Page 1: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

State-of-the-art safety engineering for BSL-3 labsDr Felix Gmünder, RBP, MOH-AFC

Page 2: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Agenda

State-of-the-art safety engineering for BSL-3 labs2

_ Integral risk control approach

_ Current BSL-3 base design characteristics

_ Integrated protection layers

_ The V-model for BSL-3 systems development and verification

Source: Basler & Hofmann

Page 3: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Integral Risk Control Approach

State-of-the-art safety engineering for BSL-3 labs3

Page 4: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Which Combination Do You Prefer?

State-of-the-art safety engineering for BSL-3 labs4

Latest safest car Old, dilapidated but functional car

Driven by “dumb” driver Driven by ”good” driver

Very safe car

A B

Page 5: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ideal Combination

State-of-the-art safety engineering for BSL-3 labs5

Driven by “good” driver

Very safe car

C

Page 6: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Containment Risk Controls

State-of-the-art safety engineering for BSL-3 labs6

Facility-related controls Organisational controls

Biosafety containment levels

1-4

Facility Management

TrainingCompetencesSkills

PPE

Architecture, structure

Engineering

Primary containment equipment

Facility-related controls Organisational controls

Architect, Engineer

User, Owner

Are these separate, independent

risk control elements?

If inseparable, what does it mean for facility design

and construction?

Page 7: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Conventional OHS Hierarchy of Controls

7 State-of-the-art safety engineering for BSL-3 labs

S• Substitution

T• Technical risk controls

(Facility related)

O• Organisational risk controls

P• Personal risk controls

Architecture introductory course:

Form Follows Function

The shape of a lab should primarily relate to its intended function

Page 8: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Actual OHS Hierarchy of Controls in BSL-3 Labs

8 State-of-the-art safety engineering for BSL-3 labs

S• Substitution

TOP• Facility-related risk controls• Organisational risk controls• Personal risk controls

A

• Attitude & discipline• Safety awareness, safety culture,

compliance with Standard Operating Procedures

Integralrisk control approach

Page 9: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

WHO Laboratory Biosafety Manual 2019

State-of-the-art safety engineering for BSL-3 labs9

“It is important to note that while a hierarchy of

control measures has been defined by many

countries, it cannot be assumed that one control

measure is always preferable to another (e.g.

engineering controls versus personal protective

equipment)”

Page 10: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Take-Home Message 1

State-of-the-art safety engineering for BSL-3 labs10

_ “Hardware”,

_ “Software” and

_ “Peopleware”

are inseparable risk controls that have an effect onsafety in BSL-3 Labs

State-of-the-art safety engineering for BSL-3 labs must factor in non facility-related controls such as administrative and personal controls

Source: Basler & Hofmann

Page 11: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Current BSL-3 Base Design Characteristics

State-of-the-art safety engineering for BSL-3 labs11

Page 12: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

High Biocontainment Base Design Concept

State-of-the-art safety engineering for BSL-3 labs12

_ It appears that structural/engineering measures are

based on a heuristic* “very-low” and “zero-release”

tolerance concept:

_ Originally borrowed from 1940s – 50s nuclear industry:

_ Isolators / safety cabinets as primary containment

_ “Leaktight” secondary containment with airlocks

_ High air exchange rates, negative pressure

_ Exhaust HEPA-Filter

_ Redundant critical systems (UPS, Fans, Filters, etc.)

https://en.wikipedia.org/wiki/Biocontainment

* An approach to problem solving that employs a practical method,

sufficient for reaching an immediate goal.

Page 13: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Empirical* Evidence

_ Empirical evidence indicates that lack of containment integrity per se is rarely a source of a lab outbreak_ Provided containment was built and is maintained according to proper biosafety design and

engineering practices!

