CA Title 24 Building CodeIMPACTS ON LIGHTING AND LIGHTING CONTROLS TO GO INTO EFFECT
ON JULY 1ST, 2014
Summary of Significant Changes to
Nonresidential Indoor Lighting Increased number of steps for mandatory multi-level lighting controls
New requirements for bi-level occupancy controls in some spaces
In all buildings except offices, lighting must be shut off completely during unoccupied times
Automatic daylighting controls are mandatory in all primary daylit zones with at least 120W of installed load, with fewer exceptions
The threshold for when alterations must comply with the Standards has been reduced from when 50% of the luminaires in a room are altered, to when 10% of the luminaires in a room are altered
A new category of alteration called “luminaire modifications in place” has been added
Demand responsive control systems are required in all buildings 10,000 square feet or larger
Mandatory Lighting Controls
Mandatory nonresidential indoor lighting controls include the
following:
Area controls: manual controls separately controlling lighting in each
area
Multi-level controls: providing occupants with the ability to use all of the light, some of the light or none of the light in the area
Shutoff controls: automatically shutting off or reducing light output of
lighting when it is not needed
Automatic daylighting controls: separately controlling some or all of the
lights in the daylight area from the lights that are not in the daylight area
Demand Responsive Lighting Controls: installing controls that are capable of receiving and automatically responding to a demand
response signal
Area Lighting Controls
A manual override control for the occupants is required
Each area enclosed by ceiling-height partitions requires a manual
switch or dimmer switch (if controlling dimmable luminaires) for ON and
OFF lighting controls
Must be readily accessible to occupants and control functionality
cannot be overridden by other lighting controls
Manual switch must be located in the same room or area with the
lighting that is being controlled by that lighting control
If controlling dimmable luminaires, be a dimmer switch that allows
manual ON and OFF functionality, and is capable of manually
controlling lighting through all multi-level lighting control steps
Multi-level Controls Requirement applies to enclosed spaces larger than 100 sq. ft. and with
a connected general lighting load greater than 0.5W/ square foot
Requires either continuous dimming or three intermediate levels between on and off settings – change from one intermediate level
Luminaires mounted at less than 24 feet over most hardscape areas will have to include bi-level control and dim when no one is present
LED luminaires and LED source systems requires continuous dimming 10-100%
In addition to the multi-level controls, each luminaire in the space must be controlled by at least one of 5 methods:
1. Manual dimming
2. Lumen maintenance – a strategy used to provide a precise, constant level of lighting from a lighting system regardless of the age of the lamps or the maintenance of the luminaires
3. Tuning – the ability to set maximum light levels at a lower level than full lighting power
4. Automatic daylight control
5. Demand responsive lighting control
Automatic Shut-Off Controls Shall be controlled with one or more of the following automatic
shut-OFF controls when the space is typically unoccupied:
Occupant sensing control
Automatic time-switch control
Signal from another building system
Other control capable of automatically shutting OFF all the lights
Separately controls the lighting for each floor
Separately controls the lighting in each room (enclosed space) and
a control can control up to 5,000 sq. ft.
Larger spaces will have more than one separately controlled zone
where each zone does not exceed 5,000 sq. ft.
Exception: may not exceed 20,000 sq. ft. in following areas:
Mall, auditorium, single tenant retail, industrial, convention center, arena
Occupancy Sensor Controls
Required to shut OFF all lighting:
Offices 250 sq. ft. or smaller
Multipurpose rooms of less than 1,000 sq. ft.
Classrooms of any size
Conference rooms of any size
Occupancy Sensor Controls (cont.)
Parking garages will have to incorporate occupancy sensors that
allow lighting on less frequently used levels to be switched off or
turned to a low level when no one is present
Warehouses, library stacks and all corridors and stairwells must
incorporate “partial off” control that partially dims the lights when
space is unoccupied
Controls will have to reduce lighting power in these spaces by at least
50% during unoccupied times
Daylighting – General Terms
General Lighting
Electric lighting that provides a uniform level of illumination throughout
an area, exclusive of any provision for special visual tasks or decorative
effect, exclusive of daylighting, and also known as ambient light.
