spca hsb gb - calor · the spca-hsb series air-cooled water heat pump consists of 9 models covering...

24
PACKAGED AIR TO WATER HEAT PUMP COOLING/HEATING OUTDOOR INSTALLATION WITH BUILT IN HYDRAULIC MODULE Cooling Capacity: 5,8kW - 31,8kW Heating Capacity: 6,9kW - 37,3kW R407c - Scroll SPCA 001-010HSB Features Optimized design for R407c refrigerant. Casing: Galvanized steel plate with polyesteric coating. Assembly Fully bolted/welding free. Built in complete hydraulic module. Compressor: Hermetically sealed scroll type. Air heat exchanger: Cross fin coil Internally grooved copper tubes and louvered aluminium fins. Direct drive propeler fan. Low rpm, quiet operation Water heat exchanger. Plate heat exchanger. Safety and functional devices - High/low pressure switch. - Linear fan speed regulation according to coil temperature. - Differential water pressostat. - Plate heat exchanger low temperature protection. - Electronic microprosessor control with digital display. The Interklima SPCA - HSB small capacity series are packaged air cooled water heat pumps for cooling and heating applications and outdoor installation. They are available in 9 models with nominal cooling capacities ranging from 5,8 to 31,8kW and 6,9kW up to 37,3kW in heating. This series is ideal in combination with Interklima fan coils or air handing units for residential and light commercial applications or for supplying water for small industrial applications.

Upload: others

Post on 25-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

PACKAGED AIR TO WATER HEAT PUMPCOOLING/HEATINGOUTDOOR INSTALLATIONWITH BUILT IN HYDRAULIC MODULE

Cooling Capacity: 5,8kW - 31,8kWHeating Capacity: 6,9kW - 37,3kWR407c - Scroll

SPCA 001-010HSB

FeaturesOptimized design for R407c refrigerant.Casing:Galvanized steel plate with polyesteric coating.

AssemblyFully bolted/welding free.

Built in complete hydraulic module. Compressor:Hermetically sealed scroll type.

Air heat exchanger:Cross fin coilInternally grooved copper tubes and louvered aluminium fins.

Direct drive propeler fan.Low rpm, quiet operation

Water heat exchanger.Plate heat exchanger.

Safety and functional devices- High/low pressure switch.- Linear fan speed regulation according to coil temperature.- Differential water pressostat.- Plate heat exchanger low temperature protection.- Electronic microprosessor control with digital display.

The Interklima SPCA - HSB small capacityseries are packaged air cooled water heatpumps for cooling and heating applicationsand outdoor installation. They are availablein 9 models with nominal cooling capacitiesranging from 5,8 to 31,8kW and 6,9kW up to37,3kW in heating.

This series is ideal in combination withInterklima fan coils or air handing units forresidential and light commercial applicationsor for supplying water for small industrialapplications.

Page 2: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

NOMENCLATURE

1 RangeS-small M-mid L-large R-screw-series

2 Packaged Chiller Air-cooledPCA

3 Model numbers001-002-003-004-005-006-007-010

4 Cool / Heat ModelR-cooling only H-heat pump

5 Compressor typeS-scroll M-tandem scroll R-reciprocatingT-twin screw

6 Refrigerant typeA-R22 B-R407c

7 Electrical Characteristic-1 Single phase -Ommited Three phase

Page 3: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 3

1. Technical Description

2. Specifications

3. Capacity Tables

4. Available External Water Pressure Curves

5. Operation Range

6. Sound Data

7. Outlook Drawings

8. Refrigerant Circuit Diagrams

9. Wiring Diagrams

10. Installation

11. Guide Specifications

Contents

Page 4: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

GeneralThe SPCA-HSB series air-cooled water heat pump consists of 9models covering cooling capacities from 5,8 up to 31,8kW andheating capacities from 6,9kW up to 37,3kW.It is the end result of a thorough study, and accurate design byexperienced Interklima research and development teams, todevelop a small size heat pump series with compact shape, highperformance, and reliability of the highest quality standards.This series meets the highest levels of aesthetic and technicalrequirements using the latest technological innovations includingenvironmentally friendly R407c refrigerant that is Chlorine-freeand has zero ozone depletion potential. SPCA-HSB units aretherefore ideal for installation in urban environments due to theirelegant design, selected materials and low operating sound levels.

CasingAll units use metal parts fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that guaranteesand preserves the units operation during the years. After fabricationmetal parts are degreased, phosphatised, and electrostaticallypowder coated with an epoxy-polyester RAL 9002 coating of athickness of 60-70 Ì. This fully automatic process ensuressuperior corrosion resistance against the most aggressive ambientconditions. The treatment can successfully withstand a salt spraytest of 500 hours, according to ASTM B-117.All components are assembled together using bolts thus avoidingthe need for welding which may harm the galvanization of thesteel, and ensures that the whole assembly can fully withstandadverse weather conditions.The compact footprint of the unit arises from detailed study anddesign by our engineering teams and results in a machine, whichfits easily in restricted areas and is simple and easy to install andmaintain, and has been designed with special fittings for easytransport and lifting.Removable panels with special locks are used to permit accessonly to authorized personnel to internal components of the unit forinspection and maintenance.

CompressorAll units use low-noise, maintenance free, Hermetic Scrollcompressor with low vibration levels, specially optimized for usewith R407c refrigerant, selected from world class suppliers.They are equipped with a crankcase electrical heater for the oil,and are internally protected against potential overloading orelectrical spikes.The compressors are mounted on special antivibration rubbermounts to eliminate vibration from the unit’s operation.

Hydraulic kitAll units are equipped, as standard, with a complete hydraulic kitcomprising of a circulating pump, buffer and expansion tank,automatic fill and make up water valve with manometer, safetyvalve, airvent, water filter, differential water pressure switch, andevacuation valve.

