shock suppressors (snubbers) · 2020. 1. 17. · table 2-6 (a), accessibility of safety-related...

26
\' * . .0 LIMITING CONDITIONS FOR OPERATION 2.18 Shock Suppressors (Snubbers) Applicability This specification applies to safety-related shock suppressors (snubbers). Operatieg Modes 1, 2, and 3 (Operating Modes 4 and 5 for snubbers located on systems required operable in those Operating Modes). Objective The objective is to specify modes of reactor operation for given conditions of safety-releted snubbers. Specifications (1) During all modes of operation, except Cold Shutdown (Oper- ating Mode 4) and Refueling (Operating Mode 5), all snubbers listed in Table 2-6 (a) and (b) shall be operable except as noted in 2.18(2) through 2.18(4) below. (2) With one or more snubbers inoperable, within 72 hours re- place or restore the inoperable snubber (s) to operable status and perform an engineering evaluation per Specifi- cation 3.14(3) on the supported component or declare che supported system inoperable end follow the appropriate actions specified in the Technical Specifications for that system. (3) A snubber may be removed for surveillance in accordance with Section 3.14(3) of these Technical Specifications, provided the following conditions are met: . (a) A given snubber station shall not be without an operable snubber for more than two hours during surveillance of attendant snubber. A snubber may be replaced by an operable snubber during surveillance and repair. (b) No other snubber station, containing snubbers listed in Table 2-6 (a) and (b), is known to be inoperable. . , ; (c) Only one snubber station, containing snubbers listed in Table 2-6 (a) and (b), shall be removed for test- ing at a time to ensure ri2t no two saubber stations are without an operab?e snubber during the sr .e time interval. (4) Snubbers may be added, changed, or deleted from Table 2-6 (a) and (b) without prior licensing amendments provided an accepted engineering analysis justifies each change. Deletions will be allowed only after an independent review of the engineering justification is performed and the deletions are approved by SARC. Any revisions to Table 2-6 04W m(a) and (b) will be included in subsequent licensing amend- 810327 ent requests. Amendment No. 27, 48 2-73 ATTACHMENT A . _ _ _ - _ _ _ -

Upload: others

Post on 28-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

\'*

.

.0 LIMITING CONDITIONS FOR OPERATION

2.18 Shock Suppressors (Snubbers)

Applicability

This specification applies to safety-related shock suppressors(snubbers). Operatieg Modes 1, 2, and 3 (Operating Modes 4 and5 for snubbers located on systems required operable in thoseOperating Modes).

Objective

The objective is to specify modes of reactor operation for givenconditions of safety-releted snubbers.

Specifications

(1) During all modes of operation, except Cold Shutdown (Oper-ating Mode 4) and Refueling (Operating Mode 5), all snubberslisted in Table 2-6 (a) and (b) shall be operable except asnoted in 2.18(2) through 2.18(4) below.

(2) With one or more snubbers inoperable, within 72 hours re-place or restore the inoperable snubber (s) to operablestatus and perform an engineering evaluation per Specifi-cation 3.14(3) on the supported component or declare chesupported system inoperable end follow the appropriateactions specified in the Technical Specifications for thatsystem.

(3) A snubber may be removed for surveillance in accordancewith Section 3.14(3) of these Technical Specifications,provided the following conditions are met:

.

(a) A given snubber station shall not be without anoperable snubber for more than two hours duringsurveillance of attendant snubber. A snubber may bereplaced by an operable snubber during surveillanceand repair.

(b) No other snubber station, containing snubbers listedin Table 2-6 (a) and (b), is known to be inoperable.

.,

;

(c) Only one snubber station, containing snubbers listedin Table 2-6 (a) and (b), shall be removed for test-ing at a time to ensure ri2t no two saubber stationsare without an operab?e snubber during the sr .e timeinterval.

(4) Snubbers may be added, changed, or deleted from Table 2-6(a) and (b) without prior licensing amendments provided anaccepted engineering analysis justifies each change.Deletions will be allowed only after an independent reviewof the engineering justification is performed and thedeletions are approved by SARC. Any revisions to Table 2-6

04W m(a) and (b) will be included in subsequent licensing amend-810327 ent requests.

Amendment No. 27, 48 2-73 ATTACHMENT A. _ _ _ - _

_ _ _ -

Page 2: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

. - . . - .

;,* .-.

2.0 LIMITING CONDITIONS FOR OPERATION2.18 Shock Suppressors (Snubbers)

| Basis

Snubbers are designed to prevent unrestrained pipe motion underdynamic loads as might occur during an earthquake or severe,

transient, while allowing normal thermal motion during startup orshutdown. The consequence of an inoperable snubber is an in-crease in the probability of structural damage to piping as aresult of a seismic, oi other event, initiating dynamic loads.It is therefore required that all snutbers required to protectthe primary coolant system or any other safety system or com-ponent be operable during reactor operation.

Because the snubber protection is required only during low,

probability events, an inoperable period of 72 hours is allowedfor repairs or replacements and an inoperable period of two hoursis allowed for surveillance.

Table 2-6 (a) and (b) lists the snubbers that are on safety-relatedsystems. The snubbers that are listed as " Inaccessible During Nor-mal Operation" are located inside of the containment building andwould require a significant expenditure in man-rems to inspect ona periodic basis. Revisions may be made to Table 2-6 (a) and (b)without prior notice provided that an engineering analysis justi-fies these changes. -

Those snubbers listed as " Difficult to Remove for FunctionalTesting" are so listed because they are either:

(1) rated at greater than 50,000 lbs. force,

(2) inaccessible due to surrounding structures, or

(3) located such that an excessive amount of time and efforewould be required to remove them for testing.

i

!

