section 27 41 30 audio-visual systems part 1 - general · 8/4/2017  · the av contractor shall be...

24
CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017 27 41 30 - 1 SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS All requirements under Instructions to Bidders, General Conditions, Supplementary Conditions, Special Conditions, Division One, Technical Specifications, Referenced Documents or Practices and any Addenda of these Specifications shall be a part of this section. Each Contractor is responsible to be thoroughly familiar with all its contents as to requirements which affect this Division or Section. Coordinate all items with Owner to ensure that all items are furnished in accordance with Owner standards. 1.2 RELATED DOCUMENTS Refer to the following design drawings: 1. AV-series drawings 1.3 REFERENCES National Fire Protection Association (N.F.P.A.) American National Safety Institute (A.N.S.I.) National Electrical Code (N.E.C.) Underwriters Laboratories (U.L.) Electronics Industries Association (E.I.A.) National Cable Television Association (N.C.T.A.) Society of Motion Picture and Television Engineers (S.M.P.T.E.) International Telecommunications Union (I.T.U.-T.) SMPTE 292M EIA RS-170A 1.4 RESPONSIBILITY AND RELATED WORK The systems described in this section will be called the "AV Systems" and the installer will be named "The AV Contractor." The AV Contractor will provide all labor, materials, equipment, necessary tools, test equipment, hoisting, transportation, supervision and coordination necessary to complete the installation of the "AV Systems" as described in these specifications and illustrated on the Project drawings. The Contract Documents are intended to include or imply all items required for the proper execution and completion of the work. Any item of work required by the Specifications or other portion of the Contract Documents but not shown on the drawings, or shown on the drawings but not specifically required in the Specification shall be identified prior to Bid Submittal.

Upload: others

Post on 27-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 1

SECTION 27 41 30 – AUDIO-VISUAL SYSTEMS

PART 1 - GENERAL

1.1 GENERAL REQUIREMENTS

All requirements under Instructions to Bidders, General Conditions, Supplementary Conditions, Special Conditions, Division One, Technical Specifications, Referenced Documents or Practices and any Addenda of these Specifications shall be a part of this section. Each Contractor is responsible to be thoroughly familiar with all its contents as to requirements which affect this Division or Section. Coordinate all items with Owner to ensure that all items are furnished in accordance with Owner standards.

1.2 RELATED DOCUMENTS

Refer to the following design drawings:

1. AV-series drawings

1.3 REFERENCES

National Fire Protection Association (N.F.P.A.)

American National Safety Institute (A.N.S.I.)

National Electrical Code (N.E.C.)

Underwriters Laboratories (U.L.)

Electronics Industries Association (E.I.A.)

National Cable Television Association (N.C.T.A.)

Society of Motion Picture and Television Engineers (S.M.P.T.E.)

International Telecommunications Union (I.T.U.-T.)

SMPTE 292M

EIA RS-170A

1.4 RESPONSIBILITY AND RELATED WORK

The systems described in this section will be called the "AV Systems" and the installer will be named "The AV Contractor." The AV Contractor will provide all labor, materials, equipment, necessary tools, test equipment, hoisting, transportation, supervision and coordination necessary to complete the installation of the "AV Systems" as described in these specifications and illustrated on the Project drawings.

The Contract Documents are intended to include or imply all items required for the proper execution and completion of the work. Any item of work required by the Specifications or other portion of the Contract Documents but not shown on the drawings, or shown on the drawings but not specifically required in the Specification shall be identified prior to Bid Submittal.

Page 2: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 2

The AV Systems consist of the materials, equipment and systems described in this specification, related drawing details, and any schedules that are part of the construction document set. This Contract is for equipment, material, installation and training. The work of this section includes a complete and operational turn-key system.

The AV Contractor shall provide minor accessories, such as connectors, adapters, matching devices and equipment items needed for a complete system, even if not specifically mentioned herein or on the drawings, without claim for additional payment.

System features or devices which are mentioned in one part of the Contract Documents may not be shown in the other. In case of conflict between the written specifications and the drawings, AV Contractor must seek clarification from the Consultant. In the event that the AV Contractor fails to obtain such clarification, the interpretation of the Consultant will prevail.

Notwithstanding any detailed information in the Contract Documents, it is the responsibility of the AV Contractor to supply systems in full working order. Notify Consultant of any discrepancies in part numbers or quantities prior to bid submittal. Failing to provide such notification, the AV Contractor shall supply items and quantities according to the intent of the Specification and Drawings, without claim for additional payment.

The AV Contractor shall obtain all licenses and permits necessary for the execution of any work pertaining to the installation, or any operation by the Owner.

The AV Contractor shall comply with all union jurisdiction requirements for the completion of the project.

If a conflict is identified between the contract documents and the appropriate codes and is reported to the Owner and confirmed prior to bid opening, Consultant will prepare the necessary clarification or revision. When a conflict is reported after contract award, the AV Contractor shall propose a resolution of the conflict and, upon approval, perform related work.

The AV Contractor will be responsible for connecting ground point to all AV equipment in accordance with applicable national and local codes, standards specified.

The Contractor will be responsible for loss calculations for the MATV distribution system, and shall provide the number of amplifiers required to fulfill the performance standards of the design.

The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the Contract Documents.

1.5 DEFINITION OF TERMS & ABBREVIATIONS:

Provide: to supply and install.

Furnish: to supply to another contractor for installation.

Supply: to supply but not install.

Install: to install but not supply.

OFE: Owner furnished (supplied) equipment. Equipment will be provided to Contractor for installation.

NIC: Not In Contract. Refers to items that are not included in the scope of work outlined in this section but may be shown for coordination purposes or reference.

Future: Equipment that will be provided by Owner at a later date. Accommodations shall be provided for future equipment as shown on the drawings.

Page 3: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 3

1.6 SYSTEMS DESCRIPTIONS

AV System

1. A video matrix switcher will be provided for routing video sources, including VGA and HDMI computer inputs, HDTV Tuners, Blu-ray/DVD players, and video production switcher. All AV sources will have the ability to be shown on any and all displays. Video display devices include 4 existing projectors and 3 existing LED displays. Four new projection screens will be installed in the existing motor housing. There are existing floor boxes in Rooms 207 and 209, as well as two floor boxes in Room 208. New HDMI and VGA transmitters and audio inputs will be installed in each floor box with new cables in the existing conduit. Rack-mounted preview monitors will be located in the Rack Room. 3 PTZ cameras will be installed, one in Room 207, 208, and 209 for use with the production switcher.

2. Existing ceiling speakers will provide sound reinforcement for voice and audio playback. Audio inputs include wired and wireless microphones, Blu-ray/DVD/CD player, HDTV Tuners, and auxiliary/computer inputs. New Dante stage boxes that plug into the floor boxes via Ethernet will provide inputs for existing tabletop gooseneck microphone during board meetings.

3. An existing owner-furnished Assistive Listening System will be used to comply with ADA requirements.

AV Control

1. AV systems will be controlled via touch panels. 3.5” touch panels will be located in Rooms 207, 208, 209, and a 10” panel in the Rack Room.

2. The AV Contractor shall be responsible for all audio, video, and control programming in this project. The control systems programmer will coordinate with building IT staff and facilities staff as necessary to interface with LAN, WiFi, and building management control systems.

1.7 PRE-BID SUBMITTALS

Bid Clarifications. AV Contractor is responsible for reading and understanding all information presented

in these specifications and related documents outlined in Section 1.2. Discrepancies between drawings and specifications or other errors or omissions should be brought to the Consultant’s attention a minimum of 5 days prior to bid date. Failure to do so does not relieve the Contractor from the requirement to provide a fully operational and turnkey system as outlined in Section 1.6. In this event, the Contractor agrees to abide by the decision of the Consultant for resolution.

