shunt power capacitor

Upload: mahmoud

Post on 14-Apr-2018

244 views

Category:

Documents


3 download

TRANSCRIPT

  • 7/27/2019 Shunt Power Capacitor

    1/32

    SHUNT CAPACITOR

    FUNDAMENTALS ANDPROTECTION

    Prepared By :

  • 7/27/2019 Shunt Power Capacitor

    2/32

    OVERVIEW

    (1) Introduction

    (2) Configurations

    (3) Design

    (4) Operation

    (5) Protection

    (6) Conclusions

  • 7/27/2019 Shunt Power Capacitor

    3/32

    INTRODUCTION

    1. Shunt capacitor banks (SCB) are mainly installed to

    provide capacitive reactive compensation/power

    factor correction.

    2. They are installed near the load terminals, in factorysubstations, in the receiving substations to provide

    leading volt-ampere-reactive.

    3. By using shunt capacitors line drop is reduced and

    the voltage regulation is improved.

    4. They are switched in when kVA demand on the

    distribution system rises and voltage of bus drops.

  • 7/27/2019 Shunt Power Capacitor

    4/32

    Disadvantages

    1. proportional to the square of the voltage and

    consequently when the voltage is low and the system

    need them most, they are the least efficient.

    Advantages

    1. Improvement of the voltage at the load.

    2. voltage regulation.

    3. reduction of losses

    4. Maximize system capacity

    5. reduction in Cu loss due to reduction in current

  • 7/27/2019 Shunt Power Capacitor

    5/32

    Fig 2. High voltage shunt

    capacitor

    Fig1. Single line diagram of SCB

  • 7/27/2019 Shunt Power Capacitor

    6/32

    THE CAPACITOR UNIT

    AND BANK

    CONFIGURATIONThe Capacitor Unit1. The capacitor unit, Fig. 3, is the building

    block of a shunt capacitor bank.

    2. The capacitor unit is made up of

    individual capacitor elements, arranged

    in parallel/ series connected groups,

    within a steel enclosure. The internaldischarge device is a resistor that

    reduces the unit residual voltage to 50V

    or less in 5 min.

  • 7/27/2019 Shunt Power Capacitor

    7/32

    Fig3. capacitor bank

  • 7/27/2019 Shunt Power Capacitor

    8/32

    SCB operation

    The SCB of the line abosrbz leadind var (i.e

    generates lagging var). At the time of light

    load the lagging vars produced by the lines

    are much larger than that required byloads. These surplus lagging vars must be

    absorbeed by additional equipment to keep

    voltage profile within limits.

    SCB are those reactive powercompensating equipment to generate

    generate or absorb vars.

  • 7/27/2019 Shunt Power Capacitor

    9/32

    S=P+jQ

    Where,S=apparent power=VI(kva)

    Q=reactive power=VIsin(kvar)

    P=active power=VIcos(kw)

  • 7/27/2019 Shunt Power Capacitor

    10/32

    Capacitorunit capabilities1. Relay protection of shunt capacitor banks

    requires some knowledge of the capabilities and

    limitations of the capacitor unit and associated

    electrical equipment including: individualcapacitor unit, bank switching devices, fuses,

    voltage and current sensing devices.

    2. Capacitors are intended to be operated at or

    below their rated voltage and frequency as they

    are very sensitive to these values; the reactivepower generated by a capacitor is proportional to

    both of them (kVar 2 f V2 ).

  • 7/27/2019 Shunt Power Capacitor

    11/32

    Bank Configurations

    1. The use of fuses for protecting the capacitor units and it location isan important subject in the design of SCBs.

    2. They also affect the failure mode of the capacitor unit and influence

    the design of the bank protection.

    3. Depending on the application any of the following configurations

    are suitable for shunt capacitor banks:(1) externally fused

    (2) internally fused

    (3) fuseless shunt capacitor bank

    (4) unfused shunt capacitor bank

  • 7/27/2019 Shunt Power Capacitor

    12/32

    External ly Fused

    1. An individual fuse, externally mounted between the capacitor unit and the

    capacitor bank fuse bus, typically protects each capacitor unit.

    2. The capacitor unit can be designed for a relatively high voltage because

    the external fuse is capable of interrupting a high-voltage fault.3. A failure of a capacitor element welds the foils together and short circuits

    the other capacitor elements connected in parallel in the same group.