.

.

I

Amendment No. 21, 48 2-74

i

-_ _ - _ _ _ _ _ _ _ _ _ _ __

Page 3: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6 (a), ,.,

ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingACS-18 996' 8" X

ACS-112 1040' 0" X X

ACS-113 1040' 0" X X

ACS-113A 1040' 0" X X

ACS-116 1031' 4" X

ACS-117 1031' 4" X

ACS-116 1031' 4" Y

ACS-121 1031' 4" X

ACS-123 1031' 4" X

ACS-127A 1040' 0" X X

ACS-128 1040' 0" X X

ACS-299 1056' 4-11/16" X

ACS-299A 1056' 6" X

ACS-302 1056' 4-11/16" X

ACS-304 1056' 4-11/16" X

ACS-305 1056' 4-11/16" X

ACS-306 1056' 4-11/16" X

ACS-307 1056' 4-11/16" X

ACS-313 1054' 11" X

ACS-385 987' Sk" X

i.

FWS-1

Top 1038' 6" X X

FWS-1

| Bottom 1038' 6" X X

FWS-1A 1033' 6" X X,

FWS-1B 1033' 5\" X X

WS-IC 1033' 5 " X X

FWS-2

| Top 1038' 6" X X ,

! FWS-2 -

Botton 1038' 6" X X

Amendment No. 27 2-75'

L - -

Page 4: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABII 2-6 (a), ..

(Continued),

-

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingWS-2A 1038' 6" X X

WS-2B 1038' 5\" X X

WS-2C 1038' 55" X X

WS-3B-

North 1038' 5\" X

WS-3B-

South 1033' 6" X

WS-7D-

North 1038' 6" X

WS-7D-

South 1038' 6" X

WS-28 1002' 6" X

WS-29A 1002' 6" X

WS-30 1002' 6" X

WS-32 1005' 1" X

WS-32A 1005' 1" X

i~ WS-33 1001' 6" X

WS-34 1001' 6" X

WS-35 1005' 5" X

WS-36 1005' 5" X

Wd-37 1005' 5" X

WS-38 1010' 0" X

WS-39 1012' 1\" X

WS-64 1043' 0" X

WS-64A 1041' 0" X

WS-64B 1041' 0" X-'

WS-65 1049' 6" X

WS-66 1049' 6" X

WS-67 1049' 6" X

WS-68 - 1049' 6" X

WS-68A - 1049' 6" X.

,

WS-69 1049' 6" X

WS-71 -1037' 6" X

Amendment No. ' 27 2-76

_

. __ --- _-- - _ , .,

Page 5: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

-_

TABLE 2-6 (a),

'

(Continued)-

located4ccessible In High Difficult toDuring Inaccessible Radiation Remove for

*Saubber Normal During Normal Areas During FunctionalNo. Elevation Operation Opcration Shutdown TestingWS-74 1053' 0" X

WS-75A 1053' 0" X

WS-7 ' 1038' 4" X

WS-79 1049' 6" X

WS-80 1049' 6" X

WS-81 1049' 6" X

WS-83 1033' 4" X

WS-86A 999' 0" X

WS-87 999' 0" X

WS-88 999' 0" X

WS-88A 999' 0" X

WS-89 1002' 6" X

WS-90 1001' 6" X

WS-90A 1005' 6-5/8" X

WS-91 1019' 0" X

WS-92 1019' 0" X

WS-92A 1026' 0" X

WS-93 1032' 0" X

WS-94 1032' 0" X

WS-95 1032' 0" X

WS-96 1032' 0" X X

WS-97 1032' 0" X X

WS-98 1032' 0" X X|

WS-100 1039' 0" X

WS-101 1039' 0" X

MSS-1 1054' 7" X X

MSS-2 1054' 8 " X'

X

MSS-3 '038' 0" X

MSS-L-

Top 1038' 6" X X

.

Amendment No. 27 2-77

Page 6: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TALLE 2-6 (c), ,.

'. (Con;inu:d)Located

Accessible In High Difiicult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FunctionalN?. Elevation Operation Operation Shutdown Testing

MSS-4

Bottom 1038' 6" X X

MS-5 1054' 7" X X

MSS-6 1054' 8\" X X

MSS-7 1038' 6" X X

MSS-8-Top 1038' 6" X X

MSS-8-

Bottom 1038' 6" X X

MSS-8A 1038' 6" X X

MSS-8B 1038' 6" X X

MSS-8C 1038' 6" X X

MSS-8D 1038' 6" X X

MSS-9 1040' 7" X

MSS-9A 1040' 7" X

MSS-9B-

North 1033' 6" X

MSS-9B-

South 1033' 6" X

MSS-13 1040' 7" X

MSS-13A-

East 1040' 0" X

MSS-13a-

West 1040' 0" X

HSS-13B-

North 1038' 6" X

MSS-13B-

South 1038' 6" X'

RCP-Al 1016' 0" X

RCP-A2 1016' 0" X

RCP-A3 1016' 0" X

RCP-A4 1016' 0" X

RCP-B1 1016' 0" X

RCP-B2 1016' 0" X

RCP-B3 1016' 0" X

RCP-B4 1016' 0" X

Amendment No. 27 2-78

_. -

Page 7: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

_ _

TABLE 2-6(n). ..

