saturation ct because of dc offset

Upload: angga-wira-pramana

Post on 03-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 saturation CT because of DC offset

    1/20

    1

    Example 1:

    A 1200/5, C400 CT with excitation curves shown on above figure, is connected to a

    2.0 burden. Based on the accuracy classification, what is the maximum symmetrical

    fault current that may be applied to this CT without exceeding a 10% ratio error?

    Answer:

    Based on the criteria that the CT can deliver 20 times rated secondary current

    without exceeding a 10% ratio error, the maximum fault current will be 24000A.

    However, with a 2.0 burden, this will result in a voltage below the knee point of the CT

    and, as a practical matter, it will be within 10% accuracy at higher currents. This can onlybe accurately determined from excitation or ratio correction curves and not from the

    accuracy classification. For example, a CT with characteristics shown in above figure

    will produce between 180-240A without exceeding the 10% ratio error, depending on the

    power factor of the 2.0 burden.

  • 7/28/2019 saturation CT because of DC offset

    2/20

    2

    Example 2:

    A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary

    burden that can be used and still maintain rated accuracy at 20 times rated symmetrical

    secondary current?

    Answer:

    Since the secondary voltage capability is directly proportional to the connected tap, the

    CT will support a voltage of 1000/1200400V or 333V. Twenty times the rated

    secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33

    Example 3:

    Assume that secondary burden in a relay circuit is 5. The relay setting is 2A and the CT

    ratio is 300/5. Using above figure, calculate the primary current required to operate the

    relay?

    Answer:

    VB=5 times 2A=10V

    The secondary exciting current from above figure is approximately 0.04A.

    )( STP INI

    )( SE IIN

    = 300/5(0.04+2) A=122A

    Example 4:

    A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.

    Secondary burden is 3.5 . What is the error for the CT shown in above figure?

    Answer:

    The total secondary fault current is (7000/600)5=58A. Assume that exciting current is

    negligible.

  • 7/28/2019 saturation CT because of DC offset

    3/20

    3

    )( SBSS RRIV

    = 58(3.5+0.31)

    = 221V

    The exciting current will not be negligible, however, and the calculation will not be

    iterated.

    Lec7

    max 1 0

    2

    2

    dc

    N RI

    N

    | |

    m

    line

    V

    Z

    1

    2

    2 | |

    m

    line

    VN R

    N Z 11 2

    2| |

    m

    line

    V NN R

    Z N 1 02

    2

    ( )dct

    N RIv t e

    N

    1 022

    tN I

    i eN

    1 02 2

    2 20

    1( ) (0) (1 )

    t tN RI

    t v dt eN N

    1 022

    ( ) (0) (1 )

    tN RI

    t eN

    Lec- 71

    2

    2

    ( ) sin( )| |

    ac m

    line

    V Nv t R t

    Z N

    d

    dtj 2

    2

    ac

    V

    j N

    1

    2

    2

    ( ) sin( )| | 2

    mac

    line

    RV Nt t

    Z N

    max 1

    2

    2| |

    mac

    line

    RV N

    Z N

    max max 1 1

    2 2

    2 2| | | |

    m mac dc

    line line

    RV RVN N

    Z N N Z

    1

    2

    2

    1

    2

    2

    | |1 1

    | |

    m

    line

    m

    line

    V NR

    Z N

    V N R

    Z N

    1 line

    line

    L

    R

    1 line

    line

    X

    R

    1 XR

    Lec-6

    20 5 100SI A 61.0SR 1000

    4001200

    SV max400

    I 1532.61

    A 1200

    1535

    VVS 3.10)15.05(2 7000

    5 58.33600

    SI A 6800

    5 68500

    SI A

    81.358)31.05.3(58 SV 6

    100 10068

    E

    S

    I

    I

    5.2BR 300 2.045

    68(2.5 0.25)SV 1IR 0.51SR

    [ 'sin( ) 'sin ] ( )tp

    i I t I e u t [ 'sin (cos ) 'cos sin ] ( )tpi I t e I t u t

    'cos sinI t 'cos [ sin cos cos sin( )]tI e t 'sin cosI t

    2'sin [ sin cos cos( )]tI e t 'sin tI e

    'sin( )

    t tIe e

  • 7/28/2019 saturation CT because of DC offset

    4/20

    4

    Lec5

    100

    p

    S

    S

    II

    N

    I

    p S E

    II I

    N 100E

    S

    I

    I 100

    p

    S

    S

    II

    N

    I

    98 45

    Lec - 9

    100th T

    th

    V V

    V

    (3 )

