Voltage and current sensors for intelligent transformer substations

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

Sensors

Page 2: Sensors - Klinkmann

2

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

By ZElisko EnErgy division ct and Vt, for both, indoor and outdoor application, are developed, produced and distributed. the range of rated values goes up to 52 kV and 50 ka. since taking over aeg instrument transformers in the year 2004, Zelisko provides in addition the former transformer product range of aeg.

to satisfy the customer’s high requirements regarding quality, flexibility, lifetime and competitive price, the engineering and production systems are improved con-tinuously. in particular, the apg casting process for epoxy resin in connection with computer-aided dimensioning of the products enables the customers to achieve an essential competitive advantage.

the high reliability, indispensable of for products in power t&d is not only due to the implementation of the latest technologies, but also based on the consistent utilization of long-time experience. Zelisko instrument

transformers have proven their quality for more than 50 years, by operating in substations under various climatic conditions all over the world.

sensors and instrument transformers are developed at Zelisko to be implemented in intelligent transformer subs-tations in the medium voltage secondary distribution grid. regrading the development, processing and production of sensors and instrument transformer, Zelisko has acess to an extensive know-how, continuously grown over the years.

ZelisKo energy

due to the standardised output voltages calibration and adjustment in the power grid are not anymore necessary. the sensors marked with a serial number and an inspection record is attached. furthermore,

all the devices are maintenance-free and can be imple-mented under elevated temperature and humidity indoor conditions.

gEnEral information about sensor types. all current and voltage sensors are finished and routine tested according to iec61869-7 and -8.

Page 3: Sensors - Klinkmann

3

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

taBlE of contEnts

1. current and voltage sensors for medium voltage applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1. background and field of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.2. customer´s benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.3. application and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.4. configuration options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.5. function and error limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2. Product overview and configuration table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2.1. Voltage sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.1.1. smVs-uW1001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.1.2. smVs-uW1002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.2. phase current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.2.1. smcs/t-JW1002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.2.2. smcs-JW1001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.3. sensor for earth fault detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.3.1. gae120/sens-JW1003 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.4. multifunction current sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.4.1. smcs3-JW1004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Page 4: Sensors - Klinkmann

4

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

* The given voltage values are exemplarly

1.1 Background and fiEld of aPPlication. in the last years, the increasing emergence of decentralized supply leads to a destabilization of the network. due to this trend,the extension of a smart grid is of high necessity.

1. current and Voltage sensors for medium Voltage applications

today<dEvEloPmEnt of ›rEnEWaBlE EnErgy‹ 4decentralized power generation systems.

4fluctuating availability

4feeding in lV- / mV- / hV-grid

<thErEBy: 4fluctuating energy flow

4variable cable load

4increased short-circuit current

4difficult handling of power quality

4increased demand for balancing energy

4different network control / protection concept

future<grid ExPansion

<nEW EnErgy storagE systEms

<intElligEnt transformEr suBstations4remote signalling and controll

4integration in power system management

<intElligEnt PoWEr grid and activE load managEmEnt

<currEnt- / voltagE mEasurEmEnt on rElEvant Points in mv-grid

actiVe distribution grid With intelligent transformer substations

110 kv*

20 kv*

0,4 kv*

Legend

communikation

Power flow to:

high-voltage grid

medium-voltage grid

low-voltage grid

primary transformer substation

Wind power station

Building infrastructure

solar power station

large power station

hydroelectric power station

industry

fuel cell

Battery

E-car

Private households

Building infrastructure

Biomasspower station

intelligenttransformer substations

Page 5: Sensors - Klinkmann

5

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

1.2 customEr‘s BEnEfits

benefits by implementing ZelisKo- i/u-sensors

<high mEasurEmEnt accuracy without on-site calibration

<good transfEr BEhaviour for harmonics for current sensors

<simPlE installation of i/u-sEnsors in original equipment

<simPlE rEtrofitting of old facilitiEs without major modifications of the local network substations

<high rEliaBility even for use in harsh environmental conditions (temp. / condensation / emc)

<mEasuring signal according to international transformer standards / iec standards

this enables

<monitoring of nEtWork conditions

4monitoring of power quality

4measurement / notification of operational

characteristics

4improved power quality /

power system stabilityt

<Exact short-circuit / Earth fault dEtEction and dirEction dEtEction

4faster fault detection / fault elimination

4less downtime / increased availability

4automatic switchovers possible

<mEasuring signal for control tasks, such as.

