series capacitor compensation requirements

Upload: jomoran

Post on 03-Jun-2018

226 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/12/2019 Series Capacitor Compensation Requirements

    1/35

    4 Series Capacitor Compensation Requirements

    4 1

    Purposes and Benefits of Series Capacitor Compensation

    As noted previously, transmission lines inherently have an inductive reactance that is in series

    with flow of current between the source and the load. This impedance is responsible for a

    significant portion of the voltage drops in the transmission systems and is proportional to the

    length of the transmission lines. Transmission line designers will attempt to keep the line

    reactance as low as possible because it provides significant benefit to keeping the system

    tightly connected - that is, it keeps the sources of generation electrically closer to the load.

    Higher transmission voltages can effectively reduce the influence of line reactance, not only

    because of differences in the line designs, but primarily because significantly reduced levels of

    current flow for a given amount of power being transmitted resulting in correspondingly reduced

    levels of voltage drop along the line. Based on a cost-effectiveness analysis, 345kV was

    selected as the appropriate voltage level for the CTP.

    The long distances associated with the transmission of the wind energy from the CREZ to the

    load centers results in several long transmission lines between the various system buses. Some

    of these are so long, that system stability is impacted and it becomes necessary to find a way to

    reduce the reactance associated with these lines. One method is to increase the number of

    circuits along the critical paths, but this is not economically desirable - particularly considering

    that the circuits will be under utilized for the amount of power to be transferred. A well known

    and understood method is to compensate a portion of the series line inductive reactance with a

    series capacitor. At normal system operating frequencies and from the perspective of total line

    reactance, this is the same as reducing the line length in proportion to the level of series

    compensation.

    Ideally,

    the total line reactance would be zero

    ( or at least, very

    low) suggesting

    that 100%

    compensation is desirable. However, there are other design considerations, such as the

    voltages along the length of the l ine and reson ances that can res ult in severe interactions w ith

    conventional thermal generat ion,

    which

    mu st also be considered in select ing the opt im al level of

    ser ies com pensat ion. Several of these design issu es are discusse d in m ore deta i l in Sect ions

    4.3 and 4.4.

    In order to address som e of these design issu es, series capacitors can be des igned

    with m ult iple sm aller se gmen ts placed at dif ferent locations along the

    line. Typically only one or

    two segments are used.

    In selecting the final series compensation levels for the CREZ transmission lines, multiple

    issues including line voltage profiles, voltage stability, system angular stability and

    subsynchronous resonances were evaluated. Several compensation levels up to

    75% were

    considered, but, driven

    primarily by the TSP's

    proposed l ine des ign cri teria

    ERCOT

    supported

    the f indings that com pens ation levels of approximate ly

    50% represented a good comprom ise

    ABB Grid Systems Consulting

    '28

    ERCOT

    000050

  • 8/12/2019 Series Capacitor Compensation Requirements

    2/35

    among competing constraints. The actual percentage of series compensation will vary slightly

    depending on the final length of the associated line and TSP implementation as a result of

    procurement.

    4.2

    Study Locations of Series apacitors

    Based on interim s tudy results, several changes were m ade to the CTP

    during the course of the

    study. The

    f inal series com pensated l ines and se ries capacitor locations shown in Table 4.2-1

    were us ed for the study.

    Table 4.2-1: CREZ Series Capacitor Locations as Studied

    TS P

    Line

    Circuit

    #

    Segmen t

    #

    Study Series Capaci tor Locat ion

    CTT

    Silverton-Tesla

    Mid-line

    2 Mid-line

    ETT

    Edith Clarke- Clear Crossing North

    Mid-line

    2 Mid-line

    Dermott - Clear Crossing West

    Mid-line

    2

    Mid-line

    Big Hill - Kendall

    Mid-line at Edison

    2

    Midway between Big Hill and Edison

    2

    Mid-line at Edison

    2

    2 Midway betw een Big Hill and Edison

    ONCOR

    Wil low Creek- C lear Crossing East Clear Crossing East

    2 Clear Crossing East

    Lone

    W. Shackelford - Sam Sw itch

    Rom ney 1(-1/3 from W. Shackelford)

    Star

    2 Kopperl 1 (-1 /3 from Sam Switch)

    W. S hackelford - Navarro

    2

    Romney 2

    2 2

    Kopper l2

    The locations of the series capacitor segments along the length of these lines as studied were

    provided by ERCOT and the TSPs. The ultimate locations on the lines will be established by the

    TSPs based on maintenance needs, line design criteria and similar considerations. The

    locations on the lines will not influence the reactive compensation requirements.

    The comprehensive reactive compensation plan developed for the CREZ initial build was

    developed assuming the series compensation levels indicated on the lines listed. It is therefore

    assumed that the series compensation is installed as an integral part of the initial build of the

    CREZ transmission system.

    4.3

    Study Approach to Determining Series Capacitor Requirements

    4.3. 9

    Series Capacitor Technology

    Series compensation to reduce the effective impedance of a transmission line can be

    accomplished by putting a capacitor bank in series with the line. This series capacitor bank will

    E3800-PR-00

    CREZ Reactive Power Compensation Study

    29

    0 005i

  • 8/12/2019 Series Capacitor Compensation Requirements

    3/35

    be installed on a platform that is insulated against the full line voltage since all of the equipment

    will be operating at the line voltage potential.

    A typical series capacitor bank consists of the arrangement shown in Figure 4.3-1. The actual

    design of these series capacitor banks is subject to detail design studies considering the actual

    network data and system requirements. The main components of the series compensation

    include the series capacitor bank, the MOV overvoltage protection, a bypass gap and/or bypass

    switch. All of the components, except the disconnectors and the bypass switch, are normally on

    the capacitor platform.

    Bypass

    Isolating

    disconnector

    isconnector\

    \

    Isolating

    \ disconnector

    I I--

    Discharge current

    l imit ing reactor

    M O V

    Bypass gap

    Bypass switch (breaker)

    IF-

    Platform structure

    Figure 4.3-1: Series capacitor bank main components

    During fault conditions, series capacitor units are generally subjected to overvoltages which are

    related to the fault current levels. When, like in the CREZ system, the series capacitors are at

    substations with limited transformations and long transmission lines, the highest fault currents -

    and therefore the highest overvoltages - are expected with three-phase faults. When a station

    has large transformers and shorter lines, it is possible for single-phase faults to result in higher

    fault currents. The fault current levels and the resulting overvoltages on the series capacitors

    need to be confirmed during the design stage.

    I

    ABB Grid Systems Consult ing

    30

    ERCOT

    0.00052

  • 8/12/2019 Series Capacitor Compensation Requirements

    4/35

    Fault related overvoltages may persist until the fault is cleared by opening of the line circuit

    breakers to the faulted circuit element. Modern series capacitor banks use highly non-linear

    Metal Oxide Varistors (MOV) to limit the voltage across the series capacitor to a desired

    protective level,

    which typically ranges between 2.0 and 2.5 times the voltage across the

    capacitor at the rated bank current. When limiting the voltage across the series capacitor to the

    protective level during fault conditions, the MOV must conduct the excess fault current and

    thereby absorb energy. The MOV energy is kept within the MOV's absorption capability by

    bypassing the parallel capacitor/MOV combination using two devices. The first is a very fast

    acting device called a triggered spark gap. After the spark gap is triggered, a slower acting

    bypass breaker will close. From a system performance point of view, overvoltage protection

    bypasses the series capacitor, thereby increasing the impedance of the circuit. This may, in

    turn, adversely impact network stability. The effect is not significant for faults that occur on the

    line section in which the series capacitors are located (i.e. internal faults), because the line

    section containing the series capacitor bank is eventually removed from service to allow fault

    clearing.

    For faults not on the same line as the series capacitor (i.e. external faults) the impact on system

    stability can be significant. Therefore, whichever type of overvoltage protection scheme is

    adopted, it is usually designed so that the capacitor bank is not bypassed during external faults.

    Protective bypassing is restricted by design to act only for the more severe internal faults

    exceeding the specified energy and fault current.

    Series capacitor compensation includes a microprocessor based control and protection system

    and the inputs are the currents measured at several points on the capacitor platform.

    The main system requirements for rating the series capacitor banks are:

    Rated capacitor reactive impedance (ohm s)

    Continuous capacitor current requirem ents

    (

    amperes)

    30 minute overload current requirem ents

    (

    amperes)

    .

    Maximum swing current fol lowing system disturbances

    Maximu m fault current for external faults

    Maximu m fault current for internal faults

    The rated reactive power and rated bank

    (

    series voltage) are determined based on the f irst two

    items. The MOV ratings are determ ined based on the fault currents.

    As m entioned previously, the total series capacitor impedance for each compe nsated CR EZ l ine

    was se lected to be approxim ately

    50% of

    the l ine im pedance base d on the analysis of m ult iple

    issues. For those l ines wi th two segm ents, each segm ent was approximately

    25% of the line

    impedance.

