sita eng&commanual 4v14 26-0353-21

Upload: caiofrade

Post on 02-Jun-2018

465 views

Category:

Documents


58 download

TRANSCRIPT

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    1/64

    26-0353 Issue 21

    Fire Detection & Alarm System Control Panel V4.14

    Control Panel Engineering andCommissioning Instructions

    (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    2/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    2

    Fikes policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has beentaken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of suchcontents.

    Due to the complexity and inherent importance of a life risk type system then training on this equipment is essential, and commissioning should only becarried out by competent persons.

    Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation.

    E&OE.

    Fike equipment is protected by one or more of the following patent nos: GB2426367, GB2370670, EP1158472, PT1035528T, GB2346758,EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    3/64

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    4/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    4

    General Fault Finding . . . . . . . . 40Common Faults . . . . . . . 40Intermittent and Recurring Faults . . . . . 40Summary of Messages . . . . . . . 42

    Advanced Connections . . . . . . . 47Monitored Relays on MO4 and MO5 . . . . . 47Magnetic Door Hold Units . . . . . . 48Connecting Two Controls Panels Together . . . . 49Connecting More than Two Sita200plus Control Panels Together . . 50

    Technical Data . . . . . . . . 52Control Panel . . . . . . . . 52System Version Compatibility . . . . . . 53Resistor Colour Codes . . . . . . . 53Technical Support . . . . . . . 53

    Further Information . . . . . . . . 54Battery Calculations . . . . . . . 54Installation Checklist . . . . . . . 55Commissioning Checklist . . . . . . 56Loop Continuity and Insulation Test Results . . . . 57Fire Alarm System Notice . . . . . . 58Device Details . . . . . . . 60Zone Details . . . . . . . . 60

    Important Points . . . . . . . . 64 Back Page

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    5/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    5

    Introduction

    This Manual is intended as a guide to the engineering and commissioning principles of the Sita200plusAddressable Intelligent Fire Alarm and Detection system, and covers the system hardware information only.

    Due to the complexity and inherent importance of a system covering a Life Protection Risk, training on thisequipment is essential, and commissioning should only be carried out by competent and approved persons. Forfurther details of the availability of commissioning services contact your supplier.

    System Design

    This document does not cover Fire Alarm system design, and a basic understanding is assumed.

    A knowledge of BS5839: Pt 1: 2002 +A2: 2008 : Fire Detection and Alarm Systems for Buildingsis essential.

    It is strongly recommended that a suitably qualified and competent person is consulted in connection

    with the Fire Alarm System design and that the entire system is commissioned in accordance with thecurrent national standards and specifications.

    Equipment Guarantee

    The equipment carries no warranty unless the system is installed, commissioned and serviced inaccordance with this manual and the relevant standards by a suitably qualified and competent personor organisation

    Anti Static Handling Guidelines

    Immediately prior to handling any PCBs or other static sensitive devices, it is essential to ensure thata personal connection to earth is made with an anti-static wrist-strapor similar apparatus.

    Always handle PCBs by their sides and avoid touching any components. PCBs should also be storedin a clean dry place, which is free from vibration, dust and excessive heat, and protected frommechanical damage.

    Warning

    Do not attempt to install this equipment until you have fully read and understood this manual.

    Failure to do so may result in damage to the equipment and could invalidate the warranty.

    Technical support will not be available if the instruction manual has not been read and understood.Please have this instruction manual available whenever you call for technical support.

    For further technical support please contact your distributor. Do not call the Fike Safety Technologysupport department unless your distributor has first given their advice and attempted to rectify theissue.

    EMC

    This equipment when installed is subject to the EMC directive 2004/108/EC. It is also subject to UKStatutory Instrument 2006 No. 3418.

    To maintain EMC compliance this system must be installed as defined within this manual. Anydeviation from this renders the installer liable for any EMC problems that may occur either to theequipment or to any other equipment affected by the installation.

    !

    !

    !

    !

    !

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    6/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    6

    The Sita200plus System

    Types of Addressable System

    The Sita200plus is an addressable intelligent detector system, with many advantages over the traditionaladdressable analogue sensor systems. In order to understand the benefits we must differentiate between theterms Fire Detector and Fire Sensor. These terms are often used interchangeably but actually have quitedifferent meanings. A fire detector is the device (component as defined in EN54) which automatically detects afire. In the majority of addressable fire detection systems, the fire devices are in fact fire sensors which onlytransfer data relating to smoke and heat levels to the control panel, and the fire decision is made by the controlpanel.

    The majority of all current addressable systems are Addressable Analogue Sensor Systemswhere the controlpanel continually scans the fire sensors, processes the returned data, and makes decisions about fire and faultstatus.

    The Sita200plus is defined as an Addressable Intelligent Detector System, or an Addressable Fire Detectionand Alarm System with Independent Distributed Intelligence.Distributed intelligence signifies that the signalprocessing is spread throughout the system, in order that the decisions about fire and fault status are made withinthe detector itself. The detector is capable of being remotely programmed for different modes of detection in orderto suit the environment.

    Thus the Sita200plus system is an analogue addressable system, with the processing power distributedacross the entire system. This dramatically reduces the complexity of the control panel and the data traffic, andimproves the efficiency of the system.

    The system addressing is carried automatically upon initialisation from the control panel, and does not need to beprogrammed manually at each device.

    Advantages of Addressable Systems

    The nature of a microprocessor control system with individually identified devices means that the precise locationof fires and faults may be indicated, complex actions may be implemented, system flexibility is improved andinstallation and cabling costs are reduced.

    In the Sita200plus system, very efficient communications mean that very low quiescent power consumptionmaximises the standby capacity, high power transfer capabilities allow more sounders to be connected to theloop, and a very fast response to events is achieved as the control panel does not have to poll every device forstatus data.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    7/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    7

    Control Panel

    Mounting the Control Panel

    Firstly identify the proposed location for the control panel. Ensure that the control panel will be easily accessible,and that account is taken of any subsequent work that may affect access. It should be located at the most likelypoint of access for the fire services.

    The control panel should be mounted on a flat, vertical wall at a height where the indicators may be seen withoutdifficulty.

    Do not locate the control panel at high level where stepladders or other access equipment may berequired, in spaces with restricted access, or in a position that may require access panels to be removed.

    Do not locate the control panel where extremes of temperature or humidity may occur, or where there is

    any possibility of condensation or water ingress.

    Like all electronic equipment, the control panel may be affected by extreme environmental conditions. Theposition selected for its installation should therefore be clean and dry, not subjected to high levels of vibration orshock and at least 2 metres away from any pager or radio transmitting equipment. Ambient temperatures shouldbe within the range given within the Technical Data section, i.e., not directly over a radiator or heater.

    In common with all microprocessor-controlled panels, the control panel may operate erratically or may bedamaged if subjected to lightning induced transients. Proper earth/ground connections will greatly reducesusceptibility to this problem.

    General Assembly

    POWER SUPPPLY

    AND MAIN FUSE

    BACK BOX

    2 x 12V 3.2AH SLA

    Yuasa NP3.2-12

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    8/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    8

    Physical Dimensions

    The control panel back box is designed as a Surface Mount unit. The 14mm flange provides a shadow foraesthetic purposes. To allow installation of the main front moulding, this flange must not be recessed into themounting surface.

    Power Supply Unit

    The Fire Alarm Panel 230V AC supply requires fixed wiring between 0.75 mm2and 2.5 mm

    2, a 3 Amp fused un-

    switched spur with local isolation, to be terminated into the fused terminals provided in the top left hand corner ofthe back box and to be suitably differentiated / protected from the low voltage cables in the control panel. Themetal cover, which is held in place with a locking nut, protects these terminals. The mains supply should bededicated to the Fire Alarm Panel and should be clearly labelled FIRE ALARM: DO NOT SWITCH OFF at all

    isolation points.

    The standby requirements are for 2 x 12v 3.2 Ah sealed lead acid batteries to be installed. These are to be sited inthe control panel back box in the enclosure provided along the bottom edge, with the terminals facing forward andoutwards (to left/right respectively). This is important to ensure that the battery terminals do not put any pressureon the main PCB, which could happen if the terminals were bent out at an angle. The batteries should beconnected in series using the connection leads supplied. See the section entitled Summary of Panel Terminals forpanel connections. We recommend the use of type Yuasa NP3.2-12 (FR) or other equivalent approved type.

    Note that batteries are electrically live at all times and great care should be taken to ensure that the terminals arenever presented with a short circuit. Care should be taken at all times, especially during transit, installation andnormal use. Use caution as there is a risk of explosion if the batteries are replaced by an incorrect type.

    Batteries no longer required should be disposed of in a safe and environmentally friendly manner by themanufacturer or a suitable recycling service. They should never be incinerated or placed in normal rubbishcollection facilities. Dispose of used batteries according to the instructions.

    Version 4v11 panels onwards use a 230V AC to 32V DC switched mode power supply. A 230V AC to 40V ACtransformer was utilised on control panels up until V4.00.