Page 4: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 4

AV Contractor Qualifications. The following contractors are pre-qualified for this project. Additional contractors will be considered by the Owner and Consultant upon receipt of qualifications as outlined in Bid Submittals section below.

Contractor Name: Anderson Audio Visual – AVI-SPL Contact: Andrea Ventola Email: [email protected] Phone: (858) 966-3452 Address: 5735 Kearny Villa Road, Suite 113, San Diego, California 92123

Contractor Name: CompView Contact: Steve Gordon Email: [email protected] Phone: (858) 762-8731 Address: 13230 Evening Creek Drive S. Suite 215, San Diego, CA 92128

Contractor Name: Digital Networks Group Contact: David Bunting Email: [email protected] Phone: (949) 428-6383 Address: 20382 Hermana Circle, Lake Forest, CA 92630

Contractor Name: Spinitar Contact: Mike Janke Email: [email protected] Phone: (760) 448-2172 Address: 5939 Darwin Court, Suite 102, Carlsbad, CA 92008

Contractor Name: Western Audio Visual Contact: Steve Hollingsworth Email: [email protected] Phone: (760) 438-1200 Address: 6353 Corte Del Abeto, Suite 106, Carlsbad, CA 92011

1.8 BID SUBMITTALS

Submit according to conditions of the Construction Contract and Project Manual.

Bidders that have not been pre-qualified shall submit the following information:

1. Company profile including history, number of employees, facility size and completed projects.

2. Installer must have previously installed at least three jobs of similar magnitude, completed within the last five years. Installer shall provide a resume for these projects including project name, scope of services, year completed, and contact information for a reference. Provide at least one such completed job for inspection by the Owner and/or Consultant.

3. Installer must have five years of experience with equipment and systems of the types specified, must maintain a fully staffed and equipped service facility, must be a franchised dealer and authorized service facility for the major brands specified, and shall be properly licensed to work in El Cajon, California.

4. Resume of key personnel to be used on this project, including but not limited to: Project Manager; Lead Engineer; Job-Site Superintendent.

5. A sample set of shop drawings or as-built documents that confirm the Contractor’s capabilities to provide engineering and documentation for the project.

6. A line sheet listing all manufacturers the AV Contractor is a dealer and/or authorized service center for.

7. A description of the AV Contractor’s abilities for in-shop assembly, fabrication and testing.

The Bidder shall disclose in the bid whether any portions of the project work will be subcontracted out. All terms of this contract, including bidding and qualification statements, shall apply to the subcontractor.

1. Name of the proposed subcontractor.

2. A statement of qualifications for each subcontractor.

3. A scope of work outlining what portions of the project for which the subcontractor will be responsible.

Page 5: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 5

Include the following information with the bid submittal:

1. The total contract price.

2. The total price for any add or deduct alternates.

3. The price for Contractor tests and adjustments as outlined in Section 3.5.

4. An itemized equipment list.

5. Unit pricing for all equipment listed in item D.4 above.

6. A breakdown of the number of labor hours for each of the following:

a. Engineering and documentation.

b. On site coordination meetings and supervision.

c. In shop fabrication and assembly.

d. On site fabrication, assembly, and installation.

e. On site verification and testing.

Substitutions. Contractor shall note all substitutions at the time of bid. Comply with General Conditions. Any proposed substitutions must meet all specifications of the specified equipment. No product substitution will be accepted without the written approval of the Consultant or Owner. Consultant and Owner retain the right to reject any proposed substitution.

Contractor to obtain all licenses and permits necessary for the execution of any work pertaining to the installation, or any operation by the Owner.

1.9 PROJECT SUBMITTALS

Submit according to conditions of the Construction Contract and Project Manual.

Each submittal shall be as a coordinated package complete with all required information. Uncoordinated sets will be returned without review.

Product Data: Submit within 30 days of contract award. Submit manufacturer's product data sheets for each item of equipment that will be provided as part of this contract. Submit electronically as a single PDF. All equipment cut sheets will be arranged per specification section number. Provide a table of contents and a bookmark at the start of every product sheet.

Shop Drawings. Submit electronic format (PDF) drawings within 60 days of contract award. Failure to submit shop drawings with ample time for evaluation shall not entitle the Contractor to an extension of contract time. There will be no work authorized on site without the prior submittal and subsequent approval of a complete set of shop drawings. Any exceptions to this must be in writing and approved by the Consultant. Shop drawings shall indicate complete details and dimensions of work to be performed. Shop drawings shall be formatted as outlined below, and should contain, but are not be limited to, the following details:

1. Submitted as a multi-sheet PDF document with:

a. 30" X 42" sheets

b. Table of Contents

c. Bookmarks for every sheet with Sheet Name and Number

2. Drawings shall be a standalone package containing all information required to locate and install all junction boxes, devices and related equipment.

a. Flat Panel Display locations, orientation, and mounting methods

b. Architectural Coordination. The layout of all spaces shall be coordinated with current architectural drawings and site conditions. Coordinate locations of all junction boxes, AC power outlets, and wire routing and management. Spaces include, but are not limited to Equipment Rooms, Audio Control Booths, Audio Production Suites and other Control Spaces.

Page 6: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 6

c. Rack Layout and Location Diagrams with overall dimensions.

1) Submit heat loads for each equipment rack and calculations showing how numbers were derived.

2) Provide AC Power requirements for each equipment rack and calculations showing how numbers were derived.

3. Conduit riser diagrams for showing interconnect of all systems.

4. Wiring spreadsheet showing all wiring pull lengths from source to destination, including wire numbers.

5. Wiring schematic. Complete, detailed wiring schematic for all systems, based on the contract documents but including cable types, identification by number and color codes, and detailed wiring of connections, both at equipment and between equipment racks and wiring in conduit.

a. Schematic drawings of any custom circuitry or equipment modifications, including connector pin-outs and component lists.

b. Terminal strip layouts for all terminal strips to be used in junction boxes or in the equipment racks.

6. Provide circuiting detail for power distribution within the rack(s) both in the equipment rooms as well as at the control positions.

7. Fabrication details for all custom panels and devices include materials, finishes and labeling.

8. Schedule of colors for all equipment and materials including speakers, wall panels, exposed cabling, and custom furniture. Include all information required for coordination of custom colors with Owner.

9. Network schematic showing logical connections of all devices including IP address and VLAN information.

Review of shop drawings is for general conformance with the design intent and general compliance with the contract documents of the project. Corrections, comments or markings made do not relieve the Contractor from compliance with the Contract Documents nor allow departure there from. Contractor remains responsible for detailing and accuracy, confirming and correlating quantities and dimensions, selecting fabrication processing and techniques of construction, coordinating work with that of other trades, and performing work in a safe a satisfactory manner.

Custom Control Software Programming and User Interface Submittal.

1. Provide for approval at least 8 weeks prior to system commissioning an electronic copy of the DSP and Control System files, showing all user interfaces and control logic flow diagrams. It is the Contractor's responsibility to provide any and all custom software interface programming for the systems provided under this section. Coordination with the Consultant is required for the development of all user interfaces and control logic.

2. All Custom Software to be the unconditional property of the Owner, and copies of the files with all passwords to be provided on disks or memory sticks.