Air heat exchanger All unit air heat exchangers are manufactured from high qualityinner grooved seamless copper tubes according to ASTM B-280,having an outside diameter of 9,52 mm (3/8"). The fins aremanufactured from aluminium and form the secondary extendedheat transfer surface. The fins are continuous across the heatexchanger and are fabricated in high precision dedicated presslines. The fin surface is waffle formed, so as to increase the finrigidity, and have special louvers that help increase heat transfer.The combination of internally grooved Copper-tubing and louveredfins has resulted in a heat transfer performance 30% superior tothat of a conventional coil for this particular application. Theassembly of the finned pack is achieved by mechanical expansionof the tubes in such a way as to form a perfect mechanical bondwith the fins. For this purpose, the fin holes have a peripheralextrusion (collar) of adjustable height. This extrusion serves todefine the distance between fins (and consequently the total heattransfer surface) and to ensure perfect contact of the fins to thetubes.Alternative fin materials are available upon request such as epoxy- coated aluminium or copper for applications in especiallyaggressive environments.

Water heat exchangerAll units are equiped with a water - refrigerant Plate HeatExchanger, selected from world class manufacturers.It is made of stainless steel plates (AISI 3161.4401) speciallyformed to achieved a large heat transfer surface and assembledby means of an automatic brazing proccess, under vaccum.

Air heat exchanger fansAll unit fans are of the axial type, single phase, 6 poles, internallyprotected against potential overheating silent and suitable foroutdoor installation. Due to the sophisticated aerodynamic designof the blades and inlet cones, as well as the perfect static anddynamic balancing, their operation is completely vibration-free. Thefan-motor assembly has a protective grid against accidentalcontact with moving parts, which is designed according to ISOregulations. Fan motors are of the external rotor type,aerodynamically shaped so as not to interfere with the airflow, and

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll4

Technical Description1.

Page 5: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

have permanently lubricated bearings that do not require servicing.Continuous linear fan speed regulation control is achievedaccording to coil temperatures including fan silent mode operation.This standard feature for Interklima SPCA units saves energy andreduces sound levels dramatically, optimizing capacity.

Microprocessor controllerAll units are equipped with a sophisticated controller easilyaccessible from outside through a transparent plastic cover thatcombines intelligence with operating simplicity. The controllerconstantly monitors all machine parameters and preciselymanages among others ñ Automatic compressor control function through return water

temperature.ñ Continuous fan speed control based on coil heat exchanger

temperature.ñ Defrost control.ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Over 150 programmable parameters.ñ Fan motor overload protection.ñ Auto diagnostic stop function due to low water circulation,

high/low operating pressures, and compressor thermaloverload.

ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.

ñ Digital displays of water inlet / outlet as well as coiltemperatures.

ñ Remote Cool / Heat selector switch.ñ Remote on / off switch.ñ Remote alarm indication capability.ñ Many optional control capabilities (listed in optional

accessories).

Refrigerant circuitAll units have a single refrigerant circuit with one compressor. Thecircuit consists, depending on the size, of either a capillary orthermal expansion valve. Other components fitted are solenoidvalve, suction accumulator, liquid receiver, check valve, 4way valve,large capacity filter dryer and high/low pressure manometers.Unit protection is provided by a high-pressure switch with manualreset, low-pressure protection is via a low-pressure switch.

Optional accessories

Microprocessor controller optionsñ Remote keyboard.ñ Dynamic set point program via a 4-20ma proportional signalñ BMS module interface kit for Modbus connection.ñ Parallel chiller operation with more than 2 units with optional

controller.ñ Microprocessor parameter reprogramming card.

Other unit accessories/optionñ R407c or R22 refrigerant.ñ Antifreeze protection.ñ Condenser fins made of copper or prepainted aluminum, and

Blygold treatment for corrosion protection.ñ Glycol application for chilled water temperature down to -5oCñ Pressure relief valve on compressor discharge.ñ High / Low pressure manometers.ñ Phase sequence - phase failure - reverse phase and voltage

monitoring device.ñ Compressor noise reduction jacket.ñ Compressor chamber noise reduction kit.ñ Other custom built options upon request.

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 5

Page 6: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

2.Technical specifications

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll6

Type

Nominal cooling capacity

Nominal heating capacity

Construction

Compressor

Quantity

Absorbed power

Nominal operating current

Maximum operating current

Air heat exchanger

Water heat exchanger

Quantity

Water content

Max. Operating pressure

Connections

Nominal water flow

Water pressure drop

Minimum system water content

Maximum unit operating water pressure

Fan

Quantity

Speed

Total air flow

Absorbed power

Nominal operating current

Maximum operating current

Pump

Absorbed power

Maximum operating current

Available external water head

Electrical characteristics

Total absorbed power

Nominal operating current

Maximum operating current

Compressor carter resistance power

Power cables cross section

Fuses

Voltage operating limits

Refrigerant circuit

Number of circuits

Expansion device

Refrigerant type

Noise level at 5m

Dimensions

Shipping weight

kW

RT

Btu/h

kW

kcal

Material/Color

kW

A

A

l

Water side bar

Refrigerant side bar

l/h

kpa

l

bar

rpm

m3/h

kW

A

A

kW

A

Kpa

kW

A

A

W

mm2

A

V

dB(A)

Width mm

Length mm

Heigth mm

kg

SPCA-001-1 SPCA-002-1 SPCA-002 SPCA-003 SPCA-0045,8

1.6

19.773

6,9

5.934

1

2,0/2,3

9,4/10,6

14.80

1

0.57

30

30

3/4"

998

26.5

29

3.0

1

920

2.500

0.12

0.57

0.63

0.13

0.58

35.0

2,3/2,6

10,6/11,8

16.0

70

4

25

1

45

474

1022

932

110

6,9

2.0

23.523

8,2

7.052

1

2,4/2,7

11,1/12,6

17.30

1

0.66

30

30

3/4"

1.187

27.6

35

3.0

1

920

2.350

0.12

0.57

0.63

0.13

0.58

32.0

2,7/3,0

12,2/13,8

18.5

70

4

25

1

45

474

1022

932

115

6,9

2.0

23.523

8,2

7.052

1

2,3/2,7

4,4/4,8

5.60

1

0.66

30

30

3/4"

1.187

27.6

35

3.0

1

920

2.350

0.12

0.57

0.63

0.13

0.58

32.0

2,6/3,0

5,6/6,0

6.8

70

2.5

3x16

1

46

474

1022

932

115

8,1

2.3

27.614

9,6

8.256

1

2,7/3,1

5,0/5,5

7.00

1

0.76

30

30

1"

