solar air heat and residential ventilation makeup air...energy recovery ventilators (hrv) are...
TRANSCRIPT
Solar Air Heat and Residential Ventilation Makeup Air
Principal Investigator: Adam Kutrich,
Supporting Investigators: Roger Garton, Scott Randall and Jason Edens
May 2013
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 2
Table of Contents Summary ....................................................................................................................................................... 4
Background ................................................................................................................................................... 5
Methods ........................................................................................................................................................ 9
Products ................................................................................................................................................ 9
House Specifications ............................................................................................................................. 9
ASHRAE 62.2 Ventilation Requirements [4] .......................................................................................... 9
Ventilation Heating and Cooling Load .................................................................................................. 9
HRV Modeling ....................................................................................................................................... 9
TRNSED ................................................................................................................................................ 10
RETScreen ........................................................................................................................................... 10
Model Comparison .............................................................................................................................. 10
Results and Discussion ................................................................................................................................ 11
Ventilation Heating Loads ................................................................................................................... 11
System Comparison ............................................................................................................................ 11
Energy Comparison ............................................................................................................................. 12
Return on Investment Comparison ..................................................................................................... 13
Combination Systems ......................................................................................................................... 16
Conclusion ................................................................................................................................................... 19
Appendix A – Energy Calculation Details .................................................................................................... 20
House Specifications ........................................................................................................................... 20
ASHRAE 62.2 Ventilation Requirements [4] ........................................................................................ 20
Ventilation Heating Load .................................................................................................................... 20
HRV Energy Savings ............................................................................................................................. 20
Standard Recirculation Loop Solar Air Heat System ........................................................................... 21
Glazed SAH for Ventilation Makeup Air .............................................................................................. 22
Effect of Increasing the Solar Collector Area ...................................................................................... 25
Energy Savings Percentage for Glazed SAH ........................................................................................ 27
Solar Transpired Air ............................................................................................................................. 28
Results Summary ................................................................................................................................. 31
Appendix B – Return on Investment Calculation Details ............................................................................ 32
References .................................................................................................................................................. 33
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 3
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 4
Summary As homes become increasingly efficient through improved building techniques and energy efficiency
measures, ventilation make-up air appliances are required to bring in fresh air to ensure indoor air
quality and combustion appliance safety and efficiency. Bringing outside air up to room temperature can
be a very energy intensive process. Normally, this heating load is reduced by using a heat recovery
ventilator (HRV) or energy recovery ventilator (ERV), which transfers thermal energy from the exhausted
air to the incoming air. Alternatively, solar air heat (SAH) collectors could be used to heat the ventilation
air.
Energy calculations, return on investment calculations, and computer simulations were used to evaluate
the performance of solar collectors used to provide heated ventilation air and to compare that to the
performance of HRV systems. The calculations detailed in this report show that using SAH collectors to
replace HRV units is not an ideal application for the solar technology. The main problem is that the
home requires a constant supply of fresh air while solar collectors only work when the sun is shining on
them. There is also the concern of matching the ideal flow rate through the SAH collectors required for
optimal heat transfer with the required volume of air exchange in a building. In addition, HRV units can
often contribute additional energy savings in the form of cooling during the summer months that SAH
technology cannot produce. All of these factors result in an HRV providing more than three times the
energy savings of a SAH system.
While SAH systems may not be an apples-to-apples replacement for HRV units, they still are effective at
heating ventilation make-up air. Since SAH technology operates at higher efficiency when its incoming
air is cooler, SAH systems used for ventilation make-up air applications produce more energy than
comparable SAH systems used in conventional recirculation heating applications. For this reason, SAH
technology could be effectively used in tandem with HRV technology to provide ventilation heating
needs.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 5
Background Mechanical ventilation is needed to provide homes with both high indoor air quality and energy
efficiency. Adequate ventilation keeps people comfortable and healthy, and prevents moisture buildup
and mold growth [1]. For a long time, homes relied mostly on natural ventilation which is not always an
efficient method for providing fresh air. There are a number of reasons why this has become an
important issue in recent decades. People now spend much more of their time indoors, meaning that
indoor air is almost all that they breathe. Windows are seldom open in order to save energy, so less
fresh air is introduced to the home [2]. At the same time, people are now exposed to a greater variety
of chemicals in the indoor environment, and more people have become sensitive to allergens in the
environment, so there is an even greater need for fresh air [3]. New energy-efficient buildings with very
tight envelopes can make these problems even worse if they are not ventilated.
There is some concern that tight house envelopes will trap moisture and contaminants, but they are
actually more healthy in practice. A study conducted by Health Canada of 400 houses in Ontario found
that the houses with the most leakage also had the worst air quality. Without dedicated ventilation
equipment, houses rely on wind pressure, the convective stack effect, and heating and AC equipment to
distribute fresh air. This means the amount of fresh air varies with time depending on weather
conditions. The pathways that fresh air will take will be unpredictable, so there is no assurance that
critical areas, especially bedrooms, will receive adequate ventilation. This situation may be made even
worse since outside air could be filtered through contaminated spaces such as a moldy wall cavity
before reaching the occupants. Natural infiltration can also damage building envelopes by creating
moisture problems in the attic during the winter, and allowing condensation inside the walls in the
summer if the house is air conditioned [2]. For all of these reasons, active ventilation is sometimes
advisable even if a house is old and leaky.
Building a home with a tight envelope and mechanical ventilation provides a more comfortable and
healthy environment in addition to improved energy efficiency. Fresh air is provided consistently and is
distributed evenly through the entire house. Air flows wherever the resistance is lowest, so providing
vents for intake and exhaust means more air is directed inside where it is needed and less air is forced
through cracks in the building where it can cause problems.
For these reasons ventilation requirements have become established in building codes. ASHRAE 62.2 is
the standard that sets the minimum ventilation requirements for residences [4]. Although this standard
includes additional details, it is very simple to calculate this ventilation rate for most situations. There
are two components: whole house continuous ventilation, and spot ventilation for bathrooms and
kitchens.
Whole house ventilation (cubic feet per minute, cfm) = Floor area (sq. ft.)/100 + 7.5*(# of
bedrooms + 1)
Each bathroom requires 50cfm intermittent ventilation, or 20cfm continuous ventilation
Each kitchen requires 100cfm intermittent ventilation, or 25cfm continuous ventilation
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 6
When homes are insulated well and sealed tightly, heating and cooling the ventilation air becomes a
large portion of the energy load. Heat recovery ventilators (HRVs) are used to save energy while keeping
the home comfortable. They work by passing the incoming and outgoing streams of air next to each
other so that the exhaust air heats up the intake air (or the reverse if it is warm outside). This way the
HRV recycles up to 80% of the thermal energy that would otherwise leave the building.
