severn trent water limited: midlands uk coverage 8 million population served 133 water treatment...

22
Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km sewers The Present and Future of Anaerobic Digestion and Combined Heat and Power Ken Shapland BSc CSci CChem MRSC Ken Shapland BSc CSci CChem MRSC FCIWEM FCIWEM

Upload: paulina-mclaughlin

Post on 29-Jan-2016

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Severn Trent Water Limited:• Midlands UK coverage• 8 Million population served• 133 Water Treatment Works• 46000 km water pipes• 1050 Sewage Works• 54000 km sewers

The Present and Future of Anaerobic Digestion and Combined Heat and Power

Ken Shapland BSc CSci CChem MRSC Ken Shapland BSc CSci CChem MRSC FCIWEMFCIWEM

Page 2: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Menu:

• What is AD?

• What is CHP?

• Why AD in the Water Industry?

• Development of AD/CHP in STWL

• Regulatory Framework

• Current Capability and Aspirations for the Future

Page 3: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

What is AD?

• Biogas first used for heating bath water in Assyria during the10th century BC and in Persia during the 16th century.

• 17th century - Jan Baptita Van Helmont discovered that decaying organic material produced a flammable gas.

• 1776 - Count Alessandro Volta discovered the amount of gas produced was proportional to the amount of organic material used.

• 1808 - Sir Humphrey Davy concluded that methane was in gases produced by decaying cattle manure.

Page 4: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

What is AD (2)?

• First AD built by a leper colony in Mumbai, India in 1859.

• 1895 - biogas collected from a sewage system and used in street lamps.

• 1930-50’s - research isolated and identified anaerobic bacteria and studied the best conditions for their growth.

Page 5: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

What is AD (3)?

• Stage 1– hydrolysis and fermentation - cellulose, protein and

lipids in the organic material broken down by anaerobic micro-organisms.

• Stage 2– acid phase where organic acids produced in Stage 1

are converted by acetogenic bacteria to smelly volatile acids (e.g. acetic, butyric, valeric), carbon dioxide and hydrogen.

• Final ‘Methanogenesis' Stage– methane-generating micro-organisms produce

methane and carbon dioxide from the volatile acids produced in the earlier two stages.

ALL STAGES ARE CARRIED OUT IN THE SAME VESSEL AT THE SAME TIME IN CONTINUOUSLY FED CONVENTIONAL

MAD

Page 6: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

AD Process

Biodegradable Organic

Waste

Anaerobic Digester

Digestate Biogas

Agriculture and other Outlets

Continuously FedMaintained at 350C“Mesophillic”

Gas Holder

Page 7: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Biogas

• Methane generated from AD is called Biogas

• Consists of approximately 60% methane and 40% carbon dioxide together with some minor impurities (H2S, water, siloxanes)

Page 8: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

What is CHP?

• CHP is the combustion of biogas to produce heat and electricity

• Combustion takes place in engines which are similar to conventional diesel engines

• Engines are often dual-fuel so they can be operated on fuel oil if the supply of biogas is interrupted

Page 9: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

AD Process

Biodegradable Organic

Waste

Anaerobic Digester

Digestate Biogas

Agriculture and other Outlets

Continuously FedMaintained at 350C“Mesophillic”

Gas Holder

Page 10: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

AD/CHP Process

Biodegradable Organic

Waste

Anaerobic Digester

Digestate Biogas

Agriculture and other Outlets

Continuously FedMaintained at 350C“Mesophillic”

Gas Holder

CHP Engines Hea

tPowe

r

Page 11: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Why AD is Used in the Water Industry?

• Because plenty of feedstock is received!

• Sludge from our sewage treatment processes.

• Readily biodegradable input to AD

• Produces renewable energy and heat

• Benefits from Renewable Obligation Certificate (ROCs)

• Product from AD is more suitable for use in agriculture

Page 12: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Development of AD/CHP in Severn Trent

• Anaerobic digestion used since 1950s

• First major plant built at Birmingham STW in 1950’s

• Originally used converted marine engines for CHP

• Over 40 AD/CHP installations in 2008

Page 13: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Further Advances in AD Technology

• Acid Phase Digestion (APD) is being introduced

– APD separates the process i.e. acetogenesis and hydrolysis stages from methanogenesis

• Advantages:• Greater volatile solids destruction than a

conventional mesophilic process• Increased gas production• Achieves greater volatile solids destruction

resulting in a greater reduction of solids

• Disadvantages• More complex

Page 14: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

APD SCADA (MIMIC)

Page 15: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Environmental Regulation

Biogas

• Biogas could be viewed as:

– A product of anaerobic digestion of waste

– A by-product of the above process

– A waste

Page 16: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Biogas

•The Environment Agency consider biogas to be a waste

– Although it does appear to satisfy European guidance criteria for by-product status

Page 17: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Biogas

•The Environment Agency consider biogas to be a waste

– Although it does appear to satisfy European guidance criteria for by-product status

•Consequence– Combustion of biogas is fully regulated

under Environmental Permitting Regulations

Page 18: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

CHP

• Transposition of IPPC Directive into UK law reduced the threshold for more rigorous permits from 50 to 3 MW thermal input

• Installations between 0.4 to 3 MW require an environmental permit

• Installations under 0.4 MW can be registered as an exempt activity

• Combustion activities are aggregated if considered associated or technically connected

Environmental Regulation

Page 19: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

CHP• Transposition of IPPC Directive into UK law reduced the

threshold for more rigorous permits from 50 to 3 MW thermal input

• Installations between 0.4 to 3 MW require an environmental permit

• Installations under 0.4 MW can be registered as an exempt activity

• Combustion activities are aggregated if considered associated or technically connected

• Consequence– Does not encourage the innovative provision of

CHP– Incentive to design installations under thresholds

despite capability– Cost benefit analysis is heavily dependant on

permit requirements– New entrants are deterred e.g. agricultural sector

Environmental Regulation

Page 20: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

Current Capability and Aspirations for the Future

• 41 AD/CHP plants in 2008

• 162 Giga Watt Hours produced in 2007/08

• 17% of the electricity used in the Company in 2007/08

• Sufficient to power over 46,000 homes

• STWL produced 45% of the renewable energy from biogas in England & Wales in 2007/8

• Additional 3.6 MW being installed in 2008/09

Page 21: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

How We Compare to Others in Sector

Chart based on Ofgem ROC register for 2006/07.

• In 2006/07 we received 42% of all the ROC’s issued for CHP

• 45% in 2007/08

ROC's Registered By Water Sector During 2006/07

4% 1%

4%3%16%

20%

7% 3%

42%

Anglian Water Services Limited Northumbrian Water Ltd Severn Trent Water Ltd

South West Water Ltd Southern Water Thames Water Utilities Ltd

United Utilities Wessex Water Services Ltd Yorkshire Water

Page 22: Severn Trent Water Limited: Midlands UK coverage 8 Million population served 133 Water Treatment Works 46000 km water pipes 1050 Sewage Works 54000 km

“The water industry will be at the hub of a national anaerobic digestion infrastructure. Where appropriate, water companies will generate additional renewable energy by using their spare capacity to process other feedstocks such as food waste.”Key Stakeholder AimThe water companies will seek to ensure that at least 20% of all energy used by the UK water industry comes from renewable sources by 2020. Anaerobic digestion will make an important contribution to this.

Severn Trent Water target is 30% by 2012/13

Support for UK Government Aspirations