1.393

29.2

41

3.0

1

920

4.000

0.17

0.80

0.90

0.13

0.58

30.0

3,0/3,4

6,4/6,9

8.5

70

2.5

3x16

1

48

474

1222

982

155

12,2

3.5

41.591

14,3

12.298

1

4,0/4,5

7,8/8,3

11.00

1

1.14

30

30

1"

2.098

29.9

61

3.0

2

920

4.600

0.24

1.14

1.26

0.25

1.1

42.0

4.5/5.0

10.0/10.5

13.4

70

2.5

3x16

1

48

522

1462

1002

190

Galvanized steel / Light grey-beige (RAL 9002)

SCROLL

High capaci ty cross finned coi l wi th internally grooved tubes and louver fins

Brazed plate

Axial type

Capi llary tubes

R407c

230 V/1 ph/50 Hz 400 V/3 ph/50 Hz

360-440 V220-240 V

2.1 SPCA 001-010HSB

Page 7: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 7

Type

Nominal cooling capacity

Nominal heating capacity

Construction

Compressor

Quantity

Absorbed power

Nominal operating current

Maximum operating current

Air heat exchanger

Water heat exchanger

Quantity

Water content

Max. Operating pressure

Connections

Nominal water flow

Water pressure drop

Minimum system water content

Maximum unit operating water pressure

Fan

Quantity

Speed

Total air flow

Absorbed power

Nominal operating current

Maximum operating current

Pump

Absorbed power

Maximum operating current

Available external water head

Electrical characteristics

Total absorbed power

Nominal operating current

Maximum operating current

Compressor carter resistance power

Power cables cross section

Fuses

Voltage operating limits

Refrigerant circuit

Number of circuits

Expansion device

Refrigerant type

Noise level at 5m

Dimensions

Shipping weight

kW

RT

Btu/h

kW

kcal

Material/Color

kW

A

A

l

Water side bar

Refrigerant side bar

l/h

kpa

l

bar

rpm

m3/h

kW

A

A

kW

A

Kpa

kW

A

A

W

mm2

A

V

dB(A)

Width mm

Length mm

Heigth mm

kg

SPCA-005 SPCA-006 SPCA-007 SPCA-01014,6

4.1

49.773

17,0

14.620

1

4,6/5,2

8,3/9,2

13.00

1

1.35

30

30

1"

2.511

34.1

73

3.0

2

920

6.200

0.34

1.60

1.80

0.30

2.00

130.0

5.3/5.8

11.9/12.8

16.8

70

4

3x25

1

51

522

1612

1002

230

18,5

5.3

63.068

21,7

18.662

1

6,0/6,8

12,2/13,1

17.00

1

1.40

30

30

1 1/4"

3.182

34.6

93

3.0

2

920

6.400

0.34

1.60

1.80

0.45

2.70

150.0

6.8/7.6

16.3/17.4

21.5

70

6

3x25

1

52

605

1732

1202

300

22,4

6.4

76.364

26,2

22.532

1

7,2/8,0

14,5/15,5

20.00

1

1.70

30

30

1 1/4"

3.853

45.4

112

3.0

2

920

10.500

0.74

3.40

3.80

0.45

2.70

120.0

8.4/9.2

20.1/21.6

26.5

70

6

3x32

1

53

800

2020

1202

350

31,8

9.0

108.409

37,3

32.078

1

10,3/11,5

17,8/19,4

27.00

1

2.50

30

30

1 1/4"

5.470

24.4

159

3.0

2

920

11.000

0.74

3.40

3.80

0.55

3.50

165.0

11.3/12.8

23.9/26.3

34.3

70

10

3x40

1

55

800

2020

1202

380

Galvanized steel / Light grey-beige (RAL 9002)

SCROLL

High capacity cross finned coil with internally grooved tubes and louver fins

Brazed plate

Axial type

Capi llary tubes Expansion valve/Capillary tubesR407c

400 V/3 ph/50 Hz

360-440 V

NOTESNominal conditions are asfollows

entering/leaving chilledwater temperature 12/7oC;ambient 35oCDB (cooling)

entering/leaving heatedwater temperature 40/45oC;ambient 7oCDB/6oCWB(heating)

electrical installationspecifications are purelyindicative and non-binding,all connections to thesystem and the electricalinstallation must be in fullaccordance with allapplicable national and localcodes.

Page 8: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll8

Capacity tables3.

SPCA-001-1

SPCA-002-1

SPCA-002

SPCA-003

SPCA-004

SPCA-005

SPCA-006

SPCA-007

SPCA-010

Water outlet ÆC

Coolingcap. kW

Absorbedpower kW Current A Cooling

cap. kWAbsorbedpower kW Current A Cooling

cap. kWAbsorbedpower kW Current A Cooling

cap. kWAbsorbedpower kW Current A

Coolingcap. kW

Absorbedpower kW Current A

25 30 35 40 45

57

1057

1057

1057

1057

1057

1057

1057

1057

10

6.16.77.57.38.08.97.27.98.88.59.2

10.412.814.015.715.416.718.719.321.023.623.525.428.433.436.140.4

1.61.61.61.91.91.81.81.81.82.12.12.13.23.23.23.73.73.74.74.74.75.75.75.78.18.18.2

7.57.57.48.98.88.73.83.73.74.34.34.36.96.96.96.96.97.0

10.910.910.913.013.013.015.115.215.2

5.86.27.06.97.58.46.87.48.38.08.79.8

12.113.114.814.515.617.518.219.722.222.123.926.831.534.038.1

1.81.81.82.12.12.12.12.02.02.42.42.43.63.63.64.14.14.15.35.35.36.46.46.49.19.19.1