_ How about the Pirbright 2007 FMDV outbreak?_ “The effluent pipes from IAH and Merial to the caustic soda final treatment plant are old and

appear not to have been subject to regular thorough inspections to ensure their integrity.” (Spratt report, 2008)

_ Cost (government and industry): ca. US$ 300 million

State-of-the-art safety engineering for BSL-3 labs13

* Gaining knowledge by means of observation or experience.

Page 14: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Laboratory-Associated Infections

LAI Frequencyper 1000 person years

Source

0.83 Clinical laboratories (BSL-2)Grist & Emslie, 1991

3 Research laboratories (BSL-2/3)US Dept Homeland Security, 2008

0 Research laboratories (BSL-4)US Dept Homeland Security, 2008

State-of-the-art safety engineering for BSL-3 labs14

All occupational incidents

60 OSHA incident rates for General Medical and Surgical Hospitals (2015)

64 Switzerland incident rates for healthcare (2014)

Page 15: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Take-Home Message 2

_ Risk assessment on BSL-3 structural/engineering measures and effectiveness in its classic meaning is not possible:_ No realistic models of containment failure exist

_ No failure data on individual containment measures available

_ No acceptability criteria: “It is unknown how safe is safe enough”

_ ALARA (as low as reasonably achievable)

_ At any cost? Overdesign issues?

_ Instead a heuristic/deterministic approach with adequate protection layers should be used:_ ALARP (as low as reasonably practicable)

State-of-the-art safety engineering for BSL-3 labs15

Page 16: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Integrated Protection Layers

State-of-the-art safety engineering for BSL-3 labs16

Page 17: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Predominant Release Routes (Alphabetic Order)

State-of-the-art safety engineering for BSL-3 labs17

_ Air

_ Effluent

_ Equipment

_ Personnel

_ Samples and reagents

_ Solid waste

Source: Basler & Hofmann

Page 18: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Preventing Laboratory Release

State-of-the-art safety engineering for BSL-3 labs18

ReleasePathogen

Risk GroupActivity

Shower airlock / H

and washing

PPE change rooms and procedures

Procedures,decontam

ination

_ Design, construction, SOPs, training, competences, skills

_ Design, construction, SOPs , training, competences, skills, PPE

_ SOPs, training, competences, skills, PPE

Page 19: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Integrated Protection Layers (Illustrative Examples)

State-of-the-art safety engineering for BSL-3 labs19

PathogenRisk

GroupActivity

Room airflow alarmMultiple compartment access routes

Room leaktightnessSelf closing doors

Inward airflow

_ For simplicity and illustration of the principle of integrated protection layers the number in this schematic is limited to three layers

_ Note that protection layers along a path are always combinations of facility and organisational controls

_ Redundant facility controls (backup systems) for critical paths

_ This emphasises the need for pre-qualification of the design

HEP

A-fil

ter

valid

atio

n

HEP

A-fil

ter

Air e

xcha

nge

rate

s

Culturevolumes, containers

Impervious floorand sealed drains

Drain integrity tests &effluent decon validation

Shower airlock / H

and washing

PPE change rooms and procedures

Procedures,decontam

ination

Page 20: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Engineering Systems: Single Point of Failure Resilience

_ A single point of failure (SPOF) is a part of a system that, if it fails, will stop the entire system from working properly

_ To make the BSL-3 ventilation resilient to single point of failure, two redundant exhaust fans are required, and the reliability and availability of the system must be tested

_ Enhanced resilience of the BSL-3 systems may be required as per risk assessment or legally required controls

State-of-the-art safety engineering for BSL-3 labs20

Aerosol release via fabric and closed

doorsInward airflow

Room leaktightnessSelf closing doors

Airflow alarmMultiple compartment

access routes

SPOF TestingPhysical inspections

Risk VerificationProtection Layers

Page 21: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

BSL-3 Systems that May Require Backup/Redundancy

System As per local legislation Operational (e.g. 24/7 lab)

Inward airflow (2 exhaust air handlers)

X (e.g. DE, US, SG, AS/NZ)

EM-power (incl. UPS) X (e.g. DE, SG) X2 supply air handlers XExhaust stack/High plume dilution fan X (e.g. US, SG)Backup autoclave XBackup effluent decon XBackup HEPA-filters (parallel config.) XEtc.

