sem 3036e rack piping
TRANSCRIPT
SAMSUNG ENGINEERING CO., LTD.
DESIGN MANUAL
SEM - 3036E
Piping Design Manual
RACK PIPING
REV. :
DATE :
5
1998. 9. 28
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
CONTENTS
Page
1. GENERAL
1.1 Purpose ------------------------------------------------------------------------------ 1
1.2 Application Scope -------------------------------------------------------------------- 1
1.3 Relevant Manuals --------------------------------------------------------------------- 1
2. PIPING DESIGN CRITERIA
2.1 Rack piping design criteria ----------------------------------------------------------- 1
2.2 General piping design criteria -------------------------------------------------------- 2
3. RACK ARRANGEMENT
3.1 Items to be considered --------------------------------------------------------------- 3
3.2 Typical Layout ----------------------------------------------------------------------- 3
4. RACK HEIGHT ------------------------------------------------------------------------------- 5
5. PIPING ARRANGEMENT AND DECISION ON THE RACK WIDTH
5.1 Piping Arrangement ------------------------------------------------------------------- 7
5.2 Rack Width -------------------------------------------------------------------------- 15
6. LOADING DATA
6.1 Type of Load ------------------------------------------------------------------------ 16
6.2 Calculation Method ------------------------------------------------------------------ 17
6.3 Layout Aids for Piperack ------------------------------------------------------------ 18
6.4 Weight Table for Thermal Insulation (for reference) --------------------------------- 21
7. EXPANSION LOOPS ------------------------------------------------------------------------ 28
8. RACK STRUCTURE (FOR REFERENCE) ----------------------------------------------------------- 41
9. HISTORY OF THIS MANUAL ------------------------------------------------------------------- 44
Appendix Ⅰ Sample of pipe rack loading data information drawing
Appendix Ⅱ Sample of calculation table for maximum bending stress, anchor force and friction
force
i i
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
1. GENERAL
1.1 Purpose
This manual provides Preconditions for standardization of forms, method of expression
and limitations of rack piping drawings which are to be designed/drafted by SECL.
1.2 Application Scope
This manual shall be applied to all jobs executed by SECL unless otherwise specially required
from vendor or licensor.
1.3 Relevant Manuals
(1) SES-H-101E "Piping Design"
(2) SEM-3002 "Requirements for Drafting Piping Drawing"
(3) SEM-3101 "Requirements for Drafting Plot Plan"
(4) SEM-3102 "Drafting of Piping Connection Drawing on Battery Limit"
(5) SEM-3104 "Drafting Key Plan"
(6) SEM-3106 "Preparation Piping Note"
(7) SEM-3112 "Decision Method on Drawing Number"
(8) SEM-3113 "Drafting of Plan Drawing"
2. PIPING DESIGN CRITERIA
2.1 Rack piping design criteria
The following piping shall be laid out on the pipe rack with 25% space for future piping.
2.1.1 Process Piping
2.1.2 Blow-down piping (flare piping)
(1) Steam and condensate piping
(2) Boiler feed water piping, potable water, process, water, demineralized water,
cooling water,... etc.
(3) Air (Plant and instrument) piping.
(4) Fuel oil, fuel gas, nitrogen piping
2.1.4 Instrument/electrical duct or cable tray
2.1.5 Catwalk
1 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
2.2 General Design Criteria
3. RACK ARRANGEMENT
Type Within the unit O.S.B.L
Rack (1) Process piping
1) Piping to connect equipment located
at 6m distance and over
2) Product piping to carry materials
from tower, heat exchanger, pump,
etc. to the storage area or other
unit and plant.
3) Raw materials or other supply
piping entered into the unit plant.
(2) Blow-down piping (flare piping)
(3) Instrument/electrical duct
(4) Utility piping
1) Steam and condensate piping
2) Gas, plant air and instrument air
piping
3) Boiler supply water, city water,
process water, demineralized water
piping, and cooling water piping
not buried
4) Fuel oil and gas piping
(5) Catway
(1) Process piping
1) Product incoming piping
2) Raw material piping
(2) Utility piping
1) Steam and condensate piping
2) Water piping
(*) Yard piping shall be above-ground
piping as far as space is available.
But rack piping is permissible if yard
piping is not available considering
the walkway and access.
Above-
ground
(1) Discharge piping and vibration piping
of reciprocating compressor
(2) Storage and in-out piping with dike
(3) Large size fluid piping
(1) In-out piping for raw material and
products
Trench (1) Cable duct for electric power
(2) Cooling water piping for pump
(3) Drain recovery piping
(4) Piping extended to the sump tank
Under-
ground
(1) Utility piping
1) Cooling water piping and oily
piping
2) Fire-fighting water piping
3) Water supply piping
2 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
Rack arrangement is generally subject to the location of process lines such as raw material piping
and products piping and the location of utility lines that enter and leave the unit boundary.
3.1 Items to be considered
(1) Installation and maintenance of equipment and transportation of equipment and materials.
(2) Piping between each unit shall be as short as possible.
(3) Length and number of rack shall be the minimum.
3.2 Typical Layout
(1) Dead end yard lines enter and (2) Straight through yard, line can
leave one end the rack. enter and leave both ends of the
rack.
(3) L-shaped yard lines can enter (4) T-shaped rack piping can enter
and leave north and east of and leave on three sides of the
the rack. rack.
3 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(5) U-shaped yard lines can enter (6) Combination of I and T shaped
and leave all four sides of the rack.
rack.
(7) Complex rack piping arrangement for
a very large chemical plant.
4. RACK HEIGHT
4 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(1) The height of top surface of the lowest rack beam shall be subject to the following:
(2) The following shall be considered in deciding the height "H".
1) Observance of minimum height of the following
2) Decisions shall be made after examining mutual relation between the equipments, and problems
on taking-in, operation and maintenance of equipment.
3) For the minimum height mentioned on above item No.1), consider the highest point of road
paving.
4) According to the road traffic act enforcement ordinance, all facilities such as a bridge,
signs above the road shall have min. 4.5m headroom from lowest point of the road.
5) When the equipment such as exchanger is located under the rack, its highest part shall be
the base of rack height after examining each exchanger as shown on the below.
5
Classification H1 Remarks
Maintenance area inside of B.L . 2500
Main road crossing at inside of B.L. 4500 Clearance for big vehicle : 3500
Main road crossing at outside of B.L.
(2nd class state road)4500 Road traffic act
Main road crossing at outside of B.L.
(1st class state road)6000 Road traffic act
Incoming railway 6700 Rail road act
(Unit : mm)
44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(3) Double level rack
Difference of height (H) for each level of rack shall be 1000mm, 1500mm, 2000mm as the
standard.