(Continu::d).

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FuncticnalNo. Elevation Operation Operation Shutdown TestingRCS-52 1007' 9" X

,

RWS-79 1046' 0" X X

RWS-128 998' 8 " X

RWS-130 998' 8\" X

RWS-131 998' 8\" X

SG-Al 1049' 0" X X

SG-A2 1049' 0" X X

SG-A3 1049' 0" X X

SG-A4 1049' 0" X X

SG-B1 1049' 0" X X

SG-B2 1049' 0" X X

SG-B3 1049' 0" X X

SG-B4 1049' 0" X X

SIS-1 979' 6" X

SIS-1A 979' 6" X

SIS-3 979' 6" X

SIS-4 979' 6" X

SIS-4A 979' 6" X

SIS-5 979' 6" X

SIS-5A 979' 6" X

'S-6 979' 6" X,

,;S-6A 979' 6" X

| SIS-7 979' 6" X

SIS-8 979' 4" X

SIS-8B 979' 6" X

SIS-8C 979' 6" X

SIS-9 979' 6" X'

SIS-9A 979' 6" X;

SIS-9B 979' 6" X

SIS-10 983' 6" X

SIS-ll 983' 6" X,

SIS-16 981' 6" X

SIS-16A 981' 6" X.

SIS-17 979' 6" X

Amendment No. 27 2-81

, . . . . . . , , , , ,

Page 8: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

_ _ _

TABLE 2-6(a). .

(Continued).

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingSIS-17A 979' 6" X

SIS-18 979' 6" X

SIS-19 979' 6" X

SIS-20 979' 6" X

SIS-21 979' 6" X

SIS-21A 981' 6" X

SIS-21B 981' 6" X

SIS-2IC 981' 6" X

SIS-22 981' 6" X

SIS-24 983' 6" X

SIS-24A 983' 6" X

_SIS-26 979' 6" X

SIS-27 981' 6" X

' SIS-27A- 981' 6" X

SIS-27B 981' 6" X

SIS-28 980' 0" X

SIS-28A 980' 0" X

SIS-29 980' 0" X'

SIS-30 979' 6" X

- SIS-30A 979' 6" X

, S-31 981' 6" X'

aIS-31A 981' 6" X

SIS-32 980' 0" X

| SIS-32A 980' 0" X

SIS-32B 980' 0" X

SIS-33-Top 981' 6" X*SIS-33-

.Botton 981' 6" X X

l''

SIS-34 980' 0" X

. SIS-35-Top 980' 0" X

SIS-35-,

Botton 980' 0" X

SIS-36-Top- 974' 6" X

' Amendment No. 27 2-82

'_

_ __

Page 9: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(c). .

(Continu:d)-

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

CSnubber hormal During Normal Areas Dur;.ng FunctionalNo. Elevation Operation Operation Shutdow*. TestingSIS-36-

Bottom 974' 6" X

SIS-37-

Top 981' 6" X

SIS-37-

Bottom 981' 6" X

SIS-38 981' 6" X X

SIS-38B 98I' 6" X X

SIS-38C 981' 6" X X

SIS-39-

Tap 973' 0" X

SIS-39-

Bottom 973' 0" X

SIS-39A 973' 0" X

SIS-40-

Top 981' 6" X

SIS-40-

Bottom 981' 6" X

SIS-41A 979' 6" X

SIS-42 979' 6" X

IS-42A 979' 6" X

SIS-43 979' 6" X

SIS-43A 979' 6" X

SIS-44 979' 6" X

SIS-o4A 979' 6" X

SIS-44B 979' 6" X'

SIS-44C 979' 6" X

SIS-45 974' 6" X

SIS-45A 979' 6" X

SIS-46 979' 6" X

SIS-47 979' 6" Xi .

SIS-48 979' 6" X

SIS-49 979' 6" X

SIS-50 979' 6" X

Amendment No. 27 2-83

Page 10: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(c).

(C:ntinu;d)Loccted

Accessible In High Difficult toDuring Inacce:Sible Radiation Remove for

CSnubber Normal During Normal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingSIS-53 997' 6" X

SIS-53A 997' 6" X

SIS-54 996' 6" X

SIS-55 996' 6" X

SIS-56 996' 6" X

SIS-56A 996' 6" X

SIS-57 995' 11-3/8" X

SIS-58 995' 11-3/8" X

SIS-59 996' 6" X

SIS-60 996' 6" X

SIS-63 990' 6" X

SIS-64 990' 6" X

SIS-65 990' 9" X

SIS-66 1000' 0" X

SIS-67 1000' 0" X

SIS-68 1001' 9-3/8" X

SIS-69 1003' 6" X X

SIS-70 1000' 0" X

SIS-71A 1002' 8" X

SIS-72 1002' 8" X

S-73 1002' 8" X

SIS-74 1002' 8" X

SIS-74A 1002' 8" X-

SIS-75 1002' 8" X

SIS-76 997' 6" X

SIS-76A 997' 6" X

SIS-77 991' 0" X'

SIS-77A 991' 0" X

SIS-78 991' 0" X

SIS-79 1501' 4" X

SIS-79A 1001' 4" X,

,

Amend =ent No. 27 2-84

_

Page 11: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(a)(Continu;d)-

LocctedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

< Snubber Normal During Normal Areas During FunctionalN2 Elevation Operation Operation Shutdown Testing

