studies are described in Section 3. In Section 4, a
comprehensive simulation program, where static and dynamic approaches for analyzing voltage
stability are implemented, is presented. With this program, case studies on a test power system are
carried out with static analysis, time-domain simulation and QSS analysis, respectively for demon-
strating the usability of the simulation program.
2. POWER SYSTEM MODELS
Voltage collapse studies and their related tools are typically based on the following general
mathematical description of the system consisting of a set of algebraic and differential equations [1]:
_x ¼ f x; y; zð Þ_z ¼ h x; y; zð Þ0 ¼ g x; y; zð Þ
ð1Þ
where x 2 Rm represents the short-term state variables corresponding to fast dynamic states of
generators, induction motor loads, FACTS and HVDC controllers, etc; y 2 Rk corresponds to the
algebraic variables, usually associated to the transmission system and steady-state element models,
such as voltage magnitudes and phases at nodes, some generating sources and loads in the network;
z 2 Rn represents the long-term dynamic state variables of slow acting devices including well known
devices such as under-load tap-change (ULTC) transformers, OXLs and secondary voltage controls (if
any), etc. The differential equations represent the dynamic behavior of the system, while algebraic
equations represent the interaction of dynamic elements.
2.1. Static analysis based on load flow with full system model
Conventional load flow calculation is normally used to evaluate operation at a specific load level
specified by a given set of load and generation, where only algebraic part of the power system model is
278 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 3: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/3.jpg)
considered and dynamic characteristics of the system is completely ignored. Concerning voltage
stability phenomena, especially when the system operating under stressed conditions, some dynamic
elements in the system such as generators, induction motors, load consumed with certain dynamic
characteristics and related controllers (e.g., AVR or OXLs, etc.) can significantly impact on steady-
state operations of the system. In this point of view, dynamic characteristics of the system elements
must be taken into account during the load flow calculation, in order to achieve such a solution that
provide insights into characteristics of the voltage stability of the system. Thus, to calculate operating
points in respect to the generator output and load consumed, the full system model Equation (1) should
be adapted, where parameters being relevant for dynamic behaviors of the system are considered.
To solve the load flow with the full system model Equation (1), conventional methods of Newton
family can be used. The procedure is similar to the conventional load flow calculation, except that the
Jacobian matrix of the full system model is stated in the form of
J ¼
@f@x
@f@y
@f@z
@h@x
@h@y
@h@z
@g@x
@g@y
@g@z
26664
37775 ¼
fx fy fz
hx hy hz
gx gy gz
264
375 ð2Þ
where only gy represents the Jacobian matrix of the conventional load power equation, others describe
interactions among the dynamic and algebraic variables in the system, respectively. By ignoring very
slow dynamics with an assumption of zi ¼ constant ði ¼ 1; 2; . . . nÞ, the Jacobian matrix Equation (2)
can be simplified as
Js ¼fx fy
gx gy
� �ð3Þ
The application of the Schur formula to the matrix Js in Equation (3) with the assumption that fx is not
singular, leads to establish the relationship
det Jsð Þ ¼ det fxð Þ det gy � gx f�1x fy
� �¼ det fxð Þ det Jdð Þ ð4Þ
where Jd is defined as a dynamic load flow matrix given in the form of
Jd ¼ gy � gx f�1x fy ð5Þ
In comparison with conventional load flow, the main advantage offered by the use of the full system
model is that it ensures a link with system differential equations, thus permitting interaction dynamics
to be taken into account.
The most common use of load power in static voltage stability analysis is to provide the P-U and U-
Q curves at selected load buses [3,5,6]. P-U curve shows the relationship between the critical bus
voltage variations and the system load changes which indicates system loadability, while U-Q
characteristics indicate reactive power margin under a given voltage condition and implies the
weak bus which needs more reactive power support. However, one of the major limitations of static
analysis is that it can not properly capture the instability caused by dynamic reasons.
STATIC AND DYNAMIC APPROACHES 279
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 4: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/4.jpg)
2.2. Dynamic analysis based on time-domain simulation
Generally, dynamic analysis based on the time-domain simulation using the full system model
Equation (1) can capture all forms of instability mechanisms and thus to replicate the entire voltage
instability process with high accuracy. With further development of modern computer technology, it
has become quite feasible to deal with large-scale power system with a full system model Equation (1).
However, in engineering application, this time-domain simulation is inevitable very CPU-time
consuming when simulating a huge system with thousands of buses. Usually, a way to escape from
this situation without loosing calculation accuracy is to use multi-time scale simulation [3] with the
full system model Equation (1), where the simulation step can be changed while ensuring the
integration error is controlled in a reasonable limit.