The figures Ⅰ,Ⅱ and Ⅲ show the elbows connected fitting to fitting and the dimensions of
For exchanger with hot or cold
insulation, the clearance of
minimum 300mm shall be
provided from the outside of
insulation material.
If an angle is necessary, special
caution is required to avoid the
interference with the adjacent pipe.
Type "Ⅰ" Type "Ⅱ" Type "Ⅲ"
6 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
the height(h) are shown in the following table.
(Note) : H ≥ 2h
For elbow 90°, 45°and 30°→ Consider it as a long radius elbow and
calculate the height.
5. PIPING ARRANGEMENT AND THE RACK WIDTH
5.1 Piping Arrangement
(1) Large size pipes (14" and larger) shall be arranged close to the column in order to
decrease the bending moment of beam.
(2) The utility piping shall be laid on the middle of the rack If the rack has a
single level and these piping shall be laid on the upper level if the rack has two levels.
Piping in the rack shall be arranged according to the "Table of arrangement classification"
on the next page.
Nominal Pipe Size 24B 26B 28B 30B 32B 34B 36B 40B
Elbow Dimension 914.4 990.6 1066.8 1143.0 1219.2 1295.4 1371.4 1524.0
Type Ⅰ (90°) - - - - - - - -
Type Ⅱ (45°) 915 991 - - - - - -
Type Ⅲ (30°) 557 625 673 721 762 817 865 961
Nominal Pipe Size 6B 8B 10B 12B 14B 16B 18B 20B
Elbow Dimension 228.6 304.8 381.0 457.2 533.4 609.6 685.8 762.0
Type Ⅰ (90°) 458 610 762 916 - - - -
Type Ⅱ (45°) - - - 458 534 610 686 762
Type Ⅲ (30°) - - - - 337 385 433 479
(Unit : mm)
7 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
8 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
Table of arrangement classification
(Note) : ◎ Expansion loop may be required.
TypeUpper Rack Lower Rack
Side Center Side Center
PROCESS
Blow-down (Flare) piping ○
Raw material inlet piping (12B and over) ◎ ○
Raw material inlet piping (10B and under) ○ ○
Product discharge piping (12B and over) ◎ ○
Product discharge piping (10B and under) ○ ○
Overhead piping from tall tower or highlyelevated vessel ○ ○
Piping from tower and vessel to pumps orexchangers ○ ○
Pump discharge piping ○ ○
Corrosive piping ○ ○
Piping located between equipments on groundleved ○ ○
Vibration piping ○
UTILITY
High and low pressure steam piping ○
Condensate piping ○
Boiler feed water piping ○ ○ ○
Hose station piping (water, air, N₂, etc.) ○ ○
Plant air piping ○ ○
Cooling water header piping for pump ○
Fuel oil and gas piping ○ ○
Instrument air piping ○
DUCT
Instrument duct ○ ○
Electric duct ○ ○
9 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(3) The end of utility header piping shall be arranged as same as the following figures.
(Note) : (*) For the class of 900LB and over, the piping similar to the above types shall
be avoided.
(4) Piping with corrosive fluids shall not be installed above the cable duct.
(5) For reciprocating compressor discharge piping, pressure drop valve and drain piping to be
installed on the pipe rack, thorough consideration shall be given to the vibration
protection.
(6) Piping at B.L. connection point shall be arranged through sufficient coordibation with the
client and the relevant contractor, discussing the piping arrangement and the anchor
locations.
(7) Platform or walkway with ladder shall be installed on the rack where frequent operation
and/or maintenance of valves are required. A ladder hall be installed with a cage .
Class Blind flange Cap
(*) 300LB and under 8B and under 10B and larger
(*) 600LB and under 6B and under 8B and larger
Type
10 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(8) When necessary to install an expansion loop on the condensate line, do it horizontally to
prevent water hammering. But, do as follows if horizontal loop is impossible.
(9) Loop of piping shall be grouped considering a fine view.
Make lines into a group and install a large size piping and high temperature piping to
the edge of the rack.
11 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(10) Grounding is necessary on the piping where static electricity is expected to occur.
[Reference]
1) fluid that could be dangerous from static electricity.
┌ 1st Petroleum (crude oil, gasoline, solvent, naphtha, tar, light oil, etc.)
│
Petroleum ┼ 2nd Petroleum (kerosene, light oil, diesel oil, xylene, etc.)
│
└ 3rd Petroleum (heavy oil, lube oil, tars such as creosote oil)
Ether, carbon bisulfide, collodion, acetone, nitric acid ester, formic acid ester,
pyridine, chloro-benzol, animals and plants oils, etc.
2) About the electrification
Safety fluid velocity → 1m/sec and under for petroleum in API
Constant fluid velocity → proportional to pipe size
Constant pipe size → proportional to fluid velocity
(*) Pneumatic conveying piping for powders susceptible to the disaster due to static
electricity and non-conductive powders (synthetic resin, wheat powder, etc.).
3) Lug installation criteria
① Bonding between pipes
12
Insulated pipe
L=30+ Insulation thickness
Fabrication and attachment
of lug by piping contractorLug for bond
44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
② Bonding between valve and pipe
③ For piping on the rack, it is recommended to consider the rack column connected
to grounding main line at every 18m as same as the piping.
(11) Harzadous gas piping shall be installed on the upper rack and it shall be away from high
temperature piping.
(12) Install steel shoes on the hot-insulated piping (except for protector) and the cold-
insulated piping operating at over 0℃.
(13) Install support with cradle (rest type or whole circumference type) for cold-insulated
piping operating at 0℃ and under.
Sus Teminal
Sus Teminal
13
Farication and
attachment of lug
by piping contractor
same as bolt hole size
* Leave some space
to take out bolts
44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(14) Install support with saddle for thin pipes or large size pipes (D/t > 95) to minimize
local stress. (But, as above support type is not necessary when the distance of rack
column is short, its application shall be determined after preliminary examination.)
(15) Changes in piping direction
(Used in O.S.B.L.) (Generally used within the unit.)
This type is economical. This type can be applied to the line
with complicated change of direction.
Care shall be taken for overhang in
the corner area.
(Proper middle beam or dummy supports
may be required.)
(16) Oxygen piping shall not be arranged adjacent to the electrical duct.
SADDLE
Plane bending 3-dimensional bending
14
SHOE CRADLE
44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
5.2 Rack Width
(1) Piping spacing on the rack shall be decided in accordance with "Drafting Data C-9
(SEM-3007)".
(Thorough consideration shall be given to the maintenance, hot insulation, cold insulation
and lateral movement by thermal expansion.)
(2) If special valve and instrument are installed on the rack, make decision on the width
considering the space of operation and maintenance.