4reactive current and harmonics compensation

4voltage regulation through inverters

4optimized control of transformer tap switch

<oPtimisEd managEmEnt of dEcEn- traliZEd PoWEr gEnEration systEms and of large consumer stations

<cost savings duE to:

4low investment costs

4cost-effective retrofitting of old facilities

4no on-site calibration

4reduced grid losses

4increased transmission power in mV grid

4delay / avoid of grid expansion

Page 6: Sensors - Klinkmann

6

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

1. current and Voltage sensors for medium Voltage applications1.3 aPPlication and usE. the current and voltage sensors have been developed primarily for medium-voltage switchgear in local network substations equipped with precision measurement technology..

the focus of the network substations are in urban, rural and industrial areas.the measuring sensors are imple-mented in order to measure, monitore and also to detect short-circuits or earth faults and to determine their

direction. the compact sensors of Zelisko enable an easy and quick retrofit without major changes in the switch-gear and in the network infrastructure.

Cablen compartment of MV switchgear type 8DJH Siemens

protectiondevice

transmitter

3 x U-sensor24 / √3kV3,25/ √3v

3 x i-sensor300a // 225mv

remoteterminal

Unit(rtU)

grid control center

modbUs

modbUs

iec 60870-5-101/104

u

i

i, u

<transmission of the instantaneous values of current and voltage transducers, protection devices, or directly to analogue rtu inputs

<rtu communication to grid control center

Intelligent transformer substation(Source: Siemens)

Page 7: Sensors - Klinkmann

7

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

1.4 configuration oPtions. the equipment of the t-connectors with the sensors depends on the type of application, the size of the cable connection compartment of the switchgear, and the local conditions (i.e. original equipment or retrofit).

original equipment retrofit

3 x smcs-JW1001 (current sensor)3 x smVs-uW1001 (voltage sensor)

2 x smcs-JW1001 (current sensor)3 x smVs-uW1001 (voltage sensor)1 x gae120/sens (sensors for earth fault detection)

1 x smcs3-JW1004 (multifunktion current sensor)3 x smVs-uW1001 (voltage sensor)

3 x smcs/t-JW1002 (current sensor)3 x smVs-uW1001 (voltage sensor)

2 x smcs/t-JW1002 (current sensor)3 x smVs-uW1001 (voltage sensor)1 x gae120/sens (sensors for earth fault detection)

3 x smcs/t-JW1002 (current sensor)3 x smVs-uW1001 (voltage sensor)1 x gae120/sens (sensors for earth fault detection)

Page 8: Sensors - Klinkmann

8

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

1. current and Voltage sensors for medium Voltage applications1.5 function and Error limits

the function principle of the voltagE sEnsor is based on a resistiVe diVider.

it consists of 2 resistive elements that divide the input signal in order to revieve a normed output value.

the surge protector provides protection of sequentially connected measuring devices.

the PhasE currEnt sEnsor is based on an almost poWer-less inductiVe current transformer.

the current is converted to a proportional voltage by using a shunt resistor.

the operating principle of this sEnsor for Earth fault dEtEction is based on the Zero current transformers.

in case of earth fault, due to a displacement of the neutral point, an asymmetric current occurs in each phase.this current is converted in a defined ratio to the voltage output of the sensor.

