STRUCTURAL SPECIFICATION STABILITY · Responsibility: Maintain the stability and structural integrity of the Works and adjacent structures during the Contract DRAWINGS · Do not scale for construction purposes. · Drawings is to be read in conjunction with Structural Specifications. · Refer to architects drawings for setting out information. · Dimensions in mm (unless otherwise stated). · Drawings is to be read in conjunction with appropriate consultants information. · Sections donated 'T' (e.g. T26) are typical sections intended to provide relevant information but may not show the exact arrangement. GENERAL NOTES · The drawings are based on limited site dimensions (a full 3D survey of the existing structure has not been provided. The contractor must check any critical dimensions before ordering or cutting any structural elements to ensure fit. · Where sections show structural members in relation to floor levels these are indicative - refer to architects drawings for levels. · All water-proofing and damp-proofing works to architects details. Where these drawings show waterproof or damp proof membranes they are simply intended to indicate their position in relation to the structure. The membranes have been designed, specified and detailed by the architect or the manufacturers and to be installed as per their drawings. · All floor separation details and acoustic insulation are to the architects details. · All insulation requirements are to architects requirements. Insulation is not always shown on the structural drawings, where it is shown it is for indicative purposes only. EXISTING STRUCTURES · Duty: Check proposed methods of work for effects on structures inside and outside the boundary. · Supports: During execution of the Works: - Provide and maintain all incidental shoring, strutting, needling and other supports as may be necessary to preserve stability of existing structures on the site or adjoining, that may be endangered or affected by the Works. - Do not remove until new work is strong enough to support existing structure. - Prevent overstressing of completed work when removing supports. Standard: Comply with BS 5975 RISK ASSESSMENT As the designer of the structure for this project an assessment of the construction risks has been carried out and it is considered that a competent builder would be able to construct this project using appropriate temporary works. Attention is drawn to the table of element sizes which provide the approximate weight of the steel elements. Any particular risks are noted in the appropriate location in the drawings with the following symbol: TIME AND COST RISKS Where indicated on drawings open up structure to confirm assumptions at the start of the project. CONSTRUCTION RISKS (CDM REGULATIONS) ACTION Check details at the earliest opportunity to ensure sections fit before ordering steel. Check foundations depths at the earliest opportunity. Check availability of scheduled members at earliest opportunity. OTHER RISKS ACTION Compressive Strength of Masonry too low Check existing masonry meet requirements where noted on drawings (eg. concrete blocks and not aircrete blocks (breeze blocks, celcon)) Poor construction A competent builder should be employed. Timber bracing not installed to roof Refer to timber specifications for bracing requirements. External steel corrosion Refer to steel specifications for proprietary steel protection. Holes reducing strength in structural members Refer to material specifications prior to any cuts and holes into members. Cantilever overturning Restraint straps not installed Check if any construction sequence or specific connections are mentioned in drawings prior to loading any cantilever members. Refer to timber and masonry specifications. Check for the presence of any sewers before commencing any ground works. Pitching plates Ensure correct number and specification of bolts are installed. ! Use of cold rolled steel instead of hot rolled steel Ensure correct grade (S355 and not S235) of steel is ordered and received from the steel fabricators 2907 Land adjacent to 153 Athelstan Road IG 12.04.2021 2907 - General Specifications & Risk Assessment AS SHOWN: A4 P1 - Project No. Dwg No. Project Name Title Drawn Rev. Date Scale THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED Offices · Basingstoke T: 01256 768 588 · London (Egham) T: 020 7112 8840 W: www.modulus.ltd

Upload: others

Post on 21-Mar-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SECTION T2 - planning.org.uk

STRUCTURAL SPECIFICATIONSTABILITY· Responsibility: Maintain the stability and structural integrity of

the Works and adjacent structures during the ContractDRAWINGS· Do not scale for construction purposes.· Drawings is to be read in conjunction with Structural

Specifications.· Refer to architects drawings for setting out information.· Dimensions in mm (unless otherwise stated).· Drawings is to be read in conjunction with appropriate

consultants information.· Sections donated 'T' (e.g. T26) are typical sections intended

to provide relevant information but may not show the exactarrangement.

GENERAL NOTES· The drawings are based on limited site dimensions (a full 3D

survey of the existing structure has not been provided. Thecontractor must check any critical dimensions before orderingor cutting any structural elements to ensure fit.

· Where sections show structural members in relation to floorlevels these are indicative - refer to architects drawings forlevels.

· All water-proofing and damp-proofing works to architectsdetails. Where these drawings show waterproof or dampproof membranes they are simply intended to indicate theirposition in relation to the structure. The membranes havebeen designed, specified and detailed by the architect or themanufacturers and to be installed as per their drawings.

· All floor separation details and acoustic insulation are to thearchitects details.

· All insulation requirements are to architects requirements.Insulation is not always shown on the structural drawings,where it is shown it is for indicative purposes only.

EXISTING STRUCTURES· Duty: Check proposed methods of work for effects on

structures inside and outside the boundary.· Supports: During execution of the Works:

- Provide and maintain all incidental shoring, strutting,needling and other supports as may be necessary topreserve stability of existing structures on the site oradjoining, that may be endangered or affected by theWorks.

