PACKAGED AIR TO WATER HEAT PUMPCOOLING/HEATINGOUTDOOR INSTALLATIONWITH BUILT IN HYDRAULIC MODULE
Cooling Capacity: 5,8kW - 31,8kWHeating Capacity: 6,9kW - 37,3kWR407c - Scroll
SPCA 001-010HSB
FeaturesOptimized design for R407c refrigerant.Casing:Galvanized steel plate with polyesteric coating.
AssemblyFully bolted/welding free.
Built in complete hydraulic module. Compressor:Hermetically sealed scroll type.
Air heat exchanger:Cross fin coilInternally grooved copper tubes and louvered aluminium fins.
Direct drive propeler fan.Low rpm, quiet operation
Water heat exchanger.Plate heat exchanger.
Safety and functional devices- High/low pressure switch.- Linear fan speed regulation according to coil temperature.- Differential water pressostat.- Plate heat exchanger low temperature protection.- Electronic microprosessor control with digital display.
The Interklima SPCA - HSB small capacityseries are packaged air cooled water heatpumps for cooling and heating applicationsand outdoor installation. They are availablein 9 models with nominal cooling capacitiesranging from 5,8 to 31,8kW and 6,9kW up to37,3kW in heating.
This series is ideal in combination withInterklima fan coils or air handing units forresidential and light commercial applicationsor for supplying water for small industrialapplications.
NOMENCLATURE
1 RangeS-small M-mid L-large R-screw-series
2 Packaged Chiller Air-cooledPCA
3 Model numbers001-002-003-004-005-006-007-010
4 Cool / Heat ModelR-cooling only H-heat pump
5 Compressor typeS-scroll M-tandem scroll R-reciprocatingT-twin screw
6 Refrigerant typeA-R22 B-R407c
7 Electrical Characteristic-1 Single phase -Ommited Three phase
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 3
1. Technical Description
2. Specifications
3. Capacity Tables
4. Available External Water Pressure Curves
5. Operation Range
6. Sound Data
7. Outlook Drawings
8. Refrigerant Circuit Diagrams
9. Wiring Diagrams
10. Installation
11. Guide Specifications
Contents
GeneralThe SPCA-HSB series air-cooled water heat pump consists of 9models covering cooling capacities from 5,8 up to 31,8kW andheating capacities from 6,9kW up to 37,3kW.It is the end result of a thorough study, and accurate design byexperienced Interklima research and development teams, todevelop a small size heat pump series with compact shape, highperformance, and reliability of the highest quality standards.This series meets the highest levels of aesthetic and technicalrequirements using the latest technological innovations includingenvironmentally friendly R407c refrigerant that is Chlorine-freeand has zero ozone depletion potential. SPCA-HSB units aretherefore ideal for installation in urban environments due to theirelegant design, selected materials and low operating sound levels.
CasingAll units use metal parts fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that guaranteesand preserves the units operation during the years. After fabricationmetal parts are degreased, phosphatised, and electrostaticallypowder coated with an epoxy-polyester RAL 9002 coating of athickness of 60-70 Ì. This fully automatic process ensuressuperior corrosion resistance against the most aggressive ambientconditions. The treatment can successfully withstand a salt spraytest of 500 hours, according to ASTM B-117.All components are assembled together using bolts thus avoidingthe need for welding which may harm the galvanization of thesteel, and ensures that the whole assembly can fully withstandadverse weather conditions.The compact footprint of the unit arises from detailed study anddesign by our engineering teams and results in a machine, whichfits easily in restricted areas and is simple and easy to install andmaintain, and has been designed with special fittings for easytransport and lifting.Removable panels with special locks are used to permit accessonly to authorized personnel to internal components of the unit forinspection and maintenance.
CompressorAll units use low-noise, maintenance free, Hermetic Scrollcompressor with low vibration levels, specially optimized for usewith R407c refrigerant, selected from world class suppliers.They are equipped with a crankcase electrical heater for the oil,and are internally protected against potential overloading orelectrical spikes.The compressors are mounted on special antivibration rubbermounts to eliminate vibration from the unit’s operation.
Hydraulic kitAll units are equipped, as standard, with a complete hydraulic kitcomprising of a circulating pump, buffer and expansion tank,automatic fill and make up water valve with manometer, safetyvalve, airvent, water filter, differential water pressure switch, andevacuation valve.
Air heat exchanger All unit air heat exchangers are manufactured from high qualityinner grooved seamless copper tubes according to ASTM B-280,having an outside diameter of 9,52 mm (3/8"). The fins aremanufactured from aluminium and form the secondary extendedheat transfer surface. The fins are continuous across the heatexchanger and are fabricated in high precision dedicated presslines. The fin surface is waffle formed, so as to increase the finrigidity, and have special louvers that help increase heat transfer.The combination of internally grooved Copper-tubing and louveredfins has resulted in a heat transfer performance 30% superior tothat of a conventional coil for this particular application. Theassembly of the finned pack is achieved by mechanical expansionof the tubes in such a way as to form a perfect mechanical bondwith the fins. For this purpose, the fin holes have a peripheralextrusion (collar) of adjustable height. This extrusion serves todefine the distance between fins (and consequently the total heattransfer surface) and to ensure perfect contact of the fins to thetubes.Alternative fin materials are available upon request such as epoxy- coated aluminium or copper for applications in especiallyaggressive environments.
Water heat exchangerAll units are equiped with a water - refrigerant Plate HeatExchanger, selected from world class manufacturers.It is made of stainless steel plates (AISI 3161.4401) speciallyformed to achieved a large heat transfer surface and assembledby means of an automatic brazing proccess, under vaccum.