voltage sensor

Phase current sensor

sensors for earth fault detection

over-voltage conductor

a

a n

n

earth s1

s2

earth

s1 s2

r1 r2

l1 l2 l3

shunt

Page 9: Sensors - Klinkmann

9

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

class Voltage error (%) phase displacement (min)

Accuracy classIEC 61869-7

0,5 0,5 20

1 1 40

3 3 limit values are not specified

class Voltage error (%) phase displacement (min)

Accuracy classIEC 61869-7

3P 3 120

6P 6 240

class current error (%) phase displacement (min)

5% in* 20% in* 50% in* 100% in* 120% in* 5% in* 20% in* 100% in* 120% in*

Accuracy classIEC 61869-8

0,5 1,5 0,75 – 0,5 0,5 90 45 30 30

1 3 1,5 – 1 1 180 90 60 60

3 – – 3 – 3 limit values are not specified

classcurrent error (%)

100% in

phase displacement (min)

composite error at rated accuracy-limits

Accuracy classIEC 61869-8

5P 1 60 5

10P 3 – 10

class composite error (%)

in* = 0,4a in*= 200a

Accuracy class ε ≤10% ≤20%

accuracy limits for Voltage sensors for measurement purposes

accuracy limits for Voltage sensors for protection purposes

accuracy limits for phase current sensors for measurement purposes

accuracy limits for phase current sensors for protection purposes

accuracy limits for earth fault detection

* IN = primary rated current

Page 10: Sensors - Klinkmann

10

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

product picture description type um (KV) usesensor inside

diameter page

not separable sensor for earth fault detection

(closed ring cores) with phase cur-

rent sensors

smcs3-JW1004 0,72 / 3 original

equipment 3 x Ø 84 mm 18

2. product oVerVieW and configuration table

product picture description type um (KV) uset-connector

manufacturer page

voltage sensor for cone according to

En 50180

smvs-uW1001 24 / 50 / 125

original equipment / retrofitting

nexans: (k)(m) 440tB

cellpack: cts-s

alternatives on request

12

voltage sensor with a shortened

cone

smvs-uW1002 24 / 50 / 125

original equipment / retrofitting

nkt: cB-24tE connectivity:

rsti-58xxrsti-cc58xx;

alternatives on request

12

product picture description type um (KV) usesensor inside

diameter page

separable phase current sensor(divisible ring

cores)

smcs/t-JW1002 0,72 / 3

retrofitting /(original

equipment)Ø 55 mm 14

not separable current sensor

(closed ring cores)

smcs-JW1001 0,72 / 3 original

equipment Ø 82 mm 14

product picture description type um (KV) usesensor inside

diameter page

separable sensor for earth fault

detection(divisible ring

cores)

gaE120/sEns-

JW10030,72 / 3

retrofitting /(original

equipment)Ø 120 mm 16

Voltage sensor

phase current sensor

sensor for earth fault detection

multifunction current sensor

Page 11: Sensors - Klinkmann

11

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

Variant sensor cable connection

1

direct connection

2

3

open-2pin

4

5

7

rJ-45 Plug

10cm cablem8 socket 3-pin

flange m8 socket 3-pin

m8 plug 3-pin

m8 right-angle plug 3-pin

m8 socket 3-pinliycy-oB 3x0,25mm²length: 3,7m or customer‘s

definition

y-adapter

2 x m8 plug 3-pin liycy-oB 3x0,25mm y-adapter Patch cable rJ-45 plug

Patch cable

coaxial rg 58

liycy-oB 3x0,25mm

liycy-oB 3x0,25mm m8 socket 3-pin(y-adapter)

voltage sensor signal

current sensor signal

Page 12: Sensors - Klinkmann

12

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

2.1 Voltage sensors

the accuracy of the sensor, i.e. the absolute value error and phase error are constant over the lifetime and have not to

be recalibrated or readjusted. the calibration to the desired nominal and secondary voltage is performed at Zelisko.

the voltage sensor is suitable for both, original equipment and retrofitting, because noreconstructions of network

stations are required.

thE voltagE sEnsor is mounted on the bacK of the t-connector to the cable outlet. therefore, the insulating plug is replaced by the voltage sensor.