3. Provide programming changes based on reviews and post-opening customer use.

Wireless frequency analysis. It is the responsibility of the Contractor to coordinate all wireless frequencies. The Contractor shall perform a spectral sweep from 140 MHz through 3 GHz in the facility and then present a written report of proposed new frequencies. The Contractor must arrange and perform this sweep at a time of day that reflects the time of facility use. The Contractor should also include in the report additional frequencies for future expansion. The Contractor will incorporate any existing and other new frequencies in the determination of the new frequencies to be used, including but not limited to wireless intercom, wireless cameras and wireless radios.

Assistive Listening System Analysis. Contractor is responsible for providing documentation showing the Assistive Listen system meets accessibility requirements of the project location. Contractor is to provide a quantity of receivers per prevailing code.

Page 7: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 7

1.10 CONTRACT CLOSEOUT SUBMITTALS

Submit according to conditions of the Construction Contract and Project Manual.

Submit all contract closeout documentation within 30 days after substantial completion, unless otherwise noted.

Contractor shall work off of approved shop drawings only. Note changes made during installation on a single set of drawings. This set of marked up drawings will not leave the jobsite until after the final system commissioning. Submit 4 corrected sets of reproducible drawings showing work as installed. All “as-built” drawings to be provided both in electronic form (ACAD 2010 or later and PDF) and in hard copy (same size as architectural drawings).

Contractor to provide a Project Manual prior to acceptance testing. Provide a minimum of 1 hard copy and one electronic copy. This manual shall contain the following information:

1. Table of Contents.

2. Contractor’s contact information for warranty and/or service.

3. A complete list of equipment, both installed and loose gear. Include manufacturer, model number, and serial number for all devices. Include settings (software or hardware) for any devices that required modification or adjustment during the acceptance testing.

4. Operating manuals for each device.

5. Documentation of all testing results as outlined in Section 3.5.

6. USB Drive containing all As-Built drawings in PDF & DWG format.

7. CD-ROM Drive(s) containing all As-Built drawings in PDF & DWG format.

8. Replacement parts lists of major items of equipment.

9. Provide a suggested schedule of routine maintenance. Schedule should include dates of replacement of all batteries, cleaning of air filters and procedures for checking speaker components.

10. Create a quick start guide to provide information specific to the system, such as procedures for system power on/off, audio/video source selection, different modes of operation, etc.

a. The guide should convey information specific to the operation of the installed system. It is not intended to be a guide on generic AV system operation.

b. Anticipated length of the guide is less than 2 pages front and back.

Provide a copy of all software installed on computers or equipment in the system, including all device configuration files on a USB drive(s).

Produce compact system flow diagrams showing all components, cables, and wire numbers that will be mounted on the wall of each equipment rooms(s). Provide as-built wiring diagrams at a reduced scale that are easy to handle and fully legible.

Asbestos and PCB Certification: After completion of installation, but prior to Substantial Completion, AV Contractor shall certify in writing that products and materials installed, and processes used, do not contain asbestos or polychlorinated biphenyls (PCB).

1.11 CODE COMPLIANCE

All work and materials must comply with all applicable codes and regulations to meet or exceed Federal, State, City, and Local Building Codes and Regulations. Advise the Owner if anything in the Plans or Specifications is out of compliance with codes and/or laws prior to bidding.

1.12 PROJECT CONDITIONS

Verify conditions on the job site applicable to this work. Notify the Owner in writing of discrepancies, conflicts, or omissions promptly upon discovery.

Page 8: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 8

The drawings diagrammatically show cabling, conduit, wiring, and arrangements of equipment fitting the space available without interference. If conditions exist which make it impossible to install work as shown, recommend solutions and/or submit drawings to the Consultant for approval, showing how the work may be installed.

1.13 GUARANTEES

The Contractor shall warrant new equipment to be free of defects in materials and workmanship for not less than one year after date of Substantial Completion. Defects occurring in labor or materials within one-year warranty shall be rectified by replacement or repair. Within the warranty period, provide answer to service calls and requests for information within a 24-hour period, and repair or replace any faulty item within a 72-hour period without charge, including parts and labor. This warranty period does not extend to any existing equipment which is reused in the project.

This warranty will not void specific warranties issued by manufacturers for greater periods of time. Nor will it void any rights guaranteed to the Owner by law.

The AV Contractor shall provide Owner with exact beginning and ending dates of the warranty period. Include the name of the person to call for service and telephone number. This information to be part of Project Record Set.

The AV Contractor shall provide a final site visit and verification that the system is operational and all items are functioning correctly at the end of the warranty period. The Contractor shall not be responsible for correcting items that have obviously been changed by the Owner or end user.

PART 2 - PRODUCTS

2.1 UNAUTHORIZED MATERIALS

Materials and products required for work of this section will not contain asbestos, polychlorinated biphenyls (PCB) or other hazardous materials identified by the Owner.

All devices shall have applicable approvals from a Nationally Recognized Testing Laboratory and meet all applicable local codes and requirements. Should any equipment lack proper approval the Contractor will arrange for onsite inspections and certification at no additional expense to the Owner.

2.2 ACCEPTABLE MANUFACTURERS

Model numbers and manufacturers included in this specification are listed as a standard of quality.

Consultant will consider other qualified manufacturers subject to review. Submit according to conditions of the Construction Contract and Project Manual.

1. Proposed substitutions must meet all specifications of the specified equipment. The AV Contractor shall supply complete technical data specifications at the time of proposed substitution.

2. The AV Contractor shall arrange for product demo at the request of the Consultant or Owner Representative and will pay ground freight shipping to and from site, or to and from Consultant's office.

3. No product substitution will be accepted without the written approval of the Consultant and Owner. The Owner and the Consultant reserve the right to accept or refuse any substitution without condition.

4. Upon acceptance of a substitution, AV Contractor assumes all responsibility for verification and coordination of all heat, power, rack space and architectural requirements.

Page 9: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 9

If product is discontinued and/or no longer publicly advertised as a part of a manufacturer's current product line-up at time of installation, the project team reserves the right to request a substitution of product for new and currently offered product of like function fulfilling the design intent. Substitution value will be based on fair market value of original product at time of bid.

2.3 GENERAL

Equipment and materials shall be new, meet the latest published specifications of that product, and conform to applicable regulatory provisions. Take care during installation to prevent scratches, dents, chips, etc.

Install rack mounted equipment with black 10-32 button head machine screws.

Provide security covers on non-user operated equipment having front panel controls. Install covers at the conclusion of Acceptance Testing.

Provide engraved lamicoid labels at the front and rear of signal processing equipment mounted in racks. Mount labels on the equipment and attach in a neat, plumb, and permanent manner. Embossed labels will not be accepted. Only provide engraved labels at the rear of equipment mounted in furniture consoles.

Delivery, Storage and Handling.

1. All products and materials to be handled and shipped in accordance with manufacturer's recommendation.

2. Provide protective covering on equipment and furniture during construction to prevent damaging or entrance of foreign matter.

3. Replace at no expense to Owner, product damaged during delivery, storage, handling or construction.

2.4 A/V RACK ROOM

Equipment Racks

1. Existing, owner-furnished

2. Location: Rack Room

3. Verify exact rack space required.

4. Place racks to allow front and rear access.

5. Include associated rack shelves, panels, and blank panels to be mounted in respective racks if not included with existing rack equipment.

Power Distribution

1. Connect UPS to the audio DSP, network switch, control processor, and any other equipment that must not suddenly lose power.