Air heat exchanger fansAll unit fans are of the axial type, single phase, 6 poles, internallyprotected against potential overheating silent and suitable foroutdoor installation. Due to the sophisticated aerodynamic designof the blades and inlet cones, as well as the perfect static anddynamic balancing, their operation is completely vibration-free. Thefan-motor assembly has a protective grid against accidentalcontact with moving parts, which is designed according to ISOregulations. Fan motors are of the external rotor type,aerodynamically shaped so as not to interfere with the airflow, and
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll4
Technical Description1.
have permanently lubricated bearings that do not require servicing.Continuous linear fan speed regulation control is achievedaccording to coil temperatures including fan silent mode operation.This standard feature for Interklima SPCA units saves energy andreduces sound levels dramatically, optimizing capacity.
Microprocessor controllerAll units are equipped with a sophisticated controller easilyaccessible from outside through a transparent plastic cover thatcombines intelligence with operating simplicity. The controllerconstantly monitors all machine parameters and preciselymanages among others ñ Automatic compressor control function through return water
temperature.ñ Continuous fan speed control based on coil heat exchanger
temperature.ñ Defrost control.ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Over 150 programmable parameters.ñ Fan motor overload protection.ñ Auto diagnostic stop function due to low water circulation,
high/low operating pressures, and compressor thermaloverload.
ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.
ñ Digital displays of water inlet / outlet as well as coiltemperatures.
ñ Remote Cool / Heat selector switch.ñ Remote on / off switch.ñ Remote alarm indication capability.ñ Many optional control capabilities (listed in optional
accessories).
Refrigerant circuitAll units have a single refrigerant circuit with one compressor. Thecircuit consists, depending on the size, of either a capillary orthermal expansion valve. Other components fitted are solenoidvalve, suction accumulator, liquid receiver, check valve, 4way valve,large capacity filter dryer and high/low pressure manometers.Unit protection is provided by a high-pressure switch with manualreset, low-pressure protection is via a low-pressure switch.
Optional accessories
Microprocessor controller optionsñ Remote keyboard.ñ Dynamic set point program via a 4-20ma proportional signalñ BMS module interface kit for Modbus connection.ñ Parallel chiller operation with more than 2 units with optional
controller.ñ Microprocessor parameter reprogramming card.
Other unit accessories/optionñ R407c or R22 refrigerant.ñ Antifreeze protection.ñ Condenser fins made of copper or prepainted aluminum, and
Blygold treatment for corrosion protection.ñ Glycol application for chilled water temperature down to -5oCñ Pressure relief valve on compressor discharge.ñ High / Low pressure manometers.ñ Phase sequence - phase failure - reverse phase and voltage
monitoring device.ñ Compressor noise reduction jacket.ñ Compressor chamber noise reduction kit.ñ Other custom built options upon request.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 5
2.Technical specifications
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll6
Type
Nominal cooling capacity
Nominal heating capacity
Construction
Compressor
Quantity
Absorbed power
Nominal operating current
Maximum operating current
Air heat exchanger
Water heat exchanger
Quantity
Water content
Max. Operating pressure
Connections
Nominal water flow
Water pressure drop
Minimum system water content
Maximum unit operating water pressure
Fan
Quantity
Speed
Total air flow
Absorbed power
Nominal operating current
Maximum operating current
Pump
Absorbed power
Maximum operating current
Available external water head
Electrical characteristics
Total absorbed power
Nominal operating current
Maximum operating current
Compressor carter resistance power
Power cables cross section