___

SIS-101 991' 0" X

SIS-101A 991' 0" X

SIS-102 991' 0" X

SIS-103 1001' 4" X

SIS-104 1001' 4" X

SIS-104A 1001' 4" X

SIS-104B 1001' 4" X

SIS-115 1009' 5-3/4" X

SIS-116 1009' 5-3/4" X

SIS-117 1009' 5-3/4" X

SIS-117A 1009' 5-3/4" X

SIS-118 1009' 5-3/4" X

SIS-118A 1009' 5-3/4" X

SIS-119 1006' 4-1/2" X

Top

SIS-119 1006' 4-1/2" X

Bottom

SIS-120 1006' 4-1/2" X

SIS-121 1007' 10" X

SIS-122 1003' 0-1/8" X

."S-122A 1003' 0-1/3" X~

21S-123 1003' 0-1/3" X

SIS-124 1010' 4" X

SIS-127 1010' 4" X

SIS-127A 1010' 10-1/2" X

SIS-129 1005' 5" X

SIS-130 1008' 2" X'

SIS-132 1008' 2" X

| SIS-134 1003' 0" X

SIS-135 1003' 0" X

SIS-140 1008' 10" X

SIS-ISO 1008' 10" X

SIS-159A 1004' 3-1/6" X

SIS-161 1014' 0" X

Amendment No. 27 2-86

. . .

Page 12: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(m)(Continu:d)

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

* Snubber Normal During Normal Areas During FunctionalN9 Elevation Operation Operation Shutdown Testing

SIS-162 1014' 6" X

SIS-164 1014' 0" X

SIS-165 1014' 6" X

SIS-165A 1014' 6" 2

Top

SIS-165A 1014' 6" X

Bottom

SIS-166 1014' 6" X

SIS-167 1014' 6" X

SIS-168 1014' 6" X

SIS-168A 1014' 6" X

Top

SIS-168A 1014' 6" X

Bottom

SIS-169 1007' 7" X

SIS-169A 1007' 7" X

SIS-170 1007' 8" X

SIS-170A 1007' 5" X

SIS-172 1032' 0" X

SIS-173 1036' 8" X

. S-174 1049' 2" X

SIS-174A 1049' 6" X

SIS-174B 1051' 7-1/4" X X*

SIS-174C 1052' 6" X X

SIS-174D 1063' 7-1/4" X X

SIS-174E 1064' 6" X X'

SIS-175 1057' 0" X X

SIS-175A 1056' 5-1/2" X

SIS-176 1064' 6" X X

SIS-176B 1052' 6" X X

SIS-1768: 1051' 7-1/4" X X

SIS-176ii 1064' 6" X X

SIS-176E 1063' 7-1/4" X X

SIS-176G 1074' 0" X X

SIS-176F 1074' 0" X X

SIS-178 981' 6" X

Amendment No. H 48 2-87

Page 13: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(c)(Continu d)

LocatedAccessible In High Difficult toDuring Inaccessible Radiatica Re:ove for

* Snubber Nor=al During Norcal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingSIS-183 1055' 9-1/2" X

SIS-184 979' 6" X

SIS-185 979' 6" X

SIS-187 983' 6" X

SIS-188 988' 6" X

SIS-202 1009' 0" X

SIS-204 995' 0" X

SIS-205 979' 6" X

SIS-206 983' 6" X

SIS-208 1003' 1-1/8" X

VDS-107 1004' 0" X

WDS-122- 991' 6" X

RightWDS-122- 991' 6" X

Left

NOTE: Modifications to this table due to changes in high radiation

areas should be submitted to the NRC as part of the nextlicensing amendment request.

.

2 Location'

ACS Auxiliary Coolant SystemFES Feedwater System

MSS Mrin Steam S); ten'

1(CP Reactor Coolant Pu=p

3 CS Reactor Coolant System- '1%S Rav Vater System

SG Steam Generator,

SIS Safety Injection Systen

VDS Vaste Disposal System

Amendment No. 27 2-88

-- _,.

Page 14: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

TABLE 2-6(b).

ACCESSIBILITY OF SAFETY-RELATED SYSTEM MECHANICAL SNUBBERS

LocatedAccessible In High Difficult toDuring Inaccessible Radiation Remove for

OSnubber Normal During Normal Areas During FunctionalNo. Elevation Operation Operation Shutdown TestingHCV-327-S 1025' X

HCV-329-S 1025' X

HCV-331-S 1025' X

HCV-333-S 1025' X

HCV-1040-S-1 1041' X

HCV-1040-S-2 1041' X

HCV-1040-S-3 1041' X

HCV-1040-S-4 1041' X

HCV-1040-S-5 1041' X

RCS-3A 996' X

RCS-16 1015' X

RCS-29 1047' X

RCS-29A 1045' X

SIS-112-C 1111'-6" X

SIS-112-D 1111'-6" X

SIS-112-E 1111'-6" X

SIS-112-F 1111'-6" X

SIS-114-A 1074' X

'IS-114-B 1074' X

.S-114-E 1074' X#

SIS-114-F 1074' X

.

0

2-88a

Page 15: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

. . .

. .

.

i3.0 SURVEILLANCE REQUIREMENTS

3.14 Shock Suppressors (Snubbers)

Applicability

This specification applies to all hydraulic snubbers on thereactor coolant and safety-related systems listed in Table 2-6(a) and (b).

Objective

The objective of this specification is to insure the overallintegrity and operability of safety-related hydraulic snubbers.

