service manual 9. maintenance...discharge temperature sensor is open/short circuited f5 ¿ ¿ during...
TRANSCRIPT
![Page 1: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/1.jpg)
44 Installation and Maintenance
Service Manual
9. Maintenance9.1 Precautions before Maintenance
-pacitor after power off.
-
--
nance safely.
A
B
AB
discharge resistance orplug of soldering iron
![Page 2: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/2.jpg)
45Installation and Maintenance
Service Manual
9.2 Error Code List
NO.MalfunctionName
Display Method of Indoor Unit
Display Method of Outdoor Unit
(Indicator has 3 kinds of display status and they will be displayed circularly every 5s.) A/C status Possible Causes
Dual-8Code
Display
Indicator Display (during blinking, ON 0.5s and OFF 0.5s)
□OFF■Illuminated Blink
OperationIndicator
CoolIndicator
HeatingIndicator
D5(D40)
D6(D41)
D16(D42)
D30(D43)
1
High pressureprotection of system
E1
During cooling and dryingoperation, except indoor fan operates, all loads stop operation.During heating operation, the complete unit stops.
Possible reasons: 1. Refrigerant was superabundant; 2. Poor heat exchange (including
and bad radiating environment );Ambient temperature is too high.
2 Antifreezingprotection E2
During cooling and dryingoperation, compressor andoutdoor fan stop while indoor fan operates.
1. Poor air-return in indoor unit;2. Fan speed is abnormal;3. Evaporator is dirty.
3
High dischargetemperatureprotection ofcompressor
E4
During cooling and dryingoperation, compressor andoutdoor fan stop while indoor fan operates. During heatingoperation, all loads stop.
Please refer to the malfunction analysis (discharge protection, overload).
4 Overcurrentprotection E5
During cooling and dryingoperation, compressor andoutdoor fan stop while indoor fan operates. During heatingoperation, all loads stop.
1. Supply voltage is unstable;2. Supply voltage is too low and load is too high;3. Evaporator is dirty.
5Communi-cationMalfunction
E6
During cooling operation,compressor stops while indoor fan motor operates. During heating operation, the complete unit stops.
Refer to the corresponding malfunction analysis.
6
Hightemperatureresistantprotection
E8
During cooling operation:compressor will stop while indoor fan will operate. During heating operation, the complete unit stops.
Refer to the malfunction analysis (overload, high temperature resistant).
7
PG motor (indoor fan motor) doesnot operate
H6
I n d o o r f a n , o u t d o o r f a n , compressor and electric heat tube stop operation. Horizontal louver stops at the current position.
1. The feedback terminal of PG motor is not connected tightly.2. The control terminal of PG motor isnot connected tightly.3. Fan blade rotates unsmoothly.4. Malfunctionof moto.r5. Controller is damaged.
8Malfunctionprotection ofjumper cap
C5
Operation of remote controller or control panel is available, but the unit won't act.
1. There's not jumper cap on the controller.2. Jumper cap is not inserted properly and tightly3. Jumper cap is damaged.4. Controller is damaged.
9
Indoor ambienttemperaturesensor isopen/shortcircuited
F1
During cooling and dryingoperation, indoor unit operateswhile other loads will stop; during heating operation, the complete unit will stop operation.
1. The wiring terminal between indoor ambient temperature sensor and controller is loosened or poorly contacted;2. There's short circuit due to trip-over of the parts on controller;3.Indoor ambient temperature sensor is damaged(Please check it by referring to the resistance table fortemperature sensor) 4. Main board is broken.
![Page 3: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/3.jpg)
46 Installation and Maintenance
Service Manual
NO. MalfunctionName
Display Method of Indoor Unit
Display Method of Outdoor Unit
(Indicator has 3 kinds of display status and they will be displayed circularly every 5s.) A/C status Possible Causes
Dual-8Code
Display
Indicator Display (during blinking, ON 0.5s and OFF 0.5s)
□OFF■Illuminated Blink
OperationIndicator
CoolIndicator
HeatingIndicator
D5(D40)
D6(D41)
D16(D42)
D30(D43)
10
Indoorevaporatortemperaturesensor isopen/shortcircuited
F2
The unit will stop operation as it reaches the temperature point. During cooling and drying operation, except indoor fan operates, other loads stop operation; During heating operation, the complete unit stops operation.