    E3800-PR-00

    CREZ Reactive Power Compensation Study

    31

    53

  • 8/12/2019 Series Capacitor Compensation Requirements

    5/35

    4.3.2 Line Voltage Profiles

    The decision to limit the total compensation of the series compensated CREZ lines to 50% was

    based primarily on the profile of the voltages along the length of the lines. The TSPs' design

    criteria limit the voltage at any point on the line to 105% under normal conditions and 110% on

    contingencies for up to 30 minutes. In order to meet the voltage criteria, the series

    compensation had to be limited to 50% and placed in the middle of the lines except for the Clear

    Crossing-Willow Creek lines for which a similar action is recommended.

    Although some initial study work considered higher compensation levels, which showed

    improved system performance, these higher levels of compensation were not able to meet the

    voltage limit criteria. However, higher levels of series compensation and/or locations at the end

    of lines could be accommodated if line designs allow for higher line voltages. Figure 4.3-2

    below is an example of the line voltage profile for series capacitors at the end of the line and in

    the middle of a line for the same voltage and power transfers.

    2

    1000MW

    15

    _ q

    05

    m

    >

    1 0

    0

    95

    Nid Line Caps

    ending End Caps

    0 9

    0

    20

    40

    60

    80 10 0

    % Line Length

    tom ReceiAng End

    Figure 4.3-2 - Line voltage

    profile for series capacitors

    at the end and middle of a line

    The line lengths - and by extension the line impedances - used for the study are, of necessity,

    preliminary since the routes of the lines have not been finalized. The changes in final line

    impedances will have some impact on the study results since the final routings may increase the

    length of the lines. There are several options to address the line length increases:

    Maintain a constant net line impedance to ensure the same performance as seen in the

    study. As the line length increases, this will require higher levels of compensation and

    line voltage profiles will need to be reviewed to ensure that the design criteria are met.

    I

    ABB Grid Systems Consult ing

    32 ERCOT

    000054

  • 8/12/2019 Series Capacitor Compensation Requirements

    6/35

    Hold the series compen sat ion

    to 50% of the

    l ine im pedance and run addit ional studies to

    determine i f more or larger SVCs are nee ded to provide acceptable system

    performance.

    Hold the series compen sat ion

    to 50% of the

    l ine im pedance and run addit ional studies to

    determine i f ser ies compen sat ion is needed in other l ines to provide acceptable system

    performance.

    Shorter line lengths that those used in the study are not a concern since they will have lower

    impedances.

    4.3.3

    Maximum Continuous Current and 30 Minute Overload Ratings

    The fundamental ratings for the continuous operating currents and the 30 minute overload

    currents were es tablished using the resu l ts of the fundamen ta l f requency study discussed in

    Section 3

    specif ical ly the generator dispatches and system contingencies that m aximize the

    current f lows through the se ries capacitors. With a redispatch

    of 10

    additional wind gen eration

    to maxim ize the l ine loading through the series capacitors, the worst case contingency u nder a

    worst case wind dispatch

    (

    determined from optimal powerflow analyses) established the

    maximum series capacitor currents.

    Series capacitors are typically designed to have a 30 minute overload rating. This overload

    capabili ty is gen eral ly used fol lowing contingencies w here the system can be readjusted within

    the 30 minutes to reduce the loading. Since the maximum currents were determined as

    discussed above, the 30 m inute ra t ing could be establ ished by these maximu m currents. The

    continuous rat ing could be selected to me et norm al system requ iremen ts. This would allow for a

    more economical design. However,

    the TSPs

    may want to have the continuous rating be

    established by the m aximu m currents in order to m eet any unknown future requi remen ts.

    4.3.4

    Maximum Swing Currents

    Following a contingency on the system, particularly one that results in line outages, the power

    flows through the system will change as the network settles into a new operating condition,

    many times experiencing overshoots during the process. The currents associated with these

    dynamic swings are temporary, but may be higher than the steady-state maximum currents.

    Some dynamic analyses were performed to monitor the highest anticipated swing currents in

    the CREZ system. These have been reported to ERCOT and the TSPs for their consideration in

    rating the series capacitors.

    4.3.5

    Maximum Fault Currents

    The maximum fault currents through the series capacitors are also an important consideration

    for the design of the capacitor protections. The location of the faults relative to the series

    compensated line must be considered. Those faults that occur on the line with the series

    capacitor segment being considered are known as internal faults, while those not on that line

    E3800-PR-00

    CREZ Reactive Power Compensation Study

    33

    ^^5i

  • 8/12/2019 Series Capacitor Compensation Requirements

    7/35

    are called external faults. The maximum fault currents determined from a protective case and

    also from the various power flow scenarios (e.g. Initial Build, Maximum Edison, etc.) were

    determined for both internal and external faults for all series capacitor segments. The results

    have been reported to ERCOT and the TSPs for their consideration in the series capacitor

    protection design.

    4.4

    Network Challenges with Series Compensation

    Series capacitor compensation has been used successfully in many locations around the world,

    and is a relatively common feature in the transmission systems of the utilities in the west and

    southwest U.S. However, the resonances that occur between the series capacitor, the

    transmission system and electric machines have the potential to result in catastrophic failure of

    the machines. Because the series capacitors are always selected to compensate only a portion

    of the transmission line of which they are a part, these resonances will always occur at

    frequencies below the normal system frequency - in other words, at subsynchronous

    frequencies.

    Regarding such subsynchronous resonances (SSR) with conventional thermal generators, the

    phenomena is well understood and the issues can generally be avoided by judicious design of

    the transmission system, by operation of the system around conditions leading to problems

    and/or by protection of the machines when undesirable resonant conditions are detected.

    With regard to the resonances with wind generation, some events have been experienced and

    the industry is quickly gaining a fuller appreciation for and understanding of the phenomena

    involved. Papers are becoming more common to address aspects of the issues and to propose

    some methods of mitigation, but as of the date of this report, no solution has actually been

    implemented and fully tested in the field.

    Nevertheless, because the CREZ transmission plan includes multiple series capacitors, ERCOT

    and the TSPs considered it prudent to include evaluations of the phenomena to estimate their

    potential for occurring on the CREZ system and to test (via simulation) various mitigation

    methods. The follow sections describe this work.

    4.4. 9

    SSI with Wind Generation

    While the potentially detrimental, series capacitor

    related phenomena evaluated in this study are

    associated with

    subsynchronous resonances,

    they do not always appear to be solely associated

    with the electrical resonance itself. In some

    Subsynchronous Interactions

    Wind

    Generators

    vs.

    Series

    apacitors

    r mp lr f r ed

    Full

    CREZ

    Test

    System

    Transmission

    syste

    cases, they appear to be exacerbated

    bSysem. J

    controls for the power e lectronic conver ters use d on som e types of wind turbine gen erators.

    Because the causes m ay be more gener ic than just the subs ynchronous reso nance, the term

    I

    ABB Grid Systems Consult ing

    34

    ERCOT

    56

  • 8/12/2019 Series Capacitor Compensation Requirements

    8/35

    subsynchronous interaction (SSI) was selected for use in this report to discuss the phenomena

    affecting wind generation. Specifically, the following types of SSI are considered

    *

    Self-excitation - a phenomenon that occurs because of the natural response

    (resonances) of the various system components to each other. It is typically stimulated

    by some system perturbation; and,

    Control interactions - phenomena that occur, in part, because of the response of

    active system devices such as the WTG controls.

    The phenomena leading to different types of SSI can be complicated given the complexity of the

    controls used in some types of wind turbine generators. Because of this, the SSI issues with

    WTG were first evaluated with the wind farms connected to a simplified radial test system and

    then confirmed on the full interconnected CREZ system.

    The simplified radial test system is illustrated in Figure 4.4-1. This topology is most susceptible

    to SSI and allowed a more rapid assessment of the issues. Tests were made representing each

    of the different types of wind turbines at the wind farm collector bus. They were started with the

    series capacitor bypass breaker closed and their susceptibility to SSI was tested by simply

    opening the bypass breakers. This was generally enough of a disturbance to trigger any

    interaction.

    Wind farm

    Transmission

    collector

    line

    bu s I r7c I

    _ Y

    Series

    Network

    capacitor

    equivalent

    34.5kV

    138kV

    Transmission

    Strong,

    medium

    Y

    line

    or weak

    bypass

    220 miles

    138kV

    breaker

    or 80 miles

    345kV

    Figure 4.4 1: Simplified radial test system for SSI evaluations

    The confirmation of the test system results on the full interconnected CREZ system, with wind

    farms at the locations currently projected by ERCOT, permitted an assessment of the likelihood

    for SSI at these locations.

    WTG Types

    Four basic types of wind turbine generators have been identified in the industry based on their

    configuration and operation. These four types are:

    Type 1 is a fixed speed wind turbine connected to an induction generator that is, in turn,

    directly connected to the grid.

    E3800-PR-00

    CREZ R eact ive Power Co mpensat ion S tudy

    35

    57

  • 8/12/2019 Series Capacitor Compensation Requirements

    9/35

    Type 2 is a variable speed wind turbine connected to a wound rotor induction generator

    which has a controlled variable external rotor resistance that is used to increase the

    operating speed range of the generator.