For purpose of understanding voltage instability mechanisms, as well as devising faster analysis
methods, it is, however, advantageous to reduce the full system model for exploiting the time
separation, which exists between the short- and long-term phenomena [2]. A basic idea of this concept
consists in assuming that fast subsystem is infinite fast and can be replaced by its equilibrium
equations when dealing with the slow subsystem. Conversely, fast dynamics can be approximated by
considering the slow variables as practically constant during fast transients. This leads to a
significantly simple analysis of both subsystems.
The short-term time scale is the time scale of synchronous generators and their regulators (AVRs
and governors), induction motors, HVDC and FACTS devices. The corresponding dynamics last
typically for several seconds following a disturbance. For a short-term approximation with an
assumption of the slow variables remaining constant, the full system model Equation (1) is reduced
to short-term dynamic model given the form of
_x ¼ f x; y; zð Þ0 ¼ g x; y; zð Þ
ð6Þ
The long-term time scale is to deal with slow subsystems regarding phenomena, controllers and
protecting devices, which act over several minutes following a disturbance. It is also assumed that
components of slow variables are so designed to act after the short-term transients have died out, to
avoid unnecessary actions or even unstable interactions with short-term dynamics. This indicates that
the following equilibrium is already established when simulating long-term dynamics of the system
0 ¼ f x; y; zð Þ ð7Þ
In particular, the QSS approximation is used for dealing with long-term dynamics dominated by a
slow subsystem. Replacing the full system model Equation (1) with the condition described in
Equation (7), the QSS can be then stated in the form of
_z ¼ h x; y; zð Þ0 ¼ f x; y; zð Þ0 ¼ g x; y; zð Þ
ð8Þ
The QSS method gives a series equilibrium of the fast subsystem driven by the slow subsystem. This
replacement greatly decreases the order of the system equations. Furthermore, because the remained
280 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 5: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/5.jpg)
differential equations are only those relevant to slow subsystem, longer integration step can be used.
Depending on the adopted model, integration step can be up to 10s, while keeping the accuracy of the
simulation [3]. As a result, QSS approximation is dramatically fast compared with full model
simulation. For instance, on the 1200-bus system described in Reference [4], the simulation of system
behavior over 15 minutes following a major contingency takes only about 15 seconds.
3. MODELING OF COMPONENT CHARACTERISTICS
The term of load model refers to the active and reactive load equations used to represent the
characteristics of the load in voltage stability studies. Due to the fact that loads are generally voltage
dependent, load modeling is a critical aspect of voltage stability analysis. This is much unlike in the
angle stability studies, where loads are commonly modeled as constant power and constant
impedance. For capturing the characteristics of different loads, various approaches for load modeling
have been addressed in literature. A comprehensive summery can be found in References [7] and [8].
3.1. Static load models
Basically, there are two kinds of the load models: static model and dynamic model. A static model
expresses the active and reactive powers at any instant of time as functions of the bus voltage
magnitude and frequency at the same instant. Static load model is used both for essentially static load
components (e.g., resistive and lighting load), and as an approximation for dynamic load components
(e.g., motor-driven loads), and it includes constant impedance load model, constant current load
model, and constant power load model. Other two commonly used static load models that represent the
power relationship to voltage magnitude are as a polynomial equation and an exponential equation,
given in the following form respectively:
Exponential load model
P ¼ P0
U
U0
� ��
;Q ¼ Q0
U
U0
� ��
ð9Þ
Polynomial load model
P ¼ P0 a1
U
U0
� �2
þ a2
U
U0
� �þ a3
" #
Q ¼ Q0 a4
U
U0
� �2
þ a5
U
U0
� �þ a6
" # ð10Þ
where P and P0 are actual and initial active power; Q and Q0 are actual and initial reactive power and U
and U0 are actual and initial voltage; � and � indicate exponential factors; aiði ¼ 1; 2; . . . 6Þ stand for
multiplying factors. Discussions on the selection of the exponential and multiplying parameters can be
found in Reference [9]. Note that restoration dynamics of the load described in Equations (9) and (10)
can significantly influence the voltage recovery after a disturbance, and thus these dynamics shall be
considered for voltage stability studies too. A detailed description of this load restoration dynamics is
given in Reference [13].
STATIC AND DYNAMIC APPROACHES 281
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 6: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/6.jpg)
3.2. Dynamic load models
A dynamic load model expresses, on the other hand, the active and reactive powers at any instant of
time as functions of voltage magnitude and frequency at past instants of time and, usually,
including the present instant. Difference or differential equations can be used to represent such
models. As a typical dynamic load, models of the electrical machines have been well established
and widely implemented into simulation programs as standard models for voltage collapse
analysis. In addition to that, several References [10–12] have recently proposed simplified dynamic
load models intending to capture the essential behavior of loads with different transient and steady-
state characteristics, such as thermostatically-controlled loads and (with considerable care) some
motor-driven loads. While the form in which these models are presented appears quite different, it
can be shown that all, except for Reference [12], can be generalized to the block diagram shown in
Figure 1. The only difference in the model proposed in Reference [12] is that the final summation is
replaced by a multiplication.