2.1.1 smvs-uW1001 (With normal cone))

2.1.2 smvs-uW1002 (With shortened cone)

the cone of the voltage sensor is according to

en 50180, iso 0181 type c. due to the standardized

design, it is possible to equip different t-connectors

with this sensor.

the voltage sensor with shortened cone fits to

common cable terminations of asymmetric

t-connectors.

smVs-uW1001

smVs-uW1002

Page 13: Sensors - Klinkmann

13

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

datasheetsmvs - uW1001 & smvs - uW1002

insulation level max. 24 / 50 / 125 kv

rated frequency 50 hz / 60 hz

rated voltages max. 24/√3 kv

voltage factor 1,2 un and 1,9 un 8h

accuracy class 0,5 / 1 / 3

rated secondary voltage 3,25/√3 v or defined by customer

standard iEc 61869-7

External conditionsoperation: -25°c to +40°c

storage: -30°c to +80°c

rated burden 200 kΩ ±1% precision

connection cable & interface see configuration table page 11

overvoltage protection internal surge protector

cable connector type

smvs - uW1001:nexans: (k) (m) 440tBcellpack: cts-salternatives on request

smvs - uW1002:nkt: cB-24tE connectivity: rsti-58xx und rsti-cc58xxalternatives on request

< smVs-uW1001

smVs-uW1002 >

symmetric cone

asymmetric cone

Page 14: Sensors - Klinkmann

14

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

2.2 phase current sensorsthE PhasE currEnt sEnsors are aVailable in different Versions, first, in the version with dividable ring core for retrofit purpose. in addition, the sensor is available with closed ring cores for original equipment.

2.2.1 smcs/t-JW1002 (diVisible ring cores)

2.2.2 smcs-JW1001 (closed ring cores)

the retrofit application in existing installations is the primary

field of application for this type. the click system enables a tool-free

mounting of the sensor on site. dismounting of the t-connector

is not necessary, since the sensor is enclosing the cable. the

sensor is delivered with two cable straps to fix it directly on

the output cable. the cut face of the iron core and a sophisticated

spring system in the sensor housing ensure that the measurement

precision of the sensor is guaranteed after assembly on the output

cable. the accuracy of this sensor, more precisely the absolute

value error and the phase error is in class 1 according

to iec 61869-8.

this type is designed for simple original equipment in switchgears.

it is slide on the not mounted output t-connector in the substation.

When the connector is screwed on the feed through, its sheathing

expands. thus, the sheathing presses against the inner surface of

the current sensor and fix it. consequently, additional fixations of

the sensor in the substation are not necessary.

due to a stable production process, it is possible to provide the

sensors in a set of threewith a standard deviation in absolute value

and phase error of 0,05% and 0,05°, respectively. consequently,

a set of three sensors enables earth fault current detection in

addition the current measurement, without using earth fault

detection transformers.

due to their small size, up to three sensors can be mounted

in a cable compartment with a width of 300mm and a phase

distance of 95mm.

smcs/t-JW1002

smcs-JW1001

Page 15: Sensors - Klinkmann

15

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

datasheetsmcs/t - JW1002 & smcs - JW1001

insulation level 0,72 / 3 kv

rated frequency 50 hz / 60 hz

rated short time thermal current 25 ka / 1 s

Primary current 300 a; Ext. 200%

accuracy class

smcs/t - JW10021 & 5P10 … 5P20;

3 & 5P10 … 5P20

smcs - JW1001

0,5 & 5P10 … 5P20

1 & 5P10 … 5P20

3 & 5P10 … 5P20

output signal 225 mv according to iEc 61869-8

standard iEc 61869-8

External conditionsoperation: -25°c to +40°c

storage: -30°c to +80°c

rated burden ≥ 20 kΩ

connection cable & interface see configuration table page 11

smcs/t - JW1002

smVs-JW1001

Page 16: Sensors - Klinkmann

16

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

2.3 sensors for earth fault detection2.3.1. gaE120/sEns-JW1003 (diVisible ring cores). the sensor for earth fault detection of type gae120/sens is based on a market proven andestablished product. all output cables are carried through this transformer.

