spg cal 50 008 a4 calculation genset foundation
DESCRIPTION
free for allTRANSCRIPT
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 1 of 10
OWNER : PT. PERTAMINA (PERSERO)
CONTRACTOR : PT. BANGUN BEJANA BAJA
LOCATION : BALIKPAPAN – KALIMANTAN TIMUR
PROJECT NAME : EPCI PROJECT UPGRADING DPPU SEPINGGAN
REV. NO
DATE DESCRIPTION PREP’D CHK’D APP’D
1 10 Nov 2015 Issued For Approval OMP ARI SWD
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 2 of 10
Revision Control Sheet
REV. NO DATE DESCRIPTION
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 3 of 10
Table of ContentsRevision Control Sheet.............................................................................................................................. 2Table of Contents...................................................................................................................................... 3List of Tables............................................................................................................................................. 31. General.................................................................................................................................................. 41.1. Background........................................................................................................................................ 41.2. Scope................................................................................................................................................. 41.3. Codes and Standards......................................................................................................................... 41.4. Material Specification......................................................................................................................... 41.4.1. Concrete.......................................................................................................................................... 41.4.2. Reinforcing Steel Bar...................................................................................................................... 51.4.3. Soil Bearing Capacity and Pile Grup Capacity................................................................................52. Equipment Data..................................................................................................................................... 72.1. Equipment Sizing............................................................................................................................... 72.2. Computing External Load................................................................................................................... 72.2.1. Dead Load....................................................................................................................................... 72.3. Structure Model.................................................................................................................................. 82.4. Node Numbers................................................................................................................................... 82.5. 3D Section.......................................................................................................................................... 93. Loading Combination............................................................................................................................. 93.1. Unfactored Load Combınation...........................................................................................................93.2. Factored Load Combınation.............................................................................................................104. Computation of External Load.............................................................................................................105. Pond Design........................................................................................................................................ 10
List of TablesTable 1.4.1. Material Class Strength.........................................................................................................2Table 1.4.2.SNI 07-2052-2002 bar designation number, section area, weight..........................................2
APPENDIX 1 External Loading CalculationAPPENDIX 2 Pond DesignAPPENDIX 3 Valve Chamber Drawing
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 4 of 10
1.General
1.1. BackgroundPT Pertamina plans to carryout the EPC of DPPU Sepinggan Air port expansion project located in Balikpapan, East of Kalimantan.
1.2. ScopeThis calculation shall include, but are not limited to design strength and stability, soil and foundation analysis and material take off.
1.3. Codes and StandardsThe following codes will be used for design :
1. Project ReferenceS-20-133-001
-
SPG-LST-10-001
General Specification for Civil Works.“Soil Investigation Report”, DPPU Sepinggan Balikpapan by PT. Geosinindo Utama.Equipment List
2. American Codes and Standards ACI (American Concrete Institute)
ACI-318-2002ACI 315
Building Code Requirements for Reinforced ConcreteDetails and Detailing Concrete Reinforcement
American Society for Testing and Materials (ASTM)ASTM A36/A ASTM A 185-01
ASTM A 307-02
ASTM A 325-02
ASTM C 33ASTM F 436-11
Carbon Structure Steel.Steel Welded Wire Reinforcement, Plain, for Concrete.Carbon Steel Bolt and Stud, 60.000 Psi Tensile Strength.Structural Bolt, Steel, Heat Treated, 120/105 Ksi Minimum Tensile Strength.Concrete Aggregates.Hardened Steel Washer.
ASCE/SEI 7-10“American Society of Civil Engineers”Minimum Design Loads for Building and Other Structures.
API STD 650“Welded Tanks for Storage”.