    FOOTPRINT TO WALL

    Incoming mains supplyfuse housing

    Power Supply housing

    Power Rating Label

    2 x 12V 3.2 Ah SealedLead Acid batteries

    Knockouts at topand rear

    AC/DC connection

    cables

    Battery connectioncables

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    9/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    9

    Topology & Cabling

    All Fire Detection and Alarm System wiring should be installed to comply with BS 5839: Pt1: 2002 and BS 7671(wiring regulations) and any other standards relevant to the area or type of installation. A cable complying with BS

    5839: Pt1: 2002 Category 1 (cables required to operate for prolonged periods during fire conditions) and BS7629:Pt1: 1997 (incorporating Amendment Nos 1 & 2, Specification for 300/500V fire resistant electrical cables) isrequired. This must be a 2-core 1.5mm

    2screened fire resistant cable (ie., MICC, FP200, Firetuff, Firecell, Lifeline

    or equivalent). Ventcroft No Burn multicore cable was utilised during the LPCB approval testing).

    The addressable circuit must be installed as a loop with a maximum length of up to 2 km. Addressablespur circuits are NOT permitted with this system.

    In order to protect against possible data corruption it is important ensure the following points are adhered to:

    1. The cable screen must be connected to the loop SCRN terminal at the control panel. Both endsmust be connected using the terminals provided.

    2. The cable screen must not be connected to earth/ground at any point other than the control panel, ie,do not connect the screen to a device back box.

    3. The cable screen continuity must be maintained at every point of the loop, using the terminalsprovided or a suitable connection block.

    4. Do not use a 4-core cable as a loop feed & return due to the possibility of data corruption. It isessential that two 2-core cables are used if this is required.

    5. Excess cable lengths must not be coiled as this will increase the inductance and causecommunication problems.

    Cable Specification

    Capacitance Core to Screen . . . . 180pf / m

    Capacitance Core to Core . . . . 100pf / m

    Inductance . . . . . . 1.0mH / Km

    Resistance Two Core Screened 1.5mm . . . 12.1 / Km

    Fire Proof . . . . . . BS5839: Pt1: 2002 Category 1

    Example . . . . . . Datwyler 8700

    Refer to the following System Wiring Schematic for further details.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    10/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    10

    System Wiring Schematic

    The following schematic may prove useful as an aid to understanding the cable requirements for the system;

    Sita MultiPoint Sita Multipoint I/O Sita Loop I/O Module

    Sita MCP Remote Indicator

    SITACONTROL

    PANEL

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    11/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    11

    Loop Loading

    In order to allow a method of calculating the maximum loop loading that the system will support, each device hasa rating assigned in Device Loading Units (DLUs). A maximum of 450 DLUs are permissible on the loop. Thisrelates to the load presented in alarm.

    The Sita OSP programming software automatically keeps control of the quantity and will provide prompts if thelimits are reached.

    PRODUCT DESCRIPTION DLU RATING

    TypeProductCode

    Subtype SP0-Off Low Medium High

    203 0003 Multipoint MK3 1 - - -MP

    205 0003 ASD MK2 1 - - -

    203 0001 Multipoint with Sounder MK3 1 1.5 4.5 6

    205 0001 ASD with Sounder MK2 1 1.5 4.5 6MPS

    205 0012 ASD with Sounder/Strobe MK2 4 4.5 7 9

    803 0003803 0005

    Multipoint I/O Module (in Relay Base)Multipoint I/O Module (in Box)

    3 - - -ANCILLARY

    600 0092 Remote Indicator 0.5 - - -

    MCP 403 0002 Manual Call Point MK2 3 - - -

    MCPS 403 0012 Manual Call Point with Sounder MK2 3 3.5 5.5 7

    313 0001313 0002313 0003

    Soundpoint MK2 1.5 2 4 5.5

    323 0001 Hipoint MK2 1.5 2 4 5.5

    303 0013 Bell MK2 2 22 22 22

    303 0012303 0022

    Flashpoint 1.5 4.5 6.5 8

    SOUNDER

    326 0021 NEW Sounder/Strobe 5 5.5 6.5 7.5

    I/O 803 0006 Loop I/O Module MK2 10.5 - - -

    CZM 803 0010 Conventional Zone Module (Ext PSU) 23.5 - - -

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    12/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    12

    Control Panel Connection Schematic

    Control Panel Terminals and Fuses

    Power In PSU+, PSU-, EARTH

    The DC input to the main PCB is connected to the red and black leads coming from the switch mode powersupply mounted within the back box, and is the primary power supply for the system. This input is protected by the3AT fuse labelled F4 3AT POWER.

    Note: Control panels up to V4.11 do not use a switch mode power supply, but instead utilise a 230V AC to 40VAC transformer, with yellow wires connecting to terminals marked TA and TB.

    Terminal DescriptionPSU+ Power Supply Low Voltage DC +ve: 32V DC InPSU- Power Supply Low Voltage DC ve: 0V DC InEARTH Mains Supply Earth

    Z30

    + -- E + --BATTERY 24V

    C NC NO SPR + -- SCRN C NC NO SPR + -- SCRN +24V 0V + -- SCRN + -- SCRN + -- SCRN + -- SCRN + -- SCRN

    CONTRO

    LPANELPCB

    LCD CONTRASTVR1

    F4 3AT POWER F3 3AT BATTERY F5 200mAF AUX PWR F2 200mAF OUTPUT4 F1 200mAF OUTPUT5

    3K3 EOL

    N/OCONTA

    CT

    FIRERESIS

    TOR

    680R

    3K3 EOL

    N/OCONTA

    CT

    FIRERESIS

    TOR

    680R

    10K EOL 10K EOL

    1

    3

    52

    6

    4230V AC

    L N E

    SWITCHMODEPSU

    MOUNTEDINBACK

    BAT 1

    + -

    BAT 2

    + -

    Z31

    Z31Z30

    ....................

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    13/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    13

    Mains Input: L, N, E

    The 230V AC input is to be connected into the mains supply connection terminals provided in the back box. Thisinput is protected by a 3.15AT fuse (1500A breaking, 250V rated).

    Terminal DescriptionL Main Supply Live 230V AC LiveE Mains Supply EarthN Mains Supply Neutral 230V AC Neutral

    Battery Connections BAT+, BAT-

    The battery terminals require 24v from 2 x 3.2Ah sealed lead acid batteries, connected in series, in order toprovide secondary backup power when the primary power fails. This input is protected by the 3A fuse labelled F33AT BATTERY.

    Note that the charging circuit will be in its high impedance state (approximately 3V DC) if no batteries, faultybatteries or only one battery is connected. The full 27V DC charging voltage should be present if the correctbatteries are connected.

    If the system shows a charger or battery fault on first power up, leave the system to charge its batteries for 5-6hours.

    In order to test for correct operation of the batteries, remove the mains 230V AC fuse and allow the batteries tosettle from their charging voltage for approximately 5 minutes. The battery voltage should then be measured usingan electronic test meter and a voltage in the region of 27V DC should be seen.

    Note that batteries are electrically live at all times and great care should be taken to ensure that the terminals arenever presented with a short circuit. Care should be taken at all times, especially during transit, installation andnormal use.

    Batteries no longer required should be disposed of in a safe and environmentally friendly manner by the batterymanufacturer or a suitable recycling service. They should never be incinerated or placed in normal rubbishcollection facilities.

    Terminal DescriptionBAT + Battery positive: 24V DC +veBAT - Battery negative: 0V

    BAT --BAT +

    MAIN PCB BATTERIES

    RED

    EARTH

    BLACK

    -- +

    12V BATTERY

    -- +

    12V BATTERY

    BACK BOX BLUE & BROWN TO SWITCH MODE POWER SUPPLY, GREEN/YELLOW TO MAIN PCB VIA EARTH

    GREEN/YELLOW

    BLUE

    BROWNEARTH

    LIVE

    NEUTRAL

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    14/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    14

    Relay 1 COM1, NC1, NO1, SPR1

    Relay 1 consists of a volt-free change-over relay contact which is not fault monitored. The relay contacts arerated at 30VDC / 2A max. The following options may be selected using SitaOSP:

    1. Not configured (relay will not operate).2. Common fire output (relay energised in fire).3. Fire alarm signal output, monitored by input 1 (MI1+, MI1-) (relay energised in fire).

    Terminal DescriptionCOM1 Common contactNC1 Normally closed contactNO1 Normally open contactSPR1 Spare terminal for general use. Not connected internally.

    Relay 2 COM2, NC2, NO2, SPR2

    Relay 2 consists of a volt-free relay contact and is not fault monitored. The relay contacts are rated at 30VDC /2A max. The following options may be selected using SitaOSP:

    1. Not configured (relay will not operate)2. Common fire output (relay energised in fire).3. Common fault output (relay de-energised in fault).4. Fault signal output, monitored by input 2 (MI2+, MI2-) (relay de-energised in fault).

