Page 1: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 1

September 2013

Rod Mahdavi, PE. LEED AP

Building Technologies

Lawrence Berkeley National Laboratory (LBNL)

Saving Energy in Data Centers

Low Cost Energy Efficiency Measures

Case Studies

Page 2: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 2

Objective

• Explore why saving energy in Data Centers?

• Get a general idea of the best practices

• Learn about low cost EEMs

• Environmental conditions adjustments

• Air management improvements

• Chiller Plant

• Examine three Case studies

Page 3: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 3

High Tech Buildings are Energy Hogs:

Page 4: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 4

US Data Center Electricity Use -

2000, 2005, and 2010

Source: Koomey 2011

2% of US Electricity consumption

Potential to double in next 5 years

Page 5: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 5

Data Center Energy Efficiency = 15% (or less)

100 Units

Source

Energy

Typical Data Center Energy End Use

Server Load

/Computing

Operations

Cooling

Equipment

Power Conversions

& Distribution

33 Units

Delivered

35 Units

Power Generation

(Energy Efficiency = Useful computation / Total Source Energy)

Page 6: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 6

Server Load/

Computing

Operations

Cooling Power

Conversion & Distribution

Alternative Power

Generation

• High voltage distribution

• High efficiency UPS systems

• Efficient redundancy strategies

• Use of DC power

• Server innovation

• Virtualization

• High efficiency

power supplies

• Load management

• Better air management

• Move to liquid cooling

• Optimized chilled-water plants

• Use of free cooling

• Heat recovery

• On-site generation

Including fuel cells and

renewable sources

• CHP applications

(Waste heat for cooling)

Energy efficiency best practices

Page 7: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 7

7

DC Pro tools Data Center Energy Practitioner

program Computing metrics development

Federal consolidation guideline

ESPC contract content

Wireless assessment kit Compressor- less cooling

LBNL develops publically available resources

Page 8: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 8

•Environmental conditions adjustments

•Air management improvements

•Chiller plant

Low Cost EEMs:

Page 9: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 9

•Environmental conditions adjustments

•Air management improvements

•Chiller plant

Low Cost EEMs:

Page 10: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 10

ASHRAE

2011

Page 11: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 11

Temp RH Tdp Temp RH Tdp Mode

AC 005 84.0 27.5 47.0 76 32.0 44.1 Cooling

AC 006 81.8 28.5 46.1 55 51.0 37.2 Cooling & Dehumidification

AC 007 72.8 38.5 46.1 70 47.0 48.9 Cooling

AC 008 80.0 31.5 47.2 74 43.0 50.2 Cooling & Humidification

AC 010 77.5 32.8 46.1 68 45.0 45.9 Cooling

AC 011 78.9 31.4 46.1 70 43.0 46.6 Cooling & Humidification

Min 72.8 27.5 46.1 55.0 32.0 37.2

Max 84.0 38.5 47.2 76.0 51.0 50.2

Avg 79.2 31.7 46.4 68.8 43.5 45.5

Visalia Probe CRAC Unit Panel

The Cost of Unnecessary Humidification

Humidity down 3%

CRAC power down 28%

Page 12: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 12

•Environmental conditions adjustments

•Air management improvements

•Chiller plant

Low Cost EEMs:

Page 13: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 13

Goal: Supply air directly to

equipment intakes without mixing

13

Equip.

Rack

No Air

Mixing

No Air

Mixing

Cool Front

Aisle

Hot Rear

Aisle

Page 14: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 14

By-pass air does no cooling

14

Misplaced perforated tiles Leaky cable penetrations

Too much supply airflow Too high tile exit

velocity

Page 15: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 15

Recirculated air causes localized cooling problems

Equip.

Rack

Recirculation

Air

Lack of blanking panels Gaps between racks

Too little air supply

Short equipment rows

Page 16: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 16

Adding Air Curtains for Hot/Cold Isolation

Page 17: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 17

95-105ºF vs. 60-70ºF (35-41C vs. 16-21C)

70-80ºF vs. 45-55ºF (21-27C vs. 7-13C)

Page 18: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 18

•Environmental conditions adjustments

•Air management improvements

•Chiller Plant

Low Cost EEMs:

Page 19: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 19

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Ch

ille

r E

ffici

en

cy (k

W/to

n)

Chiller Load Factor

Chiller 4 PerformanceSep 17 - 22, 2012

Maximum guaranteed efficiency at the chiller rated capacity of 2250 tons = 0.565 kW/ton, as per Drawing M-611 in the file "2010-01-10 NGA-NCE CUP Drawings (CONFORMED SET).pdf".