    4. The remaining capacitor elements in the unit remain in service with a

    higher voltage across them than before the failure and an increased in

    capacitor unit current.

    5. If a second element fails the process repeats itself resulting in an even

    higher voltage for the remaining elements.

    6. Successive failures within the same unit will make the fuse to operate,

    disconnecting capacitor unit and indicating the failed one.

  • 7/27/2019 Shunt Power Capacitor

    13/32

    Fig4. Externally fused shunt capacitor bank

  • 7/27/2019 Shunt Power Capacitor

    14/32

    In ternal ly Fused

    1. Each capacitor element is fused inside the capacitor unit.

    2. . Upon a capacitor element failure, the fuse removes the affected elementonly. The other elements, connected in parallel in the same group, remain

    in service but with a slightly higher voltage across them.

    3.. Banks employing internally fused capacitor units areconfigured with fewer capacitor units in parallel and

    more series groups of units than are used in banks

    employing externally fused capacitor units

  • 7/27/2019 Shunt Power Capacitor

    15/32

    Fig 5. Internally fused SCB

  • 7/27/2019 Shunt Power Capacitor

    16/32

    Fuseless Shun t Capaci tor Banks

    The capacitor units for fuseless capacitor banks are identical to those for

    externally fused described above. To form a bank, capacitor units are

    connected in series strings between phase

    and neutral, shown in Fig. 6.

    The protection is based on the capacitor elementsfailing thus short- circuiting the group. When thecapacitor element fails it welds and the capacitor unitremains in service. The voltage across the failedcapacitor element is then shared among all theremaining capacitor element groups in the series.

    The discharge energy is small because no capacitor units

    are connected directly in parallel. Another advantage of

    fuseless banks is that the unbalance protection does nothave to be delayed to coordinate with the fuses

  • 7/27/2019 Shunt Power Capacitor

    17/32Fig 6. Fuseless SCB

  • 7/27/2019 Shunt Power Capacitor

    18/32

    Unfused Shunt Capaci tor Banks

    Contrary to the fuseless configuration, where the units areconnected in series, the unfused shunt capacitor bank uses a

    series/parallel connection of the capacitor units. The unfused

    approach would normally be used on banks below 34.5 kV,

    where series strings of capacitor units are not practical, or onhigher voltage banks with modest parallel energy. This

    design does not require as many capacitor units in parallel

    as an externally fused bank.

  • 7/27/2019 Shunt Power Capacitor

    19/32

    CAPACITOR BANK DESIGN

    The protection of shunt capacitor banks requires understanding the

    basics of capacitor bank design and capacitor unit connections. The

    capacitors banks are arrangements of series/paralleled connected

    units. Capacitor units connected in paralleled make up a group and

    series connected groups form a single-phase capacitor bank.

    When a capacitor bank unit fails, other capacitors in the same parallel

    group contain some amount of charge. This charge will drain off as a high

    frequency transient current that flows through the failed capacitor unit and

    its fuse. The fuse holder and the failed capacitor unit should withstand this

    discharge transient.

  • 7/27/2019 Shunt Power Capacitor

    20/32

    The optimum connection for a SCB depends on the best

    utilization of the available voltage ratings of capacitor

    units,fusing, and protective relaying.Virtually all substationbanks are connected wye.

    various types of SCB designs are:

    (1) Grounded wye-connection banks

    (2) Underground wye-connection banks

    (3) Delta connected banks

  • 7/27/2019 Shunt Power Capacitor

    21/32

    Grounded Wye-Connected BanksGrounded wye capacitor banks are composed of series and

    parallel-connected capacitor units per phase and provide a

    low impedance path to ground. Fig. 7 shows typical bank

    arrangements.

    Fig. 7 - Grounded Wye Shunt Capacitor Banks

  • 7/27/2019 Shunt Power Capacitor

    22/32

    dvantages of the grounded capacitor banks include:

    1. Its low-impedance path to ground provides inherent self-protection for

    lightning surge currents and give some protection from surge voltages.

    2. Offer a low impedance path for high frequency currents and so they

    can be used as filters in systems with high harmonic content.