Window Head Height
The vertical distance from the finished floor level to the top of a window
Daylit Zone
A region of space considered to be close enough to a source of
daylight such as a window, clerestory, roof monitor or skylight, where
luminaires can be dimmed or switched in response to available daylight
Definitions of Daylit Zones Three different types of daylit zones:
1. Skylit Daylit Zone
1. Rough area in building plan view under each skylight, plus 0.7 times the average ceiling height in each direction from the edge of the rough opening of the skylight, minus any area on a plan beyond a permanent obstruction that is taller than the following:
1. A permanent obstruction that is taller than one-half the distance from the floor to the bottom of the skylight
2. The bottom of the skylight is measured from the bottom of the skylight well for skylights having wells, or the bottom of the skylight if no skylight well exists
2. Primary Sidelit Daylit Zone
1. The area on the building plan directly adjacent to each vertical glazing, one window head height deep into the area, and window width plus 0.5 times window head height wide on each side of the rough opening of the window, minus any area on a plan beyond a permanent obstruction that is 6 feet or taller as measured from the floor
3. Secondary Sidelit Daylit Zone
1. The area on a plan directly adjacent to each vertical glazing, two window head heights deep into the area, and window width plus 0.5 times window head height wide on each side of the rough opening of the window, minus any area on a plan beyond a permanent obstruction that is 6 feet or taller as measured from the floor
Daylighting
Luminaires providing general lighting in skylit zones and primary
daylit zones must be controlled independently to automatically
adjust lighting levels (using photosensors) through multi-level or
dimming control
Photosensor controls through multi-level or dimming required in
secondary daylit zones
Primary zone – starts at window pane and extends one window head
height back into the space
Secondary zone – starts at the back edge of the primary zone and
extends a further two window head height types
Primary and secondary zones must be controlled separately
Daylighting (cont.)
Automatic Daylighting control and installation
For each space the combined illuminance from the controlled lighting
and daylight shall not be less than the illuminance from controlled
lighting when no daylight is available
In areas served by lighting that is daylight controlled, when the
illuminance received from the daylight is greater than 150 percent of
the design illuminance received from the general lighting system at full
power, the general lighting power in that daylight zone shall be
reduced by a minimum of 65 percent
Daylighting (cont.)
Spaces requiring minimum daylighting (daylighting required) – must
meet all requirements:
Space is directly under a roof
Located in climate zones 2 through 15
Has a floor area greater than 5,000 square feet
Has a ceiling height greater than 15 feet
Exemptions: spaces that have a general lighting system with a power density
less than 0.5W per square foot or is a function area that includes: auditoriums,
churches, movie theatres, museums or refrigerated warehouses
Buildings with unfinished interiors – future enclosed spaces are exempt which
are planned to have a floor area less than 5,000 square feet and a ceiling
height less 15 feet
Daylighting (cont.)
Prescriptive daylighting requirements
At least 75% of the total space floor area shall be under Skylit Daylit Zone
or Primary Sidelit Daylit Zone
The calculation of daylit zone area to show compliance with this minimum
daylighting requirement does not need to account for the presence of
partitions, stacks or racks other than those that are ceiling high partitions
Demand Response
Automatic demand response capability for lighting systems in all
commercial buildings larger than 10,000 square feet, regardless of
space type – change from 50,000 square feet
Lighting system must be capable of receiving and automatically
responding to standards-based message, such as OpenADR, to
reduce lighting power by at least 15% below the building’s
maximum lighting power during peek and demand times
Summary of Mandatory Controls Bldg/Space Type Application LPD Control Additional
Exception
All except industrial and arenas
All except sales floors, auditoriums, malls with remote controls in view
of lighting or annunciated
- Manual light switch in each enclosed space separately controlling general, display
ornamental and special effects lighting
1
All Enclosed spaces > 100 sq. ft. & >1 luminaire with >2 lamps
>0.5W /sq. ft. Multi-level control of each luminaire 2
All except parking garage
All except hotel/motel high-rise res common area corridors and
stairwells
All Automatic full shut off controls (timeclock and timed override switch or occupancy sensor)
3
All Offices <250 sq. ft., multipurpose rooms <1,000 sq. ft., classrooms,
conference rooms
All Automatic full shut off occupancy sensors
-
Warehouse Aisles and open areas All Occupant sensor per aisle and open areas, reduce power by at least 50%
4
Library Single ended stacks >10 ft. or double ended stacks >20 ft.
All Occupant sensor per aisle, reducepower by at least 50%
-
All except hotel/motel, high rise residential
Corridors and stairwells All Occupant sensor per space, reduce power by at least 50%, turn lights on
from all paths of egress
-
Summary of Mandatory Controls Bldg Space Type Application LPD Control Additional
Exception
Hotel/motel, high rise residential
Corridors and stairwells All Occupant sensor per space, reduce power by at least 50%. No additional shut
off controls
5
Parking garages - All Partial off occupancy sensor with one sensor per 500W of lighting & with control step between 20% & 50% or rated power
6
Hotel/motel Guest room All Captive card key or occupancy sensing on/off control
7
All except parking garage
>24 sq. ft. of glazing per room and more than 120W in skylit and primary sidelit daylight zones
>0.3W/ sq. ft.
Multi-level daylighting controls separately controlling skylit, primary sidelit and
secondary sidelit daylight zones
8
All except parkinggarage
>24 sq. ft. of glazing per room and more than 120W in skylit and primary sidelit daylight zones
<0.3W/sq. ft.