Specifications

(1) All hydraulic snubbers whose seal material has been de-monstrated by operating experience, lab testine or analysisto be compatible with the operating environment shall bevisually inspected. This inspection shall include, but notnecessarily be. limited to, inspection of the hydraulicfluid reservoir, fluid connections, and linkage connectionsto the piping and anchor to verify snubber operability. Inthose locations where snubber movement can be manuallyinduced without disconnecting the snubber, verify that thesnubber has freedom of movement and is not frozen up.

[ Visual inspections shall be performed in accordance withthe following schedule:

Number of Hydraulic Snubbers Found Next RequiredInoperable.During Inspection or Inspection

During Inspection Interval Interval

-r

; O 18 months i 25%l 1 12 months i 25%

2 6 months i 25%,

| 3, 4 124 days i 25%|

5,6,7 62 days i 25%>8 31 days i 25%

||

! The required inspection interval shall not be lengthened*

more than one step at a time.

Snubbers may be categorized in two groups, " accessible" ori

|" inaccessible" based on their accessibility for inspection

!during reactor operation. These two groups may be in-

| spected independently according to the above schedule.*

!| (2) All hydraulic snubbers whose seal materials are other than

eythlene propylene or other material that has been de-monstrated to be compatible with the operating environmentshall be visually inspected for operability every 31 days.

Amendment No. 27 3-77

_

Page 16: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

-- _ - -

.(

. .

.

3.0 SURVEIU.ANCE REQUIRDENTS3.14 Shock Suppressors (Snubbers) (Continued)

(3) At least once per 18 months during shutdown, a represent-ative sample of 88 snubbers shall be functionally testedeither in-place or in a bench test. For each nu=ber ofsnubbers above 3 which does not =eet the functional testacceptance criteria, an additional sa_ple selected according

'-

to the expression 22(a-3) shall ne functionally tested,where a is the total number of snubbers found inoperableduring the functional testing of the representative sa=ple.For each inoperable snubber found during a resa=ple test, anadditional 22 snubbers will be tested until no additionalinoperable snubbers are found within a sa=ple or until all i

snubbers in Table 2-6 (a) and (b) have been functionallytested. -

The representative sample selected for functional testingshall include the various configurations, operating en-vironments and the range of size and capacity of snubbers.At least 25% of the snubbers in the representative sample t

shall include snubbers from any of the following three '

,'

categories:

(a) The first snubber away from each reactor vesselnozzle.

t

(b) Snubbers within 5 feet of heavy equipment (valve, t

pump, turbine, motor, etc). t

(c) Snubbers within 10 feet of the discharge frca asafety relief valve.

Snubbers identified in Table 2-6 (a) and (b) as "Especially' Difficult to Remove" or in "High Radiation Zones During

Shutdown"~shall also be included in the representativesample.*

In addition to the regular sample, snubbers which failed the,

previous functional test shall be retested during the nexttest-period. If a spare snubber has been installed in placeof a failed snubber, then both the failed snubber (if it is j.

repaired and installed in another position) and the spare -'

anubber shall be ratested. Test results of these snubbersmay not be included for the resampling.

.

-* Permanent or other exemptions from functional testing for individual; snubbers in these categories may be granted by the Commission only ifa justifiable basis for. exemption is presented and/or snubber lifedestructive testing was performed to qualify snubber operability forall design conditions at either the completion of their. fabricationor at a subsequent date.

~

Amendment No. 27 3-78

1. ..

Page 17: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

__.

. .

.

3.0 SURVEILLANCE REQUIREHENTS3.14 Shock Suppressors (Snubbers) (Continued)

If any snubber selected for functional testing either failsto lockup or fails to move, i.e., is frozen in place, thecause will be evaluated. If the cause is a manufacturer ordesign deficiency, appropriate action shall be taken forsnubbers of the same design subject to the same defect todetermine if any more defects exist. This testing require-ment shall be independent of the requirements stated abovefor snubbers not meeting the functional test acceptancecriteria.

For any snubber (s) found locked up during normal operationor found inoperable during a seismic event, an engineeringevaluation shall be performed on the components which aresupported by the snubber (s). The purpose of this engineer-ing evaluation shall be to determine if the components sup-

j ported by the snubber (s) were adversely affected by theinoperability of the snubber (s) in order to ensure that the'

! supported component remains capable of meeting the designedservice. If the engineering evaluation shows the components

' to be capable of meeting the designed service without thefailed snubber, that snubber may be deleted from service andTable 2-6 (a) and (b) per Specification 2.18(4).

|

! (4) Snubber Service Life Monitoring

h A record of the service life of each snubber, the date at

j which the designated service life commences and the in-stallation and maintenance records on which the designatedservice life is based shall be maintained as required bySpecification 5.10.2 m. At least once per 18 months the

; installation and maintenance record for each snubber listed'

in Table 2-6 (a) and (b) shall be reviewed to verify that-

the indicated service life has not been exceeded or will notbe exceeded prior to the next scheduled snubber service lifereview. If the indicated service life will be exceededprior to the next scheduled snubber service life review, the

;

snubber service life shall be re-evaluated or the snubberi

shall be replaced or reconditioned so as to extend its ser-| vice life-beyond the date of the next scheduled service lifei review. This re-evaluation, re?lacement or reconditioning ,

shall be indicated in the records.

Basis

All snubbers listed in Table 2-6 (a) and (b) are required operable'

| to ensure that the structural integrity of the reactor coolantsystem and all other safety-related. systems is maintained during!

and following a seismic or other event initiating dynamic loads.