    Type 3 is a doubly-fed induction generator (DFIG) which is also called by some authors

    a doubly-fed asynchronous generator (DFAG). It uses a variable-speed wind turbine

    connected to a wound rotor induction generator. A back-to-back converter is connected

    between the generator rotor and the stator in parallel to the machine. Because the full

    machine power does not flow through the converter, it can be rated for only a fraction of

    the WTG rating. It has a wider operating speed range than Type I and Type 2.

    *

    Type 4 is a variable-speed wind turbine with a generator (either asynchronous or

    synchronous generator) connected to the grid through a back-to-back converter. The

    power of the generator flows directly through the converter so it must be rated for full

    generator power. The converter acts to decouple the turbine and generator from many

    phenomena occurring on the grid.

    Self-excitation

    with Type 1 and Type

    2 Machines

    Several models of Type 1 and Type 2 WTGs were provided by ERCOT for evaluation of SSI

    issues. Not unexpectedly, a phenomenon known as self-excitation was observed with these

    types of machines under certain conditions on the simplified radial test system. Self-excitation is

    a well understood phenomenon that is a direct consequence of the resonance between the

    series capacitor and the system and machine inductances on the system. Excellent papers (see

    references [2] and [3]) were written many years ago that are still pertinent for understanding the

    conditions conducive to self-excitation and that provide insight into how it can be mitigated. The

    potential for its occurrence with wind turbine generators was noted in reference [4].

    Whether or not SSI was observed on the radial test system strongly depended upon the losses

    in the system and the parameters of the particular machine. Higher amounts of resistance in the

    system between the wind farm and the series capacitor (due to lower voltage transmission

    systems, for example) will decrease the likelihood of any undamped resonance conditions

    occurring.

    At present, ERCOT anticipates that only about 15% of the new wind turbine generators to be

    added to the system will be Type 1 or Type 2. But it is generally recommended that the new

    plant owners perform a study to assess the potential for self-excitation of their machines if they

    wil l

    be connecting in the vicinity of any of the series compensated lines, or if a reasonable

    number of system line outages would place their plant nearly radially connected through a

    series capacitor.

    I

    ABB Grid Systems Consult ing

    36 ERCOT

    00005S

  • 8/12/2019 Series Capacitor Compensation Requirements

    10/35

    SSI with Type

    3 Machines

    Out of the various types of wind turbine generators, Type 3 was found to be the most

    susceptible to SSI. This appears to be because of interactions with the controls and the

    subsynchronous series resonance.

    Only two models were made available for assessment in this study and the susceptibility to SSI

    was found to differ between the models. The first, more susceptible model had a more detailed

    representation of the converter and its controls. This along with parameter differences may

    account for its greater susceptibility to SSI.

    Because the Type 3 machines' high susceptibility, and because ERCOT currently anticipates

    that a significant portion of the new wind turbines installed in the CREZ may be of this type, they

    were carefully tested on a model of the full CREZ system. Representations were made of wind

    farms at the same locations that they were represented in the fundamental frequency analyses.

    These simulations showed particular inclination toward SSI at specific locations as listed in

    Table 4.4-1. This table also indicates the system conditions for which the SSI occurred and how

    each of the two Type 3 models responded.

    Table 4.4-1: Conditions found to be conducive to SSI with Type 3 WTGs on CREZ system

    Wind

    Size of

    turbine

    represented System

    generator

    wind farm

    contingency

    Model I

    Model 2

    #

    location

    M

    conditions

    Case description

    SSI

    SSI

    I

    West

    74 3

    N-0

    Normal system conditions

    Y N

    Shackelford

    2

    West

    74 3 N-1

    Ou tage of one circuit of the double circuit

    no t

    tested

    Y

    Shackelford

    l ine between Scurry and West Sh ackelford

    3 West

    74 3

    N- 2

    Ou tage of double circuit l ine between Scu rry

    not tested Y

    Shackelford

    and West Shackelford

    4 West

    743 N-2

    Ou tage of double circuit l ine between West

    Y

    not tested

    Shackelford

    Shackelford and Romney

    5

    West

    743

    N-2

    Outage of double circuit line between Clear

    Y

    not tes ted

    Shackelford

    Crossing and West Shackelford

    6

    Big Hill

    15 0

    N-1 ' Outage of circuit between Big Hill and Twin

    Y

    N

    B u t t e s

    7 Big Hill

    15 0

    N-2

    Outage of circuits between B ig Hill and Twin

    Y

    Y

    Buttes and between Big Hill and Bakersfield

    8

    Dermott

    56 1

    N-2

    Outage of double-circuit l ine between

    Y N

    Dermott and Scurry

    9

    Dermott

    56 1

    N-4

    Outage of double-circuit l ine between

    Y Y

    Derm ott and Scurry and doub le-circuit l ine

    between Dermott and Cottonwood

    Without mitigation measures, there is a strong potential for SSI with Type 3 wind turbine

    generators located very close to the West Shackelford, Big Hill and Dermott buses. The first

    E3800-PR-00

    CREZ R eact ive Power Compensat ion

    Study

    37

    090-059

  • 8/12/2019 Series Capacitor Compensation Requirements

    11/35

    Type 3 model, in particular, showed vulnerability at these locations with SSI being observed at

    West Shackelford with no line outages.

    Because the models assessed in the study are not representative of all WTG manufacturers

    and may not provide sufficient detail needed for a full assessment under the studied conditions,

    these results should be taken primarily as a caution and detailed studies should be conducted

    by the developers to ensure that the planned wind farm will not have SSI issues. Such studies

    should accurately represent the CREZ system actually built, any system level mitigation applied

    and any WTG level mitigation available from the manufacturers and included in the turbines

    being ordered.

    Several potent ia l mi t igat ion m ethods, thei r ef fect iveness and their l imi ta tions are discussed

    below

    in Section 4.4.3.

    While the simulations performed for the study can be considered somewhat theoretical, there is

    actual experience that emphasizes the importance of the recommended studies. A utility on the

    ERCOT system reported an incident in which a wind farm consisting of Type 3 wind turbines

    was radially connected to a series compensated line following an N-1 contingency. The

    response of the wind turbines to the new system conditions with a more direct influence from

    the series capacitor resulted in the tripping of the wind turbines, but not before equipment had

    been damaged. It has been reported that the damage was not limited to the WTGs themselves,

    but that the series capacitor also sustained some damage. Because of this experience, two

    recommendations are made regarding the protection of the series capacitors: 1) interconnection

    studies for new wind farms should include an evaluation of the potential for SSI and the

    anticipated impact on voltages at and currents through the CREZ series capacitors; and, 2)

    design efforts for the CREZ series capacitors should include an evaluation of the impact of

    various levels of subsynchronous currents, with protection schemes and/or SSI mitigation added

    if

    warranted by the evaluation results.

    Type Machines

    In the evaluations m ade for this study,

    the Type 4 WTGs

    were n ot found to be affected by the

    prese nce of the series capacitors on the system. This

    is bel ieved to be due to the decoupl ing

    that the full back-to-back converter provides. Although not observed here with the limited

    num ber of m odels available for assess me nt, i t is theoretical ly possible that some control issues

    could occur. The evaluat ion into any such issue s is left to when they man ifest themselves.

    4.4.2 SSR

    with Thermal Generation

    Subsynchronous Resonance (SSR) is a well-

    known phenomenon in which a series resonance

    between a generator and a series compensated ac

    transmission circuit can destabilize one or more

    ABB Grid Systems Consulting

    38

    ERCOT

    Subsvnchronous Resonance

    Thermal enerators and

    Series

    apacitors

    000060

  • 8/12/2019 Series Capacitor Compensation Requirements

    12/35

    torsional

    modes of oscillation on a generator shaft. Since the discovery in 1971 of the SSR

    problem on the Mohave generators of the Southern California Edison Co. there has been only

    one event where damage occurred because of the SSR problem with series compensation.

    Because of the partial - but high percentage - compensation (63%) of the 500kV line between

    the

    Mohave plant and the Lugo Substation, when a short line between the McCullough

    Substation and Mohave was opened, the system was tuned to a torsional mode involving the

    shaft between the generator and a directly-connected exciter. Other instances of SSR have also

    occurred at other locations, but damage to the generators involved has been avoided through

    proper mitigation or protection methods.

    Because the proposed

    C R E Z

    t ransm ission includes many s eries capacitors,

    ERCOT

    has taken

    a prudent step and asked ABB to perform an SSR scre ening analysis to assess the potential of

    SSR between the CREZ transmission and several nearby thermal generating plants. These

    screening analyses have considered both the poten tial for SSR and for the induction gene rator

    effect (

    self-excitation involving on ly the electrical aspects o f the syste m ).

    The S S R

    Phenomena

    In

    order to understand the SSR phenomena as it relates to conventional thermal plants,

    consideration must be given to both the torsional modes of turbine-generators and the electrical

    resonance created by the series compensated line.