1. The wiring terminal between indoor evaporator temperature sensor and controller is loosenedor poorly contacted;2. There's short circuit due to the trip-over of the parts on controller;3.Indoor evaporator temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor)4. Main board is broken.
11
Outdoor ambienttemperaturesensor isopen/shortcircuited
F3
During cooling and dryingoperating, compressor stops while indoor fan operates; During heating operation, the complete unit will stop operation
Outdoor temperature sensor hasnt been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor)
12
Outdoorcondensertemperaturesensor isopen/shortcircuited
F4
During cooling and dryingoperation, compressor stops while indoor fan will operate; During heating operation, the complete unit will stop operation.
Outdoor temperature sensor hasnt been connected well or is damaged. Please check it by referring to the resistance table for temperature sensor)
13
Outdoordischargetemperaturesensor isopen/shortcircuited
F5
During cooling and dryingoperation, compressor will sopafter operating for about 3 mins,while indoor fan will operate;During heating operation, thecomplete unit will stop afteroperating for about 3 mins.
1.Outdoor temperature sensor hasnt been connected well or is damaged. Please check it byreferring to the resistance table for temperature sensor)2.The head of temperature sensor hasnt been inserted into the copper tube
14
Limit/decreasefrequency due tooverload
F6
All loads operate normally, whileoperation frequency forcompressor is decreased
Refer to the malfunction analysis (overload, high temperature resistant)
15Decreasefrequency due toovercurrent
F8All loads operate normally, whileoperation frequency forcompressor is decreased
The input supply voltage is too low;System pressure is too high and overload
16
Decreasefrequency due tohigh airdischarge
F9
All loads operate normally, whileoperation frequency forcompressor is decreased
Overload or temperature is too high;
Malfunction of electric expansion valve (EKV)
17Voltage for DC bus-bar is too high
PH
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 265VAC, turn on the unit after the supply voltage is increased to the normal range.2 . I f the AC input is normal , measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
18Malfunction of complete units current detection
U5
During cooling and dryingoperation, the compressor willstop while indoor fan will operate; During heating operating, the complete unit will stop operation.
Theres circuit malfunction on outdoor units control panel AP1, please replace the outdoor units control panel AP1.
19
Overcurrentprotection ofphase current for compressor
P5
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
![Page 4: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/4.jpg)
47Installation and Maintenance
Service Manual
NO. MalfunctionName
Display Method of Indoor Unit
Display Method of Outdoor Unit
(Indicator has 3 kinds of display status and they will be displayed circularly every 5s.) A/C status Possible Causes
Dual-8Code
Display
Indicator Display (during blinking, ON 0.5s and OFF 0.5s)
□OFF■Illuminated Blink
OperationIndicator
CoolIndicator
HeatingIndicator
D5(D40)
D6(D41)
D16(D42)
D30(D43)
20 Defrosting
Defrosting will occur in heatingmode. Compressor will operatewhile indoor fan will stopoperation.
Its the normal state
21Overloadprotection forcompressor
H3
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
1. Wiring terminal OVC-COMP is loosened. In normal state, the resistance for this terminal shouldbe less than 1ohm. 2.Refer to the malfunction analysis ( discharge protection, overload)
22 IPM protection H5
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
23 PFC protection HC
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
Refer to the malfunction analysis
24Desynchron-izing of compressor
H7
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
Refer to the malfunction analysis (IPM protection, loss of synchronism protection and overcurrent protection of phase current for compressor.
25 Failure start-up LC
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop operation.