3. Japanese Codes and Standards JIS “Japanese Industrial Standards
JIS A 5335-1987 : Prestressed Concrete Spun Piles
1.4. Material Specification1.4.1. ConcreteStructural Concrete fc’ = 29.4 MPa = 300 Kg/cm2
Lean Concrete fc’ = 13.7 MPa = 140 Kg/cm2Poisson ratio = 0.20Berat jenis beton c = 2.4 Ton/m3 = 0.0024 Kg/cm3
Modulus Elastisitas Ec = 4700√fc’ = 4700 √(29.4) = 25485 MPa = 2.6 x 106 Kg/cm2
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 5 of 10
1.4.2. Reinforcing Steel Bar1. For structural type shall use deformed bar. Deformed bar shall conform to SNI 07-2052-2002 BJTD
40 or Equivalent.2. For non-structural type such as wall post, reinforcement for concrete block wall, etc shall use plain
bar. Plain bar shall conform to ASTM A615 Grade 40 or SNI 07-2052-2002 BJTP 24 or JIS G3112 SR 24 as table below.
3. Modulus Elastisitas (Es) = 2.1 x 106 Kg/cm2
Table 1.4.1. Material Class Strength
Material ClassYield strength Tensile strength
Mpa kg/cm2 Mpa kg/cm2
SNI 07-2052-2002 BJTD 40 390 4000 560 5700SNI 07-2052-2002 BJTP 24 235 2400 380 3900
Table 1.4.2.SNI 07-2052-2002 bar designation number, section area, weight
No.Plain Deformed
Diameter mm
Area cm2 Weight kg/m Diameter
mmArea cm2
Weight kg/m
1 6 0.2827 0.222 6 0.2827 0.222
2 8 0.5027 0.395 8 0.5027 0.395
3 10 0.7854 0.617 10 0.7854 0.617
4 12 1.131 0.888 13 1.327 1.040
5 14 1.539 1.120 16 2.011 1.580
6 16 2.011 1.580 19 2.835 2.230
7 19 2.835 2.230 22 3.801 2.980
8 22 3.801 2.980 25 4.909 3.850
9 25 4.909 3.850 29 6.625 5.180
10 28 6.158 4.830 32 8.042 6.310
11 32 8.042 6.310 36 10.180 7.990
1.4.3. Soil Bearing Capacity and Pile Grup Capacity1.4.3.1. Allowable Axial Pile CapacityBased on soil investigation reportPiles will be used for foundation, pile Ø400 mm, Length 32 m, Class B.Piles depth = 32 mCapacity of Ø400mm spun piles = 1891 kN (See soil investigation report Pg.35)Pile group efficiency factor = 0.85 (Assumed)Design capacity of Ø 400mm piles (PcapSI) = 1607 kN
= 164 Ton
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 6 of 10
Based on Piles CataloguePiles will be used for foundation, pile Ø400 mm, Length 12 m, Class B.Piles depth = 12 mCapacity of Ø400mm spun piles = 114 Ton (See piles catalogue)Pile group efficiency factor = 0.85 (Assumed)Design capacity of Ø 400mm piles (PcapPC) = 97.2 Ton
For Allowable piles capacity design, use the smallest value allowable pile capacity based on vendor piles catalogue PcapSI > PcapPC, use PcapPC
Design capacity of Ø 400mm piles Pcap = 97.2 TonPiles Depth = 12 m
1.4.3.2. Horizontal/Lateral Stress Pile CapacityCheck combined axial & bending stress in piles assuming 400D x 75WT spun piles:Area of concrete Apile = 76600 mm2 (Refer ICP Spun Pile catalogue)Section modulus Z = 5321748 mm3
Effective prestress fps = 5.5 MPa (Refer ICP Spun Pile catalogue)Concrete compression f'c = 58 MPa (Refer ICP Spun Pile catalogue)strength of piles