- Do not remove until new work is strong enough tosupport existing structure.

- Prevent overstressing of completed work when removingsupports.

Standard: Comply with BS 5975

RISK ASSESSMENTAs the designer of the structure for this project an assessment of the construction risks has been carried out and it is considered that a competent builder would be able toconstruct this project using appropriate temporary works. Attention is drawn to the table of element sizes which provide the approximate weight of the steel elements.Any particular risks are noted in the appropriate location in the drawings with the following symbol:

TIME AND COST RISKS

Where indicated on drawings open up structure to confirm assumptions at the start of the project.

CONSTRUCTION RISKS (CDM REGULATIONS) ACTION

Check details at the earliest opportunity to ensure sections fit before ordering steel.

Check foundations depths at the earliest opportunity.

Check availability of scheduled members at earliest opportunity.

OTHER RISKS ACTION

Compressive Strength of Masonry too low Check existing masonry meet requirements where noted on drawings (eg. concrete blocksand not aircrete blocks (breeze blocks, celcon))

Poor construction A competent builder should be employed.

Timber bracing not installed to roof Refer to timber specifications for bracing requirements.

External steel corrosion Refer to steel specifications for proprietary steel protection.

Holes reducing strength in structural members Refer to material specifications prior to any cuts and holes into members.

Cantilever overturning

Restraint straps not installed

Check if any construction sequence or specific connections are mentioned in drawings priorto loading any cantilever members.

Refer to timber and masonry specifications.

Check for the presence of any sewers before commencing any ground works.

Pitching plates Ensure correct number and specification of bolts are installed.

!

Use of cold rolled steel instead of hot rolledsteel

Ensure correct grade (S355 and not S235) of steel is ordered and received from the steelfabricators

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

General Specifications & Risk Assessment

AS SHOWN: A4

P1 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Page 2: SECTION T2 - planning.org.uk

BEAM & BLOCK (MAXIMUM SPAN (mm))

150 Deep @ 510 mm c/c

150 Deep @ 285 mm c/c

225 Deep @ 510 mm c/c

225 Deep @ 285 mm c/c

3200

4200

4450

5800

STRUCTURAL SPECIFICATION - PRECAST BEAM AND BLOCKDESIGN· By manufacturer.· Beams:

- Manufacturer: No specific requirements.- Product reference: None.- Type: Prestressed inverted 'T' beams.- Depth: As stated on the drawings or determined by

manufacturer.· Infill blocks:

- Type: As required by the manufacturer of the beams.- Work size: 440 x 215 x 100 mm.- Density: As required by the manufacturer of the beams.

· Infilling at beam bearings:- Installation: Infill gaps in walling below built in standard

flooring blocks.· Concrete infill: Designated concrete to BS 8500-2.

- Designation: RC25/30.- Aggregate size (maximum): 20 mm.

· Grouting:- Mix: 1:6 cement:sharp sand (1 :4 if soft sand or in wet

weather).- Execution: Brush floor clean, wet thoroughly and brush in

grout to fill all joints and surface irregularities.· In situ concrete topping (unless specified elsewhere): 75 mm thick

Designated concrete RC25/30 with centrally placed A142 mesh.Finish to suit floor finishes.

LATERAL RESTRAINT STRAPS· Preparation: Floors/ roof decks must tightly abut walls.· Type: 30 x 5 mm galvanised steel.

- Length: To extend minimum 800 mm from inside face ofwall.

- Form: Both ends cranked 100 mm.· Position: 1.25 m maximum centres to abutting external cavity

walls.· Build in:

- External cavity walls: One cranked end in tight contact withcavity face of wall inner leaf, the other cranked end groutedinto floor/ roof deck joint.

Ground level

Fill cavity withconcrete

Top of foundations

Optional trench blocks

Foundations

Floor beams

Floor blocks

Screed to meet architectsrequirements otherwise min. 75mm

Masonry walls

Install concrete blocks below beam &block level (not aircrete)

SECTION T2SCALE 1:20

· Timber walls may also be used.· Insulation not shown, refer to architects drawings.· Floor level to suit architects requirements.

Sections Details

Min.

150

mm

Ground level

Fill cavity with concrete

Top of foundations

Foundations

Beam & block floor

Screed to meet architectsrequirements otherwise min. 75mm

Masonry walls

Min.

150

mm

SECTION T3SCALE 1:20

Backfill with suitable material

Optional trench blocks

Install concrete blocks below beam &block level (not aircrete)

Backfill with suitable material

Ground level

Fill cavity with concrete

Top of foundations

Foundations

Beam & block floor

Screed to meet architectsrequirements otherwise min. 75mm

Masonry walls

Min.