Refer to the malfunction analysis
26
Malfunction of phase currentdetection circuit for compressor
U1
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
Replace outdoor control panel AP1
ON 10s and OFF 0.5s
![Page 5: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/5.jpg)
48 Installation and Maintenance
Service Manual
NO. MalfunctionName
Display Method of Indoor Unit
Display Method of Outdoor Unit
(Indicator has 3 kinds of display status and they will be displayed circularly every 5s.) A/C status Possible Causes
Dual-8Code
Display
Indicator Display (during blinking, ON 0.5s and OFF 0.5s)
□OFF■Illuminated Blink
OperationIndicator
CoolIndicator
HeatingIndicator
D5(D40)
D6(D41)
D16(D42)
D30(D43)
27 EEPROMmalfunction EE
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
Replace outdoor control panel AP1
28Chargingmalfunction of capacitor
PU
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
Refer to the part three—charging malfunction analysis of capacitor
29Malfunction of moduletemperaturesensor circuit
P7
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
Replace outdoor control panel AP1
30Module hightemperatureprotection
P8
During cooling operation,compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
After the complete unit is de-energized for 20mins, check whether the thermal grease on IPM Module of outdoor control
whether the radiator is inserted tightly. If its no use, please replace control panel AP1.
31Malfunction of voltagedropping forDC bus-bar
U3
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
Supply voltage is unstable
32Voltage of DC bus-bar is too low
PL
During cooling and dryingoperation, compressor will stopwhile indoor fan will operate;During heating operation, thecomplete unit will stop
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 150VAC,turn on the unit after the supply voltage is increased to the normal range.2.If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if its normal, theres malfunction for the circuit, please replace the control panel (AP1)
33
Limit/decreasefrequency due to hightemperature of module
EU
All loads operate normally, whileoperation frequency forcompressor is decreased
Discharging after the complete unit is de-energized for 20mins, check whether the thermal grease onIPM Module of outdoor control
whether the radiator is inserted tightly.If its no use, please replace control panel AP1.
34The four-wayvalve isabnormal
U7
If this malfunction occurs duringheating operation, the completeunit will stop operation.
1.Supply voltage is lower than AC175V;2.Wiring terminal 4V is loosened or broken;3.4V is damaged, please replace
.
35
Limit/decreasefrequency due toantifreezing
FH
All loads operate normally, whileoperation frequency forcompressor is decreased
Poor air-return in indoor unit or fan speed is too low
![Page 6: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/6.jpg)
49Installation and Maintenance
Service Manual
9.3 Troubleshooting for Main Malfunction
1. Malfunction of Temperature Sensor F1, F2
Troubleshooting for F1,F2 malfunction
Isthe wiring terminal between the
temperature sensor and the controllerloosened or poorly contacted?
Insert the temperaturesensor tightly
yes
Is malfunctioneliminated
Is there short circuit due to trip-over ofthe parts?
Make the parts upright
yes
Is malfunctioneliminated
Replace the mainboard with the same model.
End
no
no
Is the temperature sensor normal according
to the ResistanceTable?
no
Replace it with atemperature sensorwith the same model
no
yes
yesIs malfunctionremoved
no
yes
yes
no
![Page 7: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/7.jpg)
50 Installation and Maintenance
Service Manual
2. Malfunction of Blocked Protection of IDU Fan Motor H6
interface terminal 2 and 3 is 15VDC
interface terminal 2 and 4
interface terminal 1 and 2 within
![Page 8: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/8.jpg)
51Installation and Maintenance
Service Manual
Appearance ofthe jumper cap
Troubleshooting for C5malfunction
Is there jumper cap on themainboard?
Isthe jumper cap inserted
correctly and tightly?
Replace the jumper capwith the same model
End
yes
yes
Assemble the jumpercap with the samemodel
no
Is malfunctioneliminatedno
yes
Insert thejumper cap
tightly
Is malfunctioneliminated
no
no yes
Is malfunctioneliminated
no
yes
Replace the mainboard with the same model.
