spill prevention, control, and countermeasure (spcc) · pdf filefisk university, spill...

79
Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 1 of 79 Spill Prevention, Control, and Countermeasure (SPCC) Plan Facility: FISK University, Nashville Physical Location: 1000 17 th Ave. N, Nashville, TN 37208 Facility Contact and Phone Number: Norman A. Rapp Cell 615-456-9015 Home 615-865-6499 MANAGEMENT ENDORSEMENT: In accordance with 40 CFR Part 112.7, this SPCC plan is fully approved by the Administration of Fisk University, Nashville Tennessee, which commits the manpower, equipment, and materials necessary to fully implement this plan. Signature: ________________________________ Date: __________________________ Name: ___________________________________ Title: __________________________

Upload: buingoc

Post on 14-Feb-2018

220 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 1 of 79

Spill Prevention, Control, and Countermeasure (SPCC) Plan

Facility:

FISK University, Nashville

Physical Location:

1000 17th Ave. N, Nashville, TN 37208

Facility Contact and Phone Number:

Norman A. Rapp Cell 615-456-9015

Home 615-865-6499

MANAGEMENT ENDORSEMENT: In accordance with 40 CFR Part 112.7, this SPCC plan is fully approved by the Administration of Fisk University, Nashville Tennessee, which commits the manpower, equipment, and materials necessary to fully implement this plan. Signature: ________________________________ Date: __________________________ Name: ___________________________________ Title: __________________________

Page 2: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79

Table of Contents I. INTRODUCTION ---------------------------------------------------------------------------------------------------- 4 II. DEFINITIONS -------------------------------------------------------------------------------------------------------- 5 III. SPCC PLAN REVIEW - 40 CFR 112.5 ----------------------------------------------------------------------- 6 IV. FACILITY INFORMATION -------------------------------------------------------------------------------------- 7 V. PAST SPILL HISTORY - 40 CFR 112.7(A) ------------------------------------------------------------------ 9 VI. DEMONSTRATION OF PRACTICABILITY - 40 CFR 112. 7( D) -------------------------------------- 9 VII. FACILITY DRAINAGE - 40 CFR 112.7(E)(1) -------------------------------------------------------------- 9 VIII. BULK STORAGE TANKS - 40 CFR 112.7(E)(2) --------------------------------------------------------- 9 IX. FACILITY TRANSFER OPERATIONS, Pumping, & In-Plant Process 40 CFR 112.7(e)(3) ----- 10 X. FACILITY TANK TRUCK LOADING/UNLOADING - 40 CFR 112.7(E)(4) --------------------------- 10 XI. OIL PRODUCTION FACILITIES (ONSHORE) - 40 CFR 112.7(E)(5) -------------------------------- 10 XII. OIL DRILLING AND WORKOVER FACILITIES (ONSHORE) - 40 CFR 112.7(E)(6) ----------- 10 XIII. OIL DRILLING, PRODUCTION, OR WORKOVER FACILITIES (OFFSHORE) 40 CFR 112.7(E)(7) ---------------------------------------------------------------------------------------------------------------

10

XIV. INSPECTION AND RECORDS - 40 CFR 112.7(E)(8) ------------------------------------------------- 10 XV. PERSONNEL, TRAINING, AND SPILL PREVENTION PROCEDURES 40 CFR 112.7(E)(10 10 XVI. EPA FACILITY RESPONSE PLAN (FRP) CERTIFICATION OF APPLICABILITY 40 CFR 112.20(E) -----------------------------------------------------------------------------------------------------------------

13

XVII. CONTAINMENT, SECURITY, SPILL VOLUMES AND RATES - 40 CFR 112.7(B) & (C) --- A. CONTAINMENT AND DIVERSIONARY STRUCTURE – 40 CFR 112.7(C) B. SECURITY - 40 CFR 112.7(E)(9) C. POTENTIAL SPILL VOLUMES AND RATES – 112.7 (b)

14

TANK # 45116/17/18 – 1050 gallon Transformer Oil Tank (Crosthwaite) -------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

15

TANK # 13987/88/13058 – 840 gallon Transformer Oil Tank (Jubilee) ------------------------------------ A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

16

TANK # 48669/49591/49594 – 1200 gallon Transformer Oil Tank (Shane) ------------------------------ A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

17

TANK # 8555-803 – 280 gallon Transformer Oil Tank (Spence) -------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

18

TANK # 8555-806 – 250 gallon Transformer Oil Tank (Park Johnson) ----------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

19

TANK # 8555-808 – 280 gallon Transformer Oil Tank (New Livingstone) -------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9)

C, Potential Spill Volumes and Rates – 40 CFR 112.7(b)

20

TANK # 9505-807 -- 250 gallon Transformer Oil Tank (Gym) ----------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

21

TANK # 9505-806 – 250 gallon Transformer Oil Tank (DuBois) ------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

22

TANK # 8555-809 – 250 gallon Transformer Oil Tank (Cravath) ------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

23

Page 3: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 3 of 79

TANK # 9505-803 – 227 gallon Transformer Oil Tank (Apartment “A”) ----------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

24

TANK # 9505-801 – 227 gallon Transformer Oil Tank (Apartment “B”) ----------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

25

TANK # 9505-802 – 227 gallon Transformer Oil Tank (Apartment “C”) ----------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

26

TANK # 9505-803 – 227 gallon Transformer Oil Tank (Apartment “D”) ---------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

27

TANK # 32748 - 150 gallon Elevator Hydraulic Oil Tank (Crosthwaite) ---------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

30

TANK # 33071 - 300 gallon Elevator Hydraulic Oil Tank (Jubilee) ----------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

31

TANK # 21419 - 150 gallon Elevator Hydraulic Oil Tank (Shane) --------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

32

TANK # 28182 - 300 gallon Elevator Hydraulic Oil Tank (Spence) --------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

33

TANK # 1918 - 300 gallon Elevator Hydraulic Oil Tank (Spence) ------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

34

TANK # 9556-813 - 314 gallon Used cooking Oil Tank (Spence) ------------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

35

TANK # 32714 - 150 gallon Elevator Hydraulic Oil Tank (Park Johnson) --------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

36

TANK # 20125 - 300 gallon Elevator Hydraulic Oil Tank (Library) -------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

37

TANK # 20124 - 300 gallon Elevator Hydraulic Oil Tank (Library) ---------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

38

TANK # 18079 - 150 gallon Elevator Hydraulic Oil Tank (New Livingstone) ----------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

39

TANK # 24976 - 150 gallon Elevator Hydraulic Oil Tank (Van Vechten) ---------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