The visual-inspection frequency is based upon maintaining aconstant level of snubber protection to systems. Therefore, the

required inspection interval varies inversely with the observed,

'

snubber failures and is determined by the number of inoperablebefore that interval has elapsed may be used as a new reference

Amendment No. 27 3-79

-.

Page 18: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

- _- _ _ = - _ - . - - -

i

*e e

,

3.0 SURVEILLANCE REQUIREMENTS'3.14 Shock Suppressors (Snubbers) (Continued)

point to determine the next inspection. However, the results ofsuch early inspections performed before the original required timeinterval has elapsed (nominal time less 25%) may not be used to'

lengthen the required inspection interval. Any inspection whoseresults require a shorter inspection interval will override theprevious schedule.

When a snubber is found locked up or frozen in place or when asnubber has been inoperable during a seismic event, an engineeringevaluation shall be performed, in addition to the determination ofthe snubber mode of failure. The purpose of the engineeringevaluation is to determine if any safety-related component orsystem has been adversely affected by the inoperability of thesnubber. The engineering evaluation shall determine whether ornot the snubber mode of failure has imparted a significant effector degradation on the supported component or system.

To provide assurance of snubber functional reliability, a repre-sentative sample of the installed sntAbers will be functionallytested during plant shutdowns at 18 month intervals. Selection ofa representative sample according to the expression 35(1+c/2)*provides a confidence level of approximately 95% that 90% to 100%of the snubbers in the plant will be operable within acceptancelimits. Observed failures of these sample snubbers shall requirefunctional testing of additional units. For each number of

# snubbers above c which does not meet the functional test ae-ceptance criteria, an additional sample selected according to theexpression 35(1+c/2)(2/(c+1))2(a-c) will be functionally tested,where a is the total number of snubbers found inoperable duringthe functional testing of the representativa sample. Functionaltesting will continue according to the expression b(35(1+c/2)(2/(c+1))2)where b is the number of snubbers found inoperable in the previous-

resample, until no additional inoperable snubbers are foundwithin a sample or until all snubbers in Table 2-6 have beenfunctionally tested.

Hydraulic snubbers and mechanical snubbers will each be treated asa different entity for the above surveillance programs.

The service life of a snubber is evaluated via manufacturer input,

and information through consideration of the snubber serviceconditions and associated installation and maintenance records(newly installed snubber, seal replaced, spring replaced, in highradiation area, in high temperature area, etc.). The requirementto monitor the snubber service life is included to ensure that the

,

snubbers periodically undergo a performance evaluation in view oftheir age sad operating conditions.. These records will providestatistical bases for future consideration of snubber servicelife. The requirements for the maintenance of records and thesnubber service life review are not intended to affect plant

operation.

*The value c will be arbitrarily chosen by the applicant and incorporated'

into the expression for the representative sample and for the resampleprior to the issuance of tha Technical Specifications.

3-79a- --- -

Page 19: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

_. _ __

. s

*e e

.

5.0 ADMINISTRATIVE CONTROLS

5.10.2 The following records shall be retained for the duration of the-Facility Operating License:

a. Records of drawing changes reflecting facility designmodifications made to systems and equipment described inthe Final Safety Analysis Report.

b. Records of new and irradiated fuel inventory, fuel trans-fers and assembly burnup histories.

c. Records of facility radiation and contamination surveys.

d. Records of radiation exposure for all individuals enteringradiation control areas.

e. Records of gasecus and liquid radioactive material re-leased to the environs.

f. Records of transient or operational cycles for thosefacility components designed for a limited number oftransients or cycles.

g. Records of training and qualification for current membersof the plant staff.

h. Records of in-service inspections erformed pursuant tothese Technical Specifications.

1. Records of Quality Assurance activities required by the QAManual.

j. Records of reviews performed for changes made to pro-'

cedures or equipment or reviews of tests and experiments

| pursuant to 10 CFR 50.59.

ik. Records of meetings of the Plant Review Committee and the'

Safety Audit and Review Committee.

I 1. Records of Environmental Qualification which are covered( under the provisions of Section 5.12 of these Technical

( Specifications.*

m. Records of the service lives of all hydraulic and mechanicalsnubbers listed on Table 2-6 (a) and (b) including the dateat which the service life commences and associated install-

L- ation and maintenance records.*5.11 Radiation Protection Prograr, ,-

.

Procedures for personrL r J;.-ion protection shall be preparedi

consistent with the I.*qs|/c5 es of 10 CFR Part 20 and shall beapproved,_ maintained sad adaux4d to for all operations in-volving personnel radiation exposure.

Order dated: October 24, 1980 5-19

. u.

Page 20: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

. ...

DISCUSSION

The proposed revisions to the Fort Calhoun Station Unit No. 1Technical Specifications are intended to provide the following func-tions:

1. Respond to the Commission's letter dated Novenber 20, 1980.

2. Incorporate several changes, clariri +1ons, and improvementsfrom the previous version involving surveillance testing andinspection of snubbers. These changes were based on recentoperating experience.

3. Update Table 2-6, " Accessibility of Safety-Related SystemSnubbers".

One of the major changes is the method of determining the repre-sentative sample size and the resample sizes for functional testing ofthe snubbers. The present Technical Specificatiot.s state that 10snubbers, or 10% of the. total population, constitute a representativesample size and, for each snubber found inoperable in the representativesample, an additional 10 snubbers, or 10%, must be tested. The proposedTechnical Specifications use the formulas based on an arbitrary value ofc to determine representative and resa=ple sizes. The District hasselected a value of e equal to 3. Therefore, the representative samplewill include 88 snubbers. If 3 snubbers or less are found to be in-operable, then no resample will be required. For each additional in-operable snubber over 3, 22 more snubbers will be tested. For eachinoperable snubber in the resample, an additional 22 snubbers will betested.