2. Configure power sequencer to allow proper on/off so as to not damage the equipment, including during power failure.

a. Middle Atlantic Products UPS-S2200R (Qty. 1)

b. Furman CN-2400S (Qty. 1)

2.5 VIDEO SYSTEMS

Presentation Matrix Switcher

1. Mount in rack in Rack Room.

a. Extron XTP II CrossPoint 3200 Frame (Qty. 1)

Page 10: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 10

b. Input/output Boards:

1) Extron XTP CP 4i 4K (Qty. 1)

2) Extron XTP CP 4i VGA (Qty. 1)

3) Extron XTP II CP 4i HD 4K PLUS (Qty. 2)

4) Extron XTP II CP 4o HD 4K PLUS (Qty. 4)

5) Extron XTP Matrix Blank Plate (Qty. 8)

HDMI Wallplate Transmitter

1. Mount in existing floor boxes in Rooms 207, 208, 209 (one per floor box).

2. Remove existing cabling and install Cat6 cable as shown in the drawings.

a. Extron XTP T HWP 101 4K – Black (Qty. 4)

VGA Wallplate Transmitter

1. Mount in existing floor boxes in Rooms 207, 208, 209 (one per floor box).

2. Remove existing cabling and install Skew Free A/V UTP Cables as shown in the drawings.

a. Extron MTP T 15HD A D – Black (Qty. 4)

VGA Receiver

1. Mount in rack in Rack Room.

a. Extron MTP RL 15HD A (Qty. 4)

Blu-ray/DVD/CD Player

1. Mount in rack in Rack Room.

a. Denon Professional DN-500BD (Qty. 2)

HDTV Tuner

1. Mount in rack in Rack Room.

a. OFE Cox Tuner (Qty. 3)

PTZ Cameras

1. Mount in Rooms 207, 208, 209 (one per room).

a. Panasonic AW-HE40SW (Qty. 3)

1) Add Alternate #1: a) Panasonic AW-UE70W 4K (Qty. 3)

Video Preview Monitor

1. Mount in rack in rack Room.

a. Marshall Electronics V-LCD171MD 17.3" Rackmount Monitor (Qty. 1)

b. Marshall Electronics M-LYNX-503 Triple 5” Rackmount Monitor (Qty. 1)

Video Production

1. Mount in rack in Rack Room:

a. Broadcast Pix Flint LS (Qty. 1)

b. AJA Ki Pro Ultra Recorder/Player (Qty. 1)

1) Add Alternate #2: a) Broadcast Pix Rapid CG (Qty. 1)

c. Existing JVC SR-HD2500US Blu-ray/DVD Recorder

2. Provide camera control from both the Broadcast Pix Control Panel and the Panasonic Camera Controller.

3. Install on desk in Rack Room:

Page 11: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 11

a. Broadcast Pix 1000 Control Panel (Qty. 1)

b. Broadcast Pix 802 Panasonic Camera Control over IP Software Key (Qty. 1)

c. Panasonic AW-RP50 Camera Controller (Qty. 1)

4. Install on wall in Rack Room:

a. Samsung DB40E 40" LED Display (Qty. 2)

b. Chief Manufacturing MTM1U Tilt Wall Display Mount (Qty. 2)

HDMI Scaler and Transmitter

1. Mount in rack in Rack Room.

a. Extron DSC HD-HD HDMI Scaler (Qty. 7)

b. Extron XTP T HD 4K Transmitter (Qty. 7)

Displays

1. Three existing Samsung DM55D LED displays in Cafeteria

2. Remove existing cabling and install Cat6 cable as shown in the drawings.

HDMI 4K Wallplate Receiver

1. Mount behind existing Samsung LED displays in Cafeteria

a. Extron XTP R HWP 201 4K (Qty. 3)

Projector

1. Four existing Panasonic PT-RZ670 Projectors

2. Location: Room 207, two in 208, 209

3. Calibrate projectors.

4. Fix and adjust existing scissor lifts so that the projectors are level and can retract.

Projection Screen

1. Da-Lite Tensioned Advantage Electrol 16:10, High Contrast Cinema Vision

2. Reuse existing motor housings.

3. Verify the screens will fit in the existing motor housings and be operational before purchasing.

a. Da-Lite 34552LS 69” x 110” (Qty. 4)

2.6 AUDIO SYSTEMS

Digital Signal Processor

1. Mount in rack in Rack Room.

2. System functions to be controlled from the control system include: source mute, individual mic level, source selection, source level, overall system volume level, and any other audio control functions as requested by the Owner.

3. Install, configure, and program the processor for proper operation.

4. Provide audio programming for an automatic mic mixer processing system.

5. Optimize system for best gain-before-feedback performance.

6. See Section 2.8 for Programming Requirements.

a. QSC Core 510i (Qty. 1)

b. Input/output Cards:

1) QSC CIML4 (Qty. 5)

2) QSC CDN64 (Qty. 1)

3) QSC COL4 (Qty. 2)

Page 12: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 12

Power Amplifiers

1. Mount in rack in Rack Room.

2. Connect amplifier outputs to existing speaker cables.

3. Each amplifier to have an engraved lamicoid strip, on the front and rear, stating amplifier number and which speakers it is feeding.

a. QSC CXD4.3Q Processing Amplifier (Qty. 2)

Loudspeakers

1. Existing ceiling speakers

2. Connect cables to new power amplifiers.

Stage Boxes

1. Install two RJ45 input connectors in each of the four existing floor boxes in Rooms 207, 208, 209.

2. Stage boxes shall be used with existing tabletop gooseneck microphones.

a. Yamaha Tio1608-D Dante Stagebox (Qty. 2)

Digital Automatic Mixer

1. Mount in rack in Rack Room.

2. Mixer shall be configured to control the gooseneck microphone inputs from the Dante Stage Boxes.

a. Shure SCM820 Digital Automatic Mixer (Qty. 2)

Antenna Distribution System

1. Existing, owner-furnished.

2. Mount in rack in Rack Room.

Assistive Listening System

1. Existing, owner-furnished ALS transmitters and receivers.

2. Mount in rack in Rack Room.

3. Install antenna system in accordance with manufacturer’s recommendations.

4. Contractor is responsible for verification of receiver quantities per project code requirements.

a. Listen Technologies LA-166 Neck Loop (Qty. 4)

Wireless Microphone System

1. Mount in rack in Rack Room.

2. Select wireless frequency bands based upon frequency analysis preformed in Section 1.9G.

3. Include all modules necessary for a complete system.

4. Include all cabling required for remote antenna locations.

5. Contractor shall perform calculations to determine cable and connector loss based on install conditions. Install antenna boosters as required per calculations. Include this report with shop drawing submittals.

6. Mount existing antenna distribution in rack in Rack Room.

a. Shure QLXD24/SM58 – Includes QLXD4 Receiver and QLXD2/SM58 Handheld Wireless Transmitter (Qty. 3)

b. Shure QLXD14/SM35 – Includes QLXD4 Receiver, QLXD1 Wireless Bodypack Transmitter, and SM35 Headset Microphone (Qty. 3)

c. Shure QLXD14/85 – Includes QLXD4 Receiver, QLXD1 Wireless Bodypack Transmitter, and WL185 Lavalier Condenser Microphone (Qty. 2)

Audio Floorbox Inputs

1. Mount in existing floor boxes in Rooms 207, 208, 209 (one per floor box).

Page 13: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 13

2. Remove existing cabling and install line-level audio cable as shown in the drawings.

a. RDL DB-CIJ3 Input Jacks (Qty. 4)

Stereo to Mono Converter

1. Shall be used to send mono audio signal to Patio and Cafeteria from the video switcher. Meeting Rooms 207, 208, 209 shall receive stereo audio signal from the video switcher.

a. RDL TX-J2 (Qty. 2)

2.7 CONTROL SYSTEMS

Network Switch

1. Mount in rack in Rack Room.

2. Work with the Owner to allocate IP addresses and configure network VLANs to support AV system needs.

3. All network capable equipment shall be connected to the network, including but not limited to DSP, playback devices, and control systems.

a. Cisco SG300-52P PoE+ Layer 3 Network Switch (Qty. 1)

Control Processor

1. Mount in rack in Rack Room.

a. Extron IPCP Pro 550 Control Processor (Qty. 1)

b. Extron IPL T CR48 (Qty. 1)

Control Touch Screens

1. This project will include an AV control system that controls AV functionality within the rooms.

2. User interface will be via touch panels.

3. Verify color with Owner.

4. Provide programming services to accomplish Owner goals (see Control Systems Programming Section 2.8 for further details).