Figure 1: HRV Operation [5]
Energy Recovery Ventilators (HRV) are another appliance that is often used for bringing ventilation air
into a building. The main difference between an HRV and an ERV is that ERVs allow moisture to move
from one air stream to another. Because ERVs take advantage of the latent heat in moisture, they are
often more effective at recapturing heat from the exhausted air. ERVs are recommended for warmer
climates where there is more humidity and cooling loads are larger, but are not recommended for
northern climates that experience colder temperatures.
Another strategy to reduce the energy cost of ventilation is to use solar air heat (SAH) panels to heat the
air before it goes into the building. This is done for commercial buildings using solar transpired air
technology. Transpired air is a SAH technology designed specifically to heat ventilation air. It consists of
an unglazed flat plate filled with small holes. Incoming air absorbs solar energy as it is drawn through the
holes in the collector surface, and then it flows through a space behind the collector towards the
ventilation inlet. Because of its simplicity, transpired air is a very cost-effective source of heat for
commercial buildings that require a lot of makeup air. This technology provides the most benefit for
buildings with large ventilation requirements, but it could be effective for residential systems as well.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 7
Figure 2: Solar transpired air [6]
Glazed flat plate SAH collectors can also be used to heat ventilation air. In a glazed flat plate collector,
solar energy passes through a glazing and is collected by a specially coated absorber plate. When the
system operates, air is driven into a cavity behind the absorber where it collects thermal energy before
entering the house. These systems, shown in Figure 3, normally work on a closed loop, heating up air
from inside the house and recirculating it back inside. To provide heated ventilation air, the inlet could
be placed outside instead as shown in Figure 4. Glazed collectors have not been tested for this purpose,
but numerical models can estimate the energy production of this type of system in order to find out how
well this type of SAH technology will perform in ventilation make-up air applications.
Figure 3: Glazed solar air heat system in a recirculation configuration [7]
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 8
Figure 4: Glazed solar air heat in a ventilation makeup air configuration
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 9
Methods A complete list of calculations and detailed results can be found in Appendix A – Calculations.
Products
The glazed solar air heat collector modeled for this study is the Solar Powered Furnace (SPF) made by
the Rural Renewable Energy Alliance (RREAL). The solar transpired air product modeled for this study is
MatrixAir, made by Matrix Energy. Performance ratings for the SAH technologies used in this report are
provided by the Solar Rating & Certification Corporation (SRCC) and are found at www.solar-rating.org.
This study also looked at two different HRV units. The VHR 1405R, manufactured by Fantech, and the ES-
150, manufactured by Nu-Air, were selected for analysis in this study because of their size, availability of
data and price point.
House Specifications
In order to accurately compare SAH and HRV technologies, the following building was selected and used
for all modeling in this study.
Location: St. Cloud, MN and Boulder, CO.
2,500 sq. ft.
3 bedrooms
ASHRAE 62.2 Ventilation Requirements [4]
Determination of ventilation requirements for this building are based on ASHRAE 62.2 requirements.
Whole house ventilation for 2500ft2, 3 bedrooms: 2500/100 + 7.5*(3 + 1) = 55cfm
Bathroom continuous ventilation: 20cfm
Kitchen continuous ventilation: 25cfm
Total continuous ventilation: 55cfm + 20cfm + 25cfm = 100cfm
Ventilation Heating and Cooling Load
The ventilation makeup air will need to be heated or cooled most of the time in order to maintain a
comfortable environment inside the house. Historical degree day data provides a good estimate of what
these loads will be during a typical year.
HRV Modeling
HRV technology lowers the cost of introducing ventilation air by making use of the energy available in
exhaust air. Unlike SAH technology, which captures energy from the sun, HRV technology simply
recovers existing energy that would be otherwise lost in exhaust air. First, the ventilation heat load
without an HRV is calculated based on heating degree day data. In order to calculate the energy saved
by HRV units, the total ventilation load is multiplied by the HRV effectiveness, and the electric energy
used is subtracted from the total. Manufacturers of HRVs do not provide data for the cooling
effectiveness, but this is known to be lower due to the heating effect of the motors, so it is estimated at
50%. HRV modeling is based on manufacturers specifications, which are often slightly higher than actual
field performance. Energy lost to defrost cycling was not factored into these calculations, but will have a
negative effect on system performance.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 10
TRNSED
Energy production estimates for glazed SAH systems are obtained with TRNSED (Transient Simulation
Edition). SPF TRNSED is a program specially developed by Thermal Energy System Specialists in Madison,
Wisconsin and RREAL with financial support from the Clean Energy Resource Team of Minnesota
(certs.org.). TRNSED is designed to model SAH systems using the TRNSYS platform. TRNSYS is a software
environment used to model dynamic systems. In this environment, models are built by defining
relationships between multiple components, allowing for the behavior of very complex systems to be
determined. For this study, a TRNSED model of a glazed solar air heat collector was used in order to
estimate the amount of heat that will be produced over the course of a typical year. The software allows
the user to select the location for weather data, enter parameters for the house and furnace, and enter
specifications for the solar system. The program then runs an energy simulation for the entire year using
a five minute time step interval. It displays a graph of the hourly results and outputs monthly energy
production as a spreadsheet. The model has been verified by collecting data from actual recirculation
type installations, and the data has shown that the TRNSED software yields a conservative estimate of
system performance.
RETScreen
Energy production estimates for solar transpired air were obtained with RETScreen, an Excel-based
application produced by Natural Resources Canada and NASA. RETScreen is used to estimate the energy
production and energy savings from a variety of renewable energy and energy efficiency strategies. It
uses monthly average calculations, taking into account local weather data, building design and use,
renewable energy system specifications, energy efficiency strategies, etc. It also performs financial,
greenhouse gas reduction and other relevant calculations.
Model Comparison
Since there was not one uniform method or software program capable of accurately modeling all three
of these types of systems, three different methods or programs were used. Energy modeling is best used
to compare the relative benefits of different system designs. While the results are realistic compared to
the real world, they are not absolute. Since different models incorporate different assumptions and
input data, looking at the amount of energy saved would not give a fair comparison of these systems. In
order to make accurate comparisons, the percentage of energy savings for each system is calculated.
This gives a clear picture of the relative strength of each technology.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 11
Results and Discussion
Ventilation Heating Loads
System Comparison
The objective of this project was to compare the effectiveness of using solar technologies to HRVs for
the purpose of heating ventilation make-up air. Heat recovery ventilators and solar air heaters are both
excellent technologies when used as intended. The heat recovery ventilator is an appliance intended to
minimize the loss of energy from a building, whereas the solar air heater is used to collect and add solar
energy to a building.
Since HRV technology is able to operate at any time of day under any weather condition and is capable
of saving energy used for cooling in the summer, it outperforms SAH technology when used to heat or
cool ventilation make up air. SAH technology is limited in its energy production to daylight hours and is
only capable of producing energy used for heating needs.
Even though the HRV is a financially superior choice when heating ventilation make-up air, it is only able
to minimize losses and is not capable of adding energy to a home. Solar air heaters are a proven
technology that collect the sun’s energy and economically add that energy to a home. The two
technologies complement each other very well.