    Terminal Description

    COM2 Common contactNC2 Normally closed contactNO2 Normally open contactSPR2 Spare terminal for general use. Not connected internally.

    COMMON

    NORMALLY OPENNORMALLY CLOSED

    SPARE

    MAIN PCB FIELD CONNECTIONS

    COMMON

    NORMALLY OPENNORMALLY CLOSED

    SPARE

    MAIN PCB FIELD CONNECTIONS

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    15/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    15

    Input 1 MI1+, MI1-, SCRN

    Input 1 may be configured to monitor for open and short circuit faults using a 3K3 EOL resistor, and to activate analarm link to detection-zone 30 using a 680R firing resistor. The zone description will be displayed along with therelevant zone indication LED. The following options may be selected using SitaOSP;

    1. Not configured.2. Remote fire input: Latching (control panel will require manual reset).3. Common fire signal fault input

    4. Remote fire input: Non Latching (control panel will reset when trigger removed).

    Terminal DescriptionMI1+ Monitored Input positive connectionMI1- Monitored Input 0V connectionSCRN Field cable screen connection

    Input 2 MI2+, MI2-, SCRN

    Input 2 may be configured to monitor for open and short circuit faults using a 3K3 EOL resistor, and to activate analarm link to detection-zone 31 using a 680R firing resistor. The zone description will be displayed along with therelevant zone indication LED. The following options may be selected using SitaOSP;

    1. Not configured.2. Remote fire input: Latching (control panel will require manual reset).

    3. Common fault signal fault input.4. Remote fire input: Non Latching (control panel will reset when trigger removed).

    Terminal DescriptionMI2+ Monitored Input positive connectionMI2- Monitored Input 0V connectionSCRN Field cable screen connection

    MI1-

    MI1+

    SCREEN

    MAIN PCB FIELD CONNECTIONS

    3K3EOL

    SCREEN680R

    N/O CONTACT

    FIRE RESISTOR

    Note: Input 1is assigned to detection zone 30

    MI2-

    MI2+

    SCREEN

    MAIN PCB FIELD CONNECTIONS

    3K3EOL

    SCREEN680R

    N/O CONTACT

    FIRE RESISTOR

    Note: Input 2is assigned to detection zone 31

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    16/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    16

    Auxiliary Power: +12V, 0V, SCRN

    An auxiliary 24v DC constant power supply is available if required. In order to protect battery standby and alarmtimes, this output is limited to 200mAwith the fuse labelled F5 200mAF AUX PWR. Additional remote PowerSupply Units should be installed to provide power for any additional load.

    Terminal Description+24V Aux power positive connection0V Aux Power 0V connection

    Output 4 - MO4+, MO4-, SCRN

    Output 4 may be configured to monitor for open and short circuit faults with a 10K EOL resistor, and to beactivated with a stage 3 alarm to alarm-zone 30. The following options may be selected using SitaOSP;

    1. Not configured (circuit will not operate of monitor for fault).2. Sounder output (switches off on silence alarm).3. Remote Fire output (switches off on reset).

    This output is protected by the 200mA fuse labelled F3 200mAF OUTPUT 4

    Terminal DescriptionMO4+ Monitored Output positive connectionMO4- Monitored Output 0V connection

    SCRN Field cable screen connection

    OV

    +24V

    MAIN PCB FIELD CONNECTIONS

    24V DC LOAD

    MO4-

    MO4+

    SCREEN

    MAIN PCB FIELD CONNECTIONS

    +

    -

    +

    -10KEOL

    SCREEN SCREEN

    Note: Output 4is assigned to alarm zone 30

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    17/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    17

    Output 5 MO5+, MO5-

    Output 5 may be configured to monitor for open and short circuit faults with a 10K EOL resistor, and to beactivated with a stage 3 alarm to alarm-zone 31. The following options may be selected using SitaOSP;

    1. Not configured (circuit will not operate of monitor for fault).2. Sounder output (switches off on silence alarm).3. Remote Fire output (switches off on reset).

    This output is protected by the 200mA fuse labelled F4

    Terminal DescriptionMO5+ Monitored Output positive connectionMO5- Monitored Output 0V connectionSCRN Field cable screen connection

    Addressable Circuit LE1+, LE1-, SCRN, LE2+, LE2-, SCRN

    The addressable circuit must be connected to the Loop End 1 and Loop End 2 terminals. Communicationsnormally run from Loop End 1, but in the event of a continuity fault both ends of the circuit will operate.

    It is important that the cable screen is only connected to the loop SCRN terminal in the control panelat eachend, and that the screen continuity is maintained at all times. We recommend against the use of a 4-core cable as

    a loop feed & return due to the possibility of data corruption.

    Terminal Description Detector BaseLOOP END1+ Circuit End 1 positive connection: +VE OUT / LOOP + OUTLOOP END 1 - Circuit End 1 0V connection : 0V OUT / LOOP 0VSCRN Field cable screen connection: E / SCRNLOOP END2+ Circuit End 2 positive connection: +VE IN / LOOP + INLOOP END 2 - Circuit End 2 0V connection : OV IN / LOOP 0VSCRN Field cable screen connection: E / SCRN

    MO5-

    MO5+

    SCREEN

    MAIN PCB FIELD CONNECTIONS

    +

    -

    +

    -10KEOL

    SCREEN SCREEN

    Note: Output 5is assigned to alarm zone 31

    END1-

    END1+

    SCREEN

    MAIN PCB FIELD CONNECTIONS

    SCREEN

    END2+

    END2-

    SCREENSCREEN

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    18/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    18

    Fuses

    The fuses are located below the control panel terminals.

    Label Description FuseF1 Output 5 F200mAF2 Output 4 F200mAF3 Battery T3AF4 DC Input Power T3AF5 Auxiliary 24V Power F200mA

    LCD Contrast

    The LCD contrast may be adjusted by rotating the screw on the variable resistor located adjacent to the fuses.This may require many (10 to 20) rotations if the contrast is particularly out of adjustment.

    LCD CONTRASTVR1

    Rotate anticlockwiseto reduce the

    contrast (lighten text)

    Rotate clockwise toincrease the contrast

    (darken text)

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    19/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    19

    Access Level 1 (Normal)Shift LED off

    Access Level 2 (User)Shift LED on

    Access Level 3 (Engineer)Shift LED flashing

    General Operation of Control Panel

    Control Panel Front

    Soft Key Menus

    For ease of use, a context driven menu system is used to control access to the system. Soft keys (softwareallocation of button function) are used to pilot around the menu system, automatically prompting you with therelevant options for your Access Level and system status.

    The lower line of the display is arranged in the following format:

    [DISPLAYon] [testDISP] [AL2 CODE] [->nextMENU]

    Each section (eg., [AL2 CODE]) represents the function of the button immediately below on the keypad.

    The high frequency voltage that is required for the backlight may cause the display to emit a slight humming tonewhilst the LCD back-light is on. This is merely a feature of the technology required in the system and will ceasewhen the backlight switches off.

    Access Levels

    The system menus are set into three access levels as follows. For simple indication the status of the shift LEDwill show the level selected as follows;

    System Status

    Keypad

    Detection ZoneFire Indication

    LCD informationdisplay

    Fault and delay status

    ADDRESSABLE FIRE ALARM 4V14

    PROGRESSIVE FIRE SYSTEMS LTDFOR SERVICE CALL 01234 567890

    [DISPLAYon][testDISPLAY][AL2 CODE][nextMENU]

    ADDRESSABLE FIRE ALARM 4V14

    PROGRESSIVE FIRE SYSTEMS LTDFOR SERVICE CALL 01234 567890

    [DISPLAYon] [testDISPLAY] [AL2 CODE] [nextMENU]

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    20/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    20

    AL1 (NORMAL) >WARNINGs

    >DISABLEs

    >FAULTs

    Display current warnings

    Display current disablement

    Display current faults

    >TESTs Display current testsTestDISP Test LEDs and LCD

    AL2 CODE Go to Access Level 2 (User)

    Access Codes

    Access to the system menus requires the correct entry of the access level 2 (User) or access level 3 (engineer)code in order to protect against unauthorised access to the system. These codes default to the settings below but

    may be altered from the Sita OSP software.

    Access Level 2 Code - 222Access Level 3 Code 333

    As the upload and download of system information to the Sita OSP software must take place within access level 3(engineer) then programming may only be carried out by authorised personnel with the correct access level 3(engineer) code. If the access level 3 (engineer) code is not known then upload and download will not be possible.Contact your supplier in this event.

    Access Level 1 (Normal)

    Warning Status

    The >warnings function causes the control panel to display any current warnings. One point shows at atime and continuing to press the >warnings prompt button allows the messages to be scrolled through,one at a time.

    Disablement Status

    The >disables function causes the control panel to display any items which are disabled. One pointshows at a time and continuing to press the >disables prompt button allows the messages to be scrolledthrough, one at a time.