    Generator Torsional Modes

    As discussed in Section 3.7, a mechanical system with N masses with have N-1 oscillatory

    mechanical torsional modes. Consider again the generic turbine-generator system as illustrated

    in

    Figure 3.7-1 and repeated in Figure 4.4-2. In this case there are six masses - the high-

    pressure and intermediate pressure turbines, the two segments of the low-pressure turbine, the

    generator and the exciter. Any given system may have more or less masses on the shaft.

    The frequency of each oscillatory mode and how well it is damped (decays away) will be

    dependent upon the relative sizes of the masses, the stiffness of the shaft and the magnitude of

    various losses in the mechanical system. Of these modes, those that occur at frequencies

    below the system frequency - in other words, at subsynchronous frequencies - are of particular

    concern.

    Rotating

    HP-1P Turbine

    LP Turbine

    Generator

    Exciter

    Figure 4.4-2: Generic Turbine-Generator System

    The various masses on the shaft will have different degrees of participation in the different

    modes. The modes in which the generator itself has significant participation will be more

    E3800-PR-00

    CRE Z React ive Power Com pensat ion S tudy

    39

    a0-?D0Gi

  • 8/12/2019 Series Capacitor Compensation Requirements

    13/35

    susceptible to SSR. For these modes, a disturbance of the electrical system, such as a fault, will

    cause a corresponding torsional disturbance on the generator which is translated to the shaft by

    the machine which will also disturb the mechanical system. This will cause the masses to

    oscillate against each other at their various natural frequencies, with some modes stimulated

    more than others.

    The mechanical system always acts to damp out these oscillations over time (i.e. it is positively

    damped). The amount of mechanical damping is higher when the generators are fully loaded

    than when they are at minimum load.

    Subsynchronous Resonance SSR)

    For the modes in which the generator participates, currents associated with the mechanical

    mode oscillations will be generated and injected into the electrical system. The electrical system

    will

    usually provide positive damping against these currents, but under proper conditions

    negative damping can result. If electrical system damping is negative but is not sufficient to

    completely overcome the damping of the mechanical system, then the oscillations will simply

    take more time to decay, which is not usually a concern. However, if the electrical system

    provides enough negative damping to overcome the positive mechanical damping, then the

    oscillations will grow and, if proper protection is not applied, can result in catastrophic damage

    to the turbine generator.

    The conditions leading to negative electrical damping can be set up,with series compensation

    system such as that in Figure 4.4-3. In this figure, the resistance of the elements and the details

    of the generator flux dynamics are ignored for simplicity.

    Infinite

    Bus

    X d

    X T

    X S

    XC

    Figure 4.4-3: Example series compensated network

    This e lectr ica l network consists of the induct ive gene rator sub-transient reactance

    (Xd ) , the

    inductive transformer leakage reactance

    XT

    the inductive line reactance

    Xs and the

    capacit ive series com pensation reactance

    (Xc) . Therefore,

    the total inductive reactance is

    XL=Xd+XT+Xs

    A series res onance resu l ts with the combinat ion

    of

    XL

    and Xc

    at a frequency of

    T

    Al - f0

    where fo is the normal system frequency (60Hz)

    ABB Grid Systems Consulting

    40 ERCOT

    ooo sz

  • 8/12/2019 Series Capacitor Compensation Requirements

    14/35

    Because se ries compen sation is not designed to fully comp ensate the entire transm ission l ine

    (not to mention any transformer or generator reactance)

    Xc

    will always

    be less than

    XL

    and the

    resonan t frequency wil l be below

    fo .

    If f

    is at or near the subsynchronous sideband frequen cy

    associated with the curren ts injected into the system due to the m echanical osci llat ions, then

    energy can readily transfer between the m echanical and electrical system s.

    From

    the rotor side

    of the machine these frequencies will result in apparent resistances in the machine that are

    negative and which can overcome the posit ive resist ive losses of the electrical system.

    This will

    cause the e lectrical system to provide negative dam ping on the turbin e-gen erator shaft. I f this

    negative damping is large enough to overcome the mechanical damping, then the torsional

    mode becomes destabilized and oscillations at the modal

    frequency

    will

    be sustained

    indefinitely or grow.

    Such SSR has historically been a problem primari ly for large steam generators. A gen erator that

    is connected radial ly to a highly series-com pens ated transm ission l ine can be at considerable

    r isk for undamped subsyn chronous os ci lla tions.

    The risk

    also exists for generators in an

    interconnected network, al though to a lesser degree for highly meshed s ystem s.

    Induc t ion

    Generator

    Effect

    The induction generator effect is also associated with the subsynchronous resonances of the

    machine with the network. However, it involves only the electrical network and not the

    mechanical system. At frequencies below the nominal system frequency, synchronous

    generators appear as induction machines, so the same phenomenon that results in self-

    excitation of induction generators discussed above can occur. However, this effect is usually

    called the Induction Generator Effect (IGE) when speaking about synchronous machines.

    Fortunately, the same analysis used to screen for SSR, as discussed next, is ideal for

    evaluating induction generator effect.

    SSR Screening Analyses

    Analyses were conducted for selected thermal plants in the

    ERCOT system

    near the series

    compe nsated l ines to screen

    for the likelihood of SSR. The six

    plants that were screened are:

    Comanche Peak nuclear plant

    .

    Hays combined cycle plant

    Odessa-Ector combined cycle plant

    .

    Oklaunion coal plant

    .

    Tradinghouse coal plant

    .

    Willow Creek combined cycle plant

    Screening methods based on frequency scans of the network impedance from behind the

    generator under study can be made based on principles discussed in [5]. Care must be taken to

    E3800-PR-00

    CREZ

    Reactive Power Compensation

    Study

    41

    ^^^GIG-3

  • 8/12/2019 Series Capacitor Compensation Requirements

    15/35

    adequately represent the system components so that their influence is properly taken into

    account. In particular, the representation of the loads and generators, including that of multiple

    units, is essential. The frequency scan approach for SSR screening is limited to a one-machine-

    at-a-time approach. Therefore, when studying multiple units at a common high-side bus care is

    required in interpreting and handling the data.

    In

    addition, the scans must be made under multiple system conditions. Under contingency

    conditions, the outages of lines may result in the generators being more directly coupled to the

    series capacitors increasing the potential for SSR. Outages can also cause the frequency of the

    resonance to shift, aligning it with a generator mechanical mode that was not previously at risk.

    A large number of outage conditions were considered for each studied plant to consider all

    conditions from normal operation with all lines out, to a direct radial connection between the

    studied generator and the nearby series capacitors.

    A separate report for each plant has been provided to ERCOT. The reports will be provided by

    ERCOT to the individual plant owners. The data and results of these studies contain protected

    confidential information and may be considered Critical Energy Infrastructure Information. They

    will, therefore, not be made publicly available.

    It

    was noted during the study that the frequency dependent nature of the impedance presented

    by the WTGs to the system is critical to the proper screening for SSR and proper calculation of

    induction generator effects at the thermal generators. The representation of Type I machines is

    straight forward. Type 2 can become somewhat more complicated but is expected to be similar

    to Type 1. Representations for Type 3 and Type 4 must be derived from models of WTG

    operation. It is recommended that WTG suppliers be required to provide the impedance

    characteristics of their machines when looking into the wind farm from the system. These

    characteristics should cover a frequency range of 0Hz to 120Hz in 1 Hz or smaller increments for

    normal screening studies. Higher frequencies may be needed for other types of harmonic

    impedance calculation studies and should also be provided up to approximately I kHz.

    4.4.3 Potential Mitigation Measures and Their Limitations

    Because of the severity of potential SSI (including SSR) issues, three potential mitigation

    methods were evaluated:

    Thyristor Controlled

    Series

    Capacitors

    (TCSC). This is

    an active device that uses a

    thyristor controlled reactor in parallel to the series capacitor.

    The TCSC

    controls can

    regulate how the capacitor appears to the system. This allows the

    TCSC to be

    used for

    other purposes such as to help damp out large area power swings or m ake a given

    capacitor appear to have more capacitance at norm al system freque ncies

    ( i .e. boost).

    With proper controls

    (

    see below) i t is pos sible for the

    TCSC to

    appear as an inductor

    over mos t of the subsynchronou s frequen cy range, thereby el iminat ing m ost concern for

    SSI issues with both wind and thermal gen eration

    I ABB Grid Systems Consult ing

    42

    ERCOT

    000064

  • 8/12/2019 Series Capacitor Compensation Requirements

    16/35

    Series capacitor bypass

    filters.

    This is a passive device placed in parallel to the series

    capacitor. It allows an alternate path to currents at frequencies other than those at the

    normal system frequency 60Hz). This changes how the series capacitor appears to the

    system at the subsynchronous frequencies.

    Two philosophies can be used for selecting the parameters of these filters. The first

    ( damping-type ) focuses on damping undesirable currents so it increases the system

    resistance at subsynchronous frequencies. This can be tailored to focus on specific

    issues or frequencies.