    2

    0

    1( )L

    2

    0

    1

    LC 20

    1LC

    3f Hz

    1( )

    t

    eq

    div t Ri idt L

    C dt

    2

    2

    1

    eq

    dv di d iR i L

    dt dt C dt

    0

    1( )L C

    eq

    dV V jI L

    d C

    2

    0

    1(2 )

    eqI C

    2

    0

    1

    eqLC ( )I L L 2j LI ( )L CV V

    2 2

    | | 2 2tan

    | |

    L C

    R b b

    V V LI LI

    V a R I a R

    2

    2

    b

    L

    a R

    62 10mf L

    6103183.1

    2m

    L H

  • 7/28/2019 saturation CT because of DC offset

    5/20

    5

    CT saturation and DC- offset current

    Role of DC off-set current

    Typically fault current consists a symmetrical ac component and a dc offset current. To

    understand this concept, consider a transmission line unloaded exited by an equivalent voltage

    source. The fault strikes at time0tt . This can be simulated by closing the switch at 1tt

    LjR

    or

    Z models the line impedance. The fault current in the line is given by

    0)( ti 00 tt

    0

    0||

    )sin()(

    tt

    m eIZ

    tVti 0tt

    Where is the time constant of the line =L/R. The faul t current has two components in

    it. The first component models the steady state sinusoidal ac response while the second current

    is the dc offset current due to the presence of inductive component in the circuit. Recall that

    current in an inductance can not change instantaneously. As t, the instantaneous dc

    current, a consequence of maintaining initial condition )()( 00 titi , decays exponentially to

    zero and the current reaches the ac steady state values. While the dc offset current, would in

  • 7/28/2019 saturation CT because of DC offset

    6/20

    6

    theory persist till infinity, its trace in the actual wave form would not be seen beyond a certain

    time constants. Table-I illustrates the values of t

    e

    up to 10 time constants.

    Time t = 0 t = t = 2 t = 4 t = 6 t = 8 t = 10

    t

    e

    1 0.3678 0.1353 0.0183 0.0024 0.0003 0.00004

    It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.

    The value ofI0 can be worked out by setting the current at ott to zero.

    This implies that

    )sin( 00 tZ

    VI m

    Thus

    )( 0

    )sin()sin()(

    tt

    mm etZ

    Vt

    Z

    Vti

    fig.2

    Clearly, the peak value of dc offset current depends upon

    Time at which fault strikesPhase angle of ac voltage

  • 7/28/2019 saturation CT because of DC offset

    7/20

    7

    Z & of transmission line

    Figure 2 shows the waveforms of

    a)

    symmetrical ac componentb) dc offset currentc) total current for various values of , &

    0t

    It can be seen that severity of dc offset component in fault current is maximum when

    a)

    b)2

    0

    t

    For example, if angle of transmission line is 800, then with = 80

    0&

    50220

    t

    =200

    1sec = 5msec, the severity of dc offset current would equal

    Z

    VI m0 , which is also the

    peak value of symmetrical ac component of the current. This leads us to an important

    conclusion. Viz. peak value

    1) dc offset current can be as high as the symmetrical ac peak2) The dc offset current can be positive or negative (see fig2)3) Dc offset current may be totally absent

    eg. If , 00 t

    4) While, in above analysis, we have considered a single phase current, a 3 fault on a 3transmission line would always induce dc offset current in atleast 2 phases.

    In the remaining lecture, we analyze the effect of dc offset current on CT performance.

    DC- offset current and CT saturation

  • 7/28/2019 saturation CT because of DC offset

    8/20

    8

    We now plan to show that CT can saturate on dc offset current. Also, we plan to show

    that the resulting distortions in the CT secondary current can be un-acceptably high. While

    doing this analysis, we will neglect ac symmetrical component. In other words, we rest our

    belief in superposition theorem atleast qualitatively and will finally evaluate effect using it

    Notice that the current that we are dealing with is non-linear, a rigorous application of super

    position theorem is simply out of question.