8.48.38.29.99.99.84.14.04.04.74.64.67.37.37.37.67.67.6

11.511.511.513.713.713.616.316.316.4

5.45.86.66.46.97.86.36.97.87.48.19.2

11.212.213.913.514.616.417.018.520.820.722.425.229.531.835.7

2.02.02.02.42.42.32.32.32.32.72.72.74.04.04.04.74.74.76.06.05.97.27.27.2

10.210.310.3

9.49.49.2

11.111.110.94.44.44.45.15.05.07.77.87.88.38.38.3

12.212.212.214.514.514.517.717.817.8

4.95.46.15.96.47.25.86.47.26.97.58.5

10.411.312.912.513.615.215.817.219.519.320.923.527.429.633.3

2.32.32.32.72.72.72.72.62.63.13.13.14.54.54.55.25.25.26.86.86.78.08.08.1

11.511.511.6

10.610.610.412.612.512.44.84.84.85.55.55.58.38.38.39.29.29.2

13.113.113.115.515.515.519.419.419.4

4.54.95.55.35.86.65.35.86.66.36.87.89.5

10.411.811.512.514.114.716.018.117.919.421.925.327.430.8

2.62.62.63.13.13.03.03.03.03.53.53.55.05.05.05.95.95.97.77.77.79.09.09.0

13.013.013.0

12.112.011.914.314.214.15.35.35.36.16.16.08.98.99.0

10.210.210.214.114.114.116.616.616.621.321.321.4

TypeAmbient temperature oC

SPCA-001-1

SPCA-002-1

SPCA-002

SPCA-003

SPCA-004

SPCA-005

SPCA-006

SPCA-007

SPCA-010

Water outlet ÆC

Heatingcap. kW

Absorbedpower kW Current A Heating

cap. kWAbsorbedpower kW Current A Heating

cap. kWAbsorbedpower kW Current A Heating

cap. kWAbsorbedpower kW Current A Heating

cap. kWAbsorbedpower kW Current A

-5 0 2 7 10

354045354045354045354045354045354045354045354045354045

5.55.45.46.66.5646.46.36.27.57.47.3

11.110.910.713.513.112.816.916.716.520.820.520.229.829.328.9

1.82.12.32.12.42.82.12.42.72.4 2.8 3.1 3.5 4.0 4.4 4.1 4.6 5.2 5.4 6.0 6.7 6.4 7.2 8.0 9.1

10.2 11.4

8.5 9.6

10.8 10.1 11.3 12.8 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.2 7.5 8.3 9.1

11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.6 19.2

5.95.8 5.7 7.0 6.9 6.8 6.8 6.7 6.6 8.0 7.9 7.8

11.9 11.7 11.4 14.4 14.0 13.7 18.1 17.8 17.6 22.2 21.8 21.4 31.7 31.1 30.6

1.82.02.32.12.42.82.12.42.72.42.83.13.54.04.44.14.65.25.46.06.86.47.28.09.1

10.211.4

8.5 9.5

10.8 10.1 11.3 12.8 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.2 7.6 8.3 9.1

11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.3

6.2 6.1 6.0 7.4 7.3 7.2 7.3 7.1 7.0 8.5 8.4 8.2

12.8 12.5 12.2 15.3 15.0 14.6 19.3 18.9 18.7 23.6 23.1 22.7 33.6 33.0 32.4

1.8 2.0 2.3 2.1 2.4 2.7 2.1 2.4 2.7 2.4 2.8 3.1 3.6 4.0 4.4 4.1 4.6 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1

10.2 11.5

8.5 9.5

10.7 10.0 11.3 12.7 4.1 4.4 4.9 4.7 5.1 5.6 7.2 7.7 8.3 7.6 8.3 9.1

11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.3

7.3 7.1 6.9 8.7 8.5 8.2 8.6 8.4 8.2 10.0 9.8 9.6 15.1 14.7 14.3 18.0 17.5 17.0 22.6 22.1 21.7 27.5 26.9 26.2 39.2 38.2 37.3

1.8 2.0 2.3 2.1 2.4 2.7 2.1 2.3 2.7 2.4 2.7 3.1 3.6 4.0 4.5 4.1 4.7 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1

10.2 11.5

8.4 9.4

10.6 9.9

11.1 12.6 4.1 4.4 4.8 4.7 5.1 5.5 7.3 7.7 8.3 7.6 8.3 9.2 11.5 12.2 13.1 13.7 14.5 15.5 16.3 17.7 19.4

8.0 7.8 7.5 9.5 9.2 9.0 9.4 9.2 8.9

11.0 10.7 10.4 16.7 16.2 15.7 19.7 19.1 18.6 24.9 24.3 23.7 30.2 29.4 28.6 42.9 41.8 40.7

1.8 2.0 2.3 2.1 2.4 2.7 2.0 2.3 2.6 2.4 2.7 3.1 3.6 4.0 4.5 4.1 4.7 5.2 5.3 6.0 6.8 6.4 7.2 8.0 9.1

10.3 11.6

8.3 9.3

10.5 9.8

11.0 12.5 4.0 4.4 4.8 4.6 5.0 5.5 7.3 7.8 8.3 7.6 8.3 9.2

11.5 12.2 13.1 13.7 14.5 15.5 16.4 17.8 19.4

TypeAmbient temperature oC

Cooling capacity table for SPCA 001-010HSB

Heating capacity table for SPCA 001-010HSB

NOTESBold values show nominal cooling/heating capacities.

Absorbed power and current refers to the compressor.Above figures are valid for water ¢t = 5oC.

Page 9: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 9

90

80

70

60

50

40

30

20

10

00 500 1.000 2.000 3.0001.500 2.500 3.500 WF

PD

kpa

l/h

l/h

80

100120

140

160180

200220

240260280

300320340360

604020

00 500 1,000 2.000 3.0001,500 2.500 3.500 4.000 4.500 5.000 6.0005.500 WF

PD

kpa

001

002003

004

005

006

007

010

Available external water pressure curves4.

