SIPROTEC 5 - NewApplications for GridProtectionGeorg Korger, Head of DepartmentProtection

siemens.at/future-of-energyUnrestricted © Siemens AG Österreich 2017

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 2 Korger / RC-AT EM DG PRO PRT

Wind or PV(private)

Storage

Dieselgenerator

Microgrid

E-mobility

Smart buildings

Heatstorage

Onshorewind

Large-scale PVinstallation

Storage(gas, liquids)

Biomass

Cogeneration

GasdistributionPower to value

(gases, liquids,chemicals,)

Gas transport

Offshore wind farm

Onshore wind farm

Gassupplier

Gas plant

Districtheating(cooling)

Grid controlcenter

Hydropowerplant

Buildings,computer centers,nanogrid

Transformer

Substation SubstationFossil-fuel powerplant

Reliable detection and safe isolation of faults in electrical powersystems are the objectives of power system protection

§ Line infeed through distributedgeneration in distribution grids

§ Unpredictable renewables§ Volatile and higher utilization of

transmission & distribution capacity –need for resilience

Challenges§ Increased use of directional O/C and

tele-protection in distribution grids§ Enhanced supervision and active

control of power system status, assetsand protection parameters duringoperation

Measures

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 3 Korger / RC-AT EM DG PRO PRT

Innovation is a must for power system protection in orderto meet current and future requirements of the power system’sevolution

Wind or PV(private)

Storage

Dieselgenerator

Microgrid

E-mobility

Smart buildings

Heatstorage

Onshorewind

Large-scale PVinstallation

Storage(gas, liquids)

Biomass

Cogeneration

GasdistributionPower to value

(gases, liquids,chemicals,)

Gas transport

Offshore wind farm

Onshore wind farm

Gassupplier

Gas plant

Districtheating(cooling)

Grid controlcenter

Hydropowerplant

Buildings,computer centers,nanogrid

Transformer

Substation SubstationFossil-fuel powerplant

§ Protection schemes used in transmission grids move to distribution level§ More efficient and higher utilization of powers systems have impact on protection§ More advanced and performant applications through Information and Communication Technologies

Trends

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 4 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5Devices and Fields of Application

Busbar protection7SS85

Motor protection7SK8

Bay controller6MD8

Fault recorder7KE85

Breaker management7VK8

Distance protection 7SA8

Line differential protection 7SD8

Transformer differentialprotection 7UT8

Overcurrent and feederprotection 7SJ8

Combined line differential &distance protection 7SL8

Generator protection7UM85

- Modularly designed hardware- Flexible and modularly designed software- High-performance engineering tool DIGSI 5

Wide product range for every application and requirement: Generation – Transmission – Distribution – Industry & Infrastructure

PMU

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 5 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 is the answer to trends and customers’ challenges

New features :

§ New functionalitiesEarth fault detection, Protection datainterface, redundancy protocols,arc flash protection, voltage controller,impedance protection,reactance method, PMU function, etc.§ Fast GOOSE communications§ Cyber security§ New technologies

(travelling wave, …)§ Process bus§ Future Requirements can be integrated

due to flexibility of the system(FW version)

Resulting Challenges for Customers

§ More selective investments

§ CAPEX vs. OPEX optimization

§ Increasing cost pressure

With SIPROTEC 5 –the most complete protection portfolio -and its multifunctional capability ourcustomers save expenditures inengineering, operation and service

Customer Value Proposition

SIPROTEC 5§ Is modular scalable§ Offers the most complete

functionality§ Offers the highest

flexibility

Differentiation

New features:

• Ensuring reliability & availability ofenergy with new challengesesp.Renewable integration which§ threatens grid stability§ increases complexity of grid

management

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 6 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – New Solutions with Protection Data InterfaceFast fault clearance in double-feed MV lines / Interlocking

Direction comparison with PDI

§ Automatic switch over from ring to chainconfiguration

§ Highly available Communication§ Applicable for

§ Protection functionalities§ Interlockings

§ Directional DMT/IDMTL protection withoutgrading times

§ Fast fault clearance§ Low-cost due to integrated protection

interface§ Monitored data exchange§ Adaptable to different communication

infrastructures

+

+

+

+

+

Interlocking with PDI

+

+

+

7SJ82

PDICommunication

PDI Communication

7SJ82

67 PDI

7SJ827SJ82

67 PDIPDI 67 PDI 67

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 7 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Earth fault detection60% of faults are earth faultsReliable detection – essential in transmission and distribution

Energy Distribution networks10/20/30/110kV

SIPROTEC 5

Full parallel operation of different methods§ Increase of reliability§ Saving costs§ Saving engineering efforts