(3) For the area where there are orifice piping, provide space for installing orifice
considering the orientation of differential pressure taps.
Instrument Hook-Up Drawing
(Note) : * Basically, do not use type "B-2" for superheated steam.
(It is to protect stress corrosion.)
* Type "B-1" and "C-1" shall be generally installed as the following figure.
15 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(4) Leave 10-15% of space as a rule.
Also provide 20~30% of the space if future extension is expected.
(5) Rack width shall be decided as shown on the below.
B ≥ Bo + F
Bo = { (P1 + P2)) + CE } × (1 + F)
B : Rack width
Bo : Calculated rack width
P1, P2 : Pipe spacing (as per "Drafting Data C-9" in SEM-3007)
CE : Electric cable duct
α : 0.1 ~ 0.15
F : For future extension (α included)
6. LOADING DATE
6.1 Type of Load
Type Description Direction Remarks
Sustain
load(DeadWeight of piping, valve and load insulation Vertical
Thermal load
Load by thermal expansion of piping Horizontal
Reaction force by internal pressure of
expansion bellows.Horizontal
Dynamic loadLoad by vibration of piping
Load by wind and earthquake Horizontal
16 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.2 Calculation Method
(1) Weight calculation criteria of piping, valve and insulation
1) Liquid piping
a) Insulated and subject to hydrostatic pressure test
Load = piping weight + insulation weight + contents weight
b) Un-insulated and subject to hydrostatic pressure test
Load = piping weight + contents weight
c) Insulated and subject to pneumatic pressure test
Load = piping weight + insulation weight + contents weight
d) Un-insulated and subject to pneumatic pressure test
Load = piping weight + contents weight
2) Gas piping
a) Insulated and subject to hydrostatic pressure test
Load = piping weight + insulation weight + water weight
b) Un-insulated and subject to hydrostatic pressure test
Load = piping weight + water weight
c) Insulated and subject to pneumatic pressure test
Load = piping weight + insulation weight
d) Un-insulated and subject to pneumatic pressure test
Load = piping weight
Note : 1) For pipe and insulation weight, refer to weight table of paragraph 6.4.
2) For instrument duct and electric duct, refer to the following table.
Type Description Direction Remarks
Sustainedload
(Live load)
Liquid load for hydrostatic pressure test. Vertical Refer to lineschedule.
Snow load (The difference of snowfalldepending on the region shall be consideredin making decision)
Vertical
17 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
Instrumentation Design Manual "SEM-5001"
(*) Allowable span for duct is max. 6000mm.
6.3 Layout aids for piperack
(1) The stress limit on anchors and guides is 1410 kg/㎠ Max.
(2) Force limit on anchors and guides is 1000 kg Max. unbalanced force including friction
loads.
Example 1 :
Where Ft = Thermal force
Ft = Friction force
Total unbalanced force = (1600 + 1300) - (1300 + 1000)
= 700 kg
This is within the limiting criteria
Example 2 :
Total unbalanced force = (1900 + 1400) - (700 + 500)
= 2100 kg
Width (W) × Height (H) Weight (kg/m) Width (W) × Height (H) Weight (kg/m)
1500 × 500 515 600 × 300 150
1400 × 500 480 500 × 300 125
1200 × 400 350 400 × 200 75
1000 × 400 290 300 × 200 60
800 × 300 190
18 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
This exceeds the limiting criteria of 1000 kg unbalanced force.
Consult lead stress engineer for possible alternatives to comply with the force
limitation.
Notes : 1. For friction loads, we can manually calculate them getting the unit weights from
the table in para.6.4.
2. For thermal loads, we can manually calculate them using the data and nomographs.
But computer program is very well prepared and is it faster, accurate to use
computer for total unbalanced force at the anchor point.
(3) Expansion loop requirements
a) Generally, if the total expansion in any direction on the piperack is less than
100 mm, the loop could be avoided by locating an anchor in the middle of the run.
b) The total expansion between loop anchors should not exceed 350 mm.
c) The Max. expansion at the change of direction (i.e. points ⓐ and ⓑ in the example3)
should not exceed 50 mm, consult the lead stress engineer for any exceptions.
(4) Location of loops and guides
Example 3 :
Pipe material : ASTM A-53 Gr.B
Design temp. : 260 ℃
Exp. Coefficient : 3.02 mm/m
Commodity : HC (Vapor)
Insulation : 50 mm thick calsium silicate
(12.7 kg/m - from weight table)
Friction coefficient = 0.3 ( steel on steel)
a) Total expansion in the East - West direction.
150 × 3.02 = 453 mm
b) Anchor should be located in such a way that the expansion going into the loop should
not exceed 350 mm and the total unbalanced forces at the anchors should be within
19 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
the limiting criteria (para.6.3(2)). Locate anchor at 15 m from point ⓐ and ⓑ.
c) Expansion going into the loop
{138 - (2×15)} × 3.02 = 326 mm
d) Expansion loop can be sized manually using data and nomograph.
f) Anchor and guide loads can be calculated manually or by computer. calculating by
computer is more fast and accurate
For W = 1500 mm to 3000 mm, G ≥ 60000 mm
For W > 3000 mm, G ≥ 12000 mm
Fu = Total unbalanced force.
▲ To locate guides, follow the pipe guide spacing tabulated in
general note 1.6, selection guide of pipe supports (1/8).