    The second philosophy ( preventive-type ) focuses on preventing undesirable currents

    by making the series capacitor appear inductive over much of the subsynchronous

    frequency range, eliminating most concern for SSI issues with both wind and thermal

    generation.

    W TG

    control

    modifications.

    This is limited to the Type 3 wind turbines. If any SSI

    issues were to be found with Type 4, this would also be an option.

    The effectiveness of the first two solutions was evaluated

    for

    Type 3 WTGs in the full

    interconnected

    CREZ

    system for many of the system condit ions that led to SSI as discussed in

    Section 4.4.1. The resu lts are shown

    in Table 4.4-2

    As can be seen by com paring

    Table 4.4-2 to Table 4.4-1,

    the preventive

    type

    bypass fi l ter and

    the TCSC were

    effective in addressing the SSI issue s for the

    Type 3 wind

    turbines evaluated in

    the stu dy. The last condi t ion

    (

    N-4 outage at Dermott) represented

    a very

    weak system and

    control issu es becam e a problem during the simu lation so the effectiveness is undeterm ined in

    this case.

    The TCSC

    or a preventive bypass

    filter

    with

    s imi lar s ubsynchronous impedance

    characterist ics was also found through the SSR screening studies to be effective in el iminating

    concerns for SSR when universal ly appl ied.

    The damping type bypass filter was not found to be effective by itself. However, in combination

    with control modifications at the WTG it may be more effective. It is also noted that an

    exhaustive effort was not made to determine the optimal designs of the bypass filters. It may be

    possible that a design not evaluated would show greater effectiveness than that shown here.

    E3800-PR-00

    CREZ

    Reactive Power Compensation

    Study

    43

    000065

  • 8/12/2019 Series Capacitor Compensation Requirements

    17/35

    Table 4.4-2: Conditions found to be conducive to SSI with Type 3 WTGs on CREZ system

    Wind

    Modell

    Model 1

    Model 2

    turbine

    System

    SSI with SSI with SSI with

    Model 1 Model 2

    generator

    contingency

    filter

    filter filter

    SSI w i th

    SSI w i th

    # location

    conditions

    Case description type 1*

    pe 2**

    pe 2**

    TCSC

    TCSC

    I

    West

    N- 0

    Norm al system conditions

    Y

    N

    not tested N

    not tested

    Shackelford

    2

    West N-1

    Outage o f one circuit of the

    not tested

    not tested

    not tested not tested

    not tested

    Shackelford

    double circuit l ine between

    Scurry and West

    Shackelford

    3

    West

    N- 2

    Outage o f double circuit l ine

    not tested

    N

    N

    N

    Shackelford

    between Scurry and West

    Shackelford

    4 West N-2

    Outage of double circuit line

    Y

    no t tes ted

    no t t es ted N

    no t tes ted

    Shackelford

    between West Shackelford

    and Romney

    5 West

    N-2

    Outage of double circuit line

    Y

    not tested not tested N

    no t t es ted

    Shackelford

    between Clear Crossing

    and W est Shackelford

    6

    Big Hill N-1

    Outage of circuit between

    Y

    N

    not tested

    not tested

    Big Hill and Twin Buttes

    7

    Big Hill N-2

    Outage of circuits between

    Y

    N

    N

    N

    N

    Big Hill and Twin Buttes

    and between Big Hill and

    Bakersfield

    8

    Dermott

    N-2

    Outage of double-circuit

    Y

    n o t

    tested

    no t t es ted

    N

    no t t es ted

    l ine between D ermott and

    Scurry

    9 Dermott N-4

    Outage of double-circuit

    Y

    Weak

    N

    Weak N

    l ine between Dermott and

    system

    system

    Scurry and double-circuit

    control

    control

    l ine between Dermott and

    issue

    issue

    Cottonwood

    * - da m pin g ty pe filt er * * - p re ve nt iv e ty pe

    The following sections provide brief discussions on the various technologies

    T

    As i l lus trated in Figure 4.4-4, the

    TCSC

    consis ts of series capacitors in parallel with a thyristor

    controlled reactor that can boost the voltage across the series capacitors and make the

    combination appear as a larger capacitive impedance at fundamental frequency. For example,

    the fixed series capacitors may have an impedance of 20% of the line impedance and the

    thyristor control led inductor can inject a cu rrent that w il l boost the vo ltage by a factor of three,

    allowing the

    TCSC to compensate

    60% of the

    l ine reactance.

    ABB Grid Systems Consulting

    44

    ERCOT

    0 0 0 0 6 6

  • 8/12/2019 Series Capacitor Compensation Requirements

    18/35

    i v

    i L

    i C

    + uC -

    Figure 4.4-4: TCSC scheme

    During TCSC operation, the line current remains almost purely sinusoidal with little distortion

    caused by thyristor switching. Near each of the zero crossings of the capacitor voltage the

    thyristors are fired to provide a current pulse that circulates through the TCSC capacitor and

    inductor causing an increase in the capacitor voltage during the current pulse. The boost

    provided to this voltage (i.e. boost factor) can be adjusted by regulating the timing of the

    thyristor switching. This boosted voltage with the given line currents presents an effective

    impedance to the system that is larger than the fundamental frequency impedance of the

    capacitor itself.

    In the design considered here, the TCSC boost factor can typically be adjusted between 1.0 and

    3.0. The magnitude of the line current is dependent on the total power flow (real and reactive)

    on the transmission line. The magnitude of the thyristor current is dependent on the boost level

    setting.

    The TCSC modeled in this study uses a specially developed Synchronous Voltage Reversal

    (SVR) control to determine the firing of the thyristor valve. The SVR control strategy eliminates

    any series resonance in the subsynchronous range between the inductor/valve and the series

    capacitors.

    With the SVR, the effective impedance presented by the TCSC to the system is

    inductive over most of the subsynchronous frequency range, which naturally eliminates SSI by

    eliminating the subsynchronous resonances between the system and the series capacitor.

    Figure 4.4-5 shows the effective TCSC impedance. See reference [6] for a more complete

    description of how SVR results in this effective impedance characteristic.

    The effective impedance of the TCSC as modeled in the study has an inductive impedance for

    frequencies below 42 Hz, meaning that the TCSC is inductive rather than capacitive over most

    of the subsynchronous frequency range, while it is capacitive at fundamental frequency.

    At

    frequencies lower than this 42 Hz cross-over frequency the TCSC is not capacitive and cannot

    create a series resonance. This characteristic can eliminate SSI and even has the ability to

    mitigate most concerns for subsynchronous resonance (SSR) with thermal generators. There

    are multiple installations of TCSCs operating successfully around the world. To date, however,

    none have been explicitly applied to address SSI with wind turbine generators. Note also, that

    there is a patent pending on the SVR control. It is not known what methods the various vendors

    may have available to provide similar performance.

    E3800-PR-00

    CREZ R eactive Power Com pensat ion S tudy

    45

    000067

  • 8/12/2019 Series Capacitor Compensation Requirements

    19/35

    virfual

    reactance

    ideal

    SVR

    t r a n s i t i o n

    frequency

    /

    nd

    power flow

    control

    /frequency band

    tN stator

    f requency

    _rotor

    Increasing

    boost

    level

    Ned

    capacitor

    Figure 4.4-5: TCSC virtual impedance with the SVR control scheme

    At fundamenta l f requency,

    the TCSC will provide an impedance equivalent to that of the

    conventional series capacitors. For the proposed design w ith a 1.2 boost, the actual im pedance

    of the capacitors in the

    TCSC will only be 83.3% of

    the conven tional ser ies capacitors. The

    TCSC

    capacitors wil l need to be rated for the maxim um l ine current plus the peak current f rom

    the thyristor circuit. Due to this curren t from the thyristor circuit, the TCSC capacitors will also

    have a higher voltage for which the capacitors will need to be designed.

    Series Capacitor Bypass Filter

    The basic topology for the bypass

    filter

    is

    shown in Figure 4.4-6. The

    filter consists of a

    capacitor/inductor

    (

    Cf and Lf) paral lel combination w ith a series res istor (

    Rd) for damping. RL is

    resistan ce of the inductor coil and Cs c is the series capacitor itself.

    Csc

    Isc

    Figure 4.4-6: Series capacitor and bypass filter configuration

    There are different design philosophies that can be pursued for a series capacitor bypass filter.

    The first is based on the classical solution to self-excitation - providing sufficient damping to

    prevent the phenomenon or to cause it to decay before it becomes critical to system

    I ABB Grid Systems Consulting

    46 ERCOT

    000068

  • 8/12/2019 Series Capacitor Compensation Requirements

    20/35

  • 8/12/2019 Series Capacitor Compensation Requirements

    21/35

    thousands (drives) of reliable installations around the world by multiple manufacturers

    that have been operating for many years - even decades. In fact, most major

    manufacturers who have the ability to supply TCSCs state that they have functioning

    installations around the world that are operating reliably.

    There are only a couple of known instances for which a

    TCSC has been applied

    specif ical ly to address su bsynchronou s issu es. In one of these instal lat ions, the TCSC

    was us ed to address SSR with thermal generators by spl i t ting the ser ies capaci tor so

    that part was f ixed and part was

    TCSC.