Location
Heating
Degree Days
(°F-day)
Ventilation
Rate (cfm)
Ventilation
Heating Load
(mmBtu)
St. Cloud, MN 8,076 100 20.93
Boulder, CO 6,667 100 17.28
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 12
Energy Comparison
Figure 5: Energy Savings Results
HRVs are the most effective at saving energy since they have the same effect day and night regardless of
the weather. These results show that HRVs can save between 2.4 and 3.8 times the amount of energy of
a similarly priced SAH system, depending on the climate and the model of HRV. Increasing the size of the
solar collectors reduces this performance gap, but increases the cost of the system. The HRV
performance will be reduced somewhat by the need to run the defrost cycle, but this technology clearly
has the greatest impact on household energy usage.
Glazed SAH collectors deliver more energy savings when used to deliver ventilation air than they do in a
closed-loop system. This is because the collectors lose less heat to the outside when the inlet
temperature is close to the ambient temperature. If the house requires active ventilation, glazed SAH
collectors will be very effective at heating that air during the day.
In a standard SAH system, the size of the array is determined by the characteristics of the house, and the
flow rate is tailored to maximize the efficiency of the system. In this case, increasing the size of the array
results in diminishing returns since the flow rate is fixed.
The performance of the unglazed transpired air system is very close to the glazed system of the same
size, which is a surprising result. This is partly because the transpired air system uses a lower power fan
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 13
since the static pressure across the collector is very low. Glazed SAH has a greater advantage in Boulder
than in St. Cloud since the climate is windier.
Return on Investment Comparison
A key indicator of a project’s value can be found by looking at the return on investment (ROI). When
looking at any infrastructure designed to save energy, it is important to look at the initial cost and the
value of the energy savings over the lifecycle of the equipment. The motivation for installing new energy
saving equipment often is to reduce utility bill costs. Return on investment calculations are intended to
demonstrate which piece of infrastructure will be a better investment over the lifecycle of the
equipment.
There are many important figures to consider when performing a return on investment calculation. For
instance, fuel costs today may not equal fuel costs in the future. Every return on investment calculation
has inherent assumptions associated with it. The details used in the calculations performed for this
report are listed in Appendix B – Return on Investment Calculation Details.
This ROI calculation does not take into account any operation and maintenance costs during the lifetime
of the system. In addition, ROI calculations in general do not take into account the differences in quality
and longevity of the equipment and other factors such as product warranty and serviceability. It is
important to also consider these other factors outside the ROI calculation when determining the ideal
solution for a particular application.
Return on investment calculations are done for both HRV units, a 33 ft2 MatrixAir transpired plate
collector from Matrix Energy and a 32 ft2 Solar Powered Furnace from RREAL. All ROI numbers shown
here are based on the energy production calculations from the above models. ROI calculations are
shown for Saint Cloud, MN only.
Years to Simple Payback: Natural Gas Propane Electricity Fuel Oil Fantech VHR 1405R 8 3 2 3 Nu-Air ES-150 8 3 3 3 RREAL SPF32 16 8 6 7 MatrixAir Transpired Plate (33 ft2) 15 7 6 6
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 14
Figure 6: Return on Investment Against Natural Gas
Figure 7: Return on Investment Against Propane
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 15
Figure 8: Return on Investment Against Electricity
Figure 9: Return on Investment Against Fuel Oil
-$2,000.00$0.00
$2,000.00$4,000.00$6,000.00$8,000.00
$10,000.00$12,000.00$14,000.00$16,000.00$18,000.00$20,000.00$22,000.00$24,000.00$26,000.00$28,000.00$30,000.00$32,000.00
0 5 10 15 20 25
Cu
mm
ula
tive
Cas
h F
low
Year After System Installation
Return on Investment Against Electric
Fantech
NuAir
SPF
Matrix
-$5,000.00
$0.00
$5,000.00
$10,000.00
$15,000.00
$20,000.00
$25,000.00
$30,000.00
$35,000.00
$40,000.00
$45,000.00
$50,000.00
$55,000.00
$60,000.00
$65,000.00
0 5 10 15 20 25
Cu
mm
ula
tive
Cas
h F
low
Year After System Installation
Return on Investment Against Fuel Oil
Fantech
NuAir
SPF
Matrix
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 16
Combination Systems
SAH collectors produce less savings than HRVs, but they deliver additional heat to the house during the
day. Combining the two technologies could take advantage of the strengths of both. A combination
system would allow the HRV unit to conserve energy from the exhaust air while also allowing the SAH
collector(s) to capture the suns energy and use it to help meet ventilation makeup air needs.
There are two ways of designing a tandem system, the first of which is shown in Figure 10. This system
uses the SAH technology to preheat the incoming air first, then feed its heated air to the HRV. This
configuration optimizes the SAH technology by providing it with a cold inlet air temperature. The trade-
off here is that the HRV unit’s effectiveness may be reduced because the SAH may have already
significantly increased the air temperature to the point where the HRV contributes limited or no energy
to the ventilation makeup air.
Glazed collectors do not lend themselves well to this application since the temperature rise they can
generate is so large. The collector temperature quickly rises above the indoor air temperature unless it is
a very cloudy day (shown in Appendix A, Figure 17). This large temperature rise produced by glazed SAH
collectors would not only decrease the effectiveness of the HRV unit, but could also risk damaging HRV
components. In addition, if the temperature rise is such that outlet air from the SAH is warmer than the
building temperature, the HRV could end up transferring heat in the opposite direction, causing it to
effectively cool the incoming air. This could be prevented by installing a bypass whereby the air heated
by the SAH collector(s) can be routed around the HRV when appropriate. However, this would probably
not provide a large benefit, since there would only be short windows of time when the two devices
would truly work in tandem. Any additional energy savings would probably not justify the extra cost and
complexity of this system.
A transpired air collector is better suited as a preheater for HRV units. The temperature rise from the
transpired air technology analyzed here is about 20°F under typical wind conditions on a fairly sunny day
according to test results for the transpired air collector (see Appendix A, Figure 21). This means the
transpired plate will provide substantial extra heat with only minor loss of effectiveness to the HRV and
little or no risk of damaging the HRV components. Transpired air is meant to work with HVAC systems,
so no extra controls or ducts are needed.
It is not clear how using SAH technology as a preheater would affect the operation of the HRV and the
final energy savings. It cannot simply be stated the using the two technologies together would result in
the cumulative energy savings of both systems operating independently. At times, the effectiveness of
the HRV would be reduced since there would be a lower temperature differential between the incoming
and outgoing air. During colder times, the HRV’s effectiveness may be increased since it will need to
spend less time running a defrost cycle. Since the manufacturers give limited performance data at
varying temperatures for their HRV units, it is difficult to precisely determine what the overall energy
production would be, though either type of SAH technology would clearly deliver a substantial amount
of heat to the house.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 17
Figure 10: Glazed SAH installed in line with HRV
A second method for incorporating both SAH and HRV technologies into a combination system is shown
in Figure 11. This configuration uses the HRV as the first air tempering device, then uses the SAH to
further increase the air temperature. It should be stated that this configuration is only compatible with
glazed SAH technologies, not transpired plate technologies. This method eliminates some of the
concerns associated with the previous configuration, where the SAH may overheat the HRV. Since the
inlet air will be below room temperature, the SAH collectors will produce more energy savings than a
standard closed-loop system.