Fuses
Voltage operating limits
Refrigerant circuit
Number of circuits
Expansion device
Refrigerant type
Noise level at 5m
Dimensions
Shipping weight
kW
RT
Btu/h
kW
kcal
Material/Color
kW
A
A
l
Water side bar
Refrigerant side bar
l/h
kpa
l
bar
rpm
m3/h
kW
A
A
kW
A
Kpa
kW
A
A
W
mm2
A
V
dB(A)
Width mm
Length mm
Heigth mm
kg
SPCA-001-1 SPCA-002-1 SPCA-002 SPCA-003 SPCA-0045,8
1.6
19.773
6,9
5.934
1
2,0/2,3
9,4/10,6
14.80
1
0.57
30
30
3/4"
998
26.5
29
3.0
1
920
2.500
0.12
0.57
0.63
0.13
0.58
35.0
2,3/2,6
10,6/11,8
16.0
70
4
25
1
45
474
1022
932
110
6,9
2.0
23.523
8,2
7.052
1
2,4/2,7
11,1/12,6
17.30
1
0.66
30
30
3/4"
1.187
27.6
35
3.0
1
920
2.350
0.12
0.57
0.63
0.13
0.58
32.0
2,7/3,0
12,2/13,8
18.5
70
4
25
1
45
474
1022
932
115
6,9
2.0
23.523
8,2
7.052
1
2,3/2,7
4,4/4,8
5.60
1
0.66
30
30
3/4"
1.187
27.6
35
3.0
1
920
2.350
0.12
0.57
0.63
0.13
0.58
32.0
2,6/3,0
5,6/6,0
6.8
70
2.5
3x16
1
46
474
1022
932
115
8,1
2.3
27.614
9,6
8.256
1
2,7/3,1
5,0/5,5
7.00
1
0.76
30
30
1"
1.393
29.2
41
3.0
1
920
4.000
0.17
0.80
0.90
0.13
0.58
30.0
3,0/3,4
6,4/6,9
8.5
70
2.5
3x16
1
48
474
1222
982
155
12,2
3.5
41.591
14,3
12.298
1
4,0/4,5
7,8/8,3
11.00
1
1.14
30
30
1"
2.098
29.9
61
3.0
2
920
4.600
0.24
1.14
1.26
0.25
1.1
42.0
4.5/5.0
10.0/10.5
13.4
70
2.5
3x16
1
48
522
1462
1002
190
Galvanized steel / Light grey-beige (RAL 9002)
SCROLL
High capaci ty cross finned coi l wi th internally grooved tubes and louver fins
Brazed plate
Axial type
Capi llary tubes
R407c
230 V/1 ph/50 Hz 400 V/3 ph/50 Hz
360-440 V220-240 V
2.1 SPCA 001-010HSB
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 7
Type
Nominal cooling capacity
Nominal heating capacity
Construction
Compressor
Quantity
Absorbed power
Nominal operating current
Maximum operating current
Air heat exchanger
Water heat exchanger
Quantity
Water content
Max. Operating pressure
Connections
Nominal water flow
Water pressure drop
Minimum system water content
Maximum unit operating water pressure
Fan
Quantity
Speed
Total air flow
Absorbed power
Nominal operating current
Maximum operating current
Pump
Absorbed power
Maximum operating current
Available external water head
Electrical characteristics
Total absorbed power
Nominal operating current
Maximum operating current
Compressor carter resistance power
Power cables cross section
Fuses
Voltage operating limits
Refrigerant circuit
Number of circuits
Expansion device
Refrigerant type
Noise level at 5m
Dimensions
Shipping weight
kW
RT
Btu/h
kW
kcal
Material/Color
kW
A
A
l
Water side bar
Refrigerant side bar
l/h
kpa
l
bar
rpm
m3/h
kW
A
A
kW
A
Kpa
kW
A
A
W
mm2
A
V
dB(A)
Width mm
Length mm
Heigth mm
kg
SPCA-005 SPCA-006 SPCA-007 SPCA-01014,6
4.1
49.773
17,0
14.620
1
4,6/5,2
8,3/9,2
13.00
1
1.35
30
30
1"
2.511
34.1
73
3.0
2
920
6.200
0.34
1.60
1.80
0.30
2.00
130.0
5.3/5.8
11.9/12.8
16.8
70
4
3x25
1
51
522
1612
1002
230
18,5
5.3
63.068
21,7
18.662
1
6,0/6,8
12,2/13,1
17.00
1
1.40
30
30
1 1/4"
3.182
34.6
93
3.0
2
920
6.400
0.34
1.60
1.80
0.45
2.70
150.0
6.8/7.6
16.3/17.4
21.5
70
6
3x25
1
52
605
1732
1202
300
22,4
6.4
76.364
26,2
22.532
1
7,2/8,0
14,5/15,5
20.00
1
1.70
30
30
1 1/4"
3.853
45.4
112
3.0
2
920
10.500
0.74
3.40
3.80
0.45
2.70
120.0
8.4/9.2
20.1/21.6
26.5
70
6
3x32
1
53
800
2020
1202
350
31,8
9.0
108.409
37,3
32.078
1
10,3/11,5
17,8/19,4
27.00
1
2.50
30
30
1 1/4"
5.470
24.4
159
3.0
2
920
11.000
0.74
3.40
3.80
0.55
3.50
165.0
11.3/12.8
23.9/26.3
34.3
70
10
3x40
1
55
800
2020
1202
380
Galvanized steel / Light grey-beige (RAL 9002)
SCROLL
High capacity cross finned coil with internally grooved tubes and louver fins
Brazed plate
Axial type
Capi llary tubes Expansion valve/Capillary tubesR407c
400 V/3 ph/50 Hz
360-440 V
NOTESNominal conditions are asfollows
entering/leaving chilledwater temperature 12/7oC;ambient 35oCDB (cooling)
entering/leaving heatedwater temperature 40/45oC;ambient 7oCDB/6oCWB(heating)
electrical installationspecifications are purelyindicative and non-binding,all connections to thesystem and the electricalinstallation must be in fullaccordance with allapplicable national and localcodes.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll8
Capacity tables3.