△
△
▲ ▲
20 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4 Weight Table for pipe and Thermal Insulation (for reference)
6.4.1 Calcium silicate hot-insulation (ρ = 0.22 g/㎤)
Nominalpipesize(B)
Outsidediameter(mm)
Internalpipewaterweight(kg/m)
Weight of hot-insulation by thickness (THK: mm, WT: kg/m)
25 30 50 65 75 90 115 140 150 175 200 225 250
1/2 21.7 - 0.8 1.1 2.5 3.9 5.0 6.9 10.9 15.6 17.8 23.8 30.6 38.4 46.9
3/4 27.2 - 0.9 1.2 2.7 4.1 5.3 7.3 11.3 16.2 18.4 24.5 31.4 39.2 47.9
1 34.0 0.6 1.0 1.3 2.9 4.4 5.7 7.7 11.8 16.8 19.1 25.3 32.3 40.3 49.1
1½ 48.6 1.4 1.3 1.6 3.4 5.1 6.4 8.6 13.0 18.3 20.6 27.0 34.4 42.5 51.6
2 60.5 2.2 1.5 1.9 3.8 5.6 7.0 9.4 13.9 19.4 21.8 28.5 36.0 44.4 53.7
2½ 76.3 3.6 1.8 2.2 4.4 6.3 7.8 10.3 15.2 20.9 23.5 30.4 38.2 46.9 56.4
3 89.1 5.1 2.0 2.5 4.8 6.9 8.5 11.1 16.2 22.2 24.8 31.9 40.0 48.8 58.6
4 114.3 8.7 2.4 3.0 5.7 8.1 9.8 12.7 18.2 24.6 27.4 35.0 43.4 52.8 62.9
6 165.2 18.9 3.3 4.0 7.4 10.3 12.5 15.9 22.3 29.5 32.7 41.1 50.5 60.7 71.7
8 216.2 32.9 4.3 5.1 9.2 12.6 15.1 19.1 26.3 34.5 38.0 47.3 57.5 68.6 80.6
10 267.4 50.7 5.1 6.2 11.0 14.3 17.7 22.2 30.4 39.4 43.3 53.5 64.6 76.6 89.4
12 318.5 72.9 5.9 7.2 12.7 17.2 20.4 25.4 34.5 44.4 48.6 59.7 71.7 84.5 98.2
14 355.6 92.7 6.6 8.0 14.0 18.9 22.3 27.7 37.4 50.2 52.4 64.2 76.8 90.3 104.6
16 406.4 122.1 7.5 9.0 15.8 21.2 25.0 30.9 41.4 52.9 57.7 70.3 83.8 98.2 113.4
18 457.2 155.6 8.3 10.1 17.5 23.5 27.6 34.0 45.5 57.8 62.9 76.5 90.8 106.1 122.2
20 508.0 193.1 9.2 11.2 19.3 25.7 30.2 37.2 49.5 62.7 68.2 82.6 97.9 114.0 131.0
22 558.8 234.7 10.1 12.2 21.0 28.0 32.9 40.4 53.6 67.6 73.5 88.8 104.9 121.9 139.8
24 609.6 279.6 11.0 13.3 22.8 30.3 35.5 43.5 57.6 72.5 78.7 94.9 111.9 129.8 148.5
26 660.4 330.0 11.8 14.3 24.5 32.6 38.1 46.7 61.6 77.4 84.0 101.0 118.9 137.7 157.3
28 711.2 383.8 12.7 15.4 26.3 34.9 40.8 52.9 65.7 82.4 89.3 107.2 126.0 145.6 166.1
30 762.0 440.6 13.6 16.4 28.1 37.2 43.4 53.0 69.7 87.3 94.5 113.3 133.0 153.5 174.9
32 812.8 502.4 14.5 17.5 29.9 39.4 46.0 56.2 73.7 92.2 99.8 119.5 140.0 161.4 183.6
34 863.6 568.2 15.4 18.5 31.6 41.8 48.7 59.3 77.8 97.1 105.1 125.6 147.0 169.3 192.4
36 914.4 638.1 16.2 19.6 33.3 44.0 51.3 62.2 81.8 102.0 110.3 131.8 154.0 177.2 201.2
40 1016.0 782.8 18.0 21.7 36.8 48.6 56.6 68.8 89.9 111.9 120.9 144.1 168.1 193.0 218.7
42 1066.8 840.0 18.9 22.7 38.6 50.8 59.2 72.0 93.9 116.8 126.1 150.2 175.1 200.9 227.5
44 1117.6 944.7 19.7 23.8 40.3 53.1 61.8 75.1 98.0 121.7 131.4 156.3 182.1 208.8 236.3
48 1219.2 1125.0 21.5 25.9 43.9 57.7 67.1 81.4 106.0 131.5 141.9 168.6 196.2 224.6 253.9
54 1371.6 1426.0 24.1 29.1 49.1 64.5 75.0 90.9 118.2 146.3 157.7 187.1 217.2 248.3 280.2
60 1524.0 1763.0 26.8 32.2 54.4 71.4 82.9 100.4 130.3 161.0 173.5 205.5 238.3 272.0 306.5
21 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.2 Perlite hot-insulation (ρ = 0.20 g/㎤)
Nominalpipesize(B)
Outsidediameter(mm)
Internalpipewaterweight(kg/m)
Weight of hot-insulation by thickness (THK: mm, WT: kg/m)
25 30 50 65 75 90 115 140 150 175 200 225 250
1/2 21.7 - 0.7 1.0 2.3 3.5 4.6 6.3 9.9 14.2 16.2 21.6 27.9 34.9 42.7
3/4 27.2 - 0.8 1.1 2.4 3.8 4.8 6.6 10.3 14.7 16.7 22.2 28.6 35.7 43.5
1 34.0 0.6 0.9 1.2 2.6 4.0 5.1 7.0 10.8 15.3 17.3 23.0 29.4 36.6 44.6
1½ 48.6 1.4 1.2 1.5 3.1 4.6 5.8 7.8 11.8 16.6 18.7 24.6 31.2 38.7 46.9
2 60.5 2.2 1.3 1.7 3.5 5.1 6.4 8.5 12.7 17.6 19.8 25.9 32.7 40.4 48.8
2½ 76.3 3.6 1.6 2.0 4.0 5.8 7.1 9.4 13.8 19.0 21.3 27.6 34.7 42.6 51.3
3 89.1 5.1 1.8 2.3 4.4 6.3 7.7 10.2 14.7 20.2 22.6 29.0 36.5 44.4 53.4
4 114.3 8.7 2.2 2.7 5.2 7.3 8.9 11.6 16.6 22.4 24.9 31.8 39.5 48.0 57.2
6 165.2 18.9 3.0 3.7 6.8 9.4 11.3 14.4 20.2 26.8 29.7 37.4 45.9 55.2 65.2
8 216.2 32.9 3.8 4.6 8.4 11.5 13.7 17.3 23.9 31.3 34.5 43.0 52.3 62.4 73.2
10 267.4 50.7 4.6 5.6 10.0 13.6 16.1 20.2 27.6 35.8 39.3 48.6 58.7 69.6 81.3
12 318.5 72.9 5.4 6.6 11.6 15.7 18.5 23.1 31.3 40.3 44.2 54.3 65.2 76.8 89.3
14 355.6 92.7 6.0 7.3 12.7 17.2 20.3 25.2 34.0 43.6 47.7 58.3 69.8 82.1 95.1
16 406.4 122.1 6.8 8.2 14.3 19.3 22.7 28.1 37.7 48.1 52.4 63.9 76.2 89.3 103.1
18 457.2 155.6 7.6 9.2 15.9 21.3 25.1 30.9 41.3 52.5 57.2 69.5 82.6 96.4 111.1
20 508.0 193.1 8.4 10.1 17.5 23.4 27.5 33.8 45.0 57.0 62.0 75.1 89.0 103.6 119.1
22 558.8 234.7 9.2 11.1 19.1 25.5 30.0 36.7 48.7 61.5 66.8 80.7 95.4 110.8 127.0
24 609.6 279.6 10.0 12.1 20.7 27.6 32.3 39.6 52.4 65.9 71.6 86.3 101.7 118.0 136.6
26 660.4 330.0 10.8 13.0 22.3 29.6 34.7 42.4 56.0 70.4 76.4 91.9 108.1 125.2 143.0