Similar to the previously discussed method, bypasses would also be required for this configuration. The
system would need to bypass the SAH during the nighttime when there is no energy available in the SAH
and during the summer months when air heating is not necessary.
Modeling of this system is also difficult since the inlet temperatures to the SAH technology would be
dynamic based on the outlets of the HRV, ambient temperature and solar irradiance. A worst case
scenario could be assumed in which the inlet temperature for the SAH technology is equal to that of the
house temperature. This would never be the case because this scenario assumes that the HRV has 100%
effectiveness at all times. However, assuming this worst case scenario allows us to establish a lower
bound for the energy produced by this combination system by adding the energy produced by the HRV
to the energy produced by the SAH in a standard recirculation loop. By this reasoning, it can be stated
that this combination system will produce equal to or greater than the energy savings shown in the
table below.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 18
Minimum Energy Savings Produced by Combination System
Location Fantech HRV with 26ft2 of SAH Nu-Air HRV with 26ft2 of SAH
Saint Cloud, MN 65% 72%
Boulder, CO 70% 77%
Figure 11: HRV installed in line with glazed SAH
Since modeling of the first method of combining these technologies is difficult and only a lower bound
for the second scenario has been established it is difficult to numerically compare these two
configurations. However, it is highly likely that the second method will produce more energy than the
first simply because it does not reduce the HRV effectiveness while still allowing the SAH to provide
significant heat to the incoming air, at times rising its temperature well above the building air
temperature.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 19
Conclusion This report has been a study of HRV and SAH technologies and various combinations of both as a means
of tempering incoming ventilation makeup air. While it is difficult to directly compare such drastically
different technologies, this report as attempted to put numbers to this comparison through the use of
computer modeling software.
Since HRV technology has the advantage of being able to run continuously and also save energy used for
summertime cooling loads, it is overall more effective at delivering energy to the incoming ventilation
makeup air. While there are various HRV units on the market, of the two looked at in this study the Nu-
Air ES-150 was the most effective.
As with most projects, cost and return on investment are often a driving factor when deciding whether
or not to move forward. This report shows HRV technology having significantly better return on
investment figures. Since SAH technology cannot deliver as much energy to the incoming ventilation
makeup air as HRV technology, its return on investment is less lucrative.
This report further explored the option of using SAH and HRV technologies together. While modeling of
these systems together is difficult and not feasible to do accurately with the currently available tools, it
is apparent that these two technologies can work well in tandem. Using an HRV to first temper incoming
ventilation makeup air, then feeding this pre-tempered air to an SAH collector is an effective way of
using both of these technologies together.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 20
Appendix A – Energy Calculation Details The following parameters and calculations estimate the performance of SAH and HRV systems in various
configurations.
House Specifications
In order to accurately compare SAH and HRV technologies, the following building was selected and used
for all modeling in this study.
Location: St. Cloud, MN and Boulder, CO.
2,500 sq. ft.
3 bedrooms
ASHRAE 62.2 Ventilation Requirements [4]
Determination of ventilation requirements for this building are based on ASHRAE 62.2 requirements.
Whole house ventilation for 2500ft2, 3 bedrooms: 2500/100 + 7.5*(3 + 1) = 55cfm
Bathroom continuous ventilation: 20cfm
Kitchen continuous ventilation: 25cfm
Total continuous ventilation: 55cfm + 20cfm + 25cfm = 100cfm
Ventilation Heating Load
Historical degree day data provides a good estimate of what the ventilation heating load will be during a
typical year. The heating load is calculated by converting the flow rate to ft3/day, multiplying by the
heating degree days and multiplying by the specific heat of air, which is 0.018Btu/(ft3 * °F):
( )
( )
HRV Energy Savings
The following energy savings were calculated based on degree days and manufacturer’s specifications
for each HRV model.
Heating energy savings = (Heating load) * (Apparent sensible effectiveness)
Time in heating mode is an estimate of the percentage of the year that the HRV works to heat the
house, rather than cooling it. This is a weighted average based on the heating and cooling degree days
for each month of the year.
( ) ( ) ( )
( )
Location
Heating
Degree Days
(°F-day)
Ventilation
Rate (cfm)
Ventilation
Heating Load
(mmBtu)
St. Cloud, MN 8,076 100 20.93
Boulder, CO 6,667 100 17.28
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 21
( ) ( ) ( )
( )
Standard Recirculation Loop Solar Air Heat System
Most glazed SAH systems operate on a closed loop, heating up air from inside the house. Standard
systems are sized using the rule of 2-4 cfm per square foot of collector area to achieve good efficiency.
Collectors are typically available in 26 sq. ft., 32 sq. ft., and 40 sq. feet sizes. To meet the required 100
cfm ventilation air requirement, one 26 sq. ft. collector would be the recommended size. The heat
produced by this system is estimated using TRNSED, with the following input parameters.