State-of-the-art safety engineering for BSL-3 labs21

Page 22: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Redundant Systems and Their Verification (Examples)

State-of-the-art safety engineering for BSL-3 labs22

Source: Basler & Hofmann

Primary System Backup System VerificationExhaust air handler Backup air handler SPOF testGrid Power UPS

EM-Power GensetSPOF test

Supply air handler Backup air handler SPOF testEffluent decon lift pump

Backup pump SPOF test

Critical sensor Backup sensor SPOF testHEPA-Filter 2nd filter in parallel Validation only (manual

switchover)HEPA-filter Exhaust stack/High

plume dilution fanMethod of constructionDischarge velocity

Page 23: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Directional Inward Airflow Requirements

_ Inward airflow into laboratory is maintained (WHO, 2004)

_ Inward airflow at all times(AS/NZS 2243.3:2010)

_ The laboratory shall be designed such that under failure conditions the airflow will not be reversed (BMBL, 2009)

_ A constant, controlled negative pressure must be maintained in the biosafety level area (TRBA 100, 2018)

23

BSL3 Lab 1

BSL3 Lab 2

BSL3 Lab 3

BSL3 Autoclave Dirty and Corridor

Storage

Cold Storage

Entry & Exit and Shower

Washing Room Storage

BSL2 Lab 1

BSL2 Lab 2

BSL2 Lab 3

Autoclave Clean and Corridor

BSL2 EntryBMS Control

room and meeting room

Drawing is Not to Scale.State-of-the-art safety engineering for BSL-3 labs

Page 24: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Selected BSL-3 Risk Control and Oversight Guidance Documents

State-of-the-art safety engineering for BSL-3 labs24

Control Measure 2000

/54/EC

(OHS)

2009

/41/EC

(GMO)

EN 1212

8

WHO (200

4)

AS 2243

.3:20

10

TRBA 100

Sealable for fumigation Recomm’d Yes Yes Yes Sealed Yes

Negative pressure Recomm’d Yes Yes Yes Yes Yes

UPS/Genset No No Option No Yes (BSC) Yes

Effluent decontamination Validated Option Yes Option Option Thermal

Page 25: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Current Minimum BSL-3 Ventilation Setup

State-of-the-art safety engineering for BSL-3 labs25

_ In order to maintain inward airflow (whichever standard or guideline is used)

Supply 1BSL-3Lab

Exhaust 2a

Exhaust 2bHEPA

Page 26: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ventilation Failure Fault-Tree Analysis

State-of-the-art safety engineering for BSL-3 labs26

Ventilation failure

Exhaust 2a failure Exhaust 2b failure Supply failure

Equipment failure

Exhaust failure

OR

AND

Page 27: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ventilation Failure Fault-Tree Analysis

State-of-the-art safety engineering for BSL-3 labs27

Ventilation failure

Exhaust 2a failure Exhaust 2b failure Supply failure Grid failure

Power failureEquipment failure

Em-power failure

Exhaust failure

OR

AND

Page 28: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Expanded Exhaust-Side Redundancies (Operational Requirements)

Base option

Option B

Option C

State-of-the-art safety engineering for BSL-3 labs28

HEPA EF2

HEPA EF1

HEPA

EF2

EF 1

HEPA EF2

HEPA EF1

Page 29: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Example Exhaust Fan Redundancy Options

Type Capacity Explanation CommentN + 1 2 x 100% Cold redundancy Stand-by equipment is off

Stand-by equipment may fail on demand2N 2 x 100% Warm redundancy 50%–50%–Operation