40

Page 4: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 4 of 79

TANK # 33484 - 150 gallon Elevator Hydraulic Oil Tank (Cravath) ----------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

41

TANK # 29592 - 150 gallon Elevator Hydraulic Oil Tank (Talley Brady) ---------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

42

TANK # 29388 -150 gallon Elevator Hydraulic Oil Tank (Carnegie) ---------------------------------------- A. Containment and Diversionary Structure – 40 CFR 112.7(c) B. Security – 40 CFR 112.7(e)(9) C. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

43

TANK # F-964372 -300 gallon Transformer Oil Tank (Library) ---------------------------------------- D. Containment and Diversionary Structure – 40 CFR 112.7(c) E. Security – 40 CFR 112.7(e)(9) F. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

28/29

XVIII. Maps and Diagrams ------------------------------------------------------------------------------------- 44 XIX. Appendix A-1: Inspection Checklists ------------------------------------------------------------------ 73 XIX. Appendix A-2: Secondary Containment Inspection ------------------------------------------------ 74 XX. Appendix B: Spill Response Activities. ---------------------------------------------------------------- 75 XXI. APPENDIX C: Emergency Release Follow-up Notice -------------------------------------------- 79

I. Introduction This Spill Prevention Control and Countermeasures (SPCC) Plan has been prepared to meet the requirements of the United States Environmental Protection Agency (US EPA) which has published guidelines in the Federal Register Volume 28, No. 237, dated 11 December 1973, amended and codified under 40 CFR Part 112 Oil Pollution Prevention. In general, these regulations apply to facilities that could possibly discharge oil into navigable waters. Additionally, petroleum storage facilities in the State of Tennessee are subject to the statutes of Tennessee Department of Environment and Conservation section 1200-1-15. In accordance with the requirements of the Federal regulations, this plan must meet State regulation requirements. Throughout this document, Petroleum/Oils/Lubricants (POL) will refer to the low viscosity liquids subject to Federal and/or State of Tennessee regulations. As defined in 40 CFR Part 112, "Oil" means oil of any kind or in any form, including, but not limited to petroleum, fuel oil, sludge, oil refuse, and oil mixed with wastes other than dredged spoil. The term "Navigable Waters" means all navigable waters of the United States, as defined in Section 502(7) of the Federal Water Pollution Control Act (FWPCA), and includes all navigable waters of the United States, as defined in judicial decisions prior to passage of the 1972 amendments to the FWPCA, and tributaries of such waters; interstate waters, intrastate lakes, rivers, and streams which are utilized by interstate travelers for recreational or other purposes; and intrastate lakes, rivers, and streams from which fish or shellfish are taken and sold in interstate commerce. As required under 40 CFR Part 112.4, whenever a facility discharges more than 1,000 gallons of oil or discharges oil in harmful quantities as defined in 40 CFR Part 110 in two spill events within any twelve month period, into or upon the navigable waters of the United States or adjoining shorelines in a single spill event, the operator shall submit a report to the US EPA

Page 5: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 5 of 79

Regional Administrator. After review of the SPCC Plan and the submitted report, the US EPA Regional Administrator may require the owner/operator of the facility to amend the SPCC Plan. A copy of this SPCC Plan shall be maintained at the Plant Operations office at the facility. Upon request, the facility shall make the plan available to the US EPA Regional Administrator for onsite review during normal business hours. Management approval of this SPCC Plan and certification by a Registered Professional Engineer will be exhibited by endorsement signatures on the cover page of this plan.

II. Definitions Aboveground Storage Tank (AST): A tank that is wholly aboveground or with any portion of the tank visible at the surface. Partially buried, bunkered, or mounded tanks are all considered to be aboveground tanks as are tanks in subterranean vaults. Barrel: Forty-two United States gallons at sixty degrees Fahrenheit. Berm: Dirt, concrete, or other constructed embankment that is commonly employed for secondary containment of drainage diversion purposes at oil storage or related operations. Boom: A temporary floating barrier used to contain an oil spill. Bulk Storage Tank: Any container used to store oil. Containment of Diversionary Structure: Structure or equipment that prevents oil discharges from reaching navigable water. Containment of diversionary structures include dikes, berms, retaining walls, curbing, culverting, weirs, booms, spill diversion ponds, retention ponds, sorbent materials, and sumps. Dike: An embankment or wall that contains drainage water or spilled oil inside the walled area. Discharge: Any spilling, leaking, pumping, pouring, emitting, emptying, or dumping. Level Gauges and Alarms: any engineering control that indicates the level of liquid inside the tank and that is installed on tanks to prevent overfilling of the tank. Navigable Waters: Any waterway or tributary of a waterway within the United States that will ultimately end up in public waters such as a river, stream, lake, reservoir, bay, gulf, sea or ocean, either within or adjacent to the United States. Oil: Oil of any kind or in any form including, but not limited to, petroleum and petroleum-refined products, fuel oil, sludge, oil refuse, and oil mixed with wastes other than dredged spoil. Secondary Containment: Localized containment structure surrounding a potential source of oil discharge. Sheen: An iridescent appearance on the surface of water. Sludge: An aggregate of oil or oil plus other matter of any kind in any form other than dredged spoil having a combined specific gravity equivalent or greater to water. Sorbent: An aggregate of oil or oil plus other matter of any kind in any form other than dredged soil having a combined specific gravity equivalent or greater to water. Specific Gravity: The ratio of the density of a substance to the density of water.

Page 6: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 6 of 79

III. SPCC Plan Review - 40 CFR 112.5 The SPCC Plan will be reviewed and amended, if necessary, whenever: applicable regulations are revised; the plan fails in an emergency; the facility changes in its design, construction, operation, maintenance, or other circumstances in a way that materially increases the potential for fires, explosions, or releases of oil, or changes the response necessary in an emergency; the list of emergency coordinators changes; or the list of emergency equipment changes. At a minimum, the owner is required to review this plan every three years. All amendments to this SPCC Plan will be specified, or referred to, on the SPCC Plan Revisions form, provided below.