SPCA-001-1
SPCA-002-1
SPCA-002
SPCA-003
SPCA-004
SPCA-005
SPCA-006
SPCA-007
SPCA-010
Water outlet ÆC
Coolingcap. kW
Absorbedpower kW Current A Cooling
cap. kWAbsorbedpower kW Current A Cooling
cap. kWAbsorbedpower kW Current A Cooling
cap. kWAbsorbedpower kW Current A
Coolingcap. kW
Absorbedpower kW Current A
25 30 35 40 45
57
1057
1057
1057
1057
1057
1057
1057
1057
10
6.16.77.57.38.08.97.27.98.88.59.2
10.412.814.015.715.416.718.719.321.023.623.525.428.433.436.140.4
1.61.61.61.91.91.81.81.81.82.12.12.13.23.23.23.73.73.74.74.74.75.75.75.78.18.18.2
7.57.57.48.98.88.73.83.73.74.34.34.36.96.96.96.96.97.0
10.910.910.913.013.013.015.115.215.2
5.86.27.06.97.58.46.87.48.38.08.79.8
12.113.114.814.515.617.518.219.722.222.123.926.831.534.038.1
1.81.81.82.12.12.12.12.02.02.42.42.43.63.63.64.14.14.15.35.35.36.46.46.49.19.19.1
8.48.38.29.99.99.84.14.04.04.74.64.67.37.37.37.67.67.6
11.511.511.513.713.713.616.316.316.4
5.45.86.66.46.97.86.36.97.87.48.19.2
11.212.213.913.514.616.417.018.520.820.722.425.229.531.835.7
2.02.02.02.42.42.32.32.32.32.72.72.74.04.04.04.74.74.76.06.05.97.27.27.2
10.210.310.3
9.49.49.2
11.111.110.94.44.44.45.15.05.07.77.87.88.38.38.3
12.212.212.214.514.514.517.717.817.8
4.95.46.15.96.47.25.86.47.26.97.58.5
10.411.312.912.513.615.215.817.219.519.320.923.527.429.633.3
2.32.32.32.72.72.72.72.62.63.13.13.14.54.54.55.25.25.26.86.86.78.08.08.1
11.511.511.6
10.610.610.412.612.512.44.84.84.85.55.55.58.38.38.39.29.29.2
13.113.113.115.515.515.519.419.419.4
4.54.95.55.35.86.65.35.86.66.36.87.89.5
10.411.811.512.514.114.716.018.117.919.421.925.327.430.8
2.62.62.63.13.13.03.03.03.03.53.53.55.05.05.05.95.95.97.77.77.79.09.09.0
13.013.013.0
12.112.011.914.314.214.15.35.35.36.16.16.08.98.99.0
10.210.210.214.114.114.116.616.616.621.321.321.4
TypeAmbient temperature oC
SPCA-001-1
SPCA-002-1
SPCA-002
SPCA-003
SPCA-004
SPCA-005
SPCA-006
SPCA-007
SPCA-010
Water outlet ÆC
Heatingcap. kW
Absorbedpower kW Current A Heating
cap. kWAbsorbedpower kW Current A Heating
cap. kWAbsorbedpower kW Current A Heating
cap. kWAbsorbedpower kW Current A Heating
cap. kWAbsorbedpower kW Current A
-5 0 2 7 10
354045354045354045354045354045354045354045354045354045
5.55.45.46.66.5646.46.36.27.57.47.3
11.110.910.713.513.112.816.916.716.520.820.520.229.829.328.9
1.82.12.32.12.42.82.12.42.72.4 2.8 3.1 3.5 4.0 4.4 4.1 4.6 5.2 5.4 6.0 6.7 6.4 7.2 8.0 9.1
10.2 11.4
8.5 9.6
10.8 10.1 11.3 12.8 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.2 7.5 8.3 9.1
11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.6 19.2
5.95.8 5.7 7.0 6.9 6.8 6.8 6.7 6.6 8.0 7.9 7.8
11.9 11.7 11.4 14.4 14.0 13.7 18.1 17.8 17.6 22.2 21.8 21.4 31.7 31.1 30.6
1.82.02.32.12.42.82.12.42.72.42.83.13.54.04.44.14.65.25.46.06.86.47.28.09.1
10.211.4
8.5 9.5
10.8 10.1 11.3 12.8 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.2 7.6 8.3 9.1
11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.3
6.2 6.1 6.0 7.4 7.3 7.2 7.3 7.1 7.0 8.5 8.4 8.2
12.8 12.5 12.2 15.3 15.0 14.6 19.3 18.9 18.7 23.6 23.1 22.7 33.6 33.0 32.4
1.8 2.0 2.3 2.1 2.4 2.7 2.1 2.4 2.7 2.4 2.8 3.1 3.6 4.0 4.4 4.1 4.6 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1
10.2 11.5
8.5 9.5
10.7 10.0 11.3 12.7 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.3 7.6 8.3 9.1
11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.3
7.3 7.1 6.9 8.7 8.5 8.2 8.6 8.4 8.2 10.0 9.8 9.6 15.1 14.7 14.3 18.0 17.5 17.0 22.6 22.1 21.7 27.5 26.9 26.2 39.2 38.2 37.3
1.8 2.0 2.3 2.1 2.4 2.7 2.1 2.3 2.7 2.4 2.7 3.1 3.6 4.0 4.5 4.1 4.7 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1
10.2 11.5
8.4 9.4
10.6 9.9
11.1 12.6 4.1 4.4 4.8 4.7 5.1 5.5 7.3 7.7 8.3 7.6 8.3 9.2 11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.4
8.0 7.8 7.5 9.5 9.2 9.0 9.4 9.2 8.9
11.0 10.7 10.4 16.7 16.2 15.7 19.7 19.1 18.6 24.9 24.3 23.7 30.2 29.4 28.6 42.9 41.8 40.7
1.8 2.0 2.3 2.1 2.4 2.7 2.0 2.3 2.6 2.4 2.7 3.1 3.6 4.0 4.5 4.1 4.7 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1
10.3 11.6
8.3 9.3
10.5 9.8
11.0 12.5 4.0 4.4 4.8 4.6 5.0 5.5 7.3 7.8 8.3 7.6 8.3 9.2
11.5 12.2 13.1 13.7 14.5 15.5 16.4 17.8 19.4
TypeAmbient temperature oC
Cooling capacity table for SPCA 001-010HSB
Heating capacity table for SPCA 001-010HSB
NOTESBold values show nominal cooling/heating capacities.
Absorbed power and current refers to the compressor.Above figures are valid for water ¢t = 5oC.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 9
90
80
70
60
50
40
30
20
10
00 500 1.000 2.000 3.0001.500 2.500 3.500 WF
PD
kpa
l/h
l/h
80
100120
140
160180
200220
240260280
300320340360
604020
00 500 1,000 2.000 3.0001,500 2.500 3.500 4.000 4.500 5.000 6.0005.500 WF
PD
kpa
001
002003
004
005
006
007
010
Available external water pressure curves4.