Multi-level or on/off daylighting controls separately controlling sidelit, primary
sidelit and secondary sidelit daylight zones
8
Parking garage >36 sq. ft. of opening or glazing, >60 watts in combined primary
and sidelight daylight zone
- Multi-level or on/off daylighting controls controlling combined primary and
secondary sidelit daylight zones
9
All bldg. >10,000 sq. ft. Habitable spaces >0.5W/sq. ft.
Demand responsive control to lower building lighting power by 15%
-
Mandatory Controls – Additional
Exceptions1. Egress lighting up to 0.2W/sq. ft. Switch accessible to authorized
personnel for multi-staff bathrooms
2. Classrooms <0.7W/sq. ft. and bi-level lighting with step between 30% and 70% of rated power
3. Continuously occupied areas or egress lighting <0.05W/sq. ft.
4. If HID or LPD <80% of area category LPD, reduce power by at least 40%
5. LPD <80% of area category LPD, reduce power by at least 40%
6. HID lighting with mean efficacy >75 lm/W, control step between 20% and 60% of rated power
7. One high efficacy luminaire controlled by a switch and within 6 ft. of entry door
8. Skylights added to existing lighting system, ON/OFF control acceptable
9. Luminaires located in the daylight transition zone or dedicated lamps
Methods to Determine Lighting
Power Allotments
Complete Building Method
Area Category Method
Most common
Tailored Method
Most commonly used for retail lighting
Performance Method
Allows trade-offs between building envelope or mechanical systems
that can let the allowed lighting power go higher than any other
method
Complete Building Method Only applied when all areas in the entire building are complete
Building must consist of one type of use for a minimum of 90 percent of the floor area of the entire building
Allowed Indoor Lighting Power allotment for general lighting:
Conditioned building: multiply sq. ft. of conditioned space of the building X the applicable allotment of watts per square foot
Unconditioned building: multiply sq. ft. of unconditioned space X applicable allotment of watts per square foot
Used only on projects involving:
Entire buildings with one type of use or occupancy
Mixed occupancy where one type of use makes up at least 90 percent of the entire building (shall be assumed that primary use is 100 percent for calculations)
A tenant or space where one type of use makes up at least 90 percent of the entire tenant space (shall be assumed primary use is 100 percent of tenant space for calculations)
Complete Building Method Lighting Power Density Values
Type of Use Allowed Lighting
Power (W/ft2)
Auditorium 1.5
Classroom 1.1
Commercial/
Industrial Storage
0.6
Convention Center 1.2
Financial Institution 1.1
General
Commercial/
Industrial
1.0
Grocery Store 1.5
Library 1.3
Medical / Clinic 1.1
Office 0.8
Type of Use Allowed Lighting
Power (W/ft2)
Parking Garage 0.2
Religious Facility 1.6
Restaurant 1.2
School 1.0
Theatre 1.3
Other 0.6
Area Category Method Can be used for multiple tenants or partially completed buildings
“Area” defined as all contiguous spaces that accommodate or are associated with a single primary function
Area not covered by current permit is ignored
Divides building into primary function areas
Lighting Power Allotment determined by multiplying the area of each function X the lighting power density for that function
When areas are bounded or separated by interior partitions, the floor space occupied by those interior partitions shall be included in any area
The total allowed watts is the summation of the Lighting Power Allotment for each area covered by the permit application
Each function area in the building must be included as a separate area
Boundaries between primary function areas may or may not consist of walls or partitions
It is not necessary to separate aisles or entries within function areas
When used to calculate for an entire building – main entry lobbies, corridors, restrooms, and support functions treated as separate function areas
Area Category Method (cont.)
Additional Requirements
If at the time of permitting for a newly constructed building, a tenant is
not identified for a multi-tenant area, a maximum of 0.6 watts per
square foot shall be allowed for the lighting in each area in which a
tenant has not been identified
Classified as Unleased Tenant Area
The allowed Indoor Lighting Power Density for each primary area is the
Lighting Power Density Value X the square feet of the primary function
The total allowed indoor Lighting Power Density for the building is the sum of
the allowed indoor Lighting Power Densities for all areas in the building
Additional Lighting Power – Area
Category Method In addition to the allowed indoor Lighting Power calculated, the
building may add additional lighting power allowances for specialized task work, ornamental, precision, accent, display, decorative, and white boards or chalk boards