Table 1: SPCC Plan Revisions

Date

Reason for Review/Revision

Emergency Coordinator’s Name

and Initials 9/25/2008 Develop Spcc plan for the University Norm Rapp (NR) 1/13/2009 Addition of Library transformer Norm Rapp (NR)

Page 7: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 7 of 79

IV. Facility Information Facility Name: Fisk University Manned or Unmanned Facility: Manned Telephone Number: Maintenance Operations 615-329-8637 or, Campus Security 615-329-8777 Physical Address and Directions: The subject Facility is the Main Campus of Fisk University, Nashville. The Main Campus facility is located in Davidson County, Tennessee, approximately 1.15 miles west-northwest of the State Capitol. Latitude & Longitude: N 36º 09’ 59.75”, W 86º 48’ 12.30” Street Address: 1000 17th Ave. N. Nashville, Tennessee 37208 Owner/Operator Name: Fisk University Key Contact: Director of Maintenance Operations Key Contact's Telephone Number: (615) 456-9015-(615) 329-8637 Facility Description: The Fisk University Main Campus facility is a premier learning community for higher education. It was originally established in 1873. It covers approximately 68 acres, instructs approximately 1,000 enrolled students and employs close to 250 faculty and staff. Fisk University utilizes standby power generators at only two locations across campus. The Maintenance Department also oversees the maintenance of elevators across campus through the use of an outside contractor. The facilities and grounds department is broken down into the following departments.

• Grounds and Landscaping • Custodial Services • Facility Maintenance

Descriptions of the various fuel or, oil utilization locations are provided in Table 2 and Table 3. Building numbers are defined in, Section XVIII Maps and Diagrams Campus Map. Complete building diagrams are provided in the Facilities Unit Plan Emergency Procedures Manual, to help locate actual room (location) numbers.

Page 8: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 8 of 79

Table 2: Inventory of Storage Tanks, Volumes, and Contents

Building Number

Building Room

Tank ID Number

Volume (Gals.)

Product Type Use

1 Crosthwaite Hall 120 32748 150 Hydraulic Oil / Elevator 2 Jubilee Hall B156 33071 300 Hydraulic Oil / Elevator 3 Shane Hall B03 21419 150 Hydraulic Oil / Elevator 5 Spence Hall B01 1918 300 Hydraulic Oil / Elevator 5 Spence Hall B41 28182 300 Hydraulic Oil / Elevator 5 Spence Hall Used Grease 314 Cooking Grease 7 Park Johnson 32714 150 Hydraulic Oil / Elevator 13 Library G07 20124 300 Hydraulic Oil / Elevator 13 Library 204 20125 300 Hydraulic Oil / Elevator 15 New Livingstone B02 18079 150 Hydraulic Oil / Elevator 21 Van Vechten L10 24976 150 Hydraulic Oil / Elevator 23 Cravath Hall B01 33484 150 Hydraulic Oil / Elevator 24 Talley-Brady 402 29592 150 Hydraulic Oil / Elevator 25 Carnegie Hall B406 29388 150 Hydraulic Oil / Elevator

Total Volume 3,014

Table 3: Inventory of Oil Containing Transformers

Building Number Location NES ID Number Volume (Gals.)

1 Crosthwaite Hall 139 45116/45117/45118 1050 PCB cont. 2 Jubilee Hall B18 13987/13988/13058 840 PCB cont. 3 Shane Hall B07 48669/49591/49594 1200 PCB cont. 5 Spence Hall outside 8555-803 280 7 Park Johnson Outside 8555-806 250

15 NewLivingstone Outside 8555-808 280 19 Gym Outside 9505-807 250 20 DuBois Hall Outside 9505-806 250 23 Cravath Hall-Outside 8555-809 250 26 Faculty Apartments A 9505-803 227 26 Faculty Apartments B 9505-801 227 26 Faculty Apartments C 9505-802 227 26 Faculty Apartments D 9505-800 227 13 Fisk Library F-964372 300 PCB Total Volume 5,858 Gals.

Total Storage and in Process: 8,872 gallons (Maximum)

Page 9: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 9 of 79

V. Past Spill History - 40 CFR 112.7(a) Table 4, below, identifies Fisk University’s history of spills, corrective actions taken, and plans for preventing recurrence. Table 4: Past Spill History Written Description of Spill Corrective Actions Taken Plan for Preventing Recurrence

VI. Demonstration of Practicability - 40 CFR 112. 7( d) When it is determined that the installation of structures or equipment listed in 112.7(c) to prevent discharged oil from reaching the navigable waters is not practicable from the facility, the owner or operator should clearly demonstrate such impracticability by providing the following: • A strong oil spill contingency plan following the provisions of 40 CFR Part 109. • A written commitment of manpower, equipment, and materials required to expeditiously control and remove any harmful quantity of oil discharged. Fisk Facilities Operations Management has determined that the use of oil storage vessels with integral secondary containment, where necessary, applicable training and inspection procedures, and readily available equipment to prevent discharge of oil from reaching navigable waters is practical and effective at this facility. VII. Facility Drainage - 40 CFR 112.7(e)(1) The Fisk Campus facility drainage system consists of curb and gutters with drop inlets to a combination sewer/storm drainage system. This system operated by the Metropolitan Nashville Water Authority feeds into a water treatment plant and is processed before discharge into the Cumberland River. VIII. Bulk Storage Tanks - 40 CFR 112.7(e)(2)

Each of the bulk oil storage tanks and oil-containing equipment tanks is of acceptable construction and is compatible with the petroleum, oil or, lubricants they contain and the conditions of design use or storage (pressure and temperature). Several buildings on the Fisk campus have hydraulic passenger elevators. Reservoirs associated with hydraulic elevators are not considered bulk storage containers because they are “in use.” Therefore, these hydraulic reservoirs are exempt from secondary containment requirements. Hydraulic elevator reservoirs are located in self contained rooms separate from the elevator shaft. A list of these reservoirs and their capacity are contained in Table 2. These oil reservoirs do not have the potential to flow to floor drains. Several transformers are located throughout the Fisk campus. As stated in 40 CFR 112.1(b), transformers are not considered bulk oil storage containers. Rather they are considered equipment which contains oil for operational purposes. Subsequently, this equipment does not require secondary containment. A list of transformers and their capacities are contained in Table 3.

