SMMS DX Interface Installation manual

Indoor Unit Model name:

MM-DXC010

MM-DXV080 MM-DXV140

DX Controller

DX Valve Kit (5,6kW; 7,1kW; 8,0kW) DX Valve Kit (11,2kW; 14,0kW)

MM-DXV280 DX Valve Kit (22,4kW; 28,0kW)

Installation manual English

SMMS DX Interface 1

For Commercial Use

Page 2: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

1

SMMS DX Interface Installation Manual SMMS DX Interface Installation Manual

Please read this Installation Manual carefully before installing the DX interface. • This Manual describes the installation method of the DX interface. • You must also refer to the Installation and Owner’s Manual attached to the Toshiba outdoor unit. • Please follow the manual(s) for your Air Handling Unit (local supply). • Toshiba Carrier UK (Ltd) does not take any responsibility on the local design.

ADOPTION OF NEW REFRIGERANT

conventional refrigerant R22 in order to prevent destruction of the ozone layer.

This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the

Contents 1 SUPPLIED PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 ELECTRICAL WORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5 APPLICABLE CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 6 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

8 OPTIONAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 9 DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7 TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

10 SERVICE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

1-EN

This appliance is for commercial use only and should not be accessible to the general public. This appliance is not intended for use by person (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

This symbol mark is for EU countries only. This symbol mark is according to the directive 2002/96/EC Article 10 Information for users and Annex IV. This product is designed and manufactured with high quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at the end-of-life, should be disposed of separately from your household waste. Please dispose of this equipment at your local community waste collection / recycling centre. In the European Union there are separate collection systems for used electrical and electronic product.

Page 3: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

2

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

The SMMS DX Interface is designed to allow the connection of a third party air handling unit (with R410A DX Coil) to a Toshiba VRF outdoor unit (MiNi-SMMS / SMMS / SMMS-i / SHRM).

The Interface consists of a DX Controller, and a DX VALVE KIT (3 sizes). This is a kit of parts which the installer needs to assemble (including brazing).

MM-DXV080 DX Valve Kit (5.6kW, 7.1kW, 8.0kW) MM-DXV140 DX Valve Kit (11.2kW, 14.0kW) MM-DXV280 DX Valve Kit (22.4kW, 28.0kW)

DX Valve Kit contents:-

MM-DXC010 DX Controller

1 SUPPLIED PARTS

2 PRECAUTIONS FOR SAFETY

2-EN

Item Description Qty Item Description Qty Item Description Qty

TC1 Sensor (Ø4) 1 Sensor Holder (Ø4) 1 Strainer 2

TC2 / TCJ Sensor (Ø6) 2 Sensor Holder (Ø6) 2 P Clamp (TA) 1

TA Sensor (Resin) 1 Fix Plate (Ø4) 1 PMV Motor Head 1

PMV Body 1 Fix Plate (Ø6) 2

Page 4: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

3

SMMS DX Interface Installation Manual

Use the following table to determine the appropriate DX Valve Kit based on the AHU Air Volume and DX Coil Size:-

• The DX Coil must be suitable for R410A. • The counter flow principle must be observed. • Design target Evaporation temperature: approx. 6.5°C.

DX Controller Model MM-DXC010 MM-DXC010 MM-DXC010

DX Valve Kit Model MM-DXV080 MM-DXV140 MM-DXV280

Nominal Cooling Capacity (kW) 5.6 7.1 8.0 11.2 14.0 22.4 28.0

Nominal Heating Capacity (kW) 6.3 8.0 9.0 12.5 16.0 25.0 31.5

Power code (HP) 2 2.5 3 4 5 8 10

Minimum volume flow rate (m3/hr) 720 1060 1060 1280 1680 2880 3360

Maximum volume flow rate (m3/hr) 1080 1580 1580 1920 2520 4320 5040

3 INSTALLATION

Cooling & Heating output figures are based on calculations and ‘general’ test data. All figures are to be taken as approximations. The properties of the DX coils (by others) will have an affect on the performance of the outdoor units. All capacity data shown in this brochure is based on the following conditions : - Cooling : indoor air temperature 27°C db / 19°C wb, outdoor air temperature 35°C db Heating : indoor air temperature 20°C db, outdoor air temperature 7°C db / 6°C wb