SPCA 001-010HSB
NOTESPD: pressure dropWF: water flow rate1. SPCA 001-002HSB2. SPCA 003HSB3. SPCA 004HSB4. SPCA 005HSB5. SPCA 006HSB6. SPCA 007-010HSB
% ETHYLENE GLYCOL BY VOLUME
Freezing point
Output duty
Input pow er
Equivalent Flow rate
Equivalent Pressure drop
ETHYLENE GLYCOL CORRECTION FACTORSUNIT 10oC
kW
kW
L/H
kPa
-4
0,99
0,99
1,02
1,06
20
-9
0,98
0,98
1,04
1,12
30
-15
0,97
0,98
1,08
1,18
40
-23
0,96
0,97
1,13
1,25
SPCA - 001
SPCA - 002
SPCA - 003
SPCA - 004
SPCA - 005
SPCA - 006
SPCA - 007
SPCA - 010
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
Power
Pressure @1 m
Pressure @10 m
dB(A)
66
58
39
67
59
39
68
60
40
70
62
42
71
64
44
74
66
46
75
67
47
77
69
49
63
49
41
21
49
41
21
51
43
23
52
44
24
54
46
26
54
46
26
54
46
26
54
46
26
125
55
47
27
55
47
27
56
48
28
58
50
30
59
51
31
59
51
31
60
52
32
60
52
32
250
56
48
28
56
48
28
57
49
29
59
51
31
60
52
32
61
53
33
60
52
32
61
53
33
500
58
50
30
58
50
30
59
51
31
61
53
33
61
53
33
69
61
41
69
61
41
70
62
42
1000
62
54
34
62
56
36
64
56
36
65
57
37
67
59
39
68
60
40
68
60
40
69
61
41
2000
59
51
31
61
55
35
62
54
34
63
55
35
64
56
36
67
59
39
70
62
42
73
65
45
4000
54
46
26
58
53
33
58
50
30
58
50
30
65
57
37
63
55
35
65
57
37
70
62
42
8000
49
41
21
48
42
22
49
41
21
50
42
22
53
45
25
50
42
22
50
42
22
57
49
29
Type Octave band center frequency (Hz)
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll10
Operation range5.
45
-5
0
6 15
Outdoor Temperature ( CDB) COOLING HEATINGO
Leaving water temperature( C)o
Leaving water temperature( C)o
4
47
20
-5
25 50
Outdoor Temperature ( CDB)(RH=85%)O
0
Sound data6.
NOTESProtect the water circuit against freezing
- The accompanying operating limits are for general guidance only. It may bepossible for certain units to operate outside the confines of the graph. Pleasecontact Interklima if further clarification is required.
- For operation with leaving water temperature below 6 oC it is required to confirmwith Interklima at the time of order and the addition of glycol into the system.
932
450
49
1000
10221008
474460
474460
981
450 51 1200
12221208
508 1448522
1002
500 1440
1462
508 1598522 1612
1002
500 1590
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 11
Outlook drawings7.
7.1 SPCA 001-002HSB
7.2 SPCA 003HSB
7.3 SPCA 004HSB
7.4 SPCA 005HSB
1202
17401754
173260540
50
137
40 2020800
1202
20282042
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll12
7.5 SPCA 006HSB
7.6 SPCA 007-010HSB
3
15
2
9
8
8
6
6
7
4
3 8 8
1
2
101112
9
6
5
6 7
4
3
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 13
8.1 SPCA 001-005HSB
8.2 SPCA 006-010HSB
Refrigerant circuit diagrams8.
NOTES1. Scroll compressor2. Plate heat exchanger3. Air heat exchanger4. Suction accumulator5. 4-way reversing valve6. Check valve7. Filter dryer8. Capillary9. Liquid receiver10. Thermal expansion valve11. Solenoid valve12. Liquid glass
VC
VC
C1
FM1
F
CCf1
PM
CC
CM
PE
L2L1
L3
N
W
S
4V
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CC
CP
CP
PM
C
FM2
C2
Cf2
C1
FM1
F
CCf1
VC
VC
CC
CM
PE
L2L1
L3
N
W
S
4V
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CC
PMCM
CC
PE
LN
C
W
S
4VC1
FM1
F
CCf1
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CC
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll14
Wiring diagrams9.