Page 10: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 10 of 79

IX. Facility Transfer Operations, Pumping, and In-Plant Processes 40 CFR 112.7(e)(3) • All petroleum, oil or, lubricant transfer operations occur above ground and in plain sight. • All facility transfer operations occur during daylight hours, or under sufficient illumination to be capable of observing any spillage. • At least one trained, facility individual is present and observes the transfer of petroleum, oil or, lubricants during the entire transfer process. • A facility employee visually tracks all transfers of petroleum, oil or, lubricants to and from a tank to observe any spillage. • Where oil transfer is to occur near a storm drain drop inlet, the trained facility individual is present during product transfer shall cover the storm drain drop inlet with a close sealing, impermeable mat. Following successful transfer of product, the mat seal shall be removed. X. Facility Tank Truck Loading/Unloading - 40 CFR 112.7(e)(4) Not applicable to this facility. XI. Oil Production Facilities (Onshore) - 40 CFR 112.7(e)(5) Not applicable to this facility. XII. Oil Drilling and Work over Facilities (Onshore) - 40 CFR 112.7(e)(6) Not applicable to this facility. XIII. Oil Drilling, Production, or Work over Facilities (Offshore) 40 CFR 112.7(e)(7) Not applicable to this facility. XIV. Inspection and Records - 40 CFR 112.7(e)(8) Required inspections should be in accordance with written procedures developed for the facility by the owner or operator. These written procedures and a record of the inspections, signed by the appropriate manager, should be made a part of the SPCC Plan and maintained for a period of three years. The forms in Appendix A of this SPCC Plan are used to record these periodic inspections. Completed forms are filed at the Plant Operations main office. XV. Personnel, Training, and Spill Prevention Procedures 40 CFR 112.7(e)(10) Upon discovery or determination of an imminent or actual spill/release, refer to Appendix B of this SPCC plan for specific Spill Response Activities. Fisk Facilities Operations Management periodically instructs maintenance personnel in the operation and maintenance of oil pollution prevention equipment and in the basics of the facility's Emergency Procedures Manual as well as this SPCC plan. Procedures, responsibilities and the chain of command regarding the reporting of a spill at the Fisk campus are documented in this SPCC Plan Section XX Appendix B. Fisk University has designated the Director of Maintenance Operations as Emergency Coordinator, responsible for oil pollution prevention. The Emergency Coordinator can be contacted directly at (615) 456-9015 or, reached through the 24-hour Campus Security Dispatcher at (615) 329-8777. In the absence of the Primary Emergency Coordinator, Dr. Robert Wingfield, is designated the 1st Backup Emergency Coordinator. The 1st Backup Emergency Coordinator can be contacted directly at (615) 329-8626,(615) 439-0274 or reached through the 24-hour Office of Public Safety Dispatcher at (615) 329-8777.

Page 11: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 11 of 79

In the absence of the Primary and 1st Backup Emergency Coordinators, the Director of Public Safety, is designated the 2nd Backup Emergency Coordinator. The 2nd Backup Emergency Coordinator can be contacted directly at (615) 333-3420 or reached through the 24-hour Office of Public Safety Dispatcher at (615) 329-8777. The Emergency Coordinator, or his designated backup replacement, shall have the vested authority necessary to commit the manpower, equipment, and materials necessary to fully implement this plan. The Fisk University Department of Public Safety and the Facilities and Grounds Departments will control emergencies involving hazardous materials spills during normal working hours. The Office of Public Safety Personal will be the first responders for any spills or emergencies during after hours or until additional personal from either the Office of Facilities and Grounds or our contracted response company arrive on site. These specific procedures are maintained by the Department of Public Safety and the Office of Facilities and Grounds.

a. The owner or operator of a tank facility shall immediately, upon discovery, notify the Tennessee Emergency Management Agency (TEMA) at (800-262-3300) Phone Number for any of the following conditions:

i. Any spill or other release of twenty-five (25) gallons or more of petroleum

products at a tank facility. ii. Discharges of any Hazardous substances, oil, or petroleum products into or

on any waters of the state. iii. Discharges that may threaten or impact water quality.

b. If the TEMA determines that emergency response assistance is required, the

owner or operator shall notify the local responding agency or the 911 emergency system.

i. Local Emergency Response Agency (or the Local Fire Department) at 9-1-1. ii. Tennessee Emergency Management Agency 800-262-3300

c. The National Response Center will be contacted immediately at 1-800-424-8802 if any

of the following conditions are met: i. The oil spill/release will reach a navigable body of water or adjoining

shoreline. ii. Water quality standards could be violated. iii. The spill/release could cause a film, “sheen”, or discoloration. iv. The spill/release could cause sludge or emulsion. v. The spill/release exceeds Federal Reportable Quantities (CERCLA).

d. For serious injuries or harmful exposures to workers, the Tennessee Occupational Safety and Health administration (TOSHA) will be contacted at 615.741-2793

e. To the maximum extent known, the following information should be provided to the

Federal and State Reporting Agencies during the initial telephone notification: i. Your name, location, organization, and telephone number ii. Name and address of the party responsible for the incident iii. Date and time of the incident iv. Location of the incident v. Source and cause of the release or spill vi. Types of material(s) released or spilled

Page 12: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 12 of 79

vii. Quantity of materials released or spilled viii. Danger or threat posed by the release or spill ix. Number and types of injuries (if any) x. Weather conditions at the incident location xi. Any other information that may help emergency personnel respond to the

incident.

f. Immediately after a petroleum or oil spill/release, the Emergency Coordinator must provide for storing and/or disposing of all recovered oil, contaminated soil or, water.

g. As soon as practical but no later than 15 days of the spill/release, the Office of

Environmental Compliance must be contacted for report filing at 615-741-4732.

h. If the spill/release is greater than 1,000 gallons or is the second spill/release within twelve (12) months, the Emergency Coordinator must prepare a written report of the incident. The written report of the incident must be submitted to the Regional Administrator of the US EPA. The written report must include the following.

i. Name, address, and telephone number of the facility. ii. Date, time and type of incident. iii. Name and quantity of material involved. iv. An assessment of actual or potential hazards to human health or the

environment. v. The extent of injuries, if any. vi. Estimated quantity land disposition of recovered material that resulted from

the incident. vii. Efforts taken and results.

Page 13: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 13 of 79

XVI. EPA Facility Response Plan (FRP) Certification of Applicability 40 CFR 112.20(e) [Also known as the “Certification of Substantial Harm Determination Form”] If there is a “yes” answer to one or more of the five questions below, then an EPA FRP Plan is Required Facility Name: Fisk University, Nashville Tennessee, Main Campus Facility Address: 1000 17th Ave. N., Nashville TN 37208 Item Yes No Question

1.

Does the facility transfer oil over water to or from vessels and does the facility have a total oil storage capacity greater than or equal to 42,000 gallons?

2.

Does the facility have a total oil storage capacity greater than or equal to 1 million gallons and does the facility lack secondary containment that is sufficiently large to contain the capacity of the largest aboveground oil storage tank plus sufficient freeboard to allow for precipitation within any above-ground oil storage tank area?

3.

Does the facility have a total oil storage capacity greater than or equal to 1 million gallons and is the facility located at a distance (as calculated using the appropriate formula in 40 CFR 112 or a comparable formula) such that a discharge from the facility could cause injury to fish and wildlife and sensitive environments?

4.

Does the facility have a total oil storage capacity greater than or equal to 1 million gallons and is the facility located at a distance (as calculated using the appropriate formula in 40 CFR 112 or a comparable formula) such that a discharge from the facility would shut down a public drinking water intake?

5.