3. Malfunction of Protection of Jumper Cap C5
![Page 9: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/9.jpg)
52 Installation and Maintenance
Service Manual
4. Communication malfunction E6
Start
Cut off power, check if the wire between indoor unit and outdoorunit, and the wire inside electric box are connected correctly
Connected correctly? No
No
No
No
NoNo
No
End
Yes
Yes
Yes
Yes
Yes
Yes
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Malfunction is eliminated
Replace outdoormainboard
Replace indoormainboard
Communication wire connection is broken?
Replace the wire
Is there incorrectmatch between the mainboardand the display panel or between
the indoor and outdoor mainboards?
Match them according tothe requirement
Reconnect the wire according towiring diagram
Yes
![Page 10: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/10.jpg)
53Installation and Maintenance
Service Manual
Test1
Test2Test3 Test4
Test5
E
G
I
H
FD
B
A
C
L
Test9
Test6
KJ
Tset7
M
N
Test11
Test10Test8
S
TTest12
1.Key detection point
Test NO Test point Corresponding component conditionTest 1 Between A and C 160V~265VTest 2 Between B and C 160V~265VTest 3 Between D and E DC 180V~380V Test 4 Electrolytic capacitor of power DC 180V~380V Test 5 Two ends of diode D15 DC 14.5V~15.6V
Test 6 Two ends of electrolytic capacitor C715 DC 12V~13V
Test 7 Two ends of electrolytic capacitor C710 DC 5V
Test 8 Two ends of electrolytic capacitor C226 DC 3.3V
Test 9 C912 DC 15V~18V
Test 10 Between M to GNDTest 11 Between N to GNDTest 12 Between S and T DC 56V
![Page 11: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/11.jpg)
54 Installation and Maintenance
Service Manual
2.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)
Main detection point:
N
Y
N
Y
N
Y
N
Y
N
Y
Turn on the unit and wait 1 minute
Use DC voltmeter to measure the
voltage on the two ends of electrolytic
capacitor
Voltage higher than 200V?Fault with the voltage
testing circuit on control panel AP1
Replace the control panel AP1
Measure the AC voltage between terminalL andN on wiring boardXT(power supply)
Voltage within 210VAC~250VAC?
Shut down the powerand repair the powersupply to restore therange210VAC~250VAC
power on andrestart the unit
If the fault iseliminated?
Shut down the power and wait 20 minutes; oruse DC voltmeter to measure the voltage on the two ends of capacitor (test3), until the voltage is lower than 20V
Check the connection of reactor(L in the Electrical Wiring Diagram)
If the wiring of reactor L is normal?
Connect the reactorLaccording to Elec-trical Wiring Diagr-am correctly
Re-energize andturn on the unit
If the fault iseliminated?
End
Replace the control panel AP1
![Page 12: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/12.jpg)
55Installation and Maintenance
Service Manual
3.IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (AP1 below is control board of outdoor unit)
Main detection point:
![Page 13: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/13.jpg)
56 Installation and Maintenance
Service Manual
Energize and switch on
IPM protection occurs after the
machine has run for a period of time?
Use AC voltmeterto measure the voltage betweenterminal L and N on the wiring board XT)
If the voltage between terminal L and N on wiringboard XT is within 210VAC~250VAC?
Check the supply voltage and restore it to
210VAC~250VAC
Voltage between the two ends of celectrolytic
capacitor (test3) is
Restart theunit. Beforeprotection occurs,use DC voltmeter tomeasure the voltage
between the two ends of electrolyticcapacitor on control
panel AP1 (test3)
If the unit can work
normally?
Please confirm: 1. If the indoor and outdoor heatexchangers are dirty? If they are obstructed by other
objects which affectthe heat exchange of indoor andoutdoor unit. 2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting inthat the system
pressure is too high and exceeds the
permissible range? 4. If the chargevolume ofrefrigerant is too much, resulting in that the systempressure is too high?
5. Other conditionsresulting in that the system pressurebecomes too high.
The connectionof capacitor C2
is loose.