SPCA 001-010HSB

NOTESPD: pressure dropWF: water flow rate1. SPCA 001-002HSB2. SPCA 003HSB3. SPCA 004HSB4. SPCA 005HSB5. SPCA 006HSB6. SPCA 007-010HSB

% ETHYLENE GLYCOL BY VOLUME

Freezing point

Output duty

Input pow er

Equivalent Flow rate

Equivalent Pressure drop

ETHYLENE GLYCOL CORRECTION FACTORSUNIT 10oC

kW

kW

L/H

kPa

-4

0,99

0,99

1,02

1,06

20

-9

0,98

0,98

1,04

1,12

30

-15

0,97

0,98

1,08

1,18

40

-23

0,96

0,97

1,13

1,25

Page 10: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

SPCA - 001

SPCA - 002

SPCA - 003

SPCA - 004

SPCA - 005

SPCA - 006

SPCA - 007

SPCA - 010

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

Power

Pressure @1 m

Pressure @10 m

dB(A)

66

58

39

67

59

39

68

60

40

70

62

42

71

64

44

74

66

46

75

67

47

77

69

49

63

49

41

21

49

41

21

51

43

23

52

44

24

54

46

26

54

46

26

54

46

26

54

46

26

125

55

47

27

55

47

27

56

48

28

58

50

30

59

51

31

59

51

31

60

52

32

60

52

32

250

56

48

28

56

48

28

57

49

29

59

51

31

60

52

32

61

53

33

60

52

32

61

53

33

500

58

50

30

58

50

30

59

51

31

61

53

33

61

53

33

69

61

41

69

61

41

70

62

42

1000

62

54

34

62

56

36

64

56

36

65

57

37

67

59

39

68

60

40

68

60

40

69

61

41

2000

59

51

31

61

55

35

62

54

34

63

55

35

64

56

36

67

59

39

70

62

42

73

65

45

4000

54

46

26

58

53

33

58

50

30

58

50

30

65

57

37

63

55

35

65

57

37

70

62

42

8000

49

41

21

48

42

22

49

41

21

50

42

22

53

45

25

50

42

22

50

42

22

57

49

29

Type Octave band center frequency (Hz)

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll10

Operation range5.

45

-5

0

6 15

Outdoor Temperature ( CDB) COOLING HEATINGO

Leaving water temperature( C)o

Leaving water temperature( C)o

4

47

20

-5

25 50

Outdoor Temperature ( CDB)(RH=85%)O

0

Sound data6.

NOTESProtect the water circuit against freezing

- The accompanying operating limits are for general guidance only. It may bepossible for certain units to operate outside the confines of the graph. Pleasecontact Interklima if further clarification is required.

- For operation with leaving water temperature below 6 oC it is required to confirmwith Interklima at the time of order and the addition of glycol into the system.

Page 11: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

932

450

49

1000

10221008

474460

474460

981

450 51 1200

12221208

508 1448522

1002

500 1440

1462

508 1598522 1612

1002

500 1590

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 11

Outlook drawings7.

7.1 SPCA 001-002HSB

7.2 SPCA 003HSB

7.3 SPCA 004HSB

7.4 SPCA 005HSB

Page 12: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

1202

17401754

173260540

50

137

40 2020800

1202

20282042

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll12

7.5 SPCA 006HSB

7.6 SPCA 007-010HSB

Page 13: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

3

15

2

9

8

8

6

6

7

4

3 8 8

1

2

101112

9

6

5

6 7

4

3

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 13

8.1 SPCA 001-005HSB

8.2 SPCA 006-010HSB

Refrigerant circuit diagrams8.

NOTES1. Scroll compressor2. Plate heat exchanger3. Air heat exchanger4. Suction accumulator5. 4-way reversing valve6. Check valve7. Filter dryer8. Capillary9. Liquid receiver10. Thermal expansion valve11. Solenoid valve12. Liquid glass

Page 14: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

VC

VC

C1

FM1

F

CCf1

PM

CC

CM

PE

L2L1

L3

N

W

S

4V

F 2A

12V

AL

220V

AEMIFILTER

P

C

TR

12V

ON

Off

ST4ID4

GNDTK112DC12AC

12AC ALL GNDID5

S P P

F L

ST3ID3 ID2

ST2

H

ID1ST1

ALS2S3 S1

ALARM OUTPUTSM1

N

CC

CH

grdgrd grd

V

4

ENERGY 210

CC

CP

CP

PM

C

FM2

C2

Cf2

C1

FM1

F

CCf1

VC

VC

CC

CM

PE

L2L1

L3

N

W

S

4V

F 2A

12V

AL

220V

AEMIFILTER

P

C

TR

12V

ON

Off

ST4ID4

GNDTK112DC12AC

12AC ALL GNDID5

S P P

F L

ST3ID3 ID2

ST2

H

ID1ST1

ALS2S3 S1

ALARM OUTPUTSM1

N

CC

CH

grdgrd grd

V

4

ENERGY 210

CC

PMCM

CC

PE

LN

C

W

S

4VC1

FM1

F

CCf1

F 2A

12V

AL

220V

AEMIFILTER

P

C

TR

12V

ON

Off

ST4ID4

GNDTK112DC12AC

12AC ALL GNDID5

S P P

F L

ST3ID3 ID2

ST2

H

ID1ST1

ALS2S3 S1

ALARM OUTPUTSM1

N

CC

CH

grdgrd grd

V

4

ENERGY 210

CC

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll14

Wiring diagrams9.

9.1 SPCA 001-002HSB-1

9.2 SPCA 002-003HSB

9.3 SPCA 004-005HSB

Page 15: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

CP

CP

PMSV

CC

T

C

C

FM2

C2 C1

FM1

F

CCf1Cf2

VC

VC

CC

CM

PE

L2L1

L3

N

W

S

4V

F 2A

12V

AL

220V

AEMIFILTER

P

C

TR

12V

ON

Off

ST4ID4

GNDTK112DC12AC

12AC ALL GNDID5

S P P

F L

ST3ID3 ID2

ST2

H

ID1ST1

ALS2S3 S1

ALARM OUTPUTSM1

N

CC

CH

grdgrd grd

V

4

ENERGY 210

CC

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 15

CP

CP

PMC2

SV

CC

CF 22 3334

F124

FAN SPEEDCONTROLLER

C

FM2

Cf2

C1

FM1

F

CCf1

T

C

VC

VC

CC

CM

PE

L2L1

L3

N

W

S

4V

F 2A

12V

AL

220V

AEMIFILTER

P

C

TR

12V

ON

Off

ST4ID4

GNDTK112DC12AC

12AC ALL GNDID5

S P P

F L

ST3ID3 ID2

ST2

H

ID1ST1

ALS2S3 S1

ALARM OUTPUTSM1

N

CC

CH

grdgrd grd

V

4

ENERGY 210

CC

9.4 SPCA 006HSB

SM1 GENERAL CIRCUIT BREAKER CC COMPRESSOR CONTACTOR CH COMPRESSOR CRANKCASE HEATER TR TRANSFORMER 220/2x12VAC HP HIGH PRESSURE PRESSOSTAT LP LOW PRESSURE PRESSOSTAT F CONTROL CIRCUIT BREAKER (2A) C1,2 COND, FANS 1, 2 CAPACITORS FS WATER DIFFERENTIAL PRESSOSTAT TC COMPRESSOR THERMAL PROTECTION 4V 4-WAY VALVE