28 711.2 383.8 11.6 14.0 23.9 31.7 37.0 45.3 59.7 74.9 81.2 97.4 118.3 132.4 151.0
30 762.0 440.6 12.4 14.9 25.5 33.8 39.4 48.2 63.4 79.3 86.0 103.0 120.9 139.5 159.0
32 812.8 502.4 13.2 15.9 27.1 35.8 41.8 51.1 67.0 83.8 90.7 108.6 127.3 146.7 166.9
34 863.6 568.2 14.0 16.8 28.7 37.9 44.2 53.9 70.7 88.3 95.5 114.2 133.7 153.9 174.9
36 914.4 638.1 14.8 17.8 30.3 40.0 46.6 56.8 74.4 92.7 100.3 119.8 140.0 161.1 182.9
40 1016.0 782.8 16.4 19.7 33.5 44.1 51.4 62.5 81.7 101.7 109.9 131.0 152.8 175.4 198.9
42 1066.8 840.0 17.1 20.7 35.1 46.2 53.8 65.4 85.4 106.2 114.7 136.5 159.2 182.6 206.8
44 1117.6 944.7 17.9 21.6 36.7 47.9 56.2 68.3 88.3 110.6 119.5 142.1 165.6 189.8 214.8
48 1219.2 1125.0 19.5 23.5 39.9 52.4 61.0 74.0 96.4 119.6 129.0 153.3 178.3 204.2 230.8
54 1371.6 1426.0 21.9 26.4 44.7 58.7 68.2 82.7 107.6 133.0 143.4 170.1 197.5 225.7 254.7
60 1524.0 1763.0 24.3 29.3 49.4 64.9 75.4 91.3 118.4 146.4 157.8 186.8 216.6 247.3 278.7
22 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.3 Urethane foam cold-insulation (ρ = 0.035 g/㎤)
Nominalpipesize(B)
Outsidediameter(mm)
Internalpipewaterweight(kg/m)
Weight of cold-insulation by thickness (THK: mm, WT: kg/m)
25 30 40 50 65 75 90 115 140 150 175 200 225 250
1/2 21.7 - 0.1 0.2 0.3 0.4 0.6 0.8 1.1 1.7 2.5 2.8 3.8 4.9 6.1 7.5
3/4 27.2 - 0.1 0.2 0.3 0.4 0.7 0.8 1.2 1.8 2.6 2.9 3.9 5.0 6.2 7.6
1 34.0 0.6 0.2 0.2 0.3 0.5 0.7 0.9 1.2 1.9 2.7 3.0 4.0 5.1 6.4 7.8
1½ 48.6 1.4 0.2 0.3 0.4 0.5 0.8 1.0 1.4 2.1 2.9 3.3 4.3 5.5 6.8 8.2
2 60.5 2.2 0.2 0.3 0.4 0.6 0.9 1.1 1.5 2.2 3.1 3.5 4.5 5.7 7.1 8.5
2½ 76.3 3.6 0.3 0.4 0.5 0.7 1.0 1.2 1.6 2.4 3.3 3.7 4.8 6.1 7.5 9.0
3 89.1 5.1 0.3 0.4 0.6 0.8 1.1 1.4 1.8 2.6 3.5 3.9 5.1 6.4 7.8 9.3
4 114.3 8.7 0.4 0.5 0.7 0.9 1.3 1.6 2.0 2.9 3.9 4.4 5.6 6.9 8.4 10.0
6 165.2 18.9 0.5 0.6 0.9 1.2 1.6 2.0 2.5 3.5 4.7 5.2 6.5 8.0 9.7 11.4
8 216.2 32.9 0.7 0.8 1.1 1.5 2.0 2.4 3.0 4.2 5.5 6.0 7.5 9.1 10.9 12.8
10 267.4 50.7 0.8 1.0 1.4 1.8 2.3 2.8 3.5 4.8 6.3 6.9 8.5 10.3 12.2 14.2
12 318.5 72.9 0.9 1.1 1.6 2.0 2.7 3.2 4.0 5.5 7.1 7.7 9.5 11.4 13.4 15.6
14 355.6 92.7 1.0 1.3 1.7 2.2 3.0 3.5 4.4 6.0 8.0 8.3 10.2 12.2 14.4 16.6
16 406.4 122.1 1.2 1.4 2.0 2.5 3.4 4.0 4.9 6.6 8.4 9.2 11.2 13.3 15.6 18.0
18 457.2 155.6 1.3 1.6 2.2 2.8 3.7 4.4 5.4 7.2 9.2 10.0 12.1 14.4 16.9 19.4
20 508.0 193.1 1.5 1.8 2.4 3.1 4.1 4.8 5.9 7.9 10.0 10.9 13.1 15.6 18.1 20.8
22 558.8 234.7 1.6 1.9 2.6 3.3 4.5 5.2 6.4 8.5 10.8 11.7 14.1 16.7 19.4 22.2
24 609.6 279.6 1.8 2.1 2.9 3.6 4.8 5.6 6.9 9.2 11.5 12.5 15.1 17.8 20.7 23.6
26 660.4 330.0 1.9 2.3 3.1 3.9 5.2 6.1 7.4 9.8 12.3 13.4 16.1 18.9 21.9 25.0
28 711.2 383.8 2.0 2.5 3.3 4.2 5.6 6.5 8.4 10.5 13.1 14.2 17.1 20.0 23.2 26.4
30 762.0 440.6 2.2 2.6 3.5 4.5 5.9 6.9 8.4 11.1 13.9 15.0 18.0 21.2 24.4 27.8
32 812.8 502.4 2.3 2.8 3.8 4.8 6.3 7.3 8.9 11.7 14.7 15.9 19.0 22.3 25.7 29.2
34 863.6 568.2 2.5 2.9 4.2 5.0 6.7 7.7 9.4 12.4 15.4 16.7 20.0 23.4 26.9 30.6
36 914.4 638.1 2.6 3.1 4.2 5.3 7.0 8.2 9.9 13.0 16.2 17.5 20.1 24.5 28.2 32.0
40 1016.0 782.8 2.9 3.5 4.6 5.9 7.7 9.0 10.9 14.3 17.8 19.2 22.9 26.7 30.7 34.8
42 1066.8 840.0 3.0 3.6 4.9 6.1 8.1 9.4 11.5 14.9 18.6 20.1 23.9 27.9 32.0 36.2
44 1117.6 944.7 3.1 3.8 5.1 6.4 8.4 9.8 11.9 15.6 19.4 20.9 24.9 29.0 33.2 37.6
48 1219.2 1125.0 3.4 4.1 5.5 7.0 9.2 10.7 13.0 16.8 20.9 22.6 26.8 31.2 35.7 40.4
54 1371.6 1426.0 3.8 4.6 6.2 7.8 10.3 11.9 14.5 18.8 23.3 25.1 29.8 34.6 39.5 44.6
60 1524.0 1763.0 4.3 5.1 6.9 8.7 11.4 13.2 16.0 20.7 25.6 27.6 32.7 37.9 43.3 47.8
23 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.4 Cellular glass cold-insulation (ρ = 0.16 g/㎤)
Nominalpipesize(B)
Outsidediameter(mm)
Internalpipewaterweight(kg/m)
Weight of cold-insulation by thickness (THK: mm, WT: kg/m)
25 30 40 50 65 75 90 115 140 150 175 200 225
1/2 21.7 - 0.6 0.8 1.2 1.8 2.8 3.6 5.1 7.9 8.2 8.9 12.6 12.2 16.7
3/4 27.2 - 0.7 0.9 1.4 1.9 3.0 3.9 5.3 8.2 8.8 9.5 13.0 13.2 17.3
1 34.0 0.6 0.7 1.0 1.5 2.1 3.2 4.1 5.6 8.6 9.1 9.8 13.6 13.6 18.1
1½ 48.6 1.4 0.9 1.2 1.8 2.5 3.7 4.7 6.3 9.5 10.1 10.9 14.9 15.0 19.7
2 60.5 2.2 1.1 1.7 2.0 2.8 4.1 5.1 6.8 10.1 10.9 11.8 14.2 16.2 18.8
2½ 76.3 3.6 1.3 1.6 2.3 3.2 4.6 5.7 7.5 11.1 12.1 13.0 17.4 17.8 22.9
3 89.1 5.1 1.4 1.8 2.6 3.5 5.0 6.2 8.1 12.1 13.0 14.0 18.8 19.1 24.8
4 114.3 8.7 1.8 2.2 3.1 4.1 5.9 7.1 9.2 13.3 14.7 15.9 20.7 21.6 27.2
6 165.2 18.9 2.4 2.9 4.1 5.4 7.5 9.1 11.5 16.2 18.3 19.7 25.2 26.8 32.9
8 216.2 32.9 3.0 3.7 5.2 6.7 9.2 11.0 13.9 19.2 21.9 23.5 29.7 31.9 38.7