Reconnect the capacitor C2 according to Electrical WiringDiagram. Then,Restart theunit.
Stop the unit and disconnect the power supply. Wait 20 minutes, or use DC voltmeter tomeasure the voltage
between the two ends ofcapacitor C2, until the
voltage is lower than 20V
Replace the capacitor C2. Then, energize and start the unit.
Replace the control panel AP1
Take corrective actions according to TechnicalService Manual, and
then energize and start the unit.
If there is any abnormality
described above?
Replace the control panel AP1
If the connection between AP1 and COMP is unsecure or the connection order is wrong?
Connect the control panelAP1 and compressorCOMP correctly according to the Electrical WiringDiagram. Then, energizeand start the unit.
Use ohmmeter tomeasure the resistancebetween the three terminals on compressorCOMP, and compare the measurements with the
compressor resistance on Service Manual.
If the resistance is
normal?
Use ohmmeter tomeasure the resistancebetween the two
terminals of compressorCOMP and copper tube.
Replace the compressor
COMP
Resistance higherthan 500MΩ?
Replace the control panel
AP1
END
Y N
YN
Y
N
Y
If the unit can work normallv? Y
If the unit can work normally? Y
N
N
Y
N
If the unit can worknormally? YY
N N
If the unit can work
normally?Y
Y
N
Y
N
N
Y
higher than 250V
Remove the wires on the two ends ofcapacitor C2. Then,use capacitancemeter to measurethe capacitor C2.Verify as per theParameters Sheet.
Stop the unit and disconnect the power supply. Then, check the connection ofcapacitor C2according to ElectricalWiring Diagram.
If capacitorC2 is failed?
Refer to the Electrical Wiring Diagram and check if the connectionbetween AP1 andCOMP is loose and ifthe connection orderis correct.
![Page 14: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/14.jpg)
57Installation and Maintenance
Service Manual
4.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)
Main detection point:
1. Check if fan terminalOFAN is connected well2. Test if resistance value of any two terminals is less than 1k with ohmic meter
If the indoor and outdoorfan work well?
After the unit de-energized for 20min
Replacecontrol board
AP1
If the radiating of outdoor and indoor unit is well?
Improve theradiating
environment ofunit
Replaceoutdoor fan
Y
Replace fan capacitor C1
Anti-high temperature,overload protection
Normal protection, please use it after improve the outdoor
ambient temperature
If the outdoor ambient temperature is higher than 53 ºC?
N
Y
N
Y
N
End
![Page 15: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/15.jpg)
58 Installation and Maintenance
Service Manual
5.Diagnosis for failure start up malfunction (AP1 below is control board of outdoor unit)
Main detection point:
Energize the unit and start it
If the compressor wire COMP(UVW) iswell connected and connection sequence
is correct
Replace control board AP1
Replace the compressor
If malfunction is removed?
If the stop time of compressor is more than 3min?
N
If the stop time is not enough and the high and low pressure of system is not balance , please start it after 3min
Improve the connection situation of control board AP1 and compressor COMP, connect itwith wiring diagram
N
Y
N
If the refrigerant charging is too much?
Y
Does the unit start up normally?
N
Charge the refrigerant accordingto service manual
Y
Does the unit start up normally?
N
Y
End
![Page 16: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/16.jpg)
59Installation and Maintenance
Service Manual
6. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)
Main detection point:
If the compressor wire COMP(UVW) is well connected, the connection sequence
forwards to clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replacecompressor
If the outdoor fan works normally?
If the stop time ofcompressor is more than
3min
Synchronism afterenergize the unit
and start it
Connectwire well
Synchronismoccurred during
operation
Replacecontrol board
AP1
If the radiating of unit is well?
Remove
malfunction?
Improve the radiating of unit (clean heatexchanger and increase ventilation)
Replace fan capacitor C1
Replace
outdoor fan
Y
N
N
N
Y
Y
N
Replace
control board
AP1
Remove
malfunction?