S1 ENTERING WATER SENSOR S2 LEAVING WATER SENSOR S3 CONDENSER COIL TEMPERATURE SENSOR A COMMAND 220VAC FOR ELECTRICAL HEATERS (OPTIONAL) CP PUMP CONTACTOR PM PUMP CM COMPRESSOR VC VOLTAGE SURVEYOR (OPTIONAL) SV LIQUID SOLENOID VALVE

ALARM

LEGENDFIELD CONNECTIONS

ON -OFF REMOTE SWITCH (DRY CONTACT)AL-AL ALARM 12 V ACS-W REMOTE SUMMER-WINTER SWITCH (DRY CONTACT)

E00:E01:E02:E03:

E05:E06:E07:E41:

REMOTE ON/OFF IN POSITION OFFHIGH PRESSURELOW PRESSURECOMPRESSOR THERMAL PROTECTION*(*ONLY FOR SPCA 006-010∏SB)ANTIFREEZEPROBE ST2 FAULTPROBE ST3 FAULTWATER DIFFERENTIAL PRESSOSTAT

OFFON WS AL AL

9.5 SPCA 007-010HSB

Page 16: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

The SPCA-HSB unit should be installed in a location that meets thefollowing requirements:1. The foundation is strong enough to support the weight of the unit,

and the floor is flat to prevent vibration and noise generation.2. The space around the unit is adequate for servicing and the

minimum space air inlet and air outlet is available. If several unitsare being installed side by side in parallel, the minimum servicespace between them must be taken into account

3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in

case it drips out the unit.5. Make sure that the air inlet and outlet of the unit are not

positioned towards the main wind direction.Frontal wind willdisturb the operation of the unit.If necessary, use a windscreento block the wind.

6. In heavy snowfall areas, select an installation site where snowwill not affect operation of the unit.

7. Make sure that the unit mounting base can be fixed directly onconcrete.

8. In order to avoid the transmission of vibration from the operatingunit to its carrying structure, the use of antivibration material toinstall under the supports of the unit is recommended. It issuggested to install a rubber pad between the points of supportand the base of the unit, or spring antivibration mounts undereach point of support of the unit.

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll16

Installation10.

10.1 Selection of location - service space

10.2 Centre of gravity

400mm

500mm

500mm

500mm

800mm

175

420

390

SPCA 001-002HSB

420

175 490

SPCA 003HSB

570200

420

SPCA 004HSB

420

200 620

SPCA 005HSB

(1500mm for 006-010 models)

Page 17: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 17

ñ All units are equipped with a complete hydraulic kit as shownthe figure below

ñ All field conections must be carried out by a licensed technicianand must comply with the applicable local and national codes

ñ Evaporator water connections should be made in accordancewith the unit outlook respecting the water inlet – and outlets

ñ Connect a fresh water line to the water make up connection.The units are equipped with automatic make up valve tofacilitate water make up.

ñ It is advisable to connect flexible water inlet and outlet tubesto avoid vibration transmission

ñ The unit is operating in closed circuit. Avoid frequentunessasary water evacuation.

ñ It is essential to install a thermometer in the water inlet/ outlet

pipe to check temperatures.ñ Provide heat insulation with suitable vapour barrier around the

chilled water piping to prevent condensation and capacity loss.ñ Provide drain connections at all low points of the system to

permit complete drainage for maintenance and/ or shutdownñ Air vents should be provided at all high points in the system

located where they are easily accessible for servicing. Thewater inlet pipe is specially designed to obtain a complete airpurge of the evaporator.

ñ To avoid frequent on / off operation of the compressor, aminimum water volume is required in the system (table 10.4)

ñ To assure proper operation of the unit, the water qualitythrough the evaporator must be within the specified limits(table10.4).

10.3 Recomendations concerning the hydraulic circuit

650250

590

SPCA 006HSB

590

350 750

SPCA 007-010HSB

NOTES1. Pump2. Plate heat exchanger3. Automatic make up water

valve with manometer4. Buffer tank (water accumulation)5. Expansion tank6. Airvent7. Pressure relief valve8. Differential water pressure switch9. Water filter

Page 18: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

3,5-4 bar

17-19 bar

4-5 bar

21-23 bar

5,5-6 bar

24-26 bar

low pressure

high pressure

Minimum(outdoor temp. 15ÔCDB) (leaving water temp 6ÔC)

Nominal(outdoor temp. 35ÔCDB)(leaving water temp, 7ÔC)

Maximum(outdoor temp. 38ÔCDB)

(leaving water temp, 25ÔC)

Cooling mode(region)

2.5-3 bar

15-18 bar

3-3.5 bar

21-23 bar

3,5-5 bar

25-26 bar

low pressure

high pressure

Minimum(outdoor temp. -5ÔCDB)

(leaving water temp 25ÔC)

Nominal(outdoor temp. 7ÔCDB)

(leaving water temp, 45ÔC)

Maximum(outdoor temp. 21ÔCDB)

(leaving water temp, 50ÔC)

Heating mode(region)

To ensure proper operation of the unit, a minimum water volumeis required in the system and the water flow must be within theoperation range as specified in the table.

It is important to check the high and low pressure of therefrigerant circuit to ensure the proper operation of the unitand to guarantee that the rated output will be obtained.

Attention:The pressures measured will vary between a maximum andminimum value, depending on the water and ambienttemperatures at the moment of measurement.