Building or House for Simulation: 2500 square foot – 5%/10% windows – Super Insulated
Minimum House (Furnace) Thermostat Setting: 65 °F
Shut-off Temperature (Max House Temp): 80 °F
Auxiliary Heating Inlet Temperature: House Temperature
Backup Furnace/Auxiliary System
o Maximum Heating Rate of Furnace/Aux.: 120,000 Btu/hour
o Flow Rate of Furnace/Aux. Heater: 2,000 cfm
o Maximum Power of Aux. Blower Fan: 200W
o Efficiency of Backup Furnace/Aux. System: 92%
Internal Gains: Ignore Internal Gains
Slab Heat Loss: Ignore Slab Heat Loss
Solar Collector System
o Collector Inlet Temperature: House Temperature
o Collector Orientation
Slope of Collector Surface: 90°
Azimuth of Collector Surface: 0°
o SPF Collector Selection: Manufacturer’s Recommended Values
o Collector Type: SPF26
Number of Collector Modules in Series: 1
Number of Collector Modules in Parallel: 1
o Controller Settings
Upper Dead Band dT for Blower: 30 °F
Lower Dead Band dT for Blower: 8 °F
o Blower Fan Settings
Total Blower Fan Flow Rate: 100 cfm
HRV Model Location
Apparent
Sensible
Effectiveness
Power
Rating (W)
Ventilation
Heating
Load
(mmBtu)
Heating
Energy
Savings
(mmBtu)
Time In
Heating
Mode
Electric
Energy
Consumed
(mmBtu)
Net Energy
Saved
Fantech VHR 1405R St. Cloud, MN 70% 102 20.93 14.65 65.93% 2.01 60%
Fantech VHR 1405R Boulder, CO 70% 102 17.28 12.10 66.84% 2.04 58%
Nu Air ES-150 St. Cloud, MN 73% 80 20.93 15.28 65.93% 1.58 65%
Nu Air ES-150 Boulder, CO 73% 80 17.28 12.62 66.84% 1.60 64%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 22
Maximum Power of Blower Fan: 44.4 W
o Summer Operation: Do Not Shut System Down for Part of Year (No DHW Heating)
Figure 12: TRNSED results for standard glazed SAH system with 1 26 sq. ft. collector (St. Cloud, MN)
Figure 13: TRNSED results for standard glazed SAH system with 1 26 sq. ft. collector (Boulder, CO)
Glazed SAH for Ventilation Makeup Air
Several parameters from the first example have to be adjusted in order for the model to represent a
ventilation makeup air system. The first difference is the collector inlet temperature needs to be
changed to the ambient temperature. Also, since the house needs a constant supply of fresh air, the
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 983,415 198,475 20.2% 198,475 1.38 33.61 13,605,862 12,517,394 1.6%
February 1,152,297 286,143 24.8% 286,143 1.66 25.02 9,931,531 9,137,008 3.0%
March 1,312,661 313,480 23.9% 313,480 2.15 18.00 7,032,413 6,469,820 4.6%
April 843,981 204,751 24.3% 204,751 2.00 8.06 3,154,227 2,901,889 6.6%
May 791,581 178,815 22.6% 178,815 2.32 1.61 629,747 579,367 23.6%
June 724,912 136,823 18.9% 136,823 1.97 - - - 100.0%
July 777,595 63,068 8.1% 63,068 0.86 - - - 100.0%
August 836,927 142,340 17.0% 142,340 1.48 - - - 100.0%
September 887,699 275,869 31.1% 275,869 2.41 0.76 299,180 275,246 50.1%
October 932,706 307,821 33.0% 307,821 2.22 6.53 2,553,754 2,349,454 11.6%
November 779,517 222,048 28.5% 222,048 1.51 18.26 7,120,153 6,550,541 3.3%
December 701,208 138,901 19.8% 138,901 1.01 30.96 12,286,449 11,303,533 1.2%
Total 10,724,499 2,468,533 23.0% 2,468,533 20.97 142.82 56,613,316 52,084,251 4.5%
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 1,159,291 368,778 31.8% 368,778 2.38 17.52 6,850,717 6,302,659 5.5%
February 1,059,781 343,014 32.4% 343,014 2.01 13.88 5,426,876 4,992,726 6.4%
March 1,221,537 364,699 29.9% 364,699 2.72 10.63 4,142,690 3,811,274 8.7%
April 950,453 255,503 26.9% 255,503 2.57 4.37 1,710,365 1,573,536 14.0%
May 734,130 172,417 23.5% 172,417 2.38 2.07 810,735 745,876 18.8%
June 636,725 113,988 17.9% 113,988 1.76 0.38 147,075 135,309 45.7%
July 699,251 26,998 3.9% 26,998 0.37 - - - 100.0%
August 850,940 99,656 11.7% 99,656 1.10 - - - 100.0%
September 1,040,959 286,669 27.5% 286,669 2.14 0.44 172,365 158,576 64.4%
October 1,246,815 467,379 37.5% 467,379 2.89 3.50 1,368,262 1,258,801 27.1%
November 1,107,874 383,083 34.6% 383,083 2.37 11.72 4,574,726 4,208,748 8.3%
December 1,174,591 377,881 32.2% 377,881 2.31 18.50 7,234,505 6,655,745 5.4%
Total 11,882,346 3,260,065 27.4% 3,260,065 24.99 83.00 32,438,315 29,843,250 9.8%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 23
controller needs to be on all the time instead of turning on and off as temperatures change. To
accomplish this, both dead band settings are set to -100 °F. The following parameters were used in this
model.
Building or House for Simulation: 2500 square foot – 5%/10% windows – Super Insulated
Minimum House (Furnace) Thermostat Setting: 65 °F
Shut-off Temperature (Max House Temp): 80 °F
Auxiliary Heating Inlet Temperature: House Temperature
Backup Furnace/Auxiliary System
o Maximum Heating Rate of Furnace/Aux.: 120,000 Btu/hour
o Flow Rate of Furnace/Aux. Heater: 2,000 cfm
o Maximum Power of Aux. Blower Fan: 200W
o Efficiency of Backup Furnace/Aux. System: 92%
Internal Gains: Ignore Internal Gains
Slab Heat Loss: Ignore Slab Heat Loss
Solar Collector System
o Collector Inlet Temperature: Ambient (Outdoors) Temperature
o Collector Orientation:
Slope of Collector Surface: 90°
Azimuth of Collector Surface: 0°
o SPF Collector Selection: Manufacturer’s Recommended Values
o Collector Type: SPF26
Number of Collector Modules in Series: 1
Number of Collector Modules in Parallel: 1
o Controller Settings
Upper Dead Band dT for Blower: -100 °F
Lower Dead Band dT for Blower: -100 °F
o Blower Fan Settings
Total Blower Fan Flow Rate: 100 cfm
Maximum Power of Blower Fan: 44.4 W
o Summer Operation: Do Not Shut System Down for Part of Year (No DHW Heating)
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 24
Figure 14: TRNSED results for solar ventilation air heat system with 1 26 sq. ft. collector (St. Cloud,
MN)
Figure 15: TRNSED results for solar ventilation air heat system with 1 26 sq. ft. collector (Boulder, CO)
Figure 17 shows the hourly performance of this system for one week at the end of January/beginning of
February.