Replacecompressor
Y
N
N
Y
If the input voltage of unitis normal?
Start to run until thepower resume normalvoltage
N
If the refrigerant is too much?
Charge the refrigerant withservice manual
Y
Y
N
YEnd
End
![Page 17: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/17.jpg)
60 Installation and Maintenance
Service Manual
7.Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)
Main detection point:
Connect wirewell with wiring diagram
Replace EKV coil of electron
expansion valve
If the wiring terminal FA of electron expansion is well connected?
Removemalfunction?
The resistance value offirs t 4 l ead fo ot an d th e
fif th lead foot is similar,
less than 100
After the unit de-energized
for 20min
Removemalfunction?
Y
N
N
N
If the overload protector SAT is well connected?
N
Under ambient temperature, test the resistance of overload protector with ohmic
Y
Y
Replaceoverload
protector SAT
N
Y
Check refrigerant, if there isleakage, please refer to
specification
Replacecontrol board
AP1
End
![Page 18: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/18.jpg)
61Installation and Maintenance
Service Manual
8.PFC (correction for power factor) malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)
Main detection point:
Start
If the resistance value is 0
Remove PFC capacityand test resistance of
two terminals
Capacity isshort
circuit and replace it
YRe-energizethe unit and
start it
Cut the terminal of reactor,test the resistance
between two terminals ofreactor with ohmic meter
Replace the reactor
Re-energize
the unit and start it
Check the connection wireof reactor (L) ofoutdoor unit and
PFC capacity
If there is damaged short circuit
Replaceconnection
wire with circuitdiagram
Replacecontrol board
AP1
Y
N
N
Y
N
N
N
N
If there is damaged short circuit
If the malfunction isremoved?
If the malfunction isremoved?
If the malfunction isremoved?
Y
Y
Y
End
![Page 19: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/19.jpg)
62 Installation and Maintenance
Service Manual
9.Communication malfunction (AP1 below is control board of outdoor unit)
Main detection point:
-aged
Start
Check communication circuit of outdoor unit
Problem ofcommunication
circuit
Check built-in wiring ofindoor and
outdoor unit
Connectioncorrect?
Malfunction ofcircuit is
detected withcontrol board AP1 voltage
Check connectionwire of indoor and outdoor unit withcircuit diagram
Check connectionwire of indoor and outdoor unit withcircuit diagram
If the unit is operation normal before malfunction
Y
N
Y
N
If the wiring is damaged?
If the malfunction is removed?
N
Y
N
If the malfunction is removed?
N
Replace indoor board
Replace outdoormainboard AP11
If the malfunction is
removed?
Y
N
Y
N
Y
YEnd
![Page 20: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/20.jpg)
63Installation and Maintenance
Service Manual
10.Diagnosis process for outdoor communication circuit
Start
Test voltage value with Test10 position indiagram withvoltage meter
Number jumping
Outdoor unit malfunction
Test voltage value with Test13 position indiagram withvoltage meter
Number jumping
Test voltage value with Test11 position indiagram withvoltage meter
Number jumping
Test voltage value with Test12 position indiagram withvoltage meter
Y
Y
Y
Y
Number jumping
The circuit ofoutdoor unit
communicationis normal
Y
N
N
N
N
End
![Page 21: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/21.jpg)
64 Installation and Maintenance
Service Manual
motor is set too low Small wind blow
conditioner
range
Add refrigerant.
details
details
Compressor can't operate details
9.4 Troubleshooting for Normal Malfunction1. Air conditioner can't be started up
2. Poor cooling (heating) for air conditioner
3. Horizontal louver can't swing
connected well. Wrong wire connection between
or poor connection for wiring terminals
once
reliably
correctly
improper
Replace batteries for remote controllerRepair or replace remote controller
Wrong wire connection, or poor connection diagram
Connect wires according to wiring diagram to
Stepping motor is damaged Stepping motor can't operate Repair or replace stepping motor
Main board is damaged can't operate
![Page 22: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/22.jpg)
65Installation and Maintenance
Service Manual
7. Abnormal sound and vibration
conditioner
damping plaster between connected parts
coil Replace magnetic coil
compressor
6. Air conditioner is leaking
pipeReplace drain pipe
5. Compressor can't operate
Wrong wire connection, or poor connection diagram
Connect wires according to wiring diagram to
Capacity of compressor is damaged
fan capacitor.