5. Wall-mounted in Rooms 207, 208, 209 (one panel per room).

a. Extron TLP Pro 320M – White (Qty. 3)

b. Extron BB 1 Back Box (Qty. 3)

6. Mount in rack in Rack Room.

a. Extron TLP Pro 1022M – Black (Qty. 1)

b. Extron RM 4 Rack Mount Kit (Qty. 1)

2.8 PROGRAMMING

Control Systems

1. The AV Contractor shall be responsible for all AV Control System programming for this project. Prior to commencement of control system programming, the AV Contractor shall coordinate with the AV Consultant to further develop the requirements for control functionality and user interface.

2. The functionality provided by the AV Control System will include but may not be limited to:

a. System On/Off (Standby)

b. Control of projection screen and projector lift

c. System power down – manual and/or scheduled

d. Video source selection and routing AV sources to any video display

e. Control and scaling of video displays

f. Room audio source selection

Page 14: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 14

g. Room audio volume control

h. Control of Blu-Ray player

i. Control touch screen functions as per the Owner

j. Zone level/mute

k. Transport control of appropriate devices

l. Recording control

3. Create menu pages to provide simple “one-touch” system activation, selection of preset operating parameters (for example, one preset will be a predetermined setting for active microphones and system level for a typical meeting), as many as may be required to cover the various room configurations and a quantity of user-definable presets.

4. Touchscreen programming will also provide access to system individual microphone levels, playback control of CD, microphone equalization, and other functions to be determined in conversations with the owner.

5. Menu pages must be password protected to limit access beyond simple system on/off and preset selection to those trained and qualified for other operations.

6. The control system will also provide access to the lighting presets so the entire configuration of the space can be activated using the “one-touch” process.

7. An advanced section will be included allow a means of storing user definable presets that set microphone levels and custom microphone equalization. A library of microphone equalization settings will also be stored.

8. All custom programming configurations and code will remain the property of the Owner.

9. All passwords and login information and software licenses related to the control systems programming will be provided to the Owner for their distribution as appropriate among staff and end users.

10. Prototype control screen templates will be presented to the Owner and Consultant for review 4 weeks prior to systems commissioning.

11. Beta level control systems programming that have been tested with equipment will be provided for Consultant review 2 weeks prior to commissioning.

12. Completed base programming and structure will be tested and operational during system commissioning.

13. The AV Contractor shall provide for up to 2 Owner requested revision lists to functionality and GUI layout that will be incorporated into the control system programming during the first year of building operation, after the first systems use. The AV Contractor shall provide these programming revisions without request for additional payments.

14. In addition to the 2 major programming revisions, the lead programmer(s) shall be present for the first 2 times each of the systems are used by the Owner. Assume there will be 2 to 3 hours of follow-up programming changes after each of these 2 events.

a. Custom Programming (Qty. 1)

DSP Programming

1. The audio systems for spaces described above will be controlled through a Digital Signal Processing System. This will provide all equalization, cross-over settings, level control, muting, routing, signal delay, level monitoring, etc. With direction from the AV Consultant, the AV Contractor will develop signal flows for each of the systems as well as comprehensive GUIs for typical day-to-day operational control. These control screens will be accessible through both wired and wireless computers and wireless touch screen tablets. Several levels of user access are expected.

2. Pages will be formatted and sized appropriately for display resolutions of the control computers and wireless tablets. Multiple versions of some pages may be required to work with different display resolutions.

3. Wireless microphones shall be able to be individually assigned and the audio signal routed to any of the meeting rooms or combined spaces.

Page 15: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 15

4. The DSP platform will be controlled by external devices via contact closures, TCP/IP, or serial protocols. The DSP system will be heavily controlled through the Control System described above.

a. Custom Programming (Qty. 1)

2.9 CUSTOM PANELS

Panels to be fabricated by Contractor, engraved and loaded with connectors with information shown on Drawings.

Unless otherwise specified, all wall and ceiling panels shall be 1/8 inch thick, anodized aluminum. (Brush in direction of aluminum grain only.) Engraving shall be 1/8 inch block sans serif characters.

1. Coordinate all panel colors/finishes with Owner.

2. All custom panels shall have beveled edges.

3. Text color shall be white for all black/dark colored panels and black for all white/light colored panels.

4. Connector color shall be silver for all white/light colored panels and black for all black/dark colored panels.

5. Plastic plates will not be accepted.

6. Where Extron, Crestron, or other manufacturer’s transmission equipment will be mounted on a wall or ceiling plate visible to the public, uses Decora style plates, coordinate color of equipment and wall plate with Owner.

7. Wall panels sizes to be coordinated with J-boxes dimensions and mounting conditions.

a. Panels mounted on surface mount boxes shall not protrude beyond the edge of the box thereby creating a sharp edge condition.

b. Panels mounted on flush mount boxes shall extend beyond the edge of the J-box by 1/4” on all sides.

Unless otherwise specified, all rack panels and floor box panels shall be 1/8 inch thick, black anodized aluminum. (Brush in direction of aluminum grain only.) Engraving shall be 1/8 inch block sans serif characters. Lettering shall be white.

1. Coordinate all panel finishes with Owner.

2. Connector color shall be silver for all white/light colored panels and black for all black panels.

3. Rack panels shall be standard EIA sizes.

4. Plastic plates will not be accepted.

Contractor will submit panel engraving schedule and fabrication drawings for approval

Panels to be manufactured by one of the following manufacturers:

1. Panel Authority

2. Proco

3. RCI

4. Whirlwind

Panel Connectors.

1. Panels to contain components listed below:

a. Female XLR: Neutrik NC3FD-L-B-1.

b. Male XLR: Neutrik NC3MD-L-B-1.

c. Locking 1/4": Neutrik NJ3FP6C-B.

d. Female XLR-1/4” TRS Combo: Neutrik NCJ6FI-S

e. Rugged RJ45: Neutrik NE8FDP-B

f. Female RCA: Neutrik NF2D-0.

Page 16: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 16

g. BNC (75 Ohm): Neutrik NBB75DFIB-P

h. BNC (50 Ohm): Kings KC-99-40

i. 4-Pole Speaker: Neutrik NL4MP

2.10 CABLE, CONTROL WIRING & TERMINATIONS

Electrical conductors installed under this contract, except where otherwise specified, will be soft drawn annealed stranded copper having a conductivity of not less than 98% of pure copper.

AV Contractor shall supply, install, and terminate cable.

Refer to drawing AV0.00 for cables to be used.

1. Use plenum and underground cables as required by code.

2. It is assumed all underground cables, where they transition to cable tray or free-air, will not pass through plenum spaces outside of conduit.

Refer to drawing AV0.00 for minimum cable lengths required outside of boxes.

The Contractor will verify all connector details required for installation of equipment, including make, model, connector sex, attachment configuration, pin-outs, and cable clamp accessories.