Does the facility have a total oil storage capacity greater than or equal to 1 million gallons and has the facility experienced reportable oil spill in an amount greater than or equal to 10,000 gallons within the last 5 year?

Page 14: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 14 of 79

XVII. Containment, Security, Spill Volumes and Rates - 40 CFR 112.7(b) & (c) Where experience indicates a reasonable potential for equipment failure (such as tank overflow, rupture, or leakage), this plan includes a prediction of the direction, rate of flow, and total quantity of oil which could be discharged from the facility as a result of each major type of failure. Flow diagrams are provided in section, XVIII Maps and Diagrams, of this SPCC Plan. a. Containment and Diversionary Structure – 40 CFR 112.7(c) The following tables list each tank individually, the total quantity of materials stored within each tank, the security measure in place to protect tanks form vandalism, and the potential spill volumes and rates of each tank. b. Security - 40 CFR 112.7(e)(9) General security measures for the facility as a whole and for each individual oil storage location are listed below. For the Fisk University as a whole, security is the full-time responsibility of Campus Security. Campus Security maintains around the clock vigil of the campus, using squad cars, bicycles, and walking patrolmen. The campus is well lit for illumination after dark. Area lighting is located in such positions as to illuminate the storage tank areas. Consideration was given to discovering spills at night and discouraging pilferage and possible sabotage. c. Potential Spill Volumes and Rates – 112.7 (b) Appropriate containment and/or diversionary structures, equipment, and supplies to prevent discharged oil from reaching a navigable watercourse are provided herein. General measures for containment and diversionary structures for the facility as a whole and for individual storage tank locations are listed below. Where a reasonable potential exists for discharge of oil to navigable waters or adjoining shorelines, bulk fuel storage tank installations are constructed with a secondary means of containment for the entire contents of the largest single tank plus sufficient freeboard to allow for precipitation. For the main campus facility as a whole, Facilities Management maintains individual caches of spill response equipment and supplies to divert and contain releases of POLs. Caches are typically stored within labeled plastic half-barrels with lids and contain loose absorbent, absorbent sheets, absorbent pillows, absorbent booms, scoops, and gloves. Caches are maintained at the Main Chiller Plant and in the Basement storage area located in Spence Hall. Absorbent booms or other barriers are also available from the local emergency cleanup contractor.

Page 15: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 15 of 79

Tank #45116/45117/451187; 1050-gallons Transformer Oil, 3 Tanks (Crosthwaite Hall) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tanks No.’s 45116/45117/45118 are three 350 gallon capacity electrical transformers labeled as “PCB Contaminated” for electrical service to Crosthwaite Hall, they are located in a transformer vault, room 139 on the lower floor. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) These tanks are secured in a transformer vault accessible only by NES. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

350 gallons

Release would flow into floor drain and through door to ground.

Instantaneous

Partial failure of a full tank

1 to 350 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons 1 to 5 gallons could reach floor drain accessing storm drain and/or navigable waters.

5 gallons per minute

Page 16: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 16 of 79

Tank #13987/13988/13058; 840-gallons Transformer Oil, 3 Tanks (Jubilee Hall) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tanks No.’s 13987/13988/13058 are three 280 gallon capacity electrical transformers labeled as “PCB Contaminated” for electrical service to Jubilee Hall, they are located in a transformer vault, room B18 on the lower floor. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) These tanks are secured in a transformer vault accessible only by NES and Maintenance personal. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

280 gallons

Release would flow into floor drain. Instantaneous

Partial failure of a full tank

1 to 280 gallons Same as above Gradual to Instantaneous

Tank overfill 1 or more gallons 1 to 5 gallons could reach floor drain accessing storm drain and/or navigable waters.

5 gallons per minute

Page 17: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 17 of 79

Tank #48669/49591/49594; 1200-gallons Transformer Oil, 3 Tanks (Shane Hall) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tanks No.’s 48669/49591/49594 are three 400 gallon capacity electrical transformers labeled as “Non-PCB ” for electrical service to Shane Hall, they are located in a transformer vault, room B07 on the lower floor. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) These tanks are secured in a transformer vault accessible only by NES and Maintenance personal. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

400 gallons

Release would flow into floor drain and through door to ground.

Instantaneous

Partial failure of a full tank

1 to 400 gallons Same as above Gradual to Instantaneous

Tank overfill 1 or more gallons 1 to 5 gallons could reach floor drain accessing storm drain and/or navigable waters.

5 gallons per minute

Page 18: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 18 of 79

Tank #8555-803; 280-gallon Transformer Oil Tank (Spence) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 8555-803 is a 280 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for electrical service to Spence Hall. It is located on a concrete slab outside the East side of Shane Hall, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

280 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 280 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 19: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 19 of 79

Tank #8555-806; 250-gallon Transformer Oil Tank (Park Johnson) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 8555-806 is a 250 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for electrical service to Park Johnson. It is located on a concrete slab outside the North side of Park Johnson, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

250 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 250 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 20: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 20 of 79

Tank #8555-808; 280-gallon Transformer Oil Tank (New Livingstone) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 8555-808 is a 280 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for service to New Livingstone Hall. It is located on a concrete slab outside the South side of New Livingstone, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

280 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 280 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 21: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 21 of 79

Tank #9505-807; 250-gallon Transformer Oil Tank (Gym) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-807 is a 250 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for electrical service to the Gym and Biology Labs. It is located on a concrete slab outside the Northeast side of the Gym, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

250 gallons

Release would flow directly to the ground

Instantaneous

Partial failure of a full tank

1 to 250 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 22: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 22 of 79

Tank #9505-806; 250-gallon Transformer Oil Tank (DuBois) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-806 is a 250 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for electrical service to DuBois Hall. It is located on a concrete slab outside the Southwest side of DuBois Hall, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

250 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 250 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 23: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 23 of 79

Tank #8555-809; 250-gallon Transformer Oil Tank ( Cravath) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 8555-809 is a 250 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for electrical service to Cravath Hall. It is located on a concrete slab outside the West side of the building, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

250 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 250 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 24: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 24 of 79

Tank #9505-800; 227-gallon Transformer Oil Tank (Facility A) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-800 is a 227 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for service to the Faculty Apartment “A” Building. It is located on a concrete slab outside the North side of the “A” Building, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

227 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 227 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 25: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 25 of 79

Tank #9505-801; 227-gallon Transformer Oil Tank (Faculty B) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-801 is a 227 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for service to the Faculty “B” Building. It is located on a concrete slab outside the East side of “B” building, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

227 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 227 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 26: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 26 of 79

Tank #9505-802; 227-gallon Transformer Oil Tank (Faculty C) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-802 is a 227 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for service to the Faculty “C” Building. It is located on a concrete slab outside the West side of “C” building, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

227 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 227 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 27: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 27 of 79

Tank #9505-803; 227-gallon Transformer Oil Tank (Faculty D) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. 9505-803 is a 227 gallon capacity electrical transformer containing “Non-PCB” dielectric oil for service to the Facility “D” Building. It is located on a concrete slab outside the East of “D” building, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. Only primary containment is provided. b. Security – 40 CFR 112.7(e)(9) This tank is easily accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

227 gallons

Release would flow directly to the ground.