150

mm

SECTION T4SCALE 1:20

Install concrete blocks below beam &block level (not aircrete)

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Foundations SpecificationsBeam & Block

AS SHOWN: A4

P3 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Page 3: SECTION T2 - planning.org.uk

STRUCTURAL SPECIFICATION - MASONRYOUTER LEAF OF CAVITY CONSTRUCTION· In addition to the architectural specification:

- Bricks: to BS EN 771-1- Mean compressive strength: No

requirements- Density: No requirements

INNER LEAF OF CAVITY & INTERNAL LOADBEARING WALL CONSTRUCTION· In addition to the architectural specification:

- Blocks: to BS EN 771-3- Mean compressive strength: 7.3 N/mm2

- Density: No requirementsENGINEERING BRICKWORK· Bricks: to BS EN 771-1

- Type HD- Mean compressive strength:

Class A ≥ 125 N/mm2

Class B ≥ 75 N/mm2

- Water adsorption:Class A ≤ 4.5% by massClass B ≤ 7.5% by mass

- Freeze thaw category: F2- Active soluble salts content category: S2

MORTAR· Mortar: to BS EN 998-2· Strength class, except as noted below: M4(Equivalent to mortar group (iii) to BS 4721 -now withdrawn)

· Strength class for engineering brickwork: M12(Equivalent to mortar group (i) to BS 4721 - nowwithdrawn)

SAND FOR SITE MADE CEMENT GAUGEDMASONRY MORTARS· Standard: To BS EN 13139.· Grading: 0/2 (FP or MP).

- Fines content where the proportion of sandis specified as a range (e.g. 1:1: 5-6):

- Lower proportion of sand: Use category 3fines.

- Higher proportion of sand: Use category 2fines.

· Sand for facework mortar: Maintain consistentcolour and texture. Obtain from one source.

SAND FOR LIME: SAND MASONRYMORTARS· Type: Sharp, well graded.

- Quality, sampling and testing: To BS EN13139.

- Grading/ Source: As specified elsewhere.READY-MIXED LIME:SAND FOR CEMENTGAUGED MASONRY MORTARS· Standard: To BS EN 998-2.· Lime: Nonhydraulic to BS EN 459-1.

- Type: CL 90S.CEMENTS FOR MORTARS· Cement To BS EN 197-1 and CE marked.

- Types: CEMI, CEMII/A-LL, CEM II/B-S orCEM II/B-V.

- Strength class: 32.5, 42.5 or 52.5.· Masonry cement To BS EN 413-1 and CEmarked.

- Class: MC 12.5.ADMIXTURES FOR SITE MADE MORTARS· Air entraining (plasticizing) admixtures: To BSEN 934-3 and compatible with other mortarconstituents.

· Other admixtures: Submit proposals.· Prohibited admixtures: Calcium chloride,ethylene glycol and any admixture containingcalcium chloride.

MAKING MORTARS GENERALLY· Batching: By volume. Use clean and accurategauge boxes or buckets.

· Mix proportions: Based on dry sand. Allow forbulking of damp sand.

· Mixing: Mix materials thoroughly to uniformconsistency, free from lumps.

- Mortars containing air entraining admixtures:Mix mechanically. Do not overmix.

· Contamination: Prevent intermixing with othermaterials.

MAKING HYDRAULIC LIME: SANDMORTARS· Mixing hydrated hydraulic lime:sand: Follow thelime manufacturer's recommendations for eachstage of the mix.

- Water quantity: Only sufficient to produce aworkable mix.

WORKMANSHIP

· Mortar joints: Fill all vertical joints. Lay brickssolid and cellular on a full bed.

· Lift height (maximum) for walling using cementgauged or hydraulic lime mortar: 1.2 m aboveany part of work at any time.

· Daily lift height (maximum) for walling usingcement gauged or hydraulic lime mortar: 1.5 mfor any one leaf.

ALTERATIONS/EXTENSIONS· Coursing: line up with existing work· Block bonding new walls to existing: unlessagrees otherwise cut pocket requirements asfollows:

- Width: full thickness of new wall- Depth (minimum): 100 mm- Vertical spacing: as follows:

Brick to brick: 4 courses high at 8 coursecentres.Block to block: Every other course

- Pocket joints: fully filled with mortarCAVITIES BELOW GROUND LEVELUnless specified elsewhere:·Concrete generally: To BS EN 206-1 and BS8500-2

- Designated concrete: GEN1 or standard mix ST2 with high workability.

- Extent: Maintain 75 mm between top of filland external ground level and a minimum of 225 mm between top of filland ground level DPC.

· Cleanliness: Keep cavity faces, ties and DPCsfree from mortar and debris.

· Perpend joint weep holes- Form: Open clear perpend joint.- Locations: through outer leaf, immediately

above the base of the cavity, at cavity rays,stepped DPCs and over openings. 75 mmabove top of cavity fill at base of cavity

- Provision: At not greater than 1000 mmcentres and not less than two over openings

CAVITY WALL TIESUnless specified elsewhere:· Standard: To DD 140 or BS EN 845-1· Type: to comply with Table 5 of ApprovedDocument A

· Embedment: As recommended by manufacturer· Spacing (minimum, subject to requirements for

support of insulation):- Horizontal spacing: 750 mm- Vertical spacing: 450 mm- Around openings: 300 mm vertically within

225 mm of the opening.LATERAL RESTRAINT STRAPSUnless specified elsewhere:·Type: To meet requirements of ApprovedDocument A

·Size: Not less than 30 x 5 mm cross section, 150mm cranked end and length to meetrequirements of Approved Document A.

·Fixing: To top of joists/ rafters/ ties at not morethan 2 m centres.

- Ensure that cranked end is in tight contactwith cavity face of wall inner leaf and is notpointing upwards.

·Straps spanning joists/ rafters/ ties runningparallel to wall: Fix noggings and packs tightlybeneath straps.