    This adjusted the reson ant frequen cy so that it

    was not a con cern for any torsional mode on the m achine. Since no instal lat ion exists to

    specifically address SSI with wind turbine generators, the beneficial characteristics of the

    device have been demonstrated only by engineering calculation and in simulation.

    Because of this, the confidence of potential owners of the technology is somewhat

    m uted. Further, the potential owners would l ike to have a guarantee that the technology

    will eliminate SSI issues, but manufacturers are hesitant to accept the liability associated

    with such a guarantee given the novel ty and l imi ted understanding of the phenom ena

    involved.

    Prices for a

    TCSC have

    been reported to be around 1.8 times that of a conventional

    series capacitor of the sam e rat ings

    although one man ufacturer reported a price of 4 to

    5 t imes that of a convent ional series capacitor.

    Bypass filter

    Like the TCSC, the bypass f i lter is covered by patents ( albeit by a differen t

    equ ipmen t manu facturer) that may l imit the num ber of suppl iers available to the potent ial

    owne rs, who have been hesi tant to accept a technology l im i ted to a s ingle su ppl ier . It

    el iminates the opportunity for a compe ti t ive bid process and increases the risk of l imited

    future support for the equipm ent.

    While the bypass filter has the advantage of using passive elements, there are no known

    installations for SSI/SSR mitigation, so any evaluations to date are largely academic

    exercises. As indicated above, the evaluations performed for this study have shown the

    preventive

    bypass filter to provide adequate performance, but the equipment parameter

    calculations show that the filter capacitor is as large, or nearly so, as the series capacitor

    itself and very high circulating currents are needed, resulting in very large filter reactors

    that must have very low losses (i.e. high Q). The magnetic field clearances needed for

    the reactors may significantly increase the land area required.

    For the

    damping

    bypass filter,

    the componen ts can be m uch sm aller and resul t in lower

    losses in the f il ter. However , as shown above, i t may not be able to address SSI issues

    with

    WTGs

    by itself. If used for this purpose it would likely have to be coupled with

    another solut ion such

    as

    WTG

    control

    m odifications, thereby div iding the solut ion

    between a system level solution and a local development level solution. It can be

    observed here that this type of split solution may prove challenging in several areas

    ABB Grid Systems Consulting

    48 ERCOT

    000070

  • 8/12/2019 Series Capacitor Compensation Requirements

    22/35

    including the coordination between the different technologies and allocation of the

    mitigation responsibility.

    For either the preventive bypass filter or the damping bypass filters, some TSPs have

    indicated a strong preference for any supplier to guarantee performance in alleviating or

    mitigating SSI issues.

    The cost for the bypass filters was available from only one manufacturer and only for a

    damping type filter. This manufacturer suggested that the price for a series capacitor

    with a damping bypass filter would be 1.5 to 2 times that of a conventional series

    capacitor.

    .

    WTG control modifications As of the date of this report, there are no know installed

    and field tested Type 3 WTGs with control modifications that have been designed to

    address SSI. It is known that significant work is being performed in both industry and

    academia to address this issue and the reports appear promising. However, unless any

    successful control modifications can address SSI alone, it may prove necessary to

    couple the solution with other partial solutions such as a damping bypass filter. Again,

    this would divide the solution between a system level solution and a local development

    level

    solution.

    Coordinating the different technologies and determining the proper

    allocation of mitigation responsibility may prove to be difficult.

    Unless m ult iple man ufacturers are able to address the issue, patent issu es m ay present

    a sim ilar problem to that indicated above for the

    TCSC

    and bypass fi l ters.

    It

    would not be unexpected for any manufacturer to have an additional charge on each

    WTG that has the SSI mitigation controls, but it is not possible to estimate what that

    additional cost may be.

    At the time of writing, it appears that one manufacturer has successfully implemented

    control modifications that allow operation of their Type 3 turbines at the end of a radial,

    series compensated transmission line. It is not known how robust the solution will be for

    application at other sites. The solution may prove to be dependent upon the specific

    system parameters for this interconnection, but the results are quite encouraging.

    The concerns expressed in regard to the potential patent issues noted for each of the

    technologies could be alleviated if the patent holders demonstrated a willingness to license the

    technology in a manner that would allow others to supply it at a competitive price. While rare,

    this is not an unknown practice that has had the benefit of opening up a very large market that

    benefited multiple vendors instead of limiting it to a much smaller niche market.

    E3800-PR-00

    CREZ R eact ive Power Co mp ensation S tudy

    49

    000071

  • 8/12/2019 Series Capacitor Compensation Requirements

    23/35

    5

    Conclusions

    The study documented in this report is the first of its kind on the ERCOT system concerning the

    CREZ transmission and has resulted in several key findings that are summarized below.

    Reactive compensation requirements

    Series compensation of 50% is required on six 345kV double-circuit transmission lines (12

    circuits total). The locations of the series capacitor segments along the length of these lines

    as studied were provided by ERCOT and the TSPs. The ultimate locations on the lines will

    be established by the TSPs based on maintenance needs, line design criteria and similar

    considerations. The locations on the lines will not influence the reactive compensation

    requirements.

    Shunt compensation is required in a number of different forms. The recommended sizes and

    locations for switched shunt reactors have been identified. These reactors are required to

    keep bus voltage at acceptable levels under conditions with low power flow on the CREZ

    system. The reactors are needed at the time of the initial build of the system.

    In addition, the recommended sizes and locations for switched shunt capacitors needed for

    voltage support during periods with large amounts of wind generation have been identified

    for both the initial build of the CREZ system and for the long term build out envisioned in the

    study assumptions. The levels required for the initial build are significantly less than those

    for the ultimate build out.

    Finally, the size and locations for dynamic reactive compensation have been identified for

    both the initial CREZ build and the long term plan. Due to the higher levels of wind

    generation in the long term plan, the dynamic reactive requirements are significantly higher

    than for the initial build. The dynamic reactive devices must be able to provide continuous

    voltage control and respond in less than 50ms, which is well within the capability of devices

    such as SVCs and STATCOMs.

    Specific assumptions were made regarding the reactive capability and performance of the

    CREZ wind farms. Simulation results confirm that the success of the proposed

    compensation strategy relies on the availability of reactive support from wind generation as

    modeled. This, in turn requires operation of the system with such availability in mind.

    Specifically, the support from the wind farms must be available when needed, in the

    required quantity and with the required speed suggested by the simulation models. Further,

    the system must be operated to allow the wind farms to provide as close to zero reactive

    output as possible (to preserve their reactive capability for disturbances), while maintaining

    overall high voltages. Extensive testing and monitoring of wind farms is recommended to

    ensure that such performance is provided.

    ABB Grid Systems Consulting

    5 0

    ERCOT

    000072

  • 8/12/2019 Series Capacitor Compensation Requirements

    24/35

    The potential for subsynchronous torsional interactions (SSTI) between the dynamic

    reactive compensation devices and nearby thermal generators has been explored for the

    thermal generators closest to the recommended locations of the initial CREZ build out. It is

    possible for such interactions to lead to severe damage of the generators. The results

    indicate that it should be possible to design the controls of the dynamic shunt devices to

    eliminate any detrimental SSTI.

    Potential concerns for operation near series capacitors

    There are several issues of which generation developers should be cognizant when

    operating generation near series compensated lines.

    SSI with wind turbines: The first relates to wind farm and has been identified in the report

    as subsynchronous interactions (SSI). Type 1 and Type 2 wind turbine generators can

    experience self-excitation with the series capacitors that may result in the turbines being

    damaged or being tripped off line under protective action. Type 3 (DFIG) machines are more

    sensitive to SSI, apparently due to the influence of the controls responding to the

    subsynchronous series resonance. Type 4 (full converter) machines have not shown any

    sensitivity to SSI in this study.

    Type 4 (full converter) machines have not shown any sensitivity to SSI in this study.

    The locations in the CREZ system to which wind turbine generators are most likely to be

    affected by SSI have been identified.

    While the simulations performed for the study can be considered somewhat theoretical,

    there is actual experience that emphasizes the importance of the recommended studies. A

    utility on the ERCOT system reported an incident in which a wind farm consisting of Type 3

    wind turbines was radially connected to a series compensated line following an N-1

    contingency. The response of the wind turbines to the new system conditions with a more

    direct influence from the series capacitor resulted in the tripping of the wind turbines, but not

    before equipment had been damaged. It has been reported that the damage was not limited

    to the WTGs themselves, but that the series capacitor also sustained some damage.

    Because of this experience, two recommendations are made regarding the protection of the

    series capacitors: 1) interconnection studies for new wind farms should include an

    evaluation of the potential for SSI and the anticipated impact on voltages at and currents

    through the CREZ series capacitors; and, 2) design efforts for the CREZ series capacitors

    should include an evaluation of the impact of various levels of subsynchronous currents,

    with protection schemes added if warranted by the evaluation results.