Video Connectors: All primary video equipment will use crimp-on style BNC connectors. If consumer grade equipment is furnished with RCA connectors, the cable will be terminated in a crimp-on style RCA connector. It will not be acceptable to use BNC to RCA adapters for consumer grade connections.

Video Terminators: Video terminations will be comprised of commercially available 75 ohm 0.1% tolerance units with integral BNC connectors, which are applied as required, plus a 20-count spare.

Cable Mount Connectors.

1. Cables to use components listed below, unless otherwise noted:

a. Female XLR: Whirlwind WI3F-BK

b. Male XLR: Whirlwind WI3M-BK

c. Male XLR Numbered: Whirlwind WI3M -BK-#

1) To be used on all audio console and stage box inputs.

d. 1/4" TS: Switchcraft 280

e. 1/4” TRS: Switchcraft 297

f. Rugged CAT6 RJ45: Neutrik NE8MC6-MO

g. RCA: Canare 75 Ohm

h. BNC (75 Ohm): Canare 75 Ohm

i. BNC (50 Ohm) Type F Cables: Amphenol Connex 112563

j. BNC (50 Ohm) Type G Cables: Amphenol Connex 112120

k. 4-Pole Speaker smaller than 12AWG: Neutrik NL4FC

l. 4-Pole Speaker greater than 12AWG: Neutrik NLT4FX-BAG

m. 8-Pole Speaker smaller than 12AWG: Neutrik NL8FC

n. 8-Pole Speaker greater than 12AWG: Neutrik NLT8FX-BAG

o. Mass Connectors: Whirlwind W-series

p. Triax: ADC ProAx Plugs and Jacks.

q. SM Fiber Optic: Amp Metallic ST style (Flat Finish)

Page 17: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 17

Use the following chart for color coding cables for use in the AV systems. Please see the drawing package for specific cable part numbers

Signal Type Letter Color

HD Video H Violet

SDI Video H Blue, Light

Composite Video H Green

Bi-Level Sync/Reference H Red

Tri-Level Sync/Reference H Orange

V-TIE (multi-use) H Grey

Triax Camera Cable T Black

Multicore Camera Cable M Black

Analog Line Level Audio D Green

Analog Mic Level Audio E Orange

Digital Audio (AES) X Yellow

Time Code E White

RF (Distributed) K White

RF (Trunk Line) L Black

RF Antenna F/G Black

Tally E Chrome

RS-232/422/485 Control R Chrome

Network 10/100/1000 U Yellow

Network Facility LAN U Blue

KVM U Green, Dark

Intercom E Brown

Speaker A Grey

PART 3 - EXECUTION

3.1 GENERAL

Coordinate work with other trades to avoid causing delays in construction schedule.

Mount equipment and enclosures plumb and square. Permanently installed equipment to be firmly and safely held in place.

Cover edges of cable pass-through holes in chassis, racks, boxes, etc., with rubber grommets or Brady GRNY nylon grommetting. Adhesive-backed electrical tape and friction tape is not acceptable for insulating or protective purposes.

Equipment Racks

1. Mount equipment in existing racks and consoles and fully wire and test on site.

2. Provide and install equipment racks as specified under this section in a manner in keeping with local seismic codes. Ensure that all equipment racks are electrically decoupled from flooring to prevent coming into contact with any safety grounded items during operation by providing rubber mat-style isolation between racks and riser.

Page 18: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 18

3. Inspect all racks, consoles, and enclosures prior to installation. All rough or sharp edges that may cause injury to personnel must be deburred or a permanent protective coating applied.

4. Design and provide ventilation adequate to keep temperature within the rack below 85 degrees Fahrenheit. This ventilation system must be temperature actuated.

5. Provide blank rack-mount panels installed in all rack openings not occupied by equipment. Blank filler panels will not exceed five rack units in size. Install rack mounted equipment with black 10-32 Phillips head machine screws.

6. Provide security covers on non-user operated equipment having front panel controls. Install covers at the conclusion of Acceptance Testing.

7. Install rack mounted equipment with black 10-32 button head machine screws.

8. Panels or equipment mounted on the rear rack rails must not block access to any front mounted components. Front mounted equipment will be given ample space to allow for access to rear connection.

The process of acceptance testing the System may necessitate moving and adjusting certain component parts - e.g., video monitors.

AC Power and Grounding

1. The AV Contractor shall be responsible for the supply and installation of AC power connections and circuits within the equipment racks that are to be provided under this section. Install 3-conductor, 120 VAC outlets in each rack. Provide a minimum of two spare outlets in each rack. Label each outlet as to which AC circuit is feeding it and provide the same information in the circuit breaker panel.

2. The electrical safety ground shall be bonded to the frame of all metal equipment racks by use of an uninsulated ground buss lug or bar mounted in each rack.

3.2 CUSTOM CONSOLE AND WORK SURFACE DESIGN

All consoles and casework items will be rigidly constructed, and will allow for a minimum temporary additional load of 200 pounds on any horizontal surface without permanent deformation.

Consoles will be steel frame construction using extruded hollow square and angle sections welded together to form the sub-frame. This sub-frame will form the structural support for all equipment loads, work surfaces and writing surfaces.

The steel frame will be electrically arc welded or similar. Remove all spatter, and grind off excess weld and burrs. Prepare for shop priming by power wire brushing to remove rust. Degrease, shop prime, and finish with paint finish as specified. Protect for transport and shop/site and apply touch up paint as necessary. All arc weld hardware will be degaussed after the completion of all welding to be done on the piece.

All dimensions and profiles will be checked with all right-angles true and uniform. Use blank rack mount panels to confirm accuracy of mountings.

All attachments to viewable surfaces will be concealed. Attachments through the finish face of painted sections will be countersunk 1/4" below the surface. A resilient packing 1/16" thick will be placed over the screw before the hole is filled with a 2-part epoxy and finish sanded. When fitting panels allow clearances for paint finished. All laminate will be accurately scribed and fitted to the profiles required. Joints will be glued and screwed using frets or glue blocks where possible to ensure rigidity of the panels independently of the steel frame.

Perforated metalwork will be folded accurately to match adjacent profiles with 3/4" returns lapped and spot welded to form a rigid unit. Hinges and accessories will be chrome or brass, including screws.

Page 19: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 19

All consoles will have removable rear panels for rear access to installed equipment. Removable front "kick panel" doors will also be required. All panels will remove completely during installation and service to facilitate installation work. The panels when installed will present a neat and finished appearance and will have a secure mechanical latch mechanism to avoid any rattles or buzzes.

Provide a suitable method of cable access through the bottom and between sections of consoles.

Control interfaces and panels mounted in custom fitted cutouts will provide a non-gaping interface to the surrounding surface to within a 1/32" tolerance.

Clearances: There will be a minimum of 1 inch clearance inside all consoles between the top equipment mounting space and the console top. This is to allow airflow above equipment mounted in the top mounting position. Provide adequate ventilation grilles to allow continuous cooling in consoles containing equipment. This should include both supply and exhaust grilles. Provide ventilation adequate to keep temperature within the rack below 85 degrees Fahrenheit. Provide whisper type ventilation fan in each rack if temperature in rack rises above 85 degrees. This ventilation system must be temperature actuated.

All consoles and racks will have front and rear rack rails separated by at least 24 inches. The rails will be parallel and square and will conform to EIA RS-310C for 19-inch racks.

Console work surfaces will be finished with a material and color selected by the Owner. Painted and metal panels will be finished with sprayed polyester lacquer, satin finish, and color as selected by the Owner. Steel frame finish will be black enamel.

Painting:

1. Surface Preparation: Preparation for painting will involve fine paper sanding and dusting to ensure a perfectly smooth substrate.