    First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully

    replicates primary current waveform on the secondary side. Hence, the secondary current

    would be given by

    t

    eN

    Iti

    02 )(

    and the voltage developed across CT secondary would be given by

    t

    eN

    RItv

    02 )( where1

    2

    N

    NN

    Typical voltage waveform is shown in fig. (5)

  • 7/28/2019 saturation CT because of DC offset

    9/20

    9

    For simplicity, let us assume that the initial flux in the transformer core at t=0 is

    zero 0)0( ; Then we can compute the flux in the transformer core by using faradays law

    dtdNV 22 ---------(2)

    t

    dtvt0

    2)0()(

    t

    eN

    RI1

    2

    0

    )1(2

    0

    t

    eN

    LI

    )1()0()(2

    0

    t

    eN

    LIt

    )1(2

    0

    t

    eN

    LI

    ------- (3)

    as a consequence of dc offset current,

    Thus, flux in the core increases exponentially to a peak value of

    2

    0max

    N

    LIcd as t

    Z

    V

    N

    L m Z

    Vm maxcd

  • 7/28/2019 saturation CT because of DC offset

    10/20

    10

    Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac

    voltage induced flux has zero average value. However, dc offset induced does not have this

    nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.

    The ac flux in the CT core can be obtained by substituting operatordt

    dby j . Hence

    phasor relationship between phase2

    V & ac is given by

    2

    2

    Nj

    V

    If 2( ) sin( )mv t V t , then

    )2

    sin(2

    t

    N

    Vmac

    The peak value of ac flux is given by

    2

    max

    N

    Vmac

    However max02IRVm

    Hence2

    max

    02max

    N

    IRac

    and peak value of the total flux is given by

    2

    max

    0

    2

    maxmax

    N

    LI

    N

    Vmdcac

    In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core

    will saturate.

  • 7/28/2019 saturation CT because of DC offset

    11/20

    11

    As a consequence of CT core saturation, the secondary current would not faithfully replicate

    the primary current. Infact, in practice it is observed that CT secondary current is clipped. The

    clipping ofCT current leads to blinding of the relay which cannot function further. Hence,

    CT saturation in presence of dc offset current is a serious problem which relay designers have

    to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time

    constant ( ). It is apparent that saturation should not occur immediately after the inception of

    the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying

    decision would be undertaken before the CT fully saturates. This is another important reason

    for increasing the speed of relaying system. For bus-fault protection, where the dc saturation

    due to dc offset current can be a significant contributing factor, quarter cycle operations *****

    specifically are imposed. Similarly, a distance relay is expected to operate within -1 cycle

    time.

    CT oversizing factors

    Typically, an efficient design of transformer would correspond to choosing the core

    cross section such that acm should be near the knee point of B-H curve. One obvious way of

    avoiding the CT saturation on dc flux is to oversize the core so that for flux )(maxmax

    dcac , the

    corresponding B is below the knee-point. Hence, the factor max

    maxmax)(

    ac

    dcac

    is called core-

    oversizing factor.

  • 7/28/2019 saturation CT because of DC offset

    12/20

    12

    Core-oversizing factor =max

    max

    1

    ac

    dc

    20

    21

    NRI

    NLIo

    R

    L1

    R

    X 1

    Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.

    This would imply that transformer core should be oversized by a factor of 11. For a 400KV

    line, typical value of X/R 20. This would imply an oversizing required of about 21 times the

    usual design. Clearly this high amount of oversizing is not practical. Thus, the important

    conclusion is that, protection engineers have to live with the saturation problem.

    Cautions in CT selection:

    While choosing a CT for a particular application, it is necessary to observe following

    precautions.

    1. The CT rating and continuous load current should match. For example, if max loadcurrent is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.

    2. The maximum fault current should be less than 20 times the CT rated current. forexample 100:5 CT can be used, so long as burden on the CT & maximum primary fault

    current is below 2000A.

    3. The voltage rating of CT should be compatible. For example, 100:5 C100 would givelinear response, upto 20 times rated current provided CT burden is kept

    below(100/20*5=1 ). With 2 burden, this CT can be used only if maximum current

    is limited to 1000A.

    4. Parallel of CTs e.g. in differential protection, or with SLG fault can create significanterrors in CT performance. One should in general ascertain that magnetizing current is

    kept much below the pick up value.