10 267.4 50.7 3.7 4.5 6.2 8.0 10.9 12.9 16.2 22.1 25.5 27.4 34.2 37.0 44.5
12 318.5 72.9 4.3 5.3 7.2 9.3 12.5 14.8 18.5 25.1 29.1 31.3 38.7 42.2 50.3
14 355.6 92.7 4.8 5.8 8.0 10.2 13.7 15.9 20.2 27.2 31.7 34.0 41.9 45.9 54.5
16 406.4 122.1 5.4 6.6 9.0 11.5 15.4 18.1 22.5 30.1 35.3 37.9 46.4 51.0 60.2
18 457.2 155.6 6.1 7.3 10.0 12.7 17.1 20.1 24.8 33.1 38.9 41.7 50.9 56.1 66.0
20 508.0 193.1 6.7 8.1 11.0 14.0 18.7 22.0 27.1 36.0 42.4 45.5 55.3 61.2 71.7
22 558.8 234.7 7.3 8.9 12.0 15.3 20.4 23.9 29.4 38.9 46.0 49.4 59.8 66.3 77.4
24 609.6 279.6 8.0 9.6 13.0 16.6 22.0 25.8 31.6 41.9 49.6 53.2 64.2 74.2 83.2
26 660.4 330.0 8.6 10.4 14.9 17.9 23.4 27.7 33.9 44.8 53.2 57.0 68.7 76.5 88.9
28 711.2 383.8 9.3 11.2 15.1 19.1 25.4 29.6 36.2 47.8 56.7 60.9 73.2 81.7 94.7
30 762.0 440.6 9.9 11.9 16.1 20.4 27.0 31.6 38.5 50.7 60.3 64.7 77.7 86.8 100.4
32 812.8 502.4 10.5 12.7 17.1 21.7 28.7 33.5 40.8 53.6 63.9 68.5 82.1 91.9 106.2
34 863.6 568.2 11.2 13.5 18.2 23.1 30.3 35.4 43.1 56.6 67.5 72.4 86.6 97.0 111.9
36 914.4 638.1 11.8 14.2 19.2 24.2 32.0 37.3 45.4 59.5 74.2 80.3 95.8 112.0 128.9
40 1016.0 782.8 13.1 15.8 21.2 26.8 35.3 41.1 50.0 65.4 81.3 87.9 104.8 122.2 140.4
42 1066.8 840.0 13.7 16.5 22.3 28.1 37.0 43.0 52.4 68.3 84.9 91.7 109.2 127.4 146.1
44 1117.6 944.7 14.4 17.3 23.3 29.3 38.6 45.0 54.6 71.3 88.5 95.6 113.7 132.5 151.8
48 1219.2 1125.0 15.6 18.8 25.3 31.9 42.0 48.8 59.2 77.1 95.6 103.2 122.6 142.7 164.3
54 1371.6 1426.0 17.6 21.1 28.4 35.7 46.9 54.5 66.1 85.9 106.4 114.7 136.0 158.0 180.6
60 1524.0 1763.0 19.5 23.4 31.4 39.6 51.9 60.3 73.0 94.7 117.8 127.0 149.5 174.3 197.8
24 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.5 Pipe weight
Normalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
1/2"
--4080160-
--StdXs-XXS
5S10S40S80S--
1.652.112.773.734.757.47
0.8011.0001.2661.6191.9412.551
0.2540.2300.1960.1510.1100.032
3/4"
--4080160-
--StdXS-XXS
5S10S40S80S--
1.652.112.773.734.757.47
0.8011.0001.2661.6191.9412.551
0.2540.2300.1960.1510.1100.032
1"
--4080160-
--StdXs-XXS
5S10S40S80S--
1.652.112.873.915.547.82
1.0181.2751.6832.1942.8833.633
0.4290.3960.3420.2790.1910.095
1¼
--4080160-
--StdXS-XXS
5S10S40S80S--
1.652.773.384.556.359.09
1.2922.0892.4993.2324.2325.445
0.7110.6090.5570.4630.3360.182
1½
--4080160---
--StdXS-XXS--
5S10S40S80S----
1.652.773.685.087.1410.1613.3416.51
0.7400.7404.0455.4047.2319.53611.47412.915
0.6890.6551.3131.1390.9050.6130.3660.183
2"
--4080160---
--StdXS-XXS--
5S10S40S80S----
1.652.773.915.548.7111.0714.2717.45
2.3873.9265.4367.47411.07813.43716.19418.431
2.5542.3542.1651.9051.4451.1440.7930.507
2½"
--4080160---
--StdXS-XXS--
5S10S40S80S----
2.113.055.167.019.5314.0217.1520.32
3.6835.2558.62111.4011489720.38823.60726.384
3.7193.51430.892.7342.2841.5881.1790.825
Normalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
2½"
--4080160---
--StdXS-XXS--
5S10S40S80S----
2.113.055.167.019.5314.0217.1520.32
3.6835.2558.62111.4011489720.38823.60726.384
3.7193.51430.892.7342.2841.5881.1790.825
3"
--4080160---
--stdXS-XXS--
5S10S40S80S----
2.113.055.497.6211.1015.2418.4221.59
4.5096.44411.28015.25421.31127.65131.97735.801
5.6255.3724.7624.2623.4942.6802.1301.641
4"
---4080120-160---
---StdXS---XXS--
5S10S-40S80S------
2.113.054.786.028.5611.1012.7013.4917.1220.3223.50
5.8348.34912.73916.05822.29328.21631.78833.49940.98547.04652.560
9.5249.1828.6318.2007.4116.6676.1915.9835.0304.2623.558
6"
---4080120160---
---StdXS--XXS--
5S10S-40S80S-----
2.773.405.567.1110.9714.2718.2421.9525.4028.58
7.99213.82522.35328.23142.51854.15567.41579.11289.40498.345
20.80520.44819.49518.61716.80215.32813.63212.15910.8409.699
8"
---2030406080100120140160--
-----Std-XS------
5S10S---40S-80S------
2.773.765.566.357.048.1810.3112.7015.0618.2420.6223.0125.4028.58
14.74819.94229.22833.27636.75842.48853.03964.57375.70490.229100.840111.153121.194134.107
35.82135.10634.08033.45433.00832.27930.93929.46628.03726.19224.83823.51322.24120.594
a: ANSI B36.10 steel pipe schedule numbers
b: ANSI B36.10 steel pipe nominal wall thicknes designation
c: ANSI B36.10 stainless steel pipe schedule numbers.
25 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.5 Pipe weight (cont'd)
ormalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
10"
---2030406080100120-140160--
-----StdXS--------
5S10S---40S80S--------
3.404.195.566.357.809.2712.7015.0618.2421.4122.2325.4028.5831.7538.10
22.54627.82936.65441.72950.95660.24281.46395.735114.486132.746137.330154.965172.109188.732220.535