    Test Status

    The >tests function causes the control panel to display any test modes which are current. One pointshows at a time and the continued pressing of the >tests prompt allows the messages to be scrolledthrough, one at a time.

    Fault Status

    The >faults function causes the control panel to display any items which are in fault. One point shows ata time and the continued pressing of the >faults prompt allows the messages to be scrolled through, oneat a time.

    Display On

    The backlight for the system LCD display switches off after a period of time if the controls are not used.Whilst the backlight is switched off, the prompt DISPLAYon is displayed. The backlight will switch on ifthis function is selected or if any button is pressed.

    Test Display

    The TestDISP function causes the panel LEDs to pulse and the LCD to blacken in order that their correctoperation may be verified.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    21/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    21

    AL2 Code

    The AL2 CODE function enables access to Access Level 2 (user level). This is followed by a code entryprompt, so you will need to enter the code (default 222).

    Access Level 2 (User)

    Zone Disable / Enable

    This function allows the disablement or enablement of a detection-zone. Thus, all the input devices(Manual Call Points, detectors and inputs) within that detection-zone will be disabled. The control panelwill indicate that disablements are present, the device LED will still operate when activated and an eventwill be recorded to log, but no programmed actions will occur. The sounder within the device will stilloperate if triggered from elsewhere on the system. More than one detection-zone may be disabled at thesame time, and they may be viewed under the DISABLEs

    >FAULTs

    Local Audible Test

    Ends test modes

    Time and date setting

    Advance time by 1 hr

    Retard time by 1 hr

    Go to Access Level 1 (Normal)

    Test LEDs and LCD

    Go to Access Level 3 (Engr)

    Display current warnings

    Display current disablement

    Display current faults>TESTs Display current tests>EVENT log Display event log

    >INDICATE

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    22/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    22

    Fire Protection Outputs (Relay Outputs) Disable / Enable

    This function allows the global disablement or enablement of all the outputs on the system that areprogrammed for common or remote fire. The control panel will indicate that disablements are present,

    and they may be viewed under the

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    23/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    23

    Test Display

    The testDISP function causes the panel LEDs to pulse and the LCD to blacken in order that their correctoperation may be verified.

    AL3 Code

    The AL3 CODE function enables access to Access Level 3 (engineer level). This is followed by a codeentry prompt, so you will need to enter the code (default 333).

    Warnings

    Certain system warnings will be displayed upon the selection of this function. These warnings are of anon-critical nature, such as a low level optical fault. If the condition becomes more serious then it will bedisplayed as a fault at the control panel.

    Disablement Status

    The >disables function causes the control panel to display any items which are disabled. One pointshows at a time and the continued pressing of the >disables prompt allows the messages to be scrolledthrough, one at a time.

    Fault Status

    The >faults function causes the control panel to display any items which are in fault. One point shows ata time and the continued pressing of the >faults prompt allows the messages to be scrolled through, oneat a time.

    Event Log

    The event log stores 255 fire and fault events. These are displayed in text format and may be scrolledthrough by pressing the prompt.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    24/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    24

    Access Level 3 (Engineer)

    System Initialisation

    The function initLOOP is available from within the engineer menu and enables the control panel toperform its addressable circuit initialisation or automatic addressing and interrogation sequence. It startsthis process from Loop End 1, collects data on device type, position & serial number, and allocates aDevice Address. A new system will initialise with defaults of SM2, HM2, SP3, Medium Volume, Device Xlabel and Zone 32.

    Stop Loop

    The function stopLOOP is available from within the Engineer menu it performs a complete shutdown ofthe processors in each loop device. To avoid causing a processor crash it is important to stop the loopbefore removing power. If this occurs it will be manifest by random faults and stoppages duringinitialisation. To clear this problem, power the control panel down for approximately five minutes. On re-powering the system the crashed processor should reboot successfully.

    Start Loop

    This function may be termed Fast Initialise and is only suitable for use if the panel has not been powereddown and no devices have been altered in any way. If startLOOP fails then stop the loop and use theinitLoop function.

    Get Config / Re Config

    The control panel processor memory holds all the system configuration and programming details. Certainaspects such as device description, zoning and cause & effect are operated from that point. However,the individual device attributes such as smoke mode, heat mode, sound pattern and volume are stored inthe control panel, and need to be sent to the processor within the device to be operational. This is carriedout with the reconfig command, which sends out all the relevant data to the loop devices. The get configoperates in the reverse, collecting the configuration from the loop to be stored at the control panel.

    Note that the system should always be re-configured after a PC download from Sita OSP, and then thesystem should be reset using the reset button.

    Exit AL3

    The Exit AL3 prompt returns the control panel to Access Level 1 (Quiescent).

    From Access Level 2 (user) Restart an unmodified loopAL3 CODE startLOOP

    stopLOOP Shutdown loop

    initLOOP

    getCONFIG

    reCONFIG

    exitAL3

    OSP mode

    EDIT

    FIND DEV

    SYS TEST

    Autolearn loop and readdress

    Get configuration from devices

    Send configuration to devices

    Go to Access Level 1 (Normal)

    Select OSP mode for upload

    Edit device text

    Turn LED and sounder on

    Auto reset test mode

    # NODES

    RPT mode

    Show no. of devices in last init

    Select Repeater mode

    DIAG mode Select Diagnostic mode

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    25/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    25

    OSP Mode

    The system will only allow an upload or a download to the OSP software programming package when thestopLOOP function has been operated followed by pressing the OSPmode button. When any

    up/downloading has been completed then the loop may be restarted using the startLOOP command

    Edit

    Device descriptions and auxiliary zone descriptions may be programmed directly from the control panelusing this function. Upon selecting the device, the keypad may be used to set the required text. The shiftkey may be pressed (indicated by a fast flash of the shift LED), to allow access to Upper Case letters andthe forward/back keys. When the description is correct press the key marked Enter.

    Find Device (FIND DEV)

    This function activates the sounder and the LED in the device if they are present. Options are thenpresented as follows: [ QUIT ][ findPREV][findNEXT][ENTER NO].

    System Test (SYS TEST)

    The SYS test function allows the entire system to operate in a simple one-man walk test mode. Ontriggering a device the device LED operates, the event is recorded into the event log, all the assignedsounders operate for 10 seconds and the control panel indicates an alarm. After approximately 10 secondthe system will silence & reset the system, and another may be tested.

    To end this test mode simply exit from Access Level 3 (Engineer).

    Please note, with the system test mode, only the sounders assigned to operate from that device willsound, and any delays will still be present. Ie., if a delay of 2 minutes is present, the system will have beenreset before the sounders activate.

    Number of Nodes (# NODES)

    This function will display the number of nodes (devices) that the control panel found when it was lastinitialised. It is important to note that this may not be the current number of devices running on the system,if any devices are missing.

    Repeater Mode (RPT MODE)

    This function will cause the remote-bus PC/RPT LINK to restart its repeater mode of operation. Thesystem will interrogate the circuit and display if a repeater panel is found.

    A maximum of one repeater panel may be connected to the circuit.

    Diagnostic Mode (DIAG MODE)

    This function will cause the remote-bus PC/RPT LINK to restart its diagnostic mode of operation, toenable use of the Sita Diagnostic software.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    26/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    26

    LED Indication

    The operation of the LED indication on the front of the control panel is described below.

    Description Colour State Reason

    1. POWER Green Continuous

    Flashing

    This indicates that power is being supplied to thecontrol panel from either the 230V AC mains supply,or the standby batteries.

    The 230V AC mains supply has been removed.

    2. FIRE Red Flashing The control panel is in the fire state. Other indicatorswill show the origin

    3. FAULT Amber Flashing The control panel is in the fault state. Otherindicators will show the origin

    4. SYSTEM FAULT Amber Continuous The system Fault LED indicates the presence of aprocessor or a checksum error. Power the systemdown to clear, reprogram all settings and test thesystem.

    5. FIRE SIGNAL ACTIVE Red Flashing A monitored output programmed to operate as aFire Signal Transmission Output has beenactivated. Reset the system after removing thecause of the activation to clear it.

    6. FIRE SIGNAL FAULT /DISABLED

    Amber Flashing

    Continuous

    A monitored output programmed to operate as aFire Signal Transmission Output is in the fault state.

    A monitored output programmed to operate as aFire Signal Transmission Output has been disabled.

    7. DISABLED Amber Continuous This indicates that a disablement action is in place.Enable all devices / actions to clear.

    8. TEST Amber Continuous This indicates that a test routine is in place. End alltests to clear.

    9. POWER FAULT Amber Flashing Either a battery supply / charger fault has beendetected (check the fuse and the battery voltages) ,or a mains supply fault has been detected (check fora 24V AC supply on the PCB Ac terminals).

    10.

    EARTH FAULT Amber Flashing An earth fault has been detected where a path existsfrom the circuit wiring to earth. Remove circuits oneat a time to discover which one, and then rectify.