2. Primer: Sealer undercoat will be spray applied and sanded back using 250 grit. Touch up as needed and re-sand.

3. Finish coats will be spray finished in an appropriate spray booth with approved ventilation, humidity control, dust extraction, and lighting. Finished paint thickness will be 1 mil minimum and will be free from runs, orange peeling, blooming or other blemishes. Metal panels will have a similar finish using appropriate metal primer.

3.3 CABLING

Execute wiring in strict adherence to "standard broadcast practices," as excerpted from "Recommended Wiring Practices," Broadcast Audio Equipment for AM, FM, Television (5th Edition), Radio Corporation of America (RCA), Camden, N.J. 1962, and Appendix II, "Recommended Wiring Practices", Sound System Engineering, (2nd Edition), D. Davis, and performed in accordance with standard professional practice.

Take precautions to prevent and guard against electromagnetic and electrostatic hum. For line level audio signals, float cable shields at the output of source device. Shields not connected to be folded back over cable jacket and covered with heat-shrink tubing. Do not cut off unused shields.

Exercise care in wiring; damaged cables or equipment shall not be accepted. Isolate cables of different signals or different levels; and separate, organize, and route to restrict channel crosstalk or feedback oscillation. Keep wiring separated into groups for microphone level circuits, line level circuits, loudspeaker circuits, power circuits, video circuits and control/data circuits.

Route unbroken microphone, audio line, and control wiring from receptacle plate/chassis to patch panel/rack. Remove spliced cables and replace without additional charge to the Owner.

Page 20: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 20

Wiring entering equipment racks will be run directly to equipment. Use of splices or connectors to extend cabling to equipment will not be accepted. All signal wiring will be continuous and unbroken from connector plate/chassis to chassis/patch panel. Use of intermediate connections for inter rack cables is not acceptable. Use of splices or connectors to extend cabling to equipment is not acceptable.

Make joints and connections with rosin-core solder or with mechanical connectors approved by the Owner. Where spade lugs and BNC terminations are used, trim cable using manufacturer recommendations and crimp properly with ratchet type tools. Spade lugs mounted on 22 gauge or smaller cable to be soldered after crimping.

Connect audio cable to active components through screw terminal connections and spade lugs whenever available. Make connections to speaker transformers with properly sized closed end connectors crimped with factory approved ratchet type tool. Wire nut or "Scotchlock" connectors are not acceptable. Do not wrap audio cable splices or connections with adhesive backed tape.

Connect loudspeakers electrically in phase, using the same wire color code for speaker wiring throughout the project.

Wiring and connections will be completely visible and labeled in rack.

All power cables will run on the left side of the equipment rack, as viewed from the rear. All other cables will be run on the right side on the equipment rack, as viewed from the rear. Where signal cabling and any cabling types carrying power must cross, they will do so at right angles. Vertical wiring will be run with a bundling and support system, to maintain a clear and organized appearance.

Horizontally routed wiring to equipment will be neatly tied in manageable bundles with cable lengths cut to minimize excess but still allow ready access for service and testing. Provide horizontal support bars if cable bundles sag

For equipment mounted on slides, additional service loops will be provided to accommodate the full range of travel of the slides. This includes all power, ground, control and signal cables.

Neatly bundle excess AC power cables from rack-mounted equipment with plastic cable ties. Rack wiring to be bundled with plastic cable ties or lacing twine. Electrical tape and adhesive backed cable tie anchors are not acceptable. Cable tie and lacing installation will be accomplished using hand tools specifically designed to apply proper tension to the cable tie, and to cut it off flush with no protruding sharp edges. Cable ties will not be applied with excessive force, which may damage or deform sensitive and fragile cables.

All cables in cable trays shall be neatly installed with maintaining separation of the different cable types.

Required cable paths and lengths must be predetermined especially in instances where timing is a factor. The information that is essential for the implementation of this task is as follows:

1. Site Survey

2. Floor and Ceiling Plans

3. Elevation Design

4. Equipment List

5. Video and Audio Schematics

6. Cable Trays and Conduits

Screw Connections: Only insulated crimp on spade terminals will be used for application to barrier strips. Multiple gang lugs or ring lugs are not acceptable for this purpose.

1. This is only applicable to stranded conductor wires. Solid conductors will be attached directly to the barrier strip.

Page 21: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 21

2. All conductors will be stripped prior to installation underneath screws on terminals. Provide crimp lugs on stranded control cables, solid conductor wire will not require crimp lugs on individual conductors. All screw terminated solid conductors will be wrapped in the same direction as screw rotation during tightening.

Multiconductor Cables: Follow a uniform application of color codes for multiconductor cables throughout the Facility. Where there are unused conductors or pairs in a cable assembly, they can be insulated as a group, left long enough for future termination, and folded into the connector hood. Where this is impractical, they may be folded back along the outer jacket of the cable and covered with heat-shrinkable tubing.

3.4 LABELING

General

1. The attachment method for equipment identification plates will be designed for permanency unless otherwise described. All labels will be protected prior to installation, and will not be installed if damaged or scratched. Follow manufacturer's recommended procedure for surface preparation, which must be free of any dust, dirt or film. Wiping with a manufacturer-approved solvent is required. If a label is in a place that might be susceptible to damage, it will be protected with a layer of clear plastic, 1/16" or thicker, taped down. Internal labels will be replaced only if they become illegible. External labels will be replaced if they become scratched or marred.

2. On black lamicoid panels or pushbuttons, letters shall be white; on stainless steel or brushed natural aluminum plates, or light-colored pushbuttons, letters shall be black.

3. Embossed labels are not acceptable.

4. Mount labels in a neat, plumb and permanent manner except where indicated.

5. Text heights will be as follows:

a. Rack designation labels will have 1" high block sans serif text.

b. Equipment labels will be 1/4" high block sans serif text.

c. Operator Control labels will be 1/4" high block sans serif text, this may be adjusted to fit available space.

d. Panel labels will be 1/8" high block sans serif text.

e. Cable and Connector labeling will be 10 point block sans serif text, this may be adjusted to fit available space.

Equipment Labels

1. Provide engraved lamicoid labels on the front and rear of active equipment mounted in racks. Front mounted equipment labels for the Production Suite video monitor wall monitors are to be mounted with Velcro. Equipment labels to have one line of engraving, giving the schematic reference of the device, and/or its production function, i.e. "VCR #4", "PA-29A".

2. Amplifier labels to include the schematic reference of the device as well as the loudspeaker being fed. Provide color coded labels for the different levels and types of speakers.

3. Unless equipment manufacturer has clearly labeled functions, provide an engraved label over each user-operated control that describes the function or purpose of the control.

4. If the manufacturer provides a protected labeling strip such as those used for switcher control panels and patch bays, then patch/routing point labels may be typed clearly on 80 pound paper stock.

Cable Labels

1. Cables and wiring to be logically, legibly and permanently labeled for easy identification. Labels on cables to be adhesive strip type covered with clear heat-shrink tubing. Factory stamped heat shrink tubing may be used in lieu of the adhesive strip style label. Hand-written or self-laminating type labels are not acceptable.

2. All CAT6 cabling shall have color coded jackets to indicate input/output feed type.

Page 22: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 22

3. Wiring designations to be an alphanumeric code that is unique for each cable. Locate the cable designation at the start and end of each cable run and within 2 inches of the point of termination or connection. For cable runs that have intermediate splice points, the cable shall have the same designation throughout with an additional suffix to indicate each segment of the run. Actual cable designation assignments to be determined by Contractor. Add cable designation codes to system schematic drawings included with Project Record Drawings.