In response to NRC concerns identified in IE Bulletins 79-02 and' 79-14 about the adequacy of seismic analysis documentation for safety-

related piping systems, Gilbert / Commonwealth Associates was hired toreanalyze all safety-related systems and generate complete seismic

;

analysis documentationtfor the Fort Calhoun Station. The method of'

| analysis used is a response spectrum modal analysis using appropriate! floor response spectra as input, in accordance with Appendix F, Section

F.2.5, Item (C), Page F-19, of the Fort Calhoun FSAR. The computerpackage used by G/C to perform this analysis is a verified version ofthe T-PIPE code developed jointly by PMB System Engineering and Ten- -

nessee Valley Authority.|

.The dynamic method used by G/C is more refined than the original

'static method used'in the original plant design. As a result of the

- .added sophistication, some of the snubbers presently attached to safetyi systems have been shown by analysis to serve no safety function (i.e.,

removal of these snubbers will not impair the ability of the associatedpiping system to withstand design conditions). In order to eliminate

ATTACHMENT B

Page 21: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

- - --- . . -- - .- -- -, __

4 . ..,

.

-2-

,

F-

needless surveillance testing, the following snubbers have been deletedfrom Table 2-6 (a) and will be physically removed from the piping.

Tag No. Subsystem No.' Analysis I.D. Analysis Revision No.

.

FWS-72 FW-289A VEFNEO Rev. 0FWS-72A FW-289A VEFNJXO Rev. O'

SIS-62 SI-212A VH01JD1 Rev. 1ACS-296 AC-086C KWEFANF Rev. 1SIS-133 SI-074C GLQLR8D Rev. 2

Snubbers have also been added at various locations for a variety of

systems, as a result of the reanalysis. These additions ensure thatsections of safety-related piping are rigid as defined in Appendix F,Section F.2.2.2,~Fage F-7, and specified in Section F.2.5, Page F-11, of

! the FSAR. The snubbers which should be added to the current list ofTechnical Specification snubbers is as follows:

Tag No. Subsystem No. Analysis I.D. Analysis Revision No.t

ACS-385 AC-215A VEBFJVM Rev. ORWS-128 RW-231A OTRSMER Rev. ORWS-130 RW-231A OTRSMER Rev. ORWS-131 RW-231A OTRSMER Rev. OSIS-208 SI-197A VKSXJTD Rev. 2

SIS-202 SI-195A VKUHJ8D Rev. 1SIS-204 SI-201A VCRKJ72 Rev. 1'

SIS-205 SI-209A VGNVJZO Rev. 2

SIS-206 SI-209A VGNVJZO -Rev. 2' -During the review of "As Built" piping systems for NRC IE Bulletin

79-14,~a few snubbers, which were part of the Main Steam System for* which dynamic analysis documentation was available, were found to be

missing. To ensure that the related piping conformed to the availabledynamic analysis, these snubbers were installed at the appropriatelocations. . The following snubbers have been added to Table 2-6 (a):

Additions (Analysis performed by NSC and documented in the FSAR,AEC Docket No. 50-285, May 1973)

Tag No. Norm Access ' Norm Inaccess -

MSS-9 XMSS-9A XMSS-13 X

,

.

During the analysis of baseplates and anchors for NRC IE Bulletin79-02, one restraint was identified ~as being unstable as designed andcould not be credited with performing its intended function. To correct

- . - . - . . .- .. . , - .- - .- .--

Page 22: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

~

.

, ...

-3-

the unstable design, an additional snubber was added in parallel withthe existing snubber at that location. This modification created a topand bottom snubber arrangement. Therefore, Table 2-6 (a) should be changedto show:

Delete

SIS-119

Add

SIS-119 TopSIS-119 Bottom

There was also Lte snubber name change from SIS-174BB to SIS-176.This was the only snubber with a double letter designation, so thechange was made to be consistent and avoid confusion. There are a fewother snubbers added to Table 2-6 (a) that were installed previously butwere not listed la the Technical specifications before. After re-evaluation, it has since been determined that these snubbers should beincluded in Table 2-6 (a). As a result, Table 2-6 (a) should be changedas follows:

Delete

SIS-174BB

Add

SIS-29SIS-176SIS-178

.

It is concluded that, based on the following reasons, the proposedTechnical Specifications do not involve an unreviewed safety questionper 10 CFR Part 50, paragraph 50.59(a)(2):

1. The proposed changes do not increase the probability orconsequences of accidents or malfunction of safety-relatedequipment previously considered.

2. There is a reasonable assurance that the health and safety of'the public will not be endangered under the proposed changes.

3. The possibility for an accident or malfunction of a differenttype than previously evaluated is not created.

,

4. The margin of safety, as defined in the applicable TechnicalSpecifications, is not reduced.

A comparison of the Standard Technical Specifications attached tothe Commission's letter dated November 20, 1980, versus the proposedTechnical Specifications is presented on the next page.

.

s-~ -_ __ _ _ _

.,

Page 23: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

-4--

.