    11

    .

    LOOP FAULT /

    DISABLE

    Amber Flashing

    Continuous

    A fault condition is present on the addressable

    device loop, or one of the addressable devices.

    A device or an action associated with theaddressable device loop has been disabled

    12.

    SOUNDER FAULT /DISABLE

    Amber Flashing

    Continuous

    A fault condition is present on a monitored soundercircuit or on the addressable device loop sounders.

    A device or an action associated with the monitoredsounder circuits or addressable sounders has beendisabled.

    13.

    FIRE PROT / DISABLE Amber Flashing

    Continuous

    A fault condition is present on a monitored Relaycircuit or on the addressable device loop outputs.

    A device or an action associated with the monitored

    relay circuits or an addressable output has beendisabled.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    27/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    27

    14.

    FAULT SIGNAL FAULT /DISABLED

    Amber Flashing

    Continuous

    A monitored output programmed to operate as aFault Signal Transmission Output is in the faultstate.

    A monitored output programmed to operate as aFault Signal Transmission Output has beendisabled.

    15.

    OUTPUTS DELAYED Amber Continuous An action has been started which utilises aprogrammed delay.

    17.

    ZONE 1-32 Red Flashing

    Continuous

    A Manual Call Point in the zone indicated is in thealarm state and sending an alarm signal to thepanel.

    A Detector in the zone indicated is in the alarm stateand sending an alarm signal to the panel.

    18.

    SHIFT Amber Off

    Continuous

    Flashing: Slow

    Flashing: Fast

    The control panel is at Access Level 1 (Normal). It isactive and the user controls are disabled.

    The control panel is at Access Level 2 (User). It isactive and the user controls are enabled.

    The control panel is at Access Level 3 (Engineer). Itis active and the user controls are replaced with theengineer controls.

    The control panel is at Access Level 3 (Engineer) ina text entry mode, uppercase / < / > are selected.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    28/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    28

    Smoke is detected inone room of an

    apartment

    All the sounders inthat zone will sound

    for set time

    The sounder in thatdetector will sound

    for 30 seconds.

    If smoke disappears,all sounders will

    silence automaticallywithin set time

    The sounders in alinked zone will

    sound for set time

    i.e., care taker

    If the smoke is stillpresent the sounderswill continue to sound

    as above.

    If there is no smoke in theroom between

    predetermined time and 10min

    The above process willcontinue for a predetermined

    time (1-7.5 Minutes).If smoke is detected after

    this time, and up to 10minutes from the start.

    If at any time duringAlarm-Confirmation, a

    second detector detectssmoke.

    FULL ALARMOr any required actions programmed.

    The alarm is reset automaticallyand only the occupant in one

    apartment is disturbed

    If a call point or heat detector is activatedbefore, during or after the AlarmConfirmation

    then the system will activate the alarms

    4 OPTIONS TO CHOOSE

    1 2 3 4

    SMOKE CLEARS SMOKE REMAINS

    SMOKE CLEARS

    SMOKE REMAINS

    !

    The display mayshow an optional

    warning showing the

    location of incident.

    Alarm Confirmation Technology

    Alarm Confirmation Technology (ACT) is the process whereby a smoke detector may be configured to issue alocalised warning in specific regions, prior to sounding a general alarm. This is generally of great benefit in

    dwelling areas where smoke, steam or cooking fumes may trigger a Multipoint detector.

    The following drawing demonstrates some of the possibilities:

    This function affects the smoke detector only, and operates before the control panel enters the Fire state. Thus,the system Cause & Effect does not need to be adjusted, as Alarm Confirmation takes place before theprogrammed Cause & Effect sequence is reached.

    In order to activate this function, install the devices as normal and refer to the Sita OSP Programming Manual forfurther details. These functions require the use of a PC and it is not possible to use them without.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    29/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    29

    Alarm Confirmation Delay

    The Alarm Confirmation Delay timer allows an automatic reset of an unconfirmed alarm from a smokedetector.

    When a smoke detector using Alarm Confirmation is activated, the sounder within that device (or all the soundersin the zone) will activate with the sound pattern selected for Alarm Stage 1 (Alarm Confirmation). This warningsound may also be copied to any additional zone, and may also be displayed on the control panel if required.

    At the end of the Alarm Confirmation Delay time the system will check the detector again to see if the activationhas cleared. If so then the device will reset and no further action need be taken.

    The sounder operates during the chosen Alarm Confirmation Delay time, and stops for the final 20 seconds,during which time the device is reset to check for further smoke presence.

    During the Alarm Confirmation Delay, the activation of an additional smoke detector into Alarm Confirmationwillcause the delay time to cease and an instant alarm to be generated.

    If, however, the detector is still in alarm then the entire system will go into alarm, operating all the soundersprogrammed in the Cause & Effect area.

    For a further time period (10 min minus Alarm Confirmation Delay), the activation of the smoke detector will causean immediate alarm (depending on the programming of the system Cause & Effect).

    The activation of any Heat detector (even in the same device as the smoke detector in Alarm Confirmation)generates an immediate alarm (depending on the programming of the system Cause & Effect).

    Selecting the Devices

    Any smoke detectors which are to utilise Alarm Confirmationmust be selected using the Sita OSP programmingsoftware. Smoke detectors not selected will operate in a standard manner (depending on the programming of thesystem Cause & Effect).

    An Alarm Stage 1 (Alarm Confirmation)sound pattern must also be selected, and this may be set to a differentsound pattern to that chosen in Alarm Stage 3 (Evacuate) in order to provide and audible difference betweenalarm stages.

    The activation of any smoke detector set for Alarm Confirmation causes the sounder within that device only tooperate (or across the entire zone if required), but no indication shows on the control panel. This warning soundmay also be copied to any additional zone, and may also be displayed on the control panel if required.

    The activation of any Heat detector (even in the same device as the smoke detector in Alarm Confirmation)generates an immediate alarm (depending on the programming of the system Cause & Effect).

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    30/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    30

    Commissioning

    Installation 1stStage

    The installer needs to install the system wiring in the form of a 2-core and screen loop returning to the controlpanel. Addressable spur circuits are not permitted with this system.

    The cabling should be 2-core 1.5mm2, screened and fire resistant, of an MICC or FP200 equivalent type. We

    recommend against the use of a 4 core cable as a loop feed and return, due to the possibility of data corruption.See the section on Loop Topologyfor further details.

    The loop should be left as a complete loop with no devices connected, and must be tested and documented forconductor continuity and for insulation integrity, with a high voltage tester (using the shorting links provided withineach base to provide continuity in the positive core), as required for general electrical installations.

    The control panel back box should be mounted, with the mains supply tested, connected and isolated at the un-switched fused spur, ready for the commissioning engineer.

    The installer needs to provide a set of As-Wireddrawings, completed configuration sheetsand proof of loopcontinuity and insulation test readingsetc., to enable commissioning to proceed. This information is essentialfor commissioning and programming to proceed, and may be entered onto the forms provided at the rear of themanual.

    Installation 2ndStage

    Once the commissioning engineer is satisfied with the continuity / integrity of the loop, the devices may beinstalled (noting the serial numbers adjacent to the device address on the configuration sheets).

    NB/Ensure that the next section, Initialisation, is read and understood before the devices are installed.

    Initialisation

    The addressable device loop may now be initialised. This is when the control panel interrogates the loop onedevice at a time, for type, serial number and position, before allocating a loop address number. Initialisation iscarried out from the control panel keypad by utilising the [initLOOP]command located within the Access Level 3(Engineer) menu.

    Install one device (and note its serial number as normal), as near to the control panel as possible and initialise thesystem. If initialisation fails the problem may be tracked quickly, and if needs be the device is easily removed tofacilitate further high voltage testing. If the device appears to be at fault then try another Electronics Module andreinitialise. If this has no effect, then check terminations carefully and inspect the connector carefully for damage.

    Further to this a common fault on installations utilising existing cabling is the omission to remove old incompatibledevices. Once the system is initialised and happy with its one device then proceed as below.

    Add the rest of the devices in batches of 10-25, initialising each time to prove correct operation. If a fault is found,or initialisation fails, then the relevant batch of devices may be partially removed and added in smaller numbersuntil the problem is tracked.

    There is no need directly to initialise in sections in this manner, but we recommend this method as goodengineering practice to provide a controlled process of building up the system in sections.

    The system can only indicate faults present when the loop is fully initialised. If the initialisation fails then you willneed to find faults manually. You may run the initialisation backwards by reversing the loop connections, or oneended by removing one end of the loop. You may also use the SitaOSP software to identify which devices havebeen found and initialised. Noting how far the device count on the control panel screen reached will indicate many

    faults, such as open or short circuit. Further more the sounders may be operated from the control panel to indicatewhich devices are operational, or the LEDs may be switched on using the Sita Diagnostic software.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    31/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    31

    Commissioning

    Commissioning the Sita 200plus involves programming and testing the system.