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll18

10.4 Watercharge, flow and quality

29

35

35

41

61

73

93

112

159

SPCA-001-1HSB

SPCA-002-1HSB

SPCA-002HSB

SPCA-003HSB

SPCA-004HSB

SPCA-005HSB

SPCA-006HSB

SPCA-007HSB

SPCA-010HSB

Minimumwater

volume (l)

948

1127

1127

1324

1993

2386

3023

3660

5196

Minimumwater flow

(l/h)

998

1187

1187

1393

2098

2511

3182

3853

5470

Nominalwater flow

(l/h)

1097

1305

1305

1533

2308

2762

3500

4238

6017

Maximumwater flow

(l/h)

Items to be controlled:

PH AT 25ÔC

∂lectrical conduct (mS/m) at 25ÔC

Chloride ion (mg CI-/I)

Sulfate ion (mg SO 2/4/I

M-alkalinity (ph 4.8) (mg SO3/I)

Total hardness (mg CaCO3/I )

Calcium hardness (mg CaCO3/I)

Silica ion (mg SiO2/I

Items to be referred to:

Iron (mg Fe/I)

Copper (mg Cu/I)

Sulfide ion (mg S2-/I)

Amonium ion (mg NH+4/I

Remaining chloride (mg CI/I)

Free carbide (mg SO2/I)

Stability index

6.8 - 8.0

below 30

below 50

below 50

below 50

below 70

below 50

below 30

below 1.0

below 1.0

Not detectable

below 0.3

below 0.25

below 0.4

-

6.8 - 8.0

below 30

below 200

below 50

below 50

below 70

below 50

below 30

below 0.3

below 0.1

Not detectable

below 0.1

below 0.3

below 4.0

-

7.0 - 8.0

below 30

below 30

below 30

below 50

below 70

below 50

below 30

below 1.0

below 1.0

Not detectable

below 0.1

below 0.1

below 0.4

-

7.0 - 8.0

below 30

below 30

below 30

below 50

below 70

below 50

below 30

below 0.3

below 1.0

Not detectable

below 0.1

below 0.3

below 4.0

-

ItemsCirculatingwater 20C Supply water Circulating

water 20C-60C Supply water

Tendencyif out of criteria

Evaporator water Heated water

corrosion + scale

corrosion + scale

corrosion

corrosion

scale

scale

scale

scale

corrosion + scale

corrosion

corrosion

corrosion

corrosion

corrosion

corrosion + scale

Be sure the water quality is in accordance with the specificationsbelow

NOTESThe above tables are purelyindicative and non-binding

10.5 Operating pressure of the refrigerant circuit.

Page 19: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

User interface SPCA 001-010HSBThe interface on the front panel can be used to carry out all theoperations connected to the use of the instrument, and inparticular to:

Set operating mode Check the state of resourcesRespond to alarm situations

10.6.1 KeysSelects operating mode:

If the heating mode is enabled, each time thekey is pressed the following sequence occurs:Stand-by cooling heating stand by

If cooling mode is enabled:heating Stand-by cooling heating stand byIn menu mode, this key acts as a SCROLL UPor UP key (increasing value).

Resets alarms, and turns the instrument onand off. Press once to reset all manually resetalarms not currently active.

Hold down the key for 2 seconds to turn theinstrument from on to off or vice versa. When it isoff, only the decimal point remains on the display.In menu mode this key acts as a SCROLL DOWNor DOWN key (decreasing value).

Pressing the “mode” and “on-off” keys at thesame time.

If you press both keys at the same time andthen release within 2 seconds, you will moveone level deeper in the display menu. If you press both keys for more than 2 secondsyou will move one level up.If you are currently viewing the lowest level inthe menu and you press both keys and releasewithin 2 seconds, you will go up one level.

10.6.2.2 LedLed 1 compressor 1(step 1)ON if compressor 1 is activeOFF if compressor 1 is offRapid BLINK if safety timing is in progressSlow BLINK if compressor is currently set to defrost (heatpump version)Power step 2 led

Not used

Defrost led (heat pump version)ON if defrosting is in progressOFF if defrosting is disabled or has been completedBLINK if timing is in progress (defrost interval)

Electrical heater/boiler ledON if the internal anti-freeze electrical heater or boiler is onOFF if the internal anti-freeze electrical heater or boiler is off

Heating led (heat pump version)ON if the device is in heating mode

Cooling ledON if the controller is in cooling mode

If neither the HEATING led nor the COOLING led is on, thecontroller is in STAND-BY mode

10.6.2 Displays10.6.2.1 DisplayNormal display shows:

ñ Regulation temperature in tenths of degreescelsius with a decimal point, or in degreesfahrenheit without a decimal point.

ñ The alarm code, if at least one alarm is active. Ifmultiple alarms are active, the one with greaterpriority will be displayed, according to the Tableof Alarms.

ñ If temperature control is not analogue anddepends on the status of a digital input (ST1 orST2 configured as digital inputs), the “On” or“Off” label will be displayed, depending onwhether temperature control is active or not.

ñ When in menu mode, the display depends on thecurrent position; labels and codes are used tohelp the user identify the current function.

ñ Decimal point: when displaying hours of operation,indicates that the value must be multiplied x 100.

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 19

10.6 Digital controler

Front panel of the instrument

1 2

Page 20: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll20

24

Blue

Conn. A

Remote keyboard

Connection

Back side

Conn. B

Red

Blac

k

26

25

The remote keyboard on the display is an exact copy of theinformation displayed on the instrument, with the same leds;

Connection with the controller is illustrated below:

It performs exactly the same functions as those described in thedisplay section.The only difference is in use of the UP and DOWNkeys (to increase and decrease value), which are separate fromthe MODE and ON/OFF keys.