NOTES If the wiring is properly carried out by a specialist according to the local regulations, the device fulfills the protection class IP65. Diversity Ratio: Maximum 110% (When a DX Interface is connected) The MiNi-SMMS cannot be connected to MM-DXV280. Cooling Mode Coil “Air On” Temp : Minimum 15°CWB / Maximum 24°CWB Air temperatures flowing across the coil below this level, can in some circumstances, cause icing and freezing issues with the coil and eventually forcing the system to shut down and also be detrimental to the outdoor unit itself. Heating Mode Coil “Air On” Temp : Minimum 15°CDB / Maximum 28°CDB In the reverse cycle mode when the outdoor unit is producing hot gas, the coil in the AHU is effectively the condenser. Air temperatures flowing across the coil below this level, can cause over condensing of the refrigerant. This can result in liquid being returned to the compressor which will cause a mechanical failure of the outdoor unit. Low air temperatures will also cause the unit to use it's defrost mode more often. Fresh Air Intake If you wish to use Fresh Air which is outside of these Coil “Air On” limits it has to either be pre-conditioned by other equipment, or mixed with return air (or a combination of both) so that it remains inside these limits, in order to ensure reliable operation. Automatic Mode Please be aware that frequent mode changes could occur when using Automatic mode (SHRM).

3-EN

Page 5: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

4

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

PIPING SCHEMATIC

Notes: 1) The PMV must be water cooled whilst brazing, to prevent damage to the mechanism. 2) The TCJ Sensor Holder must be brazed to the capillary on the DX Coil’s lowest circuit. 3) For brazing, be sure to use nitrogen gas to avoid oxidation of pipe inner surface.

The DX controller must not be installed outside. To avoid damage, when making holes for cables glands, please first remove the Gland Plate from the DX controller. To maintain waterproof integrity IP65 glands must be used through the gland plate.

DX CONTROLLER

4-EN

Page 6: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

5

SMMS DX Interface Installation Manual

DX COIL PREPARATION

The DX Valve Kit is supplied as separate components. These will need to be assembled and then fitted to DX Coil. This is a custom process as each DX Coil will be different, time and care should be given to this activity, and it should be prepared off-site. Note that the PMV body MUST be water cooled whilst brazing. For brazing, be sure to use nitrogen gas to avoid oxidation of pipe inner surface. Typically the DX Coil will have a Gas Header, and a Liquid Capillary Distributor (see below):-

TC1 Sensor Ø4 (Small Sensor Holder). 1 x Braze. Gas Header Pipe.

TCJ Sensor Ø6 (Large Sensor Holder). 1 x Braze. This should be brazed to the lowest Distributor Pipe.

PMV Body, 2 x Strainer, TC2 Sensor Ø6 (Large Sensor Holder). Custom local Pipes. 8 x Braze. Below Distributor.

SENSOR HOLDERS

Sensor Holders MUST be brazed on to the DX Coil pipe work to ensure reliable temperature sensing. There are three coil sensors, these are inserted into the Sensor Holders, and secured with the sensor-fix-plate. The sensor holders should be brazed at the 6’oclock position.

It is essential that the sensors are correctly located to ensure efficient system performance.

TA SENSOR

Secure this sensor using the supplied plastic clamp. It must be located in the Return Air Flow (Prior to mixing with any fresh air). Ensure that the Resin Sensor bulb is not covered by the protective vinyl-tube.

5-EN

Avoid positioning Sensor holders in the Drain Pan where they could be immersed in water.

Page 7: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

6

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

MM-DXV080 DX VALVE KIT

The PMV for this model is supplied as a brazed assembly, you may need to de-braze this in order to match the piping configuration of your DX Coil.

DX VALVE KIT

The supplied components need to be assembled on to the DX Coil locally. Note the PMV body MUST be water cooled whilst brazing.

The PMV Body must be installed upright (as shown).

The flow through the PMV Body can be in either direction, however the TC2 sensor must be fitted on the distributor side.

Example

6-EN

Page 8: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

7

SMMS DX Interface Installation Manual

4 ELECTRICAL WORK

7-EN

Cable size must be calculated for site condition and correct glands fitted. All cables should be in conduit or armoured cables correctly glanded. This has to be done by the site installer.