    Whilst the software may be pre-configured before arriving at site if required (from the as-wireddrawings and theconfiguration sheets),it is generally simpler and quicker if the site configuration is uploaded and altered directlywhilst still on site, as the system will have found much of its configuration upon initialisation.

    If the configuration is written before upload from the control panel, then the software is termed a New file, anddoes not contain all the loop information required (which the control panel acquires on initialisation). This may thenbe merged on site to give a full configuration file termed an Old file.

    A comparison of serial numbers between the drawings/config sheets and the OSP upload is alwaysrecommended to prove the actual device order as opposed to the assumed device order.

    Normally, commissioning will take place as follows:

    1. Initialise the addressable device loop.2. Stop the addressable device loop, select OSP mode at Access Level 3 (Engineer) and Upload the

    configuration from the control panel to the PC with Sita OSP.3. Check that the addressable device serial numbers are in the position on the loop that was expected,

    amend the configuration to suit the site and check it carefully.4. Download the configuration from the PC to the control panel.5. Start or initialise the loop.6. Reconfigure the addressable devices with the [ReConfig] command at Access Level 3 (Engineer).7. Reset the system8. Test for correct operation.

    When the system is correctly programmed then it must be tested for correct operation. It is important to rememberthat a Walk Test mode is a service tool and not a commissioning tool, as the complete cause and effect of the

    system is not tested. Thus the Zone Test functions located at Access Level 2 (user) should not be used forcommissioning a system.

    The System Test function located within Access Level 3 (Engineer) is suitable for commissioning, as it allows thecontrol panel to be completely activated as normal. However it is recommended that a new system iscommissioned live, with all sounders active in order to prove correct operation of every device whenever a systemis programmed in any other way than a simple One off, all off configuration.

    It is essential that every device is tested in every mode of operation, and that all programmed actions areobserved for correct operation. This includes the smoke testing of smoke detectors, heat testing of heat detectors,testing of Manual Call Points, testing of all inputs, testing of all sounders and outputs, and fault testing of detectorsby head removal.

    We also recommend that all devices, which are set to heat only, are tested for smoke operation, to ensure thatthe smoke detection has been correctly disabled.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    32/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    32

    Configuration Example

    From your As-Wired drawings deviceaddresses can be assigned, starting from

    circuit end 1.

    From this the device attributes may befilled out on the configuration sheets, asshown in the following example.

    DEVICE

    ADDRESS

    SERIAL

    NUMBER

    DEVICE DESCRIPTION (24

    CHARACTERS MAX)

    ZON

    E

    DEVICE

    TYPE

    SMOKE

    MODE

    HEAT

    MODE

    ALARM

    CONFN

    1 212 Shop Floor: Main Entrance 1 MCP - - -

    2 30960 Staff Area: Rear Lobby 1 MPS SM2 HM2 -

    3 213 Staff Area: Rear Exit 1 MCP - - -

    4 30962 Staff Area: Kitchen 1 MPS SM0 HM2 -

    5 30963 Shop Floor: Rear 1 MP SM2 HM2 -

    6 30961 Shop Floor: Front 1 MPS SM2 HM2 -

    These details may then be entered into the SitaOSP programming software in order to program the operation ofthe system. See the additional SitaOSP Software Operating Instructions for further details.

    End User Training

    A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in thebuilding do not know how to operate and respond to the system. It is therefore essential that commissioningincludes training for the users of the system and responsible persons.

    User instructions and a Zone Chart should be left adjacent to the control panel. As access to the system must becontrolled by responsible persons, so it would be unusual to display the access codes on this notice. These codesmust however be available for the responsible persons, so ensure that they are notified correctly.

    The Sita200plus User Guide should be explained and left with the responsible person on site, for storage in anaccessible and known location, in order that the responsible person and the service engineer may keepinformation records up to date.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    33/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    33

    Good Practice

    The following suggestions are good practice if carried out during commissioning, and may help avoid commonproblems at a later date. The Fike Safety Technology Technical Support department may be unable to assist if the

    information is unavailable, and the guidelines not followed.

    Number of Devices

    Make a clear note in the control panel back box in a conspicuous position of the number of devices on the system.

    In the event of any future visits to site it will be clear how many devices are expected if the system is initialised.Without knowing this it is not possible to be sure that all devices have initialised correctly, ie.,

    Label the Loop Ends

    Make a clear note on the Loop cables adjacent to the terminal block to show LOOP END 1 and LOOP END 2.

    Thus, if the addressable device loop is reversed for any reason it will be plainly visible from the labels.

    Note the Loop Readings

    Make a clear note in the control panel back box of the loop continuity and insulation resistance readings, includingthose for the screen and mains earth.

    These are then available for fault finding at a later date, ie.,

    OUTPUT 5 + -- SCRNPC / RPT LINK

    + -- SCRNLOOP END 1

    + -- SCRNLOOP END 12

    LOOP

    END 1

    LOOP

    END 2

    END

    1

    END

    2

    Date +/+ -/- Scr/Scr +/- +/Scr -/Scr Earth/Scr Engineer23/04/04 9.7 9.6 6.3 OL OL OL OL J Williams

    31/04/05 10.3 10.2 6.4 OL OL OL OL T Roberts

    Date No of devices Engineer

    23/04/04 96 J Williams31/04/05 103 T Roberts

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    34/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    34

    Configuration Printout and Drawings

    Make a Text Reportprintout of the system configuration from Sita OSP and store it safely on site along with anup to date site plan marked with devices, serial numbers and wiring order.

    If any return visits are necessary all the relevant information on the system will be available without having to carryout an Upload of data to the PC. This includes address, serial number, device configuration and zonalconfiguration data.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    35/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    35

    Initialisation

    Loop Connections

    The schematic below shows a simplified site connection drawing to illustrate how each core of the circuit isconnected. The following fault scenarios are shown in detail to help gain an understanding of the procedure to findthem.

    Normal Readings

    Ensure that your addressable device loop has the correct continuity and insulation integrity. With an electronic testmeter there should be a continuity reading of approximately 1.2 ohms per 100m of 1.5mm

    2cable, and at least 1M

    ohm insulation resistance between cores.

    With the loop stopped and the loop connector block removed from the control panel, measure the continuitybetween Loop End 1 ve and Loop End 2 ve.There should be a maximum resistance of approximately 24ohm, equating to approximately 1.2 ohms per 100 metre.

    Likewise measure the continuity between Loop End 1 Screen(SCRN)and Loop End 2 Screen (SCRN).Thereshould be a maximum resistance of approximately 24 ohm, and this reading will normally be slightly lower thanthat of the Loop ve continuity, due to the greater surface area of the screen. Screen integrity is of criticalimportance.

    SCRN SCRN

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    36/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    36

    A measurement of the continuity between Loop End 1 +ve and Loop End 2 +ve should show a very highresistance, as the isolator within each device only provides continuity when energised by the control panel.

    Measuring the insulation resistance between the Loop ve and the Loop Screen should show a very highresistance preferably OC between cores. Remember that a low voltage electronic test meter should be used, andits accuracy is likely to be low when measuring high resistances, but this will give enough information to showinsulation integrity.

    Do not use a high voltage insulation test meter whilst any devices or the control panel are connected asthey may suffer damage.

    Initialisation

    When the Control panel is powered up the following LEDs will be continuously on, and the addressable deviceloop must be initialised at Access Level 3 (Engineer).

    DISABLED and LOOP FAULT/DISABLE

    In normal initialisation conditions the control panel will start from Loop end 1, find, interrogate and address eachdevice on the loop one at a time.

    Control Panel version number

    Stage of initialisation

    Devices initialised so far

    When the second end of the loop is reached the control panel will display one of the following messages toindicate whether or not a complete loop was found.

    Loop continuity ok

    No loop continuity.

    Finally the control panel will investigate any spur connections from Multipoint detectors. Spurring was a feature inearlier panels and devices which allowed up to 5 devices to be spurred from a multipoint detector over a 20mdistance (total). The overall maximum permissible cable distance of 2km for an addressable circuit included both

    the main loop and any such spur runs and up to 5 spur runs were permitted on the system. This feature is nolonger supported in current panels and devices. Even though spurs are no longer supported, the devices are stillchecked as part of the initialisation process for the presence of spurs. If the panel finds any spurs during this

    ADDRESSABLE FIRE ALARM 4V14 26/05/02 12:44** FIKE SAFETY TECHNOLOGY LIMITED **FINAL TEST DATE 20/05/02

    Please wait, initialising main loop 4[startLOOP] [stopLOOP] [initLOOP] [NEXTmenu]

    ADDRESSABLE FIRE ALARM 4V14 26/05/02 12:44** FIKE SAFETY TECHNOLOGY LIMITED **FINAL TEST DATE 20/05/02

    Loop complete, checking spurs 12

    [startLOOP] [stopLOOP] [initLOOP] [NEXTmenu]

    ADDRESSABLE FIRE ALARM 4V14 26/05/02 12:44** FIKE SAFETY TECHNOLOGY LIMITED **FINAL TEST DATE 20/05/02

    Loop not complete, checking spurs 12[startLOOP] [stopLOOP] [initLOOP] [NEXTmenu]

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    37/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    37

    process, then even if initialisation has completed, the loop should be stopped and the spurred devices rewired intothe main loop.