In this model, the steady-state load-voltage characteristic is represented by the function g(U), which
can be either an exponential or polynomial function in U. For a thermostatic load, this would normally
be represented as constant power. The transient characteristic is represented by the function f(U),
which is often constant impedance. Frequency sensitivity can also be included in both of these
functions. Note that in this model, Pnom, Ps, and Pt indicate the load power consumed at nominal
conditions, i.e., 1.0 p.u. voltage and the rated frequency, the active power in a steady-state and at a
transient condition, respectively.
3.3. Modeling of ULTC
The ULTC tends to bring the load voltages back to their base point when voltage dropping due
to lack of power infed. Since system loads are generally voltage dependent, a voltage recovery
will generally result in an increase of power consumed toward their pre-contingency level.
This will cause further stress on the system and can eventually lead to a voltage collapse
condition. Thus, proper modeling of the ULTC is one of the basic requirements for voltage
collapse studies.
One modeling technique used to capture the effect of the finite range of ULTC taps is to enforce
constant MVA behavior for a range of voltages around nominal. Outside of this range load voltage
sensitivity is included. As with the generation protection, the ULTC must be modeled with their actual
T
1
(U)fPnom
sP
nomP
tP
+
+-+
U
nomP
(U)gPnom
Figure 1. Simplified dynamic load model.
282 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 7: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/7.jpg)
tap range and size, voltage controls and dead-bands, and settings for tap delay and tap motion time. So
that, it can be modeled as
rkþ1 ¼rk þ�r if U2 > U0
2 þ d and rk < rmax and delay > Tk
rk ��r if U2 < U02 � d and rk > rmin and delay > Tk
rk else
8>><>>: ð11Þ
where rk is the ratio of the step-down transformer at tap position k, rmax and rmin are the upper and the
lower limits of the ratio, respectively, U2 is the voltage magnitude at the secondary bus of the
transformer, d is the dead-band to prevent an ULTC from acting too frequently, �r is the size of each
tap step and Tk is delay time of the tap change action when the voltage is out of dead-band. Tk is not
necessarily constant and can be variable with the voltage so that an ULTC can have an inverse-time
delay. Obviously, this model will be implemented as a discrete model for voltage collapse studies.
3.4. Modeling of AVR and OXL
At a post-contingency (after tripping a faulted transmission line) steady-state operating condition,
where the generator field current is above its rated value, the reactive output may be above the value
obtained from the generator reactive capability curve. After several minutes of operation at this
condition, the OXL control resets the excitation voltage to its rated value. This typically causes a small
oscillation, and brings the field current down to rated. The reset action will cause a reduction in the
reactive output and terminal voltage of the machine. Under a sufficiently stressed state, the loss of the
transmission line and subsequent OXL action can cause other machines to reach excitation limits. This
action, along with other control actions and the characteristics of the system loads, can drive the
system into a voltage collapse. Thus, field current limit enforced by the generator OXL control
function is of particular concern when studying voltage stability.
Many types of OXLs are encountered in practice for voltage stability studies. The model proposed
by Reference [3] is as an example shown in Figure 2. This model limits the field current Ifd under Ilimfd
by injecting a signal xoxl into the AVR main summing junction and has an inverse-time characteristic
of overload capability allowing smaller over-excitations to last longer.
0xt
0x t
limfdI
fdIoxlx
+ 1s
Ks
0
0x t ≥
0x t
-Kr
tx
RsT11
AK
refU
tUfdE
+_
Over excitation limiter
_
_ <
Figure 2. AVR and OXL model.
STATIC AND DYNAMIC APPROACHES 283
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 8: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/8.jpg)
Since the action of OXLs may differ greatly from plant to plant, and if detailed models can not be
assembled and implemented, the model illustrated in Figure 2 can used as a general AVR and OXL
model for voltage stability studies.
4. A COMPREHENSIVE SIMULATION PROGRAM
Network torsion machine control (NETOMAC) is a simulation program used widely for the
simulation of electromechanical and electromagnetic transient phenomena, as well as long-term
time scale and steady-state behaviors of a power system [14,15]. Figure 2 shows the capabilities of the
program.
As shown in Figure 3, the load flow calculation mode is not only used as an independent function for
static analysis. It is also used as a precondition for the subsequent simulation by solving system
differential equations. This program uses a current iteration process with node admittance matrix for
determining the system operating point. Thus, it is robust in critical load flow calculations. Voltage
dependence of loads and actions of controllers as well as automatic setting of transformer tap changers
can be included in load flow calculations so that a true equilibrium can be obtained.