Advantages of different methods in one device

Star point treatment often compensated

§ Different methods with different devices

Transient function Watt-metric function Other methods Directional intermittedfunction

Network sturcture

§ radial

§ Closed ring

§ meshed

Fault type

§ static

§ transient

§ intermittent (Cable fault)

Fault resistance level

§ Low (<50 Ω)

§ med. (<3000 Ω)

§ High (>3000 Ω)

Watt metric Transient Harmonics

All in One

till now

with SIPROTEC 5

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 8 Korger / RC-AT EM DG PRO PRT

Harmonics 3rd

SIPROTEC 5Earth fault detection – All Advantages in one Device

SIPROTEC 5

Harmonics 7th

Watt metric

Transient function (digital)

Harmonics 5th

Signalization of earth fault direction to control centerusing a priority scheme (user defined CFC)

Combination of Advantages of several methods inone device

§ High sensitivity20 x more compared to former algorithms

§ Detection of§ High impedance / ohmic faults§ Very short ground faults§ Static faults

Advantages

Best qualified for meshed networks and others

Unified clear use of devices

Cost efficient

+

+

+

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 9 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Adaptive ProtectionRemote control of protection settings through IEC 61850

Problem:Protection settings & thermal limitsare calculated for worst case conditionsà This leads to too restrictive limitsduring >90% of the year

Solution:Adapt settings automatically:à This leads to increased limits during >90% of the yearà This enhances the capacity of the transmissionsystem without building new lines

How is this done:Adapted settings are calculated on control center levelbefore changes of the short circuit currents. The newsettings are then loaded into all protection relays usingIEC61850

1 2 3 160

Control Center

10-40 devices 10-40 devices 10-40 devices 10-40 devices

grid transmission capacity

Today‘s reservedue to fixed limits

Grid capacityused today

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 10 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Arc ProtectionImproved Protection Functionality and personel Safety

Flash over between the poles or to earthed partsSevere risk for personal and equipment

§ Danger for personnel§ Damage of equipment

SIPROTEC 5 relays offer in addition to the base functionsthe possibility of installing optical sensors

§ traditional feeder protection§ detect arc flashes

in order to bypass the time grading of the overcurrentprotection in case of a real arc.High temperatures of ~ 10.000 ºC cause smelting,vaporizing and destruction of the different materials.

The destruction starts after:§ ~ 100 ms: cable sealing ends§ ~ 150 ms: copper§ ~ 200 ms: steel

BushingsConnection

compartment Contact system

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 11 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Arc ProtectionProtection of Air-insolated MV-Switchgears

Incoming

Binary signal / GOOSE

Feeder 1 Feeder 2

CB compartment

Cable connectioncompartment

Optical sensors(line or point)

Busbarcompartment

SIPROTEC 5§ Feeder protection§ Arc protection

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 12 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Arc ProtectionProtection of Air-insolated MV-Switchgears

Optical Arc Detection for SIPROTEC 5 using communication:

Instantaneous tripping in case of arc flashlight + current: ~4ms + contactBypass of time grading of O/C protectionIncreased safety against unwanted tripsMinimized damages of equipmentIncreased safety for personellOne module per feederOne device for feeder protection and arc flash

+

+++++

Incoming

Binary signal / GOOSE

Feeder 1 Feeder 2

CB compartment

Cable connectioncompartment

Optical sensors(line or point)

Busbarcompartment

SIPROTEC 5§ Feeder protection§ Arc protection

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 13 Korger / RC-AT EM DG PRO PRT

Transformer Protection – Classical ConceptMultitude of Devices

110kV

20kVTransformer Differential

Protection

Distance Protection

O/C Protection as backup forTransformer Differential Protection

Transformer Regulator

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 14 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Transformer Protection ConceptIntegrated Voltage Regulation and multiple Functionality

110kV

20kV

Distance Protection

O/C or Distance Protection as backupfor Transformer Differential

Protection

Transformer Regulator

Transformer DifferentialProtection

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 15 Korger / RC-AT EM DG PRO PRT

Automatic Voltage Control of Transformers with SIPROTEC 5From Single to Parallel Operation

§ Function available with version 7.50 (07/2017)

§ Required voltage regulator for transformerparallel operation§ Protection and voltage regulation in one device§ Circulating current minimization or master

follower method

§ Reduced investment with multifunction device§ Easy parameterization with DIGSI§ Reduced wiring§ Faster commissioningB

enef

its

§ SIP5 voltage regulator platform function§ Master follower, circulating current and

independent mode§ Interconnection via IEC 61850§ Supports up to 8 transformer in parallel operation

Cus

tom

erre

quire

men

tSi

emen

sSo

lutio

nSt

atus

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 16 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 - Concept Transformer ProtectionRemote Transformer / Line