    When all possible devices have been initialised the control panel will display one of the following messages:

    Complete circuit initialised ok, ensure thatthe number of devices shown is correct.

    The following LEDs will be extinguished (as long as no other faults exist).

    DISABLED and LOOP FAULT/DISABLE

    Or:

    The control panel was unable to establishcontinuity, but those devices found arecorrectly initialised.

    The following LEDs will remain on:

    DISABLED and LOOP FAULT/DISABLE

    Initialisation Faults

    Loop +ve to ve Short CircuitLoop +ve Open Circuit

    If the system faces a Loop +ve to ve short circuit, or a Loop +ve open circuit during initialisation, theinitialisation will fail at that point and a message of Loop not completewill be displayed.

    All devices up to that point will be operational, but devices beyond will not be active, the control panel willnot initialise from Loop End 2 as it becomes very difficult to understand fully where the problem lies.

    The faults list [>faults] in Access level 2 (User) will display messages accordingly. These messages needto be viewed together as a complete set. The control panel cannot determine the location of a shortcircuit, so a short circuit message will be followed by the location of the open circuit which is created whenthe isolator in that device responds to the short circuit.

    Eg., Loop s/c and Loop o/c at device X

    Thus in the Loop +ve to ve short circuitexample shown previously, the initialisation will reach device 1and fail thereafter. Thus the problem is after that point.

    An investigation of the next device (device2) will determine if a correct loop voltage of approximately 40VDC has reached that point. If this has happened then the problem lies in either the connections at thatpoint (device 2) or a faulty electronics module (device 2).

    If the correct loop voltage of approximately 40V DC is not present at the next device (device 2) then stopthe loop and investigate the device before (device 1). The problem may be due to an incorrect connection,a cable fault or a faulty electronics module.

    ADDRESSABLE FIRE ALARM 4V14 26/05/02 12:44** FIKE SAFETY TECHNOLOGY LIMITED **FINAL TEST DATE 20/05/02

    Circuit initialised: 43 nodes[startLOOP] [stopLOOP] [initLOOP] [NEXTmenu]

    ADDRESSABLE FIRE ALARM 4V14 26/05/02 12:44** FIKE SAFETY TECHNOLOGY LIMITED **FINAL TEST DATE 20/05/02

    Initialisat ion failed, Loop not complete 43[startLOOP] [stopLOOP] [initLOOP] [NEXTmenu]

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    38/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    38

    If it is suspected that a device electronics module is faulty then try linking that device out (link the +vecores together) and reinitialising the loop. If the initialisation then passes that point the device may bereplaced. It is not advisable to leave a system with a device missing (positive cores linked together) in this

    way as all future points will be displaced.

    Please note: A short circuit between cores with a value of between 3K and 300 ohm can cause corruptionof the data on the loop and although no Short Circuit fault is reported the system integrity will becompromised.

    Loop ve Open Circuit

    If the system faces a Loop ve open circuit during initialisation, the initialisation will not fail at that point,but continue as normal to the end of the loop. All devices will be operational (as long as no other faultsexist).

    A message of Addressable circuit: -ve open circuit will be displayed, but the control panel cannot

    detect where the open circuit fault is located.

    In order to locate the fault position, stop the loop, disconnect Loop end 2 and reinitialise the system. Theinitialisation will fail at that point and a message of Loop not completewill be displayed.

    Thus in the Loop ve open circuitexample shown above, the initialisation will reach device 2 and failthere. Thus the problem is after that point.

    An investigation of the next device (device 3) will determine if a correct loop voltage of approximately 40VDC has reached that point. If this has happened then the problem lies in either the connections at thatpoint (device 3) or a faulty electronics module (device 3).

    If the correct loop voltage of approximately 40V DC is not present at the next device (device 3) then stop

    the loop and investigate the device before (device 2). The problem may be incorrect connection, a cablefault or a faulty electronics module.

    If it is suspected that a device electronics module is faulty then try linking that device out (link the +vecores together) and reinitialising the loop. If the initialisation then passes that point the device may bereplaced. It is not advisable to leave a system with a device missing (positive cores linked together) in thisway as all future points will be displaced.

    Device Faults

    If the system detects a device fault or fire activation during initialisation, the initialisation will not fail atthat point. All devices will be operational (as long as no other faults exist).

    However, the system can only ignore a certain amount of fire or fault data until initialisation is complete,and beyond certain limits initialisation will fail and the various fault or fire activations will be displayed.

    In either case, the event generated should be dealt with before the loop is reinitialised.

    Firstly, investigate and rectify any Fire activations which are displayed. These may vary from Manual CallPoints which have not been reset, to Multipoint detectors which are contaminated.

    Secondly, investigate and rectify any fault conditions which are displayed. These may vary from Inputopen circuit, to a Multipoint detector with it optical chamber loose (indicating signal low).

    The system may then be reinitialised and commissioned as required.

    Please note: A short circuit between cores with a value of between 3K and 300 ohm can cause corruptionof the data on the loop and although no Short Circuit fault is reported the system integrity will becompromised.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    39/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    39

    Earth Faults

    General

    If the control panel detects a short circuit to earth/screen from one of its supply rails (either 0v or +ve) anEarth Faultwill be displayed.

    Remove the circuit cables connected to the control panel one at a time and reset the system. When thecircuit with the earth fault is disconnected, the earth fault will clear within approximately 30 seconds ofbeing reset.

    Note that some computers will generate an earth fault at the control panel, depending on their transformerconfiguration.

    A short circuit (low resistance: expected to be less than 5k ohm) may be identified and tracked with anelectronic test meter between either the positive core or the negative core and the screen of that circuit.

    It is not possible to override the earth fault monitoring as it is important for correct system operation.

    If it is shown that the earth fault is on the addressable device loop, then disconnect it from the controlpanel and investigate it with an electronic test meter.

    Loop ve to Earth

    If the fault is a short circuit from earth/screen to loop vethen it will be easily identified and rectifiedwith an electronic test meter.

    An investigation of the resistance reading between loop ve and earth/screen at the control panel for each

    end of the addressable device circuit should give a good indication of the location of the short circuit.

    Eg, if the resistance reading at Loop end 1 were 9 ohm, and at Loop end 2 were 3 ohm then it may beestimated that the short circuit lay approximately 9/(3+9) = of the way round the addressable devicecircuit from Loop end 1. Investigating that area, and introducing a split to the Loop ve as required, willallow it to be tracked and rectified.

    Loop +ve to Earth

    If the fault is a short circuit from earth/screen to loop +ve then it will only be identified with anelectronic test meter at that individual length of cable due to the inbuilt short circuit isolators in eachdevice.

    To locate this manner of fault, split the +ve core of the loop at approximately a half way point on the loop,then reinitialise with only Loop End 1 connected to the control panel.

    Even though the initialisation will fail due to the enforced open circuit, the earth fault will only be indicatedif it is located within the section of the cable which was initialised. The split may then be reinstated inanother position and the process continued, until the section of the system suspected of containing theearth fault is small enough to allow each portion of cable to be individually tested with an electronic testmeter.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    40/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    40

    General Fault Finding

    Common Faults

    In the event that inexplicable or random faults continue after any obvious indication has been dealt with, take thefollowing steps.

    1. Verify that the addressable device loop cable readings are suitable. Take particular note of thescreen resistance and rectify any faults found. Ensure also that there is no connection from thescreen to earth in the building other than at the relevant terminals at the control panel.

    2. Ensure the correct number of devices has been initialised by checking the prompt [# nodes]atAccess Level 3 (Engineer) for the number of devices found on the last initialisation, and comparethat with the number of devices on the system.

    3. Ensure that Loop End 1 and Loop End 2 are connected correctly and not running in reverse.

    4. Reconfigure the addressable devices using the [reconfig] prompt at Access Level 3 (Engineer),then reset the system and test it.

    5. Check all devices for loose connections, broken copper connecting strips in the connector, brokenconnector bodies.

    Intermittent and Recurring Faults

    1. Smoke Sensor Failed Signal High

    Ensure that the correct device is being investigated by comparing its description with thedevice address, and / or the serial number.

    Ensure that the Optical Chamber is clean, if not then replace it with a new one and allow it tore-calibrate. See the sections on Self Calibration and Replacing Contaminated OpticalChambers for further details.

    If the problem still exists consider changing the electronics module.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    41/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    41

    2. Loop Open Circuit

    If random or recurrent Loop O/C faults are reported then check the entire system for thefollowing:

    Loose connections. Ensure all terminals are reasonably tight.