Permissible comp. stress fca = 0.25 (f'c - fps) = 13.1 MPa ≈13 MPa
1.4.3.3. Soil Bearing Pressure CapacityBased on soil investigation report Pg.57, Qall = 17 Ton/m2.
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 7 of 10
2. Equipment Data
2.1. Equipment Sizing
2.2. Computing External Load2.2.1. Equipment LoadEmpty weight : 1080 Kg = 1.080 Ton (Refer to SPG-DWG-20-501-A3)Operation weight : 1080 Kg = 1.080 TonTest weight (at fab.) : -
2.2.1.1. Foundation selfweightFoundation weight will be generated automatically with AFES program
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 8 of 10
2.2.1.2. Wind LoadsWind loads will be calculated based on ASCE 7-10.Design wind load formulation : F = qz x G x CF x Af (ASCE 7 Eq. 6-28)The four variables in this equation are the velocity pressure, qz, Gusst effect factor, G, the aerodynamic force coefficient, CF, Ae
Empty Weight : 1080 Kg = 1.080 Ton Operating Weight : 1080 Kg = 1.080 Ton Test Weight : - (Test at Shop/Fab.)
2.2.1.3. Wind Load
2.3. Structure Model
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 9 of 10
2.4. Node Numbers
2.5. 3D Section
Description Dimension Material NoteGeometry b h t
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 10 of 10
(m) (m) (m)Wall Square 5.1 5 0.2 Concrete Wall (Dir-X,Y)Slab Square 6 6 0.3 Concrete Wall (Dir-Z)
3. Loading Combination3.1. Unfactored Load CombınationLoad listed herein shall be considered to act in the following combinations ; whichever produces the most unfavorable effect in the building, foundation, or structural member being considered. Effects of one or more loads not acting shall be considered.
Condition No Description1. Erection : 100 D + E (E) + L
2. Operating :
101 D + (LP + SP)102 D + E(O) + (LP + PAE) + 0.7(WV(X) + 0,3(WV(Z,-Z)))103 D + E(O) + (LP + PAE ) + 0.7(WV(-X) + 0,3(WV(Z,-Z)))104 D + E(O) + (LP + PAE) + 0.7(WV(Z) + 0,3(WV(X,-X)))105 D + E(O) + (LP + PAE) + 0.7(WV(-Z) + 0,3(WV(X,-X)))
3. Operation : 106 D + E (E) + L + SP107 D + L + E (E)+ PAE
3.2. Factored Load CombınationStructures, components, and foundations shall be designed so that their design strength equals or exceed the effect of the factored loads in the following combinations :
Condition No Descriptio
n
1. Construction :300 1.4 (D + E(E)) 301 1.2 (D + E(E)) + 1.6 L
2. Maintenance :
302 1.2 (D + E(E)) + 1.6 (L + SP)303 1.2 (D + E(E)) + 1.6 (L + PAE)
3. Operating :
304 1.2 (D + E(O)) + 1.6 (LP + SP)305 1.2 (D + E(O)) + 1.6 (LP + PAE) + 1,0WV(X) + 0,3(WV(Z,-Z))306 1.2 (D + E(O)) + 1.6 (LP + PAE) + 1,0WV(-X) + 0,3(WV(Z,-Z))307 1.2 (D + E(O)) + 1.6 (LP + PAE) + 1,0WV(Z) + 0,3(WV(X,-X))308 1.2 (D + E(O)) + 1.6 (LP + PAE) + 1,0WV(-Z) + 0,3(WV(X,-X))
Where :1. D : Dead Load2. L : Live Load3. SP : Soil Pressure Load4. LP : Liquid Pressure Load5. PAE : Soil Active Pressure Due to Seismic X-dir6. WV(X) : Hydrodynamic Pressure Due to Seismic X-dir7. WV(X) : Hydrodynamic Pressure Due to Seismic -X-dir8. WV(Z) : Hydrodynamic Pressure Due to Seismic Z-dir9. WV(-Z) : Hydrodynamic Pressure Due to Seismic -Z-dir
PROYEK EPCI PENGEMBANGAN DPPU SEPINGGAN
CALCULATION FOUNDATION FOR FILTER SEPARATOR
Doc. No : SPG-CAL-50.014
Job No : -
Rev. No : 1 Page 11 of 10
10. E(E) : Equipment Empty11. E(O) : Equipment Operating
4. Computation of External LoadSee attachments 1 for detail calculation
5. Pond DesignSee attachments 2 for detail calculation