55.65854.91453.87253.27752.08750.74748.06946.28343.90241.66941.07438.84236.60934.52630.508
12"
--2030-40-6080-100-120140-160
----Std-XS---------
5S10S--40S-80S---------
3.964.576.358.389.5310.3112.7014.2717.4519.0521.4122.2325.4028.5831.75-
31.23736.01449.67665.13873.75579.66397.357108.876131.720143.164159.534165.040186.753207.870228.586-
78.42877.68376.04673.96372.92172.17769.94568.45765.48064014161.90961.16558.48655.80753.27751.938
14"
----10-20-3040--60-80100120140160
--------Std--XS-------
5S10S-----------------
3.964.785.335.566.357.147.928.749.5311.1011.9112.7015.0615.8819.0523.8027.7631.7535.71
34.22841.22345.98547.92054.63161.31367.98074.70781.21094.307100.899107.284126.362132.866157.941194.551224.225253.320281.446
94.79893.90593.45893.16192.41791.52490.63189.73888.84587.35786.31585.57183.19082.29779.17274.40970.68966.96963.397
Normalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
16"
--102030406080100120140160
----StdXS------
5S10S----------
4.194.786.357.929.5312.7016.6621.4126.1930.9436.5040.46
41.66947.62262.57877.92293.131123.177159.980203.078245.298286.164332.819364.770
124.264123.520121.734119.799117.716113.846109.233103.72798.36993.16187.20883.190
18"
--1020-30-406080100120140160
----Std-XS-------
5S10S------------
4.194.786.357.929.5311.1012.7014.2719.0523.8029.3634.9339.6745.24
46.13453.57570.52587.848105.051122.121139.071155.888205.623254.108309.484363.326408.106459.121
158.046157.302155.218152.986150.605148.670146.438144.354137.955131.705124.561117.865112.060105.661
20"
--1020304060-80100120140160
---StdXS--------
5S10S-----------
4.785.546.359.5312.7015.0620.6222.2326.1932.5438.1044.4549.99
59.52868.45778.472116.972154.965182.913247.635265.984310.838381.125441.055507.621564.039
194.953193.762192.720187.512182.750179.178171.142168.761162.808153.789146.289137.806130.812
22"
--102030--3080100120140160
---StdXS--------
5S10S-----------
4.785.546.359.5312.7015.8819.0522.2328.5834.9341.2847.6353.98
65.48075.89886.315129.472171.142212.811252.992293.173373.535450.921526.819599.740671.173
236.771235.431234.241228.735223.526218.169212.960207.751197.631187.809177.987168.612159.534
26 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
6.4.5 Pipe weight (cont'd)
Normalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
24"
1020-30-40---6080100120140160-10-20-----
-StdXS--------------StdXS-----
-------5S----------------
6.359.5312.7017.2715.8817.4519.055.5422.2324.5930.9438.8946.0252.3759.516.357.929.5312.7015.8819.0522.2325.4028.58
94.366140.812186.753209.537232.202254.733277.16081.850321.449354.353441.040546.761639.013718.990806.50999.709127.984153.283202.394251.504300.614349.724397.346444.969
279.780273.529268.023265.046262.219259.391256.564281.119250.909246.742235.580222.187210.430200.161189.000329.485326.211323.086316.687310.436304.186297.935291.834285.881
28"
-10-2030----
--StdXS-----
---------
6.357.929.5312.7015.8819.0522.2325.4028.58
110.126136.913165.189218.764272.339324.425376.512428.598480.685
382.911379.488375.917369.071362.225355.528348.831342.283335.735
30"
-10-203040---
--StdXS-----
5S10S-------
6.357.929.5312.7015.8819.0522.2325.4028.58
117.567147.331177.094235.134291.685348.236404.787461.339516.402
440.950437.081433.361425.920418.628411.633404.490397.346390.203
Normalpipesize
schedule wallthick.(mm)
weight(kg/m)
weightof water(kg/m)a b c
32"
-10-203040----
--StdXS------
----------
6.357.929.5312.7015.8817.4819.0522.2325.4028.58
126.496157.748189.000250.016311.031342.283372.047433.063492.591552.118
502.710498.841494.823486.935479.048474.732471.309463.720455.981448.391
34"
-10-203040----
--StdXS------
----------
6.357.929.5312.7015.8817.4819.0522.2325.4028.58
133.937166.677200.906266.386331.866364.606395.585461.339525.331587.835
568.488564.470559.857551.820543.189538.873535.004526.968518.783510.746
36"
-10-203040---
--StdXS-----
---------
6.357.929.5312.7015.8819.0522.2325.4028.58
142.866177.094212.811282.756351.213419.669488.126556.583623.551
638.582634.117629.653620.724611.794603.163594.383585.751577.269
42"
-
-
20
30
40
-
-
-
-
Std
XS
-
-
-
-
-
-
-
-
-
-
-
-
-
6.35
9.53
12.70
15.88
19.05
25.40
31.75
38.10
166.677
248.528
330.3784
10.740
491.102
651.827
809.575
965.835
572.674
862.108
851.691
841.422
831.005
810.765
790.526
770.733
27 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7. Expansion Loops
Loops designed according to these charts will be stressed to the allowable limit for A-53 Gr.B
seamless Pipe. or equal, with LR elbows of the same thicikness as straight pipe.