Page 9: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

8

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

8-EN

Page 10: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

9

SMMS DX Interface Installation Manual

9-EN

Page 11: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

10

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

ELECTRICAL CONNECTION Pulse modulation valve (PMV) The connecting cable of the PMV is to be attached as follows: Terminal 81 WHITE Terminal 82 YELLOW Terminal 83 GREEN Terminal 84 BLUE Terminal 85 BLACK Terminal 86 RED The PMV cable can be extended with a 6-core cable (cross-section 0.75 mm²) to a maximum of 5 m. Temperature sensors The refrigerant temperature sensors are inserted into the brazed sensor holders (There are 2 sizes of refrigerant Sensors: Ø4 & Ø6) and secured using the supplied FIX-PLATE (There are 2 sizes of FIX-PLATE). The sensor cables are to be attached as follows: Terminal 50/51 TC1 Sensor Ø4 Terminal 52/53 TC2 Sensor Ø6 Terminal 54/55 TCJ Sensor Ø6 Terminal 56/57 TA Resin Bulb Sensor (P-CLAMP) The sensor cables can be extended with a 2-core cable (cross-section 0.75 mm²) to a maximum of 5 m. External safety contact Terminal 9/10 If this contact is open for more than 1 minute, the error message P10 is generated and the ventilation kit switches off automatically. This contact can, for instance, be used with an onsite frost protection monitor. Inside device BUS line (U1/U2) Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found in the installation manual of the S-MMS outside device. Remote control BUS line (A/B) Terminal A / B At these terminals an optional remote temperature sensor (TCB-TC21LE2) can be attached. Additionally one of either a second wired remote control or alternatively the RBC-FDP3-PE BMS accessory can be optionally attached. Note that you cannot have both a second remote control and the BMS accessory. External release (optional) Terminal 1/2 On/off over an external dry contact. If the contact is closed, the system switches on. If the contact is opened, the system switches off. If the system is switched using and external contact, then switching on/off using the remote control is still possible. Operation monitor Terminal 3/4 An operation monitor (supplied locally), of the external fan is to be attached at this terminal as a dry contact (for instance, differential pressure monitor, vane relay or similar). A closed contact generates the error message L30. Alarm signal from the ventilation kit (optional) Terminal 5/6 If there is an error at the ventilation kit, this is indicated with a dry normally open contact at this terminal. Operation notification from the ventilation kit (optional) Terminal 7/8 During operation of the ventilation kit the dry contact between 7/8 is closed. Supply Terminal L/N/PE The controller should be connected to the main power supply by means of a switch with a contact separation of at least 3mm.

If the External safety contact is not used, then the contact should be bridged.

10-EN

Page 12: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

11

SMMS DX Interface Installation Manual

WIRING DIAGRAM

11-EN

Page 13: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

12

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

5 APPLICABLE CONTROLS

12-EN

Page 14: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

13

SMMS DX Interface Installation Manual

Model MM-DXC010 MM-DXV080

MM-DXC010 MM-DXV140

MM-DXC010 MM-DXV280

Cooling power in kW 5.6 7.1 8 11.2 14 22.4 28

Indoor unit capacity rank 18 24 27 36 48 72 96 Filter display Disabled (DN 01) 0000 0000 0000

Central Control address (DN 03) 0099* 0099* 0099* AUTO MODE Enabled (DN 0d) 0000** 0000** 0000** AUTO MODE Disabled (DN 0d) 0001** Default 0001** Default 0001** Default

HEAT PUMP (DN 0F) 0000** Default 0000** Default 0000** Default COOLING ONLY (DN 0F) 0001** 0001** 0001**

Device type (DN 10) 0006 0006 0006 Capacity Code (DN 11) 0009 0011 0012 0015 0017 0021 0023 Power address (DN 12) 0099* 0099* 0099* Device address (DN 13) 0099* 0099* 0099* Group address (DN 14) 0099* 0099* 0099*

Automatic restart (DN 28) 0001 0001 0001

* 0099 = address not assigned (system addresses are assigned during the automatic addressing by the system. Central addresses can be assigned automatically with a central remote control or manually. Subsequent modifications may lead to malfunction.)

** AUTO MODE Enabled / Disabled and HEAT PUMP / COOLING ONLY are automatically selected by the connecting Outdoor unit.

The circuit board of the ventilation kit is not preconfigured at delivery. Some parameters must be set using the DN code menu. Follow to the basic operation procedure (1 → 2 → 3 → 4 → 5 → 6).