between compressor terminals and it's 0 Repair or replace compressor
Compressor can't operate Repair or replace compressor
4. ODU fan motor can't operate
Wrong wire connection, or poor connection diagram
Connect wires according to wiring diagram to
damagedfan capacitor.
is bad and ODU compressor generates a lot of
![Page 23: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/23.jpg)
66 Installation and Maintenance
Service Manual
10. Exploded View and Parts List10.1 Indoor Unit
18K Unit
12
34
56
78
10
9
21
11
12
13
14
15
16
1718
2019
2223
24
2526
2728
30
29
31 32 33
![Page 24: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/24.jpg)
67Installation and Maintenance
Service Manual
NO.Description
Part CodeQtyGWH18TC-K3DNA1B/I
CB148N031011 20012820K 1
2 Display Board 30565141 1
3 1112209105 2
4 24252016 3
5 20012821 1
6 10512225 1
7 1051222601 1
8 2611236701 1
9 1051203701 2
10 Step Motor 1501208603 1
11 7651205102 1
12 Ring of Bearing 26152025 1
13 10352045 1
14 24212139 1
15 0100238601 1
16 1252123 1
17 Motor Press Plate 26112330 1
18 1501212701 1
19 Drainage Hose 523001406 1
20 Pipe Clamp 26112188 1
21 Rear Case assy 22202361 1
22 Step Motor 1501208602 1
23 Step Motor 1521212901 1
24 10542036 2
25 Electric Box 20112181 1
26 Terminal Board 42011233 1
27 Main Board 30138000314 1
28 4202300111 1
29 20122142 1
30 2012240901 1
31 Connecting Cable 4002052317 0
32 Connecting Cable 4002054027 0
33 Remote Controller 30510137 1
![Page 25: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/25.jpg)
68 Installation and Maintenance
Service Manual
24/28K Unit
44
4241
43
1 2 3 4 5 6 78
9
10
1112
13
14 15 16
171819
2223
24
272829303132
3334
35
3637
38 39 40
26 25
45 47
2120
46
![Page 26: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/26.jpg)
69Installation and Maintenance
Service Manual
NO.Description
Part CodeQtyGWH24TD-K3DNA1C/I GWH28TD-K3DNA1B/I
CB148N04101 CB148N034011 20012894U 20012894U 12 11122136 11122136 23 242520053 242520053 44 20022004 20022004 15 10512236 10512236 16 1051223701 1051223701 17 1058211601 1058211601 18 10512252 10512252 159 1051203701 1051203701 2
10 Water Tray Assy 20182148 20182148 111 22202092 22202092 112 10352420 10352420 113 76512203 76512203 114 24212041 24212041 115 01002000041 01002000013 116 01252398 01252398 117 Sensor Insert 390000451 / 118 2421204201 2421204201 119 15012134 1501213401 120 26112324 26112324 121 26112325 26112325 122 Pipe Clamp 26112071 26112071 123 2112009 02112009 124 Drainage Hose 0523001403 0523001403 125 76712012 76712012 126 Step Motor 1521212602 1521212602 127 Step Motor 1521240208 1521240208 128 73012021 73012021 229 Step Motor 1521212301 1521212301 130 Motor Holder 26152046 26152046 131 1058211501 1058211701 132 1058211501 1058211501 133 Terminal Board 42011233 42011233 134 10542036 10542036 335 Main Board 30138000314 30138000314 136 2012214209 20122142 137 Display Board 30565141 30565141 138 1592108 01592108 139 2012216401 20122164 140 1592107 01592107 141 Electric Box 2012216401 20112140 142 Electric Box Assy 2012214209 10000200218 143 Connecting Cable 4002052330 4002052330 044 Connecting Cable 4002054026 4002054026 045 390000451 390000451 146 390000598 390000598 147 Remote Controller 30510137 30510137 1