    SSR with thermal generators: Subsynchronous resonance (SSR) between thermal

    generators and series compensated lines has been known since the 1970s. The

    phenomena can result in high stresses on the turbine-generator shaft which can lead to

    catastrophic results if the turbine-generator is not properly protected. With the introduction of

    series compensated lines on the CREZ system, some existing thermal generators may be

    E3800-PR-00

    CREZ R eact ive Power Co mp ensation S tudy

    51

    000073

  • 8/12/2019 Series Capacitor Compensation Requirements

    25/35

    susceptible to SSR. Screening studies have been performed on several generators that are

    near the CREZ series compensation. These studies were documented in separate reports

    that will not be made public because they contain proprietary confidential information and

    critical infrastructure information.

    A related issue is the so-called induction generator effect that can also result in high levels

    of subsynchronous currents in the generators and the connected system. These do not

    involve the mechanical system of the turbine-generator shaft.

    It

    is important for any future thermal generation developers to be aware of the issues

    surrounding SSR so that they can investigate the potential for undesirable resonances as

    part of their interconnection studies.

    Mitigation methods: A few mitigation methods for SSI and SSR are explored in the study.

    Bypass filters across the series capacitor, designed to provide an alternate path to

    subsynchronous currents were explored. Two philosophies - a damping filter and a

    preventive filter - were considered. The damping filter did not prove alone to be successful

    to fully eliminate SSI with wind turbine generators, but may be more successful in

    combination with other methods. The preventive filter parameters can be selected to

    eliminate SSI and SSR, but could result in a very costly design. There are no known

    installations of these types of high power bypass filters for SSI/SSR mitigation anywhere in

    the world. Estimates from a single vendor indicated a cost of 1.5 - 2.0 times that of a fixed

    series capacitor. The performance of the filters considered was unclear. Patents on bypass

    filters may limit the number of

    suppliers.

    A thyristor controlled series capacitor (TCSC) - especially

    one w ith a

    so-called SVR

    control

    - was found

    to be very effect ive in el iminat ing SSI

    and SSR. TCSCs have been su ccessful ly

    deployed in m any areas around the world by several vendors, but only one is known to have

    been deployed

    specifically

    to address

    SSR. A TCSC

    will be m ore expensive than a s imple

    series capacitor. Estimates from various vendors ranged from 1.5 to 5.0 t im es that of a f ixed

    ser ies capaci tor . Patents on

    TCSC

    controls, such as the SVR, may limit the number of

    suppl iers that can provide the necess ary performance.

    The modification of WTG controls -

    particularly

    for Type

    3 turbines

    is another m it igat ion

    me thod that is showing promise. I t is known that significant work is being performe d in both

    industry and academia to address this issue an d the repor ts appear promising. Howe ver ,

    unless an y successful control modif ications can address SSI alone, i t may prove neces sary

    to couple the solution with other partial solutions such as a damping bypass

    filter. This

    would divide the solution between a system level solution and a local development level

    solut ion. I t can be observed he re that this type of spl i t solut ion m ay prove chal lenging in

    several areas including the coordination between the different technologies and allocation of

    the m it igation responsibi l ity. Also, unless m ult iple m anufacturers are able to address the SSI

    problems, patent issues m ay limit the numbe r of suppl iers.

    ABB Grid Systems Consult ing

    52

    ERCOT

    000074

  • 8/12/2019 Series Capacitor Compensation Requirements

    26/35

    Limitation of wind turbine types - at critical locations, the limiting the types of WTGs to those

    not susceptible to SSI may be an option. The results of this study (with a limited number of

    models) indicate that Type 4 turbines may be able to operate without control modifications at

    locations where other technologies may have SSI issues.

    Operate around the issue - under some conditions, such as when SSI is only expected

    when certain lines near the wind turbines are out of service, it may be possible to utilize

    special protection schemes to prevent SSI issues. Such schemes require careful study and

    may include tripping wind generators or bypassing the series capacitors. It is noted,

    however, that bypassing the series capacitors under contingency conditions is not usually

    prudent because the series capacitors generally become particularly important under such

    contingency conditions. Further, tripping of the wind farms may not be an acceptable, first

    level response to SSI.

    Modeling needs

    for future studies

    This study

    has highlighted some of the limitations of the present models being used for

    evaluating wind generation. Several of the issue s are highl ighted below based on the types

    of studies

    for which

    they are used.

    Fundame ntal frequen cy models: The main issue observed in th is s tudy was the sens i t iv ity

    of the models to low short-circuit rat ios betwee n the system strength and the instal led wind

    generation. Under these condit ions high frequen cy oscil lat ions

    (

    somet imes in excess of 10

    Hz) were obs erved. I t was not clear i f these oscil lations are a res ult of model ing issue s or i f

    they

    would actually exist in the s ystem .

    Additional work

    would be ne eded to confirm which is

    the case. If it is found that the phenomenon is a modeling issue, then it is strongly

    recomm ended that work be done to improve the models to prevent un warranted conclusions

    f rom being drawn based on study resul ts using the m odel .

    (

    Note that in this stu dy, i t was

    determined to address the issue by using

    "

    place holder synchronous condensers to

    increase the s hort-circuit rat ios. I f such an increase is actual ly nee ded, other technologies

    may also be available to mit igate weak system s)

    Another model ing issue observed in the s tudy was the poor performance of som e dynamic

    models

    provided by

    wind developers to ERCOT. These

    m odels were m ost l ikely created by

    the wind turbine m anufacturers. It is em phasized that most of the models worked well for the

    purposes of the study, but theopoor performance of a few created num erous diff icul t ies.

    In the future, develope rs wil l sti ll be requ ired to provide appropriate mode ls for their wind

    farms. I t is recom me nded that a set of tests be developed

    which

    al l future m odels mu st pass

    before they are accepted

    by ERCOT

    Electromagnetic transient models: The evaluation of the potential

    for SSI

    with wi nd

    turbines and series capacitors is currently limited to simulations in electromagnetic transient

    programs such as

    PSCAD.

    The number of available models which wind turbine

    E3800-PR-00

    CREZ R eact ive Power Co mp ensation S tudy

    53

    000075

  • 8/12/2019 Series Capacitor Compensation Requirements

    27/35

    manufacturers are prepared to release is very limited. This is a situation that is simply

    unsustainable because it is likely that future studies will need to combine appropriate

    models of equipment from multiple vendors. It is recommended that the wind turbine

    manufacturers develop black-box models that allow the user access to appropriate control

    parameters while hiding those controls and parameters that are proprietary. Such models

    should

    be backed by the vendors as being suitable for evaluations involving

    subsynchronous, synchronous and higher frequency studies, with a clear explanation of

    their limitations.

    Frequency scan models: The SSR screening studies showed that the representation of

    the Type 3 and Type 4 impedance characteristics are important for accurate assessment of

    SSR and induction generator effects. It is recommended that WTG suppliers be required to

    provide the impedance characteristics of their machines when looking into the wind farm

    from the system. These characteristics should cover a frequency range of 0Hz to 120Hz in

    Hz or smaller increments for normal screening studies. Higher frequencies may be needed

    for other types of harmonic impedance calculation studies and should also be provided up to

    approximately I kHz.

    A number of assumptions have been made regarding the locations and chronological

    development of the wind generation. Further items such as real estate availability in substations

    (e.g. to maintain required clearances), increased annual maintenance and possible forced

    outages are not part of the study. Also, actual experience will likely differ somewhat from the

    assumptions made in the study. Therefore, the results of the study should be used as input for

    the initial design efforts and as a guide for future planning. If actual experience is found to be

    significantly different from the assumptions made in the study, some of the results may need to

    be re-examined. If the transmission providers significantly change the location of some reactive

    compensation, the impact of the relocation on system performance and stability should be

    studied.

    ABB Grid Systems Consulting

    54

    ERCOT

    00007G

  • 8/12/2019 Series Capacitor Compensation Requirements

    28/35

    6

    References

    [1 ]

    Pouyan Pourbeik, Anders Bostrom, Bhaskar Ray, Modeling and Application Studies for a

    Modern Static VAr System Installation, IEEE Transactions on Power Delivery, vol. 21, no. 1, Jan.

    2006.

    [2 ] J .

    W. Butler, C. Concordia, Analysis of Series Capacitor Application Problems,

    AIEE

    Transactions,

    vol. 56, pp. 975-988, 193 7.

    [3 ]

    C. F. Wagner, Self-excitation of Induction Motors With Series Capacitors,

    AIEE

    Transactions,

    vol. 60, pp. 1241-1247,1941.

    [4 ]

    P. Po urbeik, R. J. Koessler, D. L. Dickmander, and W . Won g, "Integration of Large W ind Farms

    into Uti li ty Grids (Part 2 - Perform ance Issues)," in

    Proc.

    2003

    IEEE PES General Meet ing,

    vol. 3,

    July 2003.

    [5]

    P. M . Anderson, B. L. Agrawal, J. E. Van Ness,

    Subsynchronous

    Resonance

    in Power Systems.

    New York: IEEE Press, 1990.