Instantaneous

Partial failure of a full tank

1 to 227 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 28: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 28 of 79

Tank #F-964372; 300-gallon Transformer Oil Tank (Library) a. Containment and Diversionary Structure – 40 CFR 112.7(b) Storage Tank No. F-964372 is a 300 gallon capacity electrical transformer containing “PCB” dielectric oil for service to the Fisk University Library Building, 250 gallons are located in the primary storage tank the other 50 gallons are held in the high voltage oil switch located in side of the transformer cabinet. It is located on a concrete slab within a brick and chain link enclosure located on the east side of the Library, within an enclosed weather-resistant electrical cabinet but otherwise exposed to precipitation. There is no diking provided, only primary tank containment is provided. “This is a Fisk University owned transformer” b. Security – 40 CFR 112.7(e)(9) This tank is not accessible to the public. However, building and area lighting provides illumination after dark. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would flow onto the concrete pad then into open storm water drains.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to Instantaneous

Tank overfill 1 to many gallons

1 or more gallons Reasonable person would not anticipate this release to reach storm drain and/or navigable waters.

5 gallons per minute

Page 29: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 29 of 79

Page 30: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 30 of 79

Tank # 32748; 150-gallon Elevator Hydraulic Tank (Crosthwaite) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (120) in the basement of the Crosthwaite Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 31: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 31 of 79

Tank # 33071; 3000 -gallon Elevator Hydraulic Tank (Jubilee) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 300 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B156) in the basement of Jubilee Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 32: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 32 of 79

Tank # 21419; 150 -gallon Elevator Hydraulic Tank (Shane) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B03) in the basement of the Shane Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to Instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 33: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 33 of 79

Tank # 28182; 300 -gallon Elevator Hydraulic Tank (Spence) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 300 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B41) on the first floor of Spence Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 34: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 34 of 79

Tank # 1918; 300 -gallon Freight Elevator Hydraulic Tank (Spence) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 300 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B01) in the basement of the Spence Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 35: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 35 of 79

Tank # Used Grease; 314-gallon Waste Cooking Grease (CEC) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 314-gallon capacity waste grease holding above ground storage tank (AST) located outside behind the Curb Café of the Curb Event Center. It is a single wall mobile AST. b. Security – 40 CFR 112.7(e)(9) The product in this container is recycled and not subject to theft or, vandalism. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm drainage ditch)

Rate of Flow

Complete failure of a full tank

314 gallons

Release would spill on the concrete surface flowing North toward a storm drain.

Instantaneous

Partial failure of a full tank

1 to 314 gallons Same as above Gradual to Instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete surface.

5 gallons per minute

Page 36: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 36 of 79

Tank # 32714; 150 -gallon Elevator Hydraulic Tank (Park Johnson) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room in the 1st floor of Park Johnson for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 37: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 37 of 79

Tank # 20125; 300 -gallon Elevator Hydraulic Tank (Library) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 300 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (204) on the second floor of the Library for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 38: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 38 of 79

Tank # 20124; 300 -gallon Elevator Hydraulic Tank (Library) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 300 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (G07) in the basement of the Library for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

300 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 300 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 39: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 39 of 79

Tank # 18079; 150 -gallon Elevator Hydraulic Tank (New Livingstone) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B02) in the basement of New Livingstone Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 40: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 40 of 79

Tank # 24976; 150 -gallon Elevator Hydraulic Tank (Van Vechten) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (L10) in the basement of the Van Vechten Gallery for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 41: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 41 of 79

Tank # 33484; 150 -gallon Elevator Hydraulic Tank (Cravath) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B01) in the basement of Cravath Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 42: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 42 of 79

Tank # 29592; 150 -gallon Elevator Hydraulic Tank (Talley Brady) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (402) on the 4th floor of Talley Brady Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 43: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 43 of 79

Tank # 29388; 150 -gallon Elevator Hydraulic Tank (Cranegie) a. Containment and Diversionary Structure – 40 CFR 112.7(c) This is a 150 gallon capacity hydraulic oil aboveground storage tank (AST) located in the equipment room (B406) in the basement of Carnegie Hall for providing elevator service. It is a single wall AST. b. Security – 40 CFR 112.7(e)(9) The mechanical room this tank is installed in is locked at all times and is only accessible by maintenance personnel. c. Potential Spill Volumes and Rates – 40 CFR 112.7(b)

Type of Major Failure

Possible Quantity Released

Direction of Flow (relative to storm Drainage ditch)

Rate of Flow

Complete failure of a full tank

150 gallons

Release would be expected to flow from the mechanical room on the concrete floor.

Instantaneous

Partial failure of a full tank

1 to 150 gallons Same as above Gradual to instantaneous

Tank overfill 1 or more gallons Release would be expected to flow on the concrete floor.

5 gallons per minute

Leaking pipe or valve packing

Several ounce to Several gallons

Same as above. Gradual to instantaneous

Page 44: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 44 of 79

XVIII. Maps and Diagrams: Complete building floor plans are contained in the Plant Operations Emergency Procedures Manual. a. Campus Map

Page 45: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 45 of 79

B. Crosthwaite Hall Transformer:

Page 46: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 46 of 79

C. Jubilee Hall Transformers:

Page 47: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 47 of 79

D. Shane Hall Transformers:

1st floor

Page 48: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 48 of 79

E. Spence Hall Transformer:

Page 49: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 49 of 79

F. Park Johnson Transformer:

Page 50: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 50 of 79

G. New Livingstone Hall Transformer:

Page 51: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 51 of 79

H. Gym Transformer:

Page 52: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 52 of 79

I. DuBois Hall Transformer:

Page 53: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 53 of 79

J. Cravath Hall Transformer:

Page 54: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 54 of 79

k. Faculty Apartment Transformers A:

Page 55: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 55 of 79

L. Faculty Apartment Transformers B:

Page 56: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 56 of 79

M. Faculty Apartment Transformers C:

Page 57: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 57 of 79

N. Faculty Apartment Transformers D:

Page 58: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 58 of 79

O. Crosthwaite Hall Elevator:

Page 59: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 59 of 79

P. Jubilee Hall Elevator:

Page 60: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 60 of 79

Q. Shane Hall Elevator:

Shane Hall1st floor

Page 61: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 61 of 79

R. Spence Hall Elevator #1:

Page 62: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 62 of 79

S. Spence Hall Elevator #2:

Page 63: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 63 of 79

T. Spence Hall Kitchen Cooking Grease:

Page 64: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 64 of 79

U. Park Johnson Elevator:

Page 65: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 65 of 79

V. Library Elevator #1:

Page 66: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 66 of 79

W. Library Elevator #2:

Page 67: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 67 of 79

X. New Livingstone Hall Elevator:

Page 68: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 68 of 79

Y. Van Vechten Art Gallery Elevator:

Page 69: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 69 of 79

Z. Cravath Hall Elevator:

Page 70: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 70 of 79

AA. Talley-Brady Elevator:

Page 71: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 71 of 79

BB. Carnegie Hall Elevator:

Page 72: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 72 of 79

CC. Library Transformer:

Page 73: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 73 of 79

XIX. Appendix A: Inspection Checklists

Appendix A-1: Double Wall Inspection Checklist Instructions: Monthly Inspect each double wall container listed below for items in check sheet. Indicate in description section the specific units that have discrepancies. Place an X in the appropriate box for each item. Further descriptions or comments should be attached on a separate sheet of paper if necessary. Inspection results are filed at Plant Operations main office.

Item Yes No Descriptions/Comments Tank surfaces show signs of leaking?

Ground or floor around tank(s) show new signs of staining?

Tank(s) show signs of damage, rust of deterioration?

Bolts, rivets or seams show signs of damage, rust or deterioration?

Tank supports are deteriorated or buckled?

Are Vents obstructed? Valve seals or gaskets leaking? Pipelines show signs of leakage? Pipelines or supports are damaged or deteriorated?

Fencing, gate and lighting is functional?

Remarks: Building Location Device Equipment ID Signature:_____________________________________ Date:__________________ Print Name: _____________________

Page 74: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 74 of 79

Appendix A-2: Secondary Containment Inspection Instructions: Weekly Ensure that all secondary containers are free of oil or sheen, if they contain water. All secondary containers are inside buildings so, if they contain water determine the source and notify Maintenance Manager. Enter the date the inspection was performed, and the name of the inspector. Write down date and any corrective actions taken. Records are to be retained for at least three years. Building Location

Device Equipment ID

Signs of leaks or spills Present (Y / N)

Corrective Action Taken if Yes

Date

Chiller Plant 55 Gal Pallet

Talley Brady Mechanical

55 Gal Pallet

Gym

55 Gal Pallet

Library Mechanical

55 Gal Pallet

Spence Boiler Room

55 Gal Pallet

Shane Mechanical Room

55 Gal Pallet

New Livingstone Hall Mechanical

55 Gal Pallet

Grounds Shop

2-55 Gal Pallets

Signature:_____________________________________ Date:__________________ Print Name: _____________________ Requirements: Provide secondary containment for all drums, containers and tanks of 1 gallon size or larger containing hazardous materials (including hazardous waste liquid). For a single primary container, secondary containment shall be 110% of the volume of the primary containers. For multiple primary containers, secondary containment shall be 150% of the volume of the largest container or 10% of the aggregate volume. Visually inspect all secondary containment weekly and document on this log. Containers shall be stored so as to prevent unauthorized access/use or tampering, exposure to rain, and extremes of temperature, and with sufficient ventilation to preclude accumulation of unsafe or unhealthy vapor levels. Secondary containment shall be free of oil or sheen at all times.

Page 75: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 75 of 79

XX. Appendix B: Spill/Release Response Activities

a. General US EPA regulations define a spill as a discharge of oil into, or upon, the navigable waters of the United States or adjoining shorelines, in harmful quantities. Harmful quantities are defined at 40 CFR 110.00 as a discharge that violates applicable water quality standards or causes a sheen upon, or discoloration of, the surface of the water of the adjoining shorelines. Contaminated ground water may also have the potential to seep, leach, or flow into navigable waters which would be included in this definition. Since most storm sewers eventually discharge into a navigable waterway, they fall under the definition of a “navigable waterway”. The goal of these emergency procedures is to eliminate the potential for oil spills to reach any drains associated with the sewer/storm system on campus. These procedures are intended to minimize human exposure and environmental impacts in the unlikely event a spill should occur.

b. Discovery of a Release Fisk University has designated the Director of Maintenance Operations as Emergency Coordinator, responsible for oil pollution prevention. The Emergency Coordinator can be contacted directly at (615) 456-9015 or, reached through the 24-hour Campus Security Dispatcher at (615) 329-8777. In the absence of the Primary Emergency Coordinator, Dr. Robert Wingfield, is designated the 1st Backup Emergency Coordinator. The 1st Backup Emergency Coordinator can be contacted directly at (615) 329-8626, (615) 439-0274 or reached through the 24-hour Office of Public Safety Dispatcher at (615) 329-8777. In the absence of the Primary and 1st Backup Emergency Coordinators, the Director of Public Safety, is designated the 2nd Backup Emergency Coordinator. The 2nd Backup Emergency Coordinator can be contacted directly at (615) 333-3420 or reached through the 24-hour Office of Public Safety Dispatcher at (615) 329-8777. The Emergency Coordinator, or his designated backup replacement, shall have the vested authority necessary to commit the manpower, equipment, and materials necessary to fully implement this plan. Any person discovering a release of liquid product from a container, tank, vehicle or other operating equipment should notify the Facility Maintenance Manager or Campus Security. They should also initiate certain countermeasures immediately, including:

i. Extinguish any sources of ignition. The material must be identified as nonflammable and noncombustible, until such time as this is determined, all potential sources of ignition must be removed. Do not turn light switches on or, off. Extinguish any flames supporting pilot lights for natural gas equipment. Any vehicles in the area must be turned off. Avoid sparks and any movement that may create static electricity.

ii. Assure that no danger to human health exists. Attempt to stop the release at its

source. Use simple procedures to turn valves, plugging leaks, turning electrical disconnects to equipment off, etc., may be attempted by the discoverer if there are no health or safety hazards and there is a reasonable certainty of the origin of the leak.