- Size of noggings and packs: Not less thanthree quarters of joists/rafter/tie depth andnot less than 38 mm thick.

- Notching: Notch joists so that straps fit flushwith surface. Do not notch rafters/ ties.

·Fasteners: Not less than four 50 mm x 8 gaugesherardized countersunk screws per strap,evenly spread.

PRECAST CONCRETE LINTELS· Standard: To BS EN 845-2· Size and type: As specified on drawing.· Placement: Bed on mortar used for adjacentwork

- Bearing length (minimum): 100 mmPADSTONES·Type: Precast concrete

- Compressive strength: Min. C30- Size: As specified on drawing.- Placement: Bed on mortar used for

adjacent work.·Type: Cast in-situ

- Concrete infill: Designated concrete toBS 8500-2.

- Designation: RC25/30- Aggregate size (maximum): 20 mm.

CATNIC LINTELS (MAXIMUM SPAN (mm))

CG

CH

CX

Verified: Catnic Product Selector

Ref. Ground Floorlevel opening

-

1000

1800

First Floorlevel opening

1200

2400

3800

NAYLOR CONCRETE LINTELS(MAXIMUM SPAN (mm))

Verified: Naylor Product Selector

Ref. Ground Floorlevel opening

850

1200

1200

First Floorlevel opening

1200

1800

1800

100 x 140ER2

100 x 215ER7

100 x 145R6

Note: In single-storey buildings firstfloor level opening lintels may beused at ground floor level.

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Masonry Specifications

AS SHOWN: A4

P6 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Page 4: SECTION T2 - planning.org.uk

COMMON FLOOR JOISTS (MAXIMUM SPAN (mm))C24 TIMBERS (gK=0.6 kN/m2 qK=2 kN/m2)

47 x 170

47 x 195

47 x 220 4000

3500

47 x 145

3100

2600

COMMON FLAT ROOF JOISTS (MAX SPAN (mm))C24 TIMBERS (gK=1.00 kN/m2 qK=0.75 kN/m2)

47 x 170

47 x 195

47 x 220 4400

3900

47 x 145

3400

2900

PROVIDE THE FOLLOWING TIMBER JOISTS SIZEUNLESS NOTED OTHERWISE

COMMON RAFTERS (MAX SPAN (mm))C24 TIMBERS (gK=1.20 kN/m2 qK=0.75 kN/m2)

47 x 150

47 x 195 3700

47 x 100

2900

1900

4500

4000

3500

3000

5000

4400

3800

3300

4300

3300

2200

AT 400 mm c/c AT 600 mm c/c

AT 400 mm c/c AT 600 mm c/c

AT 400 mm c/c AT 600 mm c/c

STRUCTURAL SPECIFICATION - TIMBERSTRUCTURAL SOFTWOOD· Grading standard: To BS 4978, BS EN 14081-1,or other national equivalent and so marked.

· Strength class to BS EN 338: As shown on thedrawings

· Treatment: Organic solvent impregnation andWood Protection Association Commodityspecification C8, Service life: 40 years

- Timing: After cutting and machining timber,and before assembling components.

SELECTION AND USE OF TIMBER· Timber members damaged, crushed or splitbeyond the limits permitted by their grading: Donot use.

STRUTTING/NOGGINGS· Timber thickness: Minimum 38 mm.· Timber depth: Minimum 3/4 of the joist depth.· Alternative: Herringbone strutting.· Provide: mid-span for joists 2.5 to 4.5 m longand 1/3 span points for joists over 4.5 m long.

NOTCHES, HOLES AND JOINTS IN TIMBER· Notches and holes: Position in relation to knotsor other defects such that the strength ofmembers will not be reduced.

· Scarf joints, finger joints and splice plates: Donot use without approval.

PROCESSING TREATED TIMBER· Cutting and machining: Carry out as much aspossible before treatment.

· Extensively processed timber: Retreat timbersawn lengthways, thicknessed, planed,ploughed, etc.

· Surfaces exposed by minor cutting/ drilling:Treat with two flood coats of a solutionrecommended by main treatment solutionmanufacturer.

MOISTURE CONTENT· Moisture content of wood and wood basedproducts at time of installation: Not more than:

- Covered in generally unheated spaces: 24%.- Covered in generally heated spaces: 20%.- Internal in continuously heated spaces: 20%.

BOLT ASSEMBLIES· Designation: Hexagonal head bolts to BS ENISO 4018, property class 4.6

· Size: As shown on drawings· Coating applied by manufacturer: None· Nuts and washers: Material grade and finish tosuit bolts Washer dimensions: Diameter/ sidelength of washers in contact with timber faces tobe minimum 3 times bolt diameter, with athickness not less than 0.25 times bolt diameter.

BOLTED JOINTS· Bolt spacings (minimum): To EN 1995 - 1 - 1,table 6.17, unless specified elsewhere.

· Holes for bolts: Located accurately and drilledto diameters as close as practical to the nominalbolt diameter and not more than 2 mm larger.

· Washers: Placed under bolt heads and nuts thatwould otherwise bear directly on timber. Usespring washers in locations which will be hiddenor inaccessible.

· Bolt tightening: So that washers just bite thesurface of the timber. Ensure that at least onecomplete thread protrudes from the nut.

- Checking: At agreed regular intervals.Tighten as necessary.

FRAMING ANCHORS· Manufacturer: Simpson Strong-Tie, WinchesterRoad, Cardinal Point, Tamworth, Staffordshire,B78 3HG

· Product reference: As shown on the drawings· Fasteners (unless specified elsewhere):Galvanized or sherardized square twist nails.

· Size: Not less than size recommended byanchor manufacturer.

· Fixing: Secure using not less than the numberof nails recommended by anchor manufacturer.

ADDITIONAL SUPPORTS· Provision: Position and fix additional studs,noggings and/or battens to support edges ofsheet materials, and wall/floor/ceiling mountedappliances, fixtures, etc. shown on drawings.

· Material properties: Timber to be of adequatesize and have the same treatment as adjacenttimber supports.

JOISTS GENERALLY· Centres: Equal, and not exceeding designedspacing.

· Bowed joists: Installed with positive camber.· End joists: Positioned about 50 mm frommasonry walls.

JOISTS ON HANGERS

· Hangers: Bedded directly on and hard againstsupporting construction. Do not use packs or bedon mortar.

· Joists: Cut to leave not more than 6 mm gap ateach end. Rebated to lie flush with underside ofhangers.

· Fixing to hangers: A nail in every hole.JOIST HANGERSUnless specified elsewhere:· Selection: Joist hangers to be installed inaccordance with manufacturer's instructions.

· Size: To suit joist.· Fasteners (unless specified elsewhere):Galvanized or sherardized square twist nails.

· Size: Not less than size recommended byanchor manufacturer.

· Fixing: Secure using not less than the numberof nails recommended by anchor manufacturer.

TRIMMING OPENINGSUnless specified elsewhere:· Trimmers and trimming joists: Use doubled-up

joists for all trimmers and trimming joists.TRUSS CLIPSUnless specified elsewhere:· Selection: Truss clips to be installed inaccordance with manufacturer's instructions.

· Size: To suit truss.· Fasteners (unless specified elsewhere):Galvanized or sherardized square twist nails.

· Size: Not less than size recommended byanchor manufacturer.

· Fixing: Secure using not less than the numberof nails recommended by anchor manufacturer.

PERMANENT BRACING OF TRUSSEDRAFTERSUnless specified elsewhere:· Bracing and binders: Strength class C16

- Size: 100 x 25 mm- Method of fixing: To every rafter, strut or tie

with not less than two fasteners.- Fasteners: 75 x 3.35 mm galvanised round

wire nails· Lap joints: Extended over and nailed to at leasttwo truss members.

VERTICAL RESTRAINT STRAPSUnless specified elsewhere:

·Type: To meet requirements of ApprovedDocument A

·Size: - Cross section: Not less than 75 mm2

- Length: At least 1 m·Centres: Not more than 2 m·Fixing:

- To meet requirements of ApprovedDocument A

- To timber members with not less than two30 x 3.5 mm galvanised square twist nails

- To masonry with not less than four 4.8 x 70mm masonry screws evenly spaced, with atleast one screw located within 150 mm ofthe bottom end of each strap.

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Timber Specifications

AS SHOWN: A4

P7 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Page 5: SECTION T2 - planning.org.uk

STRUCTURAL SPECIFICATION - STEELSTEEL SECTIONS AND PLATE· Section properties and dimensions: To BS

4-1, BS EN 10055, BS EN 10056 or BS EN10210, as appropriate. -Steel: To BS EN10025-2 or BS EN 10210-1, asappropriate.

· Grade (unless specified elsewhere):- Sections: S355J0- Plate: S275J0

· Surface condition: Free from heavypitting and rust, burrs, sharp edges andflame cutting dross.

· Cuts and holes: Accurate and neat.· Welding: Metal arc method to BS EN

1011-2.- Welded joints: Fully fused, with

mechanical properties not less thanthose of the parent metal.

- Site welding: Obtain approval.· Source: Obtain steel from a source

accredited to a national or internationallyaccepted quality standard.

BOLT ASSEMBLIES· Standard: To BS EN ISO 4014 & 4017· Designation: Class 8.8· Size: As shown on drawings· Type: Hexagonal head bolts· Nuts and washers: Material grade and

finish to suit boltsSHOP PRIMING· Preparation: To BS EN ISO 12944-4.

Remove fins, burrs, sharp edges andweld spatter, clean out crevices

- Surface finish: Manually cleaned to BSEN ISO 8501-1, grade Sa 2.

- Prepared surfaces: Keep in a dryatmosphere and apply first coatingwithout delay.

· Priming:- Primer: One coat zinc phosphate

modified alkyd, minimum dry filmthickness 40 micrometres.

- Application: To BS EN ISO 2944-7.

EXTERNAL STEEL· Use: Apply to steel members in external

locations· Preparation:

- To BS EN ISO 12944-4. Remove fins,burrs, sharp edges and weld spatter,clean out crevices

- Surface finish: Manually cleaned to BSEN ISO 8501-1, grade Sa 2½ .

- Prepared surfaces: Keep in a dryatmosphere and apply first coatingwithout delay.

· Priming:- Primer: Factory applied high build zinc

phosphate epoxy minimum dry filmthickness 120 micrometres.

- Application: To BS EN ISO 12944-7.· Coating

- High solid aliphatic polyurethanefinish minimum dry film thickness 60micrometres.

- Application: To BS EN ISO 12944-7.STEEL BELOW GROUND LEVEL· Use: For all steelwork below DPC.· Preparation:

- As per External Steel Specification.· Priming:

- As per External Steel Specification.· Coating

- As per External Steel Specification.or

- Surround steel with GEN 1 concretewith a minimum cover of 75 mm (seeSection T5).

INSTALLATION· Accuracy: Members positioned true to

line and level using, if necessary, steelpacks of sufficient area to allow fulltransfer of loads to bearing surfaces.

· Fixing: Use washers under bolt headsand nuts.

· Tapered washers: Provide under boltheads and nuts bearing on slopingsurfaces. Match taper to slope angle andalign correctly.

DRY PACKING· Spaces beneath beam and existing

masonry above: Completely filled with1:3 - cement: sand mortar withconbex 100 non-shrink additive, mixed toan earth-damp consistency and rammedin solid.

· Cement Portland cement BS EN 197-1-CEM I 42.5 or 52.5

· Sand: To BS EN 12620, grade 0/4 or 0/2(MP).

HOLES FOR SERVICES THROUGHSTEEL BEAMS· See Section T7COLUMN BASES· Levels: Adjust using steel shims or

folding wedges no larger than necessary,positioned symmetrically aroundperimeter of base plate. Do not use asingle central pack.

· Accuracy of erection: Check, and correcterrors before filling and bedding beneathbases and carrying out other adjacentwork.

MORTAR FILLING / BEDDING OFCOLUMN BASES· Bolt pockets: Completely filled with neat

cement slurry.· Spaces beneath base plates: Completely

filled with 1:1 cement and mortar, justfluid enough to pour, tamped well asfilling proceeds. Provide temporaryshuttering as necessary.

· Cement Portland cement BS EN 197-1-CEM I 42.5 or 52.5

Sand: To BS EN 12620, grade 0/4 or 0/2(MP).CE MarkingProduct Requirements· All steel products manufactured to

harmonised BS EN standards shall besupplied complete with CE Marking asfollows:

- Steel sections to BS EN 10025-1.- Hot finished hollow sections to BS EN

10210-1.- Cold formed hollow sections to BS EN

10219-1.- Fabricated sections to BS EN 1090-1.

· All fastener assemblies manufactured toharmonised BS EN standards shall besupplied with CE Markings as follows:

- Ordinary (Non-Preloaded) assembliesto BS EN 15048-1.

- Preloaded assemblies to BS EN14399-1.

· The CE Marking shall appear oninspection documents and theinformation on the inspection documentsshall be legible and written in English.

Execution Class· Unless stated otherwise all steel and

aluminium products used should have anexecution class of EXC 2.

Min. 75 mm

Min. 75 mm

Min. 75 mmMin. 75 mm

Steel beam(size varies)

Concrete

SECTION T5PROTECTION OF STEEL BELOW GROUND LEVEL

SCALE 1:20

50 mm or 1/3 of depth ofbeam a whichever is larger

Steel beamChamfer beam as required,provide steel plate to form

new flange, thickness tomatch flange of beam

SECTION T6SCALE 1:20

Padstone

Min. 500 mm Min. 3∅

SECTION T7SCALE 1:20

Steel beam(size varies)

Hole to be circular and:· less than 100 ∅· less than 13 of beam

depth (e.g. 50 mm for150 mm deep beam)

· placed at centre of beamdepth

Where applicable

Where applicable

Where applicable

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Steel Specifications

AS SHOWN: A4

P8 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

THIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Page 6: SECTION T2 - planning.org.uk

Piled retainingwalls by pilingspecialist

P1

P3 P4

P2

P5

P8

P6

P9P10

P13

P12

P11

P14

Beam& block

Retaining wall adjacent toroad to allow for highwayloading

P7

153 Athelstan Road

159 Pear Tree Avenue

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Pile loadsPoint Ref. SWL (kN)

P1 100P2 100P3 125P4 150P5 150P6 175P7 150P8 150P9 125P10 50P11 100P12 125P13 50P14 50

Each pile to be designed for aunfactored horizontal load of 5 kN.

GROUND FLOOR PLAN AT FORMATION LEVELSCALE 1:50

General Arrangement - Formation level

AS SHOWN: A1

S10 A

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTDIT SHALL ONLY BE USED FOR THE PROJECT STATED

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

For Construction OBBJ-

Notes:1. All dimensions in millimetres.2. Do not scale for construction purposes.3. Refer to drawing P1 for drawing notes.4. Refer to drawing 2907-R10 for

reinforcement details.5. Refer to drawing 2907-S101 for typical

sections and details.6. Piles to be designed to suit the loads

shown in the Pile Loads table.

Scheme revised OBIG18.08.2021A

Page 7: SECTION T2 - planning.org.uk

4H16-03 T14H16-03 B1

350

4H16-07 T14H16-07 B1

350

4H16-03 T14H16-03 B1

350

4H16-02 T14H16-02 B1

350

4H16

-01

T14H

16-0

1 B1

350

4H16

-04

T14H

16-0

4 B1

350

4H16-05 T14H16-05 B1

350

4H16-06 T14H16-06 B1

350

4H16-08 T14H16-08 B1

350

4H16

-09

T14H

16-0

9 B1

350

4H16

-10

T14H

16-1

0 B1

350

4H16-11 T14H16-11 B1

350

4H16

-12

T14H

16-1

2 B1

350

4H16

-12

T14H

16-1

2 B1

350

4H12-14 T14H12-14 B1

350

4H12-13 T14H12-13 B1

350

4H12-14 T14H12-14 B1

350

4H12-14 T14H12-14 B1

350

4H12-14 T14H12-14 B1

350

4H12-14 T14H12-14 B1

350

4H16-14 T14H16-14 B1

350

4H12-14 T14H12-14 B1

350

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

H10-16 @ 300 c/c

GROUND BEAM TYPICALSECTIONSCALE 1:25

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTDIT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBIG18.08.2021-

Reinforcement Details

1:50 @ A3

R10 -

Notes:1. All dimensions in millimetres.2. Do not scale for construction purposes.3. Refer to drawing S10 for foundation

general arrangement.4. Minimum cover to bars to be 50 mm.5. Concrete to be designated mix RC25/30.6. Refer to Bar Bending Schedule 2907-R10

Sheet 01 for reinforcement details.7. Min. laps to be:-

H12 - 500 mmH16 - 650 mm

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

PROVIDE 2 no. BAR MARK16 SHEAR LINKS AT 300CENTRES THROUGHOUT

ALL GROUNDBEAMS TOBE 450 mm WIDE BY 450mm DEEP

Page 8: SECTION T2 - planning.org.uk

Drg No: 2907 - R10

Sheet No: 01

Rev: -

Status C

Member Bar Mark Type and

size

No. of

mbrs

No. of

bars in

each

Total

no.

Length of

each bar†

mm

Shape

code

A*

mm

B*

mm

C*

mm

D*

mm

E/R*

mm

Rev Letter

01 H16 1 8 8 2400 00 2400

02 H16 1 8 8 2375 00 2375

03 H16 2 8 16 5900 00 5900

04 H16 1 8 8 3325 00 3325

05 H16 1 8 8 6150 00 6150

06 H16 1 8 8 2925 00 2925

07 H16 1 8 8 1300 00 1300

08 H16 1 8 8 2775 00 2775

09 H16 1 8 8 1800 00 1800

10 H16 1 8 8 2525 00 2525

11 H16 1 8 8 2350 23 1050 300 1050

12 H16 2 8 16 2300 26 700 890 700 725

13 H12 1 8 8 1500 11 900 600

14 H12 6 8 48 1800 11 900 900

15 H10 2 121 242 1375 51 350 250

Project Number: 2907Project Name: Land adjacent to 153 Athelstan Road

By: IG

Date: 12.04.2021

This schedule conforms to BS 8666:2005

* Specified in multiples of 5 mm.  † Specified in multiples of 25 mm

Status: P Preliminary T Tender C Construction

Page 9: SECTION T2 - planning.org.uk

MEMBER SCHEDULE (See P6 for lintel sizes & P7 for joist sizes)RefNo. Section Size Weight

TB40 2 No. 47 x 150 C24 TimbersC40 100 x 100 C24 TimberTB30 2 No. 47 x 150 C24 TimbersCJ30 47 x 100 C24 TimberB30 UC 203 x 203 x 46 299 KgTB20 2 No. 47 x 195 C24 TimbersTB21 2 No. 47 x 195 C24 TimbersL20 Catnic CN100

Floorjoists

TB20

TB21

TB21

Floorjoists

Floorjoists

L20

Bay frame bymanufacturer

T204S201

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTDIT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

General Arrangement - Ground floor level

AS SHOWN: A3

S20 -

GROUND FLOOR PLAN AT CEILING LEVELSCALE 1:50

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawings P6 to P8 for material

specifications and sizes for lintels and joists.4. All products should be installed as per

manufacturer specifications.

ALL PADSTONES TO BE 440 X 100 X 215 mmDEEP UNO

Scheme revised OBIG18.08.2021A

Page 10: SECTION T2 - planning.org.uk

CJ30ceilingjoists

CJ30ceilingjoists

CJ30ceilingjoists

CJ30 ceilingjoists

TB30

TB30

B30

B30

C40 above

C40 above

C40 aboveC40 above

Bay frame bymanufacturer

3AS301

3AS301

T200S401

T200S401

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

MEMBER SCHEDULE (See P6 for lintel sizes & P7 for joist sizes)RefNo. Section Size Weight

TB40 2 No. 47 x 150 C24 TimbersC40 100 x 100 C24 TimberTB30 2 No. 47 x 150 C24 TimbersCJ30 47 x 100 C24 TimberB30 UC 203 x 203 x 46 299 KgTB20 2 No. 47 x 195 C24 TimbersTB21 2 No. 47 x 195 C24 TimbersL20 Catnic CN100

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTDIT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

General Arrangement - First floor level

AS SHOWN: A3

S30 -

FIRST FLOOR PLAN AT CEILING LEVELSCALE 1:50

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawings P6 to P8 for material

specifications and sizes for lintels and joists.4. All products should be installed as per

manufacturer specifications.

ALL PADSTONES TO BE 440 X 100 X 215 mmDEEP UNO

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Scheme revised OBIG18.08.2021A

Page 11: SECTION T2 - planning.org.uk

Flatroofjoists

TB40

TB40

TB40TB40

C40below

C40below

C40below

C40below

Rafters belowsupported on TB30

Build off layboards

Build off layboards

Rafters belowsupported on TB30

4AS401

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

MEMBER SCHEDULE (See P6 for lintel sizes & P7 for joist sizes)RefNo. Section Size Weight

TB40 2 No. 47 x 150 C24 TimbersC40 100 x 100 C24 TimberTB30 2 No. 47 x 150 C24 TimbersCJ30 47 x 100 C24 TimberB30 UC 203 x 203 x 46 299 KgTB20 2 No. 47 x 195 C24 TimbersTB21 2 No. 47 x 195 C24 TimbersL20 Catnic CN100

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTDIT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

General Arrangement - Roof level

AS SHOWN: A3

S40 -

ROOF PLANSCALE 1:50

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawings P6 to P8 for material

specifications and sizes for lintels and joists.4. All products should be installed as per

manufacturer specifications.

ALL PADSTONES TO BE 440 X 100 X 215 mmDEEP UNO

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Scheme revised OBIG18.08.2021A

Page 12: SECTION T2 - planning.org.uk

EXTERNAL GROUND BEAM TYPICALSECTIONSCALE 1:25

450

450

RC groundbeam

Working area to bebackfilled withuncompacted material

250

50

250 mmventilated void

Insulation and finishes toArchitect's details

Beam and block floor

DPC and ventilation toArchitect's details

Cavity filled with GEN1 concrete to within

225 mm of DPC

Maximum 2 coursesof trench blocks

LC

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

L

250

Insulation and finishes toArchitect's specifications

Beam and block floor

250 mmventilated void

C

INTERNAL GROUND BEAM TYPICALSECTIONSCALE 1:25

450

450

RC groundbeam

Working area to bebackfilled withuncompacted material

Design Details - Formation level

AS SHOWN: A4

S101 A

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawing P2 for foundation

requirements.4. Refer to drawing P3 for details of beam &

block floors.5. All welds to be Min. 6 mm fillet welds.6. All bolts to be Min. Class 8.8.

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Scheme revised OBIG18.08.2021A

Page 13: SECTION T2 - planning.org.uk

Section Details· Provide proprietary fixings between timber members.· Joists may be present one or both side(s) of beam.· Bolts in timber beam to be offset vertical by 25 mm from centre

line and staggered.

Timber beam (size varies),timbers to be bolted together withm12 bolts at 450 mm c/c

Joists

Proprietary joist hangers (installedto manufacturers specifications)

Joists

SECTION T204SCALE 1:10

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Design Details - Ground floor level

AS SHOWN: A4

S201 A

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawing P2 for foundation

requirements.4. Refer to drawing P3 for details of beam &

block floors.5. All welds to be Min. 6 mm fillet welds.6. All bolts to be Min. Class 8.8.

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Scheme revised OBIG18.08.2021A

Page 14: SECTION T2 - planning.org.uk

B30

C40

Strong-Tie ABR105brackets fixed to B30with tek-screws

SECTION 3ASCALE 1:10

JoistsJoists

Proprietary joist hangers (installedto manufacturers specifications)

Timber blocking bolted toweb of beam on both sides

Section Details

· Straps to be placed at a maximum of 1.2 metres.· Attach strap to timbers with 4 No. steel screws or 4 No. 4 mm x 75mm round nails and 2 into each joist.

Provide simpson common twiststrapping (L10T10) between all

rafters and minimum 3 joists

Position noggins betweenjoists at all straps Joists

Rafters

SECTION T200SCALE 1:10

12.04.2021

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Design Details - First floor level

AS SHOWN: A4

S301 A

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBBJ-

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawing P2 for foundation

requirements.4. Refer to drawing P3 for details of beam &

block floors.5. All welds to be Min. 6 mm fillet welds.6. All bolts to be Min. Class 8.8.

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd

Scheme revised OBIG18.08.2021A

Page 15: SECTION T2 - planning.org.uk

SECTION 4ASCALE 1:10

C40

Strong-Tie ABR105brackets or equivalent

TB40

2907

Land adjacent to 153 Athelstan Road

IG 12.04.2021

2907 -

Design Details - Roof level

AS SHOWN: A4

S401 -

Project No.

Dwg No.

Project Name

Title

Drawn

Rev.

Date Scale

No. Revision Date By CkdTHIS DRAWING IS COPYRIGHT OF MODULUS SE LTD IT SHALL ONLY BE USED FOR THE PROJECT STATED

For Construction OBIG18.08.2021-

Notes:1. Do not scale for construction purposes.2. Refer to drawing P1 for drawing notes.3. Refer to drawing P2 for foundation

requirements.4. Refer to drawing P3 for details of beam &

block floors.5. All welds to be Min. 6 mm fillet welds.6. All bolts to be Min. Class 8.8.

Offices· Basingstoke T: 01256 768 588· London (Egham) T: 020 7112 8840W: www.modulus.ltd