    [6 ]

    Lennart Angquist, Gunnar Ingestrom, Hans-Ake J onsson,

    Dynamica l Per fo rmance

    of TCSC

    Systems,

    CIGRE 1996 14-302

    [7]

    IEEE S SR W orking Group, "Term s, Definitions and Symbo ls for Subsynchro nous Oscil lations,"

    IEEE Transact ions on PowerApparatus

    and Systems, vol. PAS-104, June 1985, pp.1326-1334.

    [8]

    P. M . Anderson, R. G. Farmer, Series

    Com pens at ion o f Powe r Sys tem s .

    Enc initas, California:

    PBLSH Inc., 199 0.

    [9 ]

    Chong Han, Don E. Martin, Modesto Lezama, Transient Over-Voltage (TOV) and Its

    Suppression for a Large Wind Farm Utility Interconnection, in

    Proc.

    of 1 International

    C o n f e r e n c e o n S us t a in a b l e P o w e r G e n e r a t io n a n d S up p ly ( S U P E R G EN 0 9 ) ,

    No. S03P039 7,

    NanJ ing-China, Apr., 2009 .

    [10]

    D.

    Dickmander, B. Thorvaldsson, G. Stromberg, D. Osborn, Control System Design and

    Perform ance Verification for the Chester, Maine Static VAR C omp ensator,"

    IEEE Transactions on

    Powe r Del ivery,

    vol. 7, No. 3, July 199 2.

    E3800-PR-00

    CREZ R eact ive Power Co mpensat ion S tudy

    55

    000077

  • 8/12/2019 Series Capacitor Compensation Requirements

    29/35

    App endix A - Dynam ic Shun t Co m pensat ion Techn ologies

    A.1- SVC Technology

    A Static Var Compensator (SVC) is a regulated source of leading or lagging reactive power. By

    varying its reactive power output in response to the demand of an automatic voltage regulator,

    an SVC can maintain virtually constant voltage for dynamic events at the point in the network to

    which it is connected. During steady-state it can also reset itself to minimum output. An SVC is

    comprised of standard inductive and capacitive branches that are controlled by thyristor valves

    and connected in shunt to the transmission network via a step-up transformer. Thyristor control

    gives the SVC the characteristic of a variable shunt susceptance. Unlike mechanically switched

    compensation, an SVC can operate repeatedly and is not encumbered by the delays associated

    with

    mechanical switching. This lets the SVC respond very rapidly to changing network

    conditions such as line or generator outage contingencies.

    An SVC can have an inductive and a capacitive capability. The algebraic difference between

    these two capabilities is called the dynamic range. There are three main building blocks

    available to make-up the required SVC capability. These are the thyristor-switched capacitor

    (TSC), the thyristor-controlled reactor (TCR) and the harmonic filter (HF). The TSC is a

    synchronized on-off device. The TCR reactive power absorption is continuously variable from

    zero to its rated value due to phase control of its conduction interval which controls the

    fundamental frequency component of reactor current. If a TCR is used, harmonic filters are

    usually required to limit voltage distortion in the network to acceptable values. The HF is

    capacitive at the fundamental frequency and contributes to the net capacitive output of the SVC.

    The HF is normally not switched but fixed to the SVC bus and is therefore often referred to as a

    fixed capacitor (FC).

    There are three basic SVC configurations as shown in Figure A.1-1. The first consists of a

    thyristor-switched reactor (TSR) and a thyristor-switched capacitor (TSC). Since no reactor

    phase control is used no filters are needed. The second consists of a TCR and TSC (TCR/TSC)

    which may also include a fixed filter capacitor. The third consists of a TCR and a fixed filter

    capacitor (TCR/FC). In transmission applications the SVC is coupled to the network through a

    step-up transformer and the first two configurations are the most common for transmission

    requirements. The required reactive power is measured on the high side of the transformer.

    Some manufacturers design SVCs with significant redundancy built in. The control system is

    completely redundant and one control system can be taken out of service for maintenance

    without interrupting the operation of the SVC. The thyristor valves have extra thyristors in series

    to provide redundancy. There is an extensive monitoring system as part of the SVC. For

    example, if a thyristor fails its location is noted and logged so that it can be replaced during the

    next schedule maintenance. The cooling system is a closed system with redundancy built in

    I

    ABB Grid Systems Consult ing

    56

    ERCOT

    000078

  • 8/12/2019 Series Capacitor Compensation Requirements

    30/35

    including redundant pumps. Due to this redundancy maintenance can be performed on the

    cooling syste m w ithout interrupting the operation

    of the SVC.

    r s F e

    ;sc

    ra a

    a

    b

    T

    T

    TcR

    rJtBr3

    c

    Figure A.1-1: Common SVC configurations

    Variations of the above basic configurations can be made to optimize the SVC system design.

    This is especially true for the higher rated SVC applications where it is common to have multiple

    TSC branches with overall continuous control achieved with a TCR. Factors influencing the

    design include continuous and dynamic ratings, loss evaluation, redundancy requirements,

    harmonic generation, audible noise, environmental conditions and area constraints. The

    transformer and some SVC branches need not be rated continuously. If the maximum output of

    the SVC is only required dynamically during system swings for instance, some SVC branches

    and the transformer can be rated on a short-term basis. If reliability and redundancy are

    extremely critical, the SVC can be split in two halves with each connected to a separate

    transformer secondary winding, one wye and the other delta. To extend the overall capacitive

    range or restore the SVC output to within its dynamic regulating range or continuous rating

    following systems contingencies, a mechanically switched capacitor bank can be installed on

    the high voltage bus. Such a configuration is called a static var system (SVS).

    The range of SVC operation is shown by its static voltage - current (V-I) characteristic illustrated

    in the following figure.

    E3800-PR-00

    CRE Z React ive Power Com pensat ion S tudy

    57

    000079

  • 8/12/2019 Series Capacitor Compensation Requirements

    31/35

    IV

    Current

    V limit

    War

    restriction 1.3

    to 150

    War

    pu

    10 '

    2% 1 1 o lll

    j o

    Inductive

    Capacitive

    10 r6

    Slopes

    2 r 6

    design point

    design point

    75

    War

    -150 War

    a t 1 0 2 p u

    at 0 95 pu

    - 400 kV^ V

    Base -

    i B a s e

    = 100 MVA

    operating

    voltage

    Continuous Operation

    EM Restricted Operation

    2 . 0

    1 . 5

    1 . 0

    0 5 0 . 0

    0 5

    0 I H V I p u I

    Cap Range

    Ind Range

    Figure A.1-2: SVC static V-I characteristic viewed from the transformer HV side

    The norm al continuou s operating area for an example

    SVC is

    defined by the shaded area in the

    above figure.

    This

    normal operating area is bounded by the inductive and capacitive

    susceptance limits and the minimum and maximum slopes of the voltage regulator

    character istic. Operation is al lowed o n a restr icted basis on the capacitive side above a M VAr

    l im it and on the inductive side above the maximum continuous voltage where the

    TCR current is

    l imited with increasing system voltage.

    An SVC

    can respond

    dynamically in 20 to 60

    milliseconds.

    An example

    of large SVC systems

    is described in Preve nting voltage collapse

    by large SVCs at

    power system faul ts

    by Ahmed H.

    AI-Mu barak, Saleh M. Bamsak, Bjorn Thorvaldsson, Mikael

    Halonen and Rolf GrUnbaum

    ( IEEE paper

    # 978-1-4244-3811-2/09). This paper

    includes a

    single- l ine diagram for one of three +600/-60MVAr

    system s and also d iscusses som e control

    issues en countered on the relat ively weak system to which they

    were connected.

    A.2 - STATCaM Technology

    The Static Synchronous Compensator (STATCOM) is comprised of a voltage source converter

    (VSC) connected in shunt as illustrated in Figure A.2-1. The shunt-connected VSC is based on

    converter technology with valves comprised of solid-state switching components with turn-off

    capability and anti-parallel diodes. Performance of the STATCOM is analogous to that of a

    synchronous machine generating a balanced three-phase set of sinusoidal voltages at the

    ABB Grid Systems Consult ing

    58 ERCOT

    000080

  • 8/12/2019 Series Capacitor Compensation Requirements

    32/35

    fundamental frequency with controllable amplitude and phase angle. The device, however, has

    no inertia and does not contribute to the short circuit capacity.

    vt

    T

    V5C

    VDG

    IQ

    V:> V.

    rsac?Ne power

    voc

    Ahs^xqs

    V,

  • 8/12/2019 Series Capacitor Compensation Requirements

    33/35

    special transformer connections, the pulse number can be reduced and the resulting staircase

    waveforms more closely approximate a fundamental frequency sine wave, thereby reducing the

    need

    for filtering.

    The following figure illustrates waveform generation from a three-level VSC employing pulse

    width modulation (PWM) control. The VSC is coupled to the AC bus through series air-core

    reactors. Low pass filters tuned to the switching frequency may need to be connected on the

    line side of these reactors. Together they form a low-pass filter such that only the fundamenta