    3. Reduced transient recovery voltages for circuit breakers and other

    switching equipment

    Some drawbacks for grounded wye SCB are:

    1. Increased interference on telecom circuits due to harmonic circulation

    2. Circulation of inrush currents and harmonics may cause

    misoperation of protective relays and fuses

  • 7/27/2019 Shunt Power Capacitor

    23/32

    Ungrounded Wye-Connected Banks1. Ungrounded wye banks do not permit zero sequence

    currents, third harmonic currents, or large capacitordischarge currents during system ground faults to flow.

    2. Overvoltage appearing at the CT secondaries are not as

    high as in the case of grounded banks. However, the neutral

    should be insulated for full line voltage because it ismomentarily at phase potential when the bank is switched or

    when one capacitor unit fails in a bank configured with a

    single group of units.

  • 7/27/2019 Shunt Power Capacitor

    24/32

    Fig. 8 - Ungrounded Wye Shunt Capacitor Banks

  • 7/27/2019 Shunt Power Capacitor

    25/32

    1. Delta-connected banks are generally used only atdistributions voltages and are configured with a single

    series group of capacitors rated at line-to-line voltage.

    2. With only one series group of units no overvoltage

    occurs across the remaining capacitor units from the

    isolation of a faulted capacitor unit.

    Delta-connected Banks

  • 7/27/2019 Shunt Power Capacitor

    26/32

    CAPACITOR BANKPROTECTION

    The protection of SCBs involves:

    a) protection of the bank against faults occurring within the bank includingthose inside the capacitor unit

    b) protection of the bank against system disturbances and faults.

  • 7/27/2019 Shunt Power Capacitor

    27/32

    Capacitor UnbalanceProtection1. The protective elements found in a SCB for internal faults are: individual

    fuses, unbalance protection to provide alarm/ trip and overcurrent

    elements for bank fault protection.

    2. Removal of a failed capacitor element or unit by its fuse results in anincrease in voltage across the remaining elements/ units causing an

    unbalance within the bank.

    3. Unbalance protection normally senses changes associated with the

    failure of a capacitor element or unit and removes the bank from service

    when the resulting overvoltage becomes excessive on the remaining healthycapacitor units.

    4.Unbalance protection normally provides primary protection for arcing faults

    within a capacitor bank and other abnormalities that may damage

    capacitor units

  • 7/27/2019 Shunt Power Capacitor

    28/32

    5. The unbalance protection should have minimumintentional delay in order to minimize the amount ofdamage to the bank in the event of external arcing.

    6. The need for sensitive resulted in the development of unbalance

    protection where certain voltages or currents parameters of the

    capacitor bank are monitored and compared to the bank balance

    conditions.

    7. Capacitor unbalance protection is provided in many different

    ways, depending on the capacitor bank arrangement and

    grounding.

  • 7/27/2019 Shunt Power Capacitor

    29/32

    Protection of the SCB

    Against System Disturbances

    and Faults

    System Overvoltage ProtectionThe capacitor bank may be subjected to overvoltages resulting from

    abnormal system operating conditions. If the system voltage exceeds

    the capacitor capability the bank should be removed from service. The

    removal of the capacitor bank lowers the voltage in the vicinity of the

    bank reducing the overvoltage on other system equipment. Timedelayed or inverse time delayed phase overvoltage relays are used.

  • 7/27/2019 Shunt Power Capacitor

    30/32

    Relays for Bank Closing Control

    Once disconnected from the system a shunt capacitor

    bank cannot be re-inserted immediately due to the

    electrical charge trapped within the capacitor units,

    otherwise catastrophic damage to the circuit breaker or

    switch can occur. To accelerate the discharge of the

    bank, each individual capacitor unit has a resistor todischarge the trapped charges within 5min.

  • 7/27/2019 Shunt Power Capacitor

    31/32

    CONCLUSIONS

    The protection of shunt capacitor banks uses simple, well known relaying

    principles such as overvoltage, overcurrents.

    Unbalance is the most important protection in a shunt capacitorbank, as it provides fast and effective protection to assure a long and

    reliable life for the bank. To accomplish its goal, unbalance protection

    requires high degree of sensitivity that might be difficult to achieve.

  • 7/27/2019 Shunt Power Capacitor

    32/32

    THANK YOU