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 983,415 450,930 45.9% 450,930 9.18 34.79 14,307,948 13,163,312 3.3%
February 1,152,297 512,716 44.5% 512,716 8.29 26.22 10,540,128 9,696,918 5.0%
March 1,312,661 552,512 42.1% 552,512 9.18 19.41 7,583,385 6,976,715 7.3%
April 843,981 324,417 38.4% 324,417 8.88 8.72 3,406,730 3,134,192 9.4%
May 791,581 243,874 30.8% 243,874 7.88 1.83 716,509 659,188 27.0%
June 724,912 191,098 26.4% 191,098 6.50 - - - 100.0%
July 777,595 91,442 11.8% 91,442 3.21 - - - 100.0%
August 836,927 179,142 21.4% 179,142 5.10 - - - 100.0%
September 887,699 330,317 37.2% 330,317 8.24 1.00 389,987 358,788 47.9%
October 932,706 406,293 43.6% 406,293 9.18 7.21 2,819,441 2,593,885 13.5%
November 779,517 355,754 45.6% 355,754 8.88 19.63 7,648,220 7,036,362 4.8%
December 701,208 315,522 45.0% 315,522 9.18 32.46 12,990,198 11,950,982 2.6%
Total 10,724,499 3,954,017 36.9% 3,954,017 93.68 151.26 60,402,546 55,570,343 6.6%
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered
to Building
by Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 1,159,291 534,314 46.1% 534,314 9.18 18.82 7,371,515 6,781,794 7.3%
February 1,059,781 472,414 44.6% 472,414 8.29 14.99 5,857,648 5,389,036 8.1%
March 1,221,537 502,255 41.1% 502,255 9.18 11.64 4,536,246 4,173,347 10.7%
April 950,453 347,753 36.6% 347,753 8.88 5.01 1,959,400 1,802,648 16.2%
May 734,130 236,157 32.2% 236,157 8.67 2.39 935,579 860,733 21.5%
June 636,725 148,814 23.4% 148,814 6.09 0.40 157,873 145,243 50.6%
July 699,251 34,393 4.9% 34,393 1.26 - - - 100.0%
August 850,940 113,217 13.3% 113,217 3.31 - - - 100.0%
September 1,040,959 326,344 31.4% 326,344 6.45 0.53 208,500 191,820 63.0%
October 1,246,815 542,931 43.5% 542,931 9.05 4.01 1,570,427 1,444,793 27.3%
November 1,107,874 506,340 45.7% 506,340 8.88 12.65 4,931,597 4,537,069 10.0%
December 1,174,591 542,818 46.2% 542,818 9.18 19.82 7,770,363 7,148,734 7.1%
Total 11,882,346 4,307,750 36.3% 4,307,750 88.40 90.27 35,299,147 32,475,216 11.7%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 25
Figure 16: Sample of collector temperatures for a ventilation system with 1 26 sq. ft. SAH collector (St.
Cloud, MN), taken from TRNSED simulation
Effect of Increasing the Solar Collector Area
Increasing the area of solar panels used can increase the heat output of the system. The next four charts
show the results of using one 40 sq. ft. collector and two 40 sq. ft. collectors in parallel. All the other
input parameters are the same as the 26 sq. ft. example.
Figure 17: TRNSED results for solar ventilation air heat system with 1 40 sq. ft. SAH collector (St.
Cloud, MN)
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 1,536,789 569,670 37.1% 569,670 9.18 34.60 14,201,527 13,065,405 4.2%
February 1,800,702 649,165 36.1% 649,165 8.29 25.81 10,398,011 9,566,170 6.4%
March 2,051,303 699,887 34.1% 699,887 9.18 18.95 7,417,968 6,824,531 9.3%
April 1,318,895 410,780 31.1% 410,780 8.88 8.59 3,356,899 3,088,347 11.7%
May 1,237,009 307,738 24.9% 307,738 7.74 1.75 685,768 630,907 32.8%
June 1,132,825 241,638 21.3% 241,638 6.47 - - - 100.0%
July 1,215,152 110,372 9.1% 110,372 2.97 - - - 100.0%
August 1,307,870 225,678 17.3% 225,678 5.05 - - - 100.0%
September 1,387,213 416,821 30.0% 416,821 8.23 0.93 362,722 333,704 55.5%
October 1,457,546 514,262 35.3% 514,262 9.18 7.00 2,738,123 2,519,073 17.0%
November 1,218,155 449,922 36.9% 449,922 8.88 19.42 7,562,168 6,957,195 6.1%
December 1,095,782 398,861 36.4% 398,861 9.18 32.25 12,902,981 11,870,742 3.3%
Total 16,759,242 4,994,793 29.8% 4,994,793 93.22 149.29 59,626,166 54,856,074 8.3%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 26
Figure 18: TRNSED results for solar ventilation air heat system with 1 40 sq. ft. SAH collector (Boulder,
CO)
Figure 19: TRNSED results for solar ventilation air heat system with 2 40 sq. ft. SAH collectors (St.
Cloud, MN)
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 1,811,632 675,726 37.3% 675,726 9.18 18.49 7,237,630 6,658,620 9.2%
February 1,656,126 598,032 36.1% 598,032 8.29 14.75 5,767,400 5,306,008 10.1%
March 1,908,903 635,850 33.3% 635,850 9.18 11.46 4,459,659 4,102,887 13.4%
April 1,485,279 440,345 29.6% 440,345 8.88 4.78 1,870,640 1,720,989 20.4%
May 1,147,230 299,031 26.1% 299,031 8.64 2.38 930,243 855,823 25.9%
June 995,014 184,249 18.5% 184,249 5.82 0.40 156,117 143,627 56.2%
July 1,092,724 43,441 4.0% 43,441 1.25 - - - 100.0%
August 1,329,769 143,050 10.8% 143,050 3.26 - - - 100.0%
September 1,626,713 406,322 25.0% 406,322 6.37 0.49 190,324 175,098 69.9%
October 1,948,405 686,011 35.2% 686,011 9.03 3.82 1,494,388 1,374,837 33.3%
November 1,731,281 640,532 37.0% 640,532 8.88 12.43 4,844,677 4,457,103 12.6%
December 1,835,540 687,247 37.4% 687,247 9.18 19.49 7,645,287 7,033,664 8.9%
Total 18,568,617 5,439,837 29.3% 5,439,837 87.95 88.47 34,596,364 31,828,655 14.6%
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered
to Building
by Solar
System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 3,073,579 692,874 22.5% 692,874 9.18 34.26 14,068,369 12,942,900 5.1%
February 3,601,405 791,046 22.0% 791,046 8.29 25.45 10,259,430 9,438,676 7.7%
March 4,102,606 853,205 20.8% 853,205 9.18 18.57 7,278,021 6,695,779 11.3%
April 2,637,789 500,602 19.0% 500,602 8.88 8.38 3,273,752 3,011,852 14.3%
May 2,474,018 374,873 15.2% 374,873 7.72 1.69 663,904 610,791 38.0%
June 2,265,650 286,162 12.6% 286,162 6.23 - - - 100.0%
July 2,430,304 128,715 5.3% 128,715 2.62 - - - 100.0%
August 2,615,741 274,313 10.5% 274,313 5.01 - - - 100.0%
September 2,774,425 505,490 18.2% 505,490 8.06 0.80 313,545 288,461 63.7%
October 2,915,092 626,510 21.5% 626,510 9.18 6.78 2,645,942 2,434,267 20.5%
November 2,436,311 547,747 22.5% 547,747 8.88 19.13 7,459,509 6,862,748 7.4%
December 2,191,563 485,397 22.1% 485,397 9.18 31.91 12,791,378 11,768,068 4.0%
Total 33,518,484 6,066,935 18.1% 6,066,935 92.40 146.99 58,753,850 54,053,543 10.1%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 27
Figure 20: TRNSED results for solar ventilation air heat system with 2 40 sq. ft. SAH collectors
(Boulder, CO)
Energy Savings Percentage for Glazed SAH
The TRNSED simulation calculates the heating load for the whole house, but does not show what part of
this is due to the ventilation load. An additional simulation step is required to determine what this load
is so that the percentage of energy savings can be calculated. This is done by comparing two TRNSED
runs where the only variable changed is the rate of infiltration. The difference in energy delivered to the
building between these two simulations is equal to the heating energy required to raise the ventilation
air to room the house’s setpoint.