    Broken Connectors.If the terminal is over-tightened the main body of theconnector may become broken, causing an intermittent open circuit.

    Broken or missing copper connecting strips (Multipoint only not ASD). Theconnection from the connector body to the pin which links to the Multipoint detectoris made by the copper connecting strip which may be seen entering the connectorwith the cable. Ensure that these are not broken off or bent out of place as this willcause an intermittent open circuit.

    Broken cables. Ensure that the cables are not snapped off before they enter the

    connector.A cable may seem to be connected, but not actually make a contact.

    Trapped insulation. Ensure that the cable insulation is not trapped in theconnector, stopping it from making a connection.

    The entire system should be carefully checked for the above, as a cumulative effect maytake place if a number if high resistance connections are present, causing random reportingof the location of the problem.

    3. Device(s) Lost.

    If no obvious causes are apparent then replace the device.

    Please note: A short circuit between cores with a value of between 3K and 300 ohm can causecorruption of the data on the loop and although no Short Circuit fault is reported the system integritywill be compromised.

    IMPORTANT NOTE

    When cable faults occur, the loop MUST BE STOPPED manually and the faults investigated andrectified before re-initialising the loop again. Do not attempt to rectify a cable fault or to removeand/or reinsert devices into a live loop.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    42/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    42

    Summary of Messages

    1. 1stFIRE: xxxx If more than one fire event is present on the system, then the first of those will be displayedon the top line eg, 1stFIRE: zXX SMOKE: DeviceDescription

    2. Addressable circuit fault A fault conditions exists on the addressable device circuit (loop). Additional fault messagesshould indicate the nature of that fault condition. The loop must be re-initialised to clear thisfault.

    3. Alarms silenced The ALARMS OFF button has been pressed whilst the sounders were operating, and theyhave been silenced.

    4. Alarms sounded The ALARMS ON button has been pressed whilst the sounders were not operating, and theyhave been activated.

    5. AUX input This refers to an input device located in the loop. This would relate to the auxiliary input at thedetector, and to the Loop I/O module.

    6. AUX input in alarm The auxiliary input at a detector or a Loop powered I/O module is in the alarm state. Resetthe triggering input to that device before resetting the control panel.

    7. AUX input open circuit An auxiliary input at a detector or a Loop powered I/O module is in the open circuit state.Check that the 3k3 EOL resistor is fitted, or that the EOL switch is turned on, but not both.Check also that all cables are correctly connected and that the circuit is complete.

    Note. Even if the auxiliary I/O is set to its output state, it still monitors its input circuit for EOL,and this is still reported as relating to the AUX input.

    8. AUX input short circuit An auxiliary input at a detector or a Loop powered I/O module is in the short circuit state.Check that the 3k3 EOL resistor is fitted, or that the EOL switch is turned on, but not both.Check also that all cables are correctly connected and that the circuit is complete and notpresenting a short circuit to the input.

    Note. Even if the auxiliary I/O is set to its output state, it still monitors its input circuit for EOL,and this is still reported as relating to the AUX input.

    9. AUX I/O input active The auxiliary input at a detector or a Loop powered I/O module is in the alarm state. Resetthe triggering input to that device before resetting the control panel.

    10. AUX output short circuit An auxiliary output is in the short circuit state. Check that the EOL resistor is fitted, or that theEOL switch is turned on, but not both. Check also that all cables are correctly connected andthat the circuit is complete and not presenting a short circuit to the input.

    11. Battery charger failed A fault has been detected in the battery charger circuitry. Ensure that the battery connectionsare making a good connection and that the fuse is securely clamped. If possible check thebatteries with an intelligent battery tester, or replace them with a new set to see if the faultclears.

    12. Battery failed A fault has been detected in the standby batteries. Ensure that the battery connections aremaking a good connection and that the fuse is securely clamped. If possible check thebatteries with an intelligent battery tester, or replace them with a new set to see if the faultclears.

    13. Battery restored A fault detected in the standby batteries has been cleared.

    14. C.i.e. Control and Indicating Equipment, ie, control panel.

    15. C.i.e. interfaces fault A fault condition has been detected at one of the control panel monitored inputs or outputs.Additional fault messages should indicate the nature of that fault condition.

    16. C.i.e. fault A fault condition has been detected at the control panel. Additional fault messages shouldindicate the nature of that fault condition.

    17. Circuit initialised : xxxxnode

    The addressable circuit has been correctly initialised and xxxx devices have been correctlyinitialised. Check that the number of devices found matches the number of devices on thesystem.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    43/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    43

    18. Circuit low resistance A low resistance has been detected between the +ve and the ve core of the circuit.

    This has not yet developed into a measurable short circuit, but steps should be taken torectify the condition before it worsens. Introducing a split into the loop and then initialisingfrom one end only will help to identify the location of the problem. The loop must be re-initialised to clear this fault.

    19. Commissioning mode The system has been set into the Access Level 3 Engineer system test mode.

    Operation of a detection device will allow the system to operate as programmed, but thesystem will then insert a silence and reset action after approximately 10 seconds.

    Simply exit from Access Level 3 Engineer to end this test mode.

    20. Complete loop found The addressable circuit has been correctly initialised. Check that the number of devices foundmatches the number of devices on the system.

    21. Configuration Data Error The control panel has detected a database anomaly. The system may be working, but theproblem should be dealt with immediately.

    Ensure that the system has been correctly programmed using Sita OSP, and then reconfigurethe loop devices and reset before testing for correct operation.

    22. Detection head The detection head is the optical sensing chamber for the Multipoint detector.

    23. Detection head removed The Optical Chamber has been removed from a multipoint detector.

    24. Device disabled The device has been disabled and will not operate.

    25. Device failed The device has detected a failure in its processing circuitry or memory and must be replaced.The loop must be re-initialised to clear this fault.

    26. Device(s) lost The device is not reporting to panel on it Poll Presence Count. The loop must be re-initialised to clear this fault.

    27. Earth fault The control panel has detected a short circuit to earth from one of its supply rails (either 0v or+ve).

    Remove the circuits connected to the control panel one at a time and reset the system. Whenthe circuit with the earth fault is disconnected, the earth fault will clear within approx 30seconds of being reset.

    A short circuit (low resistance expected less than 5KR) may be identified and tracked with anelectronic test meter between either the positive core or the negative core and the screen ofthat circuit.

    It is not possible to override the earth fault monitoring as it is important for correct systemoperation.

    28. Exit AL3 to end The function selected may be ended by exiting from Access Level 3 Engineer.

    29. FIRE 01:xxxx If more than one fire event is present on the system, when the list of those events isdisplayed, the fire event number will be displayed, ie, 01 = 1

    stfire event, 04 = 4

    thfire event.

    30. Fire protection output (G)disabled

    Any outputs assigned as Fire Protection outputs (firePROT or Remote Fire) are disabled.

    These will be relays or monitored outputs (but of course they could be assigned to othergroups, ie to operate as sounders).

    31. Head The detection head is the optical sensing chamber for the Multipoint detector.

    32. Heat detector in alarm The heat detector at a multipoint detector is in the alarm state. Check that device beforeresetting the control panel.

    33. Heat sensor failed (OC) A Multipoint detector has detected an open circuit in its thermistor circuitry.

    As this circuit is important even for the operation of the smoke detection modes, the deviceshould be replaced.

    34. Heat sensor failed (SC) A Multipoint detector has detected a short circuit in its thermistor circuitry.

    As this circuit is important even for the operation of the smoke detection modes, the deviceshould be replaced.

  • 8/10/2019 Sita Eng&ComManual 4V14 26-0353-21

    44/64

    Sita200plus Control Panel Engineering and Commissioning Instructions

    44

    35. Heat sensor fault cleared A fault previously detected with a multipoint detector has cleared.

    Check in the event log to see if it is occurring regularly, and if so change the device.

    36. Initialization failed: loopnot complete

    Whilst initialising the addressable device loop, the control panel was unable to sense acomplete loop from Loop End 1 returning to Loop End 2.

    Stop the loop and reinitialise to ensure repeatability, then investigate the last device found(shown on the display during initialisation) and the following device. If no faults can be foundtry temporarily linking out that device to see if initialisation will pass that point, thus the devicemay need replacing.

    37. Initialization stopped atdevice xxxx

    Whilst initialising the addressable device loop, the control panel was unable to sense acomplete loop from Loop End 1 returning to Loop End 2.

    Stop the loop and reinitialise to ensure repeatability, then investigate the last device found(indicated by xxxx) and the following device. If no faults can be found try temporarily linkingout that device to see if initialisation will pass that point, thus the device may need replacing.

    38. Loop complete, checkingspurs

    Whilst initialisation, the control panel was able to sense a complete loop from Loop End 1returning to Loop End 2. Although this system does not currently support spurs the panel willcontinue to check for their presence.

    39. Loop initialised The addressable circuit has been correctly initialised. Check that the number of devices foundmatches the number of devices on the system.

    40.