In time-domain, the program provides an instantaneous value mode similar to the EMTDC/EMTP
program and a stability mode like the PSS/E program. In stability mode, the networks are in the form
of complex impedance instead of differential equations. Machines are modeled by differential
equations. A number of standard models of machines and controllers such as synchronous machine,
induction motor, AVR, HVDC, and FACTS devices, etc., are implemented in a standard library and
can be used in simulation directly. Users can also define their own models for particular objectives
very conveniently, especially e.g. models of loads and network elements with voltage dependent
characteristics described in the previous section. In addition, the program provides also various time-
domain calculation modes used for voltage stability studies that are shaded in Figure 3, so that the
Simulation Models for System Components, Machines, Controllers and Control Units
Loadflow Initial Conditions Only Loadflow Loadflow Operating Point
Network in a-b-cAdmittances
differential equations
Single-line network complex admittancesalgebraic equations
System componentslinearization
Time range (ns~s)Instantaneous values
Time range (s~min)RMS values
Time range (min~h)RMS values
Frequencydomain analysis
Eigenvalueanalysis
Electromechanicalphenomena
for full system modelin eq (1) or
short-term dynamicmodel in eq. (6)
Electromechanicalphenomena
QSS analysisfor long-term dynamic
modelin eq. (7)
Loadflow for specialrequirements
Calculation withJacobian matrix
in eq. (2) orin eq. (3)
Small-signalcharacteristics
System oscillationand damping, Net
reduction,Controller layout
Electromagneticphenomena
for short-termdynamic
using modelin eq. (1) or in eq. (6)
Figure 3. General view of the capability of NETOMAC.
284 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 9: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/9.jpg)
voltage collapse can be analyzed with a detailed model or a QSS approximation. In Figure 4,
procedures of the program with different methodologies for voltage stability studies are illustrated.
The program can provide block-oriented language to establish corresponding models of the
controllers. Using standard control blocks, e.g., PI, PID, etc., which are implemented in a library of
the program, controllers commonly used in power system such as exciters, governors can be easily
modeled. In addition to the standard blocks, mathematical or logical statements can also be used to
describe some special functions such as discrete actions (e.g., ULTCs). Using this language, load
characteristics, e.g., equations given in Equations (9,10) or even functions described in Figure 1 can be
implemented as a variable-power unit, where voltage (U ) and frequency (f ) are defined as inputs (or
any other system variables affecting outputs) and active and reactive power as outputs. By use of such
a variable-power unit, various load characteristics and even simplified FACTS controllers and
generators can be modeled. By use of such a variable-power unit, various load characteristics and
even simplified FACTS controllers and generators can be modeled such that these elements can be
involved in both of power flow calculations and time-domain simulations, where load voltage-
dependency, controller limits and discrete functions, etc., are taken into account. The implementation
of these special units in the program is illustrated in Figure 5.
Due to the modular structure with the complex of algorithms implemented, this program offers
many advantages for voltage stability studies that are summarized as follows:
* Establishing various models depending on the requirement of studies, including full systemmodel, short-term time scale model, and QSS approximation model;
Establishing system modelstaking into account e.g.: Load characteristics Controls e.g. AVR & OXL Discrete functions e.g. ULTC
Steady state calculationPre-contingency
P-U and U-Q curvesfor detecting voltage collapse
Voltage collapse atPcritical or Qcritical
Time domain calculationPre- and post-contingency
Full system model in eq. (1)
Short-termdynamics
modelin eq. (6)
Long-termdynamics
QSS modelin eq. (8)
z remainingconstant
equilibrium ofshort-term dynamics
Identifying voltage collapse andAssessing voltage security
.
.
.
Figure 4. Studies for voltage collapse with the program.
Load flowcalculation
U, f, etc.
P+jQ
Variablepower Block
Time-domainsimulation
U, f, etc.
P+jQ
Figure 5. Variable-power unit participating in load flow calculation and time-domain simulation.
STATIC AND DYNAMIC APPROACHES 285
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 10: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/10.jpg)
* Modeling system components flexibly, including various generators, induction motors, and loadcharacteristics, devices with transient actions (e.g., exciters, governors and FACTS as wellHVDC), devices with slow actions (e.g., OXLs) and discrete actions (ULTCs);
* Static studies for determining P-U and Q-U curves with full system model or reduced model;* Time-domain simulations with full system model by changing integration’s steps or with QSS
approximation using electromechanical mode;* Time-domain simulation with short-term time-scale model using electromechanical or
electromagnetic mode;* Implementing voltage collapse indexes and further carrying out studies on voltage security
assessment flexibly;* Providing useful tools such as optimization and eigenvalue modes for voltage stability studies.