10.7 Remote keyboard

Page 21: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll 21

The supply, transport to jobsite, installation, commissioning andstart up of an air cooled water heat pump with the followingtechnical characteristics.The unit shall be factory assembled, charged with R407crefrigerant and factory tested.The capacity of the unit shall be no less than:

Cooling capacity: kWIn the following conditionsAmbient air temperature (DB) ÆCEntering water temperature ÆCLeaving water temperature ÆC

Heating capacity: kWIn the following conditionsAmbient air temperature (DB) ÆCAmbient relative humidity %Entering water temperature ÆCLeaving water temperature ÆC

The unit shall operate unhindered within 6 to 15ÆC/25oC to 50oC(cool/heat) water outlet temperature, 3.5 to 7ÆC watertemperature difference and 5 up to 45ÆC ambient air temperature.The structural requirements shall be the following:

UNIT HOUSINGThe unit housing shall be fabricated from heavy gauge galvanizedsteel sheets, formed to ensure maximum rigidity that shall guaranteeand preserve the unit operation during the years. All metal parts afterfabrication shall be degreased phosphatized, and electrostaticallypowder coated with epoxy- polyester RAL 9002 coating of athickness of 60-70 m. The corrosion resistance treatment mustsuccessfully withstand a salt spray test of 500 hours, according toASTM B- 117. All components shall be assembled exclusivelytogether using bolts, without welding. The unit shall have removableaccess panels, designed in such a manner as to permit easy accessto internal compartments only by authorized personnel.

COMPRESSORShall be of the hermetic scroll type, with low noise and vibrationlevels, specially optimized for use with R407c refrigerant. It shallbe equipped with a crank case electrical heater, to separaterefrigerant and oil when the unit is not operating. It shall alsoinclude internal protection against overloading or electrical spikes.The compressor shall be mounted on special ant vibration rubbermounts to absorb and eliminate any vibration that can begenerated from the unit base.

HYDRAULIC KITThe unit shall be equipped with a complete hydraulic kit,comprising of a circulating pump, buffer and expansion tank,automatic fill / make up water valve with manometer, safety valve,air vent, water filter and differential water pressure switch.

AIR HEAT EXCHANGERThe air hear exchanger shall be manufactured from seamlesscopper tubes having an outside diameter of 9.52mm (3/8'') of highquality according to ASTM B 280. The tubes shall be internallygrooved to achieve optimized heat transfer between refrigerant andtube. The fins shall be manufactured from aluminium. The fins shallbe continuous across the heat exchanger and the fin surface shallbe waffle formed and louvered so as to increase the fin rigidity andheat transfer. The combination of internally grooved copper tubingand louvered fins must result in a heat transfer performance 30%superior to that of a conventional coil.The assembly of the finned pack shall be achieved by mechanicalexpansion in such a way as to form a perfect mechanical bondwith the fins. For this purpose, the fin holes shall have a peripheralextrusion (collar).

WATER HEAT EXCHANGERThe water heat exchanger shall be of the plate heat exchangertype, selected from world-class manufacturers and made ofstainless steel plates (AISI 3161.4401) specially formed toachieve optimized heat transfer. The plates shall be assembled bymeans of an automatic brazing process, under vaccum.

AIR HEAT EXCHANGER FANS The unit shall be equipped with axial type fans, single phase, and6 poles, internally protected against potential overheating,noiseless and suitable for outdoor installation. The design of theblades and inlet cones shall be aerodynamic, and the fan motorassembly shall be perfectly statically and dynamically balancedallowing a completely vibration free operation. The fan motorassembly shall have a protective grid against accidental contactwith moving parts according to ISO. The fan motor shall be of theexternal rotor type with permanently lubricated bearings that donot require servicing. The motor shall be aerodynamically shapedso as not to interfere with the airflow. The unit shall be equippedwith a continuous linear fan speed regulation control according tocoil temperature.

Guide specifications11.

SPCA 001-010HSB

Page 22: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

CONTROL SYSTEM WITH MICROPROCESSOR CONTROLLER The control system shall possess a sophisticated controller thatshall constantly monitor all machine parameters and particularlymanage among others:ñ Automatic compressor control function through return water

temperature.ñ Continuous fan speed control based on coil heat exchanger

temperature.ñ Defrost control.ñ Hydraulic circuit pump control.ñ Compressor start up time delay function.ñ Compressor running time records.ñ Over 150 programmable parameters. ñ Fan motors overload protection.ñ Auto diagnostic stop function due to low water circulation,

high / low operating pressures and compressor thermaloverload.

ñ Auto diagnostic function and digital display of approximately30 possible error codes including thermistor faults.

ñ Digital displays of inlet/ outlet as well as condensingtemperatures.

ñ Remote cool/ heat and on / off selectionñ Various other optional control capabilities (listed in options)

REFRIGERANT CIRCUITThe unit shall have a single refrigerant circuit with onecompressor. The circuit shall consist of a filter dryer, expansiondevice, solenoid valve, check valve, liquid receiver, suctionaccumulator, 4way valve and a high and low pressure switch withmanual reset.

NOTEThe consultant may if required add the below mentioned optionalaccessories / functions.ñ Remote keyboard.ñ Dynamic set point program via a 4 20 mA proportional

signal.ñ BMS module interface kit for modbus connection.ñ Parallel chiller operation with more than 2 units with optional

controller. ñ Microprocessor parameters reprogramming card.ñ Condenser fins made of prepainted aluminum or copper, and

blygold treatment for additional corrosion protection.ñ Plate exchanger-freezing protection for low chilled water

temperature controlled by microprocessor.ñ Glycol for low chilled water temperatures.ñ Pressure relief valve on compressor dischargeñ High / low pressure manometers.ñ Phase sequence phase failure - reverse phase and voltage

monitoring device.

Interklima Hydronic systemsSPCA 001-010HSB ñ R407c/Scroll22

Page 23: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to
Page 24: SPCA HSB GB - calor · The SPCA-HSB series air-cooled water heat pump consists of 9 models covering cooling capacities from 5,8 up to 31,8kW and heating capacities from 6,9kW up to

Products are manufactured in ISO 9001:2000certified factories. ISO 9001:2000 pertains to quality

assurance regarding design, development,manufacturing and installation of products

as well as to services related to the product.

INTERKLIMA PRODUCTS ARE DISTRIBUTED BY:

EG

B-B

-3-2

-05/

06

Specifications subject to change without notice

Interklima units comply with the European regulations thatguarantee the safety of the product

Engineering Data 2006