    Following example, illustrates this point

    Exercise problems:

  • 7/28/2019 saturation CT because of DC offset

    13/20

    13

    If the current ratio is adequate for a protection, but CT burden is high; then the

    performance of CT may deteriorate due to large magnetizing current and/or saturation problem.

    The CT performance can be improved by connecting the CTs in series.

    1) Show the dotted terminals for correct secondary series connection2) What is the VA of CT in fig (a) & (b) respectively?1) Electromechanical relays tend to saturate at high currents. This reduces the relay burden

    on CT, and so that the CT performance at moderately high currents may be considered

    better than at relays rated burden at 5A.

    2) Use of instantaneous over current relays has the potential to overcome this problem ofsaturation of CTs

    3) Differential protection can operate on external faults due to the un equal saturation ofCTs

    Lecture-6

    Examples

    6. If a 300:5 class C CT is connected to a meter with resistance 1IR andsecondary current in the CT is 4.5A find out the primary current voltage

    developed across the meter and % rate error. Lead wire resistance

    02.0LR secondary resistance SR of a 300/5 CT 15.0

    Diagram

    1IR , 02.0LR 15.0SR AIS 5.4

    Total secondary resistance SLIT RRRR

    17.1 Secondary voltage TS RI

    17.15.4

    V265.5

    From Fig 5.7,

  • 7/28/2019 saturation CT because of DC offset

    14/20

    14

    Exciting current IE for 5.265V

    = 0.03A

    Turns ratio N = 300/5 = 60

    )( ESp IINI

    = 60(4.5 + 0.03)

    = 271.8AVoltage across meter IS RI

    14.5 = 4.5V

    Ratio error 1005.4

    03.0100

    S

    E

    I

    I

    = 0.67%

    bR

  • 7/28/2019 saturation CT because of DC offset

    15/20

    15

    Lecture8

    Examples

    1. Design a CCVT for a 132kV transmission line using the following data.Resistive Burden VA150)3(

    Hzf 3 , phase angle error= 40 minConsider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV

    Diagram 1 Diagram 2Transmission line voltage V = 132kV. Suppose V2 (P_N) be the voltage to be

    produced by the capacitive potential divider with capacitance values C1 and C2and L the value of tuning inductor. The standardized VT secondary voltage is 110

    volts (L-L).

    Here specification for phase angle error is 40 minutes variation in frequency

    can be upto Hzf 3 . Phase angle error for change in by in the above

    equation circuit, is given by

    )1

    ( 2CL

    At tuning frequencyLC

    12

    Substituting 2 1LC

    Phase angle error )( LL

    L2

    % phase angle error bRa

    L2

    2 --- (1)

    Using this equation the value L for different values of V2 is found out.

    1) Let V2 be 33kV (L - N)2

    2

    '

    3150

    b

    V

    R

    52' 108.217bb RaR

    322 f

    rad01164.060180

    40min40

    From eqn (1)

    322

    108.21701164.0

    2

    5'

    bRL

    H2.6722

    FFL

    CC

    39

    2211051.11051.1

    1

    2) )(112 NLkVV 3 2

    ' 43 (11 10 ) 242 10150

    bR

  • 7/28/2019 saturation CT because of DC offset

    16/20

    16

    ' 40.01164 242 10

    2 2 2 3

    bRL

    H2.747

    2.747)4/3(

    112221

    L

    CC

    F21036.1

    3) kVV 6.62 3 2

    ' 3 (6.6 10 )

    150bR

    41012.87 ' 4

    0.01164 87.12 10

    2 2 2 3

    bRL

    ,269H

    FCC 221 1077.3

    4) kVV 3.32 3 2

    ' 3 (3.3 10 )

    150b

    R

    41078.21 ' 40.01164 21.78 10

    2 2 2 3

    bR

    L

    H25.67

    1 2 0.151C C F

    The values of L, 21 CC for different values of V2 are tabulated below.