In the following section, case studies with different modes provided by the program are discussed.
5. CASE STUDIES
In this section, a test system shown in Figure 6 is used to illustrate the applications of NETOMAC in
voltage stability analysis in different time scales introduced in Section 2. The system represents a load
center supplied mostly by remote generators G1 and G2 and partly by a local generator G3. An ULTC
is equipped to automatically regulate the secondary voltage magnitude (Ubus11) of the step-down
transformer (T6) at Bus 11. Parameters of the system elements can be found in Reference [16].
5.1. Case study with static analysis
In this section, voltage characteristics in steady state are studied based on conventional P-U and U-Q
curves generated by a series of calculations of the system equilibrium. The case study is carried out
with two different models of L8, i.e., an exponential load model given in Equation (9) and a motor-load
shown in Figure 7. The goal of the study is to demonstrate impacts of the load voltage-dependency on
the voltage stability of the system. In this study, three sets of the �-� value in Equation (9) are used
�¼ �¼ 0 (constant power)
�¼ �¼ 1 (constant current)
�¼ �¼ 2 (constant impedance).
G1 T1 G3
G2
T5
T4
T3
T2
ULTC
1
Ubus9Ubus10
7
6
5
Ubus3
2
Ubus1T6
L8
L11
Ubus8
Ubus7
8
10
3
9
Figure 6. Test system.
286 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 11: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/11.jpg)
As motor-load, a steady-state model is used, which is represented by the well-known equivalent
circuit of a motor with a constant mechanical load Tm as shown in Figure 7.
For simplicity, Bus 1 in the test system shown in Figure 6 is defined as a slack bus, while Bus 2 and
Bus 3 in the system serve as P-U buses. To consider impacts of the field current limit of G2 and G3
voltage behaviors of the system, an upper limit of the reactive power output for each generator is
defined. In this study, generator G2 and G3 are modeled with a variable-power unit, respectively, in
which the relationship among the active and reactive power as well as voltage magnitude is magnitude
is described according to real situations. Since here effects of the load models are concerned, the active
power output and the terminal voltage magnitude of G2 and G3 are considered as constant,
respectively.
To produce P-U and U-Q curves, series of load flow calculations are performed until each load flow
fails to converge. The process runs fully automatically with the program NETOMAC. Results shown
in Figures 8 and 9 demonstrate that the load voltage-dependency largely affects the system voltage
characteristics. Under low voltage conditions, the constant impedance-load provides a load relief,
which is favorable to a stable operation of the system, whereas the constant power-load always keeps
its load requirement, so making the system prone to instability. The most serious situation is with the
motor-load. When highly loaded, motor absorbs more reactive power under low voltage conditions
than constant power-load, thus, it causes firstly voltage collapse of the system.
Rs Xs
Xm
Xr
U I
Rr
P=Tm
Figure 7. Steady-state equivalent circuit of motor with constant mechanical torque.
Figure 8. P-U curves with different types of the load (L8) at Bus 8.
STATIC AND DYNAMIC APPROACHES 287
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 12: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/12.jpg)
5.2. Case study with time-domain simulations
In this section, time-domain simulation is applied to analyze system dynamics following a loss of one
transmission line between Bus 6 and Bus 7 (without a fault). The initial operating condition is shown
in Table I.
Generators are modeled by Park equations with stator transient neglected. The model of the AVR
with the OXL used is shown in Figure 2 and the ULTC model applied is described in Equation (11),
respectively. Load L11 consists of a mixture with a half constant-current and a half constant-
impedance load for both active and reactive power. Load L8 is of two different types of the load: in
case 1, the type of L8 is the same as that of L11, while in case 2, L8 is of an equivalent induction motor
modeled as shown in Figure 7.
5.2.1. Case 1: Long-term instability. Simulation results are shown in Figures 10–13. In correspon-
dence with dynamic behaviors of the system, changes in ULTC ratios are given in Figure 14. The
evolution of the sequence of the events leading the instability is clearly reproduced.
The outage of one transmission line results in an increased reactive loss on the transmission line and
thus, largely reduces the transmission capability. As a consequence, voltages of the system drop. To
keep the terminal voltage magnitude constant, the AVR of G2 and G3 boost their field currents to
increase their reactive power outputs. With increasing the reactive power, the system becomes
transient stable and enters into a steady state by 40 seconds. During this time, the ULTC starts to act to
regulate voltage at Bus 11 (Ubus11) by lowering the tap ratio. After several tap changes, it succeeds in
Figure 9. U-Q curves with different types of the load (L8) at Bus 8.
Table I. An initial condition for time-domain simulations.