Do not use for weaker material, or extraploate beyond the range of the charts.
With long expansion lenghts and nested loops, investigate pipe movements.
If thrusts are critical, consult stress section.
The distance between the guides. "G" is a minimum.
If there is not sufficient room to accommodate the depth of loop shown on the chart, then some
relief can be found by widening the loop. This effect is small, and can only be counted on within
the following limits:
To reduce H by 0.3m, increase W by 3.6m
To reduce H by 0.6m, increase W by 7.2m
If W > 6m then G ≥ 2W
H always ≥ 1.5m, even after reduction.
No. reduction of H greatr than 0.6m is permitted.
i.e., No increase of W greater than 7.2m permitted.
If it is desirable from a layout point of view, W may always be safely increased without any
decrease on H, providing that:
W ≥ ½ anchor distance
G ≥ 2W
For loops in which there is a vertical offset:
No credit may be taken if the dimensiion V is a minimum-i.e. fitting to fitting.
If V consists partly of straight pipe, the flexibility of the loop will be increased, and the
amount of this increase shall be checked by stress engineer.
28 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.1 For 3" std wt to xxs inclusive
29 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.2 For 4" std wt to xxs inclusive
30 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.3 For 6" std wt to xxs inclusive
31 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.4 For 8" std wt to xxs inclusive
32 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.5 For 10" std wt to xxs inclusive
33 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.6 For 12" std wt to xxs inclusive
34 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.7 For 14" std wt to xxs inclusive
35 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.8 For 16" std wt to xxs inclusive
36 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.9 For 18" std wt to xxs inclusive
37 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.10 For 20" std wt to xxs inclusive
38 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.11 For 24" std wt to xxs inclusive
39 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
7.12 For 30" std wt to xxs inclusive
40 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
8. RACK STRUCTURE (for reference)
(1) Allow sufficient rack width between columns. (Refer para.5)
(Reference example) Rack span by plant
(Unit : mm)
(2) For conditions of rack span, decision shall be made considering the following:
1) Mutual relation with plot of each machinery
2) Relation with pipe diameter
Decision on what the minimum pipe diameter of rack piping shall be and what the allowable
bending of the minimum pipe diameter shall be.
3) Relation with pipe weight
Fluid weight of pipe, pipe weight, valve weight and insulation weight.
4) Support for special piping
Relation with piping whose support span is short, such as copper, many kinds of plastic and
glass lining pipes.
5) Relation with deflection
If deflection of pipe is too great, drainage is not good, fluid which is in the slurry state
of high boiling point produces crystals and condensible vapor such as steam and dowtherm
vapor causes water hammering.
Type of plant Rack span
Urea plant (600∼2,000 T/Y) 6000
Pitch Coke Plant 6000
Ethylene plant (200,000∼300,000 T/Y) 10000
Methanol, Polybuthyl, Refinery 6000 ∼ 8000
41 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(3) Basically, do not use assembled column for rack column.
(4) For rack column around structure or building, use columns of structure or building column
together if possible, and allow easy access from the ground.
(5) If necessary, rack shall be grounded.
(6) Rack column shall be fire proofed where necessary.
Construction method and range of fire proof shall be in accordance with the job specific
requirements.
(7) If rack is long (specially for O.S.B.L), provide one joint
bolt slot at the beam connection at every 50∼60m to absorb the thermal expansion
from temperature changes. And, do not joint the crossing rack each other.
(8) If there is expansion loop, or a lot of branch piping is expected to the unit on the rack,
indicate it on the structure planning drawing of the below form.
(9) Basically, ladders shall be installed at every 40∼60m of the rack considering the relation of
each area and cat way.
(10) Install bracing on the rack within the range that it does not interfere with pipe run,
operation and maintenance. (One bracing shall be installed at least every six span of racks.)
42 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
(11) Examples of rack structure
1) 1 level rack (there is also reinforced concrete.) : L = 6 m
2) 2 level
① Normal structure (number of beam is 2 : one on the upper and the other on the lower) :
L = 6 m
② When beam is one : L = 6 m
③ When beam is structured with truss : L = 10∼15m
(12) The maximum deflection of rack beam shall be generally 1/300 against 2 span.
43 44
DATE :
DESIGN MANUAL
RACK PIPING
SEM - 3036E
REV. :
1998. 9.28 PAGE OF
5
9. History of This Manual
Rev. Date Description
4 1996. 11. 15 (1) Progress of Enactment
This manual is enacted in accordance with Engineering Division
Strategic Plan, regarding the work of the rack piping.
(2) Written by : (Piping Engineering Team)
Koh Bong Hwan, Lee Joo Sang
Editorial Supervisor : Jeong Kyung Hwa
5 1998. 9. 28 (1) This manual is revised in accordance with piping design team
Strategic Plan of 1998, regarding the work of the rack piping.
(2) Piping engineerirng team
Written by : Mr. H.C. Chang, Lee joo sang
Reviewed by : Jeong kyung hwa
editorial Supervisor : Lee myung hak
44 44
Appendix Ⅰ: Sample of pipe rack loading data information drawing
Appendix Ⅱ: Sample of calculation table for maximum bending stress, anchor force and friction force