DX Interface Configuration

13-EN

Page 15: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

14

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

6 TEST RUN

14-EN

Page 16: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

15

SMMS DX Interface Installation Manual

7 TROUBLE SHOOTING

Indoor Unit Power Code incorrect Check the settings of DN Code 11 (see “DX Interface Configuration”) Fan Motor operation monitor Check the operation monitoring of the fan at terminals 3/4. If this contact is closed, the error message L30 is generated. Safety contact error Check the contact at terminals 9/10. If contact is open, the error message P10 is generated.. If this contact is not used, a bridge should be installed on the terminals 9/10.

A detailed description of all check codes can be found in the Toshiba Service manuals.

L09

L30

P10

Common Check Codes

15-EN

Page 17: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

16

SMMS DX Interface Installation Manual

En

Fr

De

It

Es

Po

Ne

Ελ

RBC-FDP3-PE This is a monitoring and control interface for Toshiba VRF and Split ranges of air-conditioners. The interface is compatible with all units that have a TCC-NET A,B remote controller network connection. No other network adaptor cards are required even for split A/C units:- HARDWIRED CONTROL Unit control can be achieved through resistance inputs using potentiometer and volt-free contact inputs. BMS INTEGRATION Unit control can be achieved through 1-10V voltage inputs integrated with BMS control outputs. REMOTE CONTROLLER Facility to individually lock and remote controller buttons associated with unit control. RUN/FAULT Outputs Readback of all indoor and outdoor unit fault codes and unit run status. DUTY/STANDBY Run/standby rotation with run on fault and programmable rotation period. MODBUS RS485 Modbus Control and Monitoring Functions. CE APPROVED The unit is fully approved for sale in Europe.

For full details see the RBC-FDP3-PE installation instructions.

8 OPTIONAL PARTS

TCB-TC21LE2 Remote Temperature Sensor The Optional remote room temperature sensor uses the A/B Bus. It is connected to terminals A and B on the DX Controller (MM-DXC010). It is recommended where there is a High Ceiling, the TA sensor may not represent the temperature experienced by the occupants.

16-EN

Page 18: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

17

SMMS DX Interface Installation Manual

9 DECLARATION OF CONFORMITY

17-EN

Page 19: SMMS DX Interface Installation manual - toshiba … · 10 SERVICE PARTS ... to a Toshiba VRF ... Terminal U1 / U2 Details regarding the wiring of the inside device BUS can be found

18

SMMS DX Interface Installation Manual

10 SERVICE PARTS

Location No. Part No. Description Qty

001 RBC-AMT32E Wired Remote Controller 1

002 43158187 Transformer 1

003 4316V247 PC Board 1

004 4316V326 PC Board 1

005 43DX0001 Wing Nut 4

006 43DX0002 KP3 Relay (R2-230A) 1

43DX0003 KP3 Relay Base (R2-T) 1

007 43DX0004 KP1/KP2 Relay & Base 2

008

43DX0005 Electrical Terminal (Grey) 29

43DX0006 Electrical Terminal (Blue - Neutral) 1

43DX0007 Electrical Terminal (Grn. / Yel. - Earth) 2 009 43DX0008 White Indicator Lamp (AD56LT-W) 1

- Part No. Description Qty

101 43DX0009 Sensor (Ø4 - TC1) 1

102 43DX0010 Sensor (Ø6 - TC2 & TCJ) 2

103 43DX0011 TA Sensor 1

104 4314Q050 PMV Body (MM-DXV080) 1

105 43146723 PMV Body (MM-DXV140) 1

106 43146729 PMV Body (MM-DXV280) 1

107 43163030 Sensor Holder (Ø4) 1

108 43DX0012 Sensor Holder (Ø6) 2

109 43DX0013 Fix Plate Sensor (Ø4) 1

110 43019904 Fix Plate Sensor (Ø6) 2

111 43A63001 P-Clip 1

112 43147664 Strainer 2

113 43DX0014 PMV Motor Head (incl. Extension Lead) 1

AHU DX Valve Kit - MM-DXV080, MM-DXV140 & MM-DXV280

DX Controller - MM-DXC010