Bus P (MW) Q (MVar)
1 4085 12562 1734 7213 1154 10.908 3320 1030
11 3435 985
288 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 13: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/13.jpg)
0.85
0.9
0.95
1
1.05
1.1
0 50 100 150 200 250
U (p.u.)
Time (sec)
Bus 11
Bus 7
Bus 3
Figure 10. Voltages at buses.
2.8
3
3.2
3.4
3.6
3.8
4
0 50 100 150 200 250
I field,G3 (p.u.)
Time(sec)
Figure 11. G3 field current.
0.6
0.8
1
1.2
1.4
0 50 100 150 200 250
Q G3 (p.u.)
Time (sec)
Figure 12. G3 reactive power output.
STATIC AND DYNAMIC APPROACHES 289
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 14: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/14.jpg)
bringing the voltage back into dead-band. Because of the limited transmission capability of the
transmission lines between Bus 6 and Bus 7, the reactive power needed for bringing Ubus11 back is
mainly contributed from G3 by overshooting the field current. At about 101 seconds after that, the
system enters into a steady state again. However, at this moment, the field current of G3 is still over its
limit which is not allowed for a long-term operation due to generator protections. Thus, after 80
seconds, the OXL is activated to force the field current back to the limit’s value. This leads to a
reduction of reactive power generation and subsequently a decrease of the system voltage. To avoid a
further fall of the system voltage, the ULTC acts again and tries to regulate Ubus11 back to its pre-
contingency level. However, without reactive support from generators, every step change has an
adverse effect, i.e., reduces the voltage. Therefore, voltages of the system continuously decrease until
the ULTC reaches its limit. In this case, the system voltage is already at a very low level that can not be
tolerant for a long time. To maintain a stable operation of the system, further measures must be taken
which will not be discussed in this paper. As additional information, behaviors of the rotor angle of the
generators G2 and G3 are also illustrated in Figure 13.
Figure 13. Rotor angle of G2 and G3.
0.85
0.875
0.9
0.925
0.95
0.975
1
1.025
1.05
0 50 100 150 200 250
r (p.u.)
Time (sec)
Figure 14. ULTC ratio.
290 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 15: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/15.jpg)
5.2.2. Case 2: Short-term instability. In the case of L8 as an induction motor, the instability
mechanism is completely different from that demonstrated in case 1. Simulation results are shown
in Figures 15 and 16. Correspondingly, the procedure of tap changes of the ULTC is demonstrated in
Figure 17.
0.9
0.92
0.94
0.96
0.98
1
0 10 20 30 40
U bus7 (p.u.)
Time (sec)
Figure 15. Voltage at Bus 7.
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0 10 20 30 40
Q motor (p.u.)
Time (sec)
Figure 16. Reactive power drawn by motor.
0.975
0.981
0.988
0.994
1.000
1.006
0 10 20 30 40
r (p.u.)
Time (sec)
Figure 17. ULTC ratio.
STATIC AND DYNAMIC APPROACHES 291
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 16: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/16.jpg)
The tripping one of the transmission lines also triggers the action of the ULTC, which tries to bring
Ubus11 back. After the first action of the ULTC, a new stable equilibrium with increased motor slip and
reduced voltage at Bus 7 (Ubus7) is obtained. But the second tap change reduces Ubus7 further and
causes the motor loosing its equilibrium. During further drops of the voltage Ubus7, large amounts of
the reactive power are absorbed. This results in a voltage collapse in very short time. This effect can be
clearly observed in Figures 15 and 16.
5.3. Case study with QSS analysis
As described in Section 2, long-term voltage dynamics assume that inter-machine synchronizing
power oscillations have damped out, and focus mainly on actions of slow elements such as ULTCs
and OXLs, etc., where fast dynamics are replaced by their equilibrium equations and thus
further simplified to static models. In this section, the QSS approximation is adopted for
long-term voltage stability studies, where all dynamic models of generators and AVRs are replaced
by the corresponding static ones. With the assumption of the direct axis synchronous reactance Xd
being equal to the quadrature axis synchronous reactance Xq, the following equations are
established
PG ¼ EqUt
Xd
sinð� � �Þ
QG ¼ EqUt
Xd
cosð� � �Þ � U2
Xd
ð12Þ
where PG and QG represent the active and reactive power output of the generator respectively, Ut is the
generator terminal voltage magnitude, Eq is the q-axis voltage, � is rotor angle, and � is terminal
voltage phase angle. With assumption of active power output PG remaining constant and equal to PG0,
the static model of the generator can be simplified as
QG ¼ EqUt
Xd
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1 � PG0Xd
EqUt
� �2s
� U2t
Xd
ð13Þ
and the static model of AVR as:
Eq ¼ KAðUref � UtÞ ð14Þ
where KA is the gain of the AVR shown in Figure 2 and Uref is the reference voltage magnitude.