Conditions:
Additional lighting power allowances used only if the plans clearly identify all applicable task areas and the lighting equipment designed to illuminate these tasks
Tasks that are performed less than 2 hours per day or poor quality tasks that can be improved are not eligible for the additional lighting power allowances
The additional lighting power allowances shall not utilize any type of luminaires that are used for general lighting in the building
Up to 1.5 watts per square foot of additional lighting power shall be allowed in a videoconferencing studio
Area Category Method – Lighting
Power Density Values (W/ft2)Primary Function
Area
Allowed Lighting
Power (W/ft2)
Auditorium 1.53
Auto Repair 0.92
Beauty Salon 1.7
Civic Meeting Place 1.33
Classroom, Lecture,
Training, Vocational
1.25
Commercial and
Industrial Storage
0.6
Convention,
Conference,
Multipurpose,
Meeting Center
1.43
Primary Function
Area
Allowed Lighting
Power (W/ft2)
Corridor, Restroom,
Stair, Support
0.6
Dining 1.13
Electrical,
Mechanical,
Telephone
0.72
Exercise Center,
Gym
1.0
Exhibit, Museum 2.0
Financial
Transaction
1.23
Area Category Method – Lighting
Power Density Values (W/ft2)Primary Function Area Allowed Lighting
Power (W/ft2)
General
Commercial/
Industrial Work
Low Bay 0.92
High Bay 1.02
Precision 1.24
Grocery Sales 1.26 and 7
Hotel Function 1.53
Kitchen, Food
Preparation
1.6
Laboratory, Scientific 1.41
Laundry 0.9
Primary Function Area Allowed Lighting
Power (W/ft2)
Library
Reading 1.23
Stacks 1.53
Lobby
Hotel 1.13
Main Entry 1.53
Locker/ Dressing
Room
0.8
Lounge 1.13
Area Category Method – Lighting
Power Density Values (W/ft2)Primary Function Area Allowed Lighting
Power (W/ft2)
Malls and Atria 1.23
Medical and Clinical
Care
1.2
Office Area
> 250 sq. ft. 0.75
< 250 sq. ft. 1.0
Parking Garage Area
Parking 0.14
Dedicated Ramps 0.3
Daylight Adaptation
Zones
0.6
Primary Function Area Allowed Lighting
Power (W/ft2)
Religious Worship 1.53
Retail Merchandise
Sales, Wholesales
Showrooms
1.26 and 7
Theatre
Motion Picture 0.93
Performance 1.43
Transportation Function 1.2
Videoconferencing
Studio
1.28
Waiting 1.13
Other 0.6
Power Allowances – Footnote
Definitions Footnote Number Type of Lighting System Allowed Maximum allowed added
lighting power (W/ft2 of task
area)
1 Specialized task work 0.2
2 Specialized task work 0.5
3 Ornamental lighting 0.5
4 Precision commercial and industrial
work
1.0
5 Per linear foot of white board or chalk
board
5.5 w per linear foot
6 Accent, display and feature lighting –
luminaires shall be adjustable or
directional
0.3
7 Decorative lighting 0.2
8 Additional Video Conferencing
Studio Lighting
1.5
Tailored Method
Establishes an allowed lighting power budget on a room-by-room or area-by-area basis
Provides additional lighting power budgets for illuminating wall displays, floor displays, task lighting, and ornaments/special effects lighting
May be helpful when a function area has a high room cavity ratio (RCR)
To calculate (applicable tables to follow):
Find the appropriate Primary Function Area
Find the corresponding General Illuminance Level (LUX)
Determine the RCR for that primary function area
Use the RCR compliance form to document the RCR calculation
Use the General Illuminance Level and RCR to determine the allowed Power Density Value
Multiply the allowed Lighting Power Density Value times the square feet of the primary function areas to get the Allowed Indoor Lighting Power allotment for general lighting for that primary area
Specific instructions to calculate Additional Allowed Power based on type of lighting
Tailored Method (cont.)
Room Cavity Ratio (RCR)
Must be determined for any primary function area using the Tailored
Lighting Method
The lighting level in a room is affected in part by the configuration of the
room, expressed as the RCR
Rooms with high ceiling more difficult to light higher RCR allowed a
higher LPD
Based on the entire space bounded by floor-to-ceiling partitions
If task area in larger space not bound by floor-to-ceiling partitions, the RCR of
the entire space must be used for the task area
Typical RCRs (task height of 2.5 ft. above floor)
When room cavity height = 5.5 ft. (8 ft. from floor to bottom of luminaire)
Room
Length
(ft.)
Room Width (ft.)
8 12 16 20 24 30 36 40
5 8.9 7.8 7.2 6.9 6.6 6.4 6.3 6.2
8 6.9 5.7 5.2 4.8 4.6 4.4 4.2 4.1
12 5.7 4.6 4.0 3.7 3.4 3.2 3.1 3.0
16 5.2 4.0 3.4 3.1 2.9 2.6 2.5 2.4
20 4.8 3.7 3.1 2.8 2.5 2.3 2.1 2.1
24 4.6 3.4 2.9 2.5 2.3 2.1 1.9 1.8
30 4.4 3.2 2.6 2.3 2.1 1.8 1.7 1.6
36 4.2 3.1 2.5 2.1 1.9 1.7 1.5 1.5
40 4.1 3.0 2.4 2.1 1.8 1.6 1.5 1.4
Typical RCRs (task height of 2.5 ft. above floor)
When room cavity height = 7.5 ft. (10 ft. from floor to bottom of luminaire)
Room
Length
(ft.)
Room Width (ft.)