Page 76: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 76 of 79

iii. Contain the material released following proper safety procedures. The spill should be contained with absorbent materials building dikes, surrounding with absorbent booms, pads, soils, or, almost anything to prevent further spread of the material. Place drain covers over any nearby storm or sewer drain that may be impacted by the spill.

iv. Recover or cleanup the material spilled. Material recovered from the spill must be

discarded as waste. Liquids absorbed by solid materials (speedy dry, absorbent pads ect.,) shall be shoveled into open top drums. Segregate speedy dry from absorbent pads for proper disposal. When drums are filled after a cleanup, the drum lids shall be secured. All drums shall then be labeled identifying the contents, the date of the spill/cleanup, and the site name with location. Be aware that combining non-compatible materials can cause potentially dangerous chemical and/or physical reactions or may severely limit disposal options. Check compatibility information on MSDS sheets before combining any dissimilar materials.

v. Decontaminate tools and equipment used in cleanup. Even if dedicated to cleanup

efforts, tools and equipment that have been used must be decontaminated before replacing them in the spill control kit.

vi. Spill control kits will be replenished and returned to their original location for future

use.

c. Generators: At this time there are no Generators on Fisk University Campus that burn fossil fuels.

d. Transformers: Most transformers containing oil are pole mounted or are located on concrete pads outside of buildings, these units are owned and maintained by Nashville Electric Service (NES). Crosthwaite Hall, Jubilee Hall and Shane Hall each have an inside transformer vault containing three, single floor mounted transformers. These units are owned and maintained by Nashville Electric Service (NES). In the unlikely event of a leak, oil will be contained within the vault of these transformers. If the vault is compromised, any oil will spill to the ground around these units.

i. Maintenance personnel will contain the spill using absorbent booms or speedy dry to prevent migration of the product to storm drains where appropriate.

ii. NES will be contacted to effect cleanup and repairs. Their numbers are contained in

the Emergency Procedures Manual.

iii. The power transformer that is located behind the Fisk University Library is part of the old power distribution network for Fisk University. This transformer is the property of Fisk University who has primary responsibility for addressing any issues with the discharge of fluid from this transformer.

All pad or floor mounted transformers located with in the boundary’s of Fisk University that are owned by Fisk University or an out side vendor are currently inspected once a month, for any indication of leaking fluids, this is documented through the universities work order system.

Page 77: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 77 of 79

e. Elevators: Elevators experiencing failure of the tank, piping, or associated fittings, will typically shut down on alarm due to low fluid levels. Any person noticing hydraulic fluid coming out from under the door of an elevator machine room should immediately notify Plant Operations or Campus Security who will in turn notify Plant Operations and/or our contracted service vendor (Nashville Machine). Ignition of hydraulic fluid has a very low probability of occurrence, and will not be of major concern with this type spill.

i. Containment of product will be accomplished by retrieving an absorbent boom from the nearest spill kit and placing it across the door opening of the machine room to prevent additional hydraulic fluid from flowing out of the room along with securing any floor drains that are located with in the equipment room space.

ii. Plant Operations or Campus Security will remove the elevator from service by

disconnecting electrical power to the affected elevator. Signs will be posted on all floors at each elevator door notifying occupants that the elevator is “Out of Service”.

iii. Plant Operations or the Office of Public Safety will notify the present service

company about the spill so they can mobilize the necessary man power or there designated clean up company to clean up the spill and remove and discard all soiled materials as per regulations. Maintenance personnel will contain the leaked hydraulic fluid using speedy dry and absorbent pads until the service company or there clean up crew is on site. Material recovered from the spill must be discarded as waste. Liquids absorbed by solid materials (speedy dry, absorbent pads etc ) shall be shoveled into open top drums. Segregate speedy dry from absorbent pads for proper disposal. When drums are filled after a cleanup, the drum lids shall be secured. All drums shall then be labeled identifying the contents, the date of the spill/cleanup, and the site name with location.

All elevator storage tanks located with in the boundary’s of Fisk University that are owned by Fisk University or an out side vendor are currently inspected once a month for any indication of leaking fluids, this is documented through the universities work order system.

Page 78: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 78 of 79

f. Waste Disposal: Waste must be disposed of properly after any spills have been absorbed and cleaned up. A disposal determination will be made by Maintenance Operations. Any free product will be containerized in waste cans or 55-gallon drums with proper labeling as defined under Section b. (iv) above. Arrangements shall then be made by Maintenance Operations for proper pickup and disposal of all waste products derived from the spill.

g. Plan Review: A complete review of the effectiveness of this plan and procedures will be made after the conclusion of any spill events. The plan and procedures will then be modified or changed accordingly if necessary. If it is determined the plan was effective during the event, and any breakdown was the result of employee knowledge, then training procedures will be reviewed and updated as necessary. This plan will be reviewed yearly prior to the end of the University’s fiscal year. Before which time a live drill or tabletop exercise will be under taken by all relevant staff members for effectiveness of the SPCC plan.

h. Spill Containment Supplies on Site:

Oil Dry Collection Drums Gloves Absorbent booms Absorbent pads 2 each, plastic shovels

Page 79: Spill Prevention, Control, and Countermeasure (SPCC)  · PDF fileFisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 2 of 79 Table of Contents

Fisk University, Spill Prevention, Control, and Countermeasure (SPCC) Plan Page 79 of 79

XXI. Appendix C: Emergency Release Follow-up Notice EMERGNCY RELEASE FOLLOW-UP NOTICE REPORTING INSTRUCTIONS GENERAL INFORMATION: Tennessee Code Annotated §1200-1-11-.11 requires that if an emergency coordinator determines that a facility has had a release, fire, or explosion which could threaten human health, or the environment, outside the facility, he must report his findings as follows:

I. If his assessment indicated that evacuation of local areas may be advisable, he must immediately notify appropriate local authorities. He must be available to help appropriate officials decide whether local areas should be evacuated; and

II. He must immediately notify either the government official designated as the on-scene coordinator for the geographical area (in the applicable regional contingency plan under federal 40 CFR 1510), the Tennessee Emergency Management Agency (TEMA) (using their 24-hour toll free number 800/262-3300 or 3400) or the National Response Center (using their 24-hour toll free number 800/424-8802). The report must include:

A. Name and telephone number of reporter; B. Name and address of facility; C. Time and type of incident (e.g., release, fire); D. Name and quantity of material(s) involved, to the extent known; E. The extent of injuries, if any; and F. The possible hazards to human health, or the environment, outside the facility. The emergency coordinator must note in the operating record the time, date and details of any incident that requires implementing this contingency plan. Within 15 days after the incident, he must submit a written report on the incident to the Commissioner. The report must include:

I. Name, address, and telephone number of the owner or operator; II. Name, address, and telephone number of the facility; III. Date, time, and type of incident (e.g., fire, explosion); IV. Name and quantity of material(s) involved; V. The extent of injuries, if any; VI. An assessment of actual or potential hazards to human health or the

environment, where this is applicable; VII. Estimated quantity and disposition of recovered material that resulted from

the incident.