9.1 SPCA 001-002HSB-1
9.2 SPCA 002-003HSB
9.3 SPCA 004-005HSB
CP
CP
PMSV
CC
T
C
C
FM2
C2 C1
FM1
F
CCf1Cf2
VC
VC
CC
CM
PE
L2L1
L3
N
W
S
4V
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CC
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 15
CP
CP
PMC2
SV
CC
CF 22 3334
F124
FAN SPEEDCONTROLLER
C
FM2
Cf2
C1
FM1
F
CCf1
T
C
VC
VC
CC
CM
PE
L2L1
L3
N
W
S
4V
F 2A
12V
AL
220V
AEMIFILTER
P
C
TR
12V
ON
Off
ST4ID4
GNDTK112DC12AC
12AC ALL GNDID5
S P P
F L
ST3ID3 ID2
ST2
H
ID1ST1
ALS2S3 S1
ALARM OUTPUTSM1
N
CC
CH
grdgrd grd
V
4
ENERGY 210
CC
9.4 SPCA 006HSB
SM1 GENERAL CIRCUIT BREAKER CC COMPRESSOR CONTACTOR CH COMPRESSOR CRANKCASE HEATER TR TRANSFORMER 220/2x12VAC HP HIGH PRESSURE PRESSOSTAT LP LOW PRESSURE PRESSOSTAT F CONTROL CIRCUIT BREAKER (2A) C1,2 COND, FANS 1, 2 CAPACITORS FS WATER DIFFERENTIAL PRESSOSTAT TC COMPRESSOR THERMAL PROTECTION 4V 4-WAY VALVE
S1 ENTERING WATER SENSOR S2 LEAVING WATER SENSOR S3 CONDENSER COIL TEMPERATURE SENSOR A COMMAND 220VAC FOR ELECTRICAL HEATERS (OPTIONAL) CP PUMP CONTACTOR PM PUMP CM COMPRESSOR VC VOLTAGE SURVEYOR (OPTIONAL) SV LIQUID SOLENOID VALVE
ALARM
LEGENDFIELD CONNECTIONS
ON -OFF REMOTE SWITCH (DRY CONTACT)AL-AL ALARM 12 V ACS-W REMOTE SUMMER-WINTER SWITCH (DRY CONTACT)
E00:E01:E02:E03:
E05:E06:E07:E41:
REMOTE ON/OFF IN POSITION OFFHIGH PRESSURELOW PRESSURECOMPRESSOR THERMAL PROTECTION*(*ONLY FOR SPCA 006-010∏SB)ANTIFREEZEPROBE ST2 FAULTPROBE ST3 FAULTWATER DIFFERENTIAL PRESSOSTAT
OFFON WS AL AL
9.5 SPCA 007-010HSB
The SPCA-HSB unit should be installed in a location that meets thefollowing requirements:1. The foundation is strong enough to support the weight of the unit,
and the floor is flat to prevent vibration and noise generation.2. The space around the unit is adequate for servicing and the
minimum space air inlet and air outlet is available. If several unitsare being installed side by side in parallel, the minimum servicespace between them must be taken into account
3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in
case it drips out the unit.5. Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction.Frontal wind willdisturb the operation of the unit.If necessary, use a windscreento block the wind.
6. In heavy snowfall areas, select an installation site where snowwill not affect operation of the unit.
7. Make sure that the unit mounting base can be fixed directly onconcrete.
8. In order to avoid the transmission of vibration from the operatingunit to its carrying structure, the use of antivibration material toinstall under the supports of the unit is recommended. It issuggested to install a rubber pad between the points of supportand the base of the unit, or spring antivibration mounts undereach point of support of the unit.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll16
Installation10.
10.1 Selection of location - service space
10.2 Centre of gravity
400mm
500mm
500mm
500mm
800mm
175
420
390
SPCA 001-002HSB
420
175 490
SPCA 003HSB
570200
420
SPCA 004HSB
420
200 620
SPCA 005HSB
(1500mm for 006-010 models)
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 17
ñ All units are equipped with a complete hydraulic kit as shownthe figure below
ñ All field conections must be carried out by a licensed technicianand must comply with the applicable local and national codes
ñ Evaporator water connections should be made in accordancewith the unit outlook respecting the water inlet – and outlets
ñ Connect a fresh water line to the water make up connection.The units are equipped with automatic make up valve tofacilitate water make up.
ñ It is advisable to connect flexible water inlet and outlet tubesto avoid vibration transmission
ñ The unit is operating in closed circuit. Avoid frequentunessasary water evacuation.
ñ It is essential to install a thermometer in the water inlet/ outlet
pipe to check temperatures.ñ Provide heat insulation with suitable vapour barrier around the
chilled water piping to prevent condensation and capacity loss.ñ Provide drain connections at all low points of the system to
permit complete drainage for maintenance and/ or shutdownñ Air vents should be provided at all high points in the system
located where they are easily accessible for servicing. Thewater inlet pipe is specially designed to obtain a complete airpurge of the evaporator.
ñ To avoid frequent on / off operation of the compressor, aminimum water volume is required in the system (table 10.4)
ñ To assure proper operation of the unit, the water qualitythrough the evaporator must be within the specified limits(table10.4).
10.3 Recomendations concerning the hydraulic circuit
650250
590
SPCA 006HSB
590
350 750
SPCA 007-010HSB
NOTES1. Pump2. Plate heat exchanger3. Automatic make up water
valve with manometer4. Buffer tank (water accumulation)5. Expansion tank6. Airvent7. Pressure relief valve8. Differential water pressure switch9. Water filter
3,5-4 bar
17-19 bar
4-5 bar
21-23 bar
5,5-6 bar
24-26 bar
low pressure
high pressure
Minimum(outdoor temp. 15ÔCDB) (leaving water temp 6ÔC)
Nominal(outdoor temp. 35ÔCDB)(leaving water temp, 7ÔC)
Maximum(outdoor temp. 38ÔCDB)
(leaving water temp, 25ÔC)
Cooling mode(region)
2.5-3 bar
15-18 bar
3-3.5 bar
21-23 bar
3,5-5 bar
25-26 bar
low pressure
high pressure
Minimum(outdoor temp. -5ÔCDB)
(leaving water temp 25ÔC)
Nominal(outdoor temp. 7ÔCDB)
(leaving water temp, 45ÔC)
Maximum(outdoor temp. 21ÔCDB)
(leaving water temp, 50ÔC)
Heating mode(region)
To ensure proper operation of the unit, a minimum water volumeis required in the system and the water flow must be within theoperation range as specified in the table.
It is important to check the high and low pressure of therefrigerant circuit to ensure the proper operation of the unitand to guarantee that the rated output will be obtained.