Equations of generator and the AVR are now only algebraic ones, which are expressed in their compact
form given in Equation (8) and are implemented in variable-power units within the simulation
program. The OXL and the ULTC are modeled in the same way as that in the time-domain simulation
with the full system model.
Figures 18 and 19 compare some results obtained from QSS approximations and detailed
simulations described in the previous section. Although some differences are observed at critical
time, results achieved with the QSS still demonstrate a satisfactory coherence with that obtained from
time-domain simulations with the full system model.
292 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 17: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/17.jpg)
6. CONCLUSION
For properly capturing static and dynamic behaviors providing insights into characteristics of the
voltage stability of a power system, various models for voltage stability studies are established in
multi-time-scale. In addition to P-U and U-Q analysis, full, long-term dynamic and short-term
dynamic simulations, modal analysis, as well as security-constrained optimal power flow analysis are
valuable tools for providing insight into the voltage instability and collapse phenomenon. This paper
has presented a comprehensive way for using different approaches that are implemented into the
simulation program. With this program adequate models can be established taking characteristics of
load and other elements of the system into account. Based on these models, voltage collapse stresses of
the system under a critical operating condition can be analyzed in steady state, and impacts of special
events on the voltage stability can also be simulated with time-domain simulations. For time-domain
simulations, a full system model and a QSS approximation can be adopted for capturing different
forms of instability mechanisms. Case studies validated the flexibility of the approaches implemented
for voltage stability studies.
Further possibilities of using the simulation program presented in this paper are such as studies on
voltage security assessment and studies on improvement of the voltage stability of a system by
0.86
0.9
0.94
0.98
1.02
1.06
1.1
0 50 100 150 200 250
U bus7 (p.u.)
Time(sec)
QSS approximation
Detailed model
Figure 18. Voltage at Bus 7.
0.4
0.6
0.8
1
1.2
1.4
0 50 100 150 200 250
Q G3 (p.u.)
Time (sec)
QSS approximation
Detailed model
Figure 19. G3 reactive power output.
STATIC AND DYNAMIC APPROACHES 293
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 18: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/18.jpg)
selecting adequate measures, e.g., FACTS or HVDC, etc. Other functions available in the program
such as optimization and eigenvalue calculation provide also useful tools for voltage stability studies.
7. LIST OF SYMBOLS AND ABBREVIATIONS
7.1. Symbols
x; z short-term and long-term state variable
_x; _z derivatives of short-term and long-term state variable
y algebraic variable
f, h short-term, long-term dynamics
g functions of algebraic variables
Rn n-dimension euler domain
J, Js Jacobian matrix of a full system and a reduced system
Jd, f(�), g(�), h(�), partition of Jacobian matrix
U, U0 voltage and nominal voltage
Ut generator terminal voltage
Uref reference voltage
P, Q active and reactive power consumption at U
P0, Q0 active and reactive power consumption at U0
PG, QG active and reactive power output of generator
PG0 initial active power output of generator
Pnom active power at normal condition
Ps, Pt steady-state and transient active power
f(U), g(U) function of transient and steady-state load-voltage characteristic
�, � exponential factor
ai multiplying factor
Efd, Ifd, Ilimfd field voltage, field current, and its limit
xt internal state variable of OXL
xoxl output signal of OXL
r, rk, rmin, rmax ratio, k-th ratio, minimum and maximum ratio of ULTC
d voltage difference dead band of ULTC
�r size of tap step of ULTC
Tk time delay of tap change of ULTC
U; I, complex voltage and current
Rs, Rr stator and rotor resistances
Xs, Xr stator and rotor leakage reactance
Xm rotor magnetizing reactance
Tm mechanical torque
Xd, Xq direct and quadrature axis synchronous reactance
Eq the q-axis voltage
�, ! rotor angle and rotor speed
� terminal voltage phase angle
Kr, KA gain constant
T, TR time constant
s Laplace operator
294 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 19: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/19.jpg)
@ partial derivative
(�)�1 matrix inversion
7.2. Abbreviations
AVR automatic voltage regulator
OXL over excitation limiter
ULTC under load tap changer
QSS quasi steady-state
FACTS flexible AC transmission systems
HVDC high voltage DC systems
NETOMAC network torsion machine control
EMTDC electromagnetic transients program for DC-application
EMTP electromagnetic transients program
PSS/E power-system simulation for engineering
PI proportional and integral block
PID proportional and integral and differential block
REFERENCES
1. Cutsem TV, Vournas CD. Voltage stability analysis in transient and mid-term time scales. IEEE Transactions on PowerSystems 1996; 1:146–154.
2. Kurita A, Oki K, Okubo H, Agematsu S, Klapper DB, Sanchez-Gasca JJ, Miller NW, Wirgau KA, Price WW, Youkins TD.Multiple time-scale power system dynamic simulation. IEEE Transactions on Power Systems 1993; 1:216–223.