8 12 16 20 24 30 36 40
5 12.2 10.6 9.8 9.4 9.1 8.8 8.5 8.4
8 9.4 7.8 7.0 6.6 6.3 5.9 5.7 5.6
12 7.8 6.3 5.5 5.0 4.7 4.4 4.2 4.1
16 7.0 5.5 4.7 4.2 3.9 3.6 3.4 3.3
20 6.6 5.0 4.2 3.8 3.4 3.1 2.9 2.8
24 6.3 4.7 3.9 3.4 3.1 2.8 2.6 2.5
30 5.9 4.4 3.6 3.1 2.8 2.5 2.3 2.2
36 5.7 4.2 3.4 2.9 2.6 2.3 2.1 2.0
40 5.6 4.1 3.3 2.8 2.5 2.2 2.0 1.9
Tailored Method
Formulas to calculate RCR:
RCR = [5 X H X (L + W)] / A
H = room cavity height, vertical distance measured from the work plane to
the center line of the luminaire
L = room length using interior dimensions
W = room width using interior dimensions
A = room area
RCR = [2.5 X H X P] / A
H = room cavity height
A = room area
P = room perimeter
Illuminance Level (LUX) Power Density Values (W/ft2)
Illuminance Level (LUX)
RCR < 2.0 RCR > 2.0 and < 3.5 RCR > 3.5 and < 7.0 RCR > 7.0
50 0.2 0.3 0.4 0.6
100 0.4 0.6 0.8 1.2
200 0.6 0.8 1.3 1.9
300 0.8 1.0 1.4 2.0
400 0.9 1.1 1.5 2.2
500 1.0 1.2 1.6 2.4
600 1.2 1.4 2.0 2.9
700 1.4 1.7 2.3 3.3
800 1.6 1.9 2.6 3.8
900 1.8 2.2 3.0 4.3
1000 1.9 2.4 3.3 4.8
Tailored Method Lighting Power Allowances
Primary Function Area General Illumination Level
(LUX)
Wall Display Power (W/ft)
Allowed Combined Floor Display Power and Task Lighting
Power (W/ft2)
Allowed Ornamental/ Special Effect Lighting
Auditorium 300 2.25 0.3 0.5
Civic Meeting Place 300 3.15 0.2 0.5
Convention, Conference,
Multipurpose, Meeting Center
300 2.5 0.4 0.5
Dining 200 1.5 0.6 0.5
Exhibit, Museum 150 15.0 1.2 0.5
Financial Transaction 300 3.15 0.2 0.5
Grocery Store 500 8.00 0.9 0.5
Hotel Function Area 400 2.25 0.2 0.5
Lobby (Hotel) 200 3.15 0.2 0.5
Lobby (Main Entrance) 200 0 0.2 0
Tailored Method Lighting Power Allowances
Primary Function Area General Illumination Level (LUX)
Wall Display Power (W/ft)
Allowed Combined Floor Display Power and Task Lighting
Power (W/ft2)
Allowed Ornamental/ Special Effect Lighting
Lounge 200 7.00 0 0.5
Malls and Atria 300 3.5 0.5 0.5
Religious Worship 300 1.5 0.5 0.5
Retail Merchandise, Sales, Showroom
400 14.00 1.0 0.5
Motion Picture Theatre 200 3.00 0 0.5
Performance Theatre 200 6.00 0 0.5
Transportation Function 300 3.15 0.3 0.5
Waiting Area 300 3.15 0.2 0.5
Performance Approach
The performance approach provides an alternative method to the
prescriptive approach for establishing the allowed lighting power for the
building
Energy use of the building is modeled using a compliance software
program approved by the Energy Commission
Standard lighting power density for the building is determined by the compliance
software program based on occupancy type, in accordance with either the
complete building, area category or tailored rules
Standard lighting power density is used to determine the energy budget for the
building
When a lighting permit is sought under the performance approach, the
applicant uses a proposed lighting power density to determine whether or
not the building meets the energy budget
If it does, this proposed lighting power density is automatically translated into the
allowed lighting power for the building by multiplying the area of the building
Power Adjustment Factor (PAF)
An adjustment, or credit, to the actual installed lighting power in a
space, so that when completing the compliance documentation,
some of the installed lighting power is not counted toward the
building’s total installed lighting load
Provided when specific lighting controls are installed, as long as they are
not required
To qualify:
The controlled lighting is permanently installed general lighting systems
and the controls are permanently installed nonresidential-rated lighting
controls
At least 50% of the light output of the controlled luminaire is within the
applicable area
Only one PAF used for each qualifying luminaire
PAF Applicable Area Partial-On Occupant Sensing Control
Any area less than or equal to 250 sq. ft. enclosed by floor-to-ceiling partitions; any size classroom, conference or waiting room PAF = 0.20
Occupant Sensing Controls in Large Open Plan Offices
In open plan offices > 250 sq. ft. one sensor controlling area:
No larger than 125 sq. ft. PAF = 0.40
From 126 to 250 sq. ft. PAF = 0.30
From 251 to 500 sq. ft. PAF = 0.20
Dimming System
Hotels/motels, restaurants, auditoriums theatres
Manual dimming PAF = 0.10
Multiscene programmable PAF = 0.20
Demand Responsive Control
All building types less than 10,000 sq. ft. PAF = 0.25
May also qualify for other PAFs
Combined Manual Dimming plus Partial-ON Occupant Sensing Control
Any area less than or equal to 250 sq. ft. enclosed by floor-to-ceiling partitions; any size classroom, conference or waiting room PAF = 0.25
Power Adjustment Factor – Partial
On Occupant Sensor Control
Control shall automatically deactivate all of the lighting power in the area within 30 minutes after the room has been vacated; and
The first stage shall automatically activate between 30-70 percent of the lighting power in the area and may be a switching or dimming system; and