![Page 27: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/27.jpg)
70 Installation and Maintenance
Service Manual
10.2 Outdoor Unit
GWH18TC-K3DNA1B/O(DRED) GWH24TD-K3DNA1C/O(DRED)
![Page 28: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/28.jpg)
71Installation and Maintenance
Service Manual
NO.Description Part Code
QtyGWH18TC-K3DNA1B/O(DRED) GWH24TD-K3DNA1C/O(DRED)CB148W03101 CB148W04101
1 15015064 15015063 1
2 01413148 / 1
3 Terminal Board 42010194 42010194 1
4 Electric Box 20113015 20115002 1
5 Radiator 49010252 49015215 1
6 Main Board 30138000287 30138000285 1
7 01413150 20125002 1
8 Electric Box Assy 10000100025 10000100026 1
9 Left Handle 26235401 26235401 1
10 Left Side Plate 01305093P 01305093P 1
11 01705259 01705125 1
12 / 01795031 1
13 01255005P 01255005P 1
14 Reactor 43130021 43130024 1
15 01232902 01235081 1
16 Condenser Assy 1163449 01163617 1
17 Rear Grill 01473043 01475020 118 Wiring clamp 26115004 71010102 1
19 3900030901 3900030902 1
20 Capacitor CBB65/CBB61 33000065 33010012 1
21 1413098 / 1
22 Handle 26235254 26235254 1
23 07133157 07133844 1
24 07130239 07130239 1
25 01713098P 01705046P 1
26 01305094P 01305090P 1
27 3063929 03163054 1
28 3123664 03073159 1
29 Magnet Coil 4300040045 4300040078 1
30 / / /
31 00103807 0010505701 1
32 0280306203P 01205816P 1
33 Drainage Connecter 06123401 06123401 1
34 6813401 06813401 3
35 10335008 10335008 1
36 20113003 / 1
37 1535013 01535013P 1
38 22415002 22415002 1
![Page 29: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/29.jpg)
72 Installation and Maintenance
Service Manual
GWH28TD-K3DNA1B/O(DRED)
![Page 30: Service Manual 9. Maintenance...discharge temperature sensor is open/short circuited F5 ¿ ¿ During cooling and drying operation, compressor will sop after operating for about 3 mins,](https://reader033.vdocuments.mx/reader033/viewer/2022060823/609c52e7ff9f99561f4b470a/html5/thumbnails/30.jpg)
73Installation and Maintenance
Service Manual
NO.Description Part Code
QtyGWH28TD-K3DNA1B/O(DRED)CB148W03401
1 22415003 1
2 15014034 1
3 01413426 1
4 Radiator 49010252 1
5 Main Board 30138000286 1
6 Electric Box Assy 10000100031 1
7 01715016 1
8 Terminal Board 42010194 1
9 Left Handle 26235401 2
10 Left Side Plate 01305043P 1
11 01255006P 1
12 01705437 1
13 01175092 1
14 Clapboard Assy 01233138 1
15 Condenser Assy 01163274 1
16 Rear Grill 01475013 1
17 Wiring Clamp 26115004 1
18 3900030901 1
19 Reactor 43130183 1
20 Capacitor CBB65 3300008107 2
21 01305044P 1
22 Big Handle 26235001 1
23 07133157 1
24 01715020P 1
25 01365435P 1
26 03063736 1
27 03123843 1
28 Magnet Coil 4300040045 1
29 76715022 3
30 00105051 1
31 Drainage Connecter 06123401 1
32 02803016P 1
33 6813401 3
34 10335014 1
35 01305086P 1
36 Cabinet 01435004P 1