Attention:The pressures measured will vary between a maximum andminimum value, depending on the water and ambienttemperatures at the moment of measurement.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll18
10.4 Watercharge, flow and quality
29
35
35
41
61
73
93
112
159
SPCA-001-1HSB
SPCA-002-1HSB
SPCA-002HSB
SPCA-003HSB
SPCA-004HSB
SPCA-005HSB
SPCA-006HSB
SPCA-007HSB
SPCA-010HSB
Minimumwater
volume (l)
948
1127
1127
1324
1993
2386
3023
3660
5196
Minimumwater flow
(l/h)
998
1187
1187
1393
2098
2511
3182
3853
5470
Nominalwater flow
(l/h)
1097
1305
1305
1533
2308
2762
3500
4238
6017
Maximumwater flow
(l/h)
Items to be controlled:
PH AT 25ÔC
∂lectrical conduct (mS/m) at 25ÔC
Chloride ion (mg CI-/I)
Sulfate ion (mg SO 2/4/I
M-alkalinity (ph 4.8) (mg SO3/I)
Total hardness (mg CaCO3/I )
Calcium hardness (mg CaCO3/I)
Silica ion (mg SiO2/I
Items to be referred to:
Iron (mg Fe/I)
Copper (mg Cu/I)
Sulfide ion (mg S2-/I)
Amonium ion (mg NH+4/I
Remaining chloride (mg CI/I)
Free carbide (mg SO2/I)
Stability index
6.8 - 8.0
below 30
below 50
below 50
below 50
below 70
below 50
below 30
below 1.0
below 1.0
Not detectable
below 0.3
below 0.25
below 0.4
-
6.8 - 8.0
below 30
below 200
below 50
below 50
below 70
below 50
below 30
below 0.3
below 0.1
Not detectable
below 0.1
below 0.3
below 4.0
-
7.0 - 8.0
below 30
below 30
below 30
below 50
below 70
below 50
below 30
below 1.0
below 1.0
Not detectable
below 0.1
below 0.1
below 0.4
-
7.0 - 8.0
below 30
below 30
below 30
below 50
below 70
below 50
below 30
below 0.3
below 1.0
Not detectable
below 0.1
below 0.3
below 4.0
-
ItemsCirculatingwater 20C Supply water Circulating
water 20C-60C Supply water
Tendencyif out of criteria
Evaporator water Heated water
corrosion + scale
corrosion + scale
corrosion
corrosion
scale
scale
scale
scale
corrosion + scale
corrosion
corrosion
corrosion
corrosion
corrosion
corrosion + scale
Be sure the water quality is in accordance with the specificationsbelow
NOTESThe above tables are purelyindicative and non-binding
10.5 Operating pressure of the refrigerant circuit.
User interface SPCA 001-010HSBThe interface on the front panel can be used to carry out all theoperations connected to the use of the instrument, and inparticular to:
Set operating mode Check the state of resourcesRespond to alarm situations
10.6.1 KeysSelects operating mode:
If the heating mode is enabled, each time thekey is pressed the following sequence occurs:Stand-by cooling heating stand by
If cooling mode is enabled:heating Stand-by cooling heating stand byIn menu mode, this key acts as a SCROLL UPor UP key (increasing value).
Resets alarms, and turns the instrument onand off. Press once to reset all manually resetalarms not currently active.
Hold down the key for 2 seconds to turn theinstrument from on to off or vice versa. When it isoff, only the decimal point remains on the display.In menu mode this key acts as a SCROLL DOWNor DOWN key (decreasing value).
Pressing the “mode” and “on-off” keys at thesame time.
If you press both keys at the same time andthen release within 2 seconds, you will moveone level deeper in the display menu. If you press both keys for more than 2 secondsyou will move one level up.If you are currently viewing the lowest level inthe menu and you press both keys and releasewithin 2 seconds, you will go up one level.
10.6.2.2 LedLed 1 compressor 1(step 1)ON if compressor 1 is activeOFF if compressor 1 is offRapid BLINK if safety timing is in progressSlow BLINK if compressor is currently set to defrost (heatpump version)Power step 2 led
Not used
Defrost led (heat pump version)ON if defrosting is in progressOFF if defrosting is disabled or has been completedBLINK if timing is in progress (defrost interval)
Electrical heater/boiler ledON if the internal anti-freeze electrical heater or boiler is onOFF if the internal anti-freeze electrical heater or boiler is off
Heating led (heat pump version)ON if the device is in heating mode
Cooling ledON if the controller is in cooling mode
If neither the HEATING led nor the COOLING led is on, thecontroller is in STAND-BY mode
10.6.2 Displays10.6.2.1 DisplayNormal display shows:
ñ Regulation temperature in tenths of degreescelsius with a decimal point, or in degreesfahrenheit without a decimal point.
ñ The alarm code, if at least one alarm is active. Ifmultiple alarms are active, the one with greaterpriority will be displayed, according to the Tableof Alarms.
ñ If temperature control is not analogue anddepends on the status of a digital input (ST1 orST2 configured as digital inputs), the “On” or“Off” label will be displayed, depending onwhether temperature control is active or not.
ñ When in menu mode, the display depends on thecurrent position; labels and codes are used tohelp the user identify the current function.
ñ Decimal point: when displaying hours of operation,indicates that the value must be multiplied x 100.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 19
10.6 Digital controler
Front panel of the instrument
1 2
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll20
24
Blue
Conn. A
Remote keyboard
Connection
Back side
Conn. B
Red
Blac
k
26
25
The remote keyboard on the display is an exact copy of theinformation displayed on the instrument, with the same leds;
Connection with the controller is illustrated below:
It performs exactly the same functions as those described in thedisplay section.The only difference is in use of the UP and DOWNkeys (to increase and decrease value), which are separate fromthe MODE and ON/OFF keys.