The second stage shall require manual activation of the alternate set of lights, and this manual-ON requirement shall not be capable of conversion from manual-ON to automatic-ON functionality via manual switches or dip switches; and
Switches shall allow occupants to manually do all of the following regardless of the sensor status: activate the alternate set of lights, activate 100 percent of the lighting power; and deactivate all of the lights
Additions and Alterations
Any space with a lighting system installed for the first time must meet
the same lighting requirements as newly constructed buildings
Lighting system alterations include modifications to lighting systems such as luminaire replacement, luminaire removal or relocation, and
other similar modifications not considered to be modifications-in-
place
Wiring alteration such as replacing or installing new wiring that
connects the luminaires to switches, relays, branch circuits, and
other control devices represents a lighting alteration
Luminaire-modifications-in-place include lamp and ballast change-
outs, reflector or optical system modifications, whole fixture retrofit kits, and similar modifications
Additions and Alterations (cont.)
Lighting system alterations include alterations where an existing
lighting system is modified, luminaires are replaced or luminaires are
disconnected from the circuit, removed and reinstalled, whether in
the same location or installed elsewhere
Lighting system alterations do not include:
Portable luminaires
Luminaires affixed to movable partitions
Additions and Alterations (cont.)
Quantity of existing affected luminaires per enclosed
space
Resulting Lighting Power for Each Enclosed Space
Applicable Mandatory Control Provisions for Each Enclosed
Space
Multi-Level Lighting Control Requirements for Each Altered
Luminaire
Alterations that do not change the area of the enclosed space or the space type (lighting alterations where enclosed space area or type has not changed and wattage has not increased)
Sum total < 10% of existing luminaires
Existing lighting power is permitted
Existing provisions are permitted
Existing controls are permitted
Sum total > 10% of existingluminaires
< 85% of allowed lightingpower per Area Category
Method
Manual Area Controls, Automatic Shut-off Controls
Two-level lighting control or Multi-level control
> 85% of allowed lighting power per Area Category
Method
Manual Area Controls, Automatic Shut-off Controls,
Daylight Controls
Multi-level lighting control
Alterations that change the area of the enclosed space or the space type or increase the lighting power in the enclosed space (lighting alterations accompanying changes to the enclosed space area or space type or accompanying an increase in lighting
power)
Any number Comply with Area Category Method
Manual Area Controls, Automatic Shut-off Controls, Daylight Controls, Demand
Responsive Controls
Multi-level lighting control
Requirements for Luminaire Alterations
Additions and Alterations (cont.)
One popular retrofit product that does save energy is the screw-
based LED retrofit kit, designed to be installed directly into a
recessed downlight not having an incandescent socket
As a screw-in retrofit, it is not recognized by the standards, either for
reducing luminaire wattage or as an alteration that triggers compliance
with the lighting alterations requirements or triggers compliance with the
luminaire modifications in place
Do not require Title 24 compliance
Additions and Alterations (cont.) The following alteration methods do not comply with the requirements
of the standards:
Luminaires and luminaire housings designed to accommodate a variety of trims or modular components that allow conversion between incandescent and any other lighting technology without changing the luminaire housing shall be classified as incandescent
Screw-based adaptors shall not be used to convert an incandescent luminaire to any type of non-incandescent technology. Screw-based adaptors, including screw-base adaptors classified as permanent by the manufacturer, shall not be recognized
Replacement of lamps in a luminaire manufactured or rated for use with linear fluorescent lamps, with linear lamps of a different technology such as linear LED lamps, shall not be recognized as converting the fluorescent luminaire to a different technology
An LED-lamp, integrated or non-integrated type, shall not be classified as an LED lighting system. LED modules having screw-bases including screw-based pig tails, screw-based sockets, or screw-based adaptors shall not be recognized as an LED lighting system
Luminaires manufactured or rated with low-voltage incandescent lamps, into which have been installed LED modules or LED lamps, shall not be recognized as an LED lighting system
Additions and Alterations (cont.)