Inside the TRNSED model, infiltration is specified in air changes per hour. The volume of the building can
be used to convert the ventilation flow rate to air changes per hour:
Volume of conditioned space: 30,217 ft3
(100 ft3/min)*(60 min/hour)*(air change/ 30,217 ft3) = 0.20 air changes per hour
Increasing the infiltration rate by this amount in TRNSED gives 19.6mmBtu for St. Cloud and 15.4mmBtu
for Boulder.
The next step is to calculate the electrical energy used by the fan. Since the fan in a glazed SAH system
has to overcome a significant amount of static pressure, the ventilation system can be made more
efficient by bypassing the collectors and using a lower powered fan when there is no solar energy
available. A good fan for this purpose is the Panasonic WhisperGreen FV-13VKM3, which consumes
15.6W while delivering 111cfm at a static pressure of 0.25in H2O. The total ventilation fan energy
consumed can be determined by first calculating the percentage of the year that the solar fan will
operate, and then having the direct ventilation fan run the rest of the time:
Energy used by solar fan if it ran the entire year:
Incident
Solar
Radiation
Collected
Energy
Collection
Efficiency
Energy
Delivered to
Building by
Solar System
Fan
Power -
Solar
Fan
Power -
Auxiliary
System
Energy
Consumed
by Auxiliary
System
Energy
Delivered to
Building by
Auxiliary
System
Solar
Fraction
Air
BTUs BTUs % BTUs kWh kWh BTUs BTUs -
January 3,623,264 822,604 22.7% 822,604 9.18 18.14 7,112,024 6,543,062 11.2%
February 3,312,253 728,635 22.0% 728,635 8.29 14.50 5,668,185 5,214,730 12.3%
March 3,817,807 774,756 20.3% 774,756 9.18 11.16 4,345,916 3,998,242 16.2%
April 2,970,558 536,648 18.1% 536,648 8.88 4.67 1,824,907 1,678,914 24.2%
May 2,294,459 357,602 15.6% 357,602 8.56 2.34 917,468 844,070 29.8%
June 1,990,028 218,797 11.0% 218,797 5.67 0.39 154,276 141,934 60.7%
July 2,185,449 53,351 2.4% 53,351 1.23 - - - 100.0%
August 2,659,539 166,779 6.3% 166,779 2.71 - - - 100.0%
September 3,253,426 494,027 15.2% 494,027 6.11 0.47 183,209 168,552 74.6%
October 3,896,810 832,844 21.4% 832,844 8.90 3.66 1,433,083 1,318,437 38.7%
November 3,462,562 779,954 22.5% 779,954 8.88 12.14 4,731,997 4,353,438 15.2%
December 3,671,080 837,425 22.8% 837,425 9.18 19.10 7,501,743 6,901,604 10.8%
Total 37,137,233 6,603,421 17.8% 6,603,421 86.77 86.57 33,872,808 31,162,984 17.5%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 28
(44.4W)*(365*24h)*(3.412Btu/Wh) = 1.33mmBtu
Energy used by direct ventilation fan if it ran the entire year:
(15.6W)*(365*24h)*(3.412Btu/Wh) = 0.466mmBtu
TRNSED gives the energy consumed by the solar fan, ESF. The total fan energy consumed is calculated by
adding in the contribution of the direct ventilation fan for the remainder of the year:
Total fan energy consumed = ESF + 0.466*(1.33 – ESF)/1.33
Combining these two new calculations with the TRNSED results gives the following results for
percentage of energy saved by the solar ventilation makeup air systems:
Solar Transpired Air
The recommended airflow rates for the MatrixAir transpired plate SAH technology are 3-8 cfm per
square foot of collector area. A lower flow rate results in a higher temperature rise, while 7-8 cfm per
square foot gives optimal efficiency per collector area. For this case, a high temperature rise is desired
to deliver as much heat as possible to the incoming air. Since the flow rate is 100 cfm, 33 square feet of
collector is used to get 3 cfm per square foot. Figure 21 shows test results for one type of transpired air
collector. For this system the temperature rise will be up to 27.5°F on a sunny day with medium wind.
TechnologyHeating Energy
Saved (mmBtu)
Fan Energy
Consumed
(mmBtu)
VMUA Fan
Energy
Consumed
(mmBtu)
Ventilation
Heating
Load
(mmBtu)
Net Energy
Saved
(mmBtu)
Percentage
Energy
Saved
Closed-loop SAH, 26 sq. ft. 2.47 0.072 0.441 19.6 1.96 10%
Ventilation SAH, 26 sq. ft. 3.95 0.32 0.354 19.6 3.28 17%
Ventilation SAH, 32 sq. ft. 4.50 0.319 0.354 19.6 3.83 20%
Ventilation SAH, 40 sq. ft. 5.00 0.318 0.355 19.6 4.33 22%
Ventilation SAH, 40 sq. ft. (x2) 6.07 0.315 0.356 19.6 5.40 28%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 29
Figure 21: Test results for MatrixAir transpired collectors
RETScreen was used to estimate the heat produced by this system over a typical year for both St. Cloud,
MN and Boulder, CO. The RETScreen setup is shown below for Boulder. For the weather data, wind
speeds are measured at 10m above ground level. Since the collectors will be close to the ground, the
wind speeds were reduced by 50%.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 30
Technology Solar air heater
Load characteristics
Application Ventilation
Process
Unit Base case Proposed case
Facility type Residential
Indoor temperature °F 65.0 65.0
Air temperature – maximum °F 80.0 80.0
R-value – wall ft² - ºF/(Btu/h) 23.7 23.7
Design airflow rate cfm 100 100
Operating days per week – weekdays d/w 5.0 5.0
Operating hours per day – weekdays h/d 24.0 24.0
Operating days per week – weekends d/w 2.0 2.0
Operating hours per day – weekends h/d 24.0 24.0
Percent of month used Month
Unit Base case Proposed case
Heating million Btu 18 18
Resource assessment
Solar tracking mode Fixed
Slope ˚ 90.0
Azimuth ˚ 0.0
Show data
Daily solar radiation - horizontal
Daily solar radiation -
tilted
Month kWh/m²/d kWh/m²/d
January 2.36 4.50
February 3.38 4.61
March 4.59 4.12
April 5.39 3.27
May 6.12 2.80
June 6.97 2.75
July 6.79 2.83
August 5.84 3.12
September 5.01 3.84
October 3.64 4.05
November 2.68 4.41
December 2.14 4.52
Annual 4.58 3.73
Annual solar radiation – horizontal MWh/m² 1.67
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 31
Annual solar radiation – tilted MWh/m² 1.36
Solar air heater
Type Transpired-plate
Design objective High temperature rise
Manufacturer Matrix Energy
Model MatrixAir TR - Black
Solar collector absorptivity 0.94
Performance factor 0.86
Solar collector area ft² 33 51
Solar collector shading - season of use % 0% Wind speed
Incremental fan power W/ft² 1.3
Electricity rate $/kWh 0.000
Summary
Incremental electricity – fan MWh 0.4
Heating delivered million Btu 4.7
Building heat loss recaptured million Btu 0.2
Results Summary
The following chart summarizes the resulting energy savings from each technology studied:
Location
Ventilation
Heating Load
(mmBtu)
Heating
Energy
Savings
(mmBtu)
Fan Energy
Consumed
(mmBtu)
Net Energy
Savings
St. Cloud, MN 21 4.5 0.466 19%
Boulder, CO 18 4.7 0.466 24%
TechnologyHeating Energy
Saved (mmBtu)
Fan Energy
Consumed
(mmBtu)
VMUA Fan
Energy
Consumed
(mmBtu)
Ventilation
Heating
Load
(mmBtu)
Net Energy
Saved
(mmBtu)
Percentage
Energy
Saved
Closed-loop SAH, 26 sq. ft. 2.47 0.072 0.441 19.6 1.96 10%
Ventilation SAH, 26 sq. ft. 3.95 0.32 0.354 19.6 3.28 17%
Ventilation SAH, 32 sq. ft. 4.50 0.319 0.354 19.6 3.83 20%
Ventilation SAH, 40 sq. ft. 5.00 0.318 0.355 19.6 4.33 22%
Ventilation SAH, 40 sq. ft. (x2) 6.07 0.315 0.356 19.6 5.40 28%
Transpired Air, 33 sq. ft. 4.50 0.466 0.000 21.0 4.03 19%
Fantech HRV 14.7 2.01 0.000 20.9 12.64 60%
Nu Air HRV 15.3 1.58 0.000 20.9 13.70 65%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 32
Appendix B – Return on Investment Calculation Details The following numbers and assumptions were used when performing return on investment calculations
for this report. All return on investment calculations are projections and are not absolute.