    V2 L 21 CC 33kV 6722.2H 0.00151 F

    11kV 747.2H 0.0136 F

    6.6kV 269H 0.0377 F

    3.3kV 67.25H 0.151 F

    From the above table it is clear that smaller the value of V2, the smaller is thevalue of L and higher the value of C1 and C2 for tuning condition. If we select too low

    value of V2 and L then capacitance values will be beyond available limits, and if we

    select higher value of V2 and L, then CCVT and inductor will become bulky. So a

    compromise is necessary and let us select V2 = 6.6kVFor V2 = 6.6kV

    L = 269H

    FCC 0377.021

    Now,1

    21

    2 C

    CC

    V

    V

  • 7/28/2019 saturation CT because of DC offset

    17/20

    17

    1

    6

    3

    3 100377.0

    106.63

    10132

    C

    3

    63

    110132

    10106.630377.0

    F

    C

    F0033.0 FC 0344.02

    In this design, we explained the basic concept for CCVT design and we assumed

    the transformer to be ideal. But in actual design practice the value of magnetizing

    impedance of transformer, resistance of reactor etc have to be taken into account,

    as ratio error and phase angle error will also get affected by these values.

    2. DiagramThe equivalent circuit of a CCVT is shown in fig 8.3. The values of C1 and C2 are

    0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of

    497H and resistance of 4620 .Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =150VA per phase. Value of Cm for compensating the current drawn by m is equal

    to F910183.3 .(a)Verify the appropriateness of choice of L and Cm.Ans: If FC 0018.01 and FC 0186.02 then the value L of tuning inductor is

    given by

    )(

    1

    21

    2 CCL

    where 2 f and f = tuning frequency

    2 6

    1

    (2 50) (0.0018 0.0186) 10L

    = 496.7H which is equal to the given value of L. Now 61 10mX

    1m

    m

    XC

    6

    1 1

    (2 50) 1 10m

    m

    CX

    93.183 10 F The value is also same as the selected value of Cm Hence the selection of both L

    and Cm is appropriate.

    (b)Find out the nominal value of V/V2Ans: 1 2

    2 1

    0.0018 0.0186

    0.0018

    C CV

    V C

    = 11.33

    V = 11.33 x 6.6132

    3kV

  • 7/28/2019 saturation CT because of DC offset

    18/20

    18

    (c) If the frequency drops from 50Hz to 47Hz, what would be the values of ratioerror and phase angle error?

    Ans: Core loss = 20w

    2

    2 20m

    VW

    R

    2 2

    2 (6600)

    20 20m

    VR

    62.18 10 VA burden = 150VA (resistive)

    2

    2 150b

    V

    R

    2 2

    2 (6600)150 150

    bVR

    52.904 10 The equivalent circuit can be represented as shown below.

    Diagram 8.12610mX at f = 50Hz

    62 10mf L 610

    3183.12 50

    mL H

    The frequency of interest is 47Hz. Hence values of Xm and other impedance can

    be calculated at 47Hz. The above circuit can be simplified asDiagram 8.13

    Where1 1 1

    m

    m m b

    jj C

    Z R X R

    9

    6 5

    1 12 47 3.183 10

    2.18 10 2 47 3183.1 2.904 10

    jj

    6 6 6 60.459 10 1.064 10 0.94 10 3.44 10j j 6 6(3.902 0.124) 10 3.904 10 1.82j

    6

    1

    3.904 10 1.82

    Z

    256147.5 1.82

    256018.32 8135.15j

    thth

    VI

    jR j L Z

    C

  • 7/28/2019 saturation CT because of DC offset

    19/20

    19

    6

    6600 0

    4620 2 47 497 256018.32 8135.152 47 0.0204 10

    jj j

    6600 0

    4620 146768.9 165994 256018.32 8135.15j j j

    6600 0

    260638.32 11089.84j

    6600 0

    260874.14 2.44A

    T thV I Z

    6600 0256147.5 1.82

    260874.14 2.44

    6480.42 4.26

    Hence % ratio error(6600 6480.42)

    1006600

    =1.81%

    Phase angle error = 4.26

    2 6.6V kV

    rM

    2 2

    0t t2

    2

    10

    eq

    d i R dii

    dt L dt LC

    12 50nw

    LC 2 n

    RIw

    L

    22

    22 0n n

    d iw w i

    dt 1

    Lec8

    12 50

    n

    eqLC 2 n

    R

    L

    22

    22 0n n

    d ii

    dt n 1

    t

    e

    0 0sin( )

    | |

    m

    line

    VI t

    Z

  • 7/28/2019 saturation CT because of DC offset

    20/20

    20