Luminaire Modifications-in-Place
Replacing lamps or ballasts with like type or quantity in a manner that
preserves the original luminaire listing
Changing the number or type of light source in a luminaire including:
socket renewal, removal or relocation of sockets of lampholders, and/or
related wiring internal to the luminaire including the addition of safety
disconnecting devices
Changing the optical system of a luminaire in part or in whole
Replacement of whole luminaires one for one in which the only
electrical modification involves disconnecting the existing luminaire and
reconnecting the replacement luminaire
Additions and Alterations (cont.)
Number of Luminaire Modifications-in-Place Is compliance required
for that enclosed space?Per annum per building
space
In an enclosed space
< 40 in number < 10% No
< 40 in number > 10% No
> 40 in number < 10% No
> 40 in number > 10% Yes
Thresholds for Luminaire-Modifications-in-Place Requirements
Additions and Alterations (cont.)
Lighting Wiring Alterations
Alterations include the following:
Adding a circuit feeding luminaire
Modifying or relocating wiring to provide power to new or relocated
luminaires
Replacing wiring between a switch or panelboard and luminaires
Replacing or installing a new panelboard feeding lighting system
Color Rendering Index (CRI)
All permanently wired LED lighting fixtures installed in California
residencies during new construction or major remodeling must have
a CRI of 90 or more to be qualified as high efficacy
Not all installed fixtures must be high efficacy as the new standards
do allow for a percentage (by wattage) of Low Efficacy fixtures to
be installed as well
The requirements for high efficacy LED luminaires do not apply to
most nonresidential lighting function areas, except for inside
dwelling units of high-rise residential, hotel/motel, fire stations and
dormitory/senior housing
Ceiling fan light kits with permanently installed LEDs must also meet the new 90 CRI requirement to be classified as high efficacy
CRI (cont.)
Low efficacy LED residential fixtures can be sold in California without
limit but the new CA Title 24 has increased the percentage of high
efficacy fixtures required in some rooms
Bathrooms – required to have one high efficacy fixture with any other
lighting controlled by vacancy sensors
Garages, laundry rooms and utility rooms – all lighting must be high
efficacy and controlled by vacancy sensors
Outdoor lighting (all lighting mounted on buildings) – all luminaires must
be high efficacy or controlled by a motion sensor plus a photocontrol or
time clock
CRI (cont.)
Low efficacy outdoor lighting must be controlled by the following:
A manual on/off switch that doesn’t override to on
A motion sensor not having an override or bypass switch that disables
the motion sensor, or a motion sensor with an override switch that
temporarily bypasses the motion sensing
A photocontrol, astronomical time clock or energy management
control system that does not have an override or bypass switch
disabling the control and is programmed to automatically turn the
outdoor lights off during daylight hours
Appendix JA8 – Qualification Requirements for
Residential Luminaires using LED light source
LED light source manufactured for use in residential applications:
When designed or rated for indoor use shall be capable of providing a nominal
CCT that contains at least one point within the range 2700K-4000K
When designed or rated for outdoor use shall be capable of providing a nominal
CCT that includes at least one point within the range 2700K-5000K
Exemption: monochromatic LEDs that are only for decorative purposes
Capable of providing a CRI of at least 90
An LED light engine shall be capable of being installed in luminaire housing
without using any type of base or socket used for incandescent lamps
May include a GU-24 or modular quick connect, but shall not include screw based sockets or adapters of type and size E12 through E29
Table JA-8
Power Rating per Integral LED
Luminaire, or per LED Light Engine
Under Test
Minimum Efficacy (Lumens per Watt)
5 watts or less 30
Over 5 watts to 15 watts 45
Over 15 watts to 40 watts 60
Over 40 watts 90
The efficacy of the integral LED luminaire or LED light engine shall be
equal or greater than the efficacies contained in the table below:
Compliance and Enforcement–
Overview
Beginning January 1st, 2015 new requirements for a documentation
procedure called registration will go into effect
Required for the construction and alteration of nonresidential buildings
All nonresidential energy compliance documents will need to be
registered with a nonresidential data registry prior to submittal to an
enforcement agency
Compliance and Enforcement
Process Design - at the design phase architects, engineers, and designers must understand both the
requirements and the underlying intent of the Standards if they are to design buildings and systems that are inherently energy efficient and cost effective
Permit Application - at the permit application, the design team must make sure that the plans contain all the information that the building official will need to verify that the building or system satisfies the requirements. (see compliance forms and worksheets)
Plan Check – during plan check, the building department plans examiner must verify that the building or system satisfies the requirements of the Standards and that the plans (not just the compliance forms) contain the information to be verified during field inspection
Construction – the contractor must carefully allow the approved plans and specification and the building department field inspector(s) must verify that the building or system is constructed according to the plans and specifications