Equipment Costs*:
Fantech VHR 1405R [9] [10] [11] $1035.93
Nu-Air ES-150 [12] $1129.00
RREAL SPF26 [13] $1100.00
Matrix Air Transpired Plate (33 ft2) [14] [15] $1107.81
*Equipment costs do not include additional components such as fasteners, hangers, etc., and labor costs
that may be required for installation. These costs have been omitted from these calculations because
they are often site specific and can vary from case to case. It should be noted that installation costs can
be a significant portion of the actual cost of the system. Installation costs will impact the payback
periods listed above.
Fuel Prices:
Natural Gas [16] $8.66/therm Propane [17] $2.189/gallon Electricity [18] $0.1096/kWh Fuel Oils [19] $3.419/gallon Energy Content for Fuels: [20]
Natural Gas 1,029,000 BTU/therm Propane 91,333 BTU/gallon Electricity 3412 BTU/kWh Fuel Oils 138,690 BTU/gallon Annual Fuel Utilization Efficiency: [21]
Natural Gas 80% Propane 80% Electricity 97%** Fuel Oils 87% **Based on indoor electric furnace or baseboard heat
Annual Inflation Rate: 2.44% [22]
Fuel Escalation Rates: [23]
Natural Gas 4.81% Propane 5.32% Electricity 3.37% Fuel Oils 9.36%
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 33
References
[1] Home Ventilating Institute, "Home Ventilating Institute (HVI Indoor Air Quality (IAQ) Position
Paper," 1 October 2009. [Online]. Available:
http://www.hvi.org/publications/pdfs/HVI_IAQPositionPaper_01Oct09.pdf. [Accessed 16 January
2013].
[2] G. Cooke, "Natural Versus Mechanical Ventilation," January 2005. [Online]. Available:
http://www.hvi.org/publications/pdfs/HPAC_CookeJanFeb05.pdf. [Accessed 16 January 2013].
[3] D. W. Wolbrink, "Mold, Moisture, and Houses - Ventilation Is an Effective Weapon," 2009. [Online].
Available: http://www.hvi.org/publications/pdfs/MoldPaper_final1June09.pdf. [Accessed 16
January 2013].
[4] ASHRAE Standard 62.2-2010: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential
Buildings, Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc., 2010.
[5] Prostar Mechanical Technologies, LTD, "HRV (Heat Recovery Ventilators)," 2012. [Online]. Available:
http://www.prostar-mechanical.com/HRV/Greentek%20HRV.htm. [Accessed 29 January 2013].
[6] Matrix Energy, "Solar Air Heating Systems," 2011. [Online]. Available:
http://www.matrixairheating.com/products.html. [Accessed 29 January 2013].
[7] Rural Renewable Energy Alliance, "Solar Air Heat Basics," 2010. [Online]. Available:
http://www.rreal.org/solar-powered-furnace/solar-air-heat-basics/. [Accessed 29 January 2013].
[8] RETScreen International, "RETScreen Version 4," Natural Resources Canada, Varennes, Quebec,
2012.
[9] AC Whole Salers, [Online]. Available: www.acwholesalers.com.
[10] Grainger, [Online]. Available: www.grainger.com.
[11] Electrical Supplies Online, [Online]. Available: www.electricalsuppliesonline.com.
[12] TMS Johnson, Price Quote, 2012.
[13] Rural Renewable Energy Alliance, MSRP Pricing, 2012.
[14] Matrix Air, West Preparatory School, Toronto ON.
[15] Matrix Air, Arts Education Building at Bemidji State University, 2012.
Rural Renewable Energy Alliance
Solar Air Heat and Residential Ventilation Makeup Air 34
[16] Energy Information Administration, "Minnesota Annual Average," 2011. [Online]. Available:
http://www.eia.gov/dnav/ng/ng_pri_sum_dcu_SMN_a.htm.
[17] Energy Information Administration, "Minnesota Annual Average," 2011. [Online]. Available:
http://www.eia.gov/dnav/pet/hist/LeafHandler.ashx?n=PET&s=M_EPLLPA_PRS_R20_DPG&f=M.
[18] Energy Information Administration, "Minnesota Annual Average," 2011. [Online]. Available:
http://www.eia.gov/electricity/data.cfm#sales.
[19] Energy Information Administration, "Minnesota Annual Average," 2011. [Online]. Available:
http://www.eia.gov/dnav/pet/hist/LeafHandler.ashx?n=PET&s=M_EPD2F_PRS_R20_DPG&f=M.
[20] Energy Information Administration, "Annual Energy Review 2011," 27 September 2011. [Online].
Available: http://www.eia.gov/totalenergy/data/annual/pdf/aer.pdf.
[21] Energy Information Administration, "Minimum Requirements beginning on May 2013," [Online].
Available: http://energy.gov/energysaver/articles/furnaces-and-boilers.
[22] Bureau of Labor Statistics, [Online]. Available: http://www.bls.gov/cpi/tables.htm.
[23] Energy Information Administration, "Based on 15 year historical average for Minnesota," [Online].