10.7 Remote keyboard
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 21
The supply, transport to jobsite, installation, commissioning andstart up of an air cooled water heat pump with the followingtechnical characteristics.The unit shall be factory assembled, charged with R407crefrigerant and factory tested.The capacity of the unit shall be no less than:
Cooling capacity: kWIn the following conditionsAmbient air temperature (DB) ÆCEntering water temperature ÆCLeaving water temperature ÆC
Heating capacity: kWIn the following conditionsAmbient air temperature (DB) ÆCAmbient relative humidity %Entering water temperature ÆCLeaving water temperature ÆC
The unit shall operate unhindered within 6 to 15ÆC/25oC to 50oC(cool/heat) water outlet temperature, 3.5 to 7ÆC watertemperature difference and 5 up to 45ÆC ambient air temperature.The structural requirements shall be the following:
UNIT HOUSINGThe unit housing shall be fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that shall guaranteeand preserve the unit operation during the years. All metal parts afterfabrication shall be degreased phosphatized, and electrostaticallypowder coated with epoxy- polyester RAL 9002 coating of athickness of 60-70 m. The corrosion resistance treatment mustsuccessfully withstand a salt spray test of 500 hours, according toASTM B- 117. All components shall be assembled exclusivelytogether using bolts, without welding. The unit shall have removableaccess panels, designed in such a manner as to permit easy accessto internal compartments only by authorized personnel.
COMPRESSORShall be of the hermetic scroll type, with low noise and vibrationlevels, specially optimized for use with R407c refrigerant. It shallbe equipped with a crank case electrical heater, to separaterefrigerant and oil when the unit is not operating. It shall alsoinclude internal protection against overloading or electrical spikes.The compressor shall be mounted on special ant vibration rubbermounts to absorb and eliminate any vibration that can begenerated from the unit base.
HYDRAULIC KITThe unit shall be equipped with a complete hydraulic kit,comprising of a circulating pump, buffer and expansion tank,automatic fill / make up water valve with manometer, safety valve,air vent, water filter and differential water pressure switch.
AIR HEAT EXCHANGERThe air hear exchanger shall be manufactured from seamlesscopper tubes having an outside diameter of 9.52mm (3/8'') of highquality according to ASTM B 280. The tubes shall be internallygrooved to achieve optimized heat transfer between refrigerant andtube. The fins shall be manufactured from aluminium. The fins shallbe continuous across the heat exchanger and the fin surface shallbe waffle formed and louvered so as to increase the fin rigidity andheat transfer. The combination of internally grooved copper tubingand louvered fins must result in a heat transfer performance 30%superior to that of a conventional coil.The assembly of the finned pack shall be achieved by mechanicalexpansion in such a way as to form a perfect mechanical bondwith the fins. For this purpose, the fin holes shall have a peripheralextrusion (collar).
WATER HEAT EXCHANGERThe water heat exchanger shall be of the plate heat exchangertype, selected from world-class manufacturers and made ofstainless steel plates (AISI 3161.4401) specially formed toachieve optimized heat transfer. The plates shall be assembled bymeans of an automatic brazing process, under vaccum.
AIR HEAT EXCHANGER FANS The unit shall be equipped with axial type fans, single phase, and6 poles, internally protected against potential overheating,noiseless and suitable for outdoor installation. The design of theblades and inlet cones shall be aerodynamic, and the fan motorassembly shall be perfectly statically and dynamically balancedallowing a completely vibration free operation. The fan motorassembly shall have a protective grid against accidental contactwith moving parts according to ISO. The fan motor shall be of theexternal rotor type with permanently lubricated bearings that donot require servicing. The motor shall be aerodynamically shapedso as not to interfere with the airflow. The unit shall be equippedwith a continuous linear fan speed regulation control according tocoil temperature.
Guide specifications11.
SPCA 001-010HSB
CONTROL SYSTEM WITH MICROPROCESSOR CONTROLLER The control system shall possess a sophisticated controller thatshall constantly monitor all machine parameters and particularlymanage among others:ñ Automatic compressor control function through return water
temperature.ñ Continuous fan speed control based on coil heat exchanger
temperature.ñ Defrost control.ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Compressor running time records.ñ Over 150 programmable parameters. ñ Fan motors overload protection.ñ Auto diagnostic stop function due to low water circulation,
high / low operating pressures and compressor thermaloverload.
ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.
ñ Digital displays of inlet/ outlet as well as condensingtemperatures.
ñ Remote cool/ heat and on / off selectionñ Various other optional control capabilities (listed in options)
REFRIGERANT CIRCUITThe unit shall have a single refrigerant circuit with onecompressor. The circuit shall consist of a filter dryer, expansiondevice, solenoid valve, check valve, liquid receiver, suctionaccumulator, 4way valve and a high and low pressure switch withmanual reset.
NOTEThe consultant may if required add the below mentioned optionalaccessories / functions.ñ Remote keyboard.ñ Dynamic set point program via a 4 20 mA proportional
signal.ñ BMS module interface kit for modbus connection.ñ Parallel chiller operation with more than 2 units with optional
controller. ñ Microprocessor parameters reprogramming card.ñ Condenser fins made of prepainted aluminum or copper, and
blygold treatment for additional corrosion protection.ñ Plate exchanger-freezing protection for low chilled water
temperature controlled by microprocessor.ñ Glycol for low chilled water temperatures.ñ Pressure relief valve on compressor dischargeñ High / low pressure manometers.ñ Phase sequence phase failure - reverse phase and voltage
monitoring device.
Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll22
Products are manufactured in ISO 9001:2000certified factories. ISO 9001:2000 pertains to quality
assurance regarding design, development,manufacturing and installation of products
as well as to services related to the product.
INTERKLIMA PRODUCTS ARE DISTRIBUTED BY:
EG
B-B
-3-2
-05/
06
Specifications subject to change without notice
Interklima units comply with the European regulations thatguarantee the safety of the product