Acceptance Commissioning – after completion of construction, the contractor and/or design team must properly commission the building and its systems and provide information and/or training to the building operators on maintenance and operation of the building and its equipment
Operation – After occupancy, the building and its systems must be correctly operated and properly maintained. In addition, building users must be advised of their opportunities and responsibilities for savings energy
Commercial Lighting Compliance Process
Commercial Lighting Compliance Process
1. Mandatory Measures are required regardless of the compliance method selected
2. Select a method for complying with the standards
1. Complete Building, Area Category or Tailored
2. This will determine how many watts of lighting power are allowed to be installed in the building
3. Calculate the actual lighting power installed by totaling all of the lighting installed in the building
4. Subtract lighting control credits
1. This process will demonstrate the adjusted actual watts of lighting power that has been installed in the building
5. If the lighting power that is allowed to be installed in the building, is equal to or greater than the adjusted actual watts installed, then the lighting in the building complies with the Standards
1. If it doesn’t comply, then the lighting power will need to be reduced or additional lighting credits will need to be acquired
Compliance Procedures – Commercial
Indoor Lighting Certificate of Compliance Forms
NRCC-LTI-01-E : Certificate of Compliance and Field Inspection Checklist
NRCC-LTI-02-E : Lighting Controls Credit Worksheet
NRCC-LTI-03-E : Indoor Lighting Power Allowance
NRCC-LTI-04-E : Tailored Method Worksheet
NRCC-LTI-05-E : Line Voltage Track Lighting Worksheet
Indoor Lighting Certificate of Installation Forms
NRCI-LTI-01-E : Validation of Certificate of Compliance
NRCI-LTI-02-E : Energy Management Control System or Lighting Control System
NRCI-LTI-03-E : Line Voltage Track Lighting
NRCI-LTI-04-E : Two Interlocked Lighting Systems
NRCI-LTI-05-H : Power Adjustment Factors (Verified by a HERS rater)
NRC-LTI-06 : Additional Videoconference Studio Lighting
Compliance Procedures (cont.) - Commercial
Measures requiring Acceptance Testing
Indoor Lighting Control Systems
Automatic Daylighting Controls Acceptance
Occupancy Sensor Acceptance
Manual Daylighting Controls Acceptance
Automatic Time Switch Control Acceptance
Demand Responsive Controls
Indoor Lighting Certificate of Acceptance Forms
NRCA-LTI-02-A : Lighting Controls
NRCA-LTI-03-A : Daylighting Controls
NRCA-LTI-04-A : Demand Responsive Controls
Nonresidential Indoor Lighting
Certificates of Compliance NRCC-LTI-01-E
Four page document
Each page must appear on the plans
Copy of document should also be submitted to the enforcement agency along with the rest of the compliance submittal at the time of building permit application
With enforcement agency approval, applicant may use alternative formats of these documents provided that the information is the same and in a similar format
NRCC-LTI-02-E
All of the lighting control documentation has been moved into a single set of compliance documents
NRCC-LTI-03-E
Three page set of compliance documents required to document and calculate how much indoor lighting power is allowed by the Standards, so that the allowed lighting power can be demonstrated to be greater than or equal to the installed lighting power in the summary table on NRCC-LTI-01-E
Nonresidential Indoor Lighting
Certificates of Compliance NRCC-LTI-04-E
Six pages
Required to document and calculate allowed lighting when the Tailored Method is the method used in any area for compliance
The light power allowances calculated in this set of compliance documents are required to be able to complete the summary table on page 2 of NRCC-LTI-01-E
NRCC-LTI-05-E
Required to calculate luminaire input wattage and document all line voltage track and busway lighting
Required to calculate and document the input wattage of every installed line voltage track lighting system
Each of the track lighting systems calculated and documented in this worksheet shall also be separately listed in the Luminaire Schedule in Section C of NRCC-LTI-01-E
Certificate of Acceptance
Acceptance requirements ensure that equipment, controls and systems operate as required by the Standards
Activities specified in requirements have 3 aspects:
Visual inspection of the equipment and installation
Review of the certification requirements
Functional tests of the systems and controls
Third party review of the information provided on the Certificate of Acceptance forms is not required for lighting
The acceptance tests required for nonresidential indoor lighting include the following:
Automatic daylighting controls
Occupancy sensors
Automatic time-switch controls
Resources
http://www.energy.ca.gov/2013publications/CEC-400-2013-002/chapters/05_indoor_lighting.pdf - Title 24 Non-residential manual
http://www.destinationlighting.com/articles/title-24.html - CRI info.
http://www.lightshowwest.com/Portals/18/LSW2013/Speaker%20PDFs/S3%20%20Flamm%20Gary%20Lt%20Show%20West.pdf
http://cltc.ucdavis.edu/sites/default/files/files/publication/title-24-2013-code-changes-140318.pdf
http://www.energy.ca.gov/title24/2013standards/rulemaking/documents/final_rulemaking_documents/44_Final_Express_Terms/2013_JA_FINAL.pdf - Appendix JA8
http://www.energy.ca.gov/2013publications/CEC-400-2013-002/chapters/05_indoor_lighting.pdf - daylighting