the sensor for earth fault detection of type gae120/sens

is based on a market tried and tested products. all output

cables of the substation are passing through this trans-

former. in case of earth fault in a three phase power supply,

a current occurs due to the displacement of the neutral

point. this current is implemented with a specific ratio

in the output of the sensor. therefore, the system enables

to detect fault and short-circuit currents, respectively. in

this sensor inductive transformer principles are combined

sophisticated sensor technology. the highly finished cut

faces of the iron core ensure a constant and high accuracy

of the measurement after assembling.

gae120/sens

Page 17: Sensors - Klinkmann

17

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

datasheetgaE120/sEns - JW1003

insulation level 0,72 / 3 kv

rated frequency 50 hz / 60 hz

rated short time thermal current 25 ka / 3 s

transmission earth fault detection 60 a // 225 mv (transmission on request))

accuracy class

Primary current: 1 … 60 a angle error: ±120

ε*@ 0,4 a: ≤ 10%ε*@ 200 a: ≤ 20%

class 1 according to iEc 61869-8

output signal 225 mv according to iEc 61869-8

standard iEc 61869-8

External conditionsoperation: -25°c to +40°c

storage: -30°c to +80°c

rated burden ≥ 20 kΩ

connection cable & interface see configuration table page 11

gae120/sens - JW1003

* composite error (%)

mEasurEmEnt PrEcision aftEr assEmBling.

Page 18: Sensors - Klinkmann

18

EfficiEnt. tEchnology. WorldWidE.EfficiEnt. tEchnology. WorldWidE.

2.4 multifunctional current sensors (phase current- and earth fault detection)

2.4.1. smcs3-JW1004 (closed ring cores). the current sensor in 3-phase design combines maximal flexibility with maximal functionality. it is possible to add the earth fault detection to the three single phase converter in the sensor.

in addition to the maximum version,

consisting in three current sensors and

a sensor for the earth fault detection,

different simpler layouts can be pro-

vided in accordance to customer

requirements.

this sensor is designed for original

equipment in switchgears.

an advantage of this system is a simple

and easy assembling of a single sensor,

which takes over the tasks of up to four

different sensors.

the size of the device is always the same, regardless of the configuration chosen by the customer. due to the closed design

of the sensor core, significantly higher accuracies, than with cut iron cores, are achieved.

the design of the sensor can be adapted to customer request regarding the distance between the poles and the

external dimensions.

smcs3 - JW1004

Page 19: Sensors - Klinkmann

19

v o ltag E a n d c u r r E n t s E n s o r s

f o r i n t e l l i g e n t t r a n s f o r m e r s u b s tat i o n s

datasheetsmcs3-JW1004

insulation level 0,72 / 3 kv

rated frequency 50 hz / 60 hz

rated short time thermal current 25 ka / 1 s

transmission phase current senor 300 a // 225 mv Ext. 200%

transmission earth fault detection 60 a // 225 mv (transmission on request)

accuracy class phase current

0,5 & 5P10

1 & 5P10

3 & 5P10

accuracy class earth fault detection

Primary current: 1 … 60 a angle error: ±120

ε*@ 0,4 a: ≤ 10%

class 1 according to iEc 61869-8

output signal at rated current 225 mv according to iEc 61869-8

integrable sensor options

3x phase

2x phase + 1 earth fault

3x phase + 1 earth fault

standard iEc 61869-8

External conditionsoperation: -25°c to +40°c

storage: -30°c to +80°c

rated burden ≥ 20 kΩ

connection cable & interface see configuration table page 11

Phase distance 95 mm; other phase distances possible on request

* composite error (%)