Reduced energy efficiency2N 2 x 100% Duty-standby 100%-100%-Operation

(Stand-by equipment is on, switchover)Running cost

2 x 0.5N + 0.5N

3 x 50% Warm redundancyor duty-standby

Running cost

State-of-the-art safety engineering for BSL-3 labs29

Page 30: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Verification Method: Pressure Differential Trending Logs

State-of-the-art safety engineering for BSL-3 labs30

_ Ventilation system controlled on and off, normal operation

_ All relevant, probable failure scenarios_ SPOF of mechanical

and electrical systems

Source: Basler & Hofmann

Page 31: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ventilation SPOF Test (Warm Redundancy Configuration)

State-of-the-art safety engineering for BSL-3 labs31

-110

-90

-70

-50

-30

-10

10

13:5

8

13:5

9

14:0

0

14:0

1

Room

Pre

ssur

e [P

a]

Time [hr:min]

(1) Lab 1 (2) Lab 2 (3) ABSL3 Lab 3 (4) Autoclave Dirty Corridor (5) Entry & Exit

Fail

Page 32: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ventilation SPOF Test

32 State-of-the-art safety engineering for BSL-3 labs

-110

-90

-70

-50

-30

-10

10

14:2

1

14:2

2

14:2

3

14:2

4

14:2

5

Room

Pre

ssur

e [P

a]

Time [hr:min]

(1) Lab 1 (2) Lab 2 (3) ABSL3 Lab 3 (4) Autoclave Dirty Corridor (5) Entry & Exit

Fail

Page 33: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Ventilation SPOF Test

33 State-of-the-art safety engineering for BSL-3 labs

-80

-60

-40

-20

0

20

40

60

80

100

14:2

4

14:2

5

14:2

6

14:2

7Room

Pre

ssur

e [P

a]

Time [hr:min]

(1) Lab 1 (2) Lab 2 (3) ABSL3 Lab 3 (4) Autoclave Dirty Corridor (5) Entry & Exit

Fail

Page 34: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Take-Home Message 3

State-of-the-art safety engineering for BSL-3 labs34

_ Choice of BSL-3 protection layers and redundancies is a result of (performance) requirements and risk assessments determined in design phase

ØDesign or pre-qualification

_ Implementation and performance to be verified during testing and commissioning (IQ, OQ)

Source: Basler & Hofmann

Page 35: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

The V-Model for BSL-3 Systems Development and Verification

State-of-the-art safety engineering for BSL-3 labs35

Page 36: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

The V-Model for Biosafety Labs

Certification of Biosafety Laboratories36

User Requirement Specifications

Validations (PQ)

Operational Qualification(Certification)

Detailed Design

InstallationQualification

Installation

Design

And

Design Pre-QualificationCom

mission

ing +

Testi

ng

Use

rB

SL-

3 P

roje

ct T

eam Functional Design

Certifier

Biorisk Management Development

Page 37: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Cost and Control Impact: Design Phase

State-of-the-art safety engineering for BSL-3 labs37

URS Validations

Operational Qualification

(BSL-3 Certification)

Detailed Design

InstallationQualificationInstallationFunctional

Design

Opportunitiesto reduce cost Cost of design changes

Design Pre-Qualification

Page 38: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Take-Home Message 4

State-of-the-art safety engineering for BSL-3 labs38

_ Pre-Qualification (DQ): Include design review by competent biosafety professional and engineer, preferably 3rd party

_ A testing and commissioning plan (IQ, OQ) is equally important as the design

_ Check the consultant’s and contractor’s competences before placing order

_ Validations are carried out by user (e.g. autoclave, fumigation, surface decontamination)

Source: Basler & Hofmann

Page 39: State-of-the-art safety engineering for BSL-3 labs...Engineering Systems: Single Point of Failure Resilience _ A single point of failure (SPOF) is a part of a system that, if it fails,

3rd International Conference onBiosafety and Laboratory

Thank you very muchBasler & Hofmann Switzerland

State-of-the-art safety engineering for BSL-3 labs39

Dr Felix Gmü[email protected]