Maximum efficiency at the full capacity as provided by the

manufacturer

Better efficiency of chiller with higher load factor

Page 20: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 20

40

50

60

70

80

90

9/16 9/17 9/18 9/19 9/20 9/21 9/22 9/23 9/24

Tem

pe

ratu

re (F

)

Chiller 4 Condenser Water Temp and Outside Air Wetbulb Temp

CW Temp

OA Wetbulb

Condenser water supply temperature

Page 21: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 21

Data center 1 5,000 sf 500 kW IT 8GWh Tropical climate Air-cooled Chillers CRAHs

IT Equipment 53%

UPS+PDU Losses

8%

Lighting 1%

CRAH Fans/Heater

8%

Chillers 26%

Pumps 1%

UPS room cooling,

Generator BH 3%

Federal Data centers Case studies

Page 22: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 22

Seal all floor leaks and those between and within the racks

Case studies

Page 23: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 23

Lesson learned: Seal the opening between the rack and floor

Supply Air temperature out of the perf tiles

= 61.6degF

Case studies

Page 24: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 24

Air temperature between perf

and rack pedestal= 89.1degF

Case studies

Page 25: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 25

Air temperature after space taped =

69.3degF

Case studies

Page 26: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 26

Replaced Perf tiles Redirect cold air from the CRAHs

Case studies

Page 27: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 27

Ceiling space as a plenum

Case studies

Page 28: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 28

Before trials begin

Case studies

RAT increased from 74degF to 84degF

After

Page 29: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 29

Individual racks intake top temperature change during trials (60-72)

Average rack exhaust temperature change during trials (75-87)

Case studies

Page 30: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 30

CRAHs Return Avg.

Temperatures 64 to 83

CRAHs Supply Avg.

Temperatures 53 to 62

Case studies

Page 31: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 31

Chillers Efficiency Improvement

Case studies

40

42

44

46

48

50

52

54

56

58

100

120

140

160

180

200

220

240

260

1 2 3 4

Chiller plant kW

CHWST

CHWST sp degF 45 49 54 56

CHWST degF 46 49 55.1 56.8

CH1 kW 75 75 0 0

CH2 kW 75 75 100 75

CH3 kW 75 50 75 75

Page 32: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 32

Saved annually: 800MWh $240,000 utility cost 780 metric tons of GHG emission

Case studies

Page 33: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 33

IT Load 56%

UPS Loss 9%

PDU/trans loss 2%

Standby Gen 1%

Lighting 2%

Cooling 16%

Fans 11%

UPS cooling

3%

Data center 2 30,000 sf 1,850 kW IT 30GWh

Case studies

Page 34: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 34

Air management issues

Case studies

Page 35: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 35

Top rack intake temp after

Top rack intake temp before shutting down 20% of the CRAHs

Case studies

Page 36: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 36

Little rack intake temperature change after CRAHs shutdown

Case studies

Page 37: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 37

Saved annually: 850MWh $55,000 utility cost 820 metric tons of GHG emission

Case studies

0

200

400

600

800

1000

1200

1400

1600

1800

2000

CURRENT

POTENTIAL

Page 38: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 38

Data center 3 8,000 sf 800 kW IT 12GWh

Current IT Load 59%

UPS Loss 3%

PDU/trans loss 2%

Standby Gen 1%

Lighting 1%

Cooling 28%

Fans 6%

Case studies

Page 39: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 39

Case studies

Page 40: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 40

Rack Door HX

Dry Cooler

CENTRAL AIR

HANDLERs

Under raised floor supply air plenum

hot aisle

containment

COIL

Ceiling return air plenum

TES

Case studies

Page 41: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 41

Case studies

Page 42: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 42

Case studies

Page 43: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 43

1.35

1.40

1.45

1.50

1.55

1.60

1.65

1.70

1.75

1.80

Reduction of water flow to

TES from 1,000 to 300

gpm

Pump power reduced Chiller more efficient (higher delta T and load factor) PUE improved

Case studies

Page 44: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 44

Saved annually: 2,100MWh, $125,000 utility cost 2,000 metric tons of GHG emission

Case studies

Page 45: Saving Energy in Data Centers Data Center low cost EEMs...Slide 2 Objective •Explore why saving energy in Data Centers? •Get a general idea of the best practices •Learn about

Slide 45

Rod Mahdavi, PE. LEED AP

[email protected]

510.495.2259

Questions?