COMPARISON OF STANDARD TECHNICAL SPECIFICATIONS (STS)AND PROPOSED TECHNICAL SPECIFICATIONS FOR

FORT CALHOUN STATION UNIT NO. 1

Section or Section orSubsection Subsection

of STS Proposed TS Remarks

1. 3.7.9 2.18 Operating Modes 1, 2, 3, and 4Applicability Applicability in the STS correspond to Oper-

ating Modes 1, 2, and 3 in theFort Calhoun Station TechnicalSpecifications. Operating Modes5 and 6 in the STS are similarto Operating Modes 4 and 5 inthe Fort Calhoun Station TechnicalSpecifications.

2. N/A 2.18(3) (c) "Only one snubber listed in Table2-6" has been changed to "Onlyone snubber station, containing

snubbers listed in Table 2-6 (a) & (b)".This will allow more than onesnubber in the same locationon the same system to be re-moved, if necessary, withoutaffecting the safety of the*

system.

3. N/A 2.18(4) This statement was added to allowthe District to add, change, ordelete snubbers listed in Table2-6 (a) & (b) without prior notice if an

,

updated, approved engineering ,

analysis justifies such changes.Any revisions will be includedin subsequent licensing requests.

4. 4. 7. 9 (b) 3.14(1) The section on " Visual Inspection

Acceptance Criteria" has beendeleted in order to be consistentwith the existing Section 3.14

-

and other similar sections ofthe Fort Calhoun Station TechnicalSpecifications. The Districtfeels that detailed acceptance

~ criteria are too cumbersome forTechnical Specifications and are

~

more appropriately placed in thespecific surveillance procedures.The District therefore intendsto include acceptance criteriain ST-HSS-1, 2, and 3_for sur-ve111ance of hydraulic snubbers.

_

Page 24: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

.

-5-. ..

.

Subsection Subsectionof STS Proposed TS Remarks

5. 4.7.9(c) 3.14(3) The STS leaves the option of test-paragraphs paragraphs ing 10% of the total nu=ber of1 and 2 1 and 2 snubbers or following the for=ula

of 35(1+c/2) to deter =ine therepresentative sa=ple size.The District has chosen theformula 35(1+c/2) with c = 3',see remarks in discussion).

6. 4.7.9(c) 3.14(3) /aragraph 7 of the STS requiresparagraph 7 an engineering evaluation to

determine if the system has beenadversely affected for eachinoperable snubber. There aretwo ways by which the systemcould be adversely affected:

1) if a seis=ic event occurredwhile a snubber was inoperable,

or 2) if a snubber beca e lockedup or frozen in place duringnormal operation preventingthermal =ovement of the sup-ported co=ponent. For a pas-sive failure, such as leakageof fluid, the snubber wouldstill allow the supported com-ponent to move freely so thesystem would not be adverselyaffected unless a seismic eventoccurred while the snubber wasinoperable. If the engineering-

evaluation shows the componentsto be capabl( of meeting the de-signed' service without the failedsnubber, that snubber may be de-leted from service and Table 2-6(a) and (b) per specification

2.18 (4) . Deletions will be allowed. jonly after an independent review .

of the engineering justificationis performed and the deletions are

. approved by SARC.

7. 4.7.9(d) : 3.14 (3) The section on !' Hydraulic Snubbers.,

Functional Test Acceptance Criteria"-

- has been deleted in order to be con-' sistent with the existing-Section

3.14 and other similar sectionsof-the Fort Calhoun Station Tech-nical Specifications. 'TheDistrict feels that detailed

_

_ _.

Page 25: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

- __

. .

-6--

Section or Section orSubsection Subsection

of STS Proposed TS Remarks

7. (Continued) acceptance criteria are too cum-bersome for Technical Spesifi-cations and are more appropriatelyplaced in the specific surveillanceprocedures. There are, in fact,acceptance criteria already out-lined in ST-HSS-4 for functionaltesting of hydraulf.c snubbers.

8. 4.7.9 3.14 The statement " snubbers excludedBasis Basis from this inspection program areparagraph l' paragraph 1 those installed on non-safety

related systems and then onlyif their failure or failure ofthe system on which they areinstalled would have no adverseeffect on any safety-relatedsystem" has been replaced by"all snubbers listed in Table2-6 (a) and (b) are requiredoperable". This list meetsall of the requirements of, andis more specific than, the pre-ceding statement.

.

9. 4.7.9 3.14 The wording has been changedBasic Basis from " inoperable snubber" toparagraph 4 "a snubber that is locked up

or frozen in place during normal*

operation or when a snubber isinoperable during a seismic

event" (see remarks for No. 6).

i

| -

.

G

O

,er, -re.---pr-e==r++=s. w u- # 3->w +=,+e p-- w e eye *

Page 26: Shock Suppressors (Snubbers) · 2020. 1. 17. · TABLE 2-6 (a), ACCESSIBILITY OF SAFETY-RELATED SYSTEM HYDRAULIC SNUBBERS Located Accessible In High Difficult to During Inaccessible

.. .- - - .- - -. _-. _ - .

. ...

JUSTIFICATION FOR FEE CLASSIFICATION

The proposed amendment is deemed to be a Class III amendmentin that it involves a single safety issue, snubber surveillance,and its acceptability has been identified by a Commission position,as detailed in the Commission's letter dated November 20, 1980.

.

,

e

i

,

?

r

i

.

|-|

|

l

.

.

!.

.

|. ATTACHMENT CL

F ...

L_ . - , - ~ ~ _ . . . . ~ _ . . . . . . . _ . . . , ,