3. Cutsem TV, Vournas CD. Voltage Stability of Electric Power Systems. Kluwer Academic Publishers: Boston/London/Dordrecht, 1998.
4. Cutsem TV, Jacquemart Y, Marquet JN, Pruvot P. A comprehensive analysis of mid-term voltage stability. IEEE Transac-tions on Power Systems 1995; 3:1173–1182.
5. Tamura Y, Mori H, Iwamoto S. Relationship between voltage instability and multiple power flow solutions in electric powersystems. IEEE Transactions on Power Apparatus and Systems 1983; 5:1115–1121.
6. IEEE Working Group on Voltage Stability: Suggested techniques for voltage stability analysis. IEEE Publication93TH0620-5PWR, USA, 1993.
7. IEEE Task Force Report. Load representation for dynamic performance analysis. IEEE Transactions on Power Systems1993; 2:472–482.
8. IEEE Task Force Paper. Standard load models for power flow and dynamic performance simulation. IEEE Transactions onPower Systems 1995; 3:1302–1313.
9. Hajagos LM, Danai B. Laboratory measurements and models of modern loads and their effect on voltage stability studies.IEEE Transactions on Power Systems 1998; 2:584–592.
10. Karlsson D, et al. Temporary load-voltage characteristics for voltage stability studies—field and laboratory measurements.CIGRE Conference: Paris/France 1992 (paper no. 38–204).
11. Karlsson D, Hill DJ. Modelling and identification of non-linear dynamic loads in power systems. IEEE Transactions onPower Systems 1994; 1:157–166.
12. Xu W, Mansour Y. Voltage stability analysis using generic dynamic load models. IEEE Transactions on Power Systems1994; 1:479–493.
13. Hill DJ. Nonlinear dynamic load models with recovery for voltage stability studies. IEEE Transactions on Power Systems1993; 1:166–176.
14. Lei X, Lerch E, Povh D, Ruhle O. A large integrated power system software package NETOMAC. POWERCON’98,International Conference on Power Systems Technology: Beijing/China 1998 (Proceedings pp. 17–22).
15. Kulicke B. NETOMAC digital program for simulating electromechanical and electromagnetic transient phenomena in a.c.systems (in German). Elektriz.-wirtsch 1979; 1:18–23.
16. Kundur P. Power system stability and control. McGraw-Hill: New York, 1994.
STATIC AND DYNAMIC APPROACHES 295
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296
![Page 20: Static and dynamic approaches for analyzing voltage stability](https://reader035.vdocuments.mx/reader035/viewer/2022072112/575004771a28ab11489eeae1/html5/thumbnails/20.jpg)
AUTHORS’ BIOGRAPHIES
Xianzhang Lei (1958) received the B.S. degree from Zhejiang University, China, and hisM.Sc. and Ph.D. degrees in Electrical Engineering from the Technical University of BerlinGermany, in 1982, 1987, and 1992, respectively. From 1987 to 1993 he worked as a researchfellow in the Department of Electrical Engineering at the Technical University of BerlinGermany. After that, he was as Post-Doctor fellow at the Yale University, USA. Since 1994 hehas been a senior manager in the Power Transmission and Distribution Group at Siemens inErlangen Germany. Now he is working with XJ Group in China as Vice President and ChiefTechnology Officer. He is junction-professor at several universities in the People’s Republicof China. (XJ Group, 100065 Beijing China, Phone: þ86 10 62982288, Fax: þ86 10
62984582, E-mail: [email protected])
Dietmar Retzmann (1947), VDE, graduated in Electrical Engineering (Dipl.-Ing.) atTechnical University of Darmstadt Germany, in 1974. He received Dr.-Ing. degree in 1983from the University of Erlangen-Nuremberg Germany. He is with Siemens ErlangenGermany, since 1982 and currently head of the Power Electronic Applications Departmentin the Power Transmission and Distribution Services Division. He is involved in developmentand testing of Advanced Technology Applications for HVDC, FACTS, Power Quality, andProtection. He co-operates with universities in Asia, Europe, and America. Since 1998 heis guest-professor of Tsinghua University in Beijing China. (Director Power ElectronicApplications, Network Analysis & Consulting, Power Transmission and Distribution Ser-
vices, Siemens AG, EV SE NC4, P. O. Box 3220, D-91050 Erlangen/Germany, Phone: þ49 9131 7-3 47 39,Fax: þ49 9131 7-3 44 45, E-mail: [email protected])
296 X. LEI AND D. RETZMANN
Copyright # 2006 John Wiley & Sons, Ltd. Euro. Trans. Electr. Power 2006; 16:277–296