>50

0m

New features of solution SIP5

7UT6

7SD6

7SD6

HV

MV

AU

S-M

itnah

me

∆I

HV

MV

7UT8

7SD8

Solution with SIPROTEC 5 and PDISolution with SIPROTEC 4

Pro

tect

ion

Dat

aIn

terfa

ce

§ Communication between

Transformer differential protection and

Line Differential protection using

PDI (Protection Data Interface,

supervised com. Interface)

§ Full range of functionalities

of the SIPROTEC 5 platform

§ Determination of fault location

(transformer or line)

§ For all kinds of star point treatment

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 17 Korger / RC-AT EM DG PRO PRT

SIPROTEC 5 – Distance Protection in Distribution NetworksDoubled Distance Function

Parameter group 1 Parameter group 2

Starpoint of the network may change during switching over actionHigher load possible / acceptable due to wearher conditions, network condistions

Starpoint groundedStarpoint compensated

Dis

tanc

eP

rote

ctio

n–

7SA

8

Doubled distance protection (in one device) does not require additional function points

activeactive

Non activeNon active

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 18 Korger / RC-AT EM DG PRO PRT

High Availability in CommunicationSeamless Redundancy – HSR

IED

RedundancyManager

IED

RedundancyManager

Redbox

Application Application

IEDIED

RedundancyManager

IED

RedundancyManager

Advantages

§ Seamless – no reconfiguration time§ 1 common communication network§ Cost reduction due to ring configuration§ Connection of “Single attached nodes” to

the HSR Network via RedBox§ Valid IEC 62439-3 standard

SIPROTEC supports

RSTP – Rapid Spanning TreePRP – Parallel Redundany ProtocolHSR – High Availability RedundancyProtocol

+++

Bay

leve

lS

tatio

nle

vel

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 19 Korger / RC-AT EM DG PRO PRT

Digital Process Level – Process bus with SIPROTEC 5A new dimension in power grid reliability and efficiency

New approach

§ Digitalization of analogue values provided by conventionalinstrument transformers (CT´s / VT´s)

§ Tranfer of measurement values via Ethernet and FO to theprotection units

§ Interoperable acc.IEC 61850-9-2

Process bus implementation - Advantages

Substation Controller

Control Center

CircuitBreakerController

Parallel wiring

Process bus

Station bus

Sampled ValuesIEC

6185

0

3rd

party

CTVT

§ Reduced cabeling, measuring directly at the process§ High availability of the network due to seamless redundancy

protocols§ Improved operational safety (CT, VT handling, EMC, …)§ Very good transient performance, advanced functionality§ Advanced flexiblity enables new sensor technolgies§ Decoupling from outside, primary influences§ Reduced space using NCIT´s

+

+

+

+

+

+

+

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 20 Korger / RC-AT EM DG PRO PRT

What is the future of process data acquisition and analysis?What if

1

2

3

4

5

You can access process data without touching operative systems(engineering & configuration of SCADA, Substation Automation)?

You have process data online available from the complete powersystem?

The data access is cyber secure and operational safe (read-only)?

You can provide data access to various stakeholders in yourorganization (asset management, service, wholesale…) in differentqualities?

You can choose powerful applications from SIEMENS, OEMs, 3rd

parties?

You can develop own applications for data processing and analysis?

The solution is fully flexible?

6

7

DataAnalyticsplatforms

Ctrl

SCADA

Substation

CtrlCtrl

ProtProt

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 21 Korger / RC-AT EM DG PRO PRT

10100011

10100011

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

10100011010011010011001011000011101010110011010101011100010011010010010

01100011010011010011010010110000

1010001110100011 1010001110100011

10100011

1010001110100011

Connecting Electrical Infrastructure AssetsSIPROTEC 5 goes MindSphere - Benefit from data monitoring

101 00 011

101 00 011

101 00 011101 00 011

Field Devices

Sensors

Third-party products

Automation IEDs

Protection IEDs Data Collecting & Analytics § Asset and Device Management§ Detection of probable system

faults prior to event?§ Adaptive protection setting?

Analytics andIntelligent Learning modules

MindSphere –The cloud-based,

open IoT operatingsystem

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 22 Korger / RC-AT EM DG PRO PRT

www.siemens.com/siprotec

SIPROTEC in the Internetwww.siemens.com/siprotec

§ Brochures§ Catalogues§ Firmwares§ Manuals

Unrestricted © Siemens AG Österreich 2017. All rights reserved.June 8, 2017Page 23 Korger / RC-AT EM DG PRO PRT

Contact

Dipl.-Ing. Georg KorgerHead of Department Protection

Siemensstraße 90A-1210 Vienna

Mobile: +43 (0)664 80 117 46580

E-Mail:[email protected]

siemens.at/future-of-energy