4. Provide adhesive labels on the rear of equipment where cables attach to indicate the designation of the cable connected at that point.

3.5 ACCEPTANCE

Provide a pre-commissioning systems report to the Consultant two weeks prior to the scheduled systems commissioning proving all systems to be in full compliance. Report shall include test results, date of each test, pertinent conditions such as control settings, etc., and test equipment employed. In addition, submit written notification that the installation has been completed in accordance with the requirements of the Contract Documents, and is ready for acceptance testing.

Acceptance testing will include operation of each major system and any other components deemed necessary by the Consultant. Contractor will assist in this testing and provide required test equipment. Contractor will provide at least three technicians familiar with installation, available for the entire testing period (day and night), to assist in tests, adjustments, and final modifications. Tools and material required to make any necessary repairs, corrections, or adjustments will be furnished by the Contractor. The Contractor will keep a running list of all acceptance tests performed and submit a final copy of the results with the closeout submittals as listed in Part 1.10. Testing process is estimated to take 1 to 2 days up to 10 hours per day and may require multiple crews / shifts.

During all Consultant walkthroughs, the project manager will be present.

If during acceptance testing it becomes evident that further adjustment or work may be required to bring the system into compliance, the Contractor will continue to work until the system is acceptable at no additional charge to the contract price. If approval is delayed because of defective equipment, poor installation, or failure of equipment to meet the requirements of these specifications, the Contractor will pay for additional time and expenses of the Consultant at the Consultant's standard rate in effect at that time, during any extension of the acceptance testing period. The Contractor will provide rental or loaner equipment to make the system operational in critical cases of equipment failure prior to contract completion.

Verify the following before beginning actual tests and adjustments on the system:

1. Electronic devices are properly grounded.

2. Powered devices have AC power from the proper circuit and hot, neutral, and ground conductors are connected correctly.

3. Insulation and shrink tubing are present where required.

4. Dust, debris, solder, splatter, etc. is removed.

5. Cable is dressed, routed, and labeled; connections are consistent with regard to polarity.

Cabling Tests

1. Submit printed test reports proving the systems to be in full compliance to the Consultant as part of the pre-commissioning systems report.

2. After installation, and before termination, all wiring and cabling shall be checked and tested with a megohmmeter to ensure there are no grounds, opens, or shorts on any conductor or shields.

3. Test all CAT5E and CAT6 cables to verify they meet full specifications. Tests will use a certified tester that will confirm bandwidth, cable distance, and error and bit rate detection.

4. Loudspeaker System Tests. Perform the following tests and adjustments. Make corrections necessary to bring system(s) into compliance with the specifications.

Page 23: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 23

a. Measure and record the impedance of each loudspeaker at the equipment rack with the amplifier disconnected. Measurements shall be documented in a table that lists the impedance for each 1/3 octave band over the loudspeakers operating frequency. Measurements shall be accurate to within one-tenth of an ohm. As an alternative, Contractor may perform and document full impedance sweeps over each individual device. Sweep to be performed over loudspeakers specified operating range.

b. Check polarity of loudspeakers with an electronic polarity checker and by applying music program or constant power per octave (pink noise) signal to system while walking through the transition areas of coverage from one loudspeaker to the next. Transition should be smooth with no apparent shift in source from one speaker to the next.

c. Apply sine wave sweep signal to each loudspeaker system, sweeping from 50 Hz to 5k Hz and at a level 10 dB below full amplifier output, and listen for rattles or noise. Correct if apparent.

5. Microphone, line level, and Tie Lines Systems. Confirm the following. Make corrections necessary to bring system(s) into compliance with the specifications.

a. Proper circuits appearing at each termination location.

b. Continuity of all conductors.

c. Proper polarity is maintained.

d. Absence of shorts between conductors.

e. Absence of shorts between conductors and conduit.

System Tests

1. The following procedures shall be performed by the Consultant:

2. Audio fidelity Verification: Driving the system with pink noise and measuring the response from 40 Hz to 16k Hz. Digital Signal Processing will be used to adjust the response of the system (s) to fit the requirements of the space.

3. Video Signal Verification: From all source inputs (for cameras, character generators, video tape units, etc.) through all VDAs, A/D and D/A converters, processors, switchers, etc., to all signal destinations. Verification of correct signal timing for each source via each path will be made using standard test patterns.

4. Control functions shall be checked for proper operation, from controlling devices to controlled devices.

5. Adjust, balance, and align equipment for optimum quality and to meet the manufacturer's published specifications. Establish and mark normal settings for each level control, and record these settings, in the "System Operation and Maintenance Manual".

6. Installed and loose equipment shall be inventoried for correct Qty.

7. Any other test on any piece of equipment or system deemed appropriate by Consultant.

8. The omission of a description of a device, function, signal path, or test in this document shall not exempt the Contractor from responsibility for checking all devices and signal paths for appropriate compliance with Industry Performance Standards and making corrections necessary to bring system(s) into compliance with the applicable standards.

3.6 TEST EQUIPMENT

Provide the following equipment on site for final acceptance testing. Test equipment to be available for the entire period through final system acceptance.

1. Multimeter: Measurement range, DC to 20,000 Hz, 100 mV to 300 V, 10 ma to 10A. Acceptable: Fluke 75.

2. Sound Level Meter: ANSI S1.4-1971 Type S1A with digital or analog display. Meter to provide ranges of 40 to 120 dBA.

Page 24: SECTION 27 41 30 AUDIO-VISUAL SYSTEMS PART 1 - GENERAL · 8/4/2017  · The AV Contractor shall be responsible for all audio DSP programming for all AV systems described within the

CUYAMACA COLLEGE STUDENT CENTER BID DOCUMENTS EL CAJON, CALIFORNIA oooooooooooooooooooooooooooooooooooooo08/04/2017

27 41 30 - 24

3. Impedance Meter: Capable of testing audio lines at three frequencies, minimum, between 250 Hz and 4k Hz. Measurement Range: 1 ohm to 100k ohms.

4. Polarity checker for mic and line level signals.

5. Polarity checker for loudspeakers.

6. (2) full height weighted base mic stands

7. CAT6 cable tester: Acceptable: Microtest Omniscanner 2.

3.7 INSTRUCTION OF OWNER PERSONNEL

Upon completion of the installation of the specified AV systems, and prior to any facility events, provide designated operating personnel training on the equipment operation. This training will be performed at the site by the Contractor's and the manufacturer's education staff.

The System Reference and Service Manuals must be complete and on-site prior to the time of the first instruction.

Provide trained personnel (one person) to be present at first use of the systems by the Owner.

Coordinate schedule of instruction with the Owner subject to availability of Owner's personnel. This may require scheduling instruction during weekends or evenings.

Training will be provided in a series of classes to operations personnel to review all aspects of operation and maintenance of the system. Follow-up sessions to better enhance the operator's ability to expand or maximize the system will be made available.

The system training will include 1/2 days or 4 hours of technical training covering the explanation of the system, including documentation, configuration, interfacing and diagnostics. Provide training of the system operators and maintenance personnel as follows:

1. System Overview: Explanation of system includes documentation, configuration, interfacing and basic diagnosis.

2. Operator Training General: Basic training in the use of system devices including powering and general operation of overall system.

3. Operator Training Specific: Advanced training in use of system devices as well as system troubleshooting and maintenance.

4. Where specified, training will be by manufacturer representatives.

Manufacturer training and commissioning is specified in this document. The Contractor will cover expenses such as flight, hotel, rental car, and meals